Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 245.1 by Hunter on 2023/04/21 15:38

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |\\
498 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
499 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
500 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
501 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
502 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
503 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
504 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
505 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
506
507 **Address List**
508
509 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
510 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
519 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
527 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
528
529 **Cable Wiring**
530
531 (% style="text-align:center" %)
532 [[image:Azbil CPL485.gif]]
533
534 = Create communication with Crouzet PLC =
535
536 == **M3 (FBD) Protocol** ==
537
538 Support Series: Crouzet Millenium 3 CD12/CB12
539
540 **HMI Settings**
541
542 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
543 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
544 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
545 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
546 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
547 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
548 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
549 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
550 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
551
552 **Address List**
553
554 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
555 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
556 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
557 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
558 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
559 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
560 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
561 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
562 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
563 Time1: Second
564
565 Time2: Minute
566
567 Time3: Hour
568
569 Time4: Day
570
571 Time5: Month
572
573 Time6: Year
574 )))
575 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
576 Running command(Write only)
577
578 ~=2: Run mode; =1: Stop mode;
579 )))
580
581 **Cable Wiring**
582
583 (% style="text-align:center" %)
584 [[image:CrouzetRS232.png]]
585
586 {{info}}
587 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
588 {{/info}}
589
590 = Create communication with Danfoss Drive =
591
592 == **FC Series Protocol** ==
593
594 Support Series: VLT FC300 Drive
595
596 **HMI Settings**
597
598 (% style="width:988px" %)
599 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
600 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
607 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
608
609 **Address List**
610
611 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
612 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
614 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
616
617 **Cable Wiring**
618
619 (% style="text-align:center" %)
620 [[image:Danfoss.png]]
621
622 = Create communication with **Delta PLC** =
623
624 == DVP serial protocol ==
625
626 (% class="wikigeneratedid" %)
627 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
628
629 **HMI Settings**
630
631 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
632 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
633 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
634 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
635 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
636 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
637 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
638 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
639
640 **Address List**
641
642 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
648 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
651 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
652
653 (% class="wikigeneratedid" %)
654 **Configure the communication protocol**
655
656 (% style="text-align:center" %)
657 [[image:image-20220829152327-6.png]]
658
659 (% style="text-align:center" %)
660 [[image:image-20220829152016-3.png]]
661
662 (% class="wikigeneratedid" %)
663 **Cable Wiring**
664
665 (% class="wikigeneratedid" id="H" %)
666 [[image:image-20220829152610-7.png]]
667
668 (% style="text-align:center" %)
669 [[image:image-20220829152102-5.png]]
670
671 == DVP Ethernet Protocol ==
672
673 (% class="wikigeneratedid" %)
674 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
675
676 **HMI Settings**
677
678 |=**Items**|=**Settings**|=**Note**
679 |Protocol|DELTA DVP Modbus TCP|
680 |Connection|Ethernet|
681 |Port No.|201|Must be the same as the PLC setting
682 |PLC station No.|0|Must be the same as the PLC setting
683
684 **Address List**
685
686 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
693 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
695 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
696
697 )))
698 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
699 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
700
701 )))
702
703 (% class="wikigeneratedid" %)
704 **Configure the communication protocol**
705
706 (% style="text-align:center" %)
707 [[image:image-20220829155452-1.png]]
708
709 [[image:image-20220829162116-2.png]]
710
711 **Cable Wiring**
712
713 (% style="text-align:center" %)
714 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
715
716 == **AS serial protocol** ==
717
718 Supported Series: Delta AS200/AS300
719
720 **HMI Settings**
721
722 |**Item**|**Settings**|**Note**
723 |Protocol|DELTA AS300 MODBUS RTU|
724 |Connection|RS485|
725 |Baud rate|9600|
726 |Data bit|8|
727 |Parity|NONE|
728 |Stop bit|1|
729 |PLC station No.|1|
730
731 **Address List**
732
733 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
734 |Bit|X|X|Xdd.dd|0~~63.15|Read only
735 |Bit|Y|Y|Ydd.dd|0~~63.15|
736 |Bit|D|D|Dddddd|0~~29999|
737 |Bit|M|M|Mdddd|0~~8191|
738 |Bit|SM|SM|SMdddd|0~~4095|
739 |Bit|S|S|Sdddd|0~~2047|
740 |Bit|T|T|Tddd|0~~511|
741 |Bit|C|C|Cddd|0~~511|
742 |Bit|HC|HC|HCddd|0~~255|Double Word
743 |Word|X|X|Xdd|0~~63|
744 |Word|Y|Y|(((
745 Ydd
746 )))|0~~63|
747 |Word|SR|SR|SRdddd|0~~2047|Special register
748 |Word|D|D|Dddddd|0~~29999|
749 |Word|T|T|Tddd|0~~511|
750 |Word|C|C|Cddd|0~~511|
751 |Word|E|E|Ed|0~~9|
752
753 **Configure the communication protocol**
754
755 Create project
756
757 (% style="text-align:center" %)
758 [[image:AsCreateProject.png]]
759
760 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
761
762 (% style="text-align:center" %)
763 [[image:AScommunicarw.png]]
764
765 Double click the HWCONFIG to open the communication settings window.
766
767 (% style="text-align:center" %)
768 [[image:ASHWCONFIG.png]]
769
770 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
771
772 (% style="text-align:center" %)
773 [[image:ASHSCONFIGICON.png]]
774
775 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
776
777 (% style="text-align:center" %)
778 [[image:ASModbusMode.png]]
779
780 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
781
782 (% style="text-align:center" %)
783 [[image:ASconfigIP.png]]
784
785 (% style="text-align:center" %)
786 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
787
788
789 (% style="text-align:center" %)
790 [[image:image-20220830094657-2.png]]
791
792 **Cable Wiring**
793
794 (% style="text-align:center" %)
795 [[image:image-20220830141138-1.png]]
796
797 Pin Definition Diagram
798
799 (% style="text-align:center" %)
800 [[image:image-20220830095131-1.png]]
801
802 == AS Ethernet Protocol ==
803
804 **HMI Settings**
805
806 |=**Items**|=**Settings**|=**Note**
807 |Protocol|DELTA AS300 MODBUS TCP|
808 |Connection|Ethernet|
809 |Port No.|502|
810 |Device No.|1|
811 |HMI No.|0|
812
813 **Address List**
814
815 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
816 |Bit|X|X|X d|0~~63|
817 |Bit|Y|Y|Y d|0~~63|
818 |Bit|D|D|D d|0~~29999|
819 |Bit|M|M|M d|0~~8191|
820 |Bit|SM|SM|SM d|0~~4095|
821 |Bit|S|S|S h|0~~2047|
822 |Bit|T|T|T d|0~~511|
823 |Bit|C|C|C d|0~~511|
824 |Bit|HC|HC|HC d|0~~255|
825 |Word|X|X|X h|0~~63|
826 |Word|Y|Y|Y d|0~~63|
827 |Word|SR|SR|SR d|0~~2047|
828 |Word|D|D|D d|0~~29999|
829 |Word|T|T|T d|0~~511|
830 |Word|C|C|C h|0~~511|
831 |Word|E|E|E d|0~~9|
832
833 **Configure the communication protocol**
834
835 (% style="text-align:center" %)
836 [[image:image-20220830140537-1.png]]
837
838 (% style="text-align:center" %)
839 [[image:image-20220830140629-2.png]]
840
841 **Cable Wiring**
842
843 [[image:image-20220830094929-1.png]]
844
845 Pin Definition Diagram
846
847 (% style="text-align:center" %)
848 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
849
850 = **Create communication with Inovance PLC** =
851
852 == **H1U/H2U serial protocol** ==
853
854 **HMI Settings**
855
856 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
857 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
858 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
859 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
860 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
861 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
862 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
863 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
864 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
865
866 (% class="wikigeneratedid" %)
867 **Address List**
868
869 (% style="width:1014px" %)
870 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
871 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
872 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
873 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
874 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
875 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
876 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
877 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
878 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
879 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
880 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
881 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
882 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
883 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
884 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
885 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
886 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
887 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
888
889 (% class="wikigeneratedid" %)
890 **Cable Wiring**
891
892 (% style="text-align:center" %)
893 [[image:Inovance.png]]
894
895 == **H3U serial protocol** ==
896
897 **HMI Settings**
898
899 |=**Item**|=**Settings**|=**Note**
900 |Protocol|INOVANCE H3U PLC|
901 |Connection|RS422|
902 |Baud rate|9600|
903 |Data bit|7|
904 |Parity|EVEN|
905 |Stop bit|1|
906 |PLC station No.|0|
907
908 **Address List**
909
910 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
911 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
912 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
913 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
914 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
915 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
916 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
917 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
918 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
919 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
920 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
921 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
922 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
923 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
924 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
925 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
926 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
927 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
928 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
929
930 **Configure the communication protocol**
931
932 (% style="text-align:center" %)
933 [[image:image-20220830170114-4.png]]
934
935 [[image:image-20220830170017-3.png]]
936
937 **Cable Wiring**
938
939 (% style="text-align:center" %)
940 [[image:Inovance.png]]
941
942 == **H3U Ethernet portocol** ==
943
944 **HMI Settings**
945
946 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
947 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
948 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
949 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
950 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
951 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
952
953 **Address List**
954
955 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
956 |Bit|M|M DDDD|0~~8511|
957 |Bit|SM|SM DDDD|0~~1023|
958 |Bit|S|S DDDD|0~~4095|
959 |Bit|T|T DDD|0~~511|
960 |Bit|C|C DDD|0~~255|
961 |Bit|X|X OOO|0~~571|
962 |Bit|Y|Y OOO|0~~571|
963 |Word|D|D DDDD|0~~8511|
964 |Word|SD |SD DDDD|0~~1023|
965 |Word|R|R DDDDD|0~~32767|
966 |Word|T|T DDD|0~~255|
967 |Word|C|C DDD|0~~199|
968 |Double Word|C|C DDD|200~~255|
969
970 **Cable Wiring**
971
972 (% style="text-align:center" %)
973 [[image:CommonEthernet.png]]
974
975 = Create communication with **Mitsubishi PLC** =
976
977 == **FX1S, 1N, 2N Series Protocol** ==
978
979 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
980
981 **HMI Settings**
982
983 |**Item**|**Settings**|**Note**
984 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
985 |Connection|RS422/RS485/RS232|
986 |Baud rate|9600~~115200|
987 |Data bit|7/8|
988 |Parity|EVEN/Odd/None|
989 |Stop bit|1/2|
990 |PLC station No.|1~~255|
991
992 **Address List**
993
994 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
995 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
996 |Y|Y|Y o|0~~303237|
997 |M|M|M d|0~~99999|
998 |T|T|T d|0~~99999|
999 |C|C|C d|0~~99999|
1000 |S|S|S d|0~~99999|
1001 |SM|SM|SM d|8000~~9999|
1002 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1003 |Y|Y|Y o|0~~303237|
1004 |M|M|M d|0~~99999|
1005 |T|T|T d|0~~99999|
1006 |C|C|C d|0~~199|
1007 |D|D|D d|0~~7999|
1008 |S|S|S d|0~~99999|
1009 |SD|SD|SD d|8000~~9999|
1010
1011 **Cable Wiring**
1012
1013 * **RS485**
1014
1015 (% style="text-align:center" %)
1016 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1017
1018 (% style="text-align:center" %)
1019 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1020
1021 * **RS422**
1022
1023 (% style="text-align:center" %)
1024 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1025
1026 **✎Note:** COM3 only available in PI8000/PI9000 series.
