Changes for page 09 Function code

Last modified by Iris on 2025/11/17 14:59

From version 12.1
edited by Iris
on 2025/11/14 16:13
Change comment: There is no comment for this version
To version 11.1
edited by Iris
on 2025/11/14 15:42
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1596,7 +1596,7 @@
1596 1596  
1597 1597  (% style="text-align:center" %)
1598 1598  (((
1599 -(% style="display:inline-block; width:357px;" %)
1599 +(% style="display:inline-block;" %)
1600 1600  [[Figure 9-5-1 simulates the correspondence between given and set quantities>>image:1763083956225-706.png||height="527" width="357"]]
1601 1601  )))
1602 1602  
... ... @@ -1735,1746 +1735,5 @@
1735 1735  [[Figure 9-5-1 Simulates the correspondence between given and set quantities>>image:1763083956228-763.png]]
1736 1736  )))
1737 1737  
1738 -== **F6 group output terminals** ==
1739 1739  
1740 -The VC series VFD standard unit has 2 multi-function relay output terminals, 1 FM terminal (which can be used as a high-speed pulse output terminal or as an open collector output), and 2 multi-function analog output terminals.
1741 -
1742 -|(% rowspan="3" %)F6.00|(% colspan="2" %)FM Terminal output selection|Factory default|1
1743 -|(% rowspan="2" %)Setting range|0|(% colspan="2" %)Pulse output
1744 -|1|(% colspan="2" %)Open collector output (FMR)
1745 -
1746 -FM terminals are programmable multiplexed terminals. Can be used as a high speed pulse output terminal (FMP), pulse frequency up to 100kHz. Refer to F6.06 for FMP related functions. Also available as an open collector output terminal (FMR). See F6.01 for FMR functions.
1747 -
1748 -FMP function needs hardware support.
1749 -
1750 -|F6.01|FMR Open collector output selection|Factory default|0
1751 -|F6.02|Relay 1 output selection|Factory default|2
1752 -|F6.03|Relay 2 output selection (Extended)|Factory default|0
1753 -|F6.06|VDO1 output selection|Factory default|0
1754 -|F6.07|VDO2 output selection|Factory default|0
1755 -|F6.08|VDO3 output selection|Factory default|0
1756 -
1757 -
1758 -
1759 -Multi-function output terminal function selection are as follows:
1760 -
1761 -|**Setting value**|**Function**|**Description**
1762 -|0|No-output|The output terminal has no function
1763 -|1|VFD in operation|Indicates that the inverter is running, there is an output frequency (can be zero) at this time output ON signal.
1764 -|2|Fault output|When the inverter fails and fails to stop, the output ON signal.
1765 -|3|Frequency level detects FDT arrival|Please refer to function codes F8.19 and F8.20 for detailed instructions
1766 -|4|Frequency arrival|Please refer to function code F8.26 for detailed instructions.
1767 -|5|Running at zero speed|The VFD operates and the output frequency is 0, and the output signal is ON.
1768 -|6|Motor overload pre-alarm|Before the motor electronic thermal protection action, according to the overload forecast value, after exceeding the forecast value output ON signal. Motor overload parameters are set in FA.00 to FA.02.
1769 -|7|Inverter overload pre-alarm|After checking the inverter overload, 10s before the protection occurs. Output ON signal.
1770 -|8|Set count pulse value to arrive|When the count value reaches the value set by FB.08, the ON signal is output.
1771 -|9|Specified count pulse value arrived|When the count value reaches the value set by FB.09, the ON signal is output. For the counting function, see FB group function description
1772 -|10|Length reached|When the actual length of the detection exceeds the length set by FB.05, the ON signal is output.
1773 -|11|PLC cycle complete|When the simple PLC completes a cycle, it outputs a pulse signal with a width of 250ms.
1774 -|12|Cumulative running time arrived|When the accumulated running time of the inverter exceeds the time set by F8.17, the output ON signal.
1775 -|13|-|-
1776 -|14|Torque limit|When the torque limit function is operated, the stall protection function automatically acts, automatically changes the output frequency, and the output ON signal indicates that the output torque is limited. This output signal can be used to reduce the load or to display an overload status signal on the monitoring device.
1777 -|15|Operational readiness|The main circuit and control circuit power supply are established, the inverter protection function is not active, and the inverter is in the running state, the ON signal is output.
1778 -|16|AI1>AI2|When the value of the analog input AI1 is greater than that of the other input AI2, the ON signal is output.
1779 -|17|Frequency upper limit reached|Output ON signal when the operating frequency reaches the upper limit frequency.
1780 -|18|(((
1781 -Frequency lower limit reached
1782 -
1783 -(Run related)
1784 -)))|Output ON signal when the operating frequency reaches the lower limit frequency. In the shutdown state, the signal is always OFF.
1785 -|19|Undervoltage state output|The inverter outputs ON signal when it is undervoltage.
1786 -|20|Communication setting|See related instructions in the communication protocol
1787 -|21|Positioning completed|Reserve
1788 -|22|Positioning close|Reserve
1789 -|23|(((
1790 -Zero speed running 2
1791 -
1792 -(Also output when shut down)
1793 -)))|VFD output frequency is 0, output ON signal (shutdown also output).
1794 -|24|Accumulative power-on time reached|When F7.13(the accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output.
1795 -|25|(((
1796 -Frequency level detection
1797 -
1798 -FDT2 output
1799 -)))|For details, see function codes F8.28 and F8.29.
1800 -|26|Frequency to 1 output|For details, see function codes F8.30 and F8.31.
1801 -|27|Frequency to 2output|For details, see function codes F8.32 and F8.33.
1802 -|28|Current reaches 1 output|For details, see function codes F8.38 and F8.39.
1803 -|29|Current reaches 2 output|For details, see function codes F8.40 and F8.41.
1804 -|30|Timed arrival output|When F8.42(timing function selection) is effective, the VFD will output ON signal when the running time reaches the set timing time.
1805 -|31|-|-
1806 -|32|-|
1807 -|33|Running direction|When the inverter runs in reverse, the ON signal is output
1808 -|34|-|
1809 -|35|Module temperature reach|
1810 -|36|Software overcurrent output|For details, see function codes F8.36 and F8.37.
1811 -|37|(((
1812 -Lower limit frequency reached
1813 -
1814 -(Run independent)
1815 -)))|Output ON signal when the operating frequency reaches the lower limit frequency. (When the conditions are met, the ON signal will also be output in the shutdown state)
1816 -|38|Fault output (Continue running)|When the inverter fails, output ON signal
1817 -|39|Reserve|
1818 -|40|The running time arrive|
1819 -|41|User defined output 1|User can define the conditions to output the terminal
1820 -|42|User-defined output 2|User can define the conditions to output the terminal
1821 -|43|Timer output|Output ON signal when the timing setting condition is met
1822 -|44|Forward running status|If the inverter is in forward running, output ON signal
1823 -|45|Reverse running status|If the inverter is in reverse running, output ON signal
1824 -
1825 -
1826 -
1827 -
1828 -|(% rowspan="2" %)F6.10|AO output signal selection|Factory default|00
1829 -|Setting range|(% colspan="2" %)(((
1830 -The ones place: AO1
1831 -
1832 -0: 0 to 10V
1833 -
1834 -1: 4.00 to 20.00mA
1835 -
1836 -2: 0.00 to 20.00mA
1837 -
1838 -Tens place: AO2 (Extended)
1839 -
1840 -0: 0 to 10V
1841 -
1842 -1: 4.00 to 20.00mA
1843 -
1844 -2: 0.00 to 20.00mA
1845 -)))
1846 -
1847 -All models 1 AO.
1848 -
1849 -|(% rowspan="2" %)F6.11|FMP (Pulse output terminal) output selection|Factory default|0
1850 -|Setting range|(% colspan="2" %)(((
1851 -0: Running frequency
1852 -
1853 -1: Set the frequency
1854 -
1855 -2: Output current
1856 -
1857 -3: Output torque
1858 -
1859 -4: Output power
1860 -
1861 -5: Output voltage
1862 -
1863 -6: Reserve
1864 -
1865 -7: AI1
1866 -
1867 -8: AI2
1868 -
1869 -9: AI3
1870 -
1871 -10: PULSE input value
1872 -
1873 -11: Reserve
1874 -
1875 -12: Communication settings
1876 -
1877 -13: Motor speed
1878 -
1879 -14: Output current (0-1000A, corresponding to 0-10V)
1880 -
1881 -15: Output voltage (0-1000V, corresponding to 0-10V)
1882 -
1883 -16: Bus voltage (0-1000V, corresponding to 0-10V)
1884 -)))
1885 -|(% rowspan="2" %)F6.12|AO1 output selection|Factory default|0
1886 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range
1887 -|(% rowspan="2" %)F6.13|AO2 output selection (Extended)|Factory default|0
1888 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range
1889 -
1890 -The standard output of the analog output (zero bias is 0, gain 1) is 0mA to 20mA (or 0V to 10V).
1891 -
1892 -The range of corresponding quantities represented is shown in the following table:
1893 -
1894 -|**Setting value**|**Function**|**Range**
1895 -|0|Operating frequency|0 to Maximum output frequency
1896 -|1|Setting frequency|0 toMaximum output frequency
1897 -|2|Output current|0 to2 times the rated motor current
1898 -|3|Output torque|0 to2 times the rated motor torque
1899 -|4|Output power|0 to 2 times rated power
1900 -|5|Output voltage|0 to 1.2 times rated voltage of inverter
1901 -|6|(% colspan="2" %)Reserve
1902 -|7|AI1|0V to10V
1903 -|8|AI2|0V to10V/0-20mA
1904 -|9|(% colspan="2" %)Reserve
1905 -|10|Length|0 to Maximum set length
1906 -|11|Count value|0 to Maximum count value
1907 -|12|Communication setting|-10000 to 10000
1908 -|13|Motor speed|0 to The maximum output frequency corresponds to the speed
1909 -|14|Output current|0 to 1000A, correspondence 0-10V
1910 -0 to 1000V, correspondence 0-10V
1911 -|15|Output voltage|0.0V to 1000.0V
1912 -|16|Bus voltage|0 to 1000V, correspondence 0-10V
1913 -
1914 -
1915 -
1916 -|(% rowspan="2" %)F6.14|FM upper frequency output limit|Factory default|20.00kHz
1917 -|Setting range|(% colspan="2" %)0.00 to- 50.00kHz
1918 -
1919 -
1920 -
1921 -F6.00 maximum frequency of pulse output when selecting pulse output.
1922 -
1923 -|(% rowspan="2" %)F6.15|AO1 minimum input|Factory default|0.00V
1924 -|Setting range|(% colspan="2" %)0.00V to F6.17
1925 -|(% rowspan="2" %)F6.16|AO1 the minimum input corresponds to the setting|Factory default|0.0%
1926 -|Setting range|(% colspan="2" %)0.0% to +100.0%
1927 -|(% rowspan="2" %)F6.17|AO1 maximum input|Factory default|10.00V
1928 -|Setting range|(% colspan="2" %)F6.15 to +10.00V
1929 -|(% rowspan="2" %)F6.18|AO1 the maximum input corresponds to the setting|Factory default|100.0%
1930 -|Setting range|(% colspan="2" %)0.0% to +100.0%
1931 -
1932 -The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application.
