Wiki source code of 06 Data Tool

Version 29.1 by Karen on 2023/06/07 09:30

Show last authors
1 (% class="wikigeneratedid" id="H8BasicFunction" %)
2 This chapter provides information about basic functions and configuration in PIStudio.
3
4 = **Alarm** =
5
6 == Bit alarm ==
7
8 Click "Project"→"Bit Alarm", it is displayed as the following figure.
9
10 (% style="text-align:center" %)
11 [[image:位报警 1.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
12
13 **Group No.: **Group number of Bit alarm. The name is unique and cannot be duplicated.
14
15 **Bit Address: **Bit address of alarm monitoring
16
17 * **Record bit alarm by default:**  Whether to record the alarm history data of bit alarm, if checked, it will be saved in the designated storage location.
18 * **Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
19
20 **Upload to Cloud: **The data upload by "bit alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
21
22 **✎Note:**
23
24 * After enable the Cloud and check the box of Upload to Cloud, the communication port settings of the address in the imported Bit Alarm record configuration must be the same as the communication port settings of the current project, otherwise it cannot be used normally.
25 * The number of Alarm records upload to Cloud shall not exceed the limit value, or the sum of the imported alarm records and the number of existing alarm records shall not exceed the limit value. the specific limitation as following table:
26
27 (% style="margin-left:auto; margin-right:auto; width:358px" %)
28 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
29 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
30 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
31 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
32 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
33
34 **Alarm Condition:** It sets alarm trigger condition, there are two types: alarm when ON and alarm when OFF.
35
36 **Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
37
38 **Beep when alarm ON: **The beep works when the alarm is triggered. If "beep once" is checked, bit address alarm only beep once and stop.
39
40 **Content: **It is used for setting alarm content (command).
41
42 **Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
43
44 * **Position: **The location of the screen alarm display.
45 * **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
46 * **Pop-up once: **Pop up alarm screen once, and the screen would not pop up again
47 * **Close window when alarm off: **Automatically close the alarm screen when alarm off.
48
49 **✎Note:**
50
51 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported bit alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
52 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
53
54 **Operating Procedures of Adding One Alarm**
55
56 * Click "Project"→"Bit Alarm" as below shows.
57
58 (% style="text-align:center" %)
59 [[image:8.Basic Function_html_5f8da20315334bac.png||data-xwiki-image-style-alignment="center" height="144" width="539" class="img-thumbnail"]]
60
61 * Click "Add" button to open "Bit Alarm" setting window.
62
63 (% style="text-align:center" %)
64 [[image:8.Basic Function_html_94a019683b506e15.png||data-xwiki-image-style-alignment="center" height="307" width="554" class="img-thumbnail"]]
65
66 * Set "Bit Address".
67 * Set "Alarm Condition".
68 * Set "Content".
69 * Other settings can be set according to the actual situation".
70 * Click "OK" button to complete settings.
71
72 == Word alarm ==
73
74 Word alarm is to monitor the word address of a device. If the data meets the set conditions, an alarm will be generated.
75
76 Click "Project"→"Word alarm", it is displayed as the following figure.
77
78 (% style="text-align:center" %)
79 [[image:字报警 1.png||class="img-thumbnail"]]
80
81 **Alarm Name:** You can set alarm name for it. Alarm Name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters.
82
83 **Alarm Address: **It is used for setting word address for word alarm, such as HDW0.
84
85 **Data Format: **16-bit unsigned decimal, 16-bit signed decimal, 16-bit BCD, 32-bit unsigned decimal, 32-bit signed decimal, 32-bit BCD, 32-bit float.
86
87 **Group No.: **Group number of word alarm. The name is unique and cannot be duplicated.
88
89 **Upload to Cloud: **The data upload by "word alarm" is stored in the Cloud and it is alarm data. (Only ig series and 8000/9000 series with -R after system upgrade are supported)
90
91 **✎Note:**
92
93 * If the "cloud" function is enabled and "upload to cloud" is checked, the communication port of the address in the configuration of the imported word alarm record must be the same as that of the current project; otherwise, it cannot be used normally.
94 * The number of alarm configuration points reported to the cloud cannot exceed 20, or the sum of imported alarm records and the current alarm records cannot exceed 20. If it exceeds, please reconfigure.
95
96 (% style="margin-left:auto; margin-right:auto; width:358px" %)
97 |=(% style="width: 79px;" %)Series|=(% style="width: 276px;" %)Number of Alarm upload to Cloud
98 |(% style="width:79px" %)8000-R|(% style="text-align:center; width:276px" %)200
99 |(% style="width:79px" %)9000-R|(% style="text-align:center; width:276px" %)200
100 |(% style="width:79px" %)3000ig|(% style="text-align:center; width:276px" %)20
101 |(% style="width:79px" %)8000ig|(% style="text-align:center; width:276px" %)200
102
103 **Record alarm:**  Whether to record the alarm history data of word alarm, if checked, it will be saved in the designated storage location.
104
105 **Not save alarm OFF:** If checked, after the alarm is dismissed, the corresponding alarm records will be deleted from the log file.
106
107 **Alarm Condition**: Alarm is triggered when designated address meets the alarm condition, it provides four conditions;
108
109 1. **High alarm:** Alarm is triggered when it reaches high limit. It can be a constant or a variable
110 1. **Low alarm:** Alarm is triggered when it reaches low limit. It can be a constant or a variable
111 1. **Range alarm:** Alarm is triggered when it exceeds the range. It can be a constant or a variable
112 1. **Equivalent alarm: **Alarm is triggered when the value equals to the given data. It can be a constant or a variable
113
114 **Alarm Info: **It is used for setting alarm content (command);
115
116 **Alert: **It is used to mark whether the alarm has occurred. if an alarm occurs, the address of "control bit" will be written to 1. If "clear alert when alarm OFF" is checked, the address of "control bit" will be written to 0.
117
118 **Alarm Screen: **Pop-up alarm screen (it need to be sub-screen);
119
120 1. **Position: **The location of the screen alarm display.
121 1. **Pop-up Interval: **The time of reopen the alarm screen when alarm screen closed.
122 1. **Pop-up once: **Pop up alarm screen once.
123 1. **Close window when alarm off: **Automatically close the alarm screen when alarm off.
