@@ -1,195 +1,0 @@ |
| 1 |
|
-1. **Introduction** |
| 2 |
|
- |
| 3 |
|
- |
| 4 |
|
- |
| 5 |
|
- |
| 6 |
|
-LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. |
| 7 |
|
- |
| 8 |
|
-LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above. |
| 9 |
|
- |
| 10 |
|
-Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above. |
| 11 |
|
- |
| 12 |
|
- |
| 13 |
|
-**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W. |
| 14 |
|
- |
| 15 |
|
-1. **Appearance and terminal description** |
| 16 |
|
-11. **Appearance and size** |
| 17 |
|
- |
| 18 |
|
- |
| 19 |
|
- |
| 20 |
|
-[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]] |
| 21 |
|
- |
| 22 |
|
-① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); |
| 23 |
|
- |
| 24 |
|
-⑤ DIN rail buckle. |
| 25 |
|
- |
| 26 |
|
- |
| 27 |
|
-1. |
| 28 |
|
-11. **Terminal description** |
| 29 |
|
- |
| 30 |
|
-The 4PT expansion module terminal are arranged as follows: |
| 31 |
|
- |
| 32 |
|
- |
| 33 |
|
-|**Module model**|(% colspan="2" %)**Terminal arrangement** |
| 34 |
|
-|LX6V-4PT| |[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]] |
| 35 |
|
- |
| 36 |
|
- |
| 37 |
|
- |
| 38 |
|
-1. |
| 39 |
|
-11. **Installation** |
| 40 |
|
- |
| 41 |
|
-Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below: |
| 42 |
|
- |
| 43 |
|
-[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]] |
| 44 |
|
- |
| 45 |
|
- |
| 46 |
|
-1. |
| 47 |
|
-11. **Indicator** |
| 48 |
|
- |
| 49 |
|
-The 4PT expansion module LED is shown below: |
| 50 |
|
- |
| 51 |
|
-|**Indicator**|**Description** |
| 52 |
|
-|PWR|((( |
| 53 |
|
-Power indicator |
| 54 |
|
- |
| 55 |
|
-1. Lights on: The module is powered on normally |
| 56 |
|
-1. Lights out: The module is not powered on or the module is abnormal |
| 57 |
|
-))) |
| 58 |
|
-|LINK|((( |
| 59 |
|
-Communication indicator |
| 60 |
|
- |
| 61 |
|
-1. Lights on: Data interaction is normal |
| 62 |
|
-1. Lights out: Data interaction is abnormal or stopped |
| 63 |
|
-))) |
| 64 |
|
-|L1+/L2+/L3+/L4 +|((( |
| 65 |
|
-Channel indicator |
| 66 |
|
- |
| 67 |
|
-1. Lights on: Channel enable |
| 68 |
|
-1. Lights out: Channel disable |
| 69 |
|
-1. Slow flash: Channel not calibrated |
| 70 |
|
-1. Fast flash: Channel abnormal (refer to status code for details) |
| 71 |
|
-))) |
| 72 |
|
-|L1-/L2-/L3-/L4-|N/A |
| 73 |
|
-|I1+/I2+/I3+/I4 +|N/A |
| 74 |
|
- |
| 75 |
|
- |
| 76 |
|
- |
| 77 |
|
- |
| 78 |
|
-1. **Parameter Specification** |
| 79 |
|
-11. **Input Specification** |
| 80 |
|
- |
| 81 |
|
-|**Item**|**Description** |
| 82 |
|
-|Input channel|4 |
| 83 |
|
-|Digital resolution|16 bit |
| 84 |
|
-|Sensitivity|0.01℃, 0.01℉ |
| 85 |
|
-|Input terminal|Thermocouple input |
| 86 |
|
-|Sensor type|PT100, PT1000, CU50 |
| 87 |
|
-|Accuracy (normal temperature 25℃)|Full range ± 0.2% |
| 88 |
|
-|Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3% |
| 89 |
|
-|Isolation or not|I/O terminals are isolated from power supply, channels are not isolated |
| 90 |
|
-|Overlimit disconnection detection|Support |
| 91 |
|
-|Power consumption|< 1.1W |
| 92 |
|
-|Power supply|Power supply via interface, DC24V±10%, 40mA |
| 93 |
|
- |
| 94 |
|
- |
| 95 |
|
- |
| 96 |
|
-1. |
| 97 |
|
-11. **Environmental specification** |
| 98 |
|
-11. |
| 99 |
|
-**Software Specifications** |
| 100 |
|
- |
| 101 |
|
-|**Item**|(% colspan="5" %)**Specification** |
| 102 |
|
-|Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust |
| 103 |
|
-|Environment temperature|(% colspan="5" %)((( |
| 104 |
|
-Working temperature: 0℃ to 55℃ |
| 105 |
|
- |
| 106 |
|
-Storage temperature: -20℃ to 70℃ |
| 107 |
|
-))) |
