Wiki source code of 10 Advanced Function

Version 14.1 by Hunter on 2023/08/11 11:21

Show last authors
1 (% class="wikigeneratedid" %)
2 This chapter provides information about advanced functions in PIStudio. **These advanced functions work only on special HMI models.**
3
4 = **Audio** =
5
6 1. Audio playing could play audio on HMI. You need to configure the relevant information, triggered by the condition, broadcast the set the mp3 audio file. The audio file can only be stored in the flash mp3 file.
7 1. Only the 9000 Series HMIs with audio modules can use this feature, and an external 3.5mm headphone head is required.
8
9 == Configuration ==
10
11 In PIStudio software, the setting procedue is as follow.
12
13 (% style="text-align:center" %)
14 [[image:音频 1.png||height="655" width="528" class="img-thumbnail"]]
15
16 **Click "Set" to open "Audio settings" window.**
17
18 (% style="text-align:center" %)
19 [[image:11.Advanced Function_html_949272a66c003cd.png||height="402" width="588" class="img-thumbnail"]]
20
21 * Audio list: Display the audio files you added. Double click the audio to configure it.
22 * Add: Add a new audio file.
23 * Delete: Delete selected audio file.
24 * Audio set: Set the configurations of the audio, contolled by address.
25
26 **Trigger configuration for audio files**
27
28 (% style="text-align:center" %)
29 [[image:音频 2.png||class="img-thumbnail"]]
30
31 * **Audio files**
32 ** MP3 file supported only.
33 ** The audio filesize should be less than 30MB.
34 ** The suffix .mp3 is necessary. The length of name should be less than 20 (including .mp3).
35 ** Audio file needs to be saved into the folder named mp3 in HMI flash, if not, it would not play. User could use the ~[[[CopyFile>>path:#_CopyFile]]] script function to import audio files into the HMI flash.
36 * **Trigger mode settings: **There are 3 kinds trigger mode to choose. They coulf be valid at the same time.
37 ** **Play according to time interval: **Set the interval time. For example ,set 3 minutes, then it will play for each 3 minutes' interval.
38 ** **Trigger to play: **There are three bit trigger conditions: Rising edge, Falling edge and Bit change. You could trigger one condition to play the audio file.
39 ** **Play according to time: **Play the audio when the time is up.
40 * **Play settings.** Set the play times and the cycle interval when it is triggered.
41
42 **Audio file playback setting**
43
44 This function is to control the playback of audio file in the list by address. (It should be used with file list.)
45
46 (% style="text-align:center" %)
47 [[image:音频 3.png||height="429" width="620" class="img-thumbnail"]]
48
49 == Control address ==
50
51 The table below describes each bit address function (including play, pause, etc). If the audio control address is HDW120, then specific function details are as shown in the table below.
52
53 (% class="table-bordered" %)
54 |=(% scope="row" %)**Function**|=(% style="width: 177px;" %)**Address**|=(% style="width: 647px;" %)**Description**
55 |(% rowspan="7" %)Play Control|(% style="width:177px" %)HDX120.0 (0(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Play control bit: Play the audio file when this bit address is triggered
56 |(% style="width:177px" %)HDX120.1 (1(% style="font-size:10.5px" %)st(%%) bit)|(% style="width:647px" %)Pause control bit: Pause playback when this bit address is triggered, or resume playback after pause
57 |(% style="width:177px" %)HDX120.2 (2(% style="font-size:10.5px" %)nd(%%) bit)|(% style="width:647px" %)Stop control bit: Stop the play when this bit address is triggered
58 |(% style="width:177px" %)HDX120.3 (3(% style="font-size:10.5px" %)rd(%%) bit)|(% style="width:647px" %)Last audio: Play last audio when this bit address is triggered.
59 |(% style="width:177px" %)HDX120.4 (4(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Next audio: Play next audio when this bit address is triggered.
60 |(% style="width:177px" %)HDX120.5 (5(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Volume increase(not supported yet), increase by 10
61 |(% style="width:177px" %)HDX120.6 (6(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Volume decrease(not supported yet), decrease by 10
62 |(% rowspan="4" %)Mode Selection|(% style="width:177px" %)HDX120.7 (7(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)once: Only play current audio file only one time
63 |(% style="width:177px" %)HDX120.8 (8(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Single cycle: Repeat playing current audio file
64 |(% style="width:177px" %)HDX120.9 (9(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Order: Play audio file orderly and stop as soon as the tas finished
65 |(% style="width:177px" %)HDX120.10 (10(% style="font-size:10.5px" %)th(%%) bit)|(% style="width:647px" %)Repeat in order: Repeat to play the audio file of the list
66
67 == State address ==
68
69 The audio play status address occupies a continuous 35 word addresses. If audio play status address is set as HDW200, the specific function allocation details are shown as below table
70
71 (% class="table-bordered" %)
72 |=(% scope="row" style="width: 183px;" %)**Address**|=(% style="width: 314px;" %)**Function**|=(% style="width: 592px;" %)**Description**
73 |=(% style="width: 183px;" %)HDW200|(% style="width:314px" %)Playback status storage address|(% style="width:592px" %)(((
74 ~=0 : stop play
75
76 ~=1 : playing
77
78 ~=2 : pause play
79 )))
80 |=(% style="width: 183px;" %)HDW201|(% style="width:314px" %)Volume value storage address|(% style="width:592px" %)Range from 0 to 100(default value is 100, and it is not adjustable so fars
81 |=(% style="width: 183px;" %)HDW202~~HDW234|(% style="width:314px" %)Audio file name|(% style="width:592px" %)Displays the file name of the audio currently playing
82
83 ✎**Note:**
84
85 * The audio file needs to be stored in the flash of PI9000 series HMI.
86 * Only PI9000 series HMI with audio module could support this function, and an external 3.5mm headphone is required.
87
88 = **Video** =
89
90 **Introduction**
91
92 1. Configure related information and play video files through conditional trigger.
93 1. Only HMI 9000 and 8150ig series support this function.
94 1. Video playing could play video on HMI project screen.
95 1. It requires "Customized Object" and "File List" objects.
96 1. Currently, the video format support by Wecon HMI are including ASF, AVI, MKV, MP4, RM, and FLV.
97 1. Olny supports playback of 360P and 480P resolution video.
98
99 == Configuration ==
100
101 **Custom object configuration**
102
103 (% style="text-align:center" %)
104 [[image:视频功能部件配置.png]]
105
106 **Basic**
107
108 The function address doesn't have to be configured. DLL file name needs to be "Custom_MoviePlayer".
109
110 **Custom Address**
111
112 * ID1 is the address for storing the video file name (including the suffix). It could not be empty and the length is 32 words.
113 * ID2 is the address for video control, and occupies 1 word. It could not be empty. Please refer to[[ "Video control address">>https://docs.we-con.com.cn/bin/view/PIStudio/11.Advanced%20Function/#HControladdress-1]].
114 * ID3 is the address of video status, and occupies 1 word. It could not be empty. 0 indicate stop, and 1 indicates play.
115 * ID4 is the address for stroring the volume of video file, and occupies 1 word. 8150ig can not adjust the volume, only 9000 series can be set.
116 * ID5 is the address for the video file path, and occupies 1 word. It could not be empty. Please refer to [["Video file path">>https://docs.we-con.com.cn/bin/view/PIStudio/11.Advanced%20Function/#HFilepath]].
117
118 == Control address ==
119
120 (% class="table-bordered" %)
121 |=(% style="width: 151px;" %)**Function**|=(% colspan="2" style="width: 200px;" %)**Address**|=(% style="width: 599px;" %)**Description**
122 |(% rowspan="7" style="width:151px" %)Play Control|(% style="width:92px" %)0(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.0|(% style="width:599px" %)(((
123 Bit for playing control:This address save the name of the video file to be played.
124 )))
125 |(% style="width:92px" %)1(% style="font-size:10.5px" %)st(%%) bit|(% style="width:107px" %)HDX100.1|(% style="width:599px" %)Bit for pause control:Pause playing when this bit address is triggered, or resume playing after pause
126 |(% style="width:92px" %)2(% style="font-size:10.5px" %)nd(%%) bit|(% style="width:107px" %)HDX100.2|(% style="width:599px" %)Bit for full screen control: Maximize the video when this bit address is triggered
127 |(% style="width:92px" %)3(% style="font-size:10.5px" %)rd(%%) bit|(% style="width:107px" %)HDX100.3|(% style="width:599px" %)Last video: Play the last video when this bit address is triggered.
128 |(% style="width:92px" %)4(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.4|(% style="width:599px" %)Next video: Play the next video when this bit address is triggered.