1027
1028 == **FX3U/3G/3GA serial protocol** ==
1029
1030 **HMI Settings**
1031
1032 |=**Item**|=**Settings**|=**Note**
1033 |Protocol|Mitsubishi FX3U/3G/3GA|
1034 |Connection|RS422|
1035 |Baud rate|9600~~115200|
1036 |Data bit|7/8|
1037 |Parity|EVEN/Odd/None|
1038 |Stop bit|1/2|
1039 |PLC station No.|1~~255|
1040
1041 **Address List**
1042
1043 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1044 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1045 |Y|Y|Y o|0~~303237|
1046 |M|M|M d|0~~99999|
1047 |T|T|T d|0~~99999|
1048 |C|C|C d|0~~99999|
1049 |S|S|S d|0~~99999|
1050 |SM|SM|SM d|8000~~9999|
1051 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1052 |Y|Y|Y o|0~~303237|
1053 |M|M|M d|0~~99999|
1054 |T|T|T d|0~~99999|
1055 |C|C|C d|0~~199|
1056 |D|D|D d|0~~7999|
1057 |S|S|S d|0~~99999|
1058 |SD|SD|SD d|8000~~9999|
1059
1060 **Configure the communication protocol**
1061
1062 (% style="text-align:center" %)
1063 [[image:image-20220831095222-1.png]]
1064
1065 (% style="text-align:center" %)
1066 [[image:image-20220831095743-2.png]]
1067
1068 **Wiring**
1069
1070 (% style="text-align:center" %)
1071 [[image:image-20220831100314-6.png]]
1072
1073 == **FX3U Ethernet Protocol** ==
1074
1075 Mitsubishi FX3U series PLC
1076
1077 **HMI Settings**
1078
1079 |Items|Settings|Note
1080 |Protocol|Mitsubishi FX3U|
1081 |Connection|Ethernet|
1082 |Port No.|5009|Must be the same as the PLC setting
1083 |PLC station No.|0|
1084
1085 **Address List**
1086
1087 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1088 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1089 |Y|Y|Y OOO|0~~377|
1090 |M|M|M DDDD|0~~7679|
1091 |SM|SM|SM DDDD|8000~~8511|
1092 |S|S|S DDDD|0~~4095|
1093 |TS|TS|TS DDD|0~~511|
1094 |CS|CS|CS DDD|0~~255|
1095 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1096 |TN|TN|TN DDD|0~~511|
1097 |D|D|D DDDD|0~~7999|
1098 |SD|SD|SD DDDD|8000~~8511|
1099 |R|R|R DDDDD|0~~32767|
1100
1101 **Ethernet Module Settings**
1102
1103 FX3U-ENET-L module configuration
1104 Set up the FX3U-ENET-L Ethernet module settings as follows.
1105 Select the module location, which in this document is Module 0.
1106
1107 [[image:image-20221115140802-1.png]]
1108
1109 Select "Operational setting" to enter the following screen.
1110
1111 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1112
1113 [[image:image-20221115142728-4.png]]
1114
1115 Select "Open setting" to enter the setting interface, the settings are as follows.
1116
1117 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1118
1119 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1120
1121 [[image:image-20221115142945-5.png]]
1122
1123 Click on "transter setup" - "PC side I/F setting", see the following figure.
1124
1125 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1126
1127 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1128
1129 [[image:image-20221115143341-6.png||height="426" width="712"]]
1130
1131 Read and write data from the Ethernet module
1132
1133 [[image:image-20221115143703-7.png]]
1134
1135 Set "Transter setup" to COM communication, and read or write operation as shown below
1136
1137 [[image:image-20221115143809-8.png]]
1138
1139 **PLC Settings (GX Works 2)**
1140
1141 Create a blank FX5U project
1142
1143 Find Current Connection in the navigation
1144
1145 [[image:image-20221115144335-9.png||height="422" width="706"]]
1146
1147 Select Connection Channel List
1148
1149 Select Ethernet board communication
1150
1151 [[image:image-20221115144824-10.png||height="421" width="705"]]
1152
1153 Select Ethernet Module
1154 Set the IP address of the PLC
1155
1156 [[image:image-20221115145228-11.png||height="674" width="708"]]
1157
1158 Read or write PLC data, in this document is read
1159
1160 [[image:image-20221115145553-12.png||height="424" width="711"]]
1161
1162 [[image:image-20221115145559-13.png||height="424" width="711"]]
1163
1164 **HMI Communication Setting**
1165
1166 [[image:image-20221115150003-14.png||height="425" width="712"]]
1167
1168 [[image:image-20221115150235-15.png||height="427" width="713"]]
1169
1170 [[image:image-20221115145559-13.png||height="424" width="711"]]
1171
1172 **HMI Communication Setting**
1173
1174 [[image:image-20221115150003-14.png||height="425" width="712"]]
1175
1176 [[image:image-20221115150235-15.png||height="427" width="713"]]
1177
1178 == **FX5U Serial Port Protocol** ==
1179
1180 Mitsubishi FX5U series PLC
1181
1182 **HMI Settings**
1183
1184 |**Item**|**Settings**|**Note**
1185 |Protocol|Mitsubishi FX5U|
1186 |Connection|RS422/RS485|
1187 |Baud rate|9600|
1188 |Data bit|7|
1189 |Parity|Odd|
1190 |Stop bit|1|
1191 |PLC station No.|1~~255|Need to be the same as PLC settings
1192
1193 **Address List**
1194
1195 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1196 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1197 |Y|Y|Y o|0~~303237|
1198 |M|M|M d|0~~99999|
1199 |B|B|B h|0~~7FFF|
1200 |F|F|F d|0~~32767|
1201 |SB|SB|SB h|0~~7FFF|
1202 |TS|TS|TS d|0~~1023|
1203 |TC|TC|TC d|0~~1023|
1204 |STS|STS|STS d|0~~1023|
1205 |STC|STC|STS d|0~~1023|
1206 |CS|CS|CS d|0~~1023|
1207 |CC|CC|CC d|0~~1023|
1208 |SM|SM|SM d|0~~9999|
1209 |L|L|L d|0~~32767|
1210 |S|S|S d|0~~4095|
1211 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1212 |TN|TN|TN d|0~~1023|
1213 |STN|STN|STN d|0~~1023|
1214 |CN|CN|CN d|0~~1023|
1215 |R|R|R d|0~~32767|
1216 |SW|SW|SW h|0~~7FFF|
1217 |Z|Z|Z d|0~~23|
1218 |D|D|D d|0~~7999|
1219 |SD|SD|SD d|0~~11999|
1220
1221 **PLC Settings (GX Works 3)**
1222
1223 Create a blank FX5U project
1224
1225 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1226
1227 (% style="text-align:center" %)
1228 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1229
1230 Select protocol in the setting item, and set parameters.
1231
1232 (% style="text-align:center" %)
1233 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1234
1235 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1236
1237 (% style="text-align:center" %)
1238 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1239
1240 Click the [Apply] button to finish the setting.
1241
1242 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1243
1244 (% style="text-align:center" %)
1245 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1246
1247 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1248
1249 Done.
1250
1251 **Cable Wiring**
1252
1253 * **RS485**
1254
1255 (% style="text-align:center" %)
1256 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1257
1258 (% style="text-align:center" %)
1259 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1260
1261 * **RS422**
1262
1263 (% style="text-align:center" %)
1264 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1265
1266 **✎Note:** COM3 only available in PI8000/PI9000 series.
1267
1268 == **L02 Serial Protocol** ==
1269
1270 Mitsubishi L02 series CPU built-in serial port.
1271
1272 **HMI Settings**
1273
1274 |=**Item**|=**Settings**|=**Note**
1275 |Protocol|Mitsubishi L02|
1276 |Connection|RS422|
1277 |Baud rate|115200|
1278 |Data bit|8|
1279 |Parity|Odd|
1280 |Stop bit|1|
1281 |PLC station No.|1~~255|Need to be the same as PLC settings
1282
1283 **Address List**
1284
1285 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1286 |Bit|X|X|X h|0~~FFFF|
1287 |Bit|Y|Y|Y h|0~~FFFF|
1288 |Bit|M|M|M d|0~~9999|
1289 |Bit|L|L|L d|0~~9999|
1290 |Bit|F|F|F d|0~~9999|
1291 |Bit|B|B|B h|0~~FFFF|
1292 |Bit|V|V|V d|0~~2047|
1293 |Bit|TC|TC|TC d|0~~9999|
1294 |Bit|SS|SS|SS d|0~~9999|
1295 |Bit|SC|SC|SC d|0~~9999|
1296 |Bit|CS|CS|CS d|0~~9999|
1297 |Bit|CC|CC|CC d|0~~9999|
1298 |Bit|SB|SB|SB h|0~~FFFF|
1299 |Bit|SM|SM|SM d|0~~2047|
1300 |Bit|STS|STS|STS d|0~~1023|
1301 |Bit|S|S|S d|0~~9999|
1302 |Bit|DX|DX|DX h|0~~FFFF|
1303 |Bit|DY|DY|DY h|0~~FFFF|
1304 |Bit|TS|TS|TS d|0~~9999|
1305 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1306 |Word|W|W|W h|0~~FFFF|
1307 |Word|TN|TN|TN d|0~~99999|
1308 |Word|SN|SN|SN d|0~~99999|
1309 |Word|CN|CN|CN d|0~~99999|
1310 |Word|R|R|R d|0~~99999|
1311 |Word|SW|SW|SW h|0~~FFFF|
1312 |Word|Z|Z|Z d|0~~99999|
1313 |Word|ZR|ZR|ZR h|0~~FFFF|
1314 |Word|D|D|D d|0~~99999|
1315
1316 **Communication Settings**
1317
1318 (% style="text-align:center" %)
1319 [[image:image-20220831105732-3.png]]
1320
1321 (% style="text-align:center" %)
1322 [[image:image-20220831110004-5.png]]
1323
1324 **Cable Wiring**
1325
1326 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1327
1328 Pin Definition Diagram
1329
1330 (% style="text-align:center" %)
1331 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1332
1333 == **L02 MELSEC (Ethernet) Protocol** ==
1334
1335 Mitsubishi Q series CPU built-in Ethernet port.
1336
1337 **HMI Settings**
1338
1339 |**Items**|**Settings**|**Note**
1340 |Protocol|MIT L02 CPU MELSEC|
1341 |Connection|Ethernet|
1342 |Port No.|1025|Must be the same as the PLC setting
1343 |PLC station No.|0|Must be the same as the PLC setting
1344
1345 **Address List**
1346
1347 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1348 |Bit|X|X|X h|0~~FFFF|
1349 |Bit|Y|Y|Y h|0~~FFFF|
1350 |Bit|M|M|M d|0~~9999|
1351 |Bit|L|L|L d|0~~9999|
1352 |Bit|F|F|F d|0~~9999|
1353 |Bit|B|B|B h|0~~FFFF|
1354 |Bit|V|V|V d|0~~2047|
1355 |Bit|TC|TC|TC d|0~~9999|
1356 |Bit|SS|SS|SS d|0~~9999|
1357 |Bit|SC|SC|SC d|0~~9999|
1358 |Bit|CS|CS|CS d|0~~9999|
1359 |Bit|CC|CC|CC d|0~~9999|
1360 |Bit|SB|SB|SB h|0~~FFFF|
1361 |Bit|SM|SM|SM d|0~~2047|
1362 |Bit|STS|STS|STS d|0~~1023|
1363 |Bit|S|S|S d|0~~9999|
1364 |Bit|DX|DX|DX h|0~~FFFF|
1365 |Bit|DY|DY|DY h|0~~FFFF|
1366 |Bit|TS|TS|TS d|0~~9999|
1367 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1368 |Word|W|W|W h|0~~FFFF|
1369 |Word|TN|TN|TN d|0~~99999|
1370 |Word|SN|SN|SN d|0~~99999|
1371 |Word|CN|CN|CN d|0~~99999|
1372 |Word|R|R|R d|0~~99999|
1373 |Word|SW|SW|SW h|0~~FFFF|
1374 |Word|Z|Z|Z d|0~~99999|
1375 |Word|ZR|ZR|ZR h|0~~FFFF|
1376 |Word|D|D|D d|0~~99999|
1377
1378 **Communication Settings**
1379
1380 Enable HMI Ethernet in [Project Settings];
1381
1382 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1383
1384 Set PLC IP in [Device IP] settings;
1385
1386 (% style="text-align:center" %)
1387 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1388
1389 **PLC Settings (GX Works2 )**
1390
1391 Create a project
1392
1393 Set PLC IP, subnet mask and gateway;
1394
1395 Select [Binary Code] as communication data code;
1396
1397 (% style="text-align:center" %)
1398 [[image:image-20221108202109-2.png||height="636" width="732"]]
1399
1400 Set PLC port number, for example 1025
1401
1402 (% style="text-align:center" %)
1403 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1404
1405 Save settings;
1406
1407 Download project into PLC device;
1408
1409 Restart PLC device;
1410
1411 **Cable Wiring**
1412
1413 (% style="text-align:center" %)
1414 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1415
1416 == **QJ71C24N MELSEC Protocol** ==
1417
1418 Mitsubishi QJ71C24N communication module built-in serial port;
1419
1420 **HMI Settings**
1421
1422 |**Items**|**Settings**|**Note**
1423 |Protocol|MIT QJ71 MELSEC|
1424 |Connection|422|
1425 |Baud rate|9600|
1426 |Data bit|8|
1427 |Parity|ODD|
1428 |Stop bit|1|
1429 |PLC station No.|1~~255|Need to be the same as PLC settings
1430
1431 **Address List**
1432
1433 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1434 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1435 |Y|Y|Y FFFF|0~~1FFF|
1436 |M|M|M DDDDD|0~~99999|
1437 |L|L|L DDDD|0~~8191|
1438 |F|F|F DDDD|0~~2047|
1439 |V|V|V DDDD|0~~2047|
1440 |B|B|B FFFF|0~~1FFF|
1441 |TS|TS|TS DDDD|0~~2047|
1442 |TC|TC|TC DDDD|0~~2047|
1443 |SS|SS|SS DDDD|0~~2047|
1444 |SC|SC|SC DDDD|0~~2047|
1445 |CS|CS|CS DDDD|0~~1023|
1446 |CC|CC|CC DDDD|0~~1023|
1447 |SB|SB|SB FFF|0~~7FF|
1448 |S|S|S D|0~~8191|
1449 |DX|DX|DX FFFF|0~~1FFF|
1450 |DY|DY|DY FFFF|0~~1FFF|
1451 |SM_|SM_|SM_ DDDD|8000~~9999|
1452 |SM|SM|SM DDDD|0~~2047|
1453 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1454 |D|D|D DDDDD|0~~12287|
1455 |W|W|W FFFF|0~~1FFF|
1456 |TN|TN|TN DDDD|0~~2047|
1457 |SN|SN|SN DDDD|0~~2047|
1458 |CN|CN|CN DDDD|0~~1023|
1459 |R|R|R DDDDD|0~~32767|
1460 |SW|SW|SW FFF|0~~7FF|
1461 |Z|Z|Z D|0~~15|
1462 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1463
1464 **Communication Settings**
1465
1466 (% style="text-align:center" %)
1467 [[image:image-20221109135738-1.png]]
1468
1469 (% style="text-align:center" %)
1470 [[image:image-20221109140016-3.png]]
1471
1472 Pin Definition Diagram
1473
1474 (% style="text-align:center" %)
1475 [[image:image-20221109140406-4.png]]
1476
1477 == **QJ71E71 MELSEC Protocol** ==
1478
1479 Mitsubishi QJ71E71 Ethernet communication module;
1480
1481 **HMI Settings**
1482
1483 |**Items**|**Settings**|**Note**
1484 |Protocol|MIT QJ71E71 MELSEC|
1485 |Connection|Ethernet|
1486 |Port No.|1025|Must be the same as the PLC setting
1487 |PLC station No.|0|Must be the same as the PLC setting
1488
1489 **Address List**
1490
1491 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1492 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1493 |Y|Y|Y h|0~~1FFF|
1494 |M|M|M d|0~~99999|
1495 |L|L|L d|0~~8191|
1496 |F|F|F d|0~~2047|
1497 |B|B|B h|0~~1FFF|
1498 |V|V|V d|0~~2047|
1499 |TS|TS|TS d|0~~2047|
1500 |TC|TC|TC d|0~~2047|
1501 |SS|SS|SS d|0~~2047|
1502 |SC|SC|SC d|0~~2047|
1503 |CS|CS|CS d|0~~1023|
1504 |CC|CC|CC d|0~~1023|
1505 |SB|SB|SB h|0~~7FF|
1506 |S|S|S d|0~~8191|
1507 |DX|DX|DX h|0~~1FFF|
1508 |DY|DY|DY h|0~~1FFF|
1509 |SM|SM|SM d|8000~~9999|
1510 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1511 |D|D|D d|0~~12287|
1512 |W|W|W h|0~~1FFF|
1513 |TN|TN|TN d|0~~2047|
1514 |SN|SN|SN d|0~~2047|
1515 |CN|CN|CN d|0~~1023|
1516 |R|R|R d|0~~32767|
1517 |SW|SW|SW h|0~~7FF|
1518 |Z|Z|Z d|0~~15|
1519 |ZR|ZR|ZR h|0~~FE7FF|
1520
1521 **HMI Communication Settings**
1522
1523 1) Enable HMI Ethernet in [Project Settings];
1524
1525 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1526
1527 2) Set PLC IP in [Device IP] settings
1528
1529 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1530
1531 **PLC Settings(GX Works2)**
1532
1533 * Click [Ethernet/CC IE/MELSECNET];
1534 * Please select [Ethernet] as network type;
1535 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1536 * Select [Online] as Mode;
1537 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1538 * Click [Operation setting] to set IP;
1539 * Select [Binary Code] as [Communication Data Code];
1540 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1541 * Click [Open setting]
1542 * Set protocol: TCP;
1543 * Set [unpassive] in [Open system];
1544 * Set [receive] in [Fixed buffer];
