Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 172.1 by Stone Wu on 2022/09/05 09:33

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with **Rockwell PLC** =
459
460 == **MicroLogix Protocol** ==
461
462 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
463
464 **HMI Settings**
465
466 (% class="table-bordered" %)
467 |**Item**|**Settings**|**Note**
468 |Protocol|Allen-Bradlley MicroLogix|
469 |Connection|RS232|
470 |Baud rate|19200|
471 |Data bit|8|
472 |Parity|None|
473 |Stop bit|1|
474 |PLC station No.|1|
475
476 **Address List**
477
478 (% class="table-bordered" %)
479 |**Type**|**Device registers**|**Format**|**Range**|**Note**
480 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
481 |O|O d.d|0.0~~255.15|
482 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
483 |S|S d.d|0.0~~255.15|
484 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
485 |(% rowspan="9" %)Word|S|S d|0~~255|
486 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
487 |TP|TP nnhh|0~~ffff
488 |CS|CS nnhh|0~~ffff
489 |CP|CP nnhh|0~~ffff
490 |N|N nnhh|0~~ffff
491 |C|C nnhh|0~~ffff
492 |T|T nnhh|0~~ffff
493 |R|R nnhh|0~~ffff
494
495 **Cable Wiring**
496
497
498 (% style="text-align:center" %)
499 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
500
501 == **CompactLogix FreeTag Ethernet protocol** ==
502
503 Allen-Brandly CompactLogix
504
505 **HMI Settings**
506
507 (% class="table-bordered" %)
508 |**Items**|**Settings**|**Note**
509 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
510 |Connection|Ethernet|
511 |Port No.|44818|
512
513 **PLC Setting**
514
515 Create new tags
516
517 (% style="text-align:center" %)
518 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
519
520 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
521
522 (% style="text-align:center" %)
523 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
524
525 Import labels, please open [Communication] window and click [Import label];
526
527 Select csv file, all tags will be displayed as belows;
528
529 (% style="text-align:center" %)
530 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
531
532 **✎Note:**
533
534 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
535
536 (% style="text-align:center" %)
537 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
538
539 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
540
541 **Communication settings in HMI**
542
543 Enable HMI Ethernet in [Project Settings];
544
545 (% style="text-align:center" %)
546 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
547
548 Set PLC IP in [Device IP] settings;
549
550 (% style="text-align:center" %)
551 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
552
553 **Cable Wiring**
554
555 (% style="text-align:center" %)
556 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
557
558 == **MicroLogix 1200** ** protocol** ==
559
560 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
561
562 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
563 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
564 * **Word address S:** The word address ranges from 0 to 255 (decimal).
565 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
566
567 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
568
569 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
570 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
571 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
572 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
573 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
574 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
575 |**PLC word address type**|**Address format**|**Address range**
576 |S|ddd|S0 ~~ 255
577 |TS|ffff|TS0 ~~ FFFF
578 |TP|ffff|TP0 ~~ FFFF
579 |CS|ffff|CS0 ~~ FFFF
580 |CP|ffff|CP0 ~~ FFFF
581 |N|ffff|N0 ~~ FFFF
582 |F|ffff|F0 ~~ FFFF
583
584 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
585
586 == **S7-200 Smart Ethernet Protocol** ==
587
588 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
589
590 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
591
592 **HMI Setting**
593
594 (% class="table-bordered" %)
595 |**Items**|**Settings**|**Note**
596 |Protocol|Simens S7-200 Smart Ethernet|
597 |Connection|Ethernet|
598 |Port No.|102|
599 |PLC station No.|2|
600
601 **Address List**
602
603 (% class="table-bordered" %)
604 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
605 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
606 |Q|Q|Q ddddd.o|0.0~~99999.7|
607 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
608 |V|V|V ddddd.o|0.0~~99999.7|
609 |M|M|M ddddd.o|0.0~~99999.7|
610 |SM|SM|ddddd.o|0.0~~99999.7|
611 |S|S|ddddd.o|0.0~~99999.7|Read only
612 |T|T|ddddd|0~~99999|Timer state, read only
613 |C|C|ddddd|0~~99999|Counter state, read only
614 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
615 |Q|QW|QW ddddd|0~~99999|
616 |AI|AIW|AIW ddddd|0~~99999|
617 |AQ|VB|VB ddddd|0~~99999|
618 |V|VW|VW ddddd|0~~99998|(((
619 VW0=VB (0~~1)
620
621 VW2=VB (2~~3)
622
623 Address value is a multiple of 2
624 )))
625 |V|VD|VD ddddd|0~~99998|(((
626 VD0=VB (0~~3)
627
628 VD2=VB (4~~7)
629
630 Address value is a multiple of 4
631 )))
632 |M|MB|MB ddddd|0~~99999|
633 |M|MW|MW ddddd|0~~99999|(((
634 MW0=MB(0~~1)
635
636 MW2=MB(2~~3)
637
638 Address value is a multiple of 2
639 )))
640 |M|MD|MD ddddd|0~~99999|(((
641 MD0=MB(0~~3)
642
643 MD4=MB(4~~7)
644
645 Address value is a multiple of 4
646 )))
647 |T|TW|TW ddddd|0~~99999|Value of timer
648 |C|CW|CW ddddd|0~~99999|Value of counter
649 |W|SW|SW ddddd|0~~99999|
650
651 **Communication Settings**
652
653 Enable HMI Ethernet in [Project Settings];
654
655 (% style="text-align:center" %)
656 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
657
658 Set PLC IP in [Device IP] settings;
659
660 (% style="text-align:center" %)
661 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
662
663 * PLC IP Address: PLC IP
664 * PLC pot No.: 102(fixed)
665 * Network:TCP_Client_2N(fixed)
666
667 (% style="text-align:center" %)
668 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
669
670 * Wait timeout: depend on actual network situation (more than 1500 ms)
671
672 **Cable Wiring**
673
674 (% style="text-align:center" %)
675 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
676
677 == **S7-300 Ethernet Protocol** ==
678
679 Supported Series: Siemens S7-300 series PLC
680
681 **HMI Setting**
682
683 (% class="table-bordered" %)
684 |**Items**|**Settings**|**Note**
685 |Protocol|Simens S7-300 Ethernet|
686 |Connection|Ethernet|
687 |Port No.|102|
688 |PLC station No.|2|Need to be same as the PLC setting
689
690 **Address List**
691
692 (% class="table-bordered" %)
693 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
694 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
695 |Q|Q|Q ddddd.o|0.0~~99999.7|
696 |M|M|M ddddd.o|0.0~~99999.7|
697 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
698 nn: block number;
699
700 dddd: address;
701 )))
702 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
703 |Q|QW|QW ddddd|0~~99999|
704 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
705 |MW|MW ddddd|0~~99999|(((
706 MW0=MB(0~~1)
707
708 MW2=MB(2~~3)
709
710 Address value is a multiple of 2
711 )))
712 |MD|MD ddddd|0~~99999|(((
713 MD0=MB(0~~3)
714
715 MD4=MB(4~~7)
716
717 Address value is a multiple of 4
718 )))
719 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
720 nn: block number;
721
722 dddd: address
723 )))
724 |DBxDBW|DBxDBW nndddd|0~~99999999
725 |DBxDBD|DBxDBD nndddd|0~~99999999
726
727 **Communication Settings**
728
729 Enable HMI Ethernet in [Project Settings];
730
731 (% style="text-align:center" %)
732 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
733
734 Set PLC IP in [Device IP] settings;
735
736 (% style="text-align:center" %)
737 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
738
739 * PLC IP Address: PLC IP
740 * PLC pot No.: 102(fixed)
741 * Network:TCP_Client_2N(fixed)
742
743 (% style="text-align:center" %)
744 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
745
746 * Wait timeout: depend on actual network situation (more than 1500 ms)
747
748 **Cable Wiring**
749
750 (% style="text-align:center" %)
751 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
752
753 == **S7-1200 Ethernet Protocol** ==
754
755 Supported Series: Siemens S7-1200
756
757 **HMI Setting**
758
759 (% class="table-bordered" %)
760 |**Items**|**Settings**|**Note**
761 |Protocol|Siemens S7-1200|
762 |Connection|Ethernet|
763 |Port No.|102|
764 |PLC station No.|2|
765
766 **Address List**
767
768 (% class="table-bordered" %)
769 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
770 |(% rowspan="4" %)Bit|I|I|M d.o|(((
771 d:0~-~-9999
772
773 o:0-7
774 )))|
775 |Q|Q|Q d.o|(((
776 d:0~-~-9999
777
778 o:0-7
779 )))|
780 |M|M|M d.o|(((
781 d:0~-~-9999
782
783 o:0-7
784 )))|
785 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
786 nn:0-9999,
787
788 dddd:0-9999,
789
790 o:0-7
791 )))|(((
792 nn:DB No.
793
794 dddd:address value
795
796 o: digit address
797 )))
798 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
799 |M|MW|MW d|d:0-99999|(((
800 MW0=MB(0~~1)
801
802 MW2=MB(2~~3)
803
804 Address value is a multiple of 2
805 )))
806 |M|MD|MD d|d:0-99999|(((
807 MD0=MB(0~~3)
808
809 MD4=MB(4~~7)
810
811 Address value is a multiple of 4
812 )))
813 |I|IW|IW d|d:0-99999|
814 |Q|QW|QW d|d:0-99999|
815 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
816 nn:0-9999
817
818 dddd:0-9999
819 )))|(((
820 nn:DB No.
821
822 dddd:address value
823 )))
824 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
825 nn:0-9999
826
827 dddd:0-9999
828 )))|(((
829 nn:DB No.
830
831 dddd:address value
832
833 Address value is a multiple of 2
834 )))
835 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
836 nn:0-9999
837
838 dddd:0-9999
839 )))|(((
840 nn:DB No.
841
842 dddd:address value
843
844 Address value is a multiple of 4
845 )))
846
847 **Communication Settings**
848
849 Enable HMI Ethernet in [Project Settings];
850
851 (% style="text-align:center" %)
852 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
853
854 Set PLC IP in [Device IP] settings;
855
856 (% style="text-align:center" %)
857 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
858
859 **✎Note:**
860
861 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
862 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
863
864 **PLC Settings**
865
866 Add BD
867
868 * Please uncheck [Symbolic access only] option;
869
870 (% style="text-align:center" %)
871 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
872
873 Address settings, using BD2 as example.
874
875 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
876 * 2 represent DB block number
877 * xxxx represent address
878
879 **Such as:**
880
881 * DBxDBB20000 = DB2.DBB0
882 * DBxDBW20004 = DB2.DBW4
883
884 (% style="text-align:center" %)
885 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
886
887 **How to connect with S7-1200 Firmware V4.0**
888
889 PLC configuration
890
891 * Double click [device configuration] in Siemens via software
892 * Double click [protection] to enter protection configuration screen
893
894 (% style="text-align:center" %)
895 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
896
897 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
898
899 (% style="text-align:center" %)
900 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
901
902 DB settings
903
904 * Right click [DB], select [properties]
905 * Uncheck [optimized block access]
906
907 **Cable Wiring**
908
909 (% style="text-align:center" %)
910 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
911
912 == **S7-XXX Ethernet Protocol** ==
913
914 Supported Series: Siemens S7-400, S7-1200 and S7-1500
915
916 **HMI Setting**
917
918 (% class="table-bordered" style="width:823px" %)
919 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
920 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
921 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
922 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
923 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
924 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
925
926 Slot from TIA Portal is equal to Device No. of PIStudio
927
928 Rack from TIA Portal is equal to HMI No. of PIStudio
929
930 (% style="text-align:center" %)
931 [[image:S7-XXXCommunication Settings.png]]
932
933 (% style="text-align:center" %)
934 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
935
936 **Address List**
937
938 (% class="table-bordered" %)
939 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
940 |(% rowspan="4" %)Bit|I|I|M d.o|(((
941 d:0~-~-9999
942
943 o:0-7
944 )))|
945 |Q|Q|Q d.o|(((
946 d:0~-~-9999
947
948 o:0-7
949 )))|
950 |M|M|M d.o|(((
951 d:0~-~-9999
952
953 o:0-7
954 )))|
955 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
956 nn:0-9999,
957
958 dddd:0-9999,
959
960 o:0-7
961 )))|(((
962 nn:DB No.
