Changes for page LX6V-4PT

Last modified by Iris on 2026/03/24 15:34

From version 2.1
edited by Iris
on 2025/10/30 10:03
Change comment: There is no comment for this version
To version 1.1
edited by Iris
on 2025/10/30 10:02
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,195 +1,0 @@
1 -1. **Introduction**
2 -
3 -
4 -
5 -
6 -LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7 -
8 -LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9 -
10 -Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11 -
12 -
13 -**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
14 -
15 -1. **Appearance and terminal description**
16 -11. **Appearance and size**
17 -
18 -
19 -
20 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]]
21 -
22 -① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);
23 -
24 -⑤ DIN rail buckle.
25 -
26 -
27 -1.
28 -11. **Terminal description**
29 -
30 -The 4PT expansion module terminal are arranged as follows:
31 -
32 -
33 -|**Module model**|(% colspan="2" %)**Terminal arrangement**
34 -|LX6V-4PT||[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]]
35 -
36 -
37 -
38 -1.
39 -11. **Installation**
40 -
41 -Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
42 -
43 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]]
44 -
45 -
46 -1.
47 -11. **Indicator**
48 -
49 -The 4PT expansion module LED is shown below:
50 -
51 -|**Indicator**|**Description**
52 -|PWR|(((
53 -Power indicator
54 -
55 -1. Lights on: The module is powered on normally
56 -1. Lights out: The module is not powered on or the module is abnormal
57 -)))
58 -|LINK|(((
59 -Communication indicator
60 -
61 -1. Lights on: Data interaction is normal
62 -1. Lights out: Data interaction is abnormal or stopped
63 -)))
64 -|L1+/L2+/L3+/L4 +|(((
65 -Channel indicator
66 -
67 -1. Lights on: Channel enable
68 -1. Lights out: Channel disable
69 -1. Slow flash: Channel not calibrated
70 -1. Fast flash: Channel abnormal (refer to status code for details)
71 -)))
72 -|L1-/L2-/L3-/L4-|N/A
73 -|I1+/I2+/I3+/I4 +|N/A
74 -
75 -
76 -
77 -
78 -1. **Parameter Specification**
79 -11. **Input Specification**
80 -
81 -|**Item**|**Description**
82 -|Input channel|4
83 -|Digital resolution|16 bit
84 -|Sensitivity|0.01℃, 0.01℉
85 -|Input terminal|Thermocouple input
86 -|Sensor type|PT100, PT1000, CU50
87 -|Accuracy (normal temperature 25℃)|Full range ± 0.2%
88 -|Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3%
89 -|Isolation or not|I/O terminals are isolated from power supply, channels are not isolated
90 -|Overlimit disconnection detection|Support
91 -|Power consumption|< 1.1W
92 -|Power supply|Power supply via interface, DC24V±10%, 40mA
93 -
94 -
95 -
96 -1.
97 -11. **Environmental specification**
98 -11.
99 -**Software Specifications**
100 -
101 -|**Item**|(% colspan="5" %)**Specification**
102 -|Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust
103 -|Environment temperature|(% colspan="5" %)(((
104 -Working temperature: 0℃ to 55℃
105 -
106 -Storage temperature: -20℃ to 70℃
107 -)))
108 -|Environment humidity|(% colspan="5" %)(((
109 -Working humidity: 10% to 90%RH (no condensation)
110 -
111 -Storage humidity: ≤ 90% RH (no condensation)
112 -)))
113 -|Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
114 -|(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard
115 -|Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)(((
116 -X, Y, Z
117 -
118 -10 times in each of three directions
119 -
120 -(80 minutes in each direction)
121 -)))
122 -|(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm
123 -|57 to 150Hz|4.9m/S^^2^^|~-~-
124 -|(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm
125 -|57 to 150Hz|9.8m/S^^2^^|~-~-
126 -|Shock resistance|(% colspan="5" %)(((
127 -Compliant with JISC0041 standard
128 -
129 -(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
130 -)))
131 -|EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2)
132 -|Altitude requirements|(% colspan="5" %)≤2000m (80 kPa)
133 -|Protection level|(% colspan="5" %)IP20
134 -|Grounding|(% colspan="5" %)Not co-located with the strong current system
135 -
136 -|**Item**|**Specification**
137 -|Input PDO data volume|Maximum 24 byte
138 -|Diagnostic reporting function configuration|Support
139 -|Diagnostic detection enable configuration|Support overlimit and disconnection detection
140 -|Sensor type configuration|(((
141 -Support thermal resistor type: PT100, PT1000, CU50, default is
142 -
143 -PT100 thermal resistance
144 -)))
145 -|Filter time|0s to 100s (can be configured by software, default 5s)
146 -|Overflow detection|Support
147 -|Overlimit detection enable configuration|Support
148 -|Independent channel configuration|Support
149 -|Temperature offset enable configuration|Support
150 -|Temperature offset configuration range|-300 to +300, temperature unit
151 -|Display mode|Celsius (℃), Fahrenheit (℉)
152 -|Display sensitivity|0.01℃, 0.01℉
153 -|Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
154 -|Stop mode|Output according to the maximum value, no more refresh
155 -|Disconnected or overlimit|Output according to the maximum value, no more refresh
156 -|System diagnostics|System power abnormality
157 -|Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
158 -|Configuration diagnostics|Configuration error identification, channel parameter configuration error
159 -
160 -
161 -
162 -
163 -1.
164 -11. **Accuracy calculation**
165 -
166 -Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
167 -
168 -|**Sensor type**|**Detection range**|**Accuracy**
169 -|PT100|(((
170 --200.0℃ to +850.0℃,
171 -
172 --328.0℉ to +1562.0℉
173 -)))|(((
174 -T < 300°C: ±0.6℃
175 -
176 -300℃ ≤ T ≤ 700℃: ±1.4℃
177 -
178 -T > 700°C: ±1.7℃
179 -)))
180 -|PT1000|(((
181 --200.0℃ to +850.0℃,
182 -
183 --328.0℉ to +1562.0℉
184 -)))|(((
185 -T < 300°C: ±0.6℃
186 -
187 -300℃ ≤ T ≤ 700℃: ±1.4℃
188 -
189 -T > 700 °C: ±1.7℃
190 -)))
191 -|CU50|(((
192 --50.0℃ to + 150.0℃,
193 -
194 --58.0℉ to +302.0℉
195 -)))|-50℃ ≤ T ≤ 150℃: ±0.3℃