Changes for page 12 PLC Protocol OLD
Last modified by Mora Zhou on 2024/12/05 14:53
From version 83.1
edited by Ben
on 2022/08/29 14:33
on 2022/08/29 14:33
Change comment:
There is no comment for this version
Summary
-
Page properties (3 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 45 removed)
- S7-XXXCommunication Settings.png
- S7-XXXCommunication SettingsPI.png
- S7-XXXCommunication SettingsPIStudio.png
- SiemensLOGODeviceIP.png
- image-20220810164710-1.png
- image-20220810165247-2.png
- image-20220810165759-3.png
- image-20220810171237-4.png
- image-20220810172010-5.png
- image-20220810172412-1.png
- image-20220811102219-3.png
- image-20220811103005-4.png
- image-20220811103131-5.png
- image-20220811103200-6.png
- image-20220811103227-7.png
- image-20220811104012-1.png
- image-20220811115454-1.png
- image-20220811140308-1.png
- image-20220811140530-2.png
- image-20220811163047-1.png
- image-20220811163943-2.png
- image-20220811170248-1.png
- image-20220811170753-2.png
- image-20220817154212-1.jpeg
- image-20220819093729-1.png
- image-20220819093729-10.png
- image-20220819093729-12.png
- image-20220819093729-15.png
- image-20220819093729-17.png
- image-20220819093729-18.png
- image-20220819093729-2.png
- image-20220819093729-3.png
- image-20220819093729-4 (1).png
- image-20220819093729-4.png
- image-20220819093729-5.png
- image-20220819093729-6.jpeg
- image-20220819093729-7.png
- image-20220819093730-19.png
- image-20220819093730-20.png
- image-20220819101447-3.jpeg
- image-20220819105530-1.png
- image-20220819105630-3.png
- image-20220819105644-4.png
- image-20220819105928-9.png
- image-20220820150853-1.png
Details
- Page properties
-
- Parent
-
... ... @@ -1,1 +1,1 @@ 1 -PIStudio.WebHome 1 +PIStudio.1 User Manual.WebHome - Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. Ben1 +XWiki.admin - Content
-
... ... @@ -18,7 +18,7 @@ 18 18 19 19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established. 20 20 21 -= **Communication Settings** =21 += **Protocol Selection & Communication Parameters** = 22 22 23 23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication]. 24 24 ... ... @@ -29,26 +29,32 @@ 29 29 (% style="text-align:center" %) 30 30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]] 31 31 32 -* Wait Timeout(ms): The time HMI waits for a response from the PLC. 33 -* Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters. 34 -* Retry Count: The number of retries when there is no response in the communication between HMI and PLC. 35 -* Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC. 36 -* Delay Time(ms): The speed at which the HMI communicates with the device. 37 -* Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length. 38 -* Maximum Span: Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses. 32 +Wait Timeout(ms): The time HMI waits for a response from the PLC. 39 39 34 +Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters. 35 + 36 +Retry Count: The number of retries when there is no response in the communication between HMI and PLC. 37 + 38 +Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC. 39 + 40 +Delay Time(ms): The speed at which the HMI communicates with the device. 41 + 42 +Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length. 43 + 44 +Maximum Span: Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses. 45 + 40 40 **Operating Procedure** 41 41 42 -After creating the [Quick_Start] project,select the [Project]->[Communication]. 48 +1) After creating the [Quick_Start] project,select the [Project]->[Communication]. 43 43 44 44 (% style="text-align:center" %) 45 45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]] 46 46 47 -Click “Setting” to open protocol setting windows. 53 +2) Click “Setting” to open protocol setting windows. 48 48 49 49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]] 50 50 51 -Select communication protocol, users could select serial port, Ethernet port, CAN port or USB. 57 +3) Select communication protocol, users could select serial port, Ethernet port, CAN port or USB. 52 52 53 53 * Serial port: 54 54 ... ... @@ -69,7 +69,7 @@ 69 69 70 70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]] 71 71 72 -About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation. 78 +4) About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation. 73 73 74 74 * Serial port: 75 75 ... ... @@ -83,395 +83,69 @@ 83 83 (% style="text-align:center" %) 84 84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]] 85 85 86 -Click [OK] button to save settings and close the dialog; 92 +5) Click [OK] button to save settings and close the dialog; 87 87 88 -= Createcommunication with WECON PLC=94 += **Allen-Bradley** = 89 89 90 -== ** LX3V SerialProtocol** ==96 +== **FreeTag Ethernet/IP (CompactLogix)** == 91 91 92 - Supportedseries: WECONLX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM98 +Allen-Brandly CompactLogix 93 93 94 94 **HMI Settings** 95 95 96 96 (% class="table-bordered" %) 97 -|**Item**|**Settings**|**Note** 98 -|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| 99 -|Connection|RS422/RS485| 100 -|Baud rate|9600| 101 -|Data bit|7| 102 -|Parity|EVEN| 103 -|Stop bit|1| 104 -|PLC station No.|1| 103 +|**Items**|**Settings**|**Note** 104 +|Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)| 105 +|Connection|Ethernet| 106 +|Port No.|44818| 105 105 106 -** AddressList**108 +**PLC Setting** 107 107 108 -(% class="table-bordered" %) 109 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 110 -|(% rowspan="6" %)Bit|X|X|Xo|0~~303237| 111 -|Y|Y|Y o|0~~303237| 112 -|M|M|M d|0~~99999| 113 -|T|T|T d|0~~99999| 114 -|C|C|C d|0~~99999| 115 -|S|S|S d|0~~99999| 116 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237| 117 -|Y|Y|Y o|0~~303237| 118 -|M|M|M d|0~~99999| 119 -|T|T|T d|0~~99999| 120 -|C|C|C d|0~~199| 121 -|D|D|D d|0~~7999| 122 -|S|S|S d|0~~99999| 123 -|SD|SD|SD d|8000~~9999| 110 +1) Create new tags 124 124 125 -**Cable Wiring** 126 - 127 -* **RS485** 128 - 129 129 (% style="text-align:center" %) 130 -[[image:12.PLC Protocol_html_ 1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]113 +[[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]] 131 131 132 - ***RS422**115 +2) Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments]) 133 133 134 134 (% style="text-align:center" %) 135 -[[image:12.PLC Protocol_html_5 c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]118 +[[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]] 136 136 137 - **✎Note:**120 +3) Import labels, please open [Communication] window and click [Import label]; 138 138 139 -* HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . 140 -* If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. 122 +4) Select csv file, all tags will be displayed as belows; 141 141 142 -[[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] 143 - 144 -(% class="wikigeneratedid" id="HHMIsettings" %) 145 -**HMI settings** 146 - 147 -**Download PIStudio Software** 148 - 149 -Please visit the link below to get the latest version PIstudio for HMI programming: 150 - 151 -* [[Download link>>doc:PIStudio.Download.3 Software.WebHome]] 152 - 153 -**Create a new HMI project connect with PLC** 154 - 155 -Check the link below for the video to show you how to get started with a new project 156 - 157 -* [[Video>>https://youtu.be/0FpmDZe_8U8]] 158 - 159 -For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]] 160 - 161 -**General** 162 - 163 -HMI could communicate with PLC and support many PLC protocols. It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example. 164 - 165 -**Protocol settings** 166 - 167 -The communication between two devices requires a protocol. The following contents show the steps of protocol settings. 168 - 169 -Please select the protocol, when creating a new project. 170 - 171 -1. Select the COM port for communication; 172 -1. PLC type: It means PLC brand, like WECON; 173 -1. PLC model: It shows the model of PLC, such as LX3V; 174 - 175 175 (% style="text-align:center" %) 176 -[[image: image-20220819093729-1.png]]125 +[[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]] 177 177 178 - If you wantto changethe protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.127 +**✎Note:** 179 179 180 -(% style="text-align:center" %) 181 -[[image:image-20220819093729-2.png]] 129 +Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format. 182 182 183 - 184 -The steps to change the protocol for project are as follows. 185 - 186 -1. Click [Setting] to open the [Communication device] window; 187 -1. Select communication port, such as COM1; 188 -1. Select Serial port for communication, such as RS422; 189 -1. Select device type (device brand), such as WECON; 190 -1. Select the protocol for communication, such as WECON LX3V; 191 - 192 192 (% style="text-align:center" %) 193 -[[image:image-20 220819093729-3.png]]132 +[[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]] 194 194 195 - **Parameter settings**134 +The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting. 196 196 197 - The parameters settings are in [Communication]window,shownas followingbelow.136 +**Communication settings in HMI** 198 198 199 -1. Click [Setting] to open the [COM port setting] window; 200 -1. Set the parameters such as [connection], [Baud rate] and so on; 138 +1) Enable HMI Ethernet in [Project Settings]; 201 201 202 202 (% style="text-align:center" %) 203 -[[image: image-20220819093729-4.png||height="636" width="818"]]141 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]] 204 204 205 -(% start="3" %) 206 -1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value. 143 +2) Set PLC IP in [Device IP] settings; 207 207 208 208 (% style="text-align:center" %) 209 -[[image:image-20 220819093729-5.png]]146 +[[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]] 210 210 211 -** Set PLCddressin HMI screen**148 +**Cable Wiring** 212 212 213 -1. Place the objects to HMI screen; 214 -1. Double-click the object to open the setting window; 215 -1. Click “Edit” to open the address setting windows; 216 -1. Connection: select the serial port in HMI; 217 -1. Address type: All the PLC address types will be display in this list, such as M; 218 -1. Address No.: Please input the number of this address, such as 0; 219 - 220 -[[image:image-20220819093729-6.jpeg]] 221 - 222 -**Communication cable** 223 - 224 -In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition. 225 - 226 226 (% style="text-align:center" %) 227 -[[image: image-20220819093729-7.png]]151 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]] 228 228 229 -** HMI communication PLC use Modbus**153 +== **MicroLogix** == 230 230 231 -* HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]] 232 -* PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]] 233 - 234 -(% class="wikigeneratedid" id="HPLCsettings" %) 235 -**PLC settings** 236 - 237 -**Download PLC Software** 238 - 239 -Please visit below link to get the latest version PLC Editor for HMI programming 240 - 241 -* LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]] 242 -* LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]] 243 - 244 -**Start a new PLC project** 245 - 246 -Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list. 247 - 248 -(% style="text-align:center" %) 249 -[[image:image-20220819101447-3.jpeg]] 250 - 251 - 252 - 253 -**Add a new instruction ** 254 - 255 -Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol. 256 - 257 -(% style="text-align:center" %) 258 -[[image:image-20220819105530-1.png]] 259 - 260 -You could also select the ladder symbol from the menu bar directly. 261 - 262 -[[image:image-20220819093729-11.png]] 263 - 264 -[[image:image-20220819093729-12.png]] 265 - 266 -**Add comment to PLC program** 267 - 268 -(% style="text-align:center" %) 269 -[[image:image-20220819105630-3.png]] 270 - 271 -**Add the statement to PLC program** 272 - 273 -Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit. 274 - 275 -(% style="text-align:center" %) 276 -[[image:image-20220819105644-4.png]] 277 - 278 -**Compile ** 279 - 280 -You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error. 281 - 282 -[[image:image-20220819093729-15.png]] 283 - 284 -**Download setting ** 285 - 286 -Click on “Transfer Setup” to select download mode. 287 - 288 -[[image:image-20220820150853-1.png]]**Download PLC program to PLC** 289 - 290 -Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK” 291 - 292 -[[image:image-20220819093729-17.png]] 293 - 294 -**Upload PLC program from PLC** 295 - 296 -Read the PLC program from PLC to computer. 297 - 298 -[[image:image-20220819093729-18.png]] 299 - 300 -**Device monitor** 301 - 302 -Monitor the value of certain address in PLC, double click “Current value” to change the value in this address. 303 - 304 -[[image:image-20220819093730-19.png]] 305 - 306 -**Online monitor** 307 - 308 -Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd. 309 - 310 -[[image:image-20220819093730-20.png]] 311 - 312 -**Monitor edit** 313 - 314 -In this mode, you could edit the PLC program during PLC is running. 315 - 316 - 317 -(% style="text-align:center" %) 318 -[[image:image-20220819105928-9.png||height="229" width="669"]] 319 - 320 -== **LX5V Serial Protocol** == 321 - 322 -This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. 