LX6V-4PT

Version 3.1 by Iris on 2025/10/30 10:03

  1. Introduction

LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.

LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.

Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.

✎Note: The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.

  1. Appearance and terminal description
    1. Appearance and size

file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png

① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);

⑤ DIN rail buckle.

    1. Terminal description

The 4PT expansion module terminal are arranged as follows:

Module modelTerminal arrangement
LX6V-4PT file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png
  1.  
    1. Installation

Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:

file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png

  1.  
    1. Indicator

The 4PT expansion module LED is shown below:

IndicatorDescription
PWR

Power indicator

  1. Lights on: The module is powered on normally
  2. Lights out: The module is not powered on or the module is abnormal
LINK

Communication indicator

  1. Lights on: Data interaction is normal
  2. Lights out: Data interaction is abnormal or stopped
L1+/L2+/L3+/L4 +

Channel indicator

  1. Lights on: Channel enable
  2. Lights out: Channel disable
  3. Slow flash: Channel not calibrated
  4. Fast flash: Channel abnormal (refer to status code for details)
L1-/L2-/L3-/L4-N/A
I1+/I2+/I3+/I4 +N/A
  1. Parameter Specification
    1. Input Specification
ItemDescription
Input channel4
Digital resolution16 bit
Sensitivity0.01℃, 0.01℉
Input terminalThermocouple input
Sensor typePT100, PT1000, CU50
Accuracy (normal temperature 25℃)Full range ± 0.2%
Accuracy (working temperature -20℃ to 55℃)Full range ± 0. 3%
Isolation or notI/O terminals are isolated from power supply, channels are not isolated
Overlimit disconnection detectionSupport
Power consumption< 1.1W
Power supplyPower supply via interface, DC24V±10%, 40mA
    1. Environmental specification

    2. Software Specifications
ItemSpecification
Usage environmentNo corrosive, combustible gas, no large amount of conductive dust
Environment temperature

Working temperature: 0℃ to 55℃

Storage temperature: -20℃ to 70℃

Environment humidity

Working humidity: 10% to 90%RH (no condensation)

Storage humidity: ≤ 90% RH (no condensation)

InstallationSnap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
Vibration resistanceAccording to JISC0040 standard
InstallationFrequencyAccelerationAmplitude

X, Y, Z

10 times in each of three directions

(80 minutes in each direction)

DIN rail installation10 to 57Hz--0.035mm
57 to 150Hz4.9m/S2--
Direct installation10 to 57Hz--0.075mm
57 to 150Hz9.8m/S2--
Shock resistance

Compliant with JISC0041 standard

(147 m/S2, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)

EMC immunity levelZone B (per IEC 61131-2)
Altitude requirements≤2000m (80 kPa)
Protection levelIP20
GroundingNot co-located with the strong current system
ItemSpecification
Input PDO data volumeMaximum 24 byte
Diagnostic reporting function configurationSupport
Diagnostic detection enable configurationSupport overlimit and disconnection detection
Sensor type configuration

Support thermal resistor type: PT100, PT1000, CU50, default is

PT100 thermal resistance

Filter time0s to 100s (can be configured by software, default 5s)
Overflow detectionSupport
Overlimit detection enable configurationSupport
Independent channel configurationSupport
Temperature offset enable configurationSupport
Temperature offset configuration range-300 to +300, temperature unit
Display modeCelsius (℃), Fahrenheit (℉)
Display sensitivity0.01℃, 0.01℉
Sample refreshRefresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
Stop modeOutput according to the maximum value, no more refresh
Disconnected or overlimitOutput according to the maximum value, no more refresh
System diagnosticsSystem power abnormality
Channel diagnosisOver upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
Configuration diagnosticsConfiguration error identification, channel parameter configuration error
    1. Accuracy calculation

Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.

Sensor typeDetection rangeAccuracy
PT100

-200.0℃ to +850.0℃,

-328.0℉ to +1562.0℉

T < 300°C: ±0.6℃

300℃ ≤ T ≤ 700℃: ±1.4℃

T > 700°C: ±1.7℃

PT1000

-200.0℃ to +850.0℃,

-328.0℉ to +1562.0℉

T < 300°C: ±0.6℃

300℃ ≤ T ≤ 700℃: ±1.4℃

T > 700 °C: ±1.7℃

CU50

-50.0℃ to + 150.0℃,

-58.0℉ to +302.0℉

-50℃ ≤ T ≤ 150℃: ±0.3℃