Wiki source code of 4 Common function of VB

Last modified by Theodore Xu on 2025/02/27 09:58

Hide last authors
Theodore Xu 36.1 1 = Parameters uploading and downloading =
2
Theodore Xu 37.1 3 (% class="box infomessage" %)
4 (((
5 **✎Note:**
6 1.Parameter uploading and downloading is only supported between the same models.
7 2.F7.11 shows the software version of the inverter, the parameters may differ between different versions, especially between 2.072 and versions below 2.072.
8 )))
Theodore Xu 36.1 9
10 1.Press MF.K and ↑ and wait while the keyboard displays "u~-~-~-~-", the keyboard is uploading the parameters.
11
12 2.Remove the keyboard and install to other VB.  Please be careful to align the pins when unplugging and plugging in the keyboard.
13
14 3.Press MF.K and ↓ and wait while the keyboard display"d~-~-~-~-", the keyboard is downloading the parameters.
15
Leo Wei 1.1 16 = **Start up** =
17
18 ~1. Keyboard start and stop, panel potentiometer speed regulation. (F5.17 adjusts the change amplitude of the panel potentiometer)
19
20 F0.01=0
21
22 F0.03=1
23
24 2. The switch starts and stops, and the external voltage potentiometer is used for speed regulation. (AI1: 0-10V input; AI2: 0-20mA/0-10V, realized by AI2 jumper cap)
25
26 F0.01=1
27
28 F0.03=2
29
30 3. The switch starts and stops, the panel up and down keys adjust the speed, and the remote terminal switch is required to control the speed up and down. (Set terminal UP and terminal DOWN in the multi-function terminal). (Control frequency in two places)
31
32 F0.01=1
33
34 F0.03=1
35
36 F5.02=6
37
38 F5.03=7
39
40 4. Switch start and stop, two switches, when operating the normally open button of one switch, lightly jog, the inverter starts; when operating a normally closed button of the other switch, lightly jog, the inverter stops , Use the three-wire system function.
41
42 F0.01=1
43
44 F0.03=1
45
46 F5.02=3
47
48 F5.16=2
49
50 5. Two places to control the speed. The inverter on one device needs two positions to control the frequency (speed). Speed (the main and auxiliary frequency sources are used for speed regulation).
51
52 F0.03=1
53
54 F0.04=2
55
56 F0.07=01
57
Mora Zhou 17.1 58 6. On some equipment, two potentiometers are required to adjust the speed, one potentiometer 0-10V controls 20HZ, and the other potentiometer controls 0-10V control 25HZ so that the spindle frequency is superimposed, and the frequency is 45HZ.
Leo Wei 1.1 59
60 F0.03=2
61
62 F0.04=3 (AI2 jumper is voltage input)
63
64 F0.07=01
65
66 F5.21=40
67
68 F5.25=50
69
70 7. The customer needs a fixed speed operation. If it needs to run at 30Hz, there is no need to adjust any place to change the speed. After stopping and then turning on, the operating frequency is still running at 30HZ. How to set the parameters?
71
72 F0.03=0
73
74 F0.08=30
75
76 8. The customer requires the terminal to start. After a power failure, the terminal must be triggered again to start. How to set the parameters?
77
78 F0.01=1
79
80 F8.18=1
81
82 = **Acceleration time** =
83
Mora Zhou 17.1 84 ~1. When the device is started, the customer feels that the startup time is too long or the startup time is too short, which parameters need to be modified? (This parameter should be fine-tuned appropriately according to the equipment load. Improper setting can easily cause fault alarms such as overcurrent).
Leo Wei 1.1 85
86 F0.18 (appropriate setting) etc.
87
88 = **Deceleration time** =
89
90 ~1. After the equipment is started, the customer feels that the deceleration (stopping) time is too long, which parameters need to be modified? (This parameter needs to be fine-tuned according to the equipment load. Improper setting may easily cause fault alarms such as overcurrent).
91
92 F0.19 (appropriate setting), etc.
93
94 = **Stop DC braking** =
95
96 ~1. The inverter is used on a CNC lathe, and the customer needs to stop quickly, that is, brake, which parameters should be set to make the motor stop quickly? (stop DC braking function)
97
98 F1.10=0 (must decelerate to stop)
99
100 F1.11 Appropriate setting
101
102 F1.12 Appropriate setting
103
104 F1.13 Appropriate setting
105
106 F1.14 Appropriate setting
107
108 = **Torque boost** =
109
110 ~1. When the inverter is started, the customer reported that the inverter is driving the motor load at low frequencies and is weak at low frequencies, and the torque needs to be increased. Which parameter should be set appropriately?
