Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 224.2 by Hunter on 2023/03/18 14:39

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488
489 = Create communication with **Rockwell PLC** =
490
491 == **DF1 Protocol** ==
492
493 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
494
495 **HMI Settings**
496
497 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
498 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
499 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
500 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
501 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
502 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
503 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
504 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
505 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
506
507 **Address List**
508
509 (% class="table-bordered" %)
510 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
511 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
512 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
513 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
514 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
515 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
516 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
517 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
518 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
519 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
520 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
521 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
522
523 **Cable Wiring**
524
525 (% style="text-align:center" %)
526 [[image:AB.gif]]
527
528 == **DF1 Advanced Protocol** ==
529
530 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
531
532 **HMI Settings**
533
534 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
535 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
536 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
537 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
538 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
539 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
540 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
541 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
542 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
543
544 **Address List**
545
546 (% class="table-bordered" %)
547 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
548 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
549 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
550 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
551 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
552 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
553 Bit data file B0~~B99
554
555 First two digits is for file number
556
557 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
558 )))
559 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
560 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
561 Integer data file bit format N0~~N99
562
563 First two digits is for file number
564
565 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
566 )))
567 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
568 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
569 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
570 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
571 Timer Preset Value
572
573 First two digits is for file number
574
575 For example, TNS99255 represents file number T99, address 255.
576 )))
577 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
578 Timer Accumulator Value
579
580 First two digits is for file number
581
582 For example, TNP99255 represents file number T99, address 255.
583 )))
584 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
585 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
586 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
587 Counter Preset Value
588
589 First two digits is for file number
590
591 For example, CNS99255 represents file number C99, address 255.
592 )))
593 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
594 Counter Accumulator Value
595
596 First two digits is for file number
597
598 For example, CNP99255 represents file number C99, address 255.
599 )))
600 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
601 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
602 Integer data file
603
604 First two digits is for file number
605
606 For example, NN99255 represents file number N99, address 255.
607 )))
608 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
609 Only able to communicate with file number N7
610 )))
611 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
612 Floating point data file
613
614 First two digits is for file number
615
616 For example, FN99255 represents file number F99, address 255.
617 )))
618 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
619
620 **Cable Wiring**
621
622 (% style="text-align:center" %)
623 [[image:AB.gif]]
624
625 == **MicroLogix Protocol** ==
626
627 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
628
629 **HMI Settings**
630
631 (% class="table-bordered" %)
632 |**Item**|**Settings**|**Note**
633 |Protocol|Allen-Bradlley MicroLogix|
634 |Connection|RS232|
635 |Baud rate|19200|
636 |Data bit|8|
637 |Parity|None|
638 |Stop bit|1|
639 |PLC station No.|1|
640
641 **Address List**
642
643 (% class="table-bordered" %)
644 |**Type**|**Device registers**|**Format**|**Range**|**Note**
645 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
646 |O|O d.d|0.0~~255.15|
647 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
648 |S|S d.d|0.0~~255.15|
649 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
650 |(% rowspan="9" %)Word|S|S d|0~~255|
651 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
652 |TP|TP nnhh|0~~ffff
653 |CS|CS nnhh|0~~ffff
654 |CP|CP nnhh|0~~ffff
655 |N|N nnhh|0~~ffff
656 |C|C nnhh|0~~ffff
657 |T|T nnhh|0~~ffff
658 |R|R nnhh|0~~ffff
659
660 **Cable Wiring**
661
662
663 (% style="text-align:center" %)
664 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
665
666 == **CompactLogix FreeTag Ethernet protocol** ==
667
668 Allen-Brandly CompactLogix
669
670 **HMI Settings**
671
672 (% class="table-bordered" %)
673 |**Items**|**Settings**|**Note**
674 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
675 |Connection|Ethernet|
676 |Port No.|44818|
677
678 **PLC Setting**
679
680 Create new tags
681
682 (% style="text-align:center" %)
683 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
684
685 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
689
690 Import labels, please open [Communication] window and click [Import label];
691
692 Select csv file, all tags will be displayed as belows;
693
694 (% style="text-align:center" %)
695 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
696
697 **✎Note:**
698
699 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
700
701 (% style="text-align:center" %)
702 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
703
704 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
705
706 **Communication settings in HMI**
707
708 Enable HMI Ethernet in [Project Settings];
709
710 (% style="text-align:center" %)
711 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
712
713 Set PLC IP in [Device IP] settings;
714
715 (% style="text-align:center" %)
716 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
717
718 **Cable Wiring**
719
720 (% style="text-align:center" %)
721 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
722
723 == **MicroLogix 1200** **protocol** ==
724
725 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
726
727 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
728 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
729 * **Word address S:** The word address ranges from 0 to 255 (decimal).
730 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
731
732 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
733
734 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
735 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
736 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
737 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
738 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
739 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
740 |**PLC word address type**|**Address format**|**Address range**
741 |S|ddd|S0 ~~ 255
742 |TS|ffff|TS0 ~~ FFFF
743 |TP|ffff|TP0 ~~ FFFF
744 |CS|ffff|CS0 ~~ FFFF
745 |CP|ffff|CP0 ~~ FFFF
746 |N|ffff|N0 ~~ FFFF
747 |F|ffff|F0 ~~ FFFF
748
749 = Create communication with Crouzet PLC =
750
751 == **M3 (FBD) Protocol** ==
752
753 Support Series: Crouzet Millenium 3 CD12/CB12
754
755 **HMI Settings**
756
757 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
758 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
759 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
760 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
761 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
762 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
763 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
764 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
765 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
766
767 **Address List**
768
769 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
770 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
771 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
772 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
773 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
774 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
775 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
776 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
777 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
778 Time1: Second
779
780 Time2: Minute
781
782 Time3: Hour
783
784 Time4: Day
785
786 Time5: Month
787
788 Time6: Year
789 )))
790 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
791 Running command(Write only)
792
793 ~=2: Run mode; =1: Stop mode;
794 )))
795
796 **Cable Wiring**
797
798 (% style="text-align:center" %)
799 [[image:CrouzetRS232.png]]
800
801
802
803 = Create communication with Danfoss Drive =
804
805 == **FC Series Protocol** ==
806
807 Support Series: VLT FC300 Drive
808
809 **HMI Settings**
810
811 (% style="width:988px" %)
812 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
813 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
814 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
815 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
816 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
817 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
818 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
819 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
820 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
821
822 **Address List**
823
824 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
825 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
826 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
827 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
828 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
829
830 **Cable Wiring**
831
832 (% style="text-align:center" %)
833 [[image:Danfoss.png]]
834
835 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
836
837 == **S7-200 Smart Ethernet Protocol** ==
838
839 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
840
841 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
842
843 **HMI Setting**
844
845 (% class="table-bordered" %)
846 |**Items**|**Settings**|**Note**
847 |Protocol|Simens S7-200 Smart Ethernet|
848 |Connection|Ethernet|
849 |Port No.|102|
850 |PLC station No.|2|
851
852 **Address List**
853
854 (% class="table-bordered" %)
855 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
856 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
857 |Q|Q|Q ddddd.o|0.0~~99999.7|
858 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
859 |V|V|V ddddd.o|0.0~~99999.7|
860 |M|M|M ddddd.o|0.0~~99999.7|
861 |SM|SM|ddddd.o|0.0~~99999.7|
862 |S|S|ddddd.o|0.0~~99999.7|Read only
863 |T|T|ddddd|0~~99999|Timer state, read only
864 |C|C|ddddd|0~~99999|Counter state, read only
865 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
866 |Q|QW|QW ddddd|0~~99999|
867 |AI|AIW|AIW ddddd|0~~99999|
868 |AQ|VB|VB ddddd|0~~99999|
869 |V|VW|VW ddddd|0~~99998|(((
870 VW0=VB (0~~1)
871
872 VW2=VB (2~~3)
873
874 Address value is a multiple of 2
875 )))
876 |V|VD|VD ddddd|0~~99998|(((
877 VD0=VB (0~~3)
878
879 VD2=VB (4~~7)
880
881 Address value is a multiple of 4
882 )))
883 |M|MB|MB ddddd|0~~99999|
884 |M|MW|MW ddddd|0~~99999|(((
885 MW0=MB(0~~1)
886
887 MW2=MB(2~~3)
888
889 Address value is a multiple of 2
890 )))
891 |M|MD|MD ddddd|0~~99999|(((
892 MD0=MB(0~~3)
893
894 MD4=MB(4~~7)
895
896 Address value is a multiple of 4
897 )))
898 |T|TW|TW ddddd|0~~99999|Value of timer
899 |C|CW|CW ddddd|0~~99999|Value of counter
900 |W|SW|SW ddddd|0~~99999|
901
902 **Communication Settings**
903
904 Enable HMI Ethernet in [Project Settings];
905
906 (% style="text-align:center" %)
907 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
908
909 Set PLC IP in [Device IP] settings;
910
911 (% style="text-align:center" %)
912 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
913
914 * PLC IP Address: PLC IP
915 * PLC pot No.: 102(fixed)
916 * Network:TCP_Client_2N(fixed)
917
918 (% style="text-align:center" %)
919 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
920
921 * Wait timeout: depend on actual network situation (more than 1500 ms)
922
923 **Cable Wiring**
924
925 (% style="text-align:center" %)
926 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
927
928 == **S7-300 Ethernet Protocol** ==
929
930 Supported Series: Siemens S7-300 series PLC
931
932 **HMI Setting**
933
934 (% class="table-bordered" %)
935 |**Items**|**Settings**|**Note**
936 |Protocol|Simens S7-300 Ethernet|
937 |Connection|Ethernet|
938 |Port No.|102|
939 |PLC station No.|2|Need to be same as the PLC setting
940
941 **Address List**
942
943 (% class="table-bordered" %)
944 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
945 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
946 |Q|Q|Q ddddd.o|0.0~~99999.7|
947 |M|M|M ddddd.o|0.0~~99999.7|
948 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
949 nnnn: block number;
950
951 dddd: address;
952 )))
953 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
954 |Q|QW|QW ddddd|0~~99999|
955 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
956 |MW|MW ddddd|0~~99999|(((
957 MW0=MB(0~~1)
958
959 MW2=MB(2~~3)
960
961 Address value is a multiple of 2
962 )))
963 |MD|MD ddddd|0~~99999|(((
964 MD0=MB(0~~3)
965
966 MD4=MB(4~~7)
967
968 Address value is a multiple of 4
969 )))
970 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
971 nnnn: block number;
972
973 dddd: address
974 )))
975 |DBxDBW|DBxDBW nnnndddd|0~~99999999
976 |DBxDBD|DBxDBD nnnndddd|0~~99999999
977
978 **Communication Settings**
979
980 Enable HMI Ethernet in [Project Settings];
981
982 (% style="text-align:center" %)
983 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
984
985 Set PLC IP in [Device IP] settings;
986
987 (% style="text-align:center" %)
988 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
989
990 * PLC IP Address: PLC IP
991 * PLC pot No.: 102(fixed)
992 * Network:TCP_Client_2N(fixed)
993
994 (% style="text-align:center" %)
995 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
996
997 * Wait timeout: depend on actual network situation (more than 1500 ms)
998
999 **Cable Wiring**
1000
1001 (% style="text-align:center" %)
1002 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1003
1004 == **S7-1200 Ethernet Protocol** ==
1005
1006 Supported Series: Siemens S7-1200
1007
1008 **HMI Setting**
1009
1010 (% class="table-bordered" %)
1011 |**Items**|**Settings**|**Note**
1012 |Protocol|Siemens S7-1200|
1013 |Connection|Ethernet|
1014 |Port No.|102|
1015 |PLC station No.|2|
1016
1017 **Address List**
1018
1019 (% class="table-bordered" %)
1020 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1021 |(% rowspan="4" %)Bit|I|I|M d.o|(((
1022 d:0~-~-9999
1023
1024 o:0-7
1025 )))|
1026 |Q|Q|Q d.o|(((
1027 d:0~-~-9999
1028
1029 o:0-7
1030 )))|
1031 |M|M|M d.o|(((
1032 d:0~-~-9999
1033
1034 o:0-7
1035 )))|
1036 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
1037 nn:0-9999,
1038
1039 dddd:0-9999,
1040
1041 o:0-7
1042 )))|(((
1043 nn:DB No.
1044
1045 dddd:address value
1046
1047 o: digit address
1048 )))
1049 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1050 |M|MW|MW d|d:0-99999|(((
1051 MW0=MB(0~~1)
1052
1053 MW2=MB(2~~3)
1054
1055 Address value is a multiple of 2
1056 )))
1057 |M|MD|MD d|d:0-99999|(((
1058 MD0=MB(0~~3)
1059
1060 MD4=MB(4~~7)
1061
1062 Address value is a multiple of 4
1063 )))
1064 |I|IW|IW d|d:0-99999|
1065 |Q|QW|QW d|d:0-99999|
1066 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1067 nn:0-9999
1068
1069 dddd:0-9999
1070 )))|(((
1071 nn:DB No.
1072
1073 dddd:address value
1074 )))
1075 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1076 nn:0-9999
1077
1078 dddd:0-9999
1079 )))|(((
1080 nn:DB No.
