Changes for page 12 PLC Protocol OLD

Last modified by Mora Zhou on 2024/12/05 14:53

From version 130.1
edited by Ben
on 2022/08/30 14:54
Change comment: There is no comment for this version
To version 103.1
edited by Ben
on 2022/08/29 16:38
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -511,7 +511,7 @@
511 511  (% style="text-align:center" %)
512 512  [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513 513  
514 -== **CompactLogix FreeTag Ethernet protocol** ==
514 +== **FreeTag Ethernet/IP (CompactLogix)** ==
515 515  
516 516  Allen-Brandly CompactLogix
517 517  
... ... @@ -568,7 +568,7 @@
568 568  (% style="text-align:center" %)
569 569  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570 570  
571 -== **MicroLogix 1200** ** protocol** ==
571 +== **AB PLC address edit** ==
572 572  
573 573  The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574 574  
... ... @@ -1631,204 +1631,242 @@
1631 1631  
1632 1632  **1)HMI Settings**
1633 1633  
1634 -|**Item**|**Settings**|**Note**
1635 -|Protocol|DELTA AS300 MODBUS RTU|
1636 -|Connection|RS485|
1637 -|Baud rate|9600|
1638 -|Data bit|8|
1639 -|Parity|NONE|
1640 -|Stop bit|1|
1641 -|PLC station No.|1|
1642 -
1643 1643  **2)Address List**
1644 1644  
1636 +**3)Configure the communication protocol**
1645 1645  
1646 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1647 -|Bit|X|X|X d|0~~63|
1648 -|Bit|Y|Y|Y d|0~~63|
1649 -|Bit|D|D|D d|0~~29999|
1650 -|Bit|M|M|M d|0~~8191|
1651 -|Bit|SM|SM|SM d|0~~4095|
1652 -|Bit|S|S|S h|0~~2047|
1653 -|Bit|T|T|T d|0~~511|
1654 -|Bit|C|C|C d|0~~511|
1655 -|Bit|HC|HC|HC d|0~~255|
1656 -|Word|X|X|X h|0~~63|
1657 -|Word|Y|Y|Y d|0~~63|
1658 -|Word|SR|SR|SR d|0~~2047|
1659 -|Word|D|D|D d|0~~29999|
1660 -|Word|T|T|T d|0~~511|
1661 -|Word|C|C|C h|0~~511|
1662 -|Word|E|E|E d|0~~9|
1638 +**4)Cable Wiring**
1663 1663  
1664 -**3)Configure the communication protocol**
1640 +== **AS Ethernet Protocol** ==
1665 1665  
1666 -[[image:image-20220830094600-1.png]]
1642 +**1)HMI Settings**
1667 1667  
1668 -[[image:image-20220830094657-2.png]]
1644 +**2)Address List**
1669 1669  
1646 +**3)Configure the communication protocol**
1647 +
1670 1670  **4)Cable Wiring**
1671 1671  
1672 -Figure
1650 += **MODBUS** =
1673 1673  
1674 -[[image:image-20220830141138-1.png]]
1652 +== **MODBUS RTU Master** ==
1675 1675  
1676 -Pin Definition Diagram
1654 +Supported Series: MODBUS RTU CONTROLLER
1677 1677  
1678 -[[image:image-20220830095131-1.png]]
1656 +HMI works as MODBUS SLAVE connecting with MASTER
1679 1679  
1680 -== **AS Ethernet Protocol** ==
1658 +(% style="text-align:center" %)
1659 +[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1681 1681  
1682 -**1)HMI Settings**
1683 1683  
1662 +(% style="text-align:center" %)
1663 +[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1684 1684  
1685 -|=**Items**|=**Settings**|=**Note**
1686 -|Protocol|DELTA AS300 MODBUS TCP|
1687 -|Connection|Ethernet|
1688 -|Port No.|502|
1689 -|Device No.|1|
1690 -|HMI No.|0|
1691 1691  
1692 -**2)Address List**
1666 +(% style="text-align:center" %)
1667 +[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1693 1693  
1669 +**HMI Settings**
1694 1694  
1695 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1696 -|Bit|X|X|X d|0~~63|
1697 -|Bit|Y|Y|Y d|0~~63|
