Changes for page 09 Function code
Last modified by Iris on 2025/11/17 14:59
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -1739,94 +1739,90 @@ 1739 1739 1740 1740 The VC series VFD standard unit has 2 multi-function relay output terminals, 1 FM terminal (which can be used as a high-speed pulse output terminal or as an open collector output), and 2 multi-function analog output terminals. 1741 1741 1742 -|(% rowspan="3" %)F6.00|(% colspan="2" %)FM Terminal output selection|Factory default|1 1743 -|(% rowspan="2" %)Setting range|0|(% colspan="2" %)Pulse output 1744 -|1|(% colspan="2" %)Open collector output (FMR) 1742 +|(% rowspan="3" style="text-align:center" %)F6.00|(% colspan="2" style="text-align:center" %)FM Terminal output selection|(% style="text-align:center" %)Factory default|1 1743 +|(% rowspan="2" style="text-align:center" %)Setting range|(% style="text-align:center" %)0|(% colspan="2" style="text-align:center" %)Pulse output 1744 +|(% style="text-align:center" %)1|(% colspan="2" style="text-align:center" %)Open collector output (FMR) 1745 1745 1746 1746 FM terminals are programmable multiplexed terminals. Can be used as a high speed pulse output terminal (FMP), pulse frequency up to 100kHz. Refer to F6.06 for FMP related functions. Also available as an open collector output terminal (FMR). See F6.01 for FMR functions. 1747 1747 1748 1748 FMP function needs hardware support. 1749 1749 1750 -|F6.01|FMR Open collector output selection|Factory default|0 1751 -|F6.02|Relay 1 output selection|Factory default|2 1752 -|F6.03|Relay 2 output selection (Extended)|Factory default|0 1753 -|F6.06|VDO1 output selection|Factory default|0 1754 -|F6.07|VDO2 output selection|Factory default|0 1755 -|F6.08|VDO3 output selection|Factory default|0 1750 +|(% style="text-align:center" %)F6.01|(% style="text-align:center" %)FMR Open collector output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1751 +|(% style="text-align:center" %)F6.02|(% style="text-align:center" %)Relay 1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2 1752 +|(% style="text-align:center" %)F6.03|(% style="text-align:center" %)Relay 2 output selection (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1753 +|(% style="text-align:center" %)F6.06|(% style="text-align:center" %)VDO1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1754 +|(% style="text-align:center" %)F6.07|(% style="text-align:center" %)VDO2 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1755 +|(% style="text-align:center" %)F6.08|(% style="text-align:center" %)VDO3 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1756 1756 1757 - 1758 - 1759 1759 Multi-function output terminal function selection are as follows: 1760 1760 1761 -|**Setting value**|**Function**|**Description** 1762 -|0|No-output|The output terminal has no function 1763 -|1|VFD in operation|Indicates that the inverter is running, there is an output frequency (can be zero) at this time output ON signal. 1764 -|2|Fault output|When the inverter fails and fails to stop, the output ON signal. 1765 -|3|Frequency level detects FDT arrival|Please refer to function codes F8.19 and F8.20 for detailed instructions 1766 -|4|Frequency arrival|Please refer to function code F8.26 for detailed instructions. 1767 -|5|Running at zero speed|The VFD operates and the output frequency is 0, and the output signal is ON. 1768 -|6|Motor overload pre-alarm|Before the motor electronic thermal protection action, according to the overload forecast value, after exceeding the forecast value output ON signal. Motor overload parameters are set in FA.00 to FA.02. 1769 -|7|Inverter overload pre-alarm|After checking the inverter overload, 10s before the protection occurs. Output ON signal. 1770 -|8|Set count pulse value to arrive|When the count value reaches the value set by FB.08, the ON signal is output. 1771 -|9|Specified count pulse value arrived|When the count value reaches the value set by FB.09, the ON signal is output. For the counting function, see FB group function description 1772 -|10|Length reached|When the actual length of the detection exceeds the length set by FB.05, the ON signal is output. 1773 -|11|PLC cycle complete|When the simple PLC completes a cycle, it outputs a pulse signal with a width of 250ms. 1774 -|12|Cumulative running time arrived|When the accumulated running time of the inverter exceeds the time set by F8.17, the output ON signal. 1775 -|13|-|- 1776 -|14|Torque limit|When the torque limit function is operated, the stall protection function automatically acts, automatically changes the output frequency, and the output ON signal indicates that the output torque is limited. This output signal can be used to reduce the load or to display an overload status signal on the monitoring device. 1777 -|15|Operational readiness|The main circuit and control circuit power supply are established, the inverter protection function is not active, and the inverter is in the running state, the ON signal is output. 1778 -|16|AI1>AI2|When the value of the analog input AI1 is greater than that of the other input AI2, the ON signal is output. 1779 -|17|Frequency upper limit reached|Output ON signal when the operating frequency reaches the upper limit frequency. 1780 -|18|((( 1759 +(% style="margin-left:auto; margin-right:auto" %) 1760 +|=**Setting value**|=**Function**|=**Description** 1761 +|=0|No-output|The output terminal has no function 1762 +|=1|VFD in operation|Indicates that the inverter is running, there is an output frequency (can be zero) at this time output ON signal. 1763 +|=2|Fault output|When the inverter fails and fails to stop, the output ON signal. 1764 +|=3|Frequency level detects FDT arrival|Please refer to function codes F8.19 and F8.20 for detailed instructions 1765 +|=4|Frequency arrival|Please refer to function code F8.26 for detailed instructions. 1766 +|=5|Running at zero speed|The VFD operates and the output frequency is 0, and the output signal is ON. 1767 +|=6|Motor overload pre-alarm|Before the motor electronic thermal protection action, according to the overload forecast value, after exceeding the forecast value output ON signal. Motor overload parameters are set in FA.00 to FA.02. 1768 +|=7|Inverter overload pre-alarm|After checking the inverter overload, 10s before the protection occurs. Output ON signal. 1769 +|=8|Set count pulse value to arrive|When the count value reaches the value set by FB.08, the ON signal is output. 