Wiki source code of 06 Data Tool

Version 13.1 by Hunter on 2022/07/09 10:49

Show last authors
1 (% class="wikigeneratedid" id="H8BasicFunction" %)
2 This chapter provides information about basic functions and configuration in PIStudio.
3
4 = **Alarm** =
5
6 == **Bit Alarm** ==
7
8 Click "Project"->"Bit Alarm", it is displayed as the following figure.
9
10 (% style="text-align:center" %)
11 [[image:位报警 1.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
12
13 **(1) Group No.: **Group number of Bit alarm. The name is unique and cannot be duplicated.
14
15 **(2) Bit Address: **Bit address of alarm monitoring
16
17 (% start="1" %)
18 1. **Record bit alarm by default:**  Whether to record the alarm history data of bit alarm, if checked, it will be saved in the designated storage location.
19 1. **Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
20
21 **(3) Upload to Cloud: **The data upload by "bit alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
22
23 **✎Note:**
24
25 * After enable the Cloud and check the box of Upload to Cloud, the communication port settings of the address in the imported Bit Alarm record configuration must be the same as the communication port settings of the current project, otherwise it cannot be used normally.
26 * The number of Alarm records upload to Cloud shall not exceed the limit value, or the sum of the imported alarm records and the number of existing alarm records shall not exceed the limit value. the specific limitation as following table:
27
28 (% style="margin-left:auto; margin-right:auto; width:358px" %)
29 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
30 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
31 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
32 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
33 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
34
35 **(4) Alarm Condition:** It sets alarm trigger condition, there are two types: alarm when ON and alarm when OFF.
36
37 **(5) Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
38
39 **(6) Beep when alarm ON: **The beep works when the alarm is triggered. If "beep once" is checked, bit address alarm only beep once and stop.
40
41 **(7) Content: **It is used for setting alarm content (command).
42
43 **(8) Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
44
45 1. **Position: **The location of the screen alarm display.
46 1. **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
47 1. **Pop-up once: **Pop up alarm screen once, and the screen would not pop up again
48 1. **Close window when alarm off: **Automatically close the alarm screen when alarm off.
49
50 **✎Note:**
51
52 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported bit alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
53 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
54
55 **Operating Procedures of Adding One Alarm**
56
57 1. Click "Project"->"Bit Alarm" as below shows.
58
59 (% style="text-align:center" %)
60 [[image:8.Basic Function_html_5f8da20315334bac.png||data-xwiki-image-style-alignment="center" height="144" width="539" class="img-thumbnail"]]
61
62 (% start="2" %)
63 1. Click "Add" button to open "Bit Alarm" setting window.
64
65 (% style="text-align:center" %)
66 [[image:8.Basic Function_html_94a019683b506e15.png||data-xwiki-image-style-alignment="center" height="307" width="554" class="img-thumbnail"]]
67
68 (% start="3" %)
69 1. Set "Bit Address".
70 1. Set "Alarm Condition".
71 1. Set "Content".
72 1. Other settings can be set according to the actual situation".
73 1. Click "OK" button to complete settings.
74
75 == **Word Alarm** ==
76
77 Word alarm is to monitor the word address of a device. If the data meets the set conditions, an alarm will be generated.
78
79 Click "Project"->"Word alarm", it is displayed as the following figure.
80
81 (% style="text-align:center" %)
82 [[image:字报警 1.png||class="img-thumbnail"]]
83
84 **(1) Alarm Name:** You can set alarm name for it. Alarm Name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters.
85
86 **(2) Alarm Address: **It is used for setting word address for word alarm, such as HDW0.
87
88 **(3) Data Format: **16-bit unsigned decimal, 16-bit signed decimal, 16-bit BCD, 32-bit unsigned decimal, 32-bit signed decimal, 32-bit BCD, 32-bit float.
89
90 **(4)  Group No.: **Group number of word alarm. The name is unique and cannot be duplicated.
91
92 **(5) Upload to Cloud: **The data upload by "word alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
93
94 **✎Note:**
95
96 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported word alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
97 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
98
99 (% style="margin-left:auto; margin-right:auto; width:358px" %)
100 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
101 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
102 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
103 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
104 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
105
106 **(6) Record alarm:**  Whether to record the alarm history data of word alarm, if checked, it will be saved in the designated storage location.
107
108 **(7) Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
109
110 **(8) Alarm Condition**: Alarm is triggered when designated address meets the alarm condition, it provides four conditions;
111
112 1. **High alarm:** Alarm is triggered when it reaches high limit. It can be a constant or a variable
113 1. **Low alarm:** Alarm is triggered when it reaches low limit. It can be a constant or a variable
114 1. **Range alarm:** Alarm is triggered when it exceeds the range. It can be a constant or a variable
115 1. **Equivalent alarm: **Alarm is triggered when the value equals to the given data. It can be a constant or a variable
116
117 **(9) Alarm Info: **It is used for setting alarm content (command);
118
119 **(10) Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
120
121 **(11) Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
122
123 1. **Position: **The location of the screen alarm display.