1545 * Set [procedure Exist] in [Fixed buffer communication];
1546 * Disable [Pairing open];
1547 * Set [No confirm] in [Existence confirmation];
1548 * Host station port number: 5009;
1549 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1550 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1551 * Download project into PLC and restart it
1552
1553 **Cable Wiring**
1554
1555
1556 (% style="text-align:center" %)
1557 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1558
1559 = Create communication with **Rockwell PLC** =
1560
1561 == **DF1 Protocol** ==
1562
1563 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1564
1565 **HMI Settings**
1566
1567 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1568 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
1569 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1570 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1571 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1572 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1573 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1574 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1575 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1576
1577 **Address List**
1578
1579 (% class="table-bordered" %)
1580 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1581 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1582 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1583 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
1584 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1585 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
1586 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1587 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1588 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1589 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1590 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1591 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
1592
1593 **Cable Wiring**
1594
1595 (% style="text-align:center" %)
1596 [[image:AB.gif]]
1597
1598 == **DF1 Advanced Protocol** ==
1599
1600 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1601
1602 **HMI Settings**
1603
1604 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1605 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
1606 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1607 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1608 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1609 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1610 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1611 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1612 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1613
1614 **Address List**
1615
1616 (% class="table-bordered" %)
1617 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1618 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1619 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1620 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1621 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
1622 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1623 Bit data file B0~~B99
1624
1625 First two digits is for file number
1626
1627 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
1628 )))
1629 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
1630 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1631 Integer data file bit format N0~~N99
1632
1633 First two digits is for file number
1634
1635 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
1636 )))
1637 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1638 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1639 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1640 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1641 Timer Preset Value
1642
1643 First two digits is for file number
1644
1645 For example, TNS99255 represents file number T99, address 255.
1646 )))
1647 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1648 Timer Accumulator Value
1649
1650 First two digits is for file number
1651
1652 For example, TNP99255 represents file number T99, address 255.
1653 )))
1654 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1655 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1656 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1657 Counter Preset Value
1658
1659 First two digits is for file number
1660
1661 For example, CNS99255 represents file number C99, address 255.
1662 )))
1663 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1664 Counter Accumulator Value
1665
1666 First two digits is for file number
1667
1668 For example, CNP99255 represents file number C99, address 255.
1669 )))
1670 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
1671 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1672 Integer data file
1673
1674 First two digits is for file number
1675
1676 For example, NN99255 represents file number N99, address 255.
1677 )))
1678 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
1679 Only able to communicate with file number F8
1680 )))
1681 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1682 Floating point data file
1683
1684 First two digits is for file number
1685
1686 For example, FN99255 represents file number F99, address 255.
1687 )))
1688 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
1689
1690 **Cable Wiring**
1691
1692 (% style="text-align:center" %)
1693 [[image:AB.gif]]
1694
1695 == **MicroLogix Protocol** ==
1696
1697 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
1698
1699 **HMI Settings**
1700
1701 (% class="table-bordered" %)
1702 |**Item**|**Settings**|**Note**
1703 |Protocol|Allen-Bradlley MicroLogix|
1704 |Connection|RS232|
1705 |Baud rate|19200|
1706 |Data bit|8|
1707 |Parity|None|
1708 |Stop bit|1|
1709 |PLC station No.|1|
1710
1711 **Address List**
1712
1713 (% class="table-bordered" %)
1714 |**Type**|**Device registers**|**Format**|**Range**|**Note**
1715 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
1716 |O|O d.d|0.0~~255.15|
1717 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1718 |S|S d.d|0.0~~255.15|
1719 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1720 |(% rowspan="9" %)Word|S|S d|0~~255|
1721 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
1722 |TP|TP nnhh|0~~ffff
1723 |CS|CS nnhh|0~~ffff
1724 |CP|CP nnhh|0~~ffff
1725 |N|N nnhh|0~~ffff
1726 |C|C nnhh|0~~ffff
1727 |T|T nnhh|0~~ffff
1728 |R|R nnhh|0~~ffff
1729
1730 **Cable Wiring**
1731
1732
1733 (% style="text-align:center" %)
1734 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
1735
1736 == **CompactLogix FreeTag Ethernet protocol** ==
1737
1738 Allen-Brandly CompactLogix
1739
1740 **HMI Settings**
1741
1742 (% class="table-bordered" %)
1743 |**Items**|**Settings**|**Note**
1744 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
1745 |Connection|Ethernet|
1746 |Port No.|44818|
1747
1748 **PLC Setting**
1749
1750 Create new tags
1751
1752 (% style="text-align:center" %)
1753 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
1754
1755 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
1756
1757 (% style="text-align:center" %)
1758 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
1759
1760 Import labels, please open [Communication] window and click [Import label];
1761
1762 Select csv file, all tags will be displayed as belows;
1763
1764 (% style="text-align:center" %)
1765 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
1766
1767 **✎Note:**
1768
1769 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
1770
1771 (% style="text-align:center" %)
1772 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
1773
1774 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
1775
1776 **Communication settings in HMI**
1777
1778 Enable HMI Ethernet in [Project Settings];
1779
1780 (% style="text-align:center" %)
1781 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
1782
1783 Set PLC IP in [Device IP] settings;
1784
1785 (% style="text-align:center" %)
1786 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1787
1788 **Cable Wiring**
1789
1790 (% style="text-align:center" %)
1791 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
1792
1793 == **MicroLogix 1200** **protocol** ==
1794
1795 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
1796
1797 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
1798 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
1799 * **Word address S:** The word address ranges from 0 to 255 (decimal).
1800 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
1801
1802 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
1803
1804 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
1805 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
1806 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
1807 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
1808 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
1809 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
1810 |**PLC word address type**|**Address format**|**Address range**
1811 |S|ddd|S0 ~~ 255
1812 |TS|ffff|TS0 ~~ FFFF
1813 |TP|ffff|TP0 ~~ FFFF
1814 |CS|ffff|CS0 ~~ FFFF
1815 |CP|ffff|CP0 ~~ FFFF
1816 |N|ffff|N0 ~~ FFFF
1817 |F|ffff|F0 ~~ FFFF
1818
1819 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
1820
1821 == **S7-200 Smart Ethernet Protocol** ==
1822
1823 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1824
1825 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1826
1827 **HMI Setting**
1828
1829 (% class="table-bordered" %)
1830 |**Items**|**Settings**|**Note**
1831 |Protocol|Simens S7-200 Smart Ethernet|
1832 |Connection|Ethernet|
1833 |Port No.|102|
1834 |PLC station No.|2|
1835
1836 **Address List**
1837
1838 (% class="table-bordered" %)
1839 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1840 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1841 |Q|Q|Q ddddd.o|0.0~~99999.7|
1842 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1843 |V|V|V ddddd.o|0.0~~99999.7|
1844 |M|M|M ddddd.o|0.0~~99999.7|
1845 |SM|SM|ddddd.o|0.0~~99999.7|
1846 |S|S|ddddd.o|0.0~~99999.7|Read only
1847 |T|T|ddddd|0~~99999|Timer state, read only
1848 |C|C|ddddd|0~~99999|Counter state, read only
1849 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1850 |Q|QW|QW ddddd|0~~99999|
1851 |AI|AIW|AIW ddddd|0~~99999|
1852 |AQ|VB|VB ddddd|0~~99999|
1853 |V|VW|VW ddddd|0~~99998|(((
1854 VW0=VB (0~~1)
1855
1856 VW2=VB (2~~3)
1857
1858 Address value is a multiple of 2
1859 )))
1860 |V|VD|VD ddddd|0~~99998|(((
1861 VD0=VB (0~~3)
1862
1863 VD2=VB (4~~7)
1864
1865 Address value is a multiple of 4
1866 )))
1867 |M|MB|MB ddddd|0~~99999|
1868 |M|MW|MW ddddd|0~~99999|(((
1869 MW0=MB(0~~1)
1870
1871 MW2=MB(2~~3)
1872
1873 Address value is a multiple of 2
1874 )))
1875 |M|MD|MD ddddd|0~~99999|(((
1876 MD0=MB(0~~3)
1877
1878 MD4=MB(4~~7)
1879
1880 Address value is a multiple of 4
1881 )))
1882 |T|TW|TW ddddd|0~~99999|Value of timer
1883 |C|CW|CW ddddd|0~~99999|Value of counter
1884 |W|SW|SW ddddd|0~~99999|
1885
1886 **Communication Settings**
1887
1888 Enable HMI Ethernet in [Project Settings];
1889
1890 (% style="text-align:center" %)
1891 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1892
1893 Set PLC IP in [Device IP] settings;
1894
1895 (% style="text-align:center" %)
1896 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1897
1898 * PLC IP Address: PLC IP
1899 * PLC pot No.: 102(fixed)
1900 * Network:TCP_Client_2N(fixed)
1901
1902 (% style="text-align:center" %)
1903 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1904
1905 * Wait timeout: depend on actual network situation (more than 1500 ms)
1906
1907 **Cable Wiring**
1908
1909 (% style="text-align:center" %)
1910 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1911
1912 == **S7-300 Ethernet Protocol** ==
1913
1914 Supported Series: Siemens S7-300 series PLC
1915
1916 **HMI Setting**
1917
1918 (% class="table-bordered" %)
1919 |**Items**|**Settings**|**Note**
1920 |Protocol|Simens S7-300 Ethernet|
1921 |Connection|Ethernet|
1922 |Port No.|102|
1923 |PLC station No.|2|Need to be same as the PLC setting
1924
1925 **Address List**
1926
1927 (% class="table-bordered" %)
1928 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1929 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1930 |Q|Q|Q ddddd.o|0.0~~99999.7|
1931 |M|M|M ddddd.o|0.0~~99999.7|
1932 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
1933 nnnn: block number;
1934
1935 dddd: address;
1936 )))
1937 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
1938 |Q|QW|QW ddddd|0~~99999|
1939 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
1940 |MW|MW ddddd|0~~99999|(((
1941 MW0=MB(0~~1)
1942
1943 MW2=MB(2~~3)
1944
1945 Address value is a multiple of 2
1946 )))
1947 |MD|MD ddddd|0~~99999|(((
1948 MD0=MB(0~~3)
1949
1950 MD4=MB(4~~7)
1951
1952 Address value is a multiple of 4
1953 )))
1954 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
1955 nnnn: block number;
1956
1957 dddd: address
1958 )))
1959 |DBxDBW|DBxDBW nnnndddd|0~~99999999
1960 |DBxDBD|DBxDBD nnnndddd|0~~99999999
1961
1962 **Communication Settings**
1963
1964 Enable HMI Ethernet in [Project Settings];
1965
1966 (% style="text-align:center" %)
1967 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1968
1969 Set PLC IP in [Device IP] settings;
1970
1971 (% style="text-align:center" %)
1972 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1973
1974 * PLC IP Address: PLC IP
1975 * PLC pot No.: 102(fixed)
1976 * Network:TCP_Client_2N(fixed)
1977
1978 (% style="text-align:center" %)
1979 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1980
1981 * Wait timeout: depend on actual network situation (more than 1500 ms)
1982
1983 **Cable Wiring**
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1987
1988 == **S7-1200 Ethernet Protocol** ==
1989
1990 Supported Series: Siemens S7-1200
1991
1992 **HMI Setting**
1993
1994 (% class="table-bordered" %)
1995 |**Items**|**Settings**|**Note**
1996 |Protocol|Siemens S7-1200|
1997 |Connection|Ethernet|
1998 |Port No.|102|
1999 |PLC station No.|2|
2000
2001 **Address List**
2002
2003 (% class="table-bordered" %)
2004 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2005 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2006 d:0~-~-9999
2007
2008 o:0-7
2009 )))|
2010 |Q|Q|Q d.o|(((
2011 d:0~-~-9999
2012
2013 o:0-7
2014 )))|
2015 |M|M|M d.o|(((
2016 d:0~-~-9999
2017
2018 o:0-7
2019 )))|
2020 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2021 nn:0-9999,
2022
2023 dddd:0-9999,
2024
2025 o:0-7
2026 )))|(((
2027 nn:DB No.