323 - 324 -**Software configuration of PLC** 325 - 326 -**1)PLC programming software** 327 - 328 -[[image:image-20220810164710-1.png]] 329 - 330 -**2)New PLC project** 331 - 332 -Click New Project and select the PLC model. 333 - 334 -[[image:image-20220810172412-1.png]] 335 - 336 - 337 -**3)Set Serial port parameters** 338 - 339 -Follow the steps below to configure Serial port parameters 340 - 341 -Baud rate:115200 342 - 343 -Data bit:8 344 - 345 -Stop bit:1 346 - 347 -Parity:No verification 348 - 349 -[[image:image-20220810165759-3.png]] 350 - 351 - 352 -**4)Registers list** 353 - 354 -[[image:image-20220811102219-3.png]] 355 - 356 - 357 -**HMI software configuration** 358 - 359 -**1)HMI programming software** 360 - 361 - [[image:image-20220810171237-4.png]] 362 - 363 -**2)New HMI project** 364 - 365 -Click New Project and select the HMI model. 366 - 367 -[[image:image-20220810172010-5.png]] 368 - 369 -**3)Set communication port parameters** 370 - 371 -Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. 372 - 373 -Baud rate:115200 374 - 375 -Data bit:8 376 - 377 -Stop bit:1 378 - 379 -Parity:No verification 380 - 381 - 382 -[[image:image-20220811104012-1.png]] 383 - 384 - 385 -**hardware connection** 386 - 387 -**1)Hardware wiring diagram** 388 - 389 -This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: 390 - 391 -[[image:image-20220811103005-4.png]] 392 - 393 - 394 -[[image:image-20220811103227-7.png]] 395 - 396 -The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. 397 - 398 -== **LX5V-N Ethernet protocol** == 399 - 400 -(% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. 401 - 402 -**Software configuration of PLC** 403 - 404 -**1)PLC programming software** 405 - 406 -[[image:image-20220810164710-1.png]] 407 - 408 -**2)New PLC project** 409 - 410 -Click New Project and select the PLC model. 411 - 412 -[[image:image-20220811115454-1.png]] 413 - 414 - 415 -**3)Set Ethernet port parameters** 416 - 417 -Follow the steps below to configure Ethernet parameters 418 - 419 -PLC IP address:192.168.39.200 420 - 421 -default gateway:192.168.39.1 422 - 423 -subnet mask:255.255.255.0 424 - 425 -[[image:image-20220811140530-2.png]] 426 - 427 - 428 -**4)Registers list** 429 - 430 -[[image:image-20220811102219-3.png]] 431 - 432 - 433 -**HMI software configuration** 434 - 435 -**1)HMI programming software** 436 - 437 - [[image:image-20220810171237-4.png]] 438 - 439 -**2)New HMI project** 440 - 441 -Click New Project and select the HMI model. 442 - 443 -[[image:image-20220810172010-5.png]] 444 - 445 -**3)Set communication port parameters** 446 - 447 -Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. 448 - 449 -HMI IP address:192.168.39.201 450 - 451 -default gateway:192.168.39.1 452 - 453 -subnet mask:255.255.255.0 454 - 455 -[[image:image-20220811170753-2.png]] 456 - 457 -Next, click Communication Settings to configure the IP of the HMI communication object. 458 - 459 -[[image:image-20220811163047-1.png]] 460 - 461 -**hardware connection** 462 - 463 -**1)Hardware wiring diagram** 464 - 465 -This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: 466 - 467 -[[image:image-20220811170248-1.png]] 468 - 469 -The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. 470 - 471 -= Create communication with **Rockwell PLC** = 472 - 473 -== **MicroLogix Protocol** == 474 - 475 475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 476 476 477 477 **HMI Settings** ... ... @@ -507,78 +507,24 @@ 507 507 508 508 **Cable Wiring** 509 509 510 - 511 511 (% style="text-align:center" %) 512 512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]] 513 513 514 -== ** FreeTagEthernet/IP(CompactLogix)** ==193 +== **AB PLC address edit** == 515 515 516 -Allen-Bra ndly CompactLogix195 +The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200. 517 517 518 -** HMISettings**197 +**Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal). 519 519 520 -(% class="table-bordered" %) 521 -|**Items**|**Settings**|**Note** 522 -|Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)| 523 -|Connection|Ethernet| 524 -|Port No.|44818| 199 +**Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal). 525 525 526 -** PLCSetting**201 +**Word address S:** The word address ranges from 0 to 255 (decimal). 527 527 528 - Create newtags203 +**Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal). 529 529 530 -(% style="text-align:center" %) 531 -[[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]] 205 +**✎Note: **Register address TP, CS, CP, N, F and TS address edit tare he same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table. 532 532 533 -Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments]) 534 534 535 -(% style="text-align:center" %) 536 -[[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]] 537 - 538 -Import labels, please open [Communication] window and click [Import label]; 539 - 540 -Select csv file, all tags will be displayed as belows; 541 - 542 -(% style="text-align:center" %) 543 -[[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]] 544 - 545 -**✎Note:** 546 - 547 -Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format. 548 - 549 -(% style="text-align:center" %) 550 -[[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]] 551 - 552 -The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting. 553 - 554 -**Communication settings in HMI** 555 - 556 -Enable HMI Ethernet in [Project Settings]; 557 - 558 -(% style="text-align:center" %) 559 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]] 560 - 561 -Set PLC IP in [Device IP] settings; 562 - 563 -(% style="text-align:center" %) 564 -[[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]] 565 - 566 -**Cable Wiring** 567 - 568 -(% style="text-align:center" %) 569 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]] 570 - 571 -== **AB PLC address edit** == 572 - 573 -The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200. 574 - 575 -* **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal). 576 -* **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal). 577 -* **Word address S:** The word address ranges from 0 to 255 (decimal). 578 -* **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal). 579 - 580 -**✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table. 581 - 582 582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range** 583 583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15 584 584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15 ... ... @@ -585,567 +585,302 @@ 585 585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15 586 586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15 587 587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15 588 -|**PLC word address type**|**Address format**|**Address range** 589 -|S|ddd|S0 ~~ 255 590 -|TS|ffff|TS0 ~~ FFFF 591 -|TP|ffff|TP0 ~~ FFFF 592 -|CS|ffff|CS0 ~~ FFFF 593 -|CP|ffff|CP0 ~~ FFFF 594 -|N|ffff|N0 ~~ FFFF 595 -|F|ffff|F0 ~~ FFFF 214 +|(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range** 215 +|(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255 216 +|(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF 217 +|(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF 218 +|(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF 219 +|(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF 220 +|(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF 221 +|(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF 596 596 597 -= (% id="cke_bm_43878S"style="display:none" %)****(%%)**Siemens**=223 += **Barcode Scanner** = 598 598 599 - == **S7-200 Smart Ethernet**==225 +Supported: DELI 14880 barcode scanner 600 600 601 -Supported Series: Siemens S7-200 SMART Series Ethernet Module. 602 - 603 -Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]] 604 - 605 605 **HMI Setting** 606 606 607 607 (% class="table-bordered" %) 608 608 |**Items**|**Settings**|**Note** 609 -|Protocol|Simens S7-200 Smart Ethernet| 610 -|Connection|Ethernet| 611 -|Port No.|102| 612 -|PLC station No.|2| 231 +|Protocol|Barcode Scanner| 232 +|Connection|USB| 613 613 614 -** Address List**234 +**Operating Procedures** 615 615 616 -(% class="table-bordered" %) 617 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** 618 -|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7| 619 -|Q|Q|Q ddddd.o|0.0~~99999.7| 620 -|V|VWbit|VWbit ddddd.o|0.0~~99999.7| 621 -|V|V|V ddddd.o|0.0~~99999.7| 622 -|M|M|M ddddd.o|0.0~~99999.7| 623 -|SM|SM|ddddd.o|0.0~~99999.7| 624 -|S|S|ddddd.o|0.0~~99999.7|Read only 625 -|T|T|ddddd|0~~99999|Timer state, read only 626 -|C|C|ddddd|0~~99999|Counter state, read only 627 -|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999| 628 -|Q|QW|QW ddddd|0~~99999| 629 -|AI|AIW|AIW ddddd|0~~99999| 630 -|AQ|VB|VB ddddd|0~~99999| 631 -|V|VW|VW ddddd|0~~99998|((( 632 -VW0=VB (0~~1) 236 +1) Select [Barcode Scanner]; 633 633 634 -VW2=VB (2~~3) 635 - 636 -Address value is a multiple of 2 637 -))) 638 -|V|VD|VD ddddd|0~~99998|((( 639 -VD0=VB (0~~3) 640 - 641 -VD2=VB (4~~7) 642 - 643 -Address value is a multiple of 4 644 -))) 645 -|M|MB|MB ddddd|0~~99999| 646 -|M|MW|MW ddddd|0~~99999|((( 647 -MW0=MB(0~~1) 648 - 649 -MW2=MB(2~~3) 650 - 651 -Address value is a multiple of 2 652 -))) 653 -|M|MD|MD ddddd|0~~99999|((( 654 -MD0=MB(0~~3) 655 - 656 -MD4=MB(4~~7) 657 - 658 -Address value is a multiple of 4 659 -))) 660 -|T|TW|TW ddddd|0~~99999|Value of timer 661 -|C|CW|CW ddddd|0~~99999|Value of counter 662 -|W|SW|SW ddddd|0~~99999| 663 - 664 -**Communication Settings** 665 - 666 -Enable HMI Ethernet in [Project Settings]; 667 - 668 668 (% style="text-align:center" %) 669 -[[image:12.PLC Protocol_html_ 43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]239 +[[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]] 670 670 671 -Set PLCIPin [DeviceIP] settings;241 +2) Set address for receiving; 672 672 673 -(% style="text-align:center" %) 674 -[[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] 243 +3) Set correct length; 675 675 676 -* PLC IP Address: PLC IP 677 -* PLC pot No.: 102(fixed) 678 -* Network:TCP_Client_2N(fixed) 679 - 680 680 (% style="text-align:center" %) 681 -[[image:12.PLC Protocol_html_ 5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]246 +[[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]] 682 682 683 -* Wait timeout: depend on actual network situation (more than 1500 ms)248 +**✎Note:** 684 684 685 - **CableWiring**250 +1) The protocol uploads the information acquired by the USB scanner to the HMI; 686 686 687 -(% style="text-align:center" %) 688 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 252 +2) The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object; 689 689 690 - == **S7-300Ethernet**==254 +3) Recommended model: DELI 14880 barcode scanner; 691 691 692 - SupportedSeries:Siemens S7-300 seriesPLC256 += **Hitachi EHV Series (Ethernet)** = 693 693 694 - **HMISetting**258 +Supported series: Hitachi EHV series 695 695 696 -(% class="table-bordered" %) 697 -|**Items**|**Settings**|**Note** 698 -|Protocol|Simens S7-300 Ethernet| 699 -|Connection|Ethernet| 700 -|Port No.|102| 701 -|PLC station No.|2|Need to be same as the PLC setting 260 +**HMI Settings** 702 702 703 -**Address List** 704 - 705 705 (% class="table-bordered" %) 706 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** 707 -|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7| 708 -|Q|Q|Q ddddd.o|0.0~~99999.7| 709 -|M|M|M ddddd.o|0.0~~99999.7| 710 -|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|((( 711 -nn: block number; 712 - 713 -dddd: address; 714 -))) 715 -|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999| 716 -|Q|QW|QW ddddd|0~~99999| 717 -|(% rowspan="3" %)M|MB|MB ddddd|0~~99999| 718 -|MW|MW ddddd|0~~99999|((( 719 -MW0=MB(0~~1) 720 - 721 -MW2=MB(2~~3) 722 - 723 -Address value is a multiple of 2 724 -))) 725 -|MD|MD ddddd|0~~99999|((( 726 -MD0=MB(0~~3) 727 - 728 -MD4=MB(4~~7) 729 - 730 -Address value is a multiple of 4 731 -))) 732 -|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)((( 733 -nn: block number; 734 - 735 -dddd: address 736 -))) 737 -|DBxDBW|DBxDBW nndddd|0~~99999999 738 -|DBxDBD|DBxDBD nndddd|0~~99999999 739 - 740 -**Communication Settings** 741 - 742 -Enable HMI Ethernet in [Project Settings]; 743 - 744 -(% style="text-align:center" %) 745 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 746 - 747 -Set PLC IP in [Device IP] settings; 748 - 749 -(% style="text-align:center" %) 750 -[[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]] 751 - 752 -* PLC IP Address: PLC IP 753 -* PLC pot No.: 102(fixed) 754 -* Network:TCP_Client_2N(fixed) 755 - 756 -(% style="text-align:center" %) 757 -[[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]] 758 - 759 -* Wait timeout: depend on actual network situation (more than 1500 ms) 760 - 761 -**Cable Wiring** 762 - 763 -(% style="text-align:center" %) 764 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 765 - 766 -== **S7-1200 Ethernet** == 767 - 768 -Supported Series: Siemens S7-1200 769 - 770 -**HMI Setting** 771 - 772 -(% class="table-bordered" %) 773 773 |**Items**|**Settings**|**Note** 774 -|Protocol| SiemensS7-1200|264 +|Protocol|Hitachi EHV series| 775 775 |Connection|Ethernet| 776 -|Port No.|102| 777 -|PLC station No.|2| 266 +|Port No.