Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 208.1 by Theodore Xu on 2022/12/28 14:51

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with **Rockwell PLC** =
459
460 == **DF1 Protocol** ==
461
462 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
467 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
468 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
469 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
470 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
471 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
472 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
473 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
474 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
475
476 **Address List**
477
478 (% class="table-bordered" %)
479 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
480 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
481 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
482 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
483 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
484 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
485 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
486 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
487 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
488 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
489 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
490 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
491
492 == **MicroLogix Protocol** ==
493
494 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
495
496 **HMI Settings**
497
498 (% class="table-bordered" %)
499 |**Item**|**Settings**|**Note**
500 |Protocol|Allen-Bradlley MicroLogix|
501 |Connection|RS232|
502 |Baud rate|19200|
503 |Data bit|8|
504 |Parity|None|
505 |Stop bit|1|
506 |PLC station No.|1|
507
508 **Address List**
509
510 (% class="table-bordered" %)
511 |**Type**|**Device registers**|**Format**|**Range**|**Note**
512 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
513 |O|O d.d|0.0~~255.15|
514 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
515 |S|S d.d|0.0~~255.15|
516 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
517 |(% rowspan="9" %)Word|S|S d|0~~255|
518 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
519 |TP|TP nnhh|0~~ffff
520 |CS|CS nnhh|0~~ffff
521 |CP|CP nnhh|0~~ffff
522 |N|N nnhh|0~~ffff
523 |C|C nnhh|0~~ffff
524 |T|T nnhh|0~~ffff
525 |R|R nnhh|0~~ffff
526
527 **Cable Wiring**
528
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
532
533 == **CompactLogix FreeTag Ethernet protocol** ==
534
535 Allen-Brandly CompactLogix
536
537 **HMI Settings**
538
539 (% class="table-bordered" %)
540 |**Items**|**Settings**|**Note**
541 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
542 |Connection|Ethernet|
543 |Port No.|44818|
544
545 **PLC Setting**
546
547 Create new tags
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
551
552 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
553
554 (% style="text-align:center" %)
555 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
556
557 Import labels, please open [Communication] window and click [Import label];
558
559 Select csv file, all tags will be displayed as belows;
560
561 (% style="text-align:center" %)
562 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
563
564 **✎Note:**
565
566 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
570
571 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
572
573 **Communication settings in HMI**
574
575 Enable HMI Ethernet in [Project Settings];
576
577 (% style="text-align:center" %)
578 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
579
580 Set PLC IP in [Device IP] settings;
581
582 (% style="text-align:center" %)
583 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
584
585 **Cable Wiring**
586
587 (% style="text-align:center" %)
588 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
589
590 == **MicroLogix 1200** ** protocol** ==
591
592 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
593
594 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
595 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
596 * **Word address S:** The word address ranges from 0 to 255 (decimal).
597 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
598
599 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
600
601 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
602 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
603 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
604 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
605 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
606 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
607 |**PLC word address type**|**Address format**|**Address range**
608 |S|ddd|S0 ~~ 255
609 |TS|ffff|TS0 ~~ FFFF
610 |TP|ffff|TP0 ~~ FFFF
611 |CS|ffff|CS0 ~~ FFFF
612 |CP|ffff|CP0 ~~ FFFF
613 |N|ffff|N0 ~~ FFFF
614 |F|ffff|F0 ~~ FFFF
615
616 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
617
618 == **S7-200 Smart Ethernet Protocol** ==
619
620 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
621
622 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
623
624 **HMI Setting**
625
626 (% class="table-bordered" %)
627 |**Items**|**Settings**|**Note**
628 |Protocol|Simens S7-200 Smart Ethernet|
629 |Connection|Ethernet|
630 |Port No.|102|
631 |PLC station No.|2|
632
633 **Address List**
634
635 (% class="table-bordered" %)
636 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
637 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
638 |Q|Q|Q ddddd.o|0.0~~99999.7|
639 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
640 |V|V|V ddddd.o|0.0~~99999.7|
641 |M|M|M ddddd.o|0.0~~99999.7|
642 |SM|SM|ddddd.o|0.0~~99999.7|
643 |S|S|ddddd.o|0.0~~99999.7|Read only
644 |T|T|ddddd|0~~99999|Timer state, read only
645 |C|C|ddddd|0~~99999|Counter state, read only
646 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
647 |Q|QW|QW ddddd|0~~99999|
648 |AI|AIW|AIW ddddd|0~~99999|
649 |AQ|VB|VB ddddd|0~~99999|
650 |V|VW|VW ddddd|0~~99998|(((
651 VW0=VB (0~~1)
652
653 VW2=VB (2~~3)
654
655 Address value is a multiple of 2
656 )))
657 |V|VD|VD ddddd|0~~99998|(((
658 VD0=VB (0~~3)
659
660 VD2=VB (4~~7)
661
662 Address value is a multiple of 4
663 )))
664 |M|MB|MB ddddd|0~~99999|
665 |M|MW|MW ddddd|0~~99999|(((
666 MW0=MB(0~~1)
667
668 MW2=MB(2~~3)
669
670 Address value is a multiple of 2
671 )))
672 |M|MD|MD ddddd|0~~99999|(((
673 MD0=MB(0~~3)
674
675 MD4=MB(4~~7)
676
677 Address value is a multiple of 4
678 )))
679 |T|TW|TW ddddd|0~~99999|Value of timer
680 |C|CW|CW ddddd|0~~99999|Value of counter
681 |W|SW|SW ddddd|0~~99999|
682
683 **Communication Settings**
684
685 Enable HMI Ethernet in [Project Settings];
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
689
690 Set PLC IP in [Device IP] settings;
691
692 (% style="text-align:center" %)
693 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
694
695 * PLC IP Address: PLC IP
696 * PLC pot No.: 102(fixed)
697 * Network:TCP_Client_2N(fixed)
698
699 (% style="text-align:center" %)
700 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
701
702 * Wait timeout: depend on actual network situation (more than 1500 ms)
703
704 **Cable Wiring**
705
706 (% style="text-align:center" %)
707 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
708
709 == **S7-300 Ethernet Protocol** ==
710
711 Supported Series: Siemens S7-300 series PLC
712
713 **HMI Setting**
714
715 (% class="table-bordered" %)
716 |**Items**|**Settings**|**Note**
717 |Protocol|Simens S7-300 Ethernet|
718 |Connection|Ethernet|
719 |Port No.|102|
720 |PLC station No.|2|Need to be same as the PLC setting
721
722 **Address List**
723
724 (% class="table-bordered" %)
725 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
726 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
727 |Q|Q|Q ddddd.o|0.0~~99999.7|
728 |M|M|M ddddd.o|0.0~~99999.7|
729 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
730 nn: block number;
731
732 dddd: address;
733 )))
734 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
735 |Q|QW|QW ddddd|0~~99999|
736 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
737 |MW|MW ddddd|0~~99999|(((
738 MW0=MB(0~~1)
739
740 MW2=MB(2~~3)
741
742 Address value is a multiple of 2
743 )))
744 |MD|MD ddddd|0~~99999|(((
745 MD0=MB(0~~3)
746
747 MD4=MB(4~~7)
748
749 Address value is a multiple of 4
750 )))
751 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
752 nn: block number;
753
754 dddd: address
755 )))
756 |DBxDBW|DBxDBW nndddd|0~~99999999
757 |DBxDBD|DBxDBD nndddd|0~~99999999
758
759 **Communication Settings**
760
761 Enable HMI Ethernet in [Project Settings];
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
765
766 Set PLC IP in [Device IP] settings;
767
768 (% style="text-align:center" %)
769 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
770
771 * PLC IP Address: PLC IP
772 * PLC pot No.: 102(fixed)
773 * Network:TCP_Client_2N(fixed)
774
775 (% style="text-align:center" %)
776 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
777
778 * Wait timeout: depend on actual network situation (more than 1500 ms)
779
780 **Cable Wiring**
781
782 (% style="text-align:center" %)
783 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
784
785 == **S7-1200 Ethernet Protocol** ==
786
787 Supported Series: Siemens S7-1200
788
789 **HMI Setting**
790
791 (% class="table-bordered" %)
792 |**Items**|**Settings**|**Note**
793 |Protocol|Siemens S7-1200|
794 |Connection|Ethernet|
795 |Port No.|102|
796 |PLC station No.|2|
797
798 **Address List**
799
800 (% class="table-bordered" %)
801 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
802 |(% rowspan="4" %)Bit|I|I|M d.o|(((
803 d:0~-~-9999
804
805 o:0-7
806 )))|
807 |Q|Q|Q d.o|(((
808 d:0~-~-9999
809
810 o:0-7
811 )))|
812 |M|M|M d.o|(((
813 d:0~-~-9999
814
815 o:0-7
816 )))|
817 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
818 nn:0-9999,
819
820 dddd:0-9999,
821
822 o:0-7
823 )))|(((
824 nn:DB No.
825
826 dddd:address value
827
828 o: digit address
829 )))
830 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
831 |M|MW|MW d|d:0-99999|(((
832 MW0=MB(0~~1)
833
834 MW2=MB(2~~3)
835
836 Address value is a multiple of 2
837 )))
838 |M|MD|MD d|d:0-99999|(((
839 MD0=MB(0~~3)
840
841 MD4=MB(4~~7)
842
843 Address value is a multiple of 4
844 )))
845 |I|IW|IW d|d:0-99999|
846 |Q|QW|QW d|d:0-99999|
847 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
848 nn:0-9999
849
850 dddd:0-9999
851 )))|(((
852 nn:DB No.
853
854 dddd:address value
855 )))
856 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
857 nn:0-9999
858
859 dddd:0-9999
860 )))|(((
861 nn:DB No.
862
863 dddd:address value
864
865 Address value is a multiple of 2
866 )))
867 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
868 nn:0-9999
869
870 dddd:0-9999
871 )))|(((
872 nn:DB No.
873
874 dddd:address value
875
876 Address value is a multiple of 4
877 )))
878
879 **Communication Settings**
880
881 Enable HMI Ethernet in [Project Settings];
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
885
886 Set PLC IP in [Device IP] settings;
887
888 (% style="text-align:center" %)
889 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
890
891 **✎Note:**
892
893 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
894 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
895
896 **PLC Settings**
897
898 Add BD
899
900 * Please uncheck [Symbolic access only] option;
901
902 (% style="text-align:center" %)
903 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
904
905 Address settings, using BD2 as example.
906
907 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
908 * 2 represent DB block number
909 * xxxx represent address
910
911 **Such as:**
912
913 * DBxDBB20000 = DB2.DBB0
914 * DBxDBW20004 = DB2.DBW4
915
916 (% style="text-align:center" %)
917 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
918
919 **How to connect with S7-1200 Firmware V4.0**
920
921 PLC configuration
922
923 * Double click [device configuration] in Siemens via software
924 * Double click [protection] to enter protection configuration screen
925
926 (% style="text-align:center" %)
927 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
928
929 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
930
931 (% style="text-align:center" %)
932 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
933
934 DB settings
935
936 * Right click [DB], select [properties]
937 * Uncheck [optimized block access]
938
939 **Cable Wiring**
940
941 (% style="text-align:center" %)
942 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
943
944 == **S7-XXX Ethernet Protocol** ==
945
946 Supported Series: Siemens S7-400, S7-1200 and S7-1500
947
948 **HMI Setting**
949
950 (% class="table-bordered" style="width:823px" %)
951 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
952 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
953 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
954 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
955 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
956 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
957
958 Slot from TIA Portal is equal to Device No. of PIStudio
959
960 Rack from TIA Portal is equal to HMI No. of PIStudio
961
962 (% style="text-align:center" %)
963 [[image:S7-XXXCommunication Settings.png]]
964
965 (% style="text-align:center" %)
966 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
967
968 **Address List**
969
970 (% class="table-bordered" %)
971 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
972 |(% rowspan="4" %)Bit|I|I|M d.o|(((
973 d:0~-~-9999
974
975 o:0-7
976 )))|
977 |Q|Q|Q d.o|(((
978 d:0~-~-9999
979
980 o:0-7
981 )))|
982 |M|M|M d.o|(((
983 d:0~-~-9999
984
985 o:0-7
986 )))|
987 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
988 nn:0-9999,
989
990 dddd:0-9999,
991
992 o:0-7
993 )))|(((
994 nn:DB No.