1770 +|=9|Specified count pulse value arrived|When the count value reaches the value set by FB.09, the ON signal is output. For the counting function, see FB group function description 1771 +|=10|Length reached|When the actual length of the detection exceeds the length set by FB.05, the ON signal is output. 1772 +|=11|PLC cycle complete|When the simple PLC completes a cycle, it outputs a pulse signal with a width of 250ms. 1773 +|=12|Cumulative running time arrived|When the accumulated running time of the inverter exceeds the time set by F8.17, the output ON signal. 1774 +|=13|-|- 1775 +|=14|Torque limit|When the torque limit function is operated, the stall protection function automatically acts, automatically changes the output frequency, and the output ON signal indicates that the output torque is limited. This output signal can be used to reduce the load or to display an overload status signal on the monitoring device. 1776 +|=15|Operational readiness|The main circuit and control circuit power supply are established, the inverter protection function is not active, and the inverter is in the running state, the ON signal is output. 1777 +|=16|AI1>AI2|When the value of the analog input AI1 is greater than that of the other input AI2, the ON signal is output. 1778 +|=17|Frequency upper limit reached|Output ON signal when the operating frequency reaches the upper limit frequency. 1779 +|=18|((( 1781 1781 Frequency lower limit reached 1782 1782 1783 1783 (Run related) 1784 1784 )))|Output ON signal when the operating frequency reaches the lower limit frequency. In the shutdown state, the signal is always OFF. 1785 -|19|Undervoltage state output|The inverter outputs ON signal when it is undervoltage. 1786 -|20|Communication setting|See related instructions in the communication protocol 1787 -|21|Positioning completed|Reserve 1788 -|22|Positioning close|Reserve 1789 -|23|((( 1784 +|=19|Undervoltage state output|The inverter outputs ON signal when it is undervoltage. 1785 +|=20|Communication setting|See related instructions in the communication protocol 1786 +|=21|Positioning completed|Reserve 1787 +|=22|Positioning close|Reserve 1788 +|=23|((( 1790 1790 Zero speed running 2 1791 1791 1792 1792 (Also output when shut down) 1793 1793 )))|VFD output frequency is 0, output ON signal (shutdown also output). 1794 -|24|Accumulative power-on time reached|When F7.13(the accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output. 1795 -|25|((( 1793 +|=24|Accumulative power-on time reached|When F7.13(the accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output. 1794 +|=25|((( 1796 1796 Frequency level detection 1797 1797 1798 1798 FDT2 output 1799 1799 )))|For details, see function codes F8.28 and F8.29. 1800 -|26|Frequency to 1 output|For details, see function codes F8.30 and F8.31. 1801 -|27|Frequency to 2output|For details, see function codes F8.32 and F8.33. 1802 -|28|Current reaches 1 output|For details, see function codes F8.38 and F8.39. 1803 -|29|Current reaches 2 output|For details, see function codes F8.40 and F8.41. 1804 -|30|Timed arrival output|When F8.42(timing function selection) is effective, the VFD will output ON signal when the running time reaches the set timing time. 1805 -|31|-|- 1806 -|32|-| 1807 -|33|Running direction|When the inverter runs in reverse, the ON signal is output 1808 -|34|-| 1809 -|35|Module temperature reach| 1810 -|36|Software overcurrent output|For details, see function codes F8.36 and F8.37. 1811 -|37|((( 1799 +|=26|Frequency to 1 output|For details, see function codes F8.30 and F8.31. 1800 +|=27|Frequency to 2output|For details, see function codes F8.32 and F8.33. 1801 +|=28|Current reaches 1 output|For details, see function codes F8.38 and F8.39. 1802 +|=29|Current reaches 2 output|For details, see function codes F8.40 and F8.41. 1803 +|=30|Timed arrival output|When F8.42(timing function selection) is effective, the VFD will output ON signal when the running time reaches the set timing time. 1804 +|=31|-|- 1805 +|=32|-| 1806 +|=33|Running direction|When the inverter runs in reverse, the ON signal is output 1807 +|=34|-| 1808 +|=35|Module temperature reach| 1809 +|=36|Software overcurrent output|For details, see function codes F8.36 and F8.37. 1810 +|=37|((( 1812 1812 Lower limit frequency reached 1813 1813 1814 1814 (Run independent) 1815 1815 )))|Output ON signal when the operating frequency reaches the lower limit frequency. (When the conditions are met, the ON signal will also be output in the shutdown state) 1816 -|38|Fault output (Continue running)|When the inverter fails, output ON signal 1817 -|39|Reserve| 1818 -|40|The running time arrive| 1819 -|41|User defined output 1|User can define the conditions to output the terminal 1820 -|42|User-defined output 2|User can define the conditions to output the terminal 1821 -|43|Timer output|Output ON signal when the timing setting condition is met 1822 -|44|Forward running status|If the inverter is in forward running, output ON signal 1823 -|45|Reverse running status|If the inverter is in reverse running, output ON signal 1815 +|=38|Fault output (Continue running)|When the inverter fails, output ON signal 1816 +|=39|Reserve| 1817 +|=40|The running time arrive| 1818 +|=41|User defined output 1|User can define the conditions to output the terminal 1819 +|=42|User-defined output 2|User can define the conditions to output the terminal 1820 +|=43|Timer output|Output ON signal when the timing setting condition is met 1821 +|=44|Forward running status|If the inverter is in forward running, output ON signal 1822 +|=45|Reverse running status|If the inverter is in reverse running, output ON signal 1824 1824 1825 - 1826 - 1827 - 1828 -|(% rowspan="2" %)F6.10|AO output signal selection|Factory default|00 1829 -|Setting range|(% colspan="2" %)((( 1824 +|(% rowspan="2" style="text-align:center" %)F6.10|(% style="text-align:center" %)AO output signal selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)00 1825 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 1830 1830 The ones place: AO1 1831 1831 1832 1832 0: 0 to 10V ... ... @@ -1846,8 +1846,8 @@ 1846 1846 1847 1847 All models 1 AO. 1848 1848 1849 -|(% rowspan="2" %)F6.11|FMP (Pulse output terminal) output selection|Factory default|0 1850 -|Setting range|(% colspan="2" %)((( 1845 +|(% rowspan="2" style="text-align:center" %)F6.11|(% style="text-align:center" %)FMP (Pulse output terminal) output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1846 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 