Wiki source code of 11 PLC Protocol

Version 115.1 by Ben on 2022/08/30 14:07

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 = Create communication with **Rockwell PLC** =
472
473 == **MicroLogix Protocol** ==
474
475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
476
477 **HMI Settings**
478
479 (% class="table-bordered" %)
480 |**Item**|**Settings**|**Note**
481 |Protocol|Allen-Bradlley MicroLogix|
482 |Connection|RS232|
483 |Baud rate|19200|
484 |Data bit|8|
485 |Parity|None|
486 |Stop bit|1|
487 |PLC station No.|1|
488
489 **Address List**
490
491 (% class="table-bordered" %)
492 |**Type**|**Device registers**|**Format**|**Range**|**Note**
493 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
494 |O|O d.d|0.0~~255.15|
495 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
496 |S|S d.d|0.0~~255.15|
497 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |(% rowspan="9" %)Word|S|S d|0~~255|
499 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
500 |TP|TP nnhh|0~~ffff
501 |CS|CS nnhh|0~~ffff
502 |CP|CP nnhh|0~~ffff
503 |N|N nnhh|0~~ffff
504 |C|C nnhh|0~~ffff
505 |T|T nnhh|0~~ffff
506 |R|R nnhh|0~~ffff
507
508 **Cable Wiring**
509
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513
514 == **CompactLogix FreeTag Ethernet protocol** ==
515
516 Allen-Brandly CompactLogix
517
518 **HMI Settings**
519
520 (% class="table-bordered" %)
521 |**Items**|**Settings**|**Note**
522 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
523 |Connection|Ethernet|
524 |Port No.|44818|
525
526 **PLC Setting**
527
528 Create new tags
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
532
533 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
534
535 (% style="text-align:center" %)
536 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
537
538 Import labels, please open [Communication] window and click [Import label];
539
540 Select csv file, all tags will be displayed as belows;
541
542 (% style="text-align:center" %)
543 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
544
545 **✎Note:**
546
547 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
551
552 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
553
554 **Communication settings in HMI**
555
556 Enable HMI Ethernet in [Project Settings];
557
558 (% style="text-align:center" %)
559 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
560
561 Set PLC IP in [Device IP] settings;
562
563 (% style="text-align:center" %)
564 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570
571 == **MicroLogix 1200** ** protocol** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |**PLC word address type**|**Address format**|**Address range**
589 |S|ddd|S0 ~~ 255
590 |TS|ffff|TS0 ~~ FFFF
591 |TP|ffff|TP0 ~~ FFFF
592 |CS|ffff|CS0 ~~ FFFF
593 |CP|ffff|CP0 ~~ FFFF
594 |N|ffff|N0 ~~ FFFF
595 |F|ffff|F0 ~~ FFFF
596
597 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
598
599 == **S7-200 Smart Ethernet Protocol** ==
600
601 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
602
603 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
604
605 **HMI Setting**
606
607 (% class="table-bordered" %)
608 |**Items**|**Settings**|**Note**
609 |Protocol|Simens S7-200 Smart Ethernet|
610 |Connection|Ethernet|
611 |Port No.|102|
612 |PLC station No.|2|
613
614 **Address List**
615
616 (% class="table-bordered" %)
617 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
618 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
619 |Q|Q|Q ddddd.o|0.0~~99999.7|
620 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
621 |V|V|V ddddd.o|0.0~~99999.7|
622 |M|M|M ddddd.o|0.0~~99999.7|
623 |SM|SM|ddddd.o|0.0~~99999.7|
624 |S|S|ddddd.o|0.0~~99999.7|Read only
625 |T|T|ddddd|0~~99999|Timer state, read only
626 |C|C|ddddd|0~~99999|Counter state, read only
627 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
628 |Q|QW|QW ddddd|0~~99999|
629 |AI|AIW|AIW ddddd|0~~99999|
630 |AQ|VB|VB ddddd|0~~99999|
631 |V|VW|VW ddddd|0~~99998|(((
632 VW0=VB (0~~1)
633
634 VW2=VB (2~~3)
635
636 Address value is a multiple of 2
637 )))
638 |V|VD|VD ddddd|0~~99998|(((
639 VD0=VB (0~~3)
640
641 VD2=VB (4~~7)
642
643 Address value is a multiple of 4
644 )))
645 |M|MB|MB ddddd|0~~99999|
646 |M|MW|MW ddddd|0~~99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD ddddd|0~~99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |T|TW|TW ddddd|0~~99999|Value of timer
661 |C|CW|CW ddddd|0~~99999|Value of counter
662 |W|SW|SW ddddd|0~~99999|
663
664 **Communication Settings**
665
666 Enable HMI Ethernet in [Project Settings];
667
668 (% style="text-align:center" %)
669 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
670
671 Set PLC IP in [Device IP] settings;
672
673 (% style="text-align:center" %)
674 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
675
676 * PLC IP Address: PLC IP
677 * PLC pot No.: 102(fixed)
678 * Network:TCP_Client_2N(fixed)
679
680 (% style="text-align:center" %)
681 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
682
683 * Wait timeout: depend on actual network situation (more than 1500 ms)
684
685 **Cable Wiring**
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
689
690 == **S7-300 Ethernet Protocol** ==
691
692 Supported Series: Siemens S7-300 series PLC
693
694 **HMI Setting**
695
696 (% class="table-bordered" %)
697 |**Items**|**Settings**|**Note**
698 |Protocol|Simens S7-300 Ethernet|
699 |Connection|Ethernet|
700 |Port No.|102|
701 |PLC station No.|2|Need to be same as the PLC setting
702
703 **Address List**
704
705 (% class="table-bordered" %)
706 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
707 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
708 |Q|Q|Q ddddd.o|0.0~~99999.7|
709 |M|M|M ddddd.o|0.0~~99999.7|
710 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
711 nn: block number;
712
713 dddd: address;
714 )))
715 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
716 |Q|QW|QW ddddd|0~~99999|
717 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
718 |MW|MW ddddd|0~~99999|(((
719 MW0=MB(0~~1)
720
721 MW2=MB(2~~3)
722
723 Address value is a multiple of 2
724 )))
725 |MD|MD ddddd|0~~99999|(((
726 MD0=MB(0~~3)
727
728 MD4=MB(4~~7)
729
730 Address value is a multiple of 4
731 )))
732 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
733 nn: block number;
734
735 dddd: address
736 )))
737 |DBxDBW|DBxDBW nndddd|0~~99999999
738 |DBxDBD|DBxDBD nndddd|0~~99999999
739
740 **Communication Settings**
741
742 Enable HMI Ethernet in [Project Settings];
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
746
747 Set PLC IP in [Device IP] settings;
748
749 (% style="text-align:center" %)
750 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
751
752 * PLC IP Address: PLC IP
753 * PLC pot No.: 102(fixed)
754 * Network:TCP_Client_2N(fixed)
755
756 (% style="text-align:center" %)
757 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
758
759 * Wait timeout: depend on actual network situation (more than 1500 ms)
760
761 **Cable Wiring**
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
765
766 == **S7-1200 Ethernet Protocol** ==
767
768 Supported Series: Siemens S7-1200
769
770 **HMI Setting**
771
772 (% class="table-bordered" %)
773 |**Items**|**Settings**|**Note**
774 |Protocol|Siemens S7-1200|
775 |Connection|Ethernet|
776 |Port No.|102|
777 |PLC station No.|2|
778
779 **Address List**
780
781 (% class="table-bordered" %)
782 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
783 |(% rowspan="4" %)Bit|I|I|M d.o|(((
784 d:0~-~-9999
785
786 o:0-7
787 )))|
788 |Q|Q|Q d.o|(((
789 d:0~-~-9999
790
791 o:0-7
792 )))|
793 |M|M|M d.o|(((
794 d:0~-~-9999
795
796 o:0-7
797 )))|
798 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
799 nn:0-9999,
800
801 dddd:0-9999,
802
803 o:0-7
804 )))|(((
805 nn:DB No.
806
807 dddd:address value
808
809 o: digit address
810 )))
811 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
812 |M|MW|MW d|d:0-99999|(((
813 MW0=MB(0~~1)
814
815 MW2=MB(2~~3)
816
817 Address value is a multiple of 2
818 )))
819 |M|MD|MD d|d:0-99999|(((
820 MD0=MB(0~~3)
821
822 MD4=MB(4~~7)
823
824 Address value is a multiple of 4
825 )))
826 |I|IW|IW d|d:0-99999|
827 |Q|QW|QW d|d:0-99999|
828 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
829 nn:0-9999
830
831 dddd:0-9999
832 )))|(((
833 nn:DB No.
