Changes for page 12 PLC Protocol OLD

Last modified by Mora Zhou on 2024/12/05 14:53

From version 38.1
edited by Stone Wu
on 2022/08/22 11:26
Change comment: There is no comment for this version
To version 5.1
edited by Joey123
on 2022/07/09 14:31
Change comment: Replaced user [xwiki:XWiki.Joey] in fields [author, contentAuthor] to user [xwiki:XWiki.Joey123]

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -PIStudio.WebHome
1 +PIStudio.1 User Manual.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.Joey123
Content
... ... @@ -18,7 +18,7 @@
18 18  
19 19  User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20 20  
21 -= **Communication Settings** =
21 += **Protocol Selection & Communication Parameters** =
22 22  
23 23  For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24 24  
... ... @@ -29,26 +29,32 @@
29 29  (% style="text-align:center" %)
30 30  [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31 31  
32 -* Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 -* Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 -* Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 -* Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 -* Delay Time(ms): The speed at which the HMI communicates with the device.
37 -* Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 -* Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
32 +Wait Timeout(ms): The time HMI waits for a response from the PLC.
39 39  
34 +Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
35 +
36 +Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
37 +
38 +Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
39 +
40 +Delay Time(ms): The speed at which the HMI communicates with the device.
41 +
42 +Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
43 +
44 +Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
45 +
40 40  **Operating Procedure**
41 41  
42 -After creating the [Quick_Start] project,select the [Project]->[Communication].
48 +1) After creating the [Quick_Start] project,select the [Project]->[Communication].
43 43  
44 44  (% style="text-align:center" %)
45 45  [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46 46  
47 -Click “Setting” to open protocol setting windows.
53 +2) Click “Setting” to open protocol setting windows.
48 48  
49 49  (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50 50  
51 -Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
57 +3) Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52 52  
53 53  * Serial port:
54 54  
... ... @@ -69,7 +69,7 @@
69 69  
70 70  (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71 71  
72 -About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
78 +4) About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73 73  
74 74  * Serial port:
75 75  
... ... @@ -83,184 +83,8 @@
83 83  (% style="text-align:center" %)
84 84  [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85 85  
86 -Click [OK] button to save settings and close the dialog;
92 +5) Click [OK] button to save settings and close the dialog;
87 87  
88 -= Create communication with WECON PLC =
89 -
90 -== HMI settings ==
91 -
92 -**Download PIStudio Software**
93 -
94 -Please visit the link below to get the latest version PIstudio for HMI programming:
95 -
96 -* [[Download>>https://ftp.we-con.com.cn/Download/Software/PIStudio20211210.zip]] or [[Download>>https://drive.google.com/open?id=1Im7YS2rtnRI7yFIHmqHDVPBUyWahqSXN]]
97 -
98 -**Create a new HMI project connect with PLC**
99 -
100 -Check the link below for the video to show you how to get started with a new project
101 -
102 -* [[Video>>https://drive.google.com/open?id=0B0j9uum1UPXbMENtRlF2VzdQdHc]]
103 -
104 -For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
105 -
106 -**General**
107 -
108 -HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
109 -
110 -**Protocol settings**
111 -
112 -The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
113 -
114 -Please select the protocol, when creating a new project.
115 -
116 -1. Select the COM port for communication;
117 -1. PLC type: It means PLC brand, like WECON;
118 -1. PLC model: It shows the model of PLC, such as LX3V;
119 -
120 -(% style="text-align:center" %)
121 -[[image:image-20220819093729-1.png]]
122 -
123 -If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
124 -
125 -(% style="text-align:center" %)
126 -[[image:image-20220819093729-2.png]]
127 -
128 -
129 -The steps to change the protocol for project are as follows.
130 -
131 -1. Click [Setting] to open the [Communication device] window;
132 -1. Select communication port, such as COM1;
133 -1. Select Serial port for communication, such as RS422;
134 -1. Select device type (device brand), such as WECON;
135 -1. Select the protocol for communication, such as WECON LX3V;
136 -
137 -(% style="text-align:center" %)
138 -[[image:image-20220819093729-3.png]]
139 -
140 -**Parameter settings**
141 -
142 -The parameters settings are in [Communication] window, shown as following below.
143 -
144 -1. Click [Setting] to open the [COM port setting] window;
145 -1. Set the parameters such as [connection], [Baud rate] and so on;
146 -
147 -(% style="text-align:center" %)
148 -[[image:image-20220819093729-4.png||height="636" width="818"]]
149 -
150 -(% start="3" %)
151 -1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
152 -
153 -(% style="text-align:center" %)
154 -[[image:image-20220819093729-5.png]]
155 -
156 -**Set PLC address in HMI screen**
157 -
158 -1. Place the objects to HMI screen;
159 -1. Double-click the object to open the setting window;
160 -1. Click “Edit” to open the address setting windows;
161 -1. Connection: select the serial port in HMI;
162 -1. Address type: All the PLC address types will be display in this list, such as M;
163 -1. Address No.: Please input the number of this address, such as 0;
164 -
165 -[[image:image-20220819093729-6.jpeg]]
166 -
167 -**Communication cable**
168 -
169 -In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
170 -
171 -(% style="text-align:center" %)
172 -[[image:image-20220819093729-7.png]]
173 -
174 -**HMI communication PLC use Modbus **
175 -
176 -* HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
177 -* PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
178 -
179 -== PLC settings ==
180 -
181 -**Download PLC Software**
182 -
183 -Please visit below link to get the latest version PLC Editor for HMI programming
184 -
185 -* LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
186 -* LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
187 -
188 -**Start a new PLC project**
189 -
190 -Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
191 -
192 -(% style="text-align:center" %)
193 -[[image:image-20220819101447-3.jpeg]]
194 -
195 -
196 -
197 -**Add a new instruction **
198 -
199 -Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
200 -
201 -(% style="text-align:center" %)
202 -[[image:image-20220819105530-1.png]]
203 -
204 -You could also select the ladder symbol from the menu bar directly.
205 -
206 -[[image:image-20220819093729-11.png]]
207 -
208 -[[image:image-20220819093729-12.png]]
209 -
210 -**Add comment to PLC program**
211 -
212 -(% style="text-align:center" %)
213 -[[image:image-20220819105630-3.png]]
214 -
215 -**Add the statement to PLC program**
216 -
217 -Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
218 -
219 -(% style="text-align:center" %)
220 -[[image:image-20220819105644-4.png]]
221 -
222 -**Compile **
223 -
224 -You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
225 -
226 -[[image:image-20220819093729-15.png]]
227 -
228 -**Download setting **
229 -
230 -Click on “Transfer Setup” to select download mode.
231 -
232 -[[image:image-20220820150853-1.png]]**Download PLC program to PLC**
233 -
234 -Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
235 -
236 -[[image:image-20220819093729-17.png]]
237 -
238 -**Upload PLC program from PLC**
239 -
240 -Read the PLC program from PLC to computer.
241 -
242 -[[image:image-20220819093729-18.png]]
243 -
244 -**Device monitor**
245 -
246 -Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
247 -
248 -[[image:image-20220819093730-19.png]]
249 -
250 -**Online monitor**
251 -
252 -Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
253 -
254 -[[image:image-20220819093730-20.png]]
255 -
256 -**Monitor edit**
257 -
258 -In this mode, you could edit the PLC program during PLC is running. 
