Version 21.3 by Stone Wu on 2022/08/05 17:23

Show last authors
1 (% class="wikigeneratedid" id="H8BasicFunction" %)
2 This chapter provides information about basic functions and configuration in PIStudio.
3
4 = **Alarm** =
5
6 == Bit alarm ==
7
8 Click "Project"→"Bit Alarm", it is displayed as the following figure.
9
10 (% style="text-align:center" %)
11 [[image:位报警 1.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
12
13 **Group No.: **Group number of Bit alarm. The name is unique and cannot be duplicated.
14
15 **Bit Address: **Bit address of alarm monitoring
16
17 * **Record bit alarm by default:**  Whether to record the alarm history data of bit alarm, if checked, it will be saved in the designated storage location.
18 * **Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
19
20 **Upload to Cloud: **The data upload by "bit alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
21
22 **✎Note:**
23
24 * After enable the Cloud and check the box of Upload to Cloud, the communication port settings of the address in the imported Bit Alarm record configuration must be the same as the communication port settings of the current project, otherwise it cannot be used normally.
25 * The number of Alarm records upload to Cloud shall not exceed the limit value, or the sum of the imported alarm records and the number of existing alarm records shall not exceed the limit value. the specific limitation as following table:
26
27 (% style="margin-left:auto; margin-right:auto; width:358px" %)
28 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
29 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
30 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
31 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
32 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
33
34 **Alarm Condition:** It sets alarm trigger condition, there are two types: alarm when ON and alarm when OFF.
35
36 **Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
37
38 **Beep when alarm ON: **The beep works when the alarm is triggered. If "beep once" is checked, bit address alarm only beep once and stop.
39
40 **Content: **It is used for setting alarm content (command).
41
42 **Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
43
44 * **Position: **The location of the screen alarm display.
45 * **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
46 * **Pop-up once: **Pop up alarm screen once, and the screen would not pop up again
47 * **Close window when alarm off: **Automatically close the alarm screen when alarm off.
48
49 **✎Note:**
50
51 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported bit alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
52 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
53
54 **Operating Procedures of Adding One Alarm**
55
56 * Click "Project"→"Bit Alarm" as below shows.
57
58 (% style="text-align:center" %)
59 [[image:8.Basic Function_html_5f8da20315334bac.png||data-xwiki-image-style-alignment="center" height="144" width="539" class="img-thumbnail"]]
60
61 * Click "Add" button to open "Bit Alarm" setting window.
62
63 (% style="text-align:center" %)
64 [[image:8.Basic Function_html_94a019683b506e15.png||data-xwiki-image-style-alignment="center" height="307" width="554" class="img-thumbnail"]]
65
66 * Set "Bit Address".
67 * Set "Alarm Condition".
68 * Set "Content".
69 * Other settings can be set according to the actual situation".
70 * Click "OK" button to complete settings.
71
72 == Word alarm ==
73
74 Word alarm is to monitor the word address of a device. If the data meets the set conditions, an alarm will be generated.
75
76 Click "Project"→"Word alarm", it is displayed as the following figure.
77
78 (% style="text-align:center" %)
79 [[image:字报警 1.png||class="img-thumbnail"]]
80
81 **Alarm Name:** You can set alarm name for it. Alarm Name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters.
82
83 **Alarm Address: **It is used for setting word address for word alarm, such as HDW0.
84
85 **Data Format: **16-bit unsigned decimal, 16-bit signed decimal, 16-bit BCD, 32-bit unsigned decimal, 32-bit signed decimal, 32-bit BCD, 32-bit float.
86
87 **Group No.: **Group number of word alarm. The name is unique and cannot be duplicated.
88
89 **Upload to Cloud: **The data upload by "word alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
90
91 **✎Note:**
92
93 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported word alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
94 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
95
96 (% style="margin-left:auto; margin-right:auto; width:358px" %)
97 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
98 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
99 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
100 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
101 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
102
103 **Record alarm:**  Whether to record the alarm history data of word alarm, if checked, it will be saved in the designated storage location.
104
105 **Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
106
107 **Alarm Condition**: Alarm is triggered when designated address meets the alarm condition, it provides four conditions;
108
109 1. **High alarm:** Alarm is triggered when it reaches high limit. It can be a constant or a variable
110 1. **Low alarm:** Alarm is triggered when it reaches low limit. It can be a constant or a variable
111 1. **Range alarm:** Alarm is triggered when it exceeds the range. It can be a constant or a variable
112 1. **Equivalent alarm: **Alarm is triggered when the value equals to the given data. It can be a constant or a variable
113
114 **Alarm Info: **It is used for setting alarm content (command);
115
116 **Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
117
118 **Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
119
120 1. **Position: **The location of the screen alarm display.
121 1. **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
122 1. **Pop-up once: **Pop up alarm screen once.
123 1. **Close window when alarm off: **Automatically close the alarm screen when alarm off.