834
835 dddd:address value
836 )))
837 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
838 nn:0-9999
839
840 dddd:0-9999
841 )))|(((
842 nn:DB No.
843
844 dddd:address value
845
846 Address value is a multiple of 2
847 )))
848 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
849 nn:0-9999
850
851 dddd:0-9999
852 )))|(((
853 nn:DB No.
854
855 dddd:address value
856
857 Address value is a multiple of 4
858 )))
859
860 **Communication Settings**
861
862 Enable HMI Ethernet in [Project Settings];
863
864 (% style="text-align:center" %)
865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
866
867 Set PLC IP in [Device IP] settings;
868
869 (% style="text-align:center" %)
870 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
871
872 **✎Note:**
873
874 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
875 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
876
877 **PLC Settings**
878
879 Add BD
880
881 * Please uncheck [Symbolic access only] option;
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
885
886 Address settings, using BD2 as example.
887
888 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
889 * 2 represent DB block number
890 * xxxx represent address
891
892 **Such as:**
893
894 * DBxDBB20000 = DB2.DBB0
895 * DBxDBW20004 = DB2.DBW4
896
897 (% style="text-align:center" %)
898 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
899
900 **How to connect with S7-1200 Firmware V4.0**
901
902 PLC configuration
903
904 * Double click [device configuration] in Siemens via software
905 * Double click [protection] to enter protection configuration screen
906
907 (% style="text-align:center" %)
908 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
909
910 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
911
912 (% style="text-align:center" %)
913 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
914
915 DB settings
916
917 * Right click [DB], select [properties]
918 * Uncheck [optimized block access]
919
920 **Cable Wiring**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924
925 == **S7-XXX Ethernet Protocol** ==
926
927 Supported Series: Siemens S7-400, S7-1200 and S7-1500
928
929 **HMI Setting**
930
931 (% class="table-bordered" style="width:823px" %)
932 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
933 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
934 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
935 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
936 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
937 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
938
939 Slot from TIA Portal is equal to Device No. of PIStudio
940
941 Rack from TIA Portal is equal to HMI No. of PIStudio
942
943 (% style="text-align:center" %)
944 [[image:S7-XXXCommunication Settings.png]]
945
946 (% style="text-align:center" %)
947 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
948
949 **Address List**
950
951 (% class="table-bordered" %)
952 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
953 |(% rowspan="4" %)Bit|I|I|M d.o|(((
954 d:0~-~-9999
955
956 o:0-7
957 )))|
958 |Q|Q|Q d.o|(((
959 d:0~-~-9999
960
961 o:0-7
962 )))|
963 |M|M|M d.o|(((
964 d:0~-~-9999
965
966 o:0-7
967 )))|
968 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
969 nn:0-9999,
970
971 dddd:0-9999,
972
973 o:0-7
974 )))|(((
975 nn:DB No.
976
977 dddd:address value
978
979 o: digit address
980 )))
981 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
982 |M|MW|MW d|d:0-99999|(((
983 MW0=MB(0~~1)
984
985 MW2=MB(2~~3)
986
987 Address value is a multiple of 2
988 )))
989 |M|MD|MD d|d:0-99999|(((
990 MD0=MB(0~~3)
991
992 MD4=MB(4~~7)
993
994 Address value is a multiple of 4
995 )))
996 |I|IW|IW d|d:0-99999|
997 |Q|QW|QW d|d:0-99999|
998 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
999 nn:0-9999
1000
1001 dddd:0-9999
1002 )))|(((
1003 nn:DB No.
1004
1005 dddd:address value
1006 )))
1007 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1008 nn:0-9999
1009
1010 dddd:0-9999
1011 )))|(((
1012 nn:DB No.
1013
1014 dddd:address value
1015
1016 Address value is a multiple of 2
1017 )))
1018 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1019 nn:0-9999
1020
1021 dddd:0-9999
1022 )))|(((
1023 nn:DB No.
1024
1025 dddd:address value
1026
1027 Address value is a multiple of 4
1028 )))
1029
1030 **Communication Settings**
1031
1032 Enable HMI Ethernet in [Project Settings];
1033
1034 (% style="text-align:center" %)
1035 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1036
1037 Set PLC IP in [Device IP] settings;
1038
1039 (% style="text-align:center" %)
1040 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1041
1042 **✎Note:**
1043
1044 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1045 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1046
1047 **Cable Wiring**
1048
1049 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1050
1051 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1052
1053 Supported Series: Siemens Logo 0BA0 series
1054
1055 **HMI Settings**
1056
1057 (% class="table-bordered" %)
1058 |**Items**|**Settings**|**Note**
1059 |Protocol|Siemens LOGO|
1060 |Connection|Ethernet|
1061 |Port No.|102|
1062 |PLC station No.|2|
1063
1064 **Address List**
1065
1066 (% class="table-bordered" %)
1067 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1068 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1069 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1070 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1071 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1072 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1073 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1074 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1075 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1076 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1077 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1078 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1079 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1080 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1081 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1082 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1083
1084 **PLC Settings in LOGO Software:**
1085
1086 Click [Tools]~-~-[Ethernet Connections],shown as below.
1087
1088 (% style="text-align:center" %)
1089 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1090
1091 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1095
1096 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1097
1098 (% style="text-align:center" %)
1099 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1100
1101 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1102
1103 (% style="text-align:center" %)
1104 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1105
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1109
1110
1111 **HMI Communication Settings**
1112
1113 Set PLC IP in [Device IP] settings;
1114
1115 (% style="text-align:center" %)
1116 [[image:SiemensLOGODeviceIP.png]]
1117
1118 Enable HMI Ethernet in [Project Settings];
1119
1120 (% style="text-align:center" %)
1121 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1122
1123 TSAP setting
1124
1125 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1126 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1127 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1128
1129 **✎Note:**
1130
1131 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1132
1133 (% style="text-align:center" %)
1134 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1135
1136
1137 * AI word address and Ibit address are read-only and cannot be written on HMI.
1138 * VW address should be even number.such as VW0, VW2, VW4...
1139 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1140 * Written value of RTC cannot exceed 255.
1141
1142 **Cable Wiring**
1143
1144 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1145
1146 = Create communication with **Mitsubishi PLC** =
1147
1148 == **FX1S, 1N, 2N Series Protocol** ==
1149
1150 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1151
1152 **HMI Settings**
1153
1154 (% class="table-bordered" %)
1155 |**Item**|**Settings**|**Note**
1156 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1157 |Connection|RS422/RS485/RS232|
1158 |Baud rate|9600~~115200|
1159 |Data bit|7/8|
1160 |Parity|EVEN/Odd/None|
1161 |Stop bit|1/2|
1162 |PLC station No.|1~~255|
1163
1164 **Address List**
1165
1166 (% class="table-bordered" %)
1167 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1168 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1169 |Y|Y|Y o|0~~303237|
1170 |M|M|M d|0~~99999|
1171 |T|T|T d|0~~99999|
1172 |C|C|C d|0~~99999|
1173 |S|S|S d|0~~99999|
1174 |SM|SM|SM d|8000~~9999|
1175 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1176 |Y|Y|Y o|0~~303237|
1177 |M|M|M d|0~~99999|
1178 |T|T|T d|0~~99999|
1179 |C|C|C d|0~~199|
1180 |D|D|D d|0~~7999|
1181 |S|S|S d|0~~99999|
1182 |SD|SD|SD d|8000~~9999|
1183
1184 **Cable Wiring**
1185
1186 * **RS485**
1187
1188 (% style="text-align:center" %)
1189 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1190
1191 (% style="text-align:center" %)
1192 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1193
1194 * **RS422**
1195
1196 (% style="text-align:center" %)
1197 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1198
1199 **✎Note:** COM3 only available in PI8000/PI9000 series.