259 -
260 -
261 -(% style="text-align:center" %)
262 -[[image:image-20220819105928-9.png||height="229" width="669"]]
263 -
264 264  = **Allen-Bradley** =
265 265  
266 266  == **FreeTag Ethernet/IP (CompactLogix)** ==
... ... @@ -277,19 +277,19 @@
277 277  
278 278  **PLC Setting**
279 279  
280 -Create new tags
110 +1) Create new tags
281 281  
282 282  (% style="text-align:center" %)
283 283  [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
284 284  
285 -Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
115 +2) Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
286 286  
287 287  (% style="text-align:center" %)
288 288  [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
289 289  
290 -Import labels, please open [Communication] window and click [Import label];
120 +3) Import labels, please open [Communication] window and click [Import label];
291 291  
292 -Select csv file, all tags will be displayed as belows;
122 +4) Select csv file, all tags will be displayed as belows;
293 293  
294 294  (% style="text-align:center" %)
295 295  [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
... ... @@ -305,12 +305,12 @@
305 305  
306 306  **Communication settings in HMI**
307 307  
308 -Enable HMI Ethernet in [Project Settings];
138 +1) Enable HMI Ethernet in [Project Settings];
309 309  
310 310  (% style="text-align:center" %)
311 311  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
312 312  
313 -Set PLC IP in [Device IP] settings;
143 +2) Set PLC IP in [Device IP] settings;
314 314  
315 315  (% style="text-align:center" %)
316 316  [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
... ... @@ -364,13 +364,17 @@
364 364  
365 365  The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
366 366  
367 -* **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
368 -* **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
369 -* **Word address S:** The word address ranges from 0 to 255 (decimal).
370 -* **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
197 +**Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
371 371  
199 +**Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
200 +
201 +**Word address S:** The word address ranges from 0 to 255 (decimal).
202 +
203 +**Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
204 +
372 372  **✎Note: **Register address TP, CS, CP, N, F and TS address edit tare he same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
373 373  
207 +
374 374  |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
375 375  |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
376 376  |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
... ... @@ -399,14 +399,14 @@
399 399  
400 400  **Operating Procedures**
401 401  
402 -Select [Barcode Scanner];
236 +1) Select [Barcode Scanner];
403 403  
404 404  (% style="text-align:center" %)
405 405  [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
406 406  
407 -Set address for receiving;
241 +2) Set address for receiving;
408 408  
409 -Set correct length;
243 +3) Set correct length;
410 410  
411 411  (% style="text-align:center" %)
412 412  [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
... ... @@ -413,10 +413,12 @@
413 413  
414 414  **✎Note:**
415 415  
416 -* The protocol uploads the information acquired by the USB scanner to the HMI;
417 -* The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
418 -* Recommended model: DELI 14880 barcode scanner;
250 +1) The protocol uploads the information acquired by the USB scanner to the HMI;
419 419  
252 +2) The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
253 +
254 +3) Recommended model: DELI 14880 barcode scanner;
255 +
420 420  = **Hitachi EHV Series (Ethernet)** =
421 421  
422 422  Supported series: Hitachi EHV series
... ... @@ -488,12 +488,12 @@
488 488  
489 489  **Communication settings in HMI**
490 490  
491 -Enable HMI Ethernet in [Project Settings];
327 +1) Enable HMI Ethernet in [Project Settings];
492 492  
493 493  (% style="text-align:center" %)
494 494  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
495 495  
496 -Set PLC IP in [Device IP] settings;
332 +2) Set PLC IP in [Device IP] settings;
497 497  
498 498  (% style="text-align:center" %)
499 499  [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
... ... @@ -500,12 +500,12 @@
500 500  
501 501  **PLC Configuration**
502 502  
503 -Connect with PLC, select[Online mode];
339 +1) Connect with PLC, select[Online mode];
504 504  
505 505  (% style="text-align:center" %)
506 506  [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
507 507  
508 -Set IP address, it is the same LAN parameters with HMI;
344 +2) Set IP address, it is the same LAN parameters with HMI;
509 509  
510 510  (% style="text-align:center" %)
511 511  [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
... ... @@ -514,22 +514,22 @@
514 514  
515 515  **PLC Monitor Mode**
516 516  
517 -Connect with PLC and choose to “online” mode
353 +1) Connect with PLC and choose to “online” mode
518 518  
519 519  (% style="text-align:center" %)
520 520  [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
521 521  
522 -Open I/O monitor sheet1
358 +2) Open I/O monitor sheet1
523 523  
524 524  (% style="text-align:center" %)
525 525  [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
526 526  
527 -During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
363 +3) During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
528 528  
529 529  (% style="text-align:center" %)
530 530  [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
531 531  
532 -Enter the register address, click OK to view the value of the register.
368 +4) Enter the register address, click OK to view the value of the register.
533 533  
534 534  (% style="text-align:center" %)
535 535  [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
... ... @@ -539,9 +539,10 @@
539 539  
540 540  **✎Note:**
541 541  
542 -* Both word registers and bit registers support even continuous read/write functions;
543 -* The range of registers is based on the specific PLC type;
378 +1) Both word registers and bit registers support even continuous read/write functions;
544 544  
380 +2) The range of registers is based on the specific PLC type;
381 +
545 545  **Cable Wiring**
546 546  
547 547  (% style="text-align:center" %)
... ... @@ -594,18 +594,18 @@
594 594  (% style="text-align:center" %)
595 595  [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
596 596  
597 -Extended tag name
434 +1) Extended tag name
598 598  
599 -Address range for the extended tag.
436 +2) Address range for the extended tag.
600 600  
601 601  **Communication Settings**
602 602  
603 -Enable HMI Ethernet in [Project Settings];
440 +1) Enable HMI Ethernet in [Project Settings];
604 604  
605 605  (% style="text-align:center" %)
606 606  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
607 607  
608 -Set PLC IP in [Device IP] settings;
445 +2) Set PLC IP in [Device IP] settings;
609 609  
610 610  (% style="text-align:center" %)
611 611  [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
... ... @@ -648,18 +648,20 @@
648 648  
649 649  **✎Note:**
650 650  
651 -* In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
652 -* The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
653 -* All bit registers are in the form of bits in word, and the range is the same as the word register;
488 +1) In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
654 654  
490 +2) The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
491 +
492 +3) All bit registers are in the form of bits in word, and the range is the same as the word register;
493 +
655 655  **Communication settings in HMI**
656 656  
657 -Enable HMI Ethernet in [Project Settings];
496 +1) Enable HMI Ethernet in [Project Settings];
658 658  
659 659  (% style="text-align:center" %)
660 660  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
661 661  
662 -Set PLC IP in [Device IP] settings;
501 +2) Set PLC IP in [Device IP] settings;
663 663  
664 664  (% style="text-align:center" %)
665 665  [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
... ... @@ -706,7 +706,7 @@
706 706  
707 707  **Cable Wiring**
708 708  
709 -* **RS485**
548 +**1) RS485**
710 710  
711 711  (% style="text-align:center" %)
712 712  [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
... ... @@ -714,13 +714,15 @@
714 714  (% style="text-align:center" %)
715 715  [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
716 716  
717 -* **RS422**
556 +**2)RS422**
718 718  
719 719  (% style="text-align:center" %)
720 720  [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
721 721  
722 -**✎Note:** COM3 only available in PI8000/PI9000 series.
561 +**✎Note:**
723 723  
563 +COM3 only available in PI8000/PI9000 series.
564 +
724 724  == **FX5U Ethernet** ==
725 725  
726 726  Mitsubishi FX5U series PLC
... ... @@ -765,32 +765,32 @@
765 765  
766 766  **PLC Settings (GX Works 3)**
767 767  
768 -Find the [Ethernet port] in the navigation area.
609 +1) Find the [Ethernet port] in the navigation area.