995
996 dddd:address value
997
998 o: digit address
999 )))
1000 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1001 |M|MW|MW d|d:0-99999|(((
1002 MW0=MB(0~~1)
1003
1004 MW2=MB(2~~3)
1005
1006 Address value is a multiple of 2
1007 )))
1008 |M|MD|MD d|d:0-99999|(((
1009 MD0=MB(0~~3)
1010
1011 MD4=MB(4~~7)
1012
1013 Address value is a multiple of 4
1014 )))
1015 |I|IW|IW d|d:0-99999|
1016 |Q|QW|QW d|d:0-99999|
1017 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1018 nn:0-9999
1019
1020 dddd:0-9999
1021 )))|(((
1022 nn:DB No.
1023
1024 dddd:address value
1025 )))
1026 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1027 nn:0-9999
1028
1029 dddd:0-9999
1030 )))|(((
1031 nn:DB No.
1032
1033 dddd:address value
1034
1035 Address value is a multiple of 2
1036 )))
1037 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1038 nn:0-9999
1039
1040 dddd:0-9999
1041 )))|(((
1042 nn:DB No.
1043
1044 dddd:address value
1045
1046 Address value is a multiple of 4
1047 )))
1048
1049 **Communication Settings**
1050
1051 Enable HMI Ethernet in [Project Settings];
1052
1053 (% style="text-align:center" %)
1054 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1055
1056 Set PLC IP in [Device IP] settings;
1057
1058 (% style="text-align:center" %)
1059 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1060
1061 **✎Note:**
1062
1063 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1064 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1065
1066 **Cable Wiring**
1067
1068 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1069
1070 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1071
1072 Supported Series: Siemens Logo 0BA0, 0BA1 series
1073
1074 **HMI Settings**
1075
1076 (% class="table-bordered" %)
1077 |**Items**|**Settings**|**Note**
1078 |Protocol|Siemens LOGO|
1079 |Connection|Ethernet|
1080 |Port No.|102|
1081 |PLC station No.|2|
1082
1083 **Address List**
1084
1085 (% class="table-bordered" %)
1086 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1087 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1088 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1089 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1090 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1091 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1092 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1093 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1094 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1095 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1096 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1097 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1098 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1099 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1100 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1101 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1102
1103 **PLC Settings in LOGO Software:**
1104
1105 Click [Tools]~-~-[Ethernet Connections],shown as below.
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1109
1110 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1111
1112 (% style="text-align:center" %)
1113 [[image:image-20221228142937-4.png]]
1114
1115 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1116
1117 (% style="text-align:center" %)
1118 [[image:image-20221228143047-5.png]]
1119
1120 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1121
1122 (% style="text-align:center" %)
1123 [[image:image-20221228143246-6.png]]
1124
1125
1126 **HMI Communication Settings**
1127
1128 Set PLC IP in [Device IP] settings;
1129
1130 (% style="text-align:center" %)
1131 [[image:image-20221228143614-7.png]]
1132
1133 Enable HMI Ethernet in [Project Settings];
1134
1135 (% style="text-align:center" %)
1136 [[image:image-20221228144229-9.png]]
1137
1138 TSAP setting
1139
1140 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1141 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
1142 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
1143 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
1144 ie, ig series: use HSW1200, HSW1201.
1145 2.0 systems: use HSW1200, HSW1201.
1146
1147 **✎Note:**
1148
1149 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
1150 * HSW10119/HSW1201 is set up as shown.
1151 * (((
1152 (% style="text-align:center" %)
1153 [[image:image-20221228144800-11.png]]
1154 )))
1155 * (((
1156 (% style="text-align:center" %)
1157 [[image:image-20221228144708-10.png]]
1158 )))
1159
1160 * AI word address and Ibit address are read-only and cannot be written on HMI.
1161 * VW address should be even number.such as VW0, VW2, VW4...
1162 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1163 * Written value of RTC cannot exceed 255.
1164
1165 **Cable Wiring**
1166
1167 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1168
1169 == S7-300 232 ==
1170
1171 **HMI Setting:**
1172
1173 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
1174 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
1175 |=**PLC I/F**|RS232| |
1176 |=**Baud rate**|19200|9600,19200|
1177 |=**Data bits**|8| |
1178 |=**Parity**|Odd| |
1179 |=**Stop bits**|1| |
1180 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
1181
1182 **Device Address**
1183
1184 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1185 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
1186 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
1187 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
1188 |=Word|(((
1189 DB1 to DB99
1190 )))|DDDDDo|0 ~~ 655327|
1191 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
1192 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
1193 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
1194 |=Double word|MD|DDDD|0 ~~ 4094|
1195 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
1196 Data Register Double Word (must be even)
1197 )))
1198 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
1199
1200 **Cable Wiring**
1201
1202 (% style="text-align:center" %)
1203 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
1204
1205 = Create communication with **Mitsubishi PLC** =
1206
1207 == **FX1S, 1N, 2N Series Protocol** ==
1208
1209 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1210
1211 **HMI Settings**
1212
1213 (% class="table-bordered" %)
1214 |**Item**|**Settings**|**Note**
1215 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1216 |Connection|RS422/RS485/RS232|
1217 |Baud rate|9600~~115200|
1218 |Data bit|7/8|
1219 |Parity|EVEN/Odd/None|
1220 |Stop bit|1/2|
1221 |PLC station No.|1~~255|
1222
1223 **Address List**
1224
1225 (% class="table-bordered" %)
1226 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1227 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1228 |Y|Y|Y o|0~~303237|
1229 |M|M|M d|0~~99999|
1230 |T|T|T d|0~~99999|
1231 |C|C|C d|0~~99999|
1232 |S|S|S d|0~~99999|
1233 |SM|SM|SM d|8000~~9999|
1234 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1235 |Y|Y|Y o|0~~303237|
1236 |M|M|M d|0~~99999|
1237 |T|T|T d|0~~99999|
1238 |C|C|C d|0~~199|
1239 |D|D|D d|0~~7999|
1240 |S|S|S d|0~~99999|
1241 |SD|SD|SD d|8000~~9999|
1242
1243 **Cable Wiring**
1244
1245 * **RS485**
1246
1247 (% style="text-align:center" %)
1248 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1249
1250 (% style="text-align:center" %)
1251 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1252
1253 * **RS422**
1254
1255 (% style="text-align:center" %)
1256 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1257
1258 **✎Note:** COM3 only available in PI8000/PI9000 series.
1259
1260 == **FX3U/3G/3GA serial protocol** ==
1261
1262 (% class="wikigeneratedid" %)
1263 **HMI Settings**
1264
1265 |=**Item**|=**Settings**|=**Note**
1266 |Protocol|Mitsubishi FX3U/3G/3GA|
1267 |Connection|RS422|
1268 |Baud rate|9600~~115200|
1269 |Data bit|7/8|
1270 |Parity|EVEN/Odd/None|
1271 |Stop bit|1/2|
1272 |PLC station No.|1~~255|
1273
1274 (% class="wikigeneratedid" %)
1275 **Address List**
1276
1277 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1278 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1279 |Y|Y|Y o|0~~303237|
1280 |M|M|M d|0~~99999|
1281 |T|T|T d|0~~99999|
1282 |C|C|C d|0~~99999|
1283 |S|S|S d|0~~99999|
1284 |SM|SM|SM d|8000~~9999|
1285 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1286 |Y|Y|Y o|0~~303237|
1287 |M|M|M d|0~~99999|
1288 |T|T|T d|0~~99999|
1289 |C|C|C d|0~~199|
1290 |D|D|D d|0~~7999|
1291 |S|S|S d|0~~99999|
1292 |SD|SD|SD d|8000~~9999|
1293
1294 **Configure the communication protocol**
1295
1296 (% style="text-align:center" %)
1297 [[image:image-20220831095222-1.png]]
1298
1299 (% style="text-align:center" %)
1300 [[image:image-20220831095743-2.png]]
1301
1302 **Wiring**
1303
1304 (% style="text-align:center" %)
1305 [[image:image-20220831100333-7.png]]
1306
1307 Pin Definition Diagram
1308
1309 (% style="text-align:center" %)
1310 [[image:image-20220831100314-6.png]]
1311
1312 == **FX3U Ethernet Protocol** ==
1313
1314 Mitsubishi FX3U series PLC
1315
1316 **HMI Settings**
1317
1318 |Items|Settings|Note
1319 |Protocol|Mitsubishi FX3U|
1320 |Connection|Ethernet|
1321 |Port No.|5009|Must be the same as the PLC setting
1322 |PLC station No.|0|
1323
1324 **Address List**
1325
1326 (% class="table-bordered" style="width:1041px" %)
1327 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|(% style="width:140px" %)**Note**
1328 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|(% style="width:140px" %)
1329 |Y|Y|Y OOO|0~~377|(% style="width:140px" %)
1330 |M|M|M DDDD|0~~7679|(% style="width:140px" %)
1331 |SM|SM|SM DDDD|8000~~8511|(% style="width:140px" %)
1332 |S|S|S DDDD|0~~4095|(% style="width:140px" %)
1333 |TS|TS|TS DDD|0~~511|(% style="width:140px" %)
1334 |CS|CS|CS DDD|0~~255|(% style="width:140px" %)
1335 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|(% style="width:140px" %)0~~199|(% style="width:30px" %)
1336 |TN|TN|TN DDD|(% style="width:140px" %)0~~511|(% style="width:30px" %)
1337 |D|D|D DDDD|(% style="width:140px" %)0~~7999|(% style="width:30px" %)
1338 |SD|SD|SD DDDD|(% style="width:140px" %)8000~~8511|(% style="width:30px" %)
1339 |R|R|R DDDDD|(% style="width:140px" %)0~~32767|(% style="width:30px" %)
1340
1341 **Ethernet Module Settings**
1342
1343 FX3U-ENET-L module configuration
1344 Set up the FX3U-ENET-L Ethernet module settings as follows.
1345 Select the module location, which in this document is Module 0.
1346
1347 [[image:image-20221115140802-1.png]]
1348
1349 Select "Operational setting" to enter the following screen.
1350
1351 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1352
1353 [[image:image-20221115142728-4.png]]
1354
1355 Select "Open setting" to enter the setting interface, the settings are as follows.
1356
1357 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1358
1359 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1360
1361 [[image:image-20221115142945-5.png]]
1362
1363 Click on "transter setup" - "PC side I/F setting", see the following figure.
1364
1365 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1366
1367 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1368
1369 [[image:image-20221115143341-6.png||height="426" width="712"]]
1370
1371 Read and write data from the Ethernet module
1372
1373 [[image:image-20221115143703-7.png]]
1374
1375 Set "Transter setup" to COM communication, and read or write operation as shown below
1376
1377 [[image:image-20221115143809-8.png]]
1378
1379 **PLC Settings (GX Works 2)**
1380
1381 Create a blank FX5U project
1382
1383 Find Current Connection in the navigation
1384
1385 [[image:image-20221115144335-9.png||height="422" width="706"]]
1386
1387 Select Connection Channel List
1388
1389 Select Ethernet board communication
1390
1391 [[image:image-20221115144824-10.png||height="421" width="705"]]
1392
1393 Select Ethernet Module
1394 Set the IP address of the PLC
1395
1396 [[image:image-20221115145228-11.png||height="674" width="708"]]
1397
1398 Read or write PLC data, in this document is read
1399
1400 [[image:image-20221115145553-12.png||height="424" width="711"]]
1401
1402 (% class="wikigeneratedid" id="H" %)
1403 [[image:image-20221115145559-13.png||height="424" width="711"]]
1404
1405 **HMI Communication Setting**
1406
1407 [[image:image-20221115150003-14.png||height="425" width="712"]]
1408
1409 [[image:image-20221115150235-15.png||height="427" width="713"]]
1410
1411 (% class="wikigeneratedid" id="H-1" %)
1412 [[image:image-20221115145559-13.png||height="424" width="711"]]
1413
1414 **HMI Communication Setting**
1415
1416 [[image:image-20221115150003-14.png||height="425" width="712"]]
1417
1418 [[image:image-20221115150235-15.png||height="427" width="713"]]
1419
1420 == **FX5U Serial Port Protocol** ==
1421
1422 Mitsubishi FX5U series PLC
1423
1424 **HMI Settings**
1425
1426 (% class="table-bordered" %)
1427 |**Item**|**Settings**|**Note**
1428 |Protocol|Mitsubishi FX5U|
1429 |Connection|RS422/RS485|
1430 |Baud rate|9600|
1431 |Data bit|7|
1432 |Parity|Odd|
1433 |Stop bit|1|
1434 |PLC station No.|1~~255|Need to be the same as PLC settings
1435
1436 **Address List**
1437
1438 (% class="table-bordered" %)
1439 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1440 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1441 |Y|Y|Y o|0~~303237|
1442 |M|M|M d|0~~99999|
1443 |B|B|B h|0~~7FFF|
1444 |F|F|F d|0~~32767|
1445 |SB|SB|SB h|0~~7FFF|
1446 |TS|TS|TS d|0~~1023|
1447 |TC|TC|TC d|0~~1023|
1448 |STS|STS|STS d|0~~1023|
1449 |STC|STC|STS d|0~~1023|
1450 |CS|CS|CS d|0~~1023|
1451 |CC|CC|CC d|0~~1023|
1452 |SM|SM|SM d|0~~9999|
1453 |L|L|L d|0~~32767|
1454 |S|S|S d|0~~4095|
1455 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1456 |TN|TN|TN d|0~~1023|
1457 |STN|STN|STN d|0~~1023|
1458 |CN|CN|CN d|0~~1023|
1459 |R|R|R d|0~~32767|
1460 |SW|SW|SW h|0~~7FFF|
1461 |Z|Z|Z d|0~~23|
1462 |D|D|D d|0~~7999|
1463 |SD|SD|SD d|0~~11999|
1464
1465 **PLC Settings (GX Works 3)**
1466
1467 Create a blank FX5U project
1468
1469 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1470
1471 (% style="text-align:center" %)
1472 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1473
1474 Select protocol in the setting item, and set parameters.
1475
1476 (% style="text-align:center" %)
1477 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1478
1479 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1480
1481 (% style="text-align:center" %)
1482 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1483
1484 Click the [Apply] button to finish the setting.
1485
1486 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1487
1488 (% style="text-align:center" %)
1489 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1490
1491 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1492
1493 Done.
1494
1495 **Cable Wiring**
1496
1497 * **RS485**
1498
1499 (% style="text-align:center" %)
1500 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1501
1502 (% style="text-align:center" %)
1503 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1504
1505 * **RS422**
1506
1507 (% style="text-align:center" %)
1508 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1509
1510 **✎Note:** COM3 only available in PI8000/PI9000 series.