1698 -|Bit|D|D|D d|0~~29999|
1699 -|Bit|M|M|M d|0~~8191|
1700 -|Bit|SM|SM|SM d|0~~4095|
1701 -|Bit|S|S|S h|0~~2047|
1702 -|Bit|T|T|T d|0~~511|
1703 -|Bit|C|C|C d|0~~511|
1704 -|Bit|HC|HC|HC d|0~~255|
1705 -|Word|X|X|X h|0~~63|
1706 -|Word|Y|Y|Y d|0~~63|
1707 -|Word|SR|SR|SR d|0~~2047|
1708 -|Word|D|D|D d|0~~29999|
1709 -|Word|T|T|T d|0~~511|
1710 -|Word|C|C|C h|0~~511|
1711 -|Word|E|E|E d|0~~9|
1671 +(% class="table-bordered" %)
1672 +|**Items**|**Settings**|**Note**
1673 +|Protocol|MODBUS RTU Master|
1674 +|Connection|RS485/RS232|
1675 +|Baud rate|2400~~187500|
1676 +|Data bit|8|
1677 +|Parity|Even/ Odd/ None|
1678 +|Stop bit|1/2|
1679 +|Station No.|0~~255|
1712 1712  
1713 -**3)Configure the communication protocol**
1681 +**Address List**
1714 1714  
1715 -[[image:image-20220830140537-1.png]]
1683 +(% class="table-bordered" %)
1684 +|**Type**|**HMI address**|**MODBUS code**|**Range**
1685 +|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1686 +|Word|HDW3500~~HDW7999|4|0~~4499
1716 1716  
1717 -[[image:image-20220830140629-2.png]]
1688 +**Cable Wiring**
1718 1718  
1719 -**4)Cable Wiring**
1690 +* **RS485**
1720 1720  
1721 -Figure
1692 +(% style="text-align:center" %)
1693 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1722 1722  
1723 -[[image:image-20220830094929-1.png]]
1695 +(% style="text-align:center" %)
1696 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1724 1724  
1725 -Pin Definition Diagram
1698 +* **RS232**
1726 1726  
1727 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1700 +(% style="text-align:center" %)
1701 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1728 1728  
1729 -= Create communication with **Omron** PLC =
1703 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1730 1730  
1731 -== **CJ TCP FINS Ethemet  Protocol** ==
1705 +== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1732 1732  
1733 -Supported device:CJ series
1707 +Supported Series: MODBUS RTU CONTROLLER
1734 1734  
1735 -**1)HMI Settings**
1709 +HMI works as MODBUS MASTER connecting with SLAVE.
1736 1736  
1737 -|=**Items**|=**Settings**|=**Note**
1738 -|Protocol|OMRON CJ TCP FINS Ethemet|
1739 -|Connection|Ethernet|
1740 -|Port No.|9600|
1741 -|Device No.|0|
1742 -|HMI No.|0|(((
1743 -
1744 -)))
1711 +The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1745 1745  
1746 -**2)Address List**
1713 +(% style="text-align:center" %)
1714 +[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1747 1747  
1748 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1749 -|Bit|CIO|CIO|CIO d|0~~99999|
1750 -|Bit|W|W|W d|0~~99999|
1751 -|Bit|D|D|D d|0~~99999|
1752 -|Bit|H|H|H d|0~~99999|
1753 -|Bit|A|A|A d|0~~99999|
1754 -|Bit|T|T|T h|0~~99999|
1755 -|Bit|CF|CF|CF d|0~~99999|
1756 -|Bit|FF|FF|FF d|0~~99999|
1757 -|Bit|C|C|C d|0~~99999|
1758 -|Bit|EM0|EM0|EM0 d|0~~99999|
1759 -|Bit|EM1|EM1|EM1 d|0~~99999|
1760 -|Bit|EM2|EM2|EM2 d|0~~99999|
1761 -|Bit|EM3|EM3|EM3 d|0~~99999|
1762 -|Bit|EM4|EM4|EM4 d|0~~99999|
1763 -|Bit|EM5|EM5|EM5 h|0~~99999|
1764 -|Bit|EM6|EM6|EM6 d|0~~99999|
1765 -|Bit|EM7|EM7|EM7 d|0~~99999|
1766 -|Bit|EM8|EM8|EM8 d|0~~99999|
1767 -|Bit|EM9|EM9|EM9 d|0~~99999|
1768 -|Bit|EMA|EMA|EMA d|0~~99999|
1769 -|Bit|EMB|EMB|EMB d|0~~99999|
1770 -|Bit|EMC|EMC|EMC d|0~~99999|
1771 -|Bit|Lamp|Lamp|Lamp d|0~~0|