124
125 **Beep when alarm ON: **beep works when the alarm is triggered, in the default mode, the beep works until the alarm is released.
126
127 **Beep once:** Beep works once, when alarm is triggered.
128
129 **Alarm List**
130
131 It displays all the word alarm lists; it will show the alarm information;
132
133 **Operating Procedures of Adding One Alarm**
134
135 * Click "Project"→ "Word Alarm" as below shows.
136
137 (% style="text-align:center" %)
138 [[image:8.Basic Function_html_1b59522c984cd7c2.png||height="144" width="492" class="img-thumbnail"]]
139
140 * Click "AddClick" button to open "Word Alarm" setting window.
141
142 (% style="text-align:center" %)
143 [[image:8.Basic Function_html_942107c81fc6901c.png||height="307" width="554" class="img-thumbnail"]]
144
145 * Set Basic information of word alarm.
146 * Set "Content".
147 * Other settings can be set according to the actual situation.
148 * Click "OK" button to complete settings.
149
150 **HMI Alarm Demo Download Link**
151
152 [[https:~~/~~/drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP>>url:https://drive.google.com/open?id=1Llq03CMISM_1mMIfU308hxFbs4rGdQGP]]
153
154 = **Recipe** =
155
156 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
157
158 Data operation
159
160 1. **Read:** Read a group of data from the recipe file and assign the group of data to the set address.
161 1. **Write: **Read a group of data from the set address and assign the group of data to the corresponding recipe file.
162
163 PI Series HMI has Recipe function, Recipe function keeps data in the HMI, used to download the data from HMI to designated device addresses, or upload the data from device addresses to HMI.
164
165 The maximum number of group in recipe is 1000, and the maximum number of member in each group is 1500.
166
167 Recipe could store the data in USB flash disk and SD card and view the recipe data by object "Recipe display". It has two mode: simple mode and advanced mode.
168
169 1. **Simple: **Only support the data operation of one recipe file, including read and write.
170 1. **Advanced:** Support the data operation of multiple recipe files, including read, write, insert and index. View and select recipe file by object "File list".
171
172 Recipe function settings will be display in "[[Recipe display>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/06.Objects/#HRecipedisplay]]" object.
173
174 **Description**
175
176 (% style="text-align:center" %)
177 [[image:8-1Recipe.png]]
178
179 **Basic**
180
181 * **Recipe Folder:** Give Recipe folder name (It can be used, when setting Recipe display object);
182 ** **✎Note: **Recipe Folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), (' ') and other non-English characters;
183 * **Group: **Set the recipe group number, the number of elements, the data format. The data format has 8 modes: 16-bit signed decimal, 16-bit unsigned decimal, 16-bit BCD, 32-bit signed decimal, 32-bit unsigned decimal, 16-bit BCD, 32-bit floating point number, 64-bit (double-precision) floating-point number, string, and the choice of data integer and decimal places.
184 * **Elements:** It sets members' initial number of each group;
185 * **Data Format:** There are some formats can be supported in Recipe, like 16-bit BCD, 16-bit signed, 16-bit unsigned, 32-bit BCD, 32-bit signed, 32-bit unsigned, 32-bit floating and string. If each member requires different formats, please set it one by one in form;
186 * **Decimal: **It sets integer and scale digits;
187
188 **Mode Selection: **Select Simple or Advanced mode. Recipe file is divided into simple mode and advanced mode. Only in advanced mode can exist multiple recipe files used at the same time. (used wiht file list onject), Simple mode can only support a recipe file; Aadvanced mode can insert group information and reordered.
189
190 Function address: all operations are done through function addresses, different operating value is as follows:
191
192 * = 0: no operation;
193 * = 1: trigger read data;
194 * = 2: new trigger or update (If there is group number, it updates.)
195 * = 4: insert (only valid in advanced mode)
196 * = 8: delete (Delete according to the writing group number. If write and read address are consistent, refer to the reading group number);
197 * = 16: delete and sorted ((Delete according to the writing group number. If write and read address are consistent, refer to the reading group number)
198 * = 64: import CSV recipe file.
199
200 **Use Multiple File**
201
202 Check it to use more than one recipe file in HMI, but this option only valid in [Advanced mode];
203
204 **Select language**
205
206 The text in HMI can be in 8 languages, user can set language in here;
207
208 **Address**
209
210 1. **Group:** This address is for selecting group number;
211 1. **Start: **This is starting address is for reading and writing in recipe, PIStudio will automatically assigns addresses for each members;
212 1. **File(16 words): **This address only available when enable the Use Multiple File. This setting address is for input the recipe file's filename.
213
214 **Use Index**
215
216 If the value from Group address is changed, Read address will display the new data according to new group number immediately. Relatively, if the data of write address is changed, the corresponding group from table is also changed.
217
218 **Query by Element**
219
220 Enable it for querying group by specify element, select a primary key from all the elements, except the group number. This element value from all groups must be unique if want to set as primary key;
221
222 (% class="box infomessage" %)
223 (((
224 **✎Note: **When this option is enabled, Group address will be invalid.
225 )))
226
227 **Use Independent Write Address**
228
229 To separate Recipe read address and write address.
230
231 **Use Insert**
232
233 It inserts data into the specified group, if the specified group already exists, it would not cover the original data, while it will move the original group next one after it.
234
235 **Discontinuous Address**
236
237 Whether enable the non-consecutive recipe operation addresses or not. If disabled, the recipe address will recover as the continuous addresses.
238
239 (% class="box infomessage" %)
240 (((
241 **✎Note: **This function only supported in HMI+, i series, ie series, ig series.
242 )))
243
244
245 **description of Adcanced mode**
246
247 According to the recipe configuration information in Figure 2 above. The function address is HDW70, and each function configuration corresponds to the group number address, recipe element address and recipe file name address. The recipe information configured in figure 2 can be displayed in the table in figure 3 with the "Record Display" object.
248
249 [[image:image-20220806111333-1.jpeg]]
250
251 **Read recipe**: Input 1 to the file name, when the group number addresses HDW100=1 and HDW70=1 (read), the element data of the first group (ID=1) is written to the recipe address from the recipe file. As shown in Figure 3 above: HDW105=1, HHDW106=2, HDW107=3, HDW108=4, HDW109=5.