2028
2029 dddd:address value
2030
2031 o: digit address
2032 )))
2033 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2034 |M|MW|MW d|d:0-99999|(((
2035 MW0=MB(0~~1)
2036
2037 MW2=MB(2~~3)
2038
2039 Address value is a multiple of 2
2040 )))
2041 |M|MD|MD d|d:0-99999|(((
2042 MD0=MB(0~~3)
2043
2044 MD4=MB(4~~7)
2045
2046 Address value is a multiple of 4
2047 )))
2048 |I|IW|IW d|d:0-99999|
2049 |Q|QW|QW d|d:0-99999|
2050 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2051 nn:0-9999
2052
2053 dddd:0-9999
2054 )))|(((
2055 nn:DB No.
2056
2057 dddd:address value
2058 )))
2059 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2060 nn:0-9999
2061
2062 dddd:0-9999
2063 )))|(((
2064 nn:DB No.
2065
2066 dddd:address value
2067
2068 Address value is a multiple of 2
2069 )))
2070 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2071 nn:0-9999
2072
2073 dddd:0-9999
2074 )))|(((
2075 nn:DB No.
2076
2077 dddd:address value
2078
2079 Address value is a multiple of 4
2080 )))
2081
2082 **Communication Settings**
2083
2084 Enable HMI Ethernet in [Project Settings];
2085
2086 (% style="text-align:center" %)
2087 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2088
2089 Set PLC IP in [Device IP] settings;
2090
2091 (% style="text-align:center" %)
2092 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2093
2094 **✎Note:**
2095
2096 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2097 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2098 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2099 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2100
2101 **PLC Settings**
2102
2103 Add BD
2104
2105 * Please uncheck [Symbolic access only] option;
2106
2107 (% style="text-align:center" %)
2108 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2109
2110 Address settings, using BD2 as example.
2111
2112 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2113 * 2 represent DB block number
2114 * xxxx represent address
2115
2116 **Such as:**
2117
2118 * DBxDBB20000 = DB2.DBB0
2119 * DBxDBW20004 = DB2.DBW4
2120
2121 (% style="text-align:center" %)
2122 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2123
2124 **How to connect with S7-1200 Firmware V4.0**
2125
2126 PLC configuration
2127
2128 * Double click [device configuration] in Siemens via software
2129 * Double click [protection] to enter protection configuration screen
2130
2131 (% style="text-align:center" %)
2132 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2133
2134 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2138
2139 DB settings
2140
2141 * Right click [DB], select [properties]
2142 * Uncheck [optimized block access]
2143
2144 **Cable Wiring**
2145
2146 (% style="text-align:center" %)
2147 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2148
2149 == **S7-XXX Ethernet Protocol** ==
2150
2151 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2152
2153 **HMI Setting**
2154
2155 (% class="table-bordered" style="width:823px" %)
2156 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2157 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2158 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2159 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2160 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2161 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2162
2163 Slot from TIA Portal is equal to Device No. of PIStudio
2164
2165 Rack from TIA Portal is equal to HMI No. of PIStudio
2166
2167 (% style="text-align:center" %)
2168 [[image:S7-XXXCommunication Settings.png]]
2169
2170 (% style="text-align:center" %)
2171 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2172
2173 **Address List**
2174
2175 (% class="table-bordered" %)
2176 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2177 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2178 d:0~-~-9999
2179
2180 o:0-7
2181 )))|
2182 |Q|Q|Q d.o|(((
2183 d:0~-~-9999
2184
2185 o:0-7
2186 )))|
2187 |M|M|M d.o|(((
2188 d:0~-~-9999
2189
2190 o:0-7
2191 )))|
2192 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2193 nn:0-9999,
2194
2195 dddd:0-9999,
2196
2197 o:0-7
2198 )))|(((
2199 nn:DB No.
2200
2201 dddd:address value
2202
2203 o: digit address
2204 )))
2205 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2206 |M|MW|MW d|d:0-99999|(((
2207 MW0=MB(0~~1)
2208
2209 MW2=MB(2~~3)
2210
2211 Address value is a multiple of 2
2212 )))
2213 |M|MD|MD d|d:0-99999|(((
2214 MD0=MB(0~~3)
2215
2216 MD4=MB(4~~7)
2217
2218 Address value is a multiple of 4
2219 )))
2220 |I|IW|IW d|d:0-99999|
2221 |Q|QW|QW d|d:0-99999|
2222 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2223 nn:0-9999
2224
2225 dddd:0-9999
2226 )))|(((
2227 nn:DB No.
2228
2229 dddd:address value
2230 )))
2231 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2232 nn:0-9999
2233
2234 dddd:0-9999
2235 )))|(((
2236 nn:DB No.
2237
2238 dddd:address value
2239
2240 Address value is a multiple of 2
2241 )))
2242 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2243 nn:0-9999
2244
2245 dddd:0-9999
2246 )))|(((
2247 nn:DB No.
2248
2249 dddd:address value
2250
2251 Address value is a multiple of 4
2252 )))
2253
2254 **Communication Settings**
2255
2256 Enable HMI Ethernet in [Project Settings];
2257
2258 (% style="text-align:center" %)
2259 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2260
2261 Set PLC IP in [Device IP] settings;
2262
2263 (% style="text-align:center" %)
2264 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2265
2266 **✎Note:**
2267
2268 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2269 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2270
2271 **Cable Wiring**
2272
2273 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2274
2275 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
2276
2277 Supported Series: Siemens Logo 0BA0, 0BA1 series
2278
2279 **HMI Settings**
2280
2281 (% class="table-bordered" %)
2282 |**Items**|**Settings**|**Note**
2283 |Protocol|Siemens LOGO|
2284 |Connection|Ethernet|
2285 |Port No.|102|
2286 |PLC station No.|2|
2287
2288 **Address List**
2289
2290 (% class="table-bordered" %)
2291 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2292 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2293 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2294 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2295 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2296 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2297 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2298 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2299 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2300 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2301 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2302 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2303 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2304 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2305 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2306 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2307
2308 **PLC Settings in LOGO Software:**
2309
2310 Click [Tools]~-~-[Ethernet Connections],shown as below.
2311
2312 (% style="text-align:center" %)
2313 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2314
2315 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2316
2317 (% style="text-align:center" %)
2318 [[image:image-20221228142937-4.png]]
2319
2320 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2321
2322 (% style="text-align:center" %)
2323 [[image:image-20221228143047-5.png]]
2324
2325 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2326
2327 (% style="text-align:center" %)
2328 [[image:image-20221228143246-6.png]]
2329
2330
2331 **HMI Communication Settings**
2332
2333 Set PLC IP in [Device IP] settings;
2334
2335 (% style="text-align:center" %)
2336 [[image:image-20221228143614-7.png]]
2337
2338 Enable HMI Ethernet in [Project Settings];
2339
2340 (% style="text-align:center" %)
2341 [[image:image-20221228144229-9.png]]
2342
2343 TSAP setting
2344
2345 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2346 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
2347 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
2348 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
2349 ie, ig series: use HSW1200, HSW1201.
2350 HMI V2.0: use HSW1200, HSW1201.
2351
2352 **✎Note:**
2353
2354 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
2355 * HSW10119/HSW1201 is set up as shown.
2356 * (((
2357 (% style="text-align:center" %)
2358 [[image:image-20221228144800-11.png]]
2359 )))
2360 * (((
2361 (% style="text-align:center" %)
2362 [[image:image-20221228144708-10.png]]
2363 )))
2364
2365 * AI word address and Ibit address are read-only and cannot be written on HMI.
2366 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
2367 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
2368 * Written value of RTC cannot exceed 255.
