Iris 1.1 1 **F0 group basic function group**
2
Iris 1.2 3 |(% rowspan="2" style="text-align:center" %)F0.00|(% style="text-align:center" %)Motor control mode|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
4 |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
Iris 1.1 5 0: Speed sensorless vector control (SVC)
6
7 1: V/F control
8 )))
9
10 0: Speed sensorless vector control
11
12 Refers to an open loop vector. Suitable for the usual high-performance control occasions, one inverter can only drive one motor. Such as machine tools, centrifuges, wire drawing machines, injection molding machines and other loads.
13
14 1: V/F control
15
16 It is suitable for occasions where the load requirement is not high or a VFD drags multiple motors, such as fans and pumps. It can be used for driving multiple motors with one VFD.
17
18 Tip: When selecting the vector control mode, the motor parameter identification process must be carried out. Only accurate motor parameters can give full play to the advantages of vector control.
19
Iris 1.2 20 |(% rowspan="2" style="text-align:center" %)F0.01|(% style="text-align:center" %)Command source selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
21 |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
Iris 1.1 22 0: Operation panel command channel
23
24 1: Terminal command channel
25
26 2: Serial port communication command
27
28 channel
29 )))
30
31 Select the channel for the inverter control command.
32
33 Inverter control commands include: start, stop, forward, reverse, point and so on.
34
35 0: Operation panel command channel
36
37 The command is controlled by the key on the operation panel.
38
39 1: Terminal command channel
40
41 It is controlled by the multi-function input terminals FWD, REV, FJOG, RJOG, etc.
42
43 2: Serial port communication command channel
44
45 The host computer gives the running command control through the communication mode.
46
Iris 1.2 47 |(% rowspan="2" style="text-align:center" %)F0.02|(% style="text-align:center" %)Run time UP/DOWN benchmark|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
48 |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
Iris 1.1 49 0: Operating frequency
50
51 1: Setting frequency
52 )))
53
54 This function only effective for frequency source digital setting, in order to determine the setting frequency of UP/DOWN is current running frequency or current setting frequency.
55
Iris 1.2 56 |(% rowspan="2" style="text-align:center" %)F0.03|(% style="text-align:center; width:240px" %)Main frequency source X choice|(% style="text-align:center; width:252px" %)Factory default|(% style="text-align:center" %)4
57 |(% style="text-align:center; width:240px" %)Setting range|(% colspan="2" style="width:332px" %)(((
Iris 1.1 58 0: Digital setting F0.08 (Adjustable terminal UP/DOWN, be not retained at power failure)
59
60 1: Digital setting F0.08 (Adjustable terminal UP/DOWN, be retained at power failure)
61
62 2: AI1
63
64 3: AI2
65
66 4: Keyboard potentiometer set
67
68 5: Set the terminal PULSE
69
70 6: Multi-speed instruction
71
72 7: Simple PLC
73
74 8: PID
75
76 9: Communication settings
77
78 10: AI3(Expansion module)
79 )))
80
81
82
83 Select the input channel for the main given frequency of the inverter. There are 10 main given frequency channels:
84
85 0: Digital setting (no memory) (Potentiometer and terminal UP/DOWN adjustable, power failure no memory) The initial value is F0.08 value of Digital Setting Preset Frequency. The set frequency value of the inverter can be changed by ▲/▼ key of the keyboard (or the UP and DOWN of the multi-function input terminal). No memory means that after the inverter power off, the set frequency value is restored to the initial value;
86
87 1: Digital setting (memory) (Potentiometer and terminal UP/DOWN adjustable, power failure memory) The initial value is F0.08 "digital setting preset frequency" value. The set frequency value of the inverter can be changed by ▲/▼ key of the keyboard (or the UP and DOWN of the multi-function input terminal). Memory means that when the inverter is powered on again after power failure, the set frequency is the set frequency before the last power failure
88
89 2: AI1 3: AI2 refers to the frequency determined by the analog input terminal. The standard unit provides two analog input terminals (AI1, AI2), of which AI1 is 0V to 10V voltage input, AI2 can be 0V to 10V voltage input, or 4mA to 20mA current input.
90
91 4: Potentiometer set by keyboard potentiometer to set the frequency
92
93 5: PULSE pulse setting (DI4) The frequency setting is set by the terminal pulse. Pulse given signal specifications: voltage range, frequency range 0kHz to 20kHz. Note: Pulse Settings can only be input from the multi-function input terminal DI4.
94
95 6: Multi-speed Select the multi-speed operation mode. The F5 "input terminal" and FD "multi-speed and PLC" parameters need to be set to determine the correspondence between a given signal and a given frequency.
96
97 7: Simple PLC Select simple PLC mode. When the frequency source is a simple PLC, the FD group "multi-speed and PLC" parameters need to be set to determine the given frequency.
98
99 8: PID selection process PID control. In this case, set the PID function of the F9 group. The operating frequency of the inverter is the frequency value after PID action. For the meaning of PID set source, feed quantity and feedback source, please refer to the introduction of F9 group "PID Function".
100
101 9: Communication set means that the main frequency source is given by the host computer through communication.
102
103 |(% rowspan="2" %)F0.04|Auxiliary frequency source Y selection|Factory default|4
104 |Setting range|(% colspan="2" %)(((
105 0: Numeric setting F0.08
106
107 (Terminal UP/DOWN can be change, Power failure does not remember. It is cleared after switching as a frequency source.)
108
109 1: Numeric setting F0.08
110
111 (Terminal UP/DOWN adjustable, be retained at power failure.)
