LX6V-4TC

Version 1.7 by Iris on 2025/09/15 14:59

1 Introduction

1757906806155-501.png

  1. LX6V to 4TC (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V to EM to ECAT module equipment

  2. Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version: 2.321. 1032 and above.

  3. LX6V to EM to ECAT firmware version that supports this module: V2.022 and above, and the corresponding XML version is 1.3 and above.

✎Note: The total power of expansion modules connected to LX6 series PLC and LX6V to EM£ to ECAT cannot be greater than 48W.

2 Appearance and terminal description

2.1 Appearance and size

1757906806164-516.png

① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole:2 (Φ4.5);  ⑤ DIN rail clip.

2.2 Terminal description

The 4TC expansion module terminal are arranged as follows:

Module modelTerminal arrangement
LX6V to 4TC1757906806166-486.png企业微信截图_17579071289562.png

2.3 Installation

Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:

企业微信截图_17579072794946.png

企业微信截图_17579072837665.png

2.4 Indicator

The 4TC expansion module LED is shown below:

Indicator lampDescription
PWRAlways lights up when the module is powered on normally.
LINK light

Communication indicator light between the expansion module and PLC.

Lights out: Data interaction is abnormal, stopped, or failed

Lights on: Data interaction is normal.

Ln +

Defined as: Status light.

Light up to indicate channel enabled;

Flashing is used to indicate that the channel is overlimit and disconnection.

Ln -N/A

3 Parameter specifications

3.1 Input specifications

ItemSpecification
Input channel4
Digital resolution16 bit
Sensitivity0.01℃, 01℉
Input terminalThermocouple input, thermocouple type: K, J, E, B, N, R, S, T
Compensation methodInternal cold junction compensation
Accuracy (normal temperature 25 ℃)Full range ±0.1% + cold junction compensation error
Accuracy (working temperature  to 20 ℃to 55 ℃)Full range ±0.3% + cold junction compensation error
Isolation or notIsolation between I/O terminals and power supply, isolation between channels
Overlimit disconnection detectionSupport
Power consumption< 0.8 W
Power supplyPower supply via interface, DC24V ± 10%, 32mA

3.2 Environmental specification

ItemSpecification
Usage environmentNo corrosive, combustible gas, no large amount of conductive dust
Environment temperature

Working temperature: 0℃ to 55℃

Storage temperature: - 20℃ to 70℃

Environment humidity

Working humidity: 10% to 90%RH (no condensation)

Storage humidity: ≤ 90% RH (no condensation)

InstallationSnap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
Vibration resistanceAccording to JISC0040 standard
 FrequencyAccelerationAmplitude

X, Y, Z

10 times in each of three directions

(80 minutes in each direction)

DIN rail installation10 to 57Hz-0.035 mm
 57 to 150Hz4.9 m/S2-
Direct installation10 to 57Hz-0.075 mm
 57 to 150Hz9.8 m/S2-
Shock resistance

Compliant with JISC0041 standard

(147 m/S2, action time 11 ms, three sinusoidal half to wave pulses in each of X, Y, and Z directions)

EMC immunity levelZone B lEC 61131 to 2
Altitude requirements≤ 2000 m (80 kPa)
Protection levelIP20
GroundingNot co - located with the strong current system

3.3 Software specification

ItemSpecification
Input PDO data volumeMaximum 24 byte
Diagnostic reporting function configurationSupport
Diagnostic detection enable configurationSupport overlimit and disconnection detection
Sensor type configurationSupport thermocouple module type: K, J, E, B, N, R, S, T, default to K to type thermocouple
Filter time0s to 100s (can be configured by software, default 5s)
Overflow detectionSupports reporting overflow status only when overflow is enabled
Overlimit detection enable configurationSupport
Independent channel configurationSupport
Temperature offset enable configurationSupport
Temperature offset configuration range-300 to +300, temperature unit
Display modeCelsius (℃), Fahrenheit (℉)
Display sensitivity0.01℃, 0.01℉
Sample refreshRefresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
Stop modeOutput according to the maximum value, no more refresh
Disconnected or ovelimitOutput according to the maximum value, no more refresh
System diagnosticsSystem power abnormality
Channel diagnosisOver upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
Configuration diagnosticsConfiguration error identification, channel parameter configuration error

3.4 Accuracy calculation

Within the working temperature range, when the temperature change rate is less than 0.3 °C/min, the accuracy of this product = ADC sampling accuracy + cold junction compensation error. According to the test principle, it is need to wait for the module to be powered on for 45 minutes before measuring.

Recommended: Within the working temperature range and under the condition of horizontal and vertical installation direction, when the adjacent module is a temperature module, the cold end compensation error is within ±3℃.