124 1. **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
125 1. **Pop-up once: **Pop up alarm screen once.
126 1. **Close window when alarm off: **Automatically close the alarm screen when alarm off.
127
128 **(12) Beep when alarm ON: **beep works when the alarm is triggered, in the default mode, the beep works until the alarm is released.
129
130 **(13) Beep once:** Beep works once, when alarm is triggered.
131
132 **(14) Alarm List**
133
134 It displays all the word alarm lists; it will show the alarm information;
135
136 **Operating Procedures of Adding One Alarm**
137
138 1. Click "Project"-> "Word Alarm" as below shows.
139
140 (% style="text-align:center" %)
141 [[image:8.Basic Function_html_1b59522c984cd7c2.png||height="144" width="492" class="img-thumbnail"]]
142
143 (% start="2" %)
144 1. Click [Add] button to open [Word Alarm] setting window.
145
146 (% style="text-align:center" %)
147 [[image:8.Basic Function_html_942107c81fc6901c.png||height="307" width="554" class="img-thumbnail"]]
148
149 (% start="3" %)
150 1. Set Basic information of word alarm.
151 1. Set "Content".
152 1. Other settings can be set according to the actual situation.
153 1. Click "OK" button to complete settings.
154
155 **HMI Alarm Demo Download Link**
156
157 [[https:~~/~~/drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP>>url:https://drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP]]
158
159 = **{{id name="_Toc17174"/}}{{id name="_Recipe"/}}Recipe** =
160
161 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
162
163 Data operation
164
165 1. **Read:** Read a group of data from the recipe file and assign the group of data to the set address.
166 1. **Write: **Read a group of data from the set address and assign the group of data to the corresponding recipe file.
167
168 PI Series HMI has Recipe function, Recipe function keeps data in the HMI, used to download the data from HMI to designated device addresses, or upload the data from device addresses to HMI.
169
170 The maximum number of group in recipe is 1000, and the maximum number of member in each group is 1500.
171
172 Recipe could store the data in USB flash disk and SD card and view the recipe data by object "Recipe display". It has two mode: simple mode and advanced mode.
173
174 1. **Simple: **Only support the data operation of one recipe file, including read and write.
175 1. **Advanced:** Support the data operation of multiple recipe files, including read, write, insert and index. View and select recipe file by object "File list".
176
177 Recipe function settings will be display in "[[Recipe display>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/06.Objects/#HRecipedisplay]]" object.
178
179 **Description**
180
181 (% style="text-align:center" %)
182 [[image:8-1Recipe.png]]
183
184 **(1) Basic**
185
186 1. **Recipe Folder:** Give Recipe folder name (It can be used, when setting Recipe display object);
187
188 * **✎Note: **Recipe Folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters;
189
190 (% start="2" %)
191 1. **Group: **It sets the groups' initial number of recipe;
192 1. **Elements:** It sets members' initial number of each group;
193 1. **Data Format:** There are some formats can be supported in Recipe, like 16-bit BCD, 16-bit signed, 16-bit unsigned, 32-bit BCD, 32-bit signed, 32-bit unsigned, 32-bit floating and string. If each member requires different formats, please set it one by one in form;
194 1. **Decimal: **It sets integer and scale digits;
195
196 **(2) Mode Selection**
197
198 Users could select Simple or Advanced mode.
199
200 **(3) Function Address:**
201
202 All the operations for recipe is by this address
203
204 * =0 No operation.
205 * =1 Read data from recipe.
206 * =2 Insert a new group or write data to exist group.
207 * =4 Inserted (only advanced mode).
208 * =8 Delete.
209 * =16 Delete and Sequence.
210
211 **(4) Use Multiple File**
212
213 Check it to use more than one recipe file in HMI, but this option only valid in [Advanced mode];
214
215 **(5) Select language**
216
217 The text in HMI can be in 8 languages, user can set language in here;
218
219 **(6) Address**
220
221 1. **Group:** This address is for selecting group number;
222 1. **Start: **This is starting address is for reading and writing in recipe, PIStudio will automatically assigns addresses for each members;
223 1. **File(16 words): **This address only available when enable the Use Multiple File. This setting address is for input the recipe file's filename.
224
225 **(7) Use Index**
226
227 If the value from Group address is changed, Read address will display the new data according to new group number immediately. Relatively, if the data of write address is changed, the corresponding group from table is also changed.
228
229 **(8) Query by Element**
230
231 Enable it for querying group by specify element, select a primary key from all the elements, except the group number. This element value from all groups must be unique if want to set as primary key;
232
233 **✎Note: **When this option is enabled, Group address will be invalid.
