Changes for page 12 PLC Protocol OLD

Last modified by Mora Zhou on 2024/12/05 14:53

From version 83.1
edited by Ben
on 2022/08/29 14:33
Change comment: There is no comment for this version
To version 126.1
edited by Ben
on 2022/08/30 14:24
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -511,7 +511,7 @@
511 511  (% style="text-align:center" %)
512 512  [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513 513  
514 -== **FreeTag Ethernet/IP (CompactLogix)** ==
514 +== **CompactLogix FreeTag Ethernet protocol** ==
515 515  
516 516  Allen-Brandly CompactLogix
517 517  
... ... @@ -568,7 +568,7 @@
568 568  (% style="text-align:center" %)
569 569  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570 570  
571 -== **AB PLC address edit** ==
571 +== **MicroLogix 1200** ** protocol** ==
572 572  
573 573  The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574 574  
... ... @@ -594,9 +594,9 @@
594 594  |N|ffff|N0 ~~ FFFF
595 595  |F|ffff|F0 ~~ FFFF
596 596  
597 -= (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens** =
597 += Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
598 598  
599 -== **S7-200 Smart Ethernet** ==
599 +== **S7-200 Smart Ethernet Protocol** ==
600 600  
601 601  Supported Series: Siemens S7-200 SMART Series Ethernet Module.
602 602  
... ... @@ -687,7 +687,7 @@
687 687  (% style="text-align:center" %)
688 688  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
689 689  
690 -== **S7-300 Ethernet** ==
690 +== **S7-300 Ethernet Protocol** ==
691 691  
692 692  Supported Series: Siemens S7-300 series PLC
693 693  
... ... @@ -763,7 +763,7 @@
763 763  (% style="text-align:center" %)
764 764  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
765 765  
766 -== **S7-1200 Ethernet** ==
766 +== **S7-1200 Ethernet Protocol** ==
767 767  
768 768  Supported Series: Siemens S7-1200
769 769  
... ... @@ -922,104 +922,8 @@
922 922  (% style="text-align:center" %)
923 923  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924 924  
925 -== **LOGO Ethernet** ==
925 +== **S7-XXX Ethernet Protocol** ==
926 926  
927 -Supported Series: Siemens Logo 0BA0 series
928 -
929 -**HMI Settings**
930 -
931 -(% class="table-bordered" %)
932 -|**Items**|**Settings**|**Note**
933 -|Protocol|Siemens LOGO|
934 -|Connection|Ethernet|
935 -|Port No.|102|
936 -|PLC station No.|2|
937 -
938 -**Address List**
939 -
940 -(% class="table-bordered" %)
941 -|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
942 -|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
943 -|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
944 -|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
945 -|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
946 -|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
947 -|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
948 -|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
949 -|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
950 -|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
951 -|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
952 -|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
953 -|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
954 -|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
955 -|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
956 -|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
957 -
958 -**PLC Settings in LOGO Software:**
959 -
960 -Click [Tools]~-~-[Ethernet Connections],shown as below.
961 -
962 -(% style="text-align:center" %)
963 -[[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
964 -
965 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
966 -
967 -(% style="text-align:center" %)
968 -[[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
969 -
970 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
971 -
972 -(% style="text-align:center" %)
973 -[[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
974 -
975 -**Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
976 -
977 -(% style="text-align:center" %)
978 -[[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
979 -
980 -
981 -(% style="text-align:center" %)
982 -[[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
983 -
984 -
985 -**HMI Communication Settings**
986 -
987 -Set PLC IP in [Device IP] settings;
988 -
989 -(% style="text-align:center" %)
990 -[[image:SiemensLOGODeviceIP.png]]
991 -
992 -Enable HMI Ethernet in [Project Settings];
993 -
994 -(% style="text-align:center" %)
995 -[[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
996 -
997 -TSAP setting
998 -
999 -* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1000 -* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1001 -* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1002 -
1003 -**✎Note:**
1004 -
1005 -* The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1006 -
1007 -(% style="text-align:center" %)
1008 -[[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1009 -
1010 -
1011 -* AI word address and Ibit address are read-only and cannot be written on HMI.
1012 -* VW address should be even number.such as VW0, VW2, VW4...
1013 -* VD address it takes two VW addresses.such as VD0,VD4,VD8...
1014 -* Written value of RTC cannot exceed 255.
1015 -
1016 -**Cable Wiring**
1017 -
1018 -(% style="text-align:center" %)
1019 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1020 -
1021 -== **S7-XXX Ethernet** ==
1022 -
1023 1023  Supported Series: Siemens S7-400, S7-1200 and S7-1500
1024 1024  
1025 1025  **HMI Setting**
... ... @@ -1142,12 +1142,107 @@
1142 1142  
1143 1143  **Cable Wiring**
1144 1144  
1145 -{{id name="OLE_LINK8"/}}
1049 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1146 1146  
1147 -= Create communication with **Mitsubishi** =
1051 +== (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1148 1148  
1149 -== **FX1S, 1N, 2N Series** ==
1053 +Supported Series: Siemens Logo 0BA0 series
1150 1150  
1055 +**HMI Settings**
1056 +
1057 +(% class="table-bordered" %)
1058 +|**Items**|**Settings**|**Note**
1059 +|Protocol|Siemens LOGO|
1060 +|Connection|Ethernet|
1061 +|Port No.|102|
1062 +|PLC station No.|2|
1063 +
1064 +**Address List**
1065 +
1066 +(% class="table-bordered" %)
1067 +|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1068 +|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1069 +|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1070 +|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1071 +|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1072 +|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1073 +|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1074 +|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1075 +|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1076 +|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1077 +|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1078 +|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1079 +|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1080 +|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1081 +|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1082 +|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1083 +
1084 +**PLC Settings in LOGO Software:**
1085 +
1086 +Click [Tools]~-~-[Ethernet Connections],shown as below.
1087 +
1088 +(% style="text-align:center" %)
1089 +[[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1090 +
1091 +Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1092 +
1093 +(% style="text-align:center" %)
1094 +[[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1095 +
1096 +**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1097 +
1098 +(% style="text-align:center" %)
1099 +[[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1100 +
1101 +**Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1102 +
1103 +(% style="text-align:center" %)
1104 +[[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1105 +
1106 +
1107 +(% style="text-align:center" %)
1108 +[[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1109 +
1110 +
1111 +**HMI Communication Settings**
1112 +
1113 +Set PLC IP in [Device IP] settings;
1114 +
1115 +(% style="text-align:center" %)
1116 +[[image:SiemensLOGODeviceIP.png]]
1117 +
1118 +Enable HMI Ethernet in [Project Settings];
1119 +
1120 +(% style="text-align:center" %)
1121 +[[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1122 +
1123 +TSAP setting
1124 +
1125 +* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1126 +* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1127 +* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1128 +
1129 +**✎Note:**
1130 +
1131 +* The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1132 +
1133 +(% style="text-align:center" %)
1134 +[[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1135 +
1136 +
1137 +* AI word address and Ibit address are read-only and cannot be written on HMI.
