Changes for page 09 Function code

Last modified by Iris on 2025/11/17 14:59

From version 14.1
edited by Iris
on 2025/11/17 14:59
Change comment: There is no comment for this version
To version 12.2
edited by Iris
on 2025/11/17 11:39
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -2424,11 +2424,15 @@
2424 2424  (% style="text-align:center" %)
2425 2425  (((
2426 2426  (% style="display:inline-block" %)
2427 -[[Figure 9-8-2 Reverse rotation dead zone time diagram>>image:1763107356720-587.png]]
2427 +[[Caption>>image:1763107356720-587.png]]
2428 2428  )))
2429 2429  
2430 -|(% rowspan="2" style="text-align:center" %)F8.14|(% style="text-align:center" %)The carrier frequency is adjusted with temperature|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2431 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2430 +
2431 +Figure 9-8-2 Reverse rotation dead zone time diagram
2432 +
2433 +
2434 +|(% rowspan="2" %)F8.14|The carrier frequency is adjusted with temperature|Factory default|1
2435 +|Setting range|(% colspan="2" %)(((
2432 2432  0: Temperature independent
2433 2433  
2434 2434  1:Temperature dependent, >75, 1.0Khz
... ... @@ -2436,8 +2436,8 @@
2436 2436  
2437 2437  Effective carrier frequency temperature adjustment means that the VFD can automatically adjust the carrier frequency according to its own temperature. Select this function to reduce the chances of VFD overheating alarm.
2438 2438  
2439 -|(% rowspan="2" style="text-align:center" %)F8.15|(% style="text-align:center" %)Terminal action is preferred|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2440 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2443 +|(% rowspan="2" %)F8.15|Terminal action is preferred|Factory default|1
2444 +|Setting range|(% colspan="2" %)(((
2441 2441  0: Invalid
2442 2442  
2443 2443  1: Valid
... ... @@ -2447,38 +2447,36 @@
2447 2447  
2448 2448  1: If the running command and the point-action command exist at the same time, the point-action command takes precedence.
2449 2449  
2450 -|(% rowspan="2" style="text-align:center" %)F8.16|(% style="text-align:center" %)Set the cumulative power-on arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0h
2451 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h
2454 +|(% rowspan="2" %)F8.16|Set the cumulative power-on arrival time|Factory default|0h
2455 +|Setting range|(% colspan="2" %)0h to 65000h
2452 2452  
2453 2453  Pre-set the power-on time of the inverter. When the cumulative power-on time (F7.13) reaches the set power-on time, set the DO output function, and the inverter multi-function digital DO output running time arrival signal.
2454 2454  
2455 -|(% rowspan="2" style="text-align:center" %)F8.17|(% style="text-align:center" %)Set the cumulative run arrival time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)65000h
2456 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0h to 65000h
2459 +|(% rowspan="2" %)F8.17|Set the cumulative run arrival time|Factory default|65000h
2460 +|Setting range|(% colspan="2" %)0h to 65000h
2457 2457  
2458 2458  Pre-set the running time of the inverter. When the accumulated running time (F7.09) reaches this set running time, set the DO output function, the inverter multi-functional digital DO output running time arrival signal.
2459 2459  
2460 -|(% rowspan="2" style="text-align:center" %)F8.20|(% style="text-align:center" %)Arrival time of this run|(% style="text-align:center" %)Factory default|0
2461 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65000min
2464 +|(% rowspan="2" %)F8.20|Arrival time of this run|Factory default|0
2465 +|Setting range|(% colspan="2" %)0 to 65000min
2462 2462  
2463 2463  Set the current running time, shutdown clear zero.
2464 2464  
2465 -|(% rowspan="2" style="text-align:center" %)F8.22|(% style="text-align:center" %)Frequency detection value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
2466 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency
2467 -|(% rowspan="2" style="text-align:center" %)F8.23|(% style="text-align:center" %)Frequency Detection Lag value (FDT1)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0%
2468 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT1 Electric level)
2469 -|(% rowspan="2" style="text-align:center" %)F8.24|(% style="text-align:center" %)Frequency detection value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
2470 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00Hz to Maximum frequency
2471 -|(% rowspan="2" style="text-align:center" %)F8.25|(% style="text-align:center" %)Frequency detection lag value (FDT2)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0%
2472 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%(FDT2 Electric level)
2469 +|(% rowspan="2" %)F8.22|Frequency detection value (FDT1)|Factory default|50.00Hz
2470 +|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2471 +|(% rowspan="2" %)F8.23|Frequency Detection Lag value (FDT1)|Factory default|5.0%
2472 +|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT1 Electric level)
2473 +|(% rowspan="2" %)F8.24|Frequency detection value (FDT2)|Factory default|50.00Hz
2474 +|Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2475 +|(% rowspan="2" %)F8.25|Frequency detection lag value (FDT2)|Factory default|5.0%
2476 +|Setting range|(% colspan="2" %)0.0% to 100.0%(FDT2 Electric level)
2473 2473  
2474 2474  Set the detection value of the output frequency and the lag value of the output action release.
2475 2475  
2476 -(% style="text-align:center" %)
2477 -(((
2478 -(% style="display:inline-block" %)
2479 -[[Figure 9-8-3 Schematic diagram of FDT1 level>>image:1763107356721-853.png]]
2480 -)))
2480 +[[image:1763107356721-853.png]]
2481 2481  
2482 +Figure 9-8-3 Schematic diagram of FDT1 level
2483 +
2482 2482  |(% rowspan="2" %)F8.26|Frequency reaches the detection width|Factory default|0.0%
2483 2483  |Setting range|(% colspan="2" %)0.00 to 100% Maximum frequency
2484 2484  
... ... @@ -2486,12 +2486,10 @@
2486 2486  
2487 2487  As shown below:
2488 2488  
2489 -(% style="text-align:center" %)
2490 -(((
2491 -(% style="display:inline-block" %)
2492 -[[Figure 9-8-4 Schematic diagram of frequency arrival detection amplitude>>image:1763107356724-721.png]]
2493 -)))
2491 +[[image:1763107356724-721.png]]
2494 2494  
2493 +Figure 9-8-4 Schematic diagram of frequency arrival detection amplitude
2494 +
2495 2495  |(% rowspan="2" %)F8.27|Arbitrary reach frequency detection value 1|Factory default|50.00Hz
2496 2496  |Setting range|(% colspan="2" %)0.00Hz to Maximum frequency
2497 2497  |(% rowspan="2" %)F8.28|Arbitrary arrival frequency detection amplitude 1|Factory default|0.0%
... ... @@ -2501,78 +2501,83 @@
2501 2501  |(% rowspan="2" %)F8.30|Arbitrary arrival frequency detection amplitude 2|Factory default|0.0%
2502 2502  |Setting range|(% colspan="2" %)0.0% to 100.0% (Maximum frequency)
2503 2503  
2504 +
2505 +
2504 2504  When the output frequency of the inverter reaches the positive and negative detection amplitude of the frequency detection value 1 and 2, the output pulse signal.
2505 2505  
2506 2506  As shown below:
2507 2507  
2508 -(% style="text-align:center" %)
2509 -(((
2510 -(% style="display:inline-block" %)
2511 -[[Figure 9-8-5 Schematic diagram of detection of arbitrary arrival frequency>>image:1763107356727-432.png]]
2512 -)))
2510 +[[image:1763107356727-432.png]]
2513 2513  
2514 -|(% rowspan="2" style="text-align:center" %)F8.31|(% style="text-align:center" %)Arbitrary arrival current 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
2515 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0%-300.0% (Rated current of motor)
2516 -|(% rowspan="2" style="text-align:center" %)F8.32|(% style="text-align:center" %)Arbitrary arrival current 1 width|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
2517 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0%-300.0% (Rated current of motor)
2518 -|(% rowspan="2" style="text-align:center" %)F8.33|(% style="text-align:center" %)Arbitrary arrival current 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
2519 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 300.0%(Rated current of motor)
2520 -|(% rowspan="2" style="text-align:center" %)F8.34|(% style="text-align:center" %)Arbitrary arrival current 2 width|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
2521 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 300.0%(Rated current of motor)
2512 +Figure 9-8-5 Schematic diagram of detection of arbitrary arrival frequency
2522 2522  
2514 +
2515 +|(% rowspan="2" %)F8.31|Arbitrary arrival current 1|Factory default|100.0%
2516 +|Setting range|(% colspan="2" %)0.0%-300.0% (Rated current of motor)
2517 +|(% rowspan="2" %)F8.32|Arbitrary arrival current 1 width|Factory default|0.0%
2518 +|Setting range|(% colspan="2" %)0.0%-300.0% (Rated current of motor)
2519 +|(% rowspan="2" %)F8.33|Arbitrary arrival current 2|Factory default|100.0%
2520 +|Setting range|(% colspan="2" %)0.0% to 300.0%(Rated current of motor)
2521 +|(% rowspan="2" %)F8.34|Arbitrary arrival current 2 width|Factory default|0.0%
2522 +|Setting range|(% colspan="2" %)0.0% to 300.0%(Rated current of motor)
2523 +
2524 +
2525 +
2523 2523  When the output current of the inverter reaches any positive or negative detection width of current 1 and 2, output pulse signal.