1933 -
1934 -|(% rowspan="2" %)F6.19|AO2 minimum input (Extended)|Factory default|(% colspan="2" %)0.00V
1935 -|Setting range|(% colspan="3" %)0.00V to F6.21
1936 -|(% rowspan="2" %)F6.20|AO2 minimum Input mapping Settings (Extended)|(% colspan="2" %)Factory default|0.0%
1937 -|Setting range|(% colspan="3" %)0.0% to +100.0%
1938 -|(% rowspan="2" %)F6.21|AO2 maximum input (Extended)|(% colspan="2" %)Factory default|10.00V
1939 -|Setting range|(% colspan="3" %)F6.19 to +10.00V
1940 -|(% rowspan="2" %)F6.22|AO2 maximum input corresponding Settings (Extended)|(% colspan="2" %)Factory default|100.0%
1941 -|Setting range|(% colspan="3" %)0.0% to +100.0%
1942 -|(% rowspan="2" %)F6.23|FMR turn-on delay time|(% colspan="2" %)Factory default|0.0s
1943 -|Setting range|(% colspan="3" %)0.0s to 3600.0s
1944 -
1945 -The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application.
1946 -
1947 -
1948 -|(% rowspan="2" %)F6.24|Relay 1 on delay time|Factory default|0.0s
1949 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1950 -|(% rowspan="2" %)F6.25|Relay 2 turn-on delay time (Extended)|Factory default|0.0s
1951 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1952 -|(% rowspan="2" %)F6.26|VDO connection delay|Factory default|0.0s
1953 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1954 -|(% rowspan="2" %)F6.27|FMR disconnect delay time|Factory default|0.0s
1955 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1956 -|(% rowspan="2" %)F6.28|Relay 1 disconnect delay time|Factory default|0.0s
1957 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1958 -|(% rowspan="2" %)F6.29|Relay 2 disconnect delay time (Extended)|Factory default|0.0s
1959 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1960 -|(% rowspan="2" %)F6.30|VDO1 disconnect delay|Factory default|0.0s
1961 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1962 -
1963 -Set the delay time of output terminals FMR, relay 1, relay 2, VDO from the change of state to the change of output.
1964 -
1965 -|(% rowspan="2" %)F6.31|Output terminal valid status Select 1|Factory default|000
1966 -|Setting range|(% colspan="2" %)(((
1967 -0: Positive logic
1968 -
1969 -1: Reverse logic
1970 -
1971 -Units place: FDOR
1972 -
1973 -Tens place: RL1
1974 -
1975 -Hundreds place: RL2 (Extended)
1976 -
1977 -Thousands place: -
1978 -)))
1979 -|(% rowspan="2" %)F6.32|Virtual output terminal valid status Select 2|Factory default|000
1980 -|Setting range|(% colspan="2" %)(((
1981 -0: Positive logic
1982 -
1983 -1: Reverse logic
1984 -
1985 -Units place: VDO1
1986 -
1987 -Tens place: VDO2
1988 -
1989 -Hundreds place: VDO3
1990 -
1991 -Thousands place: -
1992 -)))
1993 -
1994 -Define the positive and negative logic of the output terminals FMR, relay 1, relay 2.
1995 -
1996 -Positive logic: the digital output terminal and the corresponding public end are connected effectively, and the disconnect is invalid;
1997 -
1998 -Inverse logic: The digital output terminal is not connected to the corresponding public end, and the disconnect is valid.
1999 -
2000 -|(% rowspan="2" %)F6.33|User-defined output selection (EX) 1|Factory default|0
2001 -|Setting range|(% colspan="2" %)(((
2002 -0: The running frequency
2003 -
2004 -1: Set the frequency
2005 -
2006 -2: Bus voltage
2007 -
2008 -3: Output voltage
2009 -
2010 -4: Output current
2011 -
2012 -5: Output power
2013 -
2014 -6: Output torque
2015 -
2016 -7-8: Reserved
2017 -
2018 -9: AI1 input
2019 -
2020 -10: AI2 input
2021 -
2022 -11: AI3 input (Extended)
2023 -)))
2024 -
2025 -This parameter is used to select a reference variable for the custom output. Take the selected variable EX as the operation comparison object.
2026 -
2027 -
2028 -|(% rowspan="2" %)F6.34|The comparison method chosen by the user 1|Factory default|0
2029 -|Setting range|(% colspan="2" %)(((
2030 -Units: Compare test methods
2031 -
2032 -0: Equal to (EX == X1)
2033 -
2034 -1: The value is greater than or equal to
2035 -
2036 -2: Less than or equal to
2037 -
2038 -3: Interval comparison (X1 ≤ EX ≤ X2)
2039 -
2040 -4: Bit test (EX & X1=X2)
2041 -
2042 -Tens: output mode
2043 -
2044 -0: False value output
2045 -
2046 -1: Truth output
2047 -)))
2048 -
2049 -The units bit selects the comparison test mode. The variables selected by F6.37 are used as comparison test objects, and the comparison and test values are set by F6.40-F6.41.
2050 -
2051 -The way the tens select the output. False value output is output if the condition is not met, and no output if it is met; Truth output is output only when the condition is met, and no output if the condition is not met.
2052 -
2053 -|(% rowspan="2" %)F6.35|User-defined dead zone 1|Factory default|0
2054 -|Setting range|(% colspan="2" %)0 to 65535
2055 -
2056 -When the comparison test mode of F6.29 is set to greater than or equal to or less than or equal to, F6.30 is used to define the processing dead zone value centered on the comparison value X1. The processing dead zone has effect only on 1 and 2 of the comparison test mode of F6.29, and has no effect on 0, 3, and 4. For example, when F6.29 is set to 11, when EX is increased from 0 to greater than or equal to X1+F6.30, the output is valid; When EX is reduced to less than or equal to X1.F6.30, the output is invalid.
2057 -
2058 -|(% rowspan="2" %)F6.36|User-defined 2 outputs the comparison value X1|Factory default|0
2059 -|Setting range|(% colspan="2" %)0 to 65535
2060 -|(% rowspan="2" %)F6.37|User-defined 2 outputs the comparison value X2|Factory default|0
2061 -|Setting range|(% colspan="2" %)0 to 65535
2062 -|(% rowspan="2" %)F6.38|User-defined output selection (EX) 2|Factory default|0
2063 -|Setting range|(% colspan="2" %)(((
2064 -0: Running frequency
2065 -
2066 -1: Set the frequency
2067 -
2068 -2: Bus voltage
2069 -
2070 -3: Output voltage
2071 -
2072 -4: Output current
2073 -
2074 -5: Output power
2075 -
2076 -6: Output torque
2077 -
2078 -7-8: Reserved
2079 -
2080 -9: AI1 input
2081 -
2082 -10: AI2 input
2083 -
2084 -11: AI3 input(Expansion module)
2085 -)))
2086 -
2087 -These two parameters are used to set the comparison value of the custom output.
2088 -
2089 -Here is an example of a custom output:
2090 -
2091 -~1. When the set frequency is greater than or equal to 20.00HZ, the relay is closed;
2092 -
2093 -Set parameters as follows: F6.02 = 41, F6.28 = 1, F6.29 = 11, F6.30 = 0, F6.31 = 2000;
2094 -
2095 -2. When the bus voltage is less than or equal to 500.0V, the relay is closed; In order to avoid frequent operation of the relay when the detection voltage fluctuates 5.0V above and below 500.0V, it is required to process into a dead zone in the range of (500.0-5.0) to (500.0+5.0).
2096 -
2097 -Set parameters as follows: F6.02 = 41, F6.28 = 2, F6.29 = 01, F6.30 = 50, F6.31 = 5000;
2098 -
2099 -3. When the inverter is required to reverse, the relay is closed:
2100 -
2101 -Set parameters as follows: F6.02 = 41, F6.28 = 5, F6.29 = 14, F6.31 = 8, F6.32= 8;
2102 -
2103 -4. When AI1 input is required to be greater than 3.00V and less than or equal to 6.00V, the relay is closed:
2104 -
2105 -Set parameters as follows: F6.02 = 41, F6.28=13, F6.29=13, F6.31=300, F6.32=600; F6.33 to F6.37 is the same as F6.28 to F6.32.
2106 -
2107 -|(% rowspan="2" %)F6.39|The comparison method chosen by the user 2|Factory default|0
2108 -|Setting range|(% colspan="2" %)(((
2109 -Units: Compare test methods
2110 -
2111 -0: Equal to (EX == X1)
2112 -
2113 -1: The value is greater than or equal to
2114 -
2115 -2: Less than or equal to
2116 -
2117 -3: Interval comparison (X1 ≤ EX ≤ X2)
2118 -
2119 -4: Bit test (EX & X1=X2)
2120 -
2121 -Tens: output mode
2122 -
2123 -0: False value output
2124 -
2125 -1: Truth output
2126 -)))
2127 -|(% rowspan="2" %)F6.40|User-defined dead zone 2|Factory default|0
2128 -|Setting range|(% colspan="2" %)0 to 65535
2129 -|(% rowspan="2" %)F6.41|User-defined 2 outputs the comparison value X1|Factory default|0
2130 -|Setting range|(% colspan="2" %)0 to 65535
2131 -|(% rowspan="2" %)F6.42|User-defined 2 Output comparison value X2|Factory default|0
2132 -|Setting range|(% colspan="2" %)0 to 65535
2133 -
2134 -Second output. The parameter setting mode is the same as F6.33 to F6.37.
2135 -
2136 -
2137 -|(% rowspan="2" %)F6.43|Timer time unit|Factory default|0
2138 -|Setting range|(% colspan="2" %)(((
2139 -0: Second
2140 -
2141 -1: Minute
2142 -
2143 -2: Hour
2144 -)))
2145 -|(% rowspan="2" %)F6.44|Timer maximum|Factory default|0
2146 -|Setting range|(% colspan="2" %)0 to 65535 (No more when set to 65000)
2147 -|(% rowspan="2" %)F6.45|Timer set value|Factory default|0
2148 -|Setting range|(% colspan="2" %)0 to 65535
2149 -|(% rowspan="2" %)F6.46|Counter maximum|Factory default|0
2150 -|Setting range|(% colspan="2" %)0 to 65535
2151 -|(% rowspan="2" %)F6.47|Counter set value|Factory default|0
2152 -|Setting range|(% colspan="2" %)0 to 65535
2153 -
2154 -Set the timer time.