769 769  
770 770  (% style="text-align:center" %)
771 771  [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
772 772  
773 -Select [Own Node Settings] in the [Setting Item List];
614 +2) Select [Own Node Settings] in the [Setting Item List];
774 774  
775 -Set [IP Address], [Subnet Mask], [Default Gateway];
616 +3) Set [IP Address], [Subnet Mask], [Default Gateway];
776 776  
777 -Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
618 +4) Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
778 778  
779 779  (% style="text-align:center" %)
780 780  [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
781 781  
782 -Select [SLMP Connection Module] and add into host station as below picture shows;
623 +5) Select [SLMP Connection Module] and add into host station as below picture shows;
783 783  
784 -Set Port number as 5002 (this is necessary settings);
625 +6) Set Port number as 5002 (this is necessary settings);
785 785  
786 -Click [Close with Reflecting the Setting] to save and close window;
627 +7) Click [Close with Reflecting the Setting] to save and close window;
787 787  
788 788  (% style="text-align:center" %)
789 789  [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
790 790  
791 -Click [Apply] to completed Etherenet settings;
632 +8) Click [Apply] to completed Etherenet settings;
792 792  
793 -Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
634 +9) Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
794 794  
795 795  (% style="text-align:center" %)
796 796  [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
... ... @@ -847,37 +847,37 @@
847 847  
848 848  **PLC Settings (GX Works 3)**
849 849  
850 -Create a blank FX5U project
691 +1) Create a blank FX5U project
851 851  
852 -Find the 485 serial port module in the system navigation bar and double click to enter the settings.
693 +2) Find the 485 serial port module in the system navigation bar and double click to enter the settings.
853 853  
854 854  (% style="text-align:center" %)
855 855  [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
856 856  
857 -Select protocol in the setting item, and set parameters.
698 +3) Select protocol in the setting item, and set parameters.
858 858  
859 859  (% style="text-align:center" %)
860 860  [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
861 861  
862 -Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
703 +4) Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
863 863  
864 864  (% style="text-align:center" %)
865 865  [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
866 866  
867 -Click the [Apply] button to finish the setting.
708 +5) Click the [Apply] button to finish the setting.
868 868  
869 -Click download and select the items as below, then click [execute] to download the configuration to PLC.
710 +6) Click download and select the items as below, then click [execute] to download the configuration to PLC.
870 870  
871 871  (% style="text-align:center" %)
872 872  [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
873 873  
874 - As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
715 +7) As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
875 875  
876 -Done.
717 +8) Done.
877 877  
878 878  **Cable Wiring**
879 879  
880 -* **RS485**
721 +**1) RS485**
881 881  
882 882  (% style="text-align:center" %)
883 883  [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
... ... @@ -885,13 +885,15 @@
885 885  (% style="text-align:center" %)
886 886  [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
887 887  
888 -* **RS422**
729 +**2) RS422**
889 889  
890 890  (% style="text-align:center" %)
891 891  [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
892 892  
893 -**✎Note:** COM3 only available in PI8000/PI9000 series.
734 +**✎Note:**
894 894  
736 +COM3 only available in PI8000/PI9000 series.
737 +
895 895  == **L02 MELSEC (Ethernet)** ==
896 896  
897 897  Mitsubishi Q series CPU built-in Ethernet port.
... ... @@ -941,11 +941,11 @@
941 941  
942 942  **Communication Settings**
943 943  
944 -Enable HMI Ethernet in [Project Settings];
787 +1) Enable HMI Ethernet in [Project Settings];
945 945  
946 946  (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
947 947  
948 -Set PLC IP in [Device IP] settings;
791 +2) Set PLC IP in [Device IP] settings;
949 949  
950 950  (% style="text-align:center" %)
951 951  [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
... ... @@ -952,25 +952,25 @@
952 952  
953 953  **PLC Settings (GX Works2 )**
954 954  
955 -Create a project
798 +1) Create a project
956 956  
957 -Set PLC IP, subnet mask and gateway;
800 +2) Set PLC IP, subnet mask and gateway;
958 958  
959 -Select [Binary Code] as communication data code;
802 +3) Select [Binary Code] as communication data code;
960 960  
961 961  (% style="text-align:center" %)
962 962  [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
963 963  
964 -Set PLC port number, for example 1025
807 +4) Set PLC port number, for example 1025
965 965  
966 966  (% style="text-align:center" %)
967 967  [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
968 968  
969 -Save settings;
812 +5) Save settings;
970 970  
971 -Download project into PLC device;
814 +6) Download project into PLC device;
972 972  
973 -Restart PLC device;
816 +7) Restart PLC device;
974 974  
975 975  **Cable Wiring**
976 976  
... ... @@ -1036,22 +1036,42 @@
1036 1036  
1037 1037  **PLC Settings(GX Works2)**
1038 1038  
1039 -* Click [Ethernet/CC IE/MELSECNET];
1040 -* Please select [Ethernet] as network type;
1041 -* Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1042 -* Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1043 -* Click [Operation setting] to set IP;
1044 -* Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1045 -* Set protocol: TCP;
1046 -* Set [unpassive] in [Open system];
1047 -* Set [receive] in [Fixed buffer];
1048 -* Set [procedure Exist] in [Fixed buffer communication];
1049 -* Disable [Pairing open];
1050 -* Set [No confirm] in [Existence confirmation];
1051 -* Host station port number: 1025;
1052 -* (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1053 -* Download project into PLC and restart it
882 +1) Click [Ethernet/CC IE/MELSECNET];
1054 1054  
884 +2) Please select [Ethernet] as network type;
885 +
886 +3) Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
887 +
888 +4) Select [Online] as Mode;
889 +
890 +(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
891 +
892 +5) Click [Operation setting] to set IP;
893 +
894 +6) Select [Binary Code] as [Communication Data Code];
895 +
896 +(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
897 +
898 +7) Set protocol: TCP;
899 +
900 +8) Set [unpassive] in [Open system];
901 +
902 +9) Set [receive] in [Fixed buffer];
903 +
904 +10) Set [procedure Exist] in [Fixed buffer communication];
905 +
906 +11) Disable [Pairing open];
907 +
908 +12) Set [No confirm] in [Existence confirmation];
909 +
910 +13) Host station port number: 1025;
911 +
912 +(% id="cke_bm_8547S" style="display:none" %) [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]
913 +
914 +14) Save settings;
915 +
916 +15) Download project into PLC and restart it
917 +
1055 1055  **Cable Wiring**
1056 1056  
1057 1057  (% style="text-align:center" %)
... ... @@ -1097,7 +1097,7 @@
1097 1097  
1098 1098  **Cable Wiring**
1099 1099  
1100 -* **RS485**
963 +**1) RS485**
1101 1101  
1102 1102  (% style="text-align:center" %)
1103 1103  [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
... ... @@ -1105,15 +1105,17 @@
1105 1105  (% style="text-align:center" %)
1106 1106  [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1107 1107  
1108 -* **RS232**
971 +**2) RS232**
1109 1109  
1110 1110  (% style="text-align:center" %)
1111 1111  [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1112 1112  
1113 -**✎Note:** COM3 only available in PI8000/PI9000 series.
976 +**✎Note:**
1114 1114  
1115 -== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
978 +COM3 only available in PI8000/PI9000 series.
1116 1116  
980 +== **{{id name="_Toc30118"/}}MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
981 +
1117 1117  Supported Series: MODBUS RTU CONTROLLER
1118 1118  
1119 1119  HMI works as MODBUS MASTER connecting with SLAVE.
... ... @@ -1172,9 +1172,10 @@
1172 1172  
1173 1173  **✎Note:**
1174 1174  
1175 -* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1176 -* The function codes sent out are the same as those that read and write words.
1040 +Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1177 1177  
1042 +The function codes sent out are the same as those that read and write words.