1851 1851 0: Running frequency 1852 1852 1853 1853 1: Set the frequency ... ... @@ -1882,88 +1882,84 @@ 1882 1882 1883 1883 16: Bus voltage (0-1000V, corresponding to 0-10V) 1884 1884 ))) 1885 -|(% rowspan="2" %)F6.12|AO1 output selection|Factory default|0 1886 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range 1887 -|(% rowspan="2" %)F6.13|AO2 output selection (Extended)|Factory default|0 1888 -|Setting range|(% colspan="2" %)Consistent with F6.11 setting range 1881 +|(% rowspan="2" style="text-align:center" %)F6.12|(% style="text-align:center" %)AO1 output selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1882 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)Consistent with F6.11 setting range 1883 +|(% rowspan="2" style="text-align:center" %)F6.13|(% style="text-align:center" %)AO2 output selection (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1884 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)Consistent with F6.11 setting range 1889 1889 1890 1890 The standard output of the analog output (zero bias is 0, gain 1) is 0mA to 20mA (or 0V to 10V). 1891 1891 1892 1892 The range of corresponding quantities represented is shown in the following table: 1893 1893 1894 -|**Setting value**|**Function**|**Range** 1895 -|0|Operating frequency|0 to Maximum output frequency 1896 -|1|Setting frequency|0 toMaximum output frequency 1897 -|2|Output current|0 to2 times the rated motor current 1898 -|3|Output torque|0 to2 times the rated motor torque 1899 -|4|Output power|0 to 2 times rated power 1900 -|5|Output voltage|0 to 1.2 times rated voltage of inverter 1901 -|6|(% colspan="2" %)Reserve 1902 -|7|AI1|0V to10V 1903 -|8|AI2|0V to10V/0-20mA 1904 -|9|(% colspan="2" %)Reserve 1905 -|10|Length|0 to Maximum set length 1906 -|11|Count value|0 to Maximum count value 1907 -|12|Communication setting|-10000 to 10000 1908 -|13|Motor speed|0 to The maximum output frequency corresponds to the speed 1909 -|14|Output current|0 to 1000A, correspondence 0-10V 1910 -0 to 1000V, correspondence 0-10V 1911 -|15|Output voltage|0.0V to 1000.0V 1912 -|16|Bus voltage|0 to 1000V, correspondence 0-10V 1890 +(% style="margin-left:auto; margin-right:auto" %) 1891 +|=**Setting value**|=**Function**|=**Range** 1892 +|=0|(% style="text-align:center" %)Operating frequency|(% style="text-align:center" %)0 to Maximum output frequency 1893 +|=1|(% style="text-align:center" %)Setting frequency|(% style="text-align:center" %)0 to Maximum output frequency 1894 +|=2|(% style="text-align:center" %)Output current|(% style="text-align:center" %)0 to 2 times the rated motor current 1895 +|=3|(% style="text-align:center" %)Output torque|(% style="text-align:center" %)0 to 2 times the rated motor torque 1896 +|=4|(% style="text-align:center" %)Output power|(% style="text-align:center" %)0 to 2 times rated power 1897 +|=5|(% style="text-align:center" %)Output voltage|(% style="text-align:center" %)0 to 1.2 times rated voltage of inverter 1898 +|=6|(% colspan="2" style="text-align:center" %)Reserve 1899 +|=7|(% style="text-align:center" %)AI1|(% style="text-align:center" %)0V to10V 1900 +|=8|(% style="text-align:center" %)AI2|(% style="text-align:center" %)0V to 10V/0-20mA 1901 +|=9|(% colspan="2" style="text-align:center" %)Reserve 1902 +|=10|(% style="text-align:center" %)Length|(% style="text-align:center" %)0 to Maximum set length 1903 +|=11|(% style="text-align:center" %)Count value|(% style="text-align:center" %)0 to Maximum count value 1904 +|=12|(% style="text-align:center" %)Communication setting|(% style="text-align:center" %)-10000 to 10000 1905 +|=13|(% style="text-align:center" %)Motor speed|(% style="text-align:center" %)0 to The maximum output frequency corresponds to the speed 1906 +|=14|(% style="text-align:center" %)Output current|(% style="text-align:center" %)0 to 1000A, correspondence 0 to 10V 1907 +0 to 1000V, correspondence 0 to 10V 1908 +|=15|(% style="text-align:center" %)Output voltage|(% style="text-align:center" %)0.0V to 1000.0V 1909 +|=16|(% style="text-align:center" %)Bus voltage|(% style="text-align:center" %)0 to 1000V, correspondence 0 to 10V 1913 1913 1911 +|(% rowspan="2" style="text-align:center" %)F6.14|(% style="text-align:center" %)FM upper frequency output limit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.00kHz 1912 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 100.00kHz 1914 1914 1915 - 1916 -|(% rowspan="2" %)F6.14|FM upper frequency output limit|Factory default|20.00kHz 1917 -|Setting range|(% colspan="2" %)0.00 to- 50.00kHz 1918 - 1919 - 1920 - 1921 1921 F6.00 maximum frequency of pulse output when selecting pulse output. 1922 1922 1923 -|(% rowspan="2" %)F6.15|AO1 minimum input|Factory default|0.00V 1924 -|Setting range|(% colspan="2" %)0.00V to F6.17 1925 -|(% rowspan="2" %)F6.16|AO1 the minimum input corresponds to the setting|Factory default|0.0% 1926 -|Setting range|(% colspan="2" %)0.0% to +100.0% 1927 -|(% rowspan="2" %)F6.17|AO1 maximum input|Factory default|10.00V 1928 -|Setting range|(% colspan="2" %)F6.15 to +10.00V 1929 -|(% rowspan="2" %)F6.18|AO1 the maximum input corresponds to the setting|Factory default|100.0% 1930 -|Setting range|(% colspan="2" %)0.0% to +100.0% 1916 +|(% rowspan="2" style="text-align:center" %)F6.15|(% style="text-align:center" %)AO1 minimum input|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00V 1917 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00V to F6.17 1918 +|(% rowspan="2" style="text-align:center" %)F6.16|(% style="text-align:center" %)AO1 the minimum input corresponds to the setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0% 1919 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to +100.0% 1920 +|(% rowspan="2" style="text-align:center" %)F6.17|(% style="text-align:center" %)AO1 maximum input|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)10.00V 1921 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F6.15 to +10.00V 1922 +|(% rowspan="2" style="text-align:center" %)F6.18|(% style="text-align:center" %)AO1 the maximum input corresponds to the setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0% 1923 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to +100.0% 1931 1931 1932 1932 The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application. 