Wiki source code of 11 PLC Protocol

Version 171.1 by Stone Wu on 2022/09/05 09:30

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with **Rockwell PLC** =
459
460 == **MicroLogix Protocol** ==
461
462 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
463
464 **HMI Settings**
465
466 (% class="table-bordered" %)
467 |**Item**|**Settings**|**Note**
468 |Protocol|Allen-Bradlley MicroLogix|
469 |Connection|RS232|
470 |Baud rate|19200|
471 |Data bit|8|
472 |Parity|None|
473 |Stop bit|1|
474 |PLC station No.|1|
475
476 **Address List**
477
478 (% class="table-bordered" %)
479 |**Type**|**Device registers**|**Format**|**Range**|**Note**
480 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
481 |O|O d.d|0.0~~255.15|
482 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
483 |S|S d.d|0.0~~255.15|
484 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
485 |(% rowspan="9" %)Word|S|S d|0~~255|
486 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
487 |TP|TP nnhh|0~~ffff
488 |CS|CS nnhh|0~~ffff
489 |CP|CP nnhh|0~~ffff
490 |N|N nnhh|0~~ffff
491 |C|C nnhh|0~~ffff
492 |T|T nnhh|0~~ffff
493 |R|R nnhh|0~~ffff
494
495 **Cable Wiring**
496
497
498 (% style="text-align:center" %)
499 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
500
501 == **CompactLogix FreeTag Ethernet protocol** ==
502
503 Allen-Brandly CompactLogix
504
505 **HMI Settings**
506
507 (% class="table-bordered" %)
508 |**Items**|**Settings**|**Note**
509 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
510 |Connection|Ethernet|
511 |Port No.|44818|
512
513 **PLC Setting**
514
515 Create new tags
516
517 (% style="text-align:center" %)
518 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
519
520 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
521
522 (% style="text-align:center" %)
523 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
524
525 Import labels, please open [Communication] window and click [Import label];
526
527 Select csv file, all tags will be displayed as belows;
528
529 (% style="text-align:center" %)
530 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
531
532 **✎Note:**
533
534 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
535
536 (% style="text-align:center" %)
537 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
538
539 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
540
541 **Communication settings in HMI**
542
543 Enable HMI Ethernet in [Project Settings];
544
545 (% style="text-align:center" %)
546 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
547
548 Set PLC IP in [Device IP] settings;
549
550 (% style="text-align:center" %)
551 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
552
553 **Cable Wiring**
554
555 (% style="text-align:center" %)
556 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
557
558 == **MicroLogix 1200** ** protocol** ==
559
560 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
561
562 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
563 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
564 * **Word address S:** The word address ranges from 0 to 255 (decimal).
565 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
566
567 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
568
569 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
570 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
571 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
572 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
573 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
574 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
575 |**PLC word address type**|**Address format**|**Address range**
576 |S|ddd|S0 ~~ 255
577 |TS|ffff|TS0 ~~ FFFF
578 |TP|ffff|TP0 ~~ FFFF
579 |CS|ffff|CS0 ~~ FFFF
580 |CP|ffff|CP0 ~~ FFFF
581 |N|ffff|N0 ~~ FFFF
582 |F|ffff|F0 ~~ FFFF
583
584 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
585
586 == **S7-200 Smart Ethernet Protocol** ==
587
588 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
589
590 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
591
592 **HMI Setting**
593
594 (% class="table-bordered" %)
595 |**Items**|**Settings**|**Note**
596 |Protocol|Simens S7-200 Smart Ethernet|
597 |Connection|Ethernet|
598 |Port No.|102|
599 |PLC station No.|2|
600
601 **Address List**
602
603 (% class="table-bordered" %)
604 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
605 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
606 |Q|Q|Q ddddd.o|0.0~~99999.7|
607 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
608 |V|V|V ddddd.o|0.0~~99999.7|
609 |M|M|M ddddd.o|0.0~~99999.7|
610 |SM|SM|ddddd.o|0.0~~99999.7|
611 |S|S|ddddd.o|0.0~~99999.7|Read only
612 |T|T|ddddd|0~~99999|Timer state, read only
613 |C|C|ddddd|0~~99999|Counter state, read only
614 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
615 |Q|QW|QW ddddd|0~~99999|
616 |AI|AIW|AIW ddddd|0~~99999|
617 |AQ|VB|VB ddddd|0~~99999|
618 |V|VW|VW ddddd|0~~99998|(((
619 VW0=VB (0~~1)
620
621 VW2=VB (2~~3)
622
623 Address value is a multiple of 2
624 )))
625 |V|VD|VD ddddd|0~~99998|(((
626 VD0=VB (0~~3)
627
628 VD2=VB (4~~7)
629
630 Address value is a multiple of 4
631 )))
632 |M|MB|MB ddddd|0~~99999|
633 |M|MW|MW ddddd|0~~99999|(((
634 MW0=MB(0~~1)
635
636 MW2=MB(2~~3)
637
638 Address value is a multiple of 2
639 )))
640 |M|MD|MD ddddd|0~~99999|(((
641 MD0=MB(0~~3)
642
643 MD4=MB(4~~7)
644
645 Address value is a multiple of 4
646 )))
647 |T|TW|TW ddddd|0~~99999|Value of timer
648 |C|CW|CW ddddd|0~~99999|Value of counter
649 |W|SW|SW ddddd|0~~99999|
650
651 **Communication Settings**
652
653 Enable HMI Ethernet in [Project Settings];
654
655 (% style="text-align:center" %)
656 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
657
658 Set PLC IP in [Device IP] settings;
659
660 (% style="text-align:center" %)
661 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
662
663 * PLC IP Address: PLC IP
664 * PLC pot No.: 102(fixed)
665 * Network:TCP_Client_2N(fixed)
666
667 (% style="text-align:center" %)
668 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
669
670 * Wait timeout: depend on actual network situation (more than 1500 ms)
671
672 **Cable Wiring**
673
674 (% style="text-align:center" %)
675 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
676
677 == **S7-300 Ethernet Protocol** ==
678
679 Supported Series: Siemens S7-300 series PLC
680
681 **HMI Setting**
682
683 (% class="table-bordered" %)
684 |**Items**|**Settings**|**Note**
685 |Protocol|Simens S7-300 Ethernet|
686 |Connection|Ethernet|
687 |Port No.|102|
688 |PLC station No.|2|Need to be same as the PLC setting
689
690 **Address List**
691
692 (% class="table-bordered" %)
693 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
694 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
695 |Q|Q|Q ddddd.o|0.0~~99999.7|
696 |M|M|M ddddd.o|0.0~~99999.7|
697 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
698 nn: block number;
699
700 dddd: address;
701 )))
702 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
703 |Q|QW|QW ddddd|0~~99999|
704 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
705 |MW|MW ddddd|0~~99999|(((
706 MW0=MB(0~~1)
707
708 MW2=MB(2~~3)
709
710 Address value is a multiple of 2
711 )))
712 |MD|MD ddddd|0~~99999|(((
713 MD0=MB(0~~3)
714
715 MD4=MB(4~~7)
716
717 Address value is a multiple of 4
718 )))
719 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
720 nn: block number;
721
722 dddd: address
723 )))
724 |DBxDBW|DBxDBW nndddd|0~~99999999
725 |DBxDBD|DBxDBD nndddd|0~~99999999
726
727 **Communication Settings**
728
729 Enable HMI Ethernet in [Project Settings];
730
731 (% style="text-align:center" %)
732 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
733
734 Set PLC IP in [Device IP] settings;
735
736 (% style="text-align:center" %)
737 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
738
739 * PLC IP Address: PLC IP
740 * PLC pot No.: 102(fixed)
741 * Network:TCP_Client_2N(fixed)
742
743 (% style="text-align:center" %)
744 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
745
746 * Wait timeout: depend on actual network situation (more than 1500 ms)
747
748 **Cable Wiring**
749
750 (% style="text-align:center" %)
751 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
752
753 == **S7-1200 Ethernet Protocol** ==
754
755 Supported Series: Siemens S7-1200
756
757 **HMI Setting**
758
759 (% class="table-bordered" %)
760 |**Items**|**Settings**|**Note**
761 |Protocol|Siemens S7-1200|
762 |Connection|Ethernet|
763 |Port No.|102|
764 |PLC station No.|2|
765
766 **Address List**
767
768 (% class="table-bordered" %)
769 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
770 |(% rowspan="4" %)Bit|I|I|M d.o|(((
771 d:0~-~-9999
772
773 o:0-7
774 )))|
775 |Q|Q|Q d.o|(((
776 d:0~-~-9999
777
778 o:0-7
779 )))|
780 |M|M|M d.o|(((
781 d:0~-~-9999
782
783 o:0-7
784 )))|
785 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
786 nn:0-9999,
787
788 dddd:0-9999,
789
790 o:0-7
791 )))|(((
792 nn:DB No.
793
794 dddd:address value
795
796 o: digit address
797 )))
798 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
799 |M|MW|MW d|d:0-99999|(((
800 MW0=MB(0~~1)
801
802 MW2=MB(2~~3)
803
804 Address value is a multiple of 2
805 )))
806 |M|MD|MD d|d:0-99999|(((
807 MD0=MB(0~~3)
808
809 MD4=MB(4~~7)
810
811 Address value is a multiple of 4
812 )))
813 |I|IW|IW d|d:0-99999|
814 |Q|QW|QW d|d:0-99999|
815 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
816 nn:0-9999
817
818 dddd:0-9999
819 )))|(((
820 nn:DB No.
821
822 dddd:address value
823 )))
824 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
825 nn:0-9999
826
827 dddd:0-9999
828 )))|(((
829 nn:DB No.
830
831 dddd:address value
832
833 Address value is a multiple of 2
834 )))
835 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
836 nn:0-9999
837
838 dddd:0-9999
839 )))|(((
840 nn:DB No.
841
842 dddd:address value
843
844 Address value is a multiple of 4
845 )))
846
847 **Communication Settings**
848
849 Enable HMI Ethernet in [Project Settings];
850
851 (% style="text-align:center" %)
852 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
853
854 Set PLC IP in [Device IP] settings;
855
856 (% style="text-align:center" %)
857 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
858
859 **✎Note:**
860
861 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
862 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
863
864 **PLC Settings**
865
866 Add BD
867
868 * Please uncheck [Symbolic access only] option;
869
870 (% style="text-align:center" %)
871 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
872
873 Address settings, using BD2 as example.
874
875 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
876 * 2 represent DB block number
877 * xxxx represent address
878
879 **Such as:**
880
881 * DBxDBB20000 = DB2.DBB0
882 * DBxDBW20004 = DB2.DBW4
883
884 (% style="text-align:center" %)
885 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
886
887 **How to connect with S7-1200 Firmware V4.0**
888
889 PLC configuration
890
891 * Double click [device configuration] in Siemens via software
892 * Double click [protection] to enter protection configuration screen
893
894 (% style="text-align:center" %)
895 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
896
897 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
898
899 (% style="text-align:center" %)
900 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
901
902 DB settings
903
904 * Right click [DB], select [properties]
905 * Uncheck [optimized block access]
906
907 **Cable Wiring**
908
909 (% style="text-align:center" %)
910 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
911
912 == **S7-XXX Ethernet Protocol** ==
913
914 Supported Series: Siemens S7-400, S7-1200 and S7-1500
915
916 **HMI Setting**
917
918 (% class="table-bordered" style="width:823px" %)
919 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
920 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
921 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
922 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
923 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
924 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
925
926 Slot from TIA Portal is equal to Device No. of PIStudio
927
928 Rack from TIA Portal is equal to HMI No. of PIStudio
929
930 (% style="text-align:center" %)
931 [[image:S7-XXXCommunication Settings.png]]
932
933 (% style="text-align:center" %)
934 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
935
936 **Address List**
937
938 (% class="table-bordered" %)
939 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
940 |(% rowspan="4" %)Bit|I|I|M d.o|(((
941 d:0~-~-9999
942
943 o:0-7
944 )))|
945 |Q|Q|Q d.o|(((
946 d:0~-~-9999
947
948 o:0-7
949 )))|
950 |M|M|M d.o|(((
951 d:0~-~-9999
952
953 o:0-7
954 )))|
955 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
956 nn:0-9999,
957
958 dddd:0-9999,
959
960 o:0-7
961 )))|(((
962 nn:DB No.
