Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 198.1 by Hunter on 2022/11/14 18:49

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with **Rockwell PLC** =
459
460 == **DF1 Protocol** ==
461
462 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
467 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
468 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
469 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
470 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
471 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
472 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
473 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
474 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
475
476 **Address List**
477
478 (% class="table-bordered" %)
479 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
480 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
481 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
482 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
483 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
484 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
485 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
486 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
487 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
488 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
489 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
490 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
491
492 == **MicroLogix Protocol** ==
493
494 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
495
496 **HMI Settings**
497
498 (% class="table-bordered" %)
499 |**Item**|**Settings**|**Note**
500 |Protocol|Allen-Bradlley MicroLogix|
501 |Connection|RS232|
502 |Baud rate|19200|
503 |Data bit|8|
504 |Parity|None|
505 |Stop bit|1|
506 |PLC station No.|1|
507
508 **Address List**
509
510 (% class="table-bordered" %)
511 |**Type**|**Device registers**|**Format**|**Range**|**Note**
512 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
513 |O|O d.d|0.0~~255.15|
514 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
515 |S|S d.d|0.0~~255.15|
516 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
517 |(% rowspan="9" %)Word|S|S d|0~~255|
518 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
519 |TP|TP nnhh|0~~ffff
520 |CS|CS nnhh|0~~ffff
521 |CP|CP nnhh|0~~ffff
522 |N|N nnhh|0~~ffff
523 |C|C nnhh|0~~ffff
524 |T|T nnhh|0~~ffff
525 |R|R nnhh|0~~ffff
526
527 **Cable Wiring**
528
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
532
533 == **CompactLogix FreeTag Ethernet protocol** ==
534
535 Allen-Brandly CompactLogix
536
537 **HMI Settings**
538
539 (% class="table-bordered" %)
540 |**Items**|**Settings**|**Note**
541 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
542 |Connection|Ethernet|
543 |Port No.|44818|
544
545 **PLC Setting**
546
547 Create new tags
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
551
552 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
553
554 (% style="text-align:center" %)
555 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
556
557 Import labels, please open [Communication] window and click [Import label];
558
559 Select csv file, all tags will be displayed as belows;
560
561 (% style="text-align:center" %)
562 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
563
564 **✎Note:**
565
566 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
570
571 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
572
573 **Communication settings in HMI**
574
575 Enable HMI Ethernet in [Project Settings];
576
577 (% style="text-align:center" %)
578 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
579
580 Set PLC IP in [Device IP] settings;
581
582 (% style="text-align:center" %)
583 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
584
585 **Cable Wiring**
586
587 (% style="text-align:center" %)
588 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
589
590 == **MicroLogix 1200** ** protocol** ==
591
592 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
593
594 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
595 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
596 * **Word address S:** The word address ranges from 0 to 255 (decimal).
597 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
598
599 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
600
601 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
602 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
603 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
604 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
605 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
606 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
607 |**PLC word address type**|**Address format**|**Address range**
608 |S|ddd|S0 ~~ 255
609 |TS|ffff|TS0 ~~ FFFF
610 |TP|ffff|TP0 ~~ FFFF
611 |CS|ffff|CS0 ~~ FFFF
612 |CP|ffff|CP0 ~~ FFFF
613 |N|ffff|N0 ~~ FFFF
614 |F|ffff|F0 ~~ FFFF
615
616 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
617
618 == **S7-200 Smart Ethernet Protocol** ==
619
620 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
621
622 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
623
624 **HMI Setting**
625
626 (% class="table-bordered" %)
627 |**Items**|**Settings**|**Note**
628 |Protocol|Simens S7-200 Smart Ethernet|
629 |Connection|Ethernet|
630 |Port No.|102|
631 |PLC station No.|2|
632
633 **Address List**
634
635 (% class="table-bordered" %)
636 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
637 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
638 |Q|Q|Q ddddd.o|0.0~~99999.7|
639 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
640 |V|V|V ddddd.o|0.0~~99999.7|
641 |M|M|M ddddd.o|0.0~~99999.7|
642 |SM|SM|ddddd.o|0.0~~99999.7|
643 |S|S|ddddd.o|0.0~~99999.7|Read only
644 |T|T|ddddd|0~~99999|Timer state, read only
645 |C|C|ddddd|0~~99999|Counter state, read only
646 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
647 |Q|QW|QW ddddd|0~~99999|
648 |AI|AIW|AIW ddddd|0~~99999|
649 |AQ|VB|VB ddddd|0~~99999|
650 |V|VW|VW ddddd|0~~99998|(((
651 VW0=VB (0~~1)
652
653 VW2=VB (2~~3)
654
655 Address value is a multiple of 2
656 )))
657 |V|VD|VD ddddd|0~~99998|(((
658 VD0=VB (0~~3)
659
660 VD2=VB (4~~7)
661
662 Address value is a multiple of 4
663 )))
664 |M|MB|MB ddddd|0~~99999|
665 |M|MW|MW ddddd|0~~99999|(((
666 MW0=MB(0~~1)
667
668 MW2=MB(2~~3)
669
670 Address value is a multiple of 2
671 )))
672 |M|MD|MD ddddd|0~~99999|(((
673 MD0=MB(0~~3)
674
675 MD4=MB(4~~7)
676
677 Address value is a multiple of 4
678 )))
679 |T|TW|TW ddddd|0~~99999|Value of timer
680 |C|CW|CW ddddd|0~~99999|Value of counter
681 |W|SW|SW ddddd|0~~99999|
682
683 **Communication Settings**
684
685 Enable HMI Ethernet in [Project Settings];
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
689
690 Set PLC IP in [Device IP] settings;
691
692 (% style="text-align:center" %)
693 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
694
695 * PLC IP Address: PLC IP
696 * PLC pot No.: 102(fixed)
697 * Network:TCP_Client_2N(fixed)
698
699 (% style="text-align:center" %)
700 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
701
702 * Wait timeout: depend on actual network situation (more than 1500 ms)
703
704 **Cable Wiring**
705
706 (% style="text-align:center" %)
707 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
708
709 == **S7-300 Ethernet Protocol** ==
710
711 Supported Series: Siemens S7-300 series PLC
712
713 **HMI Setting**
714
715 (% class="table-bordered" %)
716 |**Items**|**Settings**|**Note**
717 |Protocol|Simens S7-300 Ethernet|
718 |Connection|Ethernet|
719 |Port No.|102|
720 |PLC station No.|2|Need to be same as the PLC setting
721
722 **Address List**
723
724 (% class="table-bordered" %)
725 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
726 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
727 |Q|Q|Q ddddd.o|0.0~~99999.7|
728 |M|M|M ddddd.o|0.0~~99999.7|
729 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
730 nn: block number;
731
732 dddd: address;
733 )))
734 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
735 |Q|QW|QW ddddd|0~~99999|
736 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
737 |MW|MW ddddd|0~~99999|(((
738 MW0=MB(0~~1)
739
740 MW2=MB(2~~3)
741
742 Address value is a multiple of 2
743 )))
744 |MD|MD ddddd|0~~99999|(((
745 MD0=MB(0~~3)
746
747 MD4=MB(4~~7)
748
749 Address value is a multiple of 4
750 )))
751 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
752 nn: block number;
753
754 dddd: address
755 )))
756 |DBxDBW|DBxDBW nndddd|0~~99999999
757 |DBxDBD|DBxDBD nndddd|0~~99999999
758
759 **Communication Settings**
760
761 Enable HMI Ethernet in [Project Settings];
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
765
766 Set PLC IP in [Device IP] settings;
767
768 (% style="text-align:center" %)
769 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
770
771 * PLC IP Address: PLC IP
772 * PLC pot No.: 102(fixed)
773 * Network:TCP_Client_2N(fixed)
774
775 (% style="text-align:center" %)
776 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
777
778 * Wait timeout: depend on actual network situation (more than 1500 ms)
779
780 **Cable Wiring**
781
782 (% style="text-align:center" %)
783 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
784
785 == **S7-1200 Ethernet Protocol** ==
786
787 Supported Series: Siemens S7-1200
788
789 **HMI Setting**
790
791 (% class="table-bordered" %)
792 |**Items**|**Settings**|**Note**
793 |Protocol|Siemens S7-1200|
794 |Connection|Ethernet|
795 |Port No.|102|
796 |PLC station No.|2|
797
798 **Address List**
799
800 (% class="table-bordered" %)
801 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
802 |(% rowspan="4" %)Bit|I|I|M d.o|(((
803 d:0~-~-9999
804
805 o:0-7
806 )))|
807 |Q|Q|Q d.o|(((
808 d:0~-~-9999
809
810 o:0-7
811 )))|
812 |M|M|M d.o|(((
813 d:0~-~-9999
814
815 o:0-7
816 )))|
817 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
818 nn:0-9999,
819
820 dddd:0-9999,
821
822 o:0-7
823 )))|(((
824 nn:DB No.
825
826 dddd:address value
827
828 o: digit address
829 )))
830 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
831 |M|MW|MW d|d:0-99999|(((
832 MW0=MB(0~~1)
833
834 MW2=MB(2~~3)
835
836 Address value is a multiple of 2
837 )))
838 |M|MD|MD d|d:0-99999|(((
839 MD0=MB(0~~3)
840
841 MD4=MB(4~~7)
842
843 Address value is a multiple of 4
844 )))
845 |I|IW|IW d|d:0-99999|
846 |Q|QW|QW d|d:0-99999|
847 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
848 nn:0-9999
849
850 dddd:0-9999
851 )))|(((
852 nn:DB No.
853
854 dddd:address value
855 )))
856 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
857 nn:0-9999
858
859 dddd:0-9999
860 )))|(((
861 nn:DB No.
862
863 dddd:address value
864
865 Address value is a multiple of 2
866 )))
867 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
868 nn:0-9999
869
870 dddd:0-9999
871 )))|(((
872 nn:DB No.
873
874 dddd:address value
875
876 Address value is a multiple of 4
877 )))
878
879 **Communication Settings**
880
881 Enable HMI Ethernet in [Project Settings];
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
885
886 Set PLC IP in [Device IP] settings;
887
888 (% style="text-align:center" %)
889 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
890
891 **✎Note:**
892
893 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
894 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
895
896 **PLC Settings**
897
898 Add BD
899
900 * Please uncheck [Symbolic access only] option;
901
902 (% style="text-align:center" %)
903 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
904
905 Address settings, using BD2 as example.
906
907 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
908 * 2 represent DB block number
909 * xxxx represent address
910
911 **Such as:**
912
913 * DBxDBB20000 = DB2.DBB0
914 * DBxDBW20004 = DB2.DBW4
915
916 (% style="text-align:center" %)
917 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
918
919 **How to connect with S7-1200 Firmware V4.0**
920
921 PLC configuration
922
923 * Double click [device configuration] in Siemens via software
924 * Double click [protection] to enter protection configuration screen
925
926 (% style="text-align:center" %)
927 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
928
929 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
930
931 (% style="text-align:center" %)
932 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
933
934 DB settings
935
936 * Right click [DB], select [properties]
937 * Uncheck [optimized block access]
938
939 **Cable Wiring**
940
941 (% style="text-align:center" %)
942 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
943
944 == **S7-XXX Ethernet Protocol** ==
945
946 Supported Series: Siemens S7-400, S7-1200 and S7-1500
947
948 **HMI Setting**
949
950 (% class="table-bordered" style="width:823px" %)
951 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
952 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
953 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
954 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
955 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
956 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
957
958 Slot from TIA Portal is equal to Device No. of PIStudio
959
960 Rack from TIA Portal is equal to HMI No. of PIStudio
961
962 (% style="text-align:center" %)
963 [[image:S7-XXXCommunication Settings.png]]
964
965 (% style="text-align:center" %)
966 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
967
968 **Address List**
969
970 (% class="table-bordered" %)
971 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
972 |(% rowspan="4" %)Bit|I|I|M d.o|(((
973 d:0~-~-9999
974
975 o:0-7
976 )))|
977 |Q|Q|Q d.o|(((
978 d:0~-~-9999
979
980 o:0-7
981 )))|
982 |M|M|M d.o|(((
983 d:0~-~-9999
984
985 o:0-7
986 )))|
987 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
988 nn:0-9999,
989
990 dddd:0-9999,
991
992 o:0-7
993 )))|(((
994 nn:DB No.
