Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 246.1 by Hunter on 2023/04/21 15:39

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with Inovance PLC** =
850
851 == **H1U/H2U serial protocol** ==
852
853 **HMI Settings**
854
855 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
856 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
857 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
858 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
859 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
860 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
861 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
862 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
863 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
864
865 (% class="wikigeneratedid" %)
866 **Address List**
867
868 (% style="width:1014px" %)
869 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
870 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
871 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
872 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
873 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
874 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
875 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
876 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
877 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
878 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
879 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
880 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
881 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
882 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
883 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
884 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
885 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
886 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
887
888 (% class="wikigeneratedid" %)
889 **Cable Wiring**
890
891 (% style="text-align:center" %)
892 [[image:Inovance.png]]
893
894 == **H3U serial protocol** ==
895
896 **HMI Settings**
897
898 |=**Item**|=**Settings**|=**Note**
899 |Protocol|INOVANCE H3U PLC|
900 |Connection|RS422|
901 |Baud rate|9600|
902 |Data bit|7|
903 |Parity|EVEN|
904 |Stop bit|1|
905 |PLC station No.|0|
906
907 **Address List**
908
909 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
910 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
911 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
912 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
913 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
914 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
915 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
916 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
917 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
918 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
919 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
920 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
921 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
922 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
923 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
924 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
925 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
926 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
927 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
928
929 **Configure the communication protocol**
930
931 (% style="text-align:center" %)
932 [[image:image-20220830170114-4.png]]
933
934 [[image:image-20220830170017-3.png]]
935
936 **Cable Wiring**
937
938 (% style="text-align:center" %)
939 [[image:Inovance.png]]
940
941 == **H3U Ethernet portocol** ==
942
943 **HMI Settings**
944
945 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
946 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
947 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
948 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
949 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
950 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
951
952 **Address List**
953
954 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
955 |Bit|M|M DDDD|0~~8511|
956 |Bit|SM|SM DDDD|0~~1023|
957 |Bit|S|S DDDD|0~~4095|
958 |Bit|T|T DDD|0~~511|
959 |Bit|C|C DDD|0~~255|
960 |Bit|X|X OOO|0~~571|
961 |Bit|Y|Y OOO|0~~571|
962 |Word|D|D DDDD|0~~8511|
963 |Word|SD |SD DDDD|0~~1023|
964 |Word|R|R DDDDD|0~~32767|
965 |Word|T|T DDD|0~~255|
966 |Word|C|C DDD|0~~199|
967 |Double Word|C|C DDD|200~~255|
968
969 **Cable Wiring**
970
971 (% style="text-align:center" %)
972 [[image:CommonEthernet.png]]
973
974 = Create communication with **Mitsubishi PLC** =
975
976 == **FX1S, 1N, 2N Series Protocol** ==
977
978 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
979
980 **HMI Settings**
981
982 |**Item**|**Settings**|**Note**
983 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
984 |Connection|RS422/RS485/RS232|
985 |Baud rate|9600~~115200|
986 |Data bit|7/8|
987 |Parity|EVEN/Odd/None|
988 |Stop bit|1/2|
989 |PLC station No.|1~~255|
990
991 **Address List**
992
993 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
994 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
995 |Y|Y|Y o|0~~303237|
996 |M|M|M d|0~~99999|
997 |T|T|T d|0~~99999|
998 |C|C|C d|0~~99999|
999 |S|S|S d|0~~99999|
1000 |SM|SM|SM d|8000~~9999|
1001 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1002 |Y|Y|Y o|0~~303237|
1003 |M|M|M d|0~~99999|
1004 |T|T|T d|0~~99999|
1005 |C|C|C d|0~~199|
1006 |D|D|D d|0~~7999|
1007 |S|S|S d|0~~99999|
1008 |SD|SD|SD d|8000~~9999|
1009
1010 **Cable Wiring**
1011
1012 * **RS485**
1013
1014 (% style="text-align:center" %)
1015 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1016
1017 (% style="text-align:center" %)
1018 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1019
1020 * **RS422**
1021
1022 (% style="text-align:center" %)
1023 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1024
1025 **✎Note:** COM3 only available in PI8000/PI9000 series.
1026
1027 == **FX3U/3G/3GA serial protocol** ==
1028
1029 **HMI Settings**
1030
1031 |=**Item**|=**Settings**|=**Note**
1032 |Protocol|Mitsubishi FX3U/3G/3GA|
1033 |Connection|RS422|
1034 |Baud rate|9600~~115200|
1035 |Data bit|7/8|
1036 |Parity|EVEN/Odd/None|
1037 |Stop bit|1/2|
1038 |PLC station No.|1~~255|
1039
1040 **Address List**
1041
1042 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1043 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1044 |Y|Y|Y o|0~~303237|
1045 |M|M|M d|0~~99999|
1046 |T|T|T d|0~~99999|
1047 |C|C|C d|0~~99999|
1048 |S|S|S d|0~~99999|
1049 |SM|SM|SM d|8000~~9999|
1050 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1051 |Y|Y|Y o|0~~303237|
1052 |M|M|M d|0~~99999|
1053 |T|T|T d|0~~99999|
1054 |C|C|C d|0~~199|
1055 |D|D|D d|0~~7999|
1056 |S|S|S d|0~~99999|
1057 |SD|SD|SD d|8000~~9999|
1058
1059 **Configure the communication protocol**
1060
1061 (% style="text-align:center" %)
1062 [[image:image-20220831095222-1.png]]
1063
1064 (% style="text-align:center" %)
1065 [[image:image-20220831095743-2.png]]
1066
1067 **Wiring**
1068
1069 (% style="text-align:center" %)
1070 [[image:image-20220831100314-6.png]]
1071
1072 == **FX3U Ethernet Protocol** ==
1073
1074 Mitsubishi FX3U series PLC
1075
1076 **HMI Settings**
1077
1078 |Items|Settings|Note
1079 |Protocol|Mitsubishi FX3U|
1080 |Connection|Ethernet|
1081 |Port No.|5009|Must be the same as the PLC setting
1082 |PLC station No.|0|
1083
1084 **Address List**
1085
1086 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1087 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1088 |Y|Y|Y OOO|0~~377|
1089 |M|M|M DDDD|0~~7679|
1090 |SM|SM|SM DDDD|8000~~8511|
1091 |S|S|S DDDD|0~~4095|
1092 |TS|TS|TS DDD|0~~511|
1093 |CS|CS|CS DDD|0~~255|
1094 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1095 |TN|TN|TN DDD|0~~511|
