Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 223.1 by Hunter on 2023/03/18 11:57

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488
489 = Create communication with **Rockwell PLC** =
490
491 == **DF1 Protocol** ==
492
493 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
494
495 **HMI Settings**
496
497 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
498 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
499 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
500 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
501 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
502 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
503 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
504 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
505 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
506
507 **Address List**
508
509 (% class="table-bordered" %)
510 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
511 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
512 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
513 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
514 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
515 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
516 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
517 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
518 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
519 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
520 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
521 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
522
523 **Cable Wiring**
524
525 (% style="text-align:center" %)
526 [[image:AB.gif]]
527
528 == **DF1 Advanced Protocol** ==
529
530 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
531
532 **HMI Settings**
533
534 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
535 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
536 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
537 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
538 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
539 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
540 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
541 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
542 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
543
544 **Address List**
545
546 (% class="table-bordered" %)
547 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
548 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
549 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
550 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
551 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
552 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
553 Bit data file B0~~B99
554
555 First two digits is for file number
556
557 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
558 )))
559 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
560 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
561 Integer data file bit format N0~~N99
562
563 First two digits is for file number
564
565 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
566 )))
567 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
568 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
569 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
570 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
571 Timer Preset Value
572
573 First two digits is for file number
574
575 For example, TNS99255 represents file number T99, address 255.
576 )))
577 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
578 Timer Accumulator Value
579
580 First two digits is for file number
581
582 For example, TNP99255 represents file number T99, address 255.
583 )))
584 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
585 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
586 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
587 Counter Preset Value
588
589 First two digits is for file number
590
591 For example, CNS99255 represents file number C99, address 255.
592 )))
593 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
594 Counter Accumulator Value
595
596 First two digits is for file number
597
598 For example, CNP99255 represents file number C99, address 255.
599 )))
600 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
601 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
602 Integer data file
603
604 First two digits is for file number
605
606 For example, NN99255 represents file number N99, address 255.
607 )))
608 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
609 Only able to communicate with file number N7
610 )))
611 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
612 Floating point data file
613
614 First two digits is for file number
615
616 For example, FN99255 represents file number F99, address 255.
617 )))
618 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
619
620 **Cable Wiring**
621
622 (% style="text-align:center" %)
623 [[image:AB.gif]]
624
625 == **MicroLogix Protocol** ==
626
627 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
628
629 **HMI Settings**
630
631 (% class="table-bordered" %)
632 |**Item**|**Settings**|**Note**
633 |Protocol|Allen-Bradlley MicroLogix|
634 |Connection|RS232|
635 |Baud rate|19200|
636 |Data bit|8|
637 |Parity|None|
638 |Stop bit|1|
639 |PLC station No.|1|
640
641 **Address List**
642
643 (% class="table-bordered" %)
644 |**Type**|**Device registers**|**Format**|**Range**|**Note**
645 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
646 |O|O d.d|0.0~~255.15|
647 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
648 |S|S d.d|0.0~~255.15|
649 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
650 |(% rowspan="9" %)Word|S|S d|0~~255|
651 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
652 |TP|TP nnhh|0~~ffff
653 |CS|CS nnhh|0~~ffff
654 |CP|CP nnhh|0~~ffff
655 |N|N nnhh|0~~ffff
656 |C|C nnhh|0~~ffff
657 |T|T nnhh|0~~ffff
658 |R|R nnhh|0~~ffff
659
660 **Cable Wiring**
661
662
663 (% style="text-align:center" %)
664 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
665
666 == **CompactLogix FreeTag Ethernet protocol** ==
667
668 Allen-Brandly CompactLogix
669
670 **HMI Settings**
671
672 (% class="table-bordered" %)
673 |**Items**|**Settings**|**Note**
674 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
675 |Connection|Ethernet|
676 |Port No.|44818|
677
678 **PLC Setting**
679
680 Create new tags
681
682 (% style="text-align:center" %)
683 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
684
685 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
689
690 Import labels, please open [Communication] window and click [Import label];
691
692 Select csv file, all tags will be displayed as belows;
693
694 (% style="text-align:center" %)
695 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
696
697 **✎Note:**
698
699 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
700
701 (% style="text-align:center" %)
702 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
703
704 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
705
706 **Communication settings in HMI**
707
708 Enable HMI Ethernet in [Project Settings];
709
710 (% style="text-align:center" %)
711 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
712
713 Set PLC IP in [Device IP] settings;
714
715 (% style="text-align:center" %)
716 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
717
718 **Cable Wiring**
719
720 (% style="text-align:center" %)
721 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
722
723 == **MicroLogix 1200** **protocol** ==
724
725 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
726
727 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
728 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
729 * **Word address S:** The word address ranges from 0 to 255 (decimal).
730 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
731
732 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
733
734 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
735 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
736 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
737 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
738 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
739 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
740 |**PLC word address type**|**Address format**|**Address range**
741 |S|ddd|S0 ~~ 255
742 |TS|ffff|TS0 ~~ FFFF
743 |TP|ffff|TP0 ~~ FFFF
744 |CS|ffff|CS0 ~~ FFFF
745 |CP|ffff|CP0 ~~ FFFF
746 |N|ffff|N0 ~~ FFFF
747 |F|ffff|F0 ~~ FFFF
748
749 = Create communication with Crouzet PLC =
750
751 == **M3 (FBD) Protocol** ==
752
753 Support Series: Crouzet Millenium 3
754
755 **HMI Settings**
756
757 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
758 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
759 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
760 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
761 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
762 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
763 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
764 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
765 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
766
767 **Address List**
768
769 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 311px;" %)**Format**|=(% style="width: 301px;" %)**Range**|=Note
770 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:311px" %)I DD|(% style="width:301px" %)1~~99|Input
771 |(% style="width:191px" %)SLIBit|(% style="width:311px" %)SLIBit DD.dd|(% style="width:301px" %)1.0~~24.15|Serial Link Input
772 |(% style="width:191px" %)SLOBit|(% style="width:311px" %)SLOBit DD.dd|(% style="width:301px" %)25.0~~48.15|Serial Link Output(Read only)
773 |(% style="width:191px" %)State|(% style="width:311px" %)State D|(% style="width:301px" %)1~~1|PLC state(Read only)
774 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:311px" %)AI DD|(% style="width:301px" %)1~~99|Analog Input
775 |(% style="width:191px" %)SLIn|(% style="width:311px" %)SLIn DD|(% style="width:301px" %)1~~24|Serial Link Input
776 |(% style="width:191px" %)SLOut|(% style="width:311px" %)SLOut DD|(% style="width:301px" %)25~~48|Serial Link Output(Read only)
777 |(% style="width:191px" %)Time|(% style="width:311px" %)Time D|(% style="width:301px" %)1~~6|(((
778 Time1: Second
779
780 Time2: Minute
781
782 Time3: Hour
783
784 Time4: Day
785
786 Time5: Month
787
788 Time6: Year
789 )))
790 |(% style="width:191px" %)Order|(% style="width:311px" %)Order D|(% style="width:301px" %)1~~1|(((
791 Running command(Write only)
792
793 ~=2: Run mode; =1: Stop mode;
794 )))
795
796 **Cable Wiring**
797
798
799
800 = Create communication with Danfoss Drive =
801
802 == **FC Series Protocol** ==
803
804 Support Series: VLT FC300 Drive
805
806 **HMI Settings**
807
808 (% style="width:988px" %)
809 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
810 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
811 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
812 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
813 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
814 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
815 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
816 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
817 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
818
819 **Address List**
820
821 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
822 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
823 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
824 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
825 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
826
827 **Cable Wiring**
828
829 (% style="text-align:center" %)
830 [[image:Danfoss.png]]
831
832 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
833
834 == **S7-200 Smart Ethernet Protocol** ==
835
836 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
837
838 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
839
840 **HMI Setting**
841
842 (% class="table-bordered" %)
843 |**Items**|**Settings**|**Note**
844 |Protocol|Simens S7-200 Smart Ethernet|
845 |Connection|Ethernet|
846 |Port No.|102|
847 |PLC station No.|2|
848
849 **Address List**
850
851 (% class="table-bordered" %)
852 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
853 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
854 |Q|Q|Q ddddd.o|0.0~~99999.7|
855 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
856 |V|V|V ddddd.o|0.0~~99999.7|
857 |M|M|M ddddd.o|0.0~~99999.7|
858 |SM|SM|ddddd.o|0.0~~99999.7|
859 |S|S|ddddd.o|0.0~~99999.7|Read only
860 |T|T|ddddd|0~~99999|Timer state, read only
861 |C|C|ddddd|0~~99999|Counter state, read only
862 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
863 |Q|QW|QW ddddd|0~~99999|
864 |AI|AIW|AIW ddddd|0~~99999|
865 |AQ|VB|VB ddddd|0~~99999|
866 |V|VW|VW ddddd|0~~99998|(((
867 VW0=VB (0~~1)
868
869 VW2=VB (2~~3)
870
871 Address value is a multiple of 2
872 )))
873 |V|VD|VD ddddd|0~~99998|(((
874 VD0=VB (0~~3)
875
876 VD2=VB (4~~7)
877
878 Address value is a multiple of 4
879 )))
880 |M|MB|MB ddddd|0~~99999|
881 |M|MW|MW ddddd|0~~99999|(((
882 MW0=MB(0~~1)
883
884 MW2=MB(2~~3)
885
886 Address value is a multiple of 2
887 )))
888 |M|MD|MD ddddd|0~~99999|(((
889 MD0=MB(0~~3)
890
891 MD4=MB(4~~7)
892
893 Address value is a multiple of 4
894 )))
895 |T|TW|TW ddddd|0~~99999|Value of timer
896 |C|CW|CW ddddd|0~~99999|Value of counter
897 |W|SW|SW ddddd|0~~99999|
898
899 **Communication Settings**
900
901 Enable HMI Ethernet in [Project Settings];
902
903 (% style="text-align:center" %)
904 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
905
906 Set PLC IP in [Device IP] settings;
907
908 (% style="text-align:center" %)
909 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
910
911 * PLC IP Address: PLC IP
912 * PLC pot No.: 102(fixed)
913 * Network:TCP_Client_2N(fixed)
914
915 (% style="text-align:center" %)
916 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
917
918 * Wait timeout: depend on actual network situation (more than 1500 ms)
919
920 **Cable Wiring**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924
925 == **S7-300 Ethernet Protocol** ==
926
927 Supported Series: Siemens S7-300 series PLC
928
929 **HMI Setting**
930
931 (% class="table-bordered" %)
932 |**Items**|**Settings**|**Note**
933 |Protocol|Simens S7-300 Ethernet|
934 |Connection|Ethernet|
935 |Port No.|102|
936 |PLC station No.|2|Need to be same as the PLC setting
937
938 **Address List**
939
940 (% class="table-bordered" %)
941 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
942 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
943 |Q|Q|Q ddddd.o|0.0~~99999.7|
944 |M|M|M ddddd.o|0.0~~99999.7|
945 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
946 nnnn: block number;
947
948 dddd: address;
949 )))
950 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
951 |Q|QW|QW ddddd|0~~99999|
952 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
953 |MW|MW ddddd|0~~99999|(((
954 MW0=MB(0~~1)
955
956 MW2=MB(2~~3)
957
958 Address value is a multiple of 2
959 )))
960 |MD|MD ddddd|0~~99999|(((
961 MD0=MB(0~~3)
962
963 MD4=MB(4~~7)
964
965 Address value is a multiple of 4
966 )))
967 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
968 nnnn: block number;
969
970 dddd: address
971 )))
972 |DBxDBW|DBxDBW nnnndddd|0~~99999999
973 |DBxDBD|DBxDBD nnnndddd|0~~99999999
974
975 **Communication Settings**
976
977 Enable HMI Ethernet in [Project Settings];
978
979 (% style="text-align:center" %)
980 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
981
982 Set PLC IP in [Device IP] settings;
983
984 (% style="text-align:center" %)
985 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
986
987 * PLC IP Address: PLC IP
988 * PLC pot No.: 102(fixed)
989 * Network:TCP_Client_2N(fixed)
990
991 (% style="text-align:center" %)
992 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
993
994 * Wait timeout: depend on actual network situation (more than 1500 ms)
995
996 **Cable Wiring**
997
998 (% style="text-align:center" %)
999 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1000
1001 == **S7-1200 Ethernet Protocol** ==
1002
1003 Supported Series: Siemens S7-1200
1004
1005 **HMI Setting**
1006
1007 (% class="table-bordered" %)
1008 |**Items**|**Settings**|**Note**
1009 |Protocol|Siemens S7-1200|
1010 |Connection|Ethernet|
1011 |Port No.|102|
1012 |PLC station No.|2|
1013
1014 **Address List**
1015
1016 (% class="table-bordered" %)
1017 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1018 |(% rowspan="4" %)Bit|I|I|M d.o|(((
1019 d:0~-~-9999
1020
1021 o:0-7
1022 )))|
1023 |Q|Q|Q d.o|(((
1024 d:0~-~-9999
1025
1026 o:0-7
1027 )))|
1028 |M|M|M d.o|(((
1029 d:0~-~-9999
1030
1031 o:0-7
1032 )))|
1033 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
1034 nn:0-9999,
1035
1036 dddd:0-9999,
1037
1038 o:0-7
1039 )))|(((
1040 nn:DB No.