1933 1933 1934 -|(% rowspan="2" %)F6.19|AO2 minimum input (Extended)|Factory default|(% colspan="2" %)0.00V 1935 -|Setting range|(% colspan="3" %)0.00V to F6.21 1936 -|(% rowspan="2" %)F6.20|AO2 minimum Input mapping Settings (Extended)|(% colspan="2" %)Factory default|0.0% 1937 -|Setting range|(% colspan="3" %)0.0% to +100.0% 1938 -|(% rowspan="2" %)F6.21|AO2 maximum input (Extended)|(% colspan="2" %)Factory default|10.00V 1939 -|Setting range|(% colspan="3" %)F6.19 to +10.00V 1940 -|(% rowspan="2" %)F6.22|AO2 maximum input corresponding Settings (Extended)|(% colspan="2" %)Factory default|100.0% 1941 -|Setting range|(% colspan="3" %)0.0% to +100.0% 1942 -|(% rowspan="2" %)F6.23|FMR turn-on delay time|(% colspan="2" %)Factory default|0.0s 1943 -|Setting range|(% colspan="3" %)0.0s to 3600.0s 1927 +|(% rowspan="2" style="text-align:center" %)F6.19|(% style="text-align:center" %)AO2 minimum input (Extended)|(% style="text-align:center" %)Factory default|(% colspan="2" style="text-align:center" %)0.00V 1928 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.00V to F6.21 1929 +|(% rowspan="2" style="text-align:center" %)F6.20|(% style="text-align:center" %)AO2 minimum Input mapping Settings (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0% 1930 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0% to +100.0% 1931 +|(% rowspan="2" style="text-align:center" %)F6.21|(% style="text-align:center" %)AO2 maximum input (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)10.00V 1932 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)F6.19 to +10.00V 1933 +|(% rowspan="2" style="text-align:center" %)F6.22|(% style="text-align:center" %)AO2 maximum input corresponding Settings (Extended)|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0% 1934 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0% to +100.0% 1935 +|(% rowspan="2" style="text-align:center" %)F6.23|(% style="text-align:center" %)FMR turn-on delay time|(% colspan="2" style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1936 +|(% style="text-align:center" %)Setting range|(% colspan="3" style="text-align:center" %)0.0s to 3600.0s 1944 1944 1945 1945 The above function code defines the relationship between the analog output voltage and the set value represented by the analog output. When the analog output voltage exceeds the set maximum output range, the other part will be calculated as the maximum output; when the analog output voltage exceeds the set minimum output range, the other part will be calculated according to the AO minimum output. When the analog output is a current output, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to the simulated 100% is different, please refer to the description of each application. 1946 1946 1940 +|(% rowspan="2" style="text-align:center" %)F6.24|(% style="text-align:center" %)Relay 1 on delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1941 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1942 +|(% rowspan="2" style="text-align:center" %)F6.25|(% style="text-align:center" %)Relay 2 turn-on delay time (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1943 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1944 +|(% rowspan="2" style="text-align:center" %)F6.26|(% style="text-align:center" %)VDO connection delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1945 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1946 +|(% rowspan="2" style="text-align:center" %)F6.27|(% style="text-align:center" %)FMR disconnect delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1947 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1948 +|(% rowspan="2" style="text-align:center" %)F6.28|(% style="text-align:center" %)Relay 1 disconnect delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1949 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1950 +|(% rowspan="2" style="text-align:center" %)F6.29|(% style="text-align:center" %)Relay 2 disconnect delay time (Extended)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1951 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1952 +|(% rowspan="2" style="text-align:center" %)F6.30|(% style="text-align:center" %)VDO1 disconnect delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 1953 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 3600.0s 1947 1947 1948 -|(% rowspan="2" %)F6.24|Relay 1 on delay time|Factory default|0.0s 1949 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1950 -|(% rowspan="2" %)F6.25|Relay 2 turn-on delay time (Extended)|Factory default|0.0s 1951 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1952 -|(% rowspan="2" %)F6.26|VDO connection delay|Factory default|0.0s 1953 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1954 -|(% rowspan="2" %)F6.27|FMR disconnect delay time|Factory default|0.0s 1955 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1956 -|(% rowspan="2" %)F6.28|Relay 1 disconnect delay time|Factory default|0.0s 1957 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1958 -|(% rowspan="2" %)F6.29|Relay 2 disconnect delay time (Extended)|Factory default|0.0s 1959 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1960 -|(% rowspan="2" %)F6.30|VDO1 disconnect delay|Factory default|0.0s 1961 -|Setting range|(% colspan="2" %)0.0s to 3600.0s 1962 - 1963 1963 Set the delay time of output terminals FMR, relay 1, relay 2, VDO from the change of state to the change of output. 1964 1964 1965 -|(% rowspan="2" %)F6.31|Output terminal valid status Select 1|Factory default|000 1966 -|Setting range|(% colspan="2" %)((( 1957 +|(% rowspan="2" style="text-align:center" %)F6.31|(% style="text-align:center" %)Output terminal valid status Select 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)000 1958 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 1967 1967 0: Positive logic 1968 1968 1969 1969 1: Reverse logic ... ... @@ -1976,8 +1976,8 @@ 1976 1976 1977 1977 Thousands place: - 1978 1978 ))) 1979 -|(% rowspan="2" %)F6.32|Virtual output terminal valid status Select 2|Factory default|000 1980 -|Setting range|(% colspan="2" %)((( 1971 +|(% rowspan="2" style="text-align:center" %)F6.32|(% style="text-align:center" %)Virtual output terminal valid status Select 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)000 1972 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 1981 1981 0: Positive logic 1982 1982 1983 1983 1: Reverse logic ... ... @@ -1997,8 +1997,8 @@ 1997 1997 1998 1998 Inverse logic: The digital output terminal is not connected to the corresponding public end, and the disconnect is valid. 