963
964 dddd:address value
965
966 o: digit address
967 )))
968 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
969 |M|MW|MW d|d:0-99999|(((
970 MW0=MB(0~~1)
971
972 MW2=MB(2~~3)
973
974 Address value is a multiple of 2
975 )))
976 |M|MD|MD d|d:0-99999|(((
977 MD0=MB(0~~3)
978
979 MD4=MB(4~~7)
980
981 Address value is a multiple of 4
982 )))
983 |I|IW|IW d|d:0-99999|
984 |Q|QW|QW d|d:0-99999|
985 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
986 nn:0-9999
987
988 dddd:0-9999
989 )))|(((
990 nn:DB No.
991
992 dddd:address value
993 )))
994 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
995 nn:0-9999
996
997 dddd:0-9999
998 )))|(((
999 nn:DB No.
1000
1001 dddd:address value
1002
1003 Address value is a multiple of 2
1004 )))
1005 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1006 nn:0-9999
1007
1008 dddd:0-9999
1009 )))|(((
1010 nn:DB No.
1011
1012 dddd:address value
1013
1014 Address value is a multiple of 4
1015 )))
1016
1017 **Communication Settings**
1018
1019 Enable HMI Ethernet in [Project Settings];
1020
1021 (% style="text-align:center" %)
1022 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1023
1024 Set PLC IP in [Device IP] settings;
1025
1026 (% style="text-align:center" %)
1027 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1028
1029 **✎Note:**
1030
1031 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1032 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1033
1034 **Cable Wiring**
1035
1036 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1037
1038 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1039
1040 Supported Series: Siemens Logo 0BA0 series
1041
1042 **HMI Settings**
1043
1044 (% class="table-bordered" %)
1045 |**Items**|**Settings**|**Note**
1046 |Protocol|Siemens LOGO|
1047 |Connection|Ethernet|
1048 |Port No.|102|
1049 |PLC station No.|2|
1050
1051 **Address List**
1052
1053 (% class="table-bordered" %)
1054 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1055 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1056 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1057 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1058 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1059 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1060 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1061 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1062 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1063 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1064 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1065 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1066 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1067 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1068 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1069 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1070
1071 **PLC Settings in LOGO Software:**
1072
1073 Click [Tools]~-~-[Ethernet Connections],shown as below.
1074
1075 (% style="text-align:center" %)
1076 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1077
1078 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1079
1080 (% style="text-align:center" %)
1081 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1082
1083 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1084
1085 (% style="text-align:center" %)
1086 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1087
1088 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1089
1090 (% style="text-align:center" %)
1091 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1092
1093
1094 (% style="text-align:center" %)
1095 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1096
1097
1098 **HMI Communication Settings**
1099
1100 Set PLC IP in [Device IP] settings;
1101
1102 (% style="text-align:center" %)
1103 [[image:SiemensLOGODeviceIP.png]]
1104
1105 Enable HMI Ethernet in [Project Settings];
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1109
1110 TSAP setting
1111
1112 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1113 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1114 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1115
1116 **✎Note:**
1117
1118 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1119
1120 (% style="text-align:center" %)
1121 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1122
1123
1124 * AI word address and Ibit address are read-only and cannot be written on HMI.
1125 * VW address should be even number.such as VW0, VW2, VW4...
1126 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1127 * Written value of RTC cannot exceed 255.
1128
1129 **Cable Wiring**
1130
1131 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1132
1133 = Create communication with **Mitsubishi PLC** =
1134
1135 == **FX1S, 1N, 2N Series Protocol** ==
1136
1137 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1138
1139 **HMI Settings**
1140
1141 (% class="table-bordered" %)
1142 |**Item**|**Settings**|**Note**
1143 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1144 |Connection|RS422/RS485/RS232|
1145 |Baud rate|9600~~115200|
1146 |Data bit|7/8|
1147 |Parity|EVEN/Odd/None|
1148 |Stop bit|1/2|
1149 |PLC station No.|1~~255|
1150
1151 **Address List**
1152
1153 (% class="table-bordered" %)
1154 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1155 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1156 |Y|Y|Y o|0~~303237|
1157 |M|M|M d|0~~99999|
1158 |T|T|T d|0~~99999|
1159 |C|C|C d|0~~99999|
1160 |S|S|S d|0~~99999|
1161 |SM|SM|SM d|8000~~9999|
1162 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1163 |Y|Y|Y o|0~~303237|
1164 |M|M|M d|0~~99999|
1165 |T|T|T d|0~~99999|
1166 |C|C|C d|0~~199|
1167 |D|D|D d|0~~7999|
1168 |S|S|S d|0~~99999|
1169 |SD|SD|SD d|8000~~9999|
1170
1171 **Cable Wiring**
1172
1173 * **RS485**
1174
1175 (% style="text-align:center" %)
1176 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1177
1178 (% style="text-align:center" %)
1179 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1180
1181 * **RS422**
1182
1183 (% style="text-align:center" %)
1184 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1185
1186 **✎Note:** COM3 only available in PI8000/PI9000 series.
1187
1188 == **FX3U/3G/3GA serial protocol** ==
1189
1190 (% class="wikigeneratedid" %)
1191 **HMI Settings**
1192
1193 |=**Item**|=**Settings**|=**Note**
1194 |Protocol|Mitsubishi FX3U/3G/3GA|
1195 |Connection|RS422|
1196 |Baud rate|9600~~115200|
1197 |Data bit|7/8|
1198 |Parity|EVEN/Odd/None|
1199 |Stop bit|1/2|
1200 |PLC station No.|1~~255|
1201
1202 (% class="wikigeneratedid" %)
1203 **Address List**
1204
1205 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1206 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1207 |Y|Y|Y o|0~~303237|
1208 |M|M|M d|0~~99999|
1209 |T|T|T d|0~~99999|
1210 |C|C|C d|0~~99999|
1211 |S|S|S d|0~~99999|
1212 |SM|SM|SM d|8000~~9999|
1213 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1214 |Y|Y|Y o|0~~303237|
1215 |M|M|M d|0~~99999|
1216 |T|T|T d|0~~99999|
1217 |C|C|C d|0~~199|
1218 |D|D|D d|0~~7999|
1219 |S|S|S d|0~~99999|
1220 |SD|SD|SD d|8000~~9999|
1221
1222 **Configure the communication protocol**
1223
1224 (% style="text-align:center" %)
1225 [[image:image-20220831095222-1.png]]
1226
1227 (% style="text-align:center" %)
1228 [[image:image-20220831095743-2.png]]
1229
1230 **Wiring**
1231
1232 (% style="text-align:center" %)
1233 [[image:image-20220831100333-7.png]]
1234
1235 Pin Definition Diagram
1236
1237 (% style="text-align:center" %)
1238 [[image:image-20220831100314-6.png]]
1239
1240 == **FX5U Ethernet Protocol** ==
1241
1242 Mitsubishi FX5U series PLC
1243
1244 **HMI Settings**
1245
1246 (% class="table-bordered" %)
1247 |**Items**|**Settings**|**Note**
1248 |Protocol|Mitsubishi FX5U|
1249 |Connection|Ethernet|
1250 |Port No.|5002|Must be the same as the PLC setting
1251 |PLC station No.|0|
1252
1253 **Address List**
1254
1255 (% class="table-bordered" %)
1256 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1257 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1258 |Y|Y|Y o|0~~303237|
1259 |M|M|M d|0~~99999|
1260 |B|B|B h|0~~7FFF|
1261 |F|F|F d|0~~32767|
1262 |SB|SB|SB h|0~~7FFF|
1263 |TS|TS|TS d|0~~1023|
1264 |TC|TC|TC d|0~~1023|
1265 |STS|STS|STS d|0~~1023|
1266 |STC|STC|STS d|0~~1023|
1267 |CS|CS|CS d|0~~1023|
1268 |CC|CC|CC d|0~~1023|
1269 |SM|SM|SM d|0~~9999|
1270 |L|L|L d|0~~32767|
1271 |S|S|S d|0~~4095|
1272 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1273 |TN|TN|TN d|0~~1023|
1274 |STN|STN|STN d|0~~1023|
1275 |CN|CN|CN d|0~~1023|
1276 |R|R|R d|0~~32767|
1277 |SW|SW|SW h|0~~7FFF|
1278 |Z|Z|Z d|0~~23|
1279 |D|D|D d|0~~7999|
1280 |SD|SD|SD d|0~~11999|
1281
1282 **PLC Settings (GX Works 3)**
1283
1284 Find the [Ethernet port] in the navigation area.
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1288
1289 Select [Own Node Settings] in the [Setting Item List];
1290
1291 Set [IP Address], [Subnet Mask], [Default Gateway];
1292
1293 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1294
1295 (% style="text-align:center" %)
1296 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1297
1298 Select [SLMP Connection Module] and add into host station as below picture shows;
1299
1300 Set Port number as 5002 (this is necessary settings);
1301
1302 Click [Close with Reflecting the Setting] to save and close window;
1303
1304 (% style="text-align:center" %)
1305 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1306
1307 Click [Apply] to completed Etherenet settings;
1308
1309 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1310
1311 (% style="text-align:center" %)
1312 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1313
1314 **Cable Wiring**
1315
1316 (% style="text-align:center" %)
1317 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1318
1319 == **FX5U Serial Port Protocol** ==
1320
1321 Mitsubishi FX5U series PLC
1322
1323 **HMI Settings**
1324
1325 (% class="table-bordered" %)
1326 |**Item**|**Settings**|**Note**
1327 |Protocol|Mitsubishi FX5U|
1328 |Connection|RS422/RS485|
1329 |Baud rate|9600|
1330 |Data bit|7|
1331 |Parity|Odd|
1332 |Stop bit|1|
1333 |PLC station No.|1~~255|Need to be the same as PLC settings
1334
1335 **Address List**
1336
1337 (% class="table-bordered" %)
1338 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1339 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1340 |Y|Y|Y o|0~~303237|
1341 |M|M|M d|0~~99999|
1342 |B|B|B h|0~~7FFF|
1343 |F|F|F d|0~~32767|
1344 |SB|SB|SB h|0~~7FFF|
1345 |TS|TS|TS d|0~~1023|
1346 |TC|TC|TC d|0~~1023|
1347 |STS|STS|STS d|0~~1023|
1348 |STC|STC|STS d|0~~1023|
1349 |CS|CS|CS d|0~~1023|
1350 |CC|CC|CC d|0~~1023|
1351 |SM|SM|SM d|0~~9999|
1352 |L|L|L d|0~~32767|
1353 |S|S|S d|0~~4095|
1354 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1355 |TN|TN|TN d|0~~1023|
1356 |STN|STN|STN d|0~~1023|
1357 |CN|CN|CN d|0~~1023|
1358 |R|R|R d|0~~32767|
1359 |SW|SW|SW h|0~~7FFF|
1360 |Z|Z|Z d|0~~23|
1361 |D|D|D d|0~~7999|
1362 |SD|SD|SD d|0~~11999|
1363
1364 **PLC Settings (GX Works 3)**
1365
1366 Create a blank FX5U project
1367
1368 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1369
1370 (% style="text-align:center" %)
1371 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1372
1373 Select protocol in the setting item, and set parameters.
1374
1375 (% style="text-align:center" %)
1376 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1377
1378 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1379
1380 (% style="text-align:center" %)
1381 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1382
1383 Click the [Apply] button to finish the setting.
1384
1385 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1386
1387 (% style="text-align:center" %)
1388 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1389
1390 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1391
1392 Done.
1393
1394 **Cable Wiring**
1395
1396 * **RS485**
1397
1398 (% style="text-align:center" %)
1399 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1400
1401 (% style="text-align:center" %)
1402 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1403
1404 * **RS422**
1405
1406 (% style="text-align:center" %)
1407 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1408
1409 **✎Note:** COM3 only available in PI8000/PI9000 series.