124
125 **Beep when alarm ON: **beep works when the alarm is triggered, in the default mode, the beep works until the alarm is released.
126
127 **Beep once:** Beep works once, when alarm is triggered.
128
129 **Alarm List**
130
131 It displays all the word alarm lists; it will show the alarm information;
132
133 **Operating Procedures of Adding One Alarm**
134
135 * Click "Project"→ "Word Alarm" as below shows.
136
137 (% style="text-align:center" %)
138 [[image:8.Basic Function_html_1b59522c984cd7c2.png||height="144" width="492" class="img-thumbnail"]]
139
140 * Click "AddClick" button to open "Word Alarm" setting window.
141
142 (% style="text-align:center" %)
143 [[image:8.Basic Function_html_942107c81fc6901c.png||height="307" width="554" class="img-thumbnail"]]
144
145 * Set Basic information of word alarm.
146 * Set "Content".
147 * Other settings can be set according to the actual situation.
148 * Click "OK" button to complete settings.
149
150 **HMI Alarm Demo Download Link**
151
152 [[https:~~/~~/drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP>>url:https://drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP]]
153
154 = **Recipe** =
155
156 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
157
158 Data operation
159
160 1. **Read:** Read a group of data from the recipe file and assign the group of data to the set address.
161 1. **Write: **Read a group of data from the set address and assign the group of data to the corresponding recipe file.
162
163 PI Series HMI has Recipe function, Recipe function keeps data in the HMI, used to download the data from HMI to designated device addresses, or upload the data from device addresses to HMI.
164
165 The maximum number of group in recipe is 1000, and the maximum number of member in each group is 1500.
166
167 Recipe could store the data in USB flash disk and SD card and view the recipe data by object "Recipe display". It has two mode: simple mode and advanced mode.
168
169 1. **Simple: **Only support the data operation of one recipe file, including read and write.
170 1. **Advanced:** Support the data operation of multiple recipe files, including read, write, insert and index. View and select recipe file by object "File list".
171
172 Recipe function settings will be display in "[[Recipe display>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/06.Objects/#HRecipedisplay]]" object.
173
174 **Description**
175
176 (% style="text-align:center" %)
177 [[image:8-1Recipe.png]]
178
179 **Basic**
180
181 * **Recipe Folder:** Give Recipe folder name (It can be used, when setting Recipe display object);
182 ** **✎Note: **Recipe Folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters;
183 * **Group: **It sets the groups' initial number of recipe;
184 * **Elements:** It sets members' initial number of each group;
185 * **Data Format:** There are some formats can be supported in Recipe, like 16-bit BCD, 16-bit signed, 16-bit unsigned, 32-bit BCD, 32-bit signed, 32-bit unsigned, 32-bit floating and string. If each member requires different formats, please set it one by one in form;
186 * **Decimal: **It sets integer and scale digits;
187
188 **Mode Selection**
189
190 Users could select Simple or Advanced mode.
191
192 **Function Address:**
193
194 All the operations for recipe is by this address
195
196 * =0 No operation.
197 * =1 Read data from recipe.
198 * =2 Insert a new group or write data to exist group.
199 * =4 Inserted (only advanced mode).
200 * =8 Delete.
201 * =16 Delete and Sequence.
202
203 **Use Multiple File**
204
205 Check it to use more than one recipe file in HMI, but this option only valid in [Advanced mode];
206
207 **Select language**
208
209 The text in HMI can be in 8 languages, user can set language in here;
210
211 **Address**
212
213 1. **Group:** This address is for selecting group number;
214 1. **Start: **This is starting address is for reading and writing in recipe, PIStudio will automatically assigns addresses for each members;
215 1. **File(16 words): **This address only available when enable the Use Multiple File. This setting address is for input the recipe file's filename.
216
217 **Use Index**
218
219 If the value from Group address is changed, Read address will display the new data according to new group number immediately. Relatively, if the data of write address is changed, the corresponding group from table is also changed.
220
221 **Query by Element**
222
223 Enable it for querying group by specify element, select a primary key from all the elements, except the group number. This element value from all groups must be unique if want to set as primary key;
224
225 (% class="box infomessage" %)
226 (((
227 **✎Note: **When this option is enabled, Group address will be invalid.
228 )))
229
230 **Use Independent Write Address**
231
232 To separate Recipe read address and write address.
233
234 **Use Insert**
235
236 It inserts data into the specified group, if the specified group already exists, it would not cover the original data, while it will move the original group next one after it.
237
238 **Discontinuous Address**
239
240 Whether enable the non-consecutive recipe operation addresses or not. If disabled, the recipe address will recover as the continuous addresses.
241
242 (% class="box infomessage" %)
243 (((
244 **✎Note: **This function only supported in HMI+, i series, ie series, ig series.
245 )))
246
247 == Simple recipe ==
248
249 The recipe function should be used together with the recipe configuration area, file list and record display object.
250
251 * Click the button [[image:image-20220805170000-1.jpeg]] in "Project"→"Bit Alarm" as below shows.