234
235 **(9) Use Independent Write Address**
236
237 To separate Recipe read address and write address.
238
239 **(10) Use Insert**
240
241 It inserts data into the specified group, if the specified group already exists, it would not cover the original data, while it will move the original group next one after it.
242
243 **(11) Discontinuous Address**
244
245 Whether enable the non-consecutive recipe operation addresses or not. If disabled, the recipe address will recover as the continuous addresses.
246
247 **✎Note: **This function only supported in HMI+, i series, ie series, ig series.
248
249 **Operating Procedures**
250
251 1) Click "Project"->"Bit Alarm" as below shows.
252
253 (% style="text-align:center" %)
254 [[image:8.Basic Function_html_a7d1546a3a9f752f.png||height="144" width="535" class="img-thumbnail"]]
255
256 2) Click "Add" button to open "Recipe" setting window.
257
258 (% style="text-align:center" %)
259 [[image:8.Basic Function_html_8f04e01413981054.png||height="307" width="554" class="img-thumbnail"]]
260
261 3) Set basic settings for recipe.
262
263 4) Select mode according to actual condition.
264
265 5) Other settings can be set according to the actual situation.
266
267 6) Click [OK] button to complete settings.
268
269 **Recipe Demo Download Link**
270
271 [[https:~~/~~/drive.google.com/open?id=1Cjbq_tW-NIirHFBpxt47g7IKvoYaWqUR>>url:https://drive.google.com/open?id=1Cjbq_tW-NIirHFBpxt47g7IKvoYaWqUR]]
272
273 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Traditional Recipe**(%%) =
274
275 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
276
277 Traditional recipe function is valid only when the LEVI project is converted to the PI project, and the original project uses the traditional recipe.
278
279 **✎Note**: Currently, only HMI+, i series, ie series, and ig series support the traditional recipe.
280
281 == **Simple recipe mode** ==
282
283 Click the "Traditional Recipe" [[image:8-2TraditionalRecipe.png]] in the "Data tool" bar in the upper side of the software, and the following interface will pop up:
284
285 (% style="text-align:center" %)
286 [[image:8-3TraditionalRecipeConfigScreen.png||class="img-thumbnail"]]
287
288 **✎Note**:
289
290 * The recipe folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), ('').
291 * The element name of the recipe cannot include following 5 special characters: " **,** " , " **|** " , " **<** " , " **>** " , " **&** " .
292
293 == **Recipe display** ==
294
295 Select the file type "Traditional recipe file" in object "Recipe Display", and it is recommended to fill in the traditional recipe group number HSW1612 to the address of select line.
296
297 **✎Note**: The Recipe Display can display up to 50 groups of 100 elements, which can be to display out of range by enabled "Address Control", as following shown:
298
299 (% style="text-align:center" %)
300 [[image:8-4TraditionalRecipeDisplayConfigScreen.png||class="img-thumbnail"]]
301
302 == **Recipe transmission address** ==
303
304 The special addresses used in the Recipe are shown in the following table:
305
306 (% class="table-bordered" %)
307 |=Address|=Description|=Function
308 |HSW1611|Traditional Recipe transfer operation.|(((
309 ~=1: Recipe download.
310
311 ~=2: Recipe upload.
312 )))
313 |HSW1612|Traditional Recipe group number.|Traditional Recipe group number.
314 |(((
315 HSW242
316 )))|(((
317 Recipe operation result prompt:
318
319 Upload: Data is written to recipe file from address.
320
321 Download: Data is written to the address from recipe file.
322 )))|(((
323 ~=1: Recipe download, start.
324
325 ~=2: Recipe download, execution error.
326
327 ~=6: Recipe download, successful.
328
329 ~=7: Recipe upload, start.
330
331 ~=8: Recipe upload, execution error.
332
333 ~=11: Recipe group name does not exist.
334
335 ~=12: Recipe upload, successful.
336 )))
337
338 == **Recipe index** ==
339
340 The recipe index address RPW is mainly used for editing traditional recipes, and it is more convenient to modify the data and display of recipes. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
341
342 The recipe index area (RPW)'s instruction as follows:
343
344 1. RPW~*~*~#~#~#~#, a total of six digits, the first two ~*~* represent the Recipe group number, ~#~#~#~# represents the element order number. For example, RPW010000 indicates the 1st element of the Recipe group No.1, and RPW110002 indicates the 3rd element of the Recipe group No.11.
345 1. If the indexed group number or element number does not exist, the value of RPW defaults to zero. For example, RPW110011 represents the 12th element of the Recipe group No.11. If it does not exist, the value returned by accessing RPW110011 is zero. The value written in RPW110011 will not be saved to the recipe file.