112
113 2: AI1 given
114
115 3: AI2 given
116
117 4: Keyboard potentiometer set.
118
119 5: The terminal PULSE pulse is set.
120
121 6: Multi-speed instruction
122
123 7: Simple PLC
124
125 8: PID
126
127 9: Communication setting
128 )))
129
130
131
132 The secondary frequency source Y is used in the same way as the primary frequency source X when it is used as an independent frequency given channel (that is, the frequency source selected to switch from X to Y).
133
134 |(% rowspan="2" %)F0.05|The auxiliary frequency source Y range is selected during superposition|Factory default|0
135 |Setting range|(% colspan="2" %)(((
136 0: Relative to the maximum frequency  F0.10
137
138 1: Relative to the frequency source X
139 )))
140 |(% rowspan="2" %)F0.06|Auxiliary frequency source Y range in superposition|Factory default|100%
141 |Setting range|(% colspan="2" %)0%-150%
142
143
144
145 When the frequency source is selected as a frequency stack (F0.07 is set to 1, 3, or 4), it is used to determine the adjustment range of the auxiliary frequency source. F0.05 is used to determine the object relative to the range, if it is relative to the maximum frequency (F0.10), the range is a fixed value; If it is relative to the primary frequency source X, its range will change as the primary frequency source X changes.
146
147 |(% rowspan="2" %)F0.07|Frequency source stack selection|Factory default|0
148 |Setting range|(% colspan="2" %)(((
149 LED bits: Frequency source selection
150
151 0: Primary frequency source
152
153 1: Results of primary and secondary operations
154
155 2: Master-auxiliary switching
156
157 3: Switch between primary frequency source and operation result
158
159 4: Switch between primary frequency source and operation result
160
161 LED ten: combination mode selection
162
163 0: Primary + Auxiliary
164
165 1: Master-auxiliary
166
167 2: Maximum value of both
168
169 3: Minimum of both
170
171 4: Main x auxiliary
172 )))
173
174
175
176 The secondary frequency source is used in the same way as the primary frequency source X when it is used as an independent frequency given channel (that is, the frequency source selected is switched from X to Y). When the secondary frequency source is used as a superposition given (i.e., the frequency source selected is X+Y, X to X+Y switching, or Y to X+Y switching), there are the following special features:
177
178 When the auxiliary frequency source for digital or pulse potentiometer timing, preset frequency (F0.08) does not work, through the keyboard ▲/▼ key (or multi-function input terminal UP, DOWN) can be adjusted on the basis of the main given frequency.
179
180 When the auxiliary frequency source is given as an analog input (AI1, AI2) or a pulse input, 100% of the input setting corresponds to the auxiliary frequency source range (see F0.05 and F0.06 instructions). If you need to adjust up or down from the main given frequency, set the analog input to a range of.n% to +n%.
181
182 The frequency source is timed for pulse input, similar to analog quantity setting.
183
184 Tip: The secondary frequency source Y and the primary frequency source X Settings cannot be the same, that is, the primary and secondary frequency sources cannot use the same frequency given channel.
185
186 |(% rowspan="2" %)F0.08|Keyboard setting frequency|Factory default|50.00Hz
187 |Setting range|(% colspan="2" %)0.00 to Maximum frequency F0.10
188
189 When the frequency source is selected “Numeric setting F0.08 (Terminal UP/DOWN Adjustable, power down memory) ", the function code value sets the initial value for the frequency number of the inverter.
190
191 |(% rowspan="2" %)F0.09|Running direction selection|Factory default|0
192 |Setting range|(% colspan="2" %)(((
193 0: The same direction
194
195 1: The direction is reversed
196
197 2: Reverse prohibition
198 )))
199
200 By changing the function code, the steering of the motor can be changed without changing any other parameters, which is equivalent to the conversion of the rotation direction of the motor by adjusting any two lines of the motor (U, V, W).
201
202 Tip: The motor running direction will be restored to the original state after parameter initialization. For the system debugging is strictly prohibited to change the motor steering occasions with caution.
203
204 |(% rowspan="2" %)F0.10|Maximum output frequency|Factory default|50.00 Hz
205 |Setting range|(% colspan="2" %)0.00 to 320.00Hz
206
207 When F0.26=1, the upper limit of the maximum frequency is 1000Hz. When F0.26=2, the upper limit of the maximum frequency is 320Hz.
208
209 |(% rowspan="2" %)F0.11|Upper limit frequency source selection|Factory default|0
210 |Setting range|(% colspan="2" %)(((
211 0: The number is F0.12
212
213 1: AI1
214
215 2: AI2
216
217 3: AI3(Expansion module)
218
219 4: Set the terminal PULSE
220
221 5: Communication given
222
223 6: Reserved
224
225 7: Keyboard potentiometer set
226 )))
227
228 Define the source of the upper limit frequency.
229
230 0: Number setting (F0.12).
231
232 1/2/3: Analog input channel. When setting an upper limit frequency with an analog input, 100% of the analog input setting corresponds to F0.12.
233
234 4: Set by terminal pulse.
235
236 5: Communication given 10000 corresponds to F0.12.
237
238 7: Set by keyboard potentiometer.
239
240 For example, in torque control, speed control is not effective. In order to avoid the "speed" of material breakage, the upper limit frequency can be set with the analog quantity. When the inverter runs to the upper limit frequency value, the torque control is invalid and the inverter continues to run at the upper limit frequency.