1200
1201 == **FX5U Ethernet Protocol** ==
1202
1203 Mitsubishi FX5U series PLC
1204
1205 **HMI Settings**
1206
1207 (% class="table-bordered" %)
1208 |**Items**|**Settings**|**Note**
1209 |Protocol|Mitsubishi FX5U|
1210 |Connection|Ethernet|
1211 |Port No.|5002|Must be the same as the PLC setting
1212 |PLC station No.|0|
1213
1214 **Address List**
1215
1216 (% class="table-bordered" %)
1217 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1218 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1219 |Y|Y|Y o|0~~303237|
1220 |M|M|M d|0~~99999|
1221 |B|B|B h|0~~7FFF|
1222 |F|F|F d|0~~32767|
1223 |SB|SB|SB h|0~~7FFF|
1224 |TS|TS|TS d|0~~1023|
1225 |TC|TC|TC d|0~~1023|
1226 |STS|STS|STS d|0~~1023|
1227 |STC|STC|STS d|0~~1023|
1228 |CS|CS|CS d|0~~1023|
1229 |CC|CC|CC d|0~~1023|
1230 |SM|SM|SM d|0~~9999|
1231 |L|L|L d|0~~32767|
1232 |S|S|S d|0~~4095|
1233 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1234 |TN|TN|TN d|0~~1023|
1235 |STN|STN|STN d|0~~1023|
1236 |CN|CN|CN d|0~~1023|
1237 |R|R|R d|0~~32767|
1238 |SW|SW|SW h|0~~7FFF|
1239 |Z|Z|Z d|0~~23|
1240 |D|D|D d|0~~7999|
1241 |SD|SD|SD d|0~~11999|
1242
1243 **PLC Settings (GX Works 3)**
1244
1245 Find the [Ethernet port] in the navigation area.
1246
1247 (% style="text-align:center" %)
1248 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1249
1250 Select [Own Node Settings] in the [Setting Item List];
1251
1252 Set [IP Address], [Subnet Mask], [Default Gateway];
1253
1254 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1255
1256 (% style="text-align:center" %)
1257 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1258
1259 Select [SLMP Connection Module] and add into host station as below picture shows;
1260
1261 Set Port number as 5002 (this is necessary settings);
1262
1263 Click [Close with Reflecting the Setting] to save and close window;
1264
1265 (% style="text-align:center" %)
1266 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1267
1268 Click [Apply] to completed Etherenet settings;
1269
1270 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1271
1272 (% style="text-align:center" %)
1273 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1274
1275 **Cable Wiring**
1276
1277 (% style="text-align:center" %)
1278 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1279
1280 == **FX5U Serial Port Protocol** ==
1281
1282 Mitsubishi FX5U series PLC
1283
1284 **HMI Settings**
1285
1286 (% class="table-bordered" %)
1287 |**Item**|**Settings**|**Note**
1288 |Protocol|Mitsubishi FX5U|
1289 |Connection|RS422/RS485|
1290 |Baud rate|9600|
1291 |Data bit|7|
1292 |Parity|Odd|
1293 |Stop bit|1|
1294 |PLC station No.|1~~255|Need to be the same as PLC settings
1295
1296 **Address List**
1297
1298 (% class="table-bordered" %)
1299 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1300 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1301 |Y|Y|Y o|0~~303237|
1302 |M|M|M d|0~~99999|
1303 |B|B|B h|0~~7FFF|
1304 |F|F|F d|0~~32767|
1305 |SB|SB|SB h|0~~7FFF|
1306 |TS|TS|TS d|0~~1023|
1307 |TC|TC|TC d|0~~1023|
1308 |STS|STS|STS d|0~~1023|
1309 |STC|STC|STS d|0~~1023|
1310 |CS|CS|CS d|0~~1023|
1311 |CC|CC|CC d|0~~1023|
1312 |SM|SM|SM d|0~~9999|
1313 |L|L|L d|0~~32767|
1314 |S|S|S d|0~~4095|
1315 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1316 |TN|TN|TN d|0~~1023|
1317 |STN|STN|STN d|0~~1023|
1318 |CN|CN|CN d|0~~1023|
1319 |R|R|R d|0~~32767|
1320 |SW|SW|SW h|0~~7FFF|
1321 |Z|Z|Z d|0~~23|
1322 |D|D|D d|0~~7999|
1323 |SD|SD|SD d|0~~11999|
1324
1325 **PLC Settings (GX Works 3)**
1326
1327 Create a blank FX5U project
1328
1329 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1330
1331 (% style="text-align:center" %)
1332 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1333
1334 Select protocol in the setting item, and set parameters.
1335
1336 (% style="text-align:center" %)
1337 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1338
1339 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1343
1344 Click the [Apply] button to finish the setting.
1345
1346 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1347
1348 (% style="text-align:center" %)
1349 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1350
1351 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1352
1353 Done.
1354
1355 **Cable Wiring**
1356
1357 * **RS485**
1358
1359 (% style="text-align:center" %)
1360 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1361
1362 (% style="text-align:center" %)
1363 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1364
1365 * **RS422**
1366
1367 (% style="text-align:center" %)
1368 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1369
1370 **✎Note:** COM3 only available in PI8000/PI9000 series.
1371
1372 == **L02 MELSEC (Ethernet) Protocol** ==
1373
1374 Mitsubishi Q series CPU built-in Ethernet port.
1375
1376 **HMI Settings**
1377
1378 (% class="table-bordered" %)
1379 |**Items**|**Settings**|**Note**
1380 |Protocol|MIT L02 CPU MELSEC|
1381 |Connection|Ethernet|
1382 |Port No.|1025|Must be the same as the PLC setting
1383 |PLC station No.|0|Must be the same as the PLC setting
1384
1385 **Address List**
1386
1387 (% class="table-bordered" %)
1388 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1389 |Bit|X|X|X h|0~~FFFF|
1390 |Bit|Y|Y|Y h|0~~FFFF|
1391 |Bit|M|M|M d|0~~9999|
1392 |Bit|L|L|L d|0~~9999|
1393 |Bit|F|F|F d|0~~9999|
1394 |Bit|B|B|B h|0~~FFFF|
1395 |Bit|V|V|V d|0~~2047|
1396 |Bit|TC|TC|TC d|0~~9999|
1397 |Bit|SS|SS|SS d|0~~9999|
1398 |Bit|SC|SC|SC d|0~~9999|
1399 |Bit|CS|CS|CS d|0~~9999|
1400 |Bit|CC|CC|CC d|0~~9999|
1401 |Bit|SB|SB|SB h|0~~FFFF|
1402 |Bit|SM|SM|SM d|0~~2047|
1403 |Bit|STS|STS|STS d|0~~1023|
1404 |Bit|S|S|S d|0~~9999|
1405 |Bit|DX|DX|DX h|0~~FFFF|
1406 |Bit|DY|DY|DY h|0~~FFFF|
1407 |Bit|TS|TS|TS d|0~~9999|
1408 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1409 |Word|W|W|W h|0~~FFFF|
1410 |Word|TN|TN|TN d|0~~99999|
1411 |Word|SN|SN|SN d|0~~99999|
1412 |Word|CN|CN|CN d|0~~99999|
1413 |Word|R|R|R d|0~~99999|
1414 |Word|SW|SW|SW h|0~~FFFF|
1415 |Word|Z|Z|Z d|0~~99999|
1416 |Word|ZR|ZR|ZR h|0~~FFFF|
1417 |Word|D|D|D d|0~~99999|
1418
1419 **Communication Settings**
1420
1421 Enable HMI Ethernet in [Project Settings];
1422
1423 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1424
1425 Set PLC IP in [Device IP] settings;
1426
1427 (% style="text-align:center" %)
1428 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1429
1430 **PLC Settings (GX Works2 )**
1431
1432 Create a project
1433
1434 Set PLC IP, subnet mask and gateway;
1435
1436 Select [Binary Code] as communication data code;
1437
1438 (% style="text-align:center" %)
1439 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1440
1441 Set PLC port number, for example 1025
1442
1443 (% style="text-align:center" %)
1444 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1445
1446 Save settings;
1447
1448 Download project into PLC device;
1449
1450 Restart PLC device;
1451
1452 **Cable Wiring**
1453
1454 (% style="text-align:center" %)
1455 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1456
1457 == **QJ71E71 MELSEC Protocol** ==
1458
1459 Mitsubishi QJ71E71 Ethernet communication module;
1460
1461 **HMI Settings**
1462
1463 (% class="table-bordered" %)
1464 |**Items**|**Settings**|**Note**
1465 |Protocol|MIT QJ71E71 MELSEC|
1466 |Connection|Ethernet|
1467 |Port No.|1025|Must be the same as the PLC setting
1468 |PLC station No.|0|Must be the same as the PLC setting
1469
1470 **Address List**
1471
1472 (% class="table-bordered" %)
1473 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1474 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1475 |Y|Y|Y h|0~~1FFF|
1476 |M|M|M d|0~~99999|
1477 |L|L|L d|0~~8191|
1478 |F|F|F d|0~~2047|
1479 |B|B|B h|0~~1FFF|
1480 |V|V|V d|0~~2047|