1081
1082 dddd:address value
1083
1084 Address value is a multiple of 2
1085 )))
1086 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1087 nn:0-9999
1088
1089 dddd:0-9999
1090 )))|(((
1091 nn:DB No.
1092
1093 dddd:address value
1094
1095 Address value is a multiple of 4
1096 )))
1097
1098 **Communication Settings**
1099
1100 Enable HMI Ethernet in [Project Settings];
1101
1102 (% style="text-align:center" %)
1103 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1104
1105 Set PLC IP in [Device IP] settings;
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1109
1110 **✎Note:**
1111
1112 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1113 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1114 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
1115 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
1116
1117 **PLC Settings**
1118
1119 Add BD
1120
1121 * Please uncheck [Symbolic access only] option;
1122
1123 (% style="text-align:center" %)
1124 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
1125
1126 Address settings, using BD2 as example.
1127
1128 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
1129 * 2 represent DB block number
1130 * xxxx represent address
1131
1132 **Such as:**
1133
1134 * DBxDBB20000 = DB2.DBB0
1135 * DBxDBW20004 = DB2.DBW4
1136
1137 (% style="text-align:center" %)
1138 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
1139
1140 **How to connect with S7-1200 Firmware V4.0**
1141
1142 PLC configuration
1143
1144 * Double click [device configuration] in Siemens via software
1145 * Double click [protection] to enter protection configuration screen
1146
1147 (% style="text-align:center" %)
1148 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
1149
1150 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
1151
1152 (% style="text-align:center" %)
1153 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
1154
1155 DB settings
1156
1157 * Right click [DB], select [properties]
1158 * Uncheck [optimized block access]
1159
1160 **Cable Wiring**
1161
1162 (% style="text-align:center" %)
1163 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1164
1165 == **S7-XXX Ethernet Protocol** ==
1166
1167 Supported Series: Siemens S7-400, S7-1200 and S7-1500
1168
1169 **HMI Setting**
1170
1171 (% class="table-bordered" style="width:823px" %)
1172 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
1173 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
1174 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
1175 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
1176 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
1177 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
1178
1179 Slot from TIA Portal is equal to Device No. of PIStudio
1180
1181 Rack from TIA Portal is equal to HMI No. of PIStudio
1182
1183 (% style="text-align:center" %)
1184 [[image:S7-XXXCommunication Settings.png]]
1185
1186 (% style="text-align:center" %)
1187 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
1188
1189 **Address List**
1190
1191 (% class="table-bordered" %)
1192 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1193 |(% rowspan="4" %)Bit|I|I|M d.o|(((
1194 d:0~-~-9999
1195
1196 o:0-7
1197 )))|
1198 |Q|Q|Q d.o|(((
1199 d:0~-~-9999
1200
1201 o:0-7
1202 )))|
1203 |M|M|M d.o|(((
1204 d:0~-~-9999
1205
1206 o:0-7
1207 )))|
1208 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
1209 nn:0-9999,
1210
1211 dddd:0-9999,
1212
1213 o:0-7
1214 )))|(((
1215 nn:DB No.
1216
1217 dddd:address value
1218
1219 o: digit address
1220 )))
1221 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1222 |M|MW|MW d|d:0-99999|(((
1223 MW0=MB(0~~1)
1224
1225 MW2=MB(2~~3)
1226
1227 Address value is a multiple of 2
1228 )))
1229 |M|MD|MD d|d:0-99999|(((
1230 MD0=MB(0~~3)
1231
1232 MD4=MB(4~~7)
1233
1234 Address value is a multiple of 4
1235 )))
1236 |I|IW|IW d|d:0-99999|
1237 |Q|QW|QW d|d:0-99999|
1238 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1239 nn:0-9999
1240
1241 dddd:0-9999
1242 )))|(((
1243 nn:DB No.
1244
1245 dddd:address value
1246 )))
1247 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1248 nn:0-9999
1249
1250 dddd:0-9999
1251 )))|(((
1252 nn:DB No.
1253
1254 dddd:address value
1255
1256 Address value is a multiple of 2
1257 )))
1258 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1259 nn:0-9999
1260
1261 dddd:0-9999
1262 )))|(((
1263 nn:DB No.
1264
1265 dddd:address value
1266
1267 Address value is a multiple of 4
1268 )))
1269
1270 **Communication Settings**
1271
1272 Enable HMI Ethernet in [Project Settings];
1273
1274 (% style="text-align:center" %)
1275 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1276
1277 Set PLC IP in [Device IP] settings;
1278
1279 (% style="text-align:center" %)
1280 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1281
1282 **✎Note:**
1283
1284 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1285 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1286
1287 **Cable Wiring**
1288
1289 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1290
1291 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1292
1293 Supported Series: Siemens Logo 0BA0, 0BA1 series
1294
1295 **HMI Settings**
1296
1297 (% class="table-bordered" %)
1298 |**Items**|**Settings**|**Note**
1299 |Protocol|Siemens LOGO|
1300 |Connection|Ethernet|
1301 |Port No.|102|
1302 |PLC station No.|2|
1303
1304 **Address List**
1305
1306 (% class="table-bordered" %)
1307 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1308 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1309 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1310 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1311 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1312 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1313 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1314 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1315 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1316 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1317 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1318 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1319 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1320 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1321 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1322 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1323
1324 **PLC Settings in LOGO Software:**
1325
1326 Click [Tools]~-~-[Ethernet Connections],shown as below.
1327
1328 (% style="text-align:center" %)
1329 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1330
1331 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1332
1333 (% style="text-align:center" %)
1334 [[image:image-20221228142937-4.png]]
1335
1336 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1337
1338 (% style="text-align:center" %)
1339 [[image:image-20221228143047-5.png]]
1340
1341 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1342
1343 (% style="text-align:center" %)
1344 [[image:image-20221228143246-6.png]]
1345
1346
1347 **HMI Communication Settings**
1348
1349 Set PLC IP in [Device IP] settings;
1350
1351 (% style="text-align:center" %)
1352 [[image:image-20221228143614-7.png]]
1353
1354 Enable HMI Ethernet in [Project Settings];
1355
1356 (% style="text-align:center" %)
1357 [[image:image-20221228144229-9.png]]
1358
1359 TSAP setting
1360
1361 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1362 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
1363 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
1364 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
1365 ie, ig series: use HSW1200, HSW1201.
1366 HMI V2.0: use HSW1200, HSW1201.
1367
1368 **✎Note:**
1369
1370 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
1371 * HSW10119/HSW1201 is set up as shown.
1372 * (((
1373 (% style="text-align:center" %)
1374 [[image:image-20221228144800-11.png]]
1375 )))
1376 * (((
1377 (% style="text-align:center" %)
1378 [[image:image-20221228144708-10.png]]
1379 )))
1380
1381 * AI word address and Ibit address are read-only and cannot be written on HMI.
1382 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
1383 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
1384 * Written value of RTC cannot exceed 255.
1385
1386 **Cable Wiring**
1387
1388 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1389
1390 == S7-300 232 ==
1391
1392 **HMI Setting:**
1393
1394 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
1395 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
1396 |=**PLC I/F**|RS232| |
1397 |=**Baud rate**|19200|9600,19200|
1398 |=**Data bits**|8| |
1399 |=**Parity**|Odd| |
1400 |=**Stop bits**|1| |
1401 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
1402
1403 **Device Address**
1404
1405 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1406 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
1407 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
1408 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
1409 |=Word|(((
1410 DB1 to DB99
1411 )))|DDDDDo|0 ~~ 655327|
1412 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
1413 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
1414 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
1415 |=Double word|MD|DDDD|0 ~~ 4094|
1416 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
1417 Data Register Double Word (must be even)
1418 )))
1419 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
1420
1421 **Cable Wiring**
1422
1423 (% style="text-align:center" %)
1424 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
1425
1426 = Create communication with **Mitsubishi PLC** =
1427
1428 == **FX1S, 1N, 2N Series Protocol** ==
1429
1430 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1431
1432 **HMI Settings**
1433
1434 (% class="table-bordered" %)
1435 |**Item**|**Settings**|**Note**
1436 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1437 |Connection|RS422/RS485/RS232|
1438 |Baud rate|9600~~115200|
1439 |Data bit|7/8|
1440 |Parity|EVEN/Odd/None|
1441 |Stop bit|1/2|
1442 |PLC station No.|1~~255|
1443
1444 **Address List**
1445
1446 (% class="table-bordered" %)
1447 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1448 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1449 |Y|Y|Y o|0~~303237|
1450 |M|M|M d|0~~99999|
1451 |T|T|T d|0~~99999|
1452 |C|C|C d|0~~99999|
1453 |S|S|S d|0~~99999|
1454 |SM|SM|SM d|8000~~9999|
1455 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1456 |Y|Y|Y o|0~~303237|
1457 |M|M|M d|0~~99999|
1458 |T|T|T d|0~~99999|
1459 |C|C|C d|0~~199|
1460 |D|D|D d|0~~7999|
1461 |S|S|S d|0~~99999|
1462 |SD|SD|SD d|8000~~9999|
1463
1464 **Cable Wiring**
1465
1466 * **RS485**
1467
1468 (% style="text-align:center" %)
1469 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1470
1471 (% style="text-align:center" %)
1472 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1473
1474 * **RS422**
1475
1476 (% style="text-align:center" %)
1477 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1478
1479 **✎Note:** COM3 only available in PI8000/PI9000 series.
1480
1481 == **FX3U/3G/3GA serial protocol** ==
1482
1483 (% class="wikigeneratedid" %)
1484 **HMI Settings**
1485
1486 |=**Item**|=**Settings**|=**Note**
1487 |Protocol|Mitsubishi FX3U/3G/3GA|
1488 |Connection|RS422|
1489 |Baud rate|9600~~115200|
1490 |Data bit|7/8|
1491 |Parity|EVEN/Odd/None|
1492 |Stop bit|1/2|
1493 |PLC station No.|1~~255|
1494
1495 (% class="wikigeneratedid" %)
1496 **Address List**
1497
1498 |=(% scope="row" %)**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1499 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1500 |Y|Y|Y o|0~~303237|
1501 |M|M|M d|0~~99999|
1502 |T|T|T d|0~~99999|
1503 |C|C|C d|0~~99999|
1504 |S|S|S d|0~~99999|
1505 |SM|SM|SM d|8000~~9999|
1506 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1507 |Y|Y|Y o|0~~303237|
1508 |M|M|M d|0~~99999|
1509 |T|T|T d|0~~99999|
1510 |C|C|C d|0~~199|
1511 |D|D|D d|0~~7999|
1512 |S|S|S d|0~~99999|
1513 |SD|SD|SD d|8000~~9999|
1514
1515 **Configure the communication protocol**
1516
1517 (% style="text-align:center" %)
1518 [[image:image-20220831095222-1.png]]
1519
1520 (% style="text-align:center" %)
1521 [[image:image-20220831095743-2.png]]
1522
1523 **Wiring**
1524
1525 (% style="text-align:center" %)
1526 [[image:image-20220831100333-7.png]]
1527
1528 Pin Definition Diagram
1529
1530 (% style="text-align:center" %)
1531 [[image:image-20220831100314-6.png]]
1532
1533 == **FX3U Ethernet Protocol** ==
1534
1535 Mitsubishi FX3U series PLC
1536
1537 **HMI Settings**
1538
1539 |Items|Settings|Note
1540 |Protocol|Mitsubishi FX3U|
1541 |Connection|Ethernet|
1542 |Port No.|5009|Must be the same as the PLC setting
1543 |PLC station No.|0|
1544
1545 **Address List**
1546
1547 (% class="table-bordered" style="width:1041px" %)
1548 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|(% style="width:140px" %)**Note**
1549 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|(% style="width:140px" %)
1550 |Y|Y|Y OOO|0~~377|(% style="width:140px" %)
1551 |M|M|M DDDD|0~~7679|(% style="width:140px" %)
1552 |SM|SM|SM DDDD|8000~~8511|(% style="width:140px" %)
1553 |S|S|S DDDD|0~~4095|(% style="width:140px" %)
1554 |TS|TS|TS DDD|0~~511|(% style="width:140px" %)
1555 |CS|CS|CS DDD|0~~255|(% style="width:140px" %)
1556 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|(% style="width:140px" %)0~~199|(% style="width:30px" %)
1557 |TN|TN|TN DDD|(% style="width:140px" %)0~~511|(% style="width:30px" %)
1558 |D|D|D DDDD|(% style="width:140px" %)0~~7999|(% style="width:30px" %)
1559 |SD|SD|SD DDDD|(% style="width:140px" %)8000~~8511|(% style="width:30px" %)
1560 |R|R|R DDDDD|(% style="width:140px" %)0~~32767|(% style="width:30px" %)