1041
1042 dddd:address value
1043
1044 o: digit address
1045 )))
1046 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1047 |M|MW|MW d|d:0-99999|(((
1048 MW0=MB(0~~1)
1049
1050 MW2=MB(2~~3)
1051
1052 Address value is a multiple of 2
1053 )))
1054 |M|MD|MD d|d:0-99999|(((
1055 MD0=MB(0~~3)
1056
1057 MD4=MB(4~~7)
1058
1059 Address value is a multiple of 4
1060 )))
1061 |I|IW|IW d|d:0-99999|
1062 |Q|QW|QW d|d:0-99999|
1063 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1064 nn:0-9999
1065
1066 dddd:0-9999
1067 )))|(((
1068 nn:DB No.
1069
1070 dddd:address value
1071 )))
1072 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1073 nn:0-9999
1074
1075 dddd:0-9999
1076 )))|(((
1077 nn:DB No.
1078
1079 dddd:address value
1080
1081 Address value is a multiple of 2
1082 )))
1083 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1084 nn:0-9999
1085
1086 dddd:0-9999
1087 )))|(((
1088 nn:DB No.
1089
1090 dddd:address value
1091
1092 Address value is a multiple of 4
1093 )))
1094
1095 **Communication Settings**
1096
1097 Enable HMI Ethernet in [Project Settings];
1098
1099 (% style="text-align:center" %)
1100 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1101
1102 Set PLC IP in [Device IP] settings;
1103
1104 (% style="text-align:center" %)
1105 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1106
1107 **✎Note:**
1108
1109 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1110 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1111 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
1112 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
1113
1114 **PLC Settings**
1115
1116 Add BD
1117
1118 * Please uncheck [Symbolic access only] option;
1119
1120 (% style="text-align:center" %)
1121 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
1122
1123 Address settings, using BD2 as example.
1124
1125 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
1126 * 2 represent DB block number
1127 * xxxx represent address
1128
1129 **Such as:**
1130
1131 * DBxDBB20000 = DB2.DBB0
1132 * DBxDBW20004 = DB2.DBW4
1133
1134 (% style="text-align:center" %)
1135 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
1136
1137 **How to connect with S7-1200 Firmware V4.0**
1138
1139 PLC configuration
1140
1141 * Double click [device configuration] in Siemens via software
1142 * Double click [protection] to enter protection configuration screen
1143
1144 (% style="text-align:center" %)
1145 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
1146
1147 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
1148
1149 (% style="text-align:center" %)
1150 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
1151
1152 DB settings
1153
1154 * Right click [DB], select [properties]
1155 * Uncheck [optimized block access]
1156
1157 **Cable Wiring**
1158
1159 (% style="text-align:center" %)
1160 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1161
1162 == **S7-XXX Ethernet Protocol** ==
1163
1164 Supported Series: Siemens S7-400, S7-1200 and S7-1500
1165
1166 **HMI Setting**
1167
1168 (% class="table-bordered" style="width:823px" %)
1169 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
1170 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
1171 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
1172 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
1173 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
1174 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
1175
1176 Slot from TIA Portal is equal to Device No. of PIStudio
1177
1178 Rack from TIA Portal is equal to HMI No. of PIStudio
1179
1180 (% style="text-align:center" %)
1181 [[image:S7-XXXCommunication Settings.png]]
1182
1183 (% style="text-align:center" %)
1184 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
1185
1186 **Address List**
1187
1188 (% class="table-bordered" %)
1189 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1190 |(% rowspan="4" %)Bit|I|I|M d.o|(((
1191 d:0~-~-9999
1192
1193 o:0-7
1194 )))|
1195 |Q|Q|Q d.o|(((
1196 d:0~-~-9999
1197
1198 o:0-7
1199 )))|
1200 |M|M|M d.o|(((
1201 d:0~-~-9999
1202
1203 o:0-7
1204 )))|
1205 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
1206 nn:0-9999,
1207
1208 dddd:0-9999,
1209
1210 o:0-7
1211 )))|(((
1212 nn:DB No.
1213
1214 dddd:address value
1215
1216 o: digit address
1217 )))
1218 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1219 |M|MW|MW d|d:0-99999|(((
1220 MW0=MB(0~~1)
1221
1222 MW2=MB(2~~3)
1223
1224 Address value is a multiple of 2
1225 )))
1226 |M|MD|MD d|d:0-99999|(((
1227 MD0=MB(0~~3)
1228
1229 MD4=MB(4~~7)
1230
1231 Address value is a multiple of 4
1232 )))
1233 |I|IW|IW d|d:0-99999|
1234 |Q|QW|QW d|d:0-99999|
1235 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1236 nn:0-9999
1237
1238 dddd:0-9999
1239 )))|(((
1240 nn:DB No.
1241
1242 dddd:address value
1243 )))
1244 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1245 nn:0-9999
1246
1247 dddd:0-9999
1248 )))|(((
1249 nn:DB No.
1250
1251 dddd:address value
1252
1253 Address value is a multiple of 2
1254 )))
1255 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1256 nn:0-9999
1257
1258 dddd:0-9999
1259 )))|(((
1260 nn:DB No.
1261
1262 dddd:address value
1263
1264 Address value is a multiple of 4
1265 )))
1266
1267 **Communication Settings**
1268
1269 Enable HMI Ethernet in [Project Settings];
1270
1271 (% style="text-align:center" %)
1272 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1273
1274 Set PLC IP in [Device IP] settings;
1275
1276 (% style="text-align:center" %)
1277 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1278
1279 **✎Note:**
1280
1281 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1282 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1283
1284 **Cable Wiring**
1285
1286 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1287
1288 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1289
1290 Supported Series: Siemens Logo 0BA0, 0BA1 series
1291
1292 **HMI Settings**
1293
1294 (% class="table-bordered" %)
1295 |**Items**|**Settings**|**Note**
1296 |Protocol|Siemens LOGO|
1297 |Connection|Ethernet|
1298 |Port No.|102|
1299 |PLC station No.|2|
1300
1301 **Address List**
1302
1303 (% class="table-bordered" %)
1304 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1305 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1306 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1307 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1308 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1309 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1310 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1311 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1312 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1313 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1314 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1315 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1316 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1317 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1318 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1319 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1320
1321 **PLC Settings in LOGO Software:**
1322
1323 Click [Tools]~-~-[Ethernet Connections],shown as below.
1324
1325 (% style="text-align:center" %)
1326 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1327
1328 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1329
1330 (% style="text-align:center" %)
1331 [[image:image-20221228142937-4.png]]
1332
1333 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1334
1335 (% style="text-align:center" %)
1336 [[image:image-20221228143047-5.png]]
1337
1338 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1339
1340 (% style="text-align:center" %)
1341 [[image:image-20221228143246-6.png]]
1342
1343
1344 **HMI Communication Settings**
1345
1346 Set PLC IP in [Device IP] settings;
1347
1348 (% style="text-align:center" %)
1349 [[image:image-20221228143614-7.png]]
1350
1351 Enable HMI Ethernet in [Project Settings];
1352
1353 (% style="text-align:center" %)
1354 [[image:image-20221228144229-9.png]]
1355
1356 TSAP setting
1357
1358 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1359 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
1360 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
1361 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
1362 ie, ig series: use HSW1200, HSW1201.
1363 HMI V2.0: use HSW1200, HSW1201.
1364
1365 **✎Note:**
1366
1367 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
1368 * HSW10119/HSW1201 is set up as shown.
1369 * (((
1370 (% style="text-align:center" %)
1371 [[image:image-20221228144800-11.png]]
1372 )))
1373 * (((
1374 (% style="text-align:center" %)
1375 [[image:image-20221228144708-10.png]]
1376 )))
1377
1378 * AI word address and Ibit address are read-only and cannot be written on HMI.
1379 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
1380 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
1381 * Written value of RTC cannot exceed 255.
1382
1383 **Cable Wiring**
1384
1385 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1386
1387 == S7-300 232 ==
1388
1389 **HMI Setting:**
1390
1391 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
1392 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
1393 |=**PLC I/F**|RS232| |
1394 |=**Baud rate**|19200|9600,19200|
1395 |=**Data bits**|8| |
1396 |=**Parity**|Odd| |
1397 |=**Stop bits**|1| |
1398 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
1399
1400 **Device Address**
1401
1402 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1403 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
1404 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
1405 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
1406 |=Word|(((
1407 DB1 to DB99
1408 )))|DDDDDo|0 ~~ 655327|
1409 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
1410 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
1411 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
1412 |=Double word|MD|DDDD|0 ~~ 4094|
1413 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
1414 Data Register Double Word (must be even)
1415 )))
1416 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
1417
1418 **Cable Wiring**
1419
1420 (% style="text-align:center" %)
1421 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
1422
1423 = Create communication with **Mitsubishi PLC** =
1424
1425 == **FX1S, 1N, 2N Series Protocol** ==
1426
1427 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1428
1429 **HMI Settings**
1430
1431 (% class="table-bordered" %)
1432 |**Item**|**Settings**|**Note**
1433 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1434 |Connection|RS422/RS485/RS232|
1435 |Baud rate|9600~~115200|
1436 |Data bit|7/8|
1437 |Parity|EVEN/Odd/None|
1438 |Stop bit|1/2|
1439 |PLC station No.|1~~255|
1440
1441 **Address List**
1442
1443 (% class="table-bordered" %)
1444 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1445 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1446 |Y|Y|Y o|0~~303237|
1447 |M|M|M d|0~~99999|
1448 |T|T|T d|0~~99999|
1449 |C|C|C d|0~~99999|
1450 |S|S|S d|0~~99999|
1451 |SM|SM|SM d|8000~~9999|
1452 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1453 |Y|Y|Y o|0~~303237|
1454 |M|M|M d|0~~99999|
1455 |T|T|T d|0~~99999|
1456 |C|C|C d|0~~199|
1457 |D|D|D d|0~~7999|
1458 |S|S|S d|0~~99999|
1459 |SD|SD|SD d|8000~~9999|
1460
1461 **Cable Wiring**
1462
1463 * **RS485**
1464
1465 (% style="text-align:center" %)
1466 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1467
1468 (% style="text-align:center" %)
1469 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1470
1471 * **RS422**
1472
1473 (% style="text-align:center" %)
1474 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1475
1476 **✎Note:** COM3 only available in PI8000/PI9000 series.
1477
1478 == **FX3U/3G/3GA serial protocol** ==
1479
1480 (% class="wikigeneratedid" %)
1481 **HMI Settings**
1482
1483 |=**Item**|=**Settings**|=**Note**
1484 |Protocol|Mitsubishi FX3U/3G/3GA|
1485 |Connection|RS422|
1486 |Baud rate|9600~~115200|
1487 |Data bit|7/8|
1488 |Parity|EVEN/Odd/None|
1489 |Stop bit|1/2|
1490 |PLC station No.|1~~255|
1491
1492 (% class="wikigeneratedid" %)
1493 **Address List**
1494
1495 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1496 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1497 |Y|Y|Y o|0~~303237|
1498 |M|M|M d|0~~99999|
1499 |T|T|T d|0~~99999|
1500 |C|C|C d|0~~99999|
1501 |S|S|S d|0~~99999|
1502 |SM|SM|SM d|8000~~9999|
1503 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1504 |Y|Y|Y o|0~~303237|
1505 |M|M|M d|0~~99999|
1506 |T|T|T d|0~~99999|
1507 |C|C|C d|0~~199|
1508 |D|D|D d|0~~7999|
1509 |S|S|S d|0~~99999|
1510 |SD|SD|SD d|8000~~9999|
1511
1512 **Configure the communication protocol**
1513
1514 (% style="text-align:center" %)
1515 [[image:image-20220831095222-1.png]]
1516
1517 (% style="text-align:center" %)
1518 [[image:image-20220831095743-2.png]]
1519
1520 **Wiring**
1521
1522 (% style="text-align:center" %)
1523 [[image:image-20220831100333-7.png]]
1524
1525 Pin Definition Diagram
1526
1527 (% style="text-align:center" %)
1528 [[image:image-20220831100314-6.png]]
1529
1530 == **FX3U Ethernet Protocol** ==
1531
1532 Mitsubishi FX3U series PLC
1533
1534 **HMI Settings**
1535
1536 |Items|Settings|Note
1537 |Protocol|Mitsubishi FX3U|
1538 |Connection|Ethernet|
1539 |Port No.|5009|Must be the same as the PLC setting
1540 |PLC station No.|0|
1541
1542 **Address List**
1543
1544 (% class="table-bordered" style="width:1041px" %)
1545 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|(% style="width:140px" %)**Note**
1546 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|(% style="width:140px" %)
1547 |Y|Y|Y OOO|0~~377|(% style="width:140px" %)
1548 |M|M|M DDDD|0~~7679|(% style="width:140px" %)
1549 |SM|SM|SM DDDD|8000~~8511|(% style="width:140px" %)
1550 |S|S|S DDDD|0~~4095|(% style="width:140px" %)
1551 |TS|TS|TS DDD|0~~511|(% style="width:140px" %)
1552 |CS|CS|CS DDD|0~~255|(% style="width:140px" %)
1553 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|(% style="width:140px" %)0~~199|(% style="width:30px" %)
1554 |TN|TN|TN DDD|(% style="width:140px" %)0~~511|(% style="width:30px" %)
1555 |D|D|D DDDD|(% style="width:140px" %)0~~7999|(% style="width:30px" %)
1556 |SD|SD|SD DDDD|(% style="width:140px" %)8000~~8511|(% style="width:30px" %)
1557 |R|R|R DDDDD|(% style="width:140px" %)0~~32767|(% style="width:30px" %)