252
253 [[image:image-20220805170046-2.jpeg]]
254
255 * Click "Add" button to open "Recipe" setting window. The recipe mode is divided into simple mode and advanced mode, and you could choose the most suitable mode for configuration according to your needs. The simple mode is as below.
256
257 [[image:image-20220805170102-3.jpeg]]
258
259 **Recipe folder: **set the name of the current recipe file.
260
261 **Group (0~~1000):** Set the recipe group number, the number of elements, the data format. The data format has 8 modes: 16-bit signed decimal, 16-bit unsigned decimal, 16-bit BCD, 32-bit signed decimal, 32-bit unsigned decimal, 16-bit BCD, 32-bit floating point number, 64-bit (double-precision) floating-point number, string, and the choice of data integer and decimal places.
262
263 (% class="box infomessage" %)
264 (((
265 ✎**Note: **data format is set for the recipe elements, and all the elements in a recipe data format is the same.
266 )))
267
268 **Mode: **Recipe file is divided into simple mode and advanced mode. Only in advanced mode can exist multiple recipe files used at the same time. (used wiht file list onject), Simple mode can only support a recipe file; Aadvanced mode can insert group information and reordered.
269
270 Function address: all operations are done through function addresses, different operating value is as follows:
271
272 * = 0: no operation;
273 * = 1: trigger read data;
274 * = 2: new trigger or update (If there is group number, it updates.)
275 * = 4: insert (only valid in advanced mode)
276 * = 8: delete (Delete according to the writing group number. If write and read address are consistent, refer to the reading group number);
277 * = 16: delete and sorted ((Delete according to the writing group number. If write and read address are consistent, refer to the reading group number)
278 * = 64: import CSV recipe file.
279
280 Recipe folder names can only consist of (0~~9), (a~~z), (A~~Z), ('_') (''), and other non-English characters.
281
282 Adcanced
283
284 **Recipe Demo Download Link: **[[Download>>url:https://drive.google.com/open?id=1Cjbq_tW-NIirHFBpxt47g7IKvoYaWqUR]]
285
286
287
288 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Traditional recipe**(%%) =
289
290 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
291
292 Traditional recipe function is valid only when the LEVI project is converted to the PI project, and the original project uses the traditional recipe.
293
294 (% class="box infomessage" %)
295 (((
296 **✎Note**: Currently, only HMI+, i series, ie series, and ig series support the traditional recipe.
297 )))
298
299 == Simple recipe mode ==
300
301 Click the "Traditional Recipe" [[image:8-2TraditionalRecipe.png]] in the "Data tool" bar in the upper side of the software, and the following interface will pop up:
302
303 (% style="text-align:center" %)
304 [[image:8-3TraditionalRecipeConfigScreen.png||class="img-thumbnail"]]
305
306 **✎Note**:
307
308 * The recipe folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), ('').
309 * The element name of the recipe cannot include following 5 special characters: " **,** " , " **|** " , " **<** " , " **>** " , " **&** " .
310
311 == Recipe display ==
312
313 Select the file type "Traditional recipe file" in object "Recipe Display", and it is recommended to fill in the traditional recipe group number HSW1612 to the address of select line.
314
315 (% class="box infomessage" %)
316 (((
317 **✎Note**: The Recipe Display can display up to 50 groups of 100 elements by default, which can be to display out of range by enabled "Address Control". After the "Address Control" is enabled, the display group number can be reached to 100. If want to display more than 100, please adjust the "Start Group" from "Address Control" to index the display group, as following shown:
318 )))
319
320 (% style="text-align:center" %)
321 [[image:8-4TraditionalRecipeDisplayConfigScreen.png||class="img-thumbnail"]]
322
323 == Recipe transmission address ==
324
325 The special addresses used in the Recipe are shown in the following table:
326
327 (% class="table-bordered" %)
328 |=Address|=Description|=Function
329 |HSW1611|Traditional Recipe transfer operation.|(((
330 ~=1: Recipe download.
331
332 ~=2: Recipe upload.
333 )))
334 |HSW1612|Traditional Recipe group number.|Traditional Recipe group number.
335 |(((
336 HSW242
337 )))|(((
338 Recipe operation result prompt:
339
340 Upload: Data is written to recipe file from address.
341
342 Download: Data is written to the address from recipe file.
343 )))|(((
344 ~=1: Recipe download, start.
345
346 ~=2: Recipe download, execution error.
347
348 ~=6: Recipe download, successful.
349
350 ~=7: Recipe upload, start.
351
352 ~=8: Recipe upload, execution error.
353
354 ~=11: Recipe group name does not exist.
355
356 ~=12: Recipe upload, successful.
