Wiki source code of LX6V-4PT

Version 3.1 by Iris on 2025/10/30 10:03

Show last authors
1 1. **Introduction**
2
3
4
5
6 LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7
8 LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9
10 Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11
12
13 **✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
14
15 1. **Appearance and terminal description**
16 11. **Appearance and size**
17
18
19
20 [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]]
21
22 ① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);
23
24 ⑤ DIN rail buckle.
25
26
27 1.
28 11. **Terminal description**
29
30 The 4PT expansion module terminal are arranged as follows:
31
32
33 |**Module model**|(% colspan="2" %)**Terminal arrangement**
34 |LX6V-4PT| |[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]]
35
36
37
38 1.
39 11. **Installation**
40
41 Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
42
43 [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]]
44
45
46 1.
47 11. **Indicator**
48
49 The 4PT expansion module LED is shown below:
50
51 |**Indicator**|**Description**
52 |PWR|(((
53 Power indicator
54
55 1. Lights on: The module is powered on normally
56 1. Lights out: The module is not powered on or the module is abnormal
57 )))
58 |LINK|(((
59 Communication indicator
60
61 1. Lights on: Data interaction is normal
62 1. Lights out: Data interaction is abnormal or stopped
63 )))
64 |L1+/L2+/L3+/L4 +|(((
65 Channel indicator
66
67 1. Lights on: Channel enable
68 1. Lights out: Channel disable
69 1. Slow flash: Channel not calibrated
70 1. Fast flash: Channel abnormal (refer to status code for details)
71 )))
72 |L1-/L2-/L3-/L4-|N/A
73 |I1+/I2+/I3+/I4 +|N/A
74
75
76
77
78 1. **Parameter Specification**
79 11. **Input Specification**
80
81 |**Item**|**Description**
82 |Input channel|4
83 |Digital resolution|16 bit
84 |Sensitivity|0.01℃, 0.01℉
85 |Input terminal|Thermocouple input
86 |Sensor type|PT100, PT1000, CU50
87 |Accuracy (normal temperature 25℃)|Full range ± 0.2%
88 |Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3%
89 |Isolation or not|I/O terminals are isolated from power supply, channels are not isolated
90 |Overlimit disconnection detection|Support
91 |Power consumption|< 1.1W
92 |Power supply|Power supply via interface, DC24V±10%, 40mA
93
94
95
96 1.
97 11. **Environmental specification**
98 11.
99 **Software Specifications**
100
101 |**Item**|(% colspan="5" %)**Specification**
102 |Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust
103 |Environment temperature|(% colspan="5" %)(((
104 Working temperature: 0℃ to 55℃
105
106 Storage temperature: -20℃ to 70℃
107 )))
108 |Environment humidity|(% colspan="5" %)(((
109 Working humidity: 10% to 90%RH (no condensation)
110
111 Storage humidity: ≤ 90% RH (no condensation)
112 )))
113 |Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
114 |(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard
115 |Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)(((
116 X, Y, Z
117
118 10 times in each of three directions
119
120 (80 minutes in each direction)
121 )))
122 |(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm
123 |57 to 150Hz|4.9m/S^^2^^|~-~-
124 |(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm
125 |57 to 150Hz|9.8m/S^^2^^|~-~-
126 |Shock resistance|(% colspan="5" %)(((
127 Compliant with JISC0041 standard
128
129 (147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
130 )))
131 |EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2)
132 |Altitude requirements|(% colspan="5" %)≤2000m (80 kPa)
133 |Protection level|(% colspan="5" %)IP20
134 |Grounding|(% colspan="5" %)Not co-located with the strong current system
135
136 |**Item**|**Specification**
137 |Input PDO data volume|Maximum 24 byte
138 |Diagnostic reporting function configuration|Support
139 |Diagnostic detection enable configuration|Support overlimit and disconnection detection
140 |Sensor type configuration|(((
141 Support thermal resistor type: PT100, PT1000, CU50, default is
142
143 PT100 thermal resistance
144 )))
145 |Filter time|0s to 100s (can be configured by software, default 5s)
146 |Overflow detection|Support
147 |Overlimit detection enable configuration|Support
148 |Independent channel configuration|Support
149 |Temperature offset enable configuration|Support
150 |Temperature offset configuration range|-300 to +300, temperature unit
151 |Display mode|Celsius (℃), Fahrenheit (℉)
152 |Display sensitivity|0.01℃, 0.01℉
153 |Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
154 |Stop mode|Output according to the maximum value, no more refresh
155 |Disconnected or overlimit|Output according to the maximum value, no more refresh
156 |System diagnostics|System power abnormality
157 |Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
158 |Configuration diagnostics|Configuration error identification, channel parameter configuration error
159
160
161
162
163 1.
164 11. **Accuracy calculation**
165
166 Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
167
168 |**Sensor type**|**Detection range**|**Accuracy**
169 |PT100|(((
170 -200.0℃ to +850.0℃,
171
172 -328.0℉ to +1562.0℉
173 )))|(((
174 T < 300°C: ±0.6℃
175
176 300℃ ≤ T ≤ 700℃: ±1.4℃
177
178 T > 700°C: ±1.7℃
179 )))
180 |PT1000|(((
181 -200.0℃ to +850.0℃,
182
183 -328.0℉ to +1562.0℉
184 )))|(((
185 T < 300°C: ±0.6℃
186
187 300℃ ≤ T ≤ 700℃: ±1.4℃
188
189 T > 700 °C: ±1.7℃
190 )))
191 |CU50|(((
192 -50.0℃ to + 150.0℃,
193
194 -58.0℉ to +302.0℉
195 )))|-50℃ ≤ T ≤ 150℃: ±0.3℃