1772 -|Word|CIO|CIO|CIO d|0~~99999|
1773 -|Word|W|W|W d|0~~99999|
1774 -|Word|D|D|D d|0~~99999|
1775 -|Word|H|H|H d|0~~99999|
1776 -|Word|A|A|A d|0~~99999|
1777 -|Word|T|T|T h|0~~99999|
1778 -|Word|CF|CF|CF d|0~~99999|
1779 -|Word|FF|FF|FF d|0~~99999|
1780 -|Word|C|C|C d|0~~99999|
1781 -|Word|EM0|EM0|EM0 d|0~~99999|
1782 -|Word|EM1|EM1|EM1 d|0~~99999|
1783 -|Word|EM2|EM2|EM2 d|0~~99999|
1784 -|Word|EM3|EM3|EM3 d|0~~99999|
1785 -|Word|EM4|EM4|EM4 d|0~~99999|
1786 -|Word|EM5|EM5|EM5 h|0~~99999|
1787 -|Word|EM6|EM6|EM6 d|0~~99999|
1788 -|Word|EM7|EM7|EM7 d|0~~99999|
1789 -|Word|EM8|EM8|EM8 d|0~~99999|
1790 -|Word|EM9|EM9|EM9 d|0~~99999|
1791 -|Word|EMA|EMA|EMA d|0~~99999|
1792 -|Word|EMB|EMB|EMB d|0~~99999|
1793 -|Word|EMC|EMC|EMC d|0~~99999|
1794 -|Word|IR|IR|IR d|0~~99999|
1795 -|Word|DR|DR|DR d|0~~99999|
1796 1796  
1797 -**3)Configure the communication protocol**
1717 +(% style="text-align:center" %)
1718 +[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1798 1798  
1799 -[[image:image-20220830143348-1.png]]
1800 1800  
1801 -[[image:image-20220830143511-2.png]]
1721 +(% style="text-align:center" %)
1722 +[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1802 1802  
1724 +**HMI Settings**
1803 1803  
1726 +(% class="table-bordered" %)
1727 +|**Items**|**Settings**|**Note**
1728 +|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1729 +|Connection|RS485/RS232|
1730 +|Baud rate|2400~~187500|
1731 +|Data bit|8|
1732 +|Parity|Even/ Odd/ None|
1733 +|Stop bit|1/2|
1734 +|PLC station No.|0~~255|
1804 1804  
1805 -**4)Cable Wiring**
1736 +**Address List**
1806 1806  
1807 -Pin Definition Diagram
1738 +(% class="table-bordered" %)
1739 +|**Type**|**Address Type**|**Function code & Description**
1740 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1741 +|06 (write single register: write a binary value to a holding register)
1742 +|10 (write values to multiple addresses )
1743 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1744 +|06 (write single register: write a binary value to a holding register)
1745 +|10 (write values to multiple addresses )
1746 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1747 +|06 (write single register: write a binary value to a holding register)
1748 +|10 (write values to multiple addresses )
1749 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1750 +|10 (write values to multiple addresses )
1751 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1752 +|05 (Force a single coil to force the on/off state of a logic coil)
1753 +|0F (Write multiple bits, ie write continuously)
1754 +|(% rowspan="3" %)1|02 (Read the input state)
1755 +|05 (Force a single coil to force the on/off state of a logic coil)
1756 +|0F (Write multiple bits)
1757 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1758 +|05 (Force a single coil to force the on/off state of a logic coil)
1759 +|0F (Write multiple bits)
1760 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1761 +|0F (Write multiple bits)
1808 1808  
1809 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1763 +**✎Note:**
1810 1810  
1811 -(% class="wikigeneratedid" %)
1812 -== ==
1765 +* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1766 +* The function codes sent out are the same as those that read and write words.