1558
1559 **Ethernet Module Settings**
1560
1561 FX3U-ENET-L module configuration
1562 Set up the FX3U-ENET-L Ethernet module settings as follows.
1563 Select the module location, which in this document is Module 0.
1564
1565 [[image:image-20221115140802-1.png]]
1566
1567 Select "Operational setting" to enter the following screen.
1568
1569 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1570
1571 [[image:image-20221115142728-4.png]]
1572
1573 Select "Open setting" to enter the setting interface, the settings are as follows.
1574
1575 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1576
1577 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1578
1579 [[image:image-20221115142945-5.png]]
1580
1581 Click on "transter setup" - "PC side I/F setting", see the following figure.
1582
1583 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1584
1585 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1586
1587 [[image:image-20221115143341-6.png||height="426" width="712"]]
1588
1589 Read and write data from the Ethernet module
1590
1591 [[image:image-20221115143703-7.png]]
1592
1593 Set "Transter setup" to COM communication, and read or write operation as shown below
1594
1595 [[image:image-20221115143809-8.png]]
1596
1597 **PLC Settings (GX Works 2)**
1598
1599 Create a blank FX5U project
1600
1601 Find Current Connection in the navigation
1602
1603 [[image:image-20221115144335-9.png||height="422" width="706"]]
1604
1605 Select Connection Channel List
1606
1607 Select Ethernet board communication
1608
1609 [[image:image-20221115144824-10.png||height="421" width="705"]]
1610
1611 Select Ethernet Module
1612 Set the IP address of the PLC
1613
1614 [[image:image-20221115145228-11.png||height="674" width="708"]]
1615
1616 Read or write PLC data, in this document is read
1617
1618 [[image:image-20221115145553-12.png||height="424" width="711"]]
1619
1620 (% class="wikigeneratedid" id="H" %)
1621 [[image:image-20221115145559-13.png||height="424" width="711"]]
1622
1623 **HMI Communication Setting**
1624
1625 [[image:image-20221115150003-14.png||height="425" width="712"]]
1626
1627 [[image:image-20221115150235-15.png||height="427" width="713"]]
1628
1629 (% class="wikigeneratedid" id="H-1" %)
1630 [[image:image-20221115145559-13.png||height="424" width="711"]]
1631
1632 **HMI Communication Setting**
1633
1634 [[image:image-20221115150003-14.png||height="425" width="712"]]
1635
1636 [[image:image-20221115150235-15.png||height="427" width="713"]]
1637
1638 == **FX5U Serial Port Protocol** ==
1639
1640 Mitsubishi FX5U series PLC
1641
1642 **HMI Settings**
1643
1644 (% class="table-bordered" %)
1645 |**Item**|**Settings**|**Note**
1646 |Protocol|Mitsubishi FX5U|
1647 |Connection|RS422/RS485|
1648 |Baud rate|9600|
1649 |Data bit|7|
1650 |Parity|Odd|
1651 |Stop bit|1|
1652 |PLC station No.|1~~255|Need to be the same as PLC settings
1653
1654 **Address List**
1655
1656 (% class="table-bordered" %)
1657 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1658 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1659 |Y|Y|Y o|0~~303237|
1660 |M|M|M d|0~~99999|
1661 |B|B|B h|0~~7FFF|
1662 |F|F|F d|0~~32767|
1663 |SB|SB|SB h|0~~7FFF|
1664 |TS|TS|TS d|0~~1023|
1665 |TC|TC|TC d|0~~1023|
1666 |STS|STS|STS d|0~~1023|
1667 |STC|STC|STS d|0~~1023|
1668 |CS|CS|CS d|0~~1023|
1669 |CC|CC|CC d|0~~1023|
1670 |SM|SM|SM d|0~~9999|
1671 |L|L|L d|0~~32767|
1672 |S|S|S d|0~~4095|
1673 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1674 |TN|TN|TN d|0~~1023|
1675 |STN|STN|STN d|0~~1023|
1676 |CN|CN|CN d|0~~1023|
1677 |R|R|R d|0~~32767|
1678 |SW|SW|SW h|0~~7FFF|
1679 |Z|Z|Z d|0~~23|
1680 |D|D|D d|0~~7999|
1681 |SD|SD|SD d|0~~11999|
1682
1683 **PLC Settings (GX Works 3)**
1684
1685 Create a blank FX5U project
1686
1687 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1688
1689 (% style="text-align:center" %)
1690 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1691
1692 Select protocol in the setting item, and set parameters.
1693
1694 (% style="text-align:center" %)
1695 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1696
1697 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1698
1699 (% style="text-align:center" %)
1700 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1701
1702 Click the [Apply] button to finish the setting.
1703
1704 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1705
1706 (% style="text-align:center" %)
1707 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1708
1709 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1710
1711 Done.
1712
1713 **Cable Wiring**
1714
1715 * **RS485**
1716
1717 (% style="text-align:center" %)
1718 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1719
1720 (% style="text-align:center" %)
1721 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1722
1723 * **RS422**
1724
1725 (% style="text-align:center" %)
1726 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1727
1728 **✎Note:** COM3 only available in PI8000/PI9000 series.
1729
1730 == **L02 Serial Protocol** ==
1731
1732 Mitsubishi L02 series CPU built-in serial port.
1733
1734 **HMI Settings**
1735
1736 |=**Item**|=**Settings**|=**Note**
1737 |Protocol|Mitsubishi L02|
1738 |Connection|RS422|
1739 |Baud rate|115200|
1740 |Data bit|8|
1741 |Parity|Odd|
1742 |Stop bit|1|
1743 |PLC station No.|1~~255|Need to be the same as PLC settings
1744
1745 **Address List**
1746
1747 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1748 |Bit|X|X|X h|0~~FFFF|
1749 |Bit|Y|Y|Y h|0~~FFFF|
1750 |Bit|M|M|M d|0~~9999|
1751 |Bit|L|L|L d|0~~9999|
1752 |Bit|F|F|F d|0~~9999|
1753 |Bit|B|B|B h|0~~FFFF|
1754 |Bit|V|V|V d|0~~2047|
1755 |Bit|TC|TC|TC d|0~~9999|
1756 |Bit|SS|SS|SS d|0~~9999|
1757 |Bit|SC|SC|SC d|0~~9999|
1758 |Bit|CS|CS|CS d|0~~9999|
1759 |Bit|CC|CC|CC d|0~~9999|
1760 |Bit|SB|SB|SB h|0~~FFFF|
1761 |Bit|SM|SM|SM d|0~~2047|
1762 |Bit|STS|STS|STS d|0~~1023|
1763 |Bit|S|S|S d|0~~9999|
1764 |Bit|DX|DX|DX h|0~~FFFF|
1765 |Bit|DY|DY|DY h|0~~FFFF|
1766 |Bit|TS|TS|TS d|0~~9999|
1767 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1768 |Word|W|W|W h|0~~FFFF|
1769 |Word|TN|TN|TN d|0~~99999|
1770 |Word|SN|SN|SN d|0~~99999|
1771 |Word|CN|CN|CN d|0~~99999|
1772 |Word|R|R|R d|0~~99999|
1773 |Word|SW|SW|SW h|0~~FFFF|
1774 |Word|Z|Z|Z d|0~~99999|
1775 |Word|ZR|ZR|ZR h|0~~FFFF|
1776 |Word|D|D|D d|0~~99999|
1777
1778 **Communication Settings**
1779
1780 (% style="text-align:center" %)
1781 [[image:image-20220831105732-3.png]]
1782
1783 (% style="text-align:center" %)
1784 [[image:image-20220831110004-5.png]]
1785
1786 **Cable Wiring**
1787
1788 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1789
1790 Pin Definition Diagram
1791
1792 (% style="text-align:center" %)
1793 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1794
1795 == **L02 MELSEC (Ethernet) Protocol** ==
1796
1797 Mitsubishi Q series CPU built-in Ethernet port.
1798
1799 **HMI Settings**
1800
1801 (% class="table-bordered" %)
1802 |**Items**|**Settings**|**Note**
1803 |Protocol|MIT L02 CPU MELSEC|
1804 |Connection|Ethernet|
1805 |Port No.|1025|Must be the same as the PLC setting
1806 |PLC station No.|0|Must be the same as the PLC setting
1807
1808 **Address List**
1809
1810 (% class="table-bordered" %)
1811 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1812 |Bit|X|X|X h|0~~FFFF|
1813 |Bit|Y|Y|Y h|0~~FFFF|
1814 |Bit|M|M|M d|0~~9999|
1815 |Bit|L|L|L d|0~~9999|
1816 |Bit|F|F|F d|0~~9999|
1817 |Bit|B|B|B h|0~~FFFF|
1818 |Bit|V|V|V d|0~~2047|
1819 |Bit|TC|TC|TC d|0~~9999|
1820 |Bit|SS|SS|SS d|0~~9999|
1821 |Bit|SC|SC|SC d|0~~9999|
1822 |Bit|CS|CS|CS d|0~~9999|
1823 |Bit|CC|CC|CC d|0~~9999|
1824 |Bit|SB|SB|SB h|0~~FFFF|
1825 |Bit|SM|SM|SM d|0~~2047|
1826 |Bit|STS|STS|STS d|0~~1023|
1827 |Bit|S|S|S d|0~~9999|
1828 |Bit|DX|DX|DX h|0~~FFFF|
1829 |Bit|DY|DY|DY h|0~~FFFF|
1830 |Bit|TS|TS|TS d|0~~9999|
1831 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1832 |Word|W|W|W h|0~~FFFF|
1833 |Word|TN|TN|TN d|0~~99999|
1834 |Word|SN|SN|SN d|0~~99999|
1835 |Word|CN|CN|CN d|0~~99999|
1836 |Word|R|R|R d|0~~99999|
1837 |Word|SW|SW|SW h|0~~FFFF|
1838 |Word|Z|Z|Z d|0~~99999|
1839 |Word|ZR|ZR|ZR h|0~~FFFF|
1840 |Word|D|D|D d|0~~99999|
1841
1842 **Communication Settings**
1843
1844 Enable HMI Ethernet in [Project Settings];
1845
1846 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1847
1848 Set PLC IP in [Device IP] settings;
1849
1850 (% style="text-align:center" %)
1851 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1852
1853 **PLC Settings (GX Works2 )**
1854
1855 Create a project
1856
1857 Set PLC IP, subnet mask and gateway;
1858
1859 Select [Binary Code] as communication data code;
1860
1861 (% style="text-align:center" %)
1862 [[image:image-20221108202109-2.png||height="636" width="732"]]
1863
1864 Set PLC port number, for example 1025
1865
1866 (% style="text-align:center" %)
1867 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1868
1869 Save settings;
1870
1871 Download project into PLC device;
1872
1873 Restart PLC device;
1874
1875 **Cable Wiring**
1876
1877 (% style="text-align:center" %)
1878 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1879
1880 == **QJ71C24N MELSEC Protocol** ==
1881
1882 Mitsubishi QJ71C24N communication module built-in serial port;
1883
1884 **HMI Settings**
1885
1886 (% class="table-bordered" %)
1887 |**Items**|**Settings**|**Note**
1888 |Protocol|MIT QJ71 MELSEC|
1889 |Connection|422|
1890 |Baud rate|9600|
1891 |Data bit|8|
1892 |Parity|ODD|
1893 |Stop bit|1|
1894 |PLC station No.|1~~255|Need to be the same as PLC settings
1895
1896 **Address List**
1897
1898 (% class="table-bordered" %)
1899 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1900 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1901 |Y|Y|Y FFFF|0~~1FFF|
1902 |M|M|M DDDDD|0~~99999|
1903 |L|L|L DDDD|0~~8191|
1904 |F|F|F DDDD|0~~2047|
1905 |V|V|V DDDD|0~~2047|
1906 |B|B|B FFFF|0~~1FFF|
1907 |TS|TS|TS DDDD|0~~2047|
1908 |TC|TC|TC DDDD|0~~2047|
1909 |SS|SS|SS DDDD|0~~2047|
1910 |SC|SC|SC DDDD|0~~2047|
1911 |CS|CS|CS DDDD|0~~1023|
1912 |CC|CC|CC DDDD|0~~1023|
1913 |SB|SB|SB FFF|0~~7FF|
1914 |S|S|S D|0~~8191|
1915 |DX|DX|DX FFFF|0~~1FFF|
1916 |DY|DY|DY FFFF|0~~1FFF|
1917 |SM_|SM_|SM_ DDDD|8000~~9999|
1918 |SM|SM|SM DDDD|0~~2047|
1919 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1920 |D|D|D DDDDD|0~~12287|
1921 |W|W|W FFFF|0~~1FFF|
1922 |TN|TN|TN DDDD|0~~2047|
1923 |SN|SN|SN DDDD|0~~2047|
1924 |CN|CN|CN DDDD|0~~1023|
1925 |R|R|R DDDDD|0~~32767|
1926 |SW|SW|SW FFF|0~~7FF|
1927 |Z|Z|Z D|0~~15|
1928 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1929
1930 **Communication Settings**
1931
1932 (% style="text-align:center" %)
1933 [[image:image-20221109135738-1.png]]
1934
1935 (% style="text-align:center" %)
1936 [[image:image-20221109140016-3.png]]
1937
1938 (% class="wikigeneratedid" id="H" %)
1939 Pin Definition Diagram
1940
1941 (% style="text-align:center" %)
1942 [[image:image-20221109140406-4.png]]
1943
1944 == **QJ71E71 MELSEC Protocol** ==
1945
1946 Mitsubishi QJ71E71 Ethernet communication module;
1947
1948 **HMI Settings**
1949
1950 (% class="table-bordered" %)
1951 |**Items**|**Settings**|**Note**
1952 |Protocol|MIT QJ71E71 MELSEC|
1953 |Connection|Ethernet|
1954 |Port No.|1025|Must be the same as the PLC setting
1955 |PLC station No.|0|Must be the same as the PLC setting
1956
1957 **Address List**
1958
1959 (% class="table-bordered" %)
1960 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1961 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1962 |Y|Y|Y h|0~~1FFF|
1963 |M|M|M d|0~~99999|
1964 |L|L|L d|0~~8191|
1965 |F|F|F d|0~~2047|
1966 |B|B|B h|0~~1FFF|
1967 |V|V|V d|0~~2047|
1968 |TS|TS|TS d|0~~2047|
1969 |TC|TC|TC d|0~~2047|
1970 |SS|SS|SS d|0~~2047|
1971 |SC|SC|SC d|0~~2047|
1972 |CS|CS|CS d|0~~1023|
1973 |CC|CC|CC d|0~~1023|
1974 |SB|SB|SB h|0~~7FF|
1975 |S|S|S d|0~~8191|
1976 |DX|DX|DX h|0~~1FFF|
1977 |DY|DY|DY h|0~~1FFF|
1978 |SM|SM|SM d|8000~~9999|
1979 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1980 |D|D|D d|0~~12287|
1981 |W|W|W h|0~~1FFF|
1982 |TN|TN|TN d|0~~2047|
1983 |SN|SN|SN d|0~~2047|
1984 |CN|CN|CN d|0~~1023|
1985 |R|R|R d|0~~32767|
1986 |SW|SW|SW h|0~~7FF|
1987 |Z|Z|Z d|0~~15|
1988 |ZR|ZR|ZR h|0~~FE7FF|
1989
1990 **HMI Communication Settings**
1991
1992 1) Enable HMI Ethernet in [Project Settings];
1993
1994 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1995
1996 2) Set PLC IP in [Device IP] settings
1997
1998 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1999
2000 **PLC Settings(GX Works2)**
2001
2002 * Click [Ethernet/CC IE/MELSECNET];
2003 * Please select [Ethernet] as network type;
2004 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
2005 * Select [Online] as Mode;
2006 * [[image:image-20221119164958-2.png||height="356" width="611"]](% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
2007 * Click [Operation setting] to set IP;