963
964 dddd:address value
965
966 o: digit address
967 )))
968 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
969 |M|MW|MW d|d:0-99999|(((
970 MW0=MB(0~~1)
971
972 MW2=MB(2~~3)
973
974 Address value is a multiple of 2
975 )))
976 |M|MD|MD d|d:0-99999|(((
977 MD0=MB(0~~3)
978
979 MD4=MB(4~~7)
980
981 Address value is a multiple of 4
982 )))
983 |I|IW|IW d|d:0-99999|
984 |Q|QW|QW d|d:0-99999|
985 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
986 nn:0-9999
987
988 dddd:0-9999
989 )))|(((
990 nn:DB No.
991
992 dddd:address value
993 )))
994 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
995 nn:0-9999
996
997 dddd:0-9999
998 )))|(((
999 nn:DB No.
1000
1001 dddd:address value
1002
1003 Address value is a multiple of 2
1004 )))
1005 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1006 nn:0-9999
1007
1008 dddd:0-9999
1009 )))|(((
1010 nn:DB No.
1011
1012 dddd:address value
1013
1014 Address value is a multiple of 4
1015 )))
1016
1017 **Communication Settings**
1018
1019 Enable HMI Ethernet in [Project Settings];
1020
1021 (% style="text-align:center" %)
1022 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1023
1024 Set PLC IP in [Device IP] settings;
1025
1026 (% style="text-align:center" %)
1027 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1028
1029 **✎Note:**
1030
1031 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1032 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1033
1034 **Cable Wiring**
1035
1036 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1037
1038 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1039
1040 Supported Series: Siemens Logo 0BA0 series
1041
1042 **HMI Settings**
1043
1044 (% class="table-bordered" %)
1045 |**Items**|**Settings**|**Note**
1046 |Protocol|Siemens LOGO|
1047 |Connection|Ethernet|
1048 |Port No.|102|
1049 |PLC station No.|2|
1050
1051 **Address List**
1052
1053 (% class="table-bordered" %)
1054 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1055 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1056 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1057 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1058 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1059 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1060 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1061 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1062 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1063 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1064 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1065 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1066 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1067 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1068 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1069 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1070
1071 **PLC Settings in LOGO Software:**
1072
1073 Click [Tools]~-~-[Ethernet Connections],shown as below.
1074
1075 (% style="text-align:center" %)
1076 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1077
1078 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1079
1080 (% style="text-align:center" %)
1081 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1082
1083 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1084
1085 (% style="text-align:center" %)
1086 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1087
1088 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1089
1090 (% style="text-align:center" %)
1091 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1092
1093
1094 (% style="text-align:center" %)
1095 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1096
1097
1098 **HMI Communication Settings**
1099
1100 Set PLC IP in [Device IP] settings;
1101
1102 (% style="text-align:center" %)
1103 [[image:SiemensLOGODeviceIP.png]]
1104
1105 Enable HMI Ethernet in [Project Settings];
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1109
1110 TSAP setting
1111
1112 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1113 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1114 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1115
1116 **✎Note:**
1117
1118 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1119
1120 (% style="text-align:center" %)
1121 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1122
1123
1124 * AI word address and Ibit address are read-only and cannot be written on HMI.
1125 * VW address should be even number.such as VW0, VW2, VW4...
1126 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1127 * Written value of RTC cannot exceed 255.
1128
1129 **Cable Wiring**
1130
1131 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1132
1133 = Create communication with **Mitsubishi PLC** =
1134
1135 == **FX1S, 1N, 2N Series Protocol** ==
1136
1137 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1138
1139 **HMI Settings**
1140
1141 (% class="table-bordered" %)
1142 |**Item**|**Settings**|**Note**
1143 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1144 |Connection|RS422/RS485/RS232|
1145 |Baud rate|9600~~115200|
1146 |Data bit|7/8|
1147 |Parity|EVEN/Odd/None|
1148 |Stop bit|1/2|
1149 |PLC station No.|1~~255|
1150
1151 **Address List**
1152
1153 (% class="table-bordered" %)
1154 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1155 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1156 |Y|Y|Y o|0~~303237|
1157 |M|M|M d|0~~99999|
1158 |T|T|T d|0~~99999|
1159 |C|C|C d|0~~99999|
1160 |S|S|S d|0~~99999|
1161 |SM|SM|SM d|8000~~9999|
1162 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1163 |Y|Y|Y o|0~~303237|
1164 |M|M|M d|0~~99999|
1165 |T|T|T d|0~~99999|
1166 |C|C|C d|0~~199|
1167 |D|D|D d|0~~7999|
1168 |S|S|S d|0~~99999|
1169 |SD|SD|SD d|8000~~9999|
1170
1171 **Cable Wiring**
1172
1173 * **RS485**
1174
1175 (% style="text-align:center" %)
1176 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1177
1178 (% style="text-align:center" %)
1179 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1180
1181 * **RS422**
1182
1183 (% style="text-align:center" %)
1184 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1185
1186 **✎Note:** COM3 only available in PI8000/PI9000 series.
1187
1188 == **FX3U/3G/3GA serial protocol** ==
1189
1190 (% class="wikigeneratedid" %)
1191 **HMI Settings**
1192
1193 |=**Item**|=**Settings**|=**Note**
1194 |Protocol|Mitsubishi FX3U/3G/3GA|
1195 |Connection|RS422|
1196 |Baud rate|9600~~115200|
1197 |Data bit|7/8|
1198 |Parity|EVEN/Odd/None|
1199 |Stop bit|1/2|
1200 |PLC station No.|1~~255|
1201
1202 (% class="wikigeneratedid" %)
1203 **Address List**
1204
1205 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1206 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1207 |Y|Y|Y o|0~~303237|
1208 |M|M|M d|0~~99999|
1209 |T|T|T d|0~~99999|
1210 |C|C|C d|0~~99999|
1211 |S|S|S d|0~~99999|
1212 |SM|SM|SM d|8000~~9999|
1213 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1214 |Y|Y|Y o|0~~303237|
1215 |M|M|M d|0~~99999|
1216 |T|T|T d|0~~99999|
1217 |C|C|C d|0~~199|
1218 |D|D|D d|0~~7999|
1219 |S|S|S d|0~~99999|
1220 |SD|SD|SD d|8000~~9999|
1221
1222 **Configure the communication protocol**
1223
1224 (% style="text-align:center" %)
1225 [[image:image-20220831095222-1.png]]
1226
1227 (% style="text-align:center" %)
1228 [[image:image-20220831095743-2.png]]
1229
1230 **Wiring**
1231
1232 (% style="text-align:center" %)
1233 [[image:image-20220831100333-7.png]]
1234
1235 Pin Definition Diagram
1236
1237 (% style="text-align:center" %)
1238 [[image:image-20220831100314-6.png]]
1239
1240 == **FX5U Ethernet Protocol** ==
1241
1242 Mitsubishi FX5U series PLC
1243
1244 **HMI Settings**
1245
1246 (% class="table-bordered" %)
1247 |**Items**|**Settings**|**Note**
1248 |Protocol|Mitsubishi FX5U|
1249 |Connection|Ethernet|
1250 |Port No.|5002|Must be the same as the PLC setting
1251 |PLC station No.|0|
1252
1253 **Address List**
1254
1255 (% class="table-bordered" %)
1256 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1257 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1258 |Y|Y|Y o|0~~303237|
1259 |M|M|M d|0~~99999|
1260 |B|B|B h|0~~7FFF|
1261 |F|F|F d|0~~32767|
1262 |SB|SB|SB h|0~~7FFF|
1263 |TS|TS|TS d|0~~1023|
1264 |TC|TC|TC d|0~~1023|
1265 |STS|STS|STS d|0~~1023|
1266 |STC|STC|STS d|0~~1023|
1267 |CS|CS|CS d|0~~1023|
1268 |CC|CC|CC d|0~~1023|
1269 |SM|SM|SM d|0~~9999|
1270 |L|L|L d|0~~32767|
1271 |S|S|S d|0~~4095|
1272 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1273 |TN|TN|TN d|0~~1023|
1274 |STN|STN|STN d|0~~1023|
1275 |CN|CN|CN d|0~~1023|
1276 |R|R|R d|0~~32767|
1277 |SW|SW|SW h|0~~7FFF|
1278 |Z|Z|Z d|0~~23|
1279 |D|D|D d|0~~7999|
1280 |SD|SD|SD d|0~~11999|
1281
1282 **PLC Settings (GX Works 3)**
1283
1284 Find the [Ethernet port] in the navigation area.
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1288
1289 Select [Own Node Settings] in the [Setting Item List];
1290
1291 Set [IP Address], [Subnet Mask], [Default Gateway];
1292
1293 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1294
1295 (% style="text-align:center" %)
1296 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1297
1298 Select [SLMP Connection Module] and add into host station as below picture shows;
1299
1300 Set Port number as 5002 (this is necessary settings);
1301
1302 Click [Close with Reflecting the Setting] to save and close window;
1303
1304 (% style="text-align:center" %)
1305 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1306
1307 Click [Apply] to completed Etherenet settings;
1308
1309 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1310
1311 (% style="text-align:center" %)
1312 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1313
1314 **Cable Wiring**
1315
1316 (% style="text-align:center" %)
1317 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1318
1319 == **FX5U Serial Port Protocol** ==
1320
1321 Mitsubishi FX5U series PLC
1322
1323 **HMI Settings**
1324
1325 (% class="table-bordered" %)
1326 |**Item**|**Settings**|**Note**
1327 |Protocol|Mitsubishi FX5U|
1328 |Connection|RS422/RS485|
1329 |Baud rate|9600|
1330 |Data bit|7|
1331 |Parity|Odd|
1332 |Stop bit|1|
1333 |PLC station No.|1~~255|Need to be the same as PLC settings
1334
1335 **Address List**
1336
1337 (% class="table-bordered" %)
1338 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1339 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1340 |Y|Y|Y o|0~~303237|
1341 |M|M|M d|0~~99999|
1342 |B|B|B h|0~~7FFF|
1343 |F|F|F d|0~~32767|
1344 |SB|SB|SB h|0~~7FFF|
1345 |TS|TS|TS d|0~~1023|
1346 |TC|TC|TC d|0~~1023|
1347 |STS|STS|STS d|0~~1023|
1348 |STC|STC|STS d|0~~1023|
1349 |CS|CS|CS d|0~~1023|
1350 |CC|CC|CC d|0~~1023|
1351 |SM|SM|SM d|0~~9999|
1352 |L|L|L d|0~~32767|
1353 |S|S|S d|0~~4095|
1354 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1355 |TN|TN|TN d|0~~1023|
1356 |STN|STN|STN d|0~~1023|
1357 |CN|CN|CN d|0~~1023|
1358 |R|R|R d|0~~32767|
1359 |SW|SW|SW h|0~~7FFF|
1360 |Z|Z|Z d|0~~23|
1361 |D|D|D d|0~~7999|
1362 |SD|SD|SD d|0~~11999|
1363
1364 **PLC Settings (GX Works 3)**
1365
1366 Create a blank FX5U project
1367
1368 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1369
1370 (% style="text-align:center" %)
1371 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1372
1373 Select protocol in the setting item, and set parameters.
1374
1375 (% style="text-align:center" %)
1376 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1377
1378 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1379
1380 (% style="text-align:center" %)
1381 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1382
1383 Click the [Apply] button to finish the setting.
1384
1385 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1386
1387 (% style="text-align:center" %)
1388 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1389
1390 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1391
1392 Done.
1393
1394 **Cable Wiring**
1395
1396 * **RS485**
1397
1398 (% style="text-align:center" %)
1399 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1400
1401 (% style="text-align:center" %)
1402 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1403
1404 * **RS422**
1405
1406 (% style="text-align:center" %)
1407 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1408
1409 **✎Note:** COM3 only available in PI8000/PI9000 series.