357 )))
358
359 == **Recipe index** ==
360
361 The recipe index address RPW is mainly used for editing traditional recipes, and it is more convenient to modify the data and display of recipes. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
362
363 The recipe index area (RPW)'s instruction as follows:
364
365 1. RPW~*~*~#~#~#~#, a total of six digits, the first two ~*~* represent the Recipe group number, ~#~#~#~# represents the element order number. For example, RPW010000 indicates the 1st element of the Recipe group No.1, and RPW110002 indicates the 3rd element of the Recipe group No.11.
366 1. If the indexed group number or element number does not exist, the value of RPW defaults to zero. For example, RPW110011 represents the 12th element of the Recipe group No.11. If it does not exist, the value returned by accessing RPW110011 is zero. The value written in RPW110011 will not be saved to the recipe file.
367
368 * **✎Note**: As long as RPW~*~*~#~#~#~# exists, any object "writes" to HPW~*~*~#~#~#~# will be saved to the recipe file. 
369
370 (% start="3" %)
371 1. The RPW register only supports word address access.
372 1. It can be known from the coding method of RPW~*~*~#~#~#~# that the range of RPW is from RPW000000-RPW990450, wherein the range of group number is 0-100, and the range of element is 0-450.
373
374 == Recipe example ==
375
376 The recipe index makes the modification and display of recipe data more convenient. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
377
378 Edit the recipe configuration, create three groups of recipes, 4 elements for per group: Red, green, blue, spraying time, as following shown:
379
380 (% style="text-align:center" %)
381 [[image:8-5TraditionalRecipeCaseConfig.png]]
382
383 RPW 0~~3 can display the data of group for the selected line. RPW10000~~10003, RPW20000~~20003, RPW30000~~30003 each address can display the single element. Directly modify the content of the RPW address and then modify the recipe data, as following shown:
384
385 (% style="text-align:center" %)
386 [[image:8-7TraditionalRecipeCaseShowNoOpera.png]]
387
388 After selecting the 2nd group, trigger the download button to download the whole group data to the corresponding element address (For this case, the data will write into HDW0~~3), or trigger the upload button to upload the content of the element address to the specified recipe group.
389
390 (% style="text-align:center" %)
391 [[image:8-6TraditionalRecipeCaseShow.png]]
392
393 = **Trend chart** =
394
395 Trend chart function is used for displaying the real-time data in HMI as curve graph, which X axis represent as time, Y axis represent as data.
396
397 Click "Project" → "Trend chart", it will pop up the following screen. Click "Add" to creat new curve record.
398
399 (% style="text-align:center" %)
400 [[image:趋势图配置 001.png||class="img-thumbnail"]]
401
402 **Settings**
403
404 (% style="text-align:center" %)
405 [[image:趋势图设置 2.png||height="507" width="866"]]
406
407 **(1) Basic settings**
408
409 1. **Curve NO.: **It is for setting curve number,
410 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
411 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
412 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
413
414 **(2) Sample Type**
415
416 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
417 1. **Sample unit:** 100ms.
418
419 **(3) Quick Setting**
420
421 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
422
423 (% style="text-align:center" %)
424 [[image:趋势图设置 3.png||class="img-thumbnail"]]
425
426 (% start="2" %)
427 1. **Sample address: **Fill in the start address that read the device data. If the sampl address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
428
429 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
430
431 (% class="box infomessage" %)
432 (((
433 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
434 )))
435
436 **Trend Chart Demo Download Link**
437
438 [[https:~~/~~/drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC>>url:https://drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC]]
439
440 = **History XY plot** =
441
442 Different from TrendChart, uses need to set history XY curve items in project. Please click "Project"-> "History XY Plot" to open the setting screen.
443
444 Recipe function settings will be display in "[[History XY Plot>>path:https://docs.we-con.com.cn/bin/view/PIStudio/08.Basic%20Function/#HHistoryXYplot]]" object.
445
446 (% style="text-align:center" %)
447 [[image:历史XY 2.png||class="img-thumbnail"]]
448
449 (% style="text-align:center" %)
450 [[image:历史XY 3.png||class="img-thumbnail"]]
451
452 **(1) Basic settings**
453
454 1. **Curve NO.: **It is for setting curve number,
455 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
456 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
457 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
458
459 **(2) Sample Type**
460
461 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
462 1. **Sample unit:** 100ms.
463
464 **(3) Quick Setting**
465
466 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
467
468 (% style="text-align:center" %)
469 [[image:image-20220616145435-1.png]]
470
471 (% start="2" %)
472 1. **Sample address: **Fill in the start address that read the device data. If the sample address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
473
474 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
475
476 (% class="box infomessage" %)
477 (((
478 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
479 )))
480
481 **Operating Procedure**
482
483 * Click "Project" → "History XY Plot" to open the function selecting windows.
484
485 (% style="text-align:center" %)
486 [[image:8.Basic Function_html_5da6ca44bd28acbe.png||height="144" width="533" class="img-thumbnail"]]
487
488 * Click "Add" button to open "History XY Plot” setting windows.
489
490 (% style="text-align:center" %)
491 [[image:8.Basic Function_html_6345b50ea55168fa.png||height="307" width="554" class="img-thumbnail"]]
492
493 * Setting the function of History XY Plot.
