06 Function parameter table
○——It indicates that the set value of the parameter can be changed when the inverter is shut down or running.
●——It indicates that the setting value of the parameter cannot be changed when the inverter is in operation;
◎——It indicates that the value of the parameter is the actual detection record value and cannot be changed;
□——It indicates that the parameter is Manufacturer parameter, which can only be set by the manufacturer and cannot be operated by users.
Mailing address description:
The following table indicates the communication addresses in hexadecimal format.
In the following table, the communication address is the RAM address, and the parameter is not saved if the power fails, you need to save, please see the instructions for writing EEPROM in section 7.4.
Basic parameter set
| Function code | Name | Setting range | Default | Property | Modbus address |
|---|---|---|---|---|---|
| F0 Basic function parameter group | |||||
| F0.00 | Motor control mode | 0: SVC 1: V/F 2: - | 1 | ● | 0x0000 |
| F0.01 | Command source selection | 0: Operation panel command channel 1: Terminal command channel 2: Serial port communication command channel | 0 | ● | 0x0001 |
| F0.02 | UP/DOWN standard | 0: Operating frequency 1: Set frequency | 1 | ● | 0x0002 |
| F0.03 | Primary frequency source X selection | 0: Digital setting F0.08 (Adjustable terminal UP/DOWN, non-relative after power failure) 1: Digit setting F0.08 (Terminal UP/DOWN adjustable, power down memory) 2: AI1 3: AI2 4: Keyboard potentiometer set 5: The terminal PULSE pulse is set 6: Multi-speed instruction 7: Simple PLC 8: PID 9: Communication setting 10: AI3(Expansion module) | 4 | ● | 0x0003 |
| F0.04 | Auxiliary frequency source Y selection | Same as F0.03 | 0 | ● | 0x0004 |
| F0.05 | Range of auxiliary frequency source Y | 0: Relative to the maximum frequency F0.10 1: Relative to the frequency source X | 0 | ○ | 0x0005 |
| F0.06 | Auxiliary frequency source Y range in superposition | 0% to 150% | 100% | ○ | 0x0006 |
| F0.07 | Frequency source operation selection | LED ones: Frequency source selection 0: The primary frequency source 1: The result of primary and secondary operations 2: Switch between primary frequency source and secondary frequency source 3: Switch between the primary frequency source and the primary and secondary operation results 4: Switch between auxiliary frequency source and primary and secondary operation results LED ten: Frequency source main and auxiliary operation relationship 0: Primary + secondary 1: Primary to secondary 2: Indicates the maximum value of both 3: The minimum value of both 4: Main*auxiliary | 0 | ○ | 0x0007 |
| F0.08 | Keyboard setting frequency | 0.00Hz to Maximum frequency F0.10 | 50.00Hz | ○ | 0x0008 |
| F0.09 | Running direction selection | 0: The same direction 1: The direction is reversed 2: Reverse prohibition | 0 | ○ | 0x0009 |
| F0.10 | Maximum output frequency | 0.00Hz to 320.00Hz | 50.00Hz | ● | 0x000A |
| F0.11 | Source of frequency upper limit | 0: The number is given F0.12 1: AI1 2: AI2 3: AI3 4: Set the terminal PULSE 5: Communication setting 6: Reservations 7: Keyboard potentiometer set | 0 | ● | 0x000B |
| F0.12 | Upper limiting frequency | F0.14 to F0.10 | 50.00Hz | ○ | 0x000C |
| F0.13 | Upper frequency bias | 0.00Hz to F0.10 | 0.00Hz | ○ | 0x000D |
| F0.14 | Lower frequency | 0.00Hz to F0.12 | 0.00Hz | ○ | 0x000E |
| F0.15 | Lower frequency operating mode | 0: Run at lower frequency 1: STOP 2: Zero speed operation | 0 | ○ | 0x000F |
| F0.16 | Carrier frequency | 0.5kHz to 16.0kHz | Model determination | ○ | 0x0010 |
| F0.17 | Carrier PWM characteristic selection | Bits: Select PWM mode 0: Automatic switching; 1: 7 waves; 2: 5 waves; 3: SPWM; LED ten: Carrier is associated with the output frequency 0: Independent of output frequency 1: It depends on the output frequency LED hundred: random PWM depth 0: OFF 1 to 8: Open, adjust depth LED kilobit: Over modulation option 0: OFF 1: ON | 1010 | ● | 0x0011 |
| F0.18 | Acceleration time 1 | 0.0s to 6500.0s | Model determination | ○ | 0x0012 |
| F0.19 | Deceleration time1 | 0.0s to 6500.0s | Model determination | ○ | 0x0013 |
| F0.20 | Parameter initialization | 0: No action is taken 1: Restore factory value (Do not restore motor parameters) 2: Clear the record information 3: Restore factory value (Restore motor parameters) | 0 | ● | 0x0014 |
| F0.23 | Unit of acceleration and deceleration time | 0: 1 s 1: 0.1s 2: 01s | 1 | ● | 0x0017 |
| F0.24 | Acceleration and deceleration time reference frequency | 0: Maximum frequency (F0.10) 1: Set the frequency 2: 100 Hz | 0 | ● | 0x0018 |
| F0.25 | Fan control | Bits: Start/stop control 0: The fan runs after the inverter is powered on 1: Shutdown is related to temperature, and operation is running 2: Stop The fan stops, and the operation is related to temperature Tens place: Enables the speed adjustment function 0: Off 1: Enable | 01 | ○ | 0x0019 |
| F0.26 | Frequency command decimal point | 1: 1 decimal place 2: 2 decimal place | 2 | ● | 0x001A |
| F0.27 | Modulation ratio coefficient | 10.0 to 150.0% | 100.0% | ○ | 0x001B |
| F1 Start stop control parameter group | |||||
| F1.00 | Start-up operation mode | LED bits: Boot mode 0: Start directly from the start frequency 1: Start after speed tracking and direction judgment 2: The asynchronous machine starts with pre-excitation | 00 | ● | 0x0100 |
| F1.01 | Speed tracking mode | LED ten: Speed tracking direction 0: One to the stop direction 1: One to the starting direction 2: Automatic search | 0 | ● | 0x0101 |
| F1.02 | Speed tracking time | 0.01 to 60.00s | 1.00s | ○ | 0x0102 |
| F1.03 | Speed tracking current loop gain | 0.00 to 100.00 | 10.00 | ○ | 0x0103 |
| F1.04 | RPM tracking speed gain | 0.01 to 10.00 | 2.00 | ○ | 0x0104 |
| F1.05 | Speed tracking current | 50 to 200% | 150% | ○ | 0x0105 |
| F1.06 | Starting frequency | 0.00 to 60.00Hz | 0.00Hz | ○ | 0x0106 |
| F1.07 | Startup frequency duration | 0.0 to 50.0s | 0.0s | ● | 0x0107 |
| F1.08 | Braking current before starting | 0.0 to 150.0% | 80.0% | ● | 0x0108 |
| F1.09 | Braking time before starting | 0.0 to 60.0s | 0.0s | ● | 0x0109 |
| F1.10 | Stop method | 0: Slow down and stop 1: Free shutdown | 0 | ○ | 0x010A |
| F1.11 | Stop DC braking start frequency | 0.00Hz to F0.10 | 0.00Hz | ○ | 0x010B |
| F1.12 | Stop DC braking wait time | 0.0s to 100.0s | 0.0s | ○ | 0x010C |
| F1.13 | Stop DC braking current | 0.0% to 150.0% | 80.0% | ○ | 0x010D |
| F1.14 | Stop DC braking duration | 0.0s to 100.0s | 0.0s | ○ | 0x010E |
| F1.16 | Energy consumption brake action voltage | 115.0% to 140.0% | 130% | ● | 0x0110 |
| F1.17 | Magnetic flux braking gain | 10 to 150% | 80% | ○ | 0x0111 |
| F1.18 | Magnetic flux braking operating voltage | 110% to 500% | 120% | ○ | 0x0112 |
| F1.19 | Flux brake limiting | 0 to 200% | 20% | ○ | 0x0113 |
| F1.20 | Acceleration and deceleration selection | 0: Straight line 1: S curve | 0 | ● | 0x0114 |
| F1.21 | S-curve initial acceleration rate | 20.0% to 100.0% | 50.0% | ● | 0x0115 |
| F1.22 | S-curve initial deceleration rate | 20.0% to 100.0% | 50.0% | ● | 0x0116 |
| F1.23 | Zero speed holding torque | 0.0 to 150.0% | 0 | ● | 0x0117 |
| F1.24 | Zero speed holding torque time | 0.0 to 6000.0s If the value is set to 6000.0s, the value remains unchanged without time limit. | Model determination | ● | 0x0118 |
| F1.25 | Start pre-excitation time | 0.00 to 60.00s | 0.20 | ○ | 0x0119 |
| F1.26 | Shutdown frequency | 0.00 to 60.00Hz | 0.00Hz | ○ | 0x011A |
| F1.27 | Power failure restart action selection | 0: Invalid 1: Valid | 0 | ○ | 0x011B |
| F1.28 | Power failure restart waiting time | 0.00 to 120.00s | 0.50s | ○ | 0x011C |
| F1.29 | Select the terminal running protection | LED bits: Select the terminal run instruction when powering on 0: The terminal running instruction is invalid during power-on. 1: Terminal running instructions are valid during power-on LED ten: Run command given channel switch terminal run instruction selection 0: The terminal running instruction is invalid 1: The terminal instruction is valid when the terminal is cut in. | 11 | ○ | 0x011D |
| F2 Motor parameter group | |||||
| F2.00 | Motor type | 0: Asynchronous machine (AM) 1: Permanent magnet synchronous motor(PM) 2: Single-phase induction motor (VF control only) | 0 | ● | 0x0200 |
| F2.01 | Rated power of motor | 0.1kW to 400.0kW | Model determination | ● | 0x0201 |
| F2.02 | Rated voltage of motor | 1V to 440V | ● | 0x0202 | |