1410
1411 == **L02 Serial Protocol** ==
1412
1413 Mitsubishi L02 series CPU built-in serial port.
1414
1415 **HMI Settings**
1416
1417 |=**Item**|=**Settings**|=**Note**
1418 |Protocol|Mitsubishi L02|
1419 |Connection|RS422|
1420 |Baud rate|115200|
1421 |Data bit|8|
1422 |Parity|Odd|
1423 |Stop bit|1|
1424 |PLC station No.|1~~255|Need to be the same as PLC settings
1425
1426 **Address List**
1427
1428 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1429 |Bit|X|X|X h|0~~FFFF|
1430 |Bit|Y|Y|Y h|0~~FFFF|
1431 |Bit|M|M|M d|0~~9999|
1432 |Bit|L|L|L d|0~~9999|
1433 |Bit|F|F|F d|0~~9999|
1434 |Bit|B|B|B h|0~~FFFF|
1435 |Bit|V|V|V d|0~~2047|
1436 |Bit|TC|TC|TC d|0~~9999|
1437 |Bit|SS|SS|SS d|0~~9999|
1438 |Bit|SC|SC|SC d|0~~9999|
1439 |Bit|CS|CS|CS d|0~~9999|
1440 |Bit|CC|CC|CC d|0~~9999|
1441 |Bit|SB|SB|SB h|0~~FFFF|
1442 |Bit|SM|SM|SM d|0~~2047|
1443 |Bit|STS|STS|STS d|0~~1023|
1444 |Bit|S|S|S d|0~~9999|
1445 |Bit|DX|DX|DX h|0~~FFFF|
1446 |Bit|DY|DY|DY h|0~~FFFF|
1447 |Bit|TS|TS|TS d|0~~9999|
1448 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1449 |Word|W|W|W h|0~~FFFF|
1450 |Word|TN|TN|TN d|0~~99999|
1451 |Word|SN|SN|SN d|0~~99999|
1452 |Word|CN|CN|CN d|0~~99999|
1453 |Word|R|R|R d|0~~99999|
1454 |Word|SW|SW|SW h|0~~FFFF|
1455 |Word|Z|Z|Z d|0~~99999|
1456 |Word|ZR|ZR|ZR h|0~~FFFF|
1457 |Word|D|D|D d|0~~99999|
1458
1459 **Communication Settings**
1460
1461 (% style="text-align:center" %)
1462 [[image:image-20220831105732-3.png]]
1463
1464 (% style="text-align:center" %)
1465 [[image:image-20220831110004-5.png]]
1466
1467 **Cable Wiring**
1468
1469 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1470
1471 Pin Definition Diagram
1472
1473 (% style="text-align:center" %)
1474 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1475
1476 == **L02 MELSEC (Ethernet) Protocol** ==
1477
1478 Mitsubishi Q series CPU built-in Ethernet port.
1479
1480 **HMI Settings**
1481
1482 (% class="table-bordered" %)
1483 |**Items**|**Settings**|**Note**
1484 |Protocol|MIT L02 CPU MELSEC|
1485 |Connection|Ethernet|
1486 |Port No.|1025|Must be the same as the PLC setting
1487 |PLC station No.|0|Must be the same as the PLC setting
1488
1489 **Address List**
1490
1491 (% class="table-bordered" %)
1492 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1493 |Bit|X|X|X h|0~~FFFF|
1494 |Bit|Y|Y|Y h|0~~FFFF|
1495 |Bit|M|M|M d|0~~9999|
1496 |Bit|L|L|L d|0~~9999|
1497 |Bit|F|F|F d|0~~9999|
1498 |Bit|B|B|B h|0~~FFFF|
1499 |Bit|V|V|V d|0~~2047|
1500 |Bit|TC|TC|TC d|0~~9999|
1501 |Bit|SS|SS|SS d|0~~9999|
1502 |Bit|SC|SC|SC d|0~~9999|
1503 |Bit|CS|CS|CS d|0~~9999|
1504 |Bit|CC|CC|CC d|0~~9999|
1505 |Bit|SB|SB|SB h|0~~FFFF|
1506 |Bit|SM|SM|SM d|0~~2047|
1507 |Bit|STS|STS|STS d|0~~1023|
1508 |Bit|S|S|S d|0~~9999|
1509 |Bit|DX|DX|DX h|0~~FFFF|
1510 |Bit|DY|DY|DY h|0~~FFFF|
1511 |Bit|TS|TS|TS d|0~~9999|
1512 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1513 |Word|W|W|W h|0~~FFFF|
1514 |Word|TN|TN|TN d|0~~99999|
1515 |Word|SN|SN|SN d|0~~99999|
1516 |Word|CN|CN|CN d|0~~99999|
1517 |Word|R|R|R d|0~~99999|
1518 |Word|SW|SW|SW h|0~~FFFF|
1519 |Word|Z|Z|Z d|0~~99999|
1520 |Word|ZR|ZR|ZR h|0~~FFFF|
1521 |Word|D|D|D d|0~~99999|
1522
1523 **Communication Settings**
1524
1525 Enable HMI Ethernet in [Project Settings];
1526
1527 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1528
1529 Set PLC IP in [Device IP] settings;
1530
1531 (% style="text-align:center" %)
1532 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1533
1534 **PLC Settings (GX Works2 )**
1535
1536 Create a project
1537
1538 Set PLC IP, subnet mask and gateway;
1539
1540 Select [Binary Code] as communication data code;
1541
1542 (% style="text-align:center" %)
1543 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1544
1545 Set PLC port number, for example 1025
1546
1547 (% style="text-align:center" %)
1548 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1549
1550 Save settings;
1551
1552 Download project into PLC device;
1553
1554 Restart PLC device;
1555
1556 **Cable Wiring**
1557
1558 (% style="text-align:center" %)
1559 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1560
1561 == **QJ71E71 MELSEC Protocol** ==
1562
1563 Mitsubishi QJ71E71 Ethernet communication module;
1564
1565 **HMI Settings**
1566
1567 (% class="table-bordered" %)
1568 |**Items**|**Settings**|**Note**
1569 |Protocol|MIT QJ71E71 MELSEC|
1570 |Connection|Ethernet|
1571 |Port No.|1025|Must be the same as the PLC setting
1572 |PLC station No.|0|Must be the same as the PLC setting
1573
1574 **Address List**
1575
1576 (% class="table-bordered" %)
1577 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1578 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1579 |Y|Y|Y h|0~~1FFF|
1580 |M|M|M d|0~~99999|
1581 |L|L|L d|0~~8191|
1582 |F|F|F d|0~~2047|
1583 |B|B|B h|0~~1FFF|
1584 |V|V|V d|0~~2047|
1585 |TS|TS|TS d|0~~2047|
1586 |TC|TC|TC d|0~~2047|
1587 |SS|SS|SS d|0~~2047|
1588 |SC|SC|SC d|0~~2047|
1589 |CS|CS|CS d|0~~1023|
1590 |CC|CC|CC d|0~~1023|
1591 |SB|SB|SB h|0~~7FF|
1592 |S|S|S d|0~~8191|
1593 |DX|DX|DX h|0~~1FFF|
1594 |DY|DY|DY h|0~~1FFF|
1595 |SM|SM|SM d|8000~~9999|
1596 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1597 |D|D|D d|0~~12287|
1598 |W|W|W h|0~~1FFF|
1599 |TN|TN|TN d|0~~2047|
1600 |SN|SN|SN d|0~~2047|
1601 |CN|CN|CN d|0~~1023|
1602 |R|R|R d|0~~32767|
1603 |SW|SW|SW h|0~~7FF|
1604 |Z|Z|Z d|0~~15|
1605 |ZR|ZR|ZR h|0~~FE7FF|
1606
1607 **HMI Communication Settings**
1608
1609 1) Enable HMI Ethernet in [Project Settings];
1610
1611 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1612
1613 2) Set PLC IP in [Device IP] settings;
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1617
1618 **PLC Settings(GX Works2)**
1619
1620 * Click [Ethernet/CC IE/MELSECNET];
1621 * Please select [Ethernet] as network type;
1622 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1623 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1624 * Click [Operation setting] to set IP;
1625 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1626 * Set protocol: TCP;
1627 * Set [unpassive] in [Open system];
1628 * Set [receive] in [Fixed buffer];
1629 * Set [procedure Exist] in [Fixed buffer communication];
1630 * Disable [Pairing open];
1631 * Set [No confirm] in [Existence confirmation];
1632 * Host station port number: 1025;
1633 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1634 * Download project into PLC and restart it
1635
1636 **Cable Wiring**
1637
1638 (% style="text-align:center" %)
1639 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1640
1641 = Create communication with **Delta PLC** =
1642
1643 == DVP serial protocol ==
1644
1645 (% class="wikigeneratedid" %)
1646 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1647
1648 **HMI Settings**
1649
1650 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
1651 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
1652 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
1653 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
1654 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
1655 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
1656 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
1657 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
1658
1659 **Address List**
1660
1661 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1662 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
1663 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
1664 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
1665 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
1666 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
1667 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
1668 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
1669 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
1670 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
1671
1672 (% class="wikigeneratedid" %)
1673 **Configure the communication protocol**
1674
1675 (% style="text-align:center" %)
1676 [[image:image-20220829152327-6.png]]
1677
1678 (% style="text-align:center" %)
1679 [[image:image-20220829152016-3.png]]
1680
1681 (% class="wikigeneratedid" %)
1682 **Cable Wiring**
1683
1684 (% class="wikigeneratedid" id="H" %)
1685 [[image:image-20220829152610-7.png]]
1686
1687 (% style="text-align:center" %)
1688 [[image:image-20220829152102-5.png]]
1689
1690 == DVP Ethernet Protocol ==
1691
1692 (% class="wikigeneratedid" %)
1693 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1694
1695 **HMI Settings**
1696
1697 |=**Items**|=**Settings**|=**Note**
1698 |Protocol|DELTA DVP Modbus TCP|
1699 |Connection|Ethernet|
1700 |Port No.|201|Must be the same as the PLC setting
1701 |PLC station No.|0|Must be the same as the PLC setting
1702
1703 **Address List**
1704
1705 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1706 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
1707 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
1708 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
1709 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