1511
1512 == **L02 Serial Protocol** ==
1513
1514 Mitsubishi L02 series CPU built-in serial port.
1515
1516 **HMI Settings**
1517
1518 |=**Item**|=**Settings**|=**Note**
1519 |Protocol|Mitsubishi L02|
1520 |Connection|RS422|
1521 |Baud rate|115200|
1522 |Data bit|8|
1523 |Parity|Odd|
1524 |Stop bit|1|
1525 |PLC station No.|1~~255|Need to be the same as PLC settings
1526
1527 **Address List**
1528
1529 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1530 |Bit|X|X|X h|0~~FFFF|
1531 |Bit|Y|Y|Y h|0~~FFFF|
1532 |Bit|M|M|M d|0~~9999|
1533 |Bit|L|L|L d|0~~9999|
1534 |Bit|F|F|F d|0~~9999|
1535 |Bit|B|B|B h|0~~FFFF|
1536 |Bit|V|V|V d|0~~2047|
1537 |Bit|TC|TC|TC d|0~~9999|
1538 |Bit|SS|SS|SS d|0~~9999|
1539 |Bit|SC|SC|SC d|0~~9999|
1540 |Bit|CS|CS|CS d|0~~9999|
1541 |Bit|CC|CC|CC d|0~~9999|
1542 |Bit|SB|SB|SB h|0~~FFFF|
1543 |Bit|SM|SM|SM d|0~~2047|
1544 |Bit|STS|STS|STS d|0~~1023|
1545 |Bit|S|S|S d|0~~9999|
1546 |Bit|DX|DX|DX h|0~~FFFF|
1547 |Bit|DY|DY|DY h|0~~FFFF|
1548 |Bit|TS|TS|TS d|0~~9999|
1549 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1550 |Word|W|W|W h|0~~FFFF|
1551 |Word|TN|TN|TN d|0~~99999|
1552 |Word|SN|SN|SN d|0~~99999|
1553 |Word|CN|CN|CN d|0~~99999|
1554 |Word|R|R|R d|0~~99999|
1555 |Word|SW|SW|SW h|0~~FFFF|
1556 |Word|Z|Z|Z d|0~~99999|
1557 |Word|ZR|ZR|ZR h|0~~FFFF|
1558 |Word|D|D|D d|0~~99999|
1559
1560 **Communication Settings**
1561
1562 (% style="text-align:center" %)
1563 [[image:image-20220831105732-3.png]]
1564
1565 (% style="text-align:center" %)
1566 [[image:image-20220831110004-5.png]]
1567
1568 **Cable Wiring**
1569
1570 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1571
1572 Pin Definition Diagram
1573
1574 (% style="text-align:center" %)
1575 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1576
1577 == **L02 MELSEC (Ethernet) Protocol** ==
1578
1579 Mitsubishi Q series CPU built-in Ethernet port.
1580
1581 **HMI Settings**
1582
1583 (% class="table-bordered" %)
1584 |**Items**|**Settings**|**Note**
1585 |Protocol|MIT L02 CPU MELSEC|
1586 |Connection|Ethernet|
1587 |Port No.|1025|Must be the same as the PLC setting
1588 |PLC station No.|0|Must be the same as the PLC setting
1589
1590 **Address List**
1591
1592 (% class="table-bordered" %)
1593 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1594 |Bit|X|X|X h|0~~FFFF|
1595 |Bit|Y|Y|Y h|0~~FFFF|
1596 |Bit|M|M|M d|0~~9999|
1597 |Bit|L|L|L d|0~~9999|
1598 |Bit|F|F|F d|0~~9999|
1599 |Bit|B|B|B h|0~~FFFF|
1600 |Bit|V|V|V d|0~~2047|
1601 |Bit|TC|TC|TC d|0~~9999|
1602 |Bit|SS|SS|SS d|0~~9999|
1603 |Bit|SC|SC|SC d|0~~9999|
1604 |Bit|CS|CS|CS d|0~~9999|
1605 |Bit|CC|CC|CC d|0~~9999|
1606 |Bit|SB|SB|SB h|0~~FFFF|
1607 |Bit|SM|SM|SM d|0~~2047|
1608 |Bit|STS|STS|STS d|0~~1023|
1609 |Bit|S|S|S d|0~~9999|
1610 |Bit|DX|DX|DX h|0~~FFFF|
1611 |Bit|DY|DY|DY h|0~~FFFF|
1612 |Bit|TS|TS|TS d|0~~9999|
1613 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1614 |Word|W|W|W h|0~~FFFF|
1615 |Word|TN|TN|TN d|0~~99999|
1616 |Word|SN|SN|SN d|0~~99999|
1617 |Word|CN|CN|CN d|0~~99999|
1618 |Word|R|R|R d|0~~99999|
1619 |Word|SW|SW|SW h|0~~FFFF|
1620 |Word|Z|Z|Z d|0~~99999|
1621 |Word|ZR|ZR|ZR h|0~~FFFF|
1622 |Word|D|D|D d|0~~99999|
1623
1624 **Communication Settings**
1625
1626 Enable HMI Ethernet in [Project Settings];
1627
1628 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1629
1630 Set PLC IP in [Device IP] settings;
1631
1632 (% style="text-align:center" %)
1633 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1634
1635 **PLC Settings (GX Works2 )**
1636
1637 Create a project
1638
1639 Set PLC IP, subnet mask and gateway;
1640
1641 Select [Binary Code] as communication data code;
1642
1643 (% style="text-align:center" %)
1644 [[image:image-20221108202109-2.png||height="636" width="732"]]
1645
1646 Set PLC port number, for example 1025
1647
1648 (% style="text-align:center" %)
1649 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1650
1651 Save settings;
1652
1653 Download project into PLC device;
1654
1655 Restart PLC device;
1656
1657 **Cable Wiring**
1658
1659 (% style="text-align:center" %)
1660 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1661
1662 == **QJ71C24N MELSEC Protocol** ==
1663
1664 Mitsubishi QJ71C24N communication module built-in serial port;
1665
1666 **HMI Settings**
1667
1668 (% class="table-bordered" %)
1669 |**Items**|**Settings**|**Note**
1670 |Protocol|MIT QJ71 MELSEC|
1671 |Connection|422|
1672 |Baud rate|9600|
1673 |Data bit|8|
1674 |Parity|ODD|
1675 |Stop bit|1|
1676 |PLC station No.|1~~255|Need to be the same as PLC settings
1677
1678 **Address List**
1679
1680 (% class="table-bordered" %)
1681 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1682 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1683 |Y|Y|Y FFFF|0~~1FFF|
1684 |M|M|M DDDDD|0~~99999|
1685 |L|L|L DDDD|0~~8191|
1686 |F|F|F DDDD|0~~2047|
1687 |V|V|V DDDD|0~~2047|
1688 |B|B|B FFFF|0~~1FFF|
1689 |TS|TS|TS DDDD|0~~2047|
1690 |TC|TC|TC DDDD|0~~2047|
1691 |SS|SS|SS DDDD|0~~2047|
1692 |SC|SC|SC DDDD|0~~2047|
1693 |CS|CS|CS DDDD|0~~1023|
1694 |CC|CC|CC DDDD|0~~1023|
1695 |SB|SB|SB FFF|0~~7FF|
1696 |S|S|S D|0~~8191|
1697 |DX|DX|DX FFFF|0~~1FFF|
1698 |DY|DY|DY FFFF|0~~1FFF|
1699 |SM_|SM_|SM_ DDDD|8000~~9999|
1700 |SM|SM|SM DDDD|0~~2047|
1701 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1702 |D|D|D DDDDD|0~~12287|
1703 |W|W|W FFFF|0~~1FFF|
1704 |TN|TN|TN DDDD|0~~2047|
1705 |SN|SN|SN DDDD|0~~2047|
1706 |CN|CN|CN DDDD|0~~1023|
1707 |R|R|R DDDDD|0~~32767|
1708 |SW|SW|SW FFF|0~~7FF|
1709 |Z|Z|Z D|0~~15|
1710 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1711
1712 **Communication Settings**
1713
1714 (% style="text-align:center" %)
1715 [[image:image-20221109135738-1.png]]
1716
1717 (% style="text-align:center" %)
1718 [[image:image-20221109140016-3.png]]
1719
1720 (% class="wikigeneratedid" id="H" %)
1721 Pin Definition Diagram
1722
1723 (% style="text-align:center" %)
1724 [[image:image-20221109140406-4.png]]
1725
1726 == **QJ71E71 MELSEC Protocol** ==
1727
1728 Mitsubishi QJ71E71 Ethernet communication module;
1729
1730 **HMI Settings**
1731
1732 (% class="table-bordered" %)
1733 |**Items**|**Settings**|**Note**
1734 |Protocol|MIT QJ71E71 MELSEC|
1735 |Connection|Ethernet|
1736 |Port No.|1025|Must be the same as the PLC setting
1737 |PLC station No.|0|Must be the same as the PLC setting
1738
1739 **Address List**
1740
1741 (% class="table-bordered" %)
1742 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1743 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1744 |Y|Y|Y h|0~~1FFF|
1745 |M|M|M d|0~~99999|
1746 |L|L|L d|0~~8191|
1747 |F|F|F d|0~~2047|
1748 |B|B|B h|0~~1FFF|
1749 |V|V|V d|0~~2047|
1750 |TS|TS|TS d|0~~2047|
1751 |TC|TC|TC d|0~~2047|
1752 |SS|SS|SS d|0~~2047|
1753 |SC|SC|SC d|0~~2047|
1754 |CS|CS|CS d|0~~1023|
1755 |CC|CC|CC d|0~~1023|
1756 |SB|SB|SB h|0~~7FF|
1757 |S|S|S d|0~~8191|
1758 |DX|DX|DX h|0~~1FFF|
1759 |DY|DY|DY h|0~~1FFF|
1760 |SM|SM|SM d|8000~~9999|
1761 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1762 |D|D|D d|0~~12287|
1763 |W|W|W h|0~~1FFF|
1764 |TN|TN|TN d|0~~2047|
1765 |SN|SN|SN d|0~~2047|
1766 |CN|CN|CN d|0~~1023|
1767 |R|R|R d|0~~32767|
1768 |SW|SW|SW h|0~~7FF|
1769 |Z|Z|Z d|0~~15|
1770 |ZR|ZR|ZR h|0~~FE7FF|
1771
1772 **HMI Communication Settings**
1773
1774 1) Enable HMI Ethernet in [Project Settings];
1775
1776 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1777
1778 2) Set PLC IP in [Device IP] settings
1779
1780 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1781
1782 **PLC Settings(GX Works2)**
1783
1784 * Click [Ethernet/CC IE/MELSECNET];
1785 * Please select [Ethernet] as network type;
1786 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1787 * Select [Online] as Mode;
1788 * [[image:image-20221119164958-2.png||height="356" width="611"]](% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1789 * Click [Operation setting] to set IP;
1790 * Select [Binary Code] as [Communication Data Code];
1791 * [[image:image-20221119165129-3.png||height="381" width="611"]](% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1792 * Click [Open setting]
1793 * Set protocol: TCP;
1794 * Set [unpassive] in [Open system];
1795 * Set [receive] in [Fixed buffer];
1796 * Set [procedure Exist] in [Fixed buffer communication];
1797 * Disable [Pairing open];
1798 * Set [No confirm] in [Existence confirmation];
1799 * Host station port number: 5009;
1800 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1801 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1802 * Download project into PLC and restart it
1803
1804 **Cable Wiring**
1805
1806 (% style="text-align:center" %)
1807 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1808
1809 = Create communication with **Delta PLC** =
1810
1811 == DVP serial protocol ==
1812
1813 (% class="wikigeneratedid" %)
1814 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1815
1816 **HMI Settings**
1817
1818 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
1819 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
1820 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
1821 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
1822 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
1823 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
1824 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
1825 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
1826
1827 **Address List**
1828
1829 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1830 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
1831 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
1832 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
1833 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
1834 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
1835 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
1836 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
1837 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
1838 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
1839
1840 (% class="wikigeneratedid" %)
1841 **Configure the communication protocol**
1842
1843 (% style="text-align:center" %)
1844 [[image:image-20220829152327-6.png]]
1845
1846 (% style="text-align:center" %)
1847 [[image:image-20220829152016-3.png]]
1848
1849 (% class="wikigeneratedid" %)
1850 **Cable Wiring**
1851
1852 (% class="wikigeneratedid" id="H" %)
1853 [[image:image-20220829152610-7.png]]
1854
1855 (% style="text-align:center" %)
1856 [[image:image-20220829152102-5.png]]
1857
1858 == DVP Ethernet Protocol ==
1859
1860 (% class="wikigeneratedid" %)
1861 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
1862
1863 **HMI Settings**
1864
1865 |=**Items**|=**Settings**|=**Note**
1866 |Protocol|DELTA DVP Modbus TCP|
1867 |Connection|Ethernet|
1868 |Port No.|201|Must be the same as the PLC setting
1869 |PLC station No.|0|Must be the same as the PLC setting
1870
1871 **Address List**
1872
1873 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1874 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
1875 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
1876 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
1877 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
1878 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
1879 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
1880 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
1881 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
1882 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
1883
1884 )))
1885 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
1886 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
1887
1888 )))
1889
1890 (% class="wikigeneratedid" %)
1891 **Configure the communication protocol**
1892
1893 (% style="text-align:center" %)
1894 [[image:image-20220829155452-1.png]]
1895
1896 [[image:image-20220829162116-2.png]]
1897
1898 **Cable Wiring**
1899
1900 (% style="text-align:center" %)
1901 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1902
