Changes for page 09 Function code

Last modified by Iris on 2025/11/17 14:59

From version 12.1
edited by Iris
on 2025/11/14 16:13
Change comment: There is no comment for this version
To version 12.3
edited by Iris
on 2025/11/17 11:46
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1739,94 +1739,90 @@
1739 1739  
1740 1740  The VC series VFD standard unit has 2 multi-function relay output terminals, 1 FM terminal (which can be used as a high-speed pulse output terminal or as an open collector output), and 2 multi-function analog output terminals.
1741 1741  
1742 -|(% rowspan="3" %)F6.00|(% colspan="2" %)FM Terminal output selection|Factory default|1
1743 -|(% rowspan="2" %)Setting range|0|(% colspan="2" %)Pulse output
1744 -|1|(% colspan="2" %)Open collector output (FMR)
1742 +|(% rowspan="3" style="text-align:center" %)F6.00|(% colspan="2" style="text-align:center" %)FM Terminal output selection|(% style="text-align:center" %)Factory default|1
1743 +|(% rowspan="2" style="text-align:center" %)Setting range|(% style="text-align:center" %)0|(% colspan="2" style="text-align:center" %)Pulse output
1744 +|(% style="text-align:center" %)1|(% colspan="2" style="text-align:center" %)Open collector output (FMR)
1745 1745  
1746 1746  FM terminals are programmable multiplexed terminals. Can be used as a high speed pulse output terminal (FMP), pulse frequency up to 100kHz. Refer to F6.06 for FMP related functions. Also available as an open collector output terminal (FMR). See F6.01 for FMR functions.
1747 1747  
1748 1748  FMP function needs hardware support.
1749 1749  
1750 -|F6.01|FMR Open collector output selection|Factory default|0
1751 -|F6.02|Relay 1 output selection|Factory default|2
1752 -|F6.03|Relay 2 output selection (Extended)|Factory default|0
1753 -|F6.06|VDO1 output selection|Factory default|0
1754 -|F6.07|VDO2 output selection|Factory default|0
1755 -|F6.08|VDO3 output selection|Factory default|0
1750 +|(% style="text-align:center" %)F6.01|(% style="text-align:center" %)FMR Open collector output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1751 +|(% style="text-align:center" %)F6.02|(% style="text-align:center" %)Relay 1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2
1752 +|(% style="text-align:center" %)F6.03|(% style="text-align:center" %)Relay 2 output selection (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1753 +|(% style="text-align:center" %)F6.06|(% style="text-align:center" %)VDO1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1754 +|(% style="text-align:center" %)F6.07|(% style="text-align:center" %)VDO2 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1755 +|(% style="text-align:center" %)F6.08|(% style="text-align:center" %)VDO3 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1756 1756  
1757 -
1758 -
1759 1759  Multi-function output terminal function selection are as follows:
1760 1760  
1761 -|**Setting value**|**Function**|**Description**
1762 -|0|No-output|The output terminal has no function
1763 -|1|VFD in operation|Indicates that the inverter is running, there is an output frequency (can be zero) at this time output ON signal.
1764 -|2|Fault output|When the inverter fails and fails to stop, the output ON signal.
1765 -|3|Frequency level detects FDT arrival|Please refer to function codes F8.19 and F8.20 for detailed instructions
1766 -|4|Frequency arrival|Please refer to function code F8.26 for detailed instructions.
1767 -|5|Running at zero speed|The VFD operates and the output frequency is 0, and the output signal is ON.
1768 -|6|Motor overload pre-alarm|Before the motor electronic thermal protection action, according to the overload forecast value, after exceeding the forecast value output ON signal. Motor overload parameters are set in FA.00 to FA.02.
1769 -|7|Inverter overload pre-alarm|After checking the inverter overload, 10s before the protection occurs. Output ON signal.
1770 -|8|Set count pulse value to arrive|When the count value reaches the value set by FB.08, the ON signal is output.
1771 -|9|Specified count pulse value arrived|When the count value reaches the value set by FB.09, the ON signal is output. For the counting function, see FB group function description
1772 -|10|Length reached|When the actual length of the detection exceeds the length set by FB.05, the ON signal is output.
1773 -|11|PLC cycle complete|When the simple PLC completes a cycle, it outputs a pulse signal with a width of 250ms.
1774 -|12|Cumulative running time arrived|When the accumulated running time of the inverter exceeds the time set by F8.17, the output ON signal.
1775 -|13|-|-
1776 -|14|Torque limit|When the torque limit function is operated, the stall protection function automatically acts, automatically changes the output frequency, and the output ON signal indicates that the output torque is limited. This output signal can be used to reduce the load or to display an overload status signal on the monitoring device.
1777 -|15|Operational readiness|The main circuit and control circuit power supply are established, the inverter protection function is not active, and the inverter is in the running state, the ON signal is output.
1778 -|16|AI1>AI2|When the value of the analog input AI1 is greater than that of the other input AI2, the ON signal is output.
1779 -|17|Frequency upper limit reached|Output ON signal when the operating frequency reaches the upper limit frequency.
1780 -|18|(((
1759 +(% style="margin-left:auto; margin-right:auto" %)
1760 +|=**Setting value**|=**Function**|=**Description**
1761 +|=0|No-output|The output terminal has no function
1762 +|=1|VFD in operation|Indicates that the inverter is running, there is an output frequency (can be zero) at this time output ON signal.
1763 +|=2|Fault output|When the inverter fails and fails to stop, the output ON signal.
1764 +|=3|Frequency level detects FDT arrival|Please refer to function codes F8.19 and F8.20 for detailed instructions
1765 +|=4|Frequency arrival|Please refer to function code F8.26 for detailed instructions.
1766 +|=5|Running at zero speed|The VFD operates and the output frequency is 0, and the output signal is ON.
1767 +|=6|Motor overload pre-alarm|Before the motor electronic thermal protection action, according to the overload forecast value, after exceeding the forecast value output ON signal. Motor overload parameters are set in FA.00 to FA.02.
1768 +|=7|Inverter overload pre-alarm|After checking the inverter overload, 10s before the protection occurs. Output ON signal.
1769 +|=8|Set count pulse value to arrive|When the count value reaches the value set by FB.08, the ON signal is output.