111
112 F4.01 (set appropriately) or change to vector control
113
114 = **Carrier frequency** =
115
116 ~1. Customers report that there are noises such as harsh screams when the motor is running, or the temperature of the running motor is too high, or when the communication function encounters interference, the function parameter needs to be adjusted to improve the effect.
117
118 F0.16 (appropriate setting)
119
120 = **Upper limit frequency** =
121
122 1.50HZ operation can not meet the needs of customer equipment, the customer needs to adjust the frequency to 100Hz, what parameters need to be set at this time?
123
124 F0.10=100
125
126 F0.12=100
127
128 = **Lower limit frequency** =
129
130 ~1. The user needs the inverter to stop after decelerating to 5HZ, which parameter should be set?
131
132 F0.14=5
133
134 F0.15=1
135
136 = **Restore factory value** =
137
138 ~1. The customer reports that the parameters are messed up, how to restore the factory value?
139
140 F0.20=1
141
142 = **Fault clearing** =
143
144 ~1. The fault record can only be recorded 15 times in total. Now the customer needs to clear the fault record, how to set it? Which parameter can make the inverter fault record automatically reset, how many times at most?
145
146 F0.20=2
147
148 FA.08=5
149
150 FE.01=15
151
152 = **Starting frequency** =
153
154 ~1. The customer needs the inverter to start running at 5HZ, how to set it?
155
156 F1.03=5
157
158 = **PLC operation** =
159
160 ~1. The simple PLC automatic operation function is used on the equipment, the first stage speed is forward rotation, the forward rotation needs 15HZ, and the operation is 5S, the first stage speed is reverse rotation, the reverse rotation requires 20HZ, and the operation is 10S, and now the customer needs to rotate forward and stop. After 10S, it starts to run in the reverse direction. After 10S after the reverse stop, it starts to run forward again, and the cycle is repeated. Which parameter should be set? (Control the acceleration and deceleration time)
161
162 F0.03=7
163
164 FD.00=30
165
166 FD.01=0
167
168 FD.02=-40
169
170 FD.03=0
171
172 FD.18=5
173
174 FD.20=10
175
176 FD.22=10
177
178 FD.24=10
179
180 (Or call F8.12 forward and reverse dead time)
181
182 = **Jump frequency** =
183
184 ~1. In order to avoid the resonance point (vibration point) of the negative cutting of the machine when the inverter is driving the load, which function is needed, and how to set the parameters appropriately for this function? At 10HZ, the vibration range is 2HZ. (Hop frequency)
185
186 F8.09=10
187
188 F8.11=2
189
190 = **Jog frequency** =
191
192 ~1. According to customer equipment requirements, a normally open button is needed to give the inverter a jog speed. How do you set the function that needs to be used? And the jog function also requires that the jog frequency acceleration and deceleration time be shortened, so set that parameter The jog frequency is 10Hz, and the acceleration and deceleration time is 5s.
193
194 F8.00=10
195
196 F8.01=5
197
198 F8.02=5
199
200 = **Multi-speed** =
201
202 ~1. According to the different equipment speed, the customer needs 4 speed stages, the first stage is 40HZ, the second stage is 25HZ, the third stage speed is 10HZ, the fourth stage speed is 50HZ, usually the keyboard potentiometer speed control, how To set which parameters and wiring to meet customer needs.
203
204 F0.03=6
205
206 F5.02=12
207
208 F5.03=13
209
210 F5.04=14
211
212 F5.05=15
213
214 FD.01=80
215
216 FD.02=50
217
218 FD.04=20
219
220 FD.08=100
221
222 FD.51=6
223
224 F0.04=1(0)
225
226 Up to 16 speeds can be achieved, please refer to page 78 of the manual for details.
227
228 = **Free stop** =
229
230 1.On some equipment, the equipment does not require deceleration to stop, but the motor stops slowly with the load inertia when it is stopped. For example, when the fan is stopped, the fan needs to be stopped by the load. Which parameter should be set?
231
232 F1.10=1
233
234 = **Reversal is prohibited** =
235
236 ~1. On some devices, customers do not need the motor to reverse, and they are also worried that during the forward rotation, some operators may improperly operate or press the reverse key on the wrong keyboard, which will cause the inverter to reverse and affect the normal operation of the equipment. Now the customer needs us to give him a parameter to prohibit the motor from reversing, which parameter should be set?