1813 1813  
1814 -(% class="wikigeneratedid" %)
1815 -== ==
1768 +**Station number for more than one slaves**
1816 1816  
1817 -(% class="wikigeneratedid" %)
1818 -== ==
1770 +If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1819 1819  
1820 -(% class="wikigeneratedid" %)
1821 -== ==
1772 +(% style="text-align:center" %)
1773 +[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1822 1822  
1823 -(% class="wikigeneratedid" %)
1824 -== ==
1775 +**Cable Wiring**
1825 1825  
1826 -== **EC55 Protocol** ==
1777 +* **RS485**
1827 1827  
1779 +(% style="text-align:center" %)
1780 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1781 +
1782 +(% style="text-align:center" %)
1783 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1784 +
1785 +* **RS232**
1786 +
1787 +(% style="text-align:center" %)
1788 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1789 +
1790 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1791 +
1792 +== **MODBUS TCP Slave (All function)** ==
1793 +
1794 +Supported series: MODBUS TCP controller
1795 +
1796 +HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1797 +
1798 +(% style="text-align:center" %)
1799 +[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1800 +
1801 +(% style="text-align:center" %)
1802 +[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1803 +
1804 +
1805 +(% style="text-align:center" %)
1806 +[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1807 +
1808 +**HMI Setting**
1809 +
1810 +(% class="table-bordered" %)
1811 +|**Items**|**Settings**|**Note**
1812 +|Protocol|MODBUS TCP Slave (All function)|
1813 +|Connection|Ethernet|
1814 +|Port No.|502|
1815 +|PLC station No.|1|
1816 +
1817 +**Address List**
1818 +
1819 +(% class="table-bordered" %)
1820 +|**Type**|**Register**|**Function code & Description**
1821 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1822 +|06 (write single register: write a binary value to a holding register)
1823 +|10 (write values to multiple addresses )
1824 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1825 +|06 (write single register: write a binary value to a holding register)
1826 +|10 (write values to multiple addresses )
1827 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1828 +|06 (write single register: write a binary value to a holding register)
1829 +|10 (write values to multiple addresses )
1830 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1831 +|10 (write values to multiple addresses )
1832 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1833 +|05 (Force a single coil to force the on/off state of a logic coil)
1834 +|0F (Write multiple bits, ie write continuously)
1835 +|(% rowspan="3" %)1|02 (Read the input state)
1836 +|05 (Force a single coil to force the on/off state of a logic coil)
1837 +|0F (Write multiple bits)
1838 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1839 +|05 (Force a single coil to force the on/off state of a logic coil)
1840 +|0F (Write multiple bits)
1841 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1842 +|0F (Write multiple bits)
1843 +
1844 +**Communication Settings**
1845 +
1846 +Enable HMI Ethernet in [Project Settings];
1847 +
1848 +(% style="text-align:center" %)
1849 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1850 +
1851 +Set PLC IP in [Device IP] settings;
1852 +
1853 +(% style="text-align:center" %)
1854 +[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1855 +
1856 +**Cable Wiring**
1857 +
1858 +(% style="text-align:center" %)
1859 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1860 +
1861 += **Omron** =
1862 +
1863 +== **EC55** ==
1864 +
1828 1828  Supported device: EC55 temperature instrument
1829 1829  
1830 1830  **HMI Settings**
1831 1831  
1869 +(% class="table-bordered" %)
1832 1832  |**Items**|**Settings**|**Note**
1833 1833  |Protocol|Omron EC55|
1834 1834  |Connection|RS485 (9600, 2, 7, EVEN)|
... ... @@ -1837,6 +1837,7 @@
1837 1837  
1838 1838  **Address List**
1839 1839  
1878 +(% class="table-bordered" %)