| 108 |
|
-|Environment humidity|(% colspan="5" %)((( |
| 109 |
|
-Working humidity: 10% to 90%RH (no condensation) |
| 110 |
|
- |
| 111 |
|
-Storage humidity: ≤ 90% RH (no condensation) |
| 112 |
|
-))) |
| 113 |
|
-|Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount |
| 114 |
|
-|(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard |
| 115 |
|
-|Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)((( |
| 116 |
|
-X, Y, Z |
| 117 |
|
- |
| 118 |
|
-10 times in each of three directions |
| 119 |
|
- |
| 120 |
|
-(80 minutes in each direction) |
| 121 |
|
-))) |
| 122 |
|
-|(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm |
| 123 |
|
-|57 to 150Hz|4.9m/S^^2^^|~-~- |
| 124 |
|
-|(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm |
| 125 |
|
-|57 to 150Hz|9.8m/S^^2^^|~-~- |
| 126 |
|
-|Shock resistance|(% colspan="5" %)((( |
| 127 |
|
-Compliant with JISC0041 standard |
| 128 |
|
- |
| 129 |
|
-(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions) |
| 130 |
|
-))) |
| 131 |
|
-|EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2) |
| 132 |
|
-|Altitude requirements|(% colspan="5" %)≤2000m (80 kPa) |
| 133 |
|
-|Protection level|(% colspan="5" %)IP20 |
| 134 |
|
-|Grounding|(% colspan="5" %)Not co-located with the strong current system |
| 135 |
|
- |
| 136 |
|
-|**Item**|**Specification** |
| 137 |
|
-|Input PDO data volume|Maximum 24 byte |
| 138 |
|
-|Diagnostic reporting function configuration|Support |
| 139 |
|
-|Diagnostic detection enable configuration|Support overlimit and disconnection detection |
| 140 |
|
-|Sensor type configuration|((( |
| 141 |
|
-Support thermal resistor type: PT100, PT1000, CU50, default is |
| 142 |
|
- |
| 143 |
|
-PT100 thermal resistance |
| 144 |
|
-))) |
| 145 |
|
-|Filter time|0s to 100s (can be configured by software, default 5s) |
| 146 |
|
-|Overflow detection|Support |
| 147 |
|
-|Overlimit detection enable configuration|Support |
| 148 |
|
-|Independent channel configuration|Support |
| 149 |
|
-|Temperature offset enable configuration|Support |
| 150 |
|
-|Temperature offset configuration range|-300 to +300, temperature unit |
| 151 |
|
-|Display mode|Celsius (℃), Fahrenheit (℉) |
| 152 |
|
-|Display sensitivity|0.01℃, 0.01℉ |
| 153 |
|
-|Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle |
| 154 |
|
-|Stop mode|Output according to the maximum value, no more refresh |
| 155 |
|
-|Disconnected or overlimit|Output according to the maximum value, no more refresh |
| 156 |
|
-|System diagnostics|System power abnormality |
| 157 |
|
-|Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm |
| 158 |
|
-|Configuration diagnostics|Configuration error identification, channel parameter configuration error |
| 159 |
|
- |
| 160 |
|
- |
| 161 |
|
- |
| 162 |
|
- |
| 163 |
|
-1. |
| 164 |
|
-11. **Accuracy calculation** |
| 165 |
|
- |
| 166 |
|
-Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring. |
| 167 |
|
- |
| 168 |
|
-|**Sensor type**|**Detection range**|**Accuracy** |
| 169 |
|
-|PT100|((( |
| 170 |
|
--200.0℃ to +850.0℃, |
| 171 |
|
- |
| 172 |
|
--328.0℉ to +1562.0℉ |
| 173 |
|
-)))|((( |
| 174 |
|
-T < 300°C: ±0.6℃ |
| 175 |
|
- |
| 176 |
|
-300℃ ≤ T ≤ 700℃: ±1.4℃ |
| 177 |
|
- |
| 178 |
|
-T > 700°C: ±1.7℃ |
| 179 |
|
-))) |
| 180 |
|
-|PT1000|((( |
| 181 |
|
--200.0℃ to +850.0℃, |
| 182 |
|
- |
| 183 |
|
--328.0℉ to +1562.0℉ |
| 184 |
|
-)))|((( |
| 185 |
|
-T < 300°C: ±0.6℃ |
| 186 |
|
- |
| 187 |
|
-300℃ ≤ T ≤ 700℃: ±1.4℃ |
| 188 |
|
- |
| 189 |
|
-T > 700 °C: ±1.7℃ |
| 190 |
|
-))) |
| 191 |
|
-|CU50|((( |
| 192 |
|
--50.0℃ to + 150.0℃, |
| 193 |
|
- |
| 194 |
|
--58.0℉ to +302.0℉ |