1096 |D|D|D DDDD|0~~7999|
1097 |SD|SD|SD DDDD|8000~~8511|
1098 |R|R|R DDDDD|0~~32767|
1099
1100 **Ethernet Module Settings**
1101
1102 FX3U-ENET-L module configuration
1103 Set up the FX3U-ENET-L Ethernet module settings as follows.
1104 Select the module location, which in this document is Module 0.
1105
1106 [[image:image-20221115140802-1.png]]
1107
1108 Select "Operational setting" to enter the following screen.
1109
1110 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1111
1112 [[image:image-20221115142728-4.png]]
1113
1114 Select "Open setting" to enter the setting interface, the settings are as follows.
1115
1116 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1117
1118 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1119
1120 [[image:image-20221115142945-5.png]]
1121
1122 Click on "transter setup" - "PC side I/F setting", see the following figure.
1123
1124 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1125
1126 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1127
1128 [[image:image-20221115143341-6.png||height="426" width="712"]]
1129
1130 Read and write data from the Ethernet module
1131
1132 [[image:image-20221115143703-7.png]]
1133
1134 Set "Transter setup" to COM communication, and read or write operation as shown below
1135
1136 [[image:image-20221115143809-8.png]]
1137
1138 **PLC Settings (GX Works 2)**
1139
1140 Create a blank FX5U project
1141
1142 Find Current Connection in the navigation
1143
1144 [[image:image-20221115144335-9.png||height="422" width="706"]]
1145
1146 Select Connection Channel List
1147
1148 Select Ethernet board communication
1149
1150 [[image:image-20221115144824-10.png||height="421" width="705"]]
1151
1152 Select Ethernet Module
1153 Set the IP address of the PLC
1154
1155 [[image:image-20221115145228-11.png||height="674" width="708"]]
1156
1157 Read or write PLC data, in this document is read
1158
1159 [[image:image-20221115145553-12.png||height="424" width="711"]]
1160
1161 [[image:image-20221115145559-13.png||height="424" width="711"]]
1162
1163 **HMI Communication Setting**
1164
1165 [[image:image-20221115150003-14.png||height="425" width="712"]]
1166
1167 [[image:image-20221115150235-15.png||height="427" width="713"]]
1168
1169 [[image:image-20221115145559-13.png||height="424" width="711"]]
1170
1171 **HMI Communication Setting**
1172
1173 [[image:image-20221115150003-14.png||height="425" width="712"]]
1174
1175 [[image:image-20221115150235-15.png||height="427" width="713"]]
1176
1177 == **FX5U Serial Port Protocol** ==
1178
1179 Mitsubishi FX5U series PLC
1180
1181 **HMI Settings**
1182
1183 |**Item**|**Settings**|**Note**
1184 |Protocol|Mitsubishi FX5U|
1185 |Connection|RS422/RS485|
1186 |Baud rate|9600|
1187 |Data bit|7|
1188 |Parity|Odd|
1189 |Stop bit|1|
1190 |PLC station No.|1~~255|Need to be the same as PLC settings
1191
1192 **Address List**
1193
1194 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1195 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1196 |Y|Y|Y o|0~~303237|
1197 |M|M|M d|0~~99999|
1198 |B|B|B h|0~~7FFF|
1199 |F|F|F d|0~~32767|
1200 |SB|SB|SB h|0~~7FFF|
1201 |TS|TS|TS d|0~~1023|
1202 |TC|TC|TC d|0~~1023|
1203 |STS|STS|STS d|0~~1023|
1204 |STC|STC|STS d|0~~1023|
1205 |CS|CS|CS d|0~~1023|
1206 |CC|CC|CC d|0~~1023|
1207 |SM|SM|SM d|0~~9999|
1208 |L|L|L d|0~~32767|
1209 |S|S|S d|0~~4095|
1210 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1211 |TN|TN|TN d|0~~1023|
1212 |STN|STN|STN d|0~~1023|
1213 |CN|CN|CN d|0~~1023|
1214 |R|R|R d|0~~32767|
1215 |SW|SW|SW h|0~~7FFF|
1216 |Z|Z|Z d|0~~23|
1217 |D|D|D d|0~~7999|
1218 |SD|SD|SD d|0~~11999|
1219
1220 **PLC Settings (GX Works 3)**
1221
1222 Create a blank FX5U project
1223
1224 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1225
1226 (% style="text-align:center" %)
1227 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1228
1229 Select protocol in the setting item, and set parameters.
1230
1231 (% style="text-align:center" %)
1232 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1233
1234 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1235
1236 (% style="text-align:center" %)
1237 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1238
1239 Click the [Apply] button to finish the setting.
1240
1241 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1242
1243 (% style="text-align:center" %)
1244 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1245
1246 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1247
1248 Done.
1249
1250 **Cable Wiring**
1251
1252 * **RS485**
1253
1254 (% style="text-align:center" %)
1255 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1256
1257 (% style="text-align:center" %)
1258 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1259
1260 * **RS422**
1261
1262 (% style="text-align:center" %)
1263 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1264
1265 **✎Note:** COM3 only available in PI8000/PI9000 series.
