1 = **1 Mounting instruction** =
2
3 Before the installation make sure that the PLC host and the equipment connected to BD module have been powered off. Please install the BD module in the corresponding position of the PLC, and lock the two standard screws.
4
5 **Caution:**
6
7 * This BD module only support the following firmware versions or later. Users can check the PLC firmware version in D8001.
8 ** LX3VP:25103;
9 ** LX3VE: 25201;
10 ** LX3V-A2:25014;
11 ** LX3V-A1: 22006;
12 ** LX2V: 24005;
13
14 When mounting module to PLC, all the lights are blinking after power ON PLC please purchase a new PLC.
15
16 * Please fixed BD module on the PLC, poor contact may lead to failure.
17 * BD module and top cover of PLC’s tightening torque is 0.3 ~~ 0.6 N.m.
18
19 (% class="box warningmessage" %)
20 (((
21 **Warning:** Make sure to power off the PLC before mounting or removing the BD module and put the cover in right place.
22 )))
23
24 = **2 Special feature** =
25
26 1. LX3V-2ADV-BD module equips with 2 channels analog input. This module will be mounted in the PLC.
27 1. The input voltage of LX3V-2ADV-BD module between -10 to 10V, and the digital value will be saved in special system address, but the numerical relationship between input and output value cannot be changed.
28
29 (% class="table-bordered" %)
30 |=(% colspan="3" %)**Expansion port 1 (far away from PLC light )**
31 |**Address**|(% colspan="2" %)**Description**
32 |M8112|(((
33 The flag of switching input mode in CH1
34
35 OFF: Voltage input mode (-10V~~10V, -2000~~2000)
36 )))|(% rowspan="2" %)ON: Disabled
37 |M8113|(((
38 The flag of switching Input mode in CH2
39
40 OFF: Voltage input mode (-10V~~10V, -2000~~2000)
41 )))
42 |D8112|(% colspan="2" %)The digital value of channel 1; (-10V~~10V, -2000~~2000)
43 |D8113|(% colspan="2" %)The digital value of channel 2; (-10V~~10V, -2000~~2000)
44 |(% colspan="3" %)**Expansion port 2 (from the PLC light near)**
45 |**Address**|(% colspan="2" %)**Description**
46 |M8116|(((
47 The flag of switching Input mode in CH1
48
49 OFF: Voltage input mode (-10V~~10V, -2000~~2000)
50 )))|(% rowspan="2" %)ON: Disabled
51 |M8117|(((
52 The flag of switching Input mode in CH2
53
54 OFF: Voltage input mode (-10V~~10V, -2000~~2000)
55 )))
56 |D8116|(% colspan="2" %)The digital value of channel 1; (-10V~~10V, -2000~~2000)
57 |D8117|(% colspan="2" %)The digital value of channel 2; (-10V~~10V, -2000~~2000)
58
59 = **3 Dimension** =
60
61 (% class="table-bordered" %)
62 |=(% colspan="2" %)**IN-2ADV input voltage range: -10~~10V**
63 |Vi1+|Anode of the channel 1 voltage input
64 |Vi1-|Cathode of the channel 1 voltage input
65 |•|No connection
66 |Vi2+|Anode of the channel 2 voltage input
67 |Vi2-|Cathode of the channel 2 voltage input
68
69 (% style="text-align:center" %)
70 [[image:LX3V-2ADV-BD_html_71ba75f4eda67646.png||height="331" width="300" class="img-thumbnail"]]
71
72 **LED lights indicating:**
73
74 1. LED1: ON when power ON.
75 1. LED2: flashes when communications.
76 1. LED3 (AD 1): On indicates enable, OFF indicates disable, flicker indicates exceeding the measurement range.
77 1. LED4 (AD 2): On indicates enable, OFF indicates disable, flicker indicates exceeding the measurement range.
78
79 **If the BD module is plugged into the PLC which uses old firmware version, when PLC power on, all LEDs will be flashing.**
80
81 = **4 Specification** =
82
83 1. Please refer to the LX3V user manual for the general specification of LX3V-2ADV-BD.
84 1. LX3V-2ADV-BD is powered supply by LX3V main unit.