1561
1562 **Ethernet Module Settings**
1563
1564 FX3U-ENET-L module configuration
1565 Set up the FX3U-ENET-L Ethernet module settings as follows.
1566 Select the module location, which in this document is Module 0.
1567
1568 [[image:image-20221115140802-1.png]]
1569
1570 Select "Operational setting" to enter the following screen.
1571
1572 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1573
1574 [[image:image-20221115142728-4.png]]
1575
1576 Select "Open setting" to enter the setting interface, the settings are as follows.
1577
1578 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1579
1580 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1581
1582 [[image:image-20221115142945-5.png]]
1583
1584 Click on "transter setup" - "PC side I/F setting", see the following figure.
1585
1586 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1587
1588 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1589
1590 [[image:image-20221115143341-6.png||height="426" width="712"]]
1591
1592 Read and write data from the Ethernet module
1593
1594 [[image:image-20221115143703-7.png]]
1595
1596 Set "Transter setup" to COM communication, and read or write operation as shown below
1597
1598 [[image:image-20221115143809-8.png]]
1599
1600 **PLC Settings (GX Works 2)**
1601
1602 Create a blank FX5U project
1603
1604 Find Current Connection in the navigation
1605
1606 [[image:image-20221115144335-9.png||height="422" width="706"]]
1607
1608 Select Connection Channel List
1609
1610 Select Ethernet board communication
1611
1612 [[image:image-20221115144824-10.png||height="421" width="705"]]
1613
1614 Select Ethernet Module
1615 Set the IP address of the PLC
1616
1617 [[image:image-20221115145228-11.png||height="674" width="708"]]
1618
1619 Read or write PLC data, in this document is read
1620
1621 [[image:image-20221115145553-12.png||height="424" width="711"]]
1622
1623 (% class="wikigeneratedid" id="H" %)
1624 [[image:image-20221115145559-13.png||height="424" width="711"]]
1625
1626 **HMI Communication Setting**
1627
1628 [[image:image-20221115150003-14.png||height="425" width="712"]]
1629
1630 [[image:image-20221115150235-15.png||height="427" width="713"]]
1631
1632 (% class="wikigeneratedid" id="H-1" %)
1633 [[image:image-20221115145559-13.png||height="424" width="711"]]
1634
1635 **HMI Communication Setting**
1636
1637 [[image:image-20221115150003-14.png||height="425" width="712"]]
1638
1639 [[image:image-20221115150235-15.png||height="427" width="713"]]
1640
1641 == **FX5U Serial Port Protocol** ==
1642
1643 Mitsubishi FX5U series PLC
1644
1645 **HMI Settings**
1646
1647 (% class="table-bordered" %)
1648 |**Item**|**Settings**|**Note**
1649 |Protocol|Mitsubishi FX5U|
1650 |Connection|RS422/RS485|
1651 |Baud rate|9600|
1652 |Data bit|7|
1653 |Parity|Odd|
1654 |Stop bit|1|
1655 |PLC station No.|1~~255|Need to be the same as PLC settings
1656
1657 **Address List**
1658
1659 (% class="table-bordered" %)
1660 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1661 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1662 |Y|Y|Y o|0~~303237|
1663 |M|M|M d|0~~99999|
1664 |B|B|B h|0~~7FFF|
1665 |F|F|F d|0~~32767|
1666 |SB|SB|SB h|0~~7FFF|
1667 |TS|TS|TS d|0~~1023|
1668 |TC|TC|TC d|0~~1023|
1669 |STS|STS|STS d|0~~1023|
1670 |STC|STC|STS d|0~~1023|
1671 |CS|CS|CS d|0~~1023|
1672 |CC|CC|CC d|0~~1023|
1673 |SM|SM|SM d|0~~9999|
1674 |L|L|L d|0~~32767|
1675 |S|S|S d|0~~4095|
1676 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1677 |TN|TN|TN d|0~~1023|
1678 |STN|STN|STN d|0~~1023|
1679 |CN|CN|CN d|0~~1023|
1680 |R|R|R d|0~~32767|
1681 |SW|SW|SW h|0~~7FFF|
1682 |Z|Z|Z d|0~~23|
1683 |D|D|D d|0~~7999|
1684 |SD|SD|SD d|0~~11999|
1685
1686 **PLC Settings (GX Works 3)**
1687
1688 Create a blank FX5U project
1689
1690 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1691
1692 (% style="text-align:center" %)
1693 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1694
1695 Select protocol in the setting item, and set parameters.
1696
1697 (% style="text-align:center" %)
1698 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1699
1700 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1701
1702 (% style="text-align:center" %)
1703 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1704
1705 Click the [Apply] button to finish the setting.
1706
1707 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1708
1709 (% style="text-align:center" %)
1710 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1711
1712 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1713
1714 Done.
1715
1716 **Cable Wiring**
1717
1718 * **RS485**
1719
1720 (% style="text-align:center" %)
1721 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1722
1723 (% style="text-align:center" %)
1724 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1725
1726 * **RS422**
1727
1728 (% style="text-align:center" %)
1729 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1730
1731 **✎Note:** COM3 only available in PI8000/PI9000 series.
1732
1733 == **L02 Serial Protocol** ==
1734
1735 Mitsubishi L02 series CPU built-in serial port.
1736
1737 **HMI Settings**
1738
1739 |=**Item**|=**Settings**|=**Note**
1740 |Protocol|Mitsubishi L02|
1741 |Connection|RS422|
1742 |Baud rate|115200|
1743 |Data bit|8|
1744 |Parity|Odd|
1745 |Stop bit|1|
1746 |PLC station No.|1~~255|Need to be the same as PLC settings
1747
1748 **Address List**
1749
1750 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1751 |Bit|X|X|X h|0~~FFFF|
1752 |Bit|Y|Y|Y h|0~~FFFF|
1753 |Bit|M|M|M d|0~~9999|
1754 |Bit|L|L|L d|0~~9999|
1755 |Bit|F|F|F d|0~~9999|
1756 |Bit|B|B|B h|0~~FFFF|
1757 |Bit|V|V|V d|0~~2047|
1758 |Bit|TC|TC|TC d|0~~9999|
1759 |Bit|SS|SS|SS d|0~~9999|
1760 |Bit|SC|SC|SC d|0~~9999|
1761 |Bit|CS|CS|CS d|0~~9999|
1762 |Bit|CC|CC|CC d|0~~9999|
1763 |Bit|SB|SB|SB h|0~~FFFF|
1764 |Bit|SM|SM|SM d|0~~2047|
1765 |Bit|STS|STS|STS d|0~~1023|
1766 |Bit|S|S|S d|0~~9999|
1767 |Bit|DX|DX|DX h|0~~FFFF|
1768 |Bit|DY|DY|DY h|0~~FFFF|
1769 |Bit|TS|TS|TS d|0~~9999|
1770 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1771 |Word|W|W|W h|0~~FFFF|
1772 |Word|TN|TN|TN d|0~~99999|
1773 |Word|SN|SN|SN d|0~~99999|
1774 |Word|CN|CN|CN d|0~~99999|
1775 |Word|R|R|R d|0~~99999|
1776 |Word|SW|SW|SW h|0~~FFFF|
1777 |Word|Z|Z|Z d|0~~99999|
1778 |Word|ZR|ZR|ZR h|0~~FFFF|
1779 |Word|D|D|D d|0~~99999|
1780
1781 **Communication Settings**
1782
1783 (% style="text-align:center" %)
1784 [[image:image-20220831105732-3.png]]
1785
1786 (% style="text-align:center" %)
1787 [[image:image-20220831110004-5.png]]
1788
1789 **Cable Wiring**
1790
1791 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1792
1793 Pin Definition Diagram
1794
1795 (% style="text-align:center" %)
1796 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1797
1798 == **L02 MELSEC (Ethernet) Protocol** ==
1799
1800 Mitsubishi Q series CPU built-in Ethernet port.
1801
1802 **HMI Settings**
1803
1804 (% class="table-bordered" %)
1805 |**Items**|**Settings**|**Note**
1806 |Protocol|MIT L02 CPU MELSEC|
1807 |Connection|Ethernet|
1808 |Port No.|1025|Must be the same as the PLC setting
1809 |PLC station No.|0|Must be the same as the PLC setting
1810
1811 **Address List**
1812
1813 (% class="table-bordered" %)
1814 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1815 |Bit|X|X|X h|0~~FFFF|
1816 |Bit|Y|Y|Y h|0~~FFFF|
1817 |Bit|M|M|M d|0~~9999|
1818 |Bit|L|L|L d|0~~9999|
1819 |Bit|F|F|F d|0~~9999|
1820 |Bit|B|B|B h|0~~FFFF|
1821 |Bit|V|V|V d|0~~2047|
1822 |Bit|TC|TC|TC d|0~~9999|
1823 |Bit|SS|SS|SS d|0~~9999|
1824 |Bit|SC|SC|SC d|0~~9999|
1825 |Bit|CS|CS|CS d|0~~9999|
1826 |Bit|CC|CC|CC d|0~~9999|
1827 |Bit|SB|SB|SB h|0~~FFFF|
1828 |Bit|SM|SM|SM d|0~~2047|
1829 |Bit|STS|STS|STS d|0~~1023|
1830 |Bit|S|S|S d|0~~9999|
1831 |Bit|DX|DX|DX h|0~~FFFF|
1832 |Bit|DY|DY|DY h|0~~FFFF|
1833 |Bit|TS|TS|TS d|0~~9999|
1834 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1835 |Word|W|W|W h|0~~FFFF|
1836 |Word|TN|TN|TN d|0~~99999|
1837 |Word|SN|SN|SN d|0~~99999|
1838 |Word|CN|CN|CN d|0~~99999|
1839 |Word|R|R|R d|0~~99999|
1840 |Word|SW|SW|SW h|0~~FFFF|
1841 |Word|Z|Z|Z d|0~~99999|
1842 |Word|ZR|ZR|ZR h|0~~FFFF|
1843 |Word|D|D|D d|0~~99999|
1844
1845 **Communication Settings**
1846
1847 Enable HMI Ethernet in [Project Settings];
1848
1849 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1850
1851 Set PLC IP in [Device IP] settings;
1852
1853 (% style="text-align:center" %)
1854 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1855
1856 **PLC Settings (GX Works2 )**
1857
1858 Create a project
1859
1860 Set PLC IP, subnet mask and gateway;
1861
1862 Select [Binary Code] as communication data code;
1863
1864 (% style="text-align:center" %)
1865 [[image:image-20221108202109-2.png||height="636" width="732"]]
1866
1867 Set PLC port number, for example 1025
1868
1869 (% style="text-align:center" %)
1870 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1871
1872 Save settings;
1873
1874 Download project into PLC device;
1875
1876 Restart PLC device;
1877
1878 **Cable Wiring**
1879
1880 (% style="text-align:center" %)
1881 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1882
1883 == **QJ71C24N MELSEC Protocol** ==
1884
1885 Mitsubishi QJ71C24N communication module built-in serial port;
1886
1887 **HMI Settings**
1888
1889 (% class="table-bordered" %)
1890 |**Items**|**Settings**|**Note**
1891 |Protocol|MIT QJ71 MELSEC|
1892 |Connection|422|
1893 |Baud rate|9600|
1894 |Data bit|8|
1895 |Parity|ODD|
1896 |Stop bit|1|
1897 |PLC station No.|1~~255|Need to be the same as PLC settings
1898
1899 **Address List**
1900
1901 (% class="table-bordered" %)
1902 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1903 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1904 |Y|Y|Y FFFF|0~~1FFF|
1905 |M|M|M DDDDD|0~~99999|
1906 |L|L|L DDDD|0~~8191|
1907 |F|F|F DDDD|0~~2047|
1908 |V|V|V DDDD|0~~2047|
1909 |B|B|B FFFF|0~~1FFF|
1910 |TS|TS|TS DDDD|0~~2047|
1911 |TC|TC|TC DDDD|0~~2047|
1912 |SS|SS|SS DDDD|0~~2047|
1913 |SC|SC|SC DDDD|0~~2047|
1914 |CS|CS|CS DDDD|0~~1023|
1915 |CC|CC|CC DDDD|0~~1023|
1916 |SB|SB|SB FFF|0~~7FF|
1917 |S|S|S D|0~~8191|
1918 |DX|DX|DX FFFF|0~~1FFF|
1919 |DY|DY|DY FFFF|0~~1FFF|
1920 |SM_|SM_|SM_ DDDD|8000~~9999|
1921 |SM|SM|SM DDDD|0~~2047|
1922 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1923 |D|D|D DDDDD|0~~12287|
1924 |W|W|W FFFF|0~~1FFF|
1925 |TN|TN|TN DDDD|0~~2047|
1926 |SN|SN|SN DDDD|0~~2047|
1927 |CN|CN|CN DDDD|0~~1023|
1928 |R|R|R DDDDD|0~~32767|
1929 |SW|SW|SW FFF|0~~7FF|
1930 |Z|Z|Z D|0~~15|
1931 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1932
1933 **Communication Settings**
1934
1935 (% style="text-align:center" %)
1936 [[image:image-20221109135738-1.png]]
1937
1938 (% style="text-align:center" %)
1939 [[image:image-20221109140016-3.png]]
1940
1941 (% class="wikigeneratedid" id="H" %)
1942 Pin Definition Diagram
1943
1944 (% style="text-align:center" %)
1945 [[image:image-20221109140406-4.png]]
1946
1947 == **QJ71E71 MELSEC Protocol** ==
1948
1949 Mitsubishi QJ71E71 Ethernet communication module;
1950
1951 **HMI Settings**
1952
1953 (% class="table-bordered" %)
1954 |**Items**|**Settings**|**Note**
1955 |Protocol|MIT QJ71E71 MELSEC|
1956 |Connection|Ethernet|
1957 |Port No.|1025|Must be the same as the PLC setting
1958 |PLC station No.|0|Must be the same as the PLC setting
1959
1960 **Address List**
1961
1962 (% class="table-bordered" %)
1963 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1964 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1965 |Y|Y|Y h|0~~1FFF|
1966 |M|M|M d|0~~99999|
1967 |L|L|L d|0~~8191|
1968 |F|F|F d|0~~2047|
1969 |B|B|B h|0~~1FFF|
1970 |V|V|V d|0~~2047|
1971 |TS|TS|TS d|0~~2047|
1972 |TC|TC|TC d|0~~2047|
1973 |SS|SS|SS d|0~~2047|
1974 |SC|SC|SC d|0~~2047|
1975 |CS|CS|CS d|0~~1023|
1976 |CC|CC|CC d|0~~1023|
1977 |SB|SB|SB h|0~~7FF|
1978 |S|S|S d|0~~8191|
1979 |DX|DX|DX h|0~~1FFF|
1980 |DY|DY|DY h|0~~1FFF|
1981 |SM|SM|SM d|8000~~9999|
1982 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1983 |D|D|D d|0~~12287|
1984 |W|W|W h|0~~1FFF|
1985 |TN|TN|TN d|0~~2047|
1986 |SN|SN|SN d|0~~2047|
1987 |CN|CN|CN d|0~~1023|
1988 |R|R|R d|0~~32767|
1989 |SW|SW|SW h|0~~7FF|
1990 |Z|Z|Z d|0~~15|
1991 |ZR|ZR|ZR h|0~~FE7FF|
1992
1993 **HMI Communication Settings**
1994
1995 1) Enable HMI Ethernet in [Project Settings];
1996
1997 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1998
1999 2) Set PLC IP in [Device IP] settings
2000
2001 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
2002
2003 **PLC Settings(GX Works2)**
2004
2005 * Click [Ethernet/CC IE/MELSECNET];
2006 * Please select [Ethernet] as network type;
2007 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
2008 * Select [Online] as Mode;
2009 * [[image:image-20221119164958-2.png||height="356" width="611"]](% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
2010 * Click [Operation setting] to set IP;