252
253 **Write recipe**: Input 1 to the file name, when the group number addresses HDW101=4 and HDW70=2 (write), the data will be read from the recipe address and written to the corresponding group of the recipe file. As shown in figure 3 above: HDW110=20, HHDW111=21, HDW112=22, HDW113=23, HDW114=24. Write the data of this set to the elements of ID=4 in the recipe table (if there is no data of Group 4 in the recipe file, a new set of data will be added; If there is data of Group 4 in the original recipe, the original data will be overwritten and the latest data will be displayed in the recipe file).
254
255 **Index recipe**: When the file name is input 1, when the group number address HDW102=3, the data of ID=3 (Group 3) in the recipe file will be directly displayed in the component address of the index, that is, HDW115=11, HHDW116=12, HDW117=13, HDW118=14 and HDW119=15. If the data of the index component address is modified, the modified data will be automatically filled into the table of the recipe file, that is, the data of the recipe file will be automatically updated after the data is modified.
256
257 [[image:image-20220806111355-2.jpeg]]
258
259 **Insert recipe**: Input 1 to the file name, when the group number addresses HDW103=3 and HDW70=4 (insert), the data of the 3rd group will be inserted, but the data of the third group already exists in the original recipe file (see Figure 3 above), then the original data will be moved down by one group, that is, the original 3rd group will become the 4th group, and so on, and HDW120=16, HHDW121=17, HDW122=18, HDW123=19 and HDW124=20 will be written into the new 3rd group of the recipe file at the same time. The results are shown in Figure 4 above.
260
261 When the group number address HDW101=2 (**The delete function only works on the group number of the write function**), HDW70=8 (delete), the data in the recipe file with ID=2 (Group 2) will be deleted.
262
263 When the group number address HDW101=5 (**The delete function only works on the group number of the write function**), HDW70=16 (delete and sort), the data of ID=5 (Group 5) in the recipe file will be deleted, and the original ID=6 (Group 6) data will be reordered to become the new Group 5 data, the original ID=7 (Group 7) data will be reordered to become the new Group 6 data, and so on.
264
265 **Recipe Demo Download Link: **[[Download>>url:https://drive.google.com/open?id=1Cjbq_tW-NIirHFBpxt47g7IKvoYaWqUR]]
266
267 == Calling CSV recipe file ==
268
269 **Overview**
270
271 The recipe files used by the regular series HMI are in CSV format, and the recipe files used by the current series HMI are in database format. In order to be compatible with CSV format recipe files on the current series of HMI, please follow the instruction when using it.
272
273 **Operations**
274
275 Create the recipe as it is configured. The default recipe file name is “1. rcp2”, which is placed in folder 123, as shown in the following figure.
276
277 (% style="text-align:center" %)
278 (((
279 (% style="display:inline-block" %)
280 [[Figure 1>>image:image-20220806100702-2.jpeg]]
281 )))
282
283 2. Place a "Recipe Record Display" object and a "File List" object on the project screen for viewing the recipe files in the folder 123, and the address configuration in the object should be consistent with the above configuration.
284
285 (% style="text-align:center" %)
286 [[image:image-20220806100753-3.jpeg]]
287
288 By configuring the address in the table and combining the recipe function, the CSV recipe files of regular series are imported.
289
290 |=Address range|=Object type|=Address function
291 |HSW1050 to 1065|Text input object|Enter the CSV recipe file name to import
292 |HSW1066|Numerical input object|Import CSV file type:(((
293 * = 0: Custom CSV file (all data in the file is valid)
294 * = 1: Normal recipe file for regular series HMI (the data in line 1 of the file is invalid)
295 * = 2: Special recipe file for regular series HMI (the data in line 1 and 2 and column 1 of the file are invalid)
296 )))
297 |HSW1067|Numerical input object|(((
298 Where the CSV file is saved:
299
300 * = 0: In the CsvFile directory of U disk
301 * = 1: In the CsvFile directory of the SD card
302
303 **The path for offline simulation is: C:\ HMIEmulation\ CustomFileDir\ CsvFile**
304 )))
305 |HSW242|Numerical input object|Returns the results of the csv import:(((
306 * = 37: CSV file imported successfully
307 * = 38: CSV file import failed
308 )))
309
310 **Select CSV recipe file (take U disk as an example):**
311
312 Using the file list object, select the recipe file in the U disk by path, and configure the recipe file name address directly to the special address HSW1050 in the above table, which can directly detect the CSV file in the U disk; Select the recipe file in the file list, and write the selected recipe file name into the recipe file name: In HSW1050 to 1065.
313
314 Use the special address of the above table to configure the path of the CSV file: HSW106, configure recipe file name: HSW1050 to1065
315
316 Use HSW1066 address to select the corresponding CSV recipe file type.
317
318 * HSW1066 = 0: Import a user-defined CSV recipe file (all data in the custom CSV file must be valid);
319
320 (% style="text-align:center" %)
321 [[image:image-20220806101129-5.jpeg]]
322
323 * HSW1066=1: Import the normal recipe file of regular series HMI (the data in line 1 of the file is invalid);
324
325 The data in line 1 of the normal recipe file is used to define the format of the recipe and will not be imported into the recipe table as recipe information, **but you must ensure that the data in line 1 representing the elements and number of groups is correct, otherwise the CSV recipe file will fail to be imported.**
326
327 (% style="text-align:center" %)
328 [[image:image-20220806101520-6.jpeg]]
329
330 * HSW1066=2: Import the special recipe file of regular series HMI (the data in line 1, 2 and column 1 of the file are invalid);
331
332 In the special recipe file, line 1 is used to define the format of the recipe, line 2 is used to define the element name of the recipe, and column 1 is used to define the group name of the recipe, so lines 1, 2 and column 1 of the special recipe will not be imported into the recipe table as recipe information. **During use, ensure that the data such as the number of groups and elements representing the recipe format in the first line are correct, otherwise the import of the CSV recipe file will fail.**
333
334 (% style="text-align:center" %)
335 [[image:image-20220806102610-7.jpeg]]
336
337 **Perform import**
338
339 After configuring the saving path of CSV recipe file, the name of recipe file and the type of recipe according to the above steps, the method of transferring CSV file to DB file is as follows:
340
341 * Configure the DB recipe file name by text input object: HDW500 = 3 (recipe file configured in Figure 1),
342 * Set the recipe function address to: HDW1000 = 64 (the function address configured in Figure 1),
343 * Transform the CSV recipe file in U disk into DB recipe file with file name “3.rcp2”.