1043 +
1178 1178  **Station number for more than one slaves**
1179 1179  
1180 1180  If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
... ... @@ -1184,7 +1184,7 @@
1184 1184  
1185 1185  **Cable Wiring**
1186 1186  
1187 -* **RS485**
1053 +**1) RS485**
1188 1188  
1189 1189  (% style="text-align:center" %)
1190 1190  [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
... ... @@ -1192,15 +1192,17 @@
1192 1192  (% style="text-align:center" %)
1193 1193  [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1194 1194  
1195 -* **RS232**
1061 +**2) RS232**
1196 1196  
1197 1197  (% style="text-align:center" %)
1198 1198  [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1199 1199  
1200 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1066 +**✎Note:**
1201 1201  
1202 -== **MODBUS TCP Slave (All function)** ==
1068 +COM3 only available in PI8000/PI9000 series.
1203 1203  
1070 +== **{{id name="_Toc16172"/}}MODBUS TCP Slave (All function)** ==
1071 +
1204 1204  Supported series: MODBUS TCP controller
1205 1205  
1206 1206  HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
... ... @@ -1253,12 +1253,12 @@
1253 1253  
1254 1254  **Communication Settings**
1255 1255  
1256 -Enable HMI Ethernet in [Project Settings];
1124 +1) Enable HMI Ethernet in [Project Settings];
1257 1257  
1258 1258  (% style="text-align:center" %)
1259 1259  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1260 1260  
1261 -Set PLC IP in [Device IP] settings;
1129 +2) Set PLC IP in [Device IP] settings;
1262 1262  
1263 1263  (% style="text-align:center" %)
1264 1264  [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
... ... @@ -1299,7 +1299,7 @@
1299 1299  
1300 1300  **Device Settings**
1301 1301  
1302 -Omron E5CC PLC configuration
1170 +1) Omron E5CC PLC configuration
1303 1303  
1304 1304  After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1305 1305  
... ... @@ -1306,13 +1306,15 @@
1306 1306  (% style="text-align:center" %)
1307 1307  [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1308 1308  
1309 -According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1177 +2) According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1310 1310  
1311 1311  (% style="text-align:center" %)
1312 1312  [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1313 1313  
1314 -**✎Note:** The communication settings for HMI should be consistent with this setting.
1182 +**✎Note:**
1315 1315  
1184 +The communication settings for HMI should be consistent with this setting.
1185 +
1316 1316  **Cable Wiring**
1317 1317  
1318 1318  (% style="text-align:center" %)
... ... @@ -1323,18 +1323,28 @@
1323 1323  
1324 1324  **✎Note:**
1325 1325  
1326 -* COM3 only available in PI8000/PI9000 series.
1327 -* CA address could not support continuous writing function;
1328 -* Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1329 -* When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1330 -* When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1331 -* Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1332 -* When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1333 -* Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1334 -* (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1196 +1) COM3 only available in PI8000/PI9000 series.
1335 1335  
1336 -== EtherNet/IP NX series ==
1198 +2) CA address could not support continuous writing function;
1337 1337  
1200 +3) Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1201 +
1202 +4) When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1203 +
1204 +5) When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1205 +
1206 +6) Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1207 +
1208 +7) When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1209 +
1210 +8) Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1211 +
1212 +(% id="cke_bm_8690S" style="display:none" %) [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]
1213 +
1214 +9) Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1215 +
1216 +== **{{id name="_Toc5393"/}}EtherNet/IP NX series** ==
1217 +
1338 1338  Supported series: Omron NX/NJ series
1339 1339  
1340 1340  **HMI Setting**
... ... @@ -1357,24 +1357,24 @@
1357 1357  
1358 1358  **Export labels from Sysmac Studio**
1359 1359  
1360 -Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1240 +1) Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1361 1361  
1362 1362  (% style="text-align:center" %)
1363 1363  [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1364 1364  
1365 -Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1245 +2) Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1366 1366  
1367 -Click [Label manage];
1247 +3) Click [Label manage];
1368 1368  
1369 1369  (% style="text-align:center" %)
1370 1370  [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1371 1371  
1372 -Click [Import labels] and then select the file exported in step 1;
1252 +4) Click [Import labels] and then select the file exported in step 1;
1373 1373  
1374 1374  (% style="text-align:center" %)
1375 1375  [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1376 1376  
1377 -The Import Status field shows the result, click [OK] to finish importing address labels;
1257 +5) The Import Status field shows the result, click [OK] to finish importing address labels;
1378 1378  
1379 1379  (% style="text-align:center" %)
1380 1380  [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
... ... @@ -1381,12 +1381,12 @@
1381 1381  
1382 1382  **Communication Settings**
1383 1383  
1384 -Enable HMI Ethernet in [Project Settings];
1264 +1) Enable HMI Ethernet in [Project Settings];
1385 1385  
1386 1386  (% style="text-align:center" %)
1387 1387  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1388 1388  
1389 -Set PLC IP in [Device IP] settings;
1269 +2) Set PLC IP in [Device IP] settings;
1390 1390  
1391 1391  (% style="text-align:center" %)
1392 1392  [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
... ... @@ -1416,12 +1416,12 @@
1416 1416  
1417 1417  **CAN frame setting in HMI**
1418 1418  
1419 -Click [OpenCAN setting] button in communication setting window;
1299 +1) Click [OpenCAN setting] button in communication setting window;
1420 1420  
1421 1421  (% style="text-align:center" %)
1422 1422  [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1423 1423  
1424 -Click [Add] to create a new frame;
1304 +2) Click [Add] to create a new frame;
1425 1425  
1426 1426  (% style="text-align:center" %)
1427 1427  [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
... ... @@ -1438,19 +1438,19 @@
1438 1438  |8|Browse|Displays configuration files in XML format in IE
1439 1439  |9|OK|Complete the configuration of the frame and exit
1440 1440  
1441 -Set CANBUS frame in setting windows
1321 +3) Set CANBUS frame in setting windows
1442 1442  
1443 1443  (% style="text-align:center" %)
1444 1444  [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1445 1445  
1446 1446  (% class="table-bordered" %)
1447 -|**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1448 -|1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1449 -|2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1450 -|3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1451 -|4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1452 -|5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1453 -|6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1327 +|**No**|**Items**|**Description**
1328 +|1|ID|Set the ID of a can frame in hexadecimal format;
1329 +|2|ID assign|split the ID by PF, PS, and SA;
1330 +|3|Frame type|Select Standard frame or Extended Frame;
1331 +|4|Frame format|Select between data frame and remote Frame;
1332 +|5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1333 +|6|Use address|(((
1454 1454  Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1455 1455  
1456 1456  **Edit:** Set a bit or word address by its format;
... ... @@ -1457,46 +1457,46 @@
1457 1457  
1458 1458  **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1459 1459  )))
1460 -|(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1461 -|(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1462 -|(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1463 -|(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1464 -|(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1465 -|(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1466 -|(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1467 -|(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1468 -|(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1469 -|(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1470 -|(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1471 -|9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1472 -|10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1473 -|11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1474 -|12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1475 -|13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1476 -|14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1477 -|15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1340 +|(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1341 +|Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1342 +|Feedback mode: feedback mode includes no response, confirm response and data response;
1343 +|No response: the device or touch screen will not receive feedback;
1344 +|Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1345 +|Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1346 +|response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1347 +|Response timeout: sets whether the response frame timeout;
1348 +|(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1349 +|Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1350 +|Manually send: a manually send tick indicates only one send;
1351 +|9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1352 +|10|Note|Fill the text to explain the meaning of the frame;
1353 +|11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
1354 +|12|Current operation display|Display the description of current operation;
1355 +|13|Add|Add a new frame;
1356 +|14|Save frame|Save the configured frame format;
1357 +|15|Cancel|Cancel the frame configuration;