1138 +* VW address should be even number.such as VW0, VW2, VW4...
1139 +* VD address it takes two VW addresses.such as VD0,VD4,VD8...
1140 +* Written value of RTC cannot exceed 255.
1141 +
1142 +**Cable Wiring**
1143 +
1144 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1145 +
1146 += Create communication with **Mitsubishi PLC** =
1147 +
1148 +== **FX1S, 1N, 2N Series Protocol** ==
1149 +
1151 1151  Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1152 1152  
1153 1153  **HMI Settings**
... ... @@ -1199,7 +1199,7 @@
1199 1199  
1200 1200  **✎Note:** COM3 only available in PI8000/PI9000 series.
1201 1201  
1202 -== **FX5U Ethernet** ==
1201 +== **FX5U Ethernet Protocol** ==
1203 1203  
1204 1204  Mitsubishi FX5U series PLC
1205 1205  
... ... @@ -1278,7 +1278,7 @@
1278 1278  (% style="text-align:center" %)
1279 1279  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1280 1280  
1281 -== **FX5U Serial Port** ==
1280 +== **FX5U Serial Port Protocol** ==
1282 1282  
1283 1283  Mitsubishi FX5U series PLC
1284 1284  
... ... @@ -1370,7 +1370,7 @@
1370 1370  
1371 1371  **✎Note:** COM3 only available in PI8000/PI9000 series.
1372 1372  
1373 -== **L02 MELSEC (Ethernet)** ==
1372 +== **L02 MELSEC (Ethernet) Protocol** ==
1374 1374  
1375 1375  Mitsubishi Q series CPU built-in Ethernet port.
1376 1376  
... ... @@ -1455,7 +1455,7 @@
1455 1455  (% style="text-align:center" %)
1456 1456  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1457 1457  
1458 -== **QJ71E71 MELSEC** ==
1457 +== **QJ71E71 MELSEC Protocol** ==
1459 1459  
1460 1460  Mitsubishi QJ71E71 Ethernet communication module;
1461 1461  
... ... @@ -1535,226 +1535,206 @@
1535 1535  (% style="text-align:center" %)
1536 1536  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1537 1537  
1538 -= **MODBUS** =
1537 += Create communication with **Delta PLC** =
1539 1539  
1540 -== **MODBUS RTU Master** ==
1539 +== **DVP serial protocol** ==
1541 1541  
1542 -Supported Series: MODBUS RTU CONTROLLER
1541 +(% class="wikigeneratedid" %)
1542 +Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1543 1543  
1544 -HMI works as MODBUS SLAVE connecting with MASTER
1544 +**1)HMI Settings**
1545 1545  
1546 -(% style="text-align:center" %)
1547 -[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1546 +|**Item**|**Settings**|**Note**
1547 +|Protocol|DELTA DVP Series|
1548 +|Connection|RS485|
1549 +|Baud rate|9600|
1550 +|Data bit|7|
1551 +|Parity|Even|
1552 +|Stop bit|1|
1553 +|PLC station No.|1~~255|Need to be the same as PLC settings
1548 1548  
1555 +**2)Address List**
1549 1549  
1550 -(% style="text-align:center" %)
1551 -[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1557 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1558 +|Bit|X|X|X d|0~~303237|
1559 +|Bit|Y|Y|Y d|0~~303237|
1560 +|Bit|M|M|M d|0~~99999|
1561 +|Bit|T|T|T d|0~~99999|
1562 +|Bit|C|C|T d|0~~99999|
1563 +|Bit|S|S|T d|0~~99999|
1564 +|Word|D|D|D d|0~~99999|
1565 +|Word|T|T|T d|0~~99999|
1566 +|Word|C|C|C d|0~~99999|
1552 1552  
1568 +(% class="wikigeneratedid" %)
1569 +**3)Configure the communication protocol**
1553 1553  
1554 -(% style="text-align:center" %)
1555 -[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1571 +(% class="wikigeneratedid" %)
1572 +[[image:image-20220829152327-6.png]]
1556 1556  
1557 -**HMI Settings**
1574 +(% class="wikigeneratedid" %)
1575 +[[image:image-20220829152016-3.png]]
1558 1558  
1559 -(% class="table-bordered" %)
1560 -|**Items**|**Settings**|**Note**
1561 -|Protocol|MODBUS RTU Master|
1562 -|Connection|RS485/RS232|
1563 -|Baud rate|2400~~187500|
1564 -|Data bit|8|
1565 -|Parity|Even/ Odd/ None|
1566 -|Stop bit|1/2|
1567 -|Station No.|0~~255|
1577 +(% class="wikigeneratedid" %)
1578 +**4)Cable Wiring**
1568 1568  
1569 -**Address List**
1580 +(% class="wikigeneratedid" id="H" %)
1581 +[[image:image-20220829152610-7.png]]
1570 1570  
1571 -(% class="table-bordered" %)
1572 -|**Type**|**HMI address**|**MODBUS code**|**Range**
1573 -|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1574 -|Word|HDW3500~~HDW7999|4|0~~4499
1583 +(% class="wikigeneratedid" id="H" %)
1584 +[[image:image-20220829152102-5.png]]
1575 1575  
1576 -**Cable Wiring**
1577 1577  
1578 -* **RS485**
1587 +== **DVP Ethernet Protocol** ==
1579 1579  
1580 -(% style="text-align:center" %)
1581 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1589 +(% class="wikigeneratedid" %)
1590 +Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1582 1582  
1583 -(% style="text-align:center" %)
1584 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1592 +**1)HMI Settings**
1585 1585  
1586 -* **RS232**
1594 +|**Items**|**Settings**|**Note**
1595 +|Protocol|DELTA DVP Modbus TCP|
1596 +|Connection|Ethernet|
1597 +|Port No.|201|Must be the same as the PLC setting
1598 +|PLC station No.|0|Must be the same as the PLC setting
1587 1587  
1588 -(% style="text-align:center" %)
1589 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1600 +**2)Address List**
1590 1590  
1591 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1602 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1603 +|Bit|X|X|X o|0~~377|
1604 +|Bit|Y|Y|Y o|0~~377|
1605 +|Bit|M0|M0|M0 d|0~~1535|
1606 +|Bit|M1|M1|M1 d|1536~~4095|
1607 +|Bit|T|T|T d|0~~255|
1608 +|Bit|C|C|C d|0~~255|
1609 +|Bit|S|S|S d|0~~1023|
1610 +|Word|D0|D0|D0 d|0~~4095|
1611 +|Word|D1|D1|D1 d|4096~~11999|(((
1612 +
1613 +)))
1614 +|Word|T|T|T d|0~~255|
1615 +|Word|C|C|C d|0~~199|(((
1616 +
1617 +)))
1592 1592  
1593 -== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1619 +(% class="wikigeneratedid" %)
1620 +**3)Configure the communication protocol**
1594 1594  
1595 -Supported Series: MODBUS RTU CONTROLLER
1622 +[[image:image-20220829155452-1.png]]
1596 1596  
1597 -HMI works as MODBUS MASTER connecting with SLAVE.