129 |(% style="width:92px" %)5(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.5|(% style="width:599px" %)Volume increase: Increased by 10 (only be supported 9000 series)
130 |(% style="width:92px" %)6(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.6|(% style="width:599px" %)Volume decrease: Decreased by 10 (only be supported 9000 series)
131 |(% rowspan="4" style="width:151px" %)Mode Selection|(% style="width:92px" %)7(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.7|(% style="width:599px" %)Once: Only play current video file once
132 |(% style="width:92px" %)8(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.8|(% style="width:599px" %)Single cycle: Repeat to play current video file
133 |(% style="width:92px" %)9(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.9|(% style="width:599px" %)Order: Play video file of the list and stop after done
134 |(% style="width:92px" %)10(% style="font-size:10.5px" %)th(%%) bit|(% style="width:107px" %)HDX100.10|(% style="width:599px" %)Repeat in order: Repeat to play the video file of the list
135
136 == (% style="color:inherit; font-family:inherit; font-size:23px" %)File path(%%) ==
137
138 (% class="table-bordered" %)
139 |=**Value**|=**Video File Path**|=**Description**
140 |0|USB flash disk|Please create a folder named mp4 in the U disk directory to store the video files to be played
141 |1|SD card|Please create a folder named mp4 in the SD card directory to store the video files to be played
142 |2|HMI flash|Copy the video files to the mp4 folder in the directory of flash
143
144 == Case ==
145
146 Operating Procedures of File List Object Settings
147
148 (% style="text-align:center" %)
149 [[image:file setting.png]]
150
151 Configure the customized object as the above picture
152
153 Configure the file list object as below:
154
155 1. Select the directory as the MP4 folder in USB flash disk. Set the file name address as HDW150
156 1. Add the video controlling address, refer to the above video controlling address table.
157 1. Compile the project and download it to HMI, trigger the bit address to play the video from the list.
158
159 == Demo ==
160
161 **PI8150ig Video Display: **[[Download link>>https://docs.we-con.com.cn/bin/view/PIStudio/2%20Demo/Applications/#H7PI8150igVideoDisplay]]
162
163 = **Email** =
164
165 Wecon HMI can send email with information from fields to the specified email address as soon as the conditions is triggered, but email sending is based on the network.
166
167 == Email setting ==
168
169 In "PIStudio" software, click "Project" → "E-mail" to open email function setting screen.
170
171 (% style="text-align:center" %)
172 [[image:邮件 1.png||height="780" width="597" class="img-thumbnail"]]
173
174 **SMTP Settings**
175
176 * **Sender Name: **Fill the sender's name, which is composed of Chinese characters, letters (case sensitive) and numbers. But it can not contain the following special English symbols:  ',', ';', '"', '<'. Maximum character length 32 is allowed.
177 * **Password:** Fill in the password or authorization code of the mailbox. If the server needs to set the authorization code, the authorization code needs to be used. If the authorization code is not used, the password is used. Please refer to the SMTP service in the mailbox for the authorization code information. It cases sensitive, maximum character length 32 allowed in password.
178 * **Confirm Password: **Confirm the password or authorization code of the mailbox.
179 * **Email Address: **Fill in the sender's email address, case sensitive, maximum character length 32 allowed in it.Such as [[support@we-con.com.cn>>path:mailto:support@we-con.com.cn]].
180 * **SMTP Server: **Please refer to the mailbox account settings. If you enter a common mailbox, the corresponding server address will be automatically written. such as smtp.exmail.qq.com.
181
182 (% class="table-bordered" %)
183 |=Email|=Email server|=Port number
184 |163 email|smtp.163.com|465
185 |126 email|smtp.126.com|465
186 |QQ email|smtp.qq.com|465
187 |Sina email|smtp.sina.com|465
188 |Sohu email|smtp.sohu.com|465
189 |Yahoo email|smtp.mail.yahoo.com.cn|465
190 |Google email|smtp.gmail.com|465
191
192 **✎Note:** Gmail also needs to enable the [allow unsafe apps] option in the account, otherwise the mail will not be sent normally.
193
194 (% style="list-style-type:disc" %)
195 * **Encryption Type: **SSL is a security protocol that provides security and data integrity for network communications. It encrypts network connections at the transport layer; TLS (STARTTLS) upgrades connections to SSL instead of using a separate encrypted communication port.
196 * **The Port Number: **Enter corresponding port number according to the SMTP serve addrress entered. You could only enter interger between 1 and 65535. Do not enter more than 6 digits in length. Common port numbers are port 25, 465 and 587.
197 ** Port 25: It does not protect the original data when transmitting data. The data can be seen. Generally, port 25 must be selected as no encryption or TLS(STARTTLS) encryption mode to send data correctly.
198 ** Port 465: It protect the original data when transmitting data. The data can not be seen. Generally, port 465 must be selected as SSL encryption mode to send data correctly.
199 ** Port 587: The original data is protected only after the TLS(STARTTLS) command is executed. Generally, port 587 must be selected as TLS(STARTTLS) encryption mode to send data correctly.
200
201 **✎Note: **Port 25 is open to SMTP servers, mainly for sending mail. But the port has vulnerability. Hackers often use port 25 to find SMTP servers to forward spam.
202
203 * **Error Message**
204 ** Set the error message receiving address, you could use the information to get the reasons of errors.
205 ** The error types in the mail function are divided into two types: custom rule error and server's error.
206 ** Custom rule errors are as follows.
207
208 (% class="table-bordered" %)
209 |**Message**
210 |Email settings are incorrect
211 |Email account is incorrect
212 |Email password could not include blank
213 |the settings of SMTP server are incorrect
214 |The range of SMTP server ports number should be integer, which is between 1 and 65535.
215 |The type of encryption for SMTP is incorrect
216 |The name of sender or email address setting is incorrect.
217 |The names of Recipients or email address setting are incorrect.
218 |The names of CC recipients or email address setting are incorrect.
219 |The names of Secret delivery recipients or email address setting are incorrect.
220 |Email topic could not be blank
221 |Email content could not be blank
222 |Total size of attachments should be below 25M
223 |Attachment "xxxx" is nonexistent
224
225 Server's errors are as follows.
226
227 (% class="table-bordered" %)
228 |**Message**
229 |smtp-server: 554 DT: SPM
230 |smtp-server: 550 RP: TRC
231 |smtp-server: 550 Limitation of connecting counts
232 |smtp-server: 535
233 |smtp-server: 550 Error: Content rejected
234 |smtp-server: 451 Internal server error
235 |smtp-server: 535 Invalid login user or password
236 |smtp-server: 550 too many sending requests today
237 |smtp-server: 452 Too many recipients received this hour.
238 |smtp-server: 535 Error: Authentication failed, system busy
239 |could not connect: Connection timed out
240 |Unexpected EOF on SMTP connection
241 |could not initiate SSL/TLS connection
242 |smtp-server: 530 Need to issue a STARTTLS command first.
243 |could not resolve host
244 |could not connect: Connection timed out
245 |could not connect: Connection refused
246 |smtp-server: 550 User not found: aaa.163.com
247
248 * **Manual Trigger**
249
250 It is for modifying the email sending settings when HMI is running. According to the set manual trigger address, the address is offset backward to get the address of the corresponding function (a total of 201 words). Take HDW100 as an example.
251
252 (% class="table-bordered" %)
253 |(% style="width:201px" %)**Address**|(% style="width:586px" %)**Description**
254 |(% style="width:201px" %)HDX100.0|(% style="width:586px" %)Sending trigger
255 |(% style="width:201px" %)HDX101.0~~101.15|(% style="width:586px" %)It is used for triggering recipient groups, for example, HDW101.0 set ON, and the address in group 1 will be in recipient list.
256 |(% style="width:201px" %)HDX103.0~~103.15|(% style="width:586px" %)It is used for triggering recipient groups, for example, HDW103.0 set ON, and the address in group 1 will be in CC list.
257 |(% style="width:201px" %)HDX105.0~~105.15|(% style="width:586px" %)It is used for triggering recipient groups, for example, HDW105.0 set ON, and the address in group 1 will be in BCC list (Secret delivery).
258 |(% style="width:201px" %)HDW107~~171|(% style="width:586px" %)The subject length is limited to 64 words. (If it exceeds, it will intercept 64 words of content); The length of 65 words only use 64 actually, the 65th word address is reserved;
259 |(% style="width:201px" %)HDW172~~300|(% style="width:586px" %)The content length is limited to 128 words. (If it exceeds, it will intercept 128 words of content)
260 |(% style="width:201px" %)HDX301.0|(% style="width:586px" %)Whether to send an alarm record file as attachment
261 (HMI V1.0 filename: AlarmDataFile.db)
262 (HMI V2.0 filename: AlarmDataFile_0.db)
263
264 1. Emails that sent manually are not queued. Emails trigger by bit change, rising edge, falling edge and timing need to be sent in the sequence of triggering. The maximum value is 100, and those who are added after it is exceeded will be discarded. If an email is sending, it would send immediately after the current email is sent. If there is no email sending, it would send immediately.