1710 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
1711 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
1712 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
1713 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
1714 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
1715
1716 )))
1717 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
1718 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
1719
1720 )))
1721
1722 (% class="wikigeneratedid" %)
1723 **Configure the communication protocol**
1724
1725 (% style="text-align:center" %)
1726 [[image:image-20220829155452-1.png]]
1727
1728 [[image:image-20220829162116-2.png]]
1729
1730 **Cable Wiring**
1731
1732 (% style="text-align:center" %)
1733 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1734
1735 == **AS serial protocol** ==
1736
1737 **HMI Settings**
1738
1739 |**Item**|**Settings**|**Note**
1740 |Protocol|DELTA AS300 MODBUS RTU|
1741 |Connection|RS485|
1742 |Baud rate|9600|
1743 |Data bit|8|
1744 |Parity|NONE|
1745 |Stop bit|1|
1746 |PLC station No.|1|
1747
1748 **Address List**
1749
1750 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1751 |Bit|X|X|X o|0~~63|
1752 |Bit|Y|Y|Y o|0~~63|
1753 |Bit|D|D|D d|0~~29999|
1754 |Bit|M|M|M d|0~~8191|
1755 |Bit|SM|SM|SM d|0~~4095|
1756 |Bit|S|S|S d|0~~2047|
1757 |Bit|T|T|T d|0~~511|
1758 |Bit|C|C|C d|0~~511|
1759 |Bit|HC|HC|HC d|0~~255|
1760 |Word|X|X|X o|0~~63|
1761 |Word|Y|Y|Y o|0~~63|
1762 |Word|SR|SR|SR d|0~~2047|
1763 |Word|D|D|D d|0~~29999|
1764 |Word|T|T|T d|0~~511|
1765 |Word|C|C|C d|0~~511|
1766 |Word|E|E|E d|0~~9|
1767
1768 **Configure the communication protocol**
1769
1770 (% style="text-align:center" %)
1771 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
1772
1773 (% style="text-align:center" %)
1774 [[image:image-20220830094657-2.png]]
1775
1776 **Cable Wiring**
1777
1778 (% style="text-align:center" %)
1779 [[image:image-20220830141138-1.png]]
1780
1781 Pin Definition Diagram
1782
1783 (% style="text-align:center" %)
1784 [[image:image-20220830095131-1.png]]
1785
1786 == AS Ethernet Protocol ==
1787
1788 **HMI Settings**
1789
1790 |=**Items**|=**Settings**|=**Note**
1791 |Protocol|DELTA AS300 MODBUS TCP|
1792 |Connection|Ethernet|
1793 |Port No.|502|
1794 |Device No.|1|
1795 |HMI No.|0|
1796
1797 **Address List**
1798
1799 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1800 |Bit|X|X|X d|0~~63|
1801 |Bit|Y|Y|Y d|0~~63|
1802 |Bit|D|D|D d|0~~29999|
1803 |Bit|M|M|M d|0~~8191|
1804 |Bit|SM|SM|SM d|0~~4095|
1805 |Bit|S|S|S h|0~~2047|
1806 |Bit|T|T|T d|0~~511|
1807 |Bit|C|C|C d|0~~511|
1808 |Bit|HC|HC|HC d|0~~255|
1809 |Word|X|X|X h|0~~63|
1810 |Word|Y|Y|Y d|0~~63|
1811 |Word|SR|SR|SR d|0~~2047|
1812 |Word|D|D|D d|0~~29999|
1813 |Word|T|T|T d|0~~511|
1814 |Word|C|C|C h|0~~511|
1815 |Word|E|E|E d|0~~9|
1816
1817 **Configure the communication protocol**
1818
1819 (% style="text-align:center" %)
1820 [[image:image-20220830140537-1.png]]
1821
1822 (% style="text-align:center" %)
1823 [[image:image-20220830140629-2.png]]
1824
1825 **Cable Wiring**
1826
1827 [[image:image-20220830094929-1.png]]
1828
1829 Pin Definition Diagram
1830
1831 (% style="text-align:center" %)
1832 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1833
1834 = Create communication with **Omron** PLC =
1835
1836 == **CJ TCP FINS Ethemet  Protocol** ==
1837
1838 Supported device:CJ series
1839
1840 **1)HMI Settings**
1841
1842 |=**Items**|=**Settings**|=**Note**
1843 |Protocol|OMRON CJ TCP FINS Ethemet|
1844 |Connection|Ethernet|
1845 |Port No.|9600|
1846 |Device No.|0|
1847 |HMI No.|0|(((
1848
1849 )))
1850
1851 **2)Address List**
1852
1853 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1854 |Bit|CIO|CIO|CIO d|0~~99999|
1855 |Bit|W|W|W d|0~~99999|
1856 |Bit|D|D|D d|0~~99999|
1857 |Bit|H|H|H d|0~~99999|
1858 |Bit|A|A|A d|0~~99999|
1859 |Bit|T|T|T h|0~~99999|
1860 |Bit|CF|CF|CF d|0~~99999|
1861 |Bit|FF|FF|FF d|0~~99999|
1862 |Bit|C|C|C d|0~~99999|
1863 |Bit|EM0|EM0|EM0 d|0~~99999|
1864 |Bit|EM1|EM1|EM1 d|0~~99999|
1865 |Bit|EM2|EM2|EM2 d|0~~99999|
1866 |Bit|EM3|EM3|EM3 d|0~~99999|
1867 |Bit|EM4|EM4|EM4 d|0~~99999|
1868 |Bit|EM5|EM5|EM5 h|0~~99999|
1869 |Bit|EM6|EM6|EM6 d|0~~99999|
1870 |Bit|EM7|EM7|EM7 d|0~~99999|
1871 |Bit|EM8|EM8|EM8 d|0~~99999|
1872 |Bit|EM9|EM9|EM9 d|0~~99999|
1873 |Bit|EMA|EMA|EMA d|0~~99999|
1874 |Bit|EMB|EMB|EMB d|0~~99999|
1875 |Bit|EMC|EMC|EMC d|0~~99999|
1876 |Bit|Lamp|Lamp|Lamp d|0~~0|
1877 |Word|CIO|CIO|CIO d|0~~99999|
1878 |Word|W|W|W d|0~~99999|
1879 |Word|D|D|D d|0~~99999|
1880 |Word|H|H|H d|0~~99999|
1881 |Word|A|A|A d|0~~99999|
1882 |Word|T|T|T h|0~~99999|
1883 |Word|CF|CF|CF d|0~~99999|
1884 |Word|FF|FF|FF d|0~~99999|
1885 |Word|C|C|C d|0~~99999|
1886 |Word|EM0|EM0|EM0 d|0~~99999|
1887 |Word|EM1|EM1|EM1 d|0~~99999|
1888 |Word|EM2|EM2|EM2 d|0~~99999|
1889 |Word|EM3|EM3|EM3 d|0~~99999|
1890 |Word|EM4|EM4|EM4 d|0~~99999|
1891 |Word|EM5|EM5|EM5 h|0~~99999|
1892 |Word|EM6|EM6|EM6 d|0~~99999|
1893 |Word|EM7|EM7|EM7 d|0~~99999|
1894 |Word|EM8|EM8|EM8 d|0~~99999|
1895 |Word|EM9|EM9|EM9 d|0~~99999|
1896 |Word|EMA|EMA|EMA d|0~~99999|
1897 |Word|EMB|EMB|EMB d|0~~99999|
1898 |Word|EMC|EMC|EMC d|0~~99999|
1899 |Word|IR|IR|IR d|0~~99999|
1900 |Word|DR|DR|DR d|0~~99999|
1901
1902 **3)Configure the communication protocol**
1903
1904 [[image:image-20220830143348-1.png]]
1905
1906 [[image:image-20220830143511-2.png]]
1907
1908 **4)Cable Wiring**
1909
1910 Pin Definition Diagram
1911
1912 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1913
1914 == **CP1E/CP1H serial protocol** ==
1915
1916 Supported device: OMRON CS1(CP1E/CP1H)
1917
1918 **1)HMI Settings**
1919
1920
1921 |**Items**|**Settings**|**Note**
1922 |Protocol|OMRON CS1(CP1E/CP1H)|
1923 |Connection|RS232 (9600, 2, 7, EVEN)|
1924 |Port No.|None|
1925 |PLC station No.|0|
1926
1927 **2)Address List**
1928
1929 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1930 |Bit|CIO|CIO|CIO d|0~~99999|
1931 |Bit|W|W|W d|0~~99999|
1932 |Bit|D|D|D d|0~~99999|
1933 |Bit|H|H|H d|0~~99999|
1934 |Bit|A|A|A d|0~~99999|
1935 |Bit|TF|T|T h|0~~99999|
1936 |Bit|CF|CF|CF d|0~~99999|
1937 |Bit|T|FF|FF d|0~~99999|
1938 |Bit|C|C|C d|0~~99999|
1939 |Bit|EM0|EM0|EM0 d|0~~99999|
1940 |Bit|EM1|EM1|EM1 d|0~~99999|
1941 |Bit|EM2|EM2|EM2 d|0~~99999|
1942 |Bit|EM3|EM3|EM3 d|0~~99999|
1943 |Bit|EM4|EM4|EM4 d|0~~99999|
1944 |Bit|EM5|EM5|EM5 h|0~~99999|
1945 |Bit|EM6|EM6|EM6 d|0~~99999|
1946 |Bit|EM7|EM7|EM7 d|0~~99999|
1947 |Bit|EM8|EM8|EM8 d|0~~99999|
1948 |Bit|EM9|EM9|EM9 d|0~~99999|
1949 |Bit|EMA|EMA|EMA d|0~~99999|
1950 |Bit|EMB|EMB|EMB d|0~~99999|
1951 |Bit|EMC|EMC|EMC d|0~~99999|
1952 |Word|CIO|CIO|CIO d|0~~99999|
1953 |Word|W|W|W d|0~~99999|
1954 |Word|D|D|D d|0~~99999|
1955 |Word|H|H|H d|0~~99999|
1956 |Word|A|A|A d|0~~99999|
1957 |Word|T|T|T h|0~~99999|
1958 |Word|CIO|CF|CF d|0~~99999|
1959 |Word|C|C|C d|0~~99999|
1960 |Word|EM0|EM0|EM0 d|0~~99999|
1961 |Word|EM1|EM1|EM1 d|0~~99999|
1962 |Word|EM2|EM2|EM2 d|0~~99999|
1963 |Word|EM3|EM3|EM3 d|0~~99999|
1964 |Word|EM4|EM4|EM4 d|0~~99999|
1965 |Word|EM5|EM5|EM5 h|0~~99999|
1966 |Word|EM6|EM6|EM6 d|0~~99999|
1967 |Word|EM7|EM7|EM7 d|0~~99999|
1968 |Word|EM8|EM8|EM8 d|0~~99999|
1969 |Word|EM9|EM9|EM9 d|0~~99999|
1970 |Word|EMA|EMA|EMA d|0~~99999|
1971 |Word|EMB|EMB|EMB d|0~~99999|
1972 |Word|EMC|EMC|EMC d|0~~99999|
1973 |Word|IR|IR|IR d|0~~99999|
1974 |Word|DR|DR|DR d|0~~99999|
1975
1976 **3)Configure the communication protocol**
1977
1978 [[image:image-20220902153118-1.png]]
1979
1980
1981 [[image:image-20220902151322-2.png]]
1982
1983 **4)Cable Wiring**
1984
1985 Figure
1986
1987 [[image:image-20220902153949-2.png]]
1988
1989 Pin Definition Diagram
1990
1991 [[image:image-20220902154056-3.png]]
1992
1993 == **EC55 Protocol** ==
1994
1995 Supported device: EC55 temperature instrument
1996
1997 **1)HMI Settings**
1998
1999 |**Items**|**Settings**|**Note**
2000 |Protocol|Omron EC55|
2001 |Connection|RS485 (9600, 2, 7, EVEN)|
2002 |Port No.|None|
2003 |PLC station No.|0|
2004
2005 **2)Address List**
2006
2007 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2008 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2009 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2010 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2011 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2012 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2013 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2014 |CP|-|0-6|Read controller intrinsic property
2015 |CS|-|0-2|Read controller states
2016 |CA|-|0-17|Action command
2017
2018 **3)Device Settings**
2019
2020 Omron E5CC PLC configuration
2021
2022 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2023
2024 (% style="text-align:center" %)
2025 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2026
2027 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2028
2029 (% style="text-align:center" %)
2030 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2031
2032 **✎Note:** The communication settings for HMI should be consistent with this setting.