1624 +[[image:image-20220829162116-2.png]]
1598 1598  
1599 -The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1626 +**4)Cable Wiring**
1600 1600  
1601 -(% style="text-align:center" %)
1602 -[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1628 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1603 1603  
1630 +== **AS serial protocol** ==
1604 1604  
1605 -(% style="text-align:center" %)
1606 -[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1632 +**1)HMI Settings**
1607 1607  
1608 -
1609 -(% style="text-align:center" %)
1610 -[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1611 -
1612 -**HMI Settings**
1613 -
1614 -(% class="table-bordered" %)
1615 -|**Items**|**Settings**|**Note**
1616 -|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1617 -|Connection|RS485/RS232|
1618 -|Baud rate|2400~~187500|
1634 +|**Item**|**Settings**|**Note**
1635 +|Protocol|DELTA AS300 MODBUS RTU|
1636 +|Connection|RS485|
1637 +|Baud rate|9600|
1619 1619  |Data bit|8|
1620 -|Parity|Even/ Odd/ None|
1621 -|Stop bit|1/2|
1622 -|PLC station No.|0~~255|
1639 +|Parity|NONE|
1640 +|Stop bit|1|
1641 +|PLC station No.|1|
1623 1623  
1624 -**Address List**
1643 +**2)Address List**
1625 1625  
1626 -(% class="table-bordered" %)
1627 -|**Type**|**Address Type**|**Function code & Description**
1628 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1629 -|06 (write single register: write a binary value to a holding register)
1630 -|10 (write values to multiple addresses )
1631 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1632 -|06 (write single register: write a binary value to a holding register)
1633 -|10 (write values to multiple addresses )
1634 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1635 -|06 (write single register: write a binary value to a holding register)
1636 -|10 (write values to multiple addresses )
1637 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1638 -|10 (write values to multiple addresses )
1639 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1640 -|05 (Force a single coil to force the on/off state of a logic coil)
1641 -|0F (Write multiple bits, ie write continuously)
1642 -|(% rowspan="3" %)1|02 (Read the input state)
1643 -|05 (Force a single coil to force the on/off state of a logic coil)
1644 -|0F (Write multiple bits)
1645 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1646 -|05 (Force a single coil to force the on/off state of a logic coil)
1647 -|0F (Write multiple bits)
1648 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1649 -|0F (Write multiple bits)
1650 1650  
1651 -**✎Note:**
1646 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1647 +|Bit|X|X|X d|0~~63|
1648 +|Bit|Y|Y|Y d|0~~63|
1649 +|Bit|D|D|D d|0~~29999|
1650 +|Bit|M|M|M d|0~~8191|
1651 +|Bit|SM|SM|SM d|0~~4095|
1652 +|Bit|S|S|S h|0~~2047|
1653 +|Bit|T|T|T d|0~~511|
1654 +|Bit|C|C|C d|0~~511|
1655 +|Bit|HC|HC|HC d|0~~255|
1656 +|Word|X|X|X h|0~~63|
1657 +|Word|Y|Y|Y d|0~~63|
1658 +|Word|SR|SR|SR d|0~~2047|
1659 +|Word|D|D|D d|0~~29999|
1660 +|Word|T|T|T d|0~~511|
1661 +|Word|C|C|C h|0~~511|
1662 +|Word|E|E|E d|0~~9|
1652 1652  
1653 -* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1654 -* The function codes sent out are the same as those that read and write words.
1664 +**3)Configure the communication protocol**
1655 1655  
1656 -**Station number for more than one slaves**
1666 +[[image:image-20220830094600-1.png]]
1657 1657  
1658 -If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1668 +[[image:image-20220830094657-2.png]]
1659 1659  
1660 -(% style="text-align:center" %)
1661 -[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1670 +**4)Cable Wiring**
1662 1662  
1663 -**Cable Wiring**
1672 +Figure
1664 1664  
1665 -* **RS485**
1674 +[[image:image-20220830141138-1.png]]
1666 1666  
1667 -(% style="text-align:center" %)
1668 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1676 +Pin Definition Diagram
1669 1669  
1670 -(% style="text-align:center" %)
1671 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1678 +[[image:image-20220830095131-1.png]]
1672 1672  
1673 -* **RS232**
1680 +== **AS Ethernet Protocol** ==
1674 1674  
1675 -(% style="text-align:center" %)
1676 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1682 +**1)HMI Settings**
1677 1677  
1678 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1679 1679  
1680 -== **MODBUS TCP Slave (All function)** ==
1681 -
1682 -Supported series: MODBUS TCP controller
1683 -
1684 -HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1685 -
1686 -(% style="text-align:center" %)
1687 -[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1688 -
1689 -(% style="text-align:center" %)
1690 -[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1691 -
1692 -
1693 -(% style="text-align:center" %)
1694 -[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1695 -
1696 -**HMI Setting**
1697 -
1698 -(% class="table-bordered" %)
1699 -|**Items**|**Settings**|**Note**
1700 -|Protocol|MODBUS TCP Slave (All function)|
1685 +|=**Items**|=**Settings**|=**Note**
1686 +|Protocol|DELTA AS300 MODBUS TCP|
1701 1701  |Connection|Ethernet|
1702 1702  |Port No.|502|
1703 -|PLC station No.|1|
1689 +|Device No.|1|
1690 +|HMI No.|0|
1704 1704  
1705 -**Address List**
1692 +**2)Address List**
1706 1706  
1707 -(% class="table-bordered" %)
1708 -|**Type**|**Register**|**Function code & Description**
1709 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1710 -|06 (write single register: write a binary value to a holding register)
1711 -|10 (write values to multiple addresses )
1712 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1713 -|06 (write single register: write a binary value to a holding register)
1714 -|10 (write values to multiple addresses )
1715 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1716 -|06 (write single register: write a binary value to a holding register)
1717 -|10 (write values to multiple addresses )
1718 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1719 -|10 (write values to multiple addresses )
1720 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1721 -|05 (Force a single coil to force the on/off state of a logic coil)
1722 -|0F (Write multiple bits, ie write continuously)
1723 -|(% rowspan="3" %)1|02 (Read the input state)
1724 -|05 (Force a single coil to force the on/off state of a logic coil)
1725 -|0F (Write multiple bits)
1726 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1727 -|05 (Force a single coil to force the on/off state of a logic coil)
1728 -|0F (Write multiple bits)
1729 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1730 -|0F (Write multiple bits)
1731 1731  
1732 -**Communication Settings**
1695 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1696 +|Bit|X|X|X d|0~~63|
1697 +|Bit|Y|Y|Y d|0~~63|
1698 +|Bit|D|D|D d|0~~29999|
1699 +|Bit|M|M|M d|0~~8191|
1700 +|Bit|SM|SM|SM d|0~~4095|
1701 +|Bit|S|S|S h|0~~2047|
1702 +|Bit|T|T|T d|0~~511|
1703 +|Bit|C|C|C d|0~~511|
1704 +|Bit|HC|HC|HC d|0~~255|
1705 +|Word|X|X|X h|0~~63|
1706 +|Word|Y|Y|Y d|0~~63|
1707 +|Word|SR|SR|SR d|0~~2047|
1708 +|Word|D|D|D d|0~~29999|
1709 +|Word|T|T|T d|0~~511|
1710 +|Word|C|C|C h|0~~511|
1711 +|Word|E|E|E d|0~~9|
1733 1733  
1734 -Enable HMI Ethernet in [Project Settings];
1713 +**3)Configure the communication protocol**
1735 1735  
1736 -(% style="text-align:center" %)