1903 (% class="wikigeneratedid" %)
1904 == **AS serial protocol** ==
1905
1906 Supported Series: Delta AS200/AS300
1907
1908 **HMI Settings**
1909
1910 |**Item**|**Settings**|**Note**
1911 |Protocol|DELTA AS300 MODBUS RTU|
1912 |Connection|RS485|
1913 |Baud rate|9600|
1914 |Data bit|8|
1915 |Parity|NONE|
1916 |Stop bit|1|
1917 |PLC station No.|1|
1918
1919 **Address List**
1920
1921 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1922 |Bit|X|X|Xdd.dd|0~~63.15|Read only
1923 |Bit|Y|Y|Ydd.dd|0~~63.15|
1924 |Bit|D|D|Dddddd|0~~29999|
1925 |Bit|M|M|Mdddd|0~~8191|
1926 |Bit|SM|SM|SMdddd|0~~4095|
1927 |Bit|S|S|Sdddd|0~~2047|
1928 |Bit|T|T|Tddd|0~~511|
1929 |Bit|C|C|Cddd|0~~511|
1930 |Bit|HC|HC|HCddd|0~~255|Double Word
1931 |Word|X|X|Xdd|0~~63|
1932 |Word|Y|Y|(((
1933 Ydd
1934 )))|0~~63|
1935 |Word|SR|SR|SRdddd|0~~2047|Special register
1936 |Word|D|D|Dddddd|0~~29999|
1937 |Word|T|T|Tddd|0~~511|
1938 |Word|C|C|Cddd|0~~511|
1939 |Word|E|E|Ed|0~~9|
1940
1941 **Configure the communication protocol**
1942
1943 Create project
1944
1945 (% style="text-align:center" %)
1946 [[image:AsCreateProject.png]]
1947
1948 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
1949
1950 (% style="text-align:center" %)
1951 [[image:AScommunicarw.png]]
1952
1953 Double click the HWCONFIG to open the communication settings window.
1954
1955 (% style="text-align:center" %)
1956 [[image:ASHWCONFIG.png]]
1957
1958 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
1959
1960 (% style="text-align:center" %)
1961 [[image:ASHSCONFIGICON.png]]
1962
1963 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
1964
1965 (% style="text-align:center" %)
1966 [[image:ASModbusMode.png]]
1967
1968 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
1969
1970 (% style="text-align:center" %)
1971 [[image:ASconfigIP.png]]
1972
1973 (% style="text-align:center" %)
1974 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
1975
1976
1977 (% style="text-align:center" %)
1978 [[image:image-20220830094657-2.png]]
1979
1980 **Cable Wiring**
1981
1982 (% style="text-align:center" %)
1983 [[image:image-20220830141138-1.png]]
1984
1985 Pin Definition Diagram
1986
1987 (% style="text-align:center" %)
1988 [[image:image-20220830095131-1.png]]
1989
1990 == AS Ethernet Protocol ==
1991
1992 **HMI Settings**
1993
1994 |=**Items**|=**Settings**|=**Note**
1995 |Protocol|DELTA AS300 MODBUS TCP|
1996 |Connection|Ethernet|
1997 |Port No.|502|
1998 |Device No.|1|
1999 |HMI No.|0|
2000
2001 **Address List**
2002
2003 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2004 |Bit|X|X|X d|0~~63|
2005 |Bit|Y|Y|Y d|0~~63|
2006 |Bit|D|D|D d|0~~29999|
2007 |Bit|M|M|M d|0~~8191|
2008 |Bit|SM|SM|SM d|0~~4095|
2009 |Bit|S|S|S h|0~~2047|
2010 |Bit|T|T|T d|0~~511|
2011 |Bit|C|C|C d|0~~511|
2012 |Bit|HC|HC|HC d|0~~255|
2013 |Word|X|X|X h|0~~63|
2014 |Word|Y|Y|Y d|0~~63|
2015 |Word|SR|SR|SR d|0~~2047|
2016 |Word|D|D|D d|0~~29999|
2017 |Word|T|T|T d|0~~511|
2018 |Word|C|C|C h|0~~511|
2019 |Word|E|E|E d|0~~9|
2020
2021 **Configure the communication protocol**
2022
2023 (% style="text-align:center" %)
2024 [[image:image-20220830140537-1.png]]
2025
2026 (% style="text-align:center" %)
2027 [[image:image-20220830140629-2.png]]
2028
2029 **Cable Wiring**
2030
2031 [[image:image-20220830094929-1.png]]
2032
2033 Pin Definition Diagram
2034
2035 (% style="text-align:center" %)
2036 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2037
2038 = Create communication with **Omron** PLC =
2039
2040 == CJ TCP FINS Ethemet  Protocol ==
2041
2042 Supported device:CJ series、CJ1W-EIP21
2043
2044 **HMI Settings**
2045
2046 |=**Items**|=**Settings**|=**Note**
2047 |Protocol|OMRON CJ TCP FINS Ethemet|
2048 |Connection|Ethernet|
2049 |Port No.|9600|
2050 |Device No.|0|
2051 |HMI No.|0|(((
2052
2053 )))
2054
2055 **Address List**
2056
2057 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2058 |Bit|CIO|CIO|CIO d|0~~99999|
2059 |Bit|W|W|W d|0~~99999|
2060 |Bit|D|D|D d|0~~99999|
2061 |Bit|H|H|H d|0~~99999|
2062 |Bit|A|A|A d|0~~99999|
2063 |Bit|T|T|T h|0~~99999|
2064 |Bit|CF|CF|CF d|0~~99999|
2065 |Bit|FF|FF|FF d|0~~99999|
2066 |Bit|C|C|C d|0~~99999|
2067 |Bit|EM0|EM0|EM0 d|0~~99999|
2068 |Bit|EM1|EM1|EM1 d|0~~99999|
2069 |Bit|EM2|EM2|EM2 d|0~~99999|
2070 |Bit|EM3|EM3|EM3 d|0~~99999|
2071 |Bit|EM4|EM4|EM4 d|0~~99999|
2072 |Bit|EM5|EM5|EM5 h|0~~99999|
2073 |Bit|EM6|EM6|EM6 d|0~~99999|
2074 |Bit|EM7|EM7|EM7 d|0~~99999|
2075 |Bit|EM8|EM8|EM8 d|0~~99999|
2076 |Bit|EM9|EM9|EM9 d|0~~99999|
2077 |Bit|EMA|EMA|EMA d|0~~99999|
2078 |Bit|EMB|EMB|EMB d|0~~99999|
2079 |Bit|EMC|EMC|EMC d|0~~99999|
2080 |Bit|Lamp|Lamp|Lamp d|0~~0|
2081 |Word|CIO|CIO|CIO d|0~~99999|
2082 |Word|W|W|W d|0~~99999|
2083 |Word|D|D|D d|0~~99999|
2084 |Word|H|H|H d|0~~99999|
2085 |Word|A|A|A d|0~~99999|
2086 |Word|T|T|T h|0~~99999|
2087 |Word|CF|CF|CF d|0~~99999|
2088 |Word|FF|FF|FF d|0~~99999|
2089 |Word|C|C|C d|0~~99999|
2090 |Word|EM0|EM0|EM0 d|0~~99999|
2091 |Word|EM1|EM1|EM1 d|0~~99999|
2092 |Word|EM2|EM2|EM2 d|0~~99999|
2093 |Word|EM3|EM3|EM3 d|0~~99999|
2094 |Word|EM4|EM4|EM4 d|0~~99999|
2095 |Word|EM5|EM5|EM5 h|0~~99999|
2096 |Word|EM6|EM6|EM6 d|0~~99999|
2097 |Word|EM7|EM7|EM7 d|0~~99999|
2098 |Word|EM8|EM8|EM8 d|0~~99999|
2099 |Word|EM9|EM9|EM9 d|0~~99999|
2100 |Word|EMA|EMA|EMA d|0~~99999|
2101 |Word|EMB|EMB|EMB d|0~~99999|
2102 |Word|EMC|EMC|EMC d|0~~99999|
2103 |Word|IR|IR|IR d|0~~99999|
2104 |Word|DR|DR|DR d|0~~99999|
2105
2106 **Configure the communication protocol**
2107
2108 (% style="text-align:center" %)
2109 [[image:image-20220830143348-1.png]]
2110
2111 (% style="text-align:center" %)
2112 [[image:image-20220830143511-2.png]]
2113
2114 **Configure CJ1W-EIP21 connect with HMI**
2115
2116 (% style="text-align:center" %)
2117 [[image:ftEVGvAprh.png]]
2118
2119 Select TCP_Client_2N
2120
2121 (% style="text-align:center" %)
2122 [[image:RURXWcgyCd.png]]
2123
2124 **Cable Wiring**
2125
2126 Pin Definition Diagram
2127
2128 (% style="text-align:center" %)
2129 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2130
2131 == **CP1E/CP1H serial protocol** ==
2132
2133 Supported device: OMRON CS1(CP1E/CP1H)
2134
2135 **HMI Settings**
2136
2137 |=**Items**|=**Settings**|=**Note**
2138 |Protocol|OMRON CS1(CP1E/CP1H)|
2139 |Connection|RS232 (9600, 2, 7, EVEN)|
2140 |Port No.|None|
2141 |PLC station No.|0|
2142
2143 **Address List**
2144
2145 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2146 |Bit|CIO|CIO|CIO d|0~~99999|
2147 |Bit|W|W|W d|0~~99999|
2148 |Bit|D|D|D d|0~~99999|
2149 |Bit|H|H|H d|0~~99999|
2150 |Bit|A|A|A d|0~~99999|
2151 |Bit|TF|T|T h|0~~99999|
2152 |Bit|CF|CF|CF d|0~~99999|
2153 |Bit|T|FF|FF d|0~~99999|
2154 |Bit|C|C|C d|0~~99999|
2155 |Bit|EM0|EM0|EM0 d|0~~99999|
2156 |Bit|EM1|EM1|EM1 d|0~~99999|
2157 |Bit|EM2|EM2|EM2 d|0~~99999|
2158 |Bit|EM3|EM3|EM3 d|0~~99999|
2159 |Bit|EM4|EM4|EM4 d|0~~99999|
2160 |Bit|EM5|EM5|EM5 h|0~~99999|
2161 |Bit|EM6|EM6|EM6 d|0~~99999|
2162 |Bit|EM7|EM7|EM7 d|0~~99999|
2163 |Bit|EM8|EM8|EM8 d|0~~99999|
2164 |Bit|EM9|EM9|EM9 d|0~~99999|
2165 |Bit|EMA|EMA|EMA d|0~~99999|
2166 |Bit|EMB|EMB|EMB d|0~~99999|
2167 |Bit|EMC|EMC|EMC d|0~~99999|
2168 |Word|CIO|CIO|CIO d|0~~99999|
2169 |Word|W|W|W d|0~~99999|
2170 |Word|D|D|D d|0~~99999|
2171 |Word|H|H|H d|0~~99999|
2172 |Word|A|A|A d|0~~99999|
2173 |Word|T|T|T h|0~~99999|
2174 |Word|CIO|CF|CF d|0~~99999|
2175 |Word|C|C|C d|0~~99999|
2176 |Word|EM0|EM0|EM0 d|0~~99999|
2177 |Word|EM1|EM1|EM1 d|0~~99999|
2178 |Word|EM2|EM2|EM2 d|0~~99999|
2179 |Word|EM3|EM3|EM3 d|0~~99999|
2180 |Word|EM4|EM4|EM4 d|0~~99999|
2181 |Word|EM5|EM5|EM5 h|0~~99999|
2182 |Word|EM6|EM6|EM6 d|0~~99999|
2183 |Word|EM7|EM7|EM7 d|0~~99999|
2184 |Word|EM8|EM8|EM8 d|0~~99999|
2185 |Word|EM9|EM9|EM9 d|0~~99999|
2186 |Word|EMA|EMA|EMA d|0~~99999|
2187 |Word|EMB|EMB|EMB d|0~~99999|
2188 |Word|EMC|EMC|EMC d|0~~99999|
2189 |Word|IR|IR|IR d|0~~99999|
2190 |Word|DR|DR|DR d|0~~99999|
2191
2192 **Configure the communication protocol**
2193
2194 (% style="text-align:center" %)
2195 [[image:image-20220902153118-1.png]]
2196
2197 (% style="text-align:center" %)
2198 [[image:image-20220902151322-2.png]]
2199
2200 **Cable Wiring**
2201
2202 (% style="text-align:center" %)
2203 [[image:image-20220902153949-2.png]]
2204
2205 Pin Definition Diagram
2206
2207 (% style="text-align:center" %)
2208 [[image:image-20220902154056-3.png]]
2209
2210 == **EC55 Protocol** ==
2211
2212 Supported device: EC55 temperature instrument
2213
2214 **1)HMI Settings**
2215
2216 |**Items**|**Settings**|**Note**
2217 |Protocol|Omron EC55|
2218 |Connection|RS485 (9600, 2, 7, EVEN)|
2219 |Port No.|None|
2220 |PLC station No.|0|
2221
2222 **2)Address List**
2223
2224 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2225 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2226 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2227 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2228 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2229 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2230 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2231 |CP|-|0-6|Read controller intrinsic property
2232 |CS|-|0-2|Read controller states
2233 |CA|-|0-17|Action command
2234
2235 **3)Device Settings**
2236
2237 Omron E5CC PLC configuration
2238
2239 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2240
2241 (% style="text-align:center" %)
2242 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2243
2244 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2245
2246 (% style="text-align:center" %)
2247 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2248
2249 **✎Note:** The communication settings for HMI should be consistent with this setting.
2250
2251 **Cable Wiring**
2252
2253 (% style="text-align:center" %)
2254 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2255
2256 (% style="text-align:center" %)
2257 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2258
2259 **✎Note:**
2260
2261 * COM3 only available in PI8000/PI9000 series.
2262 * CA address could not support continuous writing function;
2263 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2264 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2265 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2266 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2267 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2268 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2269 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2270
2271 == **EtherNet/IP NX series Protocol** ==
2272
2273 Supported series: Omron NX/NJ series
2274
2275 **HMI Setting**
2276
2277 |**Items**|**Settings**|**Note**
2278 |Protocol|Omron NX Ethernet/IP|
2279 |Connection|Ethernet|
2280 |Port No.|44818|
2281 |PLC station No.|1|
2282
2283 **Instruction**
2284
2285 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2286
2287 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2288
2289 (% style="text-align:center" %)
2290 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2291
2292 **Export labels from Sysmac Studio**
2293
2294 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2295
2296 (% style="text-align:center" %)
2297 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2298
2299 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2300
2301 Click [Label manage];
2302
2303 (% style="text-align:center" %)
2304 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2305
2306 Click [Import labels] and then select the file exported in step 1;
2307
2308 (% style="text-align:center" %)
2309 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2310
2311 The Import Status field shows the result, click [OK] to finish importing address labels;
2312
2313 (% style="text-align:center" %)
2314 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2315
2316 **Communication Settings**
2317
2318 Enable HMI Ethernet in [Project Settings];
2319
2320 (% style="text-align:center" %)
2321 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2322