1481 |TS|TS|TS d|0~~2047|
1482 |TC|TC|TC d|0~~2047|
1483 |SS|SS|SS d|0~~2047|
1484 |SC|SC|SC d|0~~2047|
1485 |CS|CS|CS d|0~~1023|
1486 |CC|CC|CC d|0~~1023|
1487 |SB|SB|SB h|0~~7FF|
1488 |S|S|S d|0~~8191|
1489 |DX|DX|DX h|0~~1FFF|
1490 |DY|DY|DY h|0~~1FFF|
1491 |SM|SM|SM d|8000~~9999|
1492 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1493 |D|D|D d|0~~12287|
1494 |W|W|W h|0~~1FFF|
1495 |TN|TN|TN d|0~~2047|
1496 |SN|SN|SN d|0~~2047|
1497 |CN|CN|CN d|0~~1023|
1498 |R|R|R d|0~~32767|
1499 |SW|SW|SW h|0~~7FF|
1500 |Z|Z|Z d|0~~15|
1501 |ZR|ZR|ZR h|0~~FE7FF|
1502
1503 **HMI Communication Settings**
1504
1505 1) Enable HMI Ethernet in [Project Settings];
1506
1507 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1508
1509 2) Set PLC IP in [Device IP] settings;
1510
1511 (% style="text-align:center" %)
1512 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1513
1514 **PLC Settings(GX Works2)**
1515
1516 * Click [Ethernet/CC IE/MELSECNET];
1517 * Please select [Ethernet] as network type;
1518 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1519 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1520 * Click [Operation setting] to set IP;
1521 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1522 * Set protocol: TCP;
1523 * Set [unpassive] in [Open system];
1524 * Set [receive] in [Fixed buffer];
1525 * Set [procedure Exist] in [Fixed buffer communication];
1526 * Disable [Pairing open];
1527 * Set [No confirm] in [Existence confirmation];
1528 * Host station port number: 1025;
1529 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1530 * Download project into PLC and restart it
1531
1532 **Cable Wiring**
1533
1534 (% style="text-align:center" %)
1535 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1536
1537 = Create communication with **Delta PLC** =
1538
1539 == **DVP serial protocol** ==
1540
1541 (% class="wikigeneratedid" %)
1542 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1543
1544 **1)HMI Settings**
1545
1546 |**Item**|**Settings**|**Note**
1547 |Protocol|DELTA DVP Series|
1548 |Connection|RS485|
1549 |Baud rate|9600|
1550 |Data bit|7|
1551 |Parity|Even|
1552 |Stop bit|1|
1553 |PLC station No.|1~~255|Need to be the same as PLC settings
1554
1555 **2)Address List**
1556
1557 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1558 |Bit|X|X|X d|0~~303237|
1559 |Bit|Y|Y|Y d|0~~303237|
1560 |Bit|M|M|M d|0~~99999|
1561 |Bit|T|T|T d|0~~99999|
1562 |Bit|C|C|T d|0~~99999|
1563 |Bit|S|S|T d|0~~99999|
1564 |Word|D|D|D d|0~~99999|
1565 |Word|T|T|T d|0~~99999|
1566 |Word|C|C|C d|0~~99999|
1567
1568 (% class="wikigeneratedid" %)
1569 **3)Configure the communication protocol**
1570
1571 (% class="wikigeneratedid" %)
1572 [[image:image-20220829152327-6.png]]
1573
1574 (% class="wikigeneratedid" %)
1575 [[image:image-20220829152016-3.png]]
1576
1577 (% class="wikigeneratedid" %)
1578 **4)Cable Wiring**
1579
1580 (% class="wikigeneratedid" id="H" %)
1581 [[image:image-20220829152610-7.png]]
1582
1583 (% class="wikigeneratedid" id="H" %)
1584 [[image:image-20220829152102-5.png]]
1585
1586
1587 == **DVP Ethernet Protocol** ==
1588
1589 (% class="wikigeneratedid" %)
1590 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1591
1592 **1)HMI Settings**
1593
1594 |**Items**|**Settings**|**Note**
1595 |Protocol|DELTA DVP Modbus TCP|
1596 |Connection|Ethernet|
1597 |Port No.|201|Must be the same as the PLC setting
1598 |PLC station No.|0|Must be the same as the PLC setting
1599
1600 **2)Address List**
1601
1602 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1603 |Bit|X|X|X o|0~~377|
1604 |Bit|Y|Y|Y o|0~~377|
1605 |Bit|M0|M0|M0 d|0~~1535|
1606 |Bit|M1|M1|M1 d|1536~~4095|
1607 |Bit|T|T|T d|0~~255|
1608 |Bit|C|C|C d|0~~255|
1609 |Bit|S|S|S d|0~~1023|
1610 |Word|D0|D0|D0 d|0~~4095|
1611 |Word|D1|D1|D1 d|4096~~11999|(((
1612
1613 )))
1614 |Word|T|T|T d|0~~255|
1615 |Word|C|C|C d|0~~199|(((
1616
1617 )))
1618
1619 (% class="wikigeneratedid" %)
1620 **3)Configure the communication protocol**
1621
1622 [[image:image-20220829155452-1.png]]
1623
1624 [[image:image-20220829162116-2.png]]
1625
1626 **4)Cable Wiring**
1627
1628 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1629
1630 == **AS serial protocol** ==
1631
1632 **1)HMI Settings**
1633
1634 |**Item**|**Settings**|**Note**
1635 |Protocol|DELTA AS300 MODBUS RTU|
1636 |Connection|RS485|
1637 |Baud rate|9600|
1638 |Data bit|8|
1639 |Parity|NONE|
1640 |Stop bit|1|
1641 |PLC station No.|1|
1642
1643 **2)Address List**
1644
1645
1646 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1647 |Bit|X|X|X d|0~~63|
1648 |Bit|Y|Y|Y d|0~~63|
1649 |Bit|D|D|D d|0~~29999|
1650 |Bit|M|M|M d|0~~8191|
1651 |Bit|SM|SM|SM d|0~~4095|
1652 |Bit|S|S|S h|0~~2047|
1653 |Bit|T|T|T d|0~~511|
1654 |Bit|C|C|C d|0~~511|
1655 |Bit|HC|HC|HC d|0~~255|
1656 |Word|X|X|X h|0~~63|
1657 |Word|Y|Y|Y d|0~~63|
1658 |Word|SR|SR|SR d|0~~2047|
1659 |Word|D|D|D d|0~~29999|
1660 |Word|T|T|T d|0~~511|
1661 |Word|C|C|C h|0~~511|
1662 |Word|E|E|E d|0~~9|
1663
1664 **3)Configure the communication protocol**
1665
1666 [[image:image-20220830094600-1.png]]
1667
1668 [[image:image-20220830094657-2.png]]
1669
1670 **4)Cable Wiring**
1671
1672 [[image:image-20220830095131-1.png]]
1673
1674 == **AS Ethernet Protocol** ==
1675
1676 **1)HMI Settings**
1677
1678
1679 |=**Items**|=**Settings**|=**Note**
1680 |Protocol|DELTA AS300 MODBUS TCP|
1681 |Connection|Ethernet|
1682 |Port No.|502|
1683 |Device No.|1|
1684 |HMI No.|0|
1685
1686 **2)Address List**
1687
1688
1689 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1690 |Bit|X|X|X d|0~~63|
1691 |Bit|Y|Y|Y d|0~~63|
1692 |Bit|D|D|D d|0~~29999|
1693 |Bit|M|M|M d|0~~8191|
1694 |Bit|SM|SM|SM d|0~~4095|
1695 |Bit|S|S|S h|0~~2047|
1696 |Bit|T|T|T d|0~~511|
1697 |Bit|C|C|C d|0~~511|
1698 |Bit|HC|HC|HC d|0~~255|
1699 |Word|X|X|X h|0~~63|
1700 |Word|Y|Y|Y d|0~~63|
1701 |Word|SR|SR|SR d|0~~2047|
1702 |Word|D|D|D d|0~~29999|
1703 |Word|T|T|T d|0~~511|
1704 |Word|C|C|C h|0~~511|
1705 |Word|E|E|E d|0~~9|
1706
1707 **3)Configure the communication protocol**
1708
1709 [[image:image-20220830140537-1.png]]
1710
1711 [[image:image-20220830140629-2.png]]
1712
1713 **4)Cable Wiring**
1714
1715 Physical map
1716
1717 [[image:image-20220830094929-1.png]]
1718
1719 Pin Definition Diagram
1720
1721 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1722
1723 = **MODBUS** =
1724
1725 == **MODBUS RTU Master** ==
1726
1727 Supported Series: MODBUS RTU CONTROLLER
1728
1729 HMI works as MODBUS SLAVE connecting with MASTER
1730
1731 (% style="text-align:center" %)
1732 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1733
1734
1735 (% style="text-align:center" %)
1736 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1737
1738
1739 (% style="text-align:center" %)
1740 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1741
1742 **HMI Settings**
1743
1744 (% class="table-bordered" %)
1745 |**Items**|**Settings**|**Note**
1746 |Protocol|MODBUS RTU Master|
1747 |Connection|RS485/RS232|
1748 |Baud rate|2400~~187500|
1749 |Data bit|8|
1750 |Parity|Even/ Odd/ None|
1751 |Stop bit|1/2|
1752 |Station No.|0~~255|
1753
1754 **Address List**
1755
1756 (% class="table-bordered" %)
1757 |**Type**|**HMI address**|**MODBUS code**|**Range**
1758 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1759 |Word|HDW3500~~HDW7999|4|0~~4499
1760
1761 **Cable Wiring**
1762
1763 * **RS485**
1764
1765 (% style="text-align:center" %)
1766 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1767
1768 (% style="text-align:center" %)
1769 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1770
1771 * **RS232**
1772
1773 (% style="text-align:center" %)
1774 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1775
1776 **✎Note:** COM3 only available in PI8000/PI9000 series.