2155 -
2156 -
2157 -**F7 group keyboard with display**
2158 -
2159 -|(% rowspan="2" %)F7.00|LCD keyboard parameter copy|Factory default|0
2160 -|Setting range|(% colspan="2" %)(((
2161 -0: No operation is performed
2162 -
2163 -1: The function parameters of the machine are uploaded to the LCD keyboard
2164 -
2165 -2: LCD keyboard function parameters download to the machine
2166 -)))
2167 -
2168 -**Note: LCD is not available.**
2169 -
2170 -
2171 -|(% rowspan="2" %)F7.01|ENT key function selection|Factory default|0
2172 -|Setting range|(% colspan="2" %)(((
2173 -0: ENT is invalid
2174 -
2175 -1: Switch between the command channel of the operation panel and the remote command channel (the remote command channel includes communication and terminal control)
2176 -
2177 -2: Forward/reverse switching
2178 -
2179 -3: Forward JOG
2180 -
2181 -4: Reverse JOG
2182 -
2183 -5: Menu mode switch
2184 -
2185 -6: Reverse operation
2186 -)))
2187 -
2188 -The ENT key is multiplexed into a multi-function key on the level 0 interface. The function of ENT key on the keyboard can be defined by parameter setting. This key can be used to switch between shutdown and operation.
2189 -
2190 -0: This key has no function if it is set to 0.
2191 -
2192 -1: Switch between keyboard commands and remote operations. Switching from the current command source to keyboard control (local operation). If the current command source is keyboard control, this command does not take effect.
2193 -
2194 -2: Forward/reverse switching
2195 -
2196 -Use the ENT key on the keyboard to switch the direction of the frequency instruction. This parameter is valid only when the command channel on the panel is operated.
2197 -
2198 -3: Forward JOG
2199 -
2200 -The forward turning point (FJOG) is achieved by the ENT key on the keyboard.
2201 -
2202 -4: Reverse JOG
2203 -
2204 -Reversal dotting (RJOG) is achieved by the ENT key on the keyboard.
2205 -
2206 -Note: After setting this function, it is only effective in the 0-level display menu, and ENT key is the function of entering the lower-level menu/saving parameters in other interfaces.
2207 -
2208 -5: Menu mode switch
2209 -
2210 -Operating instructions: base for the initial menu, -C- for the debugging menu; ENT key to switch the menu, shift key to enter the corresponding menu; debugging menu displayed as CFxx.xx
2211 -
2212 -|(% rowspan="2" %)F7.02|Keyboard STOP key range|Factory default|0011
2213 -|Setting range|(% colspan="2" %)(((
2214 -LED units place: Terminal control selection
2215 -
2216 -0: The terminal command is invalid
2217 -
2218 -1: valid for the terminal command
2219 -
2220 -LED tens place: communication control selection
2221 -
2222 -0: The communication command is invalid
2223 -
2224 -1: Valid for communication commands
2225 -
2226 -LED hundreds place: reserved
2227 -
2228 -LED thousands place: reserved
2229 -)))
2230 -
2231 -**Special note:** When the STOP button communication control is valid, if the machine is started by using the communication command and the machine is stopped by using the STOP button, it can be started only after the STOP command is issued before the next communication start.
2232 -
2233 -|(% rowspan="2" %)F7.03|Keyboard run displays parameter 1|Factory default|3420
2234 -|Setting range|(% colspan="2" %)(((
2235 -LED units place: First group display
2236 -
2237 -0: Output frequency
2238 -
2239 -1: Given frequency
2240 -
2241 -2: Bus voltage
2242 -
2243 -3: Output voltage
2244 -
2245 -4: Output current
2246 -
2247 -5: Output power
2248 -
2249 -6: Output torque
2250 -
2251 -7: DI input status
2252 -
2253 -8: DO output status
2254 -
2255 -9: AI1 voltage
2256 -
2257 -A: AI2 voltage
2258 -
2259 -B: AI3 voltage (Expansion module)
2260 -
2261 -C: Reverse
2262 -
2263 -D: Reverse
2264 -
2265 -E: Motor speed
2266 -
2267 -F: PID setting
2268 -
2269 -LED tens place: Second group display
2270 -
2271 -LED hundreds place: Third group display
2272 -
2273 -LED thousands place: Fourth group display
2274 -)))
2275 -|(% rowspan="2" %)F7.04|Keyboard run displays parameter 2|Factory default|0000
2276 -|Setting range|(% colspan="2" %)(((
2277 -LED units place: First group display
2278 -
2279 -0: No displayed
2280 -
2281 -1: PID feedback
2282 -
2283 -2: PLC stage
2284 -
2285 -3:PULSE Indicates the input pulse frequency
2286 -
2287 -4: Feedback speed
2288 -
2289 -5: Reservations
2290 -
2291 -6: Reservations
2292 -
2293 -7: Reservations
2294 -
2295 -8: Reserve
2296 -
2297 -9: Current power-on time
2298 -
2299 -A: Current running time
2300 -
2301 -B: Reserved
2302 -
2303 -C: Communication setting
2304 -
2305 -D: Reservation
2306 -
2307 -E: Main frequency X is displayed
2308 -
2309 -F: Auxiliary frequency Y is displayed
2310 -
2311 -LED ten: second group display
2312 -
2313 -LED hundreds place: Third group display
2314 -
2315 -LED thousands place: Fourth group display
2316 -)))
2317 -|(% rowspan="2" %)F7.05|Keyboard stop displays parameters|Factory default|3421
2318 -|Setting range|(% colspan="2" %)(((
2319 -LED units place: First group display
2320 -
2321 -0: Output frequency
2322 -
2323 -1: Given frequency
2324 -
2325 -2: Bus voltage
2326 -
2327 -3: Output voltage
2328 -
2329 -4: Output current
2330 -
2331 -5: Output power
2332 -
2333 -6: Output torque
2334 -
2335 -7: DI input status
2336 -
2337 -8: DO output status
2338 -
2339 -9: AI1 voltage
2340 -
2341 -A: AI2 voltage
2342 -
2343 -B: AI3 voltage(Expansion module)
2344 -
2345 -C: Motor speed
2346 -
2347 -D: PID setting
2348 -
2349 -E: PID feedback
2350 -
2351 -F: PLC stage
2352 -
2353 -LED tens place: second group display
2354 -
2355 -LED hundreds place: Third group display
2356 -
2357 -LED thousands place: Fourth group display
2358 -)))
2359 -
2360 -Control four groups of display parameters. For example, if output frequency, bus voltage, output current, and output voltage need to be displayed during operation, set the corresponding value 3420 one by one in bits to kilos.
2361 -
2362 -
2363 -|(% rowspan="2" %)F7.06|Load speed display factor|Factory default|1.000
2364 -|Setting range|(% colspan="2" %)0.001 to 65.000
2365 -
2366 -Through this parameter, the output frequency of the inverter is corresponding to the load speed, load speed = output frequency /F2.04*F2.05*F7.06.
2367 -
2368 -|(% rowspan="2" %)F7.14|High cumulative power consumption|Factory default|
2369 -|Setting range|(% colspan="2" %)(((
2370 -Power consumption = F7.14*65535+F7.15
2371 -
2372 -Unit: kWh
2373 -)))
2374 -|(% rowspan="2" %)F7.15|Low cumulative power consumption|Factory default|
2375 -|Setting range|(% colspan="2" %)(((
2376 -Power consumption=F7.14*65535+F7.15
2377 -
2378 -Unit: kWh
2379 -)))
2380 -
2381 -When the inverter power is large, the 16-bit power consumption parameter will overflow quickly, so two parameters are used to represent the power consumption, that is, 32 digits.
2382 -
2383 -|(% rowspan="2" %)F7.16|Output power correction factor|Factory default|100.0%
2384 -|Setting range|(% colspan="2" %)0 to 100.0%
2385 -
2386 -Used to correct the actual output power of the motor.
2387 -
2388 -|(% rowspan="2" %)F7.17|Power display dimension selection|Factory default|1
2389 -|Setting range|(% colspan="2" %)(((
2390 -0 to Power display percentage ~(%)
2391 -
2392 -1 to Power display kilowatts (kW)
2393 -)))
2394 -
2395 -
2396 -
2397 -Used to select the dimension of power display D0.05, 0 is displayed in the ratio of output power to motor power, and 1 is displayed in KW.
2398 -
2399 -
2400 -**F8 group accessibility**
2401 -
2402 -|(% rowspan="2" %)F8.00|JOG running frequency|Factory default|2.00Hz
2403 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency F0.10
2404 -|(% rowspan="2" %)F8.01|JOG acceleration time|Factory default|20.0s
2405 -|Setting range|(% colspan="2" %)0.01s to 6500.0s
2406 -|(% rowspan="2" %)F8.02|JOG deceleration time|Factory default|20.0s
2407 -|Setting range|(% colspan="2" %)0.01s to 6500.0s
2408 -
2409 -Define the given frequency and acceleration/deceleration time of the inverter during jog. The jog process starts and stops according to start mode 0 (F1.00, direct start) and stop mode 0 (F1.10, decelerate to stop).
2410 -
2411 -Jog acceleration time refers to the time required for the inverter to accelerate from 0Hz to the maximum output frequency (F0.10).
2412 -
2413 -Jog deceleration time refers to the time required for the inverter to decelerate from the maximum output frequency (F0.10) to 0Hz..
2414 -
2415 -|(% rowspan="2" %)F8.09|Emergency stop deceleration time|Factory default|Model determination
2416 -|Setting range|(% colspan="2" %)0. 01s to 6500.0s
2417 -
2418 -The terminal is set to downtime in case of emergency stop.
2419 -
2420 -|(% rowspan="2" %)F8.10|Jump frequency 1|Factory default|0.00Hz
2421 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2422 -|(% rowspan="2" %)F8.11|Jump frequency 2|Factory default|0.00Hz
2423 -|Setting range|(% colspan="2" %)0.00 Hz to Maximum frequency
2424 -|(% rowspan="2" %)F8.12|Jump frequency amplitude|Factory default|0.01Hz
2425 -|Setting range|(% colspan="2" %)0.00 to Maximum frequency
2426 -
2427 -When the set frequency is within the jump frequency range, the actual running frequency will run at the jump frequency boundary closer to the set frequency. By setting the jump frequency, the VFD can avoid the mechanical resonance point of the load. The inverter can be configured with two jump frequency points. This function does not work if both jump frequencies are set to 0.
2428 -
2429 -[[image:1763107356713-939.png]]
2430 -
2431 -
2432 -Figure 9-8-1 Jump frequency diagram
2433 -
2434 -
2435 -|(% rowspan="2" %)F8.13|Reversible dead zone time|Factory default|0.0s
2436 -|Setting range|(% colspan="2" %)0.0 to 120.0s
2437 -
2438 -Set the transition time at the output zero frequency during the positive and negative transition of the inverter, as shown below:
2439 -
2440 -[[image:1763107356720-587.png]]
2441 -
2442 -
2443 -Figure 9-8-2 Reverse rotation dead zone time diagram
2444 -
2445 -
2446 -|(% rowspan="2" %)F8.14|The carrier frequency is adjusted with temperature|Factory default|1
2447 -|Setting range|(% colspan="2" %)(((
2448 -0: Temperature independent
2449 -
2450 -1:Temperature dependent, >75, 1.0Khz
2451 -)))
2452 -
2453 -Effective carrier frequency temperature adjustment means that the VFD can automatically adjust the carrier frequency according to its own temperature. Select this function to reduce the chances of VFD overheating alarm.