2011 * Select [Binary Code] as [Communication Data Code];
2012 * [[image:image-20221119165129-3.png||height="381" width="611"]](% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
2013 * Click [Open setting]
2014 * Set protocol: TCP;
2015 * Set [unpassive] in [Open system];
2016 * Set [receive] in [Fixed buffer];
2017 * Set [procedure Exist] in [Fixed buffer communication];
2018 * Disable [Pairing open];
2019 * Set [No confirm] in [Existence confirmation];
2020 * Host station port number: 5009;
2021 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
2022 * [[image:image-20221119165342-4.png||height="387" width="620"]]
2023 * Download project into PLC and restart it
2024
2025 **Cable Wiring**
2026
2027 (% style="text-align:center" %)
2028 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2029
2030 = Create communication with **Delta PLC** =
2031
2032 == DVP serial protocol ==
2033
2034 (% class="wikigeneratedid" %)
2035 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
2036
2037 **HMI Settings**
2038
2039 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
2040 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
2041 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
2042 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
2043 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
2044 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
2045 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
2046 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
2047
2048 **Address List**
2049
2050 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2051 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
2052 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
2053 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
2054 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
2055 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
2056 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
2057 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
2058 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
2059 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
2060
2061 (% class="wikigeneratedid" %)
2062 **Configure the communication protocol**
2063
2064 (% style="text-align:center" %)
2065 [[image:image-20220829152327-6.png]]
2066
2067 (% style="text-align:center" %)
2068 [[image:image-20220829152016-3.png]]
2069
2070 (% class="wikigeneratedid" %)
2071 **Cable Wiring**
2072
2073 (% class="wikigeneratedid" id="H" %)
2074 [[image:image-20220829152610-7.png]]
2075
2076 (% style="text-align:center" %)
2077 [[image:image-20220829152102-5.png]]
2078
2079 == DVP Ethernet Protocol ==
2080
2081 (% class="wikigeneratedid" %)
2082 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
2083
2084 **HMI Settings**
2085
2086 |=**Items**|=**Settings**|=**Note**
2087 |Protocol|DELTA DVP Modbus TCP|
2088 |Connection|Ethernet|
2089 |Port No.|201|Must be the same as the PLC setting
2090 |PLC station No.|0|Must be the same as the PLC setting
2091
2092 **Address List**
2093
2094 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2095 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
2096 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
2097 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
2098 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
2099 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
2100 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
2101 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
2102 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
2103 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
2104
2105 )))
2106 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
2107 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
2108
2109 )))
2110
2111 (% class="wikigeneratedid" %)
2112 **Configure the communication protocol**
2113
2114 (% style="text-align:center" %)
2115 [[image:image-20220829155452-1.png]]
2116
2117 [[image:image-20220829162116-2.png]]
2118
2119 **Cable Wiring**
2120
2121 (% style="text-align:center" %)
2122 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2123
2124 == **AS serial protocol** ==
2125
2126 Supported Series: Delta AS200/AS300
2127
2128 **HMI Settings**
2129
2130 |**Item**|**Settings**|**Note**
2131 |Protocol|DELTA AS300 MODBUS RTU|
2132 |Connection|RS485|
2133 |Baud rate|9600|
2134 |Data bit|8|
2135 |Parity|NONE|
2136 |Stop bit|1|
2137 |PLC station No.|1|
2138
2139 **Address List**
2140
2141 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2142 |Bit|X|X|Xdd.dd|0~~63.15|Read only
2143 |Bit|Y|Y|Ydd.dd|0~~63.15|
2144 |Bit|D|D|Dddddd|0~~29999|
2145 |Bit|M|M|Mdddd|0~~8191|
2146 |Bit|SM|SM|SMdddd|0~~4095|
2147 |Bit|S|S|Sdddd|0~~2047|
2148 |Bit|T|T|Tddd|0~~511|
2149 |Bit|C|C|Cddd|0~~511|
2150 |Bit|HC|HC|HCddd|0~~255|Double Word
2151 |Word|X|X|Xdd|0~~63|
2152 |Word|Y|Y|(((
2153 Ydd
2154 )))|0~~63|
2155 |Word|SR|SR|SRdddd|0~~2047|Special register
2156 |Word|D|D|Dddddd|0~~29999|
2157 |Word|T|T|Tddd|0~~511|
2158 |Word|C|C|Cddd|0~~511|
2159 |Word|E|E|Ed|0~~9|
2160
2161 **Configure the communication protocol**
2162
2163 Create project
2164
2165 (% style="text-align:center" %)
2166 [[image:AsCreateProject.png]]
2167
2168 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
2169
2170 (% style="text-align:center" %)
2171 [[image:AScommunicarw.png]]
2172
2173 Double click the HWCONFIG to open the communication settings window.
2174
2175 (% style="text-align:center" %)
2176 [[image:ASHWCONFIG.png]]
2177
2178 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
2179
2180 (% style="text-align:center" %)
2181 [[image:ASHSCONFIGICON.png]]
2182
2183 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
2184
2185 (% style="text-align:center" %)
2186 [[image:ASModbusMode.png]]
2187
2188 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
2189
2190 (% style="text-align:center" %)
2191 [[image:ASconfigIP.png]]
2192
2193 (% style="text-align:center" %)
2194 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
2195
2196
2197 (% style="text-align:center" %)
2198 [[image:image-20220830094657-2.png]]
2199
2200 **Cable Wiring**
2201
2202 (% style="text-align:center" %)
2203 [[image:image-20220830141138-1.png]]
2204
2205 Pin Definition Diagram
2206
2207 (% style="text-align:center" %)
2208 [[image:image-20220830095131-1.png]]
2209
2210 == AS Ethernet Protocol ==
2211
2212 **HMI Settings**
2213
2214 |=**Items**|=**Settings**|=**Note**
2215 |Protocol|DELTA AS300 MODBUS TCP|
2216 |Connection|Ethernet|
2217 |Port No.|502|
2218 |Device No.|1|
2219 |HMI No.|0|
2220
2221 **Address List**
2222
2223 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2224 |Bit|X|X|X d|0~~63|
2225 |Bit|Y|Y|Y d|0~~63|
2226 |Bit|D|D|D d|0~~29999|
2227 |Bit|M|M|M d|0~~8191|
2228 |Bit|SM|SM|SM d|0~~4095|
2229 |Bit|S|S|S h|0~~2047|
2230 |Bit|T|T|T d|0~~511|
2231 |Bit|C|C|C d|0~~511|
2232 |Bit|HC|HC|HC d|0~~255|
2233 |Word|X|X|X h|0~~63|
2234 |Word|Y|Y|Y d|0~~63|
2235 |Word|SR|SR|SR d|0~~2047|
2236 |Word|D|D|D d|0~~29999|
2237 |Word|T|T|T d|0~~511|
2238 |Word|C|C|C h|0~~511|
2239 |Word|E|E|E d|0~~9|
2240
2241 **Configure the communication protocol**
2242
2243 (% style="text-align:center" %)
2244 [[image:image-20220830140537-1.png]]
2245
2246 (% style="text-align:center" %)
2247 [[image:image-20220830140629-2.png]]
2248
2249 **Cable Wiring**
2250
2251 [[image:image-20220830094929-1.png]]
2252
2253 Pin Definition Diagram
2254
2255 (% style="text-align:center" %)
2256 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2257
2258 = Create communication with **Omron** PLC =
2259
2260 == CJ TCP FINS Ethemet  Protocol ==
2261
2262 Supported device:CJ series、CJ1W-EIP21
2263
2264 **HMI Settings**
2265
2266 |=**Items**|=**Settings**|=**Note**
2267 |Protocol|OMRON CJ TCP FINS Ethemet|
2268 |Connection|Ethernet|
2269 |Port No.|9600|
2270 |Device No.|0|
2271 |HMI No.|0|(((
2272
2273 )))
2274
2275 **Address List**
2276
2277 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2278 |Bit|CIO|CIO|CIO d|0~~99999|
2279 |Bit|W|W|W d|0~~99999|
2280 |Bit|D|D|D d|0~~99999|
2281 |Bit|H|H|H d|0~~99999|
2282 |Bit|A|A|A d|0~~99999|
2283 |Bit|T|T|T h|0~~99999|
2284 |Bit|CF|CF|CF d|0~~99999|
2285 |Bit|FF|FF|FF d|0~~99999|
2286 |Bit|C|C|C d|0~~99999|
2287 |Bit|EM0|EM0|EM0 d|0~~99999|
2288 |Bit|EM1|EM1|EM1 d|0~~99999|
2289 |Bit|EM2|EM2|EM2 d|0~~99999|
2290 |Bit|EM3|EM3|EM3 d|0~~99999|
2291 |Bit|EM4|EM4|EM4 d|0~~99999|
2292 |Bit|EM5|EM5|EM5 h|0~~99999|
2293 |Bit|EM6|EM6|EM6 d|0~~99999|
2294 |Bit|EM7|EM7|EM7 d|0~~99999|
2295 |Bit|EM8|EM8|EM8 d|0~~99999|
2296 |Bit|EM9|EM9|EM9 d|0~~99999|
2297 |Bit|EMA|EMA|EMA d|0~~99999|
2298 |Bit|EMB|EMB|EMB d|0~~99999|
2299 |Bit|EMC|EMC|EMC d|0~~99999|
2300 |Bit|Lamp|Lamp|Lamp d|0~~0|
2301 |Word|CIO|CIO|CIO d|0~~99999|
2302 |Word|W|W|W d|0~~99999|
2303 |Word|D|D|D d|0~~99999|
2304 |Word|H|H|H d|0~~99999|
2305 |Word|A|A|A d|0~~99999|
2306 |Word|T|T|T h|0~~99999|
2307 |Word|CF|CF|CF d|0~~99999|
2308 |Word|FF|FF|FF d|0~~99999|
2309 |Word|C|C|C d|0~~99999|
2310 |Word|EM0|EM0|EM0 d|0~~99999|
2311 |Word|EM1|EM1|EM1 d|0~~99999|
2312 |Word|EM2|EM2|EM2 d|0~~99999|
2313 |Word|EM3|EM3|EM3 d|0~~99999|
2314 |Word|EM4|EM4|EM4 d|0~~99999|
2315 |Word|EM5|EM5|EM5 h|0~~99999|
2316 |Word|EM6|EM6|EM6 d|0~~99999|
2317 |Word|EM7|EM7|EM7 d|0~~99999|
2318 |Word|EM8|EM8|EM8 d|0~~99999|
2319 |Word|EM9|EM9|EM9 d|0~~99999|
2320 |Word|EMA|EMA|EMA d|0~~99999|
2321 |Word|EMB|EMB|EMB d|0~~99999|
2322 |Word|EMC|EMC|EMC d|0~~99999|
2323 |Word|IR|IR|IR d|0~~99999|
2324 |Word|DR|DR|DR d|0~~99999|
2325
2326 **Configure the communication protocol**
2327
2328 (% style="text-align:center" %)
2329 [[image:image-20220830143348-1.png]]
2330
2331 (% style="text-align:center" %)
2332 [[image:image-20220830143511-2.png]]
2333
2334 **Configure CJ1W-EIP21 connect with HMI**
2335
2336 (% style="text-align:center" %)
2337 [[image:ftEVGvAprh.png]]
2338
2339 Select TCP_Client_2N
2340
2341 (% style="text-align:center" %)
2342 [[image:RURXWcgyCd.png]]
2343
2344 **Cable Wiring**
2345
2346 Pin Definition Diagram
2347
2348 (% style="text-align:center" %)
2349 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2350
2351 == **CP1E/CP1H serial protocol** ==
2352
2353 Supported device: OMRON CS1(CP1E/CP1H)
2354
2355 **HMI Settings**
2356
2357 |=**Items**|=**Settings**|=**Note**
2358 |Protocol|OMRON CS1(CP1E/CP1H)|
2359 |Connection|RS232 (9600, 2, 7, EVEN)|
2360 |Port No.|None|
2361 |PLC station No.|0|
2362
2363 **Address List**
2364
2365 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2366 |Bit|CIO|CIO|CIO d|0~~99999|
2367 |Bit|W|W|W d|0~~99999|
2368 |Bit|D|D|D d|0~~99999|
2369 |Bit|H|H|H d|0~~99999|
2370 |Bit|A|A|A d|0~~99999|
2371 |Bit|TF|T|T h|0~~99999|
2372 |Bit|CF|CF|CF d|0~~99999|
2373 |Bit|T|FF|FF d|0~~99999|
2374 |Bit|C|C|C d|0~~99999|
2375 |Bit|EM0|EM0|EM0 d|0~~99999|
2376 |Bit|EM1|EM1|EM1 d|0~~99999|
2377 |Bit|EM2|EM2|EM2 d|0~~99999|
2378 |Bit|EM3|EM3|EM3 d|0~~99999|
2379 |Bit|EM4|EM4|EM4 d|0~~99999|
2380 |Bit|EM5|EM5|EM5 h|0~~99999|
2381 |Bit|EM6|EM6|EM6 d|0~~99999|
2382 |Bit|EM7|EM7|EM7 d|0~~99999|
2383 |Bit|EM8|EM8|EM8 d|0~~99999|
2384 |Bit|EM9|EM9|EM9 d|0~~99999|
2385 |Bit|EMA|EMA|EMA d|0~~99999|
2386 |Bit|EMB|EMB|EMB d|0~~99999|
2387 |Bit|EMC|EMC|EMC d|0~~99999|
2388 |Word|CIO|CIO|CIO d|0~~99999|
2389 |Word|W|W|W d|0~~99999|
2390 |Word|D|D|D d|0~~99999|
2391 |Word|H|H|H d|0~~99999|
2392 |Word|A|A|A d|0~~99999|
2393 |Word|T|T|T h|0~~99999|
2394 |Word|CIO|CF|CF d|0~~99999|
2395 |Word|C|C|C d|0~~99999|
2396 |Word|EM0|EM0|EM0 d|0~~99999|
2397 |Word|EM1|EM1|EM1 d|0~~99999|
2398 |Word|EM2|EM2|EM2 d|0~~99999|
2399 |Word|EM3|EM3|EM3 d|0~~99999|
2400 |Word|EM4|EM4|EM4 d|0~~99999|
2401 |Word|EM5|EM5|EM5 h|0~~99999|
2402 |Word|EM6|EM6|EM6 d|0~~99999|
2403 |Word|EM7|EM7|EM7 d|0~~99999|
2404 |Word|EM8|EM8|EM8 d|0~~99999|
2405 |Word|EM9|EM9|EM9 d|0~~99999|
2406 |Word|EMA|EMA|EMA d|0~~99999|
2407 |Word|EMB|EMB|EMB d|0~~99999|
2408 |Word|EMC|EMC|EMC d|0~~99999|
2409 |Word|IR|IR|IR d|0~~99999|
2410 |Word|DR|DR|DR d|0~~99999|
2411
2412 **Configure the communication protocol**
2413
2414 (% style="text-align:center" %)
2415 [[image:image-20220902153118-1.png]]
2416
2417 (% style="text-align:center" %)
2418 [[image:image-20220902151322-2.png]]
2419
2420 **Cable Wiring**
2421
2422 (% style="text-align:center" %)
2423 [[image:image-20220902153949-2.png]]
2424
2425 Pin Definition Diagram
2426
2427 (% style="text-align:center" %)
2428 [[image:image-20220902154056-3.png]]
2429
2430 == **EC55 Protocol** ==
2431
2432 Supported device: EC55 temperature instrument
2433
2434 **1)HMI Settings**
2435
2436 |**Items**|**Settings**|**Note**
2437 |Protocol|Omron EC55|
2438 |Connection|RS485 (9600, 2, 7, EVEN)|
2439 |Port No.|None|
2440 |PLC station No.|0|
2441
2442 **2)Address List**
2443