1999 1999 2000 -|(% rowspan="2" %)F6.33|User-defined output selection (EX) 1|Factory default|0 2001 -|Setting range|(% colspan="2" %)((( 1992 +|(% rowspan="2" style="text-align:center" %)F6.33|(% style="text-align:center" %)User-defined output selection (EX) 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 1993 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2002 2002 0: The running frequency 2003 2003 2004 2004 1: Set the frequency ... ... @@ -2024,9 +2024,8 @@ 2024 2024 2025 2025 This parameter is used to select a reference variable for the custom output. Take the selected variable EX as the operation comparison object. 2026 2026 2027 - 2028 -|(% rowspan="2" %)F6.34|The comparison method chosen by the user 1|Factory default|0 2029 -|Setting range|(% colspan="2" %)((( 2019 +|(% rowspan="2" style="text-align:center" %)F6.34|(% style="text-align:center" %)The comparison method chosen by the user 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2020 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2030 2030 Units: Compare test methods 2031 2031 2032 2032 0: Equal to (EX == X1) ... ... @@ -2050,17 +2050,17 @@ 2050 2050 2051 2051 The way the tens select the output. False value output is output if the condition is not met, and no output if it is met; Truth output is output only when the condition is met, and no output if the condition is not met. 2052 2052 2053 -|(% rowspan="2" %)F6.35|User-defined dead zone 1|Factory default|0 2054 -|Setting range|(% colspan="2" %)0 to 65535 2044 +|(% rowspan="2" style="text-align:center" %)F6.35|(% style="text-align:center" %)User-defined dead zone 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2045 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2055 2055 2056 2056 When the comparison test mode of F6.29 is set to greater than or equal to or less than or equal to, F6.30 is used to define the processing dead zone value centered on the comparison value X1. The processing dead zone has effect only on 1 and 2 of the comparison test mode of F6.29, and has no effect on 0, 3, and 4. For example, when F6.29 is set to 11, when EX is increased from 0 to greater than or equal to X1+F6.30, the output is valid; When EX is reduced to less than or equal to X1.F6.30, the output is invalid. 2057 2057 2058 -|(% rowspan="2" %)F6.36|User-defined 2 outputs the comparison value X1|Factory default|0 2059 -|Setting range|(% colspan="2" %)0 to 65535 2060 -|(% rowspan="2" %)F6.37|User-defined 2 outputs the comparison value X2|Factory default|0 2061 -|Setting range|(% colspan="2" %)0 to 65535 2062 -|(% rowspan="2" %)F6.38|User-defined output selection (EX) 2|Factory default|0 2063 -|Setting range|(% colspan="2" %)((( 2049 +|(% rowspan="2" style="text-align:center" %)F6.36|(% style="text-align:center" %)User-defined 2 outputs the comparison value X1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2050 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2051 +|(% rowspan="2" style="text-align:center" %)F6.37|(% style="text-align:center" %)User-defined 2 outputs the comparison value X2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2052 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2053 +|(% rowspan="2" style="text-align:center" %)F6.38|(% style="text-align:center" %)User-defined output selection (EX) 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2054 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2064 2064 0: Running frequency 2065 2065 2066 2066 1: Set the frequency ... ... @@ -2090,22 +2090,22 @@ 2090 2090 2091 2091 ~1. When the set frequency is greater than or equal to 20.00HZ, the relay is closed; 2092 2092 2093 -Set parameters as follows: F6.02 = 41 ,F6.28= 1,F6.29= 11,F6.30= 0,F6.31= 2000;2084 +Set parameters as follows: F6.02 = 41,F6.33 = 1,F6.34 = 11,F6.35 = 0,F6.36 = 2000; 2094 2094 2095 2095 2. When the bus voltage is less than or equal to 500.0V, the relay is closed; In order to avoid frequent operation of the relay when the detection voltage fluctuates 5.0V above and below 500.0V, it is required to process into a dead zone in the range of (500.0-5.0) to (500.0+5.0). 2096 2096 2097 -Set parameters as follows: F6.02 = 41 ,F6.28= 2,F6.29= 01,F6.30= 50,F6.31= 5000;2088 +Set parameters as follows: F6.02 = 41,F6.33 = 2,F6.34 = 01,F6.35 = 50,F6.36 = 5000; 2098 2098 2099 2099 3. When the inverter is required to reverse, the relay is closed: 2100 2100 2101 -Set parameters as follows: F6.02 = 41 ,F6.28=5,F6.29= 14,F6.31 = 8,F6.32= 8;2092 +Set parameters as follows: F6.02 = 41,F6.33 = 2,F6.34 = 01,F6.31 = 8,F6.37= 8; 2102 2102 2103 2103 4. When AI1 input is required to be greater than 3.00V and less than or equal to 6.00V, the relay is closed: 2104 2104 2105 -Set parameters as follows: F6.02 = 41 ,F6.28=13,F6.29=13,F6.31=300,F6.32=600; F6.33 to F6.37 is the same as F6.28 to F6.32.2096 +Set parameters as follows: F6.02 = 41,F6.33=13,F6.34=13,F6.36=300,F6.37=600 2106 2106 2107 -|(% rowspan="2" %)F6.39|The comparison method chosen by the user 2|Factory default|0 2108 -|Setting range|(% colspan="2" %)((( 2098 +|(% rowspan="2" style="text-align:center" %)F6.39|(% style="text-align:center" %)The comparison method chosen by the user 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2099 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2109 2109 Units: Compare test methods 2110 2110 2111 2111 0: Equal to (EX == X1) ... ... @@ -2124,18 +2124,17 @@ 2124 2124 2125 2125 1: Truth output 2126 2126 ))) 2127 -|(% rowspan="2" %)F6.40|User-defined dead zone 2|Factory default|0 2128 -|Setting range|(% colspan="2" %)0 to 65535 2129 -|(% rowspan="2" %)F6.41|User-defined 2 outputs the comparison value X1|Factory default|0 2130 -|Setting range|(% colspan="2" %)0 to 65535 2131 -|(% rowspan="2" %)F6.42|User-defined 2 Output comparison value X2|Factory default|0 2132 -|Setting range|(% colspan="2" %)0 to 65535 2118 +|(% rowspan="2" style="text-align:center" %)F6.40|(% style="text-align:center" %)User-defined dead zone 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2119 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2120 +|(% rowspan="2" style="text-align:center" %)F6.41|(% style="text-align:center" %)User-defined 2 outputs the comparison value X1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2121 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2122 +|(% rowspan="2" style="text-align:center" %)F6.42|(% style="text-align:center" %)User-defined 2 Output comparison value X2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2123 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2133 2133 2134 2134 Second output. The parameter setting mode is the same as F6.33 to F6.37. 