2454 -
2455 -|(% rowspan="2" %)F8.15|Terminal action is preferred|Factory default|1
2456 -|Setting range|(% colspan="2" %)(((
2457 -0: Invalid
2458 -
2459 -1: Valid
2460 -)))
2461 -
2462 -0: When the running command and the point command exist at the same time, the running command takes precedence.
2463 -
2464 -1: If the running command and the point-action command exist at the same time, the point-action command takes precedence.
2465 -
2466 -|(% rowspan="2" %)F8.16|Set the cumulative power-on arrival time|Factory default|0h
2467 -|Setting range|(% colspan="2" %)0h to 65000h
2468 -
2469 -Pre-set the power-on time of the inverter. When the cumulative power-on time (F7.13) reaches the set power-on time, set the DO output function, and the inverter multi-function digital DO output running time arrival signal.
2470 -
2471 -|(% rowspan="2" %)F8.17|Set the cumulative run arrival time|Factory default|65000h
2472 -|Setting range|(% colspan="2" %)0h to 65000h
2473 -
2474 -Pre-set the running time of the inverter. When the accumulated running time (F7.09) reaches this set running time, set the DO output function, the inverter multi-functional digital DO output running time arrival signal.
2475 -
2476 -|(% rowspan="2" %)F8.20|Arrival time of this run|Factory default|0
2477 -|Setting range|(% colspan="2" %)0 to 65000min
2478 -
2479 -Set the current running time, shutdown clear zero.
2480 -
2481 -|(% rowspan="2" %)F8.22|Frequency detection value (FDT1)|Factory default|50.00Hz
2482 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2483 -|(% rowspan="2" %)F8.23|Frequency Detection Lag value (FDT1)|Factory default|5.0%
2484 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT1 Electric level)
2485 -|(% rowspan="2" %)F8.24|Frequency detection value (FDT2)|Factory default|50.00Hz
2486 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2487 -|(% rowspan="2" %)F8.25|Frequency detection lag value (FDT2)|Factory default|5.0%
2488 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT2 Electric level)
2489 -
2490 -Set the detection value of the output frequency and the lag value of the output action release.
2491 -
2492 -[[image:1763107356721-853.png]]
2493 -
2494 -Figure 9-8-3 Schematic diagram of FDT1 level
2495 -
2496 -|(% rowspan="2" %)F8.26|Frequency reaches the detection width|Factory default|0.0%
2497 -|Setting range|(% colspan="2" %)0.00 to 100% Maximum frequency
2498 -
2499 -When the output frequency of the inverter reaches the set frequency value, this function can adjust its detection amplitude.
2500 -
2501 -As shown below:
2502 -
2503 -[[image:1763107356724-721.png]]
2504 -
2505 -Figure 9-8-4 Schematic diagram of frequency arrival detection amplitude
2506 -
2507 -|(% rowspan="2" %)F8.27|Arbitrary reach frequency detection value 1|Factory default|50.00Hz
2508 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2509 -|(% rowspan="2" %)F8.28|Arbitrary arrival frequency detection amplitude 1|Factory default|0.0%
2510 -|Setting range|(% colspan="2" %)0.0% to 100.0% (Maximum frequency)
2511 -|(% rowspan="2" %)F8.29|Arbitrary reach frequency detection value 2|Factory default|50.00Hz
2512 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2513 -|(% rowspan="2" %)F8.30|Arbitrary arrival frequency detection amplitude 2|Factory default|0.0%
2514 -|Setting range|(% colspan="2" %)0.0% to 100.0% (Maximum frequency)
2515 -
2516 -
2517 -
2518 -When the output frequency of the inverter reaches the positive and negative detection amplitude of the frequency detection value 1 and 2, the output pulse signal.
2519 -
2520 -As shown below:
2521 -
2522 -[[image:1763107356727-432.png]]
2523 -
2524 -Figure 9-8-5 Schematic diagram of detection of arbitrary arrival frequency
2525 -
2526 -
2527 -|(% rowspan="2" %)F8.31|Arbitrary arrival current 1|Factory default|100.0%
2528 -|Setting range|(% colspan="2" %)0.0%-300.0% (Rated current of motor)
2529 -|(% rowspan="2" %)F8.32|Arbitrary arrival current 1 width|Factory default|0.0%
2530 -|Setting range|(% colspan="2" %)0.0%-300.0% (Rated current of motor)
2531 -|(% rowspan="2" %)F8.33|Arbitrary arrival current 2|Factory default|100.0%
2532 -|Setting range|(% colspan="2" %)0.0% to 300.0%(Rated current of motor)
2533 -|(% rowspan="2" %)F8.34|Arbitrary arrival current 2 width|Factory default|0.0%
2534 -|Setting range|(% colspan="2" %)0.0% to 300.0%(Rated current of motor)
2535 -
2536 -
2537 -
2538 -When the output current of the inverter reaches any positive or negative detection width of current 1 and 2, output pulse signal.
2539 -
2540 -As shown below:
2541 -
2542 -
2543 -[[image:1763107356731-567.png]]
2544 -
2545 -Figure. 9-8-6 Schematic diagram of detection of arbitrary arrival frequency
2546 -
2547 -|(% rowspan="2" %)F8.35|Zero current detection value|Factory default|5.0%
2548 -|Setting range|(% colspan="2" %)0.0% to 300.0% (Rated current of motor)
2549 -|(% rowspan="2" %)F8.36|Zero current detection delay time|Factory default|0s
2550 -|Setting range|(% colspan="2" %)0 to 600.00s
2551 -
2552 -Figure 9-8-7 Schematic diagram of zero current detection
2553 -
2554 -When the output current of the inverter is less than or equal to the zero current detection level and the duration exceeds the zero current detection delay time, the output pulse
2555 -
2556 -Rush the signal. As shown below:
2557 -
2558 -
2559 -|
2560 -| |[[image:1763107356732-988.png]]
2561 -
2562 -
2563 -
2564 -|(% rowspan="2" %)F8.37|Software overflow point (DO output)|Factory default|200.0%
2565 -|Setting range|(% colspan="2" %)0.0% to 300.0% (Rated current of VFD)
2566 -|(% rowspan="2" %)F8.38|Software over current detection delay time|Factory default|0s
2567 -|Setting range|(% colspan="2" %)0 to 600.00s
2568 -
2569 -
2570 -
2571 -When the output current of the inverter is greater than or equal to the software over current point and the duration exceeds the software over current point detection delay time, the output pulse
2572 -
2573 -Rush the signal. As shown below:
2574 -
2575 -
2576 -|
2577 -| |[[image:1763107356734-922.png]]
2578 -
2579 -Figure 9-8-8 Schematic diagram of software overflow point detection
2580 -
2581 -
2582 -**F9 group process control PID function**
2583 -
2584 -PID control is a common method used for process control. By proportional, integral and differential operations on the difference between the feedback signal of the controlled quantity and the target quantity signal, the output frequency of the inverter is adjusted to form a negative feedback system, so that the controlled quantity is stable on the target quantity. Suitable for flow control, pressure control, temperature control and other process control. The basic control block diagram is as follows:
2585 -
2586 -
2587 -[[image:1763107356736-468.png]]
2588 -
2589 -Figure 9-9-1 Process PID schematic diagram
2590 -
2591 -|(% rowspan="2" %)F9.00|PID given source|Factory default|0
2592 -|Setting range|(% colspan="2" %)(((
2593 -0: Keyboard number PID is set to F9.01
2594 -
2595 -1: AI1
2596 -
2597 -2: AI2
2598 -
2599 -3: Reservations
2600 -
2601 -4: Set the terminal PULSE
2602 -
2603 -5: Communication given
2604 -
2605 -6: Multi-speed set
2606 -
2607 -7: Keyboard potentiometer set
2608 -)))
2609 -
2610 -When the frequency source is selected PID, that is, F0.03 or F0.04 is selected 8, this set of functions works. (See function code F0.03-F0.04.) This parameter determines the target amount of the process PID for a given channel. The set target quantity of process PID is relative value, and 100% of the set value corresponds to 100% of the feedback signal of the controlled system. The range of the PID (F9.04) is not required, because the system calculates relative values (0 to 100%) regardless of the range set. However, if the PID range is set, the actual value of the PID given and feedback corresponding to the signal can be visually observed through the keyboard display parameters.
2611 -
2612 -|(% rowspan="2" %)F9.01|PID Value setting|Factory default|50.0%
2613 -|Setting range|(% colspan="2" %)0.00 to 100.0%
2614 -
2615 -When F9.00=0 is selected, the target source is the keyboard given. This parameter needs to be set. The reference value of this parameter is the feedback amount of the system.
2616 -
2617 -
2618 -|(% rowspan="2" %)F9.02|PID feedback source|Factory default|0
2619 -|Setting range|(% colspan="2" %)(((
2620 -0: AI1
2621 -
2622 -1: AI2
2623 -
2624 -2: Reservations
2625 -
2626 -3: AI1 to AI2
2627 -
2628 -4: Set the terminal PULSE
2629 -
2630 -5: Communication given
2631 -
2632 -6: AI1+AI2
2633 -
2634 -7: MAX(|AI1|, |AI2|)
2635 -
2636 -8: MIN(|AI1|, |AI2|)
2637 -
2638 -9: Keyboard potentiometer feedback
2639 -)))
2640 -
2641 -This parameter is used to select the PID feedback channel.
2642 -
2643 -
2644 -
2645 -
2646 -
2647 -
2648 -
2649 -
2650 -
2651 -|(% rowspan="2" %)F9.03|PID control characteristic|Factory default|0
2652 -|Setting range|(% colspan="2" %)(((
2653 -LED ones digit: Feedback feature selection
2654 -
2655 -0: Positive action
2656 -
2657 -1: Negative action
2658 -
2659 -LED tens place: PID adjustment direction selection
2660 -
2661 -0: Reverse prohibition
2662 -
2663 -1: Reverse enable
2664 -
2665 -LED hundreds place: Align selection
2666 -
2667 -0: Non-center alignment
2668 -
2669 -1: Center align
2670 -
2671 -LED thousands place: reserved
2672 -)))
2673 -
2674 -Feedback feature selection:
2675 -
2676 -Positive effect: When the feedback signal is less than the given PID, the output frequency of the inverter is required to rise in order to make the PID balance. Such as winding tension PID control.
2677 -
2678 -Reverse effect: When the feedback signal is less than the feed time of the PID, the output frequency of the inverter is required to decrease in order to achieve balance of the PID. Such as unwinding tension PID control.
2679 -
2680 -The effect of this function is negatively affected by the direction of the terminal function 35: PID.
2681 -
2682 -Adjustment direction selection:
2683 -
2684 -Reverse prohibition: When the output frequency is calculated to be negative, the inverter outputs 0 Hz.
2685 -
2686 -Reverse allowed: the inverter output changes direction and the motor reverses.
2687 -
2688 -Align selection:
2689 -
2690 -When the PID set point is not at the center point of 50%, the difference between the PID set point and the PID feedback value, that is, the error range, is asymmetrical.