265 1. If the trigger condition sent manually is the rising edge trigger, before the mail is sent, no new mail will be sent even if it is triggered again. No matter the email is sent successfully or not, the corresponding trigger would be OFF.
266 1. Emails that sent manually would only be sent once no matter the sending error is custom error, network or other errors.
267
268 == Email sending settings ==
269
270 (% style="text-align:center" %)
271 [[image:邮件 2.png||class="img-thumbnail"]]
272
273 1. **Add. **A maximum of 1024 email can be added.
274 1. **Modify.** Select an email to modify the content and configuration.
275 1. **Delete. **You could select an email to delete or click the "ID" column to delete in batch.
276
277 (% style="text-align:center" %)
278 [[image:邮件 3.png||height="578" width="744" class="img-thumbnail"]]
279
280 **Email sending configuration.**
281
282 * **Theme. **The value cannot be empty and case sensitive. The total length  cannot exceed 256 characters.
283 * **Content of email. **The contents are divided into three combinations: text, alarm and variable. The list can contain only 32 items at most, and the total length of the preview cannot exceed 1024 items.
284 ** **Text. **You could directly edit the text of language 1 to language 3. If you need to set multiple languages, click "edit all text" to set. You may also select "Text library". The content is case sensitive, and the total length of English/Chinese characters/numbers/symbols does not exceed 253.
285 ** **Alarm. **You could select "bit alarm" or "word alarm" from the list. The content is from alarm text. if the alarm changes, the content changes with it. The content is case sensitive, and the total length of English/Chinese characters/numbers/symbols does not exceed 253.
286 ** **Variable. **Set the corresponding variable address. Read value or strings according to the specified format, and the read information will be displayed in the corresponding position in the mail content.
287 * **Preview. **Combine the content of current edited email and diaplay it for you to modify the content conviniently. The preview length cannot exceed 1024.
288 * **Sending method. **It is divided into timed send interval and bit address trigger tranmission. The two methods cannot be used at the same time.
289 ** timed send interval. After booting, the current system time is used to start calculating, and each time the time  is up, the information will be sent to the set recipient in the form of an email, and the minimum time should be set to 5 minutes. **Note: **The first boot is not sent.
290 ** Bit address trigger tranmission. When the set trigger address meets the trigger conditon, the information will be sent to the set recipient in the form of an email. If the content select alarm, the alarm address would be written in the trigger address. There are three methods to trigger: sending on rising edge, sending on falling edge and send when the bit changes.
291 * **Recipient.** It is set in groups. You could send  multiple groups, and each group can have multiple recipients.
292 * **Add CC.** Sends the current email to other recipients.
293 * **Add secret delivery. ** Sends the current email to other recipients, but the recipient and cc recipients do not see the BCC recipient.
294 * when sending an email, you must set a recipient. CC recipients and BCC recipients are not to be set. The total number of recipinet, CC recipients and BCC recipients is 40.
295 * **Recipient priority. **Set the priority order of recipients to recipient, BCC, and CC.
296
297 **✎Note: **If the recipient address you select exists in all three positions, it exist only in the highest priority position. For example, if the recipient of an email has aaa, the bcc has aaa, and the cc has aaa, then let aaa only be the recipient.
298
299 == Recipient group setting ==
300
301 (% style="text-align:center" %)
302 [[image:邮件 4.png||class="img-thumbnail"]]
303
304 1. **All Group.** The groups you added.
305 1. **Group to send. **The groups that you send the emails to.
306 1. **Open recipinet settings.** Set the information of recipients, and add and subtract groups.
307
308 == Recipient setting ==
309
310 (% style="text-align:center" %)
311 [[image:邮件 5.png||class="img-thumbnail"]]
312
313 1. **Add. **Add a recipient. There are non-dynamic recipient and dynamic recipient. They cannot be used at the same time. You may just fill in the  recipient's name and email address. The dynamic recipient address  is limited to 32 characters, and a maximum of 40 recipients can be added.
314
315 (% style="text-align:center" %)
316 [[image:邮件 6.png||class="img-thumbnail"]]
317
318 (% start="2" style="list-style-type:decimal" %)
319 1. **Modify. **Select one recipient and click "modify" or double click the recipient to modify. If it is non-dynamic recipient, you could modify the name and email address. The email is unique. If it is dynamic recipient, you could modify the address, and the address is unique.
320 1. **Delete.** Select one recipient or multiple recipents to delete, or click the ID column to select all.
321 1. **Nuber of group. **You could click the  up/down arrow to increase or devrease groups. The default number is 1. The maximum number is 16.
322 1. **Description. **To decribe the group information. The total length shall not exceed 32.
323
324 == Test sending settings ==
325
326 (% style="text-align:center" %)
327 [[image:邮件 7.png||class="img-thumbnail"]]
328
329 (% class="wikigeneratedid" %)
330 **✎Note: **
331
332 1. You can open this after the SMTP server is set.
333 1. When NetEase mail (126, 163 and yeah) occurs erros 554, it may be that the mailbox used is restricted by the anti-spam mechanism, and the performance may be that it cannot send emails in bulk or directly.
334 1. When TOM mail is sender's mail, the name of it and the recipient tested must be English, otherwise the email would be returned.
335 1. When testing with Zoho mailbox, there was a delay of less than 3 minutes.
336 1. The custom errors for the test error is as follows.
337
338 (% class="table-bordered" %)
339 |=(% style="width: 129px;" %)Error code|=(% style="width: 946px;" %)Cause of reason
340 |(% style="width:129px" %)0|(% style="width:946px" %)CSMTP_NO_ERROR
341 |(% style="width:129px" %)100|(% style="width:946px" %)WSA_STARTUP = Unable to initialize winsock2
342 |(% style="width:129px" %)101|(% style="width:946px" %)WSA_VER = Wrong version of the winsock2
343 |(% style="width:129px" %)102|(% style="width:946px" %)WSA_SEND = Function send() failed
344 |(% style="width:129px" %)103|(% style="width:946px" %)WSA_RECV = Function recv() failed
345 |(% style="width:129px" %)104|(% style="width:946px" %)WSA_CONNECT = Function connect failed
346 |(% style="width:129px" %)105|(% style="width:946px" %)WSA_GETHOSTBY_NAME_ADDR = Unable to determine remote server
347 |(% style="width:129px" %)106|(% style="width:946px" %)WSA_INVALID_SOCKET = Invalid winsock2 socket
348 |(% style="width:129px" %)107|(% style="width:946px" %)WSA_HOSTNAME = Function hostname() failed
349 |(% style="width:129px" %)108|(% style="width:946px" %)WSA_IOCTLSOCKET = Function ioctlsocket() failed
350 |(% style="width:129px" %)109|(% style="width:946px" %)WSA_SELECT
351 |(% style="width:129px" %)110|(% style="width:946px" %)BAD_IPV4_ADDR = Improper IPv4 address
352 |(% style="width:129px" %)200|(% style="width:946px" %)UNDEF_MSG_HEADER = Undefined message header
353 |(% style="width:129px" %)201|(% style="width:946px" %)UNDEF_MAIL_FROM = Undefined mail sender
354 |(% style="width:129px" %)202|(% style="width:946px" %)UNDEF_SUBJECT = Undefined message subject
355 |(% style="width:129px" %)203|(% style="width:946px" %)UNDEF_RECIPIENTS = Undefined recipient
356 |(% style="width:129px" %)204|(% style="width:946px" %)UNDEF_RECIPIENT_MAIL = Undefined mail recipent
357 |(% style="width:129px" %)205|(% style="width:946px" %)UNDEF_LOGIN = Undefined user login