1478 1478  
1479 -Set CAN address (Read or write operation);
1359 +4) Set CAN address (Read or write operation);
1480 1480  
1481 1481  (% style="text-align:center" %)
1482 1482  [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1483 1483  
1484 1484  (% class="table-bordered" %)
1485 -|**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1486 -|1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1487 -|(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1488 -|(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1489 -|(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1490 -|(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1491 -|(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1492 -|(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1365 +|**No.**|**Item**|**Description**
1366 +|1|Current address|Displays the register type and register address set by the user in the data access interface
1367 +|(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
1368 +|If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1369 +|If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1370 +|(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
1371 +|If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1372 +|If the trigger condition is a writing operation, there are two situations:(((
1493 1493  * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1494 1494  * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1495 1495  )))
1496 -|(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1497 -|(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1498 -|4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1499 -|5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1376 +|(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1377 +|If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1378 +|4|Add|Add current configuration
1379 +|5|Close|Close the configuration window to exit
1500 1500  
1501 1501  **Multiple Packages Settings**
1502 1502  
... ... @@ -1503,15 +1503,15 @@
1503 1503  (% style="text-align:center" %)
1504 1504  [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1505 1505  
1506 -Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1386 +1) Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1507 1507  
1508 -Select Multiple package type
1388 +2) Select Multiple package type
1509 1509  
1510 1510  * Not Multiple packages
1511 1511  * J1939 Multiple packages
1512 1512  * Customized Multiple packages
1513 1513  
1514 -Click [Edit Receive data] for [Receive] settings
1394 +3) Click [Edit Receive data] for [Receive] settings
1515 1515  
1516 1516  * Start code+ Total length (J1939)
1517 1517  
... ... @@ -1541,7 +1541,7 @@
1541 1541  
1542 1542  As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1543 1543  
1544 -Click [Edit Send data] for [Send] setting
1424 +4) Click [Edit Send data] for [Send] setting
1545 1545  
1546 1546  * J1939
1547 1547  
... ... @@ -1566,10 +1566,12 @@
1566 1566  (% style="text-align:center" %)
1567 1567  [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1568 1568  
1569 -**✎Note:** The address interval between each frame need to be more than a word address;
1449 +**✎Note:**
1570 1570  
1571 -= **SHIMADEN** =
1451 +The address interval between each frame need to be more than a word address;
1572 1572  
1453 += **{{id name="_Toc24639"/}}SHIMADEN** =
1454 +
1573 1573  == **FP23** ==
1574 1574  
1575 1575  Supported series: SHIMADEN FP23 series
... ... @@ -1604,17 +1604,22 @@
1604 1604  
1605 1605  **✎Note:**
1606 1606  
1607 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1608 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1609 -* The Ctrl register is used to store the control group number and BCC check mode.
1489 +1) The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1610 1610  
1491 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1492 +
1493 +3) The Ctrl register is used to store the control group number and BCC check mode.
1494 +
1611 1611  **Ctrl Register Description**
1612 1612  
1613 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1614 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1615 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1616 -* Ctrl3 reserved
1497 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1617 1617  
1499 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1500 +
1501 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1502 +
1503 +4) Ctrl3 reserved
1504 +
1618 1618  **✎Note:**
1619 1619  
1620 1620  After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
... ... @@ -1627,8 +1627,10 @@
1627 1627  (% style="text-align:center" %)
1628 1628  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1629 1629  
1630 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1517 +**✎Note:**
1631 1631  
1519 +COM3 only available in PI8000/PI9000 series.
1520 +
1632 1632  == **{{id name="_Toc23422"/}}SR90** ==
1633 1633  
1634 1634  Supported series: SHIMADEN SR90 series
... ... @@ -1657,17 +1657,22 @@
1657 1657  
1658 1658  **✎Note:**
1659 1659  
1660 -* The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1661 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1662 -* The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1549 +1) The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1663 1663  
1551 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1552 +
1553 +3) The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1554 +
1664 1664  **Ctrl Register Description**
1665 1665  
1666 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1667 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1668 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1669 -* Ctrl3 reserved
1557 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1670 1670  
1559 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1560 +
1561 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1562 +
1563 +4) Ctrl3 reserved
1564 +
1671 1671  **✎Note:**
1672 1672  
1673 1673  After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
... ... @@ -1680,8 +1680,10 @@
1680 1680  (% style="text-align:center" %)
1681 1681  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1682 1682  
1683 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1577 +**✎Note:**
1684 1684  
1579 +COM3 only available in PI8000/PI9000 series.
1580 +
1685 1685  == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1686 1686  
1687 1687  Supported series: SHIMADEN MR13 series
... ... @@ -1717,17 +1717,22 @@
1717 1717  
1718 1718  **✎Note:**
1719 1719  
1720 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1721 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1722 -* The Ctrl register is used to store the control group number and BCC check mode.
1616 +1) The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1723 1723  
1618 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1619 +
1620 +3) The Ctrl register is used to store the control group number and BCC check mode.
1621 +
1724 1724  **Ctrl Register Description**
1725 1725  
1726 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1727 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1728 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1729 -* Ctrl3 reserved
1624 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1730 1730  
1626 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1627 +
1628 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1629 +
1630 +4) Ctrl3 reserved
1631 +
1731 1731  **✎Note:**
1732 1732  
1733 1733  After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
... ... @@ -1740,8 +1740,10 @@
1740 1740  (% style="text-align:center" %)
1741 1741  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1742 1742  
1743 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1644 +**✎Note:**
1744 1744  
1646 +{{id name="_Toc15768"/}}COM3 only available in PI8000/PI9000 series.
1647 +
1745 1745  = **Siemens** =
1746 1746  
1747 1747  == **S7-200 Smart Ethernet** ==
... ... @@ -1811,12 +1811,12 @@
1811 1811  
1812 1812  **Communication Settings**
1813 1813  
1814 -Enable HMI Ethernet in [Project Settings];
1717 +1) Enable HMI Ethernet in [Project Settings];
1815 1815  
1816 1816  (% style="text-align:center" %)
1817 1817  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1818 1818  
1819 -Set PLC IP in [Device IP] settings;
1722 +2) Set PLC IP in [Device IP] settings;
1820 1820  
1821 1821  (% style="text-align:center" %)
1822 1822  [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
... ... @@ -1887,12 +1887,12 @@
1887 1887  
1888 1888  **Communication Settings**
1889 1889  
1890 -Enable HMI Ethernet in [Project Settings];
1793 +1) Enable HMI Ethernet in [Project Settings];
1891 1891  
1892 1892  (% style="text-align:center" %)
1893 1893  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1894 1894  
1895 -Set PLC IP in [Device IP] settings;
1798 +2) Set PLC IP in [Device IP] settings;
1896 1896  
1897 1897  (% style="text-align:center" %)
1898 1898  [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
... ... @@ -2007,12 +2007,12 @@
2007 2007  
2008 2008  **Communication Settings**
2009 2009  
2010 -Enable HMI Ethernet in [Project Settings];
1913 +1) Enable HMI Ethernet in [Project Settings];
2011 2011  
2012 2012  (% style="text-align:center" %)
2013 2013  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2014 2014  
2015 -Set PLC IP in [Device IP] settings;
1918 +2) Set PLC IP in [Device IP] settings;
2016 2016  
2017 2017  (% style="text-align:center" %)
2018 2018  [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
... ... @@ -2019,52 +2019,59 @@
2019 2019  
2020 2020  **✎Note:**
2021 2021  
2022 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2023 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1925 +1) The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2024 2024  
1927 +2) HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1928 +
2025 2025  **PLC Settings**
2026 2026  
2027 -Add BD
1931 +1) Add BD
2028 2028  
2029 -* Please uncheck [Symbolic access only] option;
1933 +Please uncheck [Symbolic access only] option;
2030 2030  
1935 +
2031 2031  (% style="text-align:center" %)
2032 2032  [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2033 2033  
2034 -Address settings, using BD2 as example.