|3004~~3007| 778 778 779 779 **Address List** 780 780 781 781 (% class="table-bordered" %) 782 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** 783 -|(% rowspan="4" %)Bit|I|I|M d.o|((( 784 -d:0~-~-9999 271 +|**Type**|**Register**|**Range**|**Format**|**Note** 272 +|(% rowspan="6" %)Bit|T|0 - 2545|T DDDD| 273 +|M|0 - 7FFF.f (Hex)|M HHHH.h| 274 +|X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)((( 275 +H1H2H3H4 Module main number 785 785 786 -o:0-7 787 -)))| 788 -|Q|Q|Q d.o|((( 789 -d:0~-~-9999 277 +H1: Remote number 790 790 791 -o:0-7 792 -)))| 793 -|M|M|M d.o|((( 794 -d:0~-~-9999 279 +H2: Unit number 795 795 796 -o:0-7 797 -)))| 798 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|((( 799 -nn:0-9999, 281 +H3: Slot number 800 800 801 -dd dd:0-9999,283 +H4: Word number of Module 802 802 803 -o:0-7 804 -)))|((( 805 -nn:DB No. 285 +H Sub number of Module 806 806 807 - dddd:addressvalue287 +For example:X21.3 808 808 809 -o: digit address 810 -))) 811 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999| 812 -|M|MW|MW d|d:0-99999|((( 813 -MW0=MB(0~~1) 289 +Slot number 2 814 814 815 - MW2=MB(2~~3)291 +Word number of module is 1 816 816 817 -Address value is a multiple of 2 818 -))) 819 -|M|MD|MD d|d:0-99999|((( 820 -MD0=MB(0~~3) 293 +Bit number of module is 3 821 821 822 -MD4=MB(4~~7) 823 - 824 -Address value is a multiple of 4 295 +Remote number and unit number are 0 825 825 ))) 826 -|I|IW|IW d|d:0-99999| 827 -|Q|QW|QW d|d:0-99999| 828 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|((( 829 -nn:0-9999 297 +|Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h 298 +|R|0 – FF.f (Hex)|R HH.h| 299 +|L|0 - 73FF.f (Hex)|L HHHH.h| 300 +|(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH| 301 +|WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)((( 302 +H1H2H3H4 Module main number 830 830 831 -dddd:0-9999 832 -)))|((( 833 -nn:DB No. 304 +H1: Remote number 834 834 835 -dddd:address value 836 -))) 837 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|((( 838 -nn:0-9999 306 +H2: Unit number 839 839 840 -dddd:0-9999 841 -)))|((( 842 -nn:DB No. 308 +H3: Slot number 843 843 844 - dddd:addressvalue310 +H4: Word number of module 845 845 846 -Address value is a multiple of 2 847 -))) 848 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|((( 849 -nn:0-9999 312 +For example:WX21 850 850 851 -dddd:0-9999 852 -)))|((( 853 -nn:DB No. 314 +Word number of module is 1 854 854 855 - dddd:address value316 +Slot number is 2 856 856 857 - Addressvalueisamultipleof4318 +Remote number and unit number are 0 858 858 ))) 320 +|WY|0 – FFFF (Hex)|WY H1H2H3H4 321 +|WR|0 – FFFF (Hex)|WR HHHH| 322 +|WL|0 - 73FF (Hex)|WL HHHH| 323 +|TC|0 - 2559|TC DDDD| 859 859 860 -**Communication Settings**325 +**Communication settings in HMI** 861 861 862 -Enable HMI Ethernet in [Project Settings]; 327 +1) Enable HMI Ethernet in [Project Settings]; 863 863 864 864 (% style="text-align:center" %) 865 865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 866 866 867 -Set PLC IP in [Device IP] settings; 332 +2) Set PLC IP in [Device IP] settings; 868 868 869 869 (% style="text-align:center" %) 870 -[[image:12.PLC Protocol_html_ f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]335 +[[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] 871 871 872 -** ✎Note:**337 +**PLC Configuration** 873 873 874 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 875 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 339 +1) Connect with PLC, select[Online mode]; 876 876 877 -**PLC Settings** 341 +(% style="text-align:center" %) 342 +[[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]] 878 878 879 - AddBD344 +2) Set IP address, it is the same LAN parameters with HMI; 880 880 881 -* Please uncheck [Symbolic access only] option; 882 - 883 883 (% style="text-align:center" %) 884 -[[image:12.PLC Protocol_html_6 43144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]347 +[[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]] 885 885 886 - Addresssettings,usingBD2asexample.349 +3) Save PLC communication parameter, and restart PLC 887 887 888 -* DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1. 889 -* 2 represent DB block number 890 -* xxxx represent address 351 +**PLC Monitor Mode** 891 891 892 - **Such as:**353 +1) Connect with PLC and choose to “online” mode 893 893 894 -* DBxDBB20000 = DB2.DBB0 895 -* DBxDBW20004 = DB2.DBW4 896 - 897 897 (% style="text-align:center" %) 898 -[[image:12.PLC Protocol_html_ 87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]356 +[[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]] 899 899 900 - **Howtoconnect with S7-1200 FirmwareV4.0**358 +2) Open I/O monitor sheet1 901 901 902 -PLC configuration 360 +(% style="text-align:center" %) 361 +[[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]] 903 903 904 -* Double click [device configuration] in Siemens via software 905 -* Double click [protection] to enter protection configuration screen 363 +3) During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected 906 906 907 907 (% style="text-align:center" %) 908 -[[image:12.PLC Protocol_html_ 9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]366 +[[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]] 909 909 910 - *Check[Permit accesswith PUT / GETcommunicationfromremotepartner(PLC, HMI, OPC,...)]368 +4) Enter the register address, click OK to view the value of the register. 911 911 912 912 (% style="text-align:center" %) 913 -[[image:12.PLC Protocol_html_ d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]371 +[[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] 914 914 915 -DB settings 373 +(% style="text-align:center" %) 374 +[[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] 916 916 917 -* Right click [DB], select [properties] 918 -* Uncheck [optimized block access] 376 +**✎Note:** 919 919 378 +1) Both word registers and bit registers support even continuous read/write functions; 379 + 380 +2) The range of registers is based on the specific PLC type; 381 + 920 920 **Cable Wiring** 921 921 922 922 (% style="text-align:center" %) 923 923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 924 924 925 -= =**LOGOEthernet** ==387 += **IEC60870-5 104 Client** = 926 926 927 - SupportedSeries: Siemens Logo 0BA0 series389 +**HMI Setting** 928 928 929 -**HMI Settings** 930 - 931 931 (% class="table-bordered" %) 932 -|**Items**|**Settings**|**Note** 933 -|Protocol|Siemens LOGO| 934 -|Connection|Ethernet| 935 -|Port No.|102| 936 -|PLC station No.|2| 392 +|**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note** 393 +|Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %) 394 +|Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %) 395 +|Port No.|(% style="width:725px" %)2404|(% style="width:309px" %) 937 937 938 938 **Address List** 939 939 940 940 (% class="table-bordered" %) 941 -|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address** 942 -|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0 943 -|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000 944 -|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000 945 -|4|VW|Word|0-1468|DB1.DBX0.0|0x000000 946 -|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0 947 -|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770 948 -|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0 949 -|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180 950 -|9|AI|Word|1-16|DB1.DBX1032.0|0x002040 951 -|10|I|Bit|1-64|DB1.DBX1024.0|0x002000 952 -|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140 953 -|12|M|Bit|1-112|DB1.DBX1104.0|0x002280 954 -|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0 955 -|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70 956 -|15|V|Bit|0-14697|DB1.DBX0.0|0x000000 400 +|(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range** 401 +|(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7 402 +|(% style="width:461px" %)SCNA|0~~16777215.7 403 +|(% style="width:461px" %)DPTB|0~~16777215.7 404 +|(% style="width:461px" %)DCNA|0~~16777215.7 405 +|(% style="width:461px" %)METF|0~~16777215.7 406 +|(% style="width:461px" %)SENC|0~~16777215.7 407 +|(% style="width:461px" %)SENA|0~~16777215.7 408 +|(% style="width:461px" %)MENA|0~~16777215.7 409 +|(% style="width:461px" %)METD|0~~16777215.7 410 +|(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215 411 +|(% style="width:461px" %)SCNA|0~~16777215 412 +|(% style="width:461px" %)DPTB|0~~16777215 413 +|(% style="width:461px" %)DCNA|0~~16777215 414 +|(% style="width:461px" %)SENA|0~~16777215 415 +|(% style="width:461px" %)MENA|0~~16777215 416 +|(% style="width:461px" %)METD|0~~16777215 417 +|(% style="width:461px" %)INRO|0~~16777215 418 +|(% style="width:461px" %)TIMESYN|0~~16777215 419 +|(% style="width:461px" %)TIMEZ|0~~16777215 420 +|(% style="width:461px" %)NTP|0~~16777215 421 +|(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215 422 +|(% style="width:461px" %)SENC|0~~16777215 957 957 958 -** PLC Settingsin LOGO Software:**424 +**Address Configuration** 959 959 960 - Click[Tools]~-~-[EthernetConnections],shown as below.426 +The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable. 961 961 962 962 (% style="text-align:center" %) 963 -[[image:12.PLC Protocol_html_ 8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]429 +[[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]] 964 964 965 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below. 966 - 967 967 (% style="text-align:center" %) 968 -[[image:12.PLC Protocol_html_ 6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]432 +[[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]] 969 969 970 - **TSAPset**:Thevaluesetby localTSAP is the remote TSAP set inHMI. PLC's remoteTSAP is the opposite,shown as below.434 +1) Extended tag name 971 971 972 -(% style="text-align:center" %) 973 -[[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]] 436 +2) Address range for the extended tag. 974 974 975 -** Download Project**:Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IPaddress can be detected. Then click “ok”, andthe system will prompt that PLC will be "STOP" mode. Click “YES”to start download.438 +**Communication Settings** 976 976 977 -(% style="text-align:center" %) 978 -[[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]] 440 +1) Enable HMI Ethernet in [Project Settings]; 979 979 980 - 981 981 (% style="text-align:center" %) 982 -[[image:12.PLC Protocol_html_ cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]443 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 983 983 445 +2) Set PLC IP in [Device IP] settings; 984 984 985 -**HMI Communication Settings** 986 - 987 -Set PLC IP in [Device IP] settings; 988 - 989 989 (% style="text-align:center" %) 990 -[[image: SiemensLOGODeviceIP.png]]448 +[[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]] 991 991 992 -Enable HMI Ethernet in [Project Settings]; 993 - 994 -(% style="text-align:center" %) 995 -[[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]] 996 - 997 -TSAP setting 998 - 999 -* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register. 1000 -* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC. 1001 -* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC. 1002 - 1003 -**✎Note:** 1004 - 1005 -* The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192. 1006 - 1007 -(% style="text-align:center" %) 1008 -[[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]] 1009 - 1010 - 1011 -* AI word address and Ibit address are read-only and cannot be written on HMI. 1012 -* VW address should be even number.such as VW0, VW2, VW4... 1013 -* VD address it takes two VW addresses.such as VD0,VD4,VD8... 1014 -* Written value of RTC cannot exceed 255. 1015 - 1016 1016 **Cable Wiring** 1017 1017 1018 1018 (% style="text-align:center" %) 1019 1019 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 1020 1020 1021 -= =**S7-XXXEthernet** ==455 += **LG XGK FEnet Ethernet** = 1022 1022 1023 -Supported Series: Sie mensS7-400,S7-1200andS7-1500457 +Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module 1024 1024 1025 -**HMI Setting** 459 +**HMI Settings** 1026 1026 1027 -(% class="table-bordered" style="width:823px" %) 1028 -|=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note** 1029 -|Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %) 1030 -|Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %) 1031 -|Port No.|(% style="width:437px" %)102|(% style="width:201px" %) 1032 -|Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %) 1033 -|HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %) 461 +(% class="table-bordered" %) 462 +|**Items**|**Settings**|**Note** 463 +|Protocol|LG XGK FEnet(Ethernet)| 464 +|Connection|Ethernet| 465 +|Port No.