... ... @@ -2640,3 +2640,34 @@ 2640 2640 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. 2641 2641 2642 2642 = **Schneider MODBUS RTU** = 2643 + 2644 +**HMI Setting** 2645 + 2646 +|=(% scope="row" %)**Parameters**|=**Recommended**|=**Notes** 2647 +|=**Protocol**|(% colspan="1" %)Schneider MODBUS RTU| 2648 +|=Connection|RS485| 2649 +|=**Baud rate**|19200| 2650 +|=**Data bit**|8| 2651 +|=**Parity**|Even| 2652 +|=**Stop bit**|1| 2653 +|=**PLC station No.**|1| 2654 + 2655 +**PLC Setting** 2656 + 2657 +|=(% scope="row" %)**Communication mode**|Modbus RTU protocol 2658 + 2659 +**Device Address** 2660 + 2661 +|=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo** 2662 +|=B|IX|DDDDDo|0 ~~ 655357|Input bit (read only) 2663 +|=B|QX|DDDDDo|0 ~~ 655357|Write multiple coils 2664 +|=B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal) 2665 +|=W|MW|DDDDDD|0 ~~ 999999|Output register 2666 +|=DW|MD|DDDDDD|0 ~~ 999999|Output register 2667 + 2668 +**Wiring Diagram** 2669 + 2670 +**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector. 2671 + 2672 +(% style="text-align:center" %) 2673 +[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
- image-20220817154212-1.jpeg
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Stone - Size
-