2008 * Select [Binary Code] as [Communication Data Code];
2009 * [[image:image-20221119165129-3.png||height="381" width="611"]](% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
2010 * Click [Open setting]
2011 * Set protocol: TCP;
2012 * Set [unpassive] in [Open system];
2013 * Set [receive] in [Fixed buffer];
2014 * Set [procedure Exist] in [Fixed buffer communication];
2015 * Disable [Pairing open];
2016 * Set [No confirm] in [Existence confirmation];
2017 * Host station port number: 5009;
2018 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
2019 * [[image:image-20221119165342-4.png||height="387" width="620"]]
2020 * Download project into PLC and restart it
2021
2022 **Cable Wiring**
2023
2024 (% style="text-align:center" %)
2025 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2026
2027 = Create communication with **Delta PLC** =
2028
2029 == DVP serial protocol ==
2030
2031 (% class="wikigeneratedid" %)
2032 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
2033
2034 **HMI Settings**
2035
2036 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
2037 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
2038 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
2039 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
2040 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
2041 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
2042 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
2043 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
2044
2045 **Address List**
2046
2047 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2048 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
2049 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
2050 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
2051 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
2052 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
2053 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
2054 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
2055 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
2056 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
2057
2058 (% class="wikigeneratedid" %)
2059 **Configure the communication protocol**
2060
2061 (% style="text-align:center" %)
2062 [[image:image-20220829152327-6.png]]
2063
2064 (% style="text-align:center" %)
2065 [[image:image-20220829152016-3.png]]
2066
2067 (% class="wikigeneratedid" %)
2068 **Cable Wiring**
2069
2070 (% class="wikigeneratedid" id="H" %)
2071 [[image:image-20220829152610-7.png]]
2072
2073 (% style="text-align:center" %)
2074 [[image:image-20220829152102-5.png]]
2075
2076 == DVP Ethernet Protocol ==
2077
2078 (% class="wikigeneratedid" %)
2079 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
2080
2081 **HMI Settings**
2082
2083 |=**Items**|=**Settings**|=**Note**
2084 |Protocol|DELTA DVP Modbus TCP|
2085 |Connection|Ethernet|
2086 |Port No.|201|Must be the same as the PLC setting
2087 |PLC station No.|0|Must be the same as the PLC setting
2088
2089 **Address List**
2090
2091 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2092 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
2093 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
2094 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
2095 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
2096 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
2097 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
2098 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
2099 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
2100 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
2101
2102 )))
2103 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
2104 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
2105
2106 )))
2107
2108 (% class="wikigeneratedid" %)
2109 **Configure the communication protocol**
2110
2111 (% style="text-align:center" %)
2112 [[image:image-20220829155452-1.png]]
2113
2114 [[image:image-20220829162116-2.png]]
2115
2116 **Cable Wiring**
2117
2118 (% style="text-align:center" %)
2119 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2120
2121 == **AS serial protocol** ==
2122
2123 Supported Series: Delta AS200/AS300
2124
2125 **HMI Settings**
2126
2127 |**Item**|**Settings**|**Note**
2128 |Protocol|DELTA AS300 MODBUS RTU|
2129 |Connection|RS485|
2130 |Baud rate|9600|
2131 |Data bit|8|
2132 |Parity|NONE|
2133 |Stop bit|1|
2134 |PLC station No.|1|
2135
2136 **Address List**
2137
2138 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2139 |Bit|X|X|Xdd.dd|0~~63.15|Read only
2140 |Bit|Y|Y|Ydd.dd|0~~63.15|
2141 |Bit|D|D|Dddddd|0~~29999|
2142 |Bit|M|M|Mdddd|0~~8191|
2143 |Bit|SM|SM|SMdddd|0~~4095|
2144 |Bit|S|S|Sdddd|0~~2047|
2145 |Bit|T|T|Tddd|0~~511|
2146 |Bit|C|C|Cddd|0~~511|
2147 |Bit|HC|HC|HCddd|0~~255|Double Word
2148 |Word|X|X|Xdd|0~~63|
2149 |Word|Y|Y|(((
2150 Ydd
2151 )))|0~~63|
2152 |Word|SR|SR|SRdddd|0~~2047|Special register
2153 |Word|D|D|Dddddd|0~~29999|
2154 |Word|T|T|Tddd|0~~511|
2155 |Word|C|C|Cddd|0~~511|
2156 |Word|E|E|Ed|0~~9|
2157
2158 **Configure the communication protocol**
2159
2160 Create project
2161
2162 (% style="text-align:center" %)
2163 [[image:AsCreateProject.png]]
2164
2165 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
2166
2167 (% style="text-align:center" %)
2168 [[image:AScommunicarw.png]]
2169
2170 Double click the HWCONFIG to open the communication settings window.
2171
2172 (% style="text-align:center" %)
2173 [[image:ASHWCONFIG.png]]
2174
2175 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
2176
2177 (% style="text-align:center" %)
2178 [[image:ASHSCONFIGICON.png]]
2179
2180 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
2181
2182 (% style="text-align:center" %)
2183 [[image:ASModbusMode.png]]
2184
2185 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
2186
2187 (% style="text-align:center" %)
2188 [[image:ASconfigIP.png]]
2189
2190 (% style="text-align:center" %)
2191 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
2192
2193
2194 (% style="text-align:center" %)
2195 [[image:image-20220830094657-2.png]]
2196
2197 **Cable Wiring**
2198
2199 (% style="text-align:center" %)
2200 [[image:image-20220830141138-1.png]]
2201
2202 Pin Definition Diagram
2203
2204 (% style="text-align:center" %)
2205 [[image:image-20220830095131-1.png]]
2206
2207 == AS Ethernet Protocol ==
2208
2209 **HMI Settings**
2210
2211 |=**Items**|=**Settings**|=**Note**
2212 |Protocol|DELTA AS300 MODBUS TCP|
2213 |Connection|Ethernet|
2214 |Port No.|502|
2215 |Device No.|1|
2216 |HMI No.|0|
2217
2218 **Address List**
2219
2220 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2221 |Bit|X|X|X d|0~~63|
2222 |Bit|Y|Y|Y d|0~~63|
2223 |Bit|D|D|D d|0~~29999|
2224 |Bit|M|M|M d|0~~8191|
2225 |Bit|SM|SM|SM d|0~~4095|
2226 |Bit|S|S|S h|0~~2047|
2227 |Bit|T|T|T d|0~~511|
2228 |Bit|C|C|C d|0~~511|
2229 |Bit|HC|HC|HC d|0~~255|
2230 |Word|X|X|X h|0~~63|
2231 |Word|Y|Y|Y d|0~~63|
2232 |Word|SR|SR|SR d|0~~2047|
2233 |Word|D|D|D d|0~~29999|
2234 |Word|T|T|T d|0~~511|
2235 |Word|C|C|C h|0~~511|
2236 |Word|E|E|E d|0~~9|
2237
2238 **Configure the communication protocol**
2239
2240 (% style="text-align:center" %)
2241 [[image:image-20220830140537-1.png]]
2242
2243 (% style="text-align:center" %)
2244 [[image:image-20220830140629-2.png]]
2245
2246 **Cable Wiring**
2247
2248 [[image:image-20220830094929-1.png]]
2249
2250 Pin Definition Diagram
2251
2252 (% style="text-align:center" %)
2253 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2254
2255 = Create communication with **Omron** PLC =
2256
2257 == CJ TCP FINS Ethemet  Protocol ==
2258
2259 Supported device:CJ series、CJ1W-EIP21
2260
2261 **HMI Settings**
2262
2263 |=**Items**|=**Settings**|=**Note**
2264 |Protocol|OMRON CJ TCP FINS Ethemet|
2265 |Connection|Ethernet|
2266 |Port No.|9600|
2267 |Device No.|0|
2268 |HMI No.|0|(((
2269
2270 )))
2271
2272 **Address List**
2273
2274 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2275 |Bit|CIO|CIO|CIO d|0~~99999|
2276 |Bit|W|W|W d|0~~99999|
2277 |Bit|D|D|D d|0~~99999|
2278 |Bit|H|H|H d|0~~99999|
2279 |Bit|A|A|A d|0~~99999|
2280 |Bit|T|T|T h|0~~99999|
2281 |Bit|CF|CF|CF d|0~~99999|
2282 |Bit|FF|FF|FF d|0~~99999|
2283 |Bit|C|C|C d|0~~99999|
2284 |Bit|EM0|EM0|EM0 d|0~~99999|
2285 |Bit|EM1|EM1|EM1 d|0~~99999|
2286 |Bit|EM2|EM2|EM2 d|0~~99999|
2287 |Bit|EM3|EM3|EM3 d|0~~99999|
2288 |Bit|EM4|EM4|EM4 d|0~~99999|
2289 |Bit|EM5|EM5|EM5 h|0~~99999|
2290 |Bit|EM6|EM6|EM6 d|0~~99999|
2291 |Bit|EM7|EM7|EM7 d|0~~99999|
2292 |Bit|EM8|EM8|EM8 d|0~~99999|
2293 |Bit|EM9|EM9|EM9 d|0~~99999|
2294 |Bit|EMA|EMA|EMA d|0~~99999|
2295 |Bit|EMB|EMB|EMB d|0~~99999|
2296 |Bit|EMC|EMC|EMC d|0~~99999|
2297 |Bit|Lamp|Lamp|Lamp d|0~~0|
2298 |Word|CIO|CIO|CIO d|0~~99999|
2299 |Word|W|W|W d|0~~99999|
2300 |Word|D|D|D d|0~~99999|
2301 |Word|H|H|H d|0~~99999|
2302 |Word|A|A|A d|0~~99999|
2303 |Word|T|T|T h|0~~99999|
2304 |Word|CF|CF|CF d|0~~99999|
2305 |Word|FF|FF|FF d|0~~99999|
2306 |Word|C|C|C d|0~~99999|
2307 |Word|EM0|EM0|EM0 d|0~~99999|
2308 |Word|EM1|EM1|EM1 d|0~~99999|
2309 |Word|EM2|EM2|EM2 d|0~~99999|
2310 |Word|EM3|EM3|EM3 d|0~~99999|
2311 |Word|EM4|EM4|EM4 d|0~~99999|
2312 |Word|EM5|EM5|EM5 h|0~~99999|
2313 |Word|EM6|EM6|EM6 d|0~~99999|
2314 |Word|EM7|EM7|EM7 d|0~~99999|
2315 |Word|EM8|EM8|EM8 d|0~~99999|
2316 |Word|EM9|EM9|EM9 d|0~~99999|
2317 |Word|EMA|EMA|EMA d|0~~99999|
2318 |Word|EMB|EMB|EMB d|0~~99999|
2319 |Word|EMC|EMC|EMC d|0~~99999|
2320 |Word|IR|IR|IR d|0~~99999|
2321 |Word|DR|DR|DR d|0~~99999|
2322
2323 **Configure the communication protocol**
2324
2325 (% style="text-align:center" %)
2326 [[image:image-20220830143348-1.png]]
2327
2328 (% style="text-align:center" %)
2329 [[image:image-20220830143511-2.png]]
2330
2331 **Configure CJ1W-EIP21 connect with HMI**
2332
2333 (% style="text-align:center" %)
2334 [[image:ftEVGvAprh.png]]
2335
2336 Select TCP_Client_2N
2337
2338 (% style="text-align:center" %)
2339 [[image:RURXWcgyCd.png]]
2340
2341 **Cable Wiring**
2342
2343 Pin Definition Diagram
2344
2345 (% style="text-align:center" %)
2346 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2347
2348 == **CP1E/CP1H serial protocol** ==
2349
2350 Supported device: OMRON CS1(CP1E/CP1H)
2351
2352 **HMI Settings**
2353
2354 |=**Items**|=**Settings**|=**Note**
2355 |Protocol|OMRON CS1(CP1E/CP1H)|
2356 |Connection|RS232 (9600, 2, 7, EVEN)|
2357 |Port No.|None|
2358 |PLC station No.|0|
2359
2360 **Address List**
2361
2362 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2363 |Bit|CIO|CIO|CIO d|0~~99999|
2364 |Bit|W|W|W d|0~~99999|
2365 |Bit|D|D|D d|0~~99999|
2366 |Bit|H|H|H d|0~~99999|
2367 |Bit|A|A|A d|0~~99999|
2368 |Bit|TF|T|T h|0~~99999|
2369 |Bit|CF|CF|CF d|0~~99999|
2370 |Bit|T|FF|FF d|0~~99999|
2371 |Bit|C|C|C d|0~~99999|
2372 |Bit|EM0|EM0|EM0 d|0~~99999|
2373 |Bit|EM1|EM1|EM1 d|0~~99999|
2374 |Bit|EM2|EM2|EM2 d|0~~99999|
2375 |Bit|EM3|EM3|EM3 d|0~~99999|
2376 |Bit|EM4|EM4|EM4 d|0~~99999|
2377 |Bit|EM5|EM5|EM5 h|0~~99999|
2378 |Bit|EM6|EM6|EM6 d|0~~99999|
2379 |Bit|EM7|EM7|EM7 d|0~~99999|
2380 |Bit|EM8|EM8|EM8 d|0~~99999|
2381 |Bit|EM9|EM9|EM9 d|0~~99999|
2382 |Bit|EMA|EMA|EMA d|0~~99999|
2383 |Bit|EMB|EMB|EMB d|0~~99999|
2384 |Bit|EMC|EMC|EMC d|0~~99999|
2385 |Word|CIO|CIO|CIO d|0~~99999|
2386 |Word|W|W|W d|0~~99999|
2387 |Word|D|D|D d|0~~99999|
2388 |Word|H|H|H d|0~~99999|
2389 |Word|A|A|A d|0~~99999|
2390 |Word|T|T|T h|0~~99999|
2391 |Word|CIO|CF|CF d|0~~99999|
2392 |Word|C|C|C d|0~~99999|
2393 |Word|EM0|EM0|EM0 d|0~~99999|
2394 |Word|EM1|EM1|EM1 d|0~~99999|
2395 |Word|EM2|EM2|EM2 d|0~~99999|
2396 |Word|EM3|EM3|EM3 d|0~~99999|
2397 |Word|EM4|EM4|EM4 d|0~~99999|
2398 |Word|EM5|EM5|EM5 h|0~~99999|
2399 |Word|EM6|EM6|EM6 d|0~~99999|
2400 |Word|EM7|EM7|EM7 d|0~~99999|
2401 |Word|EM8|EM8|EM8 d|0~~99999|
2402 |Word|EM9|EM9|EM9 d|0~~99999|
2403 |Word|EMA|EMA|EMA d|0~~99999|
2404 |Word|EMB|EMB|EMB d|0~~99999|
2405 |Word|EMC|EMC|EMC d|0~~99999|
2406 |Word|IR|IR|IR d|0~~99999|
2407 |Word|DR|DR|DR d|0~~99999|
2408
2409 **Configure the communication protocol**
2410
2411 (% style="text-align:center" %)
2412 [[image:image-20220902153118-1.png]]
2413
2414 (% style="text-align:center" %)
2415 [[image:image-20220902151322-2.png]]
2416
2417 **Cable Wiring**
2418
2419 (% style="text-align:center" %)
2420 [[image:image-20220902153949-2.png]]
2421
2422 Pin Definition Diagram
2423
2424 (% style="text-align:center" %)
2425 [[image:image-20220902154056-3.png]]
2426
2427 == **EC55 Protocol** ==
2428
2429 Supported device: EC55 temperature instrument
2430
2431 **1)HMI Settings**
2432
2433 |**Items**|**Settings**|**Note**
2434 |Protocol|Omron EC55|
2435 |Connection|RS485 (9600, 2, 7, EVEN)|
2436 |Port No.|None|
2437 |PLC station No.|0|
2438
2439 **2)Address List**
2440
