Changes for page 12 PLC Protocol OLD

Last modified by Mora Zhou on 2024/12/05 14:53

From version 100.1
edited by Ben
on 2022/08/29 15:42
Change comment: There is no comment for this version
To version 102.1
edited by Ben
on 2022/08/29 16:30
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1534,7 +1534,6 @@
1534 1534  (% style="text-align:center" %)
1535 1535  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1536 1536  
1537 -(% class="wikigeneratedid" %)
1538 1538  = Create communication with **Delta PLC** =
1539 1539  
1540 1540  == **DVP serial protocol** ==
... ... @@ -1578,12 +1578,59 @@
1578 1578  (% class="wikigeneratedid" %)
1579 1579  **4)Cable Wiring**
1580 1580  
1581 -(% class="wikigeneratedid" %)
1582 -= [[image:image-20220829152610-7.png]] =
1580 +(% class="wikigeneratedid" id="H" %)
1581 +[[image:image-20220829152610-7.png]]
1583 1583  
1584 1584  (% class="wikigeneratedid" id="H" %)
1585 1585  [[image:image-20220829152102-5.png]]
1586 1586  
1586 +
1587 +(% class="wikigeneratedid" %)
1588 +== **DVP Ethernet Protocol** ==
1589 +
1590 +
1591 +(% class="wikigeneratedid" %)
1592 +Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1593 +
1594 +**1)HMI Settings**
1595 +
1596 +
1597 +|**Items**|**Settings**|**Note**
1598 +|Protocol|DELTA DVP Modbus TCP|
1599 +|Connection|Ethernet|
1600 +|Port No.|201|Must be the same as the PLC setting
1601 +|PLC station No.|0|Must be the same as the PLC setting
1602 +
1603 +**2)Address List**
1604 +
1605 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1606 +|Bit|X|X|X o|0~~377|
1607 +|Bit|Y|Y|Y o|0~~377|
1608 +|Bit|M0|M0|M0 d|0~~1535|
1609 +|Bit|M1|M1|M1 d|1536~~4095|
1610 +|Bit|T|T|T d|0~~255|
1611 +|Bit|C|C|C d|0~~255|
1612 +|Bit|S|S|S d|0~~1023|
1613 +|Word|D0|D0|D0 d|0~~4095|
1614 +|Word|D1|D1|D1 d|4096~~11999|(((
1615 +
1616 +)))
1617 +|Word|T|T|T d|0~~255|
1618 +|Word|C|C|C d|0~~199|(((
1619 +
1620 +)))
1621 +
1622 +(% class="wikigeneratedid" %)
1623 +**3)Configure the communication protocol**
1624 +
1625 +[[image:image-20220829155452-1.png]]
1626 +
1627 +[[image:image-20220829162116-2.png]]
1628 +
1629 +**4)Cable Wiring**
1630 +
1631 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1632 +
1587 1587  = **MODBUS** =
1588 1588  
1589 1589  == **MODBUS RTU Master** ==
image-20220829155452-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +38.1 KB
Content
image-20220829162116-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +50.4 KB
Content