494 * Click "OK" to save the setting.
495
496 **Download Link**
497
498 [[https:~~/~~/drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r>>url:https://drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r]]
499
500 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Data record**(%%) =
501
502 The data record function is organized according to the structure below. In a project, there can be multiple record groups, each record group containing multiple channels. Different groups have different sampling times.
503
504 The topology is shown in the following figure.
505
506 (% style="text-align:center" %)
507 [[image:8.Basic Function_html_1b4bd09dafa7e049.png||height="332" width="554" class="img-thumbnail"]]
508
509 The data record stored in SD card is also organized according to the above figure.
510
511 The sample time and save time is consistent in the same record group. There are multiple channels in the group, When the sampling time is up, every channel would collect data to PLC register according to its own address.
512
513 **Sampling interval: **The interval between two consecutive samples was recorded.
514
515 As long as the project uses the data record function and supports the large-capacity storage module, the system will sample data according to the set sampling interval and save data according to the set saving interval.
516
517 For the file storage of data, see the file size configuration during data record configuration.
518
519 ✎**Note: **
520
521 After enable the Cloud and check the box of Upload to Cloud, the communication port settings of the address in the imported Data record configuration must be the same as the communication port settings of the current project, otherwise it cannot be used normally.
522
523 The number of Data records upload to Cloud shall not exceed the limit value, or the sum of the imported Data records and the number of existing alarm records shall not exceed the limit value. the specific limitation as following table:
524
525 (% style="margin-left:auto; margin-right:auto; width:513px" %)
526 |=(% style="width: 70px;" %)Series|=(% style="width: 442px;" %)Number of Data Record upload to Cloud
527 |(% style="width:70px" %)8000-R|(% style="text-align:center; width:442px" %)100
528 |(% style="width:70px" %)9000-R|(% style="text-align:center; width:442px" %)100
529 |(% style="width:70px" %)3000ig|(% style="text-align:center; width:442px" %)50
530 |(% style="width:70px" %)8000ig|(% style="text-align:center; width:442px" %)100
531
532 The record group name can only be composed of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_'), ('') and other non-English characters.
533
534 Channel name cannot incloud following symbols: :" , ", " | ", " < ", " > ", " & ".
535
536 (% class="wikigeneratedid" id="HSettings" %)
537 **Settings**
538
539 (% style="text-align:center" %)
540 [[image:数据记录设置 1.png||height="533" width="848" class="img-thumbnail"]]
541
542 **Operating Procedures**
543
544 1. Click "Project"->"Data record" as below shows.
545 1. Click "Add" button to open "Data record" setting window.
546 1. Enter group name, the default is "GroupName0"
547 1. Select "Trigger function" mode, such as "No trigger".
548 1. Set "Total channels", such as 3.
549 1. Click "Apply" button.
550 1. Set Sample cycle, such as 15.
551 1. Set "Start channel" in "Quick settings", such as 4 0.
552 1. Check group information in "Channel list" as below.
553 1. Click "Save" button to complete settings.
554
555 The figure above display the group of current project. The data record file would stored in "DataLogFile" folder, and the data of every  group would have a data file. The file suffix is in "db" format.
556
557 ✎**Note: **
558
559 * For HMI series 8000 and above, the size of a single file cannot exceed 300M and the total file capacity cannot exceed 1000M.
560 * For HMI series 3000, the size of a single file cannot exceed 4M and the total file capacity cannot exceed 10M.
561 * If the total amount exceeds the range, an alarm will be given during project compilation.
562
563 (% style="text-align:center" %)
564 [[image:数据记录设置 2.png||height="572" width="850" class="img-thumbnail"]]
565
566 **(1) Group name:** Set group name, and he name should be unique.
567
568 **(2) Trigger function:** There are four modes to trigger record.
569
570 1. **No trigger: **Data will be recorded in every sample time.
571 1. **Trigger to record by sample cycle: **Data will be recorded in every same time, when trigger control bit set ON.
572 1. **Trigger to record once and reset: **Data will be recorded when trigger control bit set ON, and the bit will be reset automatically.
573 1. **Trigger to record once: **Data will be recorded when trigger control bit set ON, and the bit need to be reset manually.
574 1. **Trigger address: **It is only valid when the trigger condition is selected. The monitoring cycle for trigger sampling address is 1s.
575
576 **(3) Total channels (1~~100): **Set the numbers of channels. Click "apply" to view the channel lists on the right record channel.
577
578 **(4) Sampling cycle: **If you check "collect control address", the sampling interval is the value of the address. The unit is second. For example, Sample cycle=15s. It means that records data one time every 15s.
579
580 **Timing address:** It sets address to change sample time when HMI is running;
581
582 **(5) Total records:** It sets data record number in one data record file. If the data file size is beyond the current file size. The old data will be deleted, and the new data will replace the old data. Please remember to back up the old data record file.