358 |(% style="width:129px" %)206|(% style="width:946px" %)UNDEF_PASSWORD = Undefined user password
359 |(% style="width:129px" %)207|(% style="width:946px" %)BAD_LOGIN_PASSWORD = Invalid user login or password
360 |(% style="width:129px" %)208|(% style="width:946px" %)BAD_DIGEST_RESPONSE = Server returned a bad digest MD5 response
361 |(% style="width:129px" %)209|(% style="width:946px" %)BAD_SERVER_NAME = Unable to determine server name for digest MD5 response
362 |(% style="width:129px" %)300|(% style="width:946px" %)COMMAND_MAIL_FROM = Server returned error after sending MAIL FROM
363 |(% style="width:129px" %)301|(% style="width:946px" %)COMMAND_EHLO = Server returned error after sending EHLO
364 |(% style="width:129px" %)302|(% style="width:946px" %)COMMAND_AUTH_PLAIN = Server returned error after sending AUTH PLAIN
365 |(% style="width:129px" %)303|(% style="width:946px" %)COMMAND_AUTH_LOGIN = Server returned error after sending AUTH LOGIN
366 |(% style="width:129px" %)304|(% style="width:946px" %)COMMAND_AUTH_CRAMMD5 = Server returned error after sending AUTH CRAM-MD5
367 |(% style="width:129px" %)305|(% style="width:946px" %)COMMAND_AUTH_DIGESTMD5 = Server returned error after sending AUTH DIGEST-MD5
368 |(% style="width:129px" %)306|(% style="width:946px" %)COMMAND_DIGESTMD5 = Server returned error after sending MD5 DIGEST
369 |(% style="width:129px" %)307|(% style="width:946px" %)COMMAND_DATA = Server returned error after sending DATA
370 |(% style="width:129px" %)308|(% style="width:946px" %)COMMAND_QUIT = Server returned error after sending QUIT
371 |(% style="width:129px" %)309|(% style="width:946px" %)COMMAND_RCPT_TO = Server returned error after sending RCPT TO
372 |(% style="width:129px" %)310|(% style="width:946px" %)MSG_BODY_ERROR = Error in message body (邮件正文中出现错误)
373 |(% style="width:129px" %)400|(% style="width:946px" %)CONNECTION_CLOSED = Server has closed the connection
374 |(% style="width:129px" %)401|(% style="width:946px" %)SERVER_NOT_READY = Server is not ready
375 |(% style="width:129px" %)402|(% style="width:946px" %)SERVER_NOT_RESPONDING = Server not responding
376 |(% style="width:129px" %)403|(% style="width:946px" %)SELECT_TIMEOUT
377 |(% style="width:129px" %)404|(% style="width:946px" %)FILE_NOT_EXIST = File not exist
378 |(% style="width:129px" %)405|(% style="width:946px" %)MSG_TOO_BIG = Message is too big
379 |(% style="width:129px" %)406|(% style="width:946px" %)BAD_LOGIN_PASS = Bad login or password
380 |(% style="width:129px" %)407|(% style="width:946px" %)UNDEF_XYZ_RESPONSE = Undefined xyz SMTP response
381 |(% style="width:129px" %)408|(% style="width:946px" %)LACK_OF_MEMORY = Lack of memory
382 |(% style="width:129px" %)409|(% style="width:946px" %)TIME_ERROR = time() error
383 |(% style="width:129px" %)410|(% style="width:946px" %)RECVBUF_IS_EMPTY = RecvBuf is empty
384 |(% style="width:129px" %)411|(% style="width:946px" %)SENDBUF_IS_EMPTY = SendBuf is empty
385 |(% style="width:129px" %)412|(% style="width:946px" %)OUT_OF_MSG_RANGE = Specified line number is out of message size
386 |(% style="width:129px" %)413|(% style="width:946px" %)COMMAND_EHLO_STARTTLS = Server returned error after sending STARTTLS
387 |(% style="width:129px" %)414|(% style="width:946px" %)SSL_PROBLEM = SSL problem
388 |(% style="width:129px" %)415|(% style="width:946px" %)SSL_PROBLEM = SSL problem
389 |(% style="width:129px" %)416|(% style="width:946px" %)STARTTLS_NOT_SUPPORTED = The STARTTLS command is not supported by the server
390 |(% style="width:129px" %)417|(% style="width:946px" %)LOGIN_NOT_SUPPORTED = AUTH LOGIN is not supported by the server
391
392 == Email status ==
393
394 **Network disconnection error**
395
396 If the fault is determined as a network disconnection error, the system does not delete the sent information and does not record the number of errors, and it would make an infinite send attempt.
397
398 **Custom rule error**
399
400 If the fault is determined as a custom rule error, delete the information.
401
402 **Server return error**
403
404 If the fault is determined as a server return error, then the error time add 1. It would try to send the email for 3 times. Regardless of whether the transmission is successful or not, it would delete the email to be sent. The test results are as follows.
405
406 (% class="table-bordered" %)
407 |=(% style="width: 125px;" %)**Server name**|=(% style="width: 186px;" %)**The number of sent**|=(% style="width: 765px;" %)**Consequences of exceeding the limit**
408 |(% style="width:125px" %)126|(% style="width:186px" %)160|(% style="width:765px" %)No more delivery on that day
409 |(% style="width:125px" %)163|(% style="width:186px" %)160|(% style="width:765px" %)No more delivery on that day
410 |(% style="width:125px" %)we-con|(% style="width:186px" %)800|(% style="width:765px" %)No more delivery on that day
411 |(% style="width:125px" %)qq|(% style="width:186px" %)50|(% style="width:765px" %)It can be sent again after a few minutes or a few hours
412 |(% style="width:125px" %)sohu|(% style="width:186px" %)160|(% style="width:765px" %)No more delivery on that day
413 |(% style="width:125px" %)sina|(% style="width:186px" %)50|(% style="width:765px" %)It can be sent again after a few minutes or a few hours, but cannont be received normally
414 |(% style="width:125px" %)gmail|(% style="width:186px" %)500|(% style="width:765px" %)No more delivery on that day
415
416 **Message Prompt**
417
418 1. If the email to be sent is deleted, a message will pop up.
419 1. If the email is sent successfully, a messge will pop up: "The email is sent successfully."
420 1. If the five symbols ',' , ' | ', '<', '>' and '&' appear in the fields set by the message prompt, the message prompt will display an abnormal message.
421
422 **Mail attachment**
423
424 Currently, the email attachment function only supports sending the specified alarm record (AlarmDataFile.db file), and does not support selecting content to send.
425
426 = USB keyboard =
427
428 (% class="wikigeneratedid" id="HIntroduction" %)
429 **Introduction**
430
431 1. HMI support keyboard via USB port of HMI.
432 1. When the keyboard function is enabled, the "Cursor Display" function is enabled by default. The user could move the cursor through the "up, down, left and right buttons" of the keyboard, and then press the Enter key to select the object.
433 1. Multiple devices could be connected with HMI via USB HUB (up to 4 external devices), such as: mouse, keyboard, scanner, magnetic stripe reader, etc.
434
435 == Enable function ==
436
437 In the software PIStudio, Click "Project" → "Project settings" → "Extend", and check "Enable keyboard" in "Input device" settings area as below.
438
439 (% style="text-align:center" %)
440 [[image:11.Advanced Function_html_f6cded728eedf4ce.png||height="567" width="501" class="img-thumbnail"]]
441
442 == Configuration decription ==
443
444 1. When the keyboard function is enabled, the "Cursor Display" function is enabled by default. The user could move the cursor through the “up, down, left and right buttons” of the keyboard, and then press the Enter key to select the object;
445 1. NumLock: When NumLock key is not lit, the keypad number is not allowed to be input (offline simulation does not allow all numeric keys to be input, including the numeric keys on the left side of the keyboard);
446 1. Key combination: (1) "Shift" + the left side of the keyboard and the special symbol button, to achieve special character input, such as: ~~ ! @ # $ % ^ & * ( ) _ + { } : "<> ? ;
447 1. Use the system special addresses "HSW1073 and HSW1074" to write custom key combinations in the script (currently only two key combinations are supported);
448 1. Caps Lock: In lowercase mode, shift+ letters, to enter uppercase; in uppercase mode, shift+ letters enter lowercase;
449
450 == **System special address** ==
451
452 In practical application, the [Enable Keyboard] function could be combined with the related "system special address" to achieve multi-key combination operation.