1777
1778 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1779
1780 Supported Series: MODBUS RTU CONTROLLER
1781
1782 HMI works as MODBUS MASTER connecting with SLAVE.
1783
1784 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1785
1786 (% style="text-align:center" %)
1787 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1788
1789
1790 (% style="text-align:center" %)
1791 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1792
1793
1794 (% style="text-align:center" %)
1795 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1796
1797 **HMI Settings**
1798
1799 (% class="table-bordered" %)
1800 |**Items**|**Settings**|**Note**
1801 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1802 |Connection|RS485/RS232|
1803 |Baud rate|2400~~187500|
1804 |Data bit|8|
1805 |Parity|Even/ Odd/ None|
1806 |Stop bit|1/2|
1807 |PLC station No.|0~~255|
1808
1809 **Address List**
1810
1811 (% class="table-bordered" %)
1812 |**Type**|**Address Type**|**Function code & Description**
1813 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1814 |06 (write single register: write a binary value to a holding register)
1815 |10 (write values to multiple addresses )
1816 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1817 |06 (write single register: write a binary value to a holding register)
1818 |10 (write values to multiple addresses )
1819 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1820 |06 (write single register: write a binary value to a holding register)
1821 |10 (write values to multiple addresses )
1822 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1823 |10 (write values to multiple addresses )
1824 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1825 |05 (Force a single coil to force the on/off state of a logic coil)
1826 |0F (Write multiple bits, ie write continuously)
1827 |(% rowspan="3" %)1|02 (Read the input state)
1828 |05 (Force a single coil to force the on/off state of a logic coil)
1829 |0F (Write multiple bits)
1830 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1831 |05 (Force a single coil to force the on/off state of a logic coil)
1832 |0F (Write multiple bits)
1833 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1834 |0F (Write multiple bits)
1835
1836 **✎Note:**
1837
1838 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1839 * The function codes sent out are the same as those that read and write words.
1840
1841 **Station number for more than one slaves**
1842
1843 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1844
1845 (% style="text-align:center" %)
1846 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1847
1848 **Cable Wiring**
1849
1850 * **RS485**
1851
1852 (% style="text-align:center" %)
1853 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1854
1855 (% style="text-align:center" %)
1856 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1857
1858 * **RS232**
1859
1860 (% style="text-align:center" %)
1861 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1862
1863 **✎Note:** COM3 only available in PI8000/PI9000 series.
1864
1865 == **MODBUS TCP Slave (All function)** ==
1866
1867 Supported series: MODBUS TCP controller
1868
1869 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1870
1871 (% style="text-align:center" %)
1872 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1873
1874 (% style="text-align:center" %)
1875 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1876
1877
1878 (% style="text-align:center" %)
1879 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1880
1881 **HMI Setting**
1882
1883 (% class="table-bordered" %)
1884 |**Items**|**Settings**|**Note**
1885 |Protocol|MODBUS TCP Slave (All function)|
1886 |Connection|Ethernet|
1887 |Port No.|502|
1888 |PLC station No.|1|
1889
1890 **Address List**
1891
1892 (% class="table-bordered" %)
1893 |**Type**|**Register**|**Function code & Description**
1894 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1895 |06 (write single register: write a binary value to a holding register)
1896 |10 (write values to multiple addresses )
1897 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1898 |06 (write single register: write a binary value to a holding register)
1899 |10 (write values to multiple addresses )
1900 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1901 |06 (write single register: write a binary value to a holding register)
1902 |10 (write values to multiple addresses )
1903 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1904 |10 (write values to multiple addresses )
1905 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1906 |05 (Force a single coil to force the on/off state of a logic coil)
1907 |0F (Write multiple bits, ie write continuously)
1908 |(% rowspan="3" %)1|02 (Read the input state)
1909 |05 (Force a single coil to force the on/off state of a logic coil)
1910 |0F (Write multiple bits)
1911 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1912 |05 (Force a single coil to force the on/off state of a logic coil)
1913 |0F (Write multiple bits)
1914 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1915 |0F (Write multiple bits)
1916
1917 **Communication Settings**
1918
1919 Enable HMI Ethernet in [Project Settings];
1920
1921 (% style="text-align:center" %)
1922 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1923
1924 Set PLC IP in [Device IP] settings;
1925
1926 (% style="text-align:center" %)
1927 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1928
1929 **Cable Wiring**
1930
1931 (% style="text-align:center" %)
1932 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1933
1934 = **Omron** =
1935
1936 == **EC55** ==
1937
1938 Supported device: EC55 temperature instrument
1939
1940 **HMI Settings**
1941
1942 (% class="table-bordered" %)
1943 |**Items**|**Settings**|**Note**
1944 |Protocol|Omron EC55|
1945 |Connection|RS485 (9600, 2, 7, EVEN)|
1946 |Port No.|None|
1947 |PLC station No.|0|
1948
1949 **Address List**
1950
1951 (% class="table-bordered" %)
1952 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1953 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1954 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1955 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1956 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1957 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1958 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1959 |CP|-|0-6|Read controller intrinsic property
1960 |CS|-|0-2|Read controller states
1961 |CA|-|0-17|Action command
1962
1963 **Device Settings**
1964
1965 Omron E5CC PLC configuration
1966
1967 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1968
1969 (% style="text-align:center" %)
1970 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1971
1972 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1973
1974 (% style="text-align:center" %)
1975 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1976
1977 **✎Note:** The communication settings for HMI should be consistent with this setting.
1978
1979 **Cable Wiring**
1980
1981 (% style="text-align:center" %)
1982 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1983
1984 (% style="text-align:center" %)
1985 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1986
1987 **✎Note:**
1988
1989 * COM3 only available in PI8000/PI9000 series.
1990 * CA address could not support continuous writing function;
1991 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1992 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1993 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1994 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1995 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1996 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1997 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1998
1999 == EtherNet/IP NX series ==
2000
2001 Supported series: Omron NX/NJ series
2002
2003 **HMI Setting**
2004
2005 (% class="table-bordered" %)
2006 |**Items**|**Settings**|**Note**
2007 |Protocol|Omron NX Ethernet/IP|
2008 |Connection|Ethernet|
2009 |Port No.|44818|
2010 |PLC station No.|1|
2011
2012 **Instruction**
2013
2014 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2015
2016 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2017
2018 (% style="text-align:center" %)
2019 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2020
2021 **Export labels from Sysmac Studio**
2022
2023 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2024
2025 (% style="text-align:center" %)
2026 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2027
2028 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2029
2030 Click [Label manage];
2031
2032 (% style="text-align:center" %)
2033 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2034
2035 Click [Import labels] and then select the file exported in step 1;
2036
2037 (% style="text-align:center" %)
2038 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2039
2040 The Import Status field shows the result, click [OK] to finish importing address labels;
2041
2042 (% style="text-align:center" %)
2043 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2044
2045 **Communication Settings**
2046
2047 Enable HMI Ethernet in [Project Settings];
2048
2049 (% style="text-align:center" %)
2050 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2051
2052 Set PLC IP in [Device IP] settings;
2053
2054 (% style="text-align:center" %)
2055 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2056
2057
2058 (% style="text-align:center" %)
2059 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2060
2061 **Cable Wiring**
2062
2063 (% style="text-align:center" %)
2064 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2065
2066 = **SHIMADEN** =
2067
2068 == **FP23** ==
2069
2070 Supported series: SHIMADEN FP23 series
2071
2072 **HMI Setting**
2073
2074 (% class="table-bordered" %)
2075 |**Items**|**Settings**|**Note**
2076 |Protocol|SHIMADEN FP23 series|
2077 |Connection|RS485 (9600, 1, 7, EVEN)|
2078 |Port No.|None|
2079 |PLC station No.|0|
2080
2081 **Address List**
2082
2083 (% class="table-bordered" %)
2084 |**Device address**|**HMI register**|**Address range**|**Type**
2085 |0040-0043(HEX)|FP040|100064-200067|Read only
2086 |0100-010B(HEX)|FP100|100256-200267|Read only
2087 |0110-0142(HEX)|FP110|100272-200322|Read only
2088 |0182-0252(HEX)|FP182|100386-200594|Write only
2089 |0280-0281(HEX)|FP280|100640-200641|Read only
2090 |0300-030B(HEX)|FP300|100768-200779|Read and write
2091 |0380-039F(HEX)|FP380|100896-200927|Read and write
2092 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2093 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2094 |0600-0670(HEX)|FP600|101536-201814|Read and write
2095 |0720-0738(HEX)|FP720|101824-201848|Read and write
2096 |0800-083F(HEX)|FP800|102048-202111|Read and write
2097 |0900-0952(HEX)|FP900|102304-202386|Read and write
2098 | |Ctrl|0-2|
2099
2100 **✎Note:**
2101
2102 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2103 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2104 * The Ctrl register is used to store the control group number and BCC check mode.