583
584 **Abnormal value:** It sets a value, when communication fails, data record will record this value;
585
586 **(6) Upload to Cloud**: The data uploaded by Data Record is stored in the Cloud(Only ig series). The maximum number of record is 20.
587
588 **(7) Quick Settings**
589
590 1. **Start Channel:** It sets the continuous addresses for channels.
591 1. **Data Format: **It sets the same data format for channels.
592 1. **Number of Digits:** It sets the digits’ number for channels.
593 1. **Language Settings**: The text in HMI can be in 8 languages, user can set language in here.
594
595 **(8) Channel List**: Besides quick settings, user can set channel name, address, data format, and so on one by one according to real situation.
596
597 **✎Note:**
598
599 * After enabling the Cloud function and checking the upload to the Cloud, the communication port settings of the address in the imported Data record configuration must be the same as the communication settings of the current project, otherwise it cannot be used normally.
600 * The range of upload to the Cloud from Data record configuration must not exceed 50, or the total number of imported Data records and the number of currently existing Data records must not exceed 50. If it exceeds, it will prompt you to reconfigure, should reduce the number.
601 * The channel name can only be composed of English characters, (0~~9), (a~~z), (A~~Z), ('_'), ('').
602 * The channel name does not include these 5 special characters: ", ", "| "," <", "> "," & ".
603 * The data would be overwritten automatically if the capacity exceed the maximum capacity. For 8000/9000 series, the size of single file cannot exceed 300MB, and total capacity of data records cannot exceed 1000MB. For 3000/3000i/3000ie series, the size of single file cannot exceed 4MB, and total capacity of data records cannot exceed 10MB. If the total amount exceeds the range , an error will be prompted when the project is compiled.
604
605 You could click here to jump to object "[[Data Record Display>>https://docs.we-con.com.cn/bin/view/PIStudio/06.Objects/#HDatarecorddisplay]]"
606
607 = **User permission** =
608
609 **Introduction**
610
611 1. User permission is one of expansion function in PI Series HMI; it provides multi-level of permission for control HMI operations.
612 1. User need to set the user and group during designing project. Different groups have different permission levels for accessing. Each user should be added into the specified group; it is possible to add the same user into different groups.
613 1. Operating record: it records user operations information, the records files are saved in HMI flash; its path is [~\~\flash~\~\UserOperationLogs.db].
614 1. When it is on simulator mode, the files are saved in C disk, its path is [C:~\~\WECON\UserMgrFile\UserOperationLogs.db].
615
616 (% class="box infomessage" %)
617 (((
618 ✎**Note: **The user name and password must be unique.
619 )))
620
621 == Settings ==
622
623 Open PIStudio software, then operate as the following figure.
624
625 (% style="text-align:center" %)
626 [[image:用户权限 1.png||class="img-thumbnail"]]
627
628 1. Click "User Permission" in "Data Tool" toolbar.
629 1. Edit user name, click "User0" cell under "UserName", and then enter the user name, one project allows maximum 20 users.
630 1. Edit password, click "User0" cell under "PassWord", and then enter the user name.
631 1. Edit description, click "User0" cell under "Desc", and then enter, description is not necessary。
632 1. Check the groups for each user, there are 11 groups beside admin.
633 1. Editing groups' description, but it is not necessary.
634 1. {{id name="OLE_LINK7"/}}{{id name="OLE_LINK6"/}}Click "Save and Exit" button to complete all settings.
635
636 ✎**Note:**
637
638 * Only a maximum of one administrator permission is allowed in a profile with one user permission. If you want to use "Funtion address" to modify the user permission, you must log in the administrator account to operate.
639 * When the configured file does not have the administrator account, a new user can be added  through "Funtion address" and set as the administrator.
640 * If you select hidden fucntion when configuring user account, the account would display as "~*~*~*~*~*~*" in the list. You only need to enter the password of the corresponding hidden user to log in.
641
642 == Object permission configuration ==
643
644 (% style="text-align:center" %)
645 [[image:用户权限 2.png||class="img-thumbnail"]]
646
647 **Operation Procedure of Object Permission**
648
649 1. Open the object setting windows;
650 1. Select "Security" windows;
651 1. Check the "User Permission";
652 1. Select "Level" to set permission level;
653 1. Enter "Log Message", it is for operation records, if it was empty, the operation for this object would be not be recorded;
654 1. Select the "Access Denied Setting" mode;
655
656 **Log information description**
657
658 A combination of Chinese characters, numbers, and uppercase and lowercase letters can be entered, and the number does not exceed 63.
659
660 The format of insert variable:{variable address, data format}. e.g., {HDW100,UW2.1}.
661
662 The data format are as follows.
663
664 (% class="table-bordered" %)
665 |=Letter|=Meaning
666 |B|Binary
667 |O|Octonary
668 |U|Unsigned decimal
669 |H|Hexadecimal
670 |b|BCD
671 |F|32-bit float
672 |S|Signed decimal
673 |C|Character
674 |W|Single word
675 |D|Double word
676
677 Examples.
678
679 * Unsigned decimal, BCD, 32-bit float and Signed decimal are as follows.