453
454 (% class="table-bordered" %)
455 |=(% style="width: 114px;" %)**Address**|=(% style="width: 229px;" %)**Description**|=(% style="width: 733px;" %)**Function**
456 |(% style="width:114px" %)HSW1073|(% style="width:229px" %)Keyboard key value|(% style="width:733px" %)(((
457 The currently pressed key value is displayed. The key value is shown in Table 1
458
459 (The Numeric/Character display object is not updated when it is being entered)
460 )))
461 |(% style="width:114px" %)HSW1074|(% style="width:229px" %)Keyboard key status|(% style="width:733px" %)(((
462 Display current key states
463
464 ~=0: key release
465
466 ~=1: key press
467
468 ~=2: Press and hold long
469
470 (The Numeric/Character display object is not updated when it is being entered)
471 )))
472 |(% style="width:114px" %)HSW1075|(% style="width:229px" %)Cursor speed|(% style="width:733px" %)Control the movement speed of the cursor, the range is 0~~100, the default is 20
473 |(% style="width:114px" %)HSW1076|(% style="width:229px" %)X coordinate value of cursor|(% style="width:733px" %)The X value of the current position of the cursor, range: 0~~screen width-1
474 |(% style="width:114px" %)HSW1077|(% style="width:229px" %)Y coordinate value of cursor|(% style="width:733px" %)The Y value of the current position of the cursor, range: 0~~screen height-1
475 |(% style="width:114px" %)HSW1078|(% style="width:229px" %)The ASCII code of keyboard key|(% style="width:733px" %)(((
476 Only the ASCII values of letters, numbers, and symbols are displayed. The ASCII value of the function keys is not displayed, as shown in Table 2
477
478 (The Numeric/Character display object is not updated when it is being entered)
479 )))
480 |(% style="width:114px" %)HSW1079|(% style="width:229px" %)Enable cursor position and Enter key mode|(% style="width:733px" %)(((
481 HSX1079.0 = 1: Set the cursor position according to HSW1076 and HSW1077 value;
482
483 HSX1079.1 = 0: When Numeric/Character display object is entered, enter key is for end input instruction. When no Numeric/Character display object is entered, enter key is for normal click;
484
485 HSX1079.1 = 1: Enter key only for normal click, not for keyboard end input instruction;
486 )))
487
488 **Key-Value Appendix Table (Decimal) (104Keys)**
489
490 (% class="table-bordered" %)
491 |=**Key**|=**Value**|=**Key**|=**Value**|=**Key**|=**Value**
492 |ESC|1|i I|23|Alt (Right)|100
493 |F1|59|o O|24|windows(Right)|126
494 |F2|60|p P|25|Menu|127
495 |F3|61|[ {|26|Right_ctrl|97
496 |F4|62|] }|27|Print Screen|99
497 |F5|63|Enter|28|ScrollLock|70
498 |F6|64|CapsLock|58|PauseBreak|119
499 |F7|65|a A|30|Insert|110
500 |F8|66|s S|31|Home|102
501 |F9|67|d D|32|PageUp|104
502 |F10|68|f F|33|Delete|111
503 |F11|87|g G|34|End|107
504 |F12|88|h H|35|PageDown|109
505 |` ~~|41|j J|36|↑|103
506 |1 !|2|k K|37|↓|108
507 |2 @|3|l L|38|←|105
508 |3 #|4|; :|39|→|106
509 |4 $|5|' "|40|NumLock (Keypad)|69
510 |5%|6|\ ~||43|/ (Keypad)|98
511 |6 ^|7|Shift (Left)|42|* (Keypad)|55
512 |7 &|8|z Z|44|- (Keypad)|74
513 |8 *|9|x X|45|+ (Keypad)|78
514 |9 (|10|c C|46|Enter (Keypad)|96
515 |0 )|11|v V|47|. (Keypad)|83
516 |- _|12|b B|48|0 (Keypad)|82
517 |+ =|13|n N|49|1 (Keypad)|79
518 |Backspace|14|m M|50|2 (Keypad)|80
519 |Tab|15|, <|51|3 (Keypad)|81
520 |q Q|16|. >|52|4 (Keypad)|75
521 |w W|17|/ ?|53|5 (Keypad)|76
522 |e E|18|Shift (Right)|54 |6 (Keypad)|77
523 |r R|19|Ctrl (Left)|29|7 (Keypad)|71
524 |t T|20|Windows(Left)|125|8 (Keypad)|72
525 |Y y|21|Alt (Left)|56|9 (Keypad)|73
526 |u U|22|space|57| |
527
528 **ASCII Code**
529
530 (% class="table-bordered" %)
531 |**Code**|**Value**|**Code**|**Value**|**Code**|**Value**|**Code**|**Value**
532 |32|space|56|8|80|P|104|h
533 |33|!|57|9|81|Q|105|i
534 |34|"|58|:|82|R|106|j
535 |35|#|59|;|83|S|107|k
536 |36|$|60|<|84|T|108|l
537 |37| %|61|= |85|U|109|m
538 |38|&|62|>|86|V|110|n
539 |39|'|63|?|87|W|111|o
540 |40|(|64|@|88|X|112|p
541 |41|)|65|A|89|Y|113|q
542 |42|*|66|B|90|Z|114|r
543 |43|+|67|C|91|[|115|s
544 |44|,|68|D|92|\|116|t
545 |45|-|69|E|93|]|117|u
546 |46|.|70|F|94|^|118|v
547 |47|/|71|G|95|_|119|w
548 |48|0|72|H|96|`|120|x
549 |49|1|73|I|97|a|121|y
550 |50|2|74|J|98|b|122|z
551 |51|3|75|K|99|c|123|{
552 |52|4|76|L|100|d|124|~|
553 |53|5|77|M|101|e|125|}
554 |54|6|78|N|102|f|126|~~
555 |55|7|79|O|103|g| |
556
557 == **Scripts example** ==
558
559 'HSW1073 key value
560
561 'HSW1074 key states
562
563 * 0: released;
564 * 1: pressed;
565 * 2: Holding pressed
566
567 'HSW1078 ASCII value of key
568
569 **Example 1**
570
571 {{code language="lua"}}
572 if @W_HSW1073 = 29 then                                            'Ctrl key value is 29
573
574     if @W_HSW1074 = 1 or @W_HSW1074 = 2               'Press Ctrl key
575
576               @W_HDW1000 = 1
577
578     else                                                                               'Release Ctrl key
579
580               @W_HDW1000 = 0
581
582     endif
583
584 endif
585 {{/code}}
586
587 **Example 2**
588
589 {{code language="lua"}}
590 if @W_HSW1073 = 59 and (@W_HSW1074 = 1 or @W_HSW1074 = 2) then              'F1 key value is 59
591
592    if @W_HDW1000 = 1 then                                                                                          'Combination Ctrl + F1
593
594          @W_HDW2000 = @W_HDW2000 + 1                                                                  'Function of combination key is HDW2000 + 1
595
596     endif
597
598 endif
599 {{/code}}
600
601 **Example 3**
602
603 {{code language="lua"}}
604 if @W_HSW1073 = 60 and (@W_HSW1074 = 1 or @W_HSW1074 = 2) then              'the value of F2 is 60
605
606    if @W_HDW1000 = 1 then                                                                                          'Combination Ctrl + F2
607
608             @W_HDW2000 = @W_HDW2000 - 1                                                                'Function of combination key is HDW2000 - 1
609
610   endif
611
612 endif
613 {{/code}}
614
615 **Example 4**
616
617 {{code language="lua"}}
618 if AsString(@W_HSW1078) = "a" and (@W_HSW1074 = 1 or @W_HSW1074 = 2) then          'Page up
619
620     if @W_HSW13 > 0 then
621
622            @W_HSW13 = @W_HSW13 - 1
623
624     endif
625
626 endif
627 {{/code}}
628
629 **Example 5**
630
631 {{code language="lua"}}
632 if AsString(@W_HSW1078) = "b" and (@W_HSW1074 = 1 or @W_HSW1074 = 2) then          'Page down
633
634     @W_HSW13 = @W_HSW13 + 1
635
636      if @W_HSW13 > 3 then
637
638               @W_HSW13 = 3
639
640      endif
641
642 endif
643 {{/code}}
644
645 = **rtsp web camera** =
646
647 **Introduction**
648
649 1. An external IP Camera (web camera) can be used to display the screen captured by the it to achieve real-time monitoring of the scene of the equipment.
650 1. ONVIF protocol and H.264 coding camera (RTSP web camera) are supported.
651
652 **Supported Model:**
653
654 * Hikvision
655 ** DS-2CD1321D-I
656 ** DS-2CD3T20FD-I3W
657 ** DS-2CD1221D-I3
658 ** DS-2CV3Q21FD-IW
659 * Dahua
660 ** DH-IPC-HFW1025D
661 ** DH-IPC-HFW1235M-I1
662
663 1. 8000 series HMI can view only **one **IP Camera monitoring screen at a time (only **one **camera object can be placed in a project).
664 1. 8000 series HMI can view only **four** IP Camera monitoring screen at a time (only **four **camera object can be placed in a project).
665
666 == **Camera search** ==
667
668 In the software PIStudio, Click "Project" -> "Project settings"-> "Extend", and check "Enable camera search module", shown as below.
669
670 (% style="text-align:center" %)
671 [[image:rtsp摄像头 1.png||class="img-thumbnail"]]
672
673 The maximum number of searches: Configure the number of online camera.  The maximum number of searches does not exceed 20, and should be greater than that of online camera.
674
675 === **Function address** ===
676
677 To configure the information of searches anf the records of search results. There are as follows.
678
679 (% class="table-bordered" %)
680 |(% style="width:226px" %)**Address**|(% style="width:533px" %)**Description**|(% style="width:240px" %)**Length**
681 |(% style="width:226px" %)HDW200|(% style="width:533px" %)Username|(% style="width:240px" %)20 words
682 |(% style="width:226px" %)HDW220|(% style="width:533px" %)Password|(% style="width:240px" %)20 words
683 |(% style="width:226px" %)HDX240.0|(% style="width:533px" %)Falling edge trigger search|(% style="width:240px" %)1 bit
684 |(% style="width:226px" %)HDX240.1|(% style="width:533px" %)(((
685 Search status
686
687 0: The search is complete.
688
689 1: It is searching.