2105
2106 **Ctrl Register Description**
2107
2108 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2109 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2110 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2111 * Ctrl3 reserved
2112
2113 **✎Note:**
2114
2115 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2116
2117 **Cable Wiring**
2118
2119 (% style="text-align:center" %)
2120 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2121
2122 (% style="text-align:center" %)
2123 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2124
2125 **✎Note:** COM3 only available in PI8000/PI9000 series.
2126
2127 == **{{id name="_Toc23422"/}}SR90** ==
2128
2129 Supported series: SHIMADEN SR90 series
2130
2131 **HMI Setting**
2132
2133 (% class="table-bordered" %)
2134 |**Items**|**Settings**|**Note**
2135 |Protocol|SHIMADEN SR90 protocol|
2136 |Connection|RS485 (1200, 1, 7, EVEN)|
2137 |Port No.|None|
2138 |PLC station No.|0|
2139
2140 **Address List**
2141
2142 (% class="table-bordered" %)
2143 |**Device address**|**HMI register**|**Address range**|**Type**
2144 |0040-0043 (HEX)|SR040|100064-100067|Read only
2145 |0100-010A(HEX)|SR0100|100256-100266|Read only
2146 |0182-018C(HEX)|SR0182|100386-100396|Write only
2147 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2148 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2149 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2150 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2151 | |Ctrl|0-2|~-~-
2152
2153 **✎Note:**
2154
2155 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2156 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2157 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2158
2159 **Ctrl Register Description**
2160
2161 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2162 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2163 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2164 * Ctrl3 reserved
2165
2166 **✎Note:**
2167
2168 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2169
2170 **Cable Wiring**
2171
2172 (% style="text-align:center" %)
2173 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2174
2175 (% style="text-align:center" %)
2176 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2177
2178 **✎Note:** COM3 only available in PI8000/PI9000 series.
2179
2180 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
2181
2182 Supported series: SHIMADEN MR13 series
2183
2184 **HMI Setting**
2185
2186 (% class="table-bordered" %)
2187 |**Items**|**Settings**|**Note**
2188 |Protocol|SHIMADEN standard protocol|
2189 |Connection|RS485 (1200, 1, 7, EVEN)|
2190 |Port No.|None|
2191 |PLC station No.|0|
2192
2193 **Address List**
2194
2195 (% class="table-bordered" %)
2196 |**Device address**|**HMI register**|**Address range**|**Type**
2197 |0100-010B(HEX)|MR100|100256-300267|Read only
2198 |0111-0126(HEX)|MR111|100273-300294|Read only
2199 |0184-0192(HEX)|MR184|100388-300402|Write only
2200 |0280-0282(HEX)|MR280|100640-300642|Read only
2201 |0300-030B(HEX)|MR300|100768-300779|Read/write
2202 |0314-0317(HEX)|MR314|100788-300791|Read/write
2203 |031A(HEX)|MR31A|100794-300794|Read/write
2204 |0320-0321(HEX)|MR320|100800-300801|Read/write
2205 |0400-0504(HEX)|MR400|101024-301284|Read/write
2206 |0506(HEX)|MR506|101286-301286|Read/write
2207 |0510-0514(HEX)|MR510|101296-301300|Read/write
2208 |0516-0524(HEX)|MR516|101302-301316|Read/write
2209 |0526(HEX)|MR526|101318-301318|Read/write
2210 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2211 |~-~-|Ctrl|0-2|~-~-
2212
2213 **✎Note:**
2214
2215 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2216 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2217 * The Ctrl register is used to store the control group number and BCC check mode.
2218
2219 **Ctrl Register Description**
2220
2221 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2222 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2223 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2224 * Ctrl3 reserved
2225
2226 **✎Note:**
2227
2228 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2229
2230 **Cable Wiring**
2231
2232 (% style="text-align:center" %)
2233 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2234
2235 (% style="text-align:center" %)
2236 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2237
2238 **✎Note:** COM3 only available in PI8000/PI9000 series.
2239
2240 = **User Defined Protocol** =
2241
2242 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2243
2244 **HMI Settings**
2245
2246 (% class="table-bordered" %)
2247 |**Items**|**Settings**|**Note**
2248 |Protocol|User defined protocol|
2249 |Connection|RS485/RS232|
2250 |Baud rate|2400~~187500|
2251 |Stop bits|1/ 2|
2252 |Data bits|7/ 8|
2253 |Parity|None/ Even/ ODD|
2254
2255 **Operating Procedures**
2256
2257 Select [User defined protocol];
2258
2259 Click [User defined protocol] button to open setting window as below;
2260
2261 (% style="text-align:center" %)
2262 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2263
2264 Configure user defined command;
2265
2266 (% style="text-align:center" %)
2267 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2268
2269 (% class="table-bordered" %)
2270 |**No**|**Item**|**Description**
2271 |1|Instruction edit|The required command.
2272 |2|Mode|Write to address or read from the address.
2273 |3|Format|Encode format: HEX or ASCII.
2274 |4|Other|(((
2275 **No receiving: **HMI does not respond to the receiving command.
2276
2277 **Send after receiving:** HMI responds to the receiving command.
2278 )))
2279 |5|Manually send|(((
2280 Respond once after trigger the address.
2281
2282 Address: set the trigger address.
2283 )))
2284 |6|Add|Save this setting.
2285 |7|Cancel|Cancel current settings.
2286 |(% rowspan="4" %)8|Add|Add a new command.
2287 |Edit|Edit the selected command.
2288 |Delete|Delete the selected command.
2289 |Clear|Clear all the commands.
2290 |9|Instruction list|Display all current commands.
2291 |10|Address List|Display all the addresses added.
2292 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2293 |Export|Export current command settings to local storage.
2294 |Browse|Browse local command files.
2295 |Advanced|Combine two commands.
2296 |Exit|Complete editing and exit setting.
2297
2298 **Operating Procedures**
2299
2300 Click [Add] to create a new command, as below shows;
2301
2302 (% style="text-align:center" %)
2303 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2304
2305 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2306
2307 (% style="text-align:center" %)
2308 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2309
2310 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2311
2312 (% style="text-align:center" %)
2313 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2314
2315 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2316
2317 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2318
2319 Check settings;
2320
2321 (% style="text-align:center" %)
2322 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2323
2324 (% class="table-bordered" %)
2325 |**No**|**Items**|**Description**
2326 |1|Add checking|Add checking command when receiving the data.
2327 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2328 |Differ with send check|Set return checking.
2329 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2330 |Length: The data length need to be checked.
2331
2332 Object settings;
2333
2334 (% style="text-align:center" %)
2335 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2336
2337 (% class="table-bordered" %)
2338 |**No**|**Items**|**Description**
2339 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2340 |Address: the triggering address;
2341 |Note: description to object;
2342 |2|Byte order|The numerical display order;
2343
2344 Data length settings;
2345
2346 (% style="text-align:center" %)
2347 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2348
2349 (% class="table-bordered" %)
2350 |**No**|**Item**|**Description**
2351 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2352 |Length: the return data length.
2353 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2354 |Length: the write data length.
2355
2356 Instruction length settings
2357
2358 (% style="text-align:center" %)
2359 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2360
2361 (% class="table-bordered" %)
2362 |**No**|**Item**|**Description**
2363 |1|Send length|The instruction data will only send designated data length.
2364 |2|Return length|The responds data length.
2365 |3|End code|Instruction will not be terminated until receiving [End code];
2366
2367 **Cable Wiring**
2368
2369 * **RS485**
2370
2371 (% style="text-align:center" %)
2372 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2373
2374 (% style="text-align:center" %)
2375 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2376
2377 * **RS232**
2378
2379 (% style="text-align:center" %)
2380 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2381
2382 **✎Note:** COM3 only available in PI8000/PI9000 series.