1266
1267 == **L02 Serial Protocol** ==
1268
1269 Mitsubishi L02 series CPU built-in serial port.
1270
1271 **HMI Settings**
1272
1273 |=**Item**|=**Settings**|=**Note**
1274 |Protocol|Mitsubishi L02|
1275 |Connection|RS422|
1276 |Baud rate|115200|
1277 |Data bit|8|
1278 |Parity|Odd|
1279 |Stop bit|1|
1280 |PLC station No.|1~~255|Need to be the same as PLC settings
1281
1282 **Address List**
1283
1284 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1285 |Bit|X|X|X h|0~~FFFF|
1286 |Bit|Y|Y|Y h|0~~FFFF|
1287 |Bit|M|M|M d|0~~9999|
1288 |Bit|L|L|L d|0~~9999|
1289 |Bit|F|F|F d|0~~9999|
1290 |Bit|B|B|B h|0~~FFFF|
1291 |Bit|V|V|V d|0~~2047|
1292 |Bit|TC|TC|TC d|0~~9999|
1293 |Bit|SS|SS|SS d|0~~9999|
1294 |Bit|SC|SC|SC d|0~~9999|
1295 |Bit|CS|CS|CS d|0~~9999|
1296 |Bit|CC|CC|CC d|0~~9999|
1297 |Bit|SB|SB|SB h|0~~FFFF|
1298 |Bit|SM|SM|SM d|0~~2047|
1299 |Bit|STS|STS|STS d|0~~1023|
1300 |Bit|S|S|S d|0~~9999|
1301 |Bit|DX|DX|DX h|0~~FFFF|
1302 |Bit|DY|DY|DY h|0~~FFFF|
1303 |Bit|TS|TS|TS d|0~~9999|
1304 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1305 |Word|W|W|W h|0~~FFFF|
1306 |Word|TN|TN|TN d|0~~99999|
1307 |Word|SN|SN|SN d|0~~99999|
1308 |Word|CN|CN|CN d|0~~99999|
1309 |Word|R|R|R d|0~~99999|
1310 |Word|SW|SW|SW h|0~~FFFF|
1311 |Word|Z|Z|Z d|0~~99999|
1312 |Word|ZR|ZR|ZR h|0~~FFFF|
1313 |Word|D|D|D d|0~~99999|
1314
1315 **Communication Settings**
1316
1317 (% style="text-align:center" %)
1318 [[image:image-20220831105732-3.png]]
1319
1320 (% style="text-align:center" %)
1321 [[image:image-20220831110004-5.png]]
1322
1323 **Cable Wiring**
1324
1325 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1326
1327 Pin Definition Diagram
1328
1329 (% style="text-align:center" %)
1330 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1331
1332 == **L02 MELSEC (Ethernet) Protocol** ==
1333
1334 Mitsubishi Q series CPU built-in Ethernet port.
1335
1336 **HMI Settings**
1337
1338 |**Items**|**Settings**|**Note**
1339 |Protocol|MIT L02 CPU MELSEC|
1340 |Connection|Ethernet|
1341 |Port No.|1025|Must be the same as the PLC setting
1342 |PLC station No.|0|Must be the same as the PLC setting
1343
1344 **Address List**
1345
1346 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1347 |Bit|X|X|X h|0~~FFFF|
1348 |Bit|Y|Y|Y h|0~~FFFF|
1349 |Bit|M|M|M d|0~~9999|
1350 |Bit|L|L|L d|0~~9999|
1351 |Bit|F|F|F d|0~~9999|
1352 |Bit|B|B|B h|0~~FFFF|
1353 |Bit|V|V|V d|0~~2047|
1354 |Bit|TC|TC|TC d|0~~9999|
1355 |Bit|SS|SS|SS d|0~~9999|
1356 |Bit|SC|SC|SC d|0~~9999|
1357 |Bit|CS|CS|CS d|0~~9999|
1358 |Bit|CC|CC|CC d|0~~9999|
1359 |Bit|SB|SB|SB h|0~~FFFF|
1360 |Bit|SM|SM|SM d|0~~2047|
1361 |Bit|STS|STS|STS d|0~~1023|
1362 |Bit|S|S|S d|0~~9999|
1363 |Bit|DX|DX|DX h|0~~FFFF|
1364 |Bit|DY|DY|DY h|0~~FFFF|
1365 |Bit|TS|TS|TS d|0~~9999|
1366 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1367 |Word|W|W|W h|0~~FFFF|
1368 |Word|TN|TN|TN d|0~~99999|
1369 |Word|SN|SN|SN d|0~~99999|
1370 |Word|CN|CN|CN d|0~~99999|
1371 |Word|R|R|R d|0~~99999|
1372 |Word|SW|SW|SW h|0~~FFFF|
1373 |Word|Z|Z|Z d|0~~99999|
1374 |Word|ZR|ZR|ZR h|0~~FFFF|
1375 |Word|D|D|D d|0~~99999|
1376
1377 **Communication Settings**
1378
1379 Enable HMI Ethernet in [Project Settings];
1380
1381 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1382
1383 Set PLC IP in [Device IP] settings;
1384
1385 (% style="text-align:center" %)
1386 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1387
1388 **PLC Settings (GX Works2 )**
1389
1390 Create a project
1391
1392 Set PLC IP, subnet mask and gateway;
1393
1394 Select [Binary Code] as communication data code;
1395
1396 (% style="text-align:center" %)
1397 [[image:image-20221108202109-2.png||height="636" width="732"]]
1398
1399 Set PLC port number, for example 1025
1400
1401 (% style="text-align:center" %)
1402 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1403
1404 Save settings;
1405
1406 Download project into PLC device;
1407
1408 Restart PLC device;
1409
1410 **Cable Wiring**
1411
1412 (% style="text-align:center" %)
1413 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1414
1415 == **QJ71C24N MELSEC Protocol** ==
1416
1417 Mitsubishi QJ71C24N communication module built-in serial port;
1418
1419 **HMI Settings**
1420
1421 |**Items**|**Settings**|**Note**
1422 |Protocol|MIT QJ71 MELSEC|
1423 |Connection|422|
1424 |Baud rate|9600|
1425 |Data bit|8|
1426 |Parity|ODD|
1427 |Stop bit|1|
1428 |PLC station No.|1~~255|Need to be the same as PLC settings
1429
1430 **Address List**
1431
1432 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1433 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1434 |Y|Y|Y FFFF|0~~1FFF|
1435 |M|M|M DDDDD|0~~99999|
1436 |L|L|L DDDD|0~~8191|
1437 |F|F|F DDDD|0~~2047|
1438 |V|V|V DDDD|0~~2047|
1439 |B|B|B FFFF|0~~1FFF|
1440 |TS|TS|TS DDDD|0~~2047|
1441 |TC|TC|TC DDDD|0~~2047|
1442 |SS|SS|SS DDDD|0~~2047|
1443 |SC|SC|SC DDDD|0~~2047|
1444 |CS|CS|CS DDDD|0~~1023|
1445 |CC|CC|CC DDDD|0~~1023|
1446 |SB|SB|SB FFF|0~~7FF|
1447 |S|S|S D|0~~8191|
1448 |DX|DX|DX FFFF|0~~1FFF|
1449 |DY|DY|DY FFFF|0~~1FFF|
1450 |SM_|SM_|SM_ DDDD|8000~~9999|
1451 |SM|SM|SM DDDD|0~~2047|
1452 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1453 |D|D|D DDDDD|0~~12287|
1454 |W|W|W FFFF|0~~1FFF|
1455 |TN|TN|TN DDDD|0~~2047|
1456 |SN|SN|SN DDDD|0~~2047|
1457 |CN|CN|CN DDDD|0~~1023|
1458 |R|R|R DDDDD|0~~32767|
1459 |SW|SW|SW FFF|0~~7FF|
1460 |Z|Z|Z D|0~~15|
1461 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1462