2524 2524  
2525 2525  As shown below:
2526 2526  
2527 -(% style="text-align:center" %)
2528 -(((
2529 -(% style="display:inline-block" %)
2530 -[[Figure. 9-8-6 Schematic diagram of detection of arbitrary arrival frequency>>image:1763107356731-567.png]]
2531 -)))
2532 2532  
2533 -|(% rowspan="2" style="text-align:center" %)F8.35|(% style="text-align:center" %)Zero current detection value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.0%
2534 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 300.0% (Rated current of motor)
2535 -|(% rowspan="2" style="text-align:center" %)F8.36|(% style="text-align:center" %)Zero current detection delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0s
2536 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 600.00s
2531 +[[image:1763107356731-567.png]]
2537 2537  
2533 +Figure. 9-8-6 Schematic diagram of detection of arbitrary arrival frequency
2534 +
2535 +|(% rowspan="2" %)F8.35|Zero current detection value|Factory default|5.0%
2536 +|Setting range|(% colspan="2" %)0.0% to 300.0% (Rated current of motor)
2537 +|(% rowspan="2" %)F8.36|Zero current detection delay time|Factory default|0s
2538 +|Setting range|(% colspan="2" %)0 to 600.00s
2539 +
2540 +Figure 9-8-7 Schematic diagram of zero current detection
2541 +
2538 2538  When the output current of the inverter is less than or equal to the zero current detection level and the duration exceeds the zero current detection delay time, the output pulse
2539 2539  
2540 2540  Rush the signal. As shown below:
2541 2541  
2542 -(% style="text-align:center" %)
2543 -(((
2544 -(% style="display:inline-block" %)
2545 -[[Figure 9-8-7 Schematic diagram of zero current detection>>image:1763358952427-755.png]]
2546 -)))
2547 2547  
2548 -|(% rowspan="2" style="text-align:center" %)F8.37|(% style="text-align:center" %)Software overflow point (DO output)|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)200.0%
2549 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 300.0% (Rated current of VFD)
2550 -|(% rowspan="2" style="text-align:center" %)F8.38|(% style="text-align:center" %)Software over current detection delay time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0s
2551 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 600.00s
2547 +|
2548 +| |[[image:1763107356732-988.png]]
2552 2552  
2550 +
2551 +
2552 +|(% rowspan="2" %)F8.37|Software overflow point (DO output)|Factory default|200.0%
2553 +|Setting range|(% colspan="2" %)0.0% to 300.0% (Rated current of VFD)
2554 +|(% rowspan="2" %)F8.38|Software over current detection delay time|Factory default|0s
2555 +|Setting range|(% colspan="2" %)0 to 600.00s
2556 +
2557 +
2558 +
2553 2553  When the output current of the inverter is greater than or equal to the software over current point and the duration exceeds the software over current point detection delay time, the output pulse
2554 2554  
2555 2555  Rush the signal. As shown below:
2556 2556  
2557 -(% style="text-align:center" %)
2558 -(((
2559 -(% style="display:inline-block" %)
2560 -[[Figure 9-8-8 Schematic diagram of software overflow point detection>>image:1763107356734-922.png]]
2561 -)))
2562 2562  
2563 -== **F9 group process control PID function** ==
2564 +|
2565 +| |[[image:1763107356734-922.png]]
2564 2564  
2567 +Figure 9-8-8 Schematic diagram of software overflow point detection
2568 +
2569 +
2570 +**F9 group process control PID function**
2571 +
2565 2565  PID control is a common method used for process control. By proportional, integral and differential operations on the difference between the feedback signal of the controlled quantity and the target quantity signal, the output frequency of the inverter is adjusted to form a negative feedback system, so that the controlled quantity is stable on the target quantity. Suitable for flow control, pressure control, temperature control and other process control. The basic control block diagram is as follows:
2566 2566  
2567 2567  
2568 -(% style="text-align:center" %)
2569 -(((
2570 -(% style="display:inline-block" %)
2571 -[[Figure 9-9-1 Process PID schematic diagram>>image:1763107356736-468.png]]
2572 -)))
2575 +[[image:1763107356736-468.png]]
2573 2573  
2574 -|(% rowspan="2" style="text-align:center" %)F9.00|(% style="text-align:center" %)PID given source|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2575 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2577 +Figure 9-9-1 Process PID schematic diagram
2578 +
2579 +|(% rowspan="2" %)F9.00|PID given source|Factory default|0
2580 +|Setting range|(% colspan="2" %)(((
2576 2576  0: Keyboard number PID is set to F9.01
2577 2577  
2578 2578  1: AI1
... ... @@ -2592,13 +2592,14 @@
2592 2592  
2593 2593  When the frequency source is selected PID, that is, F0.03 or F0.04 is selected 8, this set of functions works. (See function code F0.03-F0.04.) This parameter determines the target amount of the process PID for a given channel. The set target quantity of process PID is relative value, and 100% of the set value corresponds to 100% of the feedback signal of the controlled system. The range of the PID (F9.04) is not required, because the system calculates relative values (0 to 100%) regardless of the range set. However, if the PID range is set, the actual value of the PID given and feedback corresponding to the signal can be visually observed through the keyboard display parameters.
2594 2594  
2595 -|(% rowspan="2" style="text-align:center" %)F9.01|(% style="text-align:center" %)PID Value setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.0%
2596 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 100.0%
2600 +|(% rowspan="2" %)F9.01|PID Value setting|Factory default|50.0%
2601 +|Setting range|(% colspan="2" %)0.00 to 100.0%
2597 2597  
2598 2598  When F9.00=0 is selected, the target source is the keyboard given. This parameter needs to be set. The reference value of this parameter is the feedback amount of the system.
2599 2599  
2600 -|(% rowspan="2" style="text-align:center" %)F9.02|(% style="text-align:center" %)PID feedback source|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2601 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2605 +
2606 +|(% rowspan="2" %)F9.02|PID feedback source|Factory default|0
2607 +|Setting range|(% colspan="2" %)(((
2602 2602  0: AI1
2603 2603  
2604 2604  1: AI2
... ... @@ -2622,6 +2622,14 @@
2622 2622  
2623 2623  This parameter is used to select the PID feedback channel.
2624 2624  
2631 +
2632 +
2633 +
2634 +
2635 +
2636 +
2637 +
2638 +
2625 2625  |(% rowspan="2" %)F9.03|PID control characteristic|Factory default|0
2626 2626  |Setting range|(% colspan="2" %)(((
2627 2627  LED ones digit: Feedback feature selection
... ... @@ -2667,14 +2667,14 @@
2667 2667  
2668 2668  Center alignment: Error correction.
2669 2669  
2670 -|(% rowspan="2" style="text-align:center" %)F9.04|(% style="text-align:center" %)PID given feedback range|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0
2671 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 100.0
2672 -|(% rowspan="2" style="text-align:center" %)F9.05|(% style="text-align:center" %)Proportional gain P1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.00
2673 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 1000.00
2674 -|(% rowspan="2" style="text-align:center" %)F9.06|(% style="text-align:center" %)Integration time I1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00s
2675 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.00s
2676 -|(% rowspan="2" style="text-align:center" %)F9.07|(% style="text-align:center" %)D1derivative time D1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
2677 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.00s
2684 +|(% rowspan="2" %)F9.04|PID given feedback range|Factory default|100.0
2685 +|Setting range|(% colspan="2" %)0 to 100.0
2686 +|(% rowspan="2" %)F9.05|Proportional gain P1|Factory default|20.00
2687 +|Setting range|(% colspan="2" %)0.00 to 1000.00
2688 +|(% rowspan="2" %)F9.06|Integration time I1|Factory default|2.00s
2689 +|Setting range|(% colspan="2" %)0.00 to 10.00s
2690 +|(% rowspan="2" %)F9.07|D1derivative time D1|Factory default|0.00s
2691 +|Setting range|(% colspan="2" %)0.00 to 10.00s
2678 2678  
2679 2679  Proportional gain P1: Determines the adjustment intensity of the entire PID regulator, the greater the P, the greater the adjustment intensity. The parameter 100 indicates that when the deviation between the PID feedback quantity and the feed quantity is 100%, the PID: regulator's adjustment amplitude to the output frequency instruction is Maximum frequency (ignoring the integral and differential effects).
2680 2680  
... ... @@ -2682,40 +2682,49 @@
2682 2682  
2683 2683  Differential time D1: Determines the intensity with which the PID regulator adjusts the amount of PID feedback and the rate of change of the given amount of deviation. The differential time means that if the feedback quantity changes 100% in this time, the adjustment amount of the differential regulator is Maximum frequency (F0.10) (ignoring the proportional action and integral action). The longer the differential time, the greater the adjustment intensity.