85
86 (% class="table-bordered" %)
87 |=(% rowspan="2" scope="row" %)**Item**|**Specification**
88 |=**Voltage input**
89 |=Input range|DC -10 ~~ 10V (Input resistance:150KΩ)
90 |=Digital output|12 bits binary
91 |=Resolution|4mV (10 : 1/2000)
92 |=Precision|±1%
93 |=AD conversion time|One PLC scanning cycle
94 |=Characteristic|(((
95 (% style="text-align:center" %)
96 [[image:LX3V-2ADV-BD_html_96d11a227504d6ac.gif||class="img-thumbnail"]]
97 )))
98 |=Insulation|No insulation in each PLC channel
99 |=Occupied points|None
100
101 = **5 Wiring** =
102
103 **Caution:**
104
105 1. Don’t put the LX3V-2ADV-BD module near high-voltage power cable. Keep away the power cable at least 100mm;
106 1. Do not solder any terminal with the others device;
107 1. Do not connect any unsuitable cable;
108 1. Please fix cable;
109 1. Do not connect any unit to the unused terminal;
110
111 == Suitable cable ==
112
113 Connect to output device with AWG25-16.
114
115 Max tighten torque of terminal is 0.5 to 0.6N.m.
116
117 Table 5‑1
118
119 (% class="table-bordered" %)
120 |=(% scope="row" %)**Line type**|**Cross sectional area(mm^^2^^)**|**End-of-pipe treatment**|(% rowspan="4" %)(((
121 (% style="text-align:center" %)
122 [[image:LX3V-2ADV-BD_html_36c77dd4cfbf8f04.gif||class="img-thumbnail"]]
123 )))
124 |=AWG26|0.1288|(% rowspan="3" %)(((
125 Stranded cable: stripped jacket, rub Conductor, then connect the cable.
126
127 Single-core cable: stripped jacket, Then connect the cable.
128 )))
129 |=......|......
130 |=AWG16|1.309
131
132 == Input mode ==
133
134 (% style="text-align:center" %)
135 [[image:LX3V-2ADV-BD_html_98abeac11c4b1b24.png||height="136" width="500" class="img-thumbnail"]]
136
137 = **6 Example** =
138
139 The input analog of all channels(-10V~~10V)is stored inside the data memory(D8112, D8113)in the form of data. Values will be automatically stored when the “END” order is sent out. The value is calculated by the designated analog data conversion characteristics of the special auxiliary relays M8112 and M8113.
140
141 == Basic Program Examples ==
142
143 **✎Note: **
144
145 1. Start M8112 and M8113; designate the analog data conversion characteristics of CH1 and CH2.
146 1. After execution of analog data conversion, do not change the values of D8112 or D8113 through operator program, programming tools or graphic operating terminal.
147
148 The following program can set CH1 and CH2 into voltage input mode. After ADV conversion, values of all channels are stored into D0 and D2.
149
150 (% style="text-align:center" %)
151 [[image:LX3V-2ADV-BD_html_93aebf886a9799d3.png||height="129" width="528" class="img-thumbnail"]]
152
153 == Examples of Applications ==
154
155 Since the LX3V-2ADV-BD does not have offset and gain functions, if it needs for the values out of the standard specifications, Additional programming orders will be needed to multiply or divide the converted value.
156
157 **✎Note: **
158
159 1. Since the use of additional programming orders, the converted precision and resolution of the analog value are different with the specifications.
160 1. The original range of the analog output does not change.
161
162 **Voltage Input Mode**
163
164 Under the voltage input mode, the 2ADV will convert the analog value -10V~~10V into data output -2000~~2000. If the data range used in the application is 0-20000, then the range -2000~~2000 must be converted into 0-20000, as is shown in the following program examples. The data converted from the analog values are stored in D8112 or D8113.
165
166 Since the data range is converted from -2000~~2000 into 0-20000,therefore the resolution of the analog input is no longer just 8uA.
167
168 (% style="text-align:center" %)
169 [[image:LX3V-2ADV-BD_html_e5767d5bf37b750e.png||height="200" width="700" class="img-thumbnail"]]
170
171 If the data range used in D0 is (0-20000), please refer to the following text:Figures used in the user’s applications:D0=5×(D8112 or D8113)+10000.
172
173 We can give an example as follows based on the program of the above mentioned formula (under the situation of CH1)