241
242 |(% rowspan="2" %)F0.12|Upper limit frequency|Factory default|50.00Hz
243 |Setting range|(% colspan="2" %)Lower frequency F0.14-Maximum frequency F0.10
244 |(% rowspan="2" %)F0.13|Upper frequency bias|Factory default|0.00Hz
245 |Setting range|(% colspan="2" %)0.00Hz to Maximum frequency F0.10
246
247 When the upper limit frequency is given by the analog quantity, this parameter is used as the bias quantity calculated by the upper limit frequency, and this upper limit frequency offset is added to the set value of the upper limit frequency of the simulation as the set value of the final upper limit frequency.
248
249 |(% rowspan="2" %)F0.14|Lower frequency|Factory default|0.00Hz
250 |Setting range|(% colspan="2" %)0.00Hz to Upper limit frequency F0.12
251
252 When the VFD starts to run, it starts from the start frequency. If the given frequency is less than the lower limit frequency during operation, the VFD runs at the lower limit frequency, stops or runs at zero speed. You can set which mode of operation to use with F0.15.
253
254 |(% rowspan="2" %)F0.15|Lower frequency Operating mode|Factory default|0
255 |Setting range|(% colspan="2" %)(((
256 0: Run at the lower limit frequency
257
258 1: Stop
259
260 2: Zero speed operation
261 )))
262
263
264
265 Select the operating state of the inverter when the set frequency is lower than the lower limit frequency. In order to avoid the motor running at low speed for a long time, you can use this function to choose to stop.
266
267 |(% rowspan="2" %)[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps1.png]]F0.16|Carrier frequency|Factory default|Model determination
268 |Setting range|(% colspan="2" %)0.5kHz to 16.0kHz
269
270
271
272 This function regulates the carrier frequency of the inverter. By adjusting the carrier frequency, the motor noise can be reduced, the resonance point of the mechanical system can be avoided, and the interference of the line to the floor drain current and the VFD can be reduced.
273
274 When the carrier frequency is low, the higher harmonic component of the output current increases, the motor loss increases, and the motor temperature rise increases.
275
276 When the carrier frequency is high, the motor loss decreases and the motor temperature rise decreases, but the VFD loss increases, the VFD temperature rise increases and the interference increases.
277
278 The effect of adjusting the carrier frequency on the following performance:
279
280
281 |Carrier frequency|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps2.png]]Low High
282 |Motor noise|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps3.png]]High Low
283 |The output current waveform|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps4.png]]Worse Better
284 |Temperature rise in electric motors|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps5.png]]High Low
285 |VFD temperature rise|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps6.png]]Low High
286 |Leak current|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps7.png]]Low High
287 |External radiation interference|[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps8.png]]Low High
288
289
290
291 |(% rowspan="2" %)[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps9.png]]F0.17|Carrier PWM baud selection|Factory default|1010
292 |Setting range|(% colspan="2" %)(((
293 Bits: Select PWM mode
294
295 0: Automatic switching;
296
297 1: 7 wave;
298
299 2: 5 wave;
300
301 3: SPWM;
302
303 LED ten: Carrier is associated with the output frequency
304
305 0: Independent of the output frequency
306
307 1: Related to the output frequency
308
309 LED hundred: random PWM depth
310
311 0: Off
312
313 1-8: Open and adjust the depth
314
315 LED kilobit: Over modulation option
316
317 0: Off
318
319 1: On
320 )))
321 |(% rowspan="2" %)F0.18|Acceleration time 1|Factory default|Model determination
322 |Setting range|(% colspan="2" %)0.0s to 6500.0s
323 |(% rowspan="2" %)F0.19|Deceleration time1|Factory default|Model determination
324 |Setting range|(% colspan="2" %)0.0s to 6500.0s
325
326
327
328 One place: Select PWM mode
329
330 VFD can choose 5-section wave or 7-section wave, the 5-section wave converter has little heat, and the 7-section wave motor has little noise. When the bit is 0, 7 waves are generated at low frequency and 5 waves are generated at high frequency. At 1 o 'clock, the whole wave is 7 stages, and at 2 o'clock, the whole wave is 5 stages.
331
332 Tens place: The carrier is associated with the output frequency
333
334 When the output frequency is low, reducing the PWM carrier can increase the low frequency starting torque and reduce the electromagnetic interference during starting. When the bit is 1, the program automatically reduces the PWM carrier when the output frequency is low.
335
336 Hundreds palce: Random PWM depth
337
338 In order to make the motor noise spectrum flatter, you can turn on the random PWM function, after the function is turned on, the PWM carrier is no longer a fixed value, but fluctuates around the F0.16 set carrier. When the bit is not 0, the random PWM function works. The larger the value, the wider the fluctuation range and the flatter the noise spectrum. It should be noted that after opening the random carrier, the electromagnetic noise of the motor will not necessarily be reduced, and the actual noise perception varies from person to person.
339
340 Thousands place: Over modulation option
341
342 The over modulation function can increase the maximum output voltage of the inverter, but it also makes the current distortion more obvious. When the bit is 1, the over modulation function is enabled.
343
344 Acceleration time refers to the time required for the inverter to accelerate from zero frequency to the reference frequency of acceleration and deceleration (determined by F0.24), as shown in t1 in Figure 9-0-1.
345
346 Deceleration time refers to the time required for the VFD to decelerate from the reference frequency of acceleration and deceleration (determined by F0.24) to the zero frequency, see t2 in Figure 9-0-1.
347
348
349 [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps10.jpg]]
350
351 Figure 9-0-1 Acceleration and deceleration time
352
353 Note the difference between the actual acceleration and deceleration time and the set acceleration and deceleration time.