2441 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2442 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2443 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2444 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2445 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2446 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2447 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2448 |CP|-|0-6|Read controller intrinsic property
2449 |CS|-|0-2|Read controller states
2450 |CA|-|0-17|Action command
2451
2452 **3)Device Settings**
2453
2454 Omron E5CC PLC configuration
2455
2456 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2457
2458 (% style="text-align:center" %)
2459 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2460
2461 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2462
2463 (% style="text-align:center" %)
2464 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2465
2466 **✎Note:** The communication settings for HMI should be consistent with this setting.
2467
2468 **Cable Wiring**
2469
2470 (% style="text-align:center" %)
2471 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2472
2473 (% style="text-align:center" %)
2474 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2475
2476 **✎Note:**
2477
2478 * COM3 only available in PI8000/PI9000 series.
2479 * CA address could not support continuous writing function;
2480 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2481 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2482 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2483 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2484 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2485 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2486 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2487
2488 == **EtherNet/IP NX series Protocol** ==
2489
2490 Supported series: Omron NX/NJ series
2491
2492 **HMI Setting**
2493
2494 |**Items**|**Settings**|**Note**
2495 |Protocol|Omron NX Ethernet/IP|
2496 |Connection|Ethernet|
2497 |Port No.|44818|
2498 |PLC station No.|1|
2499
2500 **Instruction**
2501
2502 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2503
2504 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2505
2506 (% style="text-align:center" %)
2507 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2508
2509 **Export labels from Sysmac Studio**
2510
2511 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2512
2513 (% style="text-align:center" %)
2514 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2515
2516 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2517
2518 Click [Label manage];
2519
2520 (% style="text-align:center" %)
2521 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2522
2523 Click [Import labels] and then select the file exported in step 1;
2524
2525 (% style="text-align:center" %)
2526 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2527
2528 The Import Status field shows the result, click [OK] to finish importing address labels;
2529
2530 (% style="text-align:center" %)
2531 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2532
2533 **Communication Settings**
2534
2535 Enable HMI Ethernet in [Project Settings];
2536
2537 (% style="text-align:center" %)
2538 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2539
2540 Set PLC IP in [Device IP] settings;
2541
2542 (% style="text-align:center" %)
2543 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2544
2545 (% style="text-align:center" %)
2546 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2547
2548 **Cable Wiring**
2549
2550 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2551
2552 == CV/CJ1M/CS1H ==
2553
2554 **HMI Setting:**
2555
2556 |=(% scope="row" %)**Parameters**|=**Recommended**
2557 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2558 |=**PLC I/F**|RS232
2559 |=**Baud rate**|9600
2560 |=**Data bits**|7
2561 |=**Parity**|Even
2562 |=**Stop bits**|2
2563 |=**PLC sta. no.**|0
2564
2565 **PLC Setting:**
2566
2567 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2568
2569 **Device Address:**
2570
2571 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2572 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2573 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2574 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2575 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2576 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2577 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2578 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2579 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2580 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2581 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2582 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2583 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2584 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2585 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2586 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2587 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2588 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2589 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2590 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2591 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2592 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2593 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2594 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2595
2596 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2597 |=W|LR_W|DDDD|0 ~~ 4095|
2598 |=W|TC|DDD|0 ~~ 511|
2599 |=W|DM|DDDD|0 ~~ 9999|Data Register
2600
2601 **Wiring Diagram:**
2602
2603 **RS-232**
2604
2605 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2606
2607 Communication Module:
2608
2609 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2610
2611 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2612
2613 (% style="text-align:center" %)
2614 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2615
2616 = Create communication with Xinje** PLC** =
2617
2618 == XC serial protocol ==
2619
2620 **HMI Settings**
2621
2622 |**Item**|**Settings**|**Note**
2623 |Protocol|XINJE XC MODBUS|
2624 |Connection|RS232|
2625 |Baud rate|19200|
2626 |Data bit|8|
2627 |Parity|EVEN|
2628 |Stop bit|1|
2629 |PLC station No.|1|
2630
2631 **Address List**
2632
2633 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2634 |Bit|M|M|M d|0~~8511|
2635 |Bit|X|X|X o|0~~1747|
2636 |Bit|Y|Y|Y o|0~~1747|
2637 |Bit|S|S|S d|0~~1023|
2638 |Bit|T|T|T d|0~~4095|
2639 |Bit|C|C|C d|0~~634|
2640 |Word|D|D|D d|0~~8511|
2641 |Word|TD|TD|TD d|0~~618|
2642 |Word|CD|CD|CD d|0~~634|
2643 |Word|FD|FD|FD d|0~~8511|
2644
2645 **Configure the communication protocol**
2646
2647 (% style="text-align:center" %)
2648 [[image:image-20220830154105-1.png]]
2649
2650 (% style="text-align:center" %)
2651 [[image:image-20220830154159-3.png]]
2652
2653 **Cable Wiring**
2654
2655 Figure
2656
2657 [[image:image-20220830155728-4.png]]
2658
2659 Pin Definition Diagram
2660
2661 (% style="text-align:center" %)
2662 [[image:image-20220830154131-2.png]]
2663
2664 == XD serial protocol ==
2665
2666 **HMI Settings**
2667
2668 Supported Series: Xinjie XD/XE Series PLC
2669
2670 |=**Item**|=**Settings**|=**Note**
2671 |Protocol|XINJE XD/XC MODBUS|
2672 |Connection|RS232|
2673 |Baud rate|19200|
2674 |Data bit|8|
2675 |Parity|EVEN|
2676 |Stop bit|1|
2677 |PLC station No.|1|
2678
2679 **Address List**
2680
2681 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2682 |Bit|M|M|M d|0~~74999|
2683 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2684 |Bit|X2xx|X2xx|X2xx o|0~~277|
2685 |Bit|X|X|X o|0~~77|
2686 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2687 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2688 |Bit|Y|Y|Y o|0~~4095|
2689 |Bit|SM|SM|SM d|0~~4999|(((
2690
2691 )))
2692 |Bit|T|T|T d|0~~4999|
2693 |Bit|C|C|C d|0~~4999|
2694 |Bit|ET|ET|ET d|0~~31|
2695 |Bit|SE|SE|SE d|0~~31|
2696 |Bit|HM|HM|HM d|0~~11999|
2697 |Bit|HSC|HSC|HSC d|0~~39|
2698 |Bit|HS|HS|HS d|0~~999|
2699 |Bit|HT|HT|HT d|0~~1999|
2700 |Bit|HC|HC|HC d|0~~1999|
2701 |Bit|S|S|S d|0~~7999|
2702 |Word|D|D|D d|0~~69999|
2703 |Word|ID|ID|ID d|0~~99|
2704 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2705 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2706 |Word|QD|QD|QD d|0~~99|
2707 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2708 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2709 |Word|SD|SD|SD d|0~~4999|
2710 |Word|TD|TD|TD d|0~~575|
2711 |Word|CD|CD|CD d|0~~575|
2712 |Word|ETD|ETD|ETD d|0~~31|
2713 |Word|HD|HD|HD d|0~~24999|
2714 |Word|HSD|HSD|HSD d|0~~1023|
2715 |Word|HTD|HTD|HTD d|0~~95|
2716 |Word|HCD|HCD|HCD d|0~~95|
2717 |Word|HSCD|HSCD|HSCD d|0~~31|
2718 |Word|FD|FD|FD d|0~~8191|
2719 |Word|SFD|SFD|SFD d|0~~5999|
2720 |Word|FS|FS|FS d|0~~47|
2721
2722 **Configure the communication protocol**
2723
2724 (% style="text-align:center" %)
2725 [[image:image-20220830160042-1.png]]
2726
2727 (% style="text-align:center" %)
2728 [[image:image-20220830160129-2.png]]
2729
2730 **Cable Wiring**
2731
2732 (% style="text-align:center" %)
2733 [[image:image-20220905093902-1.png]]
2734
2735 Pin Definition Diagram
2736
2737 (% style="text-align:center" %)
2738 [[image:image-20220830160232-3.png]]
2739
2740 = Create communication with Inovance** PLC** =
2741
2742 == H3U serial protocol ==
2743
2744 **HMI Settings**
2745
2746 |=**Item**|=**Settings**|=**Note**
2747 |Protocol|INOVANCE H3U PLC|
2748 |Connection|RS422|
2749 |Baud rate|9600|
2750 |Data bit|7|
2751 |Parity|EVEN|
2752 |Stop bit|1|
2753 |PLC station No.|0|
2754
2755 **Address List**
2756
2757 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2758 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X|X o|0~~303237|
2759 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2760 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M|M d|0~~99999|
2761 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T|T d|0~~99999|
2762 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C|C d|0~~99999|
2763 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM|SM d|8000~~999|
2764 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|T|S d|0~~99999|
2765 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp|Lamp d|0~~0|
2766 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X|X o|0~~303237|
2767 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2768 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M|M d|0~~99999|
2769 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T|T d|0~~99999|
2770 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C|C d|0~~199|
2771 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D|D d|0~~7999|
2772 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S|S d|0~~99999|
2773 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD|SD d|8000~~9999|
2774 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R|R d|0~~32767|
2775
2776 **Configure the communication protocol**
2777
2778 (% style="text-align:center" %)
2779 [[image:image-20220830170114-4.png]]
2780
2781 [[image:image-20220830170017-3.png]]
2782
2783 **Cable Wiring**
2784
2785 (% style="text-align:center" %)
2786 [[image:image-20220830165930-1.png]]
2787
2788 Pin Definition Diagram
2789
2790 (% style="text-align:center" %)
2791 [[image:image-20220830165947-2.png]]
2792
2793 = Create communication with Panasonic** PLC** =
2794
2795 == **FP serial protocol** ==
2796
2797 **1)HMI Settings**
2798
2799 |**Item**|**Settings**|**Note**
2800 |Protocol|Panasonic FP MFWTOCOL|
2801 |Connection|RS232|
2802 |Baud rate|9600|
2803 |Data bit|8|
2804 |Parity|ODD|
2805 |Stop bit|1|
2806 |PLC station No.|1|
2807
2808 **2)Address List**
2809
2810 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2811 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2812 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2813 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2814 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2815 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2816 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2817 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2818 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2819 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2820 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2821 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2822 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2823 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2824 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2825 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2826
2827 **3)Configure the communication protocol**
2828
2829 [[image:image-20220830171050-1.png]]
2830
2831 [[image:image-20220830171126-2.png]]
2832
2833 **4)Cable Wiring**
2834
2835 Figure
2836
2837 [[image:image-20220830171328-4.png]]
2838
2839 Pin Definition Diagram
2840
2841 [[image:image-20220830171146-3.png]]
2842
