06 Function parameter table

Last modified by Theodore Xu on 2025/12/09 19:23

○——It indicates that the set value of the parameter can be changed when the inverter is shut down or running.

●——It indicates that the setting value of the parameter cannot be changed when the inverter is in operation;

◎——It indicates that the value of the parameter is the actual detection record value and cannot be changed;

□——It indicates that the parameter is Manufacturer parameter, which can only be set by the manufacturer and cannot be operated by users.

Mailing address description:

The following table indicates the communication addresses in hexadecimal format.

In the following table, the communication address is the RAM address, and the parameter is not saved if the power fails, you need to save, please see the instructions for writing EEPROM in section 7.4.

Basic parameter set

Function codeNameSetting rangeDefaultPropertyModbus address
F0 Basic function parameter group
F0.00Motor control mode

0: SVC

1: V/F

2: -

10x0000
F0.01Command source selection

0: Operation panel command channel

1: Terminal command channel

2: Serial port communication command channel

00x0001
F0.02 UP/DOWN standard

0: Operating frequency

1: Set frequency

10x0002
F0.03Primary frequency source X selection

0: Digital setting F0.08 (Adjustable terminal UP/DOWN, non-relative after power failure)

1: Digit setting F0.08 (Terminal

UP/DOWN adjustable, power down memory)

2: AI1

3: AI2

4: Keyboard potentiometer set

5: The terminal PULSE pulse is set

6: Multi-speed instruction

7: Simple PLC

8: PID

9: Communication setting

10: AI3(Expansion module)

40x0003
F0.04Auxiliary frequency source Y selectionSame as F0.0300x0004
F0.05Range of auxiliary frequency source Y

0: Relative to the maximum frequency F0.10

1: Relative to the frequency source X

00x0005
F0.06Auxiliary frequency source Y range in superposition0% to 150%100%0x0006
F0.07Frequency source operation selection

LED ones: Frequency source

selection

0: The primary frequency source

1: The result of primary and secondary operations

2: Switch between primary frequency source and secondary frequency source

3: Switch between the primary frequency source and the primary and secondary operation results

4: Switch between auxiliary frequency source and primary and secondary operation results

LED ten: Frequency source main and auxiliary operation relationship

0: Primary + secondary

1: Primary to secondary

2: Indicates the maximum value of both

3: The minimum value of both

4: Main*auxiliary

00x0007
F0.08Keyboard setting frequency

0.00Hz to Maximum frequency

F0.10

50.00Hz0x0008
F0.09Running direction selection

0: The same direction

1: The direction is reversed

2: Reverse prohibition

00x0009
F0.10Maximum output frequency0.00Hz to 320.00Hz50.00Hz0x000A
F0.11Source of frequency upper limit

0: The number is given F0.12

1: AI1

2: AI2

3: AI3

4: Set the terminal PULSE

5: Communication setting

6: Reservations

7: Keyboard potentiometer set

00x000B
F0.12Upper limiting frequencyF0.14 to F0.1050.00Hz0x000C
F0.13Upper frequency bias0.00Hz to F0.100.00Hz0x000D
F0.14Lower frequency0.00Hz to F0.120.00Hz0x000E
F0.15Lower frequency operating mode

0: Run at lower frequency

1: STOP

2: Zero speed operation

00x000F
F0.16Carrier frequency0.5kHz to 16.0kHzModel determination0x0010
F0.17Carrier PWM characteristic selection

Bits: Select PWM mode

0: Automatic switching;

1: 7 waves;

2: 5 waves;

3: SPWM;

LED ten: Carrier is associated with the output frequency

0: Independent of output frequency

1: It depends on the output frequency

LED hundred: random PWM depth

0: OFF

1 to 8: Open, adjust depth

LED kilobit: Over modulation option

0: OFF

1: ON

10100x0011
F0.18Acceleration time 10.0s to 6500.0sModel determination0x0012
F0.19Deceleration time10.0s to 6500.0sModel determination0x0013
F0.20Parameter initialization

0: No action is taken

1: Restore factory value (Do not restore motor parameters)

2: Clear the record information

3: Restore factory value (Restore motor parameters)

00x0014
F0.23Unit of acceleration and deceleration time

0: 1 s

1: 0.1s

2: 01s

10x0017
F0.24Acceleration and deceleration time reference frequency

0: Maximum frequency (F0.10)

1: Set the frequency

2: 100 Hz

00x0018
F0.25Fan control

Bits: Start/stop control

0: The fan runs after the inverter is powered on

1: Shutdown is related to temperature, and operation is running

2: Stop The fan stops, and the operation is related to temperature

Tens place: Enables the speed adjustment function

0: Off

1: Enable

010x0019
F0.26Frequency command decimal point

1: 1 decimal place

2: 2 decimal place

20x001A
F0.27Modulation ratio coefficient10.0 to 150.0%100.0%0x001B
F1 Start stop control parameter group
F1.00Start-up operation mode

LED bits: Boot mode

0: Start directly from the start frequency

1: Start after speed tracking and direction judgment

2: The asynchronous machine starts with pre-excitation

000x0100
F1.01Speed tracking mode

LED ten: Speed tracking direction

0: One to the stop direction

1: One to the starting direction

2: Automatic search

00x0101
F1.02Speed tracking time0.01 to 60.00s1.00s0x0102
F1.03Speed tracking current loop gain0.00 to 100.0010.000x0103
F1.04RPM tracking speed gain0.01 to 10.002.000x0104
F1.05Speed tracking current50 to 200%150%0x0105
F1.06Starting frequency0.00 to 60.00Hz0.00Hz0x0106
F1.07Startup frequency duration0.0 to 50.0s0.0s0x0107
F1.08Braking current before starting0.0 to 150.0%80.0%0x0108
F1.09Braking time before starting0.0 to 60.0s0.0s0x0109
F1.10Stop method

0: Slow down and stop

1: Free shutdown

00x010A
F1.11Stop DC braking start frequency0.00Hz to F0.100.00Hz0x010B
F1.12Stop DC braking wait time0.0s to 100.0s0.0s0x010C
F1.13Stop DC braking current0.0% to 150.0%80.0%0x010D
F1.14Stop DC braking duration0.0s to 100.0s0.0s0x010E
F1.16Energy consumption brake action voltage115.0% to 140.0%130%0x0110
F1.17Magnetic flux braking gain10 to 150%80%0x0111
F1.18Magnetic flux braking operating voltage110% to 500%120%0x0112
F1.19Flux brake limiting0 to 200%20%0x0113
F1.20Acceleration and deceleration selection

0: Straight line

1: S curve

00x0114
F1.21S-curve initial acceleration rate20.0% to 100.0%50.0%0x0115
F1.22S-curve initial deceleration rate20.0% to 100.0%50.0%0x0116
F1.23Zero speed holding torque0.0 to 150.0%00x0117
F1.24Zero speed holding torque time

0.0 to 6000.0s

If the value is set to 6000.0s, the value remains unchanged without time limit.

Model determination0x0118
F1.25Start pre-excitation time0.00 to 60.00s0.200x0119
F1.26Shutdown frequency0.00 to 60.00Hz0.00Hz0x011A
F1.27Power failure restart action selection

0: Invalid

1: Valid

00x011B
F1.28Power failure restart waiting time0.00 to 120.00s0.50s0x011C
F1.29Select the terminal running protection

LED bits: Select the terminal run instruction when powering on

0: The terminal running instruction is invalid during power-on.

1: Terminal running instructions are valid during power-on

LED ten: Run command given channel switch terminal run instruction selection

0: The terminal running instruction is invalid

1: The terminal instruction is valid when the terminal is cut in.