2323 Set PLC IP in [Device IP] settings;
2324
2325 (% style="text-align:center" %)
2326 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2327
2328 (% style="text-align:center" %)
2329 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2330
2331 **Cable Wiring**
2332
2333 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2334
2335 == CV/CJ1M/CS1H ==
2336
2337 **HMI Setting:**
2338
2339 |=(% scope="row" %)**Parameters**|=**Recommended**
2340 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2341 |=**PLC I/F**|RS232
2342 |=**Baud rate**|9600
2343 |=**Data bits**|7
2344 |=**Parity**|Even
2345 |=**Stop bits**|2
2346 |=**PLC sta. no.**|0
2347
2348 **PLC Setting:**
2349
2350 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2351
2352 **Device Address:**
2353
2354 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2355 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2356 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2357 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2358 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2359 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2360 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2361 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2362 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2363 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2364 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2365 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2366 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2367 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2368 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2369 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2370 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2371 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2372 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2373 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2374 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2375 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2376 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2377 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2378
2379 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2380 |=W|LR_W|DDDD|0 ~~ 4095|
2381 |=W|TC|DDD|0 ~~ 511|
2382 |=W|DM|DDDD|0 ~~ 9999|Data Register
2383
2384 **Wiring Diagram:**
2385
2386 **RS-232**
2387
2388 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2389
2390 Communication Module:
2391
2392 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2393
2394 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2395
2396 (% style="text-align:center" %)
2397 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2398
2399 = Create communication with Xinje** PLC** =
2400
2401 == XC serial protocol ==
2402
2403 **HMI Settings**
2404
2405 |**Item**|**Settings**|**Note**
2406 |Protocol|XINJE XC MODBUS|
2407 |Connection|RS232|
2408 |Baud rate|19200|
2409 |Data bit|8|
2410 |Parity|EVEN|
2411 |Stop bit|1|
2412 |PLC station No.|1|
2413
2414 **Address List**
2415
2416 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2417 |Bit|M|M|M d|0~~8511|
2418 |Bit|X|X|X o|0~~1747|
2419 |Bit|Y|Y|Y o|0~~1747|
2420 |Bit|S|S|S d|0~~1023|
2421 |Bit|T|T|T d|0~~4095|
2422 |Bit|C|C|C d|0~~634|
2423 |Word|D|D|D d|0~~8511|
2424 |Word|TD|TD|TD d|0~~618|
2425 |Word|CD|CD|CD d|0~~634|
2426 |Word|FD|FD|FD d|0~~8511|
2427
2428 **Configure the communication protocol**
2429
2430 (% style="text-align:center" %)
2431 [[image:image-20220830154105-1.png]]
2432
2433 (% style="text-align:center" %)
2434 [[image:image-20220830154159-3.png]]
2435
2436 **Cable Wiring**
2437
2438 Figure
2439
2440 [[image:image-20220830155728-4.png]]
2441
2442 Pin Definition Diagram
2443
2444 (% style="text-align:center" %)
2445 [[image:image-20220830154131-2.png]]
2446
2447 == XD serial protocol ==
2448
2449 **HMI Settings**
2450
2451 Supported Series: Xinjie XD/XE Series PLC
2452
2453 |=**Item**|=**Settings**|=**Note**
2454 |Protocol|XINJE XD/XC MODBUS|
2455 |Connection|RS232|
2456 |Baud rate|19200|
2457 |Data bit|8|
2458 |Parity|EVEN|
2459 |Stop bit|1|
2460 |PLC station No.|1|
2461
2462 **Address List**
2463
2464 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2465 |Bit|M|M|M d|0~~74999|
2466 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2467 |Bit|X2xx|X2xx|X2xx o|0~~277|
2468 |Bit|X|X|X o|0~~77|
2469 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2470 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2471 |Bit|Y|Y|Y o|0~~4095|
2472 |Bit|SM|SM|SM d|0~~4999|(((
2473
2474 )))
2475 |Bit|T|T|T d|0~~4999|
2476 |Bit|C|C|C d|0~~4999|
2477 |Bit|ET|ET|ET d|0~~31|
2478 |Bit|SE|SE|SE d|0~~31|
2479 |Bit|HM|HM|HM d|0~~11999|
2480 |Bit|HSC|HSC|HSC d|0~~39|
2481 |Bit|HS|HS|HS d|0~~999|
2482 |Bit|HT|HT|HT d|0~~1999|
2483 |Bit|HC|HC|HC d|0~~1999|
2484 |Bit|S|S|S d|0~~7999|
2485 |Word|D|D|D d|0~~69999|
2486 |Word|ID|ID|ID d|0~~99|
2487 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2488 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2489 |Word|QD|QD|QD d|0~~99|
2490 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2491 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2492 |Word|SD|SD|SD d|0~~4999|
2493 |Word|TD|TD|TD d|0~~575|
2494 |Word|CD|CD|CD d|0~~575|
2495 |Word|ETD|ETD|ETD d|0~~31|
2496 |Word|HD|HD|HD d|0~~24999|
2497 |Word|HSD|HSD|HSD d|0~~1023|
2498 |Word|HTD|HTD|HTD d|0~~95|
2499 |Word|HCD|HCD|HCD d|0~~95|
2500 |Word|HSCD|HSCD|HSCD d|0~~31|
2501 |Word|FD|FD|FD d|0~~8191|
2502 |Word|SFD|SFD|SFD d|0~~5999|
2503 |Word|FS|FS|FS d|0~~47|
2504
2505 **Configure the communication protocol**
2506
2507 (% style="text-align:center" %)
2508 [[image:image-20220830160042-1.png]]
2509
2510 (% style="text-align:center" %)
2511 [[image:image-20220830160129-2.png]]
2512
2513 **Cable Wiring**
2514
2515 (% style="text-align:center" %)
2516 [[image:image-20220905093902-1.png]]
2517
2518 Pin Definition Diagram
2519
2520 (% style="text-align:center" %)
2521 [[image:image-20220830160232-3.png]]
2522
2523 = Create communication with Inovance** PLC** =
2524
2525 == H3U serial protocol ==
2526
2527 **HMI Settings**
2528
2529 |=**Item**|=**Settings**|=**Note**
2530 |Protocol|INOVANCE H3U PLC|
2531 |Connection|RS422|
2532 |Baud rate|9600|
2533 |Data bit|7|
2534 |Parity|EVEN|
2535 |Stop bit|1|
2536 |PLC station No.|0|
2537
2538 **Address List**
2539
2540 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2541 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X|X o|0~~303237|
2542 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2543 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M|M d|0~~99999|
2544 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T|T d|0~~99999|
2545 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C|C d|0~~99999|
2546 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM|SM d|8000~~999|
2547 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|T|S d|0~~99999|
2548 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp|Lamp d|0~~0|
2549 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X|X o|0~~303237|
2550 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2551 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M|M d|0~~99999|
2552 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T|T d|0~~99999|
2553 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C|C d|0~~199|
2554 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D|D d|0~~7999|
2555 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S|S d|0~~99999|
2556 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD|SD d|8000~~9999|
2557 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R|R d|0~~32767|
2558
2559 **Configure the communication protocol**
2560
2561 (% style="text-align:center" %)
2562 [[image:image-20220830170114-4.png]]
2563
2564 [[image:image-20220830170017-3.png]]
2565
2566 **Cable Wiring**
2567
2568 (% style="text-align:center" %)
2569 [[image:image-20220830165930-1.png]]
2570
2571 Pin Definition Diagram
2572
2573 (% style="text-align:center" %)
2574 [[image:image-20220830165947-2.png]]
2575
2576 = Create communication with Panasonic** PLC** =
2577
2578 == **FP serial protocol** ==
2579
2580 **1)HMI Settings**
2581
2582 |**Item**|**Settings**|**Note**
2583 |Protocol|Panasonic FP MFWTOCOL|
2584 |Connection|RS232|
2585 |Baud rate|9600|
2586 |Data bit|8|
2587 |Parity|ODD|
2588 |Stop bit|1|
2589 |PLC station No.|1|
2590
2591 **2)Address List**
2592
2593 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2594 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2595 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2596 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2597 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2598 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2599 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2600 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2601 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2602 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2603 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2604 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2605 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2606 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2607 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2608 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2609
2610 **3)Configure the communication protocol**
2611
2612 [[image:image-20220830171050-1.png]]
2613
2614 [[image:image-20220830171126-2.png]]
2615
2616 **4)Cable Wiring**
2617
2618 Figure
2619
2620 [[image:image-20220830171328-4.png]]
2621
2622 Pin Definition Diagram
2623
2624 [[image:image-20220830171146-3.png]]
2625
2626 = Create communication with LS** PLC** =
2627
2628 == **XGB serial protocol ** ==
2629
2630 **HMI Settings**
2631
2632
2633 |=**Item**|=**Settings**|=**Note**
2634 |Protocol|LS XGB CPU DRIECT|
2635 |Connection|RS232|
2636 |Baud rate|115200|
2637 |Data bit|8|
2638 |Parity|NONE|
2639 |Stop bit|1|
2640 |PLC station No.|1|
2641
2642 **Address List**
2643
2644
2645 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2646 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2647 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2648 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2649 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2650 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2651 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2652 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2653 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2654 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2655 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2656 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2657 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2658 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2659 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2660 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2661 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2662 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2663 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2664 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2665 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2666 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2667 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2668 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2669 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2670 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2671 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2672
2673 **Configure the communication protocol**
2674
2675 (% style="text-align:center" %)
2676 [[image:image-20221028174410-1.png]]
2677
2678 (% style="text-align:center" %)
2679 [[image:image-20221028174753-2.png]]
2680
2681
2682 (% style="text-align:center" %)
2683 [[image:image-20221028181125-4.png]]
2684
2685 **Pin Definition Diagram**