2684 2684  
2685 -|(% rowspan="2" style="text-align:center" %)F9.08|(% style="text-align:center" %)Reverse cut-off frequency|(% style="text-align:center" %)Factory default|0.00Hz
2686 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Maximum frequency F0.10
2687 -|(% rowspan="2" style="text-align:center" %)F9.09|(% style="text-align:center" %)PID deviation limit|(% style="text-align:center" %)Factory default|0.0%
2688 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0. 0% to 100.0%
2699 +|(% rowspan="2" %)F9.08|Reverse cut-off frequency|Factory default|0.00Hz
2700 +|Setting range|(% colspan="2" %)0.00 to Maximum frequency F0.10
2701 +|(% rowspan="2" %)F9.09|PID deviation limit|Factory default|0.0%
2702 +|Setting range|(% colspan="2" %)0. 0% to 100.0%
2689 2689  
2704 +
2705 +
2690 2690  Deviation limit: When the PID feedback deviation is within this range, the PID stops adjusting.
2691 2691  
2692 -|(% rowspan="2" style="text-align:center" %)F9.10|(% style="text-align:center" %)PID differential limiting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.10%
2693 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00% to 100.00%
2694 -|(% rowspan="2" style="text-align:center" %)F9.11|(% style="text-align:center" %)PID given change time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
2695 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00s to 100.00s
2708 +|(% rowspan="2" %)F9.10|PID differential limiting|Factory default|0.10%
2709 +|Setting range|(% colspan="2" %)0.00% to 100.00%
2710 +|(% rowspan="2" %)F9.11|PID given change time|Factory default|0.00s
2711 +|Setting range|(% colspan="2" %)0.00s to 100.00s
2696 2696  
2713 +
2714 +
2697 2697  The given PID change time refers to the time required for the actual PID value to change from 0.0% to 100.0%.
2698 2698  
2699 2699  When the PID set changes, the actual value of the PID set does not follow the immediate response. And according to the given change time linear change, prevent a given mutation.
2700 2700  
2701 -|(% rowspan="2" style="text-align:center" %)F9.12|(% style="text-align:center" %)PID feedback filtering time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
2702 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00s to 60.00s
2703 -|(% rowspan="2" style="text-align:center" %)F9.13|(% style="text-align:center" %)PID output filtering time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
2704 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00s to 60.00s
2719 +|(% rowspan="2" %)F9.12|PID feedback filtering time|Factory default|0.00s
2720 +|Setting range|(% colspan="2" %)0.00s to 60.00s
2721 +|(% rowspan="2" %)F9.13|PID output filtering time|Factory default|0.00s
2722 +|Setting range|(% colspan="2" %)0.00s to 60.00s
2705 2705  
2724 +
2725 +
2706 2706  The PID feedback and output values are filtered to eliminate abrupt changes.
2707 2707  
2708 -|(% rowspan="2" style="text-align:center" %)F9.14|(% style="text-align:center" %)Proportional gain P2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0
2709 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 100.0
2710 -|(% rowspan="2" style="text-align:center" %)F9.15|(% style="text-align:center" %)Integration time I2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00s
2711 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01s to 10.00s
2712 -|(% rowspan="2" style="text-align:center" %)F9.16|(% style="text-align:center" %)Differential time D2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.000s
2713 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.000
2714 2714  
2729 +|(% rowspan="2" %)F9.14|Proportional gain P2|Factory default|20.0
2730 +|Setting range|(% colspan="2" %)0.0 to 100.0
2731 +|(% rowspan="2" %)F9.15|Integration time I2|Factory default|2.00s
2732 +|Setting range|(% colspan="2" %)0.01s to 10.00s
2733 +|(% rowspan="2" %)F9.16|Differential time D2|Factory default|0.000s
2734 +|Setting range|(% colspan="2" %)0.00 to 10.000
2735 +
2736 +
2737 +
2715 2715  The setting is similar to F9.05, F9.06, and F9.07. For details about how to change the PID parameters, see F9.18.
2716 2716  
2717 -|(% rowspan="2" style="text-align:center" %)F9.17|(% style="text-align:center" %)PID parameter switching condition|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2718 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:left" %)(((
2740 +|(% rowspan="2" %)F9.17|PID parameter switching condition|Factory default|0
2741 +|Setting range|(% colspan="2" %)(((
2719 2719  0: No switching
2720 2720  
2721 2721  1: Terminal switch
... ... @@ -2722,10 +2722,10 @@
2722 2722  
2723 2723  2: Automatically switch according to deviation
2724 2724  )))
2725 -|(% rowspan="2" style="text-align:center" %)F9.18|(% style="text-align:center" %)PID parameter switching deviation 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0%
2726 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to F9.19
2727 -|(% rowspan="2" style="text-align:center" %)F9.19|(% style="text-align:center" %)PID parameter switching deviation 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)80.0%
2728 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F9.18 to 100.0%
2748 +|(% rowspan="2" %)F9.18|PID parameter switching deviation 1|Factory default|20.0%
2749 +|Setting range|(% colspan="2" %)0.0% to F9.19
2750 +|(% rowspan="2" %)F9.19|PID parameter switching deviation 2|Factory default|80.0%
2751 +|Setting range|(% colspan="2" %)F9.18 to 100.0%
2729 2729  
2730 2730  In some applications, a single set of PID parameters may not be sufficient for the entire operation. Multiple groups of PID parameters may need to be switched.
2731 2731  
... ... @@ -2735,15 +2735,16 @@
2735 2735  
2736 2736  2: Automatic switching according to the deviation. When the deviation between the given and feedback is less than PID parameter switching deviation 1 (F9.19), F9.05, F9.06 and F9.07 are used as PID adjustment parameters. When the deviation between given and feedback is greater than PID switching deviation 2 (F9.20), F9.15, F9.16 and F9.17 are used as PID adjustment parameters. The PID parameters in the deviation section between switching deviation 1 and switching deviation 2 are linearly switched between the two groups of PID parameters.
2737 2737  
2738 -|(% rowspan="2" style="text-align:center" %)F9.20|(% style="text-align:center" %)PID initial frequency value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0%
2739 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%
2740 -|(% rowspan="2" style="text-align:center" %)F9.21|(% style="text-align:center" %)PID initial retention time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
2741 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00s to 6500.0s
2761 +|(% rowspan="2" %)F9.20|PID initial frequency value|Factory default|0%
2762 +|Setting range|(% colspan="2" %)0.0% to 100.0%
2763 +|(% rowspan="2" %)F9.21|PID initial retention time|Factory default|0.0s
2764 +|Setting range|(% colspan="2" %)0.00s to 650.00s
2742 2742  
2743 2743  During PID operation, the inverter first sets the output operation with the initial PID value (F9.20) and the duration is F9.21 (PID initial value holding time), and then starts the normal PID adjustment.
2744 2744  
2745 -|(% rowspan="2" style="text-align:center" %)F9.23|(% style="text-align:center" %)Feedback wire break action selection|(% style="text-align:center" %)Factory default|0
2746 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:left" %)(((
2768 +
2769 +|(% rowspan="2" %)F9.23|Feedback wire break action selection|Factory default|0
2770 +|Setting range|(% colspan="2" %)(((
2747 2747  0: PID continues to run and no fault is reported
2748 2748  
2749 2749  1: Stop and report fault (manual reset)
... ... @@ -2754,15 +2754,17 @@
2754 2754  
2755 2755  4: Stop and report fault (automatic reset)
2756 2756  )))
2757 -|(% rowspan="2" style="text-align:center" %)F9.24|(% style="text-align:center" %)Wire break alarm upper limit|(% style="text-align:center" %)Factory default|100.0%
2758 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F9.25 to 100.0%
2759 -|(% rowspan="2" style="text-align:center" %)F9.25|(% style="text-align:center" %)Line break alarm lower limit|(% style="text-align:center" %)Factory default|0.0%
2760 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to F9.24%
2761 -|(% rowspan="2" style="text-align:center" %)F9.26|(% style="text-align:center" %)Feedback break detection time|(% style="text-align:center" %)Factory default|0.0s
2762 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s to 120.0s
2781 +|(% rowspan="2" %)F9.24|Wire break alarm upper limit|Factory default|100.0%
2782 +|Setting range|(% colspan="2" %)F9.25 to 100.0%
2783 +|(% rowspan="2" %)F9.25|Line break alarm lower limit|Factory default|0.0%
2784 +|Setting range|(% colspan="2" %)0 to F9.24%
2785 +|(% rowspan="2" %)F9.26|Feedback break detection time|Factory default|0.0s
2786 +|Setting range|(% colspan="2" %)0.0s to 120.0s
2763 2763  
2764 -Determine whether the PID feedback is lost. If the PID feedback is lower than the disconnection alarm lower limit (F9.25) or higher than the disconnection alarm upper limit (F9.24) for a duration reaching F9.26 (feedback loss detection time), the inverter will report a fault and operate according to the F9.29 setting.
2765 2765  
2789 +
2790 +3 The upper limit (F9.24) duration reaches F9.26 (feedback loss detection time), the inverter reports a fault and runs according to F9.29 setting.