2033
2034 **Cable Wiring**
2035
2036 (% style="text-align:center" %)
2037 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2038
2039 (% style="text-align:center" %)
2040 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2041
2042 **✎Note:**
2043
2044 * COM3 only available in PI8000/PI9000 series.
2045 * CA address could not support continuous writing function;
2046 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2047 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2048 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2049 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2050 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2051 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2052 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2053
2054 == **EtherNet/IP NX series Protocol** ==
2055
2056 Supported series: Omron NX/NJ series
2057
2058 **HMI Setting**
2059
2060 |**Items**|**Settings**|**Note**
2061 |Protocol|Omron NX Ethernet/IP|
2062 |Connection|Ethernet|
2063 |Port No.|44818|
2064 |PLC station No.|1|
2065
2066 **Instruction**
2067
2068 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2069
2070 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2071
2072 (% style="text-align:center" %)
2073 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2074
2075 **Export labels from Sysmac Studio**
2076
2077 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2078
2079 (% style="text-align:center" %)
2080 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2081
2082 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2083
2084 Click [Label manage];
2085
2086 (% style="text-align:center" %)
2087 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2088
2089 Click [Import labels] and then select the file exported in step 1;
2090
2091 (% style="text-align:center" %)
2092 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2093
2094 The Import Status field shows the result, click [OK] to finish importing address labels;
2095
2096 (% style="text-align:center" %)
2097 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2098
2099 **Communication Settings**
2100
2101 Enable HMI Ethernet in [Project Settings];
2102
2103 (% style="text-align:center" %)
2104 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2105
2106 Set PLC IP in [Device IP] settings;
2107
2108 (% style="text-align:center" %)
2109 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2110
2111 (% style="text-align:center" %)
2112 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2113
2114 **Cable Wiring**
2115
2116 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2117
2118 = Create communication with Xinje** PLC** =
2119
2120 == **XC serial protocol** ==
2121
2122 **1)HMI Settings**
2123
2124 |**Item**|**Settings**|**Note**
2125 |Protocol|XINJE XC MODBUS|
2126 |Connection|RS232|
2127 |Baud rate|19200|
2128 |Data bit|8|
2129 |Parity|EVEN|
2130 |Stop bit|1|
2131 |PLC station No.|1|
2132
2133 **2)Address List**
2134
2135 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2136 |Bit|M|M|M d|0~~8511|
2137 |Bit|X|X|X o|0~~1747|
2138 |Bit|Y|Y|Y o|0~~1747|
2139 |Bit|S|S|S d|0~~1023|
2140 |Bit|T|T|T d|0~~4095|
2141 |Bit|C|C|C d|0~~634|
2142 |Word|D|D|D d|0~~8511|
2143 |Word|TD|TD|TD d|0~~618|
2144 |Word|CD|CD|CD d|0~~634|
2145 |Word|FD|FD|FD d|0~~8511|
2146
2147 **3)Configure the communication protocol**
2148
2149 [[image:image-20220830154105-1.png]]
2150
2151 [[image:image-20220830154159-3.png]]
2152
2153 **4)Cable Wiring**
2154
2155 Figure
2156
2157 [[image:image-20220830155728-4.png]]
2158
2159 Pin Definition Diagram
2160
2161 [[image:image-20220830154131-2.png]]
2162
2163 == **XD serial protocol** ==
2164
2165 **1)HMI Settings**
2166
2167 Supported Series: Delta Xinjie XD/XE Series PLC
2168
2169 |**Item**|**Settings**|**Note**
2170 |Protocol|XINJE XD/XC MODBUS|
2171 |Connection|RS232|
2172 |Baud rate|19200|
2173 |Data bit|8|
2174 |Parity|EVEN|
2175 |Stop bit|1|
2176 |PLC station No.|1|
2177
2178 **2)Address List**
2179
2180 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2181 |Bit|M|M|M d|0~~74999|
2182 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2183 |Bit|X2xx|X2xx|X2xx o|0~~277|
2184 |Bit|X|X|X o|0~~77|
2185 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2186 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2187 |Bit|Y|Y|Y o|0~~4095|
2188 |Bit|SM|SM|SM d|0~~4999|(((
2189
2190 )))
2191 |Bit|T|T|T d|0~~4999|
2192 |Bit|C|C|C d|0~~4999|
2193 |Bit|ET|ET|ET d|0~~31|
2194 |Bit|SE|SE|SE d|0~~31|
2195 |Bit|HM|HM|HM d|0~~11999|
2196 |Bit|HSC|HSC|HSC d|0~~39|
2197 |Bit|HS|HS|HS d|0~~999|
2198 |Bit|HT|HT|HT d|0~~1999|
2199 |Bit|HC|HC|HC d|0~~1999|
2200 |Bit|S|S|S d|0~~7999|
2201 |Word|D|D|D d|0~~69999|
2202 |Word|ID|ID|ID d|0~~99|
2203 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2204 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2205 |Word|QD|QD|QD d|0~~99|
2206 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2207 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2208 |Word|SD|SD|SD d|0~~4999|
2209 |Word|TD|TD|TD d|0~~575|
2210 |Word|CD|CD|CD d|0~~575|
2211 |Word|ETD|ETD|ETD d|0~~31|
2212 |Word|HD|HD|HD d|0~~24999|
2213 |Word|HSD|HSD|HSD d|0~~1023|
2214 |Word|HTD|HTD|HTD d|0~~95|
2215 |Word|HCD|HCD|HCD d|0~~95|
2216 |Word|HSCD|HSCD|HSCD d|0~~31|
2217 |Word|FD|FD|FD d|0~~8191|
2218 |Word|SFD|SFD|SFD d|0~~5999|
2219 |Word|FS|FS|FS d|0~~47|
2220
2221 **3)Configure the communication protocol**
2222
2223 [[image:image-20220830160042-1.png]]
2224
2225 [[image:image-20220830160129-2.png]]
2226
2227 **4)Cable Wiring**
2228
2229 Figure
2230
2231 [[image:image-20220830160257-4.png]]
2232
2233 Pin Definition Diagram
2234
2235 [[image:image-20220830160232-3.png]]
2236
2237 = Create communication with Inovance** PLC** =
2238
2239 == **H3U serial protocol** ==
2240
2241 **1)HMI Settings**
2242
2243 |**Item**|**Settings**|**Note**
2244 |Protocol|INOVANCE H3U PLC|
2245 |Connection|RS422|
2246 |Baud rate|9600|
2247 |Data bit|7|
2248 |Parity|EVEN|
2249 |Stop bit|1|
2250 |PLC station No.|0|
2251
2252 **2)Address List**
2253
2254 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2255 |Bit|X|X|X o|0~~303237|
2256 |Bit|Y|Y|Y o|0~~303237|
2257 |Bit|M|M|M d|0~~99999|
2258 |Bit|T|T|T d|0~~99999|
2259 |Bit|C|C|C d|0~~99999|
2260 |Bit|SM|SM|SM d|8000~~999|
2261 |Bit|S|T|S d|0~~99999|
2262 |Bit|Lamp|Lamp|Lamp d|0~~0|
2263 |Word|X|X|X o|0~~303237|
2264 |Word|Y|Y|Y o|0~~303237|
2265 |Word|M|M|M d|0~~99999|
2266 |Word|T|T|T d|0~~99999|
2267 |Word|C|C|C d|0~~199|
2268 |Word|D|D|D d|0~~7999|
2269 |Word|S|S|S d|0~~99999|
2270 |Word|SD|SD|SD d|8000~~9999|
2271 |Word|R|R|R d|0~~32767|
2272
2273 **3)Configure the communication protocol**
2274
2275 [[image:image-20220830170114-4.png]]
2276
2277 [[image:image-20220830170017-3.png]]
2278
2279
2280
2281 **4)Cable Wiring**
2282
2283 Figure
2284
2285 [[image:image-20220830165930-1.png]]
2286
2287
2288 Pin Definition Diagram
2289
2290 [[image:image-20220830165947-2.png]]
2291
2292 = Create communication with Panasonic** PLC** =
2293
2294 == **FP serial protocol** ==
2295
2296 **1)HMI Settings**
2297
2298 |**Item**|**Settings**|**Note**
2299 |Protocol|Panasonic FP MFWTOCOL|
2300 |Connection|RS232|
2301 |Baud rate|9600|
2302 |Data bit|8|
2303 |Parity|ODD|
2304 |Stop bit|1|
2305 |PLC station No.|1|
2306
2307 **2)Address List**
2308
2309 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2310 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2311 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2312 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2313 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2314 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2315 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2316 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2317 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2318 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2319 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2320 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2321 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2322 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2323 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2324 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2325
2326 **3)Configure the communication protocol**
2327
2328 [[image:image-20220830171050-1.png]]
2329
2330 [[image:image-20220830171126-2.png]]
2331
2332 **4)Cable Wiring**
2333
2334 Figure
2335
2336 [[image:image-20220830171328-4.png]]
2337
2338 Pin Definition Diagram
2339
2340 [[image:image-20220830171146-3.png]]
2341
2342 = Create communication with LS** PLC** =
2343
2344 == **XBC serial protocol** ==
2345
2346 **1)HMI Settings**
2347
2348 |**Item**|**Settings**|**Note**
2349 |Protocol|LS XBC CNet|
2350 |Connection|RS232|
2351 |Baud rate|115200|
2352 |Data bit|8|
2353 |Parity|NONE|
2354 |Stop bit|1|
2355 |PLC station No.|1|
2356
2357 **2)Address List**
2358
2359 |**Type**|(% style="width:398px" %)**Device registers**|(% style="width:331px" %)**HMI registers**|**Format**|**Range**|**Note**
2360 |Bit|(% style="width:398px" %)P|(% style="width:331px" %)P|P d|0~~2047|
2361 |Bit|(% style="width:398px" %)M|(% style="width:331px" %)M|M d|0~~2047|
2362 |Bit|(% style="width:398px" %)L|(% style="width:331px" %)L|L d|0~~11263|
2363 |Bit|(% style="width:398px" %)K|(% style="width:331px" %)K|K d|0~~16183|
2364 |Bit|(% style="width:398px" %)F|(% style="width:331px" %)F|F d|0~~2047|
2365 |Bit|(% style="width:398px" %)D|(% style="width:331px" %)D|D d|0~~32767|
2366 |Bit|(% style="width:398px" %)R|(% style="width:331px" %)R|R d|0~~32767|
2367 |Bit|(% style="width:398px" %)U|(% style="width:331px" %)U|U d|0~~4095|
2368 |Word|(% style="width:398px" %)P|(% style="width:331px" %)P|P d|0~~2047|