354
355 There are four groups of acceleration and deceleration time selection
356
357 Group 1: F0.18, F0.19;
358
359 Group 2: F8.03, F8.04;
360
361 Group 3: F8.05, F8.06;
362
363 Group 4: F8.07, F8.08.
364
365 The acceleration and deceleration time can be selected through the multifunctional digital input terminals (F5.00 to F5.03).
366
367
368 |(% rowspan="2" %)F0.20|Parameter initialization|Factory default|0
369 |Setting range|(% colspan="2" %)(((
370 0: No opreration
371
372 1: Restore factorydefault (Do not restore motor parameters)
373
374 2: Clear the record information
375
376 3: Restore factory default (Restore motor parameters)
377 )))
378
379 1: Restore factory settings, excluding motor parameters
380
381 2: Clear recorded information, clear the VFD fault record, cumulative running time (F7.09), cumulative power-on time (F7.13),
382
383 Cumulative power consumption (F7.14).
384
385 3: Restore all factory settings, including motor parameters, and clear the recorded information at the same time.
386
387 |(% rowspan="2" %)F0.23|Unit of acceleration and deceleration time|Factory default|1
388 |Setting range|(% colspan="2" %)(((
389 0: 1s
390
391 1: 0.1s
392
393 2: 0.01s
394 )))
395
396 This function is used to determine all acceleration and deceleration time units.
397
398 Note that when the value is modified, the actual acceleration and deceleration time will also change accordingly (the decimal point position changes, the actual display number remains unchanged), Therefore, it is necessary to adjust the various acceleration and deceleration Settings according to the situation.
399
400 Note the following function codes: F0.18, F0.19, F8.01, F8.02, F8.03, F8.04, F8.05, F8.06, F8.07, F8.08.
401
402 |(% rowspan="2" %)F0.24|Acceleration and deceleration time reference frequency|Factory default|0
403 |Setting range|(% colspan="2" %)(((
404 0: Maximum frequency (F0.10)
405
406 1: Set the frequency
407
408 2: 100 Hz
409 )))
410
411 Define the frequency range corresponding to the acceleration and deceleration time. See Figure 9-0-1 Acceleration and deceleration time.
412
413 |(% rowspan="2" %)F0.25|Fan control|Factory default|01
414 |Setting range|(% colspan="2" %)(((
415 One place: start/stop control
416
417 0: The fan runs after the inverter is powered on
418
419 1: Shutdown is related to temperature, and operation is running
420
421 2: Stop The fan stops and the operation is temperature-related
422
423 Tens place: Enables the speed adjustment function
424
425 0: Off
426
427 1: Enable
428 )))
429
430 1: Start-stop control: After startup, the device runs. If the temperature is above 50 degrees when stopped, it continues to run.
431
432 2: Temperature control: More than 50 degrees to start operation
433
434 Tens place: Enables the speed adjustment function
435
436 Speed control: Below 45°C: Operate at 50% speed; From 45°C to 50°C: Operate at 75% speed; At 50°C and above: Operate at 100% speed.
437
438
439 |(% rowspan="2" %)F0.26|Frequency command decimal point|Factory default|2
440 |Setting range|(% colspan="2" %)(((
441 1: 1 decimal places
442
443 2: 2 decimal places
444 )))
445
446
447
448 This parameter is not restored when restoring factory defaults.
449
450 |(% rowspan="2" %)F0.27|Modulation ratio coefficient|Factory default|100.0%
451 |Setting range|(% colspan="2" %)10.0 to 150.0%
452
453
454
455 This parameter is the upper limit of the modulation ratio. The lower the modulation ratio, the lower the maximum output voltage; The higher the modulation ratio, the more obvious the current distortion during over modulation.
456
457 **F1 group start stop control**
458
459 |(% rowspan="2" %)F1.00|Start-up operation mode|Factory default|00
460 |Setting range|(% colspan="2" %)(((
461 LED ones place: Boot mode
462
463 0: Start directly from the start frequency
464
465 1: Start after speed tracking and direction judgment
466
467 2: The asynchronous machine starts with pre-excitation
468 )))
469
470 0: Direct startup
471
472 1: Start after speed tracking and direction judgment
473
474 The inverter first detects the steering and speed of the motor, and then starts according to the real-time speed. It is suitable for instantaneous power failure and restart of large inertia load or smooth restart of rotating equipment. Set accurate F2 motor parameters for better speed tracking and restart performance.
475
476 2: The asynchronous machine starts with pre-excitation
477
478 Pre-excitation current, time and DC braking current, time share function code. If F1.09 pre-start braking time is set to 0, start from the start frequency. When the value is not set to 0, pre-excitation is implemented before startup to improve the dynamic response speed.
479
480
481 |(% rowspan="2" %)F1.01|Speed tracking mode|Factory default|0
482 |Setting range|(% colspan="2" %)(((
483 LED tens place: speed tracking direction
484
485 0: One to the stop direction
486
487 1: One to the starting direction
488
489 2: Automatic search
490 )))
491
492
493
494 Ten: speed tracking direction
495
496 This parameter determines the direction from which to start speed tracking. Please set it correctly according to the actual situation. If the setting is wrong, the startup may fail. In the case of not knowing the starting direction, you can set to automatic search, the program will automatically judge the starting direction, but the search time will be lengthened accordingly.