2686
2687 (% style="text-align:center" %)
2688 [[image:image-20221028180930-3.png]]
2689
2690 = Create communication with LS** PLC** =
2691
2692 == **XBC serial protocol** ==
2693
2694 **HMI Settings**
2695
2696 |=**Item**|=**Settings**|=**Note**
2697 |Protocol|LS XBC CNet|
2698 |Connection|RS232|
2699 |Baud rate|115200|
2700 |Data bit|8|
2701 |Parity|NONE|
2702 |Stop bit|1|
2703 |PLC station No.|1|
2704
2705 **Address List**
2706
2707 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2708 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2709 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2710 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2711 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2712 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2713 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2714 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2715 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2716 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2717 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2718 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2719 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2720 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2721 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2722 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2723 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2724 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2725 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2726 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2727 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2728 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2729
2730 **Configure the communication protocol**
2731
2732 (% style="text-align:center" %)
2733 [[image:image-20220831170807-1.png]]
2734
2735 (% style="text-align:center" %)
2736 [[image:image-20220830174733-2.png]]
2737
2738 **Cable Wiring**
2739
2740 (% style="text-align:center" %)
2741 [[image:image-20220830174659-1.png]]
2742
2743 Pin Definition Diagram
2744
2745 (% style="text-align:center" %)
2746 [[image:image-20220830173402-8.png]]
2747
2748 == **XGK FEnet Ethernet protocol** ==
2749
2750 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2751
2752 **HMI Settings**
2753
2754 |**Items**|**Settings**|**Note**
2755 |Protocol|LG XGK FEnet(Ethernet)|
2756 |Connection|Ethernet|
2757 |Port No.|2004|
2758
2759 **Address List**
2760
2761 |**Type**|**Register**|**Range**|**Format**|**Note**
2762 |(% rowspan="14" %)Word|P|0~~2047|P d|
2763 |M|0~~2047|M d|
2764 |K|0~~2047|K d|
2765 |F|0~~2047|F d|
2766 |T|0~~2047|T d|
2767 |C|0~~2047|C d|
2768 |Z|0~~127|Z d|
2769 |S|0~~127|S d|
2770 |L|0~~11263|L d|
2771 |N|0~~21503|N d|
2772 |D|0~~32767|D d|
2773 |R|0~~32767|R d|
2774 |ZR|0~~65535|ZR d|
2775 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2776
2777 **✎Note:**
2778
2779 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2780 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2781 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2782
2783 **Communication settings in HMI**
2784
2785 Enable HMI Ethernet in [Project Settings];
2786
2787 (% style="text-align:center" %)
2788 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2789
2790 Set PLC IP in [Device IP] settings;
2791
2792 (% style="text-align:center" %)
2793 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2794
2795 **Cable Wiring**
2796
2797 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2798
2799 = Create communication with LS** PLC** =
2800
2801 == **XBC serial protocol** ==
2802
2803 **HMI Settings**
2804
2805 |=**Item**|=**Settings**|=**Note**
2806 |Protocol|LS XBC CNet|
2807 |Connection|RS232|
2808 |Baud rate|115200|
2809 |Data bit|8|
2810 |Parity|NONE|
2811 |Stop bit|1|
2812 |PLC station No.|1|
2813
2814 **Address List**
2815
2816 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2817 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2818 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2819 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2820 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2821 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2822 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2823 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2824 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2825 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2826 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2827 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2828 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2829 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2830 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2831 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2832 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2833 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2834 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2835 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2836 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2837 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2838
2839 **Configure the communication protocol**
2840
2841 (% style="text-align:center" %)
2842 [[image:image-20220831170807-1.png]]
2843
2844 (% style="text-align:center" %)
2845 [[image:image-20220830174733-2.png]]
2846
2847 **Cable Wiring**
2848
2849 (% style="text-align:center" %)
2850 [[image:image-20220830174659-1.png]]
2851
2852 Pin Definition Diagram
2853
2854 (% style="text-align:center" %)
2855 [[image:image-20220830173402-8.png]]
2856
2857 == **XGK FEnet Ethernet protocol** ==
2858
2859 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2860
2861 **HMI Settings**
2862
2863 |**Items**|**Settings**|**Note**
2864 |Protocol|LG XGK FEnet(Ethernet)|
2865 |Connection|Ethernet|
2866 |Port No.|2004|
2867
2868 **Address List**
2869
2870 |**Type**|**Register**|**Range**|**Format**|**Note**
2871 |(% rowspan="14" %)Word|P|0~~2047|P d|
2872 |M|0~~2047|M d|
2873 |K|0~~2047|K d|
2874 |F|0~~2047|F d|
2875 |T|0~~2047|T d|
2876 |C|0~~2047|C d|
2877 |Z|0~~127|Z d|
2878 |S|0~~127|S d|
2879 |L|0~~11263|L d|
2880 |N|0~~21503|N d|
2881 |D|0~~32767|D d|
2882 |R|0~~32767|R d|
2883 |ZR|0~~65535|ZR d|
2884 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2885
2886 **✎Note:**
2887
2888 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2889 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2890 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2891
2892 **Communication settings in HMI**
2893
2894 Enable HMI Ethernet in [Project Settings];
2895
2896 (% style="text-align:center" %)
2897 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2898
2899 Set PLC IP in [Device IP] settings;
2900
2901 (% style="text-align:center" %)
2902 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2903
2904 **Cable Wiring**
2905
2906 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2907
2908 = Create communication with **SHIMADEN PLC** =
2909
2910 == **FP23 series protocol** ==
2911
2912 Supported series: SHIMADEN FP23 series
2913
2914 **HMI Setting**
2915
2916 |**Items**|**Settings**|**Note**
2917 |Protocol|SHIMADEN FP23 series|
2918 |Connection|RS485 (9600, 1, 7, EVEN)|
2919 |Port No.|None|
2920 |PLC station No.|0|
2921
2922 **Address List**
2923
2924 |**Device address**|**HMI register**|**Address range**|**Type**
2925 |0040-0043(HEX)|FP040|100064-200067|Read only
2926 |0100-010B(HEX)|FP100|100256-200267|Read only
2927 |0110-0142(HEX)|FP110|100272-200322|Read only
2928 |0182-0252(HEX)|FP182|100386-200594|Write only
2929 |0280-0281(HEX)|FP280|100640-200641|Read only
2930 |0300-030B(HEX)|FP300|100768-200779|Read and write
2931 |0380-039F(HEX)|FP380|100896-200927|Read and write
2932 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2933 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2934 |0600-0670(HEX)|FP600|101536-201814|Read and write
2935 |0720-0738(HEX)|FP720|101824-201848|Read and write
2936 |0800-083F(HEX)|FP800|102048-202111|Read and write
2937 |0900-0952(HEX)|FP900|102304-202386|Read and write
2938 | |Ctrl|0-2|
2939
2940 **✎Note:**
2941
2942 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2943 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2944 * The Ctrl register is used to store the control group number and BCC check mode.
2945
2946 **Ctrl Register Description**
2947
2948 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2949 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2950 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2951 * Ctrl3 reserved
2952
2953 **✎Note:**
2954
2955 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2956
2957 **Cable Wiring**
2958
2959 (% style="text-align:center" %)
2960 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2961
2962 (% style="text-align:center" %)
2963 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2964
2965 **✎Note:** COM3 only available in PI8000/PI9000 series.
2966
2967 == **SR90 protocol** ==
2968
2969 Supported series: SHIMADEN SR90 series
2970
2971 **HMI Setting**
2972
2973 |**Items**|**Settings**|**Note**
2974 |Protocol|SHIMADEN SR90 protocol|
2975 |Connection|RS485 (1200, 1, 7, EVEN)|
2976 |Port No.|None|
2977 |PLC station No.|0|
2978
2979 **Address List**
2980
2981 |**Device address**|**HMI register**|**Address range**|**Type**
2982 |0040-0043 (HEX)|SR040|100064-100067|Read only
2983 |0100-010A(HEX)|SR0100|100256-100266|Read only
2984 |0182-018C(HEX)|SR0182|100386-100396|Write only
2985 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2986 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2987 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2988 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2989 | |Ctrl|0-2|~-~-
2990
2991 **✎Note:**
2992
2993 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2994 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2995 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2996
2997 **Ctrl Register Description**
2998
2999 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3000 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3001 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3002 * Ctrl3 reserved
3003
3004 **✎Note:**
3005
3006 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3007
3008 **Cable Wiring**
3009
3010 (% style="text-align:center" %)
3011 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3012
3013 (% style="text-align:center" %)
3014 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3015
3016 **✎Note:** COM3 only available in PI8000/PI9000 series.
3017
3018 == **MR13 series(standard protocol)** ==
3019
3020 Supported series: SHIMADEN MR13 series
3021
3022 **HMI Setting**
3023
3024 |**Items**|**Settings**|**Note**
3025 |Protocol|SHIMADEN standard protocol|
3026 |Connection|RS485 (1200, 1, 7, EVEN)|
3027 |Port No.|None|
3028 |PLC station No.|0|
3029
3030 **Address List**
3031
3032 |**Device address**|**HMI register**|**Address range**|**Type**
3033 |0100-010B(HEX)|MR100|100256-300267|Read only
3034 |0111-0126(HEX)|MR111|100273-300294|Read only
3035 |0184-0192(HEX)|MR184|100388-300402|Write only
3036 |0280-0282(HEX)|MR280|100640-300642|Read only
3037 |0300-030B(HEX)|MR300|100768-300779|Read/write
3038 |0314-0317(HEX)|MR314|100788-300791|Read/write
3039 |031A(HEX)|MR31A|100794-300794|Read/write
3040 |0320-0321(HEX)|MR320|100800-300801|Read/write
3041 |0400-0504(HEX)|MR400|101024-301284|Read/write
3042 |0506(HEX)|MR506|101286-301286|Read/write
3043 |0510-0514(HEX)|MR510|101296-301300|Read/write
3044 |0516-0524(HEX)|MR516|101302-301316|Read/write
3045 |0526(HEX)|MR526|101318-301318|Read/write
3046 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3047 |~-~-|Ctrl|0-2|~-~-
3048
3049 **✎Note:**
3050
3051 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3052 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3053 * The Ctrl register is used to store the control group number and BCC check mode.