1410
1411 == **L02 Serial Protocol** ==
1412
1413 Mitsubishi L02 series CPU built-in serial port.
1414
1415 **HMI Settings**
1416
1417 |=**Item**|=**Settings**|=**Note**
1418 |Protocol|Mitsubishi L02|
1419 |Connection|RS422|
1420 |Baud rate|115200|
1421 |Data bit|8|
1422 |Parity|Odd|
1423 |Stop bit|1|
1424 |PLC station No.|1~~255|Need to be the same as PLC settings
1425
1426 **Address List**
1427
1428 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1429 |Bit|X|X|X h|0~~FFFF|
1430 |Bit|Y|Y|Y h|0~~FFFF|
1431 |Bit|M|M|M d|0~~9999|
1432 |Bit|L|L|L d|0~~9999|
1433 |Bit|F|F|F d|0~~9999|
1434 |Bit|B|B|B h|0~~FFFF|
1435 |Bit|V|V|V d|0~~2047|
1436 |Bit|TC|TC|TC d|0~~9999|
1437 |Bit|SS|SS|SS d|0~~9999|
1438 |Bit|SC|SC|SC d|0~~9999|
1439 |Bit|CS|CS|CS d|0~~9999|
1440 |Bit|CC|CC|CC d|0~~9999|
1441 |Bit|SB|SB|SB h|0~~FFFF|
1442 |Bit|SM|SM|SM d|0~~2047|
1443 |Bit|STS|STS|STS d|0~~1023|
1444 |Bit|S|S|S d|0~~9999|
1445 |Bit|DX|DX|DX h|0~~FFFF|
1446 |Bit|DY|DY|DY h|0~~FFFF|
1447 |Bit|TS|TS|TS d|0~~9999|
1448 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1449 |Word|W|W|W h|0~~FFFF|
1450 |Word|TN|TN|TN d|0~~99999|
1451 |Word|SN|SN|SN d|0~~99999|
1452 |Word|CN|CN|CN d|0~~99999|
1453 |Word|R|R|R d|0~~99999|
1454 |Word|SW|SW|SW h|0~~FFFF|
1455 |Word|Z|Z|Z d|0~~99999|
1456 |Word|ZR|ZR|ZR h|0~~FFFF|
1457 |Word|D|D|D d|0~~99999|
1458
1459 **Communication Settings**
1460
1461 (% style="text-align:center" %)
1462 [[image:image-20220831105732-3.png]]
1463
1464 (% style="text-align:center" %)
1465 [[image:image-20220831110004-5.png]]
1466
1467 **Cable Wiring**
1468
1469 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1470
1471 Pin Definition Diagram
1472
1473 (% style="text-align:center" %)
1474 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1475
1476 == **L02 MELSEC (Ethernet) Protocol** ==
1477
1478 Mitsubishi Q series CPU built-in Ethernet port.
1479
1480 **HMI Settings**
1481
1482 (% class="table-bordered" %)
1483 |**Items**|**Settings**|**Note**
1484 |Protocol|MIT L02 CPU MELSEC|
1485 |Connection|Ethernet|
1486 |Port No.|1025|Must be the same as the PLC setting
1487 |PLC station No.|0|Must be the same as the PLC setting
1488
1489 **Address List**
1490
1491 (% class="table-bordered" %)
1492 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1493 |Bit|X|X|X h|0~~FFFF|
1494 |Bit|Y|Y|Y h|0~~FFFF|
1495 |Bit|M|M|M d|0~~9999|
1496 |Bit|L|L|L d|0~~9999|
1497 |Bit|F|F|F d|0~~9999|
1498 |Bit|B|B|B h|0~~FFFF|
1499 |Bit|V|V|V d|0~~2047|
1500 |Bit|TC|TC|TC d|0~~9999|
1501 |Bit|SS|SS|SS d|0~~9999|
1502 |Bit|SC|SC|SC d|0~~9999|
1503 |Bit|CS|CS|CS d|0~~9999|
1504 |Bit|CC|CC|CC d|0~~9999|
1505 |Bit|SB|SB|SB h|0~~FFFF|
1506 |Bit|SM|SM|SM d|0~~2047|
1507 |Bit|STS|STS|STS d|0~~1023|
1508 |Bit|S|S|S d|0~~9999|
1509 |Bit|DX|DX|DX h|0~~FFFF|
1510 |Bit|DY|DY|DY h|0~~FFFF|
1511 |Bit|TS|TS|TS d|0~~9999|
1512 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1513 |Word|W|W|W h|0~~FFFF|
1514 |Word|TN|TN|TN d|0~~99999|
1515 |Word|SN|SN|SN d|0~~99999|
1516 |Word|CN|CN|CN d|0~~99999|
1517 |Word|R|R|R d|0~~99999|
1518 |Word|SW|SW|SW h|0~~FFFF|
1519 |Word|Z|Z|Z d|0~~99999|
1520 |Word|ZR|ZR|ZR h|0~~FFFF|
1521 |Word|D|D|D d|0~~99999|
1522
1523 **Communication Settings**
1524
1525 Enable HMI Ethernet in [Project Settings];
1526
1527 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1528
1529 Set PLC IP in [Device IP] settings;
1530
1531 (% style="text-align:center" %)
1532 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1533
1534 **PLC Settings (GX Works2 )**
1535
1536 Create a project
1537
1538 Set PLC IP, subnet mask and gateway;
1539
1540 Select [Binary Code] as communication data code;
1541
1542 (% style="text-align:center" %)
1543 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1544
1545 Set PLC port number, for example 1025
1546
1547 (% style="text-align:center" %)
1548 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1549
1550 Save settings;
1551
1552 Download project into PLC device;
1553
1554 Restart PLC device;
1555
1556 **Cable Wiring**
1557
1558 (% style="text-align:center" %)
1559 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1560
1561 == **QJ71E71 MELSEC Protocol** ==
1562
1563 Mitsubishi QJ71E71 Ethernet communication module;
1564
1565 **HMI Settings**
1566
1567 (% class="table-bordered" %)
1568 |**Items**|**Settings**|**Note**
1569 |Protocol|MIT QJ71E71 MELSEC|
1570 |Connection|Ethernet|
1571 |Port No.|1025|Must be the same as the PLC setting
1572 |PLC station No.|0|Must be the same as the PLC setting
1573
1574 **Address List**
1575
1576 (% class="table-bordered" %)
1577 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1578 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1579 |Y|Y|Y h|0~~1FFF|
1580 |M|M|M d|0~~99999|
1581 |L|L|L d|0~~8191|
1582 |F|F|F d|0~~2047|
1583 |B|B|B h|0~~1FFF|
1584 |V|V|V d|0~~2047|
1585 |TS|TS|TS d|0~~2047|
1586 |TC|TC|TC d|0~~2047|
1587 |SS|SS|SS d|0~~2047|
1588 |SC|SC|SC d|0~~2047|
1589 |CS|CS|CS d|0~~1023|
1590 |CC|CC|CC d|0~~1023|
1591 |SB|SB|SB h|0~~7FF|
1592 |S|S|S d|0~~8191|
1593 |DX|DX|DX h|0~~1FFF|
1594 |DY|DY|DY h|0~~1FFF|
1595 |SM|SM|SM d|8000~~9999|
1596 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1597 |D|D|D d|0~~12287|
1598 |W|W|W h|0~~1FFF|
1599 |TN|TN|TN d|0~~2047|
1600 |SN|SN|SN d|0~~2047|
1601 |CN|CN|CN d|0~~1023|
1602 |R|R|R d|0~~32767|
1603 |SW|SW|SW h|0~~7FF|
1604 |Z|Z|Z d|0~~15|
1605 |ZR|ZR|ZR h|0~~FE7FF|
1606
1607 **HMI Communication Settings**
1608
1609 1) Enable HMI Ethernet in [Project Settings];
1610
1611 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1612
1613 2) Set PLC IP in [Device IP] settings;
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1617
1618 **PLC Settings(GX Works2)**
1619
1620 * Click [Ethernet/CC IE/MELSECNET];
1621 * Please select [Ethernet] as network type;
1622 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1623 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1624 * Click [Operation setting] to set IP;
1625 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1626 * Set protocol: TCP;
1627 * Set [unpassive] in [Open system];
1628 * Set [receive] in [Fixed buffer];
1629 * Set [procedure Exist] in [Fixed buffer communication];
1630 * Disable [Pairing open];
1631 * Set [No confirm] in [Existence confirmation];
1632 * Host station port number: 1025;
1633 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1634 * Download project into PLC and restart it
1635
1636 **Cable Wiring**
1637
1638 (% style="text-align:center" %)
1639 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1640
1641 = Create communication with **Delta PLC** =
1642
1643 == **DVP serial protocol** ==
1644
1645 (% class="wikigeneratedid" %)
1646 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1647
1648 **1)HMI Settings**
1649
1650 |**Item**|**Settings**|**Note**
1651 |Protocol|DELTA DVP Series|
1652 |Connection|RS485|
1653 |Baud rate|9600|
1654 |Data bit|7|
1655 |Parity|Even|
1656 |Stop bit|1|
1657 |PLC station No.|1~~255|Need to be the same as PLC settings
1658
1659 **2)Address List**
1660
1661 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1662 |Bit|X|X|X d|0~~303237|
1663 |Bit|Y|Y|Y d|0~~303237|
1664 |Bit|M|M|M d|0~~99999|
1665 |Bit|T|T|T d|0~~99999|
1666 |Bit|C|C|T d|0~~99999|
1667 |Bit|S|S|T d|0~~99999|
1668 |Word|D|D|D d|0~~99999|
1669 |Word|T|T|T d|0~~99999|
1670 |Word|C|C|C d|0~~99999|
1671
1672 (% class="wikigeneratedid" %)
1673 **3)Configure the communication protocol**
1674
1675 (% class="wikigeneratedid" %)
1676 [[image:image-20220829152327-6.png]]
1677
1678 (% class="wikigeneratedid" %)
1679 [[image:image-20220829152016-3.png]]
1680
1681 (% class="wikigeneratedid" %)
1682 **4)Cable Wiring**
1683
1684 (% class="wikigeneratedid" id="H" %)
1685 [[image:image-20220829152610-7.png]]
1686
1687 (% class="wikigeneratedid" id="H" %)
1688 [[image:image-20220829152102-5.png]]
1689
1690
1691 == **DVP Ethernet Protocol** ==
1692
1693 (% class="wikigeneratedid" %)
1694 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1695
1696 **1)HMI Settings**
1697
1698 |**Items**|**Settings**|**Note**
1699 |Protocol|DELTA DVP Modbus TCP|
1700 |Connection|Ethernet|
1701 |Port No.|201|Must be the same as the PLC setting
1702 |PLC station No.|0|Must be the same as the PLC setting
1703
1704 **2)Address List**
1705
1706 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1707 |Bit|X|X|X o|0~~377|
1708 |Bit|Y|Y|Y o|0~~377|
1709 |Bit|M0|M0|M0 d|0~~1535|
1710 |Bit|M1|M1|M1 d|1536~~4095|
1711 |Bit|T|T|T d|0~~255|
1712 |Bit|C|C|C d|0~~255|