1770 +|=9|Specified count pulse value arrived|When the count value reaches the value set by FB.09, the ON signal is output. For the counting function, see FB group function description
1771 +|=10|Length reached|When the actual length of the detection exceeds the length set by FB.05, the ON signal is output.
1772 +|=11|PLC cycle complete|When the simple PLC completes a cycle, it outputs a pulse signal with a width of 250ms.
1773 +|=12|Cumulative running time arrived|When the accumulated running time of the inverter exceeds the time set by F8.17, the output ON signal.
1774 +|=13|-|-
1775 +|=14|Torque limit|When the torque limit function is operated, the stall protection function automatically acts, automatically changes the output frequency, and the output ON signal indicates that the output torque is limited. This output signal can be used to reduce the load or to display an overload status signal on the monitoring device.
1776 +|=15|Operational readiness|The main circuit and control circuit power supply are established, the inverter protection function is not active, and the inverter is in the running state, the ON signal is output.
1777 +|=16|AI1>AI2|When the value of the analog input AI1 is greater than that of the other input AI2, the ON signal is output.
1778 +|=17|Frequency upper limit reached|Output ON signal when the operating frequency reaches the upper limit frequency.
1779 +|=18|(((
1781 1781  Frequency lower limit reached
1782 1782  
1783 1783  (Run related)
1784 1784  )))|Output ON signal when the operating frequency reaches the lower limit frequency. In the shutdown state, the signal is always OFF.
1785 -|19|Undervoltage state output|The inverter outputs ON signal when it is undervoltage.
1786 -|20|Communication setting|See related instructions in the communication protocol
1787 -|21|Positioning completed|Reserve
1788 -|22|Positioning close|Reserve
1789 -|23|(((
1784 +|=19|Undervoltage state output|The inverter outputs ON signal when it is undervoltage.
1785 +|=20|Communication setting|See related instructions in the communication protocol
1786 +|=21|Positioning completed|Reserve
1787 +|=22|Positioning close|Reserve
1788 +|=23|(((
1790 1790  Zero speed running 2
1791 1791  
1792 1792  (Also output when shut down)
1793 1793  )))|VFD output frequency is 0, output ON signal (shutdown also output).
1794 -|24|Accumulative power-on time reached|When F7.13(the accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output.
1795 -|25|(((
1793 +|=24|Accumulative power-on time reached|When F7.13(the accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output.
1794 +|=25|(((
1796 1796  Frequency level detection
1797 1797  
1798 1798  FDT2 output
1799 1799  )))|For details, see function codes F8.28 and F8.29.
1800 -|26|Frequency to 1 output|For details, see function codes F8.30 and F8.31.
1801 -|27|Frequency to 2output|For details, see function codes F8.32 and F8.33.
1802 -|28|Current reaches 1 output|For details, see function codes F8.38 and F8.39.
1803 -|29|Current reaches 2 output|For details, see function codes F8.40 and F8.41.
1804 -|30|Timed arrival output|When F8.42(timing function selection) is effective, the VFD will output ON signal when the running time reaches the set timing time.
1805 -|31|-|-
1806 -|32|-|
1807 -|33|Running direction|When the inverter runs in reverse, the ON signal is output
1808 -|34|-|
1809 -|35|Module temperature reach|
1810 -|36|Software overcurrent output|For details, see function codes F8.36 and F8.37.
1811 -|37|(((
1799 +|=26|Frequency to 1 output|For details, see function codes F8.30 and F8.31.
1800 +|=27|Frequency to 2output|For details, see function codes F8.32 and F8.33.
1801 +|=28|Current reaches 1 output|For details, see function codes F8.38 and F8.39.
1802 +|=29|Current reaches 2 output|For details, see function codes F8.40 and F8.41.
1803 +|=30|Timed arrival output|When F8.42(timing function selection) is effective, the VFD will output ON signal when the running time reaches the set timing time.
1804 +|=31|-|-
1805 +|=32|-|
1806 +|=33|Running direction|When the inverter runs in reverse, the ON signal is output
1807 +|=34|-|
1808 +|=35|Module temperature reach|
1809 +|=36|Software overcurrent output|For details, see function codes F8.36 and F8.37.
1810 +|=37|(((
1812 1812  Lower limit frequency reached
1813 1813  
1814 1814  (Run independent)
1815 1815  )))|Output ON signal when the operating frequency reaches the lower limit frequency. (When the conditions are met, the ON signal will also be output in the shutdown state)
1816 -|38|Fault output (Continue running)|When the inverter fails, output ON signal
1817 -|39|Reserve|
1818 -|40|The running time arrive|
1819 -|41|User defined output 1|User can define the conditions to output the terminal
1820 -|42|User-defined output 2|User can define the conditions to output the terminal
1821 -|43|Timer output|Output ON signal when the timing setting condition is met
1822 -|44|Forward running status|If the inverter is in forward running, output ON signal
1823 -|45|Reverse running status|If the inverter is in reverse running, output ON signal
1815 +|=38|Fault output (Continue running)|When the inverter fails, output ON signal
1816 +|=39|Reserve|
1817 +|=40|The running time arrive|
1818 +|=41|User defined output 1|User can define the conditions to output the terminal
1819 +|=42|User-defined output 2|User can define the conditions to output the terminal
1820 +|=43|Timer output|Output ON signal when the timing setting condition is met
1821 +|=44|Forward running status|If the inverter is in forward running, output ON signal
1822 +|=45|Reverse running status|If the inverter is in reverse running, output ON signal
1824 1824  
1825 -
1826 -
1827 -
1828 -|(% rowspan="2" %)F6.10|AO output signal selection|Factory default|00
1829 -|Setting range|(% colspan="2" %)(((
1824 +|(% rowspan="2" style="text-align:center" %)F6.10|(% style="text-align:center" %)AO output signal selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)00
1825 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1830 1830  The ones place: AO1
1831 1831  
1832 1832  0: 0 to 10V
... ... @@ -1846,8 +1846,8 @@
1846 1846  
1847 1847  All models 1 AO.