3054
3055 **Ctrl Register Description**
3056
3057 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3058 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3059 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3060 * Ctrl3 reserved
3061
3062 **✎Note:**
3063
3064 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3065
3066 **Cable Wiring**
3067
3068 (% style="text-align:center" %)
3069 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3070
3071 (% style="text-align:center" %)
3072 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3073
3074 **✎Note:** COM3 only available in PI8000/PI9000 series.
3075
3076 = Create communication with **MODBUS** =
3077
3078 == **MODBUS RTU Master** ==
3079
3080 Supported Series: MODBUS RTU CONTROLLER
3081
3082 HMI works as MODBUS SLAVE connecting with MASTER
3083
3084 (% style="text-align:center" %)
3085 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3086
3087
3088 (% style="text-align:center" %)
3089 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3090
3091
3092 (% style="text-align:center" %)
3093 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3094
3095 **HMI Settings**
3096
3097 (% class="table-bordered" %)
3098 |**Items**|**Settings**|**Note**
3099 |Protocol|MODBUS RTU Master|
3100 |Connection|RS485/RS232|
3101 |Baud rate|2400~~187500|
3102 |Data bit|8|
3103 |Parity|Even/ Odd/ None|
3104 |Stop bit|1/2|
3105 |Station No.|0~~255|
3106
3107 **Address List**
3108
3109 (% class="table-bordered" %)
3110 |**Type**|**HMI address**|**MODBUS code**|**Range**
3111 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3112 |Word|HDW3500~~HDW7999|4|0~~4499
3113
3114 **Cable Wiring**
3115
3116 * **RS485**
3117
3118 (% style="text-align:center" %)
3119 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3120
3121 (% style="text-align:center" %)
3122 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3123
3124 * **RS232**
3125
3126 (% style="text-align:center" %)
3127 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3128
3129 **✎Note:** COM3 only available in PI8000/PI9000 series.
3130
3131 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3132
3133 Supported Series: MODBUS RTU CONTROLLER
3134
3135 HMI works as MODBUS MASTER connecting with SLAVE.
3136
3137 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3138
3139 (% style="text-align:center" %)
3140 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3141
3142
3143 (% style="text-align:center" %)
3144 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3145
3146
3147 (% style="text-align:center" %)
3148 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3149
3150 **HMI Settings**
3151
3152 (% class="table-bordered" %)
3153 |**Items**|**Settings**|**Note**
3154 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3155 |Connection|RS485/RS232|
3156 |Baud rate|2400~~187500|
3157 |Data bit|8|
3158 |Parity|Even/ Odd/ None|
3159 |Stop bit|1/2|
3160 |PLC station No.|0~~255|
3161
3162 **Address List**
3163
3164 (% class="table-bordered" %)
3165 |**Type**|**Address Type**|**Function code & Description**
3166 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3167 |06 (write single register: write a binary value to a holding register)
3168 |10 (write values to multiple addresses )
3169 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3170 |06 (write single register: write a binary value to a holding register)
3171 |10 (write values to multiple addresses )
3172 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3173 |06 (write single register: write a binary value to a holding register)
3174 |10 (write values to multiple addresses )
3175 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3176 |10 (write values to multiple addresses )
3177 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3178 |05 (Force a single coil to force the on/off state of a logic coil)
3179 |0F (Write multiple bits, ie write continuously)
3180 |(% rowspan="3" %)1|02 (Read the input state)
3181 |05 (Force a single coil to force the on/off state of a logic coil)
3182 |0F (Write multiple bits)
3183 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3184 |05 (Force a single coil to force the on/off state of a logic coil)
3185 |0F (Write multiple bits)
3186 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3187 |0F (Write multiple bits)
3188
3189 **✎Note:**
3190
3191 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3192 * The function codes sent out are the same as those that read and write words.
3193
3194 **Station number for more than one slaves**
3195
3196 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3197
3198 (% style="text-align:center" %)
3199 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3200
3201 **Cable Wiring**
3202
3203 * **RS485**
3204
3205 (% style="text-align:center" %)
3206 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3207
3208 (% style="text-align:center" %)
3209 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3210
3211 * **RS232**
3212
3213 (% style="text-align:center" %)
3214 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3215
3216 **✎Note:** COM3 only available in PI8000/PI9000 series.
3217
3218 == **MODBUS TCP Slave (All function)** ==
3219
3220 Supported series: MODBUS TCP controller
3221
3222 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3223
3224 (% style="text-align:center" %)
3225 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3226
3227 (% style="text-align:center" %)
3228 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3229
3230
3231 (% style="text-align:center" %)
3232 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3233
3234 **HMI Setting**
3235
3236 (% class="table-bordered" %)
3237 |**Items**|**Settings**|**Note**
3238 |Protocol|MODBUS TCP Slave (All function)|
3239 |Connection|Ethernet|
3240 |Port No.|502|
3241 |PLC station No.|1|
3242
3243 **Address List**
3244
3245 (% class="table-bordered" %)
3246 |**Type**|**Register**|**Function code & Description**
3247 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3248 |06 (write single register: write a binary value to a holding register)
3249 |10 (write values to multiple addresses )
3250 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3251 |06 (write single register: write a binary value to a holding register)
3252 |10 (write values to multiple addresses )
3253 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3254 |06 (write single register: write a binary value to a holding register)
3255 |10 (write values to multiple addresses )
3256 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3257 |10 (write values to multiple addresses )
3258 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3259 |05 (Force a single coil to force the on/off state of a logic coil)
3260 |0F (Write multiple bits, ie write continuously)
3261 |(% rowspan="3" %)1|02 (Read the input state)
3262 |05 (Force a single coil to force the on/off state of a logic coil)
3263 |0F (Write multiple bits)
3264 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3265 |05 (Force a single coil to force the on/off state of a logic coil)
3266 |0F (Write multiple bits)
3267 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3268 |0F (Write multiple bits)
3269
3270 **Communication Settings**
3271
3272 Enable HMI Ethernet in [Project Settings];
3273
3274 (% style="text-align:center" %)
3275 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3276
3277 Set PLC IP in [Device IP] settings;
3278
3279 (% style="text-align:center" %)
3280 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3281
3282 **Cable Wiring**
3283
3284 (% style="text-align:center" %)
3285 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3286
3287 = **Printer** =
3288
3289 == **TSPL label printer** ==
3290
3291 **Introduction**
3292
3293 TSPL label printer protocol supports following models.
3294
3295 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3296 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3297
3298 **Setting Step**
3299
3300 Select the protocol
3301
3302 * Create a new project, select the TSPL label printer protocol as shown below.
3303
3304 (% style="text-align:center" %)
3305 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3306
3307 Set parameters
3308
3309 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3310
3311 Printer register
3312
3313 (% class="table-bordered" %)
3314 |**Register**|**System**|**Range**|**Function**
3315 |TSPL_SP|decimal|0 - 1|Set the paper size
3316 |TSPL_PT|decimal|0 - 1999|Print text
3317 |TSPL_PQ|decimal|0 - 999|Print QR code
3318 |TSPL_PB|decimal|0 - 999|Print barcode
3319 |TSPL_PR|decimal|0 - 1|Print offset
3320 |TSPL_PN|decimal|0 - 0|Trigger printing
3321 |TSPL_PS|decimal|0 - 0|Print status
3322
3323 * Set paper size:
3324 ** TSPL_SP0: width of paper, unit: mm.
3325 ** TSPL_SP1: height of paper, unit: mm.
3326 * Print text:
3327 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3328 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3329
3330 (% class="table-bordered" %)
3331 |**Register**|**Function**|**Description**
3332 |TSPL_PT0|X coordinate|Unit: dot
3333 |TSPL_PT1|Ycoordinate|Unit: dot
3334 |TSPL_PT2|Rotation angle|(((
3335 0: 0 degrees
3336
3337 1: 90 degrees
3338
3339 2: 180 degrees
3340
3341 3: 270 degrees
3342 )))
3343 |TSPL_PT3|Size|Range: 0-3
3344 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3345
3346 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3347
3348 Print QR code:
3349
3350 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3351 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3352
3353 (% class="table-bordered" %)
3354 |**Register**|**Function**|**Description**
3355 |TSPL_PQ0|X coordinate|Unit: dot
3356 |TSPL_PQ1|Ycoordinate|Unit: dot
3357 |TSPL_PQ2|Rotation angle|(((
3358 0: 0 degrees
3359
3360 1: 90 degrees
3361
3362 2: 180 degrees
3363
3364 3: 270 degrees
3365 )))
3366 |TSPL_PQ3|Size|Range: 0-5
3367 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3368
3369 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3370
3371 Print bar code:
3372
3373 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3374 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3375
3376 (% class="table-bordered" %)
3377 |**Register**|**Function**|**Description**
3378 |TSPL_PB0|X coordinate|Unit: dot
3379 |TSPL_PB1|Ycoordinate|Unit: dot
3380 |TSPL_PB2|Rotation angle|(((
3381 0: 0 degrees
3382
3383 1: 90 degrees
3384
3385 2: 180 degrees
3386
3387 3: 270 degrees
3388 )))
3389 |TSPL_PB3|height|Unit: dot
3390 |TSPL_PB4|width|Range:0-2
3391 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3392
3393 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3394
3395 Print offset:
3396
3397 * TSPL_PR0: X coordinate offset, unit: mm;
3398 * TSPL_PR1: Y coordinate offset, unit: mm.
3399
3400 Trigger printing:
3401
3402 * TSPL_PN0 = 1: trigger the printer to start printing.
3403
3404 Printing status:
3405
3406 * TSPL_PS0 = 1: The printing is normal.
3407 * TSPL_PS0 = 1: The printing is abnormal.
3408
3409 Print picture
3410
3411 * For the function of printing pictures, please refer to the configuration of [Printer object].
3412
3413 Conversion between dot and mm
3414
3415 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3416
3417 == **EpsonTM series** ==
3418
3419 **HMI Settings**
3420
3421 (% class="table-bordered" %)
3422 |**Item**|**Settings**|**Note**
3423 |Protocol|EPSON-TM-T82II/TM-XXX|
3424 |Connection|RS232|
3425 |Baud rate|9600~~115200|
3426 |Data bit|8|
3427 |Parity|None|
3428 |Stop bit|1|
3429 |PLC station No.|1|
3430
3431 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3432
3433 **Printer Settings**
3434
3435 (% class="table-bordered" %)
3436 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3437 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3438 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3439 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3440 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3441 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3442 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3443
3444 **Cable Wiring**
3445
3446 (% style="text-align:center" %)
3447 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3448
3449 (% style="text-align:center" %)
3450 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3451
3452 **✎Note:** COM3 only available in PI8000/PI9000 series.