1713 |Bit|S|S|S d|0~~1023|
1714 |Word|D0|D0|D0 d|0~~4095|
1715 |Word|D1|D1|D1 d|4096~~11999|(((
1716
1717 )))
1718 |Word|T|T|T d|0~~255|
1719 |Word|C|C|C d|0~~199|(((
1720
1721 )))
1722
1723 (% class="wikigeneratedid" %)
1724 **3)Configure the communication protocol**
1725
1726 [[image:image-20220829155452-1.png]]
1727
1728 [[image:image-20220829162116-2.png]]
1729
1730 **4)Cable Wiring**
1731
1732 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1733
1734 == **AS serial protocol** ==
1735
1736 **1)HMI Settings**
1737
1738 |**Item**|**Settings**|**Note**
1739 |Protocol|DELTA AS300 MODBUS RTU|
1740 |Connection|RS485|
1741 |Baud rate|9600|
1742 |Data bit|8|
1743 |Parity|NONE|
1744 |Stop bit|1|
1745 |PLC station No.|1|
1746
1747 **2)Address List**
1748
1749
1750 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1751 |Bit|X|X|X o|0~~63|
1752 |Bit|Y|Y|Y o|0~~63|
1753 |Bit|D|D|D d|0~~29999|
1754 |Bit|M|M|M d|0~~8191|
1755 |Bit|SM|SM|SM d|0~~4095|
1756 |Bit|S|S|S d|0~~2047|
1757 |Bit|T|T|T d|0~~511|
1758 |Bit|C|C|C d|0~~511|
1759 |Bit|HC|HC|HC d|0~~255|
1760 |Word|X|X|X o|0~~63|
1761 |Word|Y|Y|Y o|0~~63|
1762 |Word|SR|SR|SR d|0~~2047|
1763 |Word|D|D|D d|0~~29999|
1764 |Word|T|T|T d|0~~511|
1765 |Word|C|C|C d|0~~511|
1766 |Word|E|E|E d|0~~9|
1767
1768 **3)Configure the communication protocol**
1769
1770 [[image:image-20220830094600-1.png]]
1771
1772 [[image:image-20220830094657-2.png]]
1773
1774 **4)Cable Wiring**
1775
1776 Figure
1777
1778 [[image:image-20220830141138-1.png]]
1779
1780 Pin Definition Diagram
1781
1782 [[image:image-20220830095131-1.png]]
1783
1784 == **AS Ethernet Protocol** ==
1785
1786 **1)HMI Settings**
1787
1788
1789 |=**Items**|=**Settings**|=**Note**
1790 |Protocol|DELTA AS300 MODBUS TCP|
1791 |Connection|Ethernet|
1792 |Port No.|502|
1793 |Device No.|1|
1794 |HMI No.|0|
1795
1796 **2)Address List**
1797
1798
1799 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1800 |Bit|X|X|X d|0~~63|
1801 |Bit|Y|Y|Y d|0~~63|
1802 |Bit|D|D|D d|0~~29999|
1803 |Bit|M|M|M d|0~~8191|
1804 |Bit|SM|SM|SM d|0~~4095|
1805 |Bit|S|S|S h|0~~2047|
1806 |Bit|T|T|T d|0~~511|
1807 |Bit|C|C|C d|0~~511|
1808 |Bit|HC|HC|HC d|0~~255|
1809 |Word|X|X|X h|0~~63|
1810 |Word|Y|Y|Y d|0~~63|
1811 |Word|SR|SR|SR d|0~~2047|
1812 |Word|D|D|D d|0~~29999|
1813 |Word|T|T|T d|0~~511|
1814 |Word|C|C|C h|0~~511|
1815 |Word|E|E|E d|0~~9|
1816
1817 **3)Configure the communication protocol**
1818
1819 [[image:image-20220830140537-1.png]]
1820
1821 [[image:image-20220830140629-2.png]]
1822
1823 **4)Cable Wiring**
1824
1825 Figure
1826
1827 [[image:image-20220830094929-1.png]]
1828
1829 Pin Definition Diagram
1830
1831 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1832
1833 = Create communication with **Omron** PLC =
1834
1835 == **CJ TCP FINS Ethemet  Protocol** ==
1836
1837 Supported device:CJ series
1838
1839 **1)HMI Settings**
1840
1841 |=**Items**|=**Settings**|=**Note**
1842 |Protocol|OMRON CJ TCP FINS Ethemet|
1843 |Connection|Ethernet|
1844 |Port No.|9600|
1845 |Device No.|0|
1846 |HMI No.|0|(((
1847
1848 )))
1849
1850 **2)Address List**
1851
1852 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1853 |Bit|CIO|CIO|CIO d|0~~99999|
1854 |Bit|W|W|W d|0~~99999|
1855 |Bit|D|D|D d|0~~99999|
1856 |Bit|H|H|H d|0~~99999|
1857 |Bit|A|A|A d|0~~99999|
1858 |Bit|T|T|T h|0~~99999|
1859 |Bit|CF|CF|CF d|0~~99999|
1860 |Bit|FF|FF|FF d|0~~99999|
1861 |Bit|C|C|C d|0~~99999|
1862 |Bit|EM0|EM0|EM0 d|0~~99999|
1863 |Bit|EM1|EM1|EM1 d|0~~99999|
1864 |Bit|EM2|EM2|EM2 d|0~~99999|
1865 |Bit|EM3|EM3|EM3 d|0~~99999|
1866 |Bit|EM4|EM4|EM4 d|0~~99999|
1867 |Bit|EM5|EM5|EM5 h|0~~99999|
1868 |Bit|EM6|EM6|EM6 d|0~~99999|
1869 |Bit|EM7|EM7|EM7 d|0~~99999|
1870 |Bit|EM8|EM8|EM8 d|0~~99999|
1871 |Bit|EM9|EM9|EM9 d|0~~99999|
1872 |Bit|EMA|EMA|EMA d|0~~99999|
1873 |Bit|EMB|EMB|EMB d|0~~99999|
1874 |Bit|EMC|EMC|EMC d|0~~99999|
1875 |Bit|Lamp|Lamp|Lamp d|0~~0|
1876 |Word|CIO|CIO|CIO d|0~~99999|
1877 |Word|W|W|W d|0~~99999|
1878 |Word|D|D|D d|0~~99999|
1879 |Word|H|H|H d|0~~99999|
1880 |Word|A|A|A d|0~~99999|
1881 |Word|T|T|T h|0~~99999|
1882 |Word|CF|CF|CF d|0~~99999|
1883 |Word|FF|FF|FF d|0~~99999|
1884 |Word|C|C|C d|0~~99999|
1885 |Word|EM0|EM0|EM0 d|0~~99999|
1886 |Word|EM1|EM1|EM1 d|0~~99999|
1887 |Word|EM2|EM2|EM2 d|0~~99999|
1888 |Word|EM3|EM3|EM3 d|0~~99999|
1889 |Word|EM4|EM4|EM4 d|0~~99999|
1890 |Word|EM5|EM5|EM5 h|0~~99999|
1891 |Word|EM6|EM6|EM6 d|0~~99999|
1892 |Word|EM7|EM7|EM7 d|0~~99999|
1893 |Word|EM8|EM8|EM8 d|0~~99999|
1894 |Word|EM9|EM9|EM9 d|0~~99999|
1895 |Word|EMA|EMA|EMA d|0~~99999|
1896 |Word|EMB|EMB|EMB d|0~~99999|
1897 |Word|EMC|EMC|EMC d|0~~99999|
1898 |Word|IR|IR|IR d|0~~99999|
1899 |Word|DR|DR|DR d|0~~99999|
1900
1901 **3)Configure the communication protocol**
1902
1903 [[image:image-20220830143348-1.png]]
1904
1905 [[image:image-20220830143511-2.png]]
1906
1907 **4)Cable Wiring**
1908
1909 Pin Definition Diagram
1910
1911 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1912
1913 == **CP1E/CP1H serial protocol** ==
1914
1915 Supported device: OMRON CS1(CP1E/CP1H)
1916
1917 **1)HMI Settings**
1918
1919
1920 |**Items**|**Settings**|**Note**
1921 |Protocol|OMRON CS1(CP1E/CP1H)|
1922 |Connection|RS232 (9600, 2, 7, EVEN)|
1923 |Port No.|None|
1924 |PLC station No.|0|
1925
1926 **2)Address List**
1927
1928 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1929 |Bit|CIO|CIO|CIO d|0~~99999|
1930 |Bit|W|W|W d|0~~99999|
1931 |Bit|D|D|D d|0~~99999|
1932 |Bit|H|H|H d|0~~99999|
1933 |Bit|A|A|A d|0~~99999|
1934 |Bit|TF|T|T h|0~~99999|
1935 |Bit|CF|CF|CF d|0~~99999|
1936 |Bit|T|FF|FF d|0~~99999|
1937 |Bit|C|C|C d|0~~99999|
1938 |Bit|EM0|EM0|EM0 d|0~~99999|
1939 |Bit|EM1|EM1|EM1 d|0~~99999|
1940 |Bit|EM2|EM2|EM2 d|0~~99999|
1941 |Bit|EM3|EM3|EM3 d|0~~99999|
1942 |Bit|EM4|EM4|EM4 d|0~~99999|
1943 |Bit|EM5|EM5|EM5 h|0~~99999|
1944 |Bit|EM6|EM6|EM6 d|0~~99999|
1945 |Bit|EM7|EM7|EM7 d|0~~99999|
1946 |Bit|EM8|EM8|EM8 d|0~~99999|
1947 |Bit|EM9|EM9|EM9 d|0~~99999|
1948 |Bit|EMA|EMA|EMA d|0~~99999|
1949 |Bit|EMB|EMB|EMB d|0~~99999|
1950 |Bit|EMC|EMC|EMC d|0~~99999|
1951 |Word|CIO|CIO|CIO d|0~~99999|
1952 |Word|W|W|W d|0~~99999|
1953 |Word|D|D|D d|0~~99999|
1954 |Word|H|H|H d|0~~99999|
1955 |Word|A|A|A d|0~~99999|
1956 |Word|T|T|T h|0~~99999|
1957 |Word|CIO|CF|CF d|0~~99999|
1958 |Word|C|C|C d|0~~99999|
1959 |Word|EM0|EM0|EM0 d|0~~99999|
1960 |Word|EM1|EM1|EM1 d|0~~99999|
1961 |Word|EM2|EM2|EM2 d|0~~99999|
1962 |Word|EM3|EM3|EM3 d|0~~99999|
1963 |Word|EM4|EM4|EM4 d|0~~99999|
1964 |Word|EM5|EM5|EM5 h|0~~99999|
1965 |Word|EM6|EM6|EM6 d|0~~99999|
1966 |Word|EM7|EM7|EM7 d|0~~99999|
1967 |Word|EM8|EM8|EM8 d|0~~99999|
1968 |Word|EM9|EM9|EM9 d|0~~99999|
1969 |Word|EMA|EMA|EMA d|0~~99999|
1970 |Word|EMB|EMB|EMB d|0~~99999|
1971 |Word|EMC|EMC|EMC d|0~~99999|
1972 |Word|IR|IR|IR d|0~~99999|
1973 |Word|DR|DR|DR d|0~~99999|
1974
1975 **3)Configure the communication protocol**
1976
1977 [[image:image-20220902153118-1.png]]
1978
1979
1980 [[image:image-20220902151322-2.png]]
1981
1982 **4)Cable Wiring**
1983
1984 Figure
1985
1986 [[image:image-20220902153949-2.png]]
1987
1988 Pin Definition Diagram
1989
1990 [[image:image-20220902154056-3.png]]
1991
1992 == **EC55 Protocol** ==
1993
1994 Supported device: EC55 temperature instrument
1995
1996 **1)HMI Settings**
1997
1998 |**Items**|**Settings**|**Note**
1999 |Protocol|Omron EC55|
2000 |Connection|RS485 (9600, 2, 7, EVEN)|
2001 |Port No.|None|
2002 |PLC station No.|0|
2003
2004 **2)Address List**
2005
2006 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2007 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2008 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2009 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2010 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2011 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2012 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2013 |CP|-|0-6|Read controller intrinsic property
2014 |CS|-|0-2|Read controller states
2015 |CA|-|0-17|Action command
2016
2017 **3)Device Settings**
2018
2019 Omron E5CC PLC configuration
2020
2021 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2022
2023 (% style="text-align:center" %)
2024 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2025
2026 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2027
2028 (% style="text-align:center" %)
2029 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2030
2031 **✎Note:** The communication settings for HMI should be consistent with this setting.