2843 = Create communication with LS** PLC** =
2844
2845 == **XGB serial protocol ** ==
2846
2847 **HMI Settings**
2848
2849
2850 |=**Item**|=**Settings**|=**Note**
2851 |Protocol|LS XGB CPU DRIECT|
2852 |Connection|RS232|
2853 |Baud rate|115200|
2854 |Data bit|8|
2855 |Parity|NONE|
2856 |Stop bit|1|
2857 |PLC station No.|1|
2858
2859 **Address List**
2860
2861
2862 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2863 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2864 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2865 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2866 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2867 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2868 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2869 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2870 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2871 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2872 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2873 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2874 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2875 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2876 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2877 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2878 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2879 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2880 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2881 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2882 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2883 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2884 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2885 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2886 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2887 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2888 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2889
2890 **Configure the communication protocol**
2891
2892 (% style="text-align:center" %)
2893 [[image:image-20221028174410-1.png]]
2894
2895 (% style="text-align:center" %)
2896 [[image:image-20221028174753-2.png]]
2897
2898
2899 (% style="text-align:center" %)
2900 [[image:image-20221028181125-4.png]]
2901
2902 **Pin Definition Diagram**
2903
2904 (% style="text-align:center" %)
2905 [[image:image-20221028180930-3.png]]
2906
2907 = Create communication with LS** PLC** =
2908
2909 == **XBC serial protocol** ==
2910
2911 **HMI Settings**
2912
2913 |=**Item**|=**Settings**|=**Note**
2914 |Protocol|LS XBC CNet|
2915 |Connection|RS232|
2916 |Baud rate|115200|
2917 |Data bit|8|
2918 |Parity|NONE|
2919 |Stop bit|1|
2920 |PLC station No.|1|
2921
2922 **Address List**
2923
2924 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2925 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2926 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2927 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2928 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2929 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2930 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2931 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2932 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2933 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2934 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2935 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2936 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2937 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2938 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2939 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2940 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2941 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2942 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2943 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2944 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2945 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2946
2947 **Configure the communication protocol**
2948
2949 (% style="text-align:center" %)
2950 [[image:image-20220831170807-1.png]]
2951
2952 (% style="text-align:center" %)
2953 [[image:image-20220830174733-2.png]]
2954
2955 **Cable Wiring**
2956
2957 (% style="text-align:center" %)
2958 [[image:image-20220830174659-1.png]]
2959
2960 Pin Definition Diagram
2961
2962 (% style="text-align:center" %)
2963 [[image:image-20220830173402-8.png]]
2964
2965 == **XGK FEnet Ethernet protocol** ==
2966
2967 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2968
2969 **HMI Settings**
2970
2971 |**Items**|**Settings**|**Note**
2972 |Protocol|LG XGK FEnet(Ethernet)|
2973 |Connection|Ethernet|
2974 |Port No.|2004|
2975
2976 **Address List**
2977
2978 |**Type**|**Register**|**Range**|**Format**|**Note**
2979 |(% rowspan="14" %)Word|P|0~~2047|P d|
2980 |M|0~~2047|M d|
2981 |K|0~~2047|K d|
2982 |F|0~~2047|F d|
2983 |T|0~~2047|T d|
2984 |C|0~~2047|C d|
2985 |Z|0~~127|Z d|
2986 |S|0~~127|S d|
2987 |L|0~~11263|L d|
2988 |N|0~~21503|N d|
2989 |D|0~~32767|D d|
2990 |R|0~~32767|R d|
2991 |ZR|0~~65535|ZR d|
2992 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2993
2994 **✎Note:**
2995
2996 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2997 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2998 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2999
3000 **Communication settings in HMI**
3001
3002 Enable HMI Ethernet in [Project Settings];
3003
3004 (% style="text-align:center" %)
3005 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3006
3007 Set PLC IP in [Device IP] settings;
3008
3009 (% style="text-align:center" %)
3010 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3011
3012 **Cable Wiring**
3013
3014 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3015
3016 = Create communication with LS** PLC** =
3017
3018 == **XBC serial protocol** ==
3019
3020 **HMI Settings**
3021
3022 |=**Item**|=**Settings**|=**Note**
3023 |Protocol|LS XBC CNet|
3024 |Connection|RS232|
3025 |Baud rate|115200|
3026 |Data bit|8|
3027 |Parity|NONE|
3028 |Stop bit|1|
3029 |PLC station No.|1|
3030
3031 **Address List**
3032
3033 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3034 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3035 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3036 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3037 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3038 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3039 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3040 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3041 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3042 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3043 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3044 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3045 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3046 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3047 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3048 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3049 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3050 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3051 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3052 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3053 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3054 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3055
3056 **Configure the communication protocol**
3057
3058 (% style="text-align:center" %)
3059 [[image:image-20220831170807-1.png]]
3060
3061 (% style="text-align:center" %)
3062 [[image:image-20220830174733-2.png]]
3063
3064 **Cable Wiring**
3065
3066 (% style="text-align:center" %)
3067 [[image:image-20220830174659-1.png]]
3068
3069 Pin Definition Diagram
3070
3071 (% style="text-align:center" %)
3072 [[image:image-20220830173402-8.png]]
3073
3074 == **XGK FEnet Ethernet protocol** ==
3075
3076 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3077
3078 **HMI Settings**
3079
3080 |**Items**|**Settings**|**Note**
3081 |Protocol|LG XGK FEnet(Ethernet)|
3082 |Connection|Ethernet|
3083 |Port No.|2004|
3084
3085 **Address List**
3086
3087 |**Type**|**Register**|**Range**|**Format**|**Note**
3088 |(% rowspan="14" %)Word|P|0~~2047|P d|
3089 |M|0~~2047|M d|
3090 |K|0~~2047|K d|
3091 |F|0~~2047|F d|
3092 |T|0~~2047|T d|
3093 |C|0~~2047|C d|
3094 |Z|0~~127|Z d|
3095 |S|0~~127|S d|
3096 |L|0~~11263|L d|
3097 |N|0~~21503|N d|
3098 |D|0~~32767|D d|
3099 |R|0~~32767|R d|
3100 |ZR|0~~65535|ZR d|
3101 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3102
3103 **✎Note:**
3104
3105 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3106 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3107 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3108
3109 **Communication settings in HMI**
3110
3111 Enable HMI Ethernet in [Project Settings];
3112
3113 (% style="text-align:center" %)
3114 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3115
3116 Set PLC IP in [Device IP] settings;
3117
3118 (% style="text-align:center" %)
3119 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3120
3121 **Cable Wiring**
3122
3123 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3124
3125 = Create communication with **SHIMADEN PLC** =
3126
3127 == **FP23 series protocol** ==
3128
3129 Supported series: SHIMADEN FP23 series
3130
3131 **HMI Setting**
3132
3133 |**Items**|**Settings**|**Note**
3134 |Protocol|SHIMADEN FP23 series|
3135 |Connection|RS485 (9600, 1, 7, EVEN)|
3136 |Port No.|None|
3137 |PLC station No.|0|
3138
3139 **Address List**
3140
3141 |**Device address**|**HMI register**|**Address range**|**Type**
3142 |0040-0043(HEX)|FP040|100064-200067|Read only
3143 |0100-010B(HEX)|FP100|100256-200267|Read only
3144 |0110-0142(HEX)|FP110|100272-200322|Read only
3145 |0182-0252(HEX)|FP182|100386-200594|Write only
3146 |0280-0281(HEX)|FP280|100640-200641|Read only
3147 |0300-030B(HEX)|FP300|100768-200779|Read and write
3148 |0380-039F(HEX)|FP380|100896-200927|Read and write
3149 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3150 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3151 |0600-0670(HEX)|FP600|101536-201814|Read and write
3152 |0720-0738(HEX)|FP720|101824-201848|Read and write
3153 |0800-083F(HEX)|FP800|102048-202111|Read and write
3154 |0900-0952(HEX)|FP900|102304-202386|Read and write
3155 | |Ctrl|0-2|
3156
3157 **✎Note:**
3158
3159 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3160 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3161 * The Ctrl register is used to store the control group number and BCC check mode.
3162
3163 **Ctrl Register Description**
3164
3165 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3166 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3167 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3168 * Ctrl3 reserved
3169
3170 **✎Note:**
3171
3172 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3173
3174 **Cable Wiring**
3175
3176 (% style="text-align:center" %)
3177 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3178
3179 (% style="text-align:center" %)
3180 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3181
3182 **✎Note:** COM3 only available in PI8000/PI9000 series.
3183
3184 == **SR90 protocol** ==
3185
3186 Supported series: SHIMADEN SR90 series
3187
3188 **HMI Setting**
3189
3190 |**Items**|**Settings**|**Note**
3191 |Protocol|SHIMADEN SR90 protocol|
3192 |Connection|RS485 (1200, 1, 7, EVEN)|
3193 |Port No.|None|
3194 |PLC station No.|0|
3195
3196 **Address List**
3197
3198 |**Device address**|**HMI register**|**Address range**|**Type**
3199 |0040-0043 (HEX)|SR040|100064-100067|Read only
3200 |0100-010A(HEX)|SR0100|100256-100266|Read only
3201 |0182-018C(HEX)|SR0182|100386-100396|Write only
3202 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3203 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3204 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3205 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3206 | |Ctrl|0-2|~-~-
3207
3208 **✎Note:**
3209
3210 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3211 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3212 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3213
3214 **Ctrl Register Description**
3215
3216 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3217 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3218 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3219 * Ctrl3 reserved
3220
3221 **✎Note:**
3222
3223 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3224
3225 **Cable Wiring**
3226
3227 (% style="text-align:center" %)
3228 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3229
3230 (% style="text-align:center" %)
3231 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3232
3233 **✎Note:** COM3 only available in PI8000/PI9000 series.