110x011D
F2 Motor parameter group
F2.00Motor type

0: Asynchronous machine (AM)

1: Permanent magnet synchronous motor(PM)

2: Single-phase induction motor (VF control only)

00x0200
F2.01Rated power of motor0.1kW to 400.0kWModel determination0x0201
F2.02Rated voltage of motor1V to 440V0x0202
F2.03Rated current of motor0.1to 2000.0A0x0203
F2.04Rated frequency of motor0.01Hz to F0.100x0204
F2.05Rated motor speed1rpm to 65000rpm0x0205
F2.06Motor stator resistance0.001 to 65.0000x0206
F2.07Motor rotor resistance0.001 to 65.0000x0207
F2.08Motor fixed rotor inductance0.1 to 6500.0mH0x0208
F2.09Mutual inductance of motor fixed rotor0.1 to 6500.0mH0x0209
F2.10Motor no-load current0.1 to 650.0A0x020A
F2.11Tuning selection

0: No operation is performed

1: Static tuning 1

2: Full tuning

3: Static tuning 2(AM calculated Lm)

00x020B
F2.12G/P model

0: Type G machine

1: P-type machine

Model determination0x020C
F2.13Single-phase motor turns ratio10 to 200%100%0x020D
F2.14Current calibration coefficient of single-phase motor50 to 200%120%0x020E
F2.15Number of motor poles2 to 4840x020F
F2.16Speed feedback or encoder type

Units place: encoder type

0: Expansion interface for IO module

1: Standard ABZ encoder

2: Resolver

3: UVW encoder

4: UVW encoder with reduced wiring

Tens place: encoder Direction

0: Direction same

1: Direction opposite

Hundreds place: break Detection

0: Disable

1: Enable

Thousands Digit: Reserved

00x0210
F2.17Photoelectric encoder line count0 to 6000025000x0211
F2.18PG disconnection detection time0.000 to 60.000s0.100sec0x0212
F2.19Resolver pole pairs2 to 12820x0213
F2.20Encoder installation reduction ratio0.100 to 50.0001.0000x0214
F2.21Encoder filter time1 to 1000ms10ms0x0215
F2.22Stator resistance of synchronization0.001 to 65.000 (0.0010hm)Model determination0x0216
F2.23Synchronize d-axis inductance0.01mH to 655.35mH0x0217
F2.24Synchronize Q-axis inductance0.01mH to 655.35mH0x0218
F2.25Synchronize back electromotive force0.1V to 1000.0V0x0219
F2.28High frequency injection voltage0.1% to 100.0%20.0%0x021C
F2.29Back potential identification current0.1% to 100.0%50.0%0x021D
F2.31Asynchronous no-load current per unit value0.1%Model determination0x021F
F2.32Per unit asynchronous stator resistance0.01%0x0220
F2.33Asynchronous rotor resistance per unit value0.01%0x0221
F2.34Asynchronous mutual inductance per unit value0.1%0x0222
F2.35Asynchronous leakage sensing per unit value0.01%0x0223
F2.36Per unit value of asynchronous leakage sensing coefficient0.01%0x0224
F2.37Synchronous stator resistance per unit value0.01%0x0225
F2.38Per unit value of synchronous D-axis inductance0.01%0x0226
F2.39Synchronous Q-axis inductance per unit value0.01%0x0227
F2.40Back electromotive force of synchronous motor0.1V300.0V0x0228
F2.41Encoder mounting angle0.1 °0.0 ° 
F3 Vector control parameter group
F3.00ASR (Speed loop) proportional gain 10.00 to 100.00%20%0x0300
F3.01ASR (Velocity ring) integration time 10.01s to 10.00s0.200x0301
F3.02Loss of velocity protection value

0 to 5000ms

(0 Turn off stall protection)

0ms0x0302
F3.03ASR filtering time 10.000 to 0.100s0.000s0x0303
F3.04ASR switching frequency 10.00 to 50.00Hz5.00Hz0x0304
F3.05ASR (Speed loop) proportional gain 20.00 to 100.00%20%0x0305
F3.06ASR (Velocity loop) integration time 20.01s to 10.00s0.300x0306
F3.07Retain 0-0x0307
F3.08ASR filtering time 20.000 to 0.100s0.000s0x0308
F3.09ASR switching frequency 20.00 to 50.00Hz10.00Hz0x0309
F3.10Slip compensation coefficient0 to 250%100%0x030A
F3.11Maximum electric torque0.0 to 250.0%160.0%0x030B
F3.12Maximum generating torque0.0 to 250.0%160.0%0x030C
F3.16Current loop D axis proportional gain0.1 to 10.01.00x0310
F3.17Current loop D axis integral gain0.1 to 10.01.00x0311
F3.18Current loop Q axis proportional gain0.1 to 10.01.00x0312
F3.19Current loop Q axis integral gain0.1 to 10.01.00x0313
F3.20D-axis feed-forward gain0.0 to 200.0%50.0%0x0314
F3.21Q-axis feed-forward gain0.0 to 200.0%50.0%0x0315
F3.22Optimize the current loop bandwidth0.0 to 99.99ms2.00ms0x0316
F3.23Current loop control word0 to 6553500x0317
F3.24Weak magnetic control current upper limit0 to 200%50%0x0318
F3.25Weak magnetic control feed forward gain0 to 500%0%0x0319
F3.26Weak magnetic control proportional gain0 to 99995000x031A
F3.27Weak magnetic control integral gain0 to 999910000x031B
F3.28MTPA gain0.0 to 500.0%0.0%0x031C
F3.29MTPA filtering time0.0 to 999.9ms100.0ms0x031D
F3.30Magnetic flux compensation coefficient0 to 500%100%0x031E
F3.31Open-loop vector observeration gain0 to 999910240x031F
F3.32Open loop vector observation filtering time1 to 100ms20ms0x0320
F3.33Open-loop vector compensates start frequency0 to 100.0%1.0%0x0321
F3.34Open loop vector control word0 to 999980x0322
F3.35Synchronous open loop starting mode

0: Direct startup.

1: Start at an Angle

00x0323
F3.36Dc pull in time1ms to 9999ms500ms0x0324
F3.37Synchronous open loop vector low-frequency boost0 to 100.0%20.0%0x0325
F3.38Synchronous open loop vector high-frequency boost0.0 to 100.0%0.0%0x0326
F3.39Low frequency boost to maintain frequency0.0 to 100.0%10.0%0x0327
F3.40Low frequency increases cutoff frequency0.0 to 100.0%20.0%0x0328
F3.46Speed/torque control mode

0: Speed control

1: Torque control

00x032E
F3.47Torque given channel selection

0: F3.48 is set

1: AI1╳F3.48

2: AI2╳F3.48

3: AI3╳F3.48

4: PUL╳F3.48

5: Keyboard potentiometer given ╳F7.01

6: RS485 communication given ╳F3.48

00x032F
F3.48Torque keyboard numeric setting0 to 200.0%100.0%0x0330
F3.49Torque direction selection

Units: Torque direction setting

0: The torque direction is positive

1: The torque direction is negative

Tens place: torque reversing setting

0: Torque reversal is allowed

1: Torque reversal is prohibited

000x0331
F3.50Upper limit of output torqueF3.51 to 200.0%150.0%0x0332
F3.51Lower limit of output torque0 to F3.500%0x0333
F3.52Torque control forward speed limit selection

0: F3.54 is set

1: AI1╳F3.54

2: AI2╳F3.54

3: AI3╳F3.54

4: PUL╳F3.54

5: Keyboard potentiometer given ╳F3.54

6: RS485 communication given ╳F3.54

0s0x0334
F3.53Torque control reversal speed limit selection

0: F3.55 is set

1: AI1╳F3.55

2: AI2╳F3.55

3: AI3╳F3.55

4: PUL╳F3.55

5: Keyboard potentiometer given ╳F3.55

6: RS485 communication given ╳F3.55

7: Purchase card

00x0335
F3.54Torque control positive maximum speed limit0.00 to upper limiting frequency50.00Hz0x0336
F3.55Torque control reversal maximum speed limit0.00 to upper limiting frequency50.00Hz0x0337
F3.56Speed/torque switching delay0.00 to 10.00s0.01s0x0338
F3.57Torque acceleration time0.00 to 10.00s0.01s0x0339
F3.58Torque deceleration time0.00 to 10.00s0.01s0x033A
F3.59Forward and reverse torque dead zone time0.00 to 650.00s0.00s0x033B
F4 V/F control parameter group
F4.00Linear VF curve selection

0: Linear V/F curve;

1: Multi-point V/F curve

2: Square V/F curve

3-11: 1.1 to 1.9 power VF curves, respectively;

12: V/F fully separated mode

00x0400
F4.01Manual torque lift0.1 to 30.0%, 0 automatic torque boostModel determination0x0401
F4.02Torque boost cutoff frequency0.00Hz to F0.1050.00Hz0x0402
F4.03Self-set frequency F10.00Hz to F4.053.00Hz0x0403
F4.04Self-set voltage V10.0% to 100.0%10.0%0x0404
F4.05Self-set frequency F2F4.03 to F4.075.00Hz0x0405
F4.06Self-set voltage V20.0% to 100.0%15.0%0x0406
F4.07Self-set frequency F3F4.05 to F4.098.00Hz0x0407
F4.08Self-set voltage V30.0% to 100.0%22.0%0x0408
F4.09Self-set frequency F4F4.07-Rated frequency of motor F2.0412.00Hz0x0409
F4.10Self-set voltage V40.0% to 100.0%31.0%0x040A
F4.11Oscillation suppression gain0.0 to 10.0Model determination0x040B
F4.12Oscillation suppression filtering time1 to 1000ms50ms0x040C
F4.14Percentage of output voltage25 to 100%100%