1939 +2) Address settings, using BD2 as example.
2035 2035  
2036 -* DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2037 -* 2 represent DB block number
2038 -* xxxx represent address
1941 +DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2039 2039  
1943 +2 represent DB block number
1944 +
1945 +xxxx represent address
1946 +
2040 2040  **Such as:**
2041 2041  
2042 -* DBxDBB20000 = DB2.DBB0
2043 -* DBxDBW20004 = DB2.DBW4
1949 +DBxDBB20000 = DB2.DBB0
2044 2044  
1951 +DBxDBW20004 = DB2.DBW4
1952 +
2045 2045  (% style="text-align:center" %)
2046 2046  [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2047 2047  
2048 2048  **How to connect with S7-1200 Firmware V4.0**
2049 2049  
2050 -PLC configuration
1958 +1) PLC configuration
2051 2051  
2052 -* Double click [device configuration] in Siemens via software
2053 -* Double click [protection] to enter protection configuration screen
1960 +a) Double click [device configuration] in Siemens via software
2054 2054  
1962 +b) Double click [protection] to enter protection configuration screen
1963 +
2055 2055  (% style="text-align:center" %)
2056 2056  [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2057 2057  
2058 -* Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
1967 +c) Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2059 2059  
2060 2060  (% style="text-align:center" %)
2061 2061  [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2062 2062  
2063 -DB settings
1972 +2) DB settings
2064 2064  
2065 -* Right click [DB], select [properties]
2066 -* Uncheck [optimized block access]
1974 +Right click [DB], select [properties]
2067 2067  
1976 +Uncheck [optimized block access]
1977 +
2068 2068  **Cable Wiring**
2069 2069  
2070 2070  (% style="text-align:center" %)
... ... @@ -2072,7 +2072,7 @@
2072 2072  
2073 2073  == **LOGO Ethernet** ==
2074 2074  
2075 -Supported Series: Siemens Logo 0BA0 series
1985 +Supported Series: Siemens Logo
2076 2076  
2077 2077  **HMI Settings**
2078 2078  
... ... @@ -2105,22 +2105,22 @@
2105 2105  
2106 2106  **PLC Settings in LOGO Software:**
2107 2107  
2108 -Click [Tools]~-~-[Ethernet Connections],shown as below.
2018 +1) Click [Tools]~-~-[Ethernet Connections],shown as below.
2109 2109  
2110 2110  (% style="text-align:center" %)
2111 2111  [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2112 2112  
2113 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2023 +2) Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2114 2114  
2115 2115  (% style="text-align:center" %)
2116 2116  [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2117 2117  
2118 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2028 +3) **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2119 2119  
2120 2120  (% style="text-align:center" %)
2121 2121  [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2122 2122  
2123 -**Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2033 +4) **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2124 2124  
2125 2125  (% style="text-align:center" %)
2126 2126  [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
... ... @@ -2132,35 +2132,41 @@
2132 2132  
2133 2133  **HMI Communication Settings**
2134 2134  
2135 -Set PLC IP in [Device IP] settings;
2045 +1)Set PLC IP in [Device IP] settings;
2136 2136  
2137 2137  (% style="text-align:center" %)
2138 -[[image:SiemensLOGODeviceIP.png]]
2048 +[[image:12.PLC Protocol_html_573fc64ad393cd4f.png||data-xwiki-image-style-alignment="center" height="655" width="379" class="img-thumbnail"]]
2139 2139  
2140 -Enable HMI Ethernet in [Project Settings];
2141 2141  
2051 +2)Enable HMI Ethernet in [Project Settings];
2052 +
2142 2142  (% style="text-align:center" %)
2143 2143  [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2144 2144  
2145 -TSAP setting
2056 +3)TSAP setting
2146 2146  
2147 -* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2148 -* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2149 -* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2058 +Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2150 2150  
2060 +HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2061 +
2062 +HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2063 +
2151 2151  **✎Note:**
2152 2152  
2153 -* The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2066 +1) The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2154 2154  
2155 2155  (% style="text-align:center" %)
2156 2156  [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2157 2157  
2158 2158  
2159 -* AI word address and Ibit address are read-only and cannot be written on HMI.
2160 -* VW address should be even number.such as VW0, VW2, VW4...
2161 -* VD address it takes two VW addresses.such as VD0,VD4,VD8...
2162 -* Written value of RTC cannot exceed 255.
2072 +2) AI word address and Ibit address are read-only and cannot be written on HMI.
2163 2163  
2074 +3) VW address should be even number.such as VW0, VW2, VW4...
2075 +
2076 +4) VD address it takes two VW addresses.such as VD0,VD4,VD8...
2077 +
2078 +5) Written value of RTC cannot exceed 255.
2079 +
2164 2164  **Cable Wiring**
2165 2165  
2166 2166  (% style="text-align:center" %)
... ... @@ -2168,28 +2168,17 @@
2168 2168  
2169 2169  == **S7-XXX Ethernet** ==
2170 2170  
2171 -Supported Series: Siemens S7-400, S7-1200 and S7-1500
2087 +Supported Series: Siemens S7-1200 and S7-1500
2172 2172  
2173 2173  **HMI Setting**
2174 2174  
2175 -(% class="table-bordered" style="width:823px" %)
2176 -|=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2177 -|Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2178 -|Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2179 -|Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2180 -|Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2181 -|HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2091 +(% class="table-bordered" %)
2092 +|**Items**|**Settings**|**Note**
2093 +|Protocol|Siemens S7-XXX|
2094 +|Connection|Ethernet|
2095 +|Port No.|102|
2096 +|PLC station No.|1 (for S7-1500)/ 2 (for S7-1200)|
2182 2182  
2183 -Slot from TIA Portal is equal to Device No. of PIStudio
2184 -
2185 -Rack from TIA Portal is equal to HMI No. of PIStudio
2186 -
2187 -(% style="text-align:center" %)
2188 -[[image:S7-XXXCommunication Settings.png]]
2189 -
2190 -(% style="text-align:center" %)
2191 -[[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2192 -
2193 2193  **Address List**
2194 2194  
2195 2195  (% class="table-bordered" %)
... ... @@ -2273,12 +2273,12 @@
2273 2273  
2274 2274  **Communication Settings**
2275 2275  
2276 -Enable HMI Ethernet in [Project Settings];
2181 +1) Enable HMI Ethernet in [Project Settings];
2277 2277  
2278 2278  (% style="text-align:center" %)
2279 2279  [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2280 2280  
2281 -Set PLC IP in [Device IP] settings;
2186 +2) Set PLC IP in [Device IP] settings;
2282 2282  
2283 2283  (% style="text-align:center" %)
2284 2284  [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
... ... @@ -2285,9 +2285,10 @@
2285 2285  
2286 2286  **✎Note:**
2287 2287  
2288 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2289 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2193 +1) The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2290 2290  
2195 +2) HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2196 +
2291 2291  **Cable Wiring**
2292 2292  
2293 2293  {{id name="OLE_LINK8"/}}
... ... @@ -2312,14 +2312,14 @@
2312 2312  
2313 2313  **Operating Procedures**
2314 2314  
2315 -Select [User defined protocol];
2221 +1) Select [User defined protocol];
2316 2316  
2317 -Click [User defined protocol] button to open setting window as below;
2223 +2) Click [User defined protocol] button to open setting window as below;
2318 2318  
2319 2319  (% style="text-align:center" %)
2320 2320  [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2321 2321  
2322 -Configure user defined command;
2228 +3) Configure user defined command;
2323 2323  
2324 2324  (% style="text-align:center" %)
2325 2325  [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
... ... @@ -2355,26 +2355,26 @@
2355 2355  
2356 2356  **Operating Procedures**
2357 2357  
2358 -Click [Add] to create a new command, as below shows;
2264 +1) Click [Add] to create a new command, as below shows;
2359 2359  
2360 2360  (% style="text-align:center" %)
2361 2361  [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2362 2362  
2363 -Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2269 +2) Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2364 2364  
2365 2365  (% style="text-align:center" %)
2366 2366  [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2367 2367  
2368 -Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2274 +3) Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2369 2369  
2370 2370  (% style="text-align:center" %)
2371 2371  [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2372 2372  
2373 -Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2279 +4) Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2374 2374  
2375 -Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2281 +5) Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2376 2376  
2377 -Check settings;
2283 +6) Check settings;
2378 2378  
2379 2379  (% style="text-align:center" %)
2380 2380  [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
... ... @@ -2387,7 +2387,7 @@
2387 2387  |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2388 2388  |Length: The data length need to be checked.