2444 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2445 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2446 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2447 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2448 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2449 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2450 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2451 |CP|-|0-6|Read controller intrinsic property
2452 |CS|-|0-2|Read controller states
2453 |CA|-|0-17|Action command
2454
2455 **3)Device Settings**
2456
2457 Omron E5CC PLC configuration
2458
2459 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2460
2461 (% style="text-align:center" %)
2462 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2463
2464 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2465
2466 (% style="text-align:center" %)
2467 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2468
2469 **✎Note:** The communication settings for HMI should be consistent with this setting.
2470
2471 **Cable Wiring**
2472
2473 (% style="text-align:center" %)
2474 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2475
2476 (% style="text-align:center" %)
2477 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2478
2479 **✎Note:**
2480
2481 * COM3 only available in PI8000/PI9000 series.
2482 * CA address could not support continuous writing function;
2483 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2484 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2485 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2486 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2487 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2488 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2489 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2490
2491 == **EtherNet/IP NX series Protocol** ==
2492
2493 Supported series: Omron NX/NJ series
2494
2495 **HMI Setting**
2496
2497 |**Items**|**Settings**|**Note**
2498 |Protocol|Omron NX Ethernet/IP|
2499 |Connection|Ethernet|
2500 |Port No.|44818|
2501 |PLC station No.|1|
2502
2503 **Instruction**
2504
2505 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2506
2507 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2508
2509 (% style="text-align:center" %)
2510 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2511
2512 **Export labels from Sysmac Studio**
2513
2514 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2515
2516 (% style="text-align:center" %)
2517 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2518
2519 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2520
2521 Click [Label manage];
2522
2523 (% style="text-align:center" %)
2524 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2525
2526 Click [Import labels] and then select the file exported in step 1;
2527
2528 (% style="text-align:center" %)
2529 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2530
2531 The Import Status field shows the result, click [OK] to finish importing address labels;
2532
2533 (% style="text-align:center" %)
2534 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2535
2536 **Communication Settings**
2537
2538 Enable HMI Ethernet in [Project Settings];
2539
2540 (% style="text-align:center" %)
2541 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2542
2543 Set PLC IP in [Device IP] settings;
2544
2545 (% style="text-align:center" %)
2546 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2547
2548 (% style="text-align:center" %)
2549 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2550
2551 **Cable Wiring**
2552
2553 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2554
2555 == CV/CJ1M/CS1H ==
2556
2557 **HMI Setting:**
2558
2559 |=(% scope="row" %)**Parameters**|=**Recommended**
2560 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2561 |=**PLC I/F**|RS232
2562 |=**Baud rate**|9600
2563 |=**Data bits**|7
2564 |=**Parity**|Even
2565 |=**Stop bits**|2
2566 |=**PLC sta. no.**|0
2567
2568 **PLC Setting:**
2569
2570 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2571
2572 **Device Address:**
2573
2574 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2575 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2576 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2577 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2578 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2579 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2580 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2581 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2582 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2583 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2584 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2585 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2586 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2587 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2588 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2589 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2590 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2591 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2592 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2593 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2594 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2595 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2596 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2597 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2598
2599 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2600 |=W|LR_W|DDDD|0 ~~ 4095|
2601 |=W|TC|DDD|0 ~~ 511|
2602 |=W|DM|DDDD|0 ~~ 9999|Data Register
2603
2604 **Wiring Diagram:**
2605
2606 **RS-232**
2607
2608 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2609
2610 Communication Module:
2611
2612 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2613
2614 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2615
2616 (% style="text-align:center" %)
2617 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2618
2619 = Create communication with Xinje** PLC** =
2620
2621 == XC serial protocol ==
2622
2623 **HMI Settings**
2624
2625 |**Item**|**Settings**|**Note**
2626 |Protocol|XINJE XC MODBUS|
2627 |Connection|RS232|
2628 |Baud rate|19200|
2629 |Data bit|8|
2630 |Parity|EVEN|
2631 |Stop bit|1|
2632 |PLC station No.|1|
2633
2634 **Address List**
2635
2636 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2637 |Bit|M|M|M d|0~~8511|
2638 |Bit|X|X|X o|0~~1747|
2639 |Bit|Y|Y|Y o|0~~1747|
2640 |Bit|S|S|S d|0~~1023|
2641 |Bit|T|T|T d|0~~4095|
2642 |Bit|C|C|C d|0~~634|
2643 |Word|D|D|D d|0~~8511|
2644 |Word|TD|TD|TD d|0~~618|
2645 |Word|CD|CD|CD d|0~~634|
2646 |Word|FD|FD|FD d|0~~8511|
2647
2648 **Configure the communication protocol**
2649
2650 (% style="text-align:center" %)
2651 [[image:image-20220830154105-1.png]]
2652
2653 (% style="text-align:center" %)
2654 [[image:image-20220830154159-3.png]]
2655
2656 **Cable Wiring**
2657
2658 Figure
2659
2660 [[image:image-20220830155728-4.png]]
2661
2662 Pin Definition Diagram
2663
2664 (% style="text-align:center" %)
2665 [[image:image-20220830154131-2.png]]
2666
2667 == XD serial protocol ==
2668
2669 **HMI Settings**
2670
2671 Supported Series: Xinjie XD/XE Series PLC
2672
2673 |=**Item**|=**Settings**|=**Note**
2674 |Protocol|XINJE XD/XC MODBUS|
2675 |Connection|RS232|
2676 |Baud rate|19200|
2677 |Data bit|8|
2678 |Parity|EVEN|
2679 |Stop bit|1|
2680 |PLC station No.|1|
2681
2682 **Address List**
2683
2684 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2685 |Bit|M|M|M d|0~~74999|
2686 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2687 |Bit|X2xx|X2xx|X2xx o|0~~277|
2688 |Bit|X|X|X o|0~~77|
2689 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2690 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2691 |Bit|Y|Y|Y o|0~~4095|
2692 |Bit|SM|SM|SM d|0~~4999|(((
2693
2694 )))
2695 |Bit|T|T|T d|0~~4999|
2696 |Bit|C|C|C d|0~~4999|
2697 |Bit|ET|ET|ET d|0~~31|
2698 |Bit|SE|SE|SE d|0~~31|
2699 |Bit|HM|HM|HM d|0~~11999|
2700 |Bit|HSC|HSC|HSC d|0~~39|
2701 |Bit|HS|HS|HS d|0~~999|
2702 |Bit|HT|HT|HT d|0~~1999|
2703 |Bit|HC|HC|HC d|0~~1999|
2704 |Bit|S|S|S d|0~~7999|
2705 |Word|D|D|D d|0~~69999|
2706 |Word|ID|ID|ID d|0~~99|
2707 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2708 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2709 |Word|QD|QD|QD d|0~~99|
2710 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2711 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2712 |Word|SD|SD|SD d|0~~4999|
2713 |Word|TD|TD|TD d|0~~575|
2714 |Word|CD|CD|CD d|0~~575|
2715 |Word|ETD|ETD|ETD d|0~~31|
2716 |Word|HD|HD|HD d|0~~24999|
2717 |Word|HSD|HSD|HSD d|0~~1023|
2718 |Word|HTD|HTD|HTD d|0~~95|
2719 |Word|HCD|HCD|HCD d|0~~95|
2720 |Word|HSCD|HSCD|HSCD d|0~~31|
2721 |Word|FD|FD|FD d|0~~8191|
2722 |Word|SFD|SFD|SFD d|0~~5999|
2723 |Word|FS|FS|FS d|0~~47|
2724
2725 **Configure the communication protocol**
2726
2727 (% style="text-align:center" %)
2728 [[image:image-20220830160042-1.png]]
2729
2730 (% style="text-align:center" %)
2731 [[image:image-20220830160129-2.png]]
2732
2733 **Cable Wiring**
2734
2735 (% style="text-align:center" %)
2736 [[image:image-20220905093902-1.png]]
2737
2738 Pin Definition Diagram
2739
2740 (% style="text-align:center" %)
2741 [[image:image-20220830160232-3.png]]
2742
2743 = Create communication with Inovance** PLC** =
2744
2745 == H3U serial protocol ==
2746
2747 **HMI Settings**
2748
2749 |=**Item**|=**Settings**|=**Note**
2750 |Protocol|INOVANCE H3U PLC|
2751 |Connection|RS422|
2752 |Baud rate|9600|
2753 |Data bit|7|
2754 |Parity|EVEN|
2755 |Stop bit|1|
2756 |PLC station No.|0|
2757
2758 **Address List**
2759
2760 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2761 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X|X o|0~~303237|
2762 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2763 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M|M d|0~~99999|
2764 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T|T d|0~~99999|
2765 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C|C d|0~~99999|
2766 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM|SM d|8000~~999|
2767 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|T|S d|0~~99999|
2768 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp|Lamp d|0~~0|
2769 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X|X o|0~~303237|
2770 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y|Y o|0~~303237|
2771 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M|M d|0~~99999|
2772 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T|T d|0~~99999|
2773 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C|C d|0~~199|
2774 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D|D d|0~~7999|
2775 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S|S d|0~~99999|
2776 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD|SD d|8000~~9999|
2777 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R|R d|0~~32767|
2778
2779 **Configure the communication protocol**
2780
2781 (% style="text-align:center" %)
2782 [[image:image-20220830170114-4.png]]
2783
2784 [[image:image-20220830170017-3.png]]
2785
2786 **Cable Wiring**
2787
2788 (% style="text-align:center" %)
2789 [[image:image-20220830165930-1.png]]
2790
2791 Pin Definition Diagram
2792
2793 (% style="text-align:center" %)
2794 [[image:image-20220830165947-2.png]]
2795
2796 = Create communication with Panasonic** PLC** =
2797
2798 == **FP serial protocol** ==
2799
2800 **1)HMI Settings**
2801
2802 |**Item**|**Settings**|**Note**
2803 |Protocol|Panasonic FP MFWTOCOL|
2804 |Connection|RS232|
2805 |Baud rate|9600|
2806 |Data bit|8|
2807 |Parity|ODD|
2808 |Stop bit|1|
2809 |PLC station No.|1|
2810
2811 **2)Address List**
2812
2813 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2814 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2815 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2816 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2817 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2818 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2819 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2820 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2821 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2822 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2823 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2824 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2825 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2826 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2827 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2828 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2829
2830 **3)Configure the communication protocol**
2831
2832 [[image:image-20220830171050-1.png]]
2833
2834 [[image:image-20220830171126-2.png]]
2835
2836 **4)Cable Wiring**
2837
2838 Figure
2839
2840 [[image:image-20220830171328-4.png]]
2841
2842 Pin Definition Diagram
2843
2844 [[image:image-20220830171146-3.png]]
2845