346
347 * **✎Note**: As long as RPW~*~*~#~#~#~# exists, any object "writes" to HPW~*~*~#~#~#~# will be saved to the recipe file. 
348
349 (% start="3" %)
350 1. The RPW register only supports word address access.
351 1. It can be known from the coding method of RPW~*~*~#~#~#~# that the range of RPW is from RPW000000-RPW990450, wherein the range of group number is 0-100, and the range of element is 0-450.
352
353 == **Recipe example** ==
354
355 The recipe index makes the modification and display of recipe data more convenient. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
356
357 (1) Edit the recipe configuration, create three groups of recipes, 4 elements for per group: Red, green, blue, spraying time, as following shown:
358
359 (% style="text-align:center" %)
360 [[image:8-5TraditionalRecipeCaseConfig.png]]
361
362 (2) RPW 0~~3 can display the data of group for the selected line. RPW10000~~10003, RPW20000~~20003, RPW30000~~30003 each address can display the single element. Directly modify the content of the RPW address and then modify the recipe data, as following shown:
363
364 (% style="text-align:center" %)
365 [[image:8-7TraditionalRecipeCaseShowNoOpera.png]]
366
367 (3) After selecting the 2nd group, trigger the download button to download the whole group data to the corresponding element address (For this case, the data will write into HDW0~~3), or trigger the upload button to upload the content of the element address to the specified recipe group.
368
369 (% style="text-align:center" %)
370 [[image:8-6TraditionalRecipeCaseShow.png]]
371
372 = **{{id name="_Toc5565"/}}{{id name="_Trend_Chart"/}}Trend Chart** =
373
374 Trend chart function is used for displaying the real-time data in HMI as curve graph, which X axis represent as time, Y axis represent as data.
375
376 Click "Project" → "Trend chart", it will pop up the following screen. Click "Add" to creat new curve record.
377
378 (% style="text-align:center" %)
379 [[image:趋势图配置 001.png||class="img-thumbnail"]]
380
381 **Settings**
382
383 (% style="text-align:center" %)
384 [[image:趋势图设置 2.png||height="507" width="866"]]
385
386 **(1) Basic settings**
387
388 1. **Curve NO.: **It is for setting curve number,
389 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
390 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
391 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
392
393 **(2) Sample Type**
394
395 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
396 1. **Sample unit:** 100ms.
397
398 **(3) Quick Setting**
399
400 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
401
402 (% style="text-align:center" %)
403 [[image:趋势图设置 3.png||class="img-thumbnail"]]
404
405 (% start="2" %)
406 1. **Sample address: **Fill in the start address that read the device data. If the sampl address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
407
408 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
409
410 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
411
412 **Trend Chart Demo Download Link**
413
414 [[https:~~/~~/drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC>>url:https://drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC]]
415
416 = **{{id name="_Toc7121"/}}{{id name="_History_XY_Plot"/}}History XY Plot** =
417
418 Different from TrendChart, uses need to set history XY curve items in project. Please click "Project"-> "History XY Plot" to open the setting screen.
419
420 Recipe function settings will be display in "[[History XY Plot>>path:http://docs.we-con.com.cn/wiki/pistudio/view/Helps/06.Objects/#HHistoryXYplot]]" object.
421
422 (% style="text-align:center" %)
423 [[image:历史XY 2.png||class="img-thumbnail"]]
424
425 (% style="text-align:center" %)
426 [[image:历史XY 3.png||class="img-thumbnail"]]
427
428 **(1) Basic settings**
429
430 1. **Curve NO.: **It is for setting curve number,
431 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
432 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
433 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
434
435 **(2) Sample Type**
436
437 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
438 1. **Sample unit:** 100ms.
439
440 **(3) Quick Setting**
441
442 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
443
444 (% style="text-align:center" %)
445 [[image:image-20220616145435-1.png]]
446
447 (% start="2" %)
448 1. **Sample address: **Fill in the start address that read the device data. If the sample address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
449
450 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
451
452 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
453
454 **Operating Procedure**
455
456 1. Click "Project" -> "History XY Plot" to open the function selecting windows.
457
458 (% style="text-align:center" %)
459 [[image:8.Basic Function_html_5da6ca44bd28acbe.png||height="144" width="533" class="img-thumbnail"]]
460
461 (% start="2" %)
462 1. Click "Add" button to open [History XY Plot] setting windows.
463
464 (% style="text-align:center" %)
465 [[image:8.Basic Function_html_6345b50ea55168fa.png||height="307" width="554" class="img-thumbnail"]]
466
467 1. Setting the function of History XY Plot.
468 1. Click "OK" to save the setting.
469
470 **Download Link**
471
472 [[https:~~/~~/drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r>>url:https://drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r]]
473
474 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Data Record**(%%) =
475
476 The data record function is organized according to the structure below. In a project, there can be multiple record groups, each record group containing multiple channels. Different groups have different sampling times.