|2004| 1034 1034 1035 -Slot from TIA Portal is equal to Device No. of PIStudio 1036 - 1037 -Rack from TIA Portal is equal to HMI No. of PIStudio 1038 - 1039 -(% style="text-align:center" %) 1040 -[[image:S7-XXXCommunication Settings.png]] 1041 - 1042 -(% style="text-align:center" %) 1043 -[[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]] 1044 - 1045 1045 **Address List** 1046 1046 1047 1047 (% class="table-bordered" %) 1048 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** 1049 -|(% rowspan="4" %)Bit|I|I|M d.o|((( 1050 -d:0~-~-9999 470 +|**Type**|**Register**|**Range**|**Format**|**Note** 471 +|(% rowspan="14" %)Word|P|0~~2047|P d| 472 +|M|0~~2047|M d| 473 +|K|0~~2047|K d| 474 +|F|0~~2047|F d| 475 +|T|0~~2047|T d| 476 +|C|0~~2047|C d| 477 +|Z|0~~127|Z d| 478 +|S|0~~127|S d| 479 +|L|0~~11263|L d| 480 +|N|0~~21503|N d| 481 +|D|0~~32767|D d| 482 +|R|0~~32767|R d| 483 +|ZR|0~~65535|ZR d| 484 +|UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31 1051 1051 1052 -o:0-7 1053 -)))| 1054 -|Q|Q|Q d.o|((( 1055 -d:0~-~-9999 486 +**✎Note:** 1056 1056 1057 -o:0-7 1058 -)))| 1059 -|M|M|M d.o|((( 1060 -d:0~-~-9999 488 +1) In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC; 1061 1061 1062 -o:0-7 1063 -)))| 1064 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|((( 1065 -nn:0-9999, 490 +2) The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC; 1066 1066 1067 -ddd d:0-9999,492 +3) All bit registers are in the form of bits in word, and the range is the same as the word register; 1068 1068 1069 -o:0-7 1070 -)))|((( 1071 -nn:DB No. 494 +**Communication settings in HMI** 1072 1072 1073 - dddd:addressvalue496 +1) Enable HMI Ethernet in [Project Settings]; 1074 1074 1075 -o: digit address 1076 -))) 1077 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999| 1078 -|M|MW|MW d|d:0-99999|((( 1079 -MW0=MB(0~~1) 1080 - 1081 -MW2=MB(2~~3) 1082 - 1083 -Address value is a multiple of 2 1084 -))) 1085 -|M|MD|MD d|d:0-99999|((( 1086 -MD0=MB(0~~3) 1087 - 1088 -MD4=MB(4~~7) 1089 - 1090 -Address value is a multiple of 4 1091 -))) 1092 -|I|IW|IW d|d:0-99999| 1093 -|Q|QW|QW d|d:0-99999| 1094 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|((( 1095 -nn:0-9999 1096 - 1097 -dddd:0-9999 1098 -)))|((( 1099 -nn:DB No. 1100 - 1101 -dddd:address value 1102 -))) 1103 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|((( 1104 -nn:0-9999 1105 - 1106 -dddd:0-9999 1107 -)))|((( 1108 -nn:DB No. 1109 - 1110 -dddd:address value 1111 - 1112 -Address value is a multiple of 2 1113 -))) 1114 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|((( 1115 -nn:0-9999 1116 - 1117 -dddd:0-9999 1118 -)))|((( 1119 -nn:DB No. 1120 - 1121 -dddd:address value 1122 - 1123 -Address value is a multiple of 4 1124 -))) 1125 - 1126 -**Communication Settings** 1127 - 1128 -Enable HMI Ethernet in [Project Settings]; 1129 - 1130 1130 (% style="text-align:center" %) 1131 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img- rounded img-thumbnail"]]499 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 1132 1132 1133 -Set PLC IP in [Device IP] settings; 501 +2) Set PLC IP in [Device IP] settings; 1134 1134 1135 1135 (% style="text-align:center" %) 1136 -[[image:12.PLC Protocol_html_ f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]504 +[[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] 1137 1137 1138 -**✎Note:** 1139 - 1140 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 1141 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 1142 - 1143 1143 **Cable Wiring** 1144 1144 1145 - {{idname="OLE_LINK8"/}}508 += **Mitsubishi** = 1146 1146 1147 -= Create communication with **Mitsubishi** = 1148 - 1149 1149 == **FX1S, 1N, 2N Series** == 1150 1150 1151 1151 Supported Series: Mitsubishi FX1S, FX1N, FX2N series ... ... @@ -1184,7 +1184,7 @@ 1184 1184 1185 1185 **Cable Wiring** 1186 1186 1187 -* *RS485**548 +**1) RS485** 1188 1188 1189 1189 (% style="text-align:center" %) 1190 1190 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] ... ... @@ -1192,13 +1192,15 @@ 1192 1192 (% style="text-align:center" %) 1193 1193 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] 1194 1194 1195 -* *RS422**556 +**2)RS422** 1196 1196 1197 1197 (% style="text-align:center" %) 1198 1198 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]] 1199 1199 1200 -**✎Note:** COM3 only available in PI8000/PI9000 series.561 +**✎Note:** 1201 1201 563 +COM3 only available in PI8000/PI9000 series. 564 + 1202 1202 == **FX5U Ethernet** == 1203 1203 1204 1204 Mitsubishi FX5U series PLC ... ... @@ -1243,32 +1243,32 @@ 1243 1243 1244 1244 **PLC Settings (GX Works 3)** 1245 1245 1246 -Find the [Ethernet port] in the navigation area. 609 +1) Find the [Ethernet port] in the navigation area. 1247 1247 1248 1248 (% style="text-align:center" %) 1249 1249 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]] 1250 1250 1251 -Select [Own Node Settings] in the [Setting Item List]; 614 +2) Select [Own Node Settings] in the [Setting Item List]; 1252 1252 1253 -Set [IP Address], [Subnet Mask], [Default Gateway]; 616 +3) Set [IP Address], [Subnet Mask], [Default Gateway]; 1254 1254 1255 -Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows; 618 +4) Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows; 1256 1256 1257 1257 (% style="text-align:center" %) 1258 1258 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]] 1259 1259 1260 -Select [SLMP Connection Module] and add into host station as below picture shows; 623 +5) Select [SLMP Connection Module] and add into host station as below picture shows; 1261 1261 1262 -Set Port number as 5002 (this is necessary settings); 625 +6) Set Port number as 5002 (this is necessary settings); 1263 1263 1264 -Click [Close with Reflecting the Setting] to save and close window; 627 +7) Click [Close with Reflecting the Setting] to save and close window; 1265 1265 1266 1266 (% style="text-align:center" %) 1267 1267 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]] 1268 1268 1269 -Click [Apply] to completed Etherenet settings; 632 +8) Click [Apply] to completed Etherenet settings; 1270 1270 1271 -Switch to the [On line data operation] interface as below, check the item and click [Execute] to download. 634 +9) Switch to the [On line data operation] interface as below, check the item and click [Execute] to download. 1272 1272 1273 1273 (% style="text-align:center" %) 1274 1274 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]] ... ... @@ -1325,37 +1325,37 @@ 1325 1325 1326 1326 **PLC Settings (GX Works 3)** 1327 1327 1328 -Create a blank FX5U project 691 +1) Create a blank FX5U project 1329 1329 1330 -Find the 485 serial port module in the system navigation bar and double click to enter the settings. 693 +2) Find the 485 serial port module in the system navigation bar and double click to enter the settings. 1331 1331 1332 1332 (% style="text-align:center" %) 1333 1333 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]] 1334 1334 1335 -Select protocol in the setting item, and set parameters. 698 +3) Select protocol in the setting item, and set parameters. 1336 1336 1337 1337 (% style="text-align:center" %) 1338 1338 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]] 1339 1339 1340 -Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) 703 +4) Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) 1341 1341 1342 1342 (% style="text-align:center" %) 1343 1343 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]] 1344 1344 1345 -Click the [Apply] button to finish the setting. 708 +5) Click the [Apply] button to finish the setting. 1346 1346 1347 -Click download and select the items as below, then click [execute] to download the configuration to PLC. 710 +6) Click download and select the items as below, then click [execute] to download the configuration to PLC. 1348 1348 1349 1349 (% style="text-align:center" %) 1350 1350 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]] 1351 1351 1352 - As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. 715 +7) As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. 1353 1353 1354 -Done. 717 +8) Done. 1355 1355 1356 1356 **Cable Wiring** 1357 1357 1358 -* *RS485**721 +**1) RS485** 1359 1359 1360 1360 (% style="text-align:center" %) 1361 1361 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] ... ... @@ -1363,13 +1363,15 @@ 1363 1363 (% style="text-align:center" %) 1364 1364 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] 1365 1365 1366 -* *RS422**729 +**2) RS422** 1367 1367 1368 1368 (% style="text-align:center" %) 1369 1369 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]] 1370 1370 1371 -**✎Note:** COM3 only available in PI8000/PI9000 series.734 +**✎Note:** 1372 1372 736 +COM3 only available in PI8000/PI9000 series. 737 + 1373 1373 == **L02 MELSEC (Ethernet)** == 1374 1374 1375 1375 Mitsubishi Q series CPU built-in Ethernet port. ... ... @@ -1419,11 +1419,11 @@ 1419 1419 1420 1420 **Communication Settings** 1421 1421 1422 -Enable HMI Ethernet in [Project Settings]; 787 +1) Enable HMI Ethernet in [Project Settings]; 1423 1423 1424 1424 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]] 1425 1425 1426 -Set PLC IP in [Device IP] settings; 791 +2) Set PLC IP in [Device IP] settings; 1427 1427 1428 1428 (% style="text-align:center" %) 1429 1429 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]] ... ... @@ -1430,25 +1430,25 @@ 1430 1430 1431 1431 **PLC Settings (GX Works2 )** 1432 1432 1433 -Create a project 798 +1) Create a project 1434 1434 1435 -Set PLC IP, subnet mask and gateway; 800 +2) Set PLC IP, subnet mask and gateway; 1436 1436 1437 -Select [Binary Code] as communication data code; 802 +3) Select [Binary Code] as communication data code; 1438 1438 1439 1439 (% style="text-align:center" %) 1440 1440 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]] 1441 1441 1442 -Set PLC port number, for example 1025 807 +4) Set PLC port number, for example 1025 1443 1443 1444 1444 (% style="text-align:center" %) 1445 1445 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]] 1446 1446 1447 -Save settings; 812 +5) Save settings; 1448 1448 1449 -Download project into PLC device; 814 +6) Download project into PLC device; 1450 1450 1451 -Restart PLC device; 816 +7) Restart PLC device; 1452 1452 1453 1453 **Cable Wiring** 1454 1454 ... ... @@ -1514,22 +1514,42 @@ 1514 1514 1515 1515 **PLC Settings(GX Works2)** 1516 1516 1517 -* Click [Ethernet/CC IE/MELSECNET]; 1518 -* Please select [Ethernet] as network type; 1519 -* Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order); 1520 -* Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]] 1521 -* Click [Operation setting] to set IP; 1522 -* Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]] 1523 -* Set protocol: TCP; 1524 -* Set [unpassive] in [Open system]; 1525 -* Set [receive] in [Fixed buffer]; 1526 -* Set [procedure Exist] in [Fixed buffer communication]; 1527 -* Disable [Pairing open]; 1528 -* Set [No confirm] in [Existence confirmation]; 1529 -* Host station port number: 1025; 1530 -* (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings; 1531 -* Download project into PLC and restart it 882 +1) Click [Ethernet/CC IE/MELSECNET]; 1532 1532 884 +2) Please select [Ethernet] as network type; 885 + 886 +3) Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order); 887 + 888 +4) Select [Online] as Mode; 889 + 890 +(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]] 891 + 892 +5) Click [Operation setting] to set IP; 893 + 894 +6) Select [Binary Code] as [Communication Data Code]; 895 + 896 +(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]] 897 + 898 +7) Set protocol: TCP; 899 + 900 +8) Set [unpassive] in [Open system]; 901 + 902 +9) Set [receive] in [Fixed buffer]; 903 + 904 +10) Set [procedure Exist] in [Fixed buffer communication]; 905 + 906 +11) Disable [Pairing open]; 907 + 908 +12) Set [No confirm] in [Existence confirmation]; 909 + 910 +13) Host station port number: 1025; 911 + 912 +(% id="cke_bm_8547S" style="display:none" %) [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]] 913 + 914 +14) Save settings; 915 + 916 +15) Download project into PLC and restart it 917 + 1533 1533 **Cable Wiring** 1534 1534 1535 1535 (% style="text-align:center" %) ... ... @@ -1575,7 +1575,7 @@ 1575 1575 1576 1576 **Cable Wiring** 1577 1577 1578 -* *RS485**963 +**1) RS485** 1579 1579 1580 1580 (% style="text-align:center" %) 1581 1581 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] ... ... @@ -1583,15 +1583,17 @@ 1583 1583 (% style="text-align:center" %) 1584 1584 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] 1585 1585 1586 -* *RS232**971 +**2) RS232** 1587 1587 1588 1588 (% style="text-align:center" %) 1589 1589 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]] 1590 1590 1591 -**✎Note:** COM3 only available in PI8000/PI9000 series.976 +**✎Note:** 1592 1592 1593 - == **MODBUSRTU Slave (All function)/(AllfunctionOneBaseAddress)** ==978 +COM3 only available in PI8000/PI9000 series. 1594 1594 980 +== **{{id name="_Toc30118"/}}MODBUS RTU Slave (All function)/(All function OneBaseAddress)** == 981 + 1595 1595 Supported Series: MODBUS RTU CONTROLLER 1596 1596 1597 1597 HMI works as MODBUS MASTER connecting with SLAVE. ... ... @@ -1650,9 +1650,10 @@ 1650 1650 1651 1651 **✎Note:** 1652 1652 1653 -* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats. 1654 -* The function codes sent out are the same as those that read and write words. 1040 +Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats. 1655 1655 1042 +The function codes sent out are the same as those that read and write words. 1043 + 1656 1656 **Station number for more than one slaves** 1657 1657 1658 1658 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows. ... ... @@ -1662,7 +1662,7 @@ 1662 1662 1663 1663 **Cable Wiring** 1664 1664 1665 -* *RS485**1053 +**1) RS485** 1666 1666 1667 1667 (% style="text-align:center" %) 1668 1668 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] ... ... @@ -1670,15 +1670,17 @@ 1670 1670 (% style="text-align:center" %) 1671 1671 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] 1672 1672 1673 -* *RS232**1061 +**2) RS232** 1674 1674 1675 1675 (% style="text-align:center" %) 1676 1676 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]] 1677 1677 1678 -**✎Note:** COM3 only available in PI8000/PI9000 series.1066 +**✎Note:** 1679 1679 1680 - == **MODBUSTCP Slave (Allfunction)**==1068 +COM3 only available in PI8000/PI9000 series. 