| F2.03 | Rated current of motor | 0.1to 2000.0A | ● | 0x0203 | |
| F2.04 | Rated frequency of motor | 0.01Hz to F0.10 | ● | 0x0204 | |
| F2.05 | Rated motor speed | 1rpm to 65000rpm | ● | 0x0205 | |
| F2.06 | Motor stator resistance | 0.001 to 65.000 | ● | 0x0206 | |
| F2.07 | Motor rotor resistance | 0.001 to 65.000 | ● | 0x0207 | |
| F2.08 | Motor fixed rotor inductance | 0.1 to 6500.0mH | ● | 0x0208 | |
| F2.09 | Mutual inductance of motor fixed rotor | 0.1 to 6500.0mH | ● | 0x0209 | |
| F2.10 | Motor no-load current | 0.1 to 650.0A | ● | 0x020A | |
| F2.11 | Tuning selection | 0: No operation is performed 1: Static tuning 1 2: Full tuning 3: Static tuning 2(AM calculated Lm) | 0 | ● | 0x020B |
| F2.12 | G/P model | 0: Type G machine 1: P-type machine | Model determination | ◎ | 0x020C |
| F2.13 | Single-phase motor turns ratio | 10 to 200% | 100% | ● | 0x020D |
| F2.14 | Current calibration coefficient of single-phase motor | 50 to 200% | 120% | ● | 0x020E |
| F2.15 | Number of motor poles | 2 to 48 | 4 | ● | 0x020F |
| F2.16 | Speed feedback or encoder type | Units place: encoder type 0: Expansion interface for IO module 1: Standard ABZ encoder 2: Resolver 3: UVW encoder 4: UVW encoder with reduced wiring Tens place: encoder Direction 0: Direction same 1: Direction opposite Hundreds place: break Detection 0: Disable 1: Enable Thousands Digit: Reserved | 0 | ● | 0x0210 |
| F2.17 | Photoelectric encoder line count | 0 to 60000 | 2500 | ● | 0x0211 |
| F2.18 | PG disconnection detection time | 0.000 to 60.000s | 0.100sec | ○ | 0x0212 |
| F2.19 | Resolver pole pairs | 2 to 128 | 2 | ● | 0x0213 |
| F2.20 | Encoder installation reduction ratio | 0.100 to 50.000 | 1.000 | ● | 0x0214 |
| F2.21 | Encoder filter time | 1 to 1000ms | 10ms | ● | 0x0215 |
| F2.22 | Stator resistance of synchronization | 0.001 to 65.000 (0.0010hm) | Model determination | ● | 0x0216 |
| F2.23 | Synchronize d-axis inductance | 0.01mH to 655.35mH | ● | 0x0217 | |
| F2.24 | Synchronize Q-axis inductance | 0.01mH to 655.35mH | ● | 0x0218 | |
| F2.25 | Synchronize back electromotive force | 0.1V to 1000.0V | ○ | 0x0219 | |
| F2.28 | High frequency injection voltage | 0.1% to 100.0% | 20.0% | ● | 0x021C |
| F2.29 | Back potential identification current | 0.1% to 100.0% | 50.0% | ● | 0x021D |
| F2.31 | Asynchronous no-load current per unit value | 0.1% | Model determination | ● | 0x021F |
| F2.32 | Per unit asynchronous stator resistance | 0.01% | ● | 0x0220 | |
| F2.33 | Asynchronous rotor resistance per unit value | 0.01% | ● | 0x0221 | |
| F2.34 | Asynchronous mutual inductance per unit value | 0.1% | ● | 0x0222 | |
| F2.35 | Asynchronous leakage sensing per unit value | 0.01% | ● | 0x0223 | |
| F2.36 | Per unit value of asynchronous leakage sensing coefficient | 0.01% | ● | 0x0224 | |
| F2.37 | Synchronous stator resistance per unit value | 0.01% | ● | 0x0225 | |
| F2.38 | Per unit value of synchronous D-axis inductance | 0.01% | ● | 0x0226 | |
| F2.39 | Synchronous Q-axis inductance per unit value | 0.01% | ● | 0x0227 | |
| F2.40 | Back electromotive force of synchronous motor | 0.1V | 300.0V | ● | 0x0228 |
| F2.41 | Encoder mounting angle | 0.1 ° | 0.0 ° | ● | |
| F3 Vector control parameter group | |||||
| F3.00 | ASR (Speed loop) proportional gain 1 | 0.00 to 100.00% | 20% | ○ | 0x0300 |
| F3.01 | ASR (Velocity ring) integration time 1 | 0.01s to 10.00s | 0.20 | ○ | 0x0301 |
| F3.02 | Loss of velocity protection value | 0 to 5000ms (0 Turn off stall protection) | 0ms | ○ | 0x0302 |
| F3.03 | ASR filtering time 1 | 0.000 to 0.100s | 0.000s | ○ | 0x0303 |
| F3.04 | ASR switching frequency 1 | 0.00 to 50.00Hz | 5.00Hz | ○ | 0x0304 |
| F3.05 | ASR (Speed loop) proportional gain 2 | 0.00 to 100.00% | 20% | ○ | 0x0305 |
| F3.06 | ASR (Velocity loop) integration time 2 | 0.01s to 10.00s | 0.30 | ○ | 0x0306 |
| F3.07 | Retain | 0 | - | 0x0307 | |
| F3.08 | ASR filtering time 2 | 0.000 to 0.100s | 0.000s | ○ | 0x0308 |
| F3.09 | ASR switching frequency 2 | 0.00 to 50.00Hz | 10.00Hz | ● | 0x0309 |
| F3.10 | Slip compensation coefficient | 0 to 250% | 100% | ● | 0x030A |
| F3.11 | Maximum electric torque | 0.0 to 250.0% | 160.0% | ○ | 0x030B |
| F3.12 | Maximum generating torque | 0.0 to 250.0% | 160.0% | ○ | 0x030C |
| F3.16 | Current loop D axis proportional gain | 0.1 to 10.0 | 1.0 | ● | 0x0310 |
| F3.17 | Current loop D axis integral gain | 0.1 to 10.0 | 1.0 | ○ | 0x0311 |
| F3.18 | Current loop Q axis proportional gain | 0.1 to 10.0 | 1.0 | ○ | 0x0312 |
| F3.19 | Current loop Q axis integral gain | 0.1 to 10.0 | 1.0 | ○ | 0x0313 |
| F3.20 | D-axis feed-forward gain | 0.0 to 200.0% | 50.0% | ○ | 0x0314 |
| F3.21 | Q-axis feed-forward gain | 0.0 to 200.0% | 50.0% | ○ | 0x0315 |
| F3.22 | Optimize the current loop bandwidth | 0.0 to 99.99ms | 2.00ms | ○ | 0x0316 |
| F3.23 | Current loop control word | 0 to 65535 | 0 | ○ | 0x0317 |
| F3.24 | Weak magnetic control current upper limit | 0 to 200% | 50% | ● | 0x0318 |
| F3.25 | Weak magnetic control feed forward gain | 0 to 500% | 0% | ● | 0x0319 |
| F3.26 | Weak magnetic control proportional gain | 0 to 9999 | 500 | ○ | 0x031A |
| F3.27 | Weak magnetic control integral gain | 0 to 9999 | 1000 | ○ | 0x031B |
| F3.28 | MTPA gain | 0.0 to 500.0% | 0.0% | ○ | 0x031C |
| F3.29 | MTPA filtering time | 0.0 to 999.9ms | 100.0ms | ○ | 0x031D |
| F3.30 | Magnetic flux compensation coefficient | 0 to 500% | 100% | ○ | 0x031E |
| F3.31 | Open-loop vector observeration gain | 0 to 9999 | 1024 | ○ | 0x031F |
| F3.32 | Open loop vector observation filtering time | 1 to 100ms | 20ms | ○ | 0x0320 |
| F3.33 | Open-loop vector compensates start frequency | 0 to 100.0% | 1.0% | ○ | 0x0321 |
| F3.34 | Open loop vector control word | 0 to 9999 | 8 | ○ | 0x0322 |
| F3.35 | Synchronous open loop starting mode | 0: Direct startup. 1: Start at an Angle | 0 | ○ | 0x0323 |
| F3.36 | Dc pull in time | 1ms to 9999ms | 500ms | ○ | 0x0324 |
| F3.37 | Synchronous open loop vector low-frequency boost | 0 to 100.0% | 20.0% | ○ | 0x0325 |
| F3.38 | Synchronous open loop vector high-frequency boost | 0.0 to 100.0% | 0.0% | ○ | 0x0326 |
| F3.39 | Low frequency boost to maintain frequency | 0.0 to 100.0% | 10.0% | ○ | 0x0327 |
| F3.40 | Low frequency increases cutoff frequency | 0.0 to 100.0% | 20.0% | ○ | 0x0328 |
| F3.46 | Speed/torque control mode | 0: Speed control 1: Torque control | 0 | ● | 0x032E |
| F3.47 | Torque given channel selection | 0: F3.48 is set 1: AI1╳F3.48 2: AI2╳F3.48 3: AI3╳F3.48 4: PUL╳F3.48 5: Keyboard potentiometer given ╳F7.01 6: RS485 communication given ╳F3.48 | 0 | ● | 0x032F |
| F3.48 | Torque keyboard numeric setting | 0 to 200.0% | 100.0% | ○ | 0x0330 |
| F3.49 | Torque direction selection | Units: Torque direction setting 0: The torque direction is positive 1: The torque direction is negative Tens place: torque reversing setting 0: Torque reversal is allowed 1: Torque reversal is prohibited | 00 | ○ | 0x0331 |
| F3.50 | Upper limit of output torque | F3.51 to 200.0% | 150.0% | ○ | 0x0332 |
| F3.51 | Lower limit of output torque | 0 to F3.50 | 0% | ○ | 0x0333 |
| F3.52 | Torque control forward speed limit selection | 0: F3.54 is set 1: AI1╳F3.54 2: AI2╳F3.54 3: AI3╳F3.54 4: PUL╳F3.54 5: Keyboard potentiometer given ╳F3.54 6: RS485 communication given ╳F3.54 | 0s | ○ | 0x0334 |
| F3.53 | Torque control reversal speed limit selection | 0: F3.55 is set 1: AI1╳F3.55 2: AI2╳F3.55 3: AI3╳F3.55 4: PUL╳F3.55 5: Keyboard potentiometer given ╳F3.55 6: RS485 communication given ╳F3.55 7: Purchase card | 0 | ○ | 0x0335 |
| F3.54 | Torque control positive maximum speed limit | 0.00 to upper limiting frequency | 50.00Hz | ○ | 0x0336 |
| F3.55 | Torque control reversal maximum speed limit | 0.00 to upper limiting frequency | 50.00Hz | ○ | 0x0337 |
| F3.56 | Speed/torque switching delay | 0.00 to 10.00s | 0.01s | ○ | 0x0338 |
| F3.57 | Torque acceleration time | 0.00 to 10.00s | 0.01s | ○ | 0x0339 |
| F3.58 | Torque deceleration time | 0.00 to 10.00s | 0.01s | ○ | 0x033A |
| F3.59 | Forward and reverse torque dead zone time | 0.00 to 650.00s | 0.00s | ○ | 0x033B |
| F4 V/F control parameter group | |||||
| F4.00 | Linear VF curve selection | 0: Linear V/F curve; 1: Multi-point V/F curve 2: Square V/F curve 3-11: 1.1 to 1.9 power VF curves, respectively; 12: V/F fully separated mode | 0 | ● | 0x0400 |
| F4.01 | Manual torque lift | 0.1 to 30.0%, 0 automatic torque boost | Model determination | ○ | 0x0401 |
| F4.02 | Torque boost cutoff frequency | 0.00Hz to F0.10 | 50.00Hz | ● | 0x0402 |