995
996 dddd:address value
997
998 o: digit address
999 )))
1000 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1001 |M|MW|MW d|d:0-99999|(((
1002 MW0=MB(0~~1)
1003
1004 MW2=MB(2~~3)
1005
1006 Address value is a multiple of 2
1007 )))
1008 |M|MD|MD d|d:0-99999|(((
1009 MD0=MB(0~~3)
1010
1011 MD4=MB(4~~7)
1012
1013 Address value is a multiple of 4
1014 )))
1015 |I|IW|IW d|d:0-99999|
1016 |Q|QW|QW d|d:0-99999|
1017 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1018 nn:0-9999
1019
1020 dddd:0-9999
1021 )))|(((
1022 nn:DB No.
1023
1024 dddd:address value
1025 )))
1026 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1027 nn:0-9999
1028
1029 dddd:0-9999
1030 )))|(((
1031 nn:DB No.
1032
1033 dddd:address value
1034
1035 Address value is a multiple of 2
1036 )))
1037 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1038 nn:0-9999
1039
1040 dddd:0-9999
1041 )))|(((
1042 nn:DB No.
1043
1044 dddd:address value
1045
1046 Address value is a multiple of 4
1047 )))
1048
1049 **Communication Settings**
1050
1051 Enable HMI Ethernet in [Project Settings];
1052
1053 (% style="text-align:center" %)
1054 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1055
1056 Set PLC IP in [Device IP] settings;
1057
1058 (% style="text-align:center" %)
1059 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1060
1061 **✎Note:**
1062
1063 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1064 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1065
1066 **Cable Wiring**
1067
1068 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1069
1070 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1071
1072 Supported Series: Siemens Logo 0BA0, 0BA1 series
1073
1074 **HMI Settings**
1075
1076 (% class="table-bordered" %)
1077 |**Items**|**Settings**|**Note**
1078 |Protocol|Siemens LOGO|
1079 |Connection|Ethernet|
1080 |Port No.|102|
1081 |PLC station No.|2|
1082
1083 **Address List**
1084
1085 (% class="table-bordered" %)
1086 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1087 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1088 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1089 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1090 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1091 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1092 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1093 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1094 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1095 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1096 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1097 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1098 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1099 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1100 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1101 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1102
1103 **PLC Settings in LOGO Software:**
1104
1105 Click [Tools]~-~-[Ethernet Connections],shown as below.
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1109
1110 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1111
1112 (% style="text-align:center" %)
1113 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1114
1115 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1116
1117 (% style="text-align:center" %)
1118 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1119
1120 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1121
1122 (% style="text-align:center" %)
1123 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1124
1125
1126 (% style="text-align:center" %)
1127 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1128
1129
1130 **HMI Communication Settings**
1131
1132 Set PLC IP in [Device IP] settings;
1133
1134 (% style="text-align:center" %)
1135 [[image:SiemensLOGODeviceIP.png]]
1136
1137 Enable HMI Ethernet in [Project Settings];
1138
1139 (% style="text-align:center" %)
1140 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1141
1142 TSAP setting
1143
1144 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1145 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1146 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1147
1148 **✎Note:**
1149
1150 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1151
1152 (% style="text-align:center" %)
1153 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1154
1155
1156 * AI word address and Ibit address are read-only and cannot be written on HMI.
1157 * VW address should be even number.such as VW0, VW2, VW4...
1158 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1159 * Written value of RTC cannot exceed 255.
1160
1161 **Cable Wiring**
1162
1163 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1164
1165 == S7-300 232 ==
1166
1167 **HMI Setting:**
1168
1169 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
1170 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
1171 |=**PLC I/F**|RS232| |
1172 |=**Baud rate**|19200|9600,19200|
1173 |=**Data bits**|8| |
1174 |=**Parity**|Odd| |
1175 |=**Stop bits**|1| |
1176 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
1177
1178 **Device Address**
1179
1180 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1181 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
1182 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
1183 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
1184 |=Word|(((
1185 DB1 to DB99
1186 )))|DDDDDo|0 ~~ 655327|
1187 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
1188 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
1189 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
1190 |=Double word|MD|DDDD|0 ~~ 4094|
1191 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
1192 Data Register Double Word (must be even)
1193 )))
1194 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
1195
1196 **Cable Wiring**
1197
1198 (% style="text-align:center" %)
1199 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
1200
1201 = Create communication with **Mitsubishi PLC** =
1202
1203 == **FX1S, 1N, 2N Series Protocol** ==
1204
1205 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1206
1207 **HMI Settings**
1208
1209 (% class="table-bordered" %)
1210 |**Item**|**Settings**|**Note**
1211 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1212 |Connection|RS422/RS485/RS232|
1213 |Baud rate|9600~~115200|
1214 |Data bit|7/8|
1215 |Parity|EVEN/Odd/None|
1216 |Stop bit|1/2|
1217 |PLC station No.|1~~255|
1218
1219 **Address List**
1220
1221 (% class="table-bordered" %)
1222 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1223 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1224 |Y|Y|Y o|0~~303237|
1225 |M|M|M d|0~~99999|
1226 |T|T|T d|0~~99999|
1227 |C|C|C d|0~~99999|
1228 |S|S|S d|0~~99999|
1229 |SM|SM|SM d|8000~~9999|
1230 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1231 |Y|Y|Y o|0~~303237|
1232 |M|M|M d|0~~99999|
1233 |T|T|T d|0~~99999|
1234 |C|C|C d|0~~199|
1235 |D|D|D d|0~~7999|
1236 |S|S|S d|0~~99999|
1237 |SD|SD|SD d|8000~~9999|
1238
1239 **Cable Wiring**
1240
1241 * **RS485**
1242
1243 (% style="text-align:center" %)
1244 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1245
1246 (% style="text-align:center" %)
1247 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1248
1249 * **RS422**
1250
1251 (% style="text-align:center" %)
1252 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1253
1254 **✎Note:** COM3 only available in PI8000/PI9000 series.
1255
1256 == **FX3U/3G/3GA serial protocol** ==
1257
1258 (% class="wikigeneratedid" %)
1259 **HMI Settings**
1260
1261 |=**Item**|=**Settings**|=**Note**
1262 |Protocol|Mitsubishi FX3U/3G/3GA|
1263 |Connection|RS422|
1264 |Baud rate|9600~~115200|
1265 |Data bit|7/8|
1266 |Parity|EVEN/Odd/None|
1267 |Stop bit|1/2|
1268 |PLC station No.|1~~255|
1269
1270 (% class="wikigeneratedid" %)
1271 **Address List**
1272
1273 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1274 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1275 |Y|Y|Y o|0~~303237|
1276 |M|M|M d|0~~99999|
1277 |T|T|T d|0~~99999|
1278 |C|C|C d|0~~99999|
1279 |S|S|S d|0~~99999|
1280 |SM|SM|SM d|8000~~9999|
1281 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1282 |Y|Y|Y o|0~~303237|
1283 |M|M|M d|0~~99999|
1284 |T|T|T d|0~~99999|
1285 |C|C|C d|0~~199|
1286 |D|D|D d|0~~7999|
1287 |S|S|S d|0~~99999|
1288 |SD|SD|SD d|8000~~9999|
1289
1290 **Configure the communication protocol**
1291
1292 (% style="text-align:center" %)
1293 [[image:image-20220831095222-1.png]]
1294
1295 (% style="text-align:center" %)
1296 [[image:image-20220831095743-2.png]]
1297
1298 **Wiring**
1299
1300 (% style="text-align:center" %)
1301 [[image:image-20220831100333-7.png]]
1302
1303 Pin Definition Diagram
1304
1305 (% style="text-align:center" %)
1306 [[image:image-20220831100314-6.png]]
1307
1308 == **FX5U Ethernet Protocol** ==
1309
1310 Mitsubishi FX5U series PLC
1311
1312 **HMI Settings**
1313
1314 (% class="table-bordered" %)
1315 |**Items**|**Settings**|**Note**
1316 |Protocol|Mitsubishi FX5U|
1317 |Connection|Ethernet|
1318 |Port No.|5002|Must be the same as the PLC setting
1319 |PLC station No.|0|
1320
1321 **Address List**
1322
1323 (% class="table-bordered" %)
1324 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1325 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1326 |Y|Y|Y o|0~~303237|
1327 |M|M|M d|0~~99999|
1328 |B|B|B h|0~~7FFF|
1329 |F|F|F d|0~~32767|
1330 |SB|SB|SB h|0~~7FFF|
1331 |TS|TS|TS d|0~~1023|
1332 |TC|TC|TC d|0~~1023|
1333 |STS|STS|STS d|0~~1023|
1334 |STC|STC|STS d|0~~1023|
1335 |CS|CS|CS d|0~~1023|
1336 |CC|CC|CC d|0~~1023|
1337 |SM|SM|SM d|0~~9999|
1338 |L|L|L d|0~~32767|
1339 |S|S|S d|0~~4095|
1340 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1341 |TN|TN|TN d|0~~1023|
1342 |STN|STN|STN d|0~~1023|
1343 |CN|CN|CN d|0~~1023|
1344 |R|R|R d|0~~32767|
1345 |SW|SW|SW h|0~~7FFF|
1346 |Z|Z|Z d|0~~23|
1347 |D|D|D d|0~~7999|
1348 |SD|SD|SD d|0~~11999|
1349
1350 **PLC Settings (GX Works 3)**
1351
1352 Find the [Ethernet port] in the navigation area.
1353
1354 (% style="text-align:center" %)
1355 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1356
1357 Select [Own Node Settings] in the [Setting Item List];
1358
1359 Set [IP Address], [Subnet Mask], [Default Gateway];
1360
1361 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1362
1363 (% style="text-align:center" %)
1364 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1365
1366 Select [SLMP Connection Module] and add into host station as below picture shows;
1367
1368 Set Port number as 5002 (this is necessary settings);
1369
1370 Click [Close with Reflecting the Setting] to save and close window;
1371
1372 (% style="text-align:center" %)
1373 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1374
1375 Click [Apply] to completed Etherenet settings;
1376
1377 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1378
1379 (% style="text-align:center" %)
1380 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1381
1382 **Cable Wiring**
1383
1384 (% style="text-align:center" %)
1385 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1386
1387 == **FX5U Serial Port Protocol** ==
1388
1389 Mitsubishi FX5U series PLC
1390
1391 **HMI Settings**
1392
1393 (% class="table-bordered" %)
1394 |**Item**|**Settings**|**Note**
1395 |Protocol|Mitsubishi FX5U|
1396 |Connection|RS422/RS485|
1397 |Baud rate|9600|
1398 |Data bit|7|
1399 |Parity|Odd|
1400 |Stop bit|1|
1401 |PLC station No.|1~~255|Need to be the same as PLC settings
1402
1403 **Address List**
1404
1405 (% class="table-bordered" %)
1406 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1407 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1408 |Y|Y|Y o|0~~303237|
1409 |M|M|M d|0~~99999|
1410 |B|B|B h|0~~7FFF|
1411 |F|F|F d|0~~32767|
1412 |SB|SB|SB h|0~~7FFF|
1413 |TS|TS|TS d|0~~1023|
1414 |TC|TC|TC d|0~~1023|
1415 |STS|STS|STS d|0~~1023|
1416 |STC|STC|STS d|0~~1023|
1417 |CS|CS|CS d|0~~1023|
1418 |CC|CC|CC d|0~~1023|
1419 |SM|SM|SM d|0~~9999|
1420 |L|L|L d|0~~32767|
1421 |S|S|S d|0~~4095|
1422 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1423 |TN|TN|TN d|0~~1023|
1424 |STN|STN|STN d|0~~1023|
1425 |CN|CN|CN d|0~~1023|
1426 |R|R|R d|0~~32767|
1427 |SW|SW|SW h|0~~7FFF|
1428 |Z|Z|Z d|0~~23|
1429 |D|D|D d|0~~7999|
1430 |SD|SD|SD d|0~~11999|
1431
1432 **PLC Settings (GX Works 3)**
1433
1434 Create a blank FX5U project
1435
1436 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1437
1438 (% style="text-align:center" %)
1439 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1440
1441 Select protocol in the setting item, and set parameters.
1442
1443 (% style="text-align:center" %)
1444 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1445
1446 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1447
1448 (% style="text-align:center" %)
1449 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1450
1451 Click the [Apply] button to finish the setting.
1452
1453 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1454
1455 (% style="text-align:center" %)
1456 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1457
1458 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1459
1460 Done.
1461
1462 **Cable Wiring**
1463
1464 * **RS485**
1465
1466 (% style="text-align:center" %)
1467 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1468
1469 (% style="text-align:center" %)
1470 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1471
1472 * **RS422**
1473
1474 (% style="text-align:center" %)
1475 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1476
1477 **✎Note:** COM3 only available in PI8000/PI9000 series.