690 )))|(% style="width:240px" %)1 bit
691 |(% colspan="2" rowspan="1" style="width:109px" %)The first search result|(% style="width:240px" %)80 words
692 |(% style="width:226px" %)HDW241|(% style="width:533px" %)IP address|(% style="width:240px" %)16 words
693 |(% style="width:226px" %)HDW257|(% style="width:533px" %)(((
694 ~=1: correct password
695
696 ~=0: wrong password
697 )))|(% style="width:240px" %)1 word
698 |(% style="width:226px" %)HDW258|(% style="width:533px" %)Device serial number|(% style="width:240px" %)43 words
699 |(% style="width:226px" %)HDW301|(% style="width:533px" %)Camera alias|(% style="width:240px" %)20 words
700 |(% colspan="2" rowspan="1" style="width:109px" %)The second search result|(% style="width:240px" %)80 words
701 |(% style="width:226px" %)HDW321|(% style="width:533px" %)IP address|(% style="width:240px" %)16 words
702 |(% style="width:226px" %)...|(% style="width:533px" %)...|(% style="width:240px" %)...
703
704 The username and password of function address need to entered manually. When searching for cameras, the username and password will be matched first, then each camera under the account will be retrieved, and the retrieved results will be stored in the response address. If the password is correct, the corresponding serial number would be displayed.
705
706 == **Camera display** ==
707
708 Add the object "camera display" to the project, click "Enable rtsp camera", as below.
709
710 (% style="text-align:center" %)
711 [[image:rtsp摄像头 2.png]]
712
713
714 Compile and download project, please click [Search Camera] button to get camera information in LAN The username and password here need to be entered manually. During searching camera, it will try to use this username and password to log in IP camera and store the result of login. If the password is correct, the “password correct” address will be displayed as 1 and the device serial number will be displayed. If the “password correct” address is 0, the device serial number would not be displayed.
715
716 === **Function address** ===
717
718 (% class="table-bordered" %)
719 |=(% style="width: 204px;" %)**Address**|=(% colspan="2" style="width: 702px;" %)**Description**|=(% style="width: 245px;" %)**Length**
720 |(% style="width:204px" %)HAW100|(% colspan="2" style="width:702px" %)Username|(% style="width:245px" %)20 words
721 |(% style="width:204px" %)HAW120|(% colspan="2" style="width:702px" %)password|(% style="width:245px" %)20 words
722 |(% style="width:204px" %)HAW140|(% colspan="2" style="width:702px" %)Alias|(% style="width:245px" %)20 words
723 |(% style="width:204px" %)HAW160|(% colspan="2" style="width:702px" %)Device serial number|(% style="width:245px" %)43 words
724 |(% style="width:204px" %)HAW203|(% colspan="2" style="width:702px" %)Camera ID|(% style="width:245px" %)1 word
725 |(% colspan="1" rowspan="11" style="width:204px" %)HAW204|(% colspan="2" rowspan="1" style="width:702px" %)Camera Control|(% colspan="1" style="width:245px" %)1 word
726 |(% style="width:211px" %)HAX204.0|(% style="width:787px" %)Open camera|(% colspan="1" style="width:245px" %)1 word
727 |(% style="width:211px" %)HAX204.1|(% style="width:787px" %)Close camera|(% colspan="1" style="width:245px" %)1 word
728 |(% style="width:211px" %)HAX204.2|(% style="width:787px" %)Camera up|(% colspan="1" style="width:245px" %)1 word
729 |(% style="width:211px" %)HAX204.3|(% style="width:787px" %)Camera down|(% colspan="1" style="width:245px" %)1 word
730 |(% style="width:211px" %)HAX204.4|(% style="width:787px" %)Camera left|(% colspan="1" style="width:245px" %)1 word
731 |(% style="width:211px" %)HAX204.5|(% style="width:787px" %)Camera right|(% colspan="1" style="width:245px" %)1 word
732 |(% style="width:211px" %)HAX204.6|(% style="width:787px" %)screenshot|(% colspan="1" style="width:245px" %)1 word
733 |(% style="width:211px" %)HAX204.7|(% style="width:787px" %)Binding camera|(% colspan="1" style="width:245px" %)1 word
734 |(% style="width:211px" %)HAX204.8|(% style="width:787px" %)Set Alias|(% colspan="1" style="width:245px" %)1 word
735 |(% style="width:211px" %)HAX204.9|(% style="width:787px" %)Camera stop moving|(% colspan="1" style="width:245px" %)1 word
736 |(% style="width:204px" %)HAW205|(% colspan="2" style="width:702px" %)(((
737 Camera status
738
739 ~=0: camera disconnected
740
741 ~=1: camera connected
742
743 ~=2: Camera is connecting
744 )))|(% style="width:245px" %)1 word
745 |(% style="width:204px" %)HAW206|(% colspan="2" style="width:702px" %)(((
746 Screenshot save location
747
748 ~=0: Screenshot is saved into flash
749
750 ~=1: Screenshot is saved into USB disk
751
752 ~=2: Screenshot is saved into SD card
753 )))|(% style="width:245px" %)1 word
754
755 **Operating Procedures**
756
757 Fill the camera ID address with the camera serial number searched by the camera search module, and trigger the binding address to fill username and password.
758
759 * If the camera searching is disabled, then users need to manually enter the information of this camera, including username, password, and device serial number. Device serial number could be obtained by checking the label of camera.
760
761 (% style="text-align:center" %)
762 [[image:11.Advanced Function_html_9ba06415a43f4264.png||height="232" width="412" class="img-thumbnail"]]
763
764 * If the IP CAMERA was triggered successfully, we could see the monitor screen and we could also set a alias for the camera and control the movement of the camera(up, down, left and right, some IP camera could not support the movement) or the screenshot. These operations could not be performed if camera off.
765
766 (% style="text-align:center" %)
767 [[image:11.Advanced Function_html_5e0967606b906db1.jpg||height="250" width="333" class="img-thumbnail"]]
768
769
770 **✎Note:**
771
772 * Camera configuration. When you get the camera, you need to activate the camera and enable the onvif protocol for the camera according to the user manual and tools provided by the camera manufacturer. If the configuration is not correct, the camera cannot be used on the HMI.
773 * When reading camera information, you need to configure the user name and password for the camera. When multiple cameras are enabled, you are advised to set the user names and passwords of all cameras to be the same.
774 * When using the camera function, ensure that the camera and HMI are on the same LAN. When the HMI is directly connected to the camera through a network cable, set both HMI and camera to static IP addresses as follows.
775
776 (% class="table-bordered" %)
777 |=(% style="width: 166px;" %) |=(% style="width: 256px;" %)HMI|=(% style="width: 332px;" %)Camera
778 |(% style="width:166px" %)IP address|(% style="width:256px" %)192.168.1.1|(% style="width:332px" %)192.168.1.2
779 |(% style="width:166px" %)Gateway|(% style="width:256px" %)192.168.1.1|(% style="width:332px" %)192.168.1.1
780
781 * You could obtain the camera from the "Camera Search module" in "Project parameters" or manually fill in the address. You can obtain resources for the camera display object in the Camera Search module or manually enter the parameters.
782 * You are advised to configure and confirm the user name and password of the camera before using it. Do not use the wrong user name (password) to search for or link to the camera. Once the wrong user name (password) is exceeded for a certain number of times, the camera will be locked. During the lock period, the camera will reject any connection for at least half an hour generally.
783 * When monitoring HMI cameras, do not monitor the same camera at the same time. Otherwise, the monitoring screen may be lost.
784 * When the camera is disconnected due to network reasons, the system wouyld try to reconnect the camera every 20 seconds.
785 * The alias of the camera is saved in the user database. The alias in old project is retained when downloading new project, if [user database] is selected. Otherwise the it will be deleted.
786
787 (% style="text-align:center" %)
788 [[image:11.Advanced Function_html_804b6a35561fc436.png||height="367" width="600" class="img-thumbnail"]]
789
790 **Demo download link**
791
792 [[https:~~/~~/drive.google.com/open?id=10UR1cg8KDjcTvKJYgk1KR8z4YIApIsD8>>url:https://drive.google.com/open?id=10UR1cg8KDjcTvKJYgk1KR8z4YIApIsD8]]