2032
2033 **Cable Wiring**
2034
2035 (% style="text-align:center" %)
2036 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2037
2038 (% style="text-align:center" %)
2039 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2040
2041 **✎Note:**
2042
2043 * COM3 only available in PI8000/PI9000 series.
2044 * CA address could not support continuous writing function;
2045 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2046 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2047 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2048 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2049 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2050 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2051 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2052
2053 == **EtherNet/IP NX series Protocol** ==
2054
2055 Supported series: Omron NX/NJ series
2056
2057 **HMI Setting**
2058
2059 |**Items**|**Settings**|**Note**
2060 |Protocol|Omron NX Ethernet/IP|
2061 |Connection|Ethernet|
2062 |Port No.|44818|
2063 |PLC station No.|1|
2064
2065 **Instruction**
2066
2067 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2068
2069 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2070
2071 (% style="text-align:center" %)
2072 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2073
2074 **Export labels from Sysmac Studio**
2075
2076 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2077
2078 (% style="text-align:center" %)
2079 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2080
2081 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2082
2083 Click [Label manage];
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2087
2088 Click [Import labels] and then select the file exported in step 1;
2089
2090 (% style="text-align:center" %)
2091 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2092
2093 The Import Status field shows the result, click [OK] to finish importing address labels;
2094
2095 (% style="text-align:center" %)
2096 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2097
2098 **Communication Settings**
2099
2100 Enable HMI Ethernet in [Project Settings];
2101
2102 (% style="text-align:center" %)
2103 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2104
2105 Set PLC IP in [Device IP] settings;
2106
2107 (% style="text-align:center" %)
2108 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2109
2110 (% style="text-align:center" %)
2111 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2112
2113 **Cable Wiring**
2114
2115 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2116
2117 = Create communication with Xinje** PLC** =
2118
2119 == **XC serial protocol** ==
2120
2121 **1)HMI Settings**
2122
2123 |**Item**|**Settings**|**Note**
2124 |Protocol|XINJE XC MODBUS|
2125 |Connection|RS232|
2126 |Baud rate|19200|
2127 |Data bit|8|
2128 |Parity|EVEN|
2129 |Stop bit|1|
2130 |PLC station No.|1|
2131
2132 **2)Address List**
2133
2134 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2135 |Bit|M|M|M d|0~~8511|
2136 |Bit|X|X|X o|0~~1747|
2137 |Bit|Y|Y|Y o|0~~1747|
2138 |Bit|S|S|S d|0~~1023|
2139 |Bit|T|T|T d|0~~4095|
2140 |Bit|C|C|C d|0~~634|
2141 |Word|D|D|D d|0~~8511|
2142 |Word|TD|TD|TD d|0~~618|
2143 |Word|CD|CD|CD d|0~~634|
2144 |Word|FD|FD|FD d|0~~8511|
2145
2146 **3)Configure the communication protocol**
2147
2148 [[image:image-20220830154105-1.png]]
2149
2150 [[image:image-20220830154159-3.png]]
2151
2152 **4)Cable Wiring**
2153
2154 Figure
2155
2156 [[image:image-20220830155728-4.png]]
2157
2158 Pin Definition Diagram
2159
2160 [[image:image-20220830154131-2.png]]
2161
2162 == **XD serial protocol** ==
2163
2164 **1)HMI Settings**
2165
2166 Supported Series: Delta Xinjie XD/XE Series PLC
2167
2168 |**Item**|**Settings**|**Note**
2169 |Protocol|XINJE XD/XC MODBUS|
2170 |Connection|RS232|
2171 |Baud rate|19200|
2172 |Data bit|8|
2173 |Parity|EVEN|
2174 |Stop bit|1|
2175 |PLC station No.|1|
2176
2177 **2)Address List**
2178
2179 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2180 |Bit|M|M|M d|0~~74999|
2181 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2182 |Bit|X2xx|X2xx|X2xx o|0~~277|
2183 |Bit|X|X|X o|0~~77|
2184 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2185 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2186 |Bit|Y|Y|Y o|0~~4095|
2187 |Bit|SM|SM|SM d|0~~4999|(((
2188
2189 )))
2190 |Bit|T|T|T d|0~~4999|
2191 |Bit|C|C|C d|0~~4999|
2192 |Bit|ET|ET|ET d|0~~31|
2193 |Bit|SE|SE|SE d|0~~31|
2194 |Bit|HM|HM|HM d|0~~11999|
2195 |Bit|HSC|HSC|HSC d|0~~39|
2196 |Bit|HS|HS|HS d|0~~999|
2197 |Bit|HT|HT|HT d|0~~1999|
2198 |Bit|HC|HC|HC d|0~~1999|
2199 |Bit|S|S|S d|0~~7999|
2200 |Word|D|D|D d|0~~69999|
2201 |Word|ID|ID|ID d|0~~99|
2202 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2203 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2204 |Word|QD|QD|QD d|0~~99|
2205 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2206 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2207 |Word|SD|SD|SD d|0~~4999|
2208 |Word|TD|TD|TD d|0~~575|
2209 |Word|CD|CD|CD d|0~~575|
2210 |Word|ETD|ETD|ETD d|0~~31|
2211 |Word|HD|HD|HD d|0~~24999|
2212 |Word|HSD|HSD|HSD d|0~~1023|
2213 |Word|HTD|HTD|HTD d|0~~95|
2214 |Word|HCD|HCD|HCD d|0~~95|
2215 |Word|HSCD|HSCD|HSCD d|0~~31|
2216 |Word|FD|FD|FD d|0~~8191|
2217 |Word|SFD|SFD|SFD d|0~~5999|
2218 |Word|FS|FS|FS d|0~~47|
2219
2220 **3)Configure the communication protocol**
2221
2222 [[image:image-20220830160042-1.png]]
2223
2224 [[image:image-20220830160129-2.png]]
2225
2226 **4)Cable Wiring**
2227
2228 Figure
2229
2230 [[image:image-20220830160257-4.png]]
2231
2232 Pin Definition Diagram
2233
2234 [[image:image-20220830160232-3.png]]
2235
2236 = Create communication with Inovance** PLC** =
2237
2238 == **H3U serial protocol** ==
2239
2240 **1)HMI Settings**
2241
2242 |**Item**|**Settings**|**Note**
2243 |Protocol|INOVANCE H3U PLC|
2244 |Connection|RS422|
2245 |Baud rate|9600|
2246 |Data bit|7|
2247 |Parity|EVEN|
2248 |Stop bit|1|
2249 |PLC station No.|0|
2250
2251 **2)Address List**
2252
2253 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2254 |Bit|X|X|X o|0~~303237|
2255 |Bit|Y|Y|Y o|0~~303237|
2256 |Bit|M|M|M d|0~~99999|
2257 |Bit|T|T|T d|0~~99999|
2258 |Bit|C|C|C d|0~~99999|
2259 |Bit|SM|SM|SM d|8000~~999|
2260 |Bit|S|T|S d|0~~99999|
2261 |Bit|Lamp|Lamp|Lamp d|0~~0|
2262 |Word|X|X|X o|0~~303237|
2263 |Word|Y|Y|Y o|0~~303237|
2264 |Word|M|M|M d|0~~99999|
2265 |Word|T|T|T d|0~~99999|
2266 |Word|C|C|C d|0~~199|
2267 |Word|D|D|D d|0~~7999|
2268 |Word|S|S|S d|0~~99999|
2269 |Word|SD|SD|SD d|8000~~9999|
2270 |Word|R|R|R d|0~~32767|
2271
2272 **3)Configure the communication protocol**
2273
2274 [[image:image-20220830170114-4.png]]
2275
2276 [[image:image-20220830170017-3.png]]
2277
2278
2279
2280 **4)Cable Wiring**
2281
2282 Figure
2283
2284 [[image:image-20220830165930-1.png]]
2285
2286
2287 Pin Definition Diagram
2288
2289 [[image:image-20220830165947-2.png]]
2290
2291 = Create communication with Panasonic** PLC** =
2292
2293 == **FP serial protocol** ==
2294
2295 **1)HMI Settings**
2296
2297 |**Item**|**Settings**|**Note**
2298 |Protocol|Panasonic FP MFWTOCOL|
2299 |Connection|RS232|
2300 |Baud rate|9600|
2301 |Data bit|8|
2302 |Parity|ODD|
2303 |Stop bit|1|
2304 |PLC station No.|1|
2305
2306 **2)Address List**
2307
2308 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2309 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2310 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2311 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2312 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2313 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2314 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2315 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2316 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2317 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2318 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2319 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2320 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2321 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2322 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2323 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2324
2325 **3)Configure the communication protocol**
2326
2327 [[image:image-20220830171050-1.png]]
2328
2329 [[image:image-20220830171126-2.png]]
2330
2331 **4)Cable Wiring**
2332
2333 Figure
2334
2335 [[image:image-20220830171328-4.png]]
2336
2337 Pin Definition Diagram
2338
2339 [[image:image-20220830171146-3.png]]
2340
2341 = Create communication with LS** PLC** =
2342
2343 == **XBC serial protocol** ==
2344
2345 **1)HMI Settings**
2346
2347 |**Item**|**Settings**|**Note**
2348 |Protocol|LS XBC CNet|
2349 |Connection|RS232|
2350 |Baud rate|115200|
2351 |Data bit|8|
2352 |Parity|NONE|
2353 |Stop bit|1|
2354 |PLC station No.|1|
2355
2356 **2)Address List**
2357
2358 |**Type**|(% style="width:398px" %)**Device registers**|(% style="width:331px" %)**HMI registers**|**Format**|**Range**|**Note**
2359 |Bit|(% style="width:398px" %)P|(% style="width:331px" %)P|P d|0~~2047|
2360 |Bit|(% style="width:398px" %)M|(% style="width:331px" %)M|M d|0~~2047|
2361 |Bit|(% style="width:398px" %)L|(% style="width:331px" %)L|L d|0~~11263|
2362 |Bit|(% style="width:398px" %)K|(% style="width:331px" %)K|K d|0~~16183|
2363 |Bit|(% style="width:398px" %)F|(% style="width:331px" %)F|F d|0~~2047|
2364 |Bit|(% style="width:398px" %)D|(% style="width:331px" %)D|D d|0~~32767|
2365 |Bit|(% style="width:398px" %)R|(% style="width:331px" %)R|R d|0~~32767|
2366 |Bit|(% style="width:398px" %)U|(% style="width:331px" %)U|U d|0~~4095|
2367 |Word|(% style="width:398px" %)P|(% style="width:331px" %)P|P d|0~~2047|
