Use crimp terminals of the size shown in the figure. Terminal tightening torque is 0.5 to 0.8N.m. Be sure to tighten the screws so as not to cause malfunction. |
92 |
92 |
|
... |
... |
@@ -115,7 +115,7 @@ |
115 |
115 |
= **4 Wiring ** = |
116 |
116 |
|
117 |
117 |
(% style="text-align:center" %) |
118 |
|
-[[image:image-20220622145005-5.jpeg||height="522" width="706"]] |
|
117 |
+[[image:image-20220705162452-1.jpeg]] |
119 |
119 |
|
120 |
120 |
**✎Note:** |
121 |
121 |
|
... |
... |
@@ -503,18 +503,18 @@ |
503 |
503 |
|
504 |
504 |
* Calibration with weights |
505 |
505 |
** Step1: Do not put any weights on the load cell. |
506 |
|
-** Step2: #8 value is written as 0x0001. |
|
505 |
+** Step2: Write 0x0001 to #8. |
507 |
507 |
** Step3: Add standard weights to the load cell. |
508 |
508 |
** Step4: Write the weight of the current weight on the chassis into #23. |
509 |
|
-** Step5: #8 value is written as 0x0002. |
|
508 |
+** Step5: Write 0x0002 to #8. |
510 |
510 |
* Weightless calibration |
511 |
511 |
** Step1: Do not put any weights on the load cell. |
512 |
512 |
** Step2: Write the maximum range of the sensor into #23. |
513 |
513 |
** Step3: Write the sensor sensitivity into #39, accurate to three decimal places. |
514 |
|
-** Step4: #8 value is written as 0x0003. |
|
513 |
+** Step4: Write 0x0003 to #8. |
515 |
515 |
* Modify calibration parameters: |
516 |
516 |
** Step1: Modify the calibration parameter values in BFM#35 to BFM#38; |
517 |
|
-** Step2: #8 value is written as 0x0004. |
|
516 |
+** Step2: Write 0x0004 to #8. |
518 |
518 |
|
519 |
519 |
**✎Note: **When a value is written to BFM#8 or BFM#48 using the device monitor, it is automatically reset to 0. |
520 |
520 |
|
... |
... |
@@ -534,7 +534,7 @@ |
534 |
534 |
|
535 |
535 |
|**Settings**|(% style="width:599px" %)**Description**|(% style="width:404px" %)**Remark** |
536 |
536 |
|0|(% style="width:599px" %)Do not enable zero tracking|(% style="width:404px" %)Default |
537 |
|
-|1 to 100|(% style="width:599px" %)When setting the zero tracking range (absolute value), tracking must be performed when the value is stable and the current weight is within the zero tracking range.|(% style="width:404px" %)((( |
|
536 |
+|1 to 300|(% style="width:599px" %)When setting the zero tracking range (absolute value), tracking must be performed when the value is stable and the current weight is within the zero tracking range.|(% style="width:404px" %)((( |
538 |
538 |
If set to 10, the current weight is ±9 and the stable flag is 1, the current weight is cleared. |
539 |
539 |
))) |
540 |
540 |
|(% colspan="3" %)**✎Note: **When the accuracy of the measured items is not high, the temperature drift has little effect, and this function is not required. |