237
238 F8.13=2
239
240 2. The motor originally rotates forward, but when the customer connects the phase sequence UVW of the motor wire, it is difficult to confirm. When the inverter is started, the motor reverses. Now the customer does not need to change the phase sequence UVW of the motor wire. If there is a parameter that can be directly set , Let the motor normally change to forward rotation.
241
242 F0.09=1
243
244 = **Analog output function** =
245
246 ~1. The customer needs to install an ammeter on the power distribution cabinet to display the output current. The wiring is AO1 and GND. In the corresponding function of the parameter group, which parameter should be set? The ammeter can display the output current.
247
248 F6.12=2
249
250 2. The customer connects a 0-10V tachometer, and finds that the motor speed display is a bit wrong. For example, when running at 50Hz, the speed displayed on the tachometer cannot reach it. How to adjust?
251
252 You can measure the output voltage between AO1 and GND and adjust the value of F6.15 and F6.16
253
254 = **Digital input function** =
255
256 ~1. Since an external switch is needed on the device to control the emergency stop of the motor, which function parameter should be set?
257
258 F5.02=10
259 2. The customer needs to set forward jog and reverse jog functions on the inverter, how to set and wire it?
260
261 F5.02=4
262
263 F5.03=5
264 3. When the inverter fails, an external switch is needed to operate the reset function when the inverter fails. How to set and wire?
265 F5.02=9
266 4. The inverter terminals control forward and reverse running. Which function parameter should be selected in the multi-function digital input terminal?
267
268 F0.01=1
269
270 F5.00=1
271
272 F5.01=2
273 5.How to set the remote control frequency if the customer needs an external button?
274
275 F5.02=6
276
277 F5.03=7
278
279 = **Digital output function** =
280
281 ~1. The customer needs to use the FM open-collector output function. When the inverter fails, output a switch value to make the fault alarm lamp/fault buzzer act, so that the on-site operator knows that the inverter has a fault alarm and what to do Setup and wiring?
282
283 F6.00=1
284
285 F6.01=2
286
287 2. When the inverter runs more than 20HZ, the relay T1A and T1C terminals output a switch value to control an indicator light, so that the indicator line is connected and the indicator light is on. How to set up and wire?
288
289 F6.02=41
290
291 F6.28=0
292
293 F6.29=11
294
295 F6.21=2000
296 3. When AI1 input is required to be greater than 3.00V and less than 6.00V, relay 1 is closed, how to set the parameters?
297
298 F6.02=41
299
300 F6.28=9
301
302 F6.29=13
303
304 F6.31=300
305
306 F6.32=600
307
308 4.The customer requires relay 1 to act when rotating forward or reverse, how to set it?
309
310 F6.02=1
311
Stone Wu 3.1 312 = **Motor parameter setting and self-learning** =
Leo Wei 1.1 313
314 ~1. Familiar with the motor self-learning function.
315 Need to input the motor parameters F2.01, F2.02, F2.03, F2.04, F2.05 to adjust the value of F2.11 to 1 (premise F0.01=0) or 2, press ENT first, Press RUN again, the self-learning is completed when the panel returns to the monitoring interface. (Necessary operation when changing to vector control)
316
317 = **Display monitoring** =
318
319 ~1. Master the functions of F7.03, F7.04, and F7.05, all of which are used for display and monitoring. Please refer to page 35 of the manual for details
320
321 = **Operating mode selection** =
322
323 ~1. Master the definition of each control mode of the F0.00 parameter group.
324
325 Vector control, V/F control
326
327 = **Analog signal gain** =
328
329 ~1. The user uses the AI1 terminal function, and the device is given a voltage of 0-5V for speed regulation. Which parameter should be modified accordingly?
330
331 F0.03=2
332
333 F5.20=5
334
335 2. The user uses the AI2 terminal function, and the device is given a 4-10MA (for example) current speed control, which parameter should be modified accordingly?
336
337 F0.03=3
338
339 F5.23=2
340
Stone Wu 4.1 341 = **Parameter protection** =
Leo Wei 1.1 342
343 ~1. The protection parameters cannot be modified and the parameters are locked.
344
345 F0.21=1
346
347 2. The user needs to set a password to prevent some operators from adjusting parameters randomly. Which parameter should be set?