497
498
499 |(% rowspan="2" %)F1.02|Speed tracking time|Factory default|1.00s
500 |Setting range|(% colspan="2" %)0.01 to 60.00s
501
502
503
504 If the speed tracking time is too short, the tracking may end without tracking the actual frequency. At F1.01=002X, if the search direction is wrong, two searches will be performed and the actual search time will be doubled.
505
506
507 |(% rowspan="2" %)F1.03|Speed tracking current loop gain|Factory default|10.00
508 |Setting range|(% colspan="2" %)0.00 to 10.00
509 |(% rowspan="2" %)F1.04|(((
510 RPM tracking
511
512 speed gain
513 )))|Factory default|2.00
514 |Setting range|(% colspan="2" %)0.01 to 10.00
515
516
517
518 The excitation search current loop gain and velocity loop gain are determined.
519
520
521 |(% rowspan="2" %)F1.05|Speed tracking current|Factory default|150%
522 |Setting range|(% colspan="2" %)50% to 200%
523
524
525
526 Set the excitation search current size.
527
528 |(% rowspan="2" %)F1.06|Starting frequency|Factory default|0.00Hz
529 |Setting range|(% colspan="2" %)0.0s to 60.00Hz
530 |(% rowspan="2" %)F1.07|Startup frequency duration|Factory default|0.0s
531 |Setting range|(% colspan="2" %)0.0 to 50.0s
532
533
534
535 In order to ensure the torque during startup, please use the appropriate startup frequency.In addition, the magnetic flux is established when waiting for the motor to start, so that the starting frequency is maintained for a certain time before accelerating.The starting frequency is maintained for a certain time before accelerating. The startup frequency F1.06 is not limited by the lower frequency. If the frequency given less than startup frequency, the AC driver can no be started, and it will standby state.The startup frequency holding time is not work during forward/reverse switching. The holding time is not included in the acceleration time, but is included in the running time of the simple PLC.
536
537 |(% rowspan="2" %)F1.08|Braking current before starting|Factory default|80.0%
538 |Setting range|(% colspan="2" %)0.0 to 150.0%
539 |(% rowspan="2" %)F1.09|Braking time before starting|Factory default|0.0s
540 |Setting range|(% colspan="2" %)0.0 to 60.0s
541
542
543
544 Starting DC braking is generally used to stop the motor completely before starting.
545
546 If the starting mode is starting after the DC braking, the AC driver will execute the DC braking as the setting value, and it will start running after the setting starting braking time value. It will direct start without DC braking if the setting DC braking time is 0. The braking power is greater with the greater DC braking current.
547
548
549 |(% rowspan="2" %)F1.10|Shutdown mode|Factory default|0
550 |Setting range|(% colspan="2" %)(((
551 0: Slow down stop
552
553 1: Free stop
554 )))
555
556
557
558 0: Slow down stop
559
560 After the stop command is effective, the inverter reduces the output frequency according to the deceleration mode and the defined acceleration and deceleration time, and stops after the frequency drops to 0.
561
562 1: Free stop
563
564 When the stop command is valid, the inverter terminates output immediately. The load stops freely according to mechanical inertia.
565
566 |(% rowspan="2" %)F1.11|Stop DC braking start frequency|Factory default|0.00Hz
567 |Setting range|(% colspan="2" %)0.00Hz to Maximum frequency F0.10
568 |(% rowspan="2" %)F1.12|Stop DC braking wait time|Factory default|0.0s
569 |Setting range|(% colspan="2" %)0.0s to 100.0s
570 |(% rowspan="2" %)F1.13|Stop DC braking current|Factory default|80.0%
571 |Setting range|(% colspan="2" %)0%-150%
572 |(% rowspan="2" %)F1.14|Stop DC braking duration|Factory default|0.0s
573 |Setting range|(% colspan="2" %)0.0s to 100.0s
574
575
576
577 DC braking start frequency: slow down the stopping process. When the output frequency is less than this frequency, the DC braking process starts to stop.
578
579 Dc braking waiting time: When the output frequency is reduced to F1.11 DC braking starting frequency, the inverter stops output and starts timing. After the delay time set by F1.12, DC braking starts again. Used to prevent over current failure caused by DC braking at high speeds.
580
581 Stop DC braking current: refers to the amount of DC braking applied. The greater the value, the stronger the DC braking effect.
582
583 Dc braking time: the time added to the DC braking amount. When this value is 0, it means that there is no DC braking process, and the inverter stops according to the set deceleration stop process.
584
585 [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml13344\wps11.jpg]]
586
587 Figure 9-1-1 Shutdown DC braking diagram
588
589
590 |(% rowspan="2" %)F1.16|Energy consumption brake action voltage|Factory default|Model-based setting
591 |Setting range|(% colspan="2" %)115.0% to 140.0%
592
593 Set the brake resistance operating voltage. When the relative value of the bus voltage is higher than this value, the brake resistance starts braking.
594
595 |(% rowspan="2" %)F1.17|Magnetic flux braking gain|Factory default|80%
596 |Setting range|(% colspan="2" %)10% to 500%
597 |(% rowspan="2" %)F1.18|Magnetic flux braking operating voltage|Factory default|Model-based setting
598 |Setting range|(% colspan="2" %)110% to 150%
599 |(% rowspan="2" %)F1.19|Flux brake limiting|Factory default|20%
600 |Setting range|(% colspan="2" %)0 to 200%
601
602 When the motor decelerates the feedback energy, opening the flux brake can consume the feedback energy on the motor, so as to achieve rapid deceleration of the motor. This function is only effective in asynchronous motor VF control, and turning on this function will correspondingly increase motor loss and motor temperature rise.