1848 1848  
1849 -|(% rowspan="2" %)F6.11|FMP (Pulse output terminal) output selection|Factory default|0
1850 -|Setting range|(% colspan="2" %)(((
1845 +|(% rowspan="2" style="text-align:center" %)F6.11|(% style="text-align:center" %)FMP (Pulse output terminal) output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1846 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1851 1851  0: Running frequency
1852 1852  
1853 1853  1: Set the frequency
... ... @@ -1882,88 +1882,84 @@
1882 1882  
1883 1883  16: Bus voltage (0-1000V, corresponding to 0-10V)
1884 1884  )))
1885 -|(% rowspan="2" %)F6.12|AO1 output selection|Factory default|0
1886 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range
1887 -|(% rowspan="2" %)F6.13|AO2 output selection (Extended)|Factory default|0
1888 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range
1881 +|(% rowspan="2" style="text-align:center" %)F6.12|(% style="text-align:center" %)AO1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1882 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)Consistent with F6.11 setting range
1883 +|(% rowspan="2" style="text-align:center" %)F6.13|(% style="text-align:center" %)AO2 output selection (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1884 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)Consistent with F6.11 setting range
1889 1889  
1890 1890  The standard output of the analog output (zero bias is 0, gain 1) is 0mA to 20mA (or 0V to 10V).
1891 1891  
1892 1892  The range of corresponding quantities represented is shown in the following table:
1893 1893  
1894 -|**Setting value**|**Function**|**Range**
1895 -|0|Operating frequency|0 to Maximum output frequency
1896 -|1|Setting frequency|0 toMaximum output frequency
1897 -|2|Output current|0 to2 times the rated motor current
1898 -|3|Output torque|0 to2 times the rated motor torque
1899 -|4|Output power|0 to 2 times rated power
1900 -|5|Output voltage|0 to 1.2 times rated voltage of inverter
1901 -|6|(% colspan="2" %)Reserve
1902 -|7|AI1|0V to10V
1903 -|8|AI2|0V to10V/0-20mA
1904 -|9|(% colspan="2" %)Reserve
1905 -|10|Length|0 to Maximum set length
1906 -|11|Count value|0 to Maximum count value
1907 -|12|Communication setting|-10000 to 10000
1908 -|13|Motor speed|0 to The maximum output frequency corresponds to the speed
1909 -|14|Output current|0 to 1000A, correspondence 0-10V
1910 -0 to 1000V, correspondence 0-10V
1911 -|15|Output voltage|0.0V to 1000.0V
1912 -|16|Bus voltage|0 to 1000V, correspondence 0-10V
1890 +(% style="margin-left:auto; margin-right:auto" %)
1891 +|=**Setting value**|=**Function**|=**Range**
1892 +|=0|(% style="text-align:center" %)Operating frequency|(% style="text-align:center" %)0 to Maximum output frequency
1893 +|=1|(% style="text-align:center" %)Setting frequency|(% style="text-align:center" %)0 to Maximum output frequency
1894 +|=2|(% style="text-align:center" %)Output current|(% style="text-align:center" %)0 to 2 times the rated motor current
1895 +|=3|(% style="text-align:center" %)Output torque|(% style="text-align:center" %)0 to 2 times the rated motor torque
1896 +|=4|(% style="text-align:center" %)Output power|(% style="text-align:center" %)0 to 2 times rated power
1897 +|=5|(% style="text-align:center" %)Output voltage|(% style="text-align:center" %)0 to 1.2 times rated voltage of inverter
1898 +|=6|(% colspan="2" style="text-align:center" %)Reserve
1899 +|=7|(% style="text-align:center" %)AI1|(% style="text-align:center" %)0V to10V
1900 +|=8|(% style="text-align:center" %)AI2|(% style="text-align:center" %)0V to 10V/0-20mA
1901 +|=9|(% colspan="2" style="text-align:center" %)Reserve
1902 +|=10|(% style="text-align:center" %)Length|(% style="text-align:center" %)0 to Maximum set length
1903 +|=11|(% style="text-align:center" %)Count value|(% style="text-align:center" %)0 to Maximum count value
1904 +|=12|(% style="text-align:center" %)Communication setting|(% style="text-align:center" %)-10000 to 10000
1905 +|=13|(% style="text-align:center" %)Motor speed|(% style="text-align:center" %)0 to The maximum output frequency corresponds to the speed
1906 +|=14|(% style="text-align:center" %)Output current|(% style="text-align:center" %)0 to 1000A, correspondence 0 to 10V
1907 +0 to 1000V, correspondence 0 to 10V
1908 +|=15|(% style="text-align:center" %)Output voltage|(% style="text-align:center" %)0.0V to 1000.0V
1909 +|=16|(% style="text-align:center" %)Bus voltage|(% style="text-align:center" %)0 to 1000V, correspondence 0 to 10V
1913 1913  
1911 +|(% rowspan="2" style="text-align:center" %)F6.14|(% style="text-align:center" %)FM upper frequency output limit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.00kHz
1912 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 100.00kHz
1914 1914  
1915 -
1916 -|(% rowspan="2" %)F6.14|FM upper frequency output limit|Factory default|20.00kHz
1917 -|Setting range|(% colspan="2" %)0.00 to- 50.00kHz
1918 -
1919 -
1920 -
1921 1921  F6.00 maximum frequency of pulse output when selecting pulse output.
1922 1922  
1923 -|(% rowspan="2" %)F6.15|AO1 minimum input|Factory default|0.00V
1924 -|Setting range|(% colspan="2" %)0.00V to F6.17
1925 -|(% rowspan="2" %)F6.16|AO1 the minimum input corresponds to the setting|Factory default|0.0%
1926 -|Setting range|(% colspan="2" %)0.0% to +100.0%
1927 -|(% rowspan="2" %)F6.17|AO1 maximum input|Factory default|10.00V
1928 -|Setting range|(% colspan="2" %)F6.15 to +10.00V
1929 -|(% rowspan="2" %)F6.18|AO1 the maximum input corresponds to the setting|Factory default|100.0%
1930 -|Setting range|(% colspan="2" %)0.0% to +100.0%
1916 +|(% rowspan="2" style="text-align:center" %)F6.15|(% style="text-align:center" %)AO1 minimum input|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00V
1917 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00V to F6.17
1918 +|(% rowspan="2" style="text-align:center" %)F6.16|(% style="text-align:center" %)AO1 the minimum input corresponds to the setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
1919 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to +100.0%
1920 +|(% rowspan="2" style="text-align:center" %)F6.17|(% style="text-align:center" %)AO1 maximum input|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)10.00V
1921 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F6.15 to +10.00V
1922 +|(% rowspan="2" style="text-align:center" %)F6.18|(% style="text-align:center" %)AO1 the maximum input corresponds to the setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
1923 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to +100.0%
1931 1931  
1932 1932  The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application.