 

0x040E

F4.16

AVR function

 

0: Invalid

1: Only slowing down is not effective

2: Only constant speed is effective

3: Valid

30x0410
F4.17EVF torque boost gain0 to 500.0%50.0%0x0411
F4.18EVF torque boost filtering time1 to 1000ms20ms0x0412
F4.19EVF slip compensation gain0 to 500.0%0.0%0x0413
F4.20EVF slip compensation filtering time1 to 1000ms100ms0x0414
F4.21Automatic energy saving selection

Units place: 0 is off, 1 is on

Tens place: Frequency change exit depth

Hundreds place: Reserve

Thousands place: Reserve

500x0415
F4.22Lower limit frequency of energy saving operation0.0 to 100.0%25.0%0x0416
F4.23Energy saving and pressure reduction time0.1 to 5000.0s10.0s0x0417
F4.24Lower limit of energy saving and pressure reduction20.0 to 100.0%30.0%0x0418
F4.25Energy saving and pressure reduction rate1 to 1000V/s50V/s0x0419
F4.26Voltage regulated proportional gain0 to 100200x041A
F4.27Voltage regulation integral gain0 to 100200x041B
F4.30Stabilizer proportional gain0.1% to 100.0%10.0%0x041E
F4.31Stabilizer filtering time1ms to 1000ms50ms0x041F
F4.32Low frequency current lift0.0% to 200.0%100.0%0x0420
F4.33Low frequency boost maintenance frequency0 to 100.0%10.0%0x0421
F4.34Low frequency current boosts the cutoff frequency0 to 100.0%30.0%0x0422
F4.35D-axis current gain0.0 to 100.02.00x0423
F4.36Q-axis current gain0.0 to 100.02.00x0424
F4.37Magnetic flux set strength0 to 500%30%0x0425
F4.38Magnetic flux control proportional gain0 to 99995000x0426
F4.39Magnetic flux controls the integral gain0 to 99995000x0427
F4.40Dc pull in time1ms to 9999ms1000ms0x0428
F4.41Starting frequency0.00Hz to 99.00Hz3.00Hz0x0429
F4.42Starting frequency time0.0s to 999.0s3.0s0x042A
F4.43V/F Separate the output voltage source

0: Function code F0.27 set

1: AI1 is set

2: AI2 is set

3: Reservations

4: Set the terminal PULSE

5: Multi-speed

6: Simple PLC

7: PID

8: Communication is given 100% corresponding to the rated voltage of the motor

00x042B
F4.44V/F separation output voltage digital setting0.0% to 100.0%00x042C
F4.45V/F separation voltage rise time0.0 to 1000.0s1.00x042D
F4.46V/F separation voltage drop time0.0 to 1000.0s1.00x042E
F4.47V/F separate stop mode

0: The voltage/frequency is simultaneously reduced to 0;

1: The frequency decreases after the voltage drops to 0

00x042F
F5 Enter the terminal parameter group
F5.00DI1 Terminal function selection

0: Non-function

0: Non-function

1: FWD

2: REV

3: Three-wire operation control

4: FJOG

5: RJOG

6: Terminal UP

7: Terminal DOWN

8: Free break

9: RESET

10: Running pause

11: External fault input(NO)

12: Multi-speed instruction terminal 1

13: Multi-speed instruction terminal 2

14: Multi-speed instruction terminal 3

15: Multi-speed instruction terminal 4

16: Acceleration and deceleration time select terminal 1

17: Acceleration and deceleration time select terminal 2

18: Frequency source switching (terminal, keyboard)

19: The UP/DOWN setting clears zero

20: Run the command to switch terminals

21: Acceleration and deceleration prohibition

22: PID pause

23: PLC State reset

24: Swing pause

25: Counter input

26: Counter reset

27: Length count input

28: Length reset

29: Torque control prohibited

30: PULSE impulse input(only DI4)

31: Reverse

32: Immediate DC braking

33: The external fault is normally closed

34: Reverse

35: The direction of PID action is reversed

36: External parking terminal 1

37: Control command switching terminal

38: PID integration pause terminal

39: Main frequency source and preset frequency switching terminal

40: Auxiliary frequency source and preset frequency switching terminal

41: Retain

42: Retain

43: PID parameter switching terminal

44: User-defined fault 1

45: User-defined fault 2

46: Speed control/torque control switch

47: Emergency stop

48: External parking terminal 2

49: Decelerate DC braking

50: The running time is cleared

51: Timing enable

52: Timing reset

10x0500
F5.01DI2 Terminal function selection20x0501
F5.02DI3 Terminal function selection90x0502
F5.03DI4 Terminal function selection120x0503
F5.04DI5 Terminal function selection (Extension)00x0504
F5.05DI6 Terminal function selection (Extension)00x0505
F5.08AI1 Indicates the DI terminal function00x0508
F5.09AI2 Indicates the DI terminal function00x0509
F5.10AI1 Input selection

0: 0-10V

3: 0-5V

4: 0.5-4.5V

00x050A
F5.11AI2 Input selection

0: 0-10V

1: 4-20mA

2: 0-20mA

3: 0-5V

4: 0.5-4.5V

10x050B
F5.12VDI1 terminal function selection

0: Non-function

1: FWD

2: REV

3: Three-wire operation control

4: FJOG

5: RJOG

6: Terminal UP

7: terminal DOWN

8: Free break

9: RESET

10: Running pause

11: External fault input(NO)

12: Multi-speed instruction terminal 1

13: Multi-speed instruction terminal 2

14: Multi-speed instruction terminal 3

15: Multi-speed instruction terminal 4

16: Acceleration and deceleration time select terminal 1

17: Acceleration and deceleration time select terminal 2

18: Frequency source switching (terminal, keyboard)

19: The UP/DOWN setting clears zero

20: Run the command to switch terminals

21: Acceleration and deceleration prohibition

22: PID pause

23: PLC State reset

24: Swing pause

25: Counter input

26: Counter reset

27: Length count input

28: Length reset

29: Torque control prohibited

30: PULSE impulse input(only DI4)

31: Reverse

32: Immediate DC braking

33: The external fault is normally closed

34: Reverse

35: The direction of PID action is reversed

36: External parking terminal 1

37: Control command switching terminal

38: PID integration pause terminal

39: Main frequency source and preset frequency switching terminal

40: Auxiliary frequency source and preset frequency switching terminal

41: Reverse

42: Reverse

43: PID parameter switching terminal

44: User-defined fault 1

45: User-defined fault 2

46: Speed control/torque control switch

47: Emergency stop

48: External parking terminal 2

49: Decelerate DC braking

50: The running time is cleared

51: Timing enable

52: Timing reset

00x050C
F5.13VDI2 terminal function selection00x050D
F5.14VDI3 terminal function selection00x050E
F5.15DI filtering time0.000s to 1.000s0.010s0x050F
F5.16Terminal command mode

0: Two-wire type 1

1: Two-wire type 2

2: Three-wire type 1

3: Three-wire type 2

00x0510
F5.17UP/DOWN change rate0.01Hz to 655.35Hz0.50Hz0x0511
F5.18AI1 minimum input0.00V to F5.200.00V0x0512
F5.19AI1 minimum input setting-100.0% to +100.0%0%0x0513
F5.20AI1 maximum inputF5.18 to +10.00V10.00V0x0514
F5.21AI1 maximum input setting-100.0% to +100.0%100.0%0x0515
F5.22AI1 filtering time0.00s to 10.00s0.10s0x0516
F5.23AI2 minimum input-10.00V to F5.252.00V0x0517
F5.24AI2 minimum input setting-100.0% to +100.0%0%0x0518
F5.25AI2 maximum inputF5.23 to +10.00V10.00V0x0519
F5.26AI2 maximum input setting-100.0% to +100.0%100.0%0x051A
F5.27AI2 filtering time0.00s to 10.00s0.10s0x051B
F5.28PULSE0.00 to F5.300.00kHz0x051C
F5.29PULSE input minimum frequency setting0.00 to 100.00%0%0x051D
F5.30PULSE input maximum frequencyF5.28 to 50.00kHz20.00kHz0x051E
F5.31PULSE maximum frequency setting0.00 to 100.00%100.0%0x051F
F5.32PULSE filtering time0.0s to 10.00s0.10s0x0520
F5.33DI1 Enable delay time0.0s to 360.0s0.0s0x0521
F5.34DI2 Enable delay time0.0s to 360.0s0.0s0x0522
F5.35DI1 Forbidden delay time0.0s to 360.0s0.0s0x0523
F5.36DI2 Forbidden delay time0.0s to 360.0s0.0s0x0524
F5.37Enter terminal valid status setting 1