1840 1840  |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1841 1841  |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1842 1842  |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
... ... @@ -1882,14 +1882,15 @@
1882 1882  * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1883 1883  * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1884 1884  * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1885 -* [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1924 +* (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1886 1886  
1887 -== **EtherNet/IP NX series Protocol** ==
1926 +== EtherNet/IP NX series ==
1888 1888  
1889 1889  Supported series: Omron NX/NJ series
1890 1890  
1891 1891  **HMI Setting**
1892 1892  
1932 +(% class="table-bordered" %)
1893 1893  |**Items**|**Settings**|**Note**
1894 1894  |Protocol|Omron NX Ethernet/IP|
1895 1895  |Connection|Ethernet|
... ... @@ -1941,224 +1941,183 @@
1941 1941  (% style="text-align:center" %)
1942 1942  [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1943 1943  
1984 +
1944 1944  (% style="text-align:center" %)
1945 1945  [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1946 1946  
1947 1947  **Cable Wiring**
1948 1948  
1949 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1950 -
1951 -= **MODBUS** =
1952 -
1953 -== **MODBUS RTU Master** ==
1954 -
1955 -Supported Series: MODBUS RTU CONTROLLER
1956 -
1957 -HMI works as MODBUS SLAVE connecting with MASTER
1958 -
1959 1959  (% style="text-align:center" %)
1960 -[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1991 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1961 1961  
1993 += **OpenCAN** =
1962 1962  
1963 -(% style="text-align:center" %)
1964 -[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1995 +OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1965 1965  
1997 +This protocol is only available in PI8000 series HMI.
1966 1966  
1967 -(% style="text-align:center" %)
1968 -[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1969 -
1970 1970  **HMI Settings**
1971 1971  
1972 1972  (% class="table-bordered" %)
1973 1973  |**Items**|**Settings**|**Note**
1974 -|Protocol|MODBUS RTU Master|
1975 -|Connection|RS485/RS232|
1976 -|Baud rate|2400~~187500|
1977 -|Data bit|8|
1978 -|Parity|Even/ Odd/ None|
1979 -|Stop bit|1/2|
1980 -|Station No.|0~~255|
2003 +|Protocol|OPENCAN|
2004 +|Connection|CAN port|
2005 +|Baud rate|250000|
1981 1981  
1982 -**Address List**
2007 +**CAN frame setting in HMI**
1983 1983  
1984 -(% class="table-bordered" %)
1985 -|**Type**|**HMI address**|**MODBUS code**|**Range**
1986 -|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1987 -|Word|HDW3500~~HDW7999|4|0~~4499
2009 +Click [OpenCAN setting] button in communication setting window;
1988 1988  
1989 -**Cable Wiring**
2011 +(% style="text-align:center" %)
2012 +[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1990 1990  
1991 -* **RS485**
2014 +Click [Add] to create a new frame;
1992 1992  
1993 1993  (% style="text-align:center" %)
1994 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2017 +[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1995 1995  
1996 -(% style="text-align:center" %)
1997 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2019 +(% class="table-bordered" %)
2020 +|**No**|**Items**|**Description**
2021 +|1|Add|add a frame related to register address
2022 +|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2023 +|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2024 +|4|Modify|Modify the frames in frame management
2025 +|5|Copy|Copy one frame to another
2026 +|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
2027 +|7|Empty|All frames in the list are cleared
2028 +|8|Browse|Displays configuration files in XML format in IE
2029 +|9|OK|Complete the configuration of the frame and exit
1998 1998  
1999 -* **RS232**
2031 +Set CANBUS frame in setting windows
2000 2000  
2001 2001  (% style="text-align:center" %)
2002 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2034 +[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
2003 2003  
2004 -**✎Note:** COM3 only available in PI8000/PI9000 series.