1933 1933  
1934 -|(% rowspan="2" %)F6.19|AO2 minimum input (Extended)|Factory default|(% colspan="2" %)0.00V
1935 -|Setting range|(% colspan="3" %)0.00V to F6.21
1936 -|(% rowspan="2" %)F6.20|AO2 minimum Input mapping Settings (Extended)|(% colspan="2" %)Factory default|0.0%
1937 -|Setting range|(% colspan="3" %)0.0% to +100.0%
1938 -|(% rowspan="2" %)F6.21|AO2 maximum input (Extended)|(% colspan="2" %)Factory default|10.00V
1939 -|Setting range|(% colspan="3" %)F6.19 to +10.00V
1940 -|(% rowspan="2" %)F6.22|AO2 maximum input corresponding Settings (Extended)|(% colspan="2" %)Factory default|100.0%
1941 -|Setting range|(% colspan="3" %)0.0% to +100.0%
1942 -|(% rowspan="2" %)F6.23|FMR turn-on delay time|(% colspan="2" %)Factory default|0.0s
1943 -|Setting range|(% colspan="3" %)0.0s to 3600.0s
1927 +|(% rowspan="2" style="text-align:center" %)F6.19|(% style="text-align:center" %)AO2 minimum input (Extended)|(% style="text-align:center" %)Factory default|(% colspan="2" style="text-align:center" %)0.00V
1928 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.00V to F6.21
1929 +|(% rowspan="2" style="text-align:center" %)F6.20|(% style="text-align:center" %)AO2 minimum Input mapping Settings (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
1930 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0% to +100.0%
1931 +|(% rowspan="2" style="text-align:center" %)F6.21|(% style="text-align:center" %)AO2 maximum input (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)10.00V
1932 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)F6.19 to +10.00V
1933 +|(% rowspan="2" style="text-align:center" %)F6.22|(% style="text-align:center" %)AO2 maximum input corresponding Settings (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
1934 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0% to +100.0%
1935 +|(% rowspan="2" style="text-align:center" %)F6.23|(% style="text-align:center" %)FMR turn-on delay time|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1936 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0s to 3600.0s
1944 1944  
1945 1945  The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application.
1946 1946  
1940 +|(% rowspan="2" style="text-align:center" %)F6.24|(% style="text-align:center" %)Relay 1 on delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1941 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1942 +|(% rowspan="2" style="text-align:center" %)F6.25|(% style="text-align:center" %)Relay 2 turn-on delay time (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1943 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1944 +|(% rowspan="2" style="text-align:center" %)F6.26|(% style="text-align:center" %)VDO connection delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1945 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1946 +|(% rowspan="2" style="text-align:center" %)F6.27|(% style="text-align:center" %)FMR disconnect delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1947 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1948 +|(% rowspan="2" style="text-align:center" %)F6.28|(% style="text-align:center" %)Relay 1 disconnect delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1949 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1950 +|(% rowspan="2" style="text-align:center" %)F6.29|(% style="text-align:center" %)Relay 2 disconnect delay time (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1951 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1952 +|(% rowspan="2" style="text-align:center" %)F6.30|(% style="text-align:center" %)VDO1 disconnect delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
1953 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s
1947 1947  
1948 -|(% rowspan="2" %)F6.24|Relay 1 on delay time|Factory default|0.0s
1949 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1950 -|(% rowspan="2" %)F6.25|Relay 2 turn-on delay time (Extended)|Factory default|0.0s
1951 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1952 -|(% rowspan="2" %)F6.26|VDO connection delay|Factory default|0.0s
1953 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1954 -|(% rowspan="2" %)F6.27|FMR disconnect delay time|Factory default|0.0s
1955 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1956 -|(% rowspan="2" %)F6.28|Relay 1 disconnect delay time|Factory default|0.0s
1957 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1958 -|(% rowspan="2" %)F6.29|Relay 2 disconnect delay time (Extended)|Factory default|0.0s
1959 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1960 -|(% rowspan="2" %)F6.30|VDO1 disconnect delay|Factory default|0.0s
1961 -|Setting range|(% colspan="2" %)0.0s to 3600.0s
1962 -
1963 1963  Set the delay time of output terminals FMR, relay 1, relay 2, VDO from the change of state to the change of output.
1964 1964  
1965 -|(% rowspan="2" %)F6.31|Output terminal valid status Select 1|Factory default|000
1966 -|Setting range|(% colspan="2" %)(((
1957 +|(% rowspan="2" style="text-align:center" %)F6.31|(% style="text-align:center" %)Output terminal valid status Select 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)000
1958 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1967 1967  0: Positive logic
1968 1968  
1969 1969  1: Reverse logic
... ... @@ -1976,8 +1976,8 @@
1976 1976  
1977 1977  Thousands place: -
1978 1978  )))
1979 -|(% rowspan="2" %)F6.32|Virtual output terminal valid status Select 2|Factory default|000
1980 -|Setting range|(% colspan="2" %)(((
1971 +|(% rowspan="2" style="text-align:center" %)F6.32|(% style="text-align:center" %)Virtual output terminal valid status Select 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)000
1972 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1981 1981  0: Positive logic
1982 1982  
1983 1983  1: Reverse logic
... ... @@ -1997,8 +1997,8 @@
1997 1997  
1998 1998  Inverse logic: The digital output terminal is not connected to the corresponding public end, and the disconnect is valid.
1999 1999  
2000 -|(% rowspan="2" %)F6.33|User-defined output selection (EX) 1|Factory default|0
2001 -|Setting range|(% colspan="2" %)(((
1992 +|(% rowspan="2" style="text-align:center" %)F6.33|(% style="text-align:center" %)User-defined output selection (EX) 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1993 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2002 2002  0: The running frequency
2003 2003  
2004 2004  1: Set the frequency
... ... @@ -2024,9 +2024,8 @@
2024 2024  
2025 2025  This parameter is used to select a reference variable for the custom output. Take the selected variable EX as the operation comparison object.