2368 |Word|(% style="width:398px" %)M|(% style="width:331px" %)M|M d|0~~2047|
2369 |Word|(% style="width:398px" %)L|(% style="width:331px" %)L|L d|0~~11263|
2370 |Word|(% style="width:398px" %)K|(% style="width:331px" %)K|K d|0~~16183|
2371 |Word|(% style="width:398px" %)F|(% style="width:331px" %)F|F d|0~~2047|
2372 |Word|(% style="width:398px" %)C|(% style="width:331px" %)C|C d|0~~2047|
2373 |Word|(% style="width:398px" %)T|(% style="width:331px" %)T|T d|0~~2047|
2374 |Word|(% style="width:398px" %)D|(% style="width:331px" %)D|D d|0~~32767|
2375 |Word|(% style="width:398px" %)N|(% style="width:331px" %)N|N d|0~~21503|
2376 |Word|(% style="width:398px" %)R|(% style="width:331px" %)R|R d|0~~32767|
2377 |Word|(% style="width:398px" %)U|(% style="width:331px" %)U|U d|0~~4095|
2378 |Word|(% style="width:398px" %)Z|(% style="width:398px" %)Z|Z d|0~~127|
2379 |Word|(% style="width:398px" %)S|(% style="width:331px" %)S|S d|0~~127|
2380
2381 **3)Configure the communication protocol**
2382
2383 [[image:image-20220831170807-1.png]]
2384
2385 [[image:image-20220830174733-2.png]]
2386
2387
2388
2389 **4)Cable Wiring**
2390
2391 Figure
2392
2393 [[image:image-20220830174659-1.png]]
2394
2395 Pin Definition Diagram
2396
2397 [[image:image-20220830173402-8.png]]
2398
2399 == **XGK FEnet Ethernet protocol** ==
2400
2401 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2402
2403 **HMI Settings**
2404
2405 |**Items**|**Settings**|**Note**
2406 |Protocol|LG XGK FEnet(Ethernet)|
2407 |Connection|Ethernet|
2408 |Port No.|2004|
2409
2410 **Address List**
2411
2412 |**Type**|**Register**|**Range**|**Format**|**Note**
2413 |(% rowspan="14" %)Word|P|0~~2047|P d|
2414 |M|0~~2047|M d|
2415 |K|0~~2047|K d|
2416 |F|0~~2047|F d|
2417 |T|0~~2047|T d|
2418 |C|0~~2047|C d|
2419 |Z|0~~127|Z d|
2420 |S|0~~127|S d|
2421 |L|0~~11263|L d|
2422 |N|0~~21503|N d|
2423 |D|0~~32767|D d|
2424 |R|0~~32767|R d|
2425 |ZR|0~~65535|ZR d|
2426 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2427
2428 **✎Note:**
2429
2430 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2431 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2432 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2433
2434 **Communication settings in HMI**
2435
2436 Enable HMI Ethernet in [Project Settings];
2437
2438 (% style="text-align:center" %)
2439 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2440
2441 Set PLC IP in [Device IP] settings;
2442
2443 (% style="text-align:center" %)
2444 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2445
2446 **Cable Wiring**
2447
2448 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2449
2450 = Create communication with **SHIMADEN PLC** =
2451
2452 == **FP23 series protocol** ==
2453
2454 Supported series: SHIMADEN FP23 series
2455
2456 **HMI Setting**
2457
2458 |**Items**|**Settings**|**Note**
2459 |Protocol|SHIMADEN FP23 series|
2460 |Connection|RS485 (9600, 1, 7, EVEN)|
2461 |Port No.|None|
2462 |PLC station No.|0|
2463
2464 **Address List**
2465
2466 |**Device address**|**HMI register**|**Address range**|**Type**
2467 |0040-0043(HEX)|FP040|100064-200067|Read only
2468 |0100-010B(HEX)|FP100|100256-200267|Read only
2469 |0110-0142(HEX)|FP110|100272-200322|Read only
2470 |0182-0252(HEX)|FP182|100386-200594|Write only
2471 |0280-0281(HEX)|FP280|100640-200641|Read only
2472 |0300-030B(HEX)|FP300|100768-200779|Read and write
2473 |0380-039F(HEX)|FP380|100896-200927|Read and write
2474 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2475 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2476 |0600-0670(HEX)|FP600|101536-201814|Read and write
2477 |0720-0738(HEX)|FP720|101824-201848|Read and write
2478 |0800-083F(HEX)|FP800|102048-202111|Read and write
2479 |0900-0952(HEX)|FP900|102304-202386|Read and write
2480 | |Ctrl|0-2|
2481
2482 **✎Note:**
2483
2484 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2485 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2486 * The Ctrl register is used to store the control group number and BCC check mode.
2487
2488 **Ctrl Register Description**
2489
2490 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2491 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2492 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2493 * Ctrl3 reserved
2494
2495 **✎Note:**
2496
2497 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2498
2499 **Cable Wiring**
2500
2501 (% style="text-align:center" %)
2502 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2503
2504 (% style="text-align:center" %)
2505 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2506
2507 **✎Note:** COM3 only available in PI8000/PI9000 series.
2508
2509 == **SR90 protocol** ==
2510
2511 Supported series: SHIMADEN SR90 series
2512
2513 **HMI Setting**
2514
2515 |**Items**|**Settings**|**Note**
2516 |Protocol|SHIMADEN SR90 protocol|
2517 |Connection|RS485 (1200, 1, 7, EVEN)|
2518 |Port No.|None|
2519 |PLC station No.|0|
2520
2521 **Address List**
2522
2523 |**Device address**|**HMI register**|**Address range**|**Type**
2524 |0040-0043 (HEX)|SR040|100064-100067|Read only
2525 |0100-010A(HEX)|SR0100|100256-100266|Read only
2526 |0182-018C(HEX)|SR0182|100386-100396|Write only
2527 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2528 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2529 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2530 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2531 | |Ctrl|0-2|~-~-
2532
2533 **✎Note:**
2534
2535 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2536 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2537 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2538
2539 **Ctrl Register Description**
2540
2541 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2542 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2543 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2544 * Ctrl3 reserved
2545
2546 **✎Note:**
2547
2548 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2549
2550 **Cable Wiring**
2551
2552 (% style="text-align:center" %)
2553 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2554
2555 (% style="text-align:center" %)
2556 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2557
2558 **✎Note:** COM3 only available in PI8000/PI9000 series.
2559
2560 == **MR13 series(standard protocol)** ==
2561
2562 Supported series: SHIMADEN MR13 series
2563
2564 **HMI Setting**
2565
2566 |**Items**|**Settings**|**Note**
2567 |Protocol|SHIMADEN standard protocol|
2568 |Connection|RS485 (1200, 1, 7, EVEN)|
2569 |Port No.|None|
2570 |PLC station No.|0|
2571
2572 **Address List**
2573
2574 |**Device address**|**HMI register**|**Address range**|**Type**
2575 |0100-010B(HEX)|MR100|100256-300267|Read only
2576 |0111-0126(HEX)|MR111|100273-300294|Read only
2577 |0184-0192(HEX)|MR184|100388-300402|Write only
2578 |0280-0282(HEX)|MR280|100640-300642|Read only
2579 |0300-030B(HEX)|MR300|100768-300779|Read/write
2580 |0314-0317(HEX)|MR314|100788-300791|Read/write
2581 |031A(HEX)|MR31A|100794-300794|Read/write
2582 |0320-0321(HEX)|MR320|100800-300801|Read/write
2583 |0400-0504(HEX)|MR400|101024-301284|Read/write
2584 |0506(HEX)|MR506|101286-301286|Read/write
2585 |0510-0514(HEX)|MR510|101296-301300|Read/write
2586 |0516-0524(HEX)|MR516|101302-301316|Read/write
2587 |0526(HEX)|MR526|101318-301318|Read/write
2588 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2589 |~-~-|Ctrl|0-2|~-~-
2590
2591 **✎Note:**
2592
2593 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2594 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2595 * The Ctrl register is used to store the control group number and BCC check mode.
2596
2597 **Ctrl Register Description**
2598
2599 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2600 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2601 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2602 * Ctrl3 reserved
2603
2604 **✎Note:**
2605
2606 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2607
2608 **Cable Wiring**
2609
2610 (% style="text-align:center" %)
2611 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2612
2613 (% style="text-align:center" %)
2614 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2615
2616 **✎Note:** COM3 only available in PI8000/PI9000 series.
2617
2618 = Create communication with **MODBUS** =
2619
2620 == **MODBUS RTU Master** ==
2621
2622 Supported Series: MODBUS RTU CONTROLLER
2623
2624 HMI works as MODBUS SLAVE connecting with MASTER
2625
2626 (% style="text-align:center" %)
2627 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2628
2629
2630 (% style="text-align:center" %)
2631 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2632
2633
2634 (% style="text-align:center" %)
2635 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2636
2637 **HMI Settings**
2638
2639 (% class="table-bordered" %)
2640 |**Items**|**Settings**|**Note**
2641 |Protocol|MODBUS RTU Master|
2642 |Connection|RS485/RS232|
2643 |Baud rate|2400~~187500|
2644 |Data bit|8|
2645 |Parity|Even/ Odd/ None|
2646 |Stop bit|1/2|
2647 |Station No.|0~~255|
2648
2649 **Address List**
2650
2651 (% class="table-bordered" %)
2652 |**Type**|**HMI address**|**MODBUS code**|**Range**
2653 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
2654 |Word|HDW3500~~HDW7999|4|0~~4499
2655
2656 **Cable Wiring**
2657
2658 * **RS485**
2659
2660 (% style="text-align:center" %)
2661 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2662
2663 (% style="text-align:center" %)
2664 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2665
2666 * **RS232**
2667
2668 (% style="text-align:center" %)
2669 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2670
2671 **✎Note:** COM3 only available in PI8000/PI9000 series.