2691 -
2692 -Off-center alignment: Errors are not corrected.
2693 -
2694 -Center alignment: Error correction.
2695 -
2696 -|(% rowspan="2" %)F9.04|PID given feedback range|Factory default|100.0
2697 -|Setting range|(% colspan="2" %)0 to 100.0
2698 -|(% rowspan="2" %)F9.05|Proportional gain P1|Factory default|20.00
2699 -|Setting range|(% colspan="2" %)0.00 to 1000.00
2700 -|(% rowspan="2" %)F9.06|Integration time I1|Factory default|2.00s
2701 -|Setting range|(% colspan="2" %)0.00 to 10.00s
2702 -|(% rowspan="2" %)F9.07|D1derivative time D1|Factory default|0.00s
2703 -|Setting range|(% colspan="2" %)0.00 to 10.00s
2704 -
2705 -Proportional gain P1: Determines the adjustment intensity of the entire PID regulator, the greater the P, the greater the adjustment intensity. The parameter 100 indicates that when the deviation between the PID feedback quantity and the feed quantity is 100%, the PID: regulator's adjustment amplitude to the output frequency instruction is Maximum frequency (ignoring the integral and differential effects).
2706 -
2707 -Integration time I1: determines how quickly the PID controller adjusts the amount of PID feedback and the deviation of the given quantity. Integration time refers to when the deviation of PID feedback quantity and feed quantity is 100%, the integration regulator (ignoring proportional action and differential action) is continuously adjusted through the time, and the adjustment amount reaches the Maximum frequency (F0.10). The shorter the integration time, the greater the adjustment intensity.
2708 -
2709 -Differential time D1: Determines the intensity with which the PID regulator adjusts the amount of PID feedback and the rate of change of the given amount of deviation. The differential time means that if the feedback quantity changes 100% in this time, the adjustment amount of the differential regulator is Maximum frequency (F0.10) (ignoring the proportional action and integral action). The longer the differential time, the greater the adjustment intensity.
2710 -
2711 -|(% rowspan="2" %)F9.08|Reverse cut-off frequency|Factory default|0.00Hz
2712 -|Setting range|(% colspan="2" %)0.00 to Maximum frequency F0.10
2713 -|(% rowspan="2" %)F9.09|PID deviation limit|Factory default|0.0%
2714 -|Setting range|(% colspan="2" %)0. 0% to 100.0%
2715 -
2716 -
2717 -
2718 -Deviation limit: When the PID feedback deviation is within this range, the PID stops adjusting.
2719 -
2720 -|(% rowspan="2" %)F9.10|PID differential limiting|Factory default|0.10%
2721 -|Setting range|(% colspan="2" %)0.00% to 100.00%
2722 -|(% rowspan="2" %)F9.11|PID given change time|Factory default|0.00s
2723 -|Setting range|(% colspan="2" %)0.00s to 100.00s
2724 -
2725 -
2726 -
2727 -The given PID change time refers to the time required for the actual PID value to change from 0.0% to 100.0%.
2728 -
2729 -When the PID set changes, the actual value of the PID set does not follow the immediate response. And according to the given change time linear change, prevent a given mutation.
2730 -
2731 -|(% rowspan="2" %)F9.12|PID feedback filtering time|Factory default|0.00s
2732 -|Setting range|(% colspan="2" %)0.00s to 60.00s
2733 -|(% rowspan="2" %)F9.13|PID output filtering time|Factory default|0.00s
2734 -|Setting range|(% colspan="2" %)0.00s to 60.00s
2735 -
2736 -
2737 -
2738 -The PID feedback and output values are filtered to eliminate abrupt changes.
2739 -
2740 -
2741 -|(% rowspan="2" %)F9.14|Proportional gain P2|Factory default|20.0
2742 -|Setting range|(% colspan="2" %)0.0 to 100.0
2743 -|(% rowspan="2" %)F9.15|Integration time I2|Factory default|2.00s
2744 -|Setting range|(% colspan="2" %)0.01s to 10.00s
2745 -|(% rowspan="2" %)F9.16|Differential time D2|Factory default|0.000s
2746 -|Setting range|(% colspan="2" %)0.00 to 10.000
2747 -
2748 -
2749 -
2750 -The setting is similar to F9.05, F9.06, and F9.07. For details about how to change the PID parameters, see F9.18.
2751 -
2752 -|(% rowspan="2" %)F9.17|PID parameter switching condition|Factory default|0
2753 -|Setting range|(% colspan="2" %)(((
2754 -0: No switching
2755 -
2756 -1: Terminal switch
2757 -
2758 -2: Automatically switch according to deviation
2759 -)))
2760 -|(% rowspan="2" %)F9.18|PID parameter switching deviation 1|Factory default|20.0%
2761 -|Setting range|(% colspan="2" %)0.0% to F9.19
2762 -|(% rowspan="2" %)F9.19|PID parameter switching deviation 2|Factory default|80.0%
2763 -|Setting range|(% colspan="2" %)F9.18 to 100.0%
2764 -
2765 -In some applications, a single set of PID parameters may not be sufficient for the entire operation. Multiple groups of PID parameters may need to be switched.
2766 -
2767 -0: No switching, and the PID parameter is constant as parameter group 1.
2768 -
2769 -1: Terminal switch, If the function of the multi-function terminal is set to 43: PID parameter switching terminal and the terminal is valid, select parameter group 2. Otherwise, select parameter group 1.
2770 -
2771 -2: Automatic switching according to the deviation. When the deviation between the given and feedback is less than PID parameter switching deviation 1 (F9.19), F9.05, F9.06 and F9.07 are used as PID adjustment parameters. When the deviation between given and feedback is greater than PID switching deviation 2 (F9.20), F9.15, F9.16 and F9.17 are used as PID adjustment parameters. The PID parameters in the deviation section between switching deviation 1 and switching deviation 2 are linearly switched between the two groups of PID parameters.
2772 -
2773 -|(% rowspan="2" %)F9.20|PID initial frequency value|Factory default|0%
2774 -|Setting range|(% colspan="2" %)0.0% to 100.0%
2775 -|(% rowspan="2" %)F9.21|PID initial retention time|Factory default|0.0s
2776 -|Setting range|(% colspan="2" %)0.00s to 650.00s
2777 -
2778 -During PID operation, the inverter first sets the output operation with the initial PID value (F9.20) and the duration is F9.21 (PID initial value holding time), and then starts the normal PID adjustment.
2779 -
2780 -
2781 -|(% rowspan="2" %)F9.23|Feedback wire break action selection|Factory default|0
2782 -|Setting range|(% colspan="2" %)(((
2783 -0: PID continues to run and no fault is reported
2784 -
2785 -1: Stop and report fault (manual reset)
2786 -
2787 -2: Continue PID operation, output alarm signal
2788 -
2789 -3: Run at the current frequency, output alarm signal
2790 -
2791 -4: Stop and report fault (automatic reset)
2792 -)))
2793 -|(% rowspan="2" %)F9.24|Wire break alarm upper limit|Factory default|100.0%
2794 -|Setting range|(% colspan="2" %)F9.25 to 100.0%
2795 -|(% rowspan="2" %)F9.25|Line break alarm lower limit|Factory default|0.0%
2796 -|Setting range|(% colspan="2" %)0 to F9.24%
2797 -|(% rowspan="2" %)F9.26|Feedback break detection time|Factory default|0.0s
2798 -|Setting range|(% colspan="2" %)0.0s to 120.0s
2799 -
2800 -
2801 -
2802 -3 The upper limit (F9.24) duration reaches F9.26 (feedback loss detection time), the inverter reports a fault and runs according to F9.29 setting.
2803 -
2804 -|(% rowspan="2" %)F9.27|PID stop operation|Factory default|0
2805 -|Setting range|(% colspan="2" %)(((
2806 -0: Disable calculation on shutdown​​
2807 -
2808 -1: Enable calculation on shutdown
2809 -)))
2810 -|(% rowspan="2" %)F9.28|PID function selection|Factory default|0
2811 -|Setting range|(% colspan="2" %)(((
2812 -0: Normal PID
2813 -
2814 -1: Sleep PID
2815 -)))
2816 -
2817 -0: The inverter runs with normal PID control, and the sleep function is invalid.
2818 -
2819 -1: The inverter runs with sleep PID control, and the sleep function is enabled.
2820 -
2821 -|(% rowspan="2" %)F9.29|PID sleep threshold|Factory default|60.0%
2822 -|Setting range|(% colspan="2" %)0.0% to 100.0%
2823 -|(% rowspan="2" %)F9.30|PID sleep delay|Factory default|3.0s
2824 -|Setting range|(% colspan="2" %)0.0 to 3600.0s
2825 -|(% rowspan="2" %)F9.31|PID wake-up threshold|Factory default|20.0%
2826 -|Setting range|(% colspan="2" %)0.0% to 100.0%
2827 -|(% rowspan="2" %)F9.32|PID wake up delay|Factory default|3.0s
2828 -|Setting range|(% colspan="2" %)0.0 to 3600.0s
2829 -
2830 -When selecting the sleep PID, if the feedback is higher than the sleep threshold set by F9.29 and the running frequency is less than or equal to the sleep frequency set by F9.33, the VFD starts the sleep timing. After the sleep delay time set by F9.30, if the feedback quantity is higher than the set quantity set by F9.29 and the running frequency is less than or equal to the sleep frequency set by F9.33, Then the PID stops running and the inverter enters sleep state. If the feedback is lower than the setting of F9.31 wake-up threshold, the VFD starts the wake-up timing. After the time set by F9.32 wake-up delay, if the feedback is still lower than the setting of F9.31 wake-up threshold, the wake-up is successful and PID control is performed. Refer to Figure 9-9-2 below to understand the above parameter relationships.
2831 -
2832 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml14320\wps10.png]]
2833 -
2834 -Figure 9-9-2 Schematic diagram of PID sleep and wake time sequence
2835 -
2836 -
2837 -|(% rowspan="2" %)F9.33|Dormancy detection frequency|Factory default|25.00Hz
2838 -|Setting range|(% colspan="2" %)0 to Upper limit frequency F0.12
2839 -|(% rowspan="2" %)F9.34|Minimum output|Factory default|0
2840 -|Setting range|(% colspan="2" %)(((
2841 -0: F0.14 (Lower limit frequency)
2842 -
2843 -1: 0Hz
2844 -)))
2845 -
2846 -Sleep detection frequency: Frequency at which the system determines whether the sleep condition is met.
2847 -
2848 -|(% rowspan="2" %)F9.35|Maximum forward deviation of two outputs|Factory default|1.00%.
2849 -|Setting range|(% colspan="2" %)0.00% to 100.00%
2850 -|(% rowspan="2" %)F9.36|Maximum reverse deviation of two outputs|Factory default|1.00%
2851 -|Setting range|(% colspan="2" %)0.00% to 100.00%
2852 -
2853 -
2854 -
2855 -This function code is used to limit the difference between the PID output two beats (2ms/ beat), thereby suppress the PID output changes too fast. F9.23 and F9.24 correspond to the maximum output deviation for forward and reverse rotation respectively.