| F4.03 | Self-set frequency F1 | 0.00Hz to F4.05 | 3.00Hz | ● | 0x0403 |
| F4.04 | Self-set voltage V1 | 0.0% to 100.0% | 10.0% | ● | 0x0404 |
| F4.05 | Self-set frequency F2 | F4.03 to F4.07 | 5.00Hz | ● | 0x0405 |
| F4.06 | Self-set voltage V2 | 0.0% to 100.0% | 15.0% | ● | 0x0406 |
| F4.07 | Self-set frequency F3 | F4.05 to F4.09 | 8.00Hz | ● | 0x0407 |
| F4.08 | Self-set voltage V3 | 0.0% to 100.0% | 22.0% | ● | 0x0408 |
| F4.09 | Self-set frequency F4 | F4.07-Rated frequency of motor F2.04 | 12.00Hz | ● | 0x0409 |
| F4.10 | Self-set voltage V4 | 0.0% to 100.0% | 31.0% | ● | 0x040A |
| F4.11 | Oscillation suppression gain | 0.0 to 10.0 | Model determination | ○ | 0x040B |
| F4.12 | Oscillation suppression filtering time | 1 to 1000ms | 50ms | ○ | 0x040C |
| F4.14 | Percentage of output voltage | 25 to 100% | 100% | ● |
0x040E |
| F4.16 | AVR function
| 0: Invalid 1: Only slowing down is not effective 2: Only constant speed is effective 3: Valid | 3 | ● | 0x0410 |
| F4.17 | EVF torque boost gain | 0 to 500.0% | 50.0% | ○ | 0x0411 |
| F4.18 | EVF torque boost filtering time | 1 to 1000ms | 20ms | ○ | 0x0412 |
| F4.19 | EVF slip compensation gain | 0 to 500.0% | 0.0% | ○ | 0x0413 |
| F4.20 | EVF slip compensation filtering time | 1 to 1000ms | 100ms | ○ | 0x0414 |
| F4.21 | Automatic energy saving selection | Units place: 0 is off, 1 is on Tens place: Frequency change exit depth Hundreds place: Reserve Thousands place: Reserve | 50 | ○ | 0x0415 |
| F4.22 | Lower limit frequency of energy saving operation | 0.0 to 100.0% | 25.0% | ○ | 0x0416 |
| F4.23 | Energy saving and pressure reduction time | 0.1 to 5000.0s | 10.0s | ○ | 0x0417 |
| F4.24 | Lower limit of energy saving and pressure reduction | 20.0 to 100.0% | 30.0% | ○ | 0x0418 |
| F4.25 | Energy saving and pressure reduction rate | 1 to 1000V/s | 50V/s | ○ | 0x0419 |
| F4.26 | Voltage regulated proportional gain | 0 to 100 | 20 | ○ | 0x041A |
| F4.27 | Voltage regulation integral gain | 0 to 100 | 20 | ○ | 0x041B |
| F4.30 | Stabilizer proportional gain | 0.1% to 100.0% | 10.0% | ○ | 0x041E |
| F4.31 | Stabilizer filtering time | 1ms to 1000ms | 50ms | ○ | 0x041F |
| F4.32 | Low frequency current lift | 0.0% to 200.0% | 100.0% | ○ | 0x0420 |
| F4.33 | Low frequency boost maintenance frequency | 0 to 100.0% | 10.0% | ○ | 0x0421 |
| F4.34 | Low frequency current boosts the cutoff frequency | 0 to 100.0% | 30.0% | ○ | 0x0422 |
| F4.35 | D-axis current gain | 0.0 to 100.0 | 2.0 | ○ | 0x0423 |
| F4.36 | Q-axis current gain | 0.0 to 100.0 | 2.0 | ○ | 0x0424 |
| F4.37 | Magnetic flux set strength | 0 to 500% | 30% | ○ | 0x0425 |
| F4.38 | Magnetic flux control proportional gain | 0 to 9999 | 500 | ○ | 0x0426 |
| F4.39 | Magnetic flux controls the integral gain | 0 to 9999 | 500 | ○ | 0x0427 |
| F4.40 | Dc pull in time | 1ms to 9999ms | 1000ms | ○ | 0x0428 |
| F4.41 | Starting frequency | 0.00Hz to 99.00Hz | 3.00Hz | ○ | 0x0429 |
| F4.42 | Starting frequency time | 0.0s to 999.0s | 3.0s | ○ | 0x042A |
| F4.43 | V/F Separate the output voltage source | 0: Function code F0.27 set 1: AI1 is set 2: AI2 is set 3: Reservations 4: Set the terminal PULSE 5: Multi-speed 6: Simple PLC 7: PID 8: Communication is given 100% corresponding to the rated voltage of the motor | 0 | ○ | 0x042B |
| F4.44 | V/F separation output voltage digital setting | 0.0% to 100.0% | 0 | ○ | 0x042C |
| F4.45 | V/F separation voltage rise time | 0.0 to 1000.0s | 1.0 | ○ | 0x042D |
| F4.46 | V/F separation voltage drop time | 0.0 to 1000.0s | 1.0 | ○ | 0x042E |
| F4.47 | V/F separate stop mode | 0: The voltage/frequency is simultaneously reduced to 0; 1: The frequency decreases after the voltage drops to 0 | 0 | ○ | 0x042F |
| F5 Enter the terminal parameter group | |||||
| F5.00 | DI1 Terminal function selection | 0: Non-function 0: Non-function 1: FWD 2: REV 3: Three-wire operation control 4: FJOG 5: RJOG 6: Terminal UP 7: Terminal DOWN 8: Free break 9: RESET 10: Running pause 11: External fault input(NO) 12: Multi-speed instruction terminal 1 13: Multi-speed instruction terminal 2 14: Multi-speed instruction terminal 3 15: Multi-speed instruction terminal 4 16: Acceleration and deceleration time select terminal 1 17: Acceleration and deceleration time select terminal 2 18: Frequency source switching (terminal, keyboard) 19: The UP/DOWN setting clears zero 20: Run the command to switch terminals 21: Acceleration and deceleration prohibition 22: PID pause 23: PLC State reset 24: Swing pause 25: Counter input 26: Counter reset 27: Length count input 28: Length reset 29: Torque control prohibited 30: PULSE impulse input(only DI4) 31: Reverse 32: Immediate DC braking 33: The external fault is normally closed 34: Reverse 35: The direction of PID action is reversed 36: External parking terminal 1 37: Control command switching terminal 38: PID integration pause terminal 39: Main frequency source and preset frequency switching terminal 40: Auxiliary frequency source and preset frequency switching terminal 41: Retain 42: Retain 43: PID parameter switching terminal 44: User-defined fault 1 45: User-defined fault 2 46: Speed control/torque control switch 47: Emergency stop 48: External parking terminal 2 49: Decelerate DC braking 50: The running time is cleared 51: Timing enable 52: Timing reset | 1 | ● | 0x0500 |
| F5.01 | DI2 Terminal function selection | 2 | ● | 0x0501 | |
| F5.02 | DI3 Terminal function selection | 9 | ● | 0x0502 | |
| F5.03 | DI4 Terminal function selection | 12 | ● | 0x0503 | |
| F5.04 | DI5 Terminal function selection (Extension) | 0 | ● | 0x0504 | |
| F5.05 | DI6 Terminal function selection (Extension) | 0 | ● | 0x0505 | |
| F5.08 | AI1 Indicates the DI terminal function | 0 | ● | 0x0508 | |
| F5.09 | AI2 Indicates the DI terminal function | 0 | ● | 0x0509 | |
| F5.10 | AI1 Input selection | 0: 0-10V 3: 0-5V 4: 0.5-4.5V | 0 | ● | 0x050A |
| F5.11 | AI2 Input selection | 0: 0-10V 1: 4-20mA 2: 0-20mA 3: 0-5V 4: 0.5-4.5V | 1 | ● | 0x050B |
| F5.12 | VDI1 terminal function selection | 0: Non-function 1: FWD 2: REV 3: Three-wire operation control 4: FJOG 5: RJOG 6: Terminal UP 7: terminal DOWN 8: Free break 9: RESET 10: Running pause 11: External fault input(NO) 12: Multi-speed instruction terminal 1 13: Multi-speed instruction terminal 2 14: Multi-speed instruction terminal 3 15: Multi-speed instruction terminal 4 16: Acceleration and deceleration time select terminal 1 17: Acceleration and deceleration time select terminal 2 18: Frequency source switching (terminal, keyboard) 19: The UP/DOWN setting clears zero 20: Run the command to switch terminals 21: Acceleration and deceleration prohibition 22: PID pause 23: PLC State reset 24: Swing pause 25: Counter input 26: Counter reset 27: Length count input 28: Length reset 29: Torque control prohibited 30: PULSE impulse input(only DI4) 31: Reverse 32: Immediate DC braking 33: The external fault is normally closed 34: Reverse 35: The direction of PID action is reversed 36: External parking terminal 1 37: Control command switching terminal 38: PID integration pause terminal 39: Main frequency source and preset frequency switching terminal 40: Auxiliary frequency source and preset frequency switching terminal 41: Reverse 42: Reverse 43: PID parameter switching terminal 44: User-defined fault 1 45: User-defined fault 2 46: Speed control/torque control switch 47: Emergency stop 48: External parking terminal 2 49: Decelerate DC braking 50: The running time is cleared 51: Timing enable 52: Timing reset | 0 | ● | 0x050C |
| F5.13 | VDI2 terminal function selection | 0 | ● | 0x050D | |
| F5.14 | VDI3 terminal function selection | 0 | ● | 0x050E | |
| F5.15 | DI filtering time | 0.000s to 1.000s | 0.010s | ○ | 0x050F |
| F5.16 | Terminal command mode | 0: Two-wire type 1 1: Two-wire type 2 2: Three-wire type 1 3: Three-wire type 2 | 0 | ● | 0x0510 |
| F5.17 | UP/DOWN change rate | 0.01Hz to 655.35Hz | 0.50Hz | ○ | 0x0511 |
| F5.18 | AI1 minimum input | 0.00V to F5.20 | 0.00V | ○ | 0x0512 |
| F5.19 | AI1 minimum input setting | -100.0% to +100.0% | 0% | ○ | 0x0513 |
| F5.20 | AI1 maximum input | F5.18 to +10.00V | 10.00V | ○ | 0x0514 |
| F5.21 | AI1 maximum input setting | -100.0% to +100.0% | 100.0% | ○ | 0x0515 |
| F5.22 | AI1 filtering time | 0.00s to 10.00s | 0.10s | ○ | 0x0516 |
| F5.23 | AI2 minimum input | -10.00V to F5.25 | 2.00V | ○ | 0x0517 |
| F5.24 | AI2 minimum input setting | -100.0% to +100.0% | 0% | ○ | 0x0518 |
| F5.25 | AI2 maximum input | F5.23 to +10.00V | 10.00V | ○ | 0x0519 |