2672
2673 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
2674
2675 Supported Series: MODBUS RTU CONTROLLER
2676
2677 HMI works as MODBUS MASTER connecting with SLAVE.
2678
2679 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
2680
2681 (% style="text-align:center" %)
2682 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2683
2684
2685 (% style="text-align:center" %)
2686 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2687
2688
2689 (% style="text-align:center" %)
2690 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2691
2692 **HMI Settings**
2693
2694 (% class="table-bordered" %)
2695 |**Items**|**Settings**|**Note**
2696 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2697 |Connection|RS485/RS232|
2698 |Baud rate|2400~~187500|
2699 |Data bit|8|
2700 |Parity|Even/ Odd/ None|
2701 |Stop bit|1/2|
2702 |PLC station No.|0~~255|
2703
2704 **Address List**
2705
2706 (% class="table-bordered" %)
2707 |**Type**|**Address Type**|**Function code & Description**
2708 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2709 |06 (write single register: write a binary value to a holding register)
2710 |10 (write values to multiple addresses )
2711 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2712 |06 (write single register: write a binary value to a holding register)
2713 |10 (write values to multiple addresses )
2714 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2715 |06 (write single register: write a binary value to a holding register)
2716 |10 (write values to multiple addresses )
2717 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2718 |10 (write values to multiple addresses )
2719 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2720 |05 (Force a single coil to force the on/off state of a logic coil)
2721 |0F (Write multiple bits, ie write continuously)
2722 |(% rowspan="3" %)1|02 (Read the input state)
2723 |05 (Force a single coil to force the on/off state of a logic coil)
2724 |0F (Write multiple bits)
2725 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2726 |05 (Force a single coil to force the on/off state of a logic coil)
2727 |0F (Write multiple bits)
2728 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2729 |0F (Write multiple bits)
2730
2731 **✎Note:**
2732
2733 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2734 * The function codes sent out are the same as those that read and write words.
2735
2736 **Station number for more than one slaves**
2737
2738 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2739
2740 (% style="text-align:center" %)
2741 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2742
2743 **Cable Wiring**
2744
2745 * **RS485**
2746
2747 (% style="text-align:center" %)
2748 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2749
2750 (% style="text-align:center" %)
2751 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2752
2753 * **RS232**
2754
2755 (% style="text-align:center" %)
2756 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2757
2758 **✎Note:** COM3 only available in PI8000/PI9000 series.
2759
2760 == **MODBUS TCP Slave (All function)** ==
2761
2762 Supported series: MODBUS TCP controller
2763
2764 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
2765
2766 (% style="text-align:center" %)
2767 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2768
2769 (% style="text-align:center" %)
2770 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2771
2772
2773 (% style="text-align:center" %)
2774 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2775
2776 **HMI Setting**
2777
2778 (% class="table-bordered" %)
2779 |**Items**|**Settings**|**Note**
2780 |Protocol|MODBUS TCP Slave (All function)|
2781 |Connection|Ethernet|
2782 |Port No.|502|
2783 |PLC station No.|1|
2784
2785 **Address List**
2786
2787 (% class="table-bordered" %)
2788 |**Type**|**Register**|**Function code & Description**
2789 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2790 |06 (write single register: write a binary value to a holding register)
2791 |10 (write values to multiple addresses )
2792 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2793 |06 (write single register: write a binary value to a holding register)
2794 |10 (write values to multiple addresses )
2795 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2796 |06 (write single register: write a binary value to a holding register)
2797 |10 (write values to multiple addresses )
2798 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2799 |10 (write values to multiple addresses )
2800 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2801 |05 (Force a single coil to force the on/off state of a logic coil)
2802 |0F (Write multiple bits, ie write continuously)
2803 |(% rowspan="3" %)1|02 (Read the input state)
2804 |05 (Force a single coil to force the on/off state of a logic coil)
2805 |0F (Write multiple bits)
2806 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2807 |05 (Force a single coil to force the on/off state of a logic coil)
2808 |0F (Write multiple bits)
2809 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2810 |0F (Write multiple bits)
2811
2812 **Communication Settings**
2813
2814 Enable HMI Ethernet in [Project Settings];
2815
2816 (% style="text-align:center" %)
2817 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2818
2819 Set PLC IP in [Device IP] settings;
2820
2821 (% style="text-align:center" %)
2822 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2823
2824 **Cable Wiring**
2825
2826 (% style="text-align:center" %)
2827 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2828
2829 = **Printer** =
2830
2831 == **TSPL label printer** ==
2832
2833 **Introduction**
2834
2835 TSPL label printer protocol supports following models.
2836
2837 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2838 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2839
2840 **Setting Step**
2841
2842 Select the protocol
2843
2844 * Create a new project, select the TSPL label printer protocol as shown below.
2845
2846 (% style="text-align:center" %)
2847 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2848
2849 Set parameters
2850
2851 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2852
2853 Printer register
2854
2855 (% class="table-bordered" %)
2856 |**Register**|**System**|**Range**|**Function**
2857 |TSPL_SP|decimal|0 - 1|Set the paper size
2858 |TSPL_PT|decimal|0 - 1999|Print text
2859 |TSPL_PQ|decimal|0 - 999|Print QR code
2860 |TSPL_PB|decimal|0 - 999|Print barcode
2861 |TSPL_PR|decimal|0 - 1|Print offset
2862 |TSPL_PN|decimal|0 - 0|Trigger printing
2863 |TSPL_PS|decimal|0 - 0|Print status
2864
2865 * Set paper size:
2866 ** TSPL_SP0: width of paper, unit: mm.
2867 ** TSPL_SP1: height of paper, unit: mm.
2868 * Print text:
2869 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2870 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2871
2872 (% class="table-bordered" %)
2873 |**Register**|**Function**|**Description**
2874 |TSPL_PT0|X coordinate|Unit: dot
2875 |TSPL_PT1|Ycoordinate|Unit: dot
2876 |TSPL_PT2|Rotation angle|(((
2877 0: 0 degrees
2878
2879 1: 90 degrees
2880
2881 2: 180 degrees
2882
2883 3: 270 degrees
2884 )))
2885 |TSPL_PT3|Size|Range: 0-3
2886 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2887
2888 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2889
2890 Print QR code:
2891
2892 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2893 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2894
2895 (% class="table-bordered" %)
2896 |**Register**|**Function**|**Description**
2897 |TSPL_PQ0|X coordinate|Unit: dot
2898 |TSPL_PQ1|Ycoordinate|Unit: dot
2899 |TSPL_PQ2|Rotation angle|(((
2900 0: 0 degrees
2901
2902 1: 90 degrees
2903
2904 2: 180 degrees
2905
2906 3: 270 degrees
2907 )))
2908 |TSPL_PQ3|Size|Range: 0-5
2909 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2910
2911 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2912
2913 Print bar code:
2914
2915 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2916 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2917
2918 (% class="table-bordered" %)
2919 |**Register**|**Function**|**Description**
2920 |TSPL_PB0|X coordinate|Unit: dot
2921 |TSPL_PB1|Ycoordinate|Unit: dot
2922 |TSPL_PB2|Rotation angle|(((
2923 0: 0 degrees
2924
2925 1: 90 degrees
2926
2927 2: 180 degrees
2928
2929 3: 270 degrees
2930 )))
2931 |TSPL_PB3|height|Unit: dot
2932 |TSPL_PB4|width|Range:0-2
2933 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2934
2935 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2936
2937 Print offset:
2938
2939 * TSPL_PR0: X coordinate offset, unit: mm;
2940 * TSPL_PR1: Y coordinate offset, unit: mm.
2941
2942 Trigger printing:
2943
2944 * TSPL_PN0 = 1: trigger the printer to start printing.
2945
2946 Printing status:
2947
2948 * TSPL_PS0 = 1: The printing is normal.
2949 * TSPL_PS0 = 1: The printing is abnormal.
2950
2951 Print picture
2952
2953 * For the function of printing pictures, please refer to the configuration of [Printer object].
2954
2955 Conversion between dot and mm
2956
2957 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2958
2959 == **EpsonTM series** ==
2960
2961 **HMI Settings**
2962
2963 (% class="table-bordered" %)
2964 |**Item**|**Settings**|**Note**
2965 |Protocol|EPSON-TM-T82II/TM-XXX|
2966 |Connection|RS232|
2967 |Baud rate|9600~~115200|
2968 |Data bit|8|
2969 |Parity|None|
2970 |Stop bit|1|
2971 |PLC station No.|1|
2972
2973 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2974
2975 **Printer Settings**
2976
2977 (% class="table-bordered" %)
2978 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2979 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2980 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2981 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2982 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2983 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2984 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2985
2986 **Cable Wiring**
2987
2988 (% style="text-align:center" %)
2989 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2990
2991 (% style="text-align:center" %)
2992 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2993
2994 **✎Note:** COM3 only available in PI8000/PI9000 series.
2995
2996
2997 (% class="wikigeneratedid" %)
2998 = Create communication with **Schneider PLC** =
2999
3000 == **Schneider MODBUS RTU** ==
3001
3002 **HMI Setting**
3003
3004 |=**Parameters**|=**Recommended**|=**Notes**
3005 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3006 |Connection|RS485|
3007 |**Baud rate**|19200|
3008 |**Data bit**|8|
3009 |**Parity**|Even|
3010 |**Stop bit**|1|
3011 |**PLC station No.**|1|
3012
3013 **PLC Setting**
3014
3015 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3016
3017 **Device Address**
3018
3019 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3020 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3021 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3022 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3023 |W|MW|DDDDDD|0 ~~ 999999|Output register
3024 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3025
3026 **Wiring Diagram**
3027
3028 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3029
3030 (% style="text-align:center" %)
3031 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3032
3033 = **Barcode Scanner** =
3034
3035 Supported: DELI 14880 barcode scanner
3036
3037 **HMI Setting**
3038
3039 |**Items**|**Settings**|**Note**
3040 |Protocol|Barcode Scanner|
3041 |Connection|USB|
3042
3043 **Operating Procedures**
3044
3045 Select [Barcode Scanner];
3046
3047 (% style="text-align:center" %)
3048 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3049
3050 Set address for receiving;
3051
3052 Set correct length;
3053
3054 (% style="text-align:center" %)
3055 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3056
3057 **✎Note:**
3058
3059 * The protocol uploads the information acquired by the USB scanner to the HMI;
3060 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3061 * Recommended model: DELI 14880 barcode scanner;
3062
3063 = **Hitachi EHV Series (Ethernet)** =
3064
3065 Supported series: Hitachi EHV series
3066
3067 **HMI Settings**
3068
3069 (% class="table-bordered" %)
3070 |**Items**|**Settings**|**Note**
3071 |Protocol|Hitachi EHV series|
3072 |Connection|Ethernet|
3073 |Port No.|3004~~3007|
3074
3075 **Address List**
3076
3077 (% class="table-bordered" %)
3078 |**Type**|**Register**|**Range**|**Format**|**Note**
3079 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3080 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3081 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3082 H1H2H3H4 Module main number
3083
3084 H1: Remote number
3085
3086 H2: Unit number
3087
3088 H3: Slot number
3089
3090 H4: Word number of Module
3091
3092 H Sub number of Module
3093
3094 For example:X21.3
3095
3096 Slot number 2
3097
3098 Word number of module is 1
3099
3100 Bit number of module is 3
3101
3102 Remote number and unit number are 0
3103 )))
3104 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3105 |R|0 – FF.f (Hex)|R HH.h|
3106 |L|0 - 73FF.f (Hex)|L HHHH.h|
3107 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3108 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3109 H1H2H3H4 Module main number
3110
3111 H1: Remote number
3112
3113 H2: Unit number
3114
3115 H3: Slot number
3116
3117 H4: Word number of module
3118
3119 For example:WX21
3120
3121 Word number of module is 1
3122
3123 Slot number is 2
3124
3125 Remote number and unit number are 0
3126 )))
3127 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3128 |WR|0 – FFFF (Hex)|WR HHHH|
3129 |WL|0 - 73FF (Hex)|WL HHHH|
3130 |TC|0 - 2559|TC DDDD|
3131
3132 **Communication settings in HMI**
3133
3134 Enable HMI Ethernet in [Project Settings];
3135
3136 (% style="text-align:center" %)
3137 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3138
3139 Set PLC IP in [Device IP] settings;
3140
3141 (% style="text-align:center" %)
3142 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3143
3144 **PLC Configuration**
3145
3146 Connect with PLC, select[Online mode];
3147
3148 (% style="text-align:center" %)
3149 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3150
3151 Set IP address, it is the same LAN parameters with HMI;
3152
3153 (% style="text-align:center" %)
3154 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3155
3156 3) Save PLC communication parameter, and restart PLC
3157
3158 **PLC Monitor Mode**
3159
3160 Connect with PLC and choose to “online” mode
3161
3162 (% style="text-align:center" %)
3163 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3164
3165 Open I/O monitor sheet1
3166
3167 (% style="text-align:center" %)
3168 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3169
3170 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3171
3172 (% style="text-align:center" %)