1478
1479 == **L02 Serial Protocol** ==
1480
1481 Mitsubishi L02 series CPU built-in serial port.
1482
1483 **HMI Settings**
1484
1485 |=**Item**|=**Settings**|=**Note**
1486 |Protocol|Mitsubishi L02|
1487 |Connection|RS422|
1488 |Baud rate|115200|
1489 |Data bit|8|
1490 |Parity|Odd|
1491 |Stop bit|1|
1492 |PLC station No.|1~~255|Need to be the same as PLC settings
1493
1494 **Address List**
1495
1496 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1497 |Bit|X|X|X h|0~~FFFF|
1498 |Bit|Y|Y|Y h|0~~FFFF|
1499 |Bit|M|M|M d|0~~9999|
1500 |Bit|L|L|L d|0~~9999|
1501 |Bit|F|F|F d|0~~9999|
1502 |Bit|B|B|B h|0~~FFFF|
1503 |Bit|V|V|V d|0~~2047|
1504 |Bit|TC|TC|TC d|0~~9999|
1505 |Bit|SS|SS|SS d|0~~9999|
1506 |Bit|SC|SC|SC d|0~~9999|
1507 |Bit|CS|CS|CS d|0~~9999|
1508 |Bit|CC|CC|CC d|0~~9999|
1509 |Bit|SB|SB|SB h|0~~FFFF|
1510 |Bit|SM|SM|SM d|0~~2047|
1511 |Bit|STS|STS|STS d|0~~1023|
1512 |Bit|S|S|S d|0~~9999|
1513 |Bit|DX|DX|DX h|0~~FFFF|
1514 |Bit|DY|DY|DY h|0~~FFFF|
1515 |Bit|TS|TS|TS d|0~~9999|
1516 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1517 |Word|W|W|W h|0~~FFFF|
1518 |Word|TN|TN|TN d|0~~99999|
1519 |Word|SN|SN|SN d|0~~99999|
1520 |Word|CN|CN|CN d|0~~99999|
1521 |Word|R|R|R d|0~~99999|
1522 |Word|SW|SW|SW h|0~~FFFF|
1523 |Word|Z|Z|Z d|0~~99999|
1524 |Word|ZR|ZR|ZR h|0~~FFFF|
1525 |Word|D|D|D d|0~~99999|
1526
1527 **Communication Settings**
1528
1529 (% style="text-align:center" %)
1530 [[image:image-20220831105732-3.png]]
1531
1532 (% style="text-align:center" %)
1533 [[image:image-20220831110004-5.png]]
1534
1535 **Cable Wiring**
1536
1537 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1538
1539 Pin Definition Diagram
1540
1541 (% style="text-align:center" %)
1542 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1543
1544 == **L02 MELSEC (Ethernet) Protocol** ==
1545
1546 Mitsubishi Q series CPU built-in Ethernet port.
1547
1548 **HMI Settings**
1549
1550 (% class="table-bordered" %)
1551 |**Items**|**Settings**|**Note**
1552 |Protocol|MIT L02 CPU MELSEC|
1553 |Connection|Ethernet|
1554 |Port No.|1025|Must be the same as the PLC setting
1555 |PLC station No.|0|Must be the same as the PLC setting
1556
1557 **Address List**
1558
1559 (% class="table-bordered" %)
1560 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1561 |Bit|X|X|X h|0~~FFFF|
1562 |Bit|Y|Y|Y h|0~~FFFF|
1563 |Bit|M|M|M d|0~~9999|
1564 |Bit|L|L|L d|0~~9999|
1565 |Bit|F|F|F d|0~~9999|
1566 |Bit|B|B|B h|0~~FFFF|
1567 |Bit|V|V|V d|0~~2047|
1568 |Bit|TC|TC|TC d|0~~9999|
1569 |Bit|SS|SS|SS d|0~~9999|
1570 |Bit|SC|SC|SC d|0~~9999|
1571 |Bit|CS|CS|CS d|0~~9999|
1572 |Bit|CC|CC|CC d|0~~9999|
1573 |Bit|SB|SB|SB h|0~~FFFF|
1574 |Bit|SM|SM|SM d|0~~2047|
1575 |Bit|STS|STS|STS d|0~~1023|
1576 |Bit|S|S|S d|0~~9999|
1577 |Bit|DX|DX|DX h|0~~FFFF|
1578 |Bit|DY|DY|DY h|0~~FFFF|
1579 |Bit|TS|TS|TS d|0~~9999|
1580 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1581 |Word|W|W|W h|0~~FFFF|
1582 |Word|TN|TN|TN d|0~~99999|
1583 |Word|SN|SN|SN d|0~~99999|
1584 |Word|CN|CN|CN d|0~~99999|
1585 |Word|R|R|R d|0~~99999|
1586 |Word|SW|SW|SW h|0~~FFFF|
1587 |Word|Z|Z|Z d|0~~99999|
1588 |Word|ZR|ZR|ZR h|0~~FFFF|
1589 |Word|D|D|D d|0~~99999|
1590
1591 **Communication Settings**
1592
1593 Enable HMI Ethernet in [Project Settings];
1594
1595 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1596
1597 Set PLC IP in [Device IP] settings;
1598
1599 (% style="text-align:center" %)
1600 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1601
1602 **PLC Settings (GX Works2 )**
1603
1604 Create a project
1605
1606 Set PLC IP, subnet mask and gateway;
1607
1608 Select [Binary Code] as communication data code;
1609
1610 (% style="text-align:center" %)
1611 [[image:image-20221108202109-2.png||height="636" width="732"]]
1612
1613 Set PLC port number, for example 1025
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1617
1618 Save settings;
1619
1620 Download project into PLC device;
1621
1622 Restart PLC device;
1623
1624 **Cable Wiring**
1625
1626 (% style="text-align:center" %)
1627 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1628
1629 == **QJ71C24N MELSEC Protocol** ==
1630
1631 Mitsubishi QJ71C24N communication module built-in serial port;
1632
1633 **HMI Settings**
1634
1635 (% class="table-bordered" %)
1636 |**Items**|**Settings**|**Note**
1637 |Protocol|MIT QJ71 MELSEC|
1638 |Connection|422|
1639 |Baud rate|9600|
1640 |Data bit|8|
1641 |Parity|ODD|
1642 |Stop bit|1|
1643 |PLC station No.|1~~255|Need to be the same as PLC settings
1644
1645 **Address List**
1646
1647 (% class="table-bordered" %)
1648 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1649 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1650 |Y|Y|Y FFFF|0~~1FFF|
1651 |M|M|M DDDDD|0~~99999|
1652 |L|L|L DDDD|0~~8191|
1653 |F|F|F DDDD|0~~2047|
1654 |V|V|V DDDD|0~~2047|
1655 |B|B|B FFFF|0~~1FFF|
1656 |TS|TS|TS DDDD|0~~2047|
1657 |TC|TC|TC DDDD|0~~2047|
1658 |SS|SS|SS DDDD|0~~2047|
1659 |SC|SC|SC DDDD|0~~2047|
1660 |CS|CS|CS DDDD|0~~1023|
1661 |CC|CC|CC DDDD|0~~1023|
1662 |SB|SB|SB FFF|0~~7FF|
1663 |S|S|S D|0~~8191|
1664 |DX|DX|DX FFFF|0~~1FFF|
1665 |DY|DY|DY FFFF|0~~1FFF|
1666 |SM_|SM_|SM_ DDDD|8000~~9999|
1667 |SM|SM|SM DDDD|0~~2047|
1668 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1669 |D|D|D DDDDD|0~~12287|
1670 |W|W|W FFFF|0~~1FFF|
1671 |TN|TN|TN DDDD|0~~2047|
1672 |SN|SN|SN DDDD|0~~2047|
1673 |CN|CN|CN DDDD|0~~1023|
1674 |R|R|R DDDDD|0~~32767|
1675 |SW|SW|SW FFF|0~~7FF|
1676 |Z|Z|Z D|0~~15|
1677 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1678
1679 **Communication Settings**
1680
1681 (% style="text-align:center" %)
1682 [[image:image-20221109135738-1.png]]
1683
1684 (% style="text-align:center" %)
1685 [[image:image-20221109140016-3.png]]
1686
1687 (% class="wikigeneratedid" id="H" %)
1688 Pin Definition Diagram
1689
1690 (% style="text-align:center" %)
1691 [[image:image-20221109140406-4.png]]
1692
1693 == **QJ71E71 MELSEC Protocol** ==
1694
1695 Mitsubishi QJ71E71 Ethernet communication module;
1696
1697 **HMI Settings**
1698
1699 (% class="table-bordered" %)
1700 |**Items**|**Settings**|**Note**
1701 |Protocol|MIT QJ71E71 MELSEC|
1702 |Connection|Ethernet|
1703 |Port No.|1025|Must be the same as the PLC setting
1704 |PLC station No.|0|Must be the same as the PLC setting
1705
1706 **Address List**
1707
1708 (% class="table-bordered" %)
1709 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1710 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1711 |Y|Y|Y h|0~~1FFF|
1712 |M|M|M d|0~~99999|
1713 |L|L|L d|0~~8191|
1714 |F|F|F d|0~~2047|
1715 |B|B|B h|0~~1FFF|
1716 |V|V|V d|0~~2047|
1717 |TS|TS|TS d|0~~2047|
1718 |TC|TC|TC d|0~~2047|
1719 |SS|SS|SS d|0~~2047|
1720 |SC|SC|SC d|0~~2047|
1721 |CS|CS|CS d|0~~1023|
1722 |CC|CC|CC d|0~~1023|
1723 |SB|SB|SB h|0~~7FF|
1724 |S|S|S d|0~~8191|
1725 |DX|DX|DX h|0~~1FFF|
1726 |DY|DY|DY h|0~~1FFF|
1727 |SM|SM|SM d|8000~~9999|
1728 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1729 |D|D|D d|0~~12287|
1730 |W|W|W h|0~~1FFF|
1731 |TN|TN|TN d|0~~2047|
1732 |SN|SN|SN d|0~~2047|
1733 |CN|CN|CN d|0~~1023|
1734 |R|R|R d|0~~32767|
1735 |SW|SW|SW h|0~~7FF|
1736 |Z|Z|Z d|0~~15|
1737 |ZR|ZR|ZR h|0~~FE7FF|
1738
1739 **HMI Communication Settings**
1740
1741 1) Enable HMI Ethernet in [Project Settings];
1742
1743 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1744
1745 2) Set PLC IP in [Device IP] settings;
1746
1747 (% style="text-align:center" %)
1748 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1749
1750 **PLC Settings(GX Works2)**
1751
1752 * Click [Ethernet/CC IE/MELSECNET];
1753 * Please select [Ethernet] as network type;
1754 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1755 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1756 * Click [Operation setting] to set IP;
1757 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1758 * Set protocol: TCP;
1759 * Set [unpassive] in [Open system];
1760 * Set [receive] in [Fixed buffer];
1761 * Set [procedure Exist] in [Fixed buffer communication];
1762 * Disable [Pairing open];
1763 * Set [No confirm] in [Existence confirmation];
1764 * Host station port number: 1025;
1765 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1766 * Download project into PLC and restart it
1767
1768 **Cable Wiring**
1769
1770 (% style="text-align:center" %)
1771 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1772
1773 = Create communication with **Delta PLC** =
1774
1775 == DVP serial protocol ==
1776
1777 (% class="wikigeneratedid" %)
1778 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1779
1780 **HMI Settings**
1781
1782 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
1783 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
1784 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
1785 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
1786 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
1787 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
1788 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
1789 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
1790
1791 **Address List**
1792
1793 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1794 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
1795 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
1796 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
1797 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
1798 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
1799 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
1800 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
1801 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
1802 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
1803
1804 (% class="wikigeneratedid" %)
1805 **Configure the communication protocol**
1806
1807 (% style="text-align:center" %)
1808 [[image:image-20220829152327-6.png]]
1809
1810 (% style="text-align:center" %)
1811 [[image:image-20220829152016-3.png]]
1812
1813 (% class="wikigeneratedid" %)
1814 **Cable Wiring**
1815
1816 (% class="wikigeneratedid" id="H" %)
1817 [[image:image-20220829152610-7.png]]
1818
1819 (% style="text-align:center" %)
1820 [[image:image-20220829152102-5.png]]
1821
1822 == DVP Ethernet Protocol ==
1823
1824 (% class="wikigeneratedid" %)
1825 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1826
1827 **HMI Settings**
1828
1829 |=**Items**|=**Settings**|=**Note**
1830 |Protocol|DELTA DVP Modbus TCP|
1831 |Connection|Ethernet|
1832 |Port No.|201|Must be the same as the PLC setting
1833 |PLC station No.|0|Must be the same as the PLC setting
1834
1835 **Address List**
1836
1837 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1838 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
1839 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
1840 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
1841 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
1842 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
1843 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
1844 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
1845 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
1846 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
1847
1848 )))
1849 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
1850 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
1851
1852 )))
1853
1854 (% class="wikigeneratedid" %)
1855 **Configure the communication protocol**
1856
1857 (% style="text-align:center" %)
1858 [[image:image-20220829155452-1.png]]
1859
1860 [[image:image-20220829162116-2.png]]
1861
1862 **Cable Wiring**
1863
1864 (% style="text-align:center" %)
1865 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1866
1867 (% class="wikigeneratedid" %)
1868 == **AS serial protocol** ==
1869
1870 Supported Series: Delta AS200/AS300
1871
1872 **HMI Settings**
1873
1874 |**Item**|**Settings**|**Note**
1875 |Protocol|DELTA AS300 MODBUS RTU|
1876 |Connection|RS485|
1877 |Baud rate|9600|
1878 |Data bit|8|
1879 |Parity|NONE|
1880 |Stop bit|1|
1881 |PLC station No.|1|
1882
1883 **Address List**
1884
1885 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1886 |Bit|X|X|Xdd.dd|0~~63.15|Read only
1887 |Bit|Y|Y|Ydd.dd|0~~63.15|
1888 |Bit|D|D|Dddddd|0~~29999|
1889 |Bit|M|M|Mdddd|0~~8191|
1890 |Bit|SM|SM|SMdddd|0~~4095|
1891 |Bit|S|S|Sdddd|0~~2047|
1892 |Bit|T|T|Tddd|0~~511|
1893 |Bit|C|C|Cddd|0~~511|
1894 |Bit|HC|HC|HCddd|0~~255|Double Word
1895 |Word|X|X|Xdd|0~~63|
1896 |Word|Y|Y|(((
1897 Ydd
1898 )))|0~~63|
1899 |Word|SR|SR|SRdddd|0~~2047|Special register
1900 |Word|D|D|Dddddd|0~~29999|
1901 |Word|T|T|Tddd|0~~511|
1902 |Word|C|C|Cddd|0~~511|
1903 |Word|E|E|Ed|0~~9|
1904
1905 **Configure the communication protocol**
1906
1907 Create project
1908
1909 (% style="text-align:center" %)
1910 [[image:AsCreateProject.png]]
1911
1912 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
1913
1914 (% style="text-align:center" %)
1915 [[image:AScommunicarw.png]]