3234
3235 == **MR13 series(standard protocol)** ==
3236
3237 Supported series: SHIMADEN MR13 series
3238
3239 **HMI Setting**
3240
3241 |**Items**|**Settings**|**Note**
3242 |Protocol|SHIMADEN standard protocol|
3243 |Connection|RS485 (1200, 1, 7, EVEN)|
3244 |Port No.|None|
3245 |PLC station No.|0|
3246
3247 **Address List**
3248
3249 |**Device address**|**HMI register**|**Address range**|**Type**
3250 |0100-010B(HEX)|MR100|100256-300267|Read only
3251 |0111-0126(HEX)|MR111|100273-300294|Read only
3252 |0184-0192(HEX)|MR184|100388-300402|Write only
3253 |0280-0282(HEX)|MR280|100640-300642|Read only
3254 |0300-030B(HEX)|MR300|100768-300779|Read/write
3255 |0314-0317(HEX)|MR314|100788-300791|Read/write
3256 |031A(HEX)|MR31A|100794-300794|Read/write
3257 |0320-0321(HEX)|MR320|100800-300801|Read/write
3258 |0400-0504(HEX)|MR400|101024-301284|Read/write
3259 |0506(HEX)|MR506|101286-301286|Read/write
3260 |0510-0514(HEX)|MR510|101296-301300|Read/write
3261 |0516-0524(HEX)|MR516|101302-301316|Read/write
3262 |0526(HEX)|MR526|101318-301318|Read/write
3263 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3264 |~-~-|Ctrl|0-2|~-~-
3265
3266 **✎Note:**
3267
3268 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3269 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3270 * The Ctrl register is used to store the control group number and BCC check mode.
3271
3272 **Ctrl Register Description**
3273
3274 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3275 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3276 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3277 * Ctrl3 reserved
3278
3279 **✎Note:**
3280
3281 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3282
3283 **Cable Wiring**
3284
3285 (% style="text-align:center" %)
3286 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3287
3288 (% style="text-align:center" %)
3289 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3290
3291 **✎Note:** COM3 only available in PI8000/PI9000 series.
3292
3293 = Create communication with **MODBUS** =
3294
3295 == **MODBUS RTU Master** ==
3296
3297 Supported Series: MODBUS RTU CONTROLLER
3298
3299 HMI works as MODBUS SLAVE connecting with MASTER
3300
3301 (% style="text-align:center" %)
3302 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3303
3304
3305 (% style="text-align:center" %)
3306 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3307
3308
3309 (% style="text-align:center" %)
3310 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3311
3312 **HMI Settings**
3313
3314 (% class="table-bordered" %)
3315 |**Items**|**Settings**|**Note**
3316 |Protocol|MODBUS RTU Master|
3317 |Connection|RS485/RS232|
3318 |Baud rate|2400~~187500|
3319 |Data bit|8|
3320 |Parity|Even/ Odd/ None|
3321 |Stop bit|1/2|
3322 |Station No.|0~~255|
3323
3324 **Address List**
3325
3326 (% class="table-bordered" %)
3327 |**Type**|**HMI address**|**MODBUS code**|**Range**
3328 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3329 |Word|HDW3500~~HDW7999|4|0~~4499
3330
3331 **Cable Wiring**
3332
3333 * **RS485**
3334
3335 (% style="text-align:center" %)
3336 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3337
3338 (% style="text-align:center" %)
3339 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3340
3341 * **RS232**
3342
3343 (% style="text-align:center" %)
3344 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3345
3346 **✎Note:** COM3 only available in PI8000/PI9000 series.
3347
3348 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3349
3350 Supported Series: MODBUS RTU CONTROLLER
3351
3352 HMI works as MODBUS MASTER connecting with SLAVE.
3353
3354 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3355
3356 (% style="text-align:center" %)
3357 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3358
3359
3360 (% style="text-align:center" %)
3361 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3362
3363
3364 (% style="text-align:center" %)
3365 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3366
3367 **HMI Settings**
3368
3369 (% class="table-bordered" %)
3370 |**Items**|**Settings**|**Note**
3371 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3372 |Connection|RS485/RS232|
3373 |Baud rate|2400~~187500|
3374 |Data bit|8|
3375 |Parity|Even/ Odd/ None|
3376 |Stop bit|1/2|
3377 |PLC station No.|0~~255|
3378
3379 **Address List**
3380
3381 (% class="table-bordered" %)
3382 |**Type**|**Address Type**|**Function code & Description**
3383 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3384 |06 (write single register: write a binary value to a holding register)
3385 |10 (write values to multiple addresses )
3386 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3387 |06 (write single register: write a binary value to a holding register)
3388 |10 (write values to multiple addresses )
3389 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3390 |06 (write single register: write a binary value to a holding register)
3391 |10 (write values to multiple addresses )
3392 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3393 |10 (write values to multiple addresses )
3394 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3395 |05 (Force a single coil to force the on/off state of a logic coil)
3396 |0F (Write multiple bits, ie write continuously)
3397 |(% rowspan="3" %)1|02 (Read the input state)
3398 |05 (Force a single coil to force the on/off state of a logic coil)
3399 |0F (Write multiple bits)
3400 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3401 |05 (Force a single coil to force the on/off state of a logic coil)
3402 |0F (Write multiple bits)
3403 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3404 |0F (Write multiple bits)
3405
3406 **✎Note:**
3407
3408 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3409 * The function codes sent out are the same as those that read and write words.
3410
3411 **Station number for more than one slaves**
3412
3413 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3414
3415 (% style="text-align:center" %)
3416 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3417
3418 **Cable Wiring**
3419
3420 * **RS485**
3421
3422 (% style="text-align:center" %)
3423 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3424
3425 (% style="text-align:center" %)
3426 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3427
3428 * **RS232**
3429
3430 (% style="text-align:center" %)
3431 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3432
3433 **✎Note:** COM3 only available in PI8000/PI9000 series.
3434
3435 == **MODBUS TCP Slave (All function)** ==
3436
3437 Supported series: MODBUS TCP controller
3438
3439 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3440
3441 (% style="text-align:center" %)
3442 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3443
3444 (% style="text-align:center" %)
3445 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3446
3447
3448 (% style="text-align:center" %)
3449 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3450
3451 **HMI Setting**
3452
3453 (% class="table-bordered" %)
3454 |**Items**|**Settings**|**Note**
3455 |Protocol|MODBUS TCP Slave (All function)|
3456 |Connection|Ethernet|
3457 |Port No.|502|
3458 |PLC station No.|1|
3459
3460 **Address List**
3461
3462 (% class="table-bordered" %)
3463 |**Type**|**Register**|**Function code & Description**
3464 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3465 |06 (write single register: write a binary value to a holding register)
3466 |10 (write values to multiple addresses )
3467 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3468 |06 (write single register: write a binary value to a holding register)
3469 |10 (write values to multiple addresses )
3470 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3471 |06 (write single register: write a binary value to a holding register)
3472 |10 (write values to multiple addresses )
3473 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3474 |10 (write values to multiple addresses )
3475 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3476 |05 (Force a single coil to force the on/off state of a logic coil)
3477 |0F (Write multiple bits, ie write continuously)
3478 |(% rowspan="3" %)1|02 (Read the input state)
3479 |05 (Force a single coil to force the on/off state of a logic coil)
3480 |0F (Write multiple bits)
3481 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3482 |05 (Force a single coil to force the on/off state of a logic coil)
3483 |0F (Write multiple bits)
3484 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3485 |0F (Write multiple bits)
3486
3487 **Communication Settings**
3488
3489 Enable HMI Ethernet in [Project Settings];
3490
3491 (% style="text-align:center" %)
3492 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3493
3494 Set PLC IP in [Device IP] settings;
3495
3496 (% style="text-align:center" %)
3497 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3498
3499 **Cable Wiring**
3500
3501 (% style="text-align:center" %)
3502 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3503
3504 = **Printer** =
3505
3506 == **TSPL label printer** ==
3507
3508 **Introduction**
3509
3510 TSPL label printer protocol supports following models.
3511
3512 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3513 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3514
3515 **Setting Step**
3516
3517 Select the protocol
3518
3519 * Create a new project, select the TSPL label printer protocol as shown below.
3520
3521 (% style="text-align:center" %)
3522 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3523
3524 Set parameters
3525
3526 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3527
3528 Printer register
3529
3530 (% class="table-bordered" %)
3531 |**Register**|**System**|**Range**|**Function**
3532 |TSPL_SP|decimal|0 - 1|Set the paper size
3533 |TSPL_PT|decimal|0 - 1999|Print text
3534 |TSPL_PQ|decimal|0 - 999|Print QR code
3535 |TSPL_PB|decimal|0 - 999|Print barcode
3536 |TSPL_PR|decimal|0 - 1|Print offset
3537 |TSPL_PN|decimal|0 - 0|Trigger printing
3538 |TSPL_PS|decimal|0 - 0|Print status
3539
3540 * Set paper size:
3541 ** TSPL_SP0: width of paper, unit: mm.
3542 ** TSPL_SP1: height of paper, unit: mm.
3543 * Print text:
3544 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3545 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3546
3547 (% class="table-bordered" %)
3548 |**Register**|**Function**|**Description**
3549 |TSPL_PT0|X coordinate|Unit: dot
3550 |TSPL_PT1|Ycoordinate|Unit: dot
3551 |TSPL_PT2|Rotation angle|(((
3552 0: 0 degrees
3553
3554 1: 90 degrees
3555
3556 2: 180 degrees
3557
3558 3: 270 degrees
3559 )))
3560 |TSPL_PT3|Size|Range: 0-3
3561 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3562
3563 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3564
3565 Print QR code:
3566
3567 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3568 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3569
3570 (% class="table-bordered" %)
3571 |**Register**|**Function**|**Description**
3572 |TSPL_PQ0|X coordinate|Unit: dot
3573 |TSPL_PQ1|Ycoordinate|Unit: dot
3574 |TSPL_PQ2|Rotation angle|(((
3575 0: 0 degrees
3576
3577 1: 90 degrees
3578
3579 2: 180 degrees
3580
3581 3: 270 degrees
3582 )))
3583 |TSPL_PQ3|Size|Range: 0-5
3584 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3585
3586 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3587
3588 Print bar code:
3589
3590 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3591 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3592
3593 (% class="table-bordered" %)
3594 |**Register**|**Function**|**Description**
3595 |TSPL_PB0|X coordinate|Unit: dot
3596 |TSPL_PB1|Ycoordinate|Unit: dot
3597 |TSPL_PB2|Rotation angle|(((
3598 0: 0 degrees
3599
3600 1: 90 degrees
3601
3602 2: 180 degrees
3603
3604 3: 270 degrees
3605 )))
3606 |TSPL_PB3|height|Unit: dot
3607 |TSPL_PB4|width|Range:0-2
3608 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3609
3610 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3611
3612 Print offset:
3613
3614 * TSPL_PR0: X coordinate offset, unit: mm;
3615 * TSPL_PR1: Y coordinate offset, unit: mm.
3616
3617 Trigger printing:
3618
3619 * TSPL_PN0 = 1: trigger the printer to start printing.
3620
3621 Printing status:
3622
3623 * TSPL_PS0 = 1: The printing is normal.
3624 * TSPL_PS0 = 1: The printing is abnormal.
3625
3626 Print picture
3627
3628 * For the function of printing pictures, please refer to the configuration of [Printer object].
3629
3630 Conversion between dot and mm
3631
3632 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3633
3634 == **EpsonTM series** ==
3635
3636 **HMI Settings**
3637
3638 (% class="table-bordered" %)
3639 |**Item**|**Settings**|**Note**
3640 |Protocol|EPSON-TM-T82II/TM-XXX|
3641 |Connection|RS232|
3642 |Baud rate|9600~~115200|
3643 |Data bit|8|
3644 |Parity|None|
3645 |Stop bit|1|
3646 |PLC station No.|1|
3647
3648 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3649
3650 **Printer Settings**
3651
3652 (% class="table-bordered" %)
3653 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3654 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3655 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3656 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3657 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3658 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3659 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3660
3661 **Cable Wiring**
3662
3663 (% style="text-align:center" %)
3664 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3665
3666 (% style="text-align:center" %)
3667 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3668
3669 **✎Note:** COM3 only available in PI8000/PI9000 series.