| F5.26 | AI2 maximum input setting | -100.0% to +100.0% | 100.0% | ○ | 0x051A |
| F5.27 | AI2 filtering time | 0.00s to 10.00s | 0.10s | ○ | 0x051B |
| F5.28 | PULSE | 0.00 to F5.30 | 0.00kHz | ○ | 0x051C |
| F5.29 | PULSE input minimum frequency setting | 0.00 to 100.00% | 0% | ○ | 0x051D |
| F5.30 | PULSE input maximum frequency | F5.28 to 50.00kHz | 20.00kHz | ○ | 0x051E |
| F5.31 | PULSE maximum frequency setting | 0.00 to 100.00% | 100.0% | ○ | 0x051F |
| F5.32 | PULSE filtering time | 0.0s to 10.00s | 0.10s | ○ | 0x0520 |
| F5.33 | DI1 Enable delay time | 0.0s to 360.0s | 0.0s | ○ | 0x0521 |
| F5.34 | DI2 Enable delay time | 0.0s to 360.0s | 0.0s | ○ | 0x0522 |
| F5.35 | DI1 Forbidden delay time | 0.0s to 360.0s | 0.0s | ○ | 0x0523 |
| F5.36 | DI2 Forbidden delay time | 0.0s to 360.0s | 0.0s | ○ | 0x0524 |
| F5.37 | Enter terminal valid status setting 1 | 0: Low level valid 1: High level valid LED one place: D1 terminal LED tens place: D2 terminal LED hundreds place: D3 terminal LED thousands place: D4 terminal | 0 | ● | 0x0525 |
| F5.38 | Enter terminal valid status setting 2 | 0: Low level valid 1: High level valid LED one place: D5 terminal(expend) LED tens place: D6 terminal(expend) | 0 | ● | 0x0526 |
| F5.39 | Enter terminal valid status setting 3 | 0: Low level valid 1: High level valid LED one place: AI1 LED tens place: AI2 LED hundreds place: AI3(expend) | 0 | ● | 0x0527 |
| F5.40 | Analog input curve selection | One place: AI1 Tens place: AI2 Hundreds place: AI3 (expend) 0: Straight line (default) 1: Curve 1 2: Curve 2 | 0 | ● | 0x0528 |
| F5.41 | Lower limit of curve 1 | 0.00 to F5.43 | 0.00V | ○ | 0x0529 |
| F5.42 | The lower limit of curve 1 is set accordingly | 0.00 to 100.00% | 0.0% | ○ | 0x052A |
| F5.43 | Curve 1 inflection point 1 Input voltage | F5.41 to F5.45 | 3.00V | ○ | 0x052B |
| F5.44 | Curve 1 inflection point 1 corresponds to the setting | 0.00 to 100.00% | 30.0% | ○ | 0x052C |
| F5.45 | Curve 1 inflection point 2 Input voltage | F5.43 to F5.47 | 6.00V | ○ | 0x052D |
| F5.46 | Curve 1 inflection point 2 corresponds to the setting | 0.00 to 100.00% | 60.0% | ○ | 0x052E |
| F5.47 | Upper limit of curve 1 | F5.45 to 10.00V | 10.0V | ○ | 0x052F |
| F5.48 | The upper limit of curve 1 is set accordingly | 0.00 to 100.00% | 100.0% | ○ | 0x0530 |
| F5.49 | Lower limit of curve 2 | 0.00 to F5.51 | 0.00V | ○ | 0x0531 |
| F5.50 | The lower limit of curve 2 is set accordingly | 0.00 to 100.00% | 0.0% | ○ | 0x0532 |
| F5.51 | Curve 2 Inflection point 1 Input voltage | F5.49 to F5.53 | 3.00V | ○ | 0x0533 |
| F5.52 | Curve 2 inflection point 1 corresponds to the setting | 0.00 to 100.00% | 30.0% | ○ | 0x0534 |
| F5.53 | Curve 2 Inflection point 2 Input voltage | F5.51 to F5.55 | 6.00V | ○ | 0x0535 |
| F5.54 | Curve 2 inflection point 2 corresponds to the setting | 0.00 to 100.00% | 60.0% | ○ | 0x0536 |
| F5.55 | Upper limit of curve 2 | F5.53 to 10.00V | 10.00V | ○ | 0x0537 |
| F5.56 | The upper limit of curve 2 is set accordingly | 0.00 to 100.00% | 100.0% | ○ | 0x0538 |
| F5.57 | AI3(Extension) is used to select the DI terminal function | 0: Non-function 1: FWD 2: REV 3: Three-wire operation control 4: FJOG 5: RJOG 6: Terminal UP 7: terminal DOWN 8: Free break 9: RESET 10: Running pause 11: External fault input(NO) 12: Multi-speed instruction terminal 1 13: Multi-speed instruction terminal 2 14: Multi-speed instruction terminal 3 15: Multi-speed instruction terminal 4 16: Acceleration and deceleration time select terminal 1 17: Acceleration and deceleration time select terminal 2 18: Frequency source switching (terminal, keyboard) 19: The UP/DOWN setting clears zero 20: Run the command to switch terminals 21: Acceleration and deceleration prohibition 22: PID pause 23: PLC State reset 24: Swing pause 25: Counter input 26: Counter reset 27: Length count input 28: Length reset 29: Torque control prohibited 30: PULSE impulse input(only DI4) 31: Retain 32: Immediate DC braking 33: The external fault is normally closed 34: Retain 35: The direction of PID action is reversed 36: External parking terminal 1 37: Control command switching terminal 38: PID integration pause terminal 39: Main frequency source and preset frequency switching terminal 40: Auxiliary frequency source and preset frequency switching terminal 41: Retain 42: Retain 43: PID parameter switching terminal 44: User-defined fault 1 45: User-defined fault 2 46: Speed control/torque control switch 47: Emergency stop 48: External parking terminal 2 49: Decelerate DC braking 50: The running time is cleared 51: Timing enable 52: Timing reset | ○ | 0x0539 | |
| F5.58 | AI4 (Extension) is used to select the DI terminal function | ||||
| F5.59 |
AI3(Extension) Input selection | 0: 0 to 10V 1: 4 to 20mA 2: 0 to 20mA 3: 0 to 5V 4: 0.5 to 4.5V | 0 | 0x053A | |
| F5.60 | AI4(Extension) Input selection | 0: 0 to 10V 1: 4 to 20mA 2: 0 to 20mA 3: 0 to 5V 4: 0.5 to 4.5V | 0 | 0x053B | |
| F5.61 | AI3(Extended) lower limit | 0 to F5.63 | 0.00V | ○ | 0x053C |
| F5.62 | AI3(Extended) lower limit is set accordingly | -100.0% to +100.0% | 0.00% | ○ | 0x053D |
| F5.63 | AI3(Extended) Upper limit | F5.61 to +10.00V | 10.00V | ○ | 0x053E |
| F5.64 | The AI3(Extended) upper limit corresponds to the setting | -100.0% to +100.0% | 100.00% | ○ | 0x053F |
| F5.65 | AI3(Extended) filtering time | 0.00 to 10.00s | 0.10s | ○ | 0x0540 |
| F5.71 | vX terminal valid state source | 0: Internal connection with virtual vYn 1: Whether the function code setting is valid. One place: Virtual VDI1 Tens place: Virtual VDI2 Hundred bit: Virtual VDI3 Thousands: Reserved | 0 | ○ | 0x0547 |
| F5.72 | Virtual vX terminal function code set valid status | 0: Invalid; 1: Valid Units bit: Virtual VDI1 Tens place: Virtual VDI2 Hundreds place: Virtual VDI3 Thousands place: Reserved | 0 | ○ | 0x0548 |
| F5.73 | Select the terminal action mode | LED one place: free shutdown terminal recovery mode 0: Restore the original command after it is invalid 1: The original instruction is not restored if invalid LED tens place: emergency stop terminal recovery mode 0: Restore the original command after disconnection 1: The original command is not restored after the disconnect LED hundreds place: Select terminal operation mode after fault reset 0: The terminal control can be started directly 1: Stop the terminal control before starting LED thousands place: Reserve | 111 | ○ | 0x0549 |
| F6 Output terminal parameter group | |||||
| F6.00 | FM terminal output selection | 0: Pulse output 1: Open collector output (FMR) | 1 | ○ | 0x0600 |
| F6.01 | FMR open collector output selection | 0: No output 1: The inverter is in operation 2: Fault output (Fault shutdown) 3: Frequency level detection FDT1 Output 4: Frequency reaches 5: Zero speed running 1 6: Motor overload forecast alarm 7: Inverter overload forecast alarm 8: Set meter value reached 9: The specified count value is reached 10: Length reached 11: The PLC cycle is complete 12: The accumulated running time reaches 13: Reservations 14: Torque limit 15: Ready to run 16: AI1 > AI2 17: The upper frequency reaches 18: The lower limit frequency reaches 1 19: Output in undervoltage state 20: Communication control 21: Positioning completed (reserved) 22: Positioning close (reserved) 23: Zero speed running 2 24: The cumulative power-on time reaches 25: Frequency level detection FDT2 output 26: Frequency reaches 1 output 27: Frequency reaches 2 output 28: Current reaches 1 output 29: Current reaches 2 output 30: timed to reach output 31: Reserved 32: Reserved 33: Running direction 34: Reserved 35: The module temperature reaches 36: Reserved 37: The lower limit frequency reaches 2 38: Fault output 2 39: Reserved 40: The running time arrives 41: User-defined output 1 42: User-defined output 2 43: Timer output 44: Running forward 45: Reverse running | 0 | ○ | 0x0601 |
| F6.02 | Relay 1 output selection | 2 | ○ | 0x0602 | |
| F6.03 | Relay 2 output selection (Extended) | 0 | ○ | 0x0603 | |
| F6.06 | VDO1 output selection | 0 | ● | 0x0606 | |
| F6.07 | VDO2 output selection | 0 | ● | 0x0607 | |
| F6.08 | VDO3 output selection | 0 | ● | 0x0608 | |
| F6.09 | Reserve | - | 0x0609 | ||
| F6.10 | AO Output signal selection | One place: AO1 0: 0 to 10V 1: 4.00 to 20.00mA 2: 0.00 to 20.00mA Tens place: AO2 (expend) 0: 0 to 10V 1: 4.00 to 20.00mA 2: 0.00 to 20.00mA | 00 | - | 0x060A |