1737 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1715 +[[image:image-20220830140537-1.png]]
1738 1738  
1739 -Set PLC IP in [Device IP] settings;
1717 +[[image:image-20220830140629-2.png]]
1740 1740  
1741 -(% style="text-align:center" %)
1742 -[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1719 +**4)Cable Wiring**
1743 1743  
1744 -**Cable Wiring**
1721 +Figure
1745 1745  
1746 -(% style="text-align:center" %)
1747 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1723 +[[image:image-20220830094929-1.png]]
1748 1748  
1749 -= **Omron** =
1725 +Pin Definition Diagram
1750 1750  
1751 -== **EC55** ==
1727 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1752 1752  
1729 += Create communication with **Omron** PLC =
1730 +
1731 +== **EC55 Protocol** ==
1732 +
1753 1753  Supported device: EC55 temperature instrument
1754 1754  
1755 1755  **HMI Settings**
1756 1756  
1757 -(% class="table-bordered" %)
1758 1758  |**Items**|**Settings**|**Note**
1759 1759  |Protocol|Omron EC55|
1760 1760  |Connection|RS485 (9600, 2, 7, EVEN)|
... ... @@ -1763,7 +1763,6 @@
1763 1763  
1764 1764  **Address List**
1765 1765  
1766 -(% class="table-bordered" %)
1767 1767  |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1768 1768  |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1769 1769  |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
... ... @@ -1809,15 +1809,14 @@
1809 1809  * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1810 1810  * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1811 1811  * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1812 -* (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1790 +* [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1813 1813  
1814 -== EtherNet/IP NX series ==
1792 +== **EtherNet/IP NX series **Protocol ==
1815 1815  
1816 1816  Supported series: Omron NX/NJ series
1817 1817  
1818 1818  **HMI Setting**
1819 1819  
1820 -(% class="table-bordered" %)
1821 1821  |**Items**|**Settings**|**Note**
1822 1822  |Protocol|Omron NX Ethernet/IP|
1823 1823  |Connection|Ethernet|
... ... @@ -1869,183 +1869,224 @@
1869 1869  (% style="text-align:center" %)
1870 1870  [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1871 1871  
1872 -
1873 1873  (% style="text-align:center" %)
1874 1874  [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1875 1875  
1876 1876  **Cable Wiring**
1877 1877  
1854 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1855 +
1856 += **MODBUS** =
1857 +
1858 +== **MODBUS RTU Master** ==
1859 +
1860 +Supported Series: MODBUS RTU CONTROLLER
1861 +
1862 +HMI works as MODBUS SLAVE connecting with MASTER
1863 +
1878 1878  (% style="text-align:center" %)
1879 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1865 +[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1880 1880  
1881 -= **OpenCAN** =
1882 1882  
1883 -OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1868 +(% style="text-align:center" %)
1869 +[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1884 1884  
1885 -This protocol is only available in PI8000 series HMI.
1886 1886  
1872 +(% style="text-align:center" %)
1873 +[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1874 +
1887 1887  **HMI Settings**
1888 1888  
1889 1889  (% class="table-bordered" %)
1890 1890  |**Items**|**Settings**|**Note**
1891 -|Protocol|OPENCAN|
1892 -|Connection|CAN port|
1893 -|Baud rate|250000|
1879 +|Protocol|MODBUS RTU Master|
1880 +|Connection|RS485/RS232|
1881 +|Baud rate|2400~~187500|
1882 +|Data bit|8|
1883 +|Parity|Even/ Odd/ None|
1884 +|Stop bit|1/2|
1885 +|Station No.|0~~255|
1894 1894  
1895 -**CAN frame setting in HMI**
1887 +**Address List**
1896 1896  
1897 -Click [OpenCAN setting] button in communication setting window;
1889 +(% class="table-bordered" %)
1890 +|**Type**|**HMI address**|**MODBUS code**|**Range**
1891 +|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1892 +|Word|HDW3500~~HDW7999|4|0~~4499
1898 1898  
1899 -(% style="text-align:center" %)
1900 -[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1894 +**Cable Wiring**
1901 1901  
1902 -Click [Add] to create a new frame;
1896 +* **RS485**
1903 1903  
1904 1904  (% style="text-align:center" %)
1905 -[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1899 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1906 1906  
1907 -(% class="table-bordered" %)
1908 -|**No**|**Items**|**Description**
1909 -|1|Add|add a frame related to register address
1910 -|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1911 -|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1912 -|4|Modify|Modify the frames in frame management
1913 -|5|Copy|Copy one frame to another
1914 -|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1915 -|7|Empty|All frames in the list are cleared
1916 -|8|Browse|Displays configuration files in XML format in IE
1917 -|9|OK|Complete the configuration of the frame and exit
1901 +(% style="text-align:center" %)
1902 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1918 1918  
1919 -Set CANBUS frame in setting windows
1904 +* **RS232**
1920 1920  
1921 1921  (% style="text-align:center" %)
1922 -[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1907 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1923 1923  
1924 -(% class="table-bordered" %)
1925 -|**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1926 -|1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1927 -|2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1928 -|3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1929 -|4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1930 -|5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1931 -|6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1932 -Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1909 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1933 1933  
1934 -**Edit:** Set a bit or word address by its format;
1911 +== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1935 1935  
1936 -**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1937 -)))
1938 -|(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1939 -|(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1940 -|(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1941 -|(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1942 -|(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1943 -|(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1944 -|(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1945 -|(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1946 -|(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1947 -|(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1948 -|(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1949 -|9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1950 -|10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1951 -|11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1952 -|12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1953 -|13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1954 -|14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1955 -|15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1913 +Supported Series: MODBUS RTU CONTROLLER
1956 1956  
1957 -Set CAN address (Read or write operation);
1915 +HMI works as MODBUS MASTER connecting with SLAVE.