2856 -
2857 -|(% rowspan="2" %)F9.38|PID preset switchover condition selection|Factory default|0
2858 -|Setting range|(% colspan="2" %)(((
2859 -0: Time
2860 -
2861 -1: Switch according to AI1 feedback value
2862 -)))
2863 -|(% rowspan="2" %)F9.39|PID AI feedback switching minimum|Factory default|45.0%
2864 -|Setting range|(% colspan="2" %)0.0 to F8.18
2865 -|(% rowspan="2" %)F9.40|PID AI feedback switching maximum|Factory default|55.0%
2866 -|Setting range|(% colspan="2" %)F8.17 to 100.0%
2867 -
2868 -PID preset switching condition selection: Switch from preset output frequency (F9.20) to PID given.
2869 -
2870 -0: Switch according to the running time set by F9.21.
2871 -
2872 -1: Switch when the feedback value is greater than or equal to F9.23 and less than or equal to F9.24.
2873 -
2874 -**FA group failure and protection**
2875 -
2876 -|(% rowspan="2" %)FA.00|Motor overload protection selection|Factory default|1
2877 -|Setting range|(% colspan="2" %)(((
2878 -0: Off
2879 -
2880 -1: On
2881 -)))
2882 -
2883 -Select 0: The inverter has no overload protection for the load motor, and the relay is heated in front of the motor.
2884 -
2885 -Select 1: At this time, the inverter has overload protection function for the motor. See FA.01 for protection values.
2886 -
2887 -|(% rowspan="2" %)FA.01|Motor overload protection factor|Factory default|100.0%
2888 -|Setting range|(% colspan="2" %)0.0 to 250.0%
2889 -
2890 -Motor overload protection is inverse time curve; 220% x (FA.01) x rated motor current for 1 minute, 150% x (FA.01) x rated motor current for 60 minutes.
2891 -
2892 -|(% rowspan="2" %)FA.02|Motor overload warning factor|Factory default|80.0%
2893 -|Setting range|(% colspan="2" %)20.0 to 250.0%
2894 -
2895 -The reference for this value is the overload current of the motor. When the inverter detects that the output current reaches (FA.02) x the motor overload current and continues for the specified time in the inverse time curve, the forecast alarm is output from the DO or relay.
2896 -
2897 -|(% rowspan="2" %)FA.03|Over voltage stall/over loss rate control options|Factory default|1111
2898 -|Setting range|(% colspan="2" %)(((
2899 -0: Off
2900 -
2901 -1: On
2902 -
2903 -LED units place: The over voltage suppression is enabled
2904 -
2905 -Tens place: over current suppression is enabled
2906 -
2907 -LED hundreds place: Determine whether the brake resistance is connected
2908 -
2909 -LED thousands place: Overflow suppression rapid frequency rise
2910 -)))
2911 -
2912 -LED units place: Over voltage suppression enabled
2913 -
2914 -0: Disable over voltage suppression. 1: Enable overvoltage suppression. When a braking resistor is connected, set this bit to 0.
2915 -
2916 -LED tens place: Enable over current suppression
2917 -
2918 -0: Disable over current suppression. 1: Enable the over current suppression function.
2919 -
2920 -LED hundreds place: Determine brake resistance access
2921 -
2922 -When the over voltage suppression is turned on, it may affect the energy consumption braking action. This bit is used to automatically determine whether the resistance is connected. When the brake resistance is connected, the over voltage suppression will automatically decrease.
2923 -
2924 -LED thousands place: Overflow suppression rapid frequency rise
2925 -
2926 -This bit is used to set how the frequency increases when over current suppression is withdrawn. When set to 0, the frequency is accelerated according to the acceleration time; When set to 1, the frequency is controlled by the current, so as the current decreases, the frequency will rise rapidly.
2927 -
2928 -
2929 -|(% rowspan="2" %)FA.04|Over pressure suppression point|Factory default|Model-based setting
2930 -|Setting range|(% colspan="2" %)110% to 150%
2931 -|(% rowspan="2" %)FA.05|Udc control voltage loop gain|Factory default|2.00
2932 -|Setting range|(% colspan="2" %)0.00 to 50.00
2933 -|(% rowspan="2" %)FA.06|Udc control current loop gain|Factory default|2.00
2934 -|Setting range|(% colspan="2" %)0.00 to 50.00
2935 -
2936 -When the bus voltage exceeds FA.04× rated bus voltage during the operation of the VFD, the VFD will automatically adjust the operating frequency to suppress the bus voltage rise, so as to ensure that the VFD will not cause over voltage protection due to the high bus voltage. FA.05 and FA.06 are the voltage loop gain and current loop gain when the bus voltage is regulated, respectively. Instantaneous stop of the voltage loop and current loop gain is also the reference number.
2937 -
2938 -
2939 -|(% rowspan="2" %)FA.07|Over current suppression point|Factory default|150%
2940 -|Setting range|(% colspan="2" %)50% to 200%
2941 -|(% rowspan="2" %)FA.08|Over current suppression gain|Factory default|2.00
2942 -|Setting range|(% colspan="2" %)0.00 to 50.00
2943 -|(% rowspan="2" %)FA.09|Over current suppression integral|Factory default|4.00
2944 -|Setting range|(% colspan="2" %)0.00 to 50.00
2945 -
2946 -
2947 -
2948 -When controlling the motor, the motor current increases with the increase of load, and the over current suppression gain function limits the maximum current of the motor. When the current reaches the rated current of FA.07* inverter, the output frequency automatically decreases to limit the motor current not exceeding the current set by FA.07; FA.08 and FA.09 are over current suppression controller parameters. Adjusting these two parameters can improve and optimize the over current suppression effect.
2949 -
2950 -|(% rowspan="2" %)FA.10|Power-on short-circuit detection to the ground|Factory default|1
2951 -|Setting range|(% colspan="2" %)(((
2952 -0: Invalid
2953 -
2954 -1: Valid
2955 -)))
2956 -
2957 -The inverter can be selected to detect whether the motor has a ground protection short circuit fault when it is powered on. If this function is effective, the inverter is output for a short time at the moment of power-on.
2958 -
2959 -|(% rowspan="2" %)FA.11|Input phase loss protection|Factory default|1
2960 -|Setting range|(% colspan="2" %)(((
2961 -0: Off
2962 -
2963 -1: On
2964 -)))
2965 -
2966 -Select whether to protect against input phase loss.
2967 -
2968 -|(% rowspan="2" %)FA.12|Output phase loss protection|Factory default|1
2969 -|Setting range|(% colspan="2" %)(((
2970 -0: Off
2971 -
2972 -1: On
2973 -)))
2974 -
2975 -Select whether to protect output phase loss.
2976 -
2977 -|(% rowspan="2" %)FA.13|Input phase loss protection software detection level|Factory default|15.0%
2978 -|Setting range|(% colspan="2" %)0.0 to 999.9%
2979 -
2980 -The input missing phase is judged by calculating the fluctuation of bus voltage. This parameter is used to set the threshold of bus voltage fluctuation when the input phase is out. Turning down can increase the sensitive zero of the input phase out, and turning up can reduce the probability of false positive of the input phase out.
2981 -
2982 -|(% rowspan="2" %)FA.14|PWM Parameter setting|Factory default|0010
2983 -|Setting range|(% colspan="2" %)(((
2984 -LED units place: Turn on voltage prediction compensation
2985 -
2986 -LED tens place: PWM update mode
2987 -
2988 -0: Single sample update
2989 -
2990 -1: Double sample and double update
2991 -
2992 -LED hundreds place: random carrier mode
2993 -
2994 -0: Random carrier
2995 -
2996 -1: Random 0 vector
2997 -)))
2998 -
2999 -LED units place: Turn on voltage prediction compensation
3000 -
3001 -1: Turn on the bus voltage prediction compensation.
3002 -
3003 -LED tens place: PWM update mode.
3004 -
3005 -0: single sample update. 1: Double sample and double update.
3006 -
3007 -LED hundreds place: random carrier mode.
3008 -
3009 -0: Random PWM carrier frequency. 1: Random 0 vector.
3010 -
3011 -|(% rowspan="2" %)FA.15|Hardware current and voltage protection|Factory default|0011
3012 -|Setting range|(% colspan="2" %)(((
3013 -LED units place: Current limiting (CBC)
3014 -
3015 -0: Off
3016 -
3017 -1: On
3018 -
3019 -LED tens place: -
3020 -
3021 -LED hundreds place: FAU filtering time
3022 -
3023 -1 to F
3024 -
3025 -LED thousandsd place: TZ filtering time
3026 -
3027 -1 to F
3028 -)))
3029 -
3030 -LED units place: Hardware current limiting (CBC).
3031 -
3032 -0: Disable CBC current limiting ​ 1: Enable CBC current limiting
3033 -
3034 -LED tens place: reserved.
3035 -
3036 -LED hundreds place: FAU filtering time.
3037 -
3038 -The FAU signal is the fault signal of the power device. This parameter is used to set the filtering time of the FAU signal.
3039 -
3040 -LED thousands place: TZ filtering time.
3041 -
3042 -The TZ signal is an over current signal. This parameter is used to set the filtering time of the TZ signal.
3043 -
3044 -|(% rowspan="2" %)FA.16|CBC protection point|Factory default|200%
3045 -|Setting range|(% colspan="2" %)100 to 220%
3046 -|(% rowspan="2" %)FA.17|CBC overload protection time|Factory default|500ms
3047 -|Setting range|(% colspan="2" %)1 to 5000ms
3048 -
3049 -
3050 -
3051 -When the motor current is higher than the rated current of FA.16*VFD, the per-wave current limiting starts. If the per-wave current limiting duration exceeds the time set in FA.17, the VFD reports Err. This parameter is used to set the per-wave current limiting current and fault response time.
3052 -
3053 -|(% rowspan="2" %)FA.18|Under voltage point setting|Factory default|100.0%
3054 -|Setting range|(% colspan="2" %)100 to 220%
3055 -
3056 -Adjusting this parameter can adjust the voltage point of the VFD reporting the under voltage fault (Err09), 100.0% corresponds to 350V.
3057 -
3058 -|(% rowspan="2" %)FA.20|Times of self-recovery|Factory default|0
3059 -|Setting range|(% colspan="2" %)0 to 5
3060 -
3061 -When the inverter selects fault automatic reset, it is used to set the number of times that can be automatically reset. If the value exceeds this value, the inverter is faulty and waiting for repair.
3062 -
3063 -|(% rowspan="2" %)FA.21|Interval for fault self-recovery|Factory default|1.0s
3064 -|Setting range|(% colspan="2" %)0.1 to 100.0ms
3065 -
3066 -VFD from fault alarm to automatic reset fault waiting time.