3670
3671
3672 = Create communication with **Schneider PLC** =
3673
3674 == **Schneider MODBUS RTU** ==
3675
3676 **HMI Setting**
3677
3678 |=**Parameters**|=**Recommended**|=**Notes**
3679 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3680 |Connection|RS485|
3681 |**Baud rate**|19200|
3682 |**Data bit**|8|
3683 |**Parity**|Even|
3684 |**Stop bit**|1|
3685 |**PLC station No.**|1|
3686
3687 **PLC Setting**
3688
3689 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3690
3691 **Device Address**
3692
3693 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3694 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3695 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3696 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3697 |W|MW|DDDDDD|0 ~~ 999999|Output register
3698 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3699
3700 **Wiring Diagram**
3701
3702 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3703
3704 (% style="text-align:center" %)
3705 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3706
3707 = **Barcode Scanner** =
3708
3709 Supported: DELI 14880 barcode scanner
3710
3711 **HMI Setting**
3712
3713 |**Items**|**Settings**|**Note**
3714 |Protocol|Barcode Scanner|
3715 |Connection|USB|
3716
3717 **Operating Procedures**
3718
3719 Select [Barcode Scanner];
3720
3721 (% style="text-align:center" %)
3722 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3723
3724 Set address for receiving;
3725
3726 Set correct length;
3727
3728 (% style="text-align:center" %)
3729 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3730
3731 **✎Note:**
3732
3733 * The protocol uploads the information acquired by the USB scanner to the HMI;
3734 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3735 * Recommended model: DELI 14880 barcode scanner;
3736
3737 = **Hitachi EHV Series (Ethernet)** =
3738
3739 Supported series: Hitachi EHV series
3740
3741 **HMI Settings**
3742
3743 (% class="table-bordered" %)
3744 |**Items**|**Settings**|**Note**
3745 |Protocol|Hitachi EHV series|
3746 |Connection|Ethernet|
3747 |Port No.|3004~~3007|
3748
3749 **Address List**
3750
3751 (% class="table-bordered" %)
3752 |**Type**|**Register**|**Range**|**Format**|**Note**
3753 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3754 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3755 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3756 H1H2H3H4 Module main number
3757
3758 H1: Remote number
3759
3760 H2: Unit number
3761
3762 H3: Slot number
3763
3764 H4: Word number of Module
3765
3766 H Sub number of Module
3767
3768 For example:X21.3
3769
3770 Slot number 2
3771
3772 Word number of module is 1
3773
3774 Bit number of module is 3
3775
3776 Remote number and unit number are 0
3777 )))
3778 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3779 |R|0 – FF.f (Hex)|R HH.h|
3780 |L|0 - 73FF.f (Hex)|L HHHH.h|
3781 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3782 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3783 H1H2H3H4 Module main number
3784
3785 H1: Remote number
3786
3787 H2: Unit number
3788
3789 H3: Slot number
3790
3791 H4: Word number of module
3792
3793 For example:WX21
3794
3795 Word number of module is 1
3796
3797 Slot number is 2
3798
3799 Remote number and unit number are 0
3800 )))
3801 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3802 |WR|0 – FFFF (Hex)|WR HHHH|
3803 |WL|0 - 73FF (Hex)|WL HHHH|
3804 |TC|0 - 2559|TC DDDD|
3805
3806 **Communication settings in HMI**
3807
3808 Enable HMI Ethernet in [Project Settings];
3809
3810 (% style="text-align:center" %)
3811 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3812
3813 Set PLC IP in [Device IP] settings;
3814
3815 (% style="text-align:center" %)
3816 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3817
3818 **PLC Configuration**
3819
3820 Connect with PLC, select[Online mode];
3821
3822 (% style="text-align:center" %)
3823 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3824
3825 Set IP address, it is the same LAN parameters with HMI;
3826
3827 (% style="text-align:center" %)
3828 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3829
3830 3) Save PLC communication parameter, and restart PLC
3831
3832 **PLC Monitor Mode**
3833
3834 Connect with PLC and choose to “online” mode
3835
3836 (% style="text-align:center" %)
3837 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3838
3839 Open I/O monitor sheet1
3840
3841 (% style="text-align:center" %)
3842 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3843
3844 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3845
3846 (% style="text-align:center" %)
3847 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3848
3849 Enter the register address, click OK to view the value of the register.
3850
3851 (% style="text-align:center" %)
3852 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3853
3854 (% style="text-align:center" %)
3855 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3856
3857 **✎Note:**
3858
3859 * Both word registers and bit registers support even continuous read/write functions;
3860 * The range of registers is based on the specific PLC type;
3861
3862 **Cable Wiring**
3863
3864 (% style="text-align:center" %)
3865 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3866
3867 = **IEC60870-5 104 Client** =
3868
3869 **HMI Setting**
3870
3871 (% class="table-bordered" %)
3872 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3873 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3874 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3875 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3876
3877 **Address List**
3878
3879 (% class="table-bordered" %)
3880 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3881 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3882 |(% style="width:461px" %)SCNA|0~~16777215.7
3883 |(% style="width:461px" %)DPTB|0~~16777215.7
3884 |(% style="width:461px" %)DCNA|0~~16777215.7
3885 |(% style="width:461px" %)METF|0~~16777215.7
3886 |(% style="width:461px" %)SENC|0~~16777215.7
3887 |(% style="width:461px" %)SENA|0~~16777215.7
3888 |(% style="width:461px" %)MENA|0~~16777215.7
3889 |(% style="width:461px" %)METD|0~~16777215.7
3890 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3891 |(% style="width:461px" %)SCNA|0~~16777215
3892 |(% style="width:461px" %)DPTB|0~~16777215
3893 |(% style="width:461px" %)DCNA|0~~16777215
3894 |(% style="width:461px" %)SENA|0~~16777215
3895 |(% style="width:461px" %)MENA|0~~16777215
3896 |(% style="width:461px" %)METD|0~~16777215
3897 |(% style="width:461px" %)INRO|0~~16777215
3898 |(% style="width:461px" %)TIMESYN|0~~16777215
3899 |(% style="width:461px" %)TIMEZ|0~~16777215
3900 |(% style="width:461px" %)NTP|0~~16777215
3901 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3902 |(% style="width:461px" %)SENC|0~~16777215
3903
3904 **Address Configuration**
3905
3906 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3907
3908 (% style="text-align:center" %)
3909 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3910
3911 (% style="text-align:center" %)
3912 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3913
3914 Extended tag name
3915
3916 Address range for the extended tag.
3917
3918 **Communication Settings**
3919
3920 Enable HMI Ethernet in [Project Settings];
3921
3922 (% style="text-align:center" %)
3923 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3924
3925 Set PLC IP in [Device IP] settings;
3926
3927 (% style="text-align:center" %)
3928 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3929
3930 **Cable Wiring**
3931
3932 (% style="text-align:center" %)
3933 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3934
3935 = **OpenCAN** =
3936
3937 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3938
3939 This protocol is only available in PI8000 series HMI.
3940
3941 **HMI Settings**
3942
3943 |**Items**|**Settings**|**Note**
3944 |Protocol|OPENCAN|
3945 |Connection|CAN port|
3946 |Baud rate|250000|
3947
3948 **CAN frame setting in HMI**
3949
3950 Click [OpenCAN setting] button in communication setting window;
3951
3952 (% style="text-align:center" %)
3953 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3954
3955 Click [Add] to create a new frame;
3956
3957 (% style="text-align:center" %)
3958 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3959
3960 |**No**|**Items**|**Description**
3961 |1|Add|add a frame related to register address
3962 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3963 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3964 |4|Modify|Modify the frames in frame management
3965 |5|Copy|Copy one frame to another
3966 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3967 |7|Empty|All frames in the list are cleared
3968 |8|Browse|Displays configuration files in XML format in IE
3969 |9|OK|Complete the configuration of the frame and exit
3970
3971 Set CANBUS frame in setting windows
3972
3973 (% style="text-align:center" %)
3974 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3975
3976 |**No**|**Items**|**Description**
3977 |1|ID|Set the ID of a can frame in hexadecimal format;
3978 |2|ID assign|split the ID by PF, PS, and SA;
3979 |3|Frame type|Select Standard frame or Extended Frame;
3980 |4|Frame format|Select between data frame and remote Frame;
3981 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3982 |6|Use address|(((
3983 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3984
3985 **Edit:** Set a bit or word address by its format;
3986
3987 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3988 )))
3989 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3990 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3991 |Feedback mode: feedback mode includes no response, confirm response and data response;
3992 |No response: the device or touch screen will not receive feedback;
3993 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3994 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3995 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3996 |Response timeout: sets whether the response frame timeout;
3997 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3998 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3999 |Manually send: a manually send tick indicates only one send;
4000 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4001 |10|Note|Fill the text to explain the meaning of the frame;
4002 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4003 |12|Current operation display|Display the description of current operation;
4004 |13|Add|Add a new frame;
4005 |14|Save frame|Save the configured frame format;
4006 |15|Cancel|Cancel the frame configuration;
4007
4008 Set CAN address (Read or write operation);
4009
4010 (% style="text-align:center" %)
4011 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4012
4013 |**No.**|**Item**|**Description**
4014 |1|Current address|Displays the register type and register address set by the user in the data access interface
4015 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4016 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4017 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4018 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4019 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4020 |If the trigger condition is a writing operation, there are two situations:(((
4021 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4022 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4023 )))
4024 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4025 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4026 |4|Add|Add current configuration
4027 |5|Close|Close the configuration window to exit
4028
4029 **Multiple Packages Settings**
4030
4031 (% style="text-align:center" %)
4032 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4033
4034 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4035
4036 Select Multiple package type
4037
4038 * Not Multiple packages
4039 * J1939 Multiple packages
4040 * Customized Multiple packages
4041
4042 Click [Edit Receive data] for [Receive] settings
4043
4044 * Start code+ Total length (J1939)
4045
4046 (% style="text-align:center" %)
4047 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4048
4049 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4050
4051 * Start code + Data max length (J1939)
4052
4053 (% style="text-align:center" %)
4054 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4055
4056 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4057
4058 * Data max length (J1939)
4059
4060 (% style="text-align:center" %)
4061 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4062
4063 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4064
4065 * Customized multiple package
4066
4067 (% style="text-align:center" %)
4068 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4069
4070 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4071
4072 Click [Edit Send data] for [Send] setting
4073
4074 * J1939
4075
4076 (% style="text-align:center" %)
4077 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4078
4079 [Data] is all data to be sent.
4080
4081 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4082
4083 * Customized multiple package
4084
4085 (% style="text-align:center" %)
4086 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4087
4088 [Data] is all data to be sent.
4089
4090 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4091
4092 **Cable Wiring**
4093
4094 (% style="text-align:center" %)
4095 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4096
4097 **✎Note:** The address interval between each frame need to be more than a word address;
4098
4099
4100 = **User Defined Protocol** =
4101
4102 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4103
4104 **HMI Settings**
4105
4106 |**Items**|**Settings**|**Note**
4107 |Protocol|User defined protocol|
4108 |Connection|RS485/RS232|
4109 |Baud rate|2400~~187500|
4110 |Stop bits|1/ 2|
4111 |Data bits|7/ 8|
4112 |Parity|None/ Even/ ODD|
4113
4114 **Operating Procedures**
4115
4116 Select [User defined protocol];
4117
4118 Click [User defined protocol] button to open setting window as below;
4119
4120 (% style="text-align:center" %)
4121 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4122
4123 Configure user defined command;
4124
4125 (% style="text-align:center" %)
4126 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4127
4128 |**No**|**Item**|**Description**
4129 |1|Instruction edit|The required command.
4130 |2|Mode|Write to address or read from the address.
4131 |3|Format|Encode format: HEX or ASCII.
4132 |4|Other|(((
4133 **No receiving: **HMI does not respond to the receiving command.
4134
4135 **Send after receiving:** HMI responds to the receiving command.
4136 )))
4137 |5|Manually send|(((
4138 Respond once after trigger the address.
4139
4140 Address: set the trigger address.
4141 )))
4142 |6|Add|Save this setting.
4143 |7|Cancel|Cancel current settings.
4144 |(% rowspan="4" %)8|Add|Add a new command.
4145 |Edit|Edit the selected command.
4146 |Delete|Delete the selected command.
4147 |Clear|Clear all the commands.
4148 |9|Instruction list|Display all current commands.
4149 |10|Address List|Display all the addresses added.
4150 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4151 |Export|Export current command settings to local storage.
4152 |Browse|Browse local command files.
4153 |Advanced|Combine two commands.
4154 |Exit|Complete editing and exit setting.
4155
4156 **Operating Procedures**
4157
4158 Click [Add] to create a new command, as below shows;
4159
4160 (% style="text-align:center" %)
4161 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4162
4163 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4164
4165 (% style="text-align:center" %)
4166 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4167
4168 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4169
4170 (% style="text-align:center" %)
4171 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4172
4173 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4174
4175 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4176
4177 Check settings;
4178
4179 (% style="text-align:center" %)
4180 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4181
4182 |**No**|**Items**|**Description**
4183 |1|Add checking|Add checking command when receiving the data.
4184 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4185 |Differ with send check|Set return checking.
4186 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4187 |Length: The data length need to be checked.
4188
4189 Object settings;
4190
4191 (% style="text-align:center" %)
4192 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4193
4194 |**No**|**Items**|**Description**
4195 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4196 |Address: the triggering address;
4197 |Note: description to object;
4198 |2|Byte order|The numerical display order;
4199
4200 Data length settings;
4201
4202 (% style="text-align:center" %)
4203 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4204
4205 |**No**|**Item**|**Description**
4206 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4207 |Length: the return data length.
4208 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4209 |Length: the write data length.
4210
4211 Instruction length settings
4212
4213 (% style="text-align:center" %)
4214 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4215
4216 |**No**|**Item**|**Description**
4217 |1|Send length|The instruction data will only send designated data length.
4218 |2|Return length|The responds data length.
4219 |3|End code|Instruction will not be terminated until receiving [End code];
4220
4221 **Cable Wiring**
4222
4223 * **RS485**
4224
4225 (% style="text-align:center" %)
4226 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4227
4228 (% style="text-align:center" %)
4229 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4230
4231 * **RS232**
4232
4233 (% style="text-align:center" %)
4234 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4235
4236 **✎Note:** COM3 only available in PI8000/PI9000 series.