1958 1958  
1917 +The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1918 +
1959 1959  (% style="text-align:center" %)
1960 -[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1920 +[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1961 1961  
1962 -(% class="table-bordered" %)
1963 -|**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1964 -|1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1965 -|(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1966 -|(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1967 -|(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1968 -|(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1969 -|(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1970 -|(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1971 -* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1972 -* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1973 -)))
1974 -|(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1975 -|(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1976 -|4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1977 -|5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1978 1978  
1979 -**Multiple Packages Settings**
1923 +(% style="text-align:center" %)
1924 +[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1980 1980  
1926 +
1981 1981  (% style="text-align:center" %)
1982 -[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1928 +[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1983 1983  
1984 -Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1930 +**HMI Settings**
1985 1985  
1986 -Select Multiple package type
1932 +(% class="table-bordered" %)
1933 +|**Items**|**Settings**|**Note**
1934 +|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1935 +|Connection|RS485/RS232|
1936 +|Baud rate|2400~~187500|
1937 +|Data bit|8|
1938 +|Parity|Even/ Odd/ None|
1939 +|Stop bit|1/2|
1940 +|PLC station No.|0~~255|
1987 1987  
1988 -* Not Multiple packages
1989 -* J1939 Multiple packages
1990 -* Customized Multiple packages
1942 +**Address List**
1991 1991  
1992 -Click [Edit Receive data] for [Receive] settings
1944 +(% class="table-bordered" %)
1945 +|**Type**|**Address Type**|**Function code & Description**
1946 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1947 +|06 (write single register: write a binary value to a holding register)
1948 +|10 (write values to multiple addresses )
1949 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1950 +|06 (write single register: write a binary value to a holding register)
1951 +|10 (write values to multiple addresses )
1952 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1953 +|06 (write single register: write a binary value to a holding register)
1954 +|10 (write values to multiple addresses )
1955 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1956 +|10 (write values to multiple addresses )
1957 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1958 +|05 (Force a single coil to force the on/off state of a logic coil)
1959 +|0F (Write multiple bits, ie write continuously)
1960 +|(% rowspan="3" %)1|02 (Read the input state)
1961 +|05 (Force a single coil to force the on/off state of a logic coil)
1962 +|0F (Write multiple bits)
1963 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1964 +|05 (Force a single coil to force the on/off state of a logic coil)
1965 +|0F (Write multiple bits)
1966 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1967 +|0F (Write multiple bits)
1993 1993  
1994 -* Start code+ Total length (J1939)
1969 +**✎Note:**
1995 1995  
1996 -(% style="text-align:center" %)
1997 -[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1971 +* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1972 +* The function codes sent out are the same as those that read and write words.
1998 1998  
1999 -As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1974 +**Station number for more than one slaves**
2000 2000  
2001 -* Start code + Data max length (J1939)
1976 +If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2002 2002  
2003 2003  (% style="text-align:center" %)
2004 -[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1979 +[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2005 2005  
2006 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1981 +**Cable Wiring**
2007 2007  
2008 -* Data max length (J1939)
1983 +* **RS485**
2009 2009  
2010 2010  (% style="text-align:center" %)
2011 -[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1986 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2012 2012  
2013 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1988 +(% style="text-align:center" %)
1989 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2014 2014  
2015 -* Customized multiple package
1991 +* **RS232**
2016 2016  
2017 2017  (% style="text-align:center" %)
2018 -[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1994 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2019 2019  
2020 -As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1996 +**✎Note:** COM3 only available in PI8000/PI9000 series.
2021 2021  
2022 -Click [Edit Send data] for [Send] setting
1998 +== **MODBUS TCP Slave (All function)** ==
2023 2023  
2024 -* J1939
2000 +Supported series: MODBUS TCP controller
2025 2025  
2002 +HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
2003 +
2026 2026  (% style="text-align:center" %)
2027 -[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2005 +[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2028 2028  
2029 -[Data] is all data to be sent.
2007 +(% style="text-align:center" %)
2008 +[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2030 2030  
2031 -Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2032 2032  
2033 -* Customized multiple package
2011 +(% style="text-align:center" %)
2012 +[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2034 2034  
2014 +**HMI Setting**
2015 +
2016 +(% class="table-bordered" %)
2017 +|**Items**|**Settings**|**Note**
2018 +|Protocol|MODBUS TCP Slave (All function)|
2019 +|Connection|Ethernet|
2020 +|Port No.|502|
2021 +|PLC station No.|1|
2022 +
2023 +**Address List**
2024 +
2025 +(% class="table-bordered" %)
2026 +|**Type**|**Register**|**Function code & Description**
2027 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2028 +|06 (write single register: write a binary value to a holding register)
2029 +|10 (write values to multiple addresses )
2030 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2031 +|06 (write single register: write a binary value to a holding register)
2032 +|10 (write values to multiple addresses )
2033 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2034 +|06 (write single register: write a binary value to a holding register)
2035 +|10 (write values to multiple addresses )
2036 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2037 +|10 (write values to multiple addresses )
2038 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2039 +|05 (Force a single coil to force the on/off state of a logic coil)
2040 +|0F (Write multiple bits, ie write continuously)
2041 +|(% rowspan="3" %)1|02 (Read the input state)
2042 +|05 (Force a single coil to force the on/off state of a logic coil)
2043 +|0F (Write multiple bits)
2044 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2045 +|05 (Force a single coil to force the on/off state of a logic coil)
2046 +|0F (Write multiple bits)
2047 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2048 +|0F (Write multiple bits)
2049 +
2050 +**Communication Settings**
2051 +
2052 +Enable HMI Ethernet in [Project Settings];
2053 +
2035 2035  (% style="text-align:center" %)
2036 -[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2055 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2037 2037  
2038 -[Data] is all data to be sent.
2057 +Set PLC IP in [Device IP] settings;
2039 2039  
2040 -As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2059 +(% style="text-align:center" %)
2060 +[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2041 2041  
2042 2042  **Cable Wiring**
2043 2043  
2044 2044  (% style="text-align:center" %)
2045 -[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2065 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2046 2046  
2047 -**✎Note:** The address interval between each frame need to be more than a word address;
2048 -
2049 2049  = **SHIMADEN** =
2050 2050  
2051 2051  == **FP23** ==
... ... @@ -2220,559 +2220,6 @@
2220 2220  
2221 2221  **✎Note:** COM3 only available in PI8000/PI9000 series.