1681 1681 1070 +== **{{id name="_Toc16172"/}}MODBUS TCP Slave (All function)** == 1071 + 1682 1682 Supported series: MODBUS TCP controller 1683 1683 1684 1684 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE ... ... @@ -1731,12 +1731,12 @@ 1731 1731 1732 1732 **Communication Settings** 1733 1733 1734 -Enable HMI Ethernet in [Project Settings]; 1124 +1) Enable HMI Ethernet in [Project Settings]; 1735 1735 1736 1736 (% style="text-align:center" %) 1737 1737 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 1738 1738 1739 -Set PLC IP in [Device IP] settings; 1129 +2) Set PLC IP in [Device IP] settings; 1740 1740 1741 1741 (% style="text-align:center" %) 1742 1742 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] ... ... @@ -1777,7 +1777,7 @@ 1777 1777 1778 1778 **Device Settings** 1779 1779 1780 -Omron E5CC PLC configuration 1170 +1) Omron E5CC PLC configuration 1781 1781 1782 1782 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting. 1783 1783 ... ... @@ -1784,13 +1784,15 @@ 1784 1784 (% style="text-align:center" %) 1785 1785 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]] 1786 1786 1787 -According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows 1177 +2) According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows 1788 1788 1789 1789 (% style="text-align:center" %) 1790 1790 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]] 1791 1791 1792 -**✎Note:** The communication settings for HMI should be consistent with this setting.1182 +**✎Note:** 1793 1793 1184 +The communication settings for HMI should be consistent with this setting. 1185 + 1794 1794 **Cable Wiring** 1795 1795 1796 1796 (% style="text-align:center" %) ... ... @@ -1801,18 +1801,28 @@ 1801 1801 1802 1802 **✎Note:** 1803 1803 1804 -* COM3 only available in PI8000/PI9000 series. 1805 -* CA address could not support continuous writing function; 1806 -* Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid 1807 -* When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value. 1808 -* When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail. 1809 -* Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document. 1810 -* When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable. 1811 -* Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests. 1812 -* (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written. 1196 +1) COM3 only available in PI8000/PI9000 series. 1813 1813 1814 - ==EtherNet/IPNXseries==1198 +2) CA address could not support continuous writing function; 1815 1815 1200 +3) Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid 1201 + 1202 +4) When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value. 1203 + 1204 +5) When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail. 1205 + 1206 +6) Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document. 1207 + 1208 +7) When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable. 1209 + 1210 +8) Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests. 1211 + 1212 +(% id="cke_bm_8690S" style="display:none" %) [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]] 1213 + 1214 +9) Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written. 1215 + 1216 +== **{{id name="_Toc5393"/}}EtherNet/IP NX series** == 1217 + 1816 1816 Supported series: Omron NX/NJ series 1817 1817 1818 1818 **HMI Setting** ... ... @@ -1835,24 +1835,24 @@ 1835 1835 1836 1836 **Export labels from Sysmac Studio** 1837 1837 1838 -Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables]; 1240 +1) Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables]; 1839 1839 1840 1840 (% style="text-align:center" %) 1841 1841 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]] 1842 1842 1843 -Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol; 1245 +2) Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol; 1844 1844 1845 -Click [Label manage]; 1247 +3) Click [Label manage]; 1846 1846 1847 1847 (% style="text-align:center" %) 1848 1848 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]] 1849 1849 1850 -Click [Import labels] and then select the file exported in step 1; 1252 +4) Click [Import labels] and then select the file exported in step 1; 1851 1851 1852 1852 (% style="text-align:center" %) 1853 1853 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]] 1854 1854 1855 -The Import Status field shows the result, click [OK] to finish importing address labels; 1257 +5) The Import Status field shows the result, click [OK] to finish importing address labels; 1856 1856 1857 1857 (% style="text-align:center" %) 1858 1858 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]] ... ... @@ -1859,12 +1859,12 @@ 1859 1859 1860 1860 **Communication Settings** 1861 1861 1862 -Enable HMI Ethernet in [Project Settings]; 1264 +1) Enable HMI Ethernet in [Project Settings]; 1863 1863 1864 1864 (% style="text-align:center" %) 1865 1865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 1866 1866 1867 -Set PLC IP in [Device IP] settings; 1269 +2) Set PLC IP in [Device IP] settings; 1868 1868 1869 1869 (% style="text-align:center" %) 1870 1870 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]] ... ... @@ -1894,12 +1894,12 @@ 1894 1894 1895 1895 **CAN frame setting in HMI** 1896 1896 1897 -Click [OpenCAN setting] button in communication setting window; 1299 +1) Click [OpenCAN setting] button in communication setting window; 1898 1898 1899 1899 (% style="text-align:center" %) 1900 1900 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]] 1901 1901 1902 -Click [Add] to create a new frame; 1304 +2) Click [Add] to create a new frame; 1903 1903 1904 1904 (% style="text-align:center" %) 1905 1905 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]] ... ... @@ -1916,19 +1916,19 @@ 1916 1916 |8|Browse|Displays configuration files in XML format in IE 1917 1917 |9|OK|Complete the configuration of the frame and exit 1918 1918 1919 -Set CANBUS frame in setting windows 1321 +3) Set CANBUS frame in setting windows 1920 1920 1921 1921 (% style="text-align:center" %) 1922 1922 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]] 1923 1923 1924 1924 (% class="table-bordered" %) 1925 -|**No**| (% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**1926 -|1| (% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;1927 -|2| (% style="width:185px" %)ID assign|(%style="width:854px" %)split the ID by PF, PS, and SA;1928 -|3| (% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;1929 -|4| (% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;1930 -|5| (% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;1931 -|6| (% style="width:185px" %)Use address|(% style="width:854px" %)(((1327 +|**No**|**Items**|**Description** 1328 +|1|ID|Set the ID of a can frame in hexadecimal format; 1329 +|2|ID assign|split the ID by PF, PS, and SA; 1330 +|3|Frame type|Select Standard frame or Extended Frame; 1331 +|4|Frame format|Select between data frame and remote Frame; 1332 +|5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message; 1333 +|6|Use address|((( 1932 1932 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously; 1933 1933 1934 1934 **Edit:** Set a bit or word address by its format; ... ... @@ -1935,46 +1935,46 @@ 1935 1935 1936 1936 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface; 1937 1937 ))) 1938 -|(% rowspan="8" %)7|(% rowspan="8" style="width:185px"%)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;1939 -| (% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;1940 -| (% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;1941 -| (% style="width:854px" %)No response: the device or touch screen will not receive feedback;1942 -| (% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;1943 -| (% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;1944 -| (% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;1945 -| (% style="width:854px" %)Response timeout: sets whether the response frame timeout;1946 -|(% rowspan="3" %)8|(% rowspan="3" style="width:185px"%)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.1947 -| (% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;1948 -| (% style="width:854px" %)Manually send: a manually send tick indicates only one send;1949 -|9| (% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;1950 -|10| (% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;1951 -|11| (% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;1952 -|12| (% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;1953 -|13| (% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;1954 -|14| (% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;1955 -|15| (% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;1340 +|(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback; 1341 +|Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way; 1342 +|Feedback mode: feedback mode includes no response, confirm response and data response; 1343 +|No response: the device or touch screen will not receive feedback; 1344 +|Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20; 1345 +|Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address; 1346 +|response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender; 1347 +|Response timeout: sets whether the response frame timeout; 1348 +|(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0. 1349 +|Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run; 1350 +|Manually send: a manually send tick indicates only one send; 1351 +|9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal; 1352 +|10|Note|Fill the text to explain the meaning of the frame; 1353 +|11|Data assign|Preview the display in this table based on the address and the corresponding number of digits; 1354 +|12|Current operation display|Display the description of current operation; 1355 +|13|Add|Add a new frame; 1356 +|14|Save frame|Save the configured frame format; 1357 +|15|Cancel|Cancel the frame configuration; 1956 1956 1957 -Set CAN address (Read or write operation); 1359 +4) Set CAN address (Read or write operation); 1958 1958 1959 1959 (% style="text-align:center" %) 1960 1960 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]] 1961 1961 1962 1962 (% class="table-bordered" %) 1963 -|**No.**| (% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**1964 -|1| (% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface1965 -|(% rowspan="3" %)2|(% rowspan="3" style="width:207px"%)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers1966 -| (% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.1967 -| (% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.1968 -|(% rowspan="5" %)3|(% rowspan="3" style="width:207px"%)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.1969 -| (% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.1970 -| (% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((1365 +|**No.**|**Item**|**Description** 1366 +|1|Current address|Displays the register type and register address set by the user in the data access interface 1367 +|(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers 1368 +|If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop. 1369 +|If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user. 1370 +|(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly. 1371 +|If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame. 1372 +|If the trigger condition is a writing operation, there are two situations:((( 1971 1971 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen. 1972 1972 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user. 1973 1973 ))) 1974 -|(% rowspan="2" style="width:207px"%)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.1975 -| (% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.1976 -|4| (% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration1977 -|5| (% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit1376 +|(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on. 1377 +|If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on. 1378 +|4|Add|Add current configuration 1379 +|5|Close|Close the configuration window to exit 1978 1978 1979 1979 **Multiple Packages Settings** 1980 1980 ... ... @@ -1981,15 +1981,15 @@ 1981 1981 (% style="text-align:center" %) 1982 1982 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]] 1983 1983 1984 -Check [Multiple packages supported] to open [Multiple package data] window, as below show. 1386 +1) Check [Multiple packages supported] to open [Multiple package data] window, as below show. 1985 1985 1986 -Select Multiple package type 1388 +2) Select Multiple package type 1987 1987 1988 1988 * Not Multiple packages 1989 1989 * J1939 Multiple packages 1990 1990 * Customized Multiple packages 1991 1991 1992 -Click [Edit Receive data] for [Receive] settings 1394 +3) Click [Edit Receive data] for [Receive] settings 1993 1993 1994 1994 * Start code+ Total length (J1939) 1995 1995 ... ... @@ -2019,7 +2019,7 @@ 2019 2019 2020 2020 