344
345 **DB recipe file for storing CSV data:**
346
347 Simple mode: When the recipe file is set to simple mode, the file of CSV data is saved as the DB recipe file of 1. rcp2 by default.
348
349 Advanced mode: When the recipe is enabled in advanced mode (multi-file recipe), the imported CSV file data is saved to the file recorded at the recipe file address HDW500 (the address configured in Figure 1).
350
351 **Import results:**
352
353 * HSW242 = 37: Import succeeded;
354 * HSW242 = 38: Import failed.
355
356 **Precautions:**
357
358 * Ensure that the data format of each element in the CSV file is the same as the recipe data format set in the software (DB), and ensure that the elements of each row in the valid data area is the same as the elements set in the software (DB);
359 * When the elements of a line in CSV file is more than the elements set in the software (DB), it will prompt the import failure;
360 * When the CSV file imported into the regular series HMI is a recipe file, the data representing the recipe format (elements, number of groups, whether it is a special recipe) in line 1 must be correct, otherwise the import of CSV file will fail.
361
362 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Traditional recipe**(%%) =
363
364 Traditional recipe is composed of multiple groups of information with the same structure and different data. Due to the similarity of these information, you could edit them into a set of recipes to facilitate the transfer of data between HMI and PLC.
365
366 Traditional recipe function is valid only when the LEVI project is converted to the PI project, and the original project uses the traditional recipe.
367
368 (% class="box infomessage" %)
369 (((
370 **✎Note**: Currently, only HMI+, i series, ie series, and ig series support the traditional recipe.
371 )))
372
373 == Simple recipe mode ==
374
375 Click the "Traditional Recipe" [[image:8-2TraditionalRecipe.png]] in the "Data tool" bar in the upper side of the software, and the following interface will pop up:
376
377 (% style="text-align:center" %)
378 [[image:8-3TraditionalRecipeConfigScreen.png||class="img-thumbnail"]]
379
380 **✎Note**:
381
382 * The recipe folder name can only consist of (0~~9), (a~~z), (A~~Z), ('_'), ('').
383 * The element name of the recipe cannot include following 5 special characters: " **,** " , " **|** " , " **<** " , " **>** " , " **&** " .
384
385 == Recipe display ==
386
387 Select the file type "Traditional recipe file" in object "Recipe Display", and it is recommended to fill in the traditional recipe group number HSW1612 to the address of select line.
388
389 (% class="box infomessage" %)
390 (((
391 **✎Note**: The Recipe Display can display up to 50 groups of 100 elements by default, which can be to display out of range by enabled "Address Control". After the "Address Control" is enabled, the display group number can be reached to 100. If want to display more than 100, please adjust the "Start Group" from "Address Control" to index the display group, as following shown:
392 )))
393
394 (% style="text-align:center" %)
395 [[image:8-4TraditionalRecipeDisplayConfigScreen.png||class="img-thumbnail"]]
396
397 == Recipe transmission address ==
398
399 The special addresses used in the Recipe are shown in the following table:
400
401 (% class="table-bordered" %)
402 |=Address|=Description|=Function
403 |HSW1611|Traditional Recipe transfer operation.|(((
404 ~=1: Recipe download.
405
406 ~=2: Recipe upload.
407 )))
408 |HSW1612|Traditional Recipe group number.|Traditional Recipe group number.
409 |(((
410 HSW242
411 )))|(((
412 Recipe operation result prompt:
413
414 Upload: Data is written to recipe file from address.
415
416 Download: Data is written to the address from recipe file.
417 )))|(((
418 ~=1: Recipe download, start.
419
420 ~=2: Recipe download, execution error.
421
422 ~=6: Recipe download, successful.
423
424 ~=7: Recipe upload, start.
425
426 ~=8: Recipe upload, execution error.
427
428 ~=11: Recipe group name does not exist.
429
430 ~=12: Recipe upload, successful.
431 )))
432
433 == **Recipe index** ==
434
435 The recipe index address RPW is mainly used for editing traditional recipes, and it is more convenient to modify the data and display of recipes. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
436
437 The recipe index area (RPW)'s instruction as follows:
438
439 1. RPW~*~*~#~#~#~#, a total of six digits, the first two ~*~* represent the Recipe group number, ~#~#~#~# represents the element order number. For example, RPW010000 indicates the 1st element of the Recipe group No.1, and RPW110002 indicates the 3rd element of the Recipe group No.11.
440 1. If the indexed group number or element number does not exist, the value of RPW defaults to zero. For example, RPW110011 represents the 12th element of the Recipe group No.11. If it does not exist, the value returned by accessing RPW110011 is zero. The value written in RPW110011 will not be saved to the recipe file.
441
442 * **✎Note**: As long as RPW~*~*~#~#~#~# exists, any object "writes" to HPW~*~*~#~#~#~# will be saved to the recipe file. 
443
444 (% start="3" %)
445 1. The RPW register only supports word address access.
446 1. It can be known from the coding method of RPW~*~*~#~#~#~# that the range of RPW is from RPW000000-RPW990450, wherein the range of group number is 0-100, and the range of element is 0-450.
447
448 == Recipe example ==
449
450 The recipe index makes the modification and display of recipe data more convenient. Only need to modify and display the data of the recipe file through "Numeric Input/Display" Object and "Word Switch".
451
452 Edit the recipe configuration, create three groups of recipes, 4 elements for per group: Red, green, blue, spraying time, as following shown:
453
454 (% style="text-align:center" %)
455 [[image:8-5TraditionalRecipeCaseConfig.png]]
456
457 RPW 0~~3 can display the data of group for the selected line. RPW10000~~10003, RPW20000~~20003, RPW30000~~30003 each address can display the single element. Directly modify the content of the RPW address and then modify the recipe data, as following shown:
458
459 (% style="text-align:center" %)
460 [[image:8-7TraditionalRecipeCaseShowNoOpera.png]]
461
462 After selecting the 2nd group, trigger the download button to download the whole group data to the corresponding element address (For this case, the data will write into HDW0~~3), or trigger the upload button to upload the content of the element address to the specified recipe group.