2222 2222  
2223 -= **Siemens** =
2224 -
2225 -== **S7-200 Smart Ethernet** ==
2226 -
2227 -Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2228 -
2229 -Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2230 -
2231 -**HMI Setting**
2232 -
2233 -(% class="table-bordered" %)
2234 -|**Items**|**Settings**|**Note**
2235 -|Protocol|Simens S7-200 Smart Ethernet|
2236 -|Connection|Ethernet|
2237 -|Port No.|102|
2238 -|PLC station No.|2|
2239 -
2240 -**Address List**
2241 -
2242 -(% class="table-bordered" %)
2243 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2244 -|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2245 -|Q|Q|Q ddddd.o|0.0~~99999.7|
2246 -|V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2247 -|V|V|V ddddd.o|0.0~~99999.7|
2248 -|M|M|M ddddd.o|0.0~~99999.7|
2249 -|SM|SM|ddddd.o|0.0~~99999.7|
2250 -|S|S|ddddd.o|0.0~~99999.7|Read only
2251 -|T|T|ddddd|0~~99999|Timer state, read only
2252 -|C|C|ddddd|0~~99999|Counter state, read only
2253 -|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2254 -|Q|QW|QW ddddd|0~~99999|
2255 -|AI|AIW|AIW ddddd|0~~99999|
2256 -|AQ|VB|VB ddddd|0~~99999|
2257 -|V|VW|VW ddddd|0~~99998|(((
2258 -VW0=VB (0~~1)
2259 -
2260 -VW2=VB (2~~3)
2261 -
2262 -Address value is a multiple of 2
2263 -)))
2264 -|V|VD|VD ddddd|0~~99998|(((
2265 -VD0=VB (0~~3)
2266 -
2267 -VD2=VB (4~~7)
2268 -
2269 -Address value is a multiple of 4
2270 -)))
2271 -|M|MB|MB ddddd|0~~99999|
2272 -|M|MW|MW ddddd|0~~99999|(((
2273 -MW0=MB(0~~1)
2274 -
2275 -MW2=MB(2~~3)
2276 -
2277 -Address value is a multiple of 2
2278 -)))
2279 -|M|MD|MD ddddd|0~~99999|(((
2280 -MD0=MB(0~~3)
2281 -
2282 -MD4=MB(4~~7)
2283 -
2284 -Address value is a multiple of 4
2285 -)))
2286 -|T|TW|TW ddddd|0~~99999|Value of timer
2287 -|C|CW|CW ddddd|0~~99999|Value of counter
2288 -|W|SW|SW ddddd|0~~99999|
2289 -
2290 -**Communication Settings**
2291 -
2292 -Enable HMI Ethernet in [Project Settings];
2293 -
2294 -(% style="text-align:center" %)
2295 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2296 -
2297 -Set PLC IP in [Device IP] settings;
2298 -
2299 -(% style="text-align:center" %)
2300 -[[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2301 -
2302 -* PLC IP Address: PLC IP
2303 -* PLC pot No.: 102(fixed)
2304 -* Network:TCP_Client_2N(fixed)
2305 -
2306 -(% style="text-align:center" %)
2307 -[[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2308 -
2309 -* Wait timeout: depend on actual network situation (more than 1500 ms)
2310 -
2311 -**Cable Wiring**
2312 -
2313 -(% style="text-align:center" %)
2314 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2315 -
2316 -== **S7-300 Ethernet** ==
2317 -
2318 -Supported Series: Siemens S7-300 series PLC
2319 -
2320 -**HMI Setting**
2321 -
2322 -(% class="table-bordered" %)
2323 -|**Items**|**Settings**|**Note**
2324 -|Protocol|Simens S7-300 Ethernet|
2325 -|Connection|Ethernet|
2326 -|Port No.|102|
2327 -|PLC station No.|2|Need to be same as the PLC setting
2328 -
2329 -**Address List**
2330 -
2331 -(% class="table-bordered" %)
2332 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2333 -|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2334 -|Q|Q|Q ddddd.o|0.0~~99999.7|
2335 -|M|M|M ddddd.o|0.0~~99999.7|
2336 -|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2337 -nn: block number;
2338 -
2339 -dddd: address;
2340 -)))
2341 -|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2342 -|Q|QW|QW ddddd|0~~99999|
2343 -|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2344 -|MW|MW ddddd|0~~99999|(((
2345 -MW0=MB(0~~1)
2346 -
2347 -MW2=MB(2~~3)
2348 -
2349 -Address value is a multiple of 2
2350 -)))
2351 -|MD|MD ddddd|0~~99999|(((
2352 -MD0=MB(0~~3)
2353 -
2354 -MD4=MB(4~~7)
2355 -
2356 -Address value is a multiple of 4
2357 -)))
2358 -|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2359 -nn: block number;
2360 -
2361 -dddd: address
2362 -)))
2363 -|DBxDBW|DBxDBW nndddd|0~~99999999
2364 -|DBxDBD|DBxDBD nndddd|0~~99999999
2365 -
2366 -**Communication Settings**
2367 -
2368 -Enable HMI Ethernet in [Project Settings];
2369 -
2370 -(% style="text-align:center" %)
2371 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2372 -
2373 -Set PLC IP in [Device IP] settings;
2374 -
2375 -(% style="text-align:center" %)
2376 -[[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2377 -
2378 -* PLC IP Address: PLC IP
2379 -* PLC pot No.: 102(fixed)
2380 -* Network:TCP_Client_2N(fixed)
2381 -
2382 -(% style="text-align:center" %)
2383 -[[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2384 -
2385 -* Wait timeout: depend on actual network situation (more than 1500 ms)
2386 -
2387 -**Cable Wiring**
2388 -
2389 -(% style="text-align:center" %)
2390 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2391 -
2392 -== **S7-1200 Ethernet** ==
2393 -
2394 -Supported Series: Siemens S7-1200
2395 -
2396 -**HMI Setting**
2397 -
2398 -(% class="table-bordered" %)
2399 -|**Items**|**Settings**|**Note**
2400 -|Protocol|Siemens S7-1200|
2401 -|Connection|Ethernet|
2402 -|Port No.|102|
2403 -|PLC station No.|2|
2404 -
2405 -**Address List**
2406 -
2407 -(% class="table-bordered" %)
2408 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2409 -|(% rowspan="4" %)Bit|I|I|M d.o|(((
2410 -d:0~-~-9999
2411 -
2412 -o:0-7
2413 -)))|
2414 -|Q|Q|Q d.o|(((
2415 -d:0~-~-9999
2416 -
2417 -o:0-7
2418 -)))|
2419 -|M|M|M d.o|(((
2420 -d:0~-~-9999
2421 -
2422 -o:0-7
2423 -)))|
2424 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2425 -nn:0-9999,
2426 -
2427 -dddd:0-9999,
2428 -
2429 -o:0-7
2430 -)))|(((
2431 -nn:DB No.
2432 -
2433 -dddd:address value
2434 -
2435 -o: digit address
2436 -)))
2437 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2438 -|M|MW|MW d|d:0-99999|(((
2439 -MW0=MB(0~~1)
2440 -
2441 -MW2=MB(2~~3)
2442 -
2443 -Address value is a multiple of 2
2444 -)))
2445 -|M|MD|MD d|d:0-99999|(((
2446 -MD0=MB(0~~3)
2447 -
2448 -MD4=MB(4~~7)
2449 -
2450 -Address value is a multiple of 4
2451 -)))
2452 -|I|IW|IW d|d:0-99999|
2453 -|Q|QW|QW d|d:0-99999|
2454 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2455 -nn:0-9999
2456 -
2457 -dddd:0-9999
2458 -)))|(((
2459 -nn:DB No.
2460 -
2461 -dddd:address value
2462 -)))
2463 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2464 -nn:0-9999
2465 -
2466 -dddd:0-9999
2467 -)))|(((
2468 -nn:DB No.