2026 2026  
2027 -
2028 -|(% rowspan="2" %)F6.34|The comparison method chosen by the user 1|Factory default|0
2029 -|Setting range|(% colspan="2" %)(((
2019 +|(% rowspan="2" style="text-align:center" %)F6.34|(% style="text-align:center" %)The comparison method chosen by the user 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2020 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2030 2030  Units: Compare test methods
2031 2031  
2032 2032  0: Equal to (EX == X1)
... ... @@ -2050,17 +2050,17 @@
2050 2050  
2051 2051  The way the tens select the output. False value output is output if the condition is not met, and no output if it is met; Truth output is output only when the condition is met, and no output if the condition is not met.
2052 2052  
2053 -|(% rowspan="2" %)F6.35|User-defined dead zone 1|Factory default|0
2054 -|Setting range|(% colspan="2" %)0 to 65535
2044 +|(% rowspan="2" style="text-align:center" %)F6.35|(% style="text-align:center" %)User-defined dead zone 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2045 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2055 2055  
2056 2056  When the comparison test mode of F6.29 is set to greater than or equal to or less than or equal to, F6.30 is used to define the processing dead zone value centered on the comparison value X1. The processing dead zone has effect only on 1 and 2 of the comparison test mode of F6.29, and has no effect on 0, 3, and 4. For example, when F6.29 is set to 11, when EX is increased from 0 to greater than or equal to X1+F6.30, the output is valid; When EX is reduced to less than or equal to X1.F6.30, the output is invalid.
2057 2057  
2058 -|(% rowspan="2" %)F6.36|User-defined 2 outputs the comparison value X1|Factory default|0
2059 -|Setting range|(% colspan="2" %)0 to 65535
2060 -|(% rowspan="2" %)F6.37|User-defined 2 outputs the comparison value X2|Factory default|0
2061 -|Setting range|(% colspan="2" %)0 to 65535
2062 -|(% rowspan="2" %)F6.38|User-defined output selection (EX) 2|Factory default|0
2063 -|Setting range|(% colspan="2" %)(((
2049 +|(% rowspan="2" style="text-align:center" %)F6.36|(% style="text-align:center" %)User-defined 2 outputs the comparison value X1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2050 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2051 +|(% rowspan="2" style="text-align:center" %)F6.37|(% style="text-align:center" %)User-defined 2 outputs the comparison value X2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2052 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2053 +|(% rowspan="2" style="text-align:center" %)F6.38|(% style="text-align:center" %)User-defined output selection (EX) 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2054 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2064 2064  0: Running frequency
2065 2065  
2066 2066  1: Set the frequency
... ... @@ -2090,22 +2090,22 @@
2090 2090  
2091 2091  ~1. When the set frequency is greater than or equal to 20.00HZ, the relay is closed;
2092 2092  
2093 -Set parameters as follows: F6.02 = 41, F6.28 = 1, F6.29 = 11, F6.30 = 0, F6.31 = 2000;
2084 +Set parameters as follows: F6.02 = 41F6.33 = 1F6.34 = 11F6.35 = 0F6.36 = 2000;
2094 2094  
2095 2095  2. When the bus voltage is less than or equal to 500.0V, the relay is closed; In order to avoid frequent operation of the relay when the detection voltage fluctuates 5.0V above and below 500.0V, it is required to process into a dead zone in the range of (500.0-5.0) to (500.0+5.0).
2096 2096  
2097 -Set parameters as follows: F6.02 = 41, F6.28 = 2, F6.29 = 01, F6.30 = 50, F6.31 = 5000;
2088 +Set parameters as follows: F6.02 = 41F6.33 = 2F6.34 = 01F6.35 = 50F6.36 = 5000;
2098 2098  
2099 2099  3. When the inverter is required to reverse, the relay is closed:
2100 2100  
2101 -Set parameters as follows: F6.02 = 41, F6.28 = 5, F6.29 = 14, F6.31 = 8, F6.32= 8;
2092 +Set parameters as follows: F6.02 = 41F6.33 = 2,F6.34 = 01F6.31 = 8F6.37= 8;
2102 2102  
2103 2103  4. When AI1 input is required to be greater than 3.00V and less than or equal to 6.00V, the relay is closed:
2104 2104  
2105 -Set parameters as follows: F6.02 = 41, F6.28=13, F6.29=13, F6.31=300, F6.32=600; F6.33 to F6.37 is the same as F6.28 to F6.32.
2096 +Set parameters as follows: F6.02 = 41F6.33=13F6.34=13F6.36=300F6.37=600
2106 2106  
2107 -|(% rowspan="2" %)F6.39|The comparison method chosen by the user 2|Factory default|0
2108 -|Setting range|(% colspan="2" %)(((
2098 +|(% rowspan="2" style="text-align:center" %)F6.39|(% style="text-align:center" %)The comparison method chosen by the user 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2099 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2109 2109  Units: Compare test methods
2110 2110  
2111 2111  0: Equal to (EX == X1)
... ... @@ -2124,18 +2124,17 @@
2124 2124  
2125 2125  1: Truth output
2126 2126  )))
2127 -|(% rowspan="2" %)F6.40|User-defined dead zone 2|Factory default|0
2128 -|Setting range|(% colspan="2" %)0 to 65535
2129 -|(% rowspan="2" %)F6.41|User-defined 2 outputs the comparison value X1|Factory default|0
2130 -|Setting range|(% colspan="2" %)0 to 65535
2131 -|(% rowspan="2" %)F6.42|User-defined 2 Output comparison value X2|Factory default|0
2132 -|Setting range|(% colspan="2" %)0 to 65535
2118 +|(% rowspan="2" style="text-align:center" %)F6.40|(% style="text-align:center" %)User-defined dead zone 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2119 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2120 +|(% rowspan="2" style="text-align:center" %)F6.41|(% style="text-align:center" %)User-defined 2 outputs the comparison value X1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2121 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2122 +|(% rowspan="2" style="text-align:center" %)F6.42|(% style="text-align:center" %)User-defined 2 Output comparison value X2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2123 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2133 2133  
2134 2134  Second output. The parameter setting mode is the same as F6.33 to F6.37.
