... ... @@ -1896,7 +1896,7 @@
1896 1896  
1897 1897  == **LOGO Ethernet** ==
1898 1898  
1899 -Supported Series: Siemens Logo
1899 +Supported Series: Siemens Logo 0BA0 series
1900 1900  
1901 1901  **HMI Settings**
1902 1902  
... ... @@ -1959,9 +1959,8 @@
1959 1959  Set PLC IP in [Device IP] settings;
1960 1960  
1961 1961  (% style="text-align:center" %)
1962 -[[image:12.PLC Protocol_html_573fc64ad393cd4f.png||data-xwiki-image-style-alignment="center" height="655" width="379" class="img-thumbnail"]]
1962 +[[image:SiemensLOGODeviceIP.png]]
1963 1963  
1964 -
1965 1965  Enable HMI Ethernet in [Project Settings];
1966 1966  
1967 1967  (% style="text-align:center" %)
... ... @@ -2013,7 +2013,7 @@
2013 2013  [[image:S7-XXXCommunication Settings.png]]
2014 2014  
2015 2015  (% style="text-align:center" %)
2016 -[[image:S7-XXXCommunication SettingsPI.png]]
2015 +[[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2017 2017  
2018 2018  **Address List**
2019 2019  
... ... @@ -2488,12 +2488,10 @@
2488 2488  
2489 2489  **✎Note:** COM3 only available in PI8000/PI9000 series.
2490 2490  
2490 +== HMI and Wecon LX5V serial communication ==
2491 2491  
2492 -== **1. HMI and Wecon LX5V serial communication** ==
2493 -
2494 2494  This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2495 2495  
2496 -
2497 2497  **Software configuration of PLC**
2498 2498  
2499 2499  **1)PLC programming software**
... ... @@ -2568,7 +2568,7 @@
2568 2568  
2569 2569  The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
2570 2570  
2571 -== **2. HMI and Wecon LX5V-N Ethernet communication** ==
2568 +== HMI and Wecon LX5V-N Ethernet communication ==
2572 2572  
2573 2573  (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2574 2574  
... ... @@ -2641,3 +2641,36 @@
2641 2641  [[image:image-20220811170248-1.png]]
2642 2642  
2643 2643  The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
2641 +
2642 += **Schneider MODBUS RTU** =
2643 +
2644 +**HMI Setting**
2645 +
2646 +|=**Parameters**|=**Recommended**|=**Notes**
2647 +|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2648 +|Connection|RS485|
2649 +|**Baud rate**|19200|
2650 +|**Data bit**|8|
2651 +|**Parity**|Even|
2652 +|**Stop bit**|1|
2653 +|**PLC station No.**|1|
2654 +
2655 +**PLC Setting**
2656 +
2657 +|=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2658 +
2659 +**Device Address**
2660 +
2661 +|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2662 +|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2663 +|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2664 +|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2665 +|W|MW|DDDDDD|0 ~~ 999999|Output register
2666 +|DW|MD|DDDDDD|0 ~~ 999999|Output register
2667 +
2668 +**Wiring Diagram**
2669 +
2670 +**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2671 +
2672 +(% style="text-align:center" %)
2673 +[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
S7-XXXCommunication SettingsPIStudio.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +24.9 KB
Content
SiemensLOGODeviceIP.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +24.9 KB
Content
image-20220817154212-1.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Stone
Size
... ... @@ -1,0 +1,1 @@
1 +51.8 KB
Content