2791 +
2766 2766  |(% rowspan="2" %)F9.27|PID stop operation|Factory default|0
2767 2767  |Setting range|(% colspan="2" %)(((
2768 2768  0: Disable calculation on shutdown​​
... ... @@ -2780,27 +2780,26 @@
2780 2780  
2781 2781  1: The inverter runs with sleep PID control, and the sleep function is enabled.
2782 2782  
2783 -|(% rowspan="2" style="text-align:center" %)F9.29|(% style="text-align:center" %)PID sleep threshold|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)60.0%
2784 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%
2785 -|(% rowspan="2" style="text-align:center" %)F9.30|(% style="text-align:center" %)PID sleep delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3.0s
2786 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 3600.0s
2787 -|(% rowspan="2" style="text-align:center" %)F9.31|(% style="text-align:center" %)PID wake-up threshold|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0%
2788 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%
2789 -|(% rowspan="2" style="text-align:center" %)F9.32|(% style="text-align:center" %)PID wake up delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3.0s
2790 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 3600.0s
2809 +|(% rowspan="2" %)F9.29|PID sleep threshold|Factory default|60.0%
2810 +|Setting range|(% colspan="2" %)0.0% to 100.0%
2811 +|(% rowspan="2" %)F9.30|PID sleep delay|Factory default|3.0s
2812 +|Setting range|(% colspan="2" %)0.0 to 3600.0s
2813 +|(% rowspan="2" %)F9.31|PID wake-up threshold|Factory default|20.0%
2814 +|Setting range|(% colspan="2" %)0.0% to 100.0%
2815 +|(% rowspan="2" %)F9.32|PID wake up delay|Factory default|3.0s
2816 +|Setting range|(% colspan="2" %)0.0 to 3600.0s
2791 2791  
2792 2792  When selecting the sleep PID, if the feedback is higher than the sleep threshold set by F9.29 and the running frequency is less than or equal to the sleep frequency set by F9.33, the VFD starts the sleep timing. After the sleep delay time set by F9.30, if the feedback quantity is higher than the set quantity set by F9.29 and the running frequency is less than or equal to the sleep frequency set by F9.33, Then the PID stops running and the inverter enters sleep state. If the feedback is lower than the setting of F9.31 wake-up threshold, the VFD starts the wake-up timing. After the time set by F9.32 wake-up delay, if the feedback is still lower than the setting of F9.31 wake-up threshold, the wake-up is successful and PID control is performed. Refer to Figure 9-9-2 below to understand the above parameter relationships.
2793 2793  
2794 -(% style="text-align:center" %)
2795 -(((
2796 -(% style="display:inline-block" %)
2797 -[[Figure 9-9-2 Schematic diagram of PID sleep and wake time sequence>>image:1763360417842-953.png]]
2798 -)))
2820 +[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml14320\wps10.png]]
2799 2799  
2800 -|(% rowspan="2" style="text-align:center" %)F9.33|(% style="text-align:center" %)Dormancy detection frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)25.00Hz
2801 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to upper limit frequency F0.12
2802 -|(% rowspan="2" style="text-align:center" %)F9.34|(% style="text-align:center" %)Minimum output|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2803 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:left" %)(((
2822 +Figure 9-9-2 Schematic diagram of PID sleep and wake time sequence
2823 +
2824 +
2825 +|(% rowspan="2" %)F9.33|Dormancy detection frequency|Factory default|25.00Hz
2826 +|Setting range|(% colspan="2" %)0 to Upper limit frequency F0.12
2827 +|(% rowspan="2" %)F9.34|Minimum output|Factory default|0
2828 +|Setting range|(% colspan="2" %)(((
2804 2804  0: F0.14 (Lower limit frequency)
2805 2805  
2806 2806  1: 0Hz
... ... @@ -2808,23 +2808,25 @@
2808 2808  
2809 2809  Sleep detection frequency: Frequency at which the system determines whether the sleep condition is met.
2810 2810  
2811 -|(% rowspan="2" style="text-align:center" %)F9.35|(% style="text-align:center" %)Maximum forward deviation of two outputs|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.00%.
2812 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00% to 100.00%
2813 -|(% rowspan="2" style="text-align:center" %)F9.36|(% style="text-align:center" %)Maximum reverse deviation of two outputs|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.00%
2814 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00% to 100.00%
2836 +|(% rowspan="2" %)F9.35|Maximum forward deviation of two outputs|Factory default|1.00%.
2837 +|Setting range|(% colspan="2" %)0.00% to 100.00%
2838 +|(% rowspan="2" %)F9.36|Maximum reverse deviation of two outputs|Factory default|1.00%
2839 +|Setting range|(% colspan="2" %)0.00% to 100.00%
2815 2815  
2841 +
2842 +
2816 2816  This function code is used to limit the difference between the PID output two beats (2ms/ beat), thereby suppress the PID output changes too fast. F9.23 and F9.24 correspond to the maximum output deviation for forward and reverse rotation respectively.
2817 2817  
2818 -|(% rowspan="2" style="text-align:center" %)F9.38|(% style="text-align:center" %)PID preset switchover condition selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
2819 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:left" %)(((
2845 +|(% rowspan="2" %)F9.38|PID preset switchover condition selection|Factory default|0
2846 +|Setting range|(% colspan="2" %)(((
2820 2820  0: Time
2821 2821  
2822 2822  1: Switch according to AI1 feedback value
2823 2823  )))
2824 -|(% rowspan="2" style="text-align:center" %)F9.39|(% style="text-align:center" %)PID AI feedback switching minimum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)45.0%
2825 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to F8.18
2826 -|(% rowspan="2" style="text-align:center" %)F9.40|(% style="text-align:center" %)PID AI feedback switching maximum|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)55.0%
2827 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F8.17 to 100.0%
2851 +|(% rowspan="2" %)F9.39|PID AI feedback switching minimum|Factory default|45.0%
2852 +|Setting range|(% colspan="2" %)0.0 to F8.18
2853 +|(% rowspan="2" %)F9.40|PID AI feedback switching maximum|Factory default|55.0%
2854 +|Setting range|(% colspan="2" %)F8.17 to 100.0%
2828 2828  
2829 2829  PID preset switching condition selection: Switch from preset output frequency (F9.20) to PID given.
2830 2830  
... ... @@ -2832,10 +2832,10 @@
2832 2832  
2833 2833  1: Switch when the feedback value is greater than or equal to F9.23 and less than or equal to F9.24.
2834 2834  
2835 -== **FA group failure and protection** ==
2862 +**FA group failure and protection**
2836 2836  
2837 -|(% rowspan="2" style="text-align:center" %)FA.00|(% style="text-align:center" %)Motor overload protection selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2838 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2864 +|(% rowspan="2" %)FA.00|Motor overload protection selection|Factory default|1
2865 +|Setting range|(% colspan="2" %)(((
2839 2839  0: Off
2840 2840  
2841 2841  1: On
... ... @@ -2845,18 +2845,18 @@
2845 2845  
2846 2846  Select 1: At this time, the inverter has overload protection function for the motor. See FA.01 for protection values.
2847 2847  
2848 -|(% rowspan="2" style="text-align:center" %)FA.01|(% style="text-align:center" %)Motor overload protection factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
2849 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 250.0%
2875 +|(% rowspan="2" %)FA.01|Motor overload protection factor|Factory default|100.0%
2876 +|Setting range|(% colspan="2" %)0.0 to 250.0%
2850 2850  
2851 2851  Motor overload protection is inverse time curve; 220% x (FA.01) x rated motor current for 1 minute, 150% x (FA.01) x rated motor current for 60 minutes.
2852 2852  
2853 -|(% rowspan="2" style="text-align:center" %)FA.02|(% style="text-align:center" %)Motor overload warning factor|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)80.0%
2854 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)20.0 to 250.0%
2880 +|(% rowspan="2" %)FA.02|Motor overload warning factor|Factory default|80.0%
2881 +|Setting range|(% colspan="2" %)20.0 to 250.0%
2855 2855  
2856 2856  The reference for this value is the overload current of the motor. When the inverter detects that the output current reaches (FA.02) x the motor overload current and continues for the specified time in the inverse time curve, the forecast alarm is output from the DO or relay.
2857 2857  
2858 -|(% rowspan="2" style="text-align:center" %)FA.03|(% style="text-align:center; width:361px" %)Over voltage stall/over loss rate control options|(% style="text-align:center; width:200px" %)Factory default|(% style="text-align:center" %)1111
2859 -|(% style="text-align:center; width:361px" %)Setting range|(% colspan="2" style="width:331px" %)(((
2885 +|(% rowspan="2" %)FA.03|Over voltage stall/over loss rate control options|Factory default|1111
2886 +|Setting range|(% colspan="2" %)(((
2860 2860  0: Off
2861 2861  
2862 2862  1: On
... ... @@ -2886,26 +2886,30 @@
2886 2886  
2887 2887  This bit is used to set how the frequency increases when over current suppression is withdrawn. When set to 0, the frequency is accelerated according to the acceleration time; When set to 1, the frequency is controlled by the current, so as the current decreases, the frequency will rise rapidly.