1916
1917 Double click the HWCONFIG to open the communication settings window.
1918
1919 (% style="text-align:center" %)
1920 [[image:ASHWCONFIG.png]]
1921
1922 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
1923
1924 (% style="text-align:center" %)
1925 [[image:ASHSCONFIGICON.png]]
1926
1927 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
1928
1929 (% style="text-align:center" %)
1930 [[image:ASModbusMode.png]]
1931
1932 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
1933
1934 (% style="text-align:center" %)
1935 [[image:ASconfigIP.png]]
1936
1937 (% style="text-align:center" %)
1938 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
1939
1940
1941 (% style="text-align:center" %)
1942 [[image:image-20220830094657-2.png]]
1943
1944 **Cable Wiring**
1945
1946 (% style="text-align:center" %)
1947 [[image:image-20220830141138-1.png]]
1948
1949 Pin Definition Diagram
1950
1951 (% style="text-align:center" %)
1952 [[image:image-20220830095131-1.png]]
1953
1954 == AS Ethernet Protocol ==
1955
1956 **HMI Settings**
1957
1958 |=**Items**|=**Settings**|=**Note**
1959 |Protocol|DELTA AS300 MODBUS TCP|
1960 |Connection|Ethernet|
1961 |Port No.|502|
1962 |Device No.|1|
1963 |HMI No.|0|
1964
1965 **Address List**
1966
1967 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1968 |Bit|X|X|X d|0~~63|
1969 |Bit|Y|Y|Y d|0~~63|
1970 |Bit|D|D|D d|0~~29999|
1971 |Bit|M|M|M d|0~~8191|
1972 |Bit|SM|SM|SM d|0~~4095|
1973 |Bit|S|S|S h|0~~2047|
1974 |Bit|T|T|T d|0~~511|
1975 |Bit|C|C|C d|0~~511|
1976 |Bit|HC|HC|HC d|0~~255|
1977 |Word|X|X|X h|0~~63|
1978 |Word|Y|Y|Y d|0~~63|
1979 |Word|SR|SR|SR d|0~~2047|
1980 |Word|D|D|D d|0~~29999|
1981 |Word|T|T|T d|0~~511|
1982 |Word|C|C|C h|0~~511|
1983 |Word|E|E|E d|0~~9|
1984
1985 **Configure the communication protocol**
1986
1987 (% style="text-align:center" %)
1988 [[image:image-20220830140537-1.png]]
1989
1990 (% style="text-align:center" %)
1991 [[image:image-20220830140629-2.png]]
1992
1993 **Cable Wiring**
1994
1995 [[image:image-20220830094929-1.png]]
1996
1997 Pin Definition Diagram
1998
1999 (% style="text-align:center" %)
2000 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2001
2002 = Create communication with **Omron** PLC =
2003
2004 == CJ TCP FINS Ethemet  Protocol ==
2005
2006 Supported device:CJ series
2007
2008 **HMI Settings**
2009
2010 |=**Items**|=**Settings**|=**Note**
2011 |Protocol|OMRON CJ TCP FINS Ethemet|
2012 |Connection|Ethernet|
2013 |Port No.|9600|
2014 |Device No.|0|
2015 |HMI No.|0|(((
2016
2017 )))
2018
2019 **Address List**
2020
2021 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2022 |Bit|CIO|CIO|CIO d|0~~99999|
2023 |Bit|W|W|W d|0~~99999|
2024 |Bit|D|D|D d|0~~99999|
2025 |Bit|H|H|H d|0~~99999|
2026 |Bit|A|A|A d|0~~99999|
2027 |Bit|T|T|T h|0~~99999|
2028 |Bit|CF|CF|CF d|0~~99999|
2029 |Bit|FF|FF|FF d|0~~99999|
2030 |Bit|C|C|C d|0~~99999|
2031 |Bit|EM0|EM0|EM0 d|0~~99999|
2032 |Bit|EM1|EM1|EM1 d|0~~99999|
2033 |Bit|EM2|EM2|EM2 d|0~~99999|
2034 |Bit|EM3|EM3|EM3 d|0~~99999|
2035 |Bit|EM4|EM4|EM4 d|0~~99999|
2036 |Bit|EM5|EM5|EM5 h|0~~99999|
2037 |Bit|EM6|EM6|EM6 d|0~~99999|
2038 |Bit|EM7|EM7|EM7 d|0~~99999|
2039 |Bit|EM8|EM8|EM8 d|0~~99999|
2040 |Bit|EM9|EM9|EM9 d|0~~99999|
2041 |Bit|EMA|EMA|EMA d|0~~99999|
2042 |Bit|EMB|EMB|EMB d|0~~99999|
2043 |Bit|EMC|EMC|EMC d|0~~99999|
2044 |Bit|Lamp|Lamp|Lamp d|0~~0|
2045 |Word|CIO|CIO|CIO d|0~~99999|
2046 |Word|W|W|W d|0~~99999|
2047 |Word|D|D|D d|0~~99999|
2048 |Word|H|H|H d|0~~99999|
2049 |Word|A|A|A d|0~~99999|
2050 |Word|T|T|T h|0~~99999|
2051 |Word|CF|CF|CF d|0~~99999|
2052 |Word|FF|FF|FF d|0~~99999|
2053 |Word|C|C|C d|0~~99999|
2054 |Word|EM0|EM0|EM0 d|0~~99999|
2055 |Word|EM1|EM1|EM1 d|0~~99999|
2056 |Word|EM2|EM2|EM2 d|0~~99999|
2057 |Word|EM3|EM3|EM3 d|0~~99999|
2058 |Word|EM4|EM4|EM4 d|0~~99999|
2059 |Word|EM5|EM5|EM5 h|0~~99999|
2060 |Word|EM6|EM6|EM6 d|0~~99999|
2061 |Word|EM7|EM7|EM7 d|0~~99999|
2062 |Word|EM8|EM8|EM8 d|0~~99999|
2063 |Word|EM9|EM9|EM9 d|0~~99999|
2064 |Word|EMA|EMA|EMA d|0~~99999|
2065 |Word|EMB|EMB|EMB d|0~~99999|
2066 |Word|EMC|EMC|EMC d|0~~99999|
2067 |Word|IR|IR|IR d|0~~99999|
2068 |Word|DR|DR|DR d|0~~99999|
2069
2070 **Configure the communication protocol**
2071
2072 (% style="text-align:center" %)
2073 [[image:image-20220830143348-1.png]]
2074
2075 (% style="text-align:center" %)
2076 [[image:image-20220830143511-2.png]]
2077
2078 **Cable Wiring**
2079
2080 Pin Definition Diagram
2081
2082 (% style="text-align:center" %)
2083 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2084
2085 == **CP1E/CP1H serial protocol** ==
2086
2087 Supported device: OMRON CS1(CP1E/CP1H)
2088
2089 **HMI Settings**
2090
2091 |=**Items**|=**Settings**|=**Note**
2092 |Protocol|OMRON CS1(CP1E/CP1H)|
2093 |Connection|RS232 (9600, 2, 7, EVEN)|
2094 |Port No.|None|
2095 |PLC station No.|0|
2096
2097 **Address List**
2098
2099 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2100 |Bit|CIO|CIO|CIO d|0~~99999|
2101 |Bit|W|W|W d|0~~99999|
2102 |Bit|D|D|D d|0~~99999|
2103 |Bit|H|H|H d|0~~99999|
2104 |Bit|A|A|A d|0~~99999|
2105 |Bit|TF|T|T h|0~~99999|
2106 |Bit|CF|CF|CF d|0~~99999|
2107 |Bit|T|FF|FF d|0~~99999|
2108 |Bit|C|C|C d|0~~99999|
2109 |Bit|EM0|EM0|EM0 d|0~~99999|
2110 |Bit|EM1|EM1|EM1 d|0~~99999|
2111 |Bit|EM2|EM2|EM2 d|0~~99999|
2112 |Bit|EM3|EM3|EM3 d|0~~99999|
2113 |Bit|EM4|EM4|EM4 d|0~~99999|
2114 |Bit|EM5|EM5|EM5 h|0~~99999|
2115 |Bit|EM6|EM6|EM6 d|0~~99999|
2116 |Bit|EM7|EM7|EM7 d|0~~99999|
2117 |Bit|EM8|EM8|EM8 d|0~~99999|
2118 |Bit|EM9|EM9|EM9 d|0~~99999|
2119 |Bit|EMA|EMA|EMA d|0~~99999|
2120 |Bit|EMB|EMB|EMB d|0~~99999|
2121 |Bit|EMC|EMC|EMC d|0~~99999|
2122 |Word|CIO|CIO|CIO d|0~~99999|
2123 |Word|W|W|W d|0~~99999|
2124 |Word|D|D|D d|0~~99999|
2125 |Word|H|H|H d|0~~99999|
2126 |Word|A|A|A d|0~~99999|
2127 |Word|T|T|T h|0~~99999|
2128 |Word|CIO|CF|CF d|0~~99999|
2129 |Word|C|C|C d|0~~99999|
2130 |Word|EM0|EM0|EM0 d|0~~99999|
2131 |Word|EM1|EM1|EM1 d|0~~99999|
2132 |Word|EM2|EM2|EM2 d|0~~99999|
2133 |Word|EM3|EM3|EM3 d|0~~99999|
2134 |Word|EM4|EM4|EM4 d|0~~99999|
2135 |Word|EM5|EM5|EM5 h|0~~99999|
2136 |Word|EM6|EM6|EM6 d|0~~99999|
2137 |Word|EM7|EM7|EM7 d|0~~99999|
2138 |Word|EM8|EM8|EM8 d|0~~99999|
2139 |Word|EM9|EM9|EM9 d|0~~99999|
2140 |Word|EMA|EMA|EMA d|0~~99999|
2141 |Word|EMB|EMB|EMB d|0~~99999|
2142 |Word|EMC|EMC|EMC d|0~~99999|
2143 |Word|IR|IR|IR d|0~~99999|
2144 |Word|DR|DR|DR d|0~~99999|
2145
2146 **Configure the communication protocol**
2147
2148 (% style="text-align:center" %)
2149 [[image:image-20220902153118-1.png]]
2150
2151 (% style="text-align:center" %)
2152 [[image:image-20220902151322-2.png]]
2153
2154 **Cable Wiring**
2155
2156 (% style="text-align:center" %)
2157 [[image:image-20220902153949-2.png]]
2158
2159 Pin Definition Diagram
2160
2161 (% style="text-align:center" %)
2162 [[image:image-20220902154056-3.png]]
2163
2164 == **EC55 Protocol** ==
2165
2166 Supported device: EC55 temperature instrument
2167
2168 **1)HMI Settings**
2169
2170 |**Items**|**Settings**|**Note**
2171 |Protocol|Omron EC55|
2172 |Connection|RS485 (9600, 2, 7, EVEN)|
2173 |Port No.|None|
2174 |PLC station No.|0|
2175
2176 **2)Address List**
2177
2178 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2179 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2180 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2181 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2182 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2183 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2184 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2185 |CP|-|0-6|Read controller intrinsic property
2186 |CS|-|0-2|Read controller states
2187 |CA|-|0-17|Action command
2188
2189 **3)Device Settings**
2190
2191 Omron E5CC PLC configuration
2192
2193 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2194
2195 (% style="text-align:center" %)
2196 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2197
2198 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2199
2200 (% style="text-align:center" %)
2201 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2202
2203 **✎Note:** The communication settings for HMI should be consistent with this setting.