3067 -
3068 -
3069 -|(% rowspan="2" %)FA.22|Instant stop non-stop function selection|Factory default|0000
3070 -|Setting range|(% colspan="2" %)(((
3071 -One place: Power loss ride-through enabled​​
3072 -
3073 -0: Disabled
3074 -
3075 -1: Enabled
3076 -
3077 -Tens place: Power loss ride-through selection​
3078 -
3079 -0: Discontinuous running
3080 -
3081 -1: Stop
3082 -)))
3083 -
3084 -
3085 -
3086 -Ones place: Power loss ride-through enabled​​
3087 -
3088 -0: Disable power loss ride-through . 1: Enable power loss ride-through.​
3089 -
3090 -Tens place: Power loss ride-through selection​
3091 -
3092 -​​Select the action when the frequency drops to zero during a power loss ride-through.
3093 -
3094 -0: Run at 0 Hz until under-voltage
3095 -
3096 -1: Shut down immediately
3097 -
3098 -|(% rowspan="2" %)FA.23|Power loss ride-through voltage threshold​|Factory default|75%
3099 -|Setting range|(% colspan="2" %)40% to 150%
3100 -|(% rowspan="2" %)FA.24|Power loss ride-through stable voltage|Factory default|95%
3101 -|Setting range|(% colspan="2" %)60% to 150%
3102 -
3103 -When the input power is reduced or power off, the inverter can control the motor speed down to feedback energy to avoid the VFD under voltage fault, the function is called power loss ride-through . When the bus voltage is lower than the rated bus voltage *FA.24, The power loss ride-through function is active. and control the motor to feedback energy to stabilize the bus voltage at the rated bus voltage *FA.24.
3104 -
3105 -
3106 -**FB group swing frequency, fixed length and counting**
3107 -
3108 -Swing frequency function is suitable for textile, chemical fiber and other industries and need transverse movement, winding function occasions.
3109 -
3110 -The function of swing frequency means that the output frequency of the inverter swings up and down with the set frequency as the center.
3111 -
3112 -[[image:1763107356738-341.png]]
3113 -
3114 -Figure 9-B-1 Schematic diagram of swing frequency operation
3115 -
3116 -|(% rowspan="2" %)FB.00|Swing frequency control|Factory default|0
3117 -|Setting range|(% colspan="2" %)(((
3118 -LED ones diigt: Swing frequency control
3119 -
3120 -0: The swing frequency control is disable
3121 -
3122 -1: Swing frequency control is effective
3123 -
3124 -LED tens digit: Swing frequency input mode
3125 -
3126 -0: Automatic input
3127 -
3128 -1: Manual input
3129 -
3130 -LED hundreds digit: Swing control
3131 -
3132 -0: Variable amplitude
3133 -
3134 -1: Fixed amplitude
3135 -
3136 -LED thousands digit: Reserved
3137 -)))
3138 -
3139 -LED ones diigt: Swing frequency control enable
3140 -
3141 -LED tens digit:
3142 -
3143 -0: Automatic input, according to the parameter setting, automatically enter the swing frequency run after the frequency arrives.
3144 -
3145 -1: Manual input, the frequency is controlled according to the DI terminal status control
3146 -
3147 -LED hundreds digit: 0: Variable amplitude, relative center frequency (set frequency), for variable amplitude system. The swing varies with the change of center frequency (set frequency).
3148 -
3149 -1: Fixed amplitude, relative to maximum frequency (F0.10 maximum output frequency), it is a fixed amplitude system.
3150 -
3151 -|(% rowspan="2" %)FB.01|Swing preset frequency|Factory default|0.00Hz
3152 -|Setting range|(% colspan="2" %)0.00 to Maximum frequency
3153 -|(% rowspan="2" %)FB.02|Preset frequency duration|Factory default|0.00s
3154 -|Setting range|(% colspan="2" %)0.00 to 650.00s
3155 -|(% rowspan="2" %)FB.03|Swing amplitude|Factory default|0.0%
3156 -|Setting range|(% colspan="2" %)0.0% to 100.0%
3157 -|(% rowspan="2" %)FB.04|Jump frequency amplitude|Factory default|0.0%
3158 -|Setting range|(% colspan="2" %)0.0% to 50.0%
3159 -
3160 -The value of swing amplitude and jump frequency can be determined by this parameter. The operating frequency of swing frequency is constrained by the upper and lower frequency.
3161 -
3162 -Swing relative to the center frequency (variable amplitude, select FB.00=0) : Swing amplitude, AW = frequency source F0.07× swing amplitude FB.01.
3163 -
3164 -Swing relative to Maximum frequency (fixed amplitude, FB.00=1) : Swing amplitude, AW = Maximum frequencyF0.12 x swing amplitude FB.01.
3165 -
3166 -Snap frequency = swing amplitude AW x jump frequency amplitude FB.02. That is, when the swing frequency is running, the value of the snap frequency relative to the swing amplitude.
3167 -
3168 -If the swing is selected relative to the center frequency (variable swing, select FB.00=0), the jog frequency is the change value.
3169 -
3170 -If the swing is selected relative to the Maximum frequency (fixed swing, select FB.00=1), the jog frequency is fixed.
3171 -
3172 -
3173 -|(% rowspan="2" %)FB.05|Swing frequency rise time|Factory default|5.00s
3174 -|Setting range|(% colspan="2" %)0.00 to 650.00s
3175 -|(% rowspan="2" %)FB.06|Swing frequency drop time|Factory default|5.00s
3176 -|Setting range|(% colspan="2" %)0.00 to 650.00s
3177 -
3178 -
3179 -
3180 -Triangle wave rise time = swing frequency duration FB.02× delta wave rise time coefficient FB.05 (unit: s).
3181 -Triangle wave fall time = swing frequency duration FB.02× (1- triangle wave rise time coefficient FB.06) (unit: s).
3182 -
3183 -
3184 -
3185 -
3186 -
3187 -**FC Group communication parameters**
3188 -
3189 -|(% rowspan="2" %)FC.00|Local address|Factory default|1
3190 -|Setting range|(% colspan="2" %)1 to 247, 0 is the broadcast address
3191 -
3192 -When the local address is set to 0, it is the broadcast address, and the host computer broadcast function is realized. The local address is unique (except the broadcast address), which is the basis of point-to-point communication between the host computer and the inverter.
3193 -
3194 -|(% rowspan="2" %)FC.01|Baud rate|Factory default|5
3195 -|Setting range|(% colspan="2" %)(((
3196 -0: 300 bps
3197 -
3198 -1: 600 bps
3199 -
3200 -2: 1200 bps
3201 -
3202 -3: 2400 bps
3203 -
3204 -4: 4800 bps
3205 -
3206 -5: 9600 bps
3207 -
3208 -6: 19200 bps
3209 -
3210 -7: 38400 bps
3211 -
3212 -8: 57600 bps
3213 -
3214 -9: 115200 bps
3215 -)))
3216 -
3217 -This parameter is used to set the data transmission rate between the host computer and the VFD. Note that the baud rate set by the upper computer and the VFD must be consistent, otherwise, communication cannot be carried out. The higher the baud rate, the faster the communication speed.
3218 -
3219 -|(% rowspan="2" %)FC.02|Modbus data format|Factory default|3
3220 -|Setting range|(% colspan="2" %)(((
3221 -0: (8.N.2) 8 bits, no parity, 2 stop bits
3222 -
3223 -1: (8.E.1) 8 bits, even parity, 1 stop bit
3224 -
3225 -2: (8.O.1) 8 bits, odd parity, 1 stop bit
3226 -
3227 -3: (8.n.1) 8 bits, no parity, 1 stop bit
3228 -)))
3229 -
3230 -The data format set by the upper computer and the inverter must be consistent, otherwise, the communication cannot be carried out.
3231 -
3232 -|(% rowspan="2" %)FC.03|Modbus Communication response delay|Factory default|2ms
3233 -|Setting range|(% colspan="2" %)0 to 20ms
3234 -
3235 -Response delay: the intermediate interval between the end of the VFD data acceptance and the sending of data to the upper machine. If the response delay is less than the system processing time, the response delay is based on the system processing time. If the response delay is longer than the system processing time, the system will wait until the response delay time reaches the upper computer before sending the data.
3236 -
3237 -
3238 -|(% rowspan="2" %)FC.04|Modbus Communication timeout time|Factory default|0.0s
3239 -|Setting range|(% colspan="2" %)0.0 s(In vain), 0.1-60.0s
3240 -
3241 -When the function code is set to 0.0s, the communication timeout parameter is invalid.
3242 -
3243 -When this function code is set to valid value, if the interval between one communication and the next communication exceeds the communication timeout period, the system reports a communication fault error (Err16). Usually, this is set to invalid. If you set the next parameter in a continuous communication system, you can monitor the communication status.
3244 -
3245 -
3246 -**FD Group multi-speed function and simple PLC function**
3247 -
3248 -Simple PLC function is the inverter built-in a programmable controller (PLC) to complete the automatic control of multi-segment frequency logic. Operation time, operation direction and operation frequency can be set to meet the requirements of the process. This series of inverter can realize 16 speed change control, there are 4 kinds of acceleration and deceleration time to choose. When the set PLC completes a cycle, an ON signal can be output by the multifunctional digital output terminal DO1, DO2 or the multifunctional relay relay 1, relay 2. See F1.02 to F1.05 for details. When the frequency source F0.07, F0.03, F0.04 is selected to determine the multi-speed operation mode, FD.00 to FD.15 needs to be set to determine its characteristics.
3249 -
3250 -|(% rowspan="2" %)FD.00|Multi-segment speed instruction 0|Factory default|0
3251 -|Setting range|(% colspan="2" %)-100.0% to 100.0% (100.0% refers to Maximum frequency F0.10)
3252 -|(% rowspan="2" %)FD.01|Multi-segment speed instruction 1|Factory default|0
3253 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3254 -|(% rowspan="2" %)FD.02|Multi-segment speed instruction 2|Factory default|0
3255 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3256 -|(% rowspan="2" %)FD.03|Multi-segment speed instruction 3|Factory default|0
3257 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3258 -|(% rowspan="2" %)FD.04|Multi-segment speed instruction 4|Factory default|0
3259 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3260 -|(% rowspan="2" %)FD.05|Multi-segment speed instruction 5|Factory default|0
3261 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3262 -|(% rowspan="2" %)FD.06|Multi-segment speed instruction 6|Factory default|0
3263 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3264 -|(% rowspan="2" %)FD.07|Multi-segment speed instruction 7|Factory default|0
3265 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3266 -|(% rowspan="2" %)FD.08|Multi-segment speed instruction 8|Factory default|0
3267 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3268 -|(% rowspan="2" %)FD.09|Multi-segment speed instruction 9|Factory default|0
3269 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3270 -|(% rowspan="2" %)FD.10|Multi-segment speed instruction 10|Factory default|0
3271 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3272 -|(% rowspan="2" %)FD.11|Multi-segment speed instruction 11|Factory default|0
3273 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3274 -|(% rowspan="2" %)FD.12|Multi-segment speed instruction 12|Factory default|0
3275 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3276 -|(% rowspan="2" %)FD.13|Multi-segment speed instruction 13|Factory default|0
3277 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3278 -|(% rowspan="2" %)FD.14|Multi-segment speed instruction 14|Factory default|0
3279 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3280 -|(% rowspan="2" %)FD.15|Multi-segment speed instruction 15|Factory default|0
3281 -|Setting range|(% colspan="2" %)-100.0% to 100.0%
3282 -
3283 -When the frequency source parameters F0.07, F0.03 and F0.04 are determined as the PLC operating mode, FD.00 to FD.15, FD.16, FD.17, FD.18 to FD.49 need to be set to determine their characteristics.