2888 2888  
2889 -|(% rowspan="2" style="text-align:center" %)FA.04|(% style="text-align:center" %)Over pressure suppression point|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model-based setting
2890 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)110% to 150%
2891 -|(% rowspan="2" style="text-align:center" %)FA.05|(% style="text-align:center" %)Udc control voltage loop gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00
2892 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00
2893 -|(% rowspan="2" style="text-align:center" %)FA.06|(% style="text-align:center" %)Udc control current loop gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2.00
2894 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00
2895 2895  
2917 +|(% rowspan="2" %)FA.04|Over pressure suppression point|Factory default|Model-based setting
2918 +|Setting range|(% colspan="2" %)110% to 150%
2919 +|(% rowspan="2" %)FA.05|Udc control voltage loop gain|Factory default|2.00
2920 +|Setting range|(% colspan="2" %)0.00 to 50.00
2921 +|(% rowspan="2" %)FA.06|Udc control current loop gain|Factory default|2.00
2922 +|Setting range|(% colspan="2" %)0.00 to 50.00
2923 +
2896 2896  When the bus voltage exceeds FA.04× rated bus voltage during the operation of the VFD, the VFD will automatically adjust the operating frequency to suppress the bus voltage rise, so as to ensure that the VFD will not cause over voltage protection due to the high bus voltage. FA.05 and FA.06 are the voltage loop gain and current loop gain when the bus voltage is regulated, respectively. Instantaneous stop of the voltage loop and current loop gain is also the reference number.
2897 2897  
2898 -|(% rowspan="2" style="text-align:center" %)FA.07|(% style="text-align:center" %)Over current suppression point|(% style="text-align:center" %)Factory default|150%
2899 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)50% to 200%
2900 -|(% rowspan="2" style="text-align:center" %)FA.08|(% style="text-align:center" %)Over current suppression gain|(% style="text-align:center" %)Factory default|2.00
2901 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00
2902 -|(% rowspan="2" style="text-align:center" %)FA.09|(% style="text-align:center" %)Over current suppression integral|(% style="text-align:center" %)Factory default|4.00
2903 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00
2904 2904  
2927 +|(% rowspan="2" %)FA.07|Over current suppression point|Factory default|150%
2928 +|Setting range|(% colspan="2" %)50% to 200%
2929 +|(% rowspan="2" %)FA.08|Over current suppression gain|Factory default|2.00
2930 +|Setting range|(% colspan="2" %)0.00 to 50.00
2931 +|(% rowspan="2" %)FA.09|Over current suppression integral|Factory default|4.00
2932 +|Setting range|(% colspan="2" %)0.00 to 50.00
2933 +
2934 +
2935 +
2905 2905  When controlling the motor, the motor current increases with the increase of load, and the over current suppression gain function limits the maximum current of the motor. When the current reaches the rated current of FA.07* inverter, the output frequency automatically decreases to limit the motor current not exceeding the current set by FA.07; FA.08 and FA.09 are over current suppression controller parameters. Adjusting these two parameters can improve and optimize the over current suppression effect.
2906 2906  
2907 -|(% rowspan="2" style="text-align:center" %)FA.10|(% style="text-align:center" %)Power-on short-circuit detection to the ground|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2908 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)(((
2938 +|(% rowspan="2" %)FA.10|Power-on short-circuit detection to the ground|Factory default|1
2939 +|Setting range|(% colspan="2" %)(((
2909 2909  0: Invalid
2910 2910  
2911 2911  1: Valid
... ... @@ -2913,8 +2913,8 @@
2913 2913  
2914 2914  The inverter can be selected to detect whether the motor has a ground protection short circuit fault when it is powered on. If this function is effective, the inverter is output for a short time at the moment of power-on.
2915 2915  
2916 -|(% rowspan="2" style="text-align:center" %)FA.11|(% style="text-align:center" %)Input phase loss protection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2917 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)(((
2947 +|(% rowspan="2" %)FA.11|Input phase loss protection|Factory default|1
2948 +|Setting range|(% colspan="2" %)(((
2918 2918  0: Off
2919 2919  
2920 2920  1: On
... ... @@ -2922,8 +2922,8 @@
2922 2922  
2923 2923  Select whether to protect against input phase loss.
2924 2924  
2925 -|(% rowspan="2" style="text-align:center" %)FA.12|(% style="text-align:center" %)Output phase loss protection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
2926 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)(((
2956 +|(% rowspan="2" %)FA.12|Output phase loss protection|Factory default|1
2957 +|Setting range|(% colspan="2" %)(((
2927 2927  0: Off
2928 2928  
2929 2929  1: On
... ... @@ -2931,13 +2931,13 @@
2931 2931  
2932 2932  Select whether to protect output phase loss.
2933 2933  
2934 -|(% rowspan="2" style="text-align:center" %)FA.13|(% style="text-align:center" %)Input phase loss protection software detection level|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)15.0%
2935 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 999.9%
2965 +|(% rowspan="2" %)FA.13|Input phase loss protection software detection level|Factory default|15.0%
2966 +|Setting range|(% colspan="2" %)0.0 to 999.9%
2936 2936  
2937 2937  The input missing phase is judged by calculating the fluctuation of bus voltage. This parameter is used to set the threshold of bus voltage fluctuation when the input phase is out. Turning down can increase the sensitive zero of the input phase out, and turning up can reduce the probability of false positive of the input phase out.
2938 2938  
2939 -|(% rowspan="2" style="text-align:center" %)FA.14|(% style="text-align:center" %)PWM Parameter setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0010
2940 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2970 +|(% rowspan="2" %)FA.14|PWM Parameter setting|Factory default|0010
2971 +|Setting range|(% colspan="2" %)(((
2941 2941  LED units place: Turn on voltage prediction compensation
2942 2942  
2943 2943  LED tens place: PWM update mode
... ... @@ -2946,7 +2946,7 @@
2946 2946  
2947 2947  1: Double sample and double update
2948 2948  
2949 -LED hundreds place: Random carrier mode
2980 +LED hundreds place: random carrier mode
2950 2950  
2951 2951  0: Random carrier
2952 2952  
... ... @@ -2959,14 +2959,14 @@
2959 2959  
2960 2960  LED tens place: PWM update mode.
2961 2961  
2962 -0: Single sample update. 1: Double sample and double update.
2993 +0: single sample update. 1: Double sample and double update.
2963 2963  
2964 -LED hundreds place: Random carrier mode.
2995 +LED hundreds place: random carrier mode.
2965 2965  
2966 2966  0: Random PWM carrier frequency. 1: Random 0 vector.
2967 2967  
2968 -|(% rowspan="2" style="text-align:center" %)FA.15|(% style="text-align:center" %)Hardware current and voltage protection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0011
2969 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
2999 +|(% rowspan="2" %)FA.15|Hardware current and voltage protection|Factory default|0011
3000 +|Setting range|(% colspan="2" %)(((
2970 2970  LED units place: Current limiting (CBC)
2971 2971  
2972 2972  0: Off
... ... @@ -2988,7 +2988,7 @@
2988 2988  
2989 2989  0: Disable CBC current limiting ​ 1: Enable CBC current limiting
2990 2990  
2991 -LED tens place: Reserved.
3022 +LED tens place: reserved.
2992 2992  
2993 2993  LED hundreds place: FAU filtering time.
2994 2994  
... ... @@ -2998,30 +2998,33 @@
2998 2998  
2999 2999  The TZ signal is an over current signal. This parameter is used to set the filtering time of the TZ signal.
3000 3000  
3001 -|(% rowspan="2" style="text-align:center" %)FA.16|(% style="text-align:center" %)CBC protection point|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)200%
3002 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)100 to 220%
3003 -|(% rowspan="2" style="text-align:center" %)FA.17|(% style="text-align:center" %)CBC overload protection time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)500ms
3004 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)1 to 5000ms
3032 +|(% rowspan="2" %)FA.16|CBC protection point|Factory default|200%
3033 +|Setting range|(% colspan="2" %)100 to 220%
3034 +|(% rowspan="2" %)FA.17|CBC overload protection time|Factory default|500ms
3035 +|Setting range|(% colspan="2" %)1 to 5000ms
3005 3005  
3037 +
3038 +
3006 3006  When the motor current is higher than the rated current of FA.16*VFD, the per-wave current limiting starts. If the per-wave current limiting duration exceeds the time set in FA.17, the VFD reports Err. This parameter is used to set the per-wave current limiting current and fault response time.
3007 3007  
3008 -|(% rowspan="2" style="text-align:center" %)FA.18|(% style="text-align:center" %)Under voltage point setting|(% style="text-align:center" %)Factory default|100.0%
3009 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)40.0% to 100.0%
3041 +|(% rowspan="2" %)FA.18|Under voltage point setting|Factory default|100.0%
3042 +|Setting range|(% colspan="2" %)100 to 220%
3010 3010  
3011 3011  Adjusting this parameter can adjust the voltage point of the VFD reporting the under voltage fault (Err09), 100.0% corresponds to 350V.