2204
2205 **Cable Wiring**
2206
2207 (% style="text-align:center" %)
2208 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2209
2210 (% style="text-align:center" %)
2211 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2212
2213 **✎Note:**
2214
2215 * COM3 only available in PI8000/PI9000 series.
2216 * CA address could not support continuous writing function;
2217 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2218 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2219 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2220 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2221 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2222 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2223 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2224
2225 == **EtherNet/IP NX series Protocol** ==
2226
2227 Supported series: Omron NX/NJ series
2228
2229 **HMI Setting**
2230
2231 |**Items**|**Settings**|**Note**
2232 |Protocol|Omron NX Ethernet/IP|
2233 |Connection|Ethernet|
2234 |Port No.|44818|
2235 |PLC station No.|1|
2236
2237 **Instruction**
2238
2239 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2240
2241 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2242
2243 (% style="text-align:center" %)
2244 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2245
2246 **Export labels from Sysmac Studio**
2247
2248 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2249
2250 (% style="text-align:center" %)
2251 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2252
2253 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2254
2255 Click [Label manage];
2256
2257 (% style="text-align:center" %)
2258 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2259
2260 Click [Import labels] and then select the file exported in step 1;
2261
2262 (% style="text-align:center" %)
2263 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2264
2265 The Import Status field shows the result, click [OK] to finish importing address labels;
2266
2267 (% style="text-align:center" %)
2268 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2269
2270 **Communication Settings**
2271
2272 Enable HMI Ethernet in [Project Settings];
2273
2274 (% style="text-align:center" %)
2275 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2276
2277 Set PLC IP in [Device IP] settings;
2278
2279 (% style="text-align:center" %)
2280 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2281
2282 (% style="text-align:center" %)
2283 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2284
2285 **Cable Wiring**
2286
2287 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2288
2289 == CV/CJ1M/CS1H ==
2290
2291 **HMI Setting:**
2292
2293 |=(% scope="row" %)**Parameters**|=**Recommended**
2294 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2295 |=**PLC I/F**|RS232
2296 |=**Baud rate**|9600
2297 |=**Data bits**|7
2298 |=**Parity**|Even
2299 |=**Stop bits**|2
2300 |=**PLC sta. no.**|0
2301
2302 **PLC Setting:**
2303
2304 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2305
2306 **Device Address:**
2307
2308 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2309 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2310 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2311 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2312 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2313 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2314 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2315 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2316 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2317 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2318 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2319 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2320 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2321 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2322 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2323 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2324 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2325 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2326 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2327 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2328 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2329 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2330 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2331 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2332
2333 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2334 |=W|LR_W|DDDD|0 ~~ 4095|
2335 |=W|TC|DDD|0 ~~ 511|
2336 |=W|DM|DDDD|0 ~~ 9999|Data Register
2337
2338 **Wiring Diagram:**
2339
2340 **RS-232**
2341
2342 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2343
2344 Communication Module:
2345
2346 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2347
2348 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2349
2350 (% style="text-align:center" %)
2351 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2352
2353 = Create communication with Xinje** PLC** =
2354
2355 == XC serial protocol ==
2356
2357 **HMI Settings**
2358
2359 |**Item**|**Settings**|**Note**
2360 |Protocol|XINJE XC MODBUS|
2361 |Connection|RS232|
2362 |Baud rate|19200|
2363 |Data bit|8|
2364 |Parity|EVEN|
2365 |Stop bit|1|
2366 |PLC station No.|1|
2367
2368 **Address List**
2369
2370 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2371 |Bit|M|M|M d|0~~8511|
2372 |Bit|X|X|X o|0~~1747|
2373 |Bit|Y|Y|Y o|0~~1747|
2374 |Bit|S|S|S d|0~~1023|
2375 |Bit|T|T|T d|0~~4095|
2376 |Bit|C|C|C d|0~~634|
2377 |Word|D|D|D d|0~~8511|
2378 |Word|TD|TD|TD d|0~~618|
2379 |Word|CD|CD|CD d|0~~634|
2380 |Word|FD|FD|FD d|0~~8511|
2381
2382 **Configure the communication protocol**
2383
2384 (% style="text-align:center" %)
2385 [[image:image-20220830154105-1.png]]
2386
2387 (% style="text-align:center" %)
2388 [[image:image-20220830154159-3.png]]
2389
2390 **Cable Wiring**
2391
2392 Figure
2393
2394 [[image:image-20220830155728-4.png]]
2395
2396 Pin Definition Diagram
2397
2398 (% style="text-align:center" %)
2399 [[image:image-20220830154131-2.png]]
2400
2401 == XD serial protocol ==
2402
2403 **HMI Settings**
2404
2405 Supported Series: Delta Xinjie XD/XE Series PLC
2406
2407 |=**Item**|=**Settings**|=**Note**
2408 |Protocol|XINJE XD/XC MODBUS|
2409 |Connection|RS232|
2410 |Baud rate|19200|
2411 |Data bit|8|
2412 |Parity|EVEN|
2413 |Stop bit|1|
2414 |PLC station No.|1|
2415
2416 **Address List**
2417
2418 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2419 |Bit|M|M|M d|0~~74999|
2420 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2421 |Bit|X2xx|X2xx|X2xx o|0~~277|
2422 |Bit|X|X|X o|0~~77|
2423 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2424 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2425 |Bit|Y|Y|Y o|0~~4095|
2426 |Bit|SM|SM|SM d|0~~4999|(((
2427
2428 )))
2429 |Bit|T|T|T d|0~~4999|
2430 |Bit|C|C|C d|0~~4999|
2431 |Bit|ET|ET|ET d|0~~31|
2432 |Bit|SE|SE|SE d|0~~31|
2433 |Bit|HM|HM|HM d|0~~11999|
2434 |Bit|HSC|HSC|HSC d|0~~39|
2435 |Bit|HS|HS|HS d|0~~999|
2436 |Bit|HT|HT|HT d|0~~1999|
2437 |Bit|HC|HC|HC d|0~~1999|
2438 |Bit|S|S|S d|0~~7999|
2439 |Word|D|D|D d|0~~69999|
2440 |Word|ID|ID|ID d|0~~99|
2441 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2442 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2443 |Word|QD|QD|QD d|0~~99|
2444 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2445 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2446 |Word|SD|SD|SD d|0~~4999|
2447 |Word|TD|TD|TD d|0~~575|
2448 |Word|CD|CD|CD d|0~~575|
2449 |Word|ETD|ETD|ETD d|0~~31|
2450 |Word|HD|HD|HD d|0~~24999|
2451 |Word|HSD|HSD|HSD d|0~~1023|
2452 |Word|HTD|HTD|HTD d|0~~95|
2453 |Word|HCD|HCD|HCD d|0~~95|
2454 |Word|HSCD|HSCD|HSCD d|0~~31|
2455 |Word|FD|FD|FD d|0~~8191|
2456 |Word|SFD|SFD|SFD d|0~~5999|
2457 |Word|FS|FS|FS d|0~~47|
2458
2459 **Configure the communication protocol**
2460
2461 (% style="text-align:center" %)
2462 [[image:image-20220830160042-1.png]]
2463
2464 (% style="text-align:center" %)
2465 [[image:image-20220830160129-2.png]]
2466
2467 **Cable Wiring**
2468
2469 (% style="text-align:center" %)
2470 [[image:image-20220905093902-1.png]]
2471
2472 Pin Definition Diagram
2473
2474 (% style="text-align:center" %)
2475 [[image:image-20220830160232-3.png]]
2476
2477 = Create communication with Inovance** PLC** =
2478
2479 == H3U serial protocol ==
2480
2481 **HMI Settings**
2482
2483 |=**Item**|=**Settings**|=**Note**
2484 |Protocol|INOVANCE H3U PLC|
2485 |Connection|RS422|
2486 |Baud rate|9600|
2487 |Data bit|7|
2488 |Parity|EVEN|
2489 |Stop bit|1|
2490 |PLC station No.|0|
2491
2492 **Address List**
2493
2494 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2495 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X|X o|0~~303237|
2496 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2497 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M|M d|0~~99999|
2498 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T|T d|0~~99999|
2499 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C|C d|0~~99999|
2500 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM|SM d|8000~~999|
2501 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|T|S d|0~~99999|
2502 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp|Lamp d|0~~0|
2503 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X|X o|0~~303237|
2504 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2505 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M|M d|0~~99999|
2506 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T|T d|0~~99999|
2507 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C|C d|0~~199|
2508 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D|D d|0~~7999|
2509 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S|S d|0~~99999|
2510 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD|SD d|8000~~9999|
2511 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R|R d|0~~32767|
2512
2513 **Configure the communication protocol**
2514
2515 (% style="text-align:center" %)
2516 [[image:image-20220830170114-4.png]]
2517
2518 [[image:image-20220830170017-3.png]]
2519
2520 **Cable Wiring**
2521
2522 (% style="text-align:center" %)
2523 [[image:image-20220830165930-1.png]]
2524
2525 Pin Definition Diagram
2526
2527 (% style="text-align:center" %)
2528 [[image:image-20220830165947-2.png]]
2529
2530 = Create communication with Panasonic** PLC** =
2531
2532 == **FP serial protocol** ==
2533
2534 **1)HMI Settings**
2535
2536 |**Item**|**Settings**|**Note**
2537 |Protocol|Panasonic FP MFWTOCOL|
2538 |Connection|RS232|
2539 |Baud rate|9600|
2540 |Data bit|8|
2541 |Parity|ODD|
2542 |Stop bit|1|
2543 |PLC station No.|1|
2544
2545 **2)Address List**
2546
2547 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2548 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2549 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2550 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2551 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2552 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2553 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2554 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2555 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2556 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2557 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2558 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2559 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2560 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2561 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2562 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2563
2564 **3)Configure the communication protocol**
2565
2566 [[image:image-20220830171050-1.png]]
2567
2568 [[image:image-20220830171126-2.png]]
2569
2570 **4)Cable Wiring**
2571
2572 Figure
2573
2574 [[image:image-20220830171328-4.png]]
2575
2576 Pin Definition Diagram
2577
2578 [[image:image-20220830171146-3.png]]
2579
2580 = Create communication with LS** PLC** =
2581
2582 == **XGB serial protocol ** ==
2583
2584 **HMI Settings**
2585
2586
2587 |=**Item**|=**Settings**|=**Note**
2588 |Protocol|LS XGB CPU DRIECT|
2589 |Connection|RS232|
2590 |Baud rate|115200|
2591 |Data bit|8|
2592 |Parity|NONE|
2593 |Stop bit|1|
2594 |PLC station No.|1|
2595
2596 **Address List**
2597
2598
2599 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2600 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2601 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2602 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2603 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2604 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2605 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2606 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2607 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2608 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2609 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2610 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2611 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2612 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2613 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2614 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2615 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2616 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2617 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2618 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2619 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2620 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2621 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2622 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2623 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2624 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2625 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2626