0: Low level valid

1: High level valid

LED one place: D1 terminal

LED tens place: D2 terminal

LED hundreds place: D3 terminal

LED thousands place: D4 terminal

00x0525
F5.38Enter terminal valid status setting 2

0: Low level valid

1: High level valid

LED one place: D5 terminal(expend)

LED tens place: D6 terminal(expend)

00x0526
F5.39Enter terminal valid status setting 3

0: Low level valid

1: High level valid

LED one place: AI1

LED tens place: AI2

LED hundreds place: AI3(expend)

00x0527
F5.40Analog input curve selection

One place: AI1

Tens place: AI2

Hundreds place: AI3 (expend)

0: Straight line (default)

1: Curve 1

2: Curve 2

00x0528
F5.41Lower limit of curve 10.00 to F5.430.00V0x0529
F5.42The lower limit of curve 1 is set accordingly0.00 to 100.00%0.0%0x052A
F5.43Curve 1 inflection point 1 Input voltageF5.41 to F5.453.00V0x052B
F5.44Curve 1 inflection point 1 corresponds to the setting0.00 to 100.00%30.0%0x052C
F5.45Curve 1 inflection point 2 Input voltageF5.43 to F5.476.00V0x052D
F5.46Curve 1 inflection point 2 corresponds to the setting0.00 to 100.00%60.0%0x052E
F5.47Upper limit of curve 1F5.45 to 10.00V10.0V0x052F
F5.48The upper limit of curve 1 is set accordingly0.00 to 100.00%100.0%0x0530
F5.49Lower limit of curve 20.00 to F5.510.00V0x0531
F5.50The lower limit of curve 2 is set accordingly0.00 to 100.00%0.0%0x0532
F5.51Curve 2 Inflection point 1 Input voltageF5.49 to F5.533.00V0x0533
F5.52Curve 2 inflection point 1 corresponds to the setting0.00 to 100.00%30.0%0x0534
F5.53Curve 2 Inflection point 2 Input voltageF5.51 to F5.556.00V0x0535
F5.54Curve 2 inflection point 2 corresponds to the setting0.00 to 100.00%60.0%0x0536
F5.55Upper limit of curve 2F5.53 to 10.00V10.00V0x0537
F5.56The upper limit of curve 2 is set accordingly0.00 to 100.00%100.0%0x0538
F5.57AI3(Extension) is used to select the DI terminal function

0: Non-function

1: FWD

2: REV

3: Three-wire operation control

4: FJOG

5: RJOG

6: Terminal UP

7: terminal DOWN

8: Free break

9: RESET

10: Running pause

11: External fault input(NO)

12: Multi-speed instruction terminal 1

13: Multi-speed instruction terminal 2

14: Multi-speed instruction terminal 3

15: Multi-speed instruction terminal 4

16: Acceleration and deceleration time select terminal 1

17: Acceleration and deceleration time select terminal 2

18: Frequency source switching (terminal, keyboard)

19: The UP/DOWN setting clears zero

20: Run the command to switch terminals

21: Acceleration and deceleration prohibition

22: PID pause

23: PLC State reset

24: Swing pause

25: Counter input

26: Counter reset

27: Length count input

28: Length reset

29: Torque control prohibited

30: PULSE impulse input(only DI4)

31: Retain

32: Immediate DC braking

33: The external fault is normally closed

34: Retain

35: The direction of PID action is reversed

36: External parking terminal 1

37: Control command switching terminal

38: PID integration pause terminal

39: Main frequency source and preset frequency switching terminal

40: Auxiliary frequency source and preset frequency switching terminal

41: Retain

42: Retain

43: PID parameter switching terminal

44: User-defined fault 1

45: User-defined fault 2

46: Speed control/torque control switch

47: Emergency stop

48: External parking terminal 2

49: Decelerate DC braking

50: The running time is cleared

51: Timing enable

52: Timing reset

 0x0539
F5.58AI4 (Extension) is used to select the DI terminal function   
F5.59

 

AI3(Extension) Input selection

0: 0 to 10V

1: 4 to 20mA

2: 0 to 20mA

3: 0 to 5V

4: 0.5 to 4.5V

0 0x053A
F5.60AI4(Extension) Input selection

0: 0 to 10V

1: 4 to 20mA

2: 0 to 20mA

3: 0 to 5V

4: 0.5 to 4.5V

0 0x053B
F5.61AI3(Extended) lower limit0 to F5.630.00V0x053C
F5.62AI3(Extended) lower limit is set accordingly-100.0% to +100.0%0.00%0x053D
F5.63AI3(Extended) Upper limitF5.61 to +10.00V10.00V0x053E
F5.64The AI3(Extended) upper limit corresponds to the setting-100.0% to +100.0%100.00%0x053F
F5.65AI3(Extended) filtering time0.00 to 10.00s0.10s0x0540
F5.71vX terminal valid state source

0: Internal connection with virtual vYn

1: Whether the function code setting is valid.

One place: Virtual VDI1

Tens place: Virtual VDI2

Hundred bit: Virtual VDI3

Thousands: Reserved

00x0547
F5.72Virtual vX terminal function code set valid status

0: Invalid;

1: Valid

Units bit: Virtual VDI1

Tens place: Virtual VDI2

Hundreds place: Virtual VDI3

Thousands place: Reserved

00x0548
F5.73Select the terminal action mode

LED one place: free shutdown terminal recovery mode

0: Restore the original command after it is invalid

1: The original instruction is not restored if invalid

LED tens place: emergency stop terminal recovery mode

0: Restore the original command after disconnection

1: The original command is not restored after the disconnect

LED hundreds place: Select terminal operation mode after fault reset

0: The terminal control can be started directly

1: Stop the terminal control before starting

LED thousands place: Reserve

1110x0549
F6 Output terminal parameter group
F6.00FM terminal output selection

0: Pulse output

1: Open collector output (FMR)

10x0600
F6.01FMR open collector output selection

0: No output

1: The inverter is in operation

2: Fault output (Fault shutdown)

3: Frequency level detection FDT1 Output

4: Frequency reaches

5: Zero speed running 1

6: Motor overload forecast alarm

7: Inverter overload forecast alarm

8: Set meter value reached

9: The specified count value is reached

10: Length reached

11: The PLC cycle is complete

12: The accumulated running time reaches

13: Reservations

14: Torque limit

15: Ready to run

16: AI1 > AI2

17: The upper frequency reaches

18: The lower limit frequency reaches 1

19: Output in undervoltage state

20: Communication control

21: Positioning completed (reserved)

22: Positioning close (reserved)

23: Zero speed running 2

24: The cumulative power-on time reaches

25: Frequency level detection FDT2 output

26: Frequency reaches 1 output

27: Frequency reaches 2 output

28: Current reaches 1 output

29: Current reaches 2 output

30: timed to reach output

31: Reserved

32: Reserved

33: Running direction

34: Reserved

35: The module temperature reaches

36: Reserved

37: The lower limit frequency reaches 2

38: Fault output 2

39: Reserved

40: The running time arrives

41: User-defined output 1

42: User-defined output 2

43: Timer output

44: Running forward

45: Reverse running

00x0601
F6.02Relay 1 output selection20x0602
F6.03Relay 2 output selection (Extended)00x0603
F6.06VDO1 output selection00x0606
F6.07VDO2 output selection00x0607
F6.08VDO3 output selection00x0608
F6.09Reserve -0x0609
F6.10AO Output signal selection

One place: AO1

0: 0 to 10V

1: 4.00 to 20.00mA

2: 0.00 to 20.00mA

Tens place: AO2 (expend)

0: 0 to 10V

1: 4.00 to 20.00mA

2: 0.00 to 20.00mA

00-0x060A
F6.11FMP (Pulse output terminal) output selection

0: Run frequency

1: Setting frequency

2: Output current

3: Output torque

4: Output power

5: Output voltage

6: Reserve

7: AI1

8: AI2

9: AI3(Expansion module)