463
464 (% style="text-align:center" %)
465 [[image:8-6TraditionalRecipeCaseShow.png]]
466
467 = **Trend chart** =
468
469 Trend chart function is used for displaying the real-time data in HMI as curve graph, which X axis represent as time, Y axis represent as data.
470
471 Click "Project" → "Trend chart", it will pop up the following screen. Click "Add" to creat new curve record.
472
473 (% style="text-align:center" %)
474 [[image:趋势图配置 001.png||class="img-thumbnail"]]
475
476 **Settings**
477
478 (% style="text-align:center" %)
479 [[image:趋势图设置 2.png||height="507" width="866"]]
480
481 **(1) Basic settings**
482
483 1. **Curve NO.: **It is for setting curve number,
484 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
485 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
486 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
487
488 **(2) Sample Type**
489
490 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
491 1. **Sample unit:** 100ms.
492
493 **(3) Quick Setting**
494
495 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
496
497 (% style="text-align:center" %)
498 [[image:趋势图设置 3.png||class="img-thumbnail"]]
499
500 (% start="2" %)
501 1. **Sample address: **Fill in the start address that read the device data. If the sampl address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
502
503 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
504
505 (% class="box infomessage" %)
506 (((
507 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
508 )))
509
510 **Trend Chart Demo Download Link**
511
512 [[https:~~/~~/drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC>>url:https://drive.google.com/open?id=1smnaAvSxOWC0WQK4_uvqHXWn4vUZxGJC]]
513
514 = **History XY plot** =
515
516 Different from TrendChart, uses need to set history XY curve items in project. Please click "Project"-> "History XY Plot" to open the setting screen.
517
518 Recipe function settings will be display in "[[History XY Plot>>path:https://docs.we-con.com.cn/bin/view/PIStudio/08.Basic%20Function/#HHistoryXYplot]]" object.
519
520 (% style="text-align:center" %)
521 [[image:历史XY 2.png||class="img-thumbnail"]]
522
523 (% style="text-align:center" %)
524 [[image:历史XY 3.png||class="img-thumbnail"]]
525
526 **(1) Basic settings**
527
528 1. **Curve NO.: **It is for setting curve number,
529 1. **Curve Name:** It is for setting curve name. The length limitation is 31 bytes.
530 1. **Curve (1~~8):** It is for setting the number of curves. The default is 3.
531 1. **Dots of one curve: **It is for setting dots number of each curve. The default is 1000, but the maximum dots are 10,000 for all the curves.
532
533 **(2) Sample Type**
534
535 1. **Sample method:** There are two types, one is Cycle sample, the other is Trigger cycle sample. If you select Trigger cycle same mode, the trigger sample address is required to edit.
536 1. **Sample unit:** 100ms.
537
538 **(3) Quick Setting**
539
540 1. **Data format: **It is for setting all the curves, select the data format for all curves, and setting the reading addresses for curves. There are as follows.
541
542 (% style="text-align:center" %)
543 [[image:image-20220616145435-1.png]]
544
545 (% start="2" %)
546 1. **Sample address: **Fill in the start address that read the device data. If the sample address is consecutive, check "use continuous address". For example, set HDW0 as start address, curve number is 3, then the HDW0 is for Curve 1, HDW1 is for Curve2, HDW2 is for Curve 3.
547
548 **(4) Curve Table:** The sample address you have set would display on it. Click the corresponding box to modify the content.
549
550 (% class="box infomessage" %)
551 (((
552 **✎Note: **Curve names can only consist of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_') (' '), and other non-English characters.
553 )))
554
555 **Operating Procedure**
556
557 * Click "Project" → "History XY Plot" to open the function selecting windows.
558
559 (% style="text-align:center" %)
560 [[image:8.Basic Function_html_5da6ca44bd28acbe.png||height="144" width="533" class="img-thumbnail"]]
561
562 * Click "Add" button to open "History XY Plot” setting windows.
563
564 (% style="text-align:center" %)
565 [[image:8.Basic Function_html_6345b50ea55168fa.png||height="307" width="554" class="img-thumbnail"]]
566
567 * Setting the function of History XY Plot.
568 * Click "OK" to save the setting.
569
570 **Download Link**
571
572 [[https:~~/~~/drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r>>url:https://drive.google.com/open?id=1t4_HuRmIJJ-B5ryA2kVMadD9FywKhZ4r]]
573
574 = (% style="color:inherit; font-family:inherit; font-size:29px" %)**Data record**(%%) =
575
576 The data record function is organized according to the structure below. In a project, there can be multiple record groups, each record group containing multiple channels. Different groups have different sampling times.
577
578 The topology is shown in the following figure.
579
580 (% style="text-align:center" %)
581 [[image:8.Basic Function_html_1b4bd09dafa7e049.png||height="332" width="554" class="img-thumbnail"]]
582
583 The data record stored in SD card is also organized according to the above figure.
584
585 The sample time and save time is consistent in the same record group. There are multiple channels in the group, When the sampling time is up, every channel would collect data to PLC register according to its own address.
586
587 **Sampling interval: **The interval between two consecutive samples was recorded.
588
589 As long as the project uses the data record function and supports the large-capacity storage module, the system will sample data according to the set sampling interval and save data according to the set saving interval.
590
591 For the file storage of data, see the file size configuration during data record configuration.
592
593 ✎**Note: **
594
595 After enable the Cloud and check the box of Upload to Cloud, the communication port settings of the address in the imported Data record configuration must be the same as the communication port settings of the current project, otherwise it cannot be used normally.
596
597 The number of Data records upload to Cloud shall not exceed the limit value, or the sum of the imported Data records and the number of existing alarm records shall not exceed the limit value. the specific limitation as following table:
598
599 (% style="margin-left:auto; margin-right:auto; width:513px" %)
600 |=(% style="width: 70px;" %)Series|=(% style="width: 442px;" %)Number of Data Record upload to Cloud
601 |(% style="width:70px" %)8000-R|(% style="text-align:center; width:442px" %)100
602 |(% style="width:70px" %)9000-R|(% style="text-align:center; width:442px" %)100
603 |(% style="width:70px" %)3000ig|(% style="text-align:center; width:442px" %)50
604 |(% style="width:70px" %)8000ig|(% style="text-align:center; width:442px" %)100
605
606 The record group name can only be composed of Chinese characters, (0~~9), (a~~z), (A~~Z), ('_'), ('') and other non-English characters.
