LX3V-16EYRT

Version 2.2 by Leo Wei on 2022/06/08 14:42

1 General

This manual is applied to LX3V-8EY and LX3V-16EY digital output expansion modules.

2 Naming rule

Naming rule of LX3V I/O output expansion module:

Output expansion module(new)_html_9be6fa0860691fd2.png

  1. WECON PLC;
  2. Main module;
  3. Expansion module;
  4. Product type, E means expansion;
  5. Expansion output(Y);
  6. T: transistor, R: relay;

3 Dimensions

Output expansion module(new)_html_2ea9b85e7080ee9a.png

  1. Extension cable and connector
  2. State LED: Light when normal condition
  3. Power LED: Light when connect to 24V
  4. Module name
  5. digital signal output terminal
  6. Extension module interface
  7. DIN rail mounting slot
  8. DIN rail hook
  9. Mounting holes (φ4.5)

3.1 Crimp terminations

  • Please use crimp terminals as indicated on the graph.
  • The tightening torque should be applied 5 to 8 Kg.cm.
  • Other terminals should be empty but only wiring terminals mention in this manual.

Output expansion module(new)_html_a035e325e1e93843.png

4 Output specification

ItemRelay outputTransistor output
ModeLX3V-16EYRLX3V-16EYT
Output circuitOutput expansion module(new)_html_6a3e37e544857fa9.gifOutput expansion module(new)_html_f4ae6878b93489a4.gif
Load power supplyLess than AC250V or DC 30VDC 5V~ 30V
Circuit insulationMechanicalPhoto-coupling
LEDLight when relay is energizedLight when photo-coupling is energized
LoadResistance

2A/ point

8A/ four points

8A/ eight points

0.5A/ point

0.8A/ four points

1.6A/ eight points

Inductance80VA12W/DC24V
Lamp100W1.5W/DC24V
Leakage current--0.1mA/ DC 30V
Minimum load--DC 5V 2mA
OFF->ONAbout 10msLess than 0.2ms
ON-> OFFAbout 10msLess than 0.2ms