| F6.11 | FMP (Pulse output terminal) output selection | 0: Run frequency 1: Setting frequency 2: Output current 3: Output torque 4: Output power 5: Output voltage 6: Reserve 7: AI1 8: AI2 9: AI3(Expansion module) 10: PULSE input value 11: Reserve 12: Communication setting 13: Motor speed 14: Output current (0-1000A, corresponding to 0-10V) 15: Output voltage (0-1000V, corresponding to 0-10V) 16: Bus voltage (0-1000V, corresponding to 0-10V) | 0 | ○ | 0x060B |
| F6.12 | AO1 Output selection | 0 | ○ | 0x060C | |
| F6.13 | AO2 Output(expend) | 0 | ○ | 0x060D | |
| F6.14 | FM frequency output upper limit | 0.00 to 20.00kHz | 20.00kHz | ○ | 0x060E |
| F6.15 | AO1 Minimum input | 0.00V to F6.17 | 0.00V | ○ | 0x060F |
| F6.16 | AO1 Minimum input corresponds to setting | 0.0% to +100.0% | 0.0% | ○ | 0x0610 |
| F6.17 | AO1 Maximum output | F6.15 to +10.00V | 10.00V | ○ | 0x0611 |
| F6.18 | AO1 The maximum output corresponds to the setting | 0.0% to +100.0% | 100.0% | ○ | 0x0612 |
| F6.19 | AO2 Minimum output(expend) | 0.00V to F6.21 | 0.00V | ○ | 0x0613 |
| F6.20 | AO2 Minimum output correspondence settings (expend) | 0.0% to +100.0% | 0.0% | ○ | 0x0614 |
| F6.21 | AO2 Maximum output(expend) | F6.19 to +10.00V | 10.00V | ○ | 0x0615 |
| F6.22 | AO2 Maximum output correspondence settings (expend) | 0.0% to +100.0% | 100.0% | ○ | 0x0616 |
| F6.23 | FMR connecting delay time | 0.0s to 3600.0s | 0.0s | ○ | 0x0617 |
| F6.24 | Relay 1 connecting delay time | 0.0 to 3600.0s | 0.0s | ○ | 0x0618 |
| F6.25 | Relay 2 connecting delay time(expend) | 0.0s to 3600.0s | 0.0s | ○ | 0x0619 |
| F6.26 | VDO connecting delay time | 0.0 to 3600.0s | 0.0s | ○ | 0x061A |
| F6.27 | FMR disconnect delay time | 0.0s to 3600.0s | 0.0s | ○ | 0x061B |
| F6.28 | Relay 1 disconnect delay time | 0.0 to 3600.0s | 0.0s | ○ | 0x061C |
| F6.29 | Relay 2 disconnect delay time(expend) | 0.0s to 3600.0s | 0.0s | ○ | 0x061D |
| F6.30 | VDO1 disconnect delay | 0.0 to 3600.0s | 0.0s | ○ | 0x061E |
| F6.31 | Output terminal valid status select 1 | 0: Positive logic 1: Reverse logic One place: FDOR Tens place: RL1 Hundreds place: RL2 (Extended) Thousands place: - | 000 | ○ | 0x061F |
| F6.32 | Virtual output terminal valid status Select 2 | 0: Positive logic 1: Reverse logic One place: VDO1 Tens place: VDO2 Hundreds place: VDO3 Thousands palce: - | 000 | ○ | 0x0620 |
| F6.33 | User-defined output selection (EX) 1 | 0: The running frequency 1: Set the frequency 2: Bus voltage 3: Output voltage 4: Output current 5: Output power 6: Output torque 7 to 8: Reserved 9: AI1 input 10: AI2 input 11: AI3 input(expansion module) | 0 | ○ | 0x0621 |
| F6.34 | User selected comparison method 1 | Units: Compare test methods 0: Equal to (EX == X1) 1: The value is greater than or equal to 2: Less than or equal to 3: Interval comparison (X1 ≤ EX ≤ X2) 4: Bit test (EX & X1=X2) Tens: output mode 0: False value output 1: Truth output | 0 | ○ | 0x0622 |
| F6.35 | User-defined dead zone 1 | 0 to 65535 | 0 | ○ | 0x0623 |
| F6.36 | User-defined 1 output comparison value 1 | 0 to 65535 | 0 | ○ | 0x0624 |
| F6.37 | User defined 1 output comparison value 2 | 0 to 65535 | 0 | ○ | 0x0625 |
| F6.38 | User-defined output selection (EX) 2 | 0: The running frequency 1: Set the frequency 2: Bus voltage 3: Output voltage 4: Output current 5: Output power 6: Output torque 7 to 8: Reserved 9: AI1 input 10: AI2 input 11: AI3 input(Expansion module) | 0 | ○ | 0x0626 |
| F6.39 | User defined comparison method 2 | One place: Compare test methods 0: Equal to (EX == X1) 1: The value is greater than or equal to 2: Less than or equal to 3: Interval comparison (X1 ≤ EX ≤ X2) 4: Bit test (EX & X1=X2) Tens: output mode 0: False value output 1: Truth output | 0 | ○ | 0x0627 |
| F6.40 | User-defined dead zone 2 | 0 to 65535 | 0 | ○ | 0x0628 |
| F6.41 | User defined 2 output comparison value 1 | 0 to 65535 | 0 | ○ | 0x0629 |
| F6.42 | User defined 2 output comparison value 2 | 0 to 65535 | 0 | ○ | 0x062A |
| F6.43 | Timer time unit | 0: Second 1: Min 2: Hour | 0 | ○ | 0x062B |
| F6.44 | Timer maximum | 0-65000 (No reset when the set value is 65000) | 0 | ○ | 0x062C |
| F6.45 | Timer set value | 0 to 65000 | 0 | ○ | 0x062D |
| F6.46 | Counter maximum | 0 to 65000 | 0 | ○ | 0x062E |
| F6.47 | Counter set value | 0 to 65000 | 0 | ○ | 0x062F |
| F7 Keyboard and display parameter group | |||||
| F7.00 | LCD Keyboard parameter copy | 0: No operation is performed 1: The function parameters of the machine are uploaded to the LCD keyboard 2: LCD keyboard function parameters download to the machine | 0 | ○ | 0x0700 |
| F7.01 | ENT key function selection | 0: ENT is invalid. 1: Switch between the instruction channel of the operation panel and the remote instruction channel (the remote instruction channel includes communication and terminal control) 2: Reverse switch 3: Forward jog 4: Reverse jog 5: Menu mode switch 6: Reverse operation | 0 | ● | 0x0701 |
| F7.02 | Keyboard STOP key range | LED one place: Terminal control selection 0: The terminal instruction is invalid 1: Valid for the terminal command LED tens place: Communication control selection 0: The communication instruction is invalid. 1: Valid for communication instructions LED hundreds place: Reserved LED thousands place: Reserved | 0011 | ○ | 0x0702 |
| F7.03 | Keyboard run displays parameter 1 | LED one place: First group display 0: Output frequency 1: Given frequency 2: Bus voltage 3: Output voltage 4: Output current 5: Output power 6: Output torque 7: DI input status 8: DO output status 9: AI1 voltage A: AI2 voltage B: AI3 voltage(expansion module) C: Reserved D: Reserved E: Motor speed F: PID setting LED tens place: second group display LED hundreds place: Third group display LED thousands place: Fourth group display | E420 | ○ | 0x0703 |
| F7.04 | Keyboard run displays parameter 2 | LED one place: First group display 0: Not displayed 1: PID feedback 2: PLC stage 3: PULSE input pulse frequency 4: Feedback speed 5: Reserved 6: Reserved 7: Reserved 8: Reserved 9: Current power-on time A: Current running time B: Reserved C: Communication setting D: Reserved E: Main frequency X display F: Auxiliary frequency Y display LED ten: Second group display LED hundreds place: Third group display LED thousands place: Fourth group display | 0000 | ○ | 0x0704 |
| F7.05 | Keyboard stop displays parameters | LED one place: First group display 0: Output frequency 1: Given frequency 2: Bus voltage 3: Output voltage 4: Output current 5: Output power 6: Output torque 7: DI input status 8: DO output status 9: AI1 voltage A: AI2 voltage B:AI3 voltage(Expansion module) C: Motor speed D: PID setting E: PID feedback F: PLC stage LED tens place: Second group display LED hundreds place: Third group display LED thousands place: Fourth group display | C421 | ○ | 0x0705 |
| F7.06 | Load speed display factor | 0.001 to 65.000 | 1.000 | ○ | 0x0706 |
| F7.07 | Radiator temperature of inverter module | 0℃ to 100℃ | ◎ | 0x0707 | |
| F7.08 | Radiator temperature of rectifier bridge | 0℃ to 100℃ | ◎ | 0x0708 | |
| F7.09 | Cumulative running time | 0h to 65535h | ◎ | 0x0709 | |
| F7.10 | Product number | - | ◎ | 0x070A | |
| F7.11 | Software version | - | ◎ | 0x070B | |
| F7.12 | Reverse | ◎ | 0x070C | ||
| F7.13 | Total power-on time | 0 to 65535h | ◎ | 0x070D | |
| F7.14 | High cumulative power consumption | Power consumption =F7.14*65535+F7.15 Units: kWh | ◎ | 0x070E | |
| F7.15 | Low cumulative power consumption | ◎ | 0x070F | ||
| F7.16 | Output power correction factor | 0 to 100.0% | 100.0% | ○ | 0x0710 |
| F7.17 | Power display dimension selection | 0 to Power display percentage (%) 1 to Power display kilowatts (KW) | 1 | ○ | 0x0711 |
| F8 Auxiliary function parameter group | |||||
| F8.00 | JOG running frequency | 0.00Hz to Maximum frequency F0.10 | 2.00Hz | ○ | 0x0800 |
| F8.01 | JOG acceleration time | 0.00s to 6500.0s | 20.0s | ○ | 0x0801 |
| F8.02 | JOG deceleration time | 0.00s to 6500.0s | 20.0s | ○ | 0x0802 |
| F8.03 | Acceleration time 2 | 0.00s to 6500.0s | Model determination | ○ | 0x0803 |
| F8.04 | Deceleration time 2 | 0.00s to 6500.0s | ○ | 0x0804 | |
| F8.05 | Acceleration time 3 | 0.00s to 6500.0s | ○ | 0x0805 | |
| F8.06 | Deceleration time 3 | 0.00s to 6500.0s | ○ | 0x0806 | |
| F8.07 | Acceleration time 4 | 0.00s to 6500.0s | ○ | 0x0807 | |
| F8.08 | Deceleration time 4 | 0.00s to 6500.0s | ○ | 0x0808 | |
| F8.09 | Emergency stop deceleration time | 0.00s to 6500.0s | ○ | 0x0809 | |
| F8.10 | Jump frequency 1 | 0.00Hz to Maximum frequency | 0.00Hz | ○ | 0x080A |
| F8.11 | Jump frequency 2 | 0.00Hz to Maximum frequency | 0.00Hz | ○ | 0x080B |
| F8.12 | Jump frequency amplitude | 0.00Hz to Maximum frequency | 0.00Hz | ○ | 0x080C |