1463 **Communication Settings**
1464
1465 (% style="text-align:center" %)
1466 [[image:image-20221109135738-1.png]]
1467
1468 (% style="text-align:center" %)
1469 [[image:image-20221109140016-3.png]]
1470
1471 Pin Definition Diagram
1472
1473 (% style="text-align:center" %)
1474 [[image:image-20221109140406-4.png]]
1475
1476 == **QJ71E71 MELSEC Protocol** ==
1477
1478 Mitsubishi QJ71E71 Ethernet communication module;
1479
1480 **HMI Settings**
1481
1482 |**Items**|**Settings**|**Note**
1483 |Protocol|MIT QJ71E71 MELSEC|
1484 |Connection|Ethernet|
1485 |Port No.|1025|Must be the same as the PLC setting
1486 |PLC station No.|0|Must be the same as the PLC setting
1487
1488 **Address List**
1489
1490 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1491 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1492 |Y|Y|Y h|0~~1FFF|
1493 |M|M|M d|0~~99999|
1494 |L|L|L d|0~~8191|
1495 |F|F|F d|0~~2047|
1496 |B|B|B h|0~~1FFF|
1497 |V|V|V d|0~~2047|
1498 |TS|TS|TS d|0~~2047|
1499 |TC|TC|TC d|0~~2047|
1500 |SS|SS|SS d|0~~2047|
1501 |SC|SC|SC d|0~~2047|
1502 |CS|CS|CS d|0~~1023|
1503 |CC|CC|CC d|0~~1023|
1504 |SB|SB|SB h|0~~7FF|
1505 |S|S|S d|0~~8191|
1506 |DX|DX|DX h|0~~1FFF|
1507 |DY|DY|DY h|0~~1FFF|
1508 |SM|SM|SM d|8000~~9999|
1509 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1510 |D|D|D d|0~~12287|
1511 |W|W|W h|0~~1FFF|
1512 |TN|TN|TN d|0~~2047|
1513 |SN|SN|SN d|0~~2047|
1514 |CN|CN|CN d|0~~1023|
1515 |R|R|R d|0~~32767|
1516 |SW|SW|SW h|0~~7FF|
1517 |Z|Z|Z d|0~~15|
1518 |ZR|ZR|ZR h|0~~FE7FF|
1519
1520 **HMI Communication Settings**
1521
1522 1) Enable HMI Ethernet in [Project Settings];
1523
1524 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1525
1526 2) Set PLC IP in [Device IP] settings
1527
1528 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1529
1530 **PLC Settings(GX Works2)**
1531
1532 * Click [Ethernet/CC IE/MELSECNET];
1533 * Please select [Ethernet] as network type;
1534 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1535 * Select [Online] as Mode;
1536 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1537 * Click [Operation setting] to set IP;
1538 * Select [Binary Code] as [Communication Data Code];
1539 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1540 * Click [Open setting]
1541 * Set protocol: TCP;
1542 * Set [unpassive] in [Open system];
1543 * Set [receive] in [Fixed buffer];
1544 * Set [procedure Exist] in [Fixed buffer communication];
1545 * Disable [Pairing open];
1546 * Set [No confirm] in [Existence confirmation];
1547 * Host station port number: 5009;
1548 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1549 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1550 * Download project into PLC and restart it
1551
1552 **Cable Wiring**
1553
1554
1555 (% style="text-align:center" %)
1556 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1557
1558 = Create communication with **Rockwell PLC** =
1559
1560 == **DF1 Protocol** ==
1561
1562 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1563
1564 **HMI Settings**
1565
1566 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1567 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
1568 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1569 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1570 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1571 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1572 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1573 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1574 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1575
1576 **Address List**
1577
1578 (% class="table-bordered" %)
1579 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1580 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1581 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1582 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
1583 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1584 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
1585 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1586 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1587 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1588 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1589 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1590 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
1591
1592 **Cable Wiring**
1593
1594 (% style="text-align:center" %)
1595 [[image:AB.gif]]
1596
1597 == **DF1 Advanced Protocol** ==
1598
1599 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1600
1601 **HMI Settings**
1602
1603 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1604 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
1605 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1606 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1607 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1608 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1609 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1610 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1611 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1612
1613 **Address List**
1614
1615 (% class="table-bordered" %)
1616 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1617 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1618 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1619 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1620 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