603
604 Magnetic flux braking gain: The strength of magnetic flux braking, the greater the parameter, the greater the magnetic flux braking current.
605
606 Magnetic flux braking action voltage: When the relative value of the bus voltage is higher than this value, magnetic flux braking begins to work.
607
608 Flux brake limiting: The upper limit of the flux brake voltage, which may cause the output current of the inverter to be too high.
609
610 |(% rowspan="2" %)F1.20|Acceleration and deceleration selection|Factory default|0
611 |Setting range|(% colspan="2" %)(((
612 0: Straight line
613
614 1: S curve
615 )))
616
617
618
619 0: Straight line, generally suitable for general purpose load.
620
621 1: S-curve, S-type acceleration and deceleration curve is mainly provided for the load that needs to slow down noise and vibration during acceleration and deceleration, reduce start-stop impact, or decrease torque at low frequency, and short-time acceleration at high frequency. If an over current or over load failure occurs at startup, reduce the set value of [F1.21].
622
623
624 |(% rowspan="2" %)F1.21|S-curve initial acceleration rate|Factory default|50.0%
625 |Setting range|(% colspan="2" %)20.0%-100.0%
626 |(% rowspan="2" %)F1.22|S-curve initial deceleration rate|Factory default|50.0%
627 |Setting range|(% colspan="2" %)20.0%-100.0%
628
629 S-curve Initial acceleration rate: The rate at which the acceleration process begins to increase in frequency. The smaller the initial acceleration rate, the more curved the S-curve of the acceleration process, whereas the larger the initial acceleration rate, the closer the acceleration S-curve to a straight line. To make the acceleration curve softer, you can reduce the initial acceleration rate and extend the acceleration time.
630
631 |(% rowspan="2" %)F1.23|Zero speed holding torque|Factory default|0
632 |Setting range|(% colspan="2" %)0.0% to 150.0%
633
634
635
636 Set the output torque of the inverter at zero speed. If the torque setting is large or the duration is long, attention should be paid to the heat dissipation of the motor.
637
638 |(% rowspan="2" %)F1.24|Zero speed holding torque time|Factory default|Model setting
639 |Setting range|(% colspan="2" %)(((
640 0.0 to 6000.0s
641
642 If the value is set to 6000.0s, the value remains unchanged without time limitation
643 )))
644
645
646
647 Set the torque holding time when the inverter is running at zero speed. The timing starts when the operating frequency is 0Hz, and the inverter stops output after the time reaches the set zero-speed holding torque time. Among them, the effective timing value is 0 to 5999.9s, and the parameters are set in the effective timing value of the VFD at the set time. After the time is full, the VFD terminates and maintains the zero-speed torque.
648
649 If the parameter setting is equal to 6000.0s, the VFD is not timed and defaults to long-term validity, and the zero-speed torque holding is terminated only after the stop command is given or the non-zero operating frequency is given.
650
651 Setting an appropriate zero-speed holding torque time can effectively achieve energy saving and protect the motor.
652
653 |(% rowspan="2" %)F1.25|Start pre-excitation time|Factory default|0.20
654 |Setting range|(% colspan="2" %)0.00 to 60.00s
655
656 This parameter is only valid if F0.00=0, in the open loop vector start, appropriate pre-excitation can make the start smoother.
657
658 |(% rowspan="2" %)F1.26|Shutdown frequency|Factory default|0.00Hz
659 |Setting range|(% colspan="2" %)0.00-60.00Hz
660
661 This function is defined as the frequency of the minimum output of the inverter, less than this frequency, the output of the inverter stops.
662
663 |(% rowspan="2" %)F1.27|Power failure restart action selection|Factory default|0
664 |Setting range|(% colspan="2" %)(((
665 0: Invalid
666
667 1: Valid
668 )))
669
670 0: Invalid VFD power after power failure must receive the operation instruction before running.
671
672 1: Valid If the inverter is in operation before the power is cut off, the inverter will automatically start after the power is restored and after the set waiting time (set by [F1.28]). During the waiting time of power failure and restart, the inverter does not accept the running command, but if the stop command is entered during this period, the inverter will release the restart state.
673
674 |(% rowspan="2" %)F1.28|Power failure restart waiting time|Factory default|0.50s
675 |Setting range|(% colspan="2" %)0.00 to 120.00s
676
677 When [F1.27] setting is effective, After the inverter power supply, it will wait for the time set in [F1.28] to start running.
678
679
680 |(% rowspan="2" %)F1.29|Select the terminal running protection|Factory default|11
681 |Setting range|(% colspan="2" %)(((
682 LED units digital: Select the terminal run instruction when powering on.
683
684 0: The terminal running instruction is invalid during power-on.
685
686 1: Terminal running instructions are valid during power-on.
687
688 LED tens place: Run instruction given channel switch terminal run instruction selection.
689
690 0: The terminal running instruction is invalid.
691
692 1: The terminal instruction is valid when the terminal is cut in.
693 )))
694
695 When terminal operation is selected, the initial wiring state of peripheral devices may affect the safety of the device. This parameter provides protective measures for terminal operation.
696
697
698 LED units place: Select the terminal run command when powering on
699
700 Select the mode of executing the operation instruction when the inverter is powered on with the terminal running signal in effect.
701
702 0: The terminal instruction is invalid during power-on. The terminal control stops before the power is started.
703
704 1: When the terminal is powered on, the terminal control instruction is valid.
705
706 LED tens place: Terminal run instruction selection when switching to terminal instruction from other instruction channels
707
708 Select the mode of running the instruction channel to switch to the terminal instruction mode and execute the running instruction when the terminal running signal is valid.