2135 2135 2136 - 2137 -|(% rowspan="2" %)F6.43|Timer time unit|Factory default|0 2138 -|Setting range|(% colspan="2" %)((( 2127 +|(% rowspan="2" style="text-align:center" %)F6.43|(% style="text-align:center" %)Timer time unit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2128 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)((( 2139 2139 0: Second 2140 2140 2141 2141 1: Minute ... ... @@ -2142,22 +2142,21 @@ 2142 2142 2143 2143 2: Hour 2144 2144 ))) 2145 -|(% rowspan="2" %)F6.44|Timer maximum|Factory default|0 2146 -|Setting range|(% colspan="2" %)0 to 65535 (No more when set to 65000) 2147 -|(% rowspan="2" %)F6.45|Timer set value|Factory default|0 2148 -|Setting range|(% colspan="2" %)0 to 65535 2149 -|(% rowspan="2" %)F6.46|Counter maximum|Factory default|0 2150 -|Setting range|(% colspan="2" %)0 to 65535 2151 -|(% rowspan="2" %)F6.47|Counter set value|Factory default|0 2152 -|Setting range|(% colspan="2" %)0 to 65535 2135 +|(% rowspan="2" style="text-align:center" %)F6.44|(% style="text-align:center" %)Timer maximum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2136 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 (No more when set to 65000) 2137 +|(% rowspan="2" style="text-align:center" %)F6.45|(% style="text-align:center" %)Timer set value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2138 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2139 +|(% rowspan="2" style="text-align:center" %)F6.46|(% style="text-align:center" %)Counter maximum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2140 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2141 +|(% rowspan="2" style="text-align:center" %)F6.47|(% style="text-align:center" %)Counter set value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0 2142 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535 2153 2153 2154 2154 Set the timer time. 2155 2155 2146 +== **F7 group keyboard with display** == 2156 2156 2157 -**F7 group keyboard with display** 2158 - 2159 -|(% rowspan="2" %)F7.00|LCD keyboard parameter copy|Factory default|0 2160 -|Setting range|(% colspan="2" %)((( 2148 +|(% rowspan="2" style="text-align:center" %)F7.00|(% style="text-align:center; width:252px" %)LCD keyboard parameter copy|(% style="text-align:center; width:304px" %)Factory default|(% style="text-align:center" %)0 2149 +|(% style="text-align:center; width:252px" %)Setting range|(% colspan="2" style="width:398px" %)((( 2161 2161 0: No operation is performed 2162 2162 2163 2163 1: The function parameters of the machine are uploaded to the LCD keyboard ... ... @@ -2165,11 +2165,10 @@ 2165 2165 2: LCD keyboard function parameters download to the machine 2166 2166 ))) 2167 2167 2168 -**Note: LCD is not available.** 2157 +**✎Note: LCD is not available.** 2169 2169 2170 - 2171 -|(% rowspan="2" %)F7.01|ENT key function selection|Factory default|0 2172 -|Setting range|(% colspan="2" %)((( 2159 +|(% rowspan="2" style="text-align:center" %)F7.01|(% style="text-align:center; width:230px" %)ENT key function selection|(% style="text-align:center; width:314px" %)Factory default|(% style="text-align:center" %)0 2160 +|(% style="text-align:center; width:230px" %)Setting range|(% colspan="2" style="width:421px" %)((( 2173 2173 0: ENT is invalid 2174 2174 2175 2175 1: Switch between the command channel of the operation panel and the remote command channel (the remote command channel includes communication and terminal control) ... ... @@ -2209,8 +2209,8 @@ 2209 2209 2210 2210 Operating instructions: base for the initial menu, -C- for the debugging menu; ENT key to switch the menu, shift key to enter the corresponding menu; debugging menu displayed as CFxx.xx 2211 2211 2212 -|(% rowspan="2" %)F7.02|Keyboard STOP key range|Factory default|0011 2213 -|Setting range|(% colspan="2" %)((( 2200 +|(% rowspan="2" style="text-align:center" %)F7.02|(% style="text-align:center" %)Keyboard STOP key range|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0011 2201 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2214 2214 LED units place: Terminal control selection 2215 2215 2216 2216 0: The terminal command is invalid ... ... @@ -2228,10 +2228,10 @@ 2228 2228 LED thousands place: reserved 2229 2229 ))) 2230 2230 2231 -** Special note:** When the STOP button communication control is valid, if the machine is started by using the communication command and the machine is stopped by using the STOP button, it can be started only after the STOP command is issued before the next communication start.2219 +**✎Note:** When the STOP button communication control is valid, if the machine is started by using the communication command and the machine is stopped by using the STOP button, it can be started only after the STOP command is issued before the next communication start. 2232 2232 2233 -|(% rowspan="2" %)F7.03|Keyboard run displays parameter 1|Factory default|3420 2234 -|Setting range|(% colspan="2" %)((( 2221 +|(% rowspan="2" style="text-align:center" %)F7.03|(% style="text-align:center" %)Keyboard run displays parameter 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3420 2222 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2235 2235 LED units place: First group display 2236 2236 2237 2237 0: Output frequency ... ... @@ -2272,8 +2272,8 @@ 2272 2272 2273 2273 LED thousands place: Fourth group display 2274 2274 ))) 2275 -|(% rowspan="2" %)F7.04|Keyboard run displays parameter 2|Factory default|0000 2276 -|Setting range|(% colspan="2" %)((( 2263 +|(% rowspan="2" style="text-align:center" %)F7.04|(% style="text-align:center" %)Keyboard run displays parameter 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0000 2264 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2277 2277 LED units place: First group display 2278 2278 2279 2279 0: No displayed ... ... @@ -2308,14 +2308,14 @@ 2308 2308 2309 2309 F: Auxiliary frequency Y is displayed 2310 2310 2311 -LED ten: second group display2299 +LED ten: Second group display 2312 2312 2313 2313 LED hundreds place: Third group display 2314 2314 2315 2315 LED thousands place: Fourth group display 2316 2316 ))) 2317 -|(% rowspan="2" %)F7.05|Keyboard stop displays parameters|Factory default|3421 2318 -|Setting range|(% colspan="2" %)((( 2305 +|(% rowspan="2" style="text-align:center" %)F7.05|(% style="text-align:center" %)Keyboard stop displays parameters|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3421 2306 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2319 2319 LED units place: First group display 2320 2320 2321 2321 0: Output frequency ... ... @@ -2359,20 +2359,19 @@ 2359 2359 2360 2360 Control four groups of display parameters. For example, if output frequency, bus voltage, output current, and output voltage need to be displayed during operation, set the corresponding value 3420 one by one in bits to kilos. 