2627 **Configure the communication protocol**
2628
2629 (% style="text-align:center" %)
2630 [[image:image-20221028174410-1.png]]
2631
2632 (% style="text-align:center" %)
2633 [[image:image-20221028174753-2.png]]
2634
2635
2636 (% style="text-align:center" %)
2637 [[image:image-20221028181125-4.png]]
2638
2639 **Pin Definition Diagram**
2640
2641 (% style="text-align:center" %)
2642 [[image:image-20221028180930-3.png]]
2643
2644 = Create communication with LS** PLC** =
2645
2646 == **XBC serial protocol** ==
2647
2648 **HMI Settings**
2649
2650 |=**Item**|=**Settings**|=**Note**
2651 |Protocol|LS XBC CNet|
2652 |Connection|RS232|
2653 |Baud rate|115200|
2654 |Data bit|8|
2655 |Parity|NONE|
2656 |Stop bit|1|
2657 |PLC station No.|1|
2658
2659 **Address List**
2660
2661 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2662 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2663 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2664 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2665 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2666 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2667 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2668 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2669 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2670 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2671 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2672 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2673 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2674 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2675 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2676 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2677 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2678 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2679 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2680 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2681 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2682 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2683
2684 **Configure the communication protocol**
2685
2686 (% style="text-align:center" %)
2687 [[image:image-20220831170807-1.png]]
2688
2689 (% style="text-align:center" %)
2690 [[image:image-20220830174733-2.png]]
2691
2692 **Cable Wiring**
2693
2694 (% style="text-align:center" %)
2695 [[image:image-20220830174659-1.png]]
2696
2697 Pin Definition Diagram
2698
2699 (% style="text-align:center" %)
2700 [[image:image-20220830173402-8.png]]
2701
2702 == **XGK FEnet Ethernet protocol** ==
2703
2704 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2705
2706 **HMI Settings**
2707
2708 |**Items**|**Settings**|**Note**
2709 |Protocol|LG XGK FEnet(Ethernet)|
2710 |Connection|Ethernet|
2711 |Port No.|2004|
2712
2713 **Address List**
2714
2715 |**Type**|**Register**|**Range**|**Format**|**Note**
2716 |(% rowspan="14" %)Word|P|0~~2047|P d|
2717 |M|0~~2047|M d|
2718 |K|0~~2047|K d|
2719 |F|0~~2047|F d|
2720 |T|0~~2047|T d|
2721 |C|0~~2047|C d|
2722 |Z|0~~127|Z d|
2723 |S|0~~127|S d|
2724 |L|0~~11263|L d|
2725 |N|0~~21503|N d|
2726 |D|0~~32767|D d|
2727 |R|0~~32767|R d|
2728 |ZR|0~~65535|ZR d|
2729 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2730
2731 **✎Note:**
2732
2733 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2734 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2735 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2736
2737 **Communication settings in HMI**
2738
2739 Enable HMI Ethernet in [Project Settings];
2740
2741 (% style="text-align:center" %)
2742 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2743
2744 Set PLC IP in [Device IP] settings;
2745
2746 (% style="text-align:center" %)
2747 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2748
2749 **Cable Wiring**
2750
2751 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2752
2753 = Create communication with LS** PLC** =
2754
2755 == **XBC serial protocol** ==
2756
2757 **HMI Settings**
2758
2759 |=**Item**|=**Settings**|=**Note**
2760 |Protocol|LS XBC CNet|
2761 |Connection|RS232|
2762 |Baud rate|115200|
2763 |Data bit|8|
2764 |Parity|NONE|
2765 |Stop bit|1|
2766 |PLC station No.|1|
2767
2768 **Address List**
2769
2770 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2771 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2772 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2773 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2774 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2775 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2776 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2777 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2778 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2779 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2780 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2781 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2782 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2783 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2784 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2785 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2786 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2787 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2788 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2789 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2790 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2791 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2792
2793 **Configure the communication protocol**
2794
2795 (% style="text-align:center" %)
2796 [[image:image-20220831170807-1.png]]
2797
2798 (% style="text-align:center" %)
2799 [[image:image-20220830174733-2.png]]
2800
2801 **Cable Wiring**
2802
2803 (% style="text-align:center" %)
2804 [[image:image-20220830174659-1.png]]
2805
2806 Pin Definition Diagram
2807
2808 (% style="text-align:center" %)
2809 [[image:image-20220830173402-8.png]]
2810
2811 == **XGK FEnet Ethernet protocol** ==
2812
2813 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2814
2815 **HMI Settings**
2816
2817 |**Items**|**Settings**|**Note**
2818 |Protocol|LG XGK FEnet(Ethernet)|
2819 |Connection|Ethernet|
2820 |Port No.|2004|
2821
2822 **Address List**
2823
2824 |**Type**|**Register**|**Range**|**Format**|**Note**
2825 |(% rowspan="14" %)Word|P|0~~2047|P d|
2826 |M|0~~2047|M d|
2827 |K|0~~2047|K d|
2828 |F|0~~2047|F d|
2829 |T|0~~2047|T d|
2830 |C|0~~2047|C d|
2831 |Z|0~~127|Z d|
2832 |S|0~~127|S d|
2833 |L|0~~11263|L d|
2834 |N|0~~21503|N d|
2835 |D|0~~32767|D d|
2836 |R|0~~32767|R d|
2837 |ZR|0~~65535|ZR d|
2838 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2839
2840 **✎Note:**
2841
2842 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2843 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2844 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2845
2846 **Communication settings in HMI**
2847
2848 Enable HMI Ethernet in [Project Settings];
2849
2850 (% style="text-align:center" %)
2851 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2852
2853 Set PLC IP in [Device IP] settings;
2854
2855 (% style="text-align:center" %)
2856 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2857
2858 **Cable Wiring**
2859
2860 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2861
2862 = Create communication with **SHIMADEN PLC** =
2863
2864 == **FP23 series protocol** ==
2865
2866 Supported series: SHIMADEN FP23 series
2867
2868 **HMI Setting**
2869
2870 |**Items**|**Settings**|**Note**
2871 |Protocol|SHIMADEN FP23 series|
2872 |Connection|RS485 (9600, 1, 7, EVEN)|
2873 |Port No.|None|
2874 |PLC station No.|0|
2875
2876 **Address List**
2877
2878 |**Device address**|**HMI register**|**Address range**|**Type**
2879 |0040-0043(HEX)|FP040|100064-200067|Read only
2880 |0100-010B(HEX)|FP100|100256-200267|Read only
2881 |0110-0142(HEX)|FP110|100272-200322|Read only
2882 |0182-0252(HEX)|FP182|100386-200594|Write only
2883 |0280-0281(HEX)|FP280|100640-200641|Read only
2884 |0300-030B(HEX)|FP300|100768-200779|Read and write
2885 |0380-039F(HEX)|FP380|100896-200927|Read and write
2886 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2887 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2888 |0600-0670(HEX)|FP600|101536-201814|Read and write
2889 |0720-0738(HEX)|FP720|101824-201848|Read and write
2890 |0800-083F(HEX)|FP800|102048-202111|Read and write
2891 |0900-0952(HEX)|FP900|102304-202386|Read and write
2892 | |Ctrl|0-2|
2893
2894 **✎Note:**
2895
2896 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2897 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2898 * The Ctrl register is used to store the control group number and BCC check mode.
2899
2900 **Ctrl Register Description**
2901
2902 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2903 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2904 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2905 * Ctrl3 reserved
2906
2907 **✎Note:**
2908
2909 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2910
2911 **Cable Wiring**
2912
2913 (% style="text-align:center" %)
2914 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2915
2916 (% style="text-align:center" %)
2917 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2918
2919 **✎Note:** COM3 only available in PI8000/PI9000 series.
2920
2921 == **SR90 protocol** ==
2922
2923 Supported series: SHIMADEN SR90 series
2924
2925 **HMI Setting**
2926
2927 |**Items**|**Settings**|**Note**
2928 |Protocol|SHIMADEN SR90 protocol|
2929 |Connection|RS485 (1200, 1, 7, EVEN)|
2930 |Port No.|None|
2931 |PLC station No.|0|
2932
2933 **Address List**
2934
2935 |**Device address**|**HMI register**|**Address range**|**Type**
2936 |0040-0043 (HEX)|SR040|100064-100067|Read only
2937 |0100-010A(HEX)|SR0100|100256-100266|Read only
2938 |0182-018C(HEX)|SR0182|100386-100396|Write only
2939 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2940 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2941 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2942 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2943 | |Ctrl|0-2|~-~-
2944
2945 **✎Note:**
2946
2947 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2948 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2949 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2950
2951 **Ctrl Register Description**
2952
2953 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2954 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2955 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2956 * Ctrl3 reserved
2957
2958 **✎Note:**
2959
2960 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2961
2962 **Cable Wiring**
2963
2964 (% style="text-align:center" %)
2965 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2966
2967 (% style="text-align:center" %)
2968 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2969
2970 **✎Note:** COM3 only available in PI8000/PI9000 series.
2971
2972 == **MR13 series(standard protocol)** ==
2973
2974 Supported series: SHIMADEN MR13 series
2975
2976 **HMI Setting**
2977
2978 |**Items**|**Settings**|**Note**
2979 |Protocol|SHIMADEN standard protocol|
2980 |Connection|RS485 (1200, 1, 7, EVEN)|
2981 |Port No.|None|
2982 |PLC station No.|0|
2983
2984 **Address List**
2985
2986 |**Device address**|**HMI register**|**Address range**|**Type**
2987 |0100-010B(HEX)|MR100|100256-300267|Read only
2988 |0111-0126(HEX)|MR111|100273-300294|Read only
2989 |0184-0192(HEX)|MR184|100388-300402|Write only
2990 |0280-0282(HEX)|MR280|100640-300642|Read only
2991 |0300-030B(HEX)|MR300|100768-300779|Read/write
2992 |0314-0317(HEX)|MR314|100788-300791|Read/write
2993 |031A(HEX)|MR31A|100794-300794|Read/write
2994 |0320-0321(HEX)|MR320|100800-300801|Read/write
2995 |0400-0504(HEX)|MR400|101024-301284|Read/write
2996 |0506(HEX)|MR506|101286-301286|Read/write
2997 |0510-0514(HEX)|MR510|101296-301300|Read/write
2998 |0516-0524(HEX)|MR516|101302-301316|Read/write
2999 |0526(HEX)|MR526|101318-301318|Read/write
3000 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3001 |~-~-|Ctrl|0-2|~-~-
3002
3003 **✎Note:**
3004
3005 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3006 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3007 * The Ctrl register is used to store the control group number and BCC check mode.
3008
3009 **Ctrl Register Description**
3010
3011 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3012 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3013 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3014 * Ctrl3 reserved
3015
3016 **✎Note:**
3017
3018 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3019
3020 **Cable Wiring**
3021
3022 (% style="text-align:center" %)
3023 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3024
3025 (% style="text-align:center" %)
3026 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3027
3028 **✎Note:** COM3 only available in PI8000/PI9000 series.