709
710 0: The terminal running instruction is invalid when cutting in. The terminal control stops before starting.
711
712 1: When the terminal instruction is effective, the terminal control can be started directly.
713
714
715 **F2 group motor parameters**
716
717 |(% rowspan="2" %)F2.00|Motor type|Factory default|0
718 |Setting range|(% colspan="2" %)(((
719 0: Asynchronous motor (AM)
720
721 1: Permanent magnet synchronous motor (PM)
722
723 2: Single-phase asynchronous motors (Only VF control is supported)
724 )))
725
726 2 Single-phase asynchronous motor refers to a single-phase motor without phase shift capacitance, U terminal is connected to the main winding, V terminal is connected to the common end, and W terminal is connected to the auxiliary winding.
727
728 | |(% rowspan="2" %)F2.01|(% colspan="2" %)Rated power of motor|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination|
729 | |(% colspan="2" %)Setting range|(% colspan="4" %)0.1kW to 400.0kW|
730 | |(% rowspan="2" %)F2.02|(% colspan="2" %)Rated voltage of motor|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination|
731 | |(% colspan="2" %)Setting range|(% colspan="4" %)1V to 440V|
732 | |(% rowspan="2" %)F2.03|(% colspan="2" %)Rated current of motor|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination|
733 | |(% colspan="2" %)Setting range|(% colspan="4" %)0.1A to 2000.0A|
734 | |(% rowspan="2" %)F2.04|(% colspan="2" %)Rated power of motor|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination|
735 | |(% colspan="2" %)Setting range|(% colspan="4" %)0.00Hz-Maximum frequency F0.10|
736 | |(% rowspan="2" %)F2.05|(% colspan="2" %)Rated motor speed|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination|
737 | |(% colspan="2" %)Setting range|(% colspan="4" %)1rpm to 65000rpm|
738 |(% colspan="8" %)**Note:**|
739 |(% colspan="8" %)(((
740 1. Please set according to the nameplate parameters of the motor.
741
742 2. The excellent control performance of vector control requires accurate motor parameters, and accurate parameter identification comes from the correct setting of the rated parameters of the motor.
743
744 3. In order to ensure the control performance, please configure the motor according to the inverter standard adaptation motor, if the motor power and the standard adaptation motor gap is too large, the control performance of the inverter will be significantly reduced.
745 )))|
746 |(% colspan="3" rowspan="2" %)F2.06|(% colspan="2" %)Motor stator resistance|(% colspan="2" %)Factory default|Model determination|
747 |(% colspan="2" %)Setting range|(% colspan="3" %)0.001Ω to 65.000Ω|
748 |(% colspan="3" rowspan="2" %)F2.07|(% colspan="2" %)Motor rotor resistance|(% colspan="2" %)Factory default|Model determination|
749 |(% colspan="2" %)Setting range|(% colspan="3" %)0.001Ω to 65.000Ω|
750 |(% colspan="3" rowspan="2" %)F2.08|(% colspan="2" %)Motor fixed rotor inductance|(% colspan="2" %)Factory default|Model determination|
751 |(% colspan="2" %)Setting range|(% colspan="4" %)0.1 to 6500.0mH
752 |(% colspan="3" rowspan="2" %)F2.09|(% colspan="2" %)Mutual inductance of motor fixed rotor|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination
753 |(% colspan="2" %)Setting range|(% colspan="4" %)0.1 to 6500.0mH
754 |(% colspan="3" rowspan="2" %)F2.10|(% colspan="2" %)Motor no-load current|(% colspan="2" %)Factory default|(% colspan="2" %)Model determination
755 |(% colspan="2" %)Setting range|(% colspan="4" %)0.1 to 650.0A
756
757 After the automatic tuning of the asynchronous motor is completed normally, the set values of the asynchronous motor parameters (F2.06 to F2.10) are automatically updated.
758
759 After changing the motor rated power F2.01 each time, the VFD F2.06 to F2.10 parameter values will automatically restore the default standard motor parameters, if running in vector mode, please re-tune.
760
761 |(% rowspan="2" %)F2.11|Tuning selection|Factory default|0
762 |Setting range|(% colspan="2" %)(((
763 0: No operation is performed
764
765 1: Static tuning 1
766
767 2: Full tuning
768
769 3: Static tuning 2 (AM calculated Lm)
770 )))
771
772
773
774 Tip: Before tuning, you must set the correct motor type and rating parameters (F2.00 to F2.05).
775
776 0: No operation is performed, that is, tuning is disabled.
777
778 1: Static tuning 1, suitable for the motor and the load is not easy to come off and can not be rotated tuning occasions, static tuning learning asynchronous motor F2.05-F2.10 or synchronous motor F2.22 to F2.25 parameters, wherein synchronous motor back potential is calculated according to F2.01 and F2.03, if the motor power or current and the actual difference is large, Calculations may not be accurate.
779
780 Action description: Set the function code to 1, and press the RUN key to confirm, the inverter will perform static tuning.
781
782 2: Complete tuning, in order to ensure the dynamic control performance of the inverter, please select rotary tuning, rotary tuning motor must be disconnected from the load (no-load). After selecting rotary tuning, the inverter first performs static tuning, and after static tuning, the motor accelerates to 80% of the rated frequency of the motor, and maintains it for a period of time, and then decelerates and stops, and the rotary tuning ends.
783
784 Action description: Set the function code to 2, and press the RUN key to confirm, the inverter will perform rotation tuning.