2383
2384 = **Printer** =
2385
2386 == **TSPL label printer** ==
2387
2388 **Introduction**
2389
2390 TSPL label printer protocol supports following models.
2391
2392 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2393 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2394
2395 **Setting Step**
2396
2397 Select the protocol
2398
2399 * Create a new project, select the TSPL label printer protocol as shown below.
2400
2401 (% style="text-align:center" %)
2402 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2403
2404 Set parameters
2405
2406 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2407
2408 Printer register
2409
2410 (% class="table-bordered" %)
2411 |**Register**|**System**|**Range**|**Function**
2412 |TSPL_SP|decimal|0 - 1|Set the paper size
2413 |TSPL_PT|decimal|0 - 1999|Print text
2414 |TSPL_PQ|decimal|0 - 999|Print QR code
2415 |TSPL_PB|decimal|0 - 999|Print barcode
2416 |TSPL_PR|decimal|0 - 1|Print offset
2417 |TSPL_PN|decimal|0 - 0|Trigger printing
2418 |TSPL_PS|decimal|0 - 0|Print status
2419
2420 * Set paper size:
2421 ** TSPL_SP0: width of paper, unit: mm.
2422 ** TSPL_SP1: height of paper, unit: mm.
2423 * Print text:
2424 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2425 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2426
2427 (% class="table-bordered" %)
2428 |**Register**|**Function**|**Description**
2429 |TSPL_PT0|X coordinate|Unit: dot
2430 |TSPL_PT1|Ycoordinate|Unit: dot
2431 |TSPL_PT2|Rotation angle|(((
2432 0: 0 degrees
2433
2434 1: 90 degrees
2435
2436 2: 180 degrees
2437
2438 3: 270 degrees
2439 )))
2440 |TSPL_PT3|Size|Range: 0-3
2441 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2442
2443 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2444
2445 Print QR code:
2446
2447 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2448 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2449
2450 (% class="table-bordered" %)
2451 |**Register**|**Function**|**Description**
2452 |TSPL_PQ0|X coordinate|Unit: dot
2453 |TSPL_PQ1|Ycoordinate|Unit: dot
2454 |TSPL_PQ2|Rotation angle|(((
2455 0: 0 degrees
2456
2457 1: 90 degrees
2458
2459 2: 180 degrees
2460
2461 3: 270 degrees
2462 )))
2463 |TSPL_PQ3|Size|Range: 0-5
2464 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2465
2466 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2467
2468 Print bar code:
2469
2470 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2471 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2472
2473 (% class="table-bordered" %)
2474 |**Register**|**Function**|**Description**
2475 |TSPL_PB0|X coordinate|Unit: dot
2476 |TSPL_PB1|Ycoordinate|Unit: dot
2477 |TSPL_PB2|Rotation angle|(((
2478 0: 0 degrees
2479
2480 1: 90 degrees
2481
2482 2: 180 degrees
2483
2484 3: 270 degrees
2485 )))
2486 |TSPL_PB3|height|Unit: dot
2487 |TSPL_PB4|width|Range:0-2
2488 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2489
2490 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2491
2492 Print offset:
2493
2494 * TSPL_PR0: X coordinate offset, unit: mm;
2495 * TSPL_PR1: Y coordinate offset, unit: mm.
2496
2497 Trigger printing:
2498
2499 * TSPL_PN0 = 1: trigger the printer to start printing.
2500
2501 Printing status:
2502
2503 * TSPL_PS0 = 1: The printing is normal.
2504 * TSPL_PS0 = 1: The printing is abnormal.
2505
2506 Print picture
2507
2508 * For the function of printing pictures, please refer to the configuration of [Printer object].
2509
2510 Conversion between dot and mm
2511
2512 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2513
2514 == **EpsonTM series** ==
2515
2516 **HMI Settings**
2517
2518 (% class="table-bordered" %)
2519 |**Item**|**Settings**|**Note**
2520 |Protocol|EPSON-TM-T82II/TM-XXX|
2521 |Connection|RS232|
2522 |Baud rate|9600~~115200|
2523 |Data bit|8|
2524 |Parity|None|
2525 |Stop bit|1|
2526 |PLC station No.|1|
2527
2528 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2529
2530 **Printer Settings**
2531
2532 (% class="table-bordered" %)
2533 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2534 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2535 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2536 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2537 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2538 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2539 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2540
2541 **Cable Wiring**
2542
2543 (% style="text-align:center" %)
2544 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2545
2546 (% style="text-align:center" %)
2547 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2548
2549 **✎Note:** COM3 only available in PI8000/PI9000 series.
2550
2551
2552 = **Schneider MODBUS RTU** =
2553
2554 **HMI Setting**
2555
2556 |=**Parameters**|=**Recommended**|=**Notes**
2557 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2558 |Connection|RS485|
2559 |**Baud rate**|19200|
2560 |**Data bit**|8|
2561 |**Parity**|Even|
2562 |**Stop bit**|1|
2563 |**PLC station No.**|1|
2564
2565 **PLC Setting**
2566
2567 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2568
2569 **Device Address**
2570
2571 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2572 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2573 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2574 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2575 |W|MW|DDDDDD|0 ~~ 999999|Output register
2576 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2577
2578 **Wiring Diagram**
2579
2580 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2581
2582 (% style="text-align:center" %)
2583 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
2584
2585 = **Barcode Scanner** =
2586
2587 Supported: DELI 14880 barcode scanner
2588
2589 **HMI Setting**
2590
2591 |**Items**|**Settings**|**Note**
2592 |Protocol|Barcode Scanner|
2593 |Connection|USB|
2594
2595 **Operating Procedures**
2596
2597 Select [Barcode Scanner];
2598
2599 (% style="text-align:center" %)
2600 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
2601
2602 Set address for receiving;
2603
2604 Set correct length;
2605
2606 (% style="text-align:center" %)
2607 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
2608
2609 **✎Note:**
2610
2611 * The protocol uploads the information acquired by the USB scanner to the HMI;
2612 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
2613 * Recommended model: DELI 14880 barcode scanner;
2614
2615 = **Hitachi EHV Series (Ethernet)** =
2616
2617 Supported series: Hitachi EHV series
2618
2619 **HMI Settings**
2620
2621 (% class="table-bordered" %)
2622 |**Items**|**Settings**|**Note**
2623 |Protocol|Hitachi EHV series|
2624 |Connection|Ethernet|
2625 |Port No.|3004~~3007|
2626
2627 **Address List**
2628
2629 (% class="table-bordered" %)
2630 |**Type**|**Register**|**Range**|**Format**|**Note**
2631 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
2632 |M|0 - 7FFF.f (Hex)|M HHHH.h|
2633 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
2634 H1H2H3H4 Module main number
2635
2636 H1: Remote number
2637
2638 H2: Unit number
2639
2640 H3: Slot number
2641
2642 H4: Word number of Module
2643
2644 H Sub number of Module
2645
2646 For example:X21.3
2647
2648 Slot number 2
2649
2650 Word number of module is 1
2651
2652 Bit number of module is 3
2653
2654 Remote number and unit number are 0
2655 )))
2656 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
2657 |R|0 – FF.f (Hex)|R HH.h|
2658 |L|0 - 73FF.f (Hex)|L HHHH.h|
2659 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
2660 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
2661 H1H2H3H4 Module main number
2662
2663 H1: Remote number
2664
2665 H2: Unit number
2666
2667 H3: Slot number
2668
2669 H4: Word number of module
2670
2671 For example:WX21
2672
2673 Word number of module is 1
2674
2675 Slot number is 2
2676
2677 Remote number and unit number are 0
2678 )))
2679 |WY|0 – FFFF (Hex)|WY H1H2H3H4
2680 |WR|0 – FFFF (Hex)|WR HHHH|
2681 |WL|0 - 73FF (Hex)|WL HHHH|
2682 |TC|0 - 2559|TC DDDD|
2683
2684 **Communication settings in HMI**
2685
2686 Enable HMI Ethernet in [Project Settings];
2687
2688 (% style="text-align:center" %)
2689 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2690
2691 Set PLC IP in [Device IP] settings;
2692
2693 (% style="text-align:center" %)
2694 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2695
2696 **PLC Configuration**
2697
2698 Connect with PLC, select[Online mode];
2699
2700 (% style="text-align:center" %)
2701 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
2702
2703 Set IP address, it is the same LAN parameters with HMI;
2704
2705 (% style="text-align:center" %)
2706 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
2707
2708 3) Save PLC communication parameter, and restart PLC
2709
2710 **PLC Monitor Mode**
2711
2712 Connect with PLC and choose to “online” mode
2713
2714 (% style="text-align:center" %)
2715 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
2716
2717 Open I/O monitor sheet1
2718
2719 (% style="text-align:center" %)
2720 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
2721
2722 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
2723
2724 (% style="text-align:center" %)