2369
2370 **Cable Wiring**
2371
2372 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2373
2374 == S7-300 232 ==
2375
2376 **HMI Setting:**
2377
2378 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2379 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
2380 |=**PLC I/F**|RS232| |
2381 |=**Baud rate**|19200|9600,19200|
2382 |=**Data bits**|8| |
2383 |=**Parity**|Odd| |
2384 |=**Stop bits**|1| |
2385 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
2386
2387 **Device Address**
2388
2389 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2390 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
2391 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
2392 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
2393 |=Word|(((
2394 DB1 to DB99
2395 )))|DDDDDo|0 ~~ 655327|
2396 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
2397 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
2398 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
2399 |=Double word|MD|DDDD|0 ~~ 4094|
2400 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
2401 Data Register Double Word (must be even)
2402 )))
2403 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
2404
2405 **Cable Wiring**
2406
2407 (% style="text-align:center" %)
2408 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
2409
2410 = Create communication with **Omron** PLC =
2411
2412 == CJ TCP FINS Ethemet  Protocol ==
2413
2414 Supported device:CJ series、CJ1W-EIP21
2415
2416 **HMI Settings**
2417
2418 |=**Items**|=**Settings**|=**Note**
2419 |Protocol|OMRON CJ TCP FINS Ethemet|
2420 |Connection|Ethernet|
2421 |Port No.|9600|
2422 |Device No.|0|
2423 |HMI No.|0|(((
2424
2425 )))
2426
2427 **Address List**
2428
2429 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2430 |Bit|CIO|CIO|CIO d|0~~99999|
2431 |Bit|W|W|W d|0~~99999|
2432 |Bit|D|D|D d|0~~99999|
2433 |Bit|H|H|H d|0~~99999|
2434 |Bit|A|A|A d|0~~99999|
2435 |Bit|T|T|T h|0~~99999|
2436 |Bit|CF|CF|CF d|0~~99999|
2437 |Bit|FF|FF|FF d|0~~99999|
2438 |Bit|C|C|C d|0~~99999|
2439 |Bit|EM0|EM0|EM0 d|0~~99999|
2440 |Bit|EM1|EM1|EM1 d|0~~99999|
2441 |Bit|EM2|EM2|EM2 d|0~~99999|
2442 |Bit|EM3|EM3|EM3 d|0~~99999|
2443 |Bit|EM4|EM4|EM4 d|0~~99999|
2444 |Bit|EM5|EM5|EM5 h|0~~99999|
2445 |Bit|EM6|EM6|EM6 d|0~~99999|
2446 |Bit|EM7|EM7|EM7 d|0~~99999|
2447 |Bit|EM8|EM8|EM8 d|0~~99999|
2448 |Bit|EM9|EM9|EM9 d|0~~99999|
2449 |Bit|EMA|EMA|EMA d|0~~99999|
2450 |Bit|EMB|EMB|EMB d|0~~99999|
2451 |Bit|EMC|EMC|EMC d|0~~99999|
2452 |Bit|Lamp|Lamp|Lamp d|0~~0|
2453 |Word|CIO|CIO|CIO d|0~~99999|
2454 |Word|W|W|W d|0~~99999|
2455 |Word|D|D|D d|0~~99999|
2456 |Word|H|H|H d|0~~99999|
2457 |Word|A|A|A d|0~~99999|
2458 |Word|T|T|T h|0~~99999|
2459 |Word|CF|CF|CF d|0~~99999|
2460 |Word|FF|FF|FF d|0~~99999|
2461 |Word|C|C|C d|0~~99999|
2462 |Word|EM0|EM0|EM0 d|0~~99999|
2463 |Word|EM1|EM1|EM1 d|0~~99999|
2464 |Word|EM2|EM2|EM2 d|0~~99999|
2465 |Word|EM3|EM3|EM3 d|0~~99999|
2466 |Word|EM4|EM4|EM4 d|0~~99999|
2467 |Word|EM5|EM5|EM5 h|0~~99999|
2468 |Word|EM6|EM6|EM6 d|0~~99999|
2469 |Word|EM7|EM7|EM7 d|0~~99999|
2470 |Word|EM8|EM8|EM8 d|0~~99999|
2471 |Word|EM9|EM9|EM9 d|0~~99999|
2472 |Word|EMA|EMA|EMA d|0~~99999|
2473 |Word|EMB|EMB|EMB d|0~~99999|
2474 |Word|EMC|EMC|EMC d|0~~99999|
2475 |Word|IR|IR|IR d|0~~99999|
2476 |Word|DR|DR|DR d|0~~99999|
2477
2478 **Configure the communication protocol**
2479
2480 (% style="text-align:center" %)
2481 [[image:image-20220830143348-1.png]]
2482
2483 (% style="text-align:center" %)
2484 [[image:image-20220830143511-2.png]]
2485
2486 **Configure CJ1W-EIP21 connect with HMI**
2487
2488 (% style="text-align:center" %)
2489 [[image:ftEVGvAprh.png]]
2490
2491 Select TCP_Client_2N
2492
2493 (% style="text-align:center" %)
2494 [[image:RURXWcgyCd.png]]
2495
2496 **Cable Wiring**
2497
2498 Pin Definition Diagram
2499
2500 (% style="text-align:center" %)
2501 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2502
2503 == **CP1E/CP1H serial protocol** ==
2504
2505 Supported device: OMRON CS1(CP1E/CP1H)
2506
2507 **HMI Settings**
2508
2509 |=**Items**|=**Settings**|=**Note**
2510 |Protocol|OMRON CS1(CP1E/CP1H)|
2511 |Connection|RS232 (9600, 2, 7, EVEN)|
2512 |Port No.|None|
2513 |PLC station No.|0|
2514
2515 **Address List**
2516
2517 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2518 |Bit|CIO|CIO|CIO d|0~~99999|
2519 |Bit|W|W|W d|0~~99999|
2520 |Bit|D|D|D d|0~~99999|
2521 |Bit|H|H|H d|0~~99999|
2522 |Bit|A|A|A d|0~~99999|
2523 |Bit|TF|T|T h|0~~99999|
2524 |Bit|CF|CF|CF d|0~~99999|
2525 |Bit|T|FF|FF d|0~~99999|
2526 |Bit|C|C|C d|0~~99999|
2527 |Bit|EM0|EM0|EM0 d|0~~99999|
2528 |Bit|EM1|EM1|EM1 d|0~~99999|
2529 |Bit|EM2|EM2|EM2 d|0~~99999|
2530 |Bit|EM3|EM3|EM3 d|0~~99999|
2531 |Bit|EM4|EM4|EM4 d|0~~99999|
2532 |Bit|EM5|EM5|EM5 h|0~~99999|
2533 |Bit|EM6|EM6|EM6 d|0~~99999|
2534 |Bit|EM7|EM7|EM7 d|0~~99999|
2535 |Bit|EM8|EM8|EM8 d|0~~99999|
2536 |Bit|EM9|EM9|EM9 d|0~~99999|
2537 |Bit|EMA|EMA|EMA d|0~~99999|
2538 |Bit|EMB|EMB|EMB d|0~~99999|
2539 |Bit|EMC|EMC|EMC d|0~~99999|
2540 |Word|CIO|CIO|CIO d|0~~99999|
2541 |Word|W|W|W d|0~~99999|
2542 |Word|D|D|D d|0~~99999|
2543 |Word|H|H|H d|0~~99999|
2544 |Word|A|A|A d|0~~99999|
2545 |Word|T|T|T h|0~~99999|
2546 |Word|CIO|CF|CF d|0~~99999|
2547 |Word|C|C|C d|0~~99999|
2548 |Word|EM0|EM0|EM0 d|0~~99999|
2549 |Word|EM1|EM1|EM1 d|0~~99999|
2550 |Word|EM2|EM2|EM2 d|0~~99999|
2551 |Word|EM3|EM3|EM3 d|0~~99999|
2552 |Word|EM4|EM4|EM4 d|0~~99999|
2553 |Word|EM5|EM5|EM5 h|0~~99999|
2554 |Word|EM6|EM6|EM6 d|0~~99999|
2555 |Word|EM7|EM7|EM7 d|0~~99999|
2556 |Word|EM8|EM8|EM8 d|0~~99999|
2557 |Word|EM9|EM9|EM9 d|0~~99999|
2558 |Word|EMA|EMA|EMA d|0~~99999|
2559 |Word|EMB|EMB|EMB d|0~~99999|
2560 |Word|EMC|EMC|EMC d|0~~99999|
2561 |Word|IR|IR|IR d|0~~99999|
2562 |Word|DR|DR|DR d|0~~99999|
2563
2564 **Configure the communication protocol**
2565
2566 (% style="text-align:center" %)
2567 [[image:image-20220902153118-1.png]]
2568
2569 (% style="text-align:center" %)
2570 [[image:image-20220902151322-2.png]]
2571
2572 **Cable Wiring**
2573
2574 (% style="text-align:center" %)
2575 [[image:image-20220902153949-2.png]]
2576
2577 Pin Definition Diagram
2578
2579 (% style="text-align:center" %)
2580 [[image:image-20220902154056-3.png]]
2581
2582 == **EC55 Protocol** ==
2583
2584 Supported device: EC55 temperature instrument
2585
2586 **1)HMI Settings**
2587
2588 |**Items**|**Settings**|**Note**
2589 |Protocol|Omron EC55|
2590 |Connection|RS485 (9600, 2, 7, EVEN)|
2591 |Port No.|None|
2592 |PLC station No.|0|
2593
2594 **2)Address List**
2595
2596 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2597 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2598 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2599 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2600 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2601 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2602 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2603 |CP|-|0-6|Read controller intrinsic property
2604 |CS|-|0-2|Read controller states
2605 |CA|-|0-17|Action command
2606
2607 **3)Device Settings**
2608
2609 Omron E5CC PLC configuration
2610
2611 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2612
2613 (% style="text-align:center" %)
2614 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2615
2616 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2617
2618 (% style="text-align:center" %)
2619 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2620
2621 **✎Note:** The communication settings for HMI should be consistent with this setting.
2622
2623 **Cable Wiring**
2624
2625 (% style="text-align:center" %)
2626 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2627
2628 (% style="text-align:center" %)
2629 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2630
2631 **✎Note:**
2632
2633 * COM3 only available in PI8000/PI9000 series.
2634 * CA address could not support continuous writing function;
2635 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2636 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2637 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2638 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2639 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2640 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2641 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2642
2643 == **EtherNet/IP NX series Protocol** ==
2644
2645 Supported series: Omron NX/NJ series
2646
2647 **HMI Setting**
2648
2649 |**Items**|**Settings**|**Note**
2650 |Protocol|Omron NX Ethernet/IP|
2651 |Connection|Ethernet|
2652 |Port No.|44818|
2653 |PLC station No.|1|
2654
2655 **Instruction**
2656
2657 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2658
2659 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2660
2661 (% style="text-align:center" %)
2662 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2663
2664 **Export labels from Sysmac Studio**
2665
2666 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2667
2668 (% style="text-align:center" %)
2669 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2670
2671 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2672
2673 Click [Label manage];
2674
2675 (% style="text-align:center" %)
2676 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2677
2678 Click [Import labels] and then select the file exported in step 1;
2679
2680 (% style="text-align:center" %)
2681 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2682
2683 The Import Status field shows the result, click [OK] to finish importing address labels;
2684
2685 (% style="text-align:center" %)
2686 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2687
2688 **Communication Settings**
2689
2690 Enable HMI Ethernet in [Project Settings];
2691
2692 (% style="text-align:center" %)
2693 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2694
2695 Set PLC IP in [Device IP] settings;
2696
2697 (% style="text-align:center" %)
2698 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2699
2700 (% style="text-align:center" %)
2701 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2702
2703 **Cable Wiring**
2704
2705 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2706
2707 == CV/CJ1M/CS1H ==
2708
2709 **HMI Setting:**
2710
2711 |=(% scope="row" %)**Parameters**|=**Recommended**
2712 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2713 |=**PLC I/F**|RS232
2714 |=**Baud rate**|9600
2715 |=**Data bits**|7
2716 |=**Parity**|Even
2717 |=**Stop bits**|2
2718 |=**PLC sta. no.**|0
2719
2720 **PLC Setting:**
2721
2722 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2723
2724 **Device Address:**
2725
2726 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2727 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2728 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2729 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2730 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2731 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2732 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2733 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2734 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2735 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2736 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2737 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2738 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2739 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2740 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2741 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2742 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2743 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2744 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2745 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2746 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2747 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2748 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2749 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2750
2751 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2752 |=W|LR_W|DDDD|0 ~~ 4095|
2753 |=W|TC|DDD|0 ~~ 511|
2754 |=W|DM|DDDD|0 ~~ 9999|Data Register
2755
2756 **Wiring Diagram:**
2757
2758 **RS-232**
2759
2760 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2761
2762 Communication Module:
2763
2764 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2765
2766 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2767
2768 (% style="text-align:center" %)
2769 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2770
2771 = Create communication with Xinje** PLC** =
2772
2773 == XC serial protocol ==
2774
2775 **HMI Settings**
2776
2777 |**Item**|**Settings**|**Note**
2778 |Protocol|XINJE XC MODBUS|
2779 |Connection|RS232|
2780 |Baud rate|19200|
2781 |Data bit|8|
2782 |Parity|EVEN|
2783 |Stop bit|1|
2784 |PLC station No.|1|
2785
2786 **Address List**
2787
2788 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2789 |Bit|M|M|M d|0~~8511|
2790 |Bit|X|X|X o|0~~1747|
2791 |Bit|Y|Y|Y o|0~~1747|
2792 |Bit|S|S|S d|0~~1023|
2793 |Bit|T|T|T d|0~~4095|
2794 |Bit|C|C|C d|0~~634|
2795 |Word|D|D|D d|0~~8511|
2796 |Word|TD|TD|TD d|0~~618|
2797 |Word|CD|CD|CD d|0~~634|
2798 |Word|FD|FD|FD d|0~~8511|
2799
2800 **Configure the communication protocol**
2801
2802 (% style="text-align:center" %)
2803 [[image:image-20220830154105-1.png]]
2804
2805 (% style="text-align:center" %)
2806 [[image:image-20220830154159-3.png]]
2807
2808 **Cable Wiring**
2809
2810 Figure
2811
2812 [[image:image-20220830155728-4.png]]
2813
2814 Pin Definition Diagram
2815
2816 (% style="text-align:center" %)
2817 [[image:image-20220830154131-2.png]]
2818
2819 == XD serial protocol ==
2820
2821 **HMI Settings**
2822
2823 Supported Series: Xinjie XD/XE Series PLC
2824
2825 |=**Item**|=**Settings**|=**Note**
2826 |Protocol|XINJE XD/XC MODBUS|
2827 |Connection|RS232|
2828 |Baud rate|19200|
2829 |Data bit|8|
2830 |Parity|EVEN|
2831 |Stop bit|1|
2832 |PLC station No.|1|
2833
2834 **Address List**
2835
2836 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2837 |Bit|M|M|M d|0~~74999|
2838 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2839 |Bit|X2xx|X2xx|X2xx o|0~~277|
2840 |Bit|X|X|X o|0~~77|
2841 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2842 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2843 |Bit|Y|Y|Y o|0~~4095|
2844 |Bit|SM|SM|SM d|0~~4999|(((
2845
2846 )))
2847 |Bit|T|T|T d|0~~4999|
2848 |Bit|C|C|C d|0~~4999|
2849 |Bit|ET|ET|ET d|0~~31|
2850 |Bit|SE|SE|SE d|0~~31|
2851 |Bit|HM|HM|HM d|0~~11999|
2852 |Bit|HSC|HSC|HSC d|0~~39|
2853 |Bit|HS|HS|HS d|0~~999|
2854 |Bit|HT|HT|HT d|0~~1999|
2855 |Bit|HC|HC|HC d|0~~1999|
2856 |Bit|S|S|S d|0~~7999|
2857 |Word|D|D|D d|0~~69999|
2858 |Word|ID|ID|ID d|0~~99|
2859 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2860 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2861 |Word|QD|QD|QD d|0~~99|
2862 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2863 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2864 |Word|SD|SD|SD d|0~~4999|
2865 |Word|TD|TD|TD d|0~~575|
2866 |Word|CD|CD|CD d|0~~575|
2867 |Word|ETD|ETD|ETD d|0~~31|
2868 |Word|HD|HD|HD d|0~~24999|
2869 |Word|HSD|HSD|HSD d|0~~1023|
2870 |Word|HTD|HTD|HTD d|0~~95|
2871 |Word|HCD|HCD|HCD d|0~~95|
2872 |Word|HSCD|HSCD|HSCD d|0~~31|
2873 |Word|FD|FD|FD d|0~~8191|
2874 |Word|SFD|SFD|SFD d|0~~5999|
2875 |Word|FS|FS|FS d|0~~47|
2876
2877 **Configure the communication protocol**
2878
2879 (% style="text-align:center" %)
2880 [[image:image-20220830160042-1.png]]
2881
2882 (% style="text-align:center" %)
2883 [[image:image-20220830160129-2.png]]
2884
2885 **Cable Wiring**
2886
2887 (% style="text-align:center" %)
2888 [[image:image-20220905093902-1.png]]
2889
2890 Pin Definition Diagram
2891
2892 (% style="text-align:center" %)
2893 [[image:image-20220830160232-3.png]]
2894
2895 = Create communication with Panasonic** PLC** =
2896
2897 == **FP serial protocol** ==
2898
2899 **1)HMI Settings**
2900
2901 |**Item**|**Settings**|**Note**
2902 |Protocol|Panasonic FP MFWTOCOL|
2903 |Connection|RS232|
2904 |Baud rate|9600|
2905 |Data bit|8|
2906 |Parity|ODD|
2907 |Stop bit|1|