2361 2361 2350 +|(% rowspan="2" style="text-align:center" %)F7.06|(% style="text-align:center" %)Load speed display factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.000 2351 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.001 to 65.000 2362 2362 2363 -|(% rowspan="2" %)F7.06|Load speed display factor|Factory default|1.000 2364 -|Setting range|(% colspan="2" %)0.001 to 65.000 2365 - 2366 2366 Through this parameter, the output frequency of the inverter is corresponding to the load speed, load speed = output frequency /F2.04*F2.05*F7.06. 2367 2367 2368 -|(% rowspan="2" %)F7.14|High cumulative power consumption|Factory default| 2369 -|Setting range|(% colspan="2" %)((( 2355 +|(% rowspan="2" style="text-align:center" %)F7.14|(% style="text-align:center" %)High cumulative power consumption|(% style="text-align:center" %)Factory default| 2356 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2370 2370 Power consumption = F7.14*65535+F7.15 2371 2371 2372 2372 Unit: kWh 2373 2373 ))) 2374 -|(% rowspan="2" %)F7.15|Low cumulative power consumption|Factory default| 2375 -|Setting range|(% colspan="2" %)((( 2361 +|(% rowspan="2" style="text-align:center" %)F7.15|(% style="text-align:center" %)Low cumulative power consumption|(% style="text-align:center" %)Factory default| 2362 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2376 2376 Power consumption=F7.14*65535+F7.15 2377 2377 2378 2378 Unit: kWh ... ... @@ -2380,32 +2380,29 @@ 2380 2380 2381 2381 When the inverter power is large, the 16-bit power consumption parameter will overflow quickly, so two parameters are used to represent the power consumption, that is, 32 digits. 2382 2382 2383 -|(% rowspan="2" %)F7.16|Output power correction factor|Factory default|100.0% 2384 -|Setting range|(% colspan="2" %)0 to 100.0% 2370 +|(% rowspan="2" style="text-align:center" %)F7.16|(% style="text-align:center" %)Output power correction factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0% 2371 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 100.0% 2385 2385 2386 2386 Used to correct the actual output power of the motor. 2387 2387 2388 -|(% rowspan="2" %)F7.17|Power display dimension selection|Factory default|1 2389 -|Setting range|(% colspan="2" %)((( 2375 +|(% rowspan="2" style="text-align:center" %)F7.17|(% style="text-align:center" %)Power display dimension selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1 2376 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)((( 2390 2390 0 to Power display percentage ~(%) 2391 2391 2392 2392 1 to Power display kilowatts (kW) 2393 2393 ))) 2394 2394 2395 - 2396 - 2397 2397 Used to select the dimension of power display D0.05, 0 is displayed in the ratio of output power to motor power, and 1 is displayed in KW. 2398 2398 2384 +== **F8 group accessibility** == 2399 2399 2400 -**F8 group accessibility** 2386 +|(% rowspan="2" style="text-align:center" %)F8.00|(% style="text-align:center" %)JOG running frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00Hz 2387 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency F0.10 2388 +|(% rowspan="2" style="text-align:center" %)F8.01|(% style="text-align:center" %)JOG acceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0s 2389 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01s to 6500.0s 2390 +|(% rowspan="2" style="text-align:center" %)F8.02|(% style="text-align:center" %)JOG deceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0s 2391 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01s to 6500.0s 2401 2401 2402 -|(% rowspan="2" %)F8.00|JOG running frequency|Factory default|2.00Hz 2403 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency F0.10 2404 -|(% rowspan="2" %)F8.01|JOG acceleration time|Factory default|20.0s 2405 -|Setting range|(% colspan="2" %)0.01s to 6500.0s 2406 -|(% rowspan="2" %)F8.02|JOG deceleration time|Factory default|20.0s 2407 -|Setting range|(% colspan="2" %)0.01s to 6500.0s 2408 - 2409 2409 Define the given frequency and acceleration/deceleration time of the inverter during jog. The jog process starts and stops according to start mode 0 (F1.00, direct start) and stop mode 0 (F1.10, decelerate to stop). 2410 2410 2411 2411 Jog acceleration time refers to the time required for the inverter to accelerate from 0Hz to the maximum output frequency (F0.10). ... ... @@ -2412,39 +2412,39 @@ 2412 2412 2413 2413 Jog deceleration time refers to the time required for the inverter to decelerate from the maximum output frequency (F0.10) to 0Hz.. 2414 2414 2415 -|(% rowspan="2" %)F8.09|Emergency stop deceleration time|Factory default|Model determination 2416 -|Setting range|(% colspan="2" %)0. 01s to 6500.0s 2399 +|(% rowspan="2" style="text-align:center" %)F8.09|(% style="text-align:center" %)Emergency stop deceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination 2400 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0. 01s to 6500.0s 2417 2417 2418 2418 The terminal is set to downtime in case of emergency stop. 2419 2419 2420 -|(% rowspan="2" %)F8.10|Jump frequency 1|Factory default|0.00Hz 2421 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency 2422 -|(% rowspan="2" %)F8.11|Jump frequency 2|Factory default|0.00Hz 2423 -|Setting range|(% colspan="2" %)0.00 Hz to Maximum frequency 2424 -|(% rowspan="2" %)F8.12|Jump frequency amplitude|Factory default|0.01Hz 2425 -|Setting range|(% colspan="2" %)0.00 to Maximum frequency 2404 +|(% rowspan="2" style="text-align:center" %)F8.10|(% style="text-align:center" %)Jump frequency 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00Hz 2405 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency 2406 +|(% rowspan="2" style="text-align:center" %)F8.11|(% style="text-align:center" %)Jump frequency 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00Hz 2407 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 Hz to Maximum frequency 2408 +|(% rowspan="2" style="text-align:center" %)F8.12|(% style="text-align:center" %)Jump frequency amplitude|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.01Hz 2409 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Maximum frequency 2426 2426 2427 2427 When the set frequency is within the jump frequency range, the actual running frequency will run at the jump frequency boundary closer to the set frequency. By setting the jump frequency, the VFD can avoid the mechanical resonance point of the load. The inverter can be configured with two jump frequency points. This function does not work if both jump frequencies are set to 0. 