2846 = Create communication with LS** PLC** =
2847
2848 == **XGB serial protocol ** ==
2849
2850 **HMI Settings**
2851
2852
2853 |=**Item**|=**Settings**|=**Note**
2854 |Protocol|LS XGB CPU DRIECT|
2855 |Connection|RS232|
2856 |Baud rate|115200|
2857 |Data bit|8|
2858 |Parity|NONE|
2859 |Stop bit|1|
2860 |PLC station No.|1|
2861
2862 **Address List**
2863
2864
2865 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2866 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2867 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2868 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2869 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2870 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2871 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2872 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2873 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2874 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2875 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2876 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2877 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2878 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2879 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2880 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2881 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2882 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2883 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2884 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2885 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2886 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2887 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2888 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2889 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2890 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2891 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2892
2893 **Configure the communication protocol**
2894
2895 (% style="text-align:center" %)
2896 [[image:image-20221028174410-1.png]]
2897
2898 (% style="text-align:center" %)
2899 [[image:image-20221028174753-2.png]]
2900
2901
2902 (% style="text-align:center" %)
2903 [[image:image-20221028181125-4.png]]
2904
2905 **Pin Definition Diagram**
2906
2907 (% style="text-align:center" %)
2908 [[image:image-20221028180930-3.png]]
2909
2910 = Create communication with LS** PLC** =
2911
2912 == **XBC serial protocol** ==
2913
2914 **HMI Settings**
2915
2916 |=**Item**|=**Settings**|=**Note**
2917 |Protocol|LS XBC CNet|
2918 |Connection|RS232|
2919 |Baud rate|115200|
2920 |Data bit|8|
2921 |Parity|NONE|
2922 |Stop bit|1|
2923 |PLC station No.|1|
2924
2925 **Address List**
2926
2927 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2928 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2929 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2930 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2931 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2932 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2933 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2934 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2935 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2936 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
2937 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
2938 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
2939 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
2940 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
2941 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
2942 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
2943 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
2944 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
2945 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
2946 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
2947 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
2948 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
2949
2950 **Configure the communication protocol**
2951
2952 (% style="text-align:center" %)
2953 [[image:image-20220831170807-1.png]]
2954
2955 (% style="text-align:center" %)
2956 [[image:image-20220830174733-2.png]]
2957
2958 **Cable Wiring**
2959
2960 (% style="text-align:center" %)
2961 [[image:image-20220830174659-1.png]]
2962
2963 Pin Definition Diagram
2964
2965 (% style="text-align:center" %)
2966 [[image:image-20220830173402-8.png]]
2967
2968 == **XGK FEnet Ethernet protocol** ==
2969
2970 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2971
2972 **HMI Settings**
2973
2974 |**Items**|**Settings**|**Note**
2975 |Protocol|LG XGK FEnet(Ethernet)|
2976 |Connection|Ethernet|
2977 |Port No.|2004|
2978
2979 **Address List**
2980
2981 |**Type**|**Register**|**Range**|**Format**|**Note**
2982 |(% rowspan="14" %)Word|P|0~~2047|P d|
2983 |M|0~~2047|M d|
2984 |K|0~~2047|K d|
2985 |F|0~~2047|F d|
2986 |T|0~~2047|T d|
2987 |C|0~~2047|C d|
2988 |Z|0~~127|Z d|
2989 |S|0~~127|S d|
2990 |L|0~~11263|L d|
2991 |N|0~~21503|N d|
2992 |D|0~~32767|D d|
2993 |R|0~~32767|R d|
2994 |ZR|0~~65535|ZR d|
2995 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2996
2997 **✎Note:**
2998
2999 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3000 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3001 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3002
3003 **Communication settings in HMI**
3004
3005 Enable HMI Ethernet in [Project Settings];
3006
3007 (% style="text-align:center" %)
3008 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3009
3010 Set PLC IP in [Device IP] settings;
3011
3012 (% style="text-align:center" %)
3013 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3014
3015 **Cable Wiring**
3016
3017 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3018
3019 = Create communication with LS** PLC** =
3020
3021 == **XBC serial protocol** ==
3022
3023 **HMI Settings**
3024
3025 |=**Item**|=**Settings**|=**Note**
3026 |Protocol|LS XBC CNet|
3027 |Connection|RS232|
3028 |Baud rate|115200|
3029 |Data bit|8|
3030 |Parity|NONE|
3031 |Stop bit|1|
3032 |PLC station No.|1|
3033
3034 **Address List**
3035
3036 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3037 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3038 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3039 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3040 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3041 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3042 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3043 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3044 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3045 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3046 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3047 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3048 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3049 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3050 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3051 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3052 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3053 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3054 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3055 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3056 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3057 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3058
3059 **Configure the communication protocol**
3060
3061 (% style="text-align:center" %)
3062 [[image:image-20220831170807-1.png]]
3063
3064 (% style="text-align:center" %)
3065 [[image:image-20220830174733-2.png]]
3066
3067 **Cable Wiring**
3068
3069 (% style="text-align:center" %)
3070 [[image:image-20220830174659-1.png]]
3071
3072 Pin Definition Diagram
3073
3074 (% style="text-align:center" %)
3075 [[image:image-20220830173402-8.png]]
3076
3077 == **XGK FEnet Ethernet protocol** ==
3078
3079 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3080
3081 **HMI Settings**
3082
3083 |**Items**|**Settings**|**Note**
3084 |Protocol|LG XGK FEnet(Ethernet)|
3085 |Connection|Ethernet|
3086 |Port No.|2004|
3087
3088 **Address List**
3089
3090 |**Type**|**Register**|**Range**|**Format**|**Note**
3091 |(% rowspan="14" %)Word|P|0~~2047|P d|
3092 |M|0~~2047|M d|
3093 |K|0~~2047|K d|
3094 |F|0~~2047|F d|
3095 |T|0~~2047|T d|
3096 |C|0~~2047|C d|
3097 |Z|0~~127|Z d|
3098 |S|0~~127|S d|
3099 |L|0~~11263|L d|
3100 |N|0~~21503|N d|
3101 |D|0~~32767|D d|
3102 |R|0~~32767|R d|
3103 |ZR|0~~65535|ZR d|
3104 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3105
3106 **✎Note:**
3107
3108 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3109 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3110 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3111
3112 **Communication settings in HMI**
3113
3114 Enable HMI Ethernet in [Project Settings];
3115
3116 (% style="text-align:center" %)
3117 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3118
3119 Set PLC IP in [Device IP] settings;
3120
3121 (% style="text-align:center" %)
3122 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3123
3124 **Cable Wiring**
3125
3126 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3127
3128 = Create communication with **SHIMADEN PLC** =
3129
3130 == **FP23 series protocol** ==
3131
3132 Supported series: SHIMADEN FP23 series
3133
3134 **HMI Setting**
3135
3136 |**Items**|**Settings**|**Note**
3137 |Protocol|SHIMADEN FP23 series|
3138 |Connection|RS485 (9600, 1, 7, EVEN)|
3139 |Port No.|None|
3140 |PLC station No.|0|
3141
3142 **Address List**
3143
3144 |**Device address**|**HMI register**|**Address range**|**Type**
3145 |0040-0043(HEX)|FP040|100064-200067|Read only
3146 |0100-010B(HEX)|FP100|100256-200267|Read only
3147 |0110-0142(HEX)|FP110|100272-200322|Read only
3148 |0182-0252(HEX)|FP182|100386-200594|Write only
3149 |0280-0281(HEX)|FP280|100640-200641|Read only
3150 |0300-030B(HEX)|FP300|100768-200779|Read and write
3151 |0380-039F(HEX)|FP380|100896-200927|Read and write
3152 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3153 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3154 |0600-0670(HEX)|FP600|101536-201814|Read and write
3155 |0720-0738(HEX)|FP720|101824-201848|Read and write
3156 |0800-083F(HEX)|FP800|102048-202111|Read and write
3157 |0900-0952(HEX)|FP900|102304-202386|Read and write
3158 | |Ctrl|0-2|
3159
3160 **✎Note:**
3161
3162 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3163 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3164 * The Ctrl register is used to store the control group number and BCC check mode.
3165
3166 **Ctrl Register Description**
3167
3168 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3169 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3170 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3171 * Ctrl3 reserved
3172
3173 **✎Note:**
3174
3175 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3176
3177 **Cable Wiring**
3178
3179 (% style="text-align:center" %)
3180 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3181
3182 (% style="text-align:center" %)
3183 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3184
3185 **✎Note:** COM3 only available in PI8000/PI9000 series.
3186
3187 == **SR90 protocol** ==
3188
3189 Supported series: SHIMADEN SR90 series
3190
3191 **HMI Setting**
3192
3193 |**Items**|**Settings**|**Note**
3194 |Protocol|SHIMADEN SR90 protocol|
3195 |Connection|RS485 (1200, 1, 7, EVEN)|
3196 |Port No.|None|
3197 |PLC station No.|0|
3198
3199 **Address List**
3200
3201 |**Device address**|**HMI register**|**Address range**|**Type**
3202 |0040-0043 (HEX)|SR040|100064-100067|Read only
3203 |0100-010A(HEX)|SR0100|100256-100266|Read only
3204 |0182-018C(HEX)|SR0182|100386-100396|Write only
3205 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3206 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3207 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3208 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3209 | |Ctrl|0-2|~-~-
3210
3211 **✎Note:**
3212
3213 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3214 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3215 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3216
3217 **Ctrl Register Description**
3218
3219 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3220 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3221 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3222 * Ctrl3 reserved
3223
3224 **✎Note:**
3225
3226 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3227
3228 **Cable Wiring**
3229
3230 (% style="text-align:center" %)
3231 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3232
3233 (% style="text-align:center" %)
3234 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3235
3236 **✎Note:** COM3 only available in PI8000/PI9000 series.