10: PULSE input value

11: Reserve

12: Communication setting

13: Motor speed

14: Output current (0-1000A, corresponding to 0-10V)

15: Output voltage (0-1000V, corresponding to 0-10V)

16: Bus voltage (0-1000V, corresponding to 0-10V)

00x060B
F6.12AO1 Output selection00x060C
F6.13AO2 Output(expend)00x060D
F6.14FM frequency output upper limit0.00 to 20.00kHz20.00kHz0x060E
F6.15AO1 Minimum input0.00V to F6.170.00V0x060F
F6.16AO1 Minimum input corresponds to setting0.0% to +100.0%0.0%0x0610
F6.17AO1 Maximum outputF6.15 to +10.00V10.00V0x0611
F6.18AO1 The maximum output corresponds to the setting0.0% to +100.0%100.0%0x0612
F6.19AO2 Minimum output(expend)0.00V to F6.210.00V0x0613
F6.20AO2 Minimum  output correspondence settings (expend)0.0% to +100.0%0.0%0x0614
F6.21AO2 Maximum output(expend)F6.19 to +10.00V10.00V0x0615
F6.22AO2 Maximum output correspondence settings (expend)0.0% to +100.0%100.0%0x0616
F6.23FMR connecting delay time0.0s to 3600.0s0.0s0x0617
F6.24Relay 1 connecting  delay time0.0 to 3600.0s0.0s0x0618
F6.25Relay 2 connecting delay time(expend)0.0s to 3600.0s0.0s0x0619
F6.26VDO connecting  delay time0.0 to 3600.0s0.0s0x061A
F6.27FMR disconnect delay time0.0s to 3600.0s0.0s0x061B
F6.28Relay 1 disconnect delay time0.0 to 3600.0s0.0s0x061C
F6.29Relay 2 disconnect delay time(expend)0.0s to 3600.0s0.0s0x061D
F6.30VDO1 disconnect delay0.0 to 3600.0s0.0s0x061E
F6.31Output terminal valid status select 1

0: Positive logic

1: Reverse logic

One place: FDOR

Tens place: RL1

Hundreds place: RL2 (Extended)

Thousands place: -

0000x061F
F6.32Virtual output terminal valid status Select 2

0: Positive logic

1: Reverse logic

One place: VDO1

Tens place: VDO2

Hundreds place: VDO3

Thousands palce: -

0000x0620
F6.33User-defined output selection (EX) 1

0: The running frequency

1: Set the frequency

2: Bus voltage

3: Output voltage

4: Output current

5: Output power

6: Output torque

7 to 8: Reserved

9: AI1 input

10: AI2 input

11: AI3 input(expansion module)

00x0621
F6.34User selected comparison method 1

Units: Compare test methods

0: Equal to (EX == X1)

1: The value is greater than or equal to

2: Less than or equal to

3: Interval comparison (X1 ≤ EX ≤ X2)

4: Bit test (EX & X1=X2)

Tens: output mode

0: False value output

1: Truth output

00x0622
F6.35User-defined dead zone 10 to 6553500x0623
F6.36User-defined 1 output comparison value 10 to 6553500x0624
F6.37User defined 1 output comparison value 20 to 6553500x0625
F6.38User-defined output selection (EX) 2

0: The running frequency

1: Set the frequency

2: Bus voltage

3: Output voltage

4: Output current

5: Output power

6: Output torque

7 to 8: Reserved

9: AI1 input

10: AI2 input

11: AI3 input(Expansion module)

00x0626
F6.39User defined comparison method 2

One place: Compare test methods

0: Equal to (EX == X1)

1: The value is greater than or equal to

2: Less than or equal to

3: Interval comparison (X1 ≤ EX ≤ X2)

4: Bit test (EX & X1=X2)

Tens: output mode

0: False value output

1: Truth output

00x0627
F6.40User-defined dead zone 20 to 6553500x0628
F6.41User defined 2 output comparison value 10 to 6553500x0629
F6.42User defined 2 output comparison value 20 to 6553500x062A
F6.43Timer time unit

0: Second

1: Min

2: Hour

00x062B
F6.44Timer maximum0-65000 (No reset when the set value is 65000)00x062C
F6.45Timer set value0 to 6500000x062D
F6.46Counter maximum0 to 6500000x062E
F6.47Counter set value0 to 6500000x062F
F7 Keyboard and display parameter group
F7.00LCD Keyboard parameter copy

0: No operation is performed

1: The function parameters of the machine are uploaded to the LCD keyboard

2: LCD keyboard function parameters download to the machine

00x0700
F7.01ENT key function selection

0: ENT is invalid.

1: Switch between the instruction channel of the operation panel and the remote instruction channel (the remote instruction channel includes communication and terminal control)

2: Reverse switch

3: Forward jog

4: Reverse jog

5: Menu mode switch

6: Reverse operation

00x0701
F7.02Keyboard STOP key range

LED one place: Terminal control selection

0: The terminal instruction is invalid

1: Valid for the terminal command

LED tens place: Communication control selection

0: The communication instruction is invalid.

1: Valid for communication instructions

LED hundreds place: Reserved

LED thousands place: Reserved

00110x0702
F7.03Keyboard run displays parameter 1

LED one place: First group display

0: Output frequency

1: Given frequency

2: Bus voltage

3: Output voltage

4: Output current

5: Output power

6: Output torque

7: DI input status

8: DO output status

9: AI1 voltage

A: AI2 voltage

B: AI3 voltage(expansion module)

C: Reserved

D: Reserved

E: Motor speed

F: PID setting

LED tens place: second group display

LED hundreds place: Third group display

LED thousands place: Fourth group display

E4200x0703
F7.04Keyboard run displays parameter 2

LED one place: First group display

0: Not displayed

1: PID feedback

2: PLC stage

3: PULSE input pulse frequency

4: Feedback speed

5: Reserved

6: Reserved

7: Reserved

8: Reserved

9: Current power-on time

A: Current running time

B: Reserved

C: Communication setting

D: Reserved

E: Main frequency X display

F: Auxiliary frequency Y display

LED ten: Second group display

LED hundreds place: Third group display

LED thousands place: Fourth group display

00000x0704
F7.05Keyboard stop displays parameters

LED one place: First group display

0: Output frequency

1: Given frequency

2: Bus voltage

3: Output voltage

4: Output current

5: Output power

6: Output torque

7: DI input status

8: DO output status

9: AI1 voltage

A: AI2 voltage

B:AI3 voltage(Expansion module)

C: Motor speed

D: PID setting

E: PID feedback

F: PLC stage

LED tens place: Second group display

LED hundreds place: Third group display

LED thousands place: Fourth group display

C4210x0705
F7.06Load speed display factor0.001 to 65.0001.0000x0706
F7.07Radiator temperature of inverter module0℃ to 100℃ 0x0707
F7.08Radiator temperature of rectifier bridge0℃ to 100℃ 0x0708
F7.09Cumulative running time0h to 65535h 0x0709
F7.10Product number- 0x070A
F7.11Software version- 0x070B
F7.12Reverse  0x070C
F7.13Total power-on time0 to 65535h 0x070D
F7.14High cumulative power consumption

Power consumption

=F7.14*65535+F7.15

Units: kWh

 0x070E
F7.15Low cumulative power consumption 0x070F
F7.16Output power correction factor0 to 100.0%100.0%0x0710
F7.17Power display dimension selection

0 to Power display percentage (%)

1 to Power display kilowatts (KW)

10x0711
F8 Auxiliary function parameter group
F8.00JOG running frequency0.00Hz to Maximum frequency F0.102.00Hz0x0800
F8.01JOG acceleration time0.00s to 6500.0s20.0s0x0801
F8.02JOG deceleration time0.00s to 6500.0s20.0s0x0802
F8.03Acceleration time 20.00s to 6500.0sModel determination0x0803
F8.04Deceleration time 20.00s to 6500.0s0x0804
F8.05Acceleration time 30.00s to 6500.0s0x0805
F8.06Deceleration time 30.00s to 6500.0s0x0806
F8.07Acceleration time 40.00s to 6500.0s0x0807
F8.08Deceleration time 40.00s to 6500.0s0x0808
F8.09Emergency stop deceleration time0.00s to 6500.0s0x0809
F8.10Jump frequency 10.00Hz to Maximum frequency0.00Hz0x080A
F8.11Jump frequency 20.00Hz to Maximum frequency0.00Hz0x080B
F8.12Jump frequency amplitude0.00Hz to Maximum frequency0.00Hz0x080C
F8.13Forward-reverse dead zone time0.0 to 120.0s0.0s0x080D
F8.14The carrier frequency is adjusted with temperature