785
786 3: Static tuning 2, different from static tuning 1, the tuning needs to manually input the asynchronous motor no-load current F2.10, the program will calculate the mutual inductance F2.09 according to the current, the other is the same as static tuning 1.
787
788 Action description: Set the function code to 3, and press the RUN key to confirm, the inverter will perform static tuning.
789
790 Note: Tuning can only be effective in keyboard control mode, acceleration and deceleration time is recommended to use the factory default.
791
792 |(% rowspan="2" %)F2.12|G/P Machine type|Factory default|Model determination
793 |Setting range|(% colspan="2" %)(((
794 0: G type machine;
795
796 1: P-type machine
797 )))
798
799
800
801 This parameter can only be used to view factory models.
802
803 1: Constant torque load for specified rated parameters.
804
805 2: Suitable for the specified rated parameters of the variable torque load (fan, pump load).
806
807 |(% rowspan="2" %)F2.13|Single phase asynchronous motor turns ratio|Factory default|100%
808 |Setting range|(% colspan="2" %)10 to 200%
809
810
811
812 U terminal main winding, V terminal auxiliary winding, W common end, this parameter is used to set the ratio of the number of turns between the main winding and the auxiliary winding of the single-phase motor.
813
814 |(% rowspan="2" %)F2.14|Current calibration coefficient of single-phase motor|Factory default|120%
815 |Setting range|(% colspan="2" %)50 to 200%
816
817 The single-phase motor has main and auxiliary windings, and the three-phase output current is unbalanced, so the output current displayed by the inverter needs to be multiplied by the coefficient of the resultant current.
818
819
820 |(% rowspan="2" %)F2.15|Number of motor poles|Factory default|4
821 |Setting range|(% colspan="2" %)2 to 48
822
823
824
825 Change F2.04 or F2.05, the program will automatically calculate the number of motor poles, in general, do not need to set this parameter.
826
827 |(% rowspan="2" %)F2.22|Stator resistance of synchro|Factory default|Model determination
828 |Setting range|(% colspan="2" %)0.001 to 65.000(0.001Ohm)
829 |(% rowspan="2" %)F2.23|Synchro d-axis inductance|Factory default|Model determination
830 |Setting range|(% colspan="2" %)0.01mH-655.35mH
831 |(% rowspan="2" %)F2.24|Synchro Q-axis inductance|Factory default|Model determination
832 |Setting range|(% colspan="2" %)0.01mH to 655.35mH
833 |(% rowspan="2" %)F2.25|Synchro back electromotive force|Factory default|Model determination
834 |Setting range|(% colspan="2" %)0.1V to 1000.0V
835
836 After the automatic tuning of the synchronous motor is completed, the set values of the synchronous motor parameters (F2.22 to F2.25) are automatically updated.
837
838 After changing the rated motor power F2.01 each time, the F2.22 to F2.25 parameter values of the inverter will automatically restore the default standard motor parameters, please re-tune.
839
840 |(% rowspan="2" %)F2.28|High frequency injection voltage|Factory default|20.0%
841 |Setting range|(% colspan="2" %)0.1% to 100.0%
842
843
844
845 The current injected when the synchronous motor learns the inductance of DQ axis by high frequency injection.
846
847 |(% rowspan="2" %)F2.29|Back potential identification current|Factory default|50.0%
848 |Setting range|(% colspan="2" %)0.1% to 100.0%
849
850
851
852 The output current of the inverter is the size when the synchronous motor dynamically adjusts to learn the back potential.
853
854
855 |(% rowspan="2" %)F2.31|Asynchronous no-load current per unit value|Factory default|Model determination
856 |Setting range|(% colspan="2" %)0.1%
857 |(% rowspan="2" %)F2.32|Per unit asynchronous stator resistance|Factory default|Model determination
858 |Setting range|(% colspan="2" %)0.01%
859 |(% rowspan="2" %)F2.33|Asynchronous rotor resistance per unit value|Factory default|Model determination
860 |Setting range|(% colspan="2" %)0.01%
861 |(% rowspan="2" %)F2.34|Asynchronous mutual inductance per unit value|Factory default|Model determination
862 |Setting range|(% colspan="2" %)0.1%
863 |(% rowspan="2" %)F2.35|Asynchronous leakage sensing per unit value|Factory default|Model determination
864 |Setting range|(% colspan="2" %)0.01%
865 |(% rowspan="2" %)F2.36|Per unit value of asynchronous leakage sensing coefficient|Factory default|Model determination
866 |Setting range|(% colspan="2" %)0.01%
867 |(% rowspan="2" %)F2.37|Synchronous stator resistance per unit value|Factory default|Model determination
868 |Setting range|(% colspan="2" %)0.01%
869 |(% rowspan="2" %)F2.38|Per unit value of synchronous D-axis inductance|Factory default|Model determination
870 |Setting range|(% colspan="2" %)0.01%
871 |(% rowspan="2" %)F2.39|Synchronous Q-axis inductance per unit value|Factory default|Model determination
872 |Setting range|(% colspan="2" %)0.01%
873 |(% rowspan="2" %)F2.40|Back electromotive force of synchronous motor|Factory default|Model determination
874 |Setting range|(% colspan="2" %)0.1V
875
876 The per unit value of the motor parameters is used for the actual program calculation. After learning or parameter recovery, the actual change is F2.31-F2.40. F2.06-F2.10 and F2.22-F2.25 are calculated from the per unit value, so only F2.31-F2.40 values can be modified, F2.06-F2.10 and F2.22-F2.25 are only used to display and cannot be changed.