348
349 FE.00 = non-zero number
350
Stone Wu 5.1 351 = **Set running time action** =
Leo Wei 1.1 352
353 ~1. The customer sells the machine to the user, worrying that the customer did not pay on time, set some parameters inside the inverter. After the inverter has been running for 10 hours, the inverter will automatically stop and cannot start. Wait for the user to pay before the machine can run. How to set parameters for such a function?
354 FE.00=Set password
355
356 F8.17=10+F7.09
357
358 F8.23=1
359
360 = **Display monitoring options** =
361
362 ~1. The user requires the inverter to display only the speed during operation, which parameter should be modified?
363
364 F7.03=4000
365
366 F7.06=Speed fine-tuning coefficient
367 2. The user requires the inverter to display various states during shutdown. Which parameter can be set?
368
369 F7.05
370
Theodore Xu 18.1 371 = **Constant pressure water supply** =
372
Theodore Xu 19.1 373 The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
374 Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
Theodore Xu 22.1 375 F0.20=1 Factory data reset
Theodore Xu 18.1 376 A4.00=1
Theodore Xu 22.1 377 A4.01=Set pressure
Theodore Xu 18.1 378 A4.03=Sensor range
379 A4.04=0
380
381 If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
Theodore Xu 22.1 382 F0.20=1 Factory data reset
Theodore Xu 18.1 383 F0.03=8
Theodore Xu 38.1 384 F5.23=2 Change AI2 range from 0-20mA to 4-20 mA.
Theodore Xu 18.1 385 F9.01=Upper limit water pressure
386 F9.02=1 (AI2)
387 F9.28=1
Theodore Xu 23.1 388 F9.29=Target value
Theodore Xu 18.1 389 F9.31=Lower limit water pressure
Theodore Xu 19.1 390
391
Theodore Xu 21.1 392 In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
Theodore Xu 18.1 393
Leo Wei 1.1 394 = **PID function** =
395
Theodore Xu 15.1 396 (% style="text-align:center" %)
Theodore Xu 16.1 397 [[image:生产流程图.png]]
Leo Wei 1.1 398
399 ~1. To be familiar with the PID function of constant pressure water supply, the feedback signal sources are remote pressure gauges and pressure transmitters. How to wire and which parameters should be set? For example, the maximum range of the remote pressure gauge is 1Mpa, and the current user needs to set the panel 0.45 MPa kg pressure, how to set the pressure?
400 F0.01=0 (panel start and stop)/1 (terminal start and stop)
401
402 F0.03=8
403
404 F9.00=0
405
406 F9.01=45
407
408 F9.02=7
409
410 F9.05=80
411
412 F9.06=2
413
414 F9.07=0
415
416 F9.28=1
417
418 F9.29=45.5
419
420 F9.30=3
421
422 F9.31=40
423
424 F9.32=0
425
426 = **Communication function** =
427
428 ~1. Familiar with RS485 communication function, communication address, communication speed, communication format, how to set it? Familiar with the address of communication function?
429 Please refer to page 129 of the manual
430
431 Commonly used address: Setting frequency: 1000H (Premise F0.03=9)
432
433 Control operation command address: 2000H (premise F0.01=2)
434
435 = **Grounding** =
436
437 ~1. Understand the meaning and function of the ground wire and connect it correctly.
438 The grounding terminal E of the inverter must be well grounded, the grounding resistance should be less than 102, and the grounding wire should be thick and short. Multi-strand copper core wire of 3.5mm2 or more should be used.
439
Stone Wu 7.1 440 = **Peripheral lines** =
Leo Wei 1.1 441
442 ~1. Understand the role of peripheral line equipment:
443
444 Open
445
446 AC contactor
447 Input AC reactor
448 Input side filter
449
450 DC reactor
451
452 Output AC reactor
453
454 Output filter
455
456 Braking unit
457
458 Braking resistor
459
Theodore Xu 31.1 460 = **EMC** =
Leo Wei 1.1 461
Theodore Xu 33.1 462 The input terminal of the inverter has EMC screw access option.
Theodore Xu 24.1 463
Theodore Xu 33.1 464 * EMC Screws Installation Role: Filter out the common mode interference signals on the input side to the ground.
Theodore Xu 35.1 465 * EMC Screw Removal Function: When the grounding of the whole equipment system is unstable, it is easy for the interference signal to enter the input terminal of the VFD, which leads to the inaccurate operation of the terminal motor, and then it is necessary to remove the EMC screws on the machine in order to solve the influence of external interference.
