Wecon 1.1 1 |=(% colspan="2" %)Item|=(% colspan="2" %)VB|=VM
2 |(% rowspan="8" %)Control characteristics|Control mode|Speed sensorless vector control (SVC)|V/F control|V/F control
3 |Starting torque|0.5Hz/150%|0.5Hz/100%|0.5Hz/100%
4 |Speed range|1:100|1:50|1:50
5 |Stable speed accuracy|±0.5%|±1%|±1%
6 |Carrier frequency|(% colspan="2" %)0.5kHz - 16kHz; the carrier frequency can be automatically adjusted according to the load characteristics|1kHz - 6kHz;
7 |(% rowspan="2" %)Overload capacity|(% colspan="2" %)G type machine: 150% rated current 60s, 180% rated current 1s|(% rowspan="2" %)G type machine: 150% rated current 60s, 180% rated current 1s
8 |(% colspan="2" %)P type machine: 120% rated current 60s, 150% rated current 1s
9 |Torque boost|(% colspan="2" %)0.0% automatic torque boost; manual torque boost 0.1% - 30.0%|Manual torque increase 0.1% - 30.0%
10 |(% rowspan="4" %)input Output|Input voltage range|(% colspan="2" %)220V; fluctuation range :220V(-15%)-220V(+15%);
11 380V/415V/440V; fluctuation range:380V(-15%)-440V(+10%)|220V/380V; fluctuation range: ±15%
12 |Input frequency range|(% colspan="2" %)50/60Hz; fluctuation range: ±5%|50/60Hz; fluctuation range: ±5%
13 |Output voltage range|(% colspan="2" %)0-input voltage, the error is less than 5%|0-input voltage, the error is less than 5%
14 |Output frequency range|(% colspan="2" %)SVC: 0-320Hz; V/F: 0-1000Hz|V/F: 0-400Hz
15 |(% rowspan="8" %)Operational control|Run command channel|(% colspan="2" %)3 kinds of channels: operation panel setting, control terminal setting, serial communication port setting. It can be switched in many ways.|3 kinds of channels: operation panel setting, control terminal setting, serial communication port setting. It can be switched in many ways.
16 |Frequency source|(% colspan="2" %)Digital setting, panel pulse potentiometer setting, analog voltage setting, analog current setting, serial communication setting, etc. It can be switched in many ways.|Digital setting, panel potentiometer setting, analog voltage setting, analog current setting, serial communication setting, etc. It can be switched in many ways.
17 |Auxiliary frequency source|(% colspan="2" %)Multiple auxiliary frequency sources. Frequency synthesis, frequency fine-tuning|/
18 |(% rowspan="2" %)Input terminal|(% colspan="2" %)◆ 6 digital input terminals|◆ 4 digital input terminals
19 |(% colspan="2" %)◆ 2 analog input terminals|◆ 1 analog input terminal
20 |(% rowspan="3" %)Output terminal|(% colspan="2" %)◆ 1 open collector output terminal| 
21 |(% colspan="2" %)◆ 2 relay output terminals (1 channel below 7.5kW)|◆ 1 relay output terminal
22 |(% colspan="2" %)◆ 2 analog output terminals (1 channel below 7.5kW)|◆ 1 analog output terminal
23 |(% rowspan="12" %)basic skills|DC braking function|(% colspan="2" %)Braking time: 0.0s - 100.0s, braking action current value: 0.0% - 100.0%|Braking time: 0.0s - 100.0s, braking action current value: 0.0% - 100.0%
24 |V/F curve|(% colspan="2" %)3 methods: linear type, multi-point type, square type|3 methods: linear type, multi-point type, square type
25 |Acceleration and deceleration curve|(% colspan="2" %)Linear or S-curve acceleration and deceleration mode; four groups of acceleration and deceleration time; acceleration and deceleration time range 0.0 - 6500.0s|Linear acceleration and deceleration mode, a group of acceleration and deceleration time, range 0.0 - 100.0s
26 |Simple PLC, multi-speed|(% colspan="2" %)Realize up to 16-speed operation through built-in PLC or control terminal|Realize up to 4 speeds running through built-in PLC or control terminal
27 |Built-in PID|(% colspan="2" %)It is convenient to realize the process control closed-loop control system|It is convenient to realize the process control closed-loop control system
28 |AVR function|(% colspan="2" %)When the grid voltage changes, it can automatically keep the output voltage constant|/
29 |Overvoltage over drain speed|(% colspan="2" %)Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage trips|/
30 |Fast current limiting function|(% colspan="2" %)Minimize over-current faults and improve system stability|/
31 |Torque limit and control|(% colspan="2" %)The "shovel" feature automatically limits the torque during operation to prevent frequent over-current trips;|/
32 |Safety self-check of power-on peripherals|(% colspan="2" %)It can realize the safety detection of peripheral equipment such as grounding, short circuit, etc.|/
33 |Timing control function|(% colspan="2" %)Timing control function: set time range 0h - 65535h|/
34 |Protective function|(% colspan="2" %)Input and output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheating protection, overload protection, power-on relay fault detection, etc.|Input and output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheating protection, overload protection, power-on relay fault detection, etc.
35 |Show|(% rowspan="2" %)LED display|(% colspan="2" rowspan="2" %)5-digit LED display|(% rowspan="2" %)5-digit LED display
36 |And
37 |Keyboard|Parameter lock function|(% colspan="2" %)Set parameter read-only control to prevent misoperation|Set parameter read-only control to prevent misoperation
38 |Operation|MF.K key|(% colspan="2" %)Programmable keys: command channel switching / forward and reverse running / jog running function selection / menu mode switching|/
39 |(% rowspan="6" %)Use environment|Use place|(% colspan="2" %)Indoors, free from direct sunlight, no dust, corrosive gas, flammable gas, oil mist, water vapor, dripping water or salt, etc.|Indoors, free from direct sunlight, no dust, corrosive gas, flammable gas, oil mist, water vapor, dripping water or salt, etc.
40 |Altitude|(% colspan="2" %)Lower than 1000m; when it is higher than 1000m, it must be derated for use. For every 100m increase, it needs to be derated by 1%;|Lower than 1000m; when it is higher than 1000m, it must be derated for use. For every 100m increase, it needs to be derated by 1%;
41 |Ambient temperature|(% colspan="2" %)-10℃ - 40℃, derating is required when the temperature exceeds 40℃, and the ambient temperature needs to be derated by 1% every time the ambient temperature rises by 1℃. The maximum operating ambient temperature is 50℃|-10℃ - 40℃, derating is required when the temperature exceeds 40℃, and the ambient temperature needs to be derated by 1% every time the ambient temperature rises by 1℃. The maximum operating ambient temperature is 50℃
42 |Humidity|(% colspan="2" %)≤95%RH, avoid condensation|≤95%RH, avoid condensation
43 |Vibration|(% colspan="2" %)Vibration acceleration is less than 0.6g|Vibration acceleration is less than 0.6g
44 |Storage temperature|(% colspan="2" %)-25℃ - +60℃|-25℃ - +60℃