Not recommended: Adjacent modules consume more than 3.5 W of power, for example host PLC, LX6V - 32EXYT.

Installation directionAdjacent module typeCold junction compensation error ( - 20 ℃ to 0 ℃)Cold junction compensation error (0 ℃ to 55 ℃)
Horizontal installationTemperature module± 0.8℃± 1.1℃
Non - temperature module± 0.6℃± 2.8℃
Non - horizontal installationTemperature module± 1.1℃± 2.8℃
Non - temperature module± 1.37℃± 4.9℃

4 Usage

This module is suitable for Wecon LX6 series PLC and LX6V - EM£ - ECAT module equipment. The two usage methods are as follow.

4.1 Use on LX6V/LX6S

1757906806169-137.png

The parameter configuration interface is as below:

1.2PqFNtM5AKK.jpg

Upper computer expansion module configuration process description:

① Double - click the expansion module configuration to open the configuration interface;

② Adding new modules according to the model and position of the current module connected;

③ Double - click the module in the current machine slot to open the parameter configuration interface;

  1. TC general configuration

2tx5jy13lKY.jpg

① Thermocouple cold junction compensation: Set whether the module enables cold junction compensation, and the cold junction compensation is enabled by default;

② Temperature unit: Set the temperature unit output by the module, and the supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;

③ Power frequency suppression: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz. The default suppression is 50Hz. Please set the appropriate power frequency suppression option for the module according to the actual application scenario;

      2. TC channel configuration

3PLCEditor_GOQyUoTESr.jpg

① Enable channels: It can be set whether to enable the current expansion module channel;

② Sensor type: Set the sensor type connected to the module channel, the default sensor type is K to type, there are 8 types of sensors supported by TC module, which are: K, J, E, B, N, R, S, T; The temperature range that can be measured by each sensor is as follows:

Sensor typeTemperature range
Degree CelsiusDegree Fahrenheit
K - 200℃ to 1372℃ - 328.0℉ to 2501.6℉
J - 200℃ to 1000℃ - 328.0℉ to 1832.0℉
E - 200℃ to 1000℃ - 328.0℉ to 1832.0℉
B   400℃ to 1820℃   752.0℉ to 3308.0℉
N - 200℃ to 1300℃ - 328.0℉ to 2372.0℉
R - 50℃ to 1768℃ - 58.0℉ to 3214.4℉
S - 50℃ to 1768℃ - 58.0℉ to 3214.4℉
T - 200℃ to 400℃ - 328.0℉ to 752.0℉

③Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;

④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel over to limit warning;

⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;

     3. I/O mapping

By default, channel are mapped into the R device according to the current number of module channels. The following figure shows the mapping of the modules CH1 to CH12 to the R0 to R11 device. The temperature value data type of the channel is REAL. If it is necessary to display the channel 1 The temperature value can be viewed after assigning a variable using the DEMOV instruction.

4PLCEditor_wKUemJvCam.jpg

    4. Download configuration

 Click OK to save the configuration,according to the interface shown in the figure to download the module configuration to the PLC.

5.1kMEUCQlPF7.jpg

4.2 Used on LX6V to EM□ to ECAT module

1757906806204-191.png

  1. First add EtherCAT device

According to steps ① to ④ in the figure below, right to click EtherCAT, and click [New] to >[Import] to import the ESI device description file of the device;

665sYyXQIbDT.jpg

6.5.1tortVyUgEV.jpg

After the import is completed, select the coupler according to themodule model and location connected to PLC (the figure below takes LX6V to EMB to ECAT as an example);

7.1PnEByhCLAr.jpg

  1. Configuration module

Right to click the currently added coupler to add the expansion module mounted to the current coupler.

9.1aUfQCcVoUr.jpg

✎Note: When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.

  1. Configure module parameters

10c.1 8fUdkPzrsU.jpg

10.5.1afJJ0pHUKI.jpg

General configuration

① TC module thermocouple compensation: Set whether the module enables cold junction compensation, and the cold junction compensation is enabled by default;

0: No cold junction compensation;

Others: Enable cold junction compensation;

② TC module temperature unit: Set the temperature unit output by the module. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉). The default unit is: Celsius;

0: Degrees Celsius (℃);

Others: Degrees Fahrenheit (℉);

③ TC module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;

0: Suppress 50 Hz;

Others: Suppress 60 Hz;

④ Reserve: Reserve;

⑤ CHx sensor type: Set the type of sensor connected to the channel;

Supported sensor types:

0: Not enabled

1: K;

2: J;

3: E;

4: B;

5: N

6: R

7: S

8: T

⑥ CHx filtering time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;

⑦ CHx overlimit detection: Overlimit detection enables configuration, 0: Overlimit detection detection is not enabled, others: Enable over limit detection

⑧ CHx temperature upper limit: The upper limit value of the channel over limit detection temperature;

⑨ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;

⑩ CHx temperature offset: The offset of channel data, supported offset range: - 300 to + 300;

I/O mapping

The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.