0: Temperature independent

1: Temperature dependent

10x080E
F8.15Terminal action is preferred

0: Invalid

1: Valid

10x080F
F8.16Setting of accumulated power-on arrive time0h to 65000h0h0x0810
F8.17Set the accumulative running arrival time0h to 65000h65000h0x0811
F8.18Setting of accumulated power-on arrive action

0: Continue to run

1: Fault warning

00x0812
F8.19Set the accumulative running time arrival action

0: Continue to run

1: Fault warning

00x0813
F8.20Arrival time of this run0 to 65000min00x0814
F8.21The running time reaches the action selection

0: Continue to run

1: Fault prompt

00x0815
F8.22Frequency detection value(FDT1)0.00 to Maximum frequency50.00Hz0x0816
F8.23Frequency detection lag value(FDT1)0.00 to Maximum frequency0.00Hz0x0817
F8.24Frequency detection value(FDT2)0.00 to Maximum frequency50.00Hz0x0818
F8.25Frequency detection lag value(FDT2)0.00-Maximum frequency0.00Hz0x0819
F8.26Frequency reaches the detect width

0.0% to 100.0%

(Maximum frequency)

0.0%0x081A
F8.27Arbitrary arrival frequency detection value 10.00Hz to Maximum frequency50.00Hz0x081B
F8.28Arbitrary arrival frequency detection amplitude 10.0% to 100.0% (Maximum frequency)0.0%0x081C
F8.29Arbitrary arrival frequency detection value 20.00Hz to Maximum frequency50.00Hz0x081D
F8.30Arbitrary arrival frequency detection amplitude 10.0% to 100.0% (Maximum frequency)0.0%0x081E
F8.31Arbitrarily reach current1

0.0% to 300.0%

(Motor rated current)

100.0%0x081F
F8.32Arbitrarily reach current 1 width

0.0% to 300.0%

(Motor rated current)

0.0%0x0820
F8.33Arbitrarily reach current 2

0.0% to 300.0%

(Motor rated current)

100.0%0x0821
F8.34Arbitrarily reach current 2 width

0.0% to 300.0%

(Motor rated current)

0.0%0x0822
F8.35Zero current detection value0.0% to 300.0%(Motor rated current)5.0%0x0823
F8.36Zero current detection delay time0 to 600.00s0s0x0824
F8.37Software over current point (D0 output)

0.0% to 300.0%

(AC drive rated current)

200.0%0x0825
F8.38Software over current detection delay time0 to 600.00s0s0x0826
F9 Functional parameter array
F9.00PID setting source

0: Keyboard number PID given F9.01

1: AI1

2: AI2

3: Reserve

4: Terminal pulse setting

5: Communication setting

6: Multi -stage speed setting

7: Keyboard potentiometer setting

00x0900
F9.01PID digital setting0.0% to 100.0%50.0%0x0901
F9.02PID feedback source

0: AI1

1: AI2

2: Reserve

3: AI1-AI2

4: Terminal pulse setting

5: Communication setting

6: AI1+AI2

7: MAX(|AI1|, |AI2|)

8: MIN(|AI1|, |AI2|)

9: Keyboard potentiometer setting

00x0902
F9.03PID control characteristics

LED units: Feedback characteristic selection

0: Positive action

1: Reaction

LED tens: PID adjustment direction selection

0: Reverse prohibition

1: Reverse permit

LED hundreds digit: Alignment selection

0: Off-center alignment

1: Center alignment

LED kilobit: Reserve

01000x0903
F9.04PID given feedback range0 to 6553510000x0904
F9.05Proportional gain P10 to 1000.020.000x0905
F9.06Integration time I10.00s to 10.00s2.00s0x0906
F9.07Differential time D10.00s to 10.00s0.00s0x0907
F9.08PID reverse cutoff frequency0.00 to Maximum frequency F0.100.00Hz0x0908
F9.09PID deviation limit0.0% to 100.0%0.0%0x0909
F9.10PID differential limiting0.00% to 100.00%0.10%0x090A
F9.11PID given change time0.00 to 100.00s0s0x090B
F9.12PID feedback filtering time0.00 to 60.00s0.00s0x090C
F9.13PID output filtering time0.00 to 60.00s0.00s0x090D
F9.14Proportional gain P20.0 to 1000.020.000x090E
F9.15Integration time I20.00s to 10.00s2.00s0x090F
F9.16Differential time D20.00s to 10.00s0.00s0x0910
F9.17PID parameter switching condition

0: Do not switch

1: Terminal switching

2: Automatic switching based on deviation

00x0911
F9.18PID parameter switching deviation 10.0% to F9.1920.0%0x0912
F9.19PID parameter switching deviation 2F9.18 to 100.0%80.0%0x0913
F9.20PID Initial frequency value0.0% to 100.0%0%0x0914
F9.21PID Frequency initial holding time0.0 to 6500.0s0.0s0x0915
F9.23Feedback wire break action selection

0: The PID continues to run and no fault is reported

1: Stop and report fault (Manual reset)

2: Continue PID operation, output alarm signal

3: Run at the current frequency, output alarm signal

4: Stop and report fault (Automatic reset)

00x0917
F9.24Wire break alarm upper limitF9.25 to 100.0%100.0%0x0918
F9.25Line break alarm lower limit0 to F9.240.0%0x0919
F9.26Feedback break detection time0.0s to 120.0s0.0s0x091A
F9.27PID stop operation

0: No operation at stop

1: Operation at stop

00x091B
F9.28PID function selection

0: Normal PID

1: Dormant PID

00x091C
F9.29PID sleep threshold0.0% to 100.0%60.0%0x091D
F9.30PID sleep delay0.0 to 3600.0s3.0s0x091E
F9.31PID wake-up threshold0.0% to 100.0%20.0%0x091F
F9.32PID wake up delay0.0 to 3600.0s3.0s0x0920
F9.33Dormancy detection frequency0 to Upper limit frequency F0.1225.00Hz0x0921
F9.34Minimum output

0: F0.14(Lower frequency)

1: 0Hz

 0x0922
F9.35Double output deviation reverse minimum0.00 to 100.00%1.00%0x0923
F9.36Double output deviation reverse maximum0.00 to 100.00%1.00%0x0924
F9.37PID integral attribute

Units place: integral separation

0: Invalid

1: Valid

Tens: output to the limit, whether to stop integrating

0: Continue to integrate

1: Stop collecting points

00x0925
F9.38PID Preset Switchover condition selection

0: Time

1: Switch according to AI1 feedback value

00x0926
F9.39PID Minimum value of AI feedback switching0.0 to F9.4045.0%0x0927
F9.40PID AI feedback maximum switching valueF9.39 to 100.0%55.0%0x0928
FA Fault and protection parameter group
FA.00Motor overload protection selection

0: Off

1: On

10x0A00
FA.01Motor overload protection factor0.0 to 250.0%100.0%0x0A01
FA.02Motor overload warning coefficient20.0 to 250.0%80.0%0x0A02
FA.03Overvoltage stall and overcurrent stall control selection

0: Off

1: On

Unit: Excessive suppression enable

Tens: Over current suppression enable

Hundreds: Judge the input of brakes

Thousands: Excessive suppression of fast rising frequency

11110x0A03
FA.04Over voltage protection voltage110% to 150%Model settings0x0A04
FA.05The Udc controls voltage loop gain0.00 to 50.002.000x0A05
FA.06The Udc controls current loop gain0.00 to 50.002.000x0A06
FA.07Overcurrent suppression point50% to 200%150%0x0A07
FA.08Overcurrent suppression gain0.00 to 50.002.000x0A08
FA.09Overcurrent suppression points0.00 to 50.004.000x0A09
FA.10Short -circuit detection

0: Invalid

1: Valid

10x0A0A
FA.11Input phase loss protection

0:Disable

1: Enable

10x0A0B
FA.12Output phase loss protection

0:Disable

1: Enable

10x0A0C
FA.13Input phase loss protection software detection level0.0 to 999.9%15.0%0x0A0D
FA.14PWM parameter setting