2369 |Word|(% style="width:398px" %)M|(% style="width:331px" %)M|M d|0~~2047|
2370 |Word|(% style="width:398px" %)L|(% style="width:331px" %)L|L d|0~~11263|
2371 |Word|(% style="width:398px" %)K|(% style="width:331px" %)K|K d|0~~16183|
2372 |Word|(% style="width:398px" %)F|(% style="width:331px" %)F|F d|0~~2047|
2373 |Word|(% style="width:398px" %)C|(% style="width:331px" %)C|C d|0~~2047|
2374 |Word|(% style="width:398px" %)T|(% style="width:331px" %)T|T d|0~~2047|
2375 |Word|(% style="width:398px" %)D|(% style="width:331px" %)D|D d|0~~32767|
2376 |Word|(% style="width:398px" %)N|(% style="width:331px" %)N|N d|0~~21503|
2377 |Word|(% style="width:398px" %)R|(% style="width:331px" %)R|R d|0~~32767|
2378 |Word|(% style="width:398px" %)U|(% style="width:331px" %)U|U d|0~~4095|
2379 |Word|(% style="width:398px" %)Z|(% style="width:398px" %)Z|Z d|0~~127|
2380 |Word|(% style="width:398px" %)S|(% style="width:331px" %)S|S d|0~~127|
2381
2382 **3)Configure the communication protocol**
2383
2384 [[image:image-20220831170807-1.png]]
2385
2386 [[image:image-20220830174733-2.png]]
2387
2388
2389
2390 **4)Cable Wiring**
2391
2392 Figure
2393
2394 [[image:image-20220830174659-1.png]]
2395
2396 Pin Definition Diagram
2397
2398 [[image:image-20220830173402-8.png]]
2399
2400 == **XGK FEnet Ethernet protocol** ==
2401
2402 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2403
2404 **HMI Settings**
2405
2406 |**Items**|**Settings**|**Note**
2407 |Protocol|LG XGK FEnet(Ethernet)|
2408 |Connection|Ethernet|
2409 |Port No.|2004|
2410
2411 **Address List**
2412
2413 |**Type**|**Register**|**Range**|**Format**|**Note**
2414 |(% rowspan="14" %)Word|P|0~~2047|P d|
2415 |M|0~~2047|M d|
2416 |K|0~~2047|K d|
2417 |F|0~~2047|F d|
2418 |T|0~~2047|T d|
2419 |C|0~~2047|C d|
2420 |Z|0~~127|Z d|
2421 |S|0~~127|S d|
2422 |L|0~~11263|L d|
2423 |N|0~~21503|N d|
2424 |D|0~~32767|D d|
2425 |R|0~~32767|R d|
2426 |ZR|0~~65535|ZR d|
2427 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2428
2429 **✎Note:**
2430
2431 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2432 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2433 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2434
2435 **Communication settings in HMI**
2436
2437 Enable HMI Ethernet in [Project Settings];
2438
2439 (% style="text-align:center" %)
2440 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2441
2442 Set PLC IP in [Device IP] settings;
2443
2444 (% style="text-align:center" %)
2445 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2446
2447 **Cable Wiring**
2448
2449 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2450
2451 = Create communication with **SHIMADEN PLC** =
2452
2453 == **FP23 series protocol** ==
2454
2455 Supported series: SHIMADEN FP23 series
2456
2457 **HMI Setting**
2458
2459 |**Items**|**Settings**|**Note**
2460 |Protocol|SHIMADEN FP23 series|
2461 |Connection|RS485 (9600, 1, 7, EVEN)|
2462 |Port No.|None|
2463 |PLC station No.|0|
2464
2465 **Address List**
2466
2467 |**Device address**|**HMI register**|**Address range**|**Type**
2468 |0040-0043(HEX)|FP040|100064-200067|Read only
2469 |0100-010B(HEX)|FP100|100256-200267|Read only
2470 |0110-0142(HEX)|FP110|100272-200322|Read only
2471 |0182-0252(HEX)|FP182|100386-200594|Write only
2472 |0280-0281(HEX)|FP280|100640-200641|Read only
2473 |0300-030B(HEX)|FP300|100768-200779|Read and write
2474 |0380-039F(HEX)|FP380|100896-200927|Read and write
2475 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2476 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2477 |0600-0670(HEX)|FP600|101536-201814|Read and write
2478 |0720-0738(HEX)|FP720|101824-201848|Read and write
2479 |0800-083F(HEX)|FP800|102048-202111|Read and write
2480 |0900-0952(HEX)|FP900|102304-202386|Read and write
2481 | |Ctrl|0-2|
2482
2483 **✎Note:**
2484
2485 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2486 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2487 * The Ctrl register is used to store the control group number and BCC check mode.
2488
2489 **Ctrl Register Description**
2490
2491 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2492 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2493 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2494 * Ctrl3 reserved
2495
2496 **✎Note:**
2497
2498 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2499
2500 **Cable Wiring**
2501
2502 (% style="text-align:center" %)
2503 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2504
2505 (% style="text-align:center" %)
2506 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2507
2508 **✎Note:** COM3 only available in PI8000/PI9000 series.
2509
2510 == **SR90 protocol** ==
2511
2512 Supported series: SHIMADEN SR90 series
2513
2514 **HMI Setting**
2515
2516 |**Items**|**Settings**|**Note**
2517 |Protocol|SHIMADEN SR90 protocol|
2518 |Connection|RS485 (1200, 1, 7, EVEN)|
2519 |Port No.|None|
2520 |PLC station No.|0|
2521
2522 **Address List**
2523
2524 |**Device address**|**HMI register**|**Address range**|**Type**
2525 |0040-0043 (HEX)|SR040|100064-100067|Read only
2526 |0100-010A(HEX)|SR0100|100256-100266|Read only
2527 |0182-018C(HEX)|SR0182|100386-100396|Write only
2528 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2529 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2530 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2531 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2532 | |Ctrl|0-2|~-~-
2533
2534 **✎Note:**
2535
2536 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2537 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2538 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2539
2540 **Ctrl Register Description**
2541
2542 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2543 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2544 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2545 * Ctrl3 reserved
2546
2547 **✎Note:**
2548
2549 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2550
2551 **Cable Wiring**
2552
2553 (% style="text-align:center" %)
2554 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2555
2556 (% style="text-align:center" %)
2557 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2558
2559 **✎Note:** COM3 only available in PI8000/PI9000 series.
2560
2561 == **MR13 series(standard protocol)** ==
2562
2563 Supported series: SHIMADEN MR13 series
2564
2565 **HMI Setting**
2566
2567 |**Items**|**Settings**|**Note**
2568 |Protocol|SHIMADEN standard protocol|
2569 |Connection|RS485 (1200, 1, 7, EVEN)|
2570 |Port No.|None|
2571 |PLC station No.|0|
2572
2573 **Address List**
2574
2575 |**Device address**|**HMI register**|**Address range**|**Type**
2576 |0100-010B(HEX)|MR100|100256-300267|Read only
2577 |0111-0126(HEX)|MR111|100273-300294|Read only
2578 |0184-0192(HEX)|MR184|100388-300402|Write only
2579 |0280-0282(HEX)|MR280|100640-300642|Read only
2580 |0300-030B(HEX)|MR300|100768-300779|Read/write
2581 |0314-0317(HEX)|MR314|100788-300791|Read/write
2582 |031A(HEX)|MR31A|100794-300794|Read/write
2583 |0320-0321(HEX)|MR320|100800-300801|Read/write
2584 |0400-0504(HEX)|MR400|101024-301284|Read/write
2585 |0506(HEX)|MR506|101286-301286|Read/write
2586 |0510-0514(HEX)|MR510|101296-301300|Read/write
2587 |0516-0524(HEX)|MR516|101302-301316|Read/write
2588 |0526(HEX)|MR526|101318-301318|Read/write
2589 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2590 |~-~-|Ctrl|0-2|~-~-
2591
2592 **✎Note:**
2593
2594 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2595 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2596 * The Ctrl register is used to store the control group number and BCC check mode.
2597
2598 **Ctrl Register Description**
2599
2600 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2601 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2602 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2603 * Ctrl3 reserved
2604
2605 **✎Note:**
2606
2607 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2608
2609 **Cable Wiring**
2610
2611 (% style="text-align:center" %)
2612 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2613
2614 (% style="text-align:center" %)
2615 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2616
2617 **✎Note:** COM3 only available in PI8000/PI9000 series.
2618
2619 = Create communication with **MODBUS** =
2620
2621 == **MODBUS RTU Master** ==
2622
2623 Supported Series: MODBUS RTU CONTROLLER
2624
2625 HMI works as MODBUS SLAVE connecting with MASTER
2626
2627 (% style="text-align:center" %)
2628 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2629
2630
2631 (% style="text-align:center" %)
2632 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2633
2634
2635 (% style="text-align:center" %)
2636 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2637
2638 **HMI Settings**
2639
2640 (% class="table-bordered" %)
2641 |**Items**|**Settings**|**Note**
2642 |Protocol|MODBUS RTU Master|
2643 |Connection|RS485/RS232|
2644 |Baud rate|2400~~187500|
2645 |Data bit|8|
2646 |Parity|Even/ Odd/ None|
2647 |Stop bit|1/2|
2648 |Station No.|0~~255|
2649
2650 **Address List**
2651
2652 (% class="table-bordered" %)
2653 |**Type**|**HMI address**|**MODBUS code**|**Range**
2654 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
2655 |Word|HDW3500~~HDW7999|4|0~~4499
2656
2657 **Cable Wiring**
2658
2659 * **RS485**
2660
2661 (% style="text-align:center" %)
2662 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2663
2664 (% style="text-align:center" %)
2665 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2666
2667 * **RS232**
2668
2669 (% style="text-align:center" %)
2670 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2671
2672 **✎Note:** COM3 only available in PI8000/PI9000 series.