607
608 Channel name cannot incloud following symbols: :" , ", " | ", " < ", " > ", " & ".
609
610 (% class="wikigeneratedid" id="HSettings" %)
611 **Settings**
612
613 (% style="text-align:center" %)
614 [[image:数据记录设置 1.png||height="533" width="848" class="img-thumbnail"]]
615
616 **Operating Procedures**
617
618 1. Click "Project"->"Data record" as below shows.
619 1. Click "Add" button to open "Data record" setting window.
620 1. Enter group name, the default is "GroupName0"
621 1. Select "Trigger function" mode, such as "No trigger".
622 1. Set "Total channels", such as 3.
623 1. Click "Apply" button.
624 1. Set Sample cycle, such as 15.
625 1. Set "Start channel" in "Quick settings", such as 4 0.
626 1. Check group information in "Channel list" as below.
627 1. Click "Save" button to complete settings.
628
629 The figure above display the group of current project. The data record file would stored in "DataLogFile" folder, and the data of every  group would have a data file. The file suffix is in "db" format.
630
631 ✎**Note: **
632
633 * For HMI series 8000 and above, the size of a single file cannot exceed 300M and the total file capacity cannot exceed 1000M.
634 * For HMI series 3000, the size of a single file cannot exceed 4M and the total file capacity cannot exceed 10M.
635 * If the total amount exceeds the range, an alarm will be given during project compilation.
636
637 (% style="text-align:center" %)
638 [[image:数据记录设置 2.png||height="572" width="850" class="img-thumbnail"]]
639
640 **(1) Group name:** Set group name, and he name should be unique.
641
642 **(2) Trigger function:** There are four modes to trigger record.
643
644 1. **No trigger: **Data will be recorded in every sample time.
645 1. **Trigger to record by sample cycle: **Data will be recorded in every same time, when trigger control bit set ON.
646 1. **Trigger to record once and reset: **Data will be recorded when trigger control bit set ON, and the bit will be reset automatically.
647 1. **Trigger to record once: **Data will be recorded when trigger control bit set ON, and the bit need to be reset manually.
648 1. **Trigger address: **It is only valid when the trigger condition is selected. The monitoring cycle for trigger sampling address is 1s.
649
650 **(3) Total channels (1~~100): **Set the numbers of channels. Click "apply" to view the channel lists on the right record channel.
651
652 **(4) Sampling cycle: **If you check "collect control address", the sampling interval is the value of the address. The unit is second. For example, Sample cycle=15s. It means that records data one time every 15s.
653
654 **Timing address:** It sets address to change sample time when HMI is running;
655
656 **(5) Total records:** It sets data record number in one data record file. If the data file size is beyond the current file size. The old data will be deleted, and the new data will replace the old data. Please remember to back up the old data record file.
657
658 **Abnormal value:** It sets a value, when communication fails, data record will record this value;
659
660 **(6) Upload to Cloud**: The data uploaded by Data Record is stored in the Cloud(Only ig series). The maximum number of record is 20.
661
662 **(7) Quick Settings**
663
664 1. **Start Channel:** It sets the continuous addresses for channels.
665 1. **Data Format: **It sets the same data format for channels.
666 1. **Number of Digits:** It sets the digits’ number for channels.
667 1. **Language Settings**: The text in HMI can be in 8 languages, user can set language in here.
668
669 **(8) Channel List**: Besides quick settings, user can set channel name, address, data format, and so on one by one according to real situation.
670
671 **✎Note:**
672
673 * After enabling the Cloud function and checking the upload to the Cloud, the communication port settings of the address in the imported Data record configuration must be the same as the communication settings of the current project, otherwise it cannot be used normally.
674 * The range of upload to the Cloud from Data record configuration must not exceed 50, or the total number of imported Data records and the number of currently existing Data records must not exceed 50. If it exceeds, it will prompt you to reconfigure, should reduce the number.
675 * The channel name can only be composed of English characters, (0~~9), (a~~z), (A~~Z), ('_'), ('').
676 * The channel name does not include these 5 special characters: ", ", "| "," <", "> "," & ".
677 * The data would be overwritten automatically if the capacity exceed the maximum capacity. For 8000/9000 series, the size of single file cannot exceed 300MB, and total capacity of data records cannot exceed 1000MB. For 3000/3000i/3000ie series, the size of single file cannot exceed 4MB, and total capacity of data records cannot exceed 10MB. If the total amount exceeds the range , an error will be prompted when the project is compiled.
678
679 You could click here to jump to object "[[Data Record Display>>https://docs.we-con.com.cn/bin/view/PIStudio/06.Objects/#HDatarecorddisplay]]"
680
681 = **User permission** =
682
683 **Introduction**
684
685 1. User permission is one of expansion function in PI Series HMI; it provides multi-level of permission for control HMI operations.
686 1. User need to set the user and group during designing project. Different groups have different permission levels for accessing. Each user should be added into the specified group; it is possible to add the same user into different groups.
687 1. Operating record: it records user operations information, the records files are saved in HMI flash; its path is [~\~\flash~\~\UserOperationLogs.db].
688 1. When it is on simulator mode, the files are saved in C disk, its path is [C:~\~\WECON\UserMgrFile\UserOperationLogs.db].
689
690 (% class="box infomessage" %)
691 (((
692 ✎**Note: **
693
694 * The user name and password must be unique.
695 * The multi language function of User permission only supported on HMI system version V2.0 or above
696 )))
697
698 == Settings ==
699
700 Open PIStudio software, then operate as the following figure.
701
702 (% style="text-align:center" %)
703 [[image:用户权限 1.png||class="img-thumbnail"]]
704
705 Click on the cell from UserName and Desc, which can support the multi language.
706
707 (% style="text-align:center" %)
708 [[image:UserPermissionMultilan.png]]
709
710 1. Click "User Permission" in "Data Tool" toolbar.