3012 3012  
3013 -|(% rowspan="2" style="text-align:center" %)FA.20|(% style="text-align:center" %)Times of self-recovery|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3014 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 5
3046 +|(% rowspan="2" %)FA.20|Times of self-recovery|Factory default|0
3047 +|Setting range|(% colspan="2" %)0 to 5
3015 3015  
3016 3016  When the inverter selects fault automatic reset, it is used to set the number of times that can be automatically reset. If the value exceeds this value, the inverter is faulty and waiting for repair.
3017 3017  
3018 -|(% rowspan="2" style="text-align:center" %)FA.21|(% style="text-align:center" %)Interval for fault self-recovery|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.0s
3019 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.1 to 100.0ms
3051 +|(% rowspan="2" %)FA.21|Interval for fault self-recovery|Factory default|1.0s
3052 +|Setting range|(% colspan="2" %)0.1 to 100.0ms
3020 3020  
3021 3021  VFD from fault alarm to automatic reset fault waiting time.
3022 3022  
3023 -|(% rowspan="2" style="text-align:center" %)FA.22|(% style="text-align:center" %)Instant stop non-stop function selection|(% style="text-align:center" %)Factory default|0000
3024 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3056 +
3057 +|(% rowspan="2" %)FA.22|Instant stop non-stop function selection|Factory default|0000
3058 +|Setting range|(% colspan="2" %)(((
3025 3025  One place: Power loss ride-through enabled​​
3026 3026  
3027 3027  0: Disabled
... ... @@ -3035,6 +3035,8 @@
3035 3035  1: Stop
3036 3036  )))
3037 3037  
3072 +
3073 +
3038 3038  Ones place: Power loss ride-through enabled​​
3039 3039  
3040 3040  0: Disable power loss ride-through . 1: Enable power loss ride-through.​
... ... @@ -3047,29 +3047,28 @@
3047 3047  
3048 3048  1: Shut down immediately
3049 3049  
3050 -|(% rowspan="2" style="text-align:center" %)FA.23|(% style="text-align:center" %)Power loss ride-through voltage threshold​|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)75%
3051 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)40% to 150%
3052 -|(% rowspan="2" style="text-align:center" %)FA.24|(% style="text-align:center" %)Power loss ride-through stable voltage|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)95%
3053 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)60% to 150%
3086 +|(% rowspan="2" %)FA.23|Power loss ride-through voltage threshold​|Factory default|75%
3087 +|Setting range|(% colspan="2" %)40% to 150%
3088 +|(% rowspan="2" %)FA.24|Power loss ride-through stable voltage|Factory default|95%
3089 +|Setting range|(% colspan="2" %)60% to 150%
3054 3054  
3055 3055  When the input power is reduced or power off, the inverter can control the motor speed down to feedback energy to avoid the VFD under voltage fault, the function is called power loss ride-through . When the bus voltage is lower than the rated bus voltage *FA.24, The power loss ride-through function is active. and control the motor to feedback energy to stabilize the bus voltage at the rated bus voltage *FA.24.
3056 3056  
3057 -== **FB group swing frequency, fixed length and counting** ==
3058 3058  
3094 +**FB group swing frequency, fixed length and counting**
3095 +
3059 3059  Swing frequency function is suitable for textile, chemical fiber and other industries and need transverse movement, winding function occasions.
3060 3060  
3061 3061  The function of swing frequency means that the output frequency of the inverter swings up and down with the set frequency as the center.
3062 3062  
3063 -(% style="text-align:center" %)
3064 -(((
3065 -(% style="display:inline-block" %)
3066 -[[Figure 9-B-1 Schematic diagram of swing frequency operation>>image:1763107356738-341.png]]
3067 -)))
3100 +[[image:1763107356738-341.png]]
3068 3068  
3069 -|(% rowspan="2" style="text-align:center" %)FB.00|(% style="text-align:center" %)Swing frequency control|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3070 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3071 -LED ones digit: Swing frequency control
3102 +Figure 9-B-1 Schematic diagram of swing frequency operation
3072 3072  
3104 +|(% rowspan="2" %)FB.00|Swing frequency control|Factory default|0
3105 +|Setting range|(% colspan="2" %)(((
3106 +LED ones diigt: Swing frequency control
3107 +
3073 3073  0: The swing frequency control is disable
3074 3074  
3075 3075  1: Swing frequency control is effective
... ... @@ -3089,7 +3089,7 @@
3089 3089  LED thousands digit: Reserved
3090 3090  )))
3091 3091  
3092 -LED ones digit: Swing frequency control enable
3127 +LED ones diigt: Swing frequency control enable
3093 3093  
3094 3094  LED tens digit:
3095 3095  
... ... @@ -3101,14 +3101,14 @@
3101 3101  
3102 3102  1: Fixed amplitude, relative to maximum frequency (F0.10 maximum output frequency), it is a fixed amplitude system.
3103 3103  
3104 -|(% rowspan="2" style="text-align:center" %)FB.01|(% style="text-align:center" %)Swing preset frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00Hz
3105 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Maximum frequency
3106 -|(% rowspan="2" style="text-align:center" %)FB.02|(% style="text-align:center" %)Preset frequency duration|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
3107 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 650.00s
3108 -|(% rowspan="2" style="text-align:center" %)FB.03|(% style="text-align:center" %)Swing amplitude|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
3109 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 100.0%
3110 -|(% rowspan="2" style="text-align:center" %)FB.04|(% style="text-align:center" %)Jump frequency amplitude|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
3111 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0% to 50.0%
3139 +|(% rowspan="2" %)FB.01|Swing preset frequency|Factory default|0.00Hz
3140 +|Setting range|(% colspan="2" %)0.00 to Maximum frequency
3141 +|(% rowspan="2" %)FB.02|Preset frequency duration|Factory default|0.00s
3142 +|Setting range|(% colspan="2" %)0.00 to 650.00s
3143 +|(% rowspan="2" %)FB.03|Swing amplitude|Factory default|0.0%
3144 +|Setting range|(% colspan="2" %)0.0% to 100.0%
3145 +|(% rowspan="2" %)FB.04|Jump frequency amplitude|Factory default|0.0%
3146 +|Setting range|(% colspan="2" %)0.0% to 50.0%
3112 3112  
3113 3113  The value of swing amplitude and jump frequency can be determined by this parameter. The operating frequency of swing frequency is constrained by the upper and lower frequency.
3114 3114  
... ... @@ -3122,23 +3122,30 @@
3122 3122  
3123 3123  If the swing is selected relative to the Maximum frequency (fixed swing, select FB.00=1), the jog frequency is fixed.
3124 3124  
3125 -|(% rowspan="2" style="text-align:center" %)FB.05|(% style="text-align:center" %)Swing frequency rise time|(% style="text-align:center" %)Factory default|5.00s
3126 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 650.00s
3127 -|(% rowspan="2" style="text-align:center" %)FB.06|(% style="text-align:center" %)Swing frequency drop time|(% style="text-align:center" %)Factory default|5.00s
3128 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 650.00s
3129 3129  
3161 +|(% rowspan="2" %)FB.05|Swing frequency rise time|Factory default|5.00s
3162 +|Setting range|(% colspan="2" %)0.00 to 650.00s
3163 +|(% rowspan="2" %)FB.06|Swing frequency drop time|Factory default|5.00s
3164 +|Setting range|(% colspan="2" %)0.00 to 650.00s
3165 +
3166 +
3167 +
3130 3130  Triangle wave rise time = swing frequency duration FB.02× delta wave rise time coefficient FB.05 (unit: s).
3131 3131  Triangle wave fall time = swing frequency duration FB.02× (1- triangle wave rise time coefficient FB.06) (unit: s).
3132 3132  
3133 -== **FC Group communication parameters** ==
3134 3134  
3135 -|(% rowspan="2" style="text-align:center" %)FC.00|(% style="text-align:center" %)Local address|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
3136 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)1 to 247, 0 is the broadcast address
3137 3137  
3173 +
3174 +
3175 +**FC Group communication parameters**
3176 +
3177 +|(% rowspan="2" %)FC.00|Local address|Factory default|1
3178 +|Setting range|(% colspan="2" %)1 to 247, 0 is the broadcast address
3179 +
3138 3138  When the local address is set to 0, it is the broadcast address, and the host computer broadcast function is realized. The local address is unique (except the broadcast address), which is the basis of point-to-point communication between the host computer and the inverter.
3139 3139  
3140 -|(% rowspan="2" style="text-align:center" %)FC.01|(% style="text-align:center" %)Baud rate|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5
3141 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3182 +|(% rowspan="2" %)FC.01|Baud rate|Factory default|5
3183 +|Setting range|(% colspan="2" %)(((
3142 3142  0: 300 bps
3143 3143  
3144 3144  1: 600 bps
... ... @@ -3162,8 +3162,8 @@
3162 3162  
3163 3163  This parameter is used to set the data transmission rate between the host computer and the VFD. Note that the baud rate set by the upper computer and the VFD must be consistent, otherwise, communication cannot be carried out. The higher the baud rate, the faster the communication speed.