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes. 2021 2021 2022 -Click [Edit Send data] for [Send] setting 1424 +4) Click [Edit Send data] for [Send] setting 2023 2023 2024 2024 * J1939 2025 2025 ... ... @@ -2044,10 +2044,12 @@ 2044 2044 (% style="text-align:center" %) 2045 2045 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]] 2046 2046 2047 -**✎Note:** The address interval between each frame need to be more than a word address;1449 +**✎Note:** 2048 2048 2049 - =**SHIMADEN**=1451 +The address interval between each frame need to be more than a word address; 2050 2050 1453 += **{{id name="_Toc24639"/}}SHIMADEN** = 1454 + 2051 2051 == **FP23** == 2052 2052 2053 2053 Supported series: SHIMADEN FP23 series ... ... @@ -2082,17 +2082,22 @@ 2082 2082 2083 2083 **✎Note:** 2084 2084 2085 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2086 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23; 2087 -* The Ctrl register is used to store the control group number and BCC check mode. 1489 +1) The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2088 2088 1491 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23; 1492 + 1493 +3) The Ctrl register is used to store the control group number and BCC check mode. 1494 + 2089 2089 **Ctrl Register Description** 2090 2090 2091 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2092 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 2093 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 2094 -* Ctrl3 reserved 1497 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2095 2095 1499 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 1500 + 1501 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1502 + 1503 +4) Ctrl3 reserved 1504 + 2096 2096 **✎Note:** 2097 2097 2098 2098 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. ... ... @@ -2105,8 +2105,10 @@ 2105 2105 (% style="text-align:center" %) 2106 2106 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 2107 2107 2108 -**✎Note:** COM3 only available in PI8000/PI9000 series.1517 +**✎Note:** 2109 2109 1519 +COM3 only available in PI8000/PI9000 series. 1520 + 2110 2110 == **{{id name="_Toc23422"/}}SR90** == 2111 2111 2112 2112 Supported series: SHIMADEN SR90 series ... ... @@ -2135,17 +2135,22 @@ 2135 2135 2136 2136 **✎Note:** 2137 2137 2138 -* The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2139 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90; 2140 -* The Ctrl register is used to store the control group number and BCC check mode. See how to use it below; 1549 +1) The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2141 2141 1551 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90; 1552 + 1553 +3) The Ctrl register is used to store the control group number and BCC check mode. See how to use it below; 1554 + 2142 2142 **Ctrl Register Description** 2143 2143 2144 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2145 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 2146 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 2147 -* Ctrl3 reserved 1557 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2148 2148 1559 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 1560 + 1561 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1562 + 1563 +4) Ctrl3 reserved 1564 + 2149 2149 **✎Note:** 2150 2150 2151 2151 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. ... ... @@ -2158,8 +2158,10 @@ 2158 2158 (% style="text-align:center" %) 2159 2159 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 2160 2160 2161 -**✎Note:** COM3 only available in PI8000/PI9000 series.1577 +**✎Note:** 2162 2162 1579 +COM3 only available in PI8000/PI9000 series. 1580 + 2163 2163 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** == 2164 2164 2165 2165 Supported series: SHIMADEN MR13 series ... ... @@ -2195,17 +2195,22 @@ 2195 2195 2196 2196 **✎Note:** 2197 2197 2198 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2199 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13; 2200 -* The Ctrl register is used to store the control group number and BCC check mode. 1616 +1) The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 2201 2201 1618 +2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13; 1619 + 1620 +3) The Ctrl register is used to store the control group number and BCC check mode. 1621 + 2202 2202 **Ctrl Register Description** 2203 2203 2204 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2205 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR . 2206 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 2207 -* Ctrl3 reserved 1624 +1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 2208 2208 1626 +2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR . 1627 + 1628 +3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1629 + 1630 +4) Ctrl3 reserved 1631 + 2209 2209 **✎Note:** 2210 2210 2211 2211 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. ... ... @@ -2218,8 +2218,10 @@ 2218 2218 (% style="text-align:center" %) 2219 2219 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 2220 2220 2221 -**✎Note:** COM3 only available in PI8000/PI9000 series.1644 +**✎Note:** 2222 2222 1646 +{{id name="_Toc15768"/}}COM3 only available in PI8000/PI9000 series. 1647 + 2223 2223 = **Siemens** = 2224 2224 2225 2225 == **S7-200 Smart Ethernet** == ... ... @@ -2289,12 +2289,12 @@ 2289 2289 2290 2290 **Communication Settings** 2291 2291 2292 -Enable HMI Ethernet in [Project Settings]; 1717 +1) Enable HMI Ethernet in [Project Settings]; 2293 2293 2294 2294 (% style="text-align:center" %) 2295 2295 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 2296 2296 2297 -Set PLC IP in [Device IP] settings; 1722 +2) Set PLC IP in [Device IP] settings; 2298 2298 2299 2299 (% style="text-align:center" %) 2300 2300 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] ... ... @@ -2365,12 +2365,12 @@ 2365 2365 2366 2366 **Communication Settings** 2367 2367 2368 -Enable HMI Ethernet in [Project Settings]; 1793 +1) Enable HMI Ethernet in [Project Settings]; 2369 2369 2370 2370 (% style="text-align:center" %) 2371 2371 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 2372 2372 2373 -Set PLC IP in [Device IP] settings; 1798 +2) Set PLC IP in [Device IP] settings; 2374 2374 2375 2375 (% style="text-align:center" %) 2376 2376 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]] ... ... @@ -2485,12 +2485,12 @@ 2485 2485 2486 2486 **Communication Settings** 2487 2487 2488 -Enable HMI Ethernet in [Project Settings]; 1913 +1) Enable HMI Ethernet in [Project Settings]; 2489 2489 2490 2490 (% style="text-align:center" %) 2491 2491 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 2492 2492 2493 -Set PLC IP in [Device IP] settings; 1918 +2) Set PLC IP in [Device IP] settings; 2494 2494 2495 2495 (% style="text-align:center" %) 2496 2496 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] ... ... @@ -2497,52 +2497,59 @@ 2497 2497 2498 2498 **✎Note:** 2499 2499 2500 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 2501 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 1925 +1) The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 2502 2502 1927 +2) HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 1928 + 2503 2503 **PLC Settings** 2504 2504 2505 -Add BD 1931 +1) Add BD 2506 2506 2507 - *Please uncheck [Symbolic access only] option;1933 +Please uncheck [Symbolic access only] option; 2508 2508 1935 + 2509 2509 (% style="text-align:center" %) 2510 2510 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]] 2511 2511 2512 -Address settings, using BD2 as example. 1939 +2) Address settings, using BD2 as example. 2513 2513 2514 -* DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1. 2515 -* 2 represent DB block number 2516 -* xxxx represent address 1941 +DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1. 2517 2517 1943 +2 represent DB block number 1944 + 1945 +xxxx represent address 1946 + 2518 2518 **Such as:** 2519 2519 2520 -* DBxDBB20000 = DB2.DBB0 2521 -* DBxDBW20004 = DB2.DBW4 1949 +DBxDBB20000 = DB2.DBB0 2522 2522 1951 +DBxDBW20004 = DB2.DBW4 1952 + 2523 2523 (% style="text-align:center" %) 2524 2524 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]] 2525 2525 2526 2526 **How to connect with S7-1200 Firmware V4.0** 2527 2527 2528 -PLC configuration 1958 +1) PLC configuration 2529 2529 2530 -* Double click [device configuration] in Siemens via software 2531 -* Double click [protection] to enter protection configuration screen 1960 +a) Double click [device configuration] in Siemens via software 2532 2532 1962 +b) Double click [protection] to enter protection configuration screen 1963 + 2533 2533 (% style="text-align:center" %) 2534 2534 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]] 2535 2535 2536 - *Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]1967 +c) Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)] 2537 2537 2538 2538 (% style="text-align:center" %) 2539 2539 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]] 2540 2540 2541 -DB settings 1972 +2) DB settings 2542 2542 2543 -* Right click [DB], select [properties] 2544 -* Uncheck [optimized block access] 1974 +Right click [DB], select [properties] 2545 2545 1976 +Uncheck [optimized block access] 1977 + 2546 2546 **Cable Wiring** 2547 2547 2548 2548 (% style="text-align:center" %) ... ... @@ -2550,7 +2550,7 @@ 2550 2550 2551 2551 == **LOGO Ethernet** == 2552 2552 2553 -Supported Series: Siemens Logo 0BA0 series1985 +Supported Series: Siemens Logo 2554 2554 2555 2555 **HMI Settings** 2556 2556 ... ... @@ -2583,22 +2583,22 @@ 2583 2583 2584 2584 **PLC Settings in LOGO Software:** 2585 2585 2586 -Click [Tools]~-~-[Ethernet Connections],shown as below. 2018 +1) Click [Tools]~-~-[Ethernet Connections],shown as below. 2587 2587 2588 2588 (% style="text-align:center" %) 2589 2589 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]] 2590 2590 2591 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below. 2023 +2) Set Ethernet connection parameter. IP, Subnet Mask, shown as below. 2592 2592 2593 2593 (% style="text-align:center" %) 2594 2594 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]] 2595 2595 2596 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below. 2028 +3) **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below. 2597 2597 2598 2598 (% style="text-align:center" %) 2599 2599 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]] 2600 2600 2601 -**Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download. 2033 +4) **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download. 2602 2602 2603 2603 (% style="text-align:center" %) 2604 2604 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]] ... ... @@ -2610,35 +2610,41 @@ 2610 2610 2611 2611 **HMI Communication Settings** 2612 2612 2613 -Set PLC IP in [Device IP] settings; 2045 +1)Set PLC IP in [Device IP] settings; 2614 2614 2615 2615 (% style="text-align:center" %) 2616 -[[image: SiemensLOGODeviceIP.png]]2048 +[[image:12.PLC Protocol_html_573fc64ad393cd4f.png||data-xwiki-image-style-alignment="center" height="655" width="379" class="img-thumbnail"]] 2617 2617 2618 -Enable HMI Ethernet in [Project Settings]; 2619 2619 2051 +2)Enable HMI Ethernet in [Project Settings]; 2052 + 2620 2620 (% style="text-align:center" %) 2621 2621 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]] 2622 2622 2623 -TSAP setting 2056 +3)TSAP setting 2624 2624 2625 -* Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register. 2626 -* HSW10118 = local TSAP of HMI, this is remote TSAP of PLC. 2627 -* HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC. 2058 +Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register. 2628 2628 2060 +HSW10118 = local TSAP of HMI, this is remote TSAP of PLC. 2061 + 2062 +HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC. 2063 + 2629 2629 **✎Note:** 2630 2630 2631 - *The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.2066 +1) The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192. 2632 2632 2633 2633 (% style="text-align:center" %) 2634 2634 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]] 2635 2635 2636 2636 2637 -* AI word address and Ibit address are read-only and cannot be written on HMI. 2638 -* VW address should be even number.such as VW0, VW2, VW4... 2639 -* VD address it takes two VW addresses.such as VD0,VD4,VD8... 2640 -* Written value of RTC cannot exceed 255. 2072 +2) AI word address and Ibit address are read-only and cannot be written on HMI. 2641 2641 2074 +3) VW address should be even number.such as VW0, VW2, VW4... 2075 + 2076 +4) VD address it takes two VW addresses.such as VD0,VD4,VD8... 2077 + 2078 +5) Written value of RTC cannot exceed 255. 2079 + 2642 2642 **Cable Wiring** 2643 2643 2644 2644 (% style="text-align:center" %) ... ... @@ -2646,28 +2646,17 @@ 2646 2646 2647 2647 == **S7-XXX Ethernet** == 2648 2648 2649 -Supported Series: Siemens S7- 400, S7-1200 and S7-15002087 +Supported Series: Siemens S7-1200 and S7-1500 2650 2650 2651 2651 **HMI Setting** 2652 2652 2653 -(% class="table-bordered" style="width:823px" %) 2654 -|=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note** 2655 -|Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %) 2656 -|Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %) 2657 -|Port No.