2908 |PLC station No.|1|
2909
2910 **2)Address List**
2911
2912 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2913 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2914 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2915 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2916 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2917 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2918 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2919 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2920 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2921 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2922 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2923 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2924 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2925 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2926 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2927 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2928
2929 **3)Configure the communication protocol**
2930
2931 [[image:image-20220830171050-1.png]]
2932
2933 [[image:image-20220830171126-2.png]]
2934
2935 **4)Cable Wiring**
2936
2937 Figure
2938
2939 [[image:image-20220830171328-4.png]]
2940
2941 Pin Definition Diagram
2942
2943 [[image:image-20220830171146-3.png]]
2944
2945 = Create communication with LS** PLC** =
2946
2947 == **XGB serial protocol ** ==
2948
2949 **HMI Settings**
2950
2951
2952 |=**Item**|=**Settings**|=**Note**
2953 |Protocol|LS XGB CPU DRIECT|
2954 |Connection|RS232|
2955 |Baud rate|115200|
2956 |Data bit|8|
2957 |Parity|NONE|
2958 |Stop bit|1|
2959 |PLC station No.|1|
2960
2961 **Address List**
2962
2963
2964 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2965 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2966 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2967 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2968 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2969 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2970 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2971 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2972 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2973 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2974 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2975 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2976 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2977 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2978 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2979 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2980 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2981 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2982 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2983 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2984 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2985 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2986 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2987 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2988 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2989 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2990 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2991
2992 **Configure the communication protocol**
2993
2994 (% style="text-align:center" %)
2995 [[image:image-20221028174410-1.png]]
2996
2997 (% style="text-align:center" %)
2998 [[image:image-20221028174753-2.png]]
2999
3000
3001 (% style="text-align:center" %)
3002 [[image:image-20221028181125-4.png]]
3003
3004 **Pin Definition Diagram**
3005
3006 (% style="text-align:center" %)
3007 [[image:image-20221028180930-3.png]]
3008
3009 = Create communication with LS** PLC** =
3010
3011 == **XBC serial protocol** ==
3012
3013 **HMI Settings**
3014
3015 |=**Item**|=**Settings**|=**Note**
3016 |Protocol|LS XBC CNet|
3017 |Connection|RS232|
3018 |Baud rate|115200|
3019 |Data bit|8|
3020 |Parity|NONE|
3021 |Stop bit|1|
3022 |PLC station No.|1|
3023
3024 **Address List**
3025
3026 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3027 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3028 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3029 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3030 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3031 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3032 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3033 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3034 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3035 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3036 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3037 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3038 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3039 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3040 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3041 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3042 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3043 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3044 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3045 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3046 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3047 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3048
3049 **Configure the communication protocol**
3050
3051 (% style="text-align:center" %)
3052 [[image:image-20220831170807-1.png]]
3053
3054 (% style="text-align:center" %)
3055 [[image:image-20220830174733-2.png]]
3056
3057 **Cable Wiring**
3058
3059 (% style="text-align:center" %)
3060 [[image:image-20220830174659-1.png]]
3061
3062 Pin Definition Diagram
3063
3064 (% style="text-align:center" %)
3065 [[image:image-20220830173402-8.png]]
3066
3067 == **XGK FEnet Ethernet protocol** ==
3068
3069 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3070
3071 **HMI Settings**
3072
3073 |**Items**|**Settings**|**Note**
3074 |Protocol|LG XGK FEnet(Ethernet)|
3075 |Connection|Ethernet|
3076 |Port No.|2004|
3077
3078 **Address List**
3079
3080 |**Type**|**Register**|**Range**|**Format**|**Note**
3081 |(% rowspan="14" %)Word|P|0~~2047|P d|
3082 |M|0~~2047|M d|
3083 |K|0~~2047|K d|
3084 |F|0~~2047|F d|
3085 |T|0~~2047|T d|
3086 |C|0~~2047|C d|
3087 |Z|0~~127|Z d|
3088 |S|0~~127|S d|
3089 |L|0~~11263|L d|
3090 |N|0~~21503|N d|
3091 |D|0~~32767|D d|
3092 |R|0~~32767|R d|
3093 |ZR|0~~65535|ZR d|
3094 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3095
3096 **✎Note:**
3097
3098 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3099 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3100 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3101
3102 **Communication settings in HMI**
3103
3104 Enable HMI Ethernet in [Project Settings];
3105
3106 (% style="text-align:center" %)
3107 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3108
3109 Set PLC IP in [Device IP] settings;
3110
3111 (% style="text-align:center" %)
3112 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3113
3114 **Cable Wiring**
3115
3116 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3117
3118 = Create communication with LS** PLC** =
3119
3120 == **XBC serial protocol** ==
3121
3122 **HMI Settings**
3123
3124 |=**Item**|=**Settings**|=**Note**
3125 |Protocol|LS XBC CNet|
3126 |Connection|RS232|
3127 |Baud rate|115200|
3128 |Data bit|8|
3129 |Parity|NONE|
3130 |Stop bit|1|
3131 |PLC station No.|1|
3132
3133 **Address List**
3134
3135 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3136 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3137 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3138 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3139 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3140 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3141 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3142 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3143 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3144 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3145 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3146 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3147 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3148 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3149 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3150 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3151 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3152 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3153 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3154 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3155 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3156 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3157
3158 **Configure the communication protocol**
3159
3160 (% style="text-align:center" %)
3161 [[image:image-20220831170807-1.png]]
3162
3163 (% style="text-align:center" %)
3164 [[image:image-20220830174733-2.png]]
3165
3166 **Cable Wiring**
3167
3168 (% style="text-align:center" %)
3169 [[image:image-20220830174659-1.png]]
3170
3171 Pin Definition Diagram
3172
3173 (% style="text-align:center" %)
3174 [[image:image-20220830173402-8.png]]
3175
3176 == **XGK FEnet Ethernet protocol** ==
3177
3178 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3179
3180 **HMI Settings**
3181
3182 |**Items**|**Settings**|**Note**
3183 |Protocol|LG XGK FEnet(Ethernet)|
3184 |Connection|Ethernet|
3185 |Port No.|2004|
3186
3187 **Address List**
3188
3189 |**Type**|**Register**|**Range**|**Format**|**Note**
3190 |(% rowspan="14" %)Word|P|0~~2047|P d|
3191 |M|0~~2047|M d|
3192 |K|0~~2047|K d|
3193 |F|0~~2047|F d|
3194 |T|0~~2047|T d|
3195 |C|0~~2047|C d|
3196 |Z|0~~127|Z d|
3197 |S|0~~127|S d|
3198 |L|0~~11263|L d|
3199 |N|0~~21503|N d|
3200 |D|0~~32767|D d|
3201 |R|0~~32767|R d|
3202 |ZR|0~~65535|ZR d|
3203 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3204
3205 **✎Note:**
3206
3207 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3208 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3209 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3210
3211 **Communication settings in HMI**
3212
3213 Enable HMI Ethernet in [Project Settings];
3214
3215 (% style="text-align:center" %)
3216 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3217
3218 Set PLC IP in [Device IP] settings;
3219
3220 (% style="text-align:center" %)
3221 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3222
3223 **Cable Wiring**
3224
3225 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3226
3227 = Create communication with **SHIMADEN PLC** =
3228
3229 == **FP23 series protocol** ==
3230
3231 Supported series: SHIMADEN FP23 series
3232
3233 **HMI Setting**
3234
3235 |**Items**|**Settings**|**Note**
3236 |Protocol|SHIMADEN FP23 series|
3237 |Connection|RS485 (9600, 1, 7, EVEN)|
3238 |Port No.|None|
3239 |PLC station No.|0|
3240
3241 **Address List**
3242
3243 |**Device address**|**HMI register**|**Address range**|**Type**
3244 |0040-0043(HEX)|FP040|100064-200067|Read only
3245 |0100-010B(HEX)|FP100|100256-200267|Read only
3246 |0110-0142(HEX)|FP110|100272-200322|Read only
3247 |0182-0252(HEX)|FP182|100386-200594|Write only
3248 |0280-0281(HEX)|FP280|100640-200641|Read only
3249 |0300-030B(HEX)|FP300|100768-200779|Read and write
3250 |0380-039F(HEX)|FP380|100896-200927|Read and write
3251 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3252 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3253 |0600-0670(HEX)|FP600|101536-201814|Read and write
3254 |0720-0738(HEX)|FP720|101824-201848|Read and write
3255 |0800-083F(HEX)|FP800|102048-202111|Read and write
3256 |0900-0952(HEX)|FP900|102304-202386|Read and write
3257 | |Ctrl|0-2|
3258
3259 **✎Note:**
3260
3261 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3262 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3263 * The Ctrl register is used to store the control group number and BCC check mode.
3264
3265 **Ctrl Register Description**
3266
3267 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3268 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3269 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3270 * Ctrl3 reserved
3271
3272 **✎Note:**
3273
3274 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3275
3276 **Cable Wiring**
3277
3278 (% style="text-align:center" %)
3279 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3280
3281 (% style="text-align:center" %)
3282 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3283
3284 **✎Note:** COM3 only available in PI8000/PI9000 series.
3285
3286 == **SR90 protocol** ==
3287
3288 Supported series: SHIMADEN SR90 series
3289
3290 **HMI Setting**
3291
3292 |**Items**|**Settings**|**Note**
3293 |Protocol|SHIMADEN SR90 protocol|
3294 |Connection|RS485 (1200, 1, 7, EVEN)|
3295 |Port No.|None|
3296 |PLC station No.|0|
3297
3298 **Address List**
3299
3300 |**Device address**|**HMI register**|**Address range**|**Type**
3301 |0040-0043 (HEX)|SR040|100064-100067|Read only
3302 |0100-010A(HEX)|SR0100|100256-100266|Read only
3303 |0182-018C(HEX)|SR0182|100386-100396|Write only
3304 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3305 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3306 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3307 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3308 | |Ctrl|0-2|~-~-
3309
3310 **✎Note:**
3311
3312 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3313 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3314 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3315
3316 **Ctrl Register Description**
3317
3318 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3319 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3320 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3321 * Ctrl3 reserved
3322
3323 **✎Note:**
3324
3325 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3326
3327 **Cable Wiring**
3328
3329 (% style="text-align:center" %)
3330 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3331
3332 (% style="text-align:center" %)
3333 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3334
3335 **✎Note:** COM3 only available in PI8000/PI9000 series.
3336
3337 == **MR13 series(standard protocol)** ==
3338
3339 Supported series: SHIMADEN MR13 series
3340
3341 **HMI Setting**
3342
3343 |**Items**|**Settings**|**Note**
3344 |Protocol|SHIMADEN standard protocol|
3345 |Connection|RS485 (1200, 1, 7, EVEN)|
3346 |Port No.|None|
3347 |PLC station No.|0|
3348
3349 **Address List**
3350
3351 |**Device address**|**HMI register**|**Address range**|**Type**
3352 |0100-010B(HEX)|MR100|100256-300267|Read only
3353 |0111-0126(HEX)|MR111|100273-300294|Read only
3354 |0184-0192(HEX)|MR184|100388-300402|Write only
3355 |0280-0282(HEX)|MR280|100640-300642|Read only
3356 |0300-030B(HEX)|MR300|100768-300779|Read/write
3357 |0314-0317(HEX)|MR314|100788-300791|Read/write
3358 |031A(HEX)|MR31A|100794-300794|Read/write
3359 |0320-0321(HEX)|MR320|100800-300801|Read/write
3360 |0400-0504(HEX)|MR400|101024-301284|Read/write
3361 |0506(HEX)|MR506|101286-301286|Read/write
3362 |0510-0514(HEX)|MR510|101296-301300|Read/write
3363 |0516-0524(HEX)|MR516|101302-301316|Read/write
3364 |0526(HEX)|MR526|101318-301318|Read/write
3365 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3366 |~-~-|Ctrl|0-2|~-~-
3367
3368 **✎Note:**
3369
3370 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3371 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3372 * The Ctrl register is used to store the control group number and BCC check mode.
3373
3374 **Ctrl Register Description**
3375
3376 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3377 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3378 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3379 * Ctrl3 reserved
3380
3381 **✎Note:**
3382
3383 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3384
3385 **Cable Wiring**
3386
3387 (% style="text-align:center" %)
3388 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3389
3390 (% style="text-align:center" %)
3391 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3392
3393 **✎Note:** COM3 only available in PI8000/PI9000 series.