| F8.13 | Forward-reverse dead zone time | 0.0 to 120.0s | 0.0s | ○ | 0x080D |
| F8.14 | The carrier frequency is adjusted with temperature | 0: Temperature independent 1: Temperature dependent | 1 | ○ | 0x080E |
| F8.15 | Terminal action is preferred | 0: Invalid 1: Valid | 1 | ○ | 0x080F |
| F8.16 | Setting of accumulated power-on arrive time | 0h to 65000h | 0h | ○ | 0x0810 |
| F8.17 | Set the accumulative running arrival time | 0h to 65000h | 65000h | ○ | 0x0811 |
| F8.18 | Setting of accumulated power-on arrive action | 0: Continue to run 1: Fault warning | 0 | ● | 0x0812 |
| F8.19 | Set the accumulative running time arrival action | 0: Continue to run 1: Fault warning | 0 | ● | 0x0813 |
| F8.20 | Arrival time of this run | 0 to 65000min | 0 | ○ | 0x0814 |
| F8.21 | The running time reaches the action selection | 0: Continue to run 1: Fault prompt | 0 | ● | 0x0815 |
| F8.22 | Frequency detection value(FDT1) | 0.00 to Maximum frequency | 50.00Hz | ○ | 0x0816 |
| F8.23 | Frequency detection lag value(FDT1) | 0.00 to Maximum frequency | 0.00Hz | ○ | 0x0817 |
| F8.24 | Frequency detection value(FDT2) | 0.00 to Maximum frequency | 50.00Hz | ○ | 0x0818 |
| F8.25 | Frequency detection lag value(FDT2) | 0.00-Maximum frequency | 0.00Hz | ○ | 0x0819 |
| F8.26 | Frequency reaches the detect width | 0.0% to 100.0% (Maximum frequency) | 0.0% | ○ | 0x081A |
| F8.27 | Arbitrary arrival frequency detection value 1 | 0.00Hz to Maximum frequency | 50.00Hz | ○ | 0x081B |
| F8.28 | Arbitrary arrival frequency detection amplitude 1 | 0.0% to 100.0% (Maximum frequency) | 0.0% | ○ | 0x081C |
| F8.29 | Arbitrary arrival frequency detection value 2 | 0.00Hz to Maximum frequency | 50.00Hz | ○ | 0x081D |
| F8.30 | Arbitrary arrival frequency detection amplitude 1 | 0.0% to 100.0% (Maximum frequency) | 0.0% | ○ | 0x081E |
| F8.31 | Arbitrarily reach current1 | 0.0% to 300.0% (Motor rated current) | 100.0% | ○ | 0x081F |
| F8.32 | Arbitrarily reach current 1 width | 0.0% to 300.0% (Motor rated current) | 0.0% | ○ | 0x0820 |
| F8.33 | Arbitrarily reach current 2 | 0.0% to 300.0% (Motor rated current) | 100.0% | ○ | 0x0821 |
| F8.34 | Arbitrarily reach current 2 width | 0.0% to 300.0% (Motor rated current) | 0.0% | ○ | 0x0822 |
| F8.35 | Zero current detection value | 0.0% to 300.0%(Motor rated current) | 5.0% | ○ | 0x0823 |
| F8.36 | Zero current detection delay time | 0 to 600.00s | 0s | ○ | 0x0824 |
| F8.37 | Software over current point (D0 output) | 0.0% to 300.0% (AC drive rated current) | 200.0% | ○ | 0x0825 |
| F8.38 | Software over current detection delay time | 0 to 600.00s | 0s | ○ | 0x0826 |
| F9 Functional parameter array | |||||
| F9.00 | PID setting source | 0: Keyboard number PID given F9.01 1: AI1 2: AI2 3: Reserve 4: Terminal pulse setting 5: Communication setting 6: Multi -stage speed setting 7: Keyboard potentiometer setting | 0 | ○ | 0x0900 |
| F9.01 | PID digital setting | 0.0% to 100.0% | 50.0% | ○ | 0x0901 |
| F9.02 | PID feedback source | 0: AI1 1: AI2 2: Reserve 3: AI1-AI2 4: Terminal pulse setting 5: Communication setting 6: AI1+AI2 7: MAX(|AI1|, |AI2|) 8: MIN(|AI1|, |AI2|) 9: Keyboard potentiometer setting | 0 | ○ | 0x0902 |
| F9.03 | PID control characteristics | LED units: Feedback characteristic selection 0: Positive action 1: Reaction LED tens: PID adjustment direction selection 0: Reverse prohibition 1: Reverse permit LED hundreds digit: Alignment selection 0: Off-center alignment 1: Center alignment LED kilobit: Reserve | 0100 | ○ | 0x0903 |
| F9.04 | PID given feedback range | 0 to 65535 | 1000 | ○ | 0x0904 |
| F9.05 | Proportional gain P1 | 0 to 1000.0 | 20.00 | ○ | 0x0905 |
| F9.06 | Integration time I1 | 0.00s to 10.00s | 2.00s | ○ | 0x0906 |
| F9.07 | Differential time D1 | 0.00s to 10.00s | 0.00s | ○ | 0x0907 |
| F9.08 | PID reverse cutoff frequency | 0.00 to Maximum frequency F0.10 | 0.00Hz | ○ | 0x0908 |
| F9.09 | PID deviation limit | 0.0% to 100.0% | 0.0% | ○ | 0x0909 |
| F9.10 | PID differential limiting | 0.00% to 100.00% | 0.10% | ○ | 0x090A |
| F9.11 | PID given change time | 0.00 to 100.00s | 0s | ○ | 0x090B |
| F9.12 | PID feedback filtering time | 0.00 to 60.00s | 0.00s | ○ | 0x090C |
| F9.13 | PID output filtering time | 0.00 to 60.00s | 0.00s | ○ | 0x090D |
| F9.14 | Proportional gain P2 | 0.0 to 1000.0 | 20.00 | ○ | 0x090E |
| F9.15 | Integration time I2 | 0.00s to 10.00s | 2.00s | ○ | 0x090F |
| F9.16 | Differential time D2 | 0.00s to 10.00s | 0.00s | ○ | 0x0910 |
| F9.17 | PID parameter switching condition | 0: Do not switch 1: Terminal switching 2: Automatic switching based on deviation | 0 | ○ | 0x0911 |
| F9.18 | PID parameter switching deviation 1 | 0.0% to F9.19 | 20.0% | ○ | 0x0912 |
| F9.19 | PID parameter switching deviation 2 | F9.18 to 100.0% | 80.0% | ○ | 0x0913 |
| F9.20 | PID Initial frequency value | 0.0% to 100.0% | 0% | ○ | 0x0914 |
| F9.21 | PID Frequency initial holding time | 0.0 to 6500.0s | 0.0s | ○ | 0x0915 |
| F9.23 | Feedback wire break action selection | 0: The PID continues to run and no fault is reported 1: Stop and report fault (Manual reset) 2: Continue PID operation, output alarm signal 3: Run at the current frequency, output alarm signal 4: Stop and report fault (Automatic reset) | 0 | ○ | 0x0917 |
| F9.24 | Wire break alarm upper limit | F9.25 to 100.0% | 100.0% | ○ | 0x0918 |
| F9.25 | Line break alarm lower limit | 0 to F9.24 | 0.0% | ○ | 0x0919 |
| F9.26 | Feedback break detection time | 0.0s to 120.0s | 0.0s | ○ | 0x091A |
| F9.27 | PID stop operation | 0: No operation at stop 1: Operation at stop | 0 | ○ | 0x091B |
| F9.28 | PID function selection | 0: Normal PID 1: Dormant PID | 0 | ○ | 0x091C |
| F9.29 | PID sleep threshold | 0.0% to 100.0% | 60.0% | ○ | 0x091D |
| F9.30 | PID sleep delay | 0.0 to 3600.0s | 3.0s | ○ | 0x091E |
| F9.31 | PID wake-up threshold | 0.0% to 100.0% | 20.0% | ○ | 0x091F |
| F9.32 | PID wake up delay | 0.0 to 3600.0s | 3.0s | ○ | 0x0920 |
| F9.33 | Dormancy detection frequency | 0 to Upper limit frequency F0.12 | 25.00Hz | ○ | 0x0921 |
| F9.34 | Minimum output | 0: F0.14(Lower frequency) 1: 0Hz | ● | 0x0922 | |
| F9.35 | Double output deviation reverse minimum | 0.00 to 100.00% | 1.00% | ○ | 0x0923 |
| F9.36 | Double output deviation reverse maximum | 0.00 to 100.00% | 1.00% | ○ | 0x0924 |
| F9.37 | PID integral attribute | Units place: integral separation 0: Invalid 1: Valid Tens: output to the limit, whether to stop integrating 0: Continue to integrate 1: Stop collecting points | 0 | ○ | 0x0925 |
| F9.38 | PID Preset Switchover condition selection | 0: Time 1: Switch according to AI1 feedback value | 0 | ○ | 0x0926 |
| F9.39 | PID Minimum value of AI feedback switching | 0.0 to F9.40 | 45.0% | ○ | 0x0927 |
| F9.40 | PID AI feedback maximum switching value | F9.39 to 100.0% | 55.0% | ○ | 0x0928 |
| FA Fault and protection parameter group | |||||
| FA.00 | Motor overload protection selection | 0: Off 1: On | 1 | ○ | 0x0A00 |
| FA.01 | Motor overload protection factor | 0.0 to 250.0% | 100.0% | ○ | 0x0A01 |
| FA.02 | Motor overload warning coefficient | 20.0 to 250.0% | 80.0% | ○ | 0x0A02 |
| FA.03 | Overvoltage stall and overcurrent stall control selection | 0: Off 1: On Unit: Excessive suppression enable Tens: Over current suppression enable Hundreds: Judge the input of brakes Thousands: Excessive suppression of fast rising frequency | 1111 | ○ | 0x0A03 |
| FA.04 | Over voltage protection voltage | 110% to 150% | Model settings | ○ | 0x0A04 |
| FA.05 | The Udc controls voltage loop gain | 0.00 to 50.00 | 2.00 | ○ | 0x0A05 |
| FA.06 | The Udc controls current loop gain | 0.00 to 50.00 | 2.00 | ○ | 0x0A06 |
| FA.07 | Overcurrent suppression point | 50% to 200% | 150% | ○ | 0x0A07 |
| FA.08 | Overcurrent suppression gain | 0.00 to 50.00 | 2.00 | ○ | 0x0A08 |
| FA.09 | Overcurrent suppression points | 0.00 to 50.00 | 4.00 | ○ | 0x0A09 |
| FA.10 | Short -circuit detection | 0: Invalid 1: Valid | 1 | ○ | 0x0A0A |
| FA.11 | Input phase loss protection | 0:Disable 1: Enable | 1 | ○ | 0x0A0B |
| FA.12 | Output phase loss protection | 0:Disable 1: Enable | 1 | ○ | 0x0A0C |
| FA.13 | Input phase loss protection software detection level | 0.0 to 999.9% | 15.0% | ○ | 0x0A0D |
| FA.14 | PWM parameter setting | One place: Enable voltage prediction compensation Tens place: PWM update mode 0: Single sample update 1: Double sample and double update Hundreds place: Random carrier mode 0: Random carrier 1: Random 0 vector | 0010 | 0x0A0E | |