2135 2135  
2136 -
2137 -|(% rowspan="2" %)F6.43|Timer time unit|Factory default|0
2138 -|Setting range|(% colspan="2" %)(((
2127 +|(% rowspan="2" style="text-align:center" %)F6.43|(% style="text-align:center" %)Timer time unit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2128 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)(((
2139 2139  0: Second
2140 2140  
2141 2141  1: Minute
... ... @@ -2142,22 +2142,21 @@
2142 2142  
2143 2143  2: Hour
2144 2144  )))
2145 -|(% rowspan="2" %)F6.44|Timer maximum|Factory default|0
2146 -|Setting range|(% colspan="2" %)0 to 65535 (No more when set to 65000)
2147 -|(% rowspan="2" %)F6.45|Timer set value|Factory default|0
2148 -|Setting range|(% colspan="2" %)0 to 65535
2149 -|(% rowspan="2" %)F6.46|Counter maximum|Factory default|0
2150 -|Setting range|(% colspan="2" %)0 to 65535
2151 -|(% rowspan="2" %)F6.47|Counter set value|Factory default|0
2152 -|Setting range|(% colspan="2" %)0 to 65535
2135 +|(% rowspan="2" style="text-align:center" %)F6.44|(% style="text-align:center" %)Timer maximum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2136 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 (No more when set to 65000)
2137 +|(% rowspan="2" style="text-align:center" %)F6.45|(% style="text-align:center" %)Timer set value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2138 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2139 +|(% rowspan="2" style="text-align:center" %)F6.46|(% style="text-align:center" %)Counter maximum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2140 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2141 +|(% rowspan="2" style="text-align:center" %)F6.47|(% style="text-align:center" %)Counter set value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2142 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
2153 2153  
2154 2154  Set the timer time.
2155 2155  
2146 +== **F7 group keyboard with display** ==
2156 2156  
2157 -**F7 group keyboard with display**
2158 -
2159 -|(% rowspan="2" %)F7.00|LCD keyboard parameter copy|Factory default|0
2160 -|Setting range|(% colspan="2" %)(((
2148 +|(% rowspan="2" style="text-align:center" %)F7.00|(% style="text-align:center; width:252px" %)LCD keyboard parameter copy|(% style="text-align:center; width:304px" %)Factory default|(% style="text-align:center" %)0
2149 +|(% style="text-align:center; width:252px" %)Setting range|(% colspan="2" style="width:398px" %)(((
2161 2161  0: No operation is performed
2162 2162  
2163 2163  1: The function parameters of the machine are uploaded to the LCD keyboard
... ... @@ -2165,11 +2165,10 @@
2165 2165  2: LCD keyboard function parameters download to the machine
2166 2166  )))
2167 2167  
2168 -**Note: LCD is not available.**
2157 +**Note: LCD is not available.**
2169 2169  
2170 -
2171 -|(% rowspan="2" %)F7.01|ENT key function selection|Factory default|0
2172 -|Setting range|(% colspan="2" %)(((
2159 +|(% rowspan="2" style="text-align:center" %)F7.01|(% style="text-align:center; width:230px" %)ENT key function selection|(% style="text-align:center; width:314px" %)Factory default|(% style="text-align:center" %)0
2160 +|(% style="text-align:center; width:230px" %)Setting range|(% colspan="2" style="width:421px" %)(((
2173 2173  0: ENT is invalid
2174 2174  
2175 2175  1: Switch between the command channel of the operation panel and the remote command channel (the remote command channel includes communication and terminal control)
... ... @@ -2209,8 +2209,8 @@
2209 2209  
2210 2210  Operating instructions: base for the initial menu, -C- for the debugging menu; ENT key to switch the menu, shift key to enter the corresponding menu; debugging menu displayed as CFxx.xx
2211 2211  
2212 -|(% rowspan="2" %)F7.02|Keyboard STOP key range|Factory default|0011
2213 -|Setting range|(% colspan="2" %)(((
2200 +|(% rowspan="2" style="text-align:center" %)F7.02|(% style="text-align:center" %)Keyboard STOP key range|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0011
2201 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2214 2214  LED units place: Terminal control selection
2215 2215  
2216 2216  0: The terminal command is invalid
... ... @@ -2228,10 +2228,10 @@
2228 2228  LED thousands place: reserved
2229 2229  )))
2230 2230  
2231 -**Special note:** When the STOP button communication control is valid, if the machine is started by using the communication command and the machine is stopped by using the STOP button, it can be started only after the STOP command is issued before the next communication start.
2219 +**✎Note:** When the STOP button communication control is valid, if the machine is started by using the communication command and the machine is stopped by using the STOP button, it can be started only after the STOP command is issued before the next communication start.
2232 2232  
2233 -|(% rowspan="2" %)F7.03|Keyboard run displays parameter 1|Factory default|3420
2234 -|Setting range|(% colspan="2" %)(((
2221 +|(% rowspan="2" style="text-align:center" %)F7.03|(% style="text-align:center" %)Keyboard run displays parameter 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3420
2222 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2235 2235  LED units place: First group display
2236 2236  
2237 2237  0: Output frequency
... ... @@ -2272,8 +2272,8 @@
2272 2272  
2273 2273  LED thousands place: Fourth group display
2274 2274  )))
2275 -|(% rowspan="2" %)F7.04|Keyboard run displays parameter 2|Factory default|0000
2276 -|Setting range|(% colspan="2" %)(((
2263 +|(% rowspan="2" style="text-align:center" %)F7.04|(% style="text-align:center" %)Keyboard run displays parameter 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0000
2264 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2277 2277  LED units place: First group display
2278 2278  
2279 2279  0: No displayed
... ... @@ -2308,14 +2308,14 @@
2308 2308  
2309 2309  F: Auxiliary frequency Y is displayed
2310 2310  
2311 -LED ten: second group display
2299 +LED ten: Second group display
2312 2312  
2313 2313  LED hundreds place: Third group display
2314 2314  
2315 2315  LED thousands place: Fourth group display
2316 2316  )))
2317 -|(% rowspan="2" %)F7.05|Keyboard stop displays parameters|Factory default|3421
2318 -|Setting range|(% colspan="2" %)(((
2305 +|(% rowspan="2" style="text-align:center" %)F7.05|(% style="text-align:center" %)Keyboard stop displays parameters|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3421
2306 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2319 2319  LED units place: First group display
2320 2320  
2321 2321  0: Output frequency
... ... @@ -2359,20 +2359,19 @@
2359 2359  
2360 2360  Control four groups of display parameters. For example, if output frequency, bus voltage, output current, and output voltage need to be displayed during operation, set the corresponding value 3420 one by one in bits to kilos.