3164 3164  
3165 -|(% rowspan="2" style="text-align:center" %)FC.02|(% style="text-align:center" %)Modbus data format|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)3
3166 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3207 +|(% rowspan="2" %)FC.02|Modbus data format|Factory default|3
3208 +|Setting range|(% colspan="2" %)(((
3167 3167  0: (8.N.2) 8 bits, no parity, 2 stop bits
3168 3168  
3169 3169  1: (8.E.1) 8 bits, even parity, 1 stop bit
... ... @@ -3175,20 +3175,22 @@
3175 3175  
3176 3176  The data format set by the upper computer and the inverter must be consistent, otherwise, the communication cannot be carried out.
3177 3177  
3178 -|(% rowspan="2" style="text-align:center" %)FC.03|(% style="text-align:center" %)Modbus Communication response delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)2ms
3179 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 20ms
3220 +|(% rowspan="2" %)FC.03|Modbus Communication response delay|Factory default|2ms
3221 +|Setting range|(% colspan="2" %)0 to 20ms
3180 3180  
3181 3181  Response delay: the intermediate interval between the end of the VFD data acceptance and the sending of data to the upper machine. If the response delay is less than the system processing time, the response delay is based on the system processing time. If the response delay is longer than the system processing time, the system will wait until the response delay time reaches the upper computer before sending the data.
3182 3182  
3183 -|(% rowspan="2" style="text-align:center" %)FC.04|(% style="text-align:center" %)Modbus Communication timeout time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s
3184 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 s(In vain), 0.1 to 60.0s
3185 3185  
3226 +|(% rowspan="2" %)FC.04|Modbus Communication timeout time|Factory default|0.0s
3227 +|Setting range|(% colspan="2" %)0.0 s(In vain), 0.1-60.0s
3228 +
3186 3186  When the function code is set to 0.0s, the communication timeout parameter is invalid.
3187 3187  
3188 3188  When this function code is set to valid value, if the interval between one communication and the next communication exceeds the communication timeout period, the system reports a communication fault error (Err16). Usually, this is set to invalid. If you set the next parameter in a continuous communication system, you can monitor the communication status.
3189 3189  
3190 -== **FD Group multi-speed function and simple PLC function** ==
3191 3191  
3234 +**FD Group multi-speed function and simple PLC function**
3235 +
3192 3192  Simple PLC function is the inverter built-in a programmable controller (PLC) to complete the automatic control of multi-segment frequency logic. Operation time, operation direction and operation frequency can be set to meet the requirements of the process. This series of inverter can realize 16 speed change control, there are 4 kinds of acceleration and deceleration time to choose. When the set PLC completes a cycle, an ON signal can be output by the multifunctional digital output terminal DO1, DO2 or the multifunctional relay relay 1, relay 2. See F1.02 to F1.05 for details. When the frequency source F0.07, F0.03, F0.04 is selected to determine the multi-speed operation mode, FD.00 to FD.15 needs to be set to determine its characteristics.
3193 3193  
3194 3194  |(% rowspan="2" %)FD.00|Multi-segment speed instruction 0|Factory default|0
... ... @@ -3273,72 +3273,73 @@
3273 3273  
3274 3274  PLC shutdown retention: Record the operating stage and operating frequency of the previous PLC during shutdown.
3275 3275  
3276 -|(% rowspan="2" style="text-align:center" %)FD.18|(% style="text-align:center" %)PLC stage 0 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3277 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3278 -|(% rowspan="2" style="text-align:center" %)FD.19|(% style="text-align:center" %)PLC phase 0 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3279 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3280 -|(% rowspan="2" style="text-align:center" %)FD.20|(% style="text-align:center" %)PLC stage 1 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3281 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3282 -|(% rowspan="2" style="text-align:center" %)FD.21|(% style="text-align:center" %)PLC phase 1 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3283 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3284 -|(% rowspan="2" style="text-align:center" %)FD.22|(% style="text-align:center" %)PLC stage 2 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3285 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3286 -|(% rowspan="2" style="text-align:center" %)FD.23|(% style="text-align:center" %)PLC phase 2 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3287 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3288 -|(% rowspan="2" style="text-align:center" %)FD.24|(% style="text-align:center" %)PLC stage 3 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3289 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3290 -|(% rowspan="2" style="text-align:center" %)FD.25|(% style="text-align:center" %)PLC phase 3 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3291 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3292 -|(% rowspan="2" style="text-align:center" %)FD.26|(% style="text-align:center" %)PLC stage 4 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3293 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3294 -|(% rowspan="2" style="text-align:center" %)FD.27|(% style="text-align:center" %)PLC phase 4 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3295 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3296 -|(% rowspan="2" style="text-align:center" %)FD.28|(% style="text-align:center" %)PLC stage 5 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3297 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h)-6553.5s(h)
3298 -|(% rowspan="2" style="text-align:center" %)FD.29|(% style="text-align:center" %)PLC phase 5 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3299 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3300 -|(% rowspan="2" style="text-align:center" %)FD.30|(% style="text-align:center" %)PLC stage 6 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3301 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3302 -|(% rowspan="2" style="text-align:center" %)FD.31|(% style="text-align:center" %)PLC phase 6 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3303 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3304 -|(% rowspan="2" style="text-align:center" %)FD.32|(% style="text-align:center" %)PLC stage 7 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3305 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3306 -|(% rowspan="2" style="text-align:center" %)FD.33|(% style="text-align:center" %)PLC phase 7 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3307 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3308 -|(% rowspan="2" style="text-align:center" %)FD.34|(% style="text-align:center" %)PLC stage 8 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3309 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3310 -|(% rowspan="2" style="text-align:center" %)FD.35|(% style="text-align:center" %)PLC phase 8 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3311 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0to 3
3312 -|(% rowspan="2" style="text-align:center" %)FD.36|(% style="text-align:center" %)PLC stage 9 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3313 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3314 -|(% rowspan="2" style="text-align:center" %)FD.37|(% style="text-align:center" %)PLC phase 9 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3315 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3316 -|(% rowspan="2" style="text-align:center" %)FD.38|(% style="text-align:center" %)PLC stage 10 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3317 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 s(h) to 6553.5s(h)
3318 -|(% rowspan="2" style="text-align:center" %)FD.39|(% style="text-align:center" %)PLC phase 10 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3319 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3320 -|(% rowspan="2" style="text-align:center" %)FD.40|(% style="text-align:center" %)PLC stage 11 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3321 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3322 -|(% rowspan="2" style="text-align:center" %)FD.41|(% style="text-align:center" %)PLC phase 11 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3323 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3324 -|(% rowspan="2" style="text-align:center" %)FD.42|(% style="text-align:center" %)PLC stage 12 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3325 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3326 -|(% rowspan="2" style="text-align:center" %)FD.43|(% style="text-align:center" %)PLC phase 12 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3327 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3328 -|(% rowspan="2" style="text-align:center" %)FD.44|(% style="text-align:center" %)PLC stage 13 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3329 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3330 -|(% rowspan="2" style="text-align:center" %)FD.45|(% style="text-align:center" %)PLC phase 13 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3331 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3332 -|(% rowspan="2" style="text-align:center" %)FD.46|(% style="text-align:center" %)PLC stage 14 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3333 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3334 -|(% rowspan="2" style="text-align:center" %)FD.47|(% style="text-align:center" %)PLC phase 14 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3335 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3336 -|(% rowspan="2" style="text-align:center" %)FD.48|(% style="text-align:center" %)PLC stage 15 operation time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0s(h)