| FA.15 | Hardware current and voltage protection | One place: Hardware current limit(CBC) 0: Disable 1: Enable Tens places: - Hundreds place: FAU filtering time 1 to F Thousands place: TZ filtering time 1 to F | 0001 | ○ | 0x0A0F |
| FA.16 | CBC protection point | 100-220% | 200% | ○ | 0x0A10 |
| FA.17 | CBC overload protection time | 1-5000ms | 500ms | ○ | 0x0A11 |
| FA.18 | Undervoltage threshold setting | 40.0% to 100.0% | 100.0% | ○ | 0x0A12 |
| FA.19 | Reserve | - | Model determination | ◎ | 0x0A13 |
| FA.20 | Number of failure recovery | 0 to 5 | 0 | ○ | 0x0A14 |
| FA.21 | Interval for fault self-recovery | 0.1 to 100.0s | 1.0s | ○ | 0x0A15 |
| FA.22 | Power loss ride-through selection | One place: Power loss ride-through selection function enable 0: Disable 1: Enabled Tens place: Power loss ride-through function selection 0: Continue to operation 1: Shut down | 0000 | ○ | 0x0A16 |
| FA.23 | Instant stop non-stop enter voltage | 40% to 150% | 75% | ○ | 0x0A17 |
| FA.24 | Instant stop non-stop stable voltage | 60% to 150% | 95% | ○ | 0x0A18 |
| FB Application parameter set | |||||
| FB.00 | Swing frequency control | LED one-place: Swing frequency control 0: The swing frequency control is invalid 1: Swing frequency control is valid LED tens place: Swing frequency input mode 0: Automatic input 1: Manual input LED hundreds-place: Swing control 0: Variable swing 1: Fixed swing LED thousands place: Reserved | 0 | ● | 0x0B00 |
| FB.01 | Swing preset frequency | 0.00 to Maximum frequency | 0.00Hz | ● | 0x0B01 |
| FB.02 | Preset frequency duration | 0.00 to 650.00s | 0.00s | ● | 0x0B02 |
| FB.03 | Swing amplitude | 0.0 to 100.0% | 0.0% | ● | 0x0B03 |
| FB.04 | Jump frequency amplitude | 0.0 to 50.0% | 0.0% | ● | 0x0B04 |
| FB.05 | Swing frequency rise time | 0.00 to 650.00s | 5.00s | ● | 0x0B05 |
| FB.06 | Swing frequency drop time | 0.00 to 650.00s | 5.00s | ● | 0x0B06 |
| FC Communication parameter group | |||||
| FC.00 | Local address | 1 to 247, 0 is Broadcast address | 1 | ○ | 0x0C00 |
| FC.01 | Baud rate | 0: 300 bps 1: 600 bps 2: 1200 bps 3: 2400 bps 4: 4800 bps 5: 9600 bps 6: 19200 bps 7: 38400 bps 8: 57600 bps 9: 115200 bps | 5 | ○ | 0x0C01 |
| FC.02 | Modbus data format | 0: (8.N.2) 8 data bits, no parity, 2 stop stops 1: (8.E.1) 8 data bits, even parity, 1 stop position 2: (8.O.1) 8 data bits, odd parity, 1 stop stop 3: (8.N.1) 8 data bits, no parity, 1 stop stop | 3 | ○ | 0x0C02 |
| FC.03 | Modbus Communication response delay | 0ms to 20ms | 2ms | ○ | 0x0C03 |
| FC.04 | Modbus Communication timeout | 0.0 (Invalid), 0.1s to 60.0s | 0 | ○ | 0x0C04 |
| FC.06 | Master-slave selection | LED units place: Modbus communication master-slave selection 0: Slave 1: Host | 0 | ||
| FC.07 | Communication ratio setting | 0.00 to 5.00 | 1.00 | ||
| FC.08 | Modbus communication fault action mode selection | 0: Alarm and free parking (manual reset) 1: No alarm and continue running 2: Alarm and free parking (automatic reset) 3: Parking does not alarm (based on F1.10 parking) | 1 | ||
| FC.09 | Modbus transfers response processing | Units place: Write operation response 0: Response to the write operation 1: No response to write operation Tens Place: Communication exception response 0: Response to exception 1: No response to exception Hundreds place: Communication exception response protocol 0:8001 1:83 | 000 | ||
| FC.10 | Hosts send selection | LED units place: 1st group sending frame selection LED tens place:2st group sending frame selection LED hunderds place: 3st group sending frame selection 0: Invalid 1: Running command given 2: Host given frequency 3: Host output frequency 4: Host upper limit frequency 6: Host output torque 9: Host given PID A: Host feedback PID | 0x21 | ||
| FC.11 | RS485 communication port configuration | 0: Configure to Modbus Communication 1: Quota is serial communication 2: UART_OSC | 0 | ||
| FD Multi -speed instructions and simple PLC parameter arrays | |||||
| FD.00 | Multi-speed instruction 0 | -100.0% to 100.0% (100.0% corresponds to maximum frequency F0.10) | 0 | ○ | 0x0D00 |
| FD.01 | Multi-speed instruction 1 | -100.0% to 100.0% | 0 | ○ | 0x0D01 |
| FD.02 | Multi-speed instruction 2 | -100.0% to 100.0% | 0 | ○ | 0x0D02 |
| FD.03 | Multi-speed instruction 3 | -100.0% to 100.0% | 0 | ○ | 0x0D03 |
| FD.04 | Multi-speed instruction 4 | -100.0% to 100.0% | 0 | ○ | 0x0D04 |
| FD.05 | Multi-speed instruction 5 | -100.0% to 100.0% | 0 | ○ | 0x0D05 |
| FD.06 | Multi-speed instruction 6 | -100.0% to 100.0% | 0 | ○ | 0x0D06 |
| FD.07 | Multi-speed instruction 7 | -100.0% to 100.0% | 0 | ○ | 0x0D07 |
| FD.08 | Multi-speed instruction 8 | -100.0% to 100.0% | 0 | ○ | 0x0D08 |
| FD.09 | Multi -speed instruction 9 | -100.0% to 100.0% | 0 | ○ | 0x0D09 |
| FD.10 | Multi-speed instruction10 | -100.0% to 100.0% | 0 | ○ | 0x0D0A |
| FD.11 | Multi-speed instruction11 | -100.0% to 100.0% | 0 | ○ | 0x0D0B |
| FD.12 | Multi-speed instruction12 | -100.0% to 100.0% | 0 | ○ | 0x0D0C |
| FD.13 | Multi-speed instruction13 | -100.0% to 100.0% | 0 | ○ | 0x0D0D |
| FD.14 | Multi-speed instruction14 | -100.0% to 100.0% | 0 | ○ | 0x0D0E |
| FD.15 | Multi-speed instruction15 | -100.0% to 100.0% | 0 | ○ | 0x0D0F |
| FD.16 | PLC mode of operation | 0: Stops after a single run 1: Maintain the final value at the end of a single run 2: Keep cycling | 0 | ○ | 0x0D10 |
| FD.17 | PLC Power down memory selection | Ones Slot: 0: Power failure does not memory 1: Power failure memory Ten places: 0: Stop and does not remember 1: Shutdown memory | 0 | ○ | 0x0D11 |
| FD.18 | Running time of simple PLC reference 0 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D12 |
| FD.19 | Acceleration/deceleration time of simple PLC reference 0 | 0 to 3 | 0 | ○ | 0x0D13 |
| FD.20 | Running time of simple PLC reference 1 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D14 |
| FD.21 | Acceleration/deceleration time of simple PLC reference 1 | 0 to 3 | 0 | ○ | 0x0D15 |
| FD.22 | Running time of simple PLC reference 2 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D16 |
| FD.23 | Acceleration/deceleration time of simple PLC reference 2 | 0 to 3 | 0 | ○ | 0x0D17 |
| FD.24 | Running time of simple PLC reference 3 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D18 |
| FD.25 | Acceleration/deceleration time of simple PLC reference 3 | 0 to 3 | 0 | ○ | 0x0D19 |
| FD.26 | Running time of simple PLC reference 4 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D1A |
| FD.27 | Acceleration/deceleration time of simple PLC reference 4 | 0 to 3 | 0 | ○ | 0x0D1B |
| FD.28 | Running time of simple PLC reference 5 | 0.0 to 6553.5(s/m/h) | 0.0s(h) | ○ | 0x0D1C |
| FD.29 | Acceleration/deceleration time of simple PLC reference 5 | 0 to 3 | 0 | ○ | 0x0D1D |
| FD.30 | Running time of simple PLC reference 6 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D1E |
| FD.31 | Acceleration/deceleration time of simple PLC reference 6 | 0 to 3 | 0 | ○ | 0x0D1F |
| FD.32 | Running time of simple PLC reference 7 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D20 |
| FD.33 | Acceleration/deceleration time of simple PLC reference 6 | 0 to 3 | 0 | ○ | 0x0D21 |
| FD.34 | Running time of simple PLC reference 8 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D22 |
| FD.35 | Acceleration/deceleration time of simple PLC reference 8 | 0 to 3 | 0 | ○ | 0x0D23 |
| FD.36 | Running time of simple PLC reference 9 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D24 |
| FD.37 | Acceleration/deceleration time of simple PLC reference 9 | 0 to 3 | 0 | ○ | 0x0D25 |
| FD.38 | Running time of simple PLC reference 10 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D26 |
| FD.39 | Acceleration/deceleration time of simple PLC reference 10 | 0 to 3 | 0 | ○ | 0x0D27 |
| FD.40 | Running time of simple PLC reference 11 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D28 |
| FD.41 | Acceleration/deceleration time of simple PLC reference 11 | 0 to 3 | 0 | ○ | 0x0D29 |
| FD.42 | Running time of simple PLC reference 12 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D2A |
| FD.43 | Acceleration/deceleration time of simple PLC reference 12 | 0 to 3 | 0 | ○ | 0x0D2B |
| FD.44 | Running time of simple PLC reference 13 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D2C |
| FD.45 | Acceleration/deceleration time of simple PLC reference 13 | 0 to 3 | 0 | ○ | 0x0D2D |
| FD.46 | Running time of simple PLC reference 14 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D2E |
| FD.47 | Acceleration/deceleration time of simple PLC reference 14 | 0 to 3 | 0 | ○ | 0x0D2F |