2036 +(% class="table-bordered" %)
2037 +|**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
2038 +|1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
2039 +|2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
2040 +|3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
2041 +|4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
2042 +|5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
2043 +|6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
2044 +Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
2005 2005  
2006 -== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
2046 +**Edit:** Set a bit or word address by its format;
2007 2007  
2008 -Supported Series: MODBUS RTU CONTROLLER
2048 +**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
2049 +)))
2050 +|(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
2051 +|(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
2052 +|(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
2053 +|(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
2054 +|(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
2055 +|(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
2056 +|(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
2057 +|(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
2058 +|(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
2059 +|(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
2060 +|(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
2061 +|9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
2062 +|10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
2063 +|11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
2064 +|12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
2065 +|13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
2066 +|14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
2067 +|15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
2009 2009  
2010 -HMI works as MODBUS MASTER connecting with SLAVE.
2069 +Set CAN address (Read or write operation);
2011 2011  
2012 -The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
2013 -
2014 2014  (% style="text-align:center" %)
2015 -[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2072 +[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
2016 2016  
2074 +(% class="table-bordered" %)
2075 +|**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
2076 +|1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
2077 +|(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
2078 +|(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
2079 +|(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
2080 +|(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
2081 +|(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
2082 +|(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
2083 +* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
2084 +* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
2085 +)))
2086 +|(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
2087 +|(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
2088 +|4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
2089 +|5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
2017 2017  
2018 -(% style="text-align:center" %)
2019 -[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2091 +**Multiple Packages Settings**
2020 2020  
2021 -
2022 2022  (% style="text-align:center" %)
2023 -[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2094 +[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
2024 2024  
2025 -**HMI Settings**
2096 +Check [Multiple packages supported] to open [Multiple package data] window, as below show.
2026 2026  
2027 -(% class="table-bordered" %)
2028 -|**Items**|**Settings**|**Note**
2029 -|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2030 -|Connection|RS485/RS232|
2031 -|Baud rate|2400~~187500|
2032 -|Data bit|8|
2033 -|Parity|Even/ Odd/ None|
2034 -|Stop bit|1/2|
2035 -|PLC station No.|0~~255|
2098 +Select Multiple package type
2036 2036  
2037 -**Address List**
2100 +* Not Multiple packages
2101 +* J1939 Multiple packages
2102 +* Customized Multiple packages
2038 2038  
2039 -(% class="table-bordered" %)
2040 -|**Type**|**Address Type**|**Function code & Description**
2041 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2042 -|06 (write single register: write a binary value to a holding register)
2043 -|10 (write values to multiple addresses )
2044 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2045 -|06 (write single register: write a binary value to a holding register)
2046 -|10 (write values to multiple addresses )
2047 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2048 -|06 (write single register: write a binary value to a holding register)
2049 -|10 (write values to multiple addresses )
2050 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2051 -|10 (write values to multiple addresses )
2052 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2053 -|05 (Force a single coil to force the on/off state of a logic coil)
2054 -|0F (Write multiple bits, ie write continuously)
2055 -|(% rowspan="3" %)1|02 (Read the input state)
2056 -|05 (Force a single coil to force the on/off state of a logic coil)
2057 -|0F (Write multiple bits)
2058 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2059 -|05 (Force a single coil to force the on/off state of a logic coil)
2060 -|0F (Write multiple bits)
2061 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2062 -|0F (Write multiple bits)
2104 +Click [Edit Receive data] for [Receive] settings
2063 2063  
2064 -**✎Note:**
2106 +* Start code+ Total length (J1939)
2065 2065  
2066 -* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2067 -* The function codes sent out are the same as those that read and write words.
2108 +(% style="text-align:center" %)
2109 +[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2068 2068  
2069 -**Station number for more than one slaves**
2111 +As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2070 2070  
2071 -If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2113 +* Start code + Data max length (J1939)
2072 2072  
2073 2073  (% style="text-align:center" %)
2074 -[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2116 +[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2075 2075  
2076 -**Cable Wiring**
2118 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2077 2077  
2078 -* **RS485**
2120 +* Data max length (J1939)
2079 2079  
2080 2080  (% style="text-align:center" %)
2081 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2123 +[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2082 2082  
2083 -(% style="text-align:center" %)
2084 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2125 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2085 2085  
2086 -* **RS232**
2127 +* Customized multiple package
2087 2087  
2088 2088  (% style="text-align:center" %)
2089 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2130 +[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
2090 2090  
2091 -**✎Note:** COM3 only available in PI8000/PI9000 series.