2361 2361  
2350 +|(% rowspan="2" style="text-align:center" %)F7.06|(% style="text-align:center" %)Load speed display factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.000
2351 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.001 to 65.000
2362 2362  
2363 -|(% rowspan="2" %)F7.06|Load speed display factor|Factory default|1.000
2364 -|Setting range|(% colspan="2" %)0.001 to 65.000
2365 -
2366 2366  Through this parameter, the output frequency of the inverter is corresponding to the load speed, load speed = output frequency /F2.04*F2.05*F7.06.
2367 2367  
2368 -|(% rowspan="2" %)F7.14|High cumulative power consumption|Factory default|
2369 -|Setting range|(% colspan="2" %)(((
2355 +|(% rowspan="2" style="text-align:center" %)F7.14|(% style="text-align:center" %)High cumulative power consumption|(% style="text-align:center" %)Factory default|
2356 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2370 2370  Power consumption = F7.14*65535+F7.15
2371 2371  
2372 2372  Unit: kWh
2373 2373  )))
2374 -|(% rowspan="2" %)F7.15|Low cumulative power consumption|Factory default|
2375 -|Setting range|(% colspan="2" %)(((
2361 +|(% rowspan="2" style="text-align:center" %)F7.15|(% style="text-align:center" %)Low cumulative power consumption|(% style="text-align:center" %)Factory default|
2362 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2376 2376  Power consumption=F7.14*65535+F7.15
2377 2377  
2378 2378  Unit: kWh
... ... @@ -2380,32 +2380,29 @@
2380 2380  
2381 2381  When the inverter power is large, the 16-bit power consumption parameter will overflow quickly, so two parameters are used to represent the power consumption, that is, 32 digits.
2382 2382  
2383 -|(% rowspan="2" %)F7.16|Output power correction factor|Factory default|100.0%
2384 -|Setting range|(% colspan="2" %)0 to 100.0%
2370 +|(% rowspan="2" style="text-align:center" %)F7.16|(% style="text-align:center" %)Output power correction factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
2371 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 100.0%
2385 2385  
2386 2386  Used to correct the actual output power of the motor.
2387 2387  
2388 -|(% rowspan="2" %)F7.17|Power display dimension selection|Factory default|1
2389 -|Setting range|(% colspan="2" %)(((
2375 +|(% rowspan="2" style="text-align:center" %)F7.17|(% style="text-align:center" %)Power display dimension selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2376 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)(((
2390 2390  0 to Power display percentage ~(%)
2391 2391  
2392 2392  1 to Power display kilowatts (kW)
2393 2393  )))
2394 2394  
2395 -
2396 -
2397 2397  Used to select the dimension of power display D0.05, 0 is displayed in the ratio of output power to motor power, and 1 is displayed in KW.
2398 2398  
2384 +== **F8 group accessibility** ==
2399 2399  
2400 -**F8 group accessibility**
2386 +|(% rowspan="2" style="text-align:center" %)F8.00|(% style="text-align:center" %)JOG running frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00Hz
2387 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency F0.10
2388 +|(% rowspan="2" style="text-align:center" %)F8.01|(% style="text-align:center" %)JOG acceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0s
2389 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01s to 6500.0s
2390 +|(% rowspan="2" style="text-align:center" %)F8.02|(% style="text-align:center" %)JOG deceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0s
2391 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01s to 6500.0s
2401 2401  
2402 -|(% rowspan="2" %)F8.00|JOG running frequency|Factory default|2.00Hz
2403 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency F0.10
2404 -|(% rowspan="2" %)F8.01|JOG acceleration time|Factory default|20.0s
2405 -|Setting range|(% colspan="2" %)0.01s to 6500.0s
2406 -|(% rowspan="2" %)F8.02|JOG deceleration time|Factory default|20.0s
2407 -|Setting range|(% colspan="2" %)0.01s to 6500.0s
2408 -
2409 2409  Define the given frequency and acceleration/deceleration time of the inverter during jog. The jog process starts and stops according to start mode 0 (F1.00, direct start) and stop mode 0 (F1.10, decelerate to stop).
2410 2410  
2411 2411  Jog acceleration time refers to the time required for the inverter to accelerate from 0Hz to the maximum output frequency (F0.10).
... ... @@ -2412,39 +2412,39 @@
2412 2412  
2413 2413  Jog deceleration time refers to the time required for the inverter to decelerate from the maximum output frequency (F0.10) to 0Hz..
2414 2414  
2415 -|(% rowspan="2" %)F8.09|Emergency stop deceleration time|Factory default|Model determination
2416 -|Setting range|(% colspan="2" %)0. 01s to 6500.0s
2399 +|(% rowspan="2" style="text-align:center" %)F8.09|(% style="text-align:center" %)Emergency stop deceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
2400 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0. 01s to 6500.0s
2417 2417  
2418 2418  The terminal is set to downtime in case of emergency stop.
2419 2419  
2420 -|(% rowspan="2" %)F8.10|Jump frequency 1|Factory default|0.00Hz
2421 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2422 -|(% rowspan="2" %)F8.11|Jump frequency 2|Factory default|0.00Hz
2423 -|Setting range|(% colspan="2" %)0.00 Hz to Maximum frequency
2424 -|(% rowspan="2" %)F8.12|Jump frequency amplitude|Factory default|0.01Hz
2425 -|Setting range|(% colspan="2" %)0.00 to Maximum frequency
2404 +|(% rowspan="2" style="text-align:center" %)F8.10|(% style="text-align:center" %)Jump frequency 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00Hz
2405 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency
2406 +|(% rowspan="2" style="text-align:center" %)F8.11|(% style="text-align:center" %)Jump frequency 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00Hz
2407 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 Hz to Maximum frequency
2408 +|(% rowspan="2" style="text-align:center" %)F8.12|(% style="text-align:center" %)Jump frequency amplitude|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.01Hz
2409 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Maximum frequency
2426 2426  
2427 2427  When the set frequency is within the jump frequency range, the actual running frequency will run at the jump frequency boundary closer to the set frequency. By setting the jump frequency, the VFD can avoid the mechanical resonance point of the load. The inverter can be configured with two jump frequency points. This function does not work if both jump frequencies are set to 0.
