Changes for page 12 PLC Protocol OLD
Last modified by Mora Zhou on 2024/12/05 14:53
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 1 removed)
Details
- Page properties
-
- Content
-
... ... @@ -2640,34 +2640,3 @@ 2640 2640 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. 2641 2641 2642 2642 = **Schneider MODBUS RTU** = 2643 - 2644 -**HMI Setting** 2645 - 2646 -|=(% scope="row" %)**Parameters**|=**Recommended**|=**Notes** 2647 -|=**Protocol**|(% colspan="1" %)Schneider MODBUS RTU| 2648 -|=Connection|RS485| 2649 -|=**Baud rate**|19200| 2650 -|=**Data bit**|8| 2651 -|=**Parity**|Even| 2652 -|=**Stop bit**|1| 2653 -|=**PLC station No.**|1| 2654 - 2655 -**PLC Setting** 2656 - 2657 -|=(% scope="row" %)**Communication mode**|Modbus RTU protocol 2658 - 2659 -**Device Address** 2660 - 2661 -|=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo** 2662 -|=B|IX|DDDDDo|0 ~~ 655357|Input bit (read only) 2663 -|=B|QX|DDDDDo|0 ~~ 655357|Write multiple coils 2664 -|=B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal) 2665 -|=W|MW|DDDDDD|0 ~~ 999999|Output register 2666 -|=DW|MD|DDDDDD|0 ~~ 999999|Output register 2667 - 2668 -**Wiring Diagram** 2669 - 2670 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector. 2671 - 2672 -(% style="text-align:center" %) 2673 -[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
- image-20220817154212-1.jpeg
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -51.8 KB - Content