3394
3395 = Create communication with **MODBUS** =
3396
3397 == **MODBUS RTU Master** ==
3398
3399 Supported Series: MODBUS RTU CONTROLLER
3400
3401 HMI works as MODBUS SLAVE connecting with MASTER
3402
3403 (% style="text-align:center" %)
3404 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3405
3406
3407 (% style="text-align:center" %)
3408 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3409
3410
3411 (% style="text-align:center" %)
3412 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3413
3414 **HMI Settings**
3415
3416 (% class="table-bordered" %)
3417 |**Items**|**Settings**|**Note**
3418 |Protocol|MODBUS RTU Master|
3419 |Connection|RS485/RS232|
3420 |Baud rate|2400~~187500|
3421 |Data bit|8|
3422 |Parity|Even/ Odd/ None|
3423 |Stop bit|1/2|
3424 |Station No.|0~~255|
3425
3426 **Address List**
3427
3428 (% class="table-bordered" %)
3429 |**Type**|**HMI address**|**MODBUS code**|**Range**
3430 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3431 |Word|HDW3500~~HDW7999|4|0~~4499
3432
3433 **Cable Wiring**
3434
3435 * **RS485**
3436
3437 (% style="text-align:center" %)
3438 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3439
3440 (% style="text-align:center" %)
3441 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3442
3443 * **RS232**
3444
3445 (% style="text-align:center" %)
3446 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3447
3448 **✎Note:** COM3 only available in PI8000/PI9000 series.
3449
3450 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3451
3452 Supported Series: MODBUS RTU CONTROLLER
3453
3454 HMI works as MODBUS MASTER connecting with SLAVE.
3455
3456 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3457
3458 (% style="text-align:center" %)
3459 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3460
3461
3462 (% style="text-align:center" %)
3463 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3464
3465
3466 (% style="text-align:center" %)
3467 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3468
3469 **HMI Settings**
3470
3471 (% class="table-bordered" %)
3472 |**Items**|**Settings**|**Note**
3473 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3474 |Connection|RS485/RS232|
3475 |Baud rate|2400~~187500|
3476 |Data bit|8|
3477 |Parity|Even/ Odd/ None|
3478 |Stop bit|1/2|
3479 |PLC station No.|0~~255|
3480
3481 **Address List**
3482
3483 (% class="table-bordered" %)
3484 |**Type**|**Address Type**|**Function code & Description**
3485 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3486 |06 (write single register: write a binary value to a holding register)
3487 |10 (write values to multiple addresses )
3488 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3489 |06 (write single register: write a binary value to a holding register)
3490 |10 (write values to multiple addresses )
3491 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3492 |06 (write single register: write a binary value to a holding register)
3493 |10 (write values to multiple addresses )
3494 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3495 |10 (write values to multiple addresses )
3496 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3497 |05 (Force a single coil to force the on/off state of a logic coil)
3498 |0F (Write multiple bits, ie write continuously)
3499 |(% rowspan="3" %)1|02 (Read the input state)
3500 |05 (Force a single coil to force the on/off state of a logic coil)
3501 |0F (Write multiple bits)
3502 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3503 |05 (Force a single coil to force the on/off state of a logic coil)
3504 |0F (Write multiple bits)
3505 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3506 |0F (Write multiple bits)
3507
3508 **✎Note:**
3509
3510 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3511 * The function codes sent out are the same as those that read and write words.
3512
3513 **Station number for more than one slaves**
3514
3515 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3516
3517 (% style="text-align:center" %)
3518 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3519
3520 **Cable Wiring**
3521
3522 * **RS485**
3523
3524 (% style="text-align:center" %)
3525 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3526
3527 (% style="text-align:center" %)
3528 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3529
3530 * **RS232**
3531
3532 (% style="text-align:center" %)
3533 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3534
3535 **✎Note:** COM3 only available in PI8000/PI9000 series.
3536
3537 == **Communicate with Modbus Meter** ==
3538
3539 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
3540
3541 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
3542
3543 (% style="text-align:center" %)
3544 [[image:LinfeeDiagram.png]]
3545
3546 (% class="wikigeneratedid" %)
3547 2. Check the specific Modbus parameter in the communication menu from LED display.
3548
3549 (% class="wikigeneratedid" %)
3550 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
3551
3552 {{info}}
3553 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
3554 {{/info}}
3555
3556 (% style="text-align:center" %)
3557 [[image:MeterModbusAllView.png]]
3558
3559 3. Create new project and change the Communication settings.
3560
3561 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
3562
3563 (% style="text-align:center" %)
3564 [[image:PIStudioSetupMeterModbusPara.png]]
3565
3566 (% class="wikigeneratedid" %)
3567 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
3568
3569 (% class="wikigeneratedid" %)
3570 The following table is intercept part of the manual for Linfee Modbus manual.
3571
3572 (% class="wikigeneratedid" %)
3573 **0x03/0x04 command data register address**:
3574
3575 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
3576 | HEX|DEC| | | |
3577 |0x00|0|Reserved| | |
3578 |0x02|2|Reserved| | |
3579 |0x04|4|Reserved| | |
3580 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
3581 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
3582 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
3583 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
3584 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
3585 |0x10|16|Uca|float|2|Line Voltage data, Unit V
3586 |0x12|18|Ia|float|2|Phase Current data, Unit A
3587 |0x14|20|Ib|float|2|Phase Current data, Unit A
3588 |0x16|22|Ic|float|2|Phase Current data, Unit A
3589
3590 {{info}}
3591 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
3592 {{/info}}
3593
3594 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
3595
3596 (% style="text-align:center" %)
3597 [[image:MeterModbusPInumericSet.png]]
3598
3599 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
3600
3601 (% style="text-align:center" %)
3602 [[image:MeterModbusNumericInputFormat.png]]
3603
3604 (% class="wikigeneratedid" %)
3605 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
3606
3607 (% style="text-align:center" %)
3608 [[image:ActualHMIModbusResult.jpg]]
3609
3610 == **MODBUS TCP Slave (All function)** ==
3611
3612 Supported series: MODBUS TCP controller
3613
3614 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3615
3616 (% style="text-align:center" %)
3617 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3618
3619 (% style="text-align:center" %)
3620 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3621
3622
3623 (% style="text-align:center" %)
3624 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3625
3626 **HMI Setting**
3627
3628 (% class="table-bordered" %)
3629 |**Items**|**Settings**|**Note**
3630 |Protocol|MODBUS TCP Slave (All function)|
3631 |Connection|Ethernet|
3632 |Port No.|502|
3633 |PLC station No.|1|
3634
3635 **Address List**
3636
3637 (% class="table-bordered" %)
3638 |**Type**|**Register**|**Function code & Description**
3639 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3640 |06 (write single register: write a binary value to a holding register)
3641 |10 (write values to multiple addresses )
3642 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3643 |06 (write single register: write a binary value to a holding register)
3644 |10 (write values to multiple addresses )
3645 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3646 |06 (write single register: write a binary value to a holding register)
3647 |10 (write values to multiple addresses )
3648 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3649 |10 (write values to multiple addresses )
3650 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3651 |05 (Force a single coil to force the on/off state of a logic coil)
3652 |0F (Write multiple bits, ie write continuously)
3653 |(% rowspan="3" %)1|02 (Read the input state)
3654 |05 (Force a single coil to force the on/off state of a logic coil)
3655 |0F (Write multiple bits)
3656 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3657 |05 (Force a single coil to force the on/off state of a logic coil)
3658 |0F (Write multiple bits)
3659 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3660 |0F (Write multiple bits)
3661
3662 **Communication Settings**
3663
3664 Enable HMI Ethernet in [Project Settings];
3665
3666 (% style="text-align:center" %)
3667 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3668
3669 Set PLC IP in [Device IP] settings;
3670
3671 (% style="text-align:center" %)
3672 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3673
3674 **Cable Wiring**
3675
3676 (% style="text-align:center" %)
3677 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3678
3679 = **Printer** =
3680
3681 == **TSPL label printer** ==
3682
3683 **Introduction**
3684
3685 TSPL label printer protocol supports following models.
3686
3687 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3688 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3689
3690 **Setting Step**
3691
3692 Select the protocol
3693
3694 * Create a new project, select the TSPL label printer protocol as shown below.
3695
3696 (% style="text-align:center" %)
3697 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3698
3699 Set parameters
3700
3701 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3702
3703 Printer register
3704
3705 (% class="table-bordered" %)
3706 |**Register**|**System**|**Range**|**Function**
3707 |TSPL_SP|decimal|0 - 1|Set the paper size
3708 |TSPL_PT|decimal|0 - 1999|Print text
3709 |TSPL_PQ|decimal|0 - 999|Print QR code
3710 |TSPL_PB|decimal|0 - 999|Print barcode
3711 |TSPL_PR|decimal|0 - 1|Print offset
3712 |TSPL_PN|decimal|0 - 0|Trigger printing
3713 |TSPL_PS|decimal|0 - 0|Print status
3714
3715 * Set paper size:
3716 ** TSPL_SP0: width of paper, unit: mm.
3717 ** TSPL_SP1: height of paper, unit: mm.
3718 * Print text:
3719 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3720 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3721
3722 (% class="table-bordered" %)
3723 |**Register**|**Function**|**Description**
3724 |TSPL_PT0|X coordinate|Unit: dot
3725 |TSPL_PT1|Ycoordinate|Unit: dot
3726 |TSPL_PT2|Rotation angle|(((
3727 0: 0 degrees
3728
3729 1: 90 degrees
3730
3731 2: 180 degrees
3732
3733 3: 270 degrees
3734 )))
3735 |TSPL_PT3|Size|Range: 0-3
3736 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3737
3738 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3739
3740 Print QR code:
3741
3742 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3743 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3744
3745 (% class="table-bordered" %)
3746 |**Register**|**Function**|**Description**
3747 |TSPL_PQ0|X coordinate|Unit: dot
3748 |TSPL_PQ1|Ycoordinate|Unit: dot
3749 |TSPL_PQ2|Rotation angle|(((
3750 0: 0 degrees
3751
3752 1: 90 degrees
3753
3754 2: 180 degrees
3755
3756 3: 270 degrees
3757 )))
3758 |TSPL_PQ3|Size|Range: 0-5
3759 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3760
3761 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3762
3763 Print bar code:
3764
3765 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3766 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3767
3768 (% class="table-bordered" %)
3769 |**Register**|**Function**|**Description**
3770 |TSPL_PB0|X coordinate|Unit: dot
3771 |TSPL_PB1|Ycoordinate|Unit: dot
3772 |TSPL_PB2|Rotation angle|(((
3773 0: 0 degrees
3774
3775 1: 90 degrees
3776
3777 2: 180 degrees
3778
3779 3: 270 degrees
3780 )))
3781 |TSPL_PB3|height|Unit: dot
3782 |TSPL_PB4|width|Range:0-2
3783 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3784
3785 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3786
3787 Print offset:
3788
3789 * TSPL_PR0: X coordinate offset, unit: mm;
3790 * TSPL_PR1: Y coordinate offset, unit: mm.
3791
3792 Trigger printing:
3793
3794 * TSPL_PN0 = 1: trigger the printer to start printing.
3795
3796 Printing status:
3797
3798 * TSPL_PS0 = 1: The printing is normal.
3799 * TSPL_PS0 = 1: The printing is abnormal.
3800
3801 Print picture
3802
3803 * For the function of printing pictures, please refer to the configuration of [Printer object].
3804
3805 Conversion between dot and mm
3806
3807 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3808
3809 == **EpsonTM series** ==
3810
3811 **HMI Settings**
3812
3813 (% class="table-bordered" %)
3814 |**Item**|**Settings**|**Note**
3815 |Protocol|EPSON-TM-T82II/TM-XXX|
3816 |Connection|RS232|
3817 |Baud rate|9600~~115200|
3818 |Data bit|8|
3819 |Parity|None|
3820 |Stop bit|1|
3821 |PLC station No.|1|
3822
3823 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3824
3825 **Printer Settings**
3826
3827 (% class="table-bordered" %)
3828 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3829 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3830 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3831 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3832 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3833 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3834 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3835
3836 **Cable Wiring**
3837
3838 (% style="text-align:center" %)
3839 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3840
3841 (% style="text-align:center" %)
3842 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3843
3844 **✎Note:** COM3 only available in PI8000/PI9000 series.
