... ... @@ -1896,7 +1896,7 @@
1896 1896  
1897 1897  == **LOGO Ethernet** ==
1898 1898  
1899 -Supported Series: Siemens Logo
1899 +Supported Series: Siemens Logo 0BA0 series
1900 1900  
1901 1901  **HMI Settings**
1902 1902  
... ... @@ -1959,9 +1959,8 @@
1959 1959  Set PLC IP in [Device IP] settings;
1960 1960  
1961 1961  (% style="text-align:center" %)
1962 -[[image:12.PLC Protocol_html_573fc64ad393cd4f.png||data-xwiki-image-style-alignment="center" height="655" width="379" class="img-thumbnail"]]
1962 +[[image:SiemensLOGODeviceIP.png]]
1963 1963  
1964 -
1965 1965  Enable HMI Ethernet in [Project Settings];
1966 1966  
1967 1967  (% style="text-align:center" %)
... ... @@ -2488,12 +2488,10 @@
2488 2488  
2489 2489  **✎Note:** COM3 only available in PI8000/PI9000 series.
2490 2490  
2490 +== HMI and Wecon LX5V serial communication ==
2491 2491  
2492 -== **1. HMI and Wecon LX5V serial communication** ==
2493 -
2494 2494  This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2495 2495  
2496 -
2497 2497  **Software configuration of PLC**
2498 2498  
2499 2499  **1)PLC programming software**
... ... @@ -2568,7 +2568,7 @@
2568 2568  
2569 2569  The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
2570 2570  
2571 -== **2. HMI and Wecon LX5V-N Ethernet communication** ==
2568 +== HMI and Wecon LX5V-N Ethernet communication ==
2572 2572  
2573 2573  (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2574 2574  
... ... @@ -2641,3 +2641,47 @@
2641 2641  [[image:image-20220811170248-1.png]]
2642 2642  
2643 2643  The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
2641 +
2642 += **Schneider MODBUS RTU** =
2643 +
2644 +**HMI Setting**
2645 +
2646 +|=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2647 +|=**PLC type**|(% colspan="2" %)Schneider MODBUS RTU|
2648 +|=**PLC I/F**|RS485|RS232/RS485|
2649 +|=**Baud rate**|19200|9600~~115200|
2650 +|=**Data bits**|8|7,8|
2651 +|=**Parity**|Even|Even, Odd, None|
2652 +|=**Stop bits**|1|1,2|
2653 +|=**PLC sta. no.**|1|0-255|
2654 +
2655 +|=(% scope="row" style="width: 266px;" %)**Online simulator**|(% style="width:319px" %)YES|(% style="width:336px" %)**Broadcast command**|(% style="width:155px" %)YES
2656 +|=(% style="width: 266px;" %)**Extend address mode**|(% style="width:319px" %)YES|(% style="width:336px" %) |(% style="width:155px" %)
2657 +
2658 +**PLC Setting**
2659 +
2660 +|=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2661 +
2662 +**Device Address**
2663 +
2664 +|=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2665 +|=B|%IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2666 +|=B|%QX|DDDDDo|0 ~~ 655357|Write multiple coils
2667 +|=B|%MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2668 +|=B|%M|DDDDD|0 ~~ 65535|Output bit
2669 +|=B|%MW_Bit|DDDDDdd|0 ~~ 6553515|Output register bit (decimal)
2670 +|=B|1x|DDDDD|0 ~~ 65535|Input bit (read only)
2671 +|=B|0x_multi_coils|DDDDD|0 ~~ 65535|Write multiple coils
2672 +|=B|3x_Bit|DDDDDdd|0 ~~ 6553515|Input register bit (read only)
2673 +|=W|%MW|DDDDDD|0 ~~ 999999|Output register
2674 +|=DW|%MD|DDDDDD|0 ~~ 999999|Output register
2675 +|=W|3x|DDDDD|0 ~~ 65535|Input Register (read only)
2676 +|=DW|5x|DDDDD|0 ~~ 65535|4x double word swap
2677 +|=DW|6x|DDDDD|0 ~~ 65535|4x single word write
2678 +
2679 +**Wiring Diagram**
2680 +
2681 +**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2682 +
2683 +(% style="text-align:center" %)
2684 +[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]