2725 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
2726
2727 Enter the register address, click OK to view the value of the register.
2728
2729 (% style="text-align:center" %)
2730 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2731
2732 (% style="text-align:center" %)
2733 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2734
2735 **✎Note:**
2736
2737 * Both word registers and bit registers support even continuous read/write functions;
2738 * The range of registers is based on the specific PLC type;
2739
2740 **Cable Wiring**
2741
2742 (% style="text-align:center" %)
2743 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2744
2745 = **IEC60870-5 104 Client** =
2746
2747 **HMI Setting**
2748
2749 (% class="table-bordered" %)
2750 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
2751 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
2752 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
2753 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
2754
2755 **Address List**
2756
2757 (% class="table-bordered" %)
2758 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
2759 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
2760 |(% style="width:461px" %)SCNA|0~~16777215.7
2761 |(% style="width:461px" %)DPTB|0~~16777215.7
2762 |(% style="width:461px" %)DCNA|0~~16777215.7
2763 |(% style="width:461px" %)METF|0~~16777215.7
2764 |(% style="width:461px" %)SENC|0~~16777215.7
2765 |(% style="width:461px" %)SENA|0~~16777215.7
2766 |(% style="width:461px" %)MENA|0~~16777215.7
2767 |(% style="width:461px" %)METD|0~~16777215.7
2768 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
2769 |(% style="width:461px" %)SCNA|0~~16777215
2770 |(% style="width:461px" %)DPTB|0~~16777215
2771 |(% style="width:461px" %)DCNA|0~~16777215
2772 |(% style="width:461px" %)SENA|0~~16777215
2773 |(% style="width:461px" %)MENA|0~~16777215
2774 |(% style="width:461px" %)METD|0~~16777215
2775 |(% style="width:461px" %)INRO|0~~16777215
2776 |(% style="width:461px" %)TIMESYN|0~~16777215
2777 |(% style="width:461px" %)TIMEZ|0~~16777215
2778 |(% style="width:461px" %)NTP|0~~16777215
2779 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
2780 |(% style="width:461px" %)SENC|0~~16777215
2781
2782 **Address Configuration**
2783
2784 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
2785
2786 (% style="text-align:center" %)
2787 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
2788
2789 (% style="text-align:center" %)
2790 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
2791
2792 Extended tag name
2793
2794 Address range for the extended tag.
2795
2796 **Communication Settings**
2797
2798 Enable HMI Ethernet in [Project Settings];
2799
2800 (% style="text-align:center" %)
2801 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2802
2803 Set PLC IP in [Device IP] settings;
2804
2805 (% style="text-align:center" %)
2806 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
2807
2808 **Cable Wiring**
2809
2810 (% style="text-align:center" %)
2811 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2812
2813 = **LG XGK FEnet Ethernet** =
2814
2815 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2816
2817 **HMI Settings**
2818
2819 (% class="table-bordered" %)
2820 |**Items**|**Settings**|**Note**
2821 |Protocol|LG XGK FEnet(Ethernet)|
2822 |Connection|Ethernet|
2823 |Port No.|2004|
2824
2825 **Address List**
2826
2827 (% class="table-bordered" %)
2828 |**Type**|**Register**|**Range**|**Format**|**Note**
2829 |(% rowspan="14" %)Word|P|0~~2047|P d|
2830 |M|0~~2047|M d|
2831 |K|0~~2047|K d|
2832 |F|0~~2047|F d|
2833 |T|0~~2047|T d|
2834 |C|0~~2047|C d|
2835 |Z|0~~127|Z d|
2836 |S|0~~127|S d|
2837 |L|0~~11263|L d|
2838 |N|0~~21503|N d|
2839 |D|0~~32767|D d|
2840 |R|0~~32767|R d|
2841 |ZR|0~~65535|ZR d|
2842 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2843
2844 **✎Note:**
2845
2846 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2847 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2848 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2849
2850 **Communication settings in HMI**
2851
2852 Enable HMI Ethernet in [Project Settings];
2853
2854 (% style="text-align:center" %)
2855 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2856
2857 Set PLC IP in [Device IP] settings;
2858
2859 (% style="text-align:center" %)
2860 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2861
2862 **Cable Wiring**
2863
2864 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2865
2866
2867 = **OpenCAN** =
2868
2869 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
2870
2871 This protocol is only available in PI8000 series HMI.
2872
2873 **HMI Settings**
2874
2875 |**Items**|**Settings**|**Note**
2876 |Protocol|OPENCAN|
2877 |Connection|CAN port|
2878 |Baud rate|250000|
2879
2880 **CAN frame setting in HMI**
2881
2882 Click [OpenCAN setting] button in communication setting window;
2883
2884 (% style="text-align:center" %)
2885 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
2886
2887 Click [Add] to create a new frame;
2888
2889 (% style="text-align:center" %)
2890 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
2891
2892 |**No**|**Items**|**Description**
2893 |1|Add|add a frame related to register address
2894 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2895 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2896 |4|Modify|Modify the frames in frame management
2897 |5|Copy|Copy one frame to another
2898 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
2899 |7|Empty|All frames in the list are cleared
2900 |8|Browse|Displays configuration files in XML format in IE
2901 |9|OK|Complete the configuration of the frame and exit
2902
2903 Set CANBUS frame in setting windows
2904
2905 (% style="text-align:center" %)
2906 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
2907
2908 |**No**|**Items**|**Description**
2909 |1|ID|Set the ID of a can frame in hexadecimal format;
2910 |2|ID assign|split the ID by PF, PS, and SA;
2911 |3|Frame type|Select Standard frame or Extended Frame;
2912 |4|Frame format|Select between data frame and remote Frame;
2913 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
2914 |6|Use address|(((
2915 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
2916
2917 **Edit:** Set a bit or word address by its format;
2918
2919 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
2920 )))
2921 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
2922 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
2923 |Feedback mode: feedback mode includes no response, confirm response and data response;
2924 |No response: the device or touch screen will not receive feedback;
2925 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
2926 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
2927 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
2928 |Response timeout: sets whether the response frame timeout;
2929 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
2930 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
2931 |Manually send: a manually send tick indicates only one send;
2932 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
2933 |10|Note|Fill the text to explain the meaning of the frame;
2934 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
2935 |12|Current operation display|Display the description of current operation;
2936 |13|Add|Add a new frame;
2937 |14|Save frame|Save the configured frame format;
2938 |15|Cancel|Cancel the frame configuration;
2939
2940 Set CAN address (Read or write operation);
2941
2942 (% style="text-align:center" %)
2943 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
2944
2945 |**No.**|**Item**|**Description**
2946 |1|Current address|Displays the register type and register address set by the user in the data access interface
2947 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
2948 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
2949 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
2950 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
2951 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
2952 |If the trigger condition is a writing operation, there are two situations:(((
2953 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
2954 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
2955 )))
2956 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
2957 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
2958 |4|Add|Add current configuration
2959 |5|Close|Close the configuration window to exit
2960
2961 **Multiple Packages Settings**
2962
2963 (% style="text-align:center" %)
2964 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
2965
2966 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
2967
2968 Select Multiple package type
2969
2970 * Not Multiple packages
2971 * J1939 Multiple packages
2972 * Customized Multiple packages
2973
2974 Click [Edit Receive data] for [Receive] settings
2975
2976 * Start code+ Total length (J1939)
2977
2978 (% style="text-align:center" %)
2979 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2980
2981 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2982
2983 * Start code + Data max length (J1939)
2984
2985 (% style="text-align:center" %)
2986 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2987
2988 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2989
2990 * Data max length (J1939)
2991
2992 (% style="text-align:center" %)
2993 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2994
2995 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2996
2997 * Customized multiple package
2998
2999 (% style="text-align:center" %)
3000 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3001
3002 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3003
3004 Click [Edit Send data] for [Send] setting
3005
3006 * J1939
3007
3008 (% style="text-align:center" %)
3009 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3010
3011 [Data] is all data to be sent.
3012
3013 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3014
3015 * Customized multiple package
3016
3017 (% style="text-align:center" %)
3018 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3019
3020 [Data] is all data to be sent.
3021
3022 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3023
3024 **Cable Wiring**
3025
3026 (% style="text-align:center" %)
3027 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3028
3029 **✎Note:** The address interval between each frame need to be more than a word address;