3453
3454
3455 (% class="wikigeneratedid" %)
3456 = Create communication with **Schneider PLC** =
3457
3458 == **Schneider MODBUS RTU** ==
3459
3460 **HMI Setting**
3461
3462 |=**Parameters**|=**Recommended**|=**Notes**
3463 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3464 |Connection|RS485|
3465 |**Baud rate**|19200|
3466 |**Data bit**|8|
3467 |**Parity**|Even|
3468 |**Stop bit**|1|
3469 |**PLC station No.**|1|
3470
3471 **PLC Setting**
3472
3473 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3474
3475 **Device Address**
3476
3477 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3478 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3479 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3480 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3481 |W|MW|DDDDDD|0 ~~ 999999|Output register
3482 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3483
3484 **Wiring Diagram**
3485
3486 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3487
3488 (% style="text-align:center" %)
3489 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3490
3491 = **Barcode Scanner** =
3492
3493 Supported: DELI 14880 barcode scanner
3494
3495 **HMI Setting**
3496
3497 |**Items**|**Settings**|**Note**
3498 |Protocol|Barcode Scanner|
3499 |Connection|USB|
3500
3501 **Operating Procedures**
3502
3503 Select [Barcode Scanner];
3504
3505 (% style="text-align:center" %)
3506 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3507
3508 Set address for receiving;
3509
3510 Set correct length;
3511
3512 (% style="text-align:center" %)
3513 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3514
3515 **✎Note:**
3516
3517 * The protocol uploads the information acquired by the USB scanner to the HMI;
3518 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3519 * Recommended model: DELI 14880 barcode scanner;
3520
3521 = **Hitachi EHV Series (Ethernet)** =
3522
3523 Supported series: Hitachi EHV series
3524
3525 **HMI Settings**
3526
3527 (% class="table-bordered" %)
3528 |**Items**|**Settings**|**Note**
3529 |Protocol|Hitachi EHV series|
3530 |Connection|Ethernet|
3531 |Port No.|3004~~3007|
3532
3533 **Address List**
3534
3535 (% class="table-bordered" %)
3536 |**Type**|**Register**|**Range**|**Format**|**Note**
3537 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3538 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3539 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3540 H1H2H3H4 Module main number
3541
3542 H1: Remote number
3543
3544 H2: Unit number
3545
3546 H3: Slot number
3547
3548 H4: Word number of Module
3549
3550 H Sub number of Module
3551
3552 For example:X21.3
3553
3554 Slot number 2
3555
3556 Word number of module is 1
3557
3558 Bit number of module is 3
3559
3560 Remote number and unit number are 0
3561 )))
3562 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3563 |R|0 – FF.f (Hex)|R HH.h|
3564 |L|0 - 73FF.f (Hex)|L HHHH.h|
3565 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3566 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3567 H1H2H3H4 Module main number
3568
3569 H1: Remote number
3570
3571 H2: Unit number
3572
3573 H3: Slot number
3574
3575 H4: Word number of module
3576
3577 For example:WX21
3578
3579 Word number of module is 1
3580
3581 Slot number is 2
3582
3583 Remote number and unit number are 0
3584 )))
3585 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3586 |WR|0 – FFFF (Hex)|WR HHHH|
3587 |WL|0 - 73FF (Hex)|WL HHHH|
3588 |TC|0 - 2559|TC DDDD|
3589
3590 **Communication settings in HMI**
3591
3592 Enable HMI Ethernet in [Project Settings];
3593
3594 (% style="text-align:center" %)
3595 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3596
3597 Set PLC IP in [Device IP] settings;
3598
3599 (% style="text-align:center" %)
3600 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3601
3602 **PLC Configuration**
3603
3604 Connect with PLC, select[Online mode];
3605
3606 (% style="text-align:center" %)
3607 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3608
3609 Set IP address, it is the same LAN parameters with HMI;
3610
3611 (% style="text-align:center" %)
3612 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3613
3614 3) Save PLC communication parameter, and restart PLC
3615
3616 **PLC Monitor Mode**
3617
3618 Connect with PLC and choose to “online” mode
3619
3620 (% style="text-align:center" %)
3621 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3622
3623 Open I/O monitor sheet1
3624
3625 (% style="text-align:center" %)
3626 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3627
3628 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3629
3630 (% style="text-align:center" %)
3631 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3632
3633 Enter the register address, click OK to view the value of the register.
3634
3635 (% style="text-align:center" %)
3636 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3637
3638 (% style="text-align:center" %)
3639 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3640
3641 **✎Note:**
3642
3643 * Both word registers and bit registers support even continuous read/write functions;
3644 * The range of registers is based on the specific PLC type;
3645
3646 **Cable Wiring**
3647
3648 (% style="text-align:center" %)
3649 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3650
3651 = **IEC60870-5 104 Client** =
3652
3653 **HMI Setting**
3654
3655 (% class="table-bordered" %)
3656 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3657 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3658 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3659 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3660
3661 **Address List**
3662
3663 (% class="table-bordered" %)
3664 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3665 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3666 |(% style="width:461px" %)SCNA|0~~16777215.7
3667 |(% style="width:461px" %)DPTB|0~~16777215.7
3668 |(% style="width:461px" %)DCNA|0~~16777215.7
3669 |(% style="width:461px" %)METF|0~~16777215.7
3670 |(% style="width:461px" %)SENC|0~~16777215.7
3671 |(% style="width:461px" %)SENA|0~~16777215.7
3672 |(% style="width:461px" %)MENA|0~~16777215.7
3673 |(% style="width:461px" %)METD|0~~16777215.7
3674 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3675 |(% style="width:461px" %)SCNA|0~~16777215
3676 |(% style="width:461px" %)DPTB|0~~16777215
3677 |(% style="width:461px" %)DCNA|0~~16777215
3678 |(% style="width:461px" %)SENA|0~~16777215
3679 |(% style="width:461px" %)MENA|0~~16777215
3680 |(% style="width:461px" %)METD|0~~16777215
3681 |(% style="width:461px" %)INRO|0~~16777215
3682 |(% style="width:461px" %)TIMESYN|0~~16777215
3683 |(% style="width:461px" %)TIMEZ|0~~16777215
3684 |(% style="width:461px" %)NTP|0~~16777215
3685 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3686 |(% style="width:461px" %)SENC|0~~16777215
3687
3688 **Address Configuration**
3689
3690 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3691
3692 (% style="text-align:center" %)
3693 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3694
3695 (% style="text-align:center" %)
3696 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3697
3698 Extended tag name
3699
3700 Address range for the extended tag.
3701
3702 **Communication Settings**
3703
3704 Enable HMI Ethernet in [Project Settings];
3705
3706 (% style="text-align:center" %)
3707 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3708
3709 Set PLC IP in [Device IP] settings;
3710
3711 (% style="text-align:center" %)
3712 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3713
3714 **Cable Wiring**
3715
3716 (% style="text-align:center" %)
3717 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3718
3719 = **OpenCAN** =
3720
3721 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3722
3723 This protocol is only available in PI8000 series HMI.
3724
3725 **HMI Settings**
3726
3727 |**Items**|**Settings**|**Note**
3728 |Protocol|OPENCAN|
3729 |Connection|CAN port|
3730 |Baud rate|250000|
3731
3732 **CAN frame setting in HMI**
3733
3734 Click [OpenCAN setting] button in communication setting window;
3735
3736 (% style="text-align:center" %)
3737 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3738
3739 Click [Add] to create a new frame;
3740
3741 (% style="text-align:center" %)
3742 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3743
3744 |**No**|**Items**|**Description**
3745 |1|Add|add a frame related to register address
3746 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3747 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3748 |4|Modify|Modify the frames in frame management
3749 |5|Copy|Copy one frame to another
3750 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3751 |7|Empty|All frames in the list are cleared
3752 |8|Browse|Displays configuration files in XML format in IE
3753 |9|OK|Complete the configuration of the frame and exit
3754
3755 Set CANBUS frame in setting windows
3756
3757 (% style="text-align:center" %)
3758 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3759
3760 |**No**|**Items**|**Description**
3761 |1|ID|Set the ID of a can frame in hexadecimal format;
3762 |2|ID assign|split the ID by PF, PS, and SA;
3763 |3|Frame type|Select Standard frame or Extended Frame;
3764 |4|Frame format|Select between data frame and remote Frame;
3765 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3766 |6|Use address|(((
3767 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3768
3769 **Edit:** Set a bit or word address by its format;
3770
3771 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3772 )))
3773 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3774 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3775 |Feedback mode: feedback mode includes no response, confirm response and data response;
3776 |No response: the device or touch screen will not receive feedback;
3777 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3778 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3779 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3780 |Response timeout: sets whether the response frame timeout;
3781 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3782 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3783 |Manually send: a manually send tick indicates only one send;
3784 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3785 |10|Note|Fill the text to explain the meaning of the frame;
3786 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3787 |12|Current operation display|Display the description of current operation;
3788 |13|Add|Add a new frame;
3789 |14|Save frame|Save the configured frame format;
3790 |15|Cancel|Cancel the frame configuration;
3791
3792 Set CAN address (Read or write operation);
3793
3794 (% style="text-align:center" %)
3795 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3796
3797 |**No.**|**Item**|**Description**
3798 |1|Current address|Displays the register type and register address set by the user in the data access interface
3799 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3800 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3801 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3802 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3803 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3804 |If the trigger condition is a writing operation, there are two situations:(((
3805 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3806 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3807 )))
3808 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3809 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3810 |4|Add|Add current configuration
3811 |5|Close|Close the configuration window to exit
3812
3813 **Multiple Packages Settings**
3814
3815 (% style="text-align:center" %)
3816 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3817
3818 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3819
3820 Select Multiple package type
3821
3822 * Not Multiple packages
3823 * J1939 Multiple packages
3824 * Customized Multiple packages
3825
3826 Click [Edit Receive data] for [Receive] settings
3827
3828 * Start code+ Total length (J1939)
3829
3830 (% style="text-align:center" %)
3831 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3832
3833 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3834
3835 * Start code + Data max length (J1939)
3836
3837 (% style="text-align:center" %)
3838 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3839
3840 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3841
3842 * Data max length (J1939)
3843
3844 (% style="text-align:center" %)
3845 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3846
3847 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3848
3849 * Customized multiple package
3850
3851 (% style="text-align:center" %)
3852 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3853
3854 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3855
3856 Click [Edit Send data] for [Send] setting
3857
3858 * J1939
3859
3860 (% style="text-align:center" %)
3861 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3862
3863 [Data] is all data to be sent.
3864
3865 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3866
3867 * Customized multiple package
3868
3869 (% style="text-align:center" %)
3870 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3871
3872 [Data] is all data to be sent.
3873
3874 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3875
3876 **Cable Wiring**
3877
3878 (% style="text-align:center" %)
3879 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3880
3881 **✎Note:** The address interval between each frame need to be more than a word address;
3882
3883
3884 = **User Defined Protocol** =
3885
3886 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
3887
3888 **HMI Settings**
3889
3890 |**Items**|**Settings**|**Note**
3891 |Protocol|User defined protocol|
3892 |Connection|RS485/RS232|
3893 |Baud rate|2400~~187500|
3894 |Stop bits|1/ 2|
3895 |Data bits|7/ 8|
3896 |Parity|None/ Even/ ODD|
3897
3898 **Operating Procedures**
3899
3900 Select [User defined protocol];
3901
3902 Click [User defined protocol] button to open setting window as below;
3903
3904 (% style="text-align:center" %)
3905 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
3906
3907 Configure user defined command;
3908
3909 (% style="text-align:center" %)
3910 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
3911
3912 |**No**|**Item**|**Description**
3913 |1|Instruction edit|The required command.
3914 |2|Mode|Write to address or read from the address.
3915 |3|Format|Encode format: HEX or ASCII.
3916 |4|Other|(((
3917 **No receiving: **HMI does not respond to the receiving command.
3918
3919 **Send after receiving:** HMI responds to the receiving command.
3920 )))
3921 |5|Manually send|(((
3922 Respond once after trigger the address.
3923
3924 Address: set the trigger address.
3925 )))
3926 |6|Add|Save this setting.
3927 |7|Cancel|Cancel current settings.
3928 |(% rowspan="4" %)8|Add|Add a new command.
3929 |Edit|Edit the selected command.
3930 |Delete|Delete the selected command.
3931 |Clear|Clear all the commands.
3932 |9|Instruction list|Display all current commands.
3933 |10|Address List|Display all the addresses added.
3934 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
3935 |Export|Export current command settings to local storage.
3936 |Browse|Browse local command files.
3937 |Advanced|Combine two commands.
3938 |Exit|Complete editing and exit setting.
3939
3940 **Operating Procedures**
3941
3942 Click [Add] to create a new command, as below shows;
3943
3944 (% style="text-align:center" %)
3945 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
3946
3947 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
3948
3949 (% style="text-align:center" %)
3950 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
3951
3952 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
3953
3954 (% style="text-align:center" %)
3955 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
3956
3957 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
3958
3959 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
3960
3961 Check settings;
3962
3963 (% style="text-align:center" %)
3964 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3965
3966 |**No**|**Items**|**Description**
3967 |1|Add checking|Add checking command when receiving the data.
3968 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
3969 |Differ with send check|Set return checking.
3970 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
3971 |Length: The data length need to be checked.
3972
3973 Object settings;
3974
3975 (% style="text-align:center" %)
3976 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3977
3978 |**No**|**Items**|**Description**
3979 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
3980 |Address: the triggering address;
3981 |Note: description to object;
3982 |2|Byte order|The numerical display order;
3983
3984 Data length settings;
3985
3986 (% style="text-align:center" %)
3987 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3988
3989 |**No**|**Item**|**Description**
3990 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
3991 |Length: the return data length.
3992 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
3993 |Length: the write data length.
3994
3995 Instruction length settings
3996
3997 (% style="text-align:center" %)
3998 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
3999
4000 |**No**|**Item**|**Description**
4001 |1|Send length|The instruction data will only send designated data length.
4002 |2|Return length|The responds data length.
4003 |3|End code|Instruction will not be terminated until receiving [End code];
4004
4005 **Cable Wiring**
4006
4007 * **RS485**
4008
4009 (% style="text-align:center" %)
4010 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4011
4012 (% style="text-align:center" %)
4013 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4014
4015 * **RS232**
4016
4017 (% style="text-align:center" %)
4018 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4019
4020 **✎Note:** COM3 only available in PI8000/PI9000 series.