3029
3030 = Create communication with **MODBUS** =
3031
3032 == **MODBUS RTU Master** ==
3033
3034 Supported Series: MODBUS RTU CONTROLLER
3035
3036 HMI works as MODBUS SLAVE connecting with MASTER
3037
3038 (% style="text-align:center" %)
3039 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3040
3041
3042 (% style="text-align:center" %)
3043 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3044
3045
3046 (% style="text-align:center" %)
3047 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3048
3049 **HMI Settings**
3050
3051 (% class="table-bordered" %)
3052 |**Items**|**Settings**|**Note**
3053 |Protocol|MODBUS RTU Master|
3054 |Connection|RS485/RS232|
3055 |Baud rate|2400~~187500|
3056 |Data bit|8|
3057 |Parity|Even/ Odd/ None|
3058 |Stop bit|1/2|
3059 |Station No.|0~~255|
3060
3061 **Address List**
3062
3063 (% class="table-bordered" %)
3064 |**Type**|**HMI address**|**MODBUS code**|**Range**
3065 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3066 |Word|HDW3500~~HDW7999|4|0~~4499
3067
3068 **Cable Wiring**
3069
3070 * **RS485**
3071
3072 (% style="text-align:center" %)
3073 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3074
3075 (% style="text-align:center" %)
3076 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3077
3078 * **RS232**
3079
3080 (% style="text-align:center" %)
3081 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3082
3083 **✎Note:** COM3 only available in PI8000/PI9000 series.
3084
3085 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3086
3087 Supported Series: MODBUS RTU CONTROLLER
3088
3089 HMI works as MODBUS MASTER connecting with SLAVE.
3090
3091 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3092
3093 (% style="text-align:center" %)
3094 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3095
3096
3097 (% style="text-align:center" %)
3098 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3099
3100
3101 (% style="text-align:center" %)
3102 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3103
3104 **HMI Settings**
3105
3106 (% class="table-bordered" %)
3107 |**Items**|**Settings**|**Note**
3108 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3109 |Connection|RS485/RS232|
3110 |Baud rate|2400~~187500|
3111 |Data bit|8|
3112 |Parity|Even/ Odd/ None|
3113 |Stop bit|1/2|
3114 |PLC station No.|0~~255|
3115
3116 **Address List**
3117
3118 (% class="table-bordered" %)
3119 |**Type**|**Address Type**|**Function code & Description**
3120 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3121 |06 (write single register: write a binary value to a holding register)
3122 |10 (write values to multiple addresses )
3123 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3124 |06 (write single register: write a binary value to a holding register)
3125 |10 (write values to multiple addresses )
3126 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3127 |06 (write single register: write a binary value to a holding register)
3128 |10 (write values to multiple addresses )
3129 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3130 |10 (write values to multiple addresses )
3131 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3132 |05 (Force a single coil to force the on/off state of a logic coil)
3133 |0F (Write multiple bits, ie write continuously)
3134 |(% rowspan="3" %)1|02 (Read the input state)
3135 |05 (Force a single coil to force the on/off state of a logic coil)
3136 |0F (Write multiple bits)
3137 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3138 |05 (Force a single coil to force the on/off state of a logic coil)
3139 |0F (Write multiple bits)
3140 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3141 |0F (Write multiple bits)
3142
3143 **✎Note:**
3144
3145 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3146 * The function codes sent out are the same as those that read and write words.
3147
3148 **Station number for more than one slaves**
3149
3150 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3151
3152 (% style="text-align:center" %)
3153 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3154
3155 **Cable Wiring**
3156
3157 * **RS485**
3158
3159 (% style="text-align:center" %)
3160 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3161
3162 (% style="text-align:center" %)
3163 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3164
3165 * **RS232**
3166
3167 (% style="text-align:center" %)
3168 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3169
3170 **✎Note:** COM3 only available in PI8000/PI9000 series.
3171
3172 == **MODBUS TCP Slave (All function)** ==
3173
3174 Supported series: MODBUS TCP controller
3175
3176 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3177
3178 (% style="text-align:center" %)
3179 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3180
3181 (% style="text-align:center" %)
3182 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3183
3184
3185 (% style="text-align:center" %)
3186 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3187
3188 **HMI Setting**
3189
3190 (% class="table-bordered" %)
3191 |**Items**|**Settings**|**Note**
3192 |Protocol|MODBUS TCP Slave (All function)|
3193 |Connection|Ethernet|
3194 |Port No.|502|
3195 |PLC station No.|1|
3196
3197 **Address List**
3198
3199 (% class="table-bordered" %)
3200 |**Type**|**Register**|**Function code & Description**
3201 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3202 |06 (write single register: write a binary value to a holding register)
3203 |10 (write values to multiple addresses )
3204 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3205 |06 (write single register: write a binary value to a holding register)
3206 |10 (write values to multiple addresses )
3207 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3208 |06 (write single register: write a binary value to a holding register)
3209 |10 (write values to multiple addresses )
3210 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3211 |10 (write values to multiple addresses )
3212 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3213 |05 (Force a single coil to force the on/off state of a logic coil)
3214 |0F (Write multiple bits, ie write continuously)
3215 |(% rowspan="3" %)1|02 (Read the input state)
3216 |05 (Force a single coil to force the on/off state of a logic coil)
3217 |0F (Write multiple bits)
3218 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3219 |05 (Force a single coil to force the on/off state of a logic coil)
3220 |0F (Write multiple bits)
3221 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3222 |0F (Write multiple bits)
3223
3224 **Communication Settings**
3225
3226 Enable HMI Ethernet in [Project Settings];
3227
3228 (% style="text-align:center" %)
3229 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3230
3231 Set PLC IP in [Device IP] settings;
3232
3233 (% style="text-align:center" %)
3234 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3235
3236 **Cable Wiring**
3237
3238 (% style="text-align:center" %)
3239 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3240
3241 = **Printer** =
3242
3243 == **TSPL label printer** ==
3244
3245 **Introduction**
3246
3247 TSPL label printer protocol supports following models.
3248
3249 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3250 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3251
3252 **Setting Step**
3253
3254 Select the protocol
3255
3256 * Create a new project, select the TSPL label printer protocol as shown below.
3257
3258 (% style="text-align:center" %)
3259 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3260
3261 Set parameters
3262
3263 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3264
3265 Printer register
3266
3267 (% class="table-bordered" %)
3268 |**Register**|**System**|**Range**|**Function**
3269 |TSPL_SP|decimal|0 - 1|Set the paper size
3270 |TSPL_PT|decimal|0 - 1999|Print text
3271 |TSPL_PQ|decimal|0 - 999|Print QR code
3272 |TSPL_PB|decimal|0 - 999|Print barcode
3273 |TSPL_PR|decimal|0 - 1|Print offset
3274 |TSPL_PN|decimal|0 - 0|Trigger printing
3275 |TSPL_PS|decimal|0 - 0|Print status
3276
3277 * Set paper size:
3278 ** TSPL_SP0: width of paper, unit: mm.
3279 ** TSPL_SP1: height of paper, unit: mm.
3280 * Print text:
3281 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3282 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3283
3284 (% class="table-bordered" %)
3285 |**Register**|**Function**|**Description**
3286 |TSPL_PT0|X coordinate|Unit: dot
3287 |TSPL_PT1|Ycoordinate|Unit: dot
3288 |TSPL_PT2|Rotation angle|(((
3289 0: 0 degrees
3290
3291 1: 90 degrees
3292
3293 2: 180 degrees
3294
3295 3: 270 degrees
3296 )))
3297 |TSPL_PT3|Size|Range: 0-3
3298 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3299
3300 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3301
3302 Print QR code:
3303
3304 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3305 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3306
3307 (% class="table-bordered" %)
3308 |**Register**|**Function**|**Description**
3309 |TSPL_PQ0|X coordinate|Unit: dot
3310 |TSPL_PQ1|Ycoordinate|Unit: dot
3311 |TSPL_PQ2|Rotation angle|(((
3312 0: 0 degrees
3313
3314 1: 90 degrees
3315
3316 2: 180 degrees
3317
3318 3: 270 degrees
3319 )))
3320 |TSPL_PQ3|Size|Range: 0-5
3321 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3322
3323 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3324
3325 Print bar code:
3326
3327 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3328 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3329
3330 (% class="table-bordered" %)
3331 |**Register**|**Function**|**Description**
3332 |TSPL_PB0|X coordinate|Unit: dot
3333 |TSPL_PB1|Ycoordinate|Unit: dot
3334 |TSPL_PB2|Rotation angle|(((
3335 0: 0 degrees
3336
3337 1: 90 degrees
3338
3339 2: 180 degrees
3340
3341 3: 270 degrees
3342 )))
3343 |TSPL_PB3|height|Unit: dot
3344 |TSPL_PB4|width|Range:0-2
3345 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3346
3347 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3348
3349 Print offset:
3350
3351 * TSPL_PR0: X coordinate offset, unit: mm;
3352 * TSPL_PR1: Y coordinate offset, unit: mm.
3353
3354 Trigger printing:
3355
3356 * TSPL_PN0 = 1: trigger the printer to start printing.
3357
3358 Printing status:
3359
3360 * TSPL_PS0 = 1: The printing is normal.
3361 * TSPL_PS0 = 1: The printing is abnormal.
3362
3363 Print picture
3364
3365 * For the function of printing pictures, please refer to the configuration of [Printer object].
3366
3367 Conversion between dot and mm
3368
3369 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3370
3371 == **EpsonTM series** ==
3372
3373 **HMI Settings**
3374
3375 (% class="table-bordered" %)
3376 |**Item**|**Settings**|**Note**
3377 |Protocol|EPSON-TM-T82II/TM-XXX|
3378 |Connection|RS232|
3379 |Baud rate|9600~~115200|
3380 |Data bit|8|
3381 |Parity|None|
3382 |Stop bit|1|
3383 |PLC station No.|1|
3384
3385 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3386
3387 **Printer Settings**
3388
3389 (% class="table-bordered" %)
3390 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3391 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3392 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3393 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3394 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3395 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3396 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3397
3398 **Cable Wiring**
3399
3400 (% style="text-align:center" %)
3401 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3402
3403 (% style="text-align:center" %)
3404 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3405
3406 **✎Note:** COM3 only available in PI8000/PI9000 series.
3407
3408
3409 (% class="wikigeneratedid" %)
3410 = Create communication with **Schneider PLC** =
3411
3412 == **Schneider MODBUS RTU** ==
3413
3414 **HMI Setting**
3415
3416 |=**Parameters**|=**Recommended**|=**Notes**
3417 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3418 |Connection|RS485|
3419 |**Baud rate**|19200|
3420 |**Data bit**|8|
3421 |**Parity**|Even|
3422 |**Stop bit**|1|
3423 |**PLC station No.**|1|
3424
3425 **PLC Setting**
3426
3427 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3428
3429 **Device Address**
3430
3431 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3432 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3433 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3434 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3435 |W|MW|DDDDDD|0 ~~ 999999|Output register
3436 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3437
3438 **Wiring Diagram**
3439
3440 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3441
3442 (% style="text-align:center" %)
3443 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3444
3445 = **Barcode Scanner** =
3446
3447 Supported: DELI 14880 barcode scanner
3448
3449 **HMI Setting**
3450
3451 |**Items**|**Settings**|**Note**
3452 |Protocol|Barcode Scanner|
3453 |Connection|USB|
3454
3455 **Operating Procedures**
3456
3457 Select [Barcode Scanner];
3458
3459 (% style="text-align:center" %)
3460 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3461
3462 Set address for receiving;
3463
3464 Set correct length;
3465
3466 (% style="text-align:center" %)
3467 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3468
3469 **✎Note:**
3470
3471 * The protocol uploads the information acquired by the USB scanner to the HMI;
3472 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3473 * Recommended model: DELI 14880 barcode scanner;
3474
3475 = **Hitachi EHV Series (Ethernet)** =
3476
3477 Supported series: Hitachi EHV series
3478
3479 **HMI Settings**
3480
3481 (% class="table-bordered" %)
3482 |**Items**|**Settings**|**Note**
3483 |Protocol|Hitachi EHV series|
3484 |Connection|Ethernet|
3485 |Port No.|3004~~3007|
3486
3487 **Address List**
3488
3489 (% class="table-bordered" %)
3490 |**Type**|**Register**|**Range**|**Format**|**Note**
3491 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3492 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3493 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3494 H1H2H3H4 Module main number
3495
3496 H1: Remote number
3497
3498 H2: Unit number
3499
3500 H3: Slot number
3501
3502 H4: Word number of Module
3503
3504 H Sub number of Module
3505
3506 For example:X21.3
3507
3508 Slot number 2
3509
3510 Word number of module is 1
3511
3512 Bit number of module is 3
3513
3514 Remote number and unit number are 0
3515 )))
3516 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3517 |R|0 – FF.f (Hex)|R HH.h|
3518 |L|0 - 73FF.f (Hex)|L HHHH.h|
3519 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3520 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3521 H1H2H3H4 Module main number
3522
3523 H1: Remote number
3524
3525 H2: Unit number
3526
3527 H3: Slot number
3528
3529 H4: Word number of module
3530
3531 For example:WX21
3532
3533 Word number of module is 1
3534
3535 Slot number is 2
3536
3537 Remote number and unit number are 0
3538 )))
3539 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3540 |WR|0 – FFFF (Hex)|WR HHHH|
3541 |WL|0 - 73FF (Hex)|WL HHHH|
3542 |TC|0 - 2559|TC DDDD|
3543
3544 **Communication settings in HMI**
3545
3546 Enable HMI Ethernet in [Project Settings];
3547
3548 (% style="text-align:center" %)
3549 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3550
3551 Set PLC IP in [Device IP] settings;
3552
3553 (% style="text-align:center" %)
3554 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3555
3556 **PLC Configuration**
3557
3558 Connect with PLC, select[Online mode];
3559
3560 (% style="text-align:center" %)
3561 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3562
3563 Set IP address, it is the same LAN parameters with HMI;
3564
3565 (% style="text-align:center" %)
3566 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3567
3568 3) Save PLC communication parameter, and restart PLC
3569
3570 **PLC Monitor Mode**
3571
3572 Connect with PLC and choose to “online” mode
3573
3574 (% style="text-align:center" %)
3575 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3576
3577 Open I/O monitor sheet1
3578
3579 (% style="text-align:center" %)
3580 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3581
3582 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3583
3584 (% style="text-align:center" %)