2673
2674 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
2675
2676 Supported Series: MODBUS RTU CONTROLLER
2677
2678 HMI works as MODBUS MASTER connecting with SLAVE.
2679
2680 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
2681
2682 (% style="text-align:center" %)
2683 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2684
2685
2686 (% style="text-align:center" %)
2687 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2688
2689
2690 (% style="text-align:center" %)
2691 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2692
2693 **HMI Settings**
2694
2695 (% class="table-bordered" %)
2696 |**Items**|**Settings**|**Note**
2697 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2698 |Connection|RS485/RS232|
2699 |Baud rate|2400~~187500|
2700 |Data bit|8|
2701 |Parity|Even/ Odd/ None|
2702 |Stop bit|1/2|
2703 |PLC station No.|0~~255|
2704
2705 **Address List**
2706
2707 (% class="table-bordered" %)
2708 |**Type**|**Address Type**|**Function code & Description**
2709 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2710 |06 (write single register: write a binary value to a holding register)
2711 |10 (write values to multiple addresses )
2712 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2713 |06 (write single register: write a binary value to a holding register)
2714 |10 (write values to multiple addresses )
2715 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2716 |06 (write single register: write a binary value to a holding register)
2717 |10 (write values to multiple addresses )
2718 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2719 |10 (write values to multiple addresses )
2720 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2721 |05 (Force a single coil to force the on/off state of a logic coil)
2722 |0F (Write multiple bits, ie write continuously)
2723 |(% rowspan="3" %)1|02 (Read the input state)
2724 |05 (Force a single coil to force the on/off state of a logic coil)
2725 |0F (Write multiple bits)
2726 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2727 |05 (Force a single coil to force the on/off state of a logic coil)
2728 |0F (Write multiple bits)
2729 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2730 |0F (Write multiple bits)
2731
2732 **✎Note:**
2733
2734 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2735 * The function codes sent out are the same as those that read and write words.
2736
2737 **Station number for more than one slaves**
2738
2739 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2740
2741 (% style="text-align:center" %)
2742 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2743
2744 **Cable Wiring**
2745
2746 * **RS485**
2747
2748 (% style="text-align:center" %)
2749 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2750
2751 (% style="text-align:center" %)
2752 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2753
2754 * **RS232**
2755
2756 (% style="text-align:center" %)
2757 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2758
2759 **✎Note:** COM3 only available in PI8000/PI9000 series.
2760
2761 == **MODBUS TCP Slave (All function)** ==
2762
2763 Supported series: MODBUS TCP controller
2764
2765 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
2766
2767 (% style="text-align:center" %)
2768 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2769
2770 (% style="text-align:center" %)
2771 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2772
2773
2774 (% style="text-align:center" %)
2775 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2776
2777 **HMI Setting**
2778
2779 (% class="table-bordered" %)
2780 |**Items**|**Settings**|**Note**
2781 |Protocol|MODBUS TCP Slave (All function)|
2782 |Connection|Ethernet|
2783 |Port No.|502|
2784 |PLC station No.|1|
2785
2786 **Address List**
2787
2788 (% class="table-bordered" %)
2789 |**Type**|**Register**|**Function code & Description**
2790 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2791 |06 (write single register: write a binary value to a holding register)
2792 |10 (write values to multiple addresses )
2793 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2794 |06 (write single register: write a binary value to a holding register)
2795 |10 (write values to multiple addresses )
2796 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2797 |06 (write single register: write a binary value to a holding register)
2798 |10 (write values to multiple addresses )
2799 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2800 |10 (write values to multiple addresses )
2801 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2802 |05 (Force a single coil to force the on/off state of a logic coil)
2803 |0F (Write multiple bits, ie write continuously)
2804 |(% rowspan="3" %)1|02 (Read the input state)
2805 |05 (Force a single coil to force the on/off state of a logic coil)
2806 |0F (Write multiple bits)
2807 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2808 |05 (Force a single coil to force the on/off state of a logic coil)
2809 |0F (Write multiple bits)
2810 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2811 |0F (Write multiple bits)
2812
2813 **Communication Settings**
2814
2815 Enable HMI Ethernet in [Project Settings];
2816
2817 (% style="text-align:center" %)
2818 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2819
2820 Set PLC IP in [Device IP] settings;
2821
2822 (% style="text-align:center" %)
2823 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2824
2825 **Cable Wiring**
2826
2827 (% style="text-align:center" %)
2828 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2829
2830 = **Printer** =
2831
2832 == **TSPL label printer** ==
2833
2834 **Introduction**
2835
2836 TSPL label printer protocol supports following models.
2837
2838 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2839 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2840
2841 **Setting Step**
2842
2843 Select the protocol
2844
2845 * Create a new project, select the TSPL label printer protocol as shown below.
2846
2847 (% style="text-align:center" %)
2848 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2849
2850 Set parameters
2851
2852 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2853
2854 Printer register
2855
2856 (% class="table-bordered" %)
2857 |**Register**|**System**|**Range**|**Function**
2858 |TSPL_SP|decimal|0 - 1|Set the paper size
2859 |TSPL_PT|decimal|0 - 1999|Print text
2860 |TSPL_PQ|decimal|0 - 999|Print QR code
2861 |TSPL_PB|decimal|0 - 999|Print barcode
2862 |TSPL_PR|decimal|0 - 1|Print offset
2863 |TSPL_PN|decimal|0 - 0|Trigger printing
2864 |TSPL_PS|decimal|0 - 0|Print status
2865
2866 * Set paper size:
2867 ** TSPL_SP0: width of paper, unit: mm.
2868 ** TSPL_SP1: height of paper, unit: mm.
2869 * Print text:
2870 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2871 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2872
2873 (% class="table-bordered" %)
2874 |**Register**|**Function**|**Description**
2875 |TSPL_PT0|X coordinate|Unit: dot
2876 |TSPL_PT1|Ycoordinate|Unit: dot
2877 |TSPL_PT2|Rotation angle|(((
2878 0: 0 degrees
2879
2880 1: 90 degrees
2881
2882 2: 180 degrees
2883
2884 3: 270 degrees
2885 )))
2886 |TSPL_PT3|Size|Range: 0-3
2887 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2888
2889 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2890
2891 Print QR code:
2892
2893 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2894 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2895
2896 (% class="table-bordered" %)
2897 |**Register**|**Function**|**Description**
2898 |TSPL_PQ0|X coordinate|Unit: dot
2899 |TSPL_PQ1|Ycoordinate|Unit: dot
2900 |TSPL_PQ2|Rotation angle|(((
2901 0: 0 degrees
2902
2903 1: 90 degrees
2904
2905 2: 180 degrees
2906
2907 3: 270 degrees
2908 )))
2909 |TSPL_PQ3|Size|Range: 0-5
2910 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2911
2912 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2913
2914 Print bar code:
2915
2916 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2917 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2918
2919 (% class="table-bordered" %)
2920 |**Register**|**Function**|**Description**
2921 |TSPL_PB0|X coordinate|Unit: dot
2922 |TSPL_PB1|Ycoordinate|Unit: dot
2923 |TSPL_PB2|Rotation angle|(((
2924 0: 0 degrees
2925
2926 1: 90 degrees
2927
2928 2: 180 degrees
2929
2930 3: 270 degrees
2931 )))
2932 |TSPL_PB3|height|Unit: dot
2933 |TSPL_PB4|width|Range:0-2
2934 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2935
2936 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2937
2938 Print offset:
2939
2940 * TSPL_PR0: X coordinate offset, unit: mm;
2941 * TSPL_PR1: Y coordinate offset, unit: mm.
2942
2943 Trigger printing:
2944
2945 * TSPL_PN0 = 1: trigger the printer to start printing.
2946
2947 Printing status:
2948
2949 * TSPL_PS0 = 1: The printing is normal.
2950 * TSPL_PS0 = 1: The printing is abnormal.
2951
2952 Print picture
2953
2954 * For the function of printing pictures, please refer to the configuration of [Printer object].
2955
2956 Conversion between dot and mm
2957
2958 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2959
2960 == **EpsonTM series** ==
2961
2962 **HMI Settings**
2963
2964 (% class="table-bordered" %)
2965 |**Item**|**Settings**|**Note**
2966 |Protocol|EPSON-TM-T82II/TM-XXX|
2967 |Connection|RS232|
2968 |Baud rate|9600~~115200|
2969 |Data bit|8|
2970 |Parity|None|
2971 |Stop bit|1|
2972 |PLC station No.|1|
2973
2974 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2975
2976 **Printer Settings**
2977
2978 (% class="table-bordered" %)
2979 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2980 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2981 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2982 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2983 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2984 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2985 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2986
2987 **Cable Wiring**
2988
2989 (% style="text-align:center" %)
2990 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2991
2992 (% style="text-align:center" %)
2993 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2994
2995 **✎Note:** COM3 only available in PI8000/PI9000 series.
2996
2997
2998 (% class="wikigeneratedid" %)
2999 = Create communication with **Schneider PLC** =
3000
3001 == **Schneider MODBUS RTU** ==
3002
3003 **HMI Setting**
3004
3005 |=**Parameters**|=**Recommended**|=**Notes**
3006 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3007 |Connection|RS485|
3008 |**Baud rate**|19200|
3009 |**Data bit**|8|
3010 |**Parity**|Even|
3011 |**Stop bit**|1|
3012 |**PLC station No.**|1|
3013
3014 **PLC Setting**
3015
3016 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3017
3018 **Device Address**
3019
3020 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3021 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3022 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3023 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3024 |W|MW|DDDDDD|0 ~~ 999999|Output register
3025 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3026
3027 **Wiring Diagram**
3028
3029 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3030
3031 (% style="text-align:center" %)
3032 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3033
3034 = **Barcode Scanner** =
3035
3036 Supported: DELI 14880 barcode scanner
3037
3038 **HMI Setting**
3039
3040 |**Items**|**Settings**|**Note**
3041 |Protocol|Barcode Scanner|
3042 |Connection|USB|
3043
3044 **Operating Procedures**
3045
3046 Select [Barcode Scanner];
3047
3048 (% style="text-align:center" %)
3049 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3050
3051 Set address for receiving;
3052
3053 Set correct length;
3054
3055 (% style="text-align:center" %)
3056 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3057
3058 **✎Note:**
3059
3060 * The protocol uploads the information acquired by the USB scanner to the HMI;
3061 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3062 * Recommended model: DELI 14880 barcode scanner;
3063
3064 = **Hitachi EHV Series (Ethernet)** =
3065
3066 Supported series: Hitachi EHV series
3067
3068 **HMI Settings**
3069
3070 (% class="table-bordered" %)
3071 |**Items**|**Settings**|**Note**
3072 |Protocol|Hitachi EHV series|
3073 |Connection|Ethernet|
3074 |Port No.|3004~~3007|
3075
3076 **Address List**
3077
3078 (% class="table-bordered" %)
3079 |**Type**|**Register**|**Range**|**Format**|**Note**
3080 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3081 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3082 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3083 H1H2H3H4 Module main number
3084
3085 H1: Remote number
3086
3087 H2: Unit number
3088
3089 H3: Slot number
3090
3091 H4: Word number of Module
3092
3093 H Sub number of Module
3094
3095 For example:X21.3
3096
3097 Slot number 2
3098
3099 Word number of module is 1
3100
3101 Bit number of module is 3
3102
3103 Remote number and unit number are 0
3104 )))
3105 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3106 |R|0 – FF.f (Hex)|R HH.h|
3107 |L|0 - 73FF.f (Hex)|L HHHH.h|
3108 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3109 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3110 H1H2H3H4 Module main number
3111
3112 H1: Remote number
3113
3114 H2: Unit number
3115
3116 H3: Slot number
3117
3118 H4: Word number of module
3119
3120 For example:WX21
3121
3122 Word number of module is 1
3123
3124 Slot number is 2
3125
3126 Remote number and unit number are 0
3127 )))
3128 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3129 |WR|0 – FFFF (Hex)|WR HHHH|
3130 |WL|0 - 73FF (Hex)|WL HHHH|
3131 |TC|0 - 2559|TC DDDD|
3132
3133 **Communication settings in HMI**
3134
3135 Enable HMI Ethernet in [Project Settings];
3136
3137 (% style="text-align:center" %)
3138 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3139
3140 Set PLC IP in [Device IP] settings;
3141
3142 (% style="text-align:center" %)
3143 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3144
3145 **PLC Configuration**
3146
3147 Connect with PLC, select[Online mode];
3148
3149 (% style="text-align:center" %)
3150 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3151
3152 Set IP address, it is the same LAN parameters with HMI;
3153
3154 (% style="text-align:center" %)
3155 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3156
3157 3) Save PLC communication parameter, and restart PLC
3158
3159 **PLC Monitor Mode**
3160
3161 Connect with PLC and choose to “online” mode
3162
3163 (% style="text-align:center" %)
3164 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3165
3166 Open I/O monitor sheet1
3167
3168 (% style="text-align:center" %)
3169 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3170
3171 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3172
3173 (% style="text-align:center" %)