3237
3238 == **MR13 series(standard protocol)** ==
3239
3240 Supported series: SHIMADEN MR13 series
3241
3242 **HMI Setting**
3243
3244 |**Items**|**Settings**|**Note**
3245 |Protocol|SHIMADEN standard protocol|
3246 |Connection|RS485 (1200, 1, 7, EVEN)|
3247 |Port No.|None|
3248 |PLC station No.|0|
3249
3250 **Address List**
3251
3252 |**Device address**|**HMI register**|**Address range**|**Type**
3253 |0100-010B(HEX)|MR100|100256-300267|Read only
3254 |0111-0126(HEX)|MR111|100273-300294|Read only
3255 |0184-0192(HEX)|MR184|100388-300402|Write only
3256 |0280-0282(HEX)|MR280|100640-300642|Read only
3257 |0300-030B(HEX)|MR300|100768-300779|Read/write
3258 |0314-0317(HEX)|MR314|100788-300791|Read/write
3259 |031A(HEX)|MR31A|100794-300794|Read/write
3260 |0320-0321(HEX)|MR320|100800-300801|Read/write
3261 |0400-0504(HEX)|MR400|101024-301284|Read/write
3262 |0506(HEX)|MR506|101286-301286|Read/write
3263 |0510-0514(HEX)|MR510|101296-301300|Read/write
3264 |0516-0524(HEX)|MR516|101302-301316|Read/write
3265 |0526(HEX)|MR526|101318-301318|Read/write
3266 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3267 |~-~-|Ctrl|0-2|~-~-
3268
3269 **✎Note:**
3270
3271 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3272 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3273 * The Ctrl register is used to store the control group number and BCC check mode.
3274
3275 **Ctrl Register Description**
3276
3277 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3278 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3279 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3280 * Ctrl3 reserved
3281
3282 **✎Note:**
3283
3284 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3285
3286 **Cable Wiring**
3287
3288 (% style="text-align:center" %)
3289 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3290
3291 (% style="text-align:center" %)
3292 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3293
3294 **✎Note:** COM3 only available in PI8000/PI9000 series.
3295
3296 = Create communication with **MODBUS** =
3297
3298 == **MODBUS RTU Master** ==
3299
3300 Supported Series: MODBUS RTU CONTROLLER
3301
3302 HMI works as MODBUS SLAVE connecting with MASTER
3303
3304 (% style="text-align:center" %)
3305 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3306
3307
3308 (% style="text-align:center" %)
3309 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3310
3311
3312 (% style="text-align:center" %)
3313 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3314
3315 **HMI Settings**
3316
3317 (% class="table-bordered" %)
3318 |**Items**|**Settings**|**Note**
3319 |Protocol|MODBUS RTU Master|
3320 |Connection|RS485/RS232|
3321 |Baud rate|2400~~187500|
3322 |Data bit|8|
3323 |Parity|Even/ Odd/ None|
3324 |Stop bit|1/2|
3325 |Station No.|0~~255|
3326
3327 **Address List**
3328
3329 (% class="table-bordered" %)
3330 |**Type**|**HMI address**|**MODBUS code**|**Range**
3331 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3332 |Word|HDW3500~~HDW7999|4|0~~4499
3333
3334 **Cable Wiring**
3335
3336 * **RS485**
3337
3338 (% style="text-align:center" %)
3339 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3340
3341 (% style="text-align:center" %)
3342 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3343
3344 * **RS232**
3345
3346 (% style="text-align:center" %)
3347 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3348
3349 **✎Note:** COM3 only available in PI8000/PI9000 series.
3350
3351 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3352
3353 Supported Series: MODBUS RTU CONTROLLER
3354
3355 HMI works as MODBUS MASTER connecting with SLAVE.
3356
3357 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3358
3359 (% style="text-align:center" %)
3360 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3361
3362
3363 (% style="text-align:center" %)
3364 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3365
3366
3367 (% style="text-align:center" %)
3368 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3369
3370 **HMI Settings**
3371
3372 (% class="table-bordered" %)
3373 |**Items**|**Settings**|**Note**
3374 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3375 |Connection|RS485/RS232|
3376 |Baud rate|2400~~187500|
3377 |Data bit|8|
3378 |Parity|Even/ Odd/ None|
3379 |Stop bit|1/2|
3380 |PLC station No.|0~~255|
3381
3382 **Address List**
3383
3384 (% class="table-bordered" %)
3385 |**Type**|**Address Type**|**Function code & Description**
3386 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3387 |06 (write single register: write a binary value to a holding register)
3388 |10 (write values to multiple addresses )
3389 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3390 |06 (write single register: write a binary value to a holding register)
3391 |10 (write values to multiple addresses )
3392 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3393 |06 (write single register: write a binary value to a holding register)
3394 |10 (write values to multiple addresses )
3395 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3396 |10 (write values to multiple addresses )
3397 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3398 |05 (Force a single coil to force the on/off state of a logic coil)
3399 |0F (Write multiple bits, ie write continuously)
3400 |(% rowspan="3" %)1|02 (Read the input state)
3401 |05 (Force a single coil to force the on/off state of a logic coil)
3402 |0F (Write multiple bits)
3403 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3404 |05 (Force a single coil to force the on/off state of a logic coil)
3405 |0F (Write multiple bits)
3406 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3407 |0F (Write multiple bits)
3408
3409 **✎Note:**
3410
3411 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3412 * The function codes sent out are the same as those that read and write words.
3413
3414 **Station number for more than one slaves**
3415
3416 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3417
3418 (% style="text-align:center" %)
3419 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3420
3421 **Cable Wiring**
3422
3423 * **RS485**
3424
3425 (% style="text-align:center" %)
3426 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3427
3428 (% style="text-align:center" %)
3429 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3430
3431 * **RS232**
3432
3433 (% style="text-align:center" %)
3434 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3435
3436 **✎Note:** COM3 only available in PI8000/PI9000 series.
3437
3438 == **MODBUS TCP Slave (All function)** ==
3439
3440 Supported series: MODBUS TCP controller
3441
3442 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3443
3444 (% style="text-align:center" %)
3445 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3446
3447 (% style="text-align:center" %)
3448 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3449
3450
3451 (% style="text-align:center" %)
3452 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3453
3454 **HMI Setting**
3455
3456 (% class="table-bordered" %)
3457 |**Items**|**Settings**|**Note**
3458 |Protocol|MODBUS TCP Slave (All function)|
3459 |Connection|Ethernet|
3460 |Port No.|502|
3461 |PLC station No.|1|
3462
3463 **Address List**
3464
3465 (% class="table-bordered" %)
3466 |**Type**|**Register**|**Function code & Description**
3467 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3468 |06 (write single register: write a binary value to a holding register)
3469 |10 (write values to multiple addresses )
3470 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3471 |06 (write single register: write a binary value to a holding register)
3472 |10 (write values to multiple addresses )
3473 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3474 |06 (write single register: write a binary value to a holding register)
3475 |10 (write values to multiple addresses )
3476 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3477 |10 (write values to multiple addresses )
3478 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3479 |05 (Force a single coil to force the on/off state of a logic coil)
3480 |0F (Write multiple bits, ie write continuously)
3481 |(% rowspan="3" %)1|02 (Read the input state)
3482 |05 (Force a single coil to force the on/off state of a logic coil)
3483 |0F (Write multiple bits)
3484 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3485 |05 (Force a single coil to force the on/off state of a logic coil)
3486 |0F (Write multiple bits)
3487 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3488 |0F (Write multiple bits)
3489
3490 **Communication Settings**
3491
3492 Enable HMI Ethernet in [Project Settings];
3493
3494 (% style="text-align:center" %)
3495 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3496
3497 Set PLC IP in [Device IP] settings;
3498
3499 (% style="text-align:center" %)
3500 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3501
3502 **Cable Wiring**
3503
3504 (% style="text-align:center" %)
3505 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3506
3507 = **Printer** =
3508
3509 == **TSPL label printer** ==
3510
3511 **Introduction**
3512
3513 TSPL label printer protocol supports following models.
3514
3515 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3516 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3517
3518 **Setting Step**
3519
3520 Select the protocol
3521
3522 * Create a new project, select the TSPL label printer protocol as shown below.
3523
3524 (% style="text-align:center" %)
3525 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3526
3527 Set parameters
3528
3529 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3530
3531 Printer register
3532
3533 (% class="table-bordered" %)
3534 |**Register**|**System**|**Range**|**Function**
3535 |TSPL_SP|decimal|0 - 1|Set the paper size
3536 |TSPL_PT|decimal|0 - 1999|Print text
3537 |TSPL_PQ|decimal|0 - 999|Print QR code
3538 |TSPL_PB|decimal|0 - 999|Print barcode
3539 |TSPL_PR|decimal|0 - 1|Print offset
3540 |TSPL_PN|decimal|0 - 0|Trigger printing
3541 |TSPL_PS|decimal|0 - 0|Print status
3542
3543 * Set paper size:
3544 ** TSPL_SP0: width of paper, unit: mm.
3545 ** TSPL_SP1: height of paper, unit: mm.
3546 * Print text:
3547 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3548 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3549
3550 (% class="table-bordered" %)
3551 |**Register**|**Function**|**Description**
3552 |TSPL_PT0|X coordinate|Unit: dot
3553 |TSPL_PT1|Ycoordinate|Unit: dot
3554 |TSPL_PT2|Rotation angle|(((
3555 0: 0 degrees
3556
3557 1: 90 degrees
3558
3559 2: 180 degrees
3560
3561 3: 270 degrees
3562 )))
3563 |TSPL_PT3|Size|Range: 0-3
3564 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3565
3566 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3567
3568 Print QR code:
3569
3570 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3571 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3572
3573 (% class="table-bordered" %)
3574 |**Register**|**Function**|**Description**
3575 |TSPL_PQ0|X coordinate|Unit: dot
3576 |TSPL_PQ1|Ycoordinate|Unit: dot
3577 |TSPL_PQ2|Rotation angle|(((
3578 0: 0 degrees
3579
3580 1: 90 degrees
3581
3582 2: 180 degrees
3583
3584 3: 270 degrees
3585 )))
3586 |TSPL_PQ3|Size|Range: 0-5
3587 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3588
3589 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3590
3591 Print bar code:
3592
3593 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3594 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3595
3596 (% class="table-bordered" %)
3597 |**Register**|**Function**|**Description**
3598 |TSPL_PB0|X coordinate|Unit: dot
3599 |TSPL_PB1|Ycoordinate|Unit: dot
3600 |TSPL_PB2|Rotation angle|(((
3601 0: 0 degrees
3602
3603 1: 90 degrees
3604
3605 2: 180 degrees
3606
3607 3: 270 degrees
3608 )))
3609 |TSPL_PB3|height|Unit: dot
3610 |TSPL_PB4|width|Range:0-2
3611 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3612
3613 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3614
3615 Print offset:
3616
3617 * TSPL_PR0: X coordinate offset, unit: mm;
3618 * TSPL_PR1: Y coordinate offset, unit: mm.
3619
3620 Trigger printing:
3621
3622 * TSPL_PN0 = 1: trigger the printer to start printing.
3623
3624 Printing status:
3625
3626 * TSPL_PS0 = 1: The printing is normal.
3627 * TSPL_PS0 = 1: The printing is abnormal.
3628
3629 Print picture
3630
3631 * For the function of printing pictures, please refer to the configuration of [Printer object].
3632
3633 Conversion between dot and mm
3634
3635 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3636
3637 == **EpsonTM series** ==
3638
3639 **HMI Settings**
3640
3641 (% class="table-bordered" %)
3642 |**Item**|**Settings**|**Note**
3643 |Protocol|EPSON-TM-T82II/TM-XXX|
3644 |Connection|RS232|
3645 |Baud rate|9600~~115200|
3646 |Data bit|8|
3647 |Parity|None|
3648 |Stop bit|1|
3649 |PLC station No.|1|
3650
3651 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3652
3653 **Printer Settings**
3654
3655 (% class="table-bordered" %)
3656 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3657 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3658 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3659 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3660 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3661 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3662 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3663
3664 **Cable Wiring**
3665
3666 (% style="text-align:center" %)
3667 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3668
3669 (% style="text-align:center" %)
3670 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3671
3672 **✎Note:** COM3 only available in PI8000/PI9000 series.