2428 2428 2429 -[[image:1763107356713-939.png]] 2413 +(% style="text-align:center" %) 2414 +((( 2415 +(% style="display:inline-block" %) 2416 +[[Figure 9-8-1 Jump frequency diagram>>image:1763107356713-939.png]] 2417 +))) 2430 2430 2419 +|(% rowspan="2" style="text-align:center" %)F8.13|(% style="text-align:center" %)Reversible dead zone time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s 2420 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 120.0s 2431 2431 2432 -Figure 9-8-1 Jump frequency diagram 2433 - 2434 - 2435 -|(% rowspan="2" %)F8.13|Reversible dead zone time|Factory default|0.0s 2436 -|Setting range|(% colspan="2" %)0.0 to 120.0s 2437 - 2438 2438 Set the transition time at the output zero frequency during the positive and negative transition of the inverter, as shown below: 2439 2439 2440 -[[image:1763107356720-587.png]] 2424 +(% style="text-align:center" %) 2425 +((( 2426 +(% style="display:inline-block" %) 2427 +[[Figure 9-8-2 Reverse rotation dead zone time diagram>>image:1763107356720-587.png]] 2428 +))) 2441 2441 2442 - 2443 -Figure 9-8-2 Reverse rotation dead zone time diagram 2444 - 2445 - 2446 -|(% rowspan="2" %)F8.14|The carrier frequency is adjusted with temperature|Factory default|1 2447 -|Setting range|(% colspan="2" %)((( 2430 +|(% rowspan="2" style="text-align:center" %)F8.14|(% style="text-align:center" %)The carrier frequency is adjusted with temperature|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1 2431 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2448 2448 0: Temperature independent 2449 2449 2450 2450 1:Temperature dependent, >75, 1.0Khz ... ... @@ -2452,8 +2452,8 @@ 2452 2452 2453 2453 Effective carrier frequency temperature adjustment means that the VFD can automatically adjust the carrier frequency according to its own temperature. Select this function to reduce the chances of VFD overheating alarm. 2454 2454 2455 -|(% rowspan="2" %)F8.15|Terminal action is preferred|Factory default|1 2456 -|Setting range|(% colspan="2" %)((( 2439 +|(% rowspan="2" style="text-align:center" %)F8.15|(% style="text-align:center" %)Terminal action is preferred|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1 2440 +|(% style="text-align:center" %)Setting range|(% colspan="2" %)((( 2457 2457 0: Invalid 2458 2458 2459 2459 1: Valid ... ... @@ -2463,33 +2463,37 @@ 2463 2463 2464 2464 1: If the running command and the point-action command exist at the same time, the point-action command takes precedence. 2465 2465 2466 -|(% rowspan="2" %)F8.16|Set the cumulative power-on arrival time|Factory default|0h 2467 -|Setting range|(% colspan="2" %)0h to 65000h 2450 +|(% rowspan="2" style="text-align:center" %)F8.16|(% style="text-align:center" %)Set the cumulative power-on arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0h 2451 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h 2468 2468 2469 2469 Pre-set the power-on time of the inverter. When the cumulative power-on time (F7.13) reaches the set power-on time, set the DO output function, and the inverter multi-function digital DO output running time arrival signal. 2470 2470 2471 -|(% rowspan="2" %)F8.17|Set the cumulative run arrival time|Factory default|65000h 2472 -|Setting range|(% colspan="2" %)0h to 65000h 2455 +|(% rowspan="2" style="text-align:center" %)F8.17|(% style="text-align:center" %)Set the cumulative run arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)65000h 2456 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h 2473 2473 2474 2474 Pre-set the running time of the inverter. When the accumulated running time (F7.09) reaches this set running time, set the DO output function, the inverter multi-functional digital DO output running time arrival signal. 2475 2475 2476 -|(% rowspan="2" %)F8.20|Arrival time of this run|Factory default|0 2477 -|Setting range|(% colspan="2" %)0 to 65000min 2460 +|(% rowspan="2" style="text-align:center" %)F8.20|(% style="text-align:center" %)Arrival time of this run|(% style="text-align:center" %)Factory default|0 2461 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65000min 2478 2478 2479 2479 Set the current running time, shutdown clear zero. 2480 2480 2481 -|(% rowspan="2" %)F8.22|Frequency detection value (FDT1)|Factory default|50.00Hz 2482 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency 2483 -|(% rowspan="2" %)F8.23|Frequency Detection Lag value (FDT1)|Factory default|5.0% 2484 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT1 Electric level) 2485 -|(% rowspan="2" %)F8.24|Frequency detection value (FDT2)|Factory default|50.00Hz 2486 -|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency 2487 -|(% rowspan="2" %)F8.25|Frequency detection lag value (FDT2)|Factory default|5.0% 2488 -|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT2 Electric level) 2465 +|(% rowspan="2" style="text-align:center" %)F8.22|(% style="text-align:center" %)Frequency detection value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz 2466 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency 2467 +|(% rowspan="2" style="text-align:center" %)F8.23|(% style="text-align:center" %)Frequency Detection Lag value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0% 2468 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT1 Electric level) 2469 +|(% rowspan="2" style="text-align:center" %)F8.24|(% style="text-align:center" %)Frequency detection value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz 2470 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency 2471 +|(% rowspan="2" style="text-align:center" %)F8.25|(% style="text-align:center" %)Frequency detection lag value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0% 2472 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT2 Electric level) 2489 2489 2490 2490 Set the detection value of the output frequency and the lag value of the output action release. 2491 2491 2492 -[[image:1763107356721-853.png]] 2476 +(% style="text-align:center" %) 2477 +((( 2478 +(% style="display:inline-block" %) 2479 +[[Caption>>image:1763107356721-853.png]] 2480 +))) 2493 2493 2494 2494 Figure 9-8-3 Schematic diagram of FDT1 level 2495 2495