3845
3846
3847 = Create communication with **Schneider PLC** =
3848
3849 == **Schneider MODBUS RTU** ==
3850
3851 **HMI Setting**
3852
3853 |=**Parameters**|=**Recommended**|=**Notes**
3854 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3855 |Connection|RS485|
3856 |**Baud rate**|19200|
3857 |**Data bit**|8|
3858 |**Parity**|Even|
3859 |**Stop bit**|1|
3860 |**PLC station No.**|1|
3861
3862 **PLC Setting**
3863
3864 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3865
3866 **Device Address**
3867
3868 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3869 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3870 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3871 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3872 |W|MW|DDDDDD|0 ~~ 999999|Output register
3873 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3874
3875 **Wiring Diagram**
3876
3877 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3878
3879 (% style="text-align:center" %)
3880 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3881
3882 = **Barcode Scanner** =
3883
3884 Supported: DELI 14880 barcode scanner
3885
3886 **HMI Setting**
3887
3888 |**Items**|**Settings**|**Note**
3889 |Protocol|Barcode Scanner|
3890 |Connection|USB|
3891
3892 **Operating Procedures**
3893
3894 Select [Barcode Scanner];
3895
3896 (% style="text-align:center" %)
3897 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3898
3899 Set address for receiving;
3900
3901 Set correct length;
3902
3903 (% style="text-align:center" %)
3904 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3905
3906 **✎Note:**
3907
3908 * The protocol uploads the information acquired by the USB scanner to the HMI;
3909 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3910 * Recommended model: DELI 14880 barcode scanner;
3911
3912 = **Hitachi EHV Series (Ethernet)** =
3913
3914 Supported series: Hitachi EHV series
3915
3916 **HMI Settings**
3917
3918 (% class="table-bordered" %)
3919 |**Items**|**Settings**|**Note**
3920 |Protocol|Hitachi EHV series|
3921 |Connection|Ethernet|
3922 |Port No.|3004~~3007|
3923
3924 **Address List**
3925
3926 (% class="table-bordered" %)
3927 |**Type**|**Register**|**Range**|**Format**|**Note**
3928 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3929 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3930 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3931 H1H2H3H4 Module main number
3932
3933 H1: Remote number
3934
3935 H2: Unit number
3936
3937 H3: Slot number
3938
3939 H4: Word number of Module
3940
3941 H Sub number of Module
3942
3943 For example:X21.3
3944
3945 Slot number 2
3946
3947 Word number of module is 1
3948
3949 Bit number of module is 3
3950
3951 Remote number and unit number are 0
3952 )))
3953 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3954 |R|0 – FF.f (Hex)|R HH.h|
3955 |L|0 - 73FF.f (Hex)|L HHHH.h|
3956 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3957 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3958 H1H2H3H4 Module main number
3959
3960 H1: Remote number
3961
3962 H2: Unit number
3963
3964 H3: Slot number
3965
3966 H4: Word number of module
3967
3968 For example:WX21
3969
3970 Word number of module is 1
3971
3972 Slot number is 2
3973
3974 Remote number and unit number are 0
3975 )))
3976 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3977 |WR|0 – FFFF (Hex)|WR HHHH|
3978 |WL|0 - 73FF (Hex)|WL HHHH|
3979 |TC|0 - 2559|TC DDDD|
3980
3981 **Communication settings in HMI**
3982
3983 Enable HMI Ethernet in [Project Settings];
3984
3985 (% style="text-align:center" %)
3986 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3987
3988 Set PLC IP in [Device IP] settings;
3989
3990 (% style="text-align:center" %)
3991 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3992
3993 **PLC Configuration**
3994
3995 Connect with PLC, select[Online mode];
3996
3997 (% style="text-align:center" %)
3998 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3999
4000 Set IP address, it is the same LAN parameters with HMI;
4001
4002 (% style="text-align:center" %)
4003 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4004
4005 3) Save PLC communication parameter, and restart PLC
4006
4007 **PLC Monitor Mode**
4008
4009 Connect with PLC and choose to “online” mode
4010
4011 (% style="text-align:center" %)
4012 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4013
4014 Open I/O monitor sheet1
4015
4016 (% style="text-align:center" %)
4017 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4018
4019 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4020
4021 (% style="text-align:center" %)
4022 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4023
4024 Enter the register address, click OK to view the value of the register.
4025
4026 (% style="text-align:center" %)
4027 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4028
4029 (% style="text-align:center" %)
4030 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4031
4032 **✎Note:**
4033
4034 * Both word registers and bit registers support even continuous read/write functions;
4035 * The range of registers is based on the specific PLC type;
4036
4037 **Cable Wiring**
4038
4039 (% style="text-align:center" %)
4040 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4041
4042 = **IEC60870-5 104 Client** =
4043
4044 **HMI Setting**
4045
4046 (% class="table-bordered" %)
4047 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4048 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4049 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4050 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4051
4052 **Address List**
4053
4054 (% class="table-bordered" %)
4055 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4056 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4057 |(% style="width:461px" %)SCNA|0~~16777215.7
4058 |(% style="width:461px" %)DPTB|0~~16777215.7
4059 |(% style="width:461px" %)DCNA|0~~16777215.7
4060 |(% style="width:461px" %)METF|0~~16777215.7
4061 |(% style="width:461px" %)SENC|0~~16777215.7
4062 |(% style="width:461px" %)SENA|0~~16777215.7
4063 |(% style="width:461px" %)MENA|0~~16777215.7
4064 |(% style="width:461px" %)METD|0~~16777215.7
4065 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4066 |(% style="width:461px" %)SCNA|0~~16777215
4067 |(% style="width:461px" %)DPTB|0~~16777215
4068 |(% style="width:461px" %)DCNA|0~~16777215
4069 |(% style="width:461px" %)SENA|0~~16777215
4070 |(% style="width:461px" %)MENA|0~~16777215
4071 |(% style="width:461px" %)METD|0~~16777215
4072 |(% style="width:461px" %)INRO|0~~16777215
4073 |(% style="width:461px" %)TIMESYN|0~~16777215
4074 |(% style="width:461px" %)TIMEZ|0~~16777215
4075 |(% style="width:461px" %)NTP|0~~16777215
4076 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4077 |(% style="width:461px" %)SENC|0~~16777215
4078
4079 **Address Configuration**
4080
4081 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4082
4083 (% style="text-align:center" %)
4084 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4085
4086 (% style="text-align:center" %)
4087 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4088
4089 Extended tag name
4090
4091 Address range for the extended tag.
4092
4093 **Communication Settings**
4094
4095 Enable HMI Ethernet in [Project Settings];
4096
4097 (% style="text-align:center" %)
4098 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4099
4100 Set PLC IP in [Device IP] settings;
4101
4102 (% style="text-align:center" %)
4103 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4104
4105 **Cable Wiring**
4106
4107 (% style="text-align:center" %)
4108 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4109
4110 = **OpenCAN** =
4111
4112 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4113
4114 This protocol is only available in PI8000 series HMI.
4115
4116 **HMI Settings**
4117
4118 |**Items**|**Settings**|**Note**
4119 |Protocol|OPENCAN|
4120 |Connection|CAN port|
4121 |Baud rate|250000|
4122
4123 **CAN frame setting in HMI**
4124
4125 Click [OpenCAN setting] button in communication setting window;
4126
4127 (% style="text-align:center" %)
4128 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4129
4130 Click [Add] to create a new frame;
4131
4132 (% style="text-align:center" %)
4133 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4134
4135 |**No**|**Items**|**Description**
4136 |1|Add|add a frame related to register address
4137 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4138 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4139 |4|Modify|Modify the frames in frame management
4140 |5|Copy|Copy one frame to another
4141 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4142 |7|Empty|All frames in the list are cleared
4143 |8|Browse|Displays configuration files in XML format in IE
4144 |9|OK|Complete the configuration of the frame and exit
4145
4146 Set CANBUS frame in setting windows
4147
4148 (% style="text-align:center" %)
4149 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4150
4151 |**No**|**Items**|**Description**
4152 |1|ID|Set the ID of a can frame in hexadecimal format;
4153 |2|ID assign|split the ID by PF, PS, and SA;
4154 |3|Frame type|Select Standard frame or Extended Frame;
4155 |4|Frame format|Select between data frame and remote Frame;
4156 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4157 |6|Use address|(((
4158 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4159
4160 **Edit:** Set a bit or word address by its format;
4161
4162 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4163 )))
4164 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4165 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4166 |Feedback mode: feedback mode includes no response, confirm response and data response;
4167 |No response: the device or touch screen will not receive feedback;
4168 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4169 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4170 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4171 |Response timeout: sets whether the response frame timeout;
4172 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4173 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4174 |Manually send: a manually send tick indicates only one send;
4175 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4176 |10|Note|Fill the text to explain the meaning of the frame;
4177 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4178 |12|Current operation display|Display the description of current operation;
4179 |13|Add|Add a new frame;
4180 |14|Save frame|Save the configured frame format;
4181 |15|Cancel|Cancel the frame configuration;
4182
4183 Set CAN address (Read or write operation);
4184
4185 (% style="text-align:center" %)
4186 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4187
4188 |**No.**|**Item**|**Description**
4189 |1|Current address|Displays the register type and register address set by the user in the data access interface
4190 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4191 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4192 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4193 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4194 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4195 |If the trigger condition is a writing operation, there are two situations:(((
4196 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4197 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4198 )))
4199 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4200 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4201 |4|Add|Add current configuration
4202 |5|Close|Close the configuration window to exit
4203
4204 **Multiple Packages Settings**
4205
4206 (% style="text-align:center" %)
4207 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4208
4209 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4210
4211 Select Multiple package type
4212
4213 * Not Multiple packages
4214 * J1939 Multiple packages
4215 * Customized Multiple packages
4216
4217 Click [Edit Receive data] for [Receive] settings
4218
4219 * Start code+ Total length (J1939)
4220
4221 (% style="text-align:center" %)
4222 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4223
4224 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4225
4226 * Start code + Data max length (J1939)
4227
4228 (% style="text-align:center" %)
4229 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4230
4231 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4232
4233 * Data max length (J1939)
4234
4235 (% style="text-align:center" %)
4236 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4237
4238 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4239
4240 * Customized multiple package
4241
4242 (% style="text-align:center" %)
4243 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4244
4245 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4246
4247 Click [Edit Send data] for [Send] setting
4248
4249 * J1939
4250
4251 (% style="text-align:center" %)
4252 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4253
4254 [Data] is all data to be sent.
4255
4256 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4257
4258 * Customized multiple package
4259
4260 (% style="text-align:center" %)
4261 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4262
4263 [Data] is all data to be sent.
4264
4265 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4266
4267 **Cable Wiring**
4268
4269 (% style="text-align:center" %)
4270 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4271
4272 **✎Note:** The address interval between each frame need to be more than a word address;
4273
4274
4275 = **User Defined Protocol** =
4276
4277 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4278
4279 **HMI Settings**
4280
4281 |**Items**|**Settings**|**Note**
4282 |Protocol|User defined protocol|
4283 |Connection|RS485/RS232|
4284 |Baud rate|2400~~187500|
4285 |Stop bits|1/ 2|
4286 |Data bits|7/ 8|
4287 |Parity|None/ Even/ ODD|
4288
4289 **Operating Procedures**
4290
4291 Select [User defined protocol];
4292
4293 Click [User defined protocol] button to open setting window as below;
4294
4295 (% style="text-align:center" %)
4296 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4297
4298 Configure user defined command;
4299
4300 (% style="text-align:center" %)
4301 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4302
4303 |**No**|**Item**|**Description**
4304 |1|Instruction edit|The required command.
4305 |2|Mode|Write to address or read from the address.
4306 |3|Format|Encode format: HEX or ASCII.
4307 |4|Other|(((
4308 **No receiving: **HMI does not respond to the receiving command.
4309
4310 **Send after receiving:** HMI responds to the receiving command.
4311 )))
4312 |5|Manually send|(((
4313 Respond once after trigger the address.
4314
4315 Address: set the trigger address.
4316 )))
4317 |6|Add|Save this setting.
4318 |7|Cancel|Cancel current settings.
4319 |(% rowspan="4" %)8|Add|Add a new command.
4320 |Edit|Edit the selected command.
4321 |Delete|Delete the selected command.
4322 |Clear|Clear all the commands.
4323 |9|Instruction list|Display all current commands.
4324 |10|Address List|Display all the addresses added.
4325 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4326 |Export|Export current command settings to local storage.
4327 |Browse|Browse local command files.
4328 |Advanced|Combine two commands.
4329 |Exit|Complete editing and exit setting.
4330
4331 **Operating Procedures**
4332
4333 Click [Add] to create a new command, as below shows;
4334
4335 (% style="text-align:center" %)
4336 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4337
4338 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4339
4340 (% style="text-align:center" %)
4341 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4342
4343 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4344
4345 (% style="text-align:center" %)
4346 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4347
4348 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4349
4350 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4351
4352 Check settings;
4353
4354 (% style="text-align:center" %)
4355 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4356
4357 |**No**|**Items**|**Description**
4358 |1|Add checking|Add checking command when receiving the data.
4359 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4360 |Differ with send check|Set return checking.
4361 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4362 |Length: The data length need to be checked.
4363
4364 Object settings;
4365
4366 (% style="text-align:center" %)
4367 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4368
4369 |**No**|**Items**|**Description**
4370 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4371 |Address: the triggering address;
4372 |Note: description to object;
4373 |2|Byte order|The numerical display order;
4374
4375 Data length settings;
4376
4377 (% style="text-align:center" %)
4378 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4379
4380 |**No**|**Item**|**Description**
4381 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4382 |Length: the return data length.
4383 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4384 |Length: the write data length.
4385
4386 Instruction length settings
4387
4388 (% style="text-align:center" %)
4389 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4390
4391 |**No**|**Item**|**Description**
4392 |1|Send length|The instruction data will only send designated data length.
4393 |2|Return length|The responds data length.
4394 |3|End code|Instruction will not be terminated until receiving [End code];
4395
4396 **Cable Wiring**
4397
4398 * **RS485**
4399
4400 (% style="text-align:center" %)
4401 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4402
4403 (% style="text-align:center" %)
4404 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4405
4406 * **RS232**
4407
4408 (% style="text-align:center" %)
4409 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4410
4411 **✎Note:** COM3 only available in PI8000/PI9000 series.