Theodore Xu 33.1 466
Theodore Xu 34.1 467 (% class="box infomessage" %)
468 (((
469 Do not remove the EMC unless there are special circumstances.
470 )))
471
Theodore Xu 30.1 472 (% style="text-align:center" %)
473 [[image:企业微信截图_16890580824807.png||height="394" width="284"]]
474
475
476
Theodore Xu 29.1 477 = Torque mode control on winding project =
Theodore Xu 25.1 478
479 Torque mode can only be vector control, torque control refers to the strength, that in the torque mode F0.03 is the default value, modify F0.03 for other values is invalid.
480
481 Debugging ideas:
482
Theodore Xu 26.1 483 ~1. According to the application requirements of the torque command and the upper limit of the frequency.
Theodore Xu 25.1 484
485 2. Set the frequency acceleration/deceleration time F0.18/F0.19 and the torque acceleration/deceleration time F3.14/F3.15, the torque acceleration/deceleration time is less than or equal to the frequency acceleration/deceleration time.
486
487 3. Start the motor and observe whether the motor can run or not, if it can't run normally, rotate the motor with external force, if it can be started, it is judged to be necessary to increase the static friction coefficient compensation.
488
489 4. After the motor is running, observe the motor running state, if the motor is blocked, check whether it is shaking when it is blocked, if it is shaking, increase F3.07, generally 0.01 amplitude increment.
490
491 5. When the torque command F3.10 is lower than the percentage of "no-load current / rated current", the running frequency is about: rated frequency * torque command percentage * rated current / no-load current.
492
493 6. Static Friction Compensation Logic: During startup, the torque command 1 = F3.11* F3.24 /100 is passed to the performance; after a maintenance time of F3.25 seconds, it reverts to torque command 2 = F3.11; the switching of torque commands 1 /2 occurs through the torque acceleration and deceleration times F3.14 / F3.15;
494
495 7. Auxiliary debugging parameters: filter coefficient F3.07 and static friction compensation F3.24/ F3.25.
496
Theodore Xu 26.1 497 F0.00=0 Vector control
Theodore Xu 25.1 498
Theodore Xu 27.1 499 F0.18=2.0 Acceleration time
Theodore Xu 25.1 500
Theodore Xu 27.1 501 F0.19=2.0 Deceleration time
Theodore Xu 25.1 502
Theodore Xu 27.1 503 F2.01=Motor rated power
Theodore Xu 25.1 504
505 F2.02=Motor rated voltage
506
507 F2.03=Rated motor current
508
509 F2.04=Rated motor frequency
510
511 F2.05=Rated motor speed
512
Theodore Xu 27.1 513 F2.11=1 Static tuning
Theodore Xu 25.1 514
Theodore Xu 27.1 515 F3.01=0.2 Speed loop integration time
Theodore Xu 25.1 516
Theodore Xu 27.1 517 F3.07=0.005 Speed loop filter coefficient
Theodore Xu 25.1 518
Theodore Xu 27.1 519 F3.09=1 Torque control
Theodore Xu 25.1 520
Theodore Xu 27.1 521 F3.10=1 Torque control upper limit source
Theodore Xu 25.1 522
Theodore Xu 27.1 523 F3.11=200 Torque upper limit setting
Theodore Xu 25.1 524
Theodore Xu 27.1 525 F3.12=50 Torque control maximum frequency
Theodore Xu 25.1 526
Theodore Xu 27.1 527 F3.14=1.2 Torque control acceleration time
Theodore Xu 25.1 528
Theodore Xu 27.1 529 F3.15=1.2 Torque control deceleration time
Theodore Xu 25.1 530
Theodore Xu 28.1 531 F3.16=120 Torque stiffness factor
Theodore Xu 25.1 532
533 Torque control commissioning instructions:
534
Theodore Xu 27.1 535 F0.18: Frequency acceleration time
Theodore Xu 25.1 536
Theodore Xu 27.1 537 F0.19: Frequency deceleration time
Theodore Xu 25.1 538
Theodore Xu 27.1 539 F3.14: Torque acceleration time
Theodore Xu 25.1 540
Theodore Xu 27.1 541 F3.15: Torque deceleration time
Theodore Xu 25.1 542
Theodore Xu 27.1 543 F3.07: Frequency low-pass filtering factor
Theodore Xu 25.1 544
Theodore Xu 27.1 545 F3.24: Static friction compensation
Theodore Xu 25.1 546
Theodore Xu 27.1 547 F3.25: Static friction compensation time