2132 +As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
2092 2092  
2093 -== **MODBUS TCP Slave (All function)** ==
2134 +Click [Edit Send data] for [Send] setting
2094 2094  
2095 -Supported series: MODBUS TCP controller
2136 +* J1939
2096 2096  
2097 -HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
2098 -
2099 2099  (% style="text-align:center" %)
2100 -[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2139 +[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2101 2101  
2102 -(% style="text-align:center" %)
2103 -[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2141 +[Data] is all data to be sent.
2104 2104  
2143 +Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2105 2105  
2106 -(% style="text-align:center" %)
2107 -[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2145 +* Customized multiple package
2108 2108  
2109 -**HMI Setting**
2110 -
2111 -(% class="table-bordered" %)
2112 -|**Items**|**Settings**|**Note**
2113 -|Protocol|MODBUS TCP Slave (All function)|
2114 -|Connection|Ethernet|
2115 -|Port No.|502|
2116 -|PLC station No.|1|
2117 -
2118 -**Address List**
2119 -
2120 -(% class="table-bordered" %)
2121 -|**Type**|**Register**|**Function code & Description**
2122 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2123 -|06 (write single register: write a binary value to a holding register)
2124 -|10 (write values to multiple addresses )
2125 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2126 -|06 (write single register: write a binary value to a holding register)
2127 -|10 (write values to multiple addresses )
2128 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2129 -|06 (write single register: write a binary value to a holding register)
2130 -|10 (write values to multiple addresses )
2131 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2132 -|10 (write values to multiple addresses )
2133 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2134 -|05 (Force a single coil to force the on/off state of a logic coil)
2135 -|0F (Write multiple bits, ie write continuously)
2136 -|(% rowspan="3" %)1|02 (Read the input state)
2137 -|05 (Force a single coil to force the on/off state of a logic coil)
2138 -|0F (Write multiple bits)
2139 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2140 -|05 (Force a single coil to force the on/off state of a logic coil)
2141 -|0F (Write multiple bits)
2142 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2143 -|0F (Write multiple bits)
2144 -
2145 -**Communication Settings**
2146 -
2147 -Enable HMI Ethernet in [Project Settings];
2148 -
2149 2149  (% style="text-align:center" %)
2150 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2148 +[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2151 2151  
2152 -Set PLC IP in [Device IP] settings;
2150 +[Data] is all data to be sent.
2153 2153  
2154 -(% style="text-align:center" %)
2155 -[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2152 +As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2156 2156  
2157 2157  **Cable Wiring**
2158 2158  
2159 2159  (% style="text-align:center" %)
2160 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2157 +[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2161 2161  
2159 +**✎Note:** The address interval between each frame need to be more than a word address;
2160 +
2162 2162  = **SHIMADEN** =
2163 2163  
2164 2164  == **FP23** ==
... ... @@ -2958,168 +2958,3 @@
2958 2958  **Cable Wiring**
2959 2959  
2960 2960  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2961 -
2962 -
2963 -= **OpenCAN** =
2964 -
2965 -OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
2966 -
2967 -This protocol is only available in PI8000 series HMI.