2389 2389  
2390 -Object settings;
2296 +7) Object settings;
2391 2391  
2392 2392  (% style="text-align:center" %)
2393 2393  [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
... ... @@ -2399,7 +2399,7 @@
2399 2399  |Note: description to object;
2400 2400  |2|Byte order|The numerical display order;
2401 2401  
2402 -Data length settings;
2308 +8) Data length settings;
2403 2403  
2404 2404  (% style="text-align:center" %)
2405 2405  [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
... ... @@ -2411,7 +2411,7 @@
2411 2411  |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2412 2412  |Length: the write data length.
2413 2413  
2414 -Instruction length settings
2320 +9) Instruction length settings
2415 2415  
2416 2416  (% style="text-align:center" %)
2417 2417  [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
... ... @@ -2424,7 +2424,7 @@
2424 2424  
2425 2425  **Cable Wiring**
2426 2426  
2427 -* **RS485**
2333 +**1)RS485**
2428 2428  
2429 2429  (% style="text-align:center" %)
2430 2430  [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
... ... @@ -2432,15 +2432,17 @@
2432 2432  (% style="text-align:center" %)
2433 2433  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2434 2434  
2435 -* **RS232**
2341 +**2)RS232**
2436 2436  
2437 2437  (% style="text-align:center" %)
2438 2438  [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2439 2439  
2440 -**✎Note:** COM3 only available in PI8000/PI9000 series.
2346 +**✎Note:**
2441 2441  
2442 -= **WECON PLC** =
2348 +COM3 only available in PI8000/PI9000 series.
2443 2443  
2350 += **{{id name="_Toc23479"/}}WECON PLC LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM** =
2351 +
2444 2444  Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
2445 2445  
2446 2446  **HMI Settings**
... ... @@ -2476,12 +2476,15 @@
2476 2476  
2477 2477  **Cable Wiring**
2478 2478  
2479 -* **RS485**
2387 +**1)RS485**
2480 2480  
2481 2481  (% style="text-align:center" %)
2390 +[[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2391 +
2392 +(% style="text-align:center" %)
2482 2482  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2483 2483  
2484 -* **RS422**
2395 +**2)RS422**
2485 2485  
2486 2486  (% style="text-align:center" %)
2487 2487  [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
... ... @@ -2488,189 +2488,38 @@
2488 2488  
2489 2489  **✎Note:**
2490 2490  
2491 -* HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
2492 -* If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
2402 +~1. HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
2493 2493  
2404 +2. If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
2405 +
2494 2494  [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
2495 2495  
2496 -
2497 -== **HMI and Wecon LX5V serial communication** ==
2498 -
2499 -This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2500 -
2501 -**Software configuration of PLC**
2502 -
2503 -**1)PLC programming software**
2504 -
2505 -[[image:image-20220810164710-1.png]]
2506 -
2507 -**2)New PLC project**
2508 -
2509 -Click New Project and select the PLC model.
2510 -
2511 -[[image:image-20220810172412-1.png]]
2512 -
2513 -
2514 -**3)Set Serial port parameters**
2515 -
2516 -Follow the steps below to configure Serial port parameters
2517 -
2518 -Baud rate:115200
2519 -
2520 -Data bit:8
2521 -
2522 -Stop bit:1
2523 -
2524 -Parity:No verification
2525 -
2526 -[[image:image-20220810165759-3.png]]
2527 -
2528 -
2529 -**4)Registers list**
2530 -
2531 -[[image:image-20220811102219-3.png]]
2532 -
2533 -
2534 -**HMI software configuration**
2535 -
2536 -**1)HMI programming software**
2537 -
2538 - [[image:image-20220810171237-4.png]]
2539 -
2540 -**2)New HMI project**
2541 -
2542 -Click New Project and select the HMI model.
2543 -
2544 -[[image:image-20220810172010-5.png]]
2545 -
2546 -**3)Set communication port parameters**
2547 -
2548 -Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
2549 -
2550 -Baud rate:115200
2551 -
2552 -Data bit:8
2553 -
2554 -Stop bit:1
2555 -
2556 -Parity:No verification
2557 -
2558 -
2559 -[[image:image-20220811104012-1.png]]
2560 -
2561 -
2562 -**hardware connection**
2563 -
2564 -**1)Hardware wiring diagram**
2565 -
2566 -This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
2567 -
2568 -[[image:image-20220811103005-4.png]]
2569 -
2570 -
2571 -[[image:image-20220811103227-7.png]]
2572 -
2573 -The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
2574 -
2575 -== **HMI and Wecon LX5V-N Ethernet communication** ==
2576 -
2577 -(% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
2578 -
2579 -
2580 -**Software configuration of PLC**
2581 -
2582 -**1)PLC programming software**
2583 -
2584 -[[image:image-20220810164710-1.png]]
2585 -
2586 -**2)New PLC project**
2587 -
2588 -Click New Project and select the PLC model.
2589 -
2590 -[[image:image-20220811115454-1.png]]
2591 -
2592 -
2593 -**3)Set Ethernet port parameters**
2594 -
2595 -Follow the steps below to configure Ethernet parameters
2596 -
2597 -PLC IP address:192.168.39.200
2598 -
2599 -default gateway:192.168.39.1
2600 -
2601 -subnet mask:255.255.255.0
2602 -
2603 -[[image:image-20220811140530-2.png]]
2604 -
2605 -
2606 -**4)Registers list**
2607 -
2608 -[[image:image-20220811102219-3.png]]
2609 -
2610 -
2611 -**HMI software configuration**
2612 -
2613 -**1)HMI programming software**
2614 -
2615 - [[image:image-20220810171237-4.png]]
2616 -
2617 -**2)New HMI project**
2618 -
2619 -Click New Project and select the HMI model.
2620 -
2621 -[[image:image-20220810172010-5.png]]
2622 -
2623 -**3)Set communication port parameters**
2624 -
2625 -Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
2626 -
2627 -HMI IP address:192.168.39.201
2628 -
2629 -default gateway:192.168.39.1
2630 -
2631 -subnet mask:255.255.255.0
2632 -
2633 -[[image:image-20220811170753-2.png]]
2634 -
2635 -Next, click Communication Settings to configure the IP of the HMI communication object.