1621 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1622 Bit data file B0~~B99
1623
1624 First two digits is for file number
1625
1626 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
1627 )))
1628 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
1629 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1630 Integer data file bit format N0~~N99
1631
1632 First two digits is for file number
1633
1634 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
1635 )))
1636 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1637 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1638 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1639 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1640 Timer Preset Value
1641
1642 First two digits is for file number
1643
1644 For example, TNS99255 represents file number T99, address 255.
1645 )))
1646 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1647 Timer Accumulator Value
1648
1649 First two digits is for file number
1650
1651 For example, TNP99255 represents file number T99, address 255.
1652 )))
1653 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1654 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1655 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1656 Counter Preset Value
1657
1658 First two digits is for file number
1659
1660 For example, CNS99255 represents file number C99, address 255.
1661 )))
1662 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1663 Counter Accumulator Value
1664
1665 First two digits is for file number
1666
1667 For example, CNP99255 represents file number C99, address 255.
1668 )))
1669 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
1670 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1671 Integer data file
1672
1673 First two digits is for file number
1674
1675 For example, NN99255 represents file number N99, address 255.
1676 )))
1677 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
1678 Only able to communicate with file number F8
1679 )))
1680 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1681 Floating point data file
1682
1683 First two digits is for file number
1684
1685 For example, FN99255 represents file number F99, address 255.
1686 )))
1687 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
1688
1689 **Cable Wiring**
1690
1691 (% style="text-align:center" %)
1692 [[image:AB.gif]]
1693
1694 == **MicroLogix Protocol** ==
1695
1696 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
1697
1698 **HMI Settings**
1699
1700 (% class="table-bordered" %)
1701 |**Item**|**Settings**|**Note**
1702 |Protocol|Allen-Bradlley MicroLogix|
1703 |Connection|RS232|
1704 |Baud rate|19200|
1705 |Data bit|8|
1706 |Parity|None|
1707 |Stop bit|1|
1708 |PLC station No.|1|
1709
1710 **Address List**
1711
1712 (% class="table-bordered" %)
1713 |**Type**|**Device registers**|**Format**|**Range**|**Note**
1714 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
1715 |O|O d.d|0.0~~255.15|
1716 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1717 |S|S d.d|0.0~~255.15|
1718 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1719 |(% rowspan="9" %)Word|S|S d|0~~255|
1720 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
1721 |TP|TP nnhh|0~~ffff
1722 |CS|CS nnhh|0~~ffff
1723 |CP|CP nnhh|0~~ffff
1724 |N|N nnhh|0~~ffff
1725 |C|C nnhh|0~~ffff
1726 |T|T nnhh|0~~ffff
1727 |R|R nnhh|0~~ffff
1728
1729 **Cable Wiring**
1730
1731
1732 (% style="text-align:center" %)
1733 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
1734
1735 == **CompactLogix FreeTag Ethernet protocol** ==
1736
1737 Allen-Brandly CompactLogix
1738
1739 **HMI Settings**
1740
1741 (% class="table-bordered" %)
1742 |**Items**|**Settings**|**Note**
1743 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
1744 |Connection|Ethernet|
1745 |Port No.|44818|
1746
1747 **PLC Setting**
1748
1749 Create new tags
1750
1751 (% style="text-align:center" %)
1752 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
1753
1754 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
1755
1756 (% style="text-align:center" %)
1757 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
1758
1759 Import labels, please open [Communication] window and click [Import label];
1760
1761 Select csv file, all tags will be displayed as belows;
1762
1763 (% style="text-align:center" %)
1764 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
1765
1766 **✎Note:**
1767
1768 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
1769
1770 (% style="text-align:center" %)
1771 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
1772
1773 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
1774
1775 **Communication settings in HMI**
1776
1777 Enable HMI Ethernet in [Project Settings];
1778
1779 (% style="text-align:center" %)
1780 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
1781
1782 Set PLC IP in [Device IP] settings;
1783
1784 (% style="text-align:center" %)
1785 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1786
1787 **Cable Wiring**
1788
1789 (% style="text-align:center" %)
1790 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
1791
1792 == **MicroLogix 1200** **protocol** ==
1793
1794 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
1795
1796 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
1797 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
1798 * **Word address S:** The word address ranges from 0 to 255 (decimal).