711 1. Edit user name, click "User0" cell under "UserName", and then enter the user name, one project allows maximum 20 users.
712 1. Edit password, click "User0" cell under "PassWord", and then enter the user name.
713 1. Edit description, click "User0" cell under "Desc", and then enter, description is not necessary。
714 1. Check the groups for each user, there are 11 groups beside admin.
715 1. Editing groups' description, but it is not necessary.
716 1. {{id name="OLE_LINK7"/}}{{id name="OLE_LINK6"/}}Click "Save and Exit" button to complete all settings.
717
718 ✎**Note:**
719
720 * Only a maximum of one administrator permission is allowed in a profile with one user permission. If you want to use "Funtion address" to modify the user permission, you must log in the administrator account to operate.
721 * When the configured file does not have the administrator account, a new user can be added  through "Funtion address" and set as the administrator.
722 * If you select hidden fucntion when configuring user account, the account would display as "~*~*~*~*~*~*" in the list. You only need to enter the password of the corresponding hidden user to log in.
723 * (((
724 Adding new UserName and Desc on the HMI by special addresses in the current language of the HMI, other languages will also configure the user names and user descriptions to the current language by default, i.e. switching to other languages, the new user names and user descriptions will not change with the language.
725 )))
726
727 == Object permission configuration ==
728
729 (% style="text-align:center" %)
730 [[image:用户权限 2.png||class="img-thumbnail"]]
731
732 User operation logs support multi languages configuration. Click on the Log Message, the text editor of multi language will be pop up:
733
734 (% style="text-align:center" %)
735 [[image:LogMessagesMultilan.png]]
736
737 **Operation Procedure of Object Permission**
738
739 1. Open the object setting windows;
740 1. Select "Security" windows;
741 1. Check the "User Permission";
742 1. Select "Level" to set permission level;
743 1. Enter "Log Message", it is for operation records, if it was empty, the operation for this object would be not be recorded;
744 1. Select the "Access Denied Setting" mode;
745
746 **Log information description**
747
748 A combination of Chinese characters, numbers, and uppercase and lowercase letters can be entered, and the number does not exceed 63.
749
750 The format of insert variable:{variable address, data format}. e.g., {HDW100,UW2.1}.
751
752 The data format are as follows.
753
754 (% class="table-bordered" %)
755 |=Letter|=Meaning
756 |B|Binary
757 |O|Octonary
758 |U|Unsigned decimal
759 |H|Hexadecimal
760 |b|BCD
761 |F|32-bit float
762 |S|Signed decimal
763 |C|Character
764 |W|Single word
765 |D|Double word
766
767 Examples.
768
769 * Unsigned decimal, BCD, 32-bit float and Signed decimal are as follows.
770
771 {HDW100,UW2.1}:  Indicates the variable address is HDW100. The data format are: unsigned decimal, single word, two integer bits, one decimal place.
772
773 * (((
774 Binary, Octonary and Hexadecimal are as follows.
775 )))
776
777 {HDW100,HD8}: Indicates the variable address is HDW100. The data format are: hexadecimal, double word, eight integer bits.
778
779 * (((
780 Character is as follows.
781 )))
782
783 {HDW100,C32}: Indicates the variable address is HDW100. The data format are: 32 characters.
784
785 When a record is generated, the contents of this variable are replaced by the value of your corresponding address.
786
787 == **Function address** ==
788
789 A user must first log in before performing an operation, and after the login is successful, the user can perform the required operation, and log out after completing the operation, making the operation permission invalid. User login, log out, modification of user password during operation and user management and other functions need to be configured.
790
791 HMI allows managing user accounts on screen. Including adding, deleting and editing the user account. HMI provide built-in screen for [Sign in] and [change password] (screen No. 1006 and 1007).
792
793 Functions and addresses are as follows.
794
795 (% class="table-bordered" %)
796 |=**Function**|=**Address**|=**Object type**|=**Address function**
797 |(% rowspan="3" %)Sign in|HUW1158~~1335|Drop down list|User name
798 |HUW1002|Character input object|Password
799 |HUW1000|Word Switch (Input 1)|OK (sign in)
800 |(% rowspan="5" %)Change password|HUW1158~~1335|Drop down list|User name
801 |HUW1002|Character input object|Old password
802 |HUW1006|Character input object|New password
803 |HUW1010|Character input object|Confirm password
804 |HUW1000|Word Switch (Input 2)|OK(change password)
805 |Sign out|HUW1000|Word Switch (Input 3) |Sign out
806 |(% rowspan="7" %)(((
807 New user ***1**
808 )))|HUW1014|Character input object|User name
809 |HUW1006|Character input object|password
810 |HUW1010|Character input object|Confirm password
811 |HUW1000|Word Switch (Input 4) |OK(add new user)
812 |HUW1336~~1345|Character input object|User description
813 |HUX1347.0|Bit switch|(((
814 ~=1: User hidden
815
816 ~=0: Visible (Defaults)
817 )))
818 |HUW1000|Word Switch (Input 8) |Save(add Hide features)
819 |(% rowspan="2" %)(((
820 Delete user ***2**
821 )))|HUW1158~~1335|Drop down list|User name
822 |HUW1000|Word Switch (Input 5)|OK (delete user)
823 |Delete Profile|HUW1000|Word Switch (Input 9)|OK(delete)
824 |Export Profile|HUW1000|Word Switch (Input 10)|OK(export)
825 |Import profile|HUW1000|Word Switch (Input 11)|OK(import)
826 |Export log file|HUW1000|Word Switch (Input 12)|OK(export)
827 |Delete log file|HUW1000|Word Switch (Input 13)|OK (delete)
828 |Current user name|HUW1349|Character object|32 Word
829 |System state information|HUW1030|Character input object|System state information
830 |(% rowspan="3" %)Permission settings|HUW1014|Character input object|User name
831 |HUW1348|Bit switch|(((
832 Set the user group:
833
834 HUX1348.0 = 1 administrator;
835
836 HUX1348.1 = 1 group 0 permission;
837
838 HUX1348.2 = 1 group 1 permission;
839
840 (Total group 0 - group 10)
841 )))
842 |HUW1000|Word Switch (Input 6)|Add user rights (set according to HUW1348)
843 |User login mode setting|HUW1382|Word Switch/Numeric input object|(((
844 0: Select a user name from the drop-down list
845
846 1: Use character input object (address HUW1014) to log in with a user name
847 )))
848
849 When the user performs a function operation, the operation result is displayed in the HUW1001.
850
851 (% class="table-bordered" %)
852 |=**Value (HUW1001)**|=**Meaning**
853 |1|Insufficient permissions.