3673
3674
3675 = Create communication with **Schneider PLC** =
3676
3677 == **Schneider MODBUS RTU** ==
3678
3679 **HMI Setting**
3680
3681 |=**Parameters**|=**Recommended**|=**Notes**
3682 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3683 |Connection|RS485|
3684 |**Baud rate**|19200|
3685 |**Data bit**|8|
3686 |**Parity**|Even|
3687 |**Stop bit**|1|
3688 |**PLC station No.**|1|
3689
3690 **PLC Setting**
3691
3692 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3693
3694 **Device Address**
3695
3696 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3697 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3698 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3699 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3700 |W|MW|DDDDDD|0 ~~ 999999|Output register
3701 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3702
3703 **Wiring Diagram**
3704
3705 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3706
3707 (% style="text-align:center" %)
3708 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3709
3710 = **Barcode Scanner** =
3711
3712 Supported: DELI 14880 barcode scanner
3713
3714 **HMI Setting**
3715
3716 |**Items**|**Settings**|**Note**
3717 |Protocol|Barcode Scanner|
3718 |Connection|USB|
3719
3720 **Operating Procedures**
3721
3722 Select [Barcode Scanner];
3723
3724 (% style="text-align:center" %)
3725 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3726
3727 Set address for receiving;
3728
3729 Set correct length;
3730
3731 (% style="text-align:center" %)
3732 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3733
3734 **✎Note:**
3735
3736 * The protocol uploads the information acquired by the USB scanner to the HMI;
3737 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3738 * Recommended model: DELI 14880 barcode scanner;
3739
3740 = **Hitachi EHV Series (Ethernet)** =
3741
3742 Supported series: Hitachi EHV series
3743
3744 **HMI Settings**
3745
3746 (% class="table-bordered" %)
3747 |**Items**|**Settings**|**Note**
3748 |Protocol|Hitachi EHV series|
3749 |Connection|Ethernet|
3750 |Port No.|3004~~3007|
3751
3752 **Address List**
3753
3754 (% class="table-bordered" %)
3755 |**Type**|**Register**|**Range**|**Format**|**Note**
3756 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3757 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3758 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3759 H1H2H3H4 Module main number
3760
3761 H1: Remote number
3762
3763 H2: Unit number
3764
3765 H3: Slot number
3766
3767 H4: Word number of Module
3768
3769 H Sub number of Module
3770
3771 For example:X21.3
3772
3773 Slot number 2
3774
3775 Word number of module is 1
3776
3777 Bit number of module is 3
3778
3779 Remote number and unit number are 0
3780 )))
3781 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3782 |R|0 – FF.f (Hex)|R HH.h|
3783 |L|0 - 73FF.f (Hex)|L HHHH.h|
3784 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3785 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3786 H1H2H3H4 Module main number
3787
3788 H1: Remote number
3789
3790 H2: Unit number
3791
3792 H3: Slot number
3793
3794 H4: Word number of module
3795
3796 For example:WX21
3797
3798 Word number of module is 1
3799
3800 Slot number is 2
3801
3802 Remote number and unit number are 0
3803 )))
3804 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3805 |WR|0 – FFFF (Hex)|WR HHHH|
3806 |WL|0 - 73FF (Hex)|WL HHHH|
3807 |TC|0 - 2559|TC DDDD|
3808
3809 **Communication settings in HMI**
3810
3811 Enable HMI Ethernet in [Project Settings];
3812
3813 (% style="text-align:center" %)
3814 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3815
3816 Set PLC IP in [Device IP] settings;
3817
3818 (% style="text-align:center" %)
3819 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3820
3821 **PLC Configuration**
3822
3823 Connect with PLC, select[Online mode];
3824
3825 (% style="text-align:center" %)
3826 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3827
3828 Set IP address, it is the same LAN parameters with HMI;
3829
3830 (% style="text-align:center" %)
3831 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3832
3833 3) Save PLC communication parameter, and restart PLC
3834
3835 **PLC Monitor Mode**
3836
3837 Connect with PLC and choose to “online” mode
3838
3839 (% style="text-align:center" %)
3840 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3841
3842 Open I/O monitor sheet1
3843
3844 (% style="text-align:center" %)
3845 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3846
3847 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3848
3849 (% style="text-align:center" %)
3850 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3851
3852 Enter the register address, click OK to view the value of the register.
3853
3854 (% style="text-align:center" %)
3855 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3856
3857 (% style="text-align:center" %)
3858 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3859
3860 **✎Note:**
3861
3862 * Both word registers and bit registers support even continuous read/write functions;
3863 * The range of registers is based on the specific PLC type;
3864
3865 **Cable Wiring**
3866
3867 (% style="text-align:center" %)
3868 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3869
3870 = **IEC60870-5 104 Client** =
3871
3872 **HMI Setting**
3873
3874 (% class="table-bordered" %)
3875 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3876 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3877 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3878 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3879
3880 **Address List**
3881
3882 (% class="table-bordered" %)
3883 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3884 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3885 |(% style="width:461px" %)SCNA|0~~16777215.7
3886 |(% style="width:461px" %)DPTB|0~~16777215.7
3887 |(% style="width:461px" %)DCNA|0~~16777215.7
3888 |(% style="width:461px" %)METF|0~~16777215.7
3889 |(% style="width:461px" %)SENC|0~~16777215.7
3890 |(% style="width:461px" %)SENA|0~~16777215.7
3891 |(% style="width:461px" %)MENA|0~~16777215.7
3892 |(% style="width:461px" %)METD|0~~16777215.7
3893 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3894 |(% style="width:461px" %)SCNA|0~~16777215
3895 |(% style="width:461px" %)DPTB|0~~16777215
3896 |(% style="width:461px" %)DCNA|0~~16777215
3897 |(% style="width:461px" %)SENA|0~~16777215
3898 |(% style="width:461px" %)MENA|0~~16777215
3899 |(% style="width:461px" %)METD|0~~16777215
3900 |(% style="width:461px" %)INRO|0~~16777215
3901 |(% style="width:461px" %)TIMESYN|0~~16777215
3902 |(% style="width:461px" %)TIMEZ|0~~16777215
3903 |(% style="width:461px" %)NTP|0~~16777215
3904 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3905 |(% style="width:461px" %)SENC|0~~16777215
3906
3907 **Address Configuration**
3908
3909 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3910
3911 (% style="text-align:center" %)
3912 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3913
3914 (% style="text-align:center" %)
3915 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3916
3917 Extended tag name
3918
3919 Address range for the extended tag.
3920
3921 **Communication Settings**
3922
3923 Enable HMI Ethernet in [Project Settings];
3924
3925 (% style="text-align:center" %)
3926 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3927
3928 Set PLC IP in [Device IP] settings;
3929
3930 (% style="text-align:center" %)
3931 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3932
3933 **Cable Wiring**
3934
3935 (% style="text-align:center" %)
3936 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3937
3938 = **OpenCAN** =
3939
3940 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
3941
3942 This protocol is only available in PI8000 series HMI.
3943
3944 **HMI Settings**
3945
3946 |**Items**|**Settings**|**Note**
3947 |Protocol|OPENCAN|
3948 |Connection|CAN port|
3949 |Baud rate|250000|
3950
3951 **CAN frame setting in HMI**
3952
3953 Click [OpenCAN setting] button in communication setting window;
3954
3955 (% style="text-align:center" %)
3956 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
3957
3958 Click [Add] to create a new frame;
3959
3960 (% style="text-align:center" %)
3961 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
3962
3963 |**No**|**Items**|**Description**
3964 |1|Add|add a frame related to register address
3965 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
3966 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
3967 |4|Modify|Modify the frames in frame management
3968 |5|Copy|Copy one frame to another
3969 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3970 |7|Empty|All frames in the list are cleared
3971 |8|Browse|Displays configuration files in XML format in IE
3972 |9|OK|Complete the configuration of the frame and exit
3973
3974 Set CANBUS frame in setting windows
3975
3976 (% style="text-align:center" %)
3977 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3978
3979 |**No**|**Items**|**Description**
3980 |1|ID|Set the ID of a can frame in hexadecimal format;
3981 |2|ID assign|split the ID by PF, PS, and SA;
3982 |3|Frame type|Select Standard frame or Extended Frame;
3983 |4|Frame format|Select between data frame and remote Frame;
3984 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3985 |6|Use address|(((
3986 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3987
3988 **Edit:** Set a bit or word address by its format;
3989
3990 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3991 )))
3992 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3993 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3994 |Feedback mode: feedback mode includes no response, confirm response and data response;
3995 |No response: the device or touch screen will not receive feedback;
3996 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3997 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3998 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3999 |Response timeout: sets whether the response frame timeout;
4000 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4001 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4002 |Manually send: a manually send tick indicates only one send;
4003 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4004 |10|Note|Fill the text to explain the meaning of the frame;
4005 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4006 |12|Current operation display|Display the description of current operation;
4007 |13|Add|Add a new frame;
4008 |14|Save frame|Save the configured frame format;
4009 |15|Cancel|Cancel the frame configuration;
4010
4011 Set CAN address (Read or write operation);
4012
4013 (% style="text-align:center" %)
4014 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4015
4016 |**No.**|**Item**|**Description**
4017 |1|Current address|Displays the register type and register address set by the user in the data access interface
4018 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4019 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4020 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4021 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4022 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4023 |If the trigger condition is a writing operation, there are two situations:(((
4024 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4025 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4026 )))
4027 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4028 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4029 |4|Add|Add current configuration
4030 |5|Close|Close the configuration window to exit
4031
4032 **Multiple Packages Settings**
4033
4034 (% style="text-align:center" %)
4035 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4036
4037 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4038
4039 Select Multiple package type
4040
4041 * Not Multiple packages
4042 * J1939 Multiple packages
4043 * Customized Multiple packages
4044
4045 Click [Edit Receive data] for [Receive] settings
4046
4047 * Start code+ Total length (J1939)
4048
4049 (% style="text-align:center" %)
4050 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4051
4052 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4053
4054 * Start code + Data max length (J1939)
4055
4056 (% style="text-align:center" %)
4057 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4058
4059 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4060
4061 * Data max length (J1939)
4062
4063 (% style="text-align:center" %)
4064 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4065
4066 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4067
4068 * Customized multiple package
4069
4070 (% style="text-align:center" %)
4071 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4072
4073 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4074
4075 Click [Edit Send data] for [Send] setting
4076
4077 * J1939
4078
4079 (% style="text-align:center" %)
4080 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4081
4082 [Data] is all data to be sent.
4083
4084 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4085
4086 * Customized multiple package
4087
4088 (% style="text-align:center" %)
4089 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4090
4091 [Data] is all data to be sent.
4092
4093 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4094
4095 **Cable Wiring**
4096
4097 (% style="text-align:center" %)
4098 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4099
4100 **✎Note:** The address interval between each frame need to be more than a word address;
4101
4102
4103 = **User Defined Protocol** =
4104
4105 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4106
4107 **HMI Settings**
4108
4109 |**Items**|**Settings**|**Note**
4110 |Protocol|User defined protocol|
4111 |Connection|RS485/RS232|
4112 |Baud rate|2400~~187500|
4113 |Stop bits|1/ 2|
4114 |Data bits|7/ 8|
4115 |Parity|None/ Even/ ODD|
4116
4117 **Operating Procedures**
4118
4119 Select [User defined protocol];
4120
4121 Click [User defined protocol] button to open setting window as below;
4122
4123 (% style="text-align:center" %)
4124 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4125
4126 Configure user defined command;
4127
4128 (% style="text-align:center" %)
4129 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4130
4131 |**No**|**Item**|**Description**
4132 |1|Instruction edit|The required command.
4133 |2|Mode|Write to address or read from the address.
4134 |3|Format|Encode format: HEX or ASCII.
4135 |4|Other|(((
4136 **No receiving: **HMI does not respond to the receiving command.
4137
4138 **Send after receiving:** HMI responds to the receiving command.
4139 )))
4140 |5|Manually send|(((
4141 Respond once after trigger the address.
4142
4143 Address: set the trigger address.
4144 )))
4145 |6|Add|Save this setting.
4146 |7|Cancel|Cancel current settings.
4147 |(% rowspan="4" %)8|Add|Add a new command.
4148 |Edit|Edit the selected command.
4149 |Delete|Delete the selected command.
4150 |Clear|Clear all the commands.
4151 |9|Instruction list|Display all current commands.
4152 |10|Address List|Display all the addresses added.
4153 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4154 |Export|Export current command settings to local storage.
4155 |Browse|Browse local command files.
4156 |Advanced|Combine two commands.
4157 |Exit|Complete editing and exit setting.
4158
4159 **Operating Procedures**
4160
4161 Click [Add] to create a new command, as below shows;
4162
4163 (% style="text-align:center" %)
4164 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4165
4166 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4167
4168 (% style="text-align:center" %)
4169 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4170
4171 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4172
4173 (% style="text-align:center" %)
4174 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4175
4176 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4177
4178 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4179
4180 Check settings;
4181
4182 (% style="text-align:center" %)
4183 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4184
4185 |**No**|**Items**|**Description**
4186 |1|Add checking|Add checking command when receiving the data.
4187 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4188 |Differ with send check|Set return checking.
4189 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4190 |Length: The data length need to be checked.
4191
4192 Object settings;
4193
4194 (% style="text-align:center" %)
4195 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4196
4197 |**No**|**Items**|**Description**
4198 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4199 |Address: the triggering address;
4200 |Note: description to object;
4201 |2|Byte order|The numerical display order;
4202
4203 Data length settings;
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4207
4208 |**No**|**Item**|**Description**
4209 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4210 |Length: the return data length.
4211 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4212 |Length: the write data length.
4213
4214 Instruction length settings
4215
4216 (% style="text-align:center" %)
4217 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4218
4219 |**No**|**Item**|**Description**
4220 |1|Send length|The instruction data will only send designated data length.
4221 |2|Return length|The responds data length.
4222 |3|End code|Instruction will not be terminated until receiving [End code];
4223
4224 **Cable Wiring**
4225
4226 * **RS485**
4227
4228 (% style="text-align:center" %)
4229 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4230
4231 (% style="text-align:center" %)
4232 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4233
4234 * **RS232**
4235
4236 (% style="text-align:center" %)
4237 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4238
4239 **✎Note:** COM3 only available in PI8000/PI9000 series.