793
794 = **LAN Monitoring** =
795
796 WECON provides [HMI Monitor System] software for user to monitor PI3000 series HMI in Local area network (LAN).
797
798 This function is only for the model with -O. For example PI3070N-O.
799
800 == **[HMI Monitor System] software** ==
801
802 **Device List: **It displays HMIs, that connected into this monitor software;
803
804 **State Indicator:** It shows state of HMI, green means online, gray means offline;
805
806 **Operation Buttons: **It provides three operations for HMI device;
807
808 * Add: Click it to open add setting window;
809 * Delete: Click it to delete selected HMI device;
810 * Monitor: Click it to open monitor window for selected HMI device;
811
812 (% style="text-align:center" %)
813 [[image:11.Advanced Function_html_fdfb5186d5dd123d.png||height="302" width="600" class="img-thumbnail"]]
814
815 == **Operating procedures** ==
816
817 Click [Add] button to open setting window;
818
819 Enter HMI IP and Note;
820
821 Click [Connection test] button;
822
823 * If IP is correct, it will display tip as below;
824
825 (% style="text-align:center" %)
826 [[image:11.Advanced Function_html_130ed411da07f4c4.png||height="376" width="550" class="img-thumbnail"]]
827
828 * If IP is incorrect, it will display tip as below
829
830 (% style="text-align:center" %)
831 [[image:11.Advanced Function_html_878d04362f1b81b6.png||height="122" width="150" class="img-thumbnail"]]
832
833 **✎Note:** For using this function in PC, it requires the setup of LAN Monitoring Firewall, using Windows 7 system as example. **If this function works well in your PC, please ignore below content.**
834
835 **Solution 1: Disable Firmware Completely**
836
837 Open "Control Panel" and select "System Security".
838
839 (% style="text-align:center" %)
840 [[image:11.Advanced Function_html_9616a538bd5b8890.png||height="426" width="600" class="img-thumbnail"]]
841
842 Select "Windows Firewall"
843
844 (% style="text-align:center" %)
845 [[image:11.Advanced Function_html_4ff5d9c605179616.png||height="427" width="600" class="img-thumbnail"]]
846
847 Select "turn Windows Firewall on or off"
848
849 (% style="text-align:center" %)
850 [[image:11.Advanced Function_html_8cce81685e77dd93.png||height="532" width="850" class="img-thumbnail"]]
851
852 Select "Turn off Windows Firewall"
853
854 (% style="text-align:center" %)
855 [[image:11.Advanced Function_html_8e40bd24335bee5f.png||height="451" width="700" class="img-thumbnail"]]
856
857 **Solution 2: Do not close the firewall, but allow HMIUI to pass through the firewall**
858
859 Open Control Panel selection "system Security"
860
861 (% style="text-align:center" %)
862 [[image:11.Advanced Function_html_4a5370b15f8344bf.png||height="363" width="550" class="img-thumbnail"]]
863
864 Select "Windows Firewall"
865
866 (% style="text-align:center" %)
867 [[image:11.Advanced Function_html_3f00b4c76667d218.png||height="394" width="600" class="img-thumbnail"]]
868
869 Select "run a program or function through Windows Firewall"
870
871 (% style="text-align:center" %)
872 [[image:11.Advanced Function_html_2ce833853fe2fe08.png||height="422" width="600" class="img-thumbnail"]]
873
874 Select "Allow to run another program".
875
876 (% style="text-align:center" %)
877 [[image:11.Advanced Function_html_49e43fd3e9e58bc3.png||height="401" width="600" class="img-thumbnail"]]
878
879 Select "browse" in the pop-up dialog box.
880
881 (% style="text-align:center" %)
882 [[image:11.Advanced Function_html_714b05b4f66641fb.png||height="447" width="450"]]
883
884 Locate the HMIUI.exe file in the HMIUI directory under the installation path of the monitoring software, and double-click HMIUI.exe.
885
886 (% style="text-align:center" %)
887 [[image:11.Advanced Function_html_cdf52e5522e2e568.png||height="596" width="600" class="img-thumbnail"]]
888
889 Select "add".
890
891 (% style="text-align:center" %)
892 [[image:11.Advanced Function_html_2cf5b5f0c9aa4f7a.png||height="467" width="535" class="img-thumbnail"]]
893
894 Check the corresponding options.
895
896 (% style="text-align:center" %)
897 [[image:11.Advanced Function_html_ffc611cca1a173f9.png||height="361" width="600" class="img-thumbnail"]]
898
899 select "OK".
900
901 (% style="text-align:center" %)
902 [[image:11.Advanced Function_html_934ebd63c53af3ee.png||height="442" width="600" class="img-thumbnail"]]
903
904 = **Remote access config** =
905
906 **Introduction**
907
908 In the traditional concept, it is rather Difficult and complicated to remotely connect HMI via Ethernet. Users not only need to consider the security issue, but also need to set up complex network parameters. In addition, subject to the stage of the network environment, users have to do everything possible to think of ways through all levels of routers and switches. And an independent IP could only correspond to one HMI in tradition sense of the remote control. The WECON remote access system will solve all of those problems.
909
910 The solution of WECON HMI remote access is "Everything is possible with one network, one HMI, one cable". No matter where the HMI is, users could easily remote access HMI through the network, to achieve exclude exceptions and resolve them in the first time. In local area network or remote Internet, users could make HMI connect to Ethernet by one cable without setting any parameters. All network settings could be set by WECON remote access system.
911
912 **Set the IP of HMI**
913
914 (% style="text-align:center" %)
915 [[image:远程访问 1.png||class="img-thumbnail"]]
916
917 **Use mobile phones, computers, tablets, etc., open a browser, enter the IP, you could access the project in the HMI screen.**
918
919 * You are advised to use Chrome or Firefox. If you want to use Internet Explorer, use Internet Explorer 9 or later.
920 * 360, Sogou and other browsers need to use speed mode.
921 * Support the iphone's own browser, or install a latest UC browser.
922 * As long as the browser supports HTML5.
923
924 **Access through the cloud**
925
926 Access through the cloud platform, enter the machine code (the machine code of each HMI is independent) and model, then monitor the HMI remotely.
927
928 **Access through V-NET (ig series)**
929
930 Access through the V-NET, enter the machine code (the machine code of each HMI is independent) and the device password, bind the HMI, and monitor the HMI remotely.
931
932 **System Components**
933
934 WECON PI8000 and advanced HMI with [-R], such as PI8070-R;
935
936 WECON Smart APP or WECON Cloud platform
937
938 **User manual for WECON Smart and cloud platform download link**
939
940 [[https:~~/~~/drive.google.com/open?id=1hI8QI4vmJhAis2GFuCISChV9xGU0BxQ9>>url:https://drive.google.com/open?id=1hI8QI4vmJhAis2GFuCISChV9xGU0BxQ9]]
941
942 **FAQ**
943
944 * What is the difference between the-R model and the normal model?
945 ** The-R model can be accessed directly and unrestricted. Normal models need to buy cloudmonitoring products before access. The number of monitoring normal model is limitedaccording to the customer's purchase of cloud monitor packages.
946 * How many customers could remote access HMI at the same time?
947 ** It supports max. 4 customers access HMI in the same time.
948
949 = **Mulit-link** =
950
951 == **Introduction** ==
952
953 The main principle of Multi-link is to use the method of Master&Slave to implement the One machine-Multiple screens by ethernet port. For example, one Master HMI connect to one Slave HMI, the Slave one can write or read value from PLC which is communicated with Master.
954
955 In Multi-link, there is only one Master, and all the other HMIs are Slaves. The Master HMI is the only one device communicate with PLC, and the data received from the PLC is transmitted to each slave through the host HMI(Master).
956
957 (% style="text-align:center" %)
958 [[image:1652345241521-592.png||class="img-thumbnail"]]
959
960 At present, the Multi-link is regarded as special function. So not any model HMI support it. Need the HMI come with the special machine code. The series support Multi-link function right now: General, HMI+, i Series. Multi link doesn’t support the online simulaion. PI3000/PI3000+/PI3000i series can only have one Slave when using this function, while PI8000/9000,PI8000+/PI9000+ series can use at most 5 Slaves.
961
962 == **PIStudio settings** ==
963
964 Check to enable Multi-link, select the corresponding option. For example, if it is a slave HMI, select Slave.
965
966 (% style="text-align:center" %)
967 [[image:多机互联.png||class="img-thumbnail"]]
968
969
970 (% class="wikigeneratedid" %)
971 Master IP address setting: Click "Project"→"Project settings"→"HMI IP", as below.
972
973 (% style="text-align:center" %)
974 [[image:远程访问 1.png||height="516" width="594" class="img-thumbnail"]]
975
976 == **Slave project** ==
977
978 In order to let the fonts in the Slave and the Master consistent with each others, so Slave project needs to add one screen that can set the IP address of Master HMI for connecting to the Master, on the original the Master project. If Master project has components that use other font styles, and Slave project If there is no component corresponding to Master project, then the default font style SimSun would be displayed when the Multi-link is enabled. To avoid the Slave device prompts communication timeout message, you can add HSW9 = 1 in the initial script of Slave device.
979
980 == **Address** ==
981
982 |Address|Address Description|Usage Method
983 |HSW1100|(% rowspan="4" %)The IP of Master HMI|IP address high endian 1
984 |HSW1101|IP address high endian 2
985 |HSW1102|IP address high endian 3
986 |HSW1103|IP address high endian 4
987 |HSW1104|(((
988 Control the Slave to connect to
989
990 the Master or not
991 )))|(((
992 1: Connect to Master
993
994 0: Disconnect
995 )))
996
997 == **Notice** ==
998
999 During the connection, if the Master is downloading program, there is a highly chances that the slave screen is abnormal, and the Gallery and imported pictures cannot be displayed.