3585 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3586
3587 Enter the register address, click OK to view the value of the register.
3588
3589 (% style="text-align:center" %)
3590 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3591
3592 (% style="text-align:center" %)
3593 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3594
3595 **✎Note:**
3596
3597 * Both word registers and bit registers support even continuous read/write functions;
3598 * The range of registers is based on the specific PLC type;
3599
3600 **Cable Wiring**
3601
3602 (% style="text-align:center" %)
3603 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3604
3605 = **IEC60870-5 104 Client** =
3606
3607 **HMI Setting**
3608
3609 (% class="table-bordered" %)
3610 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3611 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3612 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3613 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3614
3615 **Address List**
3616
3617 (% class="table-bordered" %)
3618 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3619 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3620 |(% style="width:461px" %)SCNA|0~~16777215.7
3621 |(% style="width:461px" %)DPTB|0~~16777215.7
3622 |(% style="width:461px" %)DCNA|0~~16777215.7
3623 |(% style="width:461px" %)METF|0~~16777215.7
3624 |(% style="width:461px" %)SENC|0~~16777215.7
3625 |(% style="width:461px" %)SENA|0~~16777215.7
3626 |(% style="width:461px" %)MENA|0~~16777215.7
3627 |(% style="width:461px" %)METD|0~~16777215.7
3628 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3629 |(% style="width:461px" %)SCNA|0~~16777215
3630 |(% style="width:461px" %)DPTB|0~~16777215
3631 |(% style="width:461px" %)DCNA|0~~16777215
3632 |(% style="width:461px" %)SENA|0~~16777215
3633 |(% style="width:461px" %)MENA|0~~16777215
3634 |(% style="width:461px" %)METD|0~~16777215
3635 |(% style="width:461px" %)INRO|0~~16777215
3636 |(% style="width:461px" %)TIMESYN|0~~16777215
3637 |(% style="width:461px" %)TIMEZ|0~~16777215
3638 |(% style="width:461px" %)NTP|0~~16777215
3639 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3640 |(% style="width:461px" %)SENC|0~~16777215
3641
3642 **Address Configuration**
3643
3644 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3645
3646 (% style="text-align:center" %)
3647 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3648
3649 (% style="text-align:center" %)
3650 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3651
3652 Extended tag name
3653
3654 Address range for the extended tag.
3655
3656 **Communication Settings**
3657
3658 Enable HMI Ethernet in [Project Settings];
3659
3660 (% style="text-align:center" %)
3661 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3662
3663 Set PLC IP in [Device IP] settings;
3664
3665 (% style="text-align:center" %)
3666 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3667
3668 **Cable Wiring**
3669
3670 (% style="text-align:center" %)
3671 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3672
3673 = **OpenCAN** =
3674
3675 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3676
3677 This protocol is only available in PI8000 series HMI.
3678
3679 **HMI Settings**
3680
3681 |**Items**|**Settings**|**Note**
3682 |Protocol|OPENCAN|
3683 |Connection|CAN port|
3684 |Baud rate|250000|
3685
3686 **CAN frame setting in HMI**
3687
3688 Click [OpenCAN setting] button in communication setting window;
3689
3690 (% style="text-align:center" %)
3691 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3692
3693 Click [Add] to create a new frame;
3694
3695 (% style="text-align:center" %)
3696 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3697
3698 |**No**|**Items**|**Description**
3699 |1|Add|add a frame related to register address
3700 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3701 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3702 |4|Modify|Modify the frames in frame management
3703 |5|Copy|Copy one frame to another
3704 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3705 |7|Empty|All frames in the list are cleared
3706 |8|Browse|Displays configuration files in XML format in IE
3707 |9|OK|Complete the configuration of the frame and exit
3708
3709 Set CANBUS frame in setting windows
3710
3711 (% style="text-align:center" %)
3712 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3713
3714 |**No**|**Items**|**Description**
3715 |1|ID|Set the ID of a can frame in hexadecimal format;
3716 |2|ID assign|split the ID by PF, PS, and SA;
3717 |3|Frame type|Select Standard frame or Extended Frame;
3718 |4|Frame format|Select between data frame and remote Frame;
3719 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3720 |6|Use address|(((
3721 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3722
3723 **Edit:** Set a bit or word address by its format;
3724
3725 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3726 )))
3727 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3728 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3729 |Feedback mode: feedback mode includes no response, confirm response and data response;
3730 |No response: the device or touch screen will not receive feedback;
3731 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3732 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3733 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3734 |Response timeout: sets whether the response frame timeout;
3735 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3736 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3737 |Manually send: a manually send tick indicates only one send;
3738 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3739 |10|Note|Fill the text to explain the meaning of the frame;
3740 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3741 |12|Current operation display|Display the description of current operation;
3742 |13|Add|Add a new frame;
3743 |14|Save frame|Save the configured frame format;
3744 |15|Cancel|Cancel the frame configuration;
3745
3746 Set CAN address (Read or write operation);
3747
3748 (% style="text-align:center" %)
3749 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3750
3751 |**No.**|**Item**|**Description**
3752 |1|Current address|Displays the register type and register address set by the user in the data access interface
3753 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3754 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3755 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3756 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3757 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3758 |If the trigger condition is a writing operation, there are two situations:(((
3759 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3760 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3761 )))
3762 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3763 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3764 |4|Add|Add current configuration
3765 |5|Close|Close the configuration window to exit
3766
3767 **Multiple Packages Settings**
3768
3769 (% style="text-align:center" %)
3770 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3771
3772 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3773
3774 Select Multiple package type
3775
3776 * Not Multiple packages
3777 * J1939 Multiple packages
3778 * Customized Multiple packages
3779
3780 Click [Edit Receive data] for [Receive] settings
3781
3782 * Start code+ Total length (J1939)
3783
3784 (% style="text-align:center" %)
3785 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3786
3787 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3788
3789 * Start code + Data max length (J1939)
3790
3791 (% style="text-align:center" %)
3792 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3793
3794 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3795
3796 * Data max length (J1939)
3797
3798 (% style="text-align:center" %)
3799 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3800
3801 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3802
3803 * Customized multiple package
3804
3805 (% style="text-align:center" %)
3806 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3807
3808 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3809
3810 Click [Edit Send data] for [Send] setting
3811
3812 * J1939
3813
3814 (% style="text-align:center" %)
3815 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3816
3817 [Data] is all data to be sent.
3818
3819 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3820
3821 * Customized multiple package
3822
3823 (% style="text-align:center" %)
3824 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3825
3826 [Data] is all data to be sent.
3827
3828 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3829
3830 **Cable Wiring**
3831
3832 (% style="text-align:center" %)
3833 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3834
3835 **✎Note:** The address interval between each frame need to be more than a word address;
3836
3837
3838 = **User Defined Protocol** =
3839
3840 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
3841
3842 **HMI Settings**
3843
3844 |**Items**|**Settings**|**Note**
3845 |Protocol|User defined protocol|
3846 |Connection|RS485/RS232|
3847 |Baud rate|2400~~187500|
3848 |Stop bits|1/ 2|
3849 |Data bits|7/ 8|
3850 |Parity|None/ Even/ ODD|
3851
3852 **Operating Procedures**
3853
3854 Select [User defined protocol];
3855
3856 Click [User defined protocol] button to open setting window as below;
3857
3858 (% style="text-align:center" %)
3859 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
3860
3861 Configure user defined command;
3862
3863 (% style="text-align:center" %)
3864 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
3865
3866 |**No**|**Item**|**Description**
3867 |1|Instruction edit|The required command.
3868 |2|Mode|Write to address or read from the address.
3869 |3|Format|Encode format: HEX or ASCII.
3870 |4|Other|(((
3871 **No receiving: **HMI does not respond to the receiving command.
3872
3873 **Send after receiving:** HMI responds to the receiving command.
3874 )))
3875 |5|Manually send|(((
3876 Respond once after trigger the address.
3877
3878 Address: set the trigger address.
3879 )))
3880 |6|Add|Save this setting.
3881 |7|Cancel|Cancel current settings.
3882 |(% rowspan="4" %)8|Add|Add a new command.
3883 |Edit|Edit the selected command.
3884 |Delete|Delete the selected command.
3885 |Clear|Clear all the commands.
3886 |9|Instruction list|Display all current commands.
3887 |10|Address List|Display all the addresses added.
3888 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
3889 |Export|Export current command settings to local storage.
3890 |Browse|Browse local command files.
3891 |Advanced|Combine two commands.
3892 |Exit|Complete editing and exit setting.
3893
3894 **Operating Procedures**
3895
3896 Click [Add] to create a new command, as below shows;
3897
3898 (% style="text-align:center" %)
3899 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
3900
3901 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
3902
3903 (% style="text-align:center" %)
3904 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
3905
3906 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
3907
3908 (% style="text-align:center" %)
3909 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
3910
3911 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
3912
3913 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
3914
3915 Check settings;
3916
3917 (% style="text-align:center" %)
3918 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3919
3920 |**No**|**Items**|**Description**
3921 |1|Add checking|Add checking command when receiving the data.
3922 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
3923 |Differ with send check|Set return checking.
3924 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
3925 |Length: The data length need to be checked.
3926
3927 Object settings;
3928
3929 (% style="text-align:center" %)
3930 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3931
3932 |**No**|**Items**|**Description**
3933 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
3934 |Address: the triggering address;
3935 |Note: description to object;
3936 |2|Byte order|The numerical display order;
3937
3938 Data length settings;
3939
3940 (% style="text-align:center" %)
3941 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3942
3943 |**No**|**Item**|**Description**
3944 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
3945 |Length: the return data length.
3946 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
3947 |Length: the write data length.
3948
3949 Instruction length settings
3950
3951 (% style="text-align:center" %)
3952 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3953
3954 |**No**|**Item**|**Description**
3955 |1|Send length|The instruction data will only send designated data length.
3956 |2|Return length|The responds data length.
3957 |3|End code|Instruction will not be terminated until receiving [End code];
3958
3959 **Cable Wiring**
3960
3961 * **RS485**
3962
3963 (% style="text-align:center" %)
3964 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3965
3966 (% style="text-align:center" %)
3967 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3968
3969 * **RS232**
3970
3971 (% style="text-align:center" %)
3972 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
3973
3974 **✎Note:** COM3 only available in PI8000/PI9000 series.