1 +1. **Introduction**
2 +
3 +
4 +
5 +
6 +LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7 +
8 +LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9 +
10 +Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11 +
12 +
13 +**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
14 +
15 +1. **Appearance and terminal description**
16 +11. **Appearance and size**
17 +
18 +
19 +
20 +[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]]
21 +
22 +① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);
23 +
24 +⑤ DIN rail buckle.
25 +
26 +
27 +1.
28 +11. **Terminal description**
29 +
30 +The 4PT expansion module terminal are arranged as follows:
31 +
32 +
33 +|**Module model**|(% colspan="2" %)**Terminal arrangement**
34 +|LX6V-4PT| |[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]]
35 +
36 +
37 +
38 +1.
39 +11. **Installation**
40 +
41 +Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
42 +
43 +[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]]
44 +
45 +
46 +1.
47 +11. **Indicator**
48 +
49 +The 4PT expansion module LED is shown below:
50 +
51 +|**Indicator**|**Description**
52 +|PWR|(((
53 +Power indicator
54 +
55 +1. Lights on: The module is powered on normally
56 +1. Lights out: The module is not powered on or the module is abnormal
57 +)))
58 +|LINK|(((
59 +Communication indicator
60 +
61 +1. Lights on: Data interaction is normal
62 +1. Lights out: Data interaction is abnormal or stopped
63 +)))
64 +|L1+/L2+/L3+/L4 +|(((
65 +Channel indicator
66 +
67 +1. Lights on: Channel enable
68 +1. Lights out: Channel disable
69 +1. Slow flash: Channel not calibrated
70 +1. Fast flash: Channel abnormal (refer to status code for details)
71 +)))
72 +|L1-/L2-/L3-/L4-|N/A
73 +|I1+/I2+/I3+/I4 +|N/A
74 +
75 +
76 +
77 +
78 +1. **Parameter Specification**
79 +11. **Input Specification**
80 +
81 +|**Item**|**Description**
82 +|Input channel|4
83 +|Digital resolution|16 bit
84 +|Sensitivity|0.01℃, 0.01℉
85 +|Input terminal|Thermocouple input
86 +|Sensor type|PT100, PT1000, CU50
87 +|Accuracy (normal temperature 25℃)|Full range ± 0.2%
88 +|Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3%
89 +|Isolation or not|I/O terminals are isolated from power supply, channels are not isolated
90 +|Overlimit disconnection detection|Support
91 +|Power consumption|< 1.1W
92 +|Power supply|Power supply via interface, DC24V±10%, 40mA
93 +
94 +
95 +
96 +1.
97 +11. **Environmental specification**
98 +11.
99 +**Software Specifications**
100 +
101 +|**Item**|(% colspan="5" %)**Specification**
102 +|Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust
103 +|Environment temperature|(% colspan="5" %)(((
104 +Working temperature: 0℃ to 55℃
105 +
106 +Storage temperature: -20℃ to 70℃
107 +)))
108 +|Environment humidity|(% colspan="5" %)(((
109 +Working humidity: 10% to 90%RH (no condensation)
110 +
111 +Storage humidity: ≤ 90% RH (no condensation)
112 +)))
113 +|Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
114 +|(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard
115 +|Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)(((
116 +X, Y, Z
117 +
118 +10 times in each of three directions
119 +
120 +(80 minutes in each direction)
121 +)))
122 +|(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm
123 +|57 to 150Hz|4.9m/S^^2^^|~-~-
124 +|(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm
125 +|57 to 150Hz|9.8m/S^^2^^|~-~-
126 +|Shock resistance|(% colspan="5" %)(((
127 +Compliant with JISC0041 standard
128 +
129 +(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
130 +)))
131 +|EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2)
132 +|Altitude requirements|(% colspan="5" %)≤2000m (80 kPa)
133 +|Protection level|(% colspan="5" %)IP20
134 +|Grounding|(% colspan="5" %)Not co-located with the strong current system
135 +
136 +|**Item**|**Specification**
137 +|Input PDO data volume|Maximum 24 byte
138 +|Diagnostic reporting function configuration|Support
139 +|Diagnostic detection enable configuration|Support overlimit and disconnection detection
140 +|Sensor type configuration|(((
141 +Support thermal resistor type: PT100, PT1000, CU50, default is
142 +
143 +PT100 thermal resistance
144 +)))
145 +|Filter time|0s to 100s (can be configured by software, default 5s)
146 +|Overflow detection|Support
147 +|Overlimit detection enable configuration|Support
148 +|Independent channel configuration|Support
149 +|Temperature offset enable configuration|Support
150 +|Temperature offset configuration range|-300 to +300, temperature unit
151 +|Display mode|Celsius (℃), Fahrenheit (℉)
152 +|Display sensitivity|0.01℃, 0.01℉
153 +|Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
154 +|Stop mode|Output according to the maximum value, no more refresh
155 +|Disconnected or overlimit|Output according to the maximum value, no more refresh
156 +|System diagnostics|System power abnormality
157 +|Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
158 +|Configuration diagnostics|Configuration error identification, channel parameter configuration error
159 +
160 +
161 +
162 +
163 +1.
164 +11. **Accuracy calculation**
165 +
166 +Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
167 +
168 +|**Sensor type**|**Detection range**|**Accuracy**
169 +|PT100|(((
170 +-200.0℃ to +850.0℃,
171 +
172 +-328.0℉ to +1562.0℉
173 +)))|(((
174 +T < 300°C: ±0.6℃
175 +
176 +300℃ ≤ T ≤ 700℃: ±1.4℃
177 +
178 +T > 700°C: ±1.7℃
179 +)))
180 +|PT1000|(((
181 +-200.0℃ to +850.0℃,
182 +
183 +-328.0℉ to +1562.0℉
184 +)))|(((
185 +T < 300°C: ±0.6℃
186 +
187 +300℃ ≤ T ≤ 700℃: ±1.4℃
188 +
189 +T > 700 °C: ±1.7℃
190 +)))
191 +|CU50|(((
192 +-50.0℃ to + 150.0℃,
193 +
194 +-58.0℉ to +302.0℉
195 +)))|-50℃ ≤ T ≤ 150℃: ±0.3℃