|(% style="width:437px" %)102|(% style="width:201px" %) 2658 -|Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %) 2659 -|HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %) 2091 +(% class="table-bordered" %) 2092 +|**Items**|**Settings**|**Note** 2093 +|Protocol|Siemens S7-XXX| 2094 +|Connection|Ethernet| 2095 +|Port No.|102| 2096 +|PLC station No.|1 (for S7-1500)/ 2 (for S7-1200)| 2660 2660 2661 -Slot from TIA Portal is equal to Device No. of PIStudio 2662 - 2663 -Rack from TIA Portal is equal to HMI No. of PIStudio 2664 - 2665 -(% style="text-align:center" %) 2666 -[[image:S7-XXXCommunication Settings.png]] 2667 - 2668 -(% style="text-align:center" %) 2669 -[[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]] 2670 - 2671 2671 **Address List** 2672 2672 2673 2673 (% class="table-bordered" %) ... ... @@ -2751,12 +2751,12 @@ 2751 2751 2752 2752 **Communication Settings** 2753 2753 2754 -Enable HMI Ethernet in [Project Settings]; 2181 +1) Enable HMI Ethernet in [Project Settings]; 2755 2755 2756 2756 (% style="text-align:center" %) 2757 2757 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]] 2758 2758 2759 -Set PLC IP in [Device IP] settings; 2186 +2) Set PLC IP in [Device IP] settings; 2760 2760 2761 2761 (% style="text-align:center" %) 2762 2762 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] ... ... @@ -2763,9 +2763,10 @@ 2763 2763 2764 2764 **✎Note:** 2765 2765 2766 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 2767 -* HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 2193 +1) The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. 2768 2768 2195 +2) HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. 2196 + 2769 2769 **Cable Wiring** 2770 2770 2771 2771 {{id name="OLE_LINK8"/}} ... ... @@ -2790,14 +2790,14 @@ 2790 2790 2791 2791 **Operating Procedures** 2792 2792 2793 -Select [User defined protocol]; 2221 +1) Select [User defined protocol]; 2794 2794 2795 -Click [User defined protocol] button to open setting window as below; 2223 +2) Click [User defined protocol] button to open setting window as below; 2796 2796 2797 2797 (% style="text-align:center" %) 2798 2798 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]] 2799 2799 2800 -Configure user defined command; 2228 +3) Configure user defined command; 2801 2801 2802 2802 (% style="text-align:center" %) 2803 2803 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]] ... ... @@ -2833,26 +2833,26 @@ 2833 2833 2834 2834 **Operating Procedures** 2835 2835 2836 -Click [Add] to create a new command, as below shows; 2264 +1) Click [Add] to create a new command, as below shows; 2837 2837 2838 2838 (% style="text-align:center" %) 2839 2839 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]] 2840 2840 2841 -Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows; 2269 +2) Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows; 2842 2842 2843 2843 (% style="text-align:center" %) 2844 2844 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]] 2845 2845 2846 -Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows 2274 +3) Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows 2847 2847 2848 2848 (% style="text-align:center" %) 2849 2849 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]] 2850 2850 2851 -Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send]. 2279 +4) Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send]. 2852 2852 2853 -Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input; 2281 +5) Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input; 2854 2854 2855 -Check settings; 2283 +6) Check settings; 2856 2856 2857 2857 (% style="text-align:center" %) 2858 2858 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] ... ... @@ -2865,7 +2865,7 @@ 2865 2865 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check. 2866 2866 |Length: The data length need to be checked. 2867 2867 2868 -Object settings; 2296 +7) Object settings; 2869 2869 2870 2870 (% style="text-align:center" %) 2871 2871 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] ... ... @@ -2877,7 +2877,7 @@ 2877 2877 |Note: description to object; 2878 2878 |2|Byte order|The numerical display order; 2879 2879 2880 -Data length settings; 2308 +8) Data length settings; 2881 2881 2882 2882 (% style="text-align:center" %) 2883 2883 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] ... ... @@ -2889,7 +2889,7 @@ 2889 2889 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data. 2890 2890 |Length: the write data length. 2891 2891 2892 -Instruction length settings 2320 +9) Instruction length settings 2893 2893 2894 2894 (% style="text-align:center" %) 2895 2895 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] ... ... @@ -2902,7 +2902,7 @@ 2902 2902 2903 2903 **Cable Wiring** 2904 2904 2905 -* *RS485**2333 +**1)RS485** 2906 2906 2907 2907 (% style="text-align:center" %) 2908 2908 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] ... ... @@ -2910,38 +2910,99 @@ 2910 2910 (% style="text-align:center" %) 2911 2911 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 2912 2912 2913 -* *RS232**2341 +**2)RS232** 2914 2914 2915 2915 (% style="text-align:center" %) 2916 2916 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]] 2917 2917 2918 -**✎Note:** COM3 only available in PI8000/PI9000 series.2346 +**✎Note:** 2919 2919 2348 +COM3 only available in PI8000/PI9000 series. 2349 + 2350 += **WECON PLC** = 2351 + 2352 +Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM 2353 + 2354 +**HMI Settings** 2355 + 2356 +(% class="table-bordered" %) 2357 +|**Item**|**Settings**|**Note** 2358 +|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| 2359 +|Connection|RS422/RS485| 2360 +|Baud rate|9600| 2361 +|Data bit|7| 2362 +|Parity|EVEN| 2363 +|Stop bit|1| 2364 +|PLC station No.|1| 2365 + 2366 +**Address List** 2367 + 2368 +(% class="table-bordered" %) 2369 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 2370 +|(% rowspan="6" %)Bit|X|X|Xo|0~~303237| 2371 +|Y|Y|Y o|0~~303237| 2372 +|M|M|M d|0~~99999| 2373 +|T|T|T d|0~~99999| 2374 +|C|C|C d|0~~99999| 2375 +|S|S|S d|0~~99999| 2376 +|(% rowspan="8" %)Word|X|X|Xo|0~~303237| 2377 +|Y|Y|Y o|0~~303237| 2378 +|M|M|M d|0~~99999| 2379 +|T|T|T d|0~~99999| 2380 +|C|C|C d|0~~199| 2381 +|D|D|D d|0~~7999| 2382 +|S|S|S d|0~~99999| 2383 +|SD|SD|SD d|8000~~9999| 2384 + 2385 +**Cable Wiring** 2386 + 2387 +**1)RS485** 2388 + 2389 +(% style="text-align:center" %) 2390 +[[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] 2391 + 2392 +(% style="text-align:center" %) 2393 +[[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 2394 + 2395 +**2)RS422** 2396 + 2397 +(% style="text-align:center" %) 2398 +[[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]] 2399 + 2400 +**✎Note:** 2401 + 2402 +~1. HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . 2403 + 2404 +2. If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. 2405 + 2406 +[[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] 2407 + 2920 2920 = **Printer** = 2921 2921 2922 2922 == **TSPL label printer** == 2923 2923 2924 -**Introduction** 2412 +**I. Introduction** 2925 2925 2926 2926 TSPL label printer protocol supports following models. 2927 2927 2928 -* SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]] 2929 -* DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]] 2416 +SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]] 2930 2930 2931 - **Setting Step**2418 +DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]] 2932 2932 2933 -Se lect therotocol2420 +**II. Setting Step** 2934 2934 2935 - *Create a new project, select theTSPL labelprinter protocolas shown below.2422 +1) Select the protocol 2936 2936 2424 +Create a new project, select the TSPL label printer protocol as shown below. 2425 + 2937 2937 (% style="text-align:center" %) 2938 2938 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]] 2939 2939 2940 -Set parameters 2429 +2) Set parameters 2941 2941 2942 - *The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.2431 +The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters. 2943 2943 2944 -Printer register 2433 +3)Printer register 2945 2945 2946 2946 (% class="table-bordered" %) 2947 2947 |**Register**|**System**|**Range**|**Function** ... ... @@ -2953,13 +2953,18 @@ 2953 2953 |TSPL_PN|decimal|0 - 0|Trigger printing 2954 2954 |TSPL_PS|decimal|0 - 0|Print status 2955 2955 2956 -* Set paper size: 2957 -** TSPL_SP0: width of paper, unit: mm. 2958 -** TSPL_SP1: height of paper, unit: mm. 2959 -* Print text: 2960 -** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text. 2961 -** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99. 2445 +1.Set paper size: 2962 2962 2447 +TSPL_SP0: width of paper, unit: mm. 2448 + 2449 + TSPL_SP1: height of paper, unit: mm. 2450 + 2451 +2.Print text: 2452 + 2453 +TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text. 2454 + 2455 +Detailed parameter settings of each text is shown as below table.for example,first text,TSPL_PT0-TSPL_PT99. 2456 + 2963 2963 (% class="table-bordered" %) 2964 2964 |**Register**|**Function**|**Description** 2965 2965 |TSPL_PT0|X coordinate|Unit: dot ... ... @@ -2978,11 +2978,12 @@ 2978 2978 2979 2979 By analogy, we can know the text information configuration of the 2nd to 20th QR codes 2980 2980 2981 -Print QR code: 2475 +3.Print QR code: 2982 2982 2983 -* TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code. 2984 -* Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99: 2477 +TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code. 2985 2985 2479 +Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99: 2480 + 2986 2986 (% class="table-bordered" %) 2987 2987 |**Register**|**Function**|**Description** 2988 2988 |TSPL_PQ0|X coordinate|Unit: dot ... ... @@ -2999,13 +2999,14 @@ 2999 2999 |TSPL_PQ3|Size|Range: 0-5 3000 3000 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure 3001 3001 3002 - *By analogy, we can know the text information configuration of the 2nd to 20th QR codes.2497 +By analogy, we can know the text information configuration of the 2nd to 20th QR codes. 3003 3003 3004 -Print bar code: 2499 +4.Print bar code: 3005 3005 3006 -* TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code. 3007 -* Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99: 2501 +TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code. 3008 3008 2503 +Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99: 2504 + 3009 3009 (% class="table-bordered" %) 3010 3010 |**Register**|**Function**|**Description** 3011 3011 |TSPL_PB0|X coordinate|Unit: dot ... ... @@ -3025,28 +3025,30 @@ 3025 3025 3026 3026 By analogy, we can know the text information configuration of the 2nd to 20th bar codes. 3027 3027 3028 -Print offset: 2524 +5.Print offset: 3029 3029 3030 -* TSPL_PR0: X coordinate offset, unit: mm; 3031 -* TSPL_PR1: Y coordinate offset, unit: mm. 2526 + TSPL_PR0: X coordinate offset, unit: mm; 3032 3032 3033 -T riggerprinting:2528 + TSPL_PR1: Y coordinate offset, unit: mm. 3034 3034 3035 - *TSPL_PN0 = 1: triggertheprinter to start printing.2530 +6.Trigger printing: 3036 3036 3037 -Pri ntingstatus:2532 + TSPL_PN0 = 1: trigger the printer to start printing. 3038 3038 3039 -* TSPL_PS0 = 1: The printing is normal. 3040 -* TSPL_PS0 = 1: The printing is abnormal. 2534 +7.Printing status: 3041 3041 3042 -Print picture2536 + TSPL_PS0 = 1: The printing is normal. 3043 3043 3044 - *Forthefunctionofprintingpictures,please refer to the configuration of [Printer object].2538 + TSPL_PS0 = 1: The printing is abnormal. 3045 3045 3046 - Conversionbetweendotand mm2540 +4)Print picture 3047 3047 3048 - * Dotisthemeaningof pixels. Forthe conversionbetweendotand mm, please refer to theprinter manual orconsultthe customerserviceofthe corresponding printermanufacturer. Forexample, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.2542 +For the function of printing pictures, please refer to the configuration of [Printer object]. 3049 3049 2544 +5)Conversion between dot and mm 2545 + 2546 +Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot. 2547 + 3050 3050 == **EpsonTM series** == 3051 3051 3052 3052 **HMI Settings** ... ... @@ -3082,319 +3082,6 @@ 3082 3082 (% style="text-align:center" %) 3083 3083 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] 3084 3084 3085 -**✎Note:** COM3 only available in PI8000/PI9000 series. 3086 - 3087 - 3088 -= **Schneider MODBUS RTU** = 3089 - 3090 -**HMI Setting** 3091 - 3092 -|=**Parameters**|=**Recommended**|=**Notes** 3093 -|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU| 3094 -|Connection|RS485| 3095 -|**Baud rate**|19200| 3096 -|**Data bit**|8| 3097 -|**Parity**|Even| 3098 -|**Stop bit**|1| 3099 -|**PLC station No.**|1| 3100 - 3101 -**PLC Setting** 3102 - 3103 -|=(% scope="row" %)**Communication mode**|Modbus RTU protocol 3104 - 3105 -**Device Address** 3106 - 3107 -|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo** 3108 -|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only) 3109 -|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils 3110 -|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal) 3111 -|W|MW|DDDDDD|0 ~~ 999999|Output register 3112 -|DW|MD|DDDDDD|0 ~~ 999999|Output register 3113 - 3114 -**Wiring Diagram** 3115 - 3116 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector. 