3284 -
3285 -**Instructions:** The symbol determines the simple PLC running direction. If the value is negative, it indicates the opposite direction.
3286 -
3287 -
3288 -|(% rowspan="2" %)FD.16|PLC mode of operation|Factory default|0
3289 -|Setting range|(% colspan="2" %)(((
3290 -0: Stop after a single run
3291 -
3292 -1: Maintain the final value at the end of a single run
3293 -
3294 -2: Keep cycling
3295 -)))
3296 -
3297 -0: Stops after a single run
3298 -
3299 -The inverter automatically stops after completing a single cycle and needs to give the running command again to start.
3300 -
3301 -1: Maintain the final value at the end of a single run
3302 -
3303 -The VFD automatically maintains the operating frequency and direction of the last section after completing a single cycle.
3304 -
3305 -2: Keep cycling
3306 -
3307 -After the inverter completes a cycle, it automatically starts the next cycle until the system stops when there is a stop command.
3308 -
3309 -|(% rowspan="2" %)FD.17|PLC power down memory selection|Factory default|00
3310 -|Setting range|(% colspan="2" %)(((
3311 -Ones place:
3312 -
3313 -0: Non-retentive on power down
3314 -
3315 -1: Retentive on power down
3316 -
3317 -Tens place:
3318 -
3319 -0: Non-retentive on shutdown
3320 -
3321 -1: Retentive on shutdown
3322 -)))
3323 -
3324 -Ones place: Power down retension selection
3325 -
3326 -PLC power down retension: The operating stage and operating frequency of PLC before power down.
3327 -
3328 -Tens place: Shutdown retention selection
3329 -
3330 -PLC shutdown retention: Record the operating stage and operating frequency of the previous PLC during shutdown.
3331 -
3332 -
3333 -|(% rowspan="2" %)FD.18|PLC stage 0 operation time|Factory default|0.0s(h)
3334 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3335 -|(% rowspan="2" %)FD.19|PLC phase 0 acceleration and deceleration time selection|Factory default|0
3336 -|Setting range|(% colspan="2" %)0to 3
3337 -|(% rowspan="2" %)FD.20|PLC stage 1 operation time|Factory default|0.0s(h)
3338 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3339 -|(% rowspan="2" %)FD.21|PLC phase 1 acceleration and deceleration time selection|Factory default|0
3340 -|Setting range|(% colspan="2" %)0to 3
3341 -|(% rowspan="2" %)FD.22|PLC stage 2 operation time|Factory default|0.0s(h)
3342 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3343 -|(% rowspan="2" %)FD.23|PLC phase 2 acceleration and deceleration time selection|Factory default|0
3344 -|Setting range|(% colspan="2" %)0to 3
3345 -|(% rowspan="2" %)FD.24|PLC stage 3 operation time|Factory default|0.0s(h)
3346 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3347 -|(% rowspan="2" %)FD.25|PLC phase 3 acceleration and deceleration time selection|Factory default|0
3348 -|Setting range|(% colspan="2" %)0to 3
3349 -|(% rowspan="2" %)FD.26|PLC stage 4 operation time|Factory default|0.0s(h)
3350 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3351 -|(% rowspan="2" %)FD.27|PLC phase 4 acceleration and deceleration time selection|Factory default|0
3352 -|Setting range|(% colspan="2" %)0to 3
3353 -|(% rowspan="2" %)FD.28|PLC stage 5 operation time|Factory default|0.0s(h)
3354 -|Setting range|(% colspan="2" %)0.0s(h)-6553.5s(h)
3355 -|(% rowspan="2" %)FD.29|PLC phase 5 acceleration and deceleration time selection|Factory default|0
3356 -|Setting range|(% colspan="2" %)0to 3
3357 -|(% rowspan="2" %)FD.30|PLC stage 6 operation time|Factory default|0.0s(h)
3358 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3359 -|(% rowspan="2" %)FD.31|PLC phase 6 acceleration and deceleration time selection|Factory default|0
3360 -|Setting range|(% colspan="2" %)0to 3
3361 -|(% rowspan="2" %)FD.32|PLC stage 7 operation time|Factory default|0.0s(h)
3362 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3363 -|(% rowspan="2" %)FD.33|PLC phase 7 acceleration and deceleration time selection|Factory default|0
3364 -|Setting range|(% colspan="2" %)0to 3
3365 -|(% rowspan="2" %)FD.34|PLC stage 8 operation time|Factory default|0.0s(h)
3366 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3367 -|(% rowspan="2" %)FD.35|PLC phase 8 acceleration and deceleration time selection|Factory default|0
3368 -|Setting range|(% colspan="2" %)0to 3
3369 -|(% rowspan="2" %)FD.36|PLC stage 9 operation time|Factory default|0.0s(h)
3370 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3371 -|(% rowspan="2" %)FD.37|PLC phase 9 acceleration and deceleration time selection|Factory default|0
3372 -|Setting range|(% colspan="2" %)0 to 3
3373 -|(% rowspan="2" %)FD.38|PLC stage 10 operation time|Factory default|0.0s(h)
3374 -|Setting range|(% colspan="2" %)0.0 s(h) to 6553.5s(h)
3375 -|(% rowspan="2" %)FD.39|PLC phase 10 acceleration and deceleration time selection|Factory default|0
3376 -|Setting range|(% colspan="2" %)0 to 3
3377 -|(% rowspan="2" %)FD.40|PLC stage 11 operation time|Factory default|0.0s(h)
3378 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3379 -|(% rowspan="2" %)FD.41|PLC phase 11 acceleration and deceleration time selection|Factory default|0
3380 -|Setting range|(% colspan="2" %)0 to 3
3381 -|(% rowspan="2" %)FD.42|PLC stage 12 operation time|Factory default|0.0s(h)
3382 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3383 -|(% rowspan="2" %)FD.43|PLC phase 12 acceleration and deceleration time selection|Factory default|0
3384 -|Setting range|(% colspan="2" %)0 to 3
3385 -|(% rowspan="2" %)FD.44|PLC stage 13 operation time|Factory default|0.0s(h)
3386 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3387 -|(% rowspan="2" %)FD.45|PLC phase 13 acceleration and deceleration time selection|Factory default|0
3388 -|Setting range|(% colspan="2" %)0 to 3
3389 -|(% rowspan="2" %)FD.46|PLC stage 14 operation time|Factory default|0.0s(h)
3390 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3391 -|(% rowspan="2" %)FD.47|PLC phase 14 acceleration and deceleration time selection|Factory default|0
3392 -|Setting range|(% colspan="2" %)0 to 3
3393 -|(% rowspan="2" %)FD.48|PLC stage 15 operation time|Factory default|0.0s(h)
3394 -|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3395 -|(% rowspan="2" %)FD.49|PLC phase 15 acceleration and deceleration time selection|Factory default|0
3396 -|Setting range|(% colspan="2" %)0 to 3
3397 -|(% rowspan="2" %)FD.50|PLC operating time unit|Factory default|0
3398 -|Setting range|(% colspan="2" %)(((
3399 -LED units: Timing unit
3400 -
3401 -0: s(seconds)
3402 -
3403 -1: h(hours)
3404 -
3405 -2: min(minutes)
3406 -)))
3407 -|(% rowspan="2" %)FD.51|Multi-segment speed instruction 0 given mode|Factory default|0
3408 -|Setting range|(% colspan="2" %)(((
3409 -0: Function code FD.00 given
3410 -
3411 -1: AI1
3412 -
3413 -2: AI2
3414 -
3415 -3: AI3
3416 -
3417 -4: Set the terminal PULSE
3418 -
3419 -5: PID
3420 -
3421 -6: Preset frequency (F0.08) given, UP/DOWN can be modified
3422 -
3423 -7: keyboard potentiometer set
3424 -)))
3425 -
3426 -
3427 -
3428 -This parameter determines the target amount of the multi-segment speed 0 given channel.
3429 -
3430 -FD.50: PLC operating time unit.
3431 -
3432 -
3433 -|(% rowspan="2" %)FD.52|Multiple speed is preferred|Factory default|1
3434 -|Set range|(% colspan="2" %)(((
3435 -0: Invalid
3436 -
3437 -1: Valid
3438 -)))
3439 -
3440 -Set this parameter to 1, F0.03 set the main frequency source not to multi-segment speed, and set F5 group terminal parameter multi-segment speed function~,~, when the terminal is valid, the frequency source switches to the multi-segment speed set, the multi-segment speed priority has nothing to do with the multi-segment speed 0.
3441 -
3442 -**FE Group user password**
3443 -
3444 -|(% rowspan="2" %)FE.00|User password|Factory default|0
3445 -|Setting range|(% colspan="2" %)0 to 65535
3446 -
3447 -If the value is set to any non-zero number, the password protection function takes effect. 00000: Clears the previously set password value and invalidates the password protection function. After the user password is set and takes effect, if you enter the parameter setting state again and the user password is incorrect, the parameter group cannot be entered and cannot be viewed/modified. Remember the user password you set. If you accidentally set or forget, please contact the manufacturer.
3448 -
3449 -|(% rowspan="2" %)FE.01|Number of times to display fault records|Factory default|4
3450 -|Setting range|(% colspan="2" %)0 to 8
3451 -
3452 -This function code is used to set the number of times that fault records are displayed.
3453 -
3454 -
3455 -|(% rowspan="2" %)FE.02|Parameter and key lock selection|Factory default|0
3456 -|Setting range|(% colspan="2" %)(((
3457 -0: Not locked
3458 -
3459 -1: The function parameter is locked
3460 -)))
3461 -
3462 -This function code is used to lock a parameter. After the parameter is locked, it cannot be modified.
3463 -
3464 -
3465 -**A0 Displays the parameter group**
3466 -
3467 -|(% rowspan="2" %)A0.00|Application macro|Factory default|0
3468 -|Setting range|(% colspan="2" %)(((
3469 -0: Default macro
3470 -
3471 -1: Tile press macro
3472 -
3473 -2: Spring mechanical macro
3474 -
3475 -3: Woodworking machinery macro
3476 -)))
3477 -
3478 -User macro parameter setting.
3479 -
3480 3480  
1763107356713-939.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -76.0 KB
Content
1763107356720-587.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -29.5 KB
Content
1763107356721-853.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -60.7 KB
Content
1763107356724-721.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -69.4 KB
Content
1763107356727-432.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -74.7 KB
Content
1763107356731-567.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -46.1 KB
Content
1763107356732-988.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -62.7 KB
Content
1763107356734-922.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -63.4 KB
Content
1763107356736-468.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -52.6 KB
Content
1763107356738-341.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -103.5 KB
Content