854 |2|Username does not exist.
855 |3|Username already exists.
856 |4|Wrong username or password.
857 |5|Login successfully.
858 |6|Passwords are inconsistent in twice time.
859 |7|Password changed successfully.
860 |8|User added successfully.
861 |9|User deleted successfully.
862 |10|Maximum number of users exceeded.
863 |11|Admin user already exists.
864 |12|User permission modified successfully.
865 |13|File imported successfully.
866 |14|File imported failed.
867 |15|File exported successfully.
868 |16|File exported failed.
869 |17|Logout successfully.
870 |18|Profile deleted successfully.
871 |19|Log file deleted successfully.
872 |20|Hide settings modified successfully.
873 |21|Hide settings modified failed.
874 |22|(((
875 Password already occupied, please reset.
876
877 (For both username and password, it can not repetition)
878 )))
879
880 **✎Note:**
881
882 * *1: If there is an admin user account, then the new user can no longer add one more admin, that is, one project can only have one administrator account.
883 * *1: When adding new user, the password could not be duplicated with other users.
884 * *2: When deleting user, it is forbidden to delete the admin user.
885
886 **User Permission Demo Download**
887
888 [[https:~~/~~/drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq>>url:https://drive.google.com/open?id=1qOiEDvo_1H1YqpoLDpS77dGaAFm8nrGq]]
889
890 = Message prompt =
891
892 A message box is a window used to show some prompts or warnings to users. For example, the application process a task in the process of pop-up message box, suggesting that "U disk has been detected", then the customer can carry out data dump function.
893
894 (% style="text-align:center" %)
895 [[image:消息提示 2.png||class="img-thumbnail"]]
896
897 (% style="text-align:center" %)
898 [[image:8.Basic Function_html_5ce2091d6f7cd732.png||height="515" width="704" class="img-thumbnail"]]
899
900 **(1) Message**
901
902 It includes system classes (u disk, SD card, and others), chart classes (alarm, data record, recipe, file list), curve classes (Trend Chart, historical XY trend Plot).
903
904 **(2) Control**
905
906 1. **Current item: **It shows selected message information.
907 1. **Use trigger address: **When the message is triggered, the trigger address would be set ON.
908
909 **For Example:**
910
911 Trigger address is 011, during inserting a USB flash disk into HMI, and 011 would be set ON, once HMI recognizes USB flash disk, and display message.
912
913 1. **Show message: **Check it to display message when HMI is running. It is checked by default.
914 1. **Show on web: **Check it to display message when remote access HMI screen, it is unchecked by default.
915
916 **(3) Message Content**
917
918 Each message has default content, but you could set different content according to the actual situation. And the same message could be displayed in 8 languages.
919
920 **(4) Reload Text: **It means discard changes.
921
922 **For Example**
923
924 User deletes default content or modifies default content, but he wants to give up modification back to original, just click "Reload text".
925
926 **✎Note:**
927
928 * If you do not want this prompt during the running of HMI, please uncheck "Show message".
929 * "Reload text" function would be invalid after clicking "save".
930 * These 5 special characters are not supported in the header Multi language settings: ",", "|", "<", ">", "&".
931
932 = **Cloud** =
933
934 **Introduction**
935
936 Cloud function is available for following models: the ig series and 8000/9000 series with -R after system upgrade
937
938 You may configure the basic settings of Cloud functions, tags, and User MQTT according to your needs. (If the device supports the Cloud function, you can use the function and configure the tags after checking the box to enable it, or upload the data to the 3rd party server.)
939
940 Click "Project"-"[[image:hh_B4H5OuNT87.png||height="29" width="30"]]Cloud" in the upper left corner of the software, as shown in the following figure.
941
942 (% style="text-align:center" %)
943 [[image:云配置1.png||height="494" width="750" class="img-thumbnail"]]
944
945 **(1) Enable**
946
947 If the HMI supports the Cloud function, check it to enable the Cloud function, and it will collect the real-time data from HMI upload to the Cloud. The number of data collection is limited, and the specific parameters are as follows:
948
949 |=Series|=Monitoring Tags|=Alarm Record|=Data Record|=OpenCloud Data
950 |8000-R|300|200|100|1000
951 |9000-R|300|200|100|1000
952 |3000ig|100|20|50|500
953 |8000ig|300|200|100|1000
954
955 For example:
956
957 * In 3000ig's Cloud, the monitoring tags upload to the Cloud in real time is limited to 100.
958 * For 3000ig's Alarm, the Alarm records of word alarms and bit alarms upload to Cloud is limited to 20. (See [["Alarm">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HAlarm]] for details).
959 * For 3000ig's Data record, the Data records upload to Cloud is limited to 50. (For details, please refer to [["Data Record">>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/08.Basic%20Function/#HDataRecord]]).
960
961 **(2) Server Selection**
962
963 **Server**: China, ASEAN, and Europe.
964
965 **Password**:
966
967 1. If the HMI is not bound, this access password will be updated and downloaded into the HMI screen simultaneously.
968 1. If the HMI is bound, this access password in the project cannot effectively change the binding password of the device, and it can only be changed through V-NET.
969
970 **(3) Upload Selection**: 
971
972 To upload the data collected by HMI to the cloud or a to the third-party server, only one upload method can be selected.
973
974 1. **to Cloud**: All the configured tags, data records, and alarm records would be pushed to V-NET.
975 1. **to User MQTT**: All the configured tags, data records, and alarm records would be pushed to to the third-party server, and the relevant Lua function calls please refer to "[[Cloud interface>>http://docs.we-con.com.cn/wiki/pistudio/view/Helps/10.Lua/#HCloudInterface]]".
976
977 After the "to User MQTT" is checked. The tags, data records, and alarms cannot be viewed on V-NET, but the device can be bound to V-NET and remote monitoring the device screen normally.
978
979 **4) Low Data Mode setting**