2469 -
2470 -dddd:address value
2471 -
2472 -Address value is a multiple of 2
2473 -)))
2474 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2475 -nn:0-9999
2476 -
2477 -dddd:0-9999
2478 -)))|(((
2479 -nn:DB No.
2480 -
2481 -dddd:address value
2482 -
2483 -Address value is a multiple of 4
2484 -)))
2485 -
2486 -**Communication Settings**
2487 -
2488 -Enable HMI Ethernet in [Project Settings];
2489 -
2490 -(% style="text-align:center" %)
2491 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2492 -
2493 -Set PLC IP in [Device IP] settings;
2494 -
2495 -(% style="text-align:center" %)
2496 -[[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2497 -
2498 -**✎Note:**
2499 -
2500 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2501 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2502 -
2503 -**PLC Settings**
2504 -
2505 -Add BD
2506 -
2507 -* Please uncheck [Symbolic access only] option;
2508 -
2509 -(% style="text-align:center" %)
2510 -[[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2511 -
2512 -Address settings, using BD2 as example.
2513 -
2514 -* DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2515 -* 2 represent DB block number
2516 -* xxxx represent address
2517 -
2518 -**Such as:**
2519 -
2520 -* DBxDBB20000 = DB2.DBB0
2521 -* DBxDBW20004 = DB2.DBW4
2522 -
2523 -(% style="text-align:center" %)
2524 -[[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2525 -
2526 -**How to connect with S7-1200 Firmware V4.0**
2527 -
2528 -PLC configuration
2529 -
2530 -* Double click [device configuration] in Siemens via software
2531 -* Double click [protection] to enter protection configuration screen
2532 -
2533 -(% style="text-align:center" %)
2534 -[[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2535 -
2536 -* Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2537 -
2538 -(% style="text-align:center" %)
2539 -[[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2540 -
2541 -DB settings
2542 -
2543 -* Right click [DB], select [properties]
2544 -* Uncheck [optimized block access]
2545 -
2546 -**Cable Wiring**
2547 -
2548 -(% style="text-align:center" %)
2549 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2550 -
2551 -== **LOGO Ethernet** ==
2552 -
2553 -Supported Series: Siemens Logo 0BA0 series
2554 -
2555 -**HMI Settings**
2556 -
2557 -(% class="table-bordered" %)
2558 -|**Items**|**Settings**|**Note**
2559 -|Protocol|Siemens LOGO|
2560 -|Connection|Ethernet|
2561 -|Port No.|102|
2562 -|PLC station No.|2|
2563 -
2564 -**Address List**
2565 -
2566 -(% class="table-bordered" %)
2567 -|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2568 -|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2569 -|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2570 -|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2571 -|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2572 -|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2573 -|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2574 -|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2575 -|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2576 -|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2577 -|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2578 -|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2579 -|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2580 -|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2581 -|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2582 -|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2583 -
2584 -**PLC Settings in LOGO Software:**
2585 -
2586 -Click [Tools]~-~-[Ethernet Connections],shown as below.
2587 -
2588 -(% style="text-align:center" %)
2589 -[[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2590 -
2591 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2592 -
2593 -(% style="text-align:center" %)
2594 -[[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2595 -
2596 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2597 -
2598 -(% style="text-align:center" %)
2599 -[[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2600 -
2601 -**Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2602 -
2603 -(% style="text-align:center" %)
2604 -[[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2605 -
2606 -
2607 -(% style="text-align:center" %)
2608 -[[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2609 -
2610 -
2611 -**HMI Communication Settings**
2612 -
2613 -Set PLC IP in [Device IP] settings;
2614 -
2615 -(% style="text-align:center" %)
2616 -[[image:SiemensLOGODeviceIP.png]]
2617 -
2618 -Enable HMI Ethernet in [Project Settings];
2619 -
2620 -(% style="text-align:center" %)
2621 -[[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2622 -
2623 -TSAP setting
2624 -
2625 -* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2626 -* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2627 -* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2628 -
2629 -**✎Note:**
2630 -
2631 -* The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2632 -
2633 -(% style="text-align:center" %)
2634 -[[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2635 -
2636 -
2637 -* AI word address and Ibit address are read-only and cannot be written on HMI.
2638 -* VW address should be even number.such as VW0, VW2, VW4...
2639 -* VD address it takes two VW addresses.such as VD0,VD4,VD8...
2640 -* Written value of RTC cannot exceed 255.
2641 -
2642 -**Cable Wiring**
2643 -
2644 -(% style="text-align:center" %)
2645 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2646 -
2647 -== **S7-XXX Ethernet** ==
2648 -
2649 -Supported Series: Siemens S7-400, S7-1200 and S7-1500
2650 -
2651 -**HMI Setting**
2652 -
2653 -(% class="table-bordered" style="width:823px" %)
2654 -|=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2655 -|Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2656 -|Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2657 -|Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2658 -|Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2659 -|HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2660 -
2661 -Slot from TIA Portal is equal to Device No. of PIStudio
2662 -
2663 -Rack from TIA Portal is equal to HMI No. of PIStudio
2664 -
2665 -(% style="text-align:center" %)
2666 -[[image:S7-XXXCommunication Settings.png]]
2667 -
2668 -(% style="text-align:center" %)
2669 -[[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2670 -
2671 -**Address List**
2672 -
2673 -(% class="table-bordered" %)
2674 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2675 -|(% rowspan="4" %)Bit|I|I|M d.o|(((
2676 -d:0~-~-9999
2677 -
2678 -o:0-7
2679 -)))|
2680 -|Q|Q|Q d.o|(((
2681 -d:0~-~-9999
2682 -
2683 -o:0-7
2684 -)))|
2685 -|M|M|M d.o|(((
2686 -d:0~-~-9999
2687 -
2688 -o:0-7
2689 -)))|
2690 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2691 -nn:0-9999,
2692 -
2693 -dddd:0-9999,
2694 -
2695 -o:0-7
2696 -)))|(((
2697 -nn:DB No.
2698 -
2699 -dddd:address value
2700 -
2701 -o: digit address
2702 -)))
2703 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2704 -|M|MW|MW d|d:0-99999|(((
2705 -MW0=MB(0~~1)
2706 -
2707 -MW2=MB(2~~3)
2708 -
2709 -Address value is a multiple of 2
2710 -)))
2711 -|M|MD|MD d|d:0-99999|(((
2712 -MD0=MB(0~~3)
2713 -
2714 -MD4=MB(4~~7)
2715 -
2716 -Address value is a multiple of 4
2717 -)))
2718 -|I|IW|IW d|d:0-99999|
2719 -|Q|QW|QW d|d:0-99999|
2720 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2721 -nn:0-9999
2722 -
2723 -dddd:0-9999
2724 -)))|(((
2725 -nn:DB No.
2726 -
2727 -dddd:address value
2728 -)))
2729 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2730 -nn:0-9999
2731 -
2732 -dddd:0-9999
2733 -)))|(((
2734 -nn:DB No.