1799 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
1800
1801 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
1802
1803 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
1804 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
1805 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
1806 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
1807 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
1808 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
1809 |**PLC word address type**|**Address format**|**Address range**
1810 |S|ddd|S0 ~~ 255
1811 |TS|ffff|TS0 ~~ FFFF
1812 |TP|ffff|TP0 ~~ FFFF
1813 |CS|ffff|CS0 ~~ FFFF
1814 |CP|ffff|CP0 ~~ FFFF
1815 |N|ffff|N0 ~~ FFFF
1816 |F|ffff|F0 ~~ FFFF
1817
1818 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
1819
1820 == **S7-200 Smart Ethernet Protocol** ==
1821
1822 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1823
1824 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1825
1826 **HMI Setting**
1827
1828 (% class="table-bordered" %)
1829 |**Items**|**Settings**|**Note**
1830 |Protocol|Simens S7-200 Smart Ethernet|
1831 |Connection|Ethernet|
1832 |Port No.|102|
1833 |PLC station No.|2|
1834
1835 **Address List**
1836
1837 (% class="table-bordered" %)
1838 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1839 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1840 |Q|Q|Q ddddd.o|0.0~~99999.7|
1841 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1842 |V|V|V ddddd.o|0.0~~99999.7|
1843 |M|M|M ddddd.o|0.0~~99999.7|
1844 |SM|SM|ddddd.o|0.0~~99999.7|
1845 |S|S|ddddd.o|0.0~~99999.7|Read only
1846 |T|T|ddddd|0~~99999|Timer state, read only
1847 |C|C|ddddd|0~~99999|Counter state, read only
1848 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1849 |Q|QW|QW ddddd|0~~99999|
1850 |AI|AIW|AIW ddddd|0~~99999|
1851 |AQ|VB|VB ddddd|0~~99999|
1852 |V|VW|VW ddddd|0~~99998|(((
1853 VW0=VB (0~~1)
1854
1855 VW2=VB (2~~3)
1856
1857 Address value is a multiple of 2
1858 )))
1859 |V|VD|VD ddddd|0~~99998|(((
1860 VD0=VB (0~~3)
1861
1862 VD2=VB (4~~7)
1863
1864 Address value is a multiple of 4
1865 )))
1866 |M|MB|MB ddddd|0~~99999|
1867 |M|MW|MW ddddd|0~~99999|(((
1868 MW0=MB(0~~1)
1869
1870 MW2=MB(2~~3)
1871
1872 Address value is a multiple of 2
1873 )))
1874 |M|MD|MD ddddd|0~~99999|(((
1875 MD0=MB(0~~3)
1876
1877 MD4=MB(4~~7)
1878
1879 Address value is a multiple of 4
1880 )))
1881 |T|TW|TW ddddd|0~~99999|Value of timer
1882 |C|CW|CW ddddd|0~~99999|Value of counter
1883 |W|SW|SW ddddd|0~~99999|
1884
1885 **Communication Settings**
1886
1887 Enable HMI Ethernet in [Project Settings];
1888
1889 (% style="text-align:center" %)
1890 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1891
1892 Set PLC IP in [Device IP] settings;
1893
1894 (% style="text-align:center" %)
1895 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1896
1897 * PLC IP Address: PLC IP
1898 * PLC pot No.: 102(fixed)
1899 * Network:TCP_Client_2N(fixed)
1900
1901 (% style="text-align:center" %)
1902 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1903
1904 * Wait timeout: depend on actual network situation (more than 1500 ms)
1905
1906 **Cable Wiring**
1907
1908 (% style="text-align:center" %)
1909 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1910
1911 == **S7-300 Ethernet Protocol** ==
1912
1913 Supported Series: Siemens S7-300 series PLC
1914
1915 **HMI Setting**
1916
1917 (% class="table-bordered" %)
1918 |**Items**|**Settings**|**Note**
1919 |Protocol|Simens S7-300 Ethernet|
1920 |Connection|Ethernet|
1921 |Port No.|102|
1922 |PLC station No.|2|Need to be same as the PLC setting
1923
1924 **Address List**
1925
1926 (% class="table-bordered" %)
1927 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1928 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1929 |Q|Q|Q ddddd.o|0.0~~99999.7|
1930 |M|M|M ddddd.o|0.0~~99999.7|
1931 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
1932 nnnn: block number;
1933
1934 dddd: address;
1935 )))
1936 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
1937 |Q|QW|QW ddddd|0~~99999|
1938 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
1939 |MW|MW ddddd|0~~99999|(((
1940 MW0=MB(0~~1)
1941
1942 MW2=MB(2~~3)
1943
1944 Address value is a multiple of 2
1945 )))
1946 |MD|MD ddddd|0~~99999|(((
1947 MD0=MB(0~~3)
1948
1949 MD4=MB(4~~7)
1950
1951 Address value is a multiple of 4
1952 )))
1953 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
1954 nnnn: block number;
1955
1956 dddd: address
1957 )))
1958 |DBxDBW|DBxDBW nnnndddd|0~~99999999
1959 |DBxDBD|DBxDBD nnnndddd|0~~99999999
1960
1961 **Communication Settings**
1962
1963 Enable HMI Ethernet in [Project Settings];
1964
1965 (% style="text-align:center" %)
1966 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1967
1968 Set PLC IP in [Device IP] settings;
1969
1970 (% style="text-align:center" %)
1971 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1972
1973 * PLC IP Address: PLC IP
1974 * PLC pot No.: 102(fixed)
1975 * Network:TCP_Client_2N(fixed)
1976
1977 (% style="text-align:center" %)
1978 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1979
1980 * Wait timeout: depend on actual network situation (more than 1500 ms)
1981
1982 **Cable Wiring**
1983
1984 (% style="text-align:center" %)
1985 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1986
1987 == **S7-1200 Ethernet Protocol** ==
1988
1989 Supported Series: Siemens S7-1200
1990
1991 **HMI Setting**
1992
1993 (% class="table-bordered" %)
1994 |**Items**|**Settings**|**Note**
1995 |Protocol|Siemens S7-1200|
1996 |Connection|Ethernet|
1997 |Port No.|102|
1998 |PLC station No.|2|
1999
2000 **Address List**
2001
2002 (% class="table-bordered" %)
2003 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2004 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2005 d:0~-~-9999
2006
2007 o:0-7
2008 )))|
2009 |Q|Q|Q d.o|(((
2010 d:0~-~-9999
2011
2012 o:0-7
2013 )))|
2014 |M|M|M d.o|(((
2015 d:0~-~-9999
2016
2017 o:0-7
2018 )))|
2019 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2020 nn:0-9999,
2021
2022 dddd:0-9999,
2023
2024 o:0-7
2025 )))|(((
2026 nn:DB No.