2428 2428  
2429 -[[image:1763107356713-939.png]]
2413 +(% style="text-align:center" %)
2414 +(((
2415 +(% style="display:inline-block" %)
2416 +[[Figure 9-8-1 Jump frequency diagram>>image:1763107356713-939.png]]
2417 +)))
2430 2430  
2419 +|(% rowspan="2" style="text-align:center" %)F8.13|(% style="text-align:center" %)Reversible dead zone time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
2420 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 120.0s
2431 2431  
2432 -Figure 9-8-1 Jump frequency diagram
2433 -
2434 -
2435 -|(% rowspan="2" %)F8.13|Reversible dead zone time|Factory default|0.0s
2436 -|Setting range|(% colspan="2" %)0.0 to 120.0s
2437 -
2438 2438  Set the transition time at the output zero frequency during the positive and negative transition of the inverter, as shown below:
2439 2439  
2440 -[[image:1763107356720-587.png]]
2424 +(% style="text-align:center" %)
2425 +(((
2426 +(% style="display:inline-block" %)
2427 +[[Figure 9-8-2 Reverse rotation dead zone time diagram>>image:1763107356720-587.png]]
2428 +)))
2441 2441  
2442 -
2443 -Figure 9-8-2 Reverse rotation dead zone time diagram
2444 -
2445 -
2446 -|(% rowspan="2" %)F8.14|The carrier frequency is adjusted with temperature|Factory default|1
2447 -|Setting range|(% colspan="2" %)(((
2430 +|(% rowspan="2" style="text-align:center" %)F8.14|(% style="text-align:center" %)The carrier frequency is adjusted with temperature|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2431 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2448 2448  0: Temperature independent
2449 2449  
2450 2450  1:Temperature dependent, >75, 1.0Khz
... ... @@ -2452,8 +2452,8 @@
2452 2452  
2453 2453  Effective carrier frequency temperature adjustment means that the VFD can automatically adjust the carrier frequency according to its own temperature. Select this function to reduce the chances of VFD overheating alarm.
2454 2454  
2455 -|(% rowspan="2" %)F8.15|Terminal action is preferred|Factory default|1
2456 -|Setting range|(% colspan="2" %)(((
2439 +|(% rowspan="2" style="text-align:center" %)F8.15|(% style="text-align:center" %)Terminal action is preferred|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2440 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2457 2457  0: Invalid
2458 2458  
2459 2459  1: Valid
... ... @@ -2463,33 +2463,37 @@
2463 2463  
2464 2464  1: If the running command and the point-action command exist at the same time, the point-action command takes precedence.
2465 2465  
2466 -|(% rowspan="2" %)F8.16|Set the cumulative power-on arrival time|Factory default|0h
2467 -|Setting range|(% colspan="2" %)0h to 65000h
2450 +|(% rowspan="2" style="text-align:center" %)F8.16|(% style="text-align:center" %)Set the cumulative power-on arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0h
2451 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h
2468 2468  
2469 2469  Pre-set the power-on time of the inverter. When the cumulative power-on time (F7.13) reaches the set power-on time, set the DO output function, and the inverter multi-function digital DO output running time arrival signal.
2470 2470  
2471 -|(% rowspan="2" %)F8.17|Set the cumulative run arrival time|Factory default|65000h
2472 -|Setting range|(% colspan="2" %)0h to 65000h
2455 +|(% rowspan="2" style="text-align:center" %)F8.17|(% style="text-align:center" %)Set the cumulative run arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)65000h
2456 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h
2473 2473  
2474 2474  Pre-set the running time of the inverter. When the accumulated running time (F7.09) reaches this set running time, set the DO output function, the inverter multi-functional digital DO output running time arrival signal.
2475 2475  
2476 -|(% rowspan="2" %)F8.20|Arrival time of this run|Factory default|0
2477 -|Setting range|(% colspan="2" %)0 to 65000min
2460 +|(% rowspan="2" style="text-align:center" %)F8.20|(% style="text-align:center" %)Arrival time of this run|(% style="text-align:center" %)Factory default|0
2461 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65000min
2478 2478  
2479 2479  Set the current running time, shutdown clear zero.
2480 2480  
2481 -|(% rowspan="2" %)F8.22|Frequency detection value (FDT1)|Factory default|50.00Hz
2482 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2483 -|(% rowspan="2" %)F8.23|Frequency Detection Lag value (FDT1)|Factory default|5.0%
2484 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT1 Electric level)
2485 -|(% rowspan="2" %)F8.24|Frequency detection value (FDT2)|Factory default|50.00Hz
2486 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2487 -|(% rowspan="2" %)F8.25|Frequency detection lag value (FDT2)|Factory default|5.0%
2488 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT2 Electric level)
2465 +|(% rowspan="2" style="text-align:center" %)F8.22|(% style="text-align:center" %)Frequency detection value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
2466 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency
2467 +|(% rowspan="2" style="text-align:center" %)F8.23|(% style="text-align:center" %)Frequency Detection Lag value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0%
2468 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT1 Electric level)
2469 +|(% rowspan="2" style="text-align:center" %)F8.24|(% style="text-align:center" %)Frequency detection value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
2470 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency
2471 +|(% rowspan="2" style="text-align:center" %)F8.25|(% style="text-align:center" %)Frequency detection lag value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0%
2472 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT2 Electric level)
2489 2489  
2490 2490  Set the detection value of the output frequency and the lag value of the output action release.
2491 2491  
2492 -[[image:1763107356721-853.png]]
2476 +(% style="text-align:center" %)
2477 +(((
2478 +(% style="display:inline-block" %)
2479 +[[Caption>>image:1763107356721-853.png]]
2480 +)))
2493 2493  
2494 2494  Figure 9-8-3 Schematic diagram of FDT1 level
2495 2495