680
681 {HDW100,UW2.1}:  Indicates the variable address is HDW100. The data format are: unsigned decimal, single word, two integer bits, one decimal place.
682
683 * (((
684 Binary, Octonary and Hexadecimal are as follows.
685 )))
686
687 {HDW100,HD8}: Indicates the variable address is HDW100. The data format are: hexadecimal, double word, eight integer bits.
688
689 * (((
690 Character is as follows.
691 )))
692
693 {HDW100,C32}: Indicates the variable address is HDW100. The data format are: 32 characters.
694
695 When a record is generated, the contents of this variable are replaced by the value of your corresponding address.
696
697 == **Function address** ==
698
699 A user must first log in before performing an operation, and after the login is successful, the user can perform the required operation, and log out after completing the operation, making the operation permission invalid. User login, log out, modification of user password during operation and user management and other functions need to be configured.
700
701 HMI allows managing user accounts on screen. Including adding, deleting and editing the user account. HMI provide built-in screen for [Sign in] and [change password] (screen No. 1006 and 1007).
702
703 Functions and addresses are as follows.
704
705 (% class="table-bordered" %)
706 |=**Function**|=**Address**|=**Object type**|=**Address function**
707 |(% rowspan="3" %)Sign in|HUW1158~~1335|Drop down list|User name
708 |HUW1002|Character input object|Password
709 |HUW1000|Word Switch (Input 1)|OK (sign in)
710 |(% rowspan="5" %)Change password|HUW1158~~1335|Drop down list|User name
711 |HUW1002|Character input object|Old password
712 |HUW1006|Character input object|New password
713 |HUW1010|Character input object|Confirm password
714 |HUW1000|Word Switch (Input 2)|OK(change password)
715 |Sign out|HUW1000|Word Switch (Input 3) |Sign out
716 |(% rowspan="7" %)(((
717 New user ***1**
718 )))|HUW1014|Character input object|User name
719 |HUW1006|Character input object|password
720 |HUW1010|Character input object|Confirm password
721 |HUW1000|Word Switch (Input 4) |OK(add new user)
722 |HUW1336~~1345|Character input object|User description
723 |HUX1347.0|Bit switch|(((
724 ~=1: User hidden
725
726 ~=0: Visible (Defaults)
727 )))
728 |HUW1000|Word Switch (Input 8) |Save(add Hide features)
729 |(% rowspan="2" %)(((
730 Delete user ***2**
731 )))|HUW1158~~1335|Drop down list|User name
732 |HUW1000|Word Switch (Input 5)|OK (delete user)
733 |Delete Profile|HUW1000|Word Switch (Input 9)|OK(delete)
734 |Export Profile|HUW1000|Word Switch (Input 10)|OK(export)
735 |Import profile|HUW1000|Word Switch (Input 11)|OK(import)
736 |Export log file|HUW1000|Word Switch (Input 12)|OK(export)
737 |Delete log file|HUW1000|Word Switch (Input 13)|OK (delete)
738 |Current user name|HUW1349|Character object|32 Word
739 |System state information|HUW1030|Character input object|System state information
740 |(% rowspan="3" %)Permission settings|HUW1014|Character input object|User name
741 |HUW1348|Bit switch|(((
742 Set the user group:
743
744 HUX1348.0 = 1 administrator;
745
746 HUX1348.1 = 1 group 0 permission;
747
748 HUX1348.2 = 1 group 1 permission;
749
750 (Total group 0 - group 10)
751 )))
752 |HUW1000|Word Switch (Input 6)|Add user rights (set according to HUW1348)
753 |User login mode setting|HUW1382|Word Switch/Numeric input object|(((
754 0: Select a user name from the drop-down list
755
756 1: Use character input object (address HUW1014) to log in with a user name
757 )))
758
759 When the user performs a function operation, the operation result is displayed in the HUW1001.
760
761 (% class="table-bordered" %)
762 |=**Value (HUW1001)**|=**Meaning**
763 |1|Insufficient permissions.
764 |2|Username does not exist.
765 |3|Username already exists.
766 |4|Wrong username or password.
767 |5|Login successfully.
768 |6|Passwords are inconsistent in twice time.
769 |7|Password changed successfully.
770 |8|User added successfully.
771 |9|User deleted successfully.
772 |10|Maximum number of users exceeded.
773 |11|Admin user already exists.
774 |12|User permission modified successfully.
775 |13|File imported successfully.
776 |14|File imported failed.
777 |15|File exported successfully.
778 |16|File exported failed.
779 |17|Logout successfully.
780 |18|Profile deleted successfully.
781 |19|Log file deleted successfully.
782 |20|Hide settings modified successfully.
783 |21|Hide settings modified failed.