3337 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0s(h) to 6553.5s(h)
3338 -|(% rowspan="2" style="text-align:center" %)FD.49|(% style="text-align:center" %)PLC phase 15 acceleration and deceleration time selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3339 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 3
3340 -|(% rowspan="2" style="text-align:center" %)FD.50|(% style="text-align:center" %)PLC operating time unit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3341 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:left" %)(((
3320 +
3321 +|(% rowspan="2" %)FD.18|PLC stage 0 operation time|Factory default|0.0s(h)
3322 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3323 +|(% rowspan="2" %)FD.19|PLC phase 0 acceleration and deceleration time selection|Factory default|0
3324 +|Setting range|(% colspan="2" %)0to 3
3325 +|(% rowspan="2" %)FD.20|PLC stage 1 operation time|Factory default|0.0s(h)
3326 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3327 +|(% rowspan="2" %)FD.21|PLC phase 1 acceleration and deceleration time selection|Factory default|0
3328 +|Setting range|(% colspan="2" %)0to 3
3329 +|(% rowspan="2" %)FD.22|PLC stage 2 operation time|Factory default|0.0s(h)
3330 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3331 +|(% rowspan="2" %)FD.23|PLC phase 2 acceleration and deceleration time selection|Factory default|0
3332 +|Setting range|(% colspan="2" %)0to 3
3333 +|(% rowspan="2" %)FD.24|PLC stage 3 operation time|Factory default|0.0s(h)
3334 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3335 +|(% rowspan="2" %)FD.25|PLC phase 3 acceleration and deceleration time selection|Factory default|0
3336 +|Setting range|(% colspan="2" %)0to 3
3337 +|(% rowspan="2" %)FD.26|PLC stage 4 operation time|Factory default|0.0s(h)
3338 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3339 +|(% rowspan="2" %)FD.27|PLC phase 4 acceleration and deceleration time selection|Factory default|0
3340 +|Setting range|(% colspan="2" %)0to 3
3341 +|(% rowspan="2" %)FD.28|PLC stage 5 operation time|Factory default|0.0s(h)
3342 +|Setting range|(% colspan="2" %)0.0s(h)-6553.5s(h)
3343 +|(% rowspan="2" %)FD.29|PLC phase 5 acceleration and deceleration time selection|Factory default|0
3344 +|Setting range|(% colspan="2" %)0to 3
3345 +|(% rowspan="2" %)FD.30|PLC stage 6 operation time|Factory default|0.0s(h)
3346 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3347 +|(% rowspan="2" %)FD.31|PLC phase 6 acceleration and deceleration time selection|Factory default|0
3348 +|Setting range|(% colspan="2" %)0to 3
3349 +|(% rowspan="2" %)FD.32|PLC stage 7 operation time|Factory default|0.0s(h)
3350 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3351 +|(% rowspan="2" %)FD.33|PLC phase 7 acceleration and deceleration time selection|Factory default|0
3352 +|Setting range|(% colspan="2" %)0to 3
3353 +|(% rowspan="2" %)FD.34|PLC stage 8 operation time|Factory default|0.0s(h)
3354 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3355 +|(% rowspan="2" %)FD.35|PLC phase 8 acceleration and deceleration time selection|Factory default|0
3356 +|Setting range|(% colspan="2" %)0to 3
3357 +|(% rowspan="2" %)FD.36|PLC stage 9 operation time|Factory default|0.0s(h)
3358 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3359 +|(% rowspan="2" %)FD.37|PLC phase 9 acceleration and deceleration time selection|Factory default|0
3360 +|Setting range|(% colspan="2" %)0 to 3
3361 +|(% rowspan="2" %)FD.38|PLC stage 10 operation time|Factory default|0.0s(h)
3362 +|Setting range|(% colspan="2" %)0.0 s(h) to 6553.5s(h)
3363 +|(% rowspan="2" %)FD.39|PLC phase 10 acceleration and deceleration time selection|Factory default|0
3364 +|Setting range|(% colspan="2" %)0 to 3
3365 +|(% rowspan="2" %)FD.40|PLC stage 11 operation time|Factory default|0.0s(h)
3366 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3367 +|(% rowspan="2" %)FD.41|PLC phase 11 acceleration and deceleration time selection|Factory default|0
3368 +|Setting range|(% colspan="2" %)0 to 3
3369 +|(% rowspan="2" %)FD.42|PLC stage 12 operation time|Factory default|0.0s(h)
3370 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3371 +|(% rowspan="2" %)FD.43|PLC phase 12 acceleration and deceleration time selection|Factory default|0
3372 +|Setting range|(% colspan="2" %)0 to 3
3373 +|(% rowspan="2" %)FD.44|PLC stage 13 operation time|Factory default|0.0s(h)
3374 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3375 +|(% rowspan="2" %)FD.45|PLC phase 13 acceleration and deceleration time selection|Factory default|0
3376 +|Setting range|(% colspan="2" %)0 to 3
3377 +|(% rowspan="2" %)FD.46|PLC stage 14 operation time|Factory default|0.0s(h)
3378 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3379 +|(% rowspan="2" %)FD.47|PLC phase 14 acceleration and deceleration time selection|Factory default|0
3380 +|Setting range|(% colspan="2" %)0 to 3
3381 +|(% rowspan="2" %)FD.48|PLC stage 15 operation time|Factory default|0.0s(h)
3382 +|Setting range|(% colspan="2" %)0.0s(h) to 6553.5s(h)
3383 +|(% rowspan="2" %)FD.49|PLC phase 15 acceleration and deceleration time selection|Factory default|0
3384 +|Setting range|(% colspan="2" %)0 to 3
3385 +|(% rowspan="2" %)FD.50|PLC operating time unit|Factory default|0
3386 +|Setting range|(% colspan="2" %)(((
3342 3342  LED units: Timing unit
3343 3343  
3344 3344  0: s(seconds)
... ... @@ -3347,15 +3347,15 @@
3347 3347  
3348 3348  2: min(minutes)
3349 3349  )))
3350 -|(% rowspan="2" style="text-align:center" %)FD.51|(% style="text-align:center" %)Multi-segment speed instruction 0 given mode|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3351 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3395 +|(% rowspan="2" %)FD.51|Multi-segment speed instruction 0 given mode|Factory default|0
3396 +|Setting range|(% colspan="2" %)(((
3352 3352  0: Function code FD.00 given
3353 3353  
3354 -1: AI1 given
3399 +1: AI1
3355 3355  
3356 -2: AI2 given
3401 +2: AI2
3357 3357  
3358 -3: AI3 given
3403 +3: AI3
3359 3359  
3360 3360  4: Set the terminal PULSE
3361 3361  
... ... @@ -3363,15 +3363,18 @@
3363 3363  
3364 3364  6: Preset frequency (F0.08) given, UP/DOWN can be modified
3365 3365  
3366 -7: Keyboard potentiometer set
3411 +7: keyboard potentiometer set
3367 3367  )))
3368 3368  
3414 +
3415 +
3369 3369  This parameter determines the target amount of the multi-segment speed 0 given channel.
3370 3370  
3371 3371  FD.50: PLC operating time unit.
3372 3372  
3373 -|(% rowspan="2" style="text-align:center" %)FD.52|(% style="text-align:center" %)Multiple speed is preferred|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
3374 -|(% style="text-align:center" %)Set range|(% colspan="2" style="text-align:center" %)(((
3420 +
3421 +|(% rowspan="2" %)FD.52|Multiple speed is preferred|Factory default|1
3422 +|Set range|(% colspan="2" %)(((
3375 3375  0: Invalid
3376 3376  
3377 3377  1: Valid
... ... @@ -3379,20 +3379,21 @@
3379 3379  
3380 3380  Set this parameter to 1, F0.03 set the main frequency source not to multi-segment speed, and set F5 group terminal parameter multi-segment speed function~,~, when the terminal is valid, the frequency source switches to the multi-segment speed set, the multi-segment speed priority has nothing to do with the multi-segment speed 0.
3381 3381  
3382 -== **FE Group user password** ==
3430 +**FE Group user password**
3383 3383  
3384 -|(% rowspan="2" style="text-align:center" %)FE.00|(% style="text-align:center" %)User password|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3385 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 65535
3432 +|(% rowspan="2" %)FE.00|User password|Factory default|0
3433 +|Setting range|(% colspan="2" %)0 to 65535
3386 3386  
3387 3387  If the value is set to any non-zero number, the password protection function takes effect. 00000: Clears the previously set password value and invalidates the password protection function. After the user password is set and takes effect, if you enter the parameter setting state again and the user password is incorrect, the parameter group cannot be entered and cannot be viewed/modified. Remember the user password you set. If you accidentally set or forget, please contact the manufacturer.
3388 3388  
3389 -|(% rowspan="2" style="text-align:center" %)FE.01|(% style="text-align:center" %)Number of times to display fault records|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)4
3390 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 8
3437 +|(% rowspan="2" %)FE.01|Number of times to display fault records|Factory default|4
3438 +|Setting range|(% colspan="2" %)0 to 8
3391 3391  
3392 3392  This function code is used to set the number of times that fault records are displayed.
3393 3393  
3394 -|(% rowspan="2" style="text-align:center" %)FE.02|(% style="text-align:center" %)Parameter and key lock selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3395 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3442 +
3443 +|(% rowspan="2" %)FE.02|Parameter and key lock selection|Factory default|0
3444 +|Setting range|(% colspan="2" %)(((
3396 3396  0: Not locked
3397 3397  
3398 3398  1: The function parameter is locked
... ... @@ -3400,10 +3400,11 @@
3400 3400  
3401 3401  This function code is used to lock a parameter. After the parameter is locked, it cannot be modified.
3402 3402  
3403 -== **A0 Displays the parameter group** ==
3404 3404  
3405 -|(% rowspan="2" style="text-align:center" %)A0.00|(% style="text-align:center" %)Application macro|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
3406 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
3453 +**A0 Displays the parameter group**
3454 +
3455 +|(% rowspan="2" %)A0.00|Application macro|Factory default|0
3456 +|Setting range|(% colspan="2" %)(((
3407 3407  0: Default macro
3408 3408  
3409 3409  1: Tile press macro
1763358952427-755.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -637.5 KB
Content
1763360417842-953.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -32.9 KB
Content
wps2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -418.7 KB
Content