One place: Enable voltage prediction compensation

Tens place: PWM update mode

0: Single sample update

1: Double sample and double update

Hundreds place: Random carrier mode

0: Random carrier

1: Random 0 vector

0010 0x0A0E
FA.15Hardware current and voltage protection

One place: Hardware current limit(CBC)

0: Disable

1: Enable

Tens places: -

Hundreds place: FAU filtering time

1 to F

Thousands place: TZ filtering time

1 to F

00010x0A0F
FA.16CBC protection point100-220%200%0x0A10
FA.17CBC overload protection time1-5000ms500ms0x0A11
FA.18Undervoltage threshold setting40.0% to 100.0%100.0%0x0A12
FA.19Reserve-Model determination0x0A13
FA.20Number of failure recovery0 to 500x0A14
FA.21Interval for fault self-recovery0.1 to 100.0s1.0s0x0A15
FA.22Power loss ride-through selection

One place: Power loss ride-through selection function enable

0: Disable

1: Enabled

Tens place: Power loss ride-through function selection

0: Continue to operation

1: Shut down

00000x0A16
FA.23Instant stop non-stop enter voltage40% to 150%75%0x0A17
FA.24Instant stop non-stop stable voltage60% to 150%95%0x0A18
FB Application parameter set
FB.00Swing frequency control

LED one-place: Swing frequency control

0: The swing frequency control is invalid

1: Swing frequency control is valid

LED tens place: Swing frequency input mode

0: Automatic input

1: Manual input

LED hundreds-place: Swing control

0: Variable swing

1: Fixed swing

LED thousands place: Reserved

00x0B00
FB.01Swing preset frequency0.00 to Maximum frequency0.00Hz0x0B01
FB.02Preset frequency duration0.00 to 650.00s0.00s0x0B02
FB.03Swing amplitude0.0 to 100.0%0.0%0x0B03
FB.04Jump frequency amplitude0.0 to 50.0%0.0%0x0B04
FB.05Swing frequency rise time0.00 to 650.00s5.00s0x0B05
FB.06Swing frequency drop time0.00 to 650.00s5.00s0x0B06
FC Communication parameter group
FC.00Local address1 to 247, 0 is Broadcast address10x0C00
FC.01Baud rate

0: 300 bps

1: 600 bps

2: 1200 bps

3: 2400 bps

4: 4800 bps

5: 9600 bps

6: 19200 bps

7: 38400 bps

8: 57600 bps

9: 115200 bps

50x0C01
FC.02Modbus data format

0: (8.N.2) 8 data bits, no parity, 2 stop stops

1: (8.E.1) 8 data bits, even parity, 1 stop position

2: (8.O.1) 8 data bits, odd parity, 1 stop stop

3: (8.N.1) 8 data bits, no parity, 1 stop stop

30x0C02
FC.03Modbus Communication response delay0ms to 20ms2ms0x0C03
FC.04Modbus Communication timeout0.0 (Invalid), 0.1s to 60.0s00x0C04
FC.06​Master-slave selection

LED units place: Modbus communication master-slave selection

0: Slave 1: Host

0  
FC.07Communication ratio setting0.00 to 5.001.00  
FC.08Modbus communication fault action mode selection

0: Alarm and free parking (manual reset)

1: No alarm and continue running

2: Alarm and free parking (automatic reset)

3: Parking does not alarm (based on F1.10 parking)

1  
FC.09Modbus transfers response processing

Units place: Write operation response

0: Response to the write operation

1: No response to write operation

Tens Place: Communication exception response​​

0: Response to exception

1: No response to exception

Hundreds place: Communication exception response protocol​

0:8001 1:83

000  
FC.10Hosts send selection

LED units place: 1st group sending frame selection

LED tens place:2st group sending frame selection

LED hunderds place: 3st group sending frame selection

0: Invalid

1: Running command given

2: Host given frequency

3: Host output frequency

4: Host upper limit frequency

6: Host output torque

9: Host given PID  A: Host feedback PID

0x21  
FC.11RS485 communication port configuration

0: Configure to Modbus Communication

1: Quota is serial communication

2: UART_OSC

0  
FD Multi -speed instructions and simple PLC parameter arrays
FD.00Multi-speed instruction 0-100.0% to 100.0% (100.0% corresponds to maximum frequency F0.10)00x0D00
FD.01Multi-speed instruction 1-100.0% to 100.0%00x0D01
FD.02Multi-speed instruction 2-100.0% to 100.0%00x0D02
FD.03Multi-speed instruction 3-100.0% to 100.0%00x0D03
FD.04Multi-speed instruction 4-100.0% to 100.0%00x0D04
FD.05Multi-speed instruction 5-100.0% to 100.0%00x0D05
FD.06Multi-speed instruction 6-100.0% to 100.0%00x0D06
FD.07Multi-speed instruction 7-100.0% to 100.0%00x0D07
FD.08Multi-speed instruction 8-100.0% to 100.0%00x0D08
FD.09Multi -speed instruction 9-100.0% to 100.0%00x0D09
FD.10Multi-speed instruction10-100.0% to 100.0%00x0D0A
FD.11Multi-speed instruction11-100.0% to 100.0%00x0D0B
FD.12Multi-speed instruction12-100.0% to 100.0%00x0D0C
FD.13Multi-speed instruction13-100.0% to 100.0%00x0D0D
FD.14Multi-speed instruction14-100.0% to 100.0%00x0D0E
FD.15Multi-speed instruction15-100.0% to 100.0%00x0D0F
FD.16PLC mode of operation

0: Stops after a single run

1: Maintain the final value at the end of a single run

2: Keep cycling

00x0D10
FD.17PLC Power down memory selection

Ones Slot:

0: Power failure does not memory

1: Power failure memory

Ten places:

0: Stop and does not remember

1: Shutdown memory

00x0D11
FD.18Running time of simple PLC reference 00.0 to 6553.5 (s/m/h)0.0s(h)0x0D12
FD.19Acceleration/deceleration time of simple PLC reference 00 to 300x0D13
FD.20Running time of simple PLC reference 10.0 to 6553.5 (s/m/h)0.0s(h)0x0D14
FD.21Acceleration/deceleration time of simple PLC reference 10 to 300x0D15
FD.22Running time of simple PLC reference 20.0 to 6553.5 (s/m/h)0.0s(h)0x0D16
FD.23Acceleration/deceleration time of simple PLC reference 20 to 300x0D17
FD.24Running time of simple PLC reference 30.0 to 6553.5 (s/m/h)0.0s(h)0x0D18
FD.25Acceleration/deceleration time of simple PLC reference 30 to 300x0D19
FD.26Running time of simple PLC reference 40.0 to 6553.5 (s/m/h)0.0s(h)0x0D1A
FD.27Acceleration/deceleration time of simple PLC reference 40 to 300x0D1B
FD.28Running time of simple PLC reference 50.0 to 6553.5(s/m/h)0.0s(h)0x0D1C
FD.29Acceleration/deceleration time of simple PLC reference 50 to 300x0D1D
FD.30Running time of simple PLC reference 60.0 to 6553.5 (s/m/h)0.0s(h)0x0D1E
FD.31Acceleration/deceleration time of simple PLC reference 60 to 300x0D1F
FD.32Running time of simple PLC reference 70.0 to 6553.5 (s/m/h)0.0s(h)0x0D20
FD.33Acceleration/deceleration time of simple PLC reference 60 to 300x0D21
FD.34Running time of simple PLC reference 80.0 to 6553.5 (s/m/h)0.0s(h)0x0D22
FD.35Acceleration/deceleration time of simple PLC reference 80 to 300x0D23
FD.36Running time of simple PLC reference 90.0 to 6553.5 (s/m/h)0.0s(h)0x0D24
FD.37Acceleration/deceleration time of simple PLC reference 90 to 300x0D25
FD.38Running time of simple PLC reference 100.0 to 6553.5 (s/m/h)0.0s(h)0x0D26
FD.39Acceleration/deceleration time of simple PLC reference 100 to 300x0D27
FD.40Running time of simple PLC reference 110.0 to 6553.5 (s/m/h)0.0s(h)0x0D28
FD.41Acceleration/deceleration time of simple PLC reference 110 to 300x0D29
FD.42Running time of simple PLC reference 120.0 to 6553.5 (s/m/h)0.0s(h)0x0D2A
FD.43Acceleration/deceleration time of simple PLC reference 120 to 300x0D2B
FD.44Running time of simple PLC reference 130.0 to 6553.5 (s/m/h)0.0s(h)0x0D2C
FD.45Acceleration/deceleration time of simple PLC reference 130 to 300x0D2D
FD.46Running time of simple PLC reference 140.0 to 6553.5 (s/m/h)0.0s(h)0x0D2E
FD.47Acceleration/deceleration time of simple PLC reference 140 to 300x0D2F
FD.48Running time of simple PLC reference 150.0 to 6553.5 (s/m/h)0.0s(h)0x0D30
FD.49Acceleration/deceleration time of simple PLC reference 150 to 300x0D31
FD.50PLC Run-time unit