477
478 The topology is shown in the following figure.
479
480 (% style="text-align:center" %)
481 [[image:8.Basic Function_html_1b4bd09dafa7e049.png||height="332" width="554" class="img-thumbnail"]]
482
483 The data record stored in SD card is also organized according to the above figure.
484
485 The sample time and save time is consistent in the same record group. There are multiple channels in the group, When the sampling time is up, every channel would collect data to PLC register according to its own address.
486
487 **Sampling interval: **The interval between two consecutive samples was recorded.
488
489 As long as the project uses the data record function and supports the large-capacity storage module, the system will sample data according to the set sampling interval and save data according to the set saving interval.
490
491 For the file storage of data, see the file size configuration during data record configuration.
492
493 ✎**Note: **The record group name can only be composed of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_'), ('') and other non-English characters.
494
495 (% class="wikigeneratedid" id="HSettings" %)
496 **Settings**
497
498 (% style="text-align:center" %)
499 [[image:数据记录设置 1.png||height="533" width="848" class="img-thumbnail"]]
500
501 **Operating Procedures**
502
503 1. Click "Project"->"Data record" as below shows.
504 1. Click "Add" button to open "Data record" setting window.
505 1. Enter group name, the default is "GroupName0"
506 1. Select "Trigger function" mode, such as "No trigger".
507 1. Set "Total channels", such as 3.
508 1. Click "Apply" button.
509 1. Set Sample cycle, such as 15.
510 1. Set "Start channel" in "Quick settings", such as 4 0.
511 1. Check group information in "Channel list" as below.
512 1. Click "Save" button to complete settings.
513
514 The figure above display the group of current project. The data record file would stored in "DataLogFile" folder, and the data of every  group would have a data file. The file suffix is in "db" format.
515
516 ✎**Note: **
517
518 * For HMI series 8000 and above, the size of a single file cannot exceed 300M and the total file capacity cannot exceed 1000M.
519 * For HMI series 3000, the size of a single file cannot exceed 4M and the total file capacity cannot exceed 10M.
520 * If the total amount exceeds the range, an alarm will be given during project compilation.
521
522 (% style="text-align:center" %)
523 [[image:数据记录设置 2.png||height="572" width="850" class="img-thumbnail"]]
524
525 **(1) Group name:** Set group name, and he name should be unique.
526
527 **(2) Trigger function:** There are four modes to trigger record.
528
529 1. **No trigger: **Data will be recorded in every sample time.
530 1. **Trigger to record by sample cycle: **Data will be recorded in every same time, when trigger control bit set ON.
531 1. **Trigger to record once and reset: **Data will be recorded when trigger control bit set ON, and the bit will be reset automatically.
532 1. **Trigger to record once: **Data will be recorded when trigger control bit set ON, and the bit need to be reset manually.
533 1. **Trigger address: **It is only valid when the trigger condition is selected. The monitoring cycle for trigger sampling address is 1s.
534
535 **(3) Total channels (1~~100): **Set the numbers of channels. Click "apply" to view the channel lists on the right record channel.
536
537 **(4) Sampling cycle: **If you check "collect control address", the sampling interval is the value of the address. The unit is second. For example, Sample cycle=15s. It means that records data one time every 15s.
538
539 **Timing address:** It sets address to change sample time when HMI is running;
540
541 **(5) Total records:** It sets data record number in one data record file. If the data file size is beyond the current file size. The old data will be deleted, and the new data will replace the old data. Please remember to back up the old data record file.
542
543 **Abnormal value:** It sets a value, when communication fails, data record will record this value;
544
545 **(6) Upload to Cloud**: The data uploaded by Data Record is stored in the Cloud(Only ig series). The maximum number of record is 20.
546
547 **(7) Quick Settings**
548
549 1. **Start Channel:** It sets the continuous addresses for channels.
550 1. **Data Format: **It sets the same data format for channels.
551 1. **Number of Digits:** It sets the digits’ number for channels.
552 1. **Language Settings**: The text in HMI can be in 8 languages, user can set language in here.
553
554 **(8) Channel List**: Besides quick settings, user can set channel name, address, data format, and so on one by one according to real situation.
555
556 **✎Note:**
557
558 * After enabling the Cloud function and checking the upload to the Cloud, the communication port settings of the address in the imported Data record configuration must be the same as the communication settings of the current project, otherwise it cannot be used normally.
559 * The range of upload to the Cloud from Data record configuration must not exceed 50, or the total number of imported Data records and the number of currently existing Data records must not exceed 50. If it exceeds, it will prompt you to reconfigure, should reduce the number.
560 * The channel name can only be composed of English characters, (0~~9), (a~~z), (A~~Z), ('_'), ('').
561 * The channel name does not include these 5 special characters: ", ", "| "," <", "> "," & ".
