... ... @@ -2640,3 +2640,34 @@
2640 2640  The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
2641 2641  
2642 2642  = **Schneider MODBUS RTU** =
2643 +
2644 +**HMI Setting**
2645 +
2646 +|=**Parameters**|=**Recommended**|=**Notes**
2647 +|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2648 +|Connection|RS485|
2649 +|**Baud rate**|19200|
2650 +|**Data bit**|8|
2651 +|**Parity**|Even|
2652 +|**Stop bit**|1|
2653 +|**PLC station No.**|1|
2654 +
2655 +**PLC Setting**
2656 +
2657 +|=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2658 +
2659 +**Device Address**
2660 +
2661 +|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2662 +|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2663 +|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2664 +|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2665 +|W|MW|DDDDDD|0 ~~ 999999|Output register
2666 +|DW|MD|DDDDDD|0 ~~ 999999|Output register
2667 +
2668 +**Wiring Diagram**
2669 +
2670 +**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2671 +
2672 +(% style="text-align:center" %)
2673 +[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]