1000
1001 After the download process of Master HMI is finished, Slave needs to be restarted to monitor normally.
1002
1003 * If the Master and Slave are operated on any screen, the screen also will follow the changes and synchronize for other side.
1004 ** Using HSW12 = 1 on the Master, which can not affect each other.
1005 * There is no momentary delay function for buttons.
1006 * Multi-link version bit switch has no Min. holding time.
1007 * PI3000 series can only have one Slave when using this function, while PI8000/9000 series can use this function at most 5 Slaves.
1008 * Only supports Multi-link connection in the LAN network (local area network), or direct connection between Master and Slave.
1009 * The Master and Slave projects must be consistent (mainly for keeping the font style used by the Master and Slave HMI consistent), and the Slave HMI always adds the configuration of the “Master IP address".
1010 * After the special address is enabled, Slave will remotely monitor the interfaces from Master, and the source project will not be executed.
1011
1012 ✎Note: Slave project only needs to ensure that there is "the HSW address of the Master HMI IP" and the font style used by the Master.
1013
1014 = **V-NET Access (PC Side)** =
1015
1016 == **Login interface** ==
1017
1018 Enter the platform, as shown in Figure 1:
1019
1020 New users need to register first.
1021
1022 * The successfully registered account is the administrator account, which can bind the device and other operations.
1023 * The user needs to remember the registered account and password, and able to log in simultaneously on the PC Client/APP.
1024 * If the user forgets the password, he can click "Forgot Password" to reconfigure the password.
1025
1026 (% style="text-align:center" %)
1027 [[image:11.2-1.png||class="img-thumbnail"]]
1028
1029 Figure 1
1030
1031 Enter the account and password, and then click the "Login" button.
1032
1033 After successfully logging in, enter the "V-NET" interface, as shown in Figure 2. Add the HMI information you want to access through the "+" in the lower left corner.
1034
1035 (% style="text-align:center" %)
1036 [[image:11.Advanced Function_html_7618c4f92465545c.png||height="670" width="1366" class="img-thumbnail"]]
1037
1038 Figure 2
1039
1040 After the Add Device window pops up, enter the machine code and password of the device to add the device, as shown in Figure 3:   
1041
1042 (% style="text-align:center" %)
1043 [[image:11.Advanced Function_html_9b4cc907cf4a8c13.png||height="502" width="601" class="img-thumbnail"]]
1044
1045 Figure 3
1046
1047 * **Device machine code:** Each HMI has a unique and independent machine code, which is used to identify every remote device. (When binding multiple devices at the same time, the device passwords must be the same. Only one machine code can be entered on one line. When entering multiple machine codes, use the "Enter" key to change the line. If the format is wrong, the binding operation will fail and error will occur). Method of obtain machine code:
1048 ** PIStudio → "Project" → "Tool"→ "Download" →Copy the machine code.        
1049 ** Long press the upper right corner of HMI to enter the backstage, you can see "Machine Id" in "Machine Info".       
1050 ** Obtain the machine code from the backlabel of the device.
1051 * **Device password**: Refers to the Cloud access password, the default is 6 digits 8 (888888). Please refer to the cloud configuration if you first time binding the device.
1052 ** The length is 6 digits, English and special characters in English are allowed, spaces are not allowed, and cannot be empty.
1053 * **Device alias:** Refers to the name recognition of device in the menu bar of V-NET.
1054 ** Maximum 12 digits, except ·_-+=}]",.?,;: ""”【】—()...! these Special characters allowed others are limited to input, no spaces or blanks are allowed.
1055 ** If the device is successfully bound, click OK, and it would prompt message: The device is bound successfully!
1056
1057 (% class="box infomessage" %)
1058 (((
1059 **✎Note: **If you bind multiple machine codes in batch, the device alias will use the input device alias as the prefix, and the system will automatically add a suffix. Example: Default group (device alias)_1 (automatically added suffix).
1060 )))
1061
1062 == **V-NET module** ==
1063
1064 **Remote Monitoring**
1065
1066 The remote monitoring module can display the project page of the current screen in real time, and can operate the project on the web page, and the control of the screen. As shown in Figure 4:
1067
1068 (% style="text-align:center" %)
1069 [[image:11.2-4.png||class="img-thumbnail"]]
1070
1071 Figure 4
1072
1073 **Data Viewing**
1074
1075 The data viewing module is divided into Communication port, Collection point, Alarm configuration, Alarm records, Data Record configuration , Data Record, etc. As shown in Figure 5:
1076
1077 (% style="text-align:center" %)
1078 [[image:11.2-5.png||class="img-thumbnail"]]
1079
1080 Figure 5
1081
1082 The parameter configuration is as follows:
1083
1084 * Communication port : The communication port information, includes connection method and protocol name, can only be viewed, and cannot be added or modified. This info comes from the settings from HMI.
1085 * Collect point:Data monitoring module of the device. The collection point is the monitoring data, and its read-write, write-only, and read-only permissions also come from the Tags settings from HMI.
1086 * Note: You cannot add or delete collection points here. The read & write permissions of the collection points in the HMI will directly restrict the modification of the read & write permissions of the collection points by V-NET.
1087 * Alarm configuration: Alarm records of the device, monitoring points cannot be added, confirming the Alarm record and exporting data can be performed.
1088 * Data Record configuration: Data Record is historical data of the device, monitoring points cannot be added, curve and list viewing method are supported, and data records can be exported.
1089
1090 **Remote Download**
1091
1092 This function allows application on the PC to download directly to PLC or HMI, as shown in Figure 6:
1093
1094 (% style="text-align:center" %)
1095 [[image:11.2-6.png||class="img-thumbnail"]]
1096
1097 Figure 6
1098
1099 (% class="box infomessage" %)
1100 (((
1101 **✎Note: **The pass through function of remote download is temporarily unavailable on the web page, and it can be used normally in PC client. The configuration is as follows:
1102 )))
1103
1104 PLC download (only for Pass-through)
1105
1106 * Click the setting (gear icon) in the upper right corner of PC Client, and a dialog will pop up. The red area is the COM port configuration when the PLC pass-through downloads. As shown in Figure 7:
1107
1108 (% style="text-align:center" %)
1109 [[image:11.Advanced Function_html_870ebc5415b1a534.png||height="565" width="526" class="img-thumbnail"]]
1110
1111 Figure 7
1112
1113 * After configuring the COM port, go to the remote downloaded, PLC download, to config the name, communication port, virtual serial port and other configurations as shown in Figure 6.
1114
1115 HMI Download (only for Pass-through)
1116
1117 * Click the setting (gear icon) button in the upper right corner of PC Client, and a dialog will pop up. The red area is the configuration of the HMI download tool. As shown in Figure 8:
1118
1119 (% style="text-align:center" %)
1120 [[image:11.Advanced Function_html_64e406f9862f887e.png||height="565" width="526" class="img-thumbnail"]]
1121
1122 Figure 8
1123
1124 * Click the setting (gear icon) button, a dialog box will pop up, and automatically detect and find the PIStudio that has been installed in PC and conforms to the version, as shown in Figure 9:
1125 ** Location: Display the installation path of the current PIStudio.
1126 ** Version: Corresponding to the version of the current PIStudio.
1127 ** Browse: Click to manually set the installation path of PIStudio.
1128
1129 [[image:11.Advanced Function_html_df9946a5a7574454.png||height="349" width="642"]]
1130
1131 Figure 9
1132
1133 **Basic**
1134
1135 In the "Basic" sub-page of Basic, HMI name, record reserved selection, password, location and remarks, etc. As shown in Figure 10:
1136
1137 [[image:11.Advanced Function_html_c76828978cb6b697.png||height="670" width="1366"]] Figure 10
1138
1139 The device name is an alias of HMI, which is mainly used for easy distinction.
1140
1141 Online status: You can click the refresh button to refresh the online status of the HMI.
1142
1143 Machine code: Each HMI has a unique and independent machine code.
1144
1145 Record reserved: Checking the corresponding options will let HMI to suspend updating the corresponding configuration after downloading a new project.
1146
1147 Password: Refers to the cloud access password, the default is 6 digits 8 (888888); the cloud access password can be set and modified, the specific location is:
1148
1149 * V-NET → specified HMI → Baisc → "password” → modify and save, as shown in Figure 10.        
1150 * "Project" → "Cloud" → "Basic" → "Password" → of PIStudio (only unbind HMI can be modified), see Cloud Configuration.
1151
1152 Maximum storage of Alarm data: The maximum number of alarm data saved, with a range of 1 to 50000.    
1153
1154 Positioning:
1155
1156 * Use the device base station positioning to locate.        
1157 * Use manual positioning.
1158
1159 (% class="box infomessage" %)
1160 (((
1161 **✎Note:** After modifying the basic information of the device, you need to click Save below to save the modification successfully. If it is not saved successfully, please click Force Synchronization.
1162 )))