562 * The data would be overwritten automatically if the capacity exceed the maximum capacity. For 8000/9000 series, the size of single file cannot exceed 300MB, and total capacity of data records cannot exceed 1000MB. For 3000/3000i/3000ie series, the size of single file cannot exceed 4MB, and total capacity of data records cannot exceed 10MB. If the total amount exceeds the range , an error will be prompted when the project is compiled.
563
564 You could click here to jump to object "[[Data Record Display>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/06.Objects/#HDataRecordDisplay]]"
565
566 (% class="wikigeneratedid" id="H" %)
567 **PI Data Record Demo Download**
568
569 **[[Demo Link>>https://drive.google.com/open?id=1h7VUsIJqH4LIRjjtphbv9Kmzd6jUMPtE]]**
570
571 **[[Video Link>>https://drive.google.com/open?id=1h7VUsIJqH4LIRjjtphbv9Kmzd6jUMPtE]]**
572
573 = **{{id name="_Toc3497"/}}{{id name="_User_Permission"/}}User Permission** =
574
575 **Introduction**
576
577 1. User permission is one of expansion function in PI Series HMI; it provides multi-level of permission for control HMI operations.
578 1. User need to set the user and group during designing project. Different groups have different permission levels for accessing. Each user should be added into the specified group; it is possible to add the same user into different groups.
579 1. Operating record: it records user operations information, the records files are saved in HMI flash; its path is [~\~\flash~\~\UserOperationLogs.db].
580 1. When it is on simulator mode, the files are saved in C disk, its path is [C:~\~\WECON\UserMgrFile\UserOperationLogs.db].
581
582 ✎**Note: **The user name and password must be unique.
583
584 == **Settings** ==
585
586 **Open PIStudio software, then operate as the following figure.**
587
588 (% style="text-align:center" %)
589 [[image:用户权限 1.png||class="img-thumbnail"]]
590
591 1. Click "User Permission" in "Data Tool" toolbar.
592 1. Edit user name, click "User0" cell under "UserName", and then enter the user name, one project allows maximum 20 users.
593 1. Edit password, click "User0" cell under "PassWord", and then enter the user name.
594 1. Edit description, click "User0" cell under "Desc", and then enter, description is not necessary。
595 1. Check the groups for each user, there are 11 groups beside admin.
596 1. Editing groups' description, but it is not necessary.
597 1. {{id name="OLE_LINK7"/}}{{id name="OLE_LINK6"/}}Click "Save and Exit" button to complete all settings.
598
599 ✎**Note:**
600
601 * Only a maximum of one administrator permission is allowed in a profile with one user permission. If you want to use "Funtion address" to modify the user permission, you must log in the administrator account to operate.
602 * When the configured file does not have the administrator account, a new user can be added  through "Funtion address" and set as the administrator.
603 * If you select hidden fucntion when configuring user account, the account would display as "~*~*~*~*~*~*" in the list. You only need to enter the password of the corresponding hidden user to log in.
604
605 == **Object permission configuration** ==
606
607 (% style="text-align:center" %)
608 [[image:用户权限 2.png||class="img-thumbnail"]]
609
610 {{id name="OLE_LINK3"/}}{{id name="OLE_LINK4"/}}**Operation Procedure of Object Permission**
611
612 1. Open the object setting windows;
613 1. Select [Security] windows;
614 1. Check the [User Permission];
615 1. Select [Level] to set permission level;
616 1. Enter [Log Message], it is for operation records, if it was empty, the operation for this object would be not be recorded;
617 1. Select the ~[[[Access Denied Setting>>path:#_Security]]] mode;
618
619 **Log information description**
620
621 1. A combination of Chinese characters, numbers, and uppercase and lowercase letters can be entered, and the number does not exceed 63.
622 1. The format of insert variable:{variable address, data format}. e.g., {HDW100,UW2.1}.
623
624 The data format are as follows.
625
626 (% class="table-bordered" %)
627 |=Letter|=Meaning
628 |B|Binary
629 |O|Octonary
630 |U|Unsigned decimal
631 |H|Hexadecimal
632 |b|BCD
633 |F|32-bit float
634 |S|Signed decimal
635 |C|Character
636 |W|Single word
637 |D|Double word
638
639 (% start="3" %)
640 1. Examples.
641
642 * Unsigned decimal, BCD, 32-bit float and Signed decimal are as follows.
643
644 {HDW100,UW2.1}:  Indicates the variable address is HDW100. The data format are: unsigned decimal, single word, two integer bits, one decimal place.
645
646 * (((
647 Binary, Octonary and Hexadecimal are as follows.
648 )))
649
650 {HDW100,HD8}: Indicates the variable address is HDW100. The data format are: hexadecimal, double word, eight integer bits.