| FD.48 | Running time of simple PLC reference 15 | 0.0 to 6553.5 (s/m/h) | 0.0s(h) | ○ | 0x0D30 |
| FD.49 | Acceleration/deceleration time of simple PLC reference 15 | 0 to 3 | 0 | ○ | 0x0D31 |
| FD.50 | PLC Run-time unit | LED units: timing unit 0: s(seconds) 1: h(hours) 2: min(minutes) | 0 | ○ | 0x0D32 |
| FD.51 | Multi-segment speed instruction 0 given mode | 0: Function code FD.00 is given 1: AI1 2: AI2 3: AI3 (expansion) 4: Terminal pulse PULSE given 5: PID 6: Preset frequency (F0.08) given, UP/DOWN modifiable 7: Keyboard potentiometer given | 0 | ○ | 0x0D33 |
| FD.52 | Multispeed priority | 0: Invalid 1: Valid | 1 | ○ | 0x0D34 |
| FE User parameter group | |||||
| FE.00 | User password | 0 to 65535 | 0 | ○ | 0x0E00 |
| FE.01 | Fault record display times | 0 to 8 | 4 | ○ | 0x0E01 |
| FE.02 | Parameter and key lock selection | 0: Not locked 1: The function parameter is locked | 0 | ○ | 0x0E02 |
| A0 Application parameter group | |||||
| A0.00 | Application macro | 0:Default macro 1: Pressure machine macro 2: Spring machinery macro 3: woodworking machinery macro | 0 | ● | 0xA000 |
| A4 Constant pressure water supply parameter group | |||||
| A4.00 | Water supply function selection | 0: Invalid 1: Valid | 0 | ● | 0xA400 |
| A4.01 | Setting pressure | 1.0 to A4.19 | 3.0bar | ○ | 0xA401 |
| A4.02 | Starting pressure | 0.0 to A4.01 | 0.3bar | ○ | 0xA402 |
| A4.03 | Sensor range | 1.0 to 200.0bar | 16.0bar | ○ | 0xA403 |
| A4.04 | Sensor feedback type | 0: 4 to 20mA(AI2) 1: 0 to 10V(AI1) | 0 | ○ | 0xA404 |
| A4.05 | Pressure calibration factor | 0.750 to 1.250 | 1.000 | ○ | 0xA405 |
| A4.06 | Proportional gain P | 0.0 to 100.0 | 50.0 | ○ | 0xA406 |
| A4.07 | Integration time I | 0.00s to 10.00s | 0.50 | ○ | 0xA407 |
| A4.08 | Differential time | 0.000s to 10.000s | 0.000 | ○ | 0xA408 |
| A4.09 | Sleep time | 0: Disable 1: Sleep mode 1 2: Sleep mode 2 |
1 | ○ |
0xA409 |
| A4.10 | Sleep delay | 0.0s to 100.0s | 5.0s | ○ | 0xA40A |
| A4.11 | Wake up delay | 0.0s to 100.0s | 3.0 | ○ | 0xA40B |
| A4.12 | Low-frequency hold frequency | 0.0 to A4.14 | 20.00Hz | ○ | 0xA40C |
| A4.13 | Low frequency hold frequency running time | 0.0s to 100.0s | 5.0s | ○ | 0xA40D |
| A4.14 | Sleep frequency | A4.12 to F0.12 | 25.00Hz | ○ | 0xA40E |
| A4.15 | Sleep detection cycle | 0.0s to 600.0s | 30.0s | ○ | 0xA40F |
| A4.16 | Leaking coefficient | 0.1s to 100.0s | 2.5s | ○ | 0xA410 |
| A4.17 | Sleep detection coefficient | 1 to 10 | 4 | ○ | 0xA411 |
| A4.18 | Deadband pressure | 0.0bar to 1.0bar | 0.1bar | ○ | 0xA412 |
| A4.19 | High voltage alarm setting value | A4.00 to A4.03 | 15.0bar | ○ | 0xA413 |
| A4.20 | Low voltage alarm setting value | 0.0 to A4.01 | 0.0bar | ○ | 0xA414 |
| A4.21 | Water pressure alarm delay time | 0.0 to 100.0 | 3.0s | ○ | 0xA415 |
| A4.22 | Sensor disconnection detection value | 0.00 to 10.00V | 0.20 | ○ | 0xA416 |
| A4.23 | Sensor disconnection detection time | 0.0s to 100.0s | 30.0s | ○ | 0xA417 |
| A4.24 | Water shortage protection function | 0: Disable 1: Judging by frequency and current 2: Judging by frequency and pressure | 2 | ○ | 0xA418 |
| A4.25 | Water shortage fault detection threshold | 0.00s to 10.00s | 0.50 | ○ | 0xA419 |
| A4.26 | Water shortage protection detection frequency | 0 to F0.12 | 48.00Hz | ○ | 0xA41A |
| A4.27 | Water shortage protection detection current percentage | 0.0 to 100.0% | 40.0% | ○ | 0xA41B |
| A4.28 | Water shortage protection detection time | 0.0 to 200.0s | 60.0s | ○ | 0xA41C |
| A4.29 | Water shortage protection automatic reset delay | 0 to 1000 | 15 | ○ | 0xA41D |
| A4.30 | Number of Auto-resets for water shortage protection | 0 to 100 | 10 | ○ | 0xA41E |
| A4.31 | Pressure rise control function | 0: Invalid 1: Valid | 0 | ○ | 0xA41F |
A4.35 | Constant frequency water shortage function selection | One place: Turn on protection 0: Disable 1: Enable Tens place: Current detected 0: Total current 1: Torque current | 0010 | ||
| A4.36 | Constant frequency water shortage protection current | 0% to 150% | 40% | ||
| A4.37 | Constant frequency water shortage protection frequency | 0% to 100% | 50% | ||
| A4.38 | Constant frequency water shortage protection detection time | 1 to 1000s | 30s | ||
| A4.39 | Constant frequency water shortage protection recovery time | 1 to 10000s | 600s | ||
| A4.40 | Constant frequency water shortage protection recovery times | 0 to 100 | 3 | ||
Fault record parameter group
| Function code | Name | Setting range and description | Change | Modbus address |
|---|---|---|---|---|
| E0 Fault parameter set | ||||
| E0.00 | Fault type | Refer to the fault Information code table for detail | ◎ | 0xE000 |
| E0.01 | Failure operating frequency | 0.0 to Maximum frequency | ◎ | 0xE001 |
| E0.02 | Fault output current | 0.1 to 2000.0A | ◎ | 0xE002 |
| E0.03 | Fault bus voltage | 0 to 810.0V | ◎ | 0xE003 |
| E0.04 | Fault input terminal status | Refer to the input terminal state diagram | ◎ | 0xE004 |
| E0.05 | Fault output terminal status | Refer to the output terminal state diagram | ◎ | 0xE005 |
| E0.06 | Fault module temperature | 0 to 100℃ | ◎ | 0xE006 |
| E0.07 | Fault VFD condition | LED one place: Running direction 0: Forward 1: Reverse LED tens place: Running status 0: Stop 1: Steady speed 2: Speed up 3: Slow down | ◎ | 0xE007 |
| E0.08 | Down time (Count from this power-on) | 0 to 65535min | ◎ | 0xE008 |
| E0.09 | Down time (From total running time) | 0 to 65535H | ◎ | 0xE009 |
| E0.10 | Fault output voltage | 0 to 1500V | ◎ | 0xE00A |
| E0.11 | Fault diagnosis information | Refer to (Chapter 8 to Fault Code Details) | ◎ | 0xE00B |
| E0.12 | Number of faulty CBC | 10Sec if no CBC zeroing | ◎ | 0xE00C |
Display parameter group
| Function code | Name | Minimum unit | Change | Modbus address |
|---|---|---|---|---|
| D0 Display parameter group | ||||
| D0.00 | Running frequency(Hz) | 0.01Hz | ◎ | 0xD000 |
| D0.01 | Setting frequency(Hz) | 0.01Hz | ◎ | 0xD001 |
| D0.02 | Bus voltage(V) | 0.1V | ◎ | 0xD002 |
| D0.03 | Output voltage(V) | 1V | ◎ | 0xD003 |
| D0.04 | Output current(A) | 0.1A | ◎ | 0xD004 |
| D0.05 | Output power(kW) | 0.1kW | ◎ | 0xD005 |
| D0.06 | Output torque(%) | 0.1% | ◎ | 0xD006 |
| D0.07 | DI Input state | ◎ | 0xD007 | |
| D0.08 | DO Output state | ◎ | 0xD008 | |
| D0.09 | AI1 Voltage (V) | 0.01V | ◎ | 0xD009 |
| D0.10 | AI2 Voltage(V) | 0.01V | ◎ | 0xD00A |
| D0.11 | AO1 Voltage(V) | 0.01V | ◎ | 0xD00B |
| D0.12 | Count value | ◎ | 0xD00C | |
| D0.13 | Axis Frequency | ◎ | 0xD00D | |
| D0.14 | Load speed display | 1rpm | ◎ | 0xD00E |
| D0.15 | PID setting | ◎ | 0xD00F | |
| D0.16 | PID feedback | ◎ | 0xD010 | |
| D0.17 | PLC phase | ◎ | 0xD011 | |
| D0.18 | PULSE input pulse frequency | ◎ | 0xD012 | |
| D0.19 | Feedback speed(Unit0.1Hz) | ◎ | 0xD013 | |
| D0.20 | Remaining running time | ◎ | 0xD014 | |
| D0.21 | AI1Pre-correction voltage | ◎ | 0xD015 | |
| D0.22 | AI2Pre-correction voltage | ◎ | 0xD016 | |
| D0.23 | Reserve | ◎ | 0xD017 | |
| D0.24 | Linear velocity | ◎ | 0xD018 | |
| D0.25 | Current power-on time | 1min | ◎ | 0xD019 |
| D0.26 | Current running time | 0.1min | ◎ | 0xD01A |
| D0.27 | CPU temperature | ◎ | 0xD01B | |
| D0.28 | Communication setting | ◎ | 0xD01C | |
| D0.29 | Radiator temperature | ◎ | 0xD01D | |
| D0.30 | Main frequency X display | 0.01Hz | ◎ | 0xD01E |
| D0.31 | Auxiliary frequency Y display | 0.01Hz | ◎ | 0xD01F |
| D0.34 | Reserve | ◎ | 0xD022 | |
| D0.35 | Analog grounding | ◎ | 0xD023 | |
| D0.36 | 3.3VA | ◎ | 0xD024 | |
| D0.37 | Control board plate number | ◎ | 0xD025 | |
| D0.38 | Plate number of the power board | ◎ | 0xD026 | |
| D0.39 | Power factor Angle | ◎ | 0xD027 | |
| D0.40 | Virtual VDI state | ◎ | 0xD100 | |
| D0.41 | Virtual VDO state | ◎ | 0xD101 | |
| D0.42 | Expand DI input status | ◎ | 0xD102 | |
| D0.43 | Expand DO input status | ◎ | 0xD103 | |
| D0.44 | Expansion board version | ◎ | 0xD104 | |
| D0.45 | AI3 (Expand) voltage (V) | 0.01V | ◎ | 0xD105 |
| D0.46 | AI4 (Expand) voltage (V) | 0.01V | ◎ | 0xD106 |
| D0.49 | AO2 Voltage (V) | 0.01V | ◎ | 0xD109 |
| D0.53 | Communication status of the main control board | ◎ | 0xD10D | |
| D0.54 | Extended communication status | ◎ | 0xD10E | |
A0 Application parameter group
✎Notes: As the software iterates, the parameter list may change.
| Function code | Name | Minimum unit | Change | Modbus address |
|---|---|---|---|---|
| A0 Application parameter set | ||||
| A0.00 | Application macro | 0: Default macro 1: Pressure tile machinery macro 2: Spring machinery macro 3: Woodworking machinery macro | ● | 0xA000 |