3173 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3174
3175 Enter the register address, click OK to view the value of the register.
3176
3177 (% style="text-align:center" %)
3178 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3179
3180 (% style="text-align:center" %)
3181 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3182
3183 **✎Note:**
3184
3185 * Both word registers and bit registers support even continuous read/write functions;
3186 * The range of registers is based on the specific PLC type;
3187
3188 **Cable Wiring**
3189
3190 (% style="text-align:center" %)
3191 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3192
3193 = **IEC60870-5 104 Client** =
3194
3195 **HMI Setting**
3196
3197 (% class="table-bordered" %)
3198 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3199 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3200 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3201 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3202
3203 **Address List**
3204
3205 (% class="table-bordered" %)
3206 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3207 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3208 |(% style="width:461px" %)SCNA|0~~16777215.7
3209 |(% style="width:461px" %)DPTB|0~~16777215.7
3210 |(% style="width:461px" %)DCNA|0~~16777215.7
3211 |(% style="width:461px" %)METF|0~~16777215.7
3212 |(% style="width:461px" %)SENC|0~~16777215.7
3213 |(% style="width:461px" %)SENA|0~~16777215.7
3214 |(% style="width:461px" %)MENA|0~~16777215.7
3215 |(% style="width:461px" %)METD|0~~16777215.7
3216 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3217 |(% style="width:461px" %)SCNA|0~~16777215
3218 |(% style="width:461px" %)DPTB|0~~16777215
3219 |(% style="width:461px" %)DCNA|0~~16777215
3220 |(% style="width:461px" %)SENA|0~~16777215
3221 |(% style="width:461px" %)MENA|0~~16777215
3222 |(% style="width:461px" %)METD|0~~16777215
3223 |(% style="width:461px" %)INRO|0~~16777215
3224 |(% style="width:461px" %)TIMESYN|0~~16777215
3225 |(% style="width:461px" %)TIMEZ|0~~16777215
3226 |(% style="width:461px" %)NTP|0~~16777215
3227 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3228 |(% style="width:461px" %)SENC|0~~16777215
3229
3230 **Address Configuration**
3231
3232 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3233
3234 (% style="text-align:center" %)
3235 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3236
3237 (% style="text-align:center" %)
3238 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3239
3240 Extended tag name
3241
3242 Address range for the extended tag.
3243
3244 **Communication Settings**
3245
3246 Enable HMI Ethernet in [Project Settings];
3247
3248 (% style="text-align:center" %)
3249 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3250
3251 Set PLC IP in [Device IP] settings;
3252
3253 (% style="text-align:center" %)
3254 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3255
3256 **Cable Wiring**
3257
3258 (% style="text-align:center" %)
3259 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3260
3261 = **OpenCAN** =
3262
3263 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3264
3265 This protocol is only available in PI8000 series HMI.
3266
3267 **HMI Settings**
3268
3269 |**Items**|**Settings**|**Note**
3270 |Protocol|OPENCAN|
3271 |Connection|CAN port|
3272 |Baud rate|250000|
3273
3274 **CAN frame setting in HMI**
3275
3276 Click [OpenCAN setting] button in communication setting window;
3277
3278 (% style="text-align:center" %)
3279 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3280
3281 Click [Add] to create a new frame;
3282
3283 (% style="text-align:center" %)
3284 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3285
3286 |**No**|**Items**|**Description**
3287 |1|Add|add a frame related to register address
3288 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3289 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3290 |4|Modify|Modify the frames in frame management
3291 |5|Copy|Copy one frame to another
3292 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3293 |7|Empty|All frames in the list are cleared
3294 |8|Browse|Displays configuration files in XML format in IE
3295 |9|OK|Complete the configuration of the frame and exit
3296
3297 Set CANBUS frame in setting windows
3298
3299 (% style="text-align:center" %)
3300 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3301
3302 |**No**|**Items**|**Description**
3303 |1|ID|Set the ID of a can frame in hexadecimal format;
3304 |2|ID assign|split the ID by PF, PS, and SA;
3305 |3|Frame type|Select Standard frame or Extended Frame;
3306 |4|Frame format|Select between data frame and remote Frame;
3307 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3308 |6|Use address|(((
3309 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3310
3311 **Edit:** Set a bit or word address by its format;
3312
3313 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3314 )))
3315 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3316 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3317 |Feedback mode: feedback mode includes no response, confirm response and data response;
3318 |No response: the device or touch screen will not receive feedback;
3319 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3320 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3321 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3322 |Response timeout: sets whether the response frame timeout;
3323 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3324 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3325 |Manually send: a manually send tick indicates only one send;
3326 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3327 |10|Note|Fill the text to explain the meaning of the frame;
3328 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3329 |12|Current operation display|Display the description of current operation;
3330 |13|Add|Add a new frame;
3331 |14|Save frame|Save the configured frame format;
3332 |15|Cancel|Cancel the frame configuration;
3333
3334 Set CAN address (Read or write operation);
3335
3336 (% style="text-align:center" %)
3337 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3338
3339 |**No.**|**Item**|**Description**
3340 |1|Current address|Displays the register type and register address set by the user in the data access interface
3341 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3342 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3343 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3344 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3345 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3346 |If the trigger condition is a writing operation, there are two situations:(((
3347 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3348 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3349 )))
3350 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3351 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3352 |4|Add|Add current configuration
3353 |5|Close|Close the configuration window to exit
3354
3355 **Multiple Packages Settings**
3356
3357 (% style="text-align:center" %)
3358 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3359
3360 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3361
3362 Select Multiple package type
3363
3364 * Not Multiple packages
3365 * J1939 Multiple packages
3366 * Customized Multiple packages
3367
3368 Click [Edit Receive data] for [Receive] settings
3369
3370 * Start code+ Total length (J1939)
3371
3372 (% style="text-align:center" %)
3373 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3374
3375 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3376
3377 * Start code + Data max length (J1939)
3378
3379 (% style="text-align:center" %)
3380 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3381
3382 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3383
3384 * Data max length (J1939)
3385
3386 (% style="text-align:center" %)
3387 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3388
3389 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3390
3391 * Customized multiple package
3392
3393 (% style="text-align:center" %)
3394 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3395
3396 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3397
3398 Click [Edit Send data] for [Send] setting
3399
3400 * J1939
3401
3402 (% style="text-align:center" %)
3403 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3404
3405 [Data] is all data to be sent.
3406
3407 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3408
3409 * Customized multiple package
3410
3411 (% style="text-align:center" %)
3412 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3413
3414 [Data] is all data to be sent.
3415
3416 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3417
3418 **Cable Wiring**
3419
3420 (% style="text-align:center" %)
3421 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3422
3423 **✎Note:** The address interval between each frame need to be more than a word address;
3424
3425
3426 = **User Defined Protocol** =
3427
3428 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
3429
3430 **HMI Settings**
3431
3432 |**Items**|**Settings**|**Note**
3433 |Protocol|User defined protocol|
3434 |Connection|RS485/RS232|
3435 |Baud rate|2400~~187500|
3436 |Stop bits|1/ 2|
3437 |Data bits|7/ 8|
3438 |Parity|None/ Even/ ODD|
3439
3440 **Operating Procedures**
3441
3442 Select [User defined protocol];
3443
3444 Click [User defined protocol] button to open setting window as below;
3445
3446 (% style="text-align:center" %)
3447 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
3448
3449 Configure user defined command;
3450
3451 (% style="text-align:center" %)
3452 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
3453
3454 |**No**|**Item**|**Description**
3455 |1|Instruction edit|The required command.
3456 |2|Mode|Write to address or read from the address.
3457 |3|Format|Encode format: HEX or ASCII.
3458 |4|Other|(((
3459 **No receiving: **HMI does not respond to the receiving command.
3460
3461 **Send after receiving:** HMI responds to the receiving command.
3462 )))
3463 |5|Manually send|(((
3464 Respond once after trigger the address.
3465
3466 Address: set the trigger address.
3467 )))
3468 |6|Add|Save this setting.
3469 |7|Cancel|Cancel current settings.
3470 |(% rowspan="4" %)8|Add|Add a new command.
3471 |Edit|Edit the selected command.
3472 |Delete|Delete the selected command.
3473 |Clear|Clear all the commands.
3474 |9|Instruction list|Display all current commands.
3475 |10|Address List|Display all the addresses added.
3476 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
3477 |Export|Export current command settings to local storage.
3478 |Browse|Browse local command files.
3479 |Advanced|Combine two commands.
3480 |Exit|Complete editing and exit setting.
3481
3482 **Operating Procedures**
3483
3484 Click [Add] to create a new command, as below shows;
3485
3486 (% style="text-align:center" %)
3487 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
3488
3489 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
3490
3491 (% style="text-align:center" %)
3492 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
3493
3494 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
3495
3496 (% style="text-align:center" %)
3497 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
3498
3499 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
3500
3501 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
3502
3503 Check settings;
3504
3505 (% style="text-align:center" %)
3506 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3507
3508 |**No**|**Items**|**Description**
3509 |1|Add checking|Add checking command when receiving the data.
3510 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
3511 |Differ with send check|Set return checking.
3512 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
3513 |Length: The data length need to be checked.
3514
3515 Object settings;
3516
3517 (% style="text-align:center" %)
3518 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3519
3520 |**No**|**Items**|**Description**
3521 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
3522 |Address: the triggering address;
3523 |Note: description to object;
3524 |2|Byte order|The numerical display order;
3525
3526 Data length settings;
3527
3528 (% style="text-align:center" %)
3529 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3530
3531 |**No**|**Item**|**Description**
3532 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
3533 |Length: the return data length.
3534 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
3535 |Length: the write data length.
3536
3537 Instruction length settings
3538
3539 (% style="text-align:center" %)
3540 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3541
3542 |**No**|**Item**|**Description**
3543 |1|Send length|The instruction data will only send designated data length.
3544 |2|Return length|The responds data length.
3545 |3|End code|Instruction will not be terminated until receiving [End code];
3546
3547 **Cable Wiring**
3548
3549 * **RS485**
3550
3551 (% style="text-align:center" %)
3552 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3553
3554 (% style="text-align:center" %)
3555 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3556
3557 * **RS232**
3558
3559 (% style="text-align:center" %)
3560 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
3561
3562 **✎Note:** COM3 only available in PI8000/PI9000 series.