3174 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3175
3176 Enter the register address, click OK to view the value of the register.
3177
3178 (% style="text-align:center" %)
3179 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3180
3181 (% style="text-align:center" %)
3182 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3183
3184 **✎Note:**
3185
3186 * Both word registers and bit registers support even continuous read/write functions;
3187 * The range of registers is based on the specific PLC type;
3188
3189 **Cable Wiring**
3190
3191 (% style="text-align:center" %)
3192 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3193
3194 = **IEC60870-5 104 Client** =
3195
3196 **HMI Setting**
3197
3198 (% class="table-bordered" %)
3199 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3200 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3201 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3202 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3203
3204 **Address List**
3205
3206 (% class="table-bordered" %)
3207 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3208 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3209 |(% style="width:461px" %)SCNA|0~~16777215.7
3210 |(% style="width:461px" %)DPTB|0~~16777215.7
3211 |(% style="width:461px" %)DCNA|0~~16777215.7
3212 |(% style="width:461px" %)METF|0~~16777215.7
3213 |(% style="width:461px" %)SENC|0~~16777215.7
3214 |(% style="width:461px" %)SENA|0~~16777215.7
3215 |(% style="width:461px" %)MENA|0~~16777215.7
3216 |(% style="width:461px" %)METD|0~~16777215.7
3217 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3218 |(% style="width:461px" %)SCNA|0~~16777215
3219 |(% style="width:461px" %)DPTB|0~~16777215
3220 |(% style="width:461px" %)DCNA|0~~16777215
3221 |(% style="width:461px" %)SENA|0~~16777215
3222 |(% style="width:461px" %)MENA|0~~16777215
3223 |(% style="width:461px" %)METD|0~~16777215
3224 |(% style="width:461px" %)INRO|0~~16777215
3225 |(% style="width:461px" %)TIMESYN|0~~16777215
3226 |(% style="width:461px" %)TIMEZ|0~~16777215
3227 |(% style="width:461px" %)NTP|0~~16777215
3228 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3229 |(% style="width:461px" %)SENC|0~~16777215
3230
3231 **Address Configuration**
3232
3233 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3234
3235 (% style="text-align:center" %)
3236 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3237
3238 (% style="text-align:center" %)
3239 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3240
3241 Extended tag name
3242
3243 Address range for the extended tag.
3244
3245 **Communication Settings**
3246
3247 Enable HMI Ethernet in [Project Settings];
3248
3249 (% style="text-align:center" %)
3250 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3251
3252 Set PLC IP in [Device IP] settings;
3253
3254 (% style="text-align:center" %)
3255 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3256
3257 **Cable Wiring**
3258
3259 (% style="text-align:center" %)
3260 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3261
3262 = **OpenCAN** =
3263
3264 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3265
3266 This protocol is only available in PI8000 series HMI.
3267
3268 **HMI Settings**
3269
3270 |**Items**|**Settings**|**Note**
3271 |Protocol|OPENCAN|
3272 |Connection|CAN port|
3273 |Baud rate|250000|
3274
3275 **CAN frame setting in HMI**
3276
3277 Click [OpenCAN setting] button in communication setting window;
3278
3279 (% style="text-align:center" %)
3280 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3281
3282 Click [Add] to create a new frame;
3283
3284 (% style="text-align:center" %)
3285 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3286
3287 |**No**|**Items**|**Description**
3288 |1|Add|add a frame related to register address
3289 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3290 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3291 |4|Modify|Modify the frames in frame management
3292 |5|Copy|Copy one frame to another
3293 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3294 |7|Empty|All frames in the list are cleared
3295 |8|Browse|Displays configuration files in XML format in IE
3296 |9|OK|Complete the configuration of the frame and exit
3297
3298 Set CANBUS frame in setting windows
3299
3300 (% style="text-align:center" %)
3301 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3302
3303 |**No**|**Items**|**Description**
3304 |1|ID|Set the ID of a can frame in hexadecimal format;
3305 |2|ID assign|split the ID by PF, PS, and SA;
3306 |3|Frame type|Select Standard frame or Extended Frame;
3307 |4|Frame format|Select between data frame and remote Frame;
3308 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3309 |6|Use address|(((
3310 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3311
3312 **Edit:** Set a bit or word address by its format;
3313
3314 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3315 )))
3316 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3317 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3318 |Feedback mode: feedback mode includes no response, confirm response and data response;
3319 |No response: the device or touch screen will not receive feedback;
3320 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3321 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3322 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3323 |Response timeout: sets whether the response frame timeout;
3324 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3325 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3326 |Manually send: a manually send tick indicates only one send;
3327 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3328 |10|Note|Fill the text to explain the meaning of the frame;
3329 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3330 |12|Current operation display|Display the description of current operation;
3331 |13|Add|Add a new frame;
3332 |14|Save frame|Save the configured frame format;
3333 |15|Cancel|Cancel the frame configuration;
3334
3335 Set CAN address (Read or write operation);
3336
3337 (% style="text-align:center" %)
3338 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3339
3340 |**No.**|**Item**|**Description**
3341 |1|Current address|Displays the register type and register address set by the user in the data access interface
3342 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3343 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3344 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3345 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3346 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3347 |If the trigger condition is a writing operation, there are two situations:(((
3348 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3349 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3350 )))
3351 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3352 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3353 |4|Add|Add current configuration
3354 |5|Close|Close the configuration window to exit
3355
3356 **Multiple Packages Settings**
3357
3358 (% style="text-align:center" %)
3359 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3360
3361 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3362
3363 Select Multiple package type
3364
3365 * Not Multiple packages
3366 * J1939 Multiple packages
3367 * Customized Multiple packages
3368
3369 Click [Edit Receive data] for [Receive] settings
3370
3371 * Start code+ Total length (J1939)
3372
3373 (% style="text-align:center" %)
3374 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3375
3376 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3377
3378 * Start code + Data max length (J1939)
3379
3380 (% style="text-align:center" %)
3381 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3382
3383 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3384
3385 * Data max length (J1939)
3386
3387 (% style="text-align:center" %)
3388 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3389
3390 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3391
3392 * Customized multiple package
3393
3394 (% style="text-align:center" %)
3395 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3396
3397 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3398
3399 Click [Edit Send data] for [Send] setting
3400
3401 * J1939
3402
3403 (% style="text-align:center" %)
3404 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3405
3406 [Data] is all data to be sent.
3407
3408 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3409
3410 * Customized multiple package
3411
3412 (% style="text-align:center" %)
3413 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3414
3415 [Data] is all data to be sent.
3416
3417 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3418
3419 **Cable Wiring**
3420
3421 (% style="text-align:center" %)
3422 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3423
3424 **✎Note:** The address interval between each frame need to be more than a word address;
3425
3426
3427 = **User Defined Protocol** =
3428
3429 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
3430
3431 **HMI Settings**
3432
3433 |**Items**|**Settings**|**Note**
3434 |Protocol|User defined protocol|
3435 |Connection|RS485/RS232|
3436 |Baud rate|2400~~187500|
3437 |Stop bits|1/ 2|
3438 |Data bits|7/ 8|
3439 |Parity|None/ Even/ ODD|
3440
3441 **Operating Procedures**
3442
3443 Select [User defined protocol];
3444
3445 Click [User defined protocol] button to open setting window as below;
3446
3447 (% style="text-align:center" %)
3448 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
3449
3450 Configure user defined command;
3451
3452 (% style="text-align:center" %)
3453 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
3454
3455 |**No**|**Item**|**Description**
3456 |1|Instruction edit|The required command.
3457 |2|Mode|Write to address or read from the address.
3458 |3|Format|Encode format: HEX or ASCII.
3459 |4|Other|(((
3460 **No receiving: **HMI does not respond to the receiving command.
3461
3462 **Send after receiving:** HMI responds to the receiving command.
3463 )))
3464 |5|Manually send|(((
3465 Respond once after trigger the address.
3466
3467 Address: set the trigger address.
3468 )))
3469 |6|Add|Save this setting.
3470 |7|Cancel|Cancel current settings.
3471 |(% rowspan="4" %)8|Add|Add a new command.
3472 |Edit|Edit the selected command.
3473 |Delete|Delete the selected command.
3474 |Clear|Clear all the commands.
3475 |9|Instruction list|Display all current commands.
3476 |10|Address List|Display all the addresses added.
3477 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
3478 |Export|Export current command settings to local storage.
3479 |Browse|Browse local command files.
3480 |Advanced|Combine two commands.
3481 |Exit|Complete editing and exit setting.
3482
3483 **Operating Procedures**
3484
3485 Click [Add] to create a new command, as below shows;
3486
3487 (% style="text-align:center" %)
3488 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
3489
3490 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
3491
3492 (% style="text-align:center" %)
3493 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
3494
3495 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
3496
3497 (% style="text-align:center" %)
3498 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
3499
3500 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
3501
3502 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
3503
3504 Check settings;
3505
3506 (% style="text-align:center" %)
3507 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3508
3509 |**No**|**Items**|**Description**
3510 |1|Add checking|Add checking command when receiving the data.
3511 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
3512 |Differ with send check|Set return checking.
3513 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
3514 |Length: The data length need to be checked.
3515
3516 Object settings;
3517
3518 (% style="text-align:center" %)
3519 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3520
3521 |**No**|**Items**|**Description**
3522 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
3523 |Address: the triggering address;
3524 |Note: description to object;
3525 |2|Byte order|The numerical display order;
3526
3527 Data length settings;
3528
3529 (% style="text-align:center" %)
3530 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3531
3532 |**No**|**Item**|**Description**
3533 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
3534 |Length: the return data length.
3535 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
3536 |Length: the write data length.
3537
3538 Instruction length settings
3539
3540 (% style="text-align:center" %)
3541 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3542
3543 |**No**|**Item**|**Description**
3544 |1|Send length|The instruction data will only send designated data length.
3545 |2|Return length|The responds data length.
3546 |3|End code|Instruction will not be terminated until receiving [End code];
3547
3548 **Cable Wiring**
3549
3550 * **RS485**
3551
3552 (% style="text-align:center" %)
3553 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3554
3555 (% style="text-align:center" %)
3556 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3557
3558 * **RS232**
3559
3560 (% style="text-align:center" %)
3561 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
3562
3563 **✎Note:** COM3 only available in PI8000/PI9000 series.