2968 -
2969 -**HMI Settings**
2970 -
2971 -|**Items**|**Settings**|**Note**
2972 -|Protocol|OPENCAN|
2973 -|Connection|CAN port|
2974 -|Baud rate|250000|
2975 -
2976 -**CAN frame setting in HMI**
2977 -
2978 -Click [OpenCAN setting] button in communication setting window;
2979 -
2980 -(% style="text-align:center" %)
2981 -[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
2982 -
2983 -Click [Add] to create a new frame;
2984 -
2985 -(% style="text-align:center" %)
2986 -[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
2987 -
2988 -|**No**|**Items**|**Description**
2989 -|1|Add|add a frame related to register address
2990 -|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2991 -|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2992 -|4|Modify|Modify the frames in frame management
2993 -|5|Copy|Copy one frame to another
2994 -|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
2995 -|7|Empty|All frames in the list are cleared
2996 -|8|Browse|Displays configuration files in XML format in IE
2997 -|9|OK|Complete the configuration of the frame and exit
2998 -
2999 -Set CANBUS frame in setting windows
3000 -
3001 -(% style="text-align:center" %)
3002 -[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3003 -
3004 -|**No**|**Items**|**Description**
3005 -|1|ID|Set the ID of a can frame in hexadecimal format;
3006 -|2|ID assign|split the ID by PF, PS, and SA;
3007 -|3|Frame type|Select Standard frame or Extended Frame;
3008 -|4|Frame format|Select between data frame and remote Frame;
3009 -|5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3010 -|6|Use address|(((
3011 -Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3012 -
3013 -**Edit:** Set a bit or word address by its format;
3014 -
3015 -**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3016 -)))
3017 -|(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3018 -|Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3019 -|Feedback mode: feedback mode includes no response, confirm response and data response;
3020 -|No response: the device or touch screen will not receive feedback;
3021 -|Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3022 -|Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3023 -|response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3024 -|Response timeout: sets whether the response frame timeout;
3025 -|(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3026 -|Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3027 -|Manually send: a manually send tick indicates only one send;
3028 -|9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3029 -|10|Note|Fill the text to explain the meaning of the frame;
3030 -|11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3031 -|12|Current operation display|Display the description of current operation;
3032 -|13|Add|Add a new frame;
3033 -|14|Save frame|Save the configured frame format;
3034 -|15|Cancel|Cancel the frame configuration;
3035 -
3036 -Set CAN address (Read or write operation);
3037 -
3038 -(% style="text-align:center" %)
3039 -[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3040 -
3041 -|**No.**|**Item**|**Description**
3042 -|1|Current address|Displays the register type and register address set by the user in the data access interface
3043 -|(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3044 -|If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3045 -|If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3046 -|(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3047 -|If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3048 -|If the trigger condition is a writing operation, there are two situations:(((
3049 -* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3050 -* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3051 -)))
3052 -|(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3053 -|If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3054 -|4|Add|Add current configuration
3055 -|5|Close|Close the configuration window to exit
3056 -
3057 -**Multiple Packages Settings**
3058 -
3059 -(% style="text-align:center" %)
3060 -[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3061 -
3062 -Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3063 -
3064 -Select Multiple package type
3065 -
3066 -* Not Multiple packages
3067 -* J1939 Multiple packages
3068 -* Customized Multiple packages
3069 -
3070 -Click [Edit Receive data] for [Receive] settings
3071 -
3072 -* Start code+ Total length (J1939)
3073 -
3074 -(% style="text-align:center" %)
3075 -[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3076 -
3077 -As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3078 -
3079 -* Start code + Data max length (J1939)
3080 -
3081 -(% style="text-align:center" %)
3082 -[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3083 -
3084 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3085 -
3086 -* Data max length (J1939)
3087 -
3088 -(% style="text-align:center" %)
3089 -[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3090 -
3091 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3092 -
3093 -* Customized multiple package
3094 -
3095 -(% style="text-align:center" %)
3096 -[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3097 -
3098 -As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3099 -
3100 -Click [Edit Send data] for [Send] setting
3101 -
3102 -* J1939
3103 -
3104 -(% style="text-align:center" %)
3105 -[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3106 -
3107 -[Data] is all data to be sent.
3108 -
3109 -Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3110 -
3111 -* Customized multiple package
3112 -
3113 -(% style="text-align:center" %)
3114 -[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3115 -
3116 -[Data] is all data to be sent.
3117 -
3118 -As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3119 -
3120 -**Cable Wiring**
3121 -
3122 -(% style="text-align:center" %)
3123 -[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3124 -
3125 -**✎Note:** The address interval between each frame need to be more than a word address;
image-20220830094600-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -40.4 KB
Content
image-20220830094657-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -53.4 KB
Content
image-20220830094929-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -90.4 KB
Content
image-20220830095131-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -25.7 KB
Content
image-20220830140537-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -35.2 KB
Content
image-20220830140629-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -48.4 KB
Content
image-20220830141138-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -82.9 KB
Content
image-20220830143348-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -35.9 KB
Content
image-20220830143511-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -46.3 KB
Content