2636 -
2637 -[[image:image-20220811163047-1.png]]
2638 -
2639 -**hardware connection**
2640 -
2641 -**1)Hardware wiring diagram**
2642 -
2643 -This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
2644 -
2645 -[[image:image-20220811170248-1.png]]
2646 -
2647 -The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
2648 -
2649 2649  = **Printer** =
2650 2650  
2651 2651  == **TSPL label printer** ==
2652 2652  
2653 -**Introduction**
2412 +**I. Introduction**
2654 2654  
2655 2655  TSPL label printer protocol supports following models.
2656 2656  
2657 -* SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2658 -* DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2416 +SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2659 2659  
2660 -**Setting Step**
2418 +DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2661 2661  
2662 -Select the protocol
2420 +**II. Setting Step**
2663 2663  
2664 -* Create a new project, select the TSPL label printer protocol as shown below.
2422 +1) Select the protocol
2665 2665  
2424 +Create a new project, select the TSPL label printer protocol as shown below.
2425 +
2666 2666  (% style="text-align:center" %)
2667 2667  [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2668 2668  
2669 -Set parameters
2429 +2) Set parameters
2670 2670  
2671 -* The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2431 +The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2672 2672  
2673 -Printer register
2433 +3)Printer register
2674 2674  
2675 2675  (% class="table-bordered" %)
2676 2676  |**Register**|**System**|**Range**|**Function**
... ... @@ -2682,13 +2682,18 @@
2682 2682  |TSPL_PN|decimal|0 - 0|Trigger printing
2683 2683  |TSPL_PS|decimal|0 - 0|Print status
2684 2684  
2685 -* Set paper size:
2686 -** TSPL_SP0: width of paper, unit: mm.
2687 -** TSPL_SP1: height of paper, unit: mm.
2688 -* Print text:
2689 -** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2690 -** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2445 +1.Set paper size:
2691 2691  
2447 +TSPL_SP0: width of paper, unit: mm.
2448 +
2449 + TSPL_SP1: height of paper, unit: mm.
2450 +
2451 +2.Print text:
2452 +
2453 +TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2454 +
2455 +Detailed parameter settings of each text is shown as below table.for example,first text,TSPL_PT0-TSPL_PT99.
2456 +
2692 2692  (% class="table-bordered" %)
2693 2693  |**Register**|**Function**|**Description**
2694 2694  |TSPL_PT0|X coordinate|Unit: dot
... ... @@ -2707,11 +2707,12 @@
2707 2707  
2708 2708  By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2709 2709  
2710 -Print QR code:
2475 +3.Print QR code:
2711 2711  
2712 -* TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2713 -* Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2477 +TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2714 2714  
2479 +Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2480 +
2715 2715  (% class="table-bordered" %)
2716 2716  |**Register**|**Function**|**Description**
2717 2717  |TSPL_PQ0|X coordinate|Unit: dot
... ... @@ -2728,13 +2728,14 @@
2728 2728  |TSPL_PQ3|Size|Range: 0-5
2729 2729  |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2730 2730  
2731 -* By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2497 +By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2732 2732  
2733 -Print bar code:
2499 +4.Print bar code:
2734 2734  
2735 -* TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2736 -* Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2501 +TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2737 2737  
2503 +Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2504 +
2738 2738  (% class="table-bordered" %)
2739 2739  |**Register**|**Function**|**Description**
2740 2740  |TSPL_PB0|X coordinate|Unit: dot
... ... @@ -2754,28 +2754,30 @@
2754 2754  
2755 2755  By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2756 2756  
2757 -Print offset:
2524 +5.Print offset:
2758 2758  
2759 -* TSPL_PR0: X coordinate offset, unit: mm;
2760 -* TSPL_PR1: Y coordinate offset, unit: mm.
2526 + TSPL_PR0: X coordinate offset, unit: mm;
2761 2761  
2762 -Trigger printing:
2528 + TSPL_PR1: Y coordinate offset, unit: mm.
2763 2763  
2764 -* TSPL_PN0 = 1: trigger the printer to start printing.
2530 +6.Trigger printing:
2765 2765  
2766 -Printing status:
2532 + TSPL_PN0 = 1: trigger the printer to start printing.
2767 2767  
2768 -* TSPL_PS0 = 1: The printing is normal.
2769 -* TSPL_PS0 = 1: The printing is abnormal.
2534 +7.Printing status:
2770 2770  
2771 -Print picture
2536 + TSPL_PS0 = 1: The printing is normal.
2772 2772  
2773 -* For the function of printing pictures, please refer to the configuration of [Printer object].
2538 + TSPL_PS0 = 1: The printing is abnormal.
2774 2774  
2775 -Conversion between dot and mm
2540 +4)Print picture
2776 2776  
2777 -* Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2542 +For the function of printing pictures, please refer to the configuration of [Printer object].
2778 2778  
2544 +5)Conversion between dot and mm
2545 +
2546 +Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2547 +
2779 2779  == **EpsonTM series** ==
2780 2780  
2781 2781  **HMI Settings**
... ... @@ -2811,38 +2811,6 @@
2811 2811  (% style="text-align:center" %)
2812 2812  [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2813 2813  
2814 -**✎Note:** COM3 only available in PI8000/PI9000 series.
2583 +**✎Note:**
2815 2815  
2816 -
2817 -= **Schneider MODBUS RTU** =
2818 -
2819 -**HMI Setting**
2820 -
2821 -|=**Parameters**|=**Recommended**|=**Notes**
2822 -|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2823 -|Connection|RS485|
2824 -|**Baud rate**|19200|
2825 -|**Data bit**|8|
2826 -|**Parity**|Even|
2827 -|**Stop bit**|1|
2828 -|**PLC station No.**|1|
2829 -
2830 -**PLC Setting**
2831 -
2832 -|=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2833 -
2834 -**Device Address**
2835 -
2836 -|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2837 -|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2838 -|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2839 -|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2840 -|W|MW|DDDDDD|0 ~~ 999999|Output register
2841 -|DW|MD|DDDDDD|0 ~~ 999999|Output register
2842 -
2843 -**Wiring Diagram**
2844 -
2845 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2846 -
2847 -(% style="text-align:center" %)
2848 -[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
2585 +COM3 only available in PI8000/PI9000 series.
S7-XXXCommunication Settings.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -32.6 KB
Content
S7-XXXCommunication SettingsPI.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -24.6 KB
Content
S7-XXXCommunication SettingsPIStudio.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -24.9 KB
Content
SiemensLOGODeviceIP.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -24.9 KB
Content
image-20220810164710-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -7.3 KB
Content
image-20220810165247-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -131.7 KB
Content
image-20220810165759-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -127.8 KB
Content
image-20220810171237-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -12.2 KB
Content
image-20220810172010-5.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -350.7 KB
Content
image-20220810172412-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -165.3 KB
Content
image-20220811102219-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -49.8 KB
Content
image-20220811103005-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -72.7 KB
Content
image-20220811103131-5.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -256.1 KB
Content
image-20220811103200-6.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -17.6 KB
Content
image-20220811103227-7.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -16.0 KB
Content
image-20220811104012-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -113.6 KB
Content
image-20220811115454-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -204.7 KB
Content
image-20220811140308-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -122.3 KB
Content
image-20220811140530-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -126.0 KB
Content
image-20220811163047-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -165.7 KB
Content
image-20220811163943-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -153.6 KB
Content
image-20220811170248-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -91.7 KB
Content
image-20220811170753-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -154.4 KB
Content
image-20220817154212-1.jpeg
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Stone
Size
... ... @@ -1,1 +1,0 @@
1 -51.8 KB
Content