1757906806304-135.jpeg

Click save configuration and download the configuration to PLC.

5 Object dictionary

ModelIndexSub - indexDescription

Data

Type

RangeRead - writeUnitDefaultName
LX6V - 4TC16#800016#01

TC module thermocouple cold junction compensation

0: No compensation

Others: Cold junction compensation

UINT80 to 255W-1TC module thermocouple compensation
16#02

TC module temperature unit

0: Degrees Celsius (℃)

Others: Degrees Fahrenheit (℉)

UINT80 to 255W-0TC module temperature unit
16#03

TC module power frequency suppression

0: Suppress 50 Hz

Others: Suppress 60Hz

UINT80 to 255W-0TC module power frequency suppression
16#04Reserve parameter 0UINT80 to 255W-0Reserve 0
16#05Reserve parameter 1UINT80 to 255W- 0Reserve1
16#06Reserve parameter2UINT80 to 255W-0Reserve 2
16#800116#01

Sensor type

0: Disable

1: K

2: J

3: E

4: B

5: N

6: R

7: S

8: T

Others: Not supported

UINT80 to 8W-1CH0 sensor type
16#02CH1 sensor type
16#03CH2 sensor type
16#04CH3 sensor type
16#800216#01

TC module channel filtering time: 0 to 100s

Others: 100s

UINT80 to 255Ws5CH0 filter time
16#02CH1 filter time
16#03CH2 filter time
16#04CH3 filter time
16#800316#01

Overlimit detection enable

0: Disable

Others: Enable

UINT80 to 255W-0CH0 overlimit detection
16#02CH1 overlimit detection
16#03CH2 overlimit detection
16#04CH3 overlimit detection
16#800416#01

Temperature unit: 0.1℃/0.1℉

The upper and lower limits of sensors are different for each model

INT32-2147483648 to 2147483647W-32767CH0 temperature upper limit
16#02CH1 temperature upper limit
16#03CH2 temperature upper limit
16#04CH3 temperature upper limit
16#800516#01INT32-2147483648 to 2147483647W--32768CH0 temperature lower limit
16#02CH1 temperature upper limit
16#03CH2 temperature upper limit
16#04CH3 temperature lower limit
16#800616#01

Offset temperature value (0.1 ℃/0.1 ℉)

0: No offset

INT163000 to 3000W-0CH0 temperature offset
16#02CH1 temperature offset
16#03CH2 temperature offset
16#04CH3 temperature offset
16#A00016#00Module status informationUINT16-R--Module status
16#01Version codeUINT16-R--Version
16#02Error statusUINT16-R--Run status
16#03Channel statusUINT16-R--Channel status
16#600016#01Current temperature value of TC CH0 to CH3 channel (℃/℉)Float-400 to 32767R--TC CH0 temperature
16#02Float-400 to 32767R--TC CH1 temperature
16#03Float-400 to 32767R--TC CH2 temperature
16#04Float to 400 to 32767R--TC CH3 temperature
16 # 600116#01

AD CH0 to CH3 channel value.

Status code

0, no error

0xFF, sensor not supported

0x10, configuration abnormal: Temperature overlimit configuration overlimit

0x11, configuration error: The upper limit of the over limit configuration is less than the lower limit

0x12, configuration error: Temperature offset configuration overlimit

0x13, configuration error: NTC B Value over limit

0x40, channel disconnection error

0x41, channel temperature overflow

0x42, channel temperature overlimit

UINT160 to 65535R--TC CH0 status
16#02UINT160 to 65535R--TC CH1 status
16#03UINT160 to 65535R--TC CH2 status
16#04UINT160 to 65535R - -TC CH3 status

6 Error code

Error codeDescriptionActionSolutionDetection time
7080Expansion module and checksum errorContinue to runDetect whether there is external interference between the expansion module and the PLC.Instruction running
7081Expansion module communication message errorContinue to runDetect whether there is external interference between the expansion module and the PLCInstruction running
7083Expansion module access errorContinue to runDetect the link between the expansion module and the hostInstruction running
7084The number of expansion modules configured does not match the actual numberContinue to runCheck whether the configuration is correct.Instruction running
7110Extension module configuration errorStop runningCheck whether the extension module is configured correctlyInstruction running