LED units: timing unit

0: s(seconds)

1: h(hours)

2: min(minutes)

00x0D32
FD.51Multi-segment speed instruction 0 given mode

0: Function code FD.00 is given

1: AI1

2: AI2

3: AI3 (expansion)

4: Terminal pulse PULSE given

5: PID

6: Preset frequency (F0.08) given, UP/DOWN modifiable

7: Keyboard potentiometer given

00x0D33
FD.52Multispeed priority

0: Invalid

1: Valid

10x0D34
FE User parameter group
FE.00User password0 to 6553500x0E00
FE.01Fault record display times0 to 840x0E01
FE.02Parameter and key lock selection

0: Not locked

1: The function parameter is locked

00x0E02
A0 Application parameter group
A0.00Application macro

0:Default macro

1: Pressure machine macro

2: Spring machinery macro

3: woodworking machinery macro

00xA000
A4 Constant pressure water supply parameter group
A4.00Water supply function selection

0: Invalid

1: Valid

00xA400
A4.01Setting pressure1.0 to A4.193.0bar0xA401
A4.02Starting pressure0.0 to A4.010.3bar0xA402
A4.03Sensor range1.0 to 200.0bar16.0bar0xA403
A4.04Sensor feedback type

0: 4 to 20mA(AI2)

1: 0 to 10V(AI1)

00xA404
A4.05Pressure calibration factor0.750 to 1.2501.0000xA405
A4.06Proportional gain P0.0 to 100.050.00xA406
A4.07Integration time I0.00s to 10.00s0.500xA407
A4.08Differential time0.000s to 10.000s0.0000xA408
A4.09Sleep time

0: Disable

1: Sleep mode 1

2: Sleep mode 2

 

1

 

0xA409

A4.10Sleep delay0.0s to 100.0s5.0s0xA40A
A4.11Wake up delay0.0s to 100.0s3.00xA40B
A4.12Low-frequency hold frequency0.0 to A4.1420.00Hz0xA40C
A4.13Low frequency hold frequency running time0.0s to 100.0s5.0s0xA40D
A4.14Sleep frequencyA4.12 to F0.1225.00Hz0xA40E
A4.15Sleep detection cycle0.0s to 600.0s30.0s0xA40F
A4.16Leaking coefficient0.1s to 100.0s2.5s0xA410
A4.17Sleep detection coefficient1 to 1040xA411
A4.18Deadband pressure0.0bar to 1.0bar0.1bar0xA412
A4.19 High voltage alarm setting valueA4.00 to A4.0315.0bar0xA413
A4.20 Low voltage alarm setting value0.0 to A4.010.0bar0xA414
A4.21Water pressure alarm delay time0.0 to 100.03.0s0xA415
A4.22Sensor disconnection detection value0.00 to 10.00V0.200xA416
A4.23Sensor disconnection detection time0.0s to 100.0s30.0s0xA417
A4.24Water shortage protection function

0: Disable

1: Judging by frequency and current

2: Judging by frequency and pressure

20xA418
A4.25Water shortage fault detection threshold0.00s to 10.00s0.500xA419
A4.26Water shortage protection detection frequency0 to F0.1248.00Hz0xA41A
A4.27Water shortage protection detection current percentage0.0 to 100.0%40.0%0xA41B
A4.28Water shortage protection detection time0.0 to 200.0s60.0s0xA41C
A4.29Water shortage protection automatic reset delay0 to 1000150xA41D
A4.30Number of Auto-resets for water shortage protection0 to 100100xA41E
A4.31Pressure rise control function

0: Invalid

1: Valid

00xA41F

 

A4.35

Constant frequency water shortage function selection

One place: Turn on protection

0: Disable 1: Enable

Tens place: Current detected

0: Total current 1: Torque current

0010

  
A4.36Constant frequency water shortage protection current0% to 150%40%  
A4.37Constant frequency water shortage protection frequency0% to 100%50%  
A4.38Constant frequency water shortage protection detection time1 to 1000s30s  
A4.39Constant frequency water shortage protection recovery time1 to 10000s600s  
A4.40 Constant frequency water shortage protection recovery times0 to 1003  

Fault record parameter group

Function codeNameSetting range and descriptionChange

Modbus

address

E0 Fault parameter set
E0.00Fault typeRefer to the fault Information code table for detail0xE000
E0.01Failure operating frequency0.0 to Maximum frequency0xE001
E0.02Fault output current0.1 to 2000.0A0xE002
E0.03Fault bus voltage0 to 810.0V0xE003
E0.04Fault input terminal statusRefer to the input terminal state diagram0xE004
E0.05Fault output terminal statusRefer to the output terminal state diagram0xE005
E0.06Fault module temperature0 to 100℃0xE006
E0.07Fault VFD condition

LED one place: Running direction

0: Forward

1: Reverse

LED tens place: Running status

0: Stop

1: Steady speed

2: Speed up

3: Slow down

0xE007
E0.08

Down time

(Count from this power-on)

0 to 65535min0xE008
E0.09

Down time

(From total running time)

0 to 65535H0xE009
E0.10Fault output voltage0 to 1500V0xE00A
E0.11Fault diagnosis informationRefer to (Chapter 8 to Fault Code Details)0xE00B
E0.12Number of faulty CBC10Sec if no CBC zeroing0xE00C

Display parameter group

Function codeNameMinimum unitChangeModbus address
D0 Display parameter group
D0.00Running frequency(Hz)0.01Hz0xD000
D0.01Setting frequency(Hz)0.01Hz0xD001
D0.02Bus voltage(V)0.1V0xD002
D0.03Output voltage(V)1V0xD003
D0.04Output current(A)0.1A0xD004
D0.05Output power(kW)0.1kW0xD005
D0.06Output torque(%)0.1%0xD006
D0.07DI Input state 0xD007
D0.08DO Output state 0xD008
D0.09AI1 Voltage (V)0.01V0xD009
D0.10AI2 Voltage(V)0.01V0xD00A
D0.11AO1 Voltage(V)0.01V0xD00B
D0.12Count value 0xD00C
D0.13Axis Frequency 0xD00D
D0.14Load speed display1rpm0xD00E
D0.15PID setting 0xD00F
D0.16PID feedback 0xD010
D0.17PLC phase 0xD011
D0.18PULSE input pulse frequency 0xD012
D0.19Feedback speed(Unit0.1Hz) 0xD013
D0.20Remaining running time 0xD014
D0.21AI1Pre-correction voltage 0xD015
D0.22AI2Pre-correction voltage 0xD016
D0.23Reserve 0xD017
D0.24Linear velocity 0xD018
D0.25Current power-on time1min0xD019
D0.26Current running time0.1min0xD01A
D0.27CPU temperature 0xD01B
D0.28Communication setting 0xD01C
D0.29Radiator temperature 0xD01D
D0.30Main frequency X display0.01Hz0xD01E
D0.31Auxiliary frequency Y display0.01Hz0xD01F
D0.34Reserve 0xD022
D0.35Analog grounding 0xD023
D0.363.3VA 0xD024
D0.37Control board plate number 0xD025
D0.38Plate number of the power board 0xD026
D0.39Power factor Angle 0xD027
D0.40Virtual VDI state 0xD100
D0.41Virtual VDO state 0xD101
D0.42Expand DI input status 0xD102
D0.43Expand DO input status 0xD103
D0.44Expansion board version 0xD104
D0.45AI3 (Expand) voltage (V)0.01V0xD105
D0.46AI4 (Expand) voltage (V)0.01V0xD106
D0.49AO2 Voltage (V)0.01V0xD109
D0.53Communication status of the main control board 0xD10D
D0.54Extended communication status 0xD10E

A0 Application parameter group

✎Notes: As the software iterates, the parameter list may change.

Function codeNameMinimum unitChange

Modbus

address

A0 Application parameter set
A0.00Application macro

0: Default macro

1: Pressure tile machinery macro

2: Spring machinery macro

3: Woodworking machinery macro

0xA000