651
652 * (((
653 Character is as follows.
654 )))
655
656 {HDW100,C32}: Indicates the variable address is HDW100. The data format are: 32 characters.
657
658 When a record is generated, the contents of this variable are replaced by the value of your corresponding address.
659
660 == **Function address** ==
661
662 A user must first log in before performing an operation, and after the login is successful, the user can perform the required operation, and log out after completing the operation, making the operation permission invalid. User login, log out, modification of user password during operation and user management and other functions need to be configured.
663
664 HMI allows managing user accounts on screen. Including adding, deleting and editing the user account. HMI provide built-in screen for [Sign in] and [change password] (screen No. 1006 and 1007).
665
666 Functions and addresses are as follows.
667
668 (% class="table-bordered" %)
669 |=**Function**|=**Address**|=**Object type**|=**Address function**
670 |(% rowspan="3" %)Sign in|HUW1158~~1335|Drop down list|User name
671 |HUW1002|Character input object|Password
672 |HUW1000|Word Switch (Input 1)|OK (sign in)
673 |(% rowspan="5" %)Change password|HUW1158~~1335|Drop down list|User name
674 |HUW1002|Character input object|Old password
675 |HUW1006|Character input object|New password
676 |HUW1010|Character input object|Confirm password
677 |HUW1000|Word Switch (Input 2)|OK(change password)
678 |Sign out|HUW1000|Word Switch (Input 3) |Sign out
679 |(% rowspan="7" %)(((
680 New user ***1**
681 )))|HUW1014|Character input object|User name
682 |HUW1006|Character input object|password
683 |HUW1010|Character input object|Confirm password
684 |HUW1000|Word Switch (Input 4) |OK(add new user)
685 |HUW1336~~1345|Character input object|User description
686 |HUX1347.0|Bit switch|(((
687 ~=1: User hidden
688
689 ~=0: Visible (Defaults)
690 )))
691 |HUW1000|Word Switch (Input 8) |Save(add Hide features)
692 |(% rowspan="2" %)(((
693 Delete user ***2**
694 )))|HUW1158~~1335|Drop down list|User name
695 |HUW1000|Word Switch (Input 5)|OK (delete user)
696 |Delete Profile|HUW1000|Word Switch (Input 9)|OK(delete)
697 |Export Profile|HUW1000|Word Switch (Input 10)|OK(export)
698 |Import profile|HUW1000|Word Switch (Input 11)|OK(import)
699 |Export log file|HUW1000|Word Switch (Input 12)|OK(export)
700 |Delete log file|HUW1000|Word Switch (Input 13)|OK (delete)
701 |Current user name|HUW1349|Character object|32 Word
702 |System state information|HUW1030|Character input object|System state information
703 |(% rowspan="3" %)Permission settings|HUW1014|Character input object|User name
704 |HUW1348|Bit switch|(((
705 Set the user group:
706
707 HUX1348.0 = 1 administrator;
708
709 HUX1348.1 = 1 group 0 permission;
710
711 HUX1348.2 = 1 group 1 permission;
712
713 (Total group 0 - group 10)
714 )))
715 |HUW1000|Word Switch (Input 6)|Add user rights (set according to HUW1348)
716 |User login mode setting|HUW1382|Word Switch/Numeric input object|(((
717 0: Select a user name from the drop-down list
718
719 1: Use character input object (address HUW1014) to log in with a user name
720 )))
721
722 When the user performs a function operation, the operation result is displayed in the HUW1001.
723
724 (% class="table-bordered" %)
725 |=**Value (HUW1001)**|=**Meaning**
726 |1|Insufficient permissions.
727 |2|Username does not exist.
728 |3|Username already exists.
729 |4|Wrong username or password.
730 |5|Login successfully.
731 |6|Passwords are inconsistent in twice time.
732 |7|Password changed successfully.
733 |8|User added successfully.
734 |9|User deleted successfully.
735 |10|Maximum number of users exceeded.
736 |11|Admin user already exists.
737 |12|User permission modified successfully.
738 |13|File imported successfully.
739 |14|File imported failed.
740 |15|File exported successfully.
741 |16|File exported failed.
742 |17|Logout successfully.
743 |18|Profile deleted successfully.
744 |19|Log file deleted successfully.
745 |20|Hide settings modified successfully.
746 |21|Hide settings modified failed.
747 |22|(((
748 Password already occupied, please reset.
749
750 (For both username and password, it can not repetition)
751 )))
752
753 **✎Note:**
754
755 * *1: If there is an admin user account, then the new user can no longer add one more admin, that is, one project can only have one administrator account.
756 * *1: When adding new user, the password could not be duplicated with other users.
757 * *2: When deleting user, it is forbidden to delete the admin user.