784 |22|(((
785 Password already occupied, please reset.
786
787 (For both username and password, it can not repetition)
788 )))
789
790 **✎Note:**
791
792 * *1: If there is an admin user account, then the new user can no longer add one more admin, that is, one project can only have one administrator account.
793 * *1: When adding new user, the password could not be duplicated with other users.
794 * *2: When deleting user, it is forbidden to delete the admin user.
795
796 **User Permission Demo Download**
797
798 [[https:~~/~~/drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq>>url:https://drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq]]
799
800 = Message prompt =
801
802 A message box is a window used to show some prompts or warnings to users. For example, the application process a task in the process of pop-up message box, suggesting that "U disk has been detected", then the customer can carry out data dump function.
803
804 (% style="text-align:center" %)
805 [[image:消息提示 2.png||class="img-thumbnail"]]
806
807 (% style="text-align:center" %)
808 [[image:8.Basic Function_html_5ce2091d6f7cd732.png||height="515" width="704" class="img-thumbnail"]]
809
810 **(1) Message**
811
812 It includes system classes (u disk, SD card, and others), chart classes (alarm, data record, recipe, file list), curve classes (Trend Chart, historical XY trend Plot).
813
814 **(2) Control**
815
816 1. **Current item: **It shows selected message information.
817 1. **Use trigger address: **When the message is triggered, the trigger address would be set ON.
818
819 **For Example:**
820
821 Trigger address is 011, during inserting a USB flash disk into HMI, and 011 would be set ON, once HMI recognizes USB flash disk, and display message.
822
823 1. **Show message: **Check it to display message when HMI is running. It is checked by default.
824 1. **Show on web: **Check it to display message when remote access HMI screen, it is unchecked by default.
825
826 **(3) Message Content**
827
828 Each message has default content, but you could set different content according to the actual situation. And the same message could be displayed in 8 languages.
829
830 **(4) Reload Text: **It means discard changes.
831
832 **For Example**
833
834 User deletes default content or modifies default content, but he wants to give up modification back to original, just click "Reload text".
835
836 **✎Note:**
837
838 * If you do not want this prompt during the running of HMI, please uncheck "Show message".
839 * "Reload text" function would be invalid after clicking "save".
840 * These 5 special characters are not supported in the header Multi language settings: ",", "|", "<", ">", "&".
841
842 = **Cloud** =
843
844 **Introduction**
845
846 Cloud function is available for following models: the ig series and 8000/9000 series with -R after system upgrade
847
848 You may configure the basic settings of Cloud functions, tags, and User MQTT according to your needs. (If the device supports the Cloud function, you can use the function and configure the tags after checking the box to enable it, or upload the data to the 3rd party server.)
849
850 Click "Project"-"[[image:hh_B4H5OuNT87.png||height="29" width="30"]]Cloud" in the upper left corner of the software, as shown in the following figure.
851
852 (% style="text-align:center" %)
853 [[image:云配置1.png||height="494" width="750" class="img-thumbnail"]]
854
855 **(1) Enable**
856
857 If the HMI supports the Cloud function, check it to enable the Cloud function, and it will collect the real-time data from HMI upload to the Cloud. The number of data collection is limited, and the specific parameters are as follows:
858
859 |=Series|=Monitoring Tags|=Alarm Record|=Data Record|=OpenCloud Data
860 |8000-R|300|200|100|1000
861 |9000-R|300|200|100|1000
862 |3000ig|100|20|50|500
863 |8000ig|300|200|100|1000
864
865 For example:
866
867 * In 3000ig's Cloud, the monitoring tags upload to the Cloud in real time is limited to 100.
868 * For 3000ig's Alarm, the Alarm records of word alarms and bit alarms upload to Cloud is limited to 20. (See [["Alarm">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HAlarm]] for details).
869 * For 3000ig's Data record, the Data records upload to Cloud is limited to 50. (For details, please refer to [["Data Record">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HDataRecord]]).
870
871 **(2) Server Selection**
872
873 **Server**: China, ASEAN, and Europe.
874
875 **Password**:
876
877 1. If the HMI is not bound, this access password will be updated and downloaded into the HMI screen simultaneously.
878 1. If the HMI is bound, this access password in the project cannot effectively change the binding password of the device, and it can only be changed through V-NET.
879
880 **(3) Upload Selection**: 
881
882 To upload the data collected by HMI to the cloud or a to the third-party server, only one upload method can be selected.
883
884 1. **to Cloud**: All the configured tags, data records, and alarm records would be pushed to V-NET.
885 1. **to User MQTT**: All the configured tags, data records, and alarm records would be pushed to to the third-party server, and the relevant Lua function calls please refer to "[[Cloud interface>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/10.Lua/#HCloudInterface]]".
886
887 After the "to User MQTT" is checked. The tags, data records, and alarms cannot be viewed on V-NET, but the device can be bound to V-NET and remote monitoring the device screen normally.
888
889 **4) Low Data Mode setting**