2735 -
2736 -dddd:address value
2737 -
2738 -Address value is a multiple of 2
2739 -)))
2740 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2741 -nn:0-9999
2742 -
2743 -dddd:0-9999
2744 -)))|(((
2745 -nn:DB No.
2746 -
2747 -dddd:address value
2748 -
2749 -Address value is a multiple of 4
2750 -)))
2751 -
2752 -**Communication Settings**
2753 -
2754 -Enable HMI Ethernet in [Project Settings];
2755 -
2756 -(% style="text-align:center" %)
2757 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2758 -
2759 -Set PLC IP in [Device IP] settings;
2760 -
2761 -(% style="text-align:center" %)
2762 -[[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2763 -
2764 -**✎Note:**
2765 -
2766 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2767 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2768 -
2769 -**Cable Wiring**
2770 -
2771 -{{id name="OLE_LINK8"/}}
2772 -
2773 -(% style="text-align:center" %)
2774 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2775 -
2776 2776  = **User Defined Protocol** =
2777 2777  
2778 2778  If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
... ... @@ -3398,3 +3398,168 @@
3398 3398  **Cable Wiring**
3399 3399  
3400 3400  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2866 +
2867 +
2868 += **OpenCAN** =
2869 +
2870 +OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
2871 +
2872 +This protocol is only available in PI8000 series HMI.
2873 +
2874 +**HMI Settings**
2875 +
2876 +|**Items**|**Settings**|**Note**
2877 +|Protocol|OPENCAN|
2878 +|Connection|CAN port|
2879 +|Baud rate|250000|
2880 +
2881 +**CAN frame setting in HMI**
2882 +
2883 +Click [OpenCAN setting] button in communication setting window;
2884 +
2885 +(% style="text-align:center" %)
2886 +[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
2887 +
2888 +Click [Add] to create a new frame;
2889 +
2890 +(% style="text-align:center" %)
2891 +[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
2892 +
2893 +|**No**|**Items**|**Description**
2894 +|1|Add|add a frame related to register address
2895 +|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2896 +|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2897 +|4|Modify|Modify the frames in frame management
2898 +|5|Copy|Copy one frame to another
2899 +|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
2900 +|7|Empty|All frames in the list are cleared
2901 +|8|Browse|Displays configuration files in XML format in IE
2902 +|9|OK|Complete the configuration of the frame and exit
2903 +
2904 +Set CANBUS frame in setting windows
2905 +
2906 +(% style="text-align:center" %)
2907 +[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
2908 +
2909 +|**No**|**Items**|**Description**
2910 +|1|ID|Set the ID of a can frame in hexadecimal format;
2911 +|2|ID assign|split the ID by PF, PS, and SA;
2912 +|3|Frame type|Select Standard frame or Extended Frame;
2913 +|4|Frame format|Select between data frame and remote Frame;
2914 +|5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
2915 +|6|Use address|(((
2916 +Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
2917 +
2918 +**Edit:** Set a bit or word address by its format;
2919 +
2920 +**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
2921 +)))
2922 +|(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
2923 +|Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
2924 +|Feedback mode: feedback mode includes no response, confirm response and data response;
2925 +|No response: the device or touch screen will not receive feedback;
2926 +|Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
2927 +|Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
2928 +|response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
2929 +|Response timeout: sets whether the response frame timeout;
2930 +|(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
2931 +|Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
2932 +|Manually send: a manually send tick indicates only one send;
2933 +|9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
2934 +|10|Note|Fill the text to explain the meaning of the frame;
2935 +|11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
2936 +|12|Current operation display|Display the description of current operation;
2937 +|13|Add|Add a new frame;
2938 +|14|Save frame|Save the configured frame format;
2939 +|15|Cancel|Cancel the frame configuration;
2940 +
2941 +Set CAN address (Read or write operation);
2942 +
2943 +(% style="text-align:center" %)
2944 +[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
2945 +
2946 +|**No.**|**Item**|**Description**
2947 +|1|Current address|Displays the register type and register address set by the user in the data access interface
2948 +|(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
2949 +|If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
2950 +|If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
2951 +|(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
2952 +|If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
2953 +|If the trigger condition is a writing operation, there are two situations:(((
2954 +* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
2955 +* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
2956 +)))
2957 +|(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
2958 +|If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
2959 +|4|Add|Add current configuration
2960 +|5|Close|Close the configuration window to exit
2961 +
2962 +**Multiple Packages Settings**
2963 +
2964 +(% style="text-align:center" %)
2965 +[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
2966 +
2967 +Check [Multiple packages supported] to open [Multiple package data] window, as below show.
2968 +
2969 +Select Multiple package type
2970 +
2971 +* Not Multiple packages
2972 +* J1939 Multiple packages
2973 +* Customized Multiple packages
2974 +
2975 +Click [Edit Receive data] for [Receive] settings
2976 +
2977 +* Start code+ Total length (J1939)
2978 +
2979 +(% style="text-align:center" %)
2980 +[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2981 +
2982 +As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2983 +
2984 +* Start code + Data max length (J1939)
2985 +
2986 +(% style="text-align:center" %)
2987 +[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2988 +
2989 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2990 +
2991 +* Data max length (J1939)
2992 +
2993 +(% style="text-align:center" %)
2994 +[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2995 +
2996 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2997 +
2998 +* Customized multiple package
2999 +
3000 +(% style="text-align:center" %)
3001 +[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3002 +
3003 +As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3004 +
3005 +Click [Edit Send data] for [Send] setting
3006 +
3007 +* J1939
3008 +
3009 +(% style="text-align:center" %)
3010 +[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3011 +
3012 +[Data] is all data to be sent.
3013 +
3014 +Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3015 +
3016 +* Customized multiple package
3017 +
3018 +(% style="text-align:center" %)
3019 +[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3020 +
3021 +[Data] is all data to be sent.
3022 +
3023 +As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3024 +
3025 +**Cable Wiring**
3026 +
3027 +(% style="text-align:center" %)
3028 +[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3029 +
3030 +**✎Note:** The address interval between each frame need to be more than a word address;
image-20220829151746-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +53.1 KB
Content
image-20220829151848-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +15.0 KB
Content
image-20220829152016-3.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +51.2 KB
Content
image-20220829152042-4.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +17.0 KB
Content
image-20220829152102-5.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +16.3 KB
Content
image-20220829152327-6.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +42.5 KB
Content
image-20220829152610-7.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +55.5 KB
Content
image-20220829155452-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +38.1 KB
Content
image-20220829162116-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +50.4 KB
Content
image-20220830094600-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +40.4 KB
Content
image-20220830094657-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +53.4 KB
Content
image-20220830094929-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +90.4 KB
Content
image-20220830095131-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +25.7 KB
Content
image-20220830140537-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +35.2 KB
Content
image-20220830140629-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +48.4 KB
Content
image-20220830141138-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +82.9 KB
Content