758
759 **User Permission Demo Download**
760
761 [[https:~~/~~/drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq>>url:https://drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq]]
762
763 = **{{id name="_Toc29015"/}}{{id name="_MessagePrompt"/}}Message Prompt** =
764
765 A message box is a window used to show some prompts or warnings to users. For example, the application process a task in the process of pop-up message box, suggesting that "U disk has been detected", then the customer can carry out data dump function.
766
767 (% style="text-align:center" %)
768 [[image:消息提示 2.png||class="img-thumbnail"]]
769
770 (% style="text-align:center" %)
771 [[image:8.Basic Function_html_5ce2091d6f7cd732.png||height="515" width="704" class="img-thumbnail"]]
772
773 **(1) Message**
774
775 It includes system classes (u disk, SD card, and others), chart classes (alarm, data record, recipe, file list), curve classes (Trend Chart, historical XY trend Plot).
776
777 **(2) Control**
778
779 1. **Current item: **It shows selected message information.
780 1. **Use trigger address: **When the message is triggered, the trigger address would be set ON.
781
782 **For Example:**
783
784 Trigger address is 011, during inserting a USB flash disk into HMI, and 011 would be set ON, once HMI recognizes USB flash disk, and display message.
785
786 1. **Show message: **Check it to display message when HMI is running. It is checked by default.
787 1. **Show on web: **Check it to display message when remote access HMI screen, it is unchecked by default.
788
789 **(3) Message Content**
790
791 Each message has default content, but you could set different content according to the actual situation. And the same message could be displayed in 8 languages.
792
793 **(4) Reload Text: **It means discard changes.
794
795 **For Example**
796
797 User deletes default content or modifies default content, but he wants to give up modification back to original, just click "Reload text".
798
799 **✎Note:**
800
801 * If you do not want this prompt during the running of HMI, please uncheck "Show message".
802 * "Reload text" function would be invalid after clicking "save".
803 * These 5 special characters are not supported in the header Multi language settings: ",", "|", "<", ">", "&".
804
805 = **Cloud** =
806
807 **Introduction**
808
809 Cloud function is available for following models: the ig series and 8000/9000 series with -R after system upgrade
810
811 You may configure the basic settings of Cloud functions, tags, and User MQTT according to your needs. (If the device supports the Cloud function, you can use the function and configure the tags after checking the box to enable it, or upload the data to the 3rd party server.)
812
813 Click "Project"-"[[image:hh_B4H5OuNT87.png||height="29" width="30"]]Cloud" in the upper left corner of the software, as shown in the following figure.
814
815 (% style="text-align:center" %)
816 [[image:云配置1.png||height="494" width="750" class="img-thumbnail"]]
817
818 **(1) Enable**
819
820 If the HMI supports the Cloud function, check it to enable the Cloud function, and it will collect the real-time data from HMI upload to the Cloud. The number of data collection is limited, and the specific parameters are as follows:
821
822 |=Series|=Monitoring Tags|=Alarm Record|=Data Record|=OpenCloud Data
823 |8000-R|300|200|100|1000
824 |9000-R|300|200|100|1000
825 |3000ig|100|20|50|500
826 |8000ig|300|200|100|1000
827
828 For example:
829
830 ~1. In 3000ig's Cloud, the monitoring tags upload to the Cloud in real time is limited to 100.
831
832 2. For 3000ig's Alarm, the Alarm records of word alarms and bit alarms upload to Cloud is limited to 20. (See [["Alarm">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HAlarm]] for details).
833
834 3. For 3000ig's Data record, the Data records upload to Cloud is limited to 50. (For details, please refer to [["Data Record">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HDataRecord]]).
835
836 **(2) Server Selection**
837
838 **Server**: China, ASEAN, and Europe.
839
840 **Password**:
841
842 1. If the HMI is not bound, this access password will be updated and downloaded into the HMI screen simultaneously.
843 1. If the HMI is bound, this access password in the project cannot effectively change the binding password of the device, and it can only be changed through V-NET.
844
845 **(3) Upload Selection**: 
846
847 To upload the data collected by HMI to the cloud or a to the third-party server, only one upload method can be selected.
848
849 1. **to Cloud**: All the configured tags, data records, and alarm records would be pushed to V-NET.
850 1. **to User MQTT**: All the configured tags, data records, and alarm records would be pushed to to the third-party server, and the relevant Lua function calls please refer to "[[Cloud interface>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/10.Lua/#HCloudInterface]]".
851
852 After the "to User MQTT" is checked. The tags, data records, and alarms cannot be viewed on V-NET, but the device can be bound to V-NET and remote monitoring the device screen normally.
853
854 **4) Low Data Mode setting**
855
856 1. When you check the "low Data Mod" by default on new tags, the newly added tags will be enabled in Low Data Mode by default.
857 1. The longer the refresh interval, the slower the data upload, and the more traffic data will be saved. This function is only used for the control of tags.