3117 - 3118 -(% style="text-align:center" %) 3119 -[[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]] 3120 - 3121 -= **Barcode Scanner** = 3122 - 3123 -Supported: DELI 14880 barcode scanner 3124 - 3125 -**HMI Setting** 3126 - 3127 -|**Items**|**Settings**|**Note** 3128 -|Protocol|Barcode Scanner| 3129 -|Connection|USB| 3130 - 3131 -**Operating Procedures** 3132 - 3133 -Select [Barcode Scanner]; 3134 - 3135 -(% style="text-align:center" %) 3136 -[[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]] 3137 - 3138 -Set address for receiving; 3139 - 3140 -Set correct length; 3141 - 3142 -(% style="text-align:center" %) 3143 -[[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]] 3144 - 3145 3145 **✎Note:** 3146 3146 3147 -* The protocol uploads the information acquired by the USB scanner to the HMI; 3148 -* The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object; 3149 -* Recommended model: DELI 14880 barcode scanner; 3150 - 3151 -= **Hitachi EHV Series (Ethernet)** = 3152 - 3153 -Supported series: Hitachi EHV series 3154 - 3155 -**HMI Settings** 3156 - 3157 -(% class="table-bordered" %) 3158 -|**Items**|**Settings**|**Note** 3159 -|Protocol|Hitachi EHV series| 3160 -|Connection|Ethernet| 3161 -|Port No.|3004~~3007| 3162 - 3163 -**Address List** 3164 - 3165 -(% class="table-bordered" %) 3166 -|**Type**|**Register**|**Range**|**Format**|**Note** 3167 -|(% rowspan="6" %)Bit|T|0 - 2545|T DDDD| 3168 -|M|0 - 7FFF.f (Hex)|M HHHH.h| 3169 -|X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)((( 3170 -H1H2H3H4 Module main number 3171 - 3172 -H1: Remote number 3173 - 3174 -H2: Unit number 3175 - 3176 -H3: Slot number 3177 - 3178 -H4: Word number of Module 3179 - 3180 -H Sub number of Module 3181 - 3182 -For example:X21.3 3183 - 3184 -Slot number 2 3185 - 3186 -Word number of module is 1 3187 - 3188 -Bit number of module is 3 3189 - 3190 -Remote number and unit number are 0 3191 -))) 3192 -|Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h 3193 -|R|0 – FF.f (Hex)|R HH.h| 3194 -|L|0 - 73FF.f (Hex)|L HHHH.h| 3195 -|(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH| 3196 -|WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)((( 3197 -H1H2H3H4 Module main number 3198 - 3199 -H1: Remote number 3200 - 3201 -H2: Unit number 3202 - 3203 -H3: Slot number 3204 - 3205 -H4: Word number of module 3206 - 3207 -For example:WX21 3208 - 3209 -Word number of module is 1 3210 - 3211 -Slot number is 2 3212 - 3213 -Remote number and unit number are 0 3214 -))) 3215 -|WY|0 – FFFF (Hex)|WY H1H2H3H4 3216 -|WR|0 – FFFF (Hex)|WR HHHH| 3217 -|WL|0 - 73FF (Hex)|WL HHHH| 3218 -|TC|0 - 2559|TC DDDD| 3219 - 3220 -**Communication settings in HMI** 3221 - 3222 -Enable HMI Ethernet in [Project Settings]; 3223 - 3224 -(% style="text-align:center" %) 3225 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 3226 - 3227 -Set PLC IP in [Device IP] settings; 3228 - 3229 -(% style="text-align:center" %) 3230 -[[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] 3231 - 3232 -**PLC Configuration** 3233 - 3234 -Connect with PLC, select[Online mode]; 3235 - 3236 -(% style="text-align:center" %) 3237 -[[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]] 3238 - 3239 -Set IP address, it is the same LAN parameters with HMI; 3240 - 3241 -(% style="text-align:center" %) 3242 -[[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]] 3243 - 3244 -3) Save PLC communication parameter, and restart PLC 3245 - 3246 -**PLC Monitor Mode** 3247 - 3248 -Connect with PLC and choose to “online” mode 3249 - 3250 -(% style="text-align:center" %) 3251 -[[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]] 3252 - 3253 -Open I/O monitor sheet1 3254 - 3255 -(% style="text-align:center" %) 3256 -[[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]] 3257 - 3258 -During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected 3259 - 3260 -(% style="text-align:center" %) 3261 -[[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]] 3262 - 3263 -Enter the register address, click OK to view the value of the register. 3264 - 3265 -(% style="text-align:center" %) 3266 -[[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] 3267 - 3268 -(% style="text-align:center" %) 3269 -[[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] 3270 - 3271 -**✎Note:** 3272 - 3273 -* Both word registers and bit registers support even continuous read/write functions; 3274 -* The range of registers is based on the specific PLC type; 3275 - 3276 -**Cable Wiring** 3277 - 3278 -(% style="text-align:center" %) 3279 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 3280 - 3281 -= **IEC60870-5 104 Client** = 3282 - 3283 -**HMI Setting** 3284 - 3285 -(% class="table-bordered" %) 3286 -|**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note** 3287 -|Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %) 3288 -|Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %) 3289 -|Port No.|(% style="width:725px" %)2404|(% style="width:309px" %) 3290 - 3291 -**Address List** 3292 - 3293 -(% class="table-bordered" %) 3294 -|(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range** 3295 -|(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7 3296 -|(% style="width:461px" %)SCNA|0~~16777215.7 3297 -|(% style="width:461px" %)DPTB|0~~16777215.7 3298 -|(% style="width:461px" %)DCNA|0~~16777215.7 3299 -|(% style="width:461px" %)METF|0~~16777215.7 3300 -|(% style="width:461px" %)SENC|0~~16777215.7 3301 -|(% style="width:461px" %)SENA|0~~16777215.7 3302 -|(% style="width:461px" %)MENA|0~~16777215.7 3303 -|(% style="width:461px" %)METD|0~~16777215.7 3304 -|(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215 3305 -|(% style="width:461px" %)SCNA|0~~16777215 3306 -|(% style="width:461px" %)DPTB|0~~16777215 3307 -|(% style="width:461px" %)DCNA|0~~16777215 3308 -|(% style="width:461px" %)SENA|0~~16777215 3309 -|(% style="width:461px" %)MENA|0~~16777215 3310 -|(% style="width:461px" %)METD|0~~16777215 3311 -|(% style="width:461px" %)INRO|0~~16777215 3312 -|(% style="width:461px" %)TIMESYN|0~~16777215 3313 -|(% style="width:461px" %)TIMEZ|0~~16777215 3314 -|(% style="width:461px" %)NTP|0~~16777215 3315 -|(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215 3316 -|(% style="width:461px" %)SENC|0~~16777215 3317 - 3318 -**Address Configuration** 3319 - 3320 -The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable. 3321 - 3322 -(% style="text-align:center" %) 3323 -[[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]] 3324 - 3325 -(% style="text-align:center" %) 3326 -[[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]] 3327 - 3328 -Extended tag name 3329 - 3330 -Address range for the extended tag. 3331 - 3332 -**Communication Settings** 3333 - 3334 -Enable HMI Ethernet in [Project Settings]; 3335 - 3336 -(% style="text-align:center" %) 3337 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 3338 - 3339 -Set PLC IP in [Device IP] settings; 3340 - 3341 -(% style="text-align:center" %) 3342 -[[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]] 3343 - 3344 -**Cable Wiring** 3345 - 3346 -(% style="text-align:center" %) 3347 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] 3348 - 3349 -= **LG XGK FEnet Ethernet** = 3350 - 3351 -Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module 3352 - 3353 -**HMI Settings** 3354 - 3355 -(% class="table-bordered" %) 3356 -|**Items**|**Settings**|**Note** 3357 -|Protocol|LG XGK FEnet(Ethernet)| 3358 -|Connection|Ethernet| 3359 -|Port No.|2004| 3360 - 3361 -**Address List** 3362 - 3363 -(% class="table-bordered" %) 3364 -|**Type**|**Register**|**Range**|**Format**|**Note** 3365 -|(% rowspan="14" %)Word|P|0~~2047|P d| 3366 -|M|0~~2047|M d| 3367 -|K|0~~2047|K d| 3368 -|F|0~~2047|F d| 3369 -|T|0~~2047|T d| 3370 -|C|0~~2047|C d| 3371 -|Z|0~~127|Z d| 3372 -|S|0~~127|S d| 3373 -|L|0~~11263|L d| 3374 -|N|0~~21503|N d| 3375 -|D|0~~32767|D d| 3376 -|R|0~~32767|R d| 3377 -|ZR|0~~65535|ZR d| 3378 -|UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31 3379 - 3380 -**✎Note:** 3381 - 3382 -* In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC; 3383 -* The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC; 3384 -* All bit registers are in the form of bits in word, and the range is the same as the word register; 3385 - 3386 -**Communication settings in HMI** 3387 - 3388 -Enable HMI Ethernet in [Project Settings]; 3389 - 3390 -(% style="text-align:center" %) 3391 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] 3392 - 3393 -Set PLC IP in [Device IP] settings; 3394 - 3395 -(% style="text-align:center" %) 3396 -[[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] 3397 - 3398 -**Cable Wiring** 3399 - 3400 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]] 2585 +COM3 only available in PI8000/PI9000 series.
- S7-XXXCommunication Settings.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Hunter - Size
-
... ... @@ -1,1 +1,0 @@ 1 -32.6 KB - Content
- S7-XXXCommunication SettingsPI.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Hunter - Size
-
... ... @@ -1,1 +1,0 @@ 1 -24.6 KB - Content
- S7-XXXCommunication SettingsPIStudio.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Hunter - Size
-
... ... @@ -1,1 +1,0 @@ 1 -24.9 KB - Content
- SiemensLOGODeviceIP.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Hunter - Size
-
... ... @@ -1,1 +1,0 @@ 1 -24.9 KB - Content
- image-20220810164710-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -7.3 KB - Content
- image-20220810165247-2.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -131.7 KB - Content
- image-20220810165759-3.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -127.8 KB - Content
- image-20220810171237-4.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -12.2 KB - Content
- image-20220810172010-5.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -350.7 KB - Content
- image-20220810172412-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -165.3 KB - Content
- image-20220811102219-3.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -49.8 KB - Content
- image-20220811103005-4.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -72.7 KB - Content
- image-20220811103131-5.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -256.1 KB - Content
- image-20220811103200-6.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -17.6 KB - Content
- image-20220811103227-7.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -16.0 KB - Content
- image-20220811104012-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -113.6 KB - Content
- image-20220811115454-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -204.7 KB - Content
- image-20220811140308-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -122.3 KB - Content
- image-20220811140530-2.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -126.0 KB - Content
- image-20220811163047-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -165.7 KB - Content
- image-20220811163943-2.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -153.6 KB - Content
- image-20220811170248-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -91.7 KB - Content
- image-20220811170753-2.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Ben - Size
-
... ... @@ -1,1 +1,0 @@ 1 -154.4 KB - Content
- image-20220817154212-1.jpeg
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -51.8 KB - Content
- image-20220819093729-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -10.3 KB - Content
- image-20220819093729-10.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -79.4 KB - Content
- image-20220819093729-12.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -147.9 KB - Content
- image-20220819093729-15.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -74.6 KB - Content
- image-20220819093729-17.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -115.0 KB - Content
- image-20220819093729-18.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -112.1 KB - Content
- image-20220819093729-2.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -34.1 KB - Content
- image-20220819093729-3.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -44.2 KB - Content
- image-20220819093729-4 (1).png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -82.4 KB - Content
- image-20220819093729-4.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -82.4 KB - Content
- image-20220819093729-5.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -6.6 KB - Content
- image-20220819093729-6.jpeg
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -100.2 KB - Content
- image-20220819093729-7.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -46.9 KB - Content
- image-20220819093730-19.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -122.5 KB - Content
- image-20220819093730-20.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -99.6 KB - Content
- image-20220819101447-3.jpeg
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -56.6 KB - Content
- image-20220819105530-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -1.0 MB - Content
- image-20220819105630-3.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -1.1 MB - Content
- image-20220819105644-4.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -942.6 KB - Content
- image-20220819105928-9.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -72.6 KB - Content
- image-20220820150853-1.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.Stone - Size
-
... ... @@ -1,1 +1,0 @@ 1 -171.7 KB - Content