2027
2028 dddd:address value
2029
2030 o: digit address
2031 )))
2032 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2033 |M|MW|MW d|d:0-99999|(((
2034 MW0=MB(0~~1)
2035
2036 MW2=MB(2~~3)
2037
2038 Address value is a multiple of 2
2039 )))
2040 |M|MD|MD d|d:0-99999|(((
2041 MD0=MB(0~~3)
2042
2043 MD4=MB(4~~7)
2044
2045 Address value is a multiple of 4
2046 )))
2047 |I|IW|IW d|d:0-99999|
2048 |Q|QW|QW d|d:0-99999|
2049 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2050 nn:0-9999
2051
2052 dddd:0-9999
2053 )))|(((
2054 nn:DB No.
2055
2056 dddd:address value
2057 )))
2058 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2059 nn:0-9999
2060
2061 dddd:0-9999
2062 )))|(((
2063 nn:DB No.
2064
2065 dddd:address value
2066
2067 Address value is a multiple of 2
2068 )))
2069 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2070 nn:0-9999
2071
2072 dddd:0-9999
2073 )))|(((
2074 nn:DB No.
2075
2076 dddd:address value
2077
2078 Address value is a multiple of 4
2079 )))
2080
2081 **Communication Settings**
2082
2083 Enable HMI Ethernet in [Project Settings];
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2087
2088 Set PLC IP in [Device IP] settings;
2089
2090 (% style="text-align:center" %)
2091 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2092
2093 **✎Note:**
2094
2095 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2096 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2097 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2098 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2099
2100 **PLC Settings**
2101
2102 Add BD
2103
2104 * Please uncheck [Symbolic access only] option;
2105
2106 (% style="text-align:center" %)
2107 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2108
2109 Address settings, using BD2 as example.
2110
2111 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2112 * 2 represent DB block number
2113 * xxxx represent address
2114
2115 **Such as:**
2116
2117 * DBxDBB20000 = DB2.DBB0
2118 * DBxDBW20004 = DB2.DBW4
2119
2120 (% style="text-align:center" %)
2121 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2122
2123 **How to connect with S7-1200 Firmware V4.0**
2124
2125 PLC configuration
2126
2127 * Double click [device configuration] in Siemens via software
2128 * Double click [protection] to enter protection configuration screen
2129
2130 (% style="text-align:center" %)
2131 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2132
2133 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2134
2135 (% style="text-align:center" %)
2136 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2137
2138 DB settings
2139
2140 * Right click [DB], select [properties]
2141 * Uncheck [optimized block access]
2142
2143 **Cable Wiring**
2144
2145 (% style="text-align:center" %)
2146 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2147
2148 == **S7-XXX Ethernet Protocol** ==
2149
2150 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2151
2152 **HMI Setting**
2153
2154 (% class="table-bordered" style="width:823px" %)
2155 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2156 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2157 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2158 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2159 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2160 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2161
2162 Slot from TIA Portal is equal to Device No. of PIStudio
2163
2164 Rack from TIA Portal is equal to HMI No. of PIStudio
2165
2166 (% style="text-align:center" %)
2167 [[image:S7-XXXCommunication Settings.png]]
2168
2169 (% style="text-align:center" %)
2170 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2171
2172 **Address List**
2173
2174 (% class="table-bordered" %)
2175 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2176 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2177 d:0~-~-9999
2178
2179 o:0-7
2180 )))|
2181 |Q|Q|Q d.o|(((
2182 d:0~-~-9999
2183
2184 o:0-7
2185 )))|
2186 |M|M|M d.o|(((
2187 d:0~-~-9999
2188
2189 o:0-7
2190 )))|
2191 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2192 nn:0-9999,
2193
2194 dddd:0-9999,
2195
2196 o:0-7
2197 )))|(((
2198 nn:DB No.
2199
2200 dddd:address value
2201
2202 o: digit address
2203 )))
2204 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2205 |M|MW|MW d|d:0-99999|(((
2206 MW0=MB(0~~1)
2207
2208 MW2=MB(2~~3)
2209
2210 Address value is a multiple of 2
2211 )))
2212 |M|MD|MD d|d:0-99999|(((
2213 MD0=MB(0~~3)
2214
2215 MD4=MB(4~~7)
2216
2217 Address value is a multiple of 4
2218 )))
2219 |I|IW|IW d|d:0-99999|
2220 |Q|QW|QW d|d:0-99999|
2221 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2222 nn:0-9999
2223
2224 dddd:0-9999
2225 )))|(((
2226 nn:DB No.
2227
2228 dddd:address value
2229 )))
2230 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2231 nn:0-9999
2232
2233 dddd:0-9999
2234 )))|(((
2235 nn:DB No.
2236
2237 dddd:address value
2238
2239 Address value is a multiple of 2
2240 )))
2241 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2242 nn:0-9999
2243
2244 dddd:0-9999
2245 )))|(((
2246 nn:DB No.
2247
2248 dddd:address value
2249
2250 Address value is a multiple of 4
2251 )))
2252
2253 **Communication Settings**
2254
2255 Enable HMI Ethernet in [Project Settings];
2256
2257 (% style="text-align:center" %)
2258 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2259
2260 Set PLC IP in [Device IP] settings;
2261
2262 (% style="text-align:center" %)
2263 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2264
2265 **✎Note:**
2266
2267 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2268 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2269
2270 **Cable Wiring**
2271
2272 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2273
2274 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
2275
2276 Supported Series: Siemens Logo 0BA0, 0BA1 series
2277
2278 **HMI Settings**
2279
2280 (% class="table-bordered" %)
2281 |**Items**|**Settings**|**Note**
2282 |Protocol|Siemens LOGO|
2283 |Connection|Ethernet|
2284 |Port No.|102|
2285 |PLC station No.|2|
2286
2287 **Address List**
2288
2289 (% class="table-bordered" %)
2290 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2291 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2292 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2293 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2294 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2295 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2296 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2297 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2298 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2299 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2300 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2301 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2302 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2303 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2304 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2305 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2306
2307 **PLC Settings in LOGO Software:**
2308
2309 Click [Tools]~-~-[Ethernet Connections],shown as below.
2310
2311 (% style="text-align:center" %)
2312 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2313
2314 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2315
2316 (% style="text-align:center" %)
2317 [[image:image-20221228142937-4.png]]
2318
2319 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2320
2321 (% style="text-align:center" %)
2322 [[image:image-20221228143047-5.png]]
2323
2324 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2325
2326 (% style="text-align:center" %)
2327 [[image:image-20221228143246-6.png]]
2328
2329
2330 **HMI Communication Settings**
2331
2332 Set PLC IP in [Device IP] settings;
2333
2334 (% style="text-align:center" %)
2335 [[image:image-20221228143614-7.png]]
2336
2337 Enable HMI Ethernet in [Project Settings];
2338
2339 (% style="text-align:center" %)
2340 [[image:image-20221228144229-9.png]]
2341
2342 TSAP setting
2343
2344 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2345 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
2346 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
2347 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
2348 ie, ig series: use HSW1200, HSW1201.
2349 HMI V2.0: use HSW1200, HSW1201.
2350
2351 **✎Note:**
2352
2353 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
2354 * HSW10119/HSW1201 is set up as shown.
2355 * (((
2356 (% style="text-align:center" %)
2357 [[image:image-20221228144800-11.png]]
2358 )))
2359 * (((
2360 (% style="text-align:center" %)
2361 [[image:image-20221228144708-10.png]]
2362 )))
2363
2364 * AI word address and Ibit address are read-only and cannot be written on HMI.
2365 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
2366 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
2367 * Written value of RTC cannot exceed 255.
2368
2369 **Cable Wiring**
2370
2371 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2372
2373 == S7-300 232 ==
2374
2375 **HMI Setting:**
2376
2377 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2378 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
2379 |=**PLC I/F**|RS232| |
2380 |=**Baud rate**|19200|9600,19200|
2381 |=**Data bits**|8| |
2382 |=**Parity**|Odd| |
2383 |=**Stop bits**|1| |
2384 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
2385
2386 **Device Address**
2387
2388 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2389 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
2390 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
2391 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
2392 |=Word|(((
2393 DB1 to DB99
2394 )))|DDDDDo|0 ~~ 655327|
2395 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
2396 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
2397 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
2398 |=Double word|MD|DDDD|0 ~~ 4094|
2399 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
2400 Data Register Double Word (must be even)
2401 )))
2402 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
2403
2404 **Cable Wiring**
2405
2406 (% style="text-align:center" %)
2407 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
2408
2409 = Create communication with **Omron** PLC =
2410
2411 == CJ TCP FINS Ethemet  Protocol ==
2412
2413 Supported device:CJ series、CJ1W-EIP21
2414
2415 **HMI Settings**
2416
2417 |=**Items**|=**Settings**|=**Note**
2418 |Protocol|OMRON CJ TCP FINS Ethemet|
2419 |Connection|Ethernet|
2420 |Port No.|9600|
2421 |Device No.|0|
2422 |HMI No.|0|(((
2423
2424 )))
2425
2426 **Address List**
2427
2428 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2429 |Bit|CIO|CIO|CIO d|0~~99999|
2430 |Bit|W|W|W d|0~~99999|
2431 |Bit|D|D|D d|0~~99999|
2432 |Bit|H|H|H d|0~~99999|
2433 |Bit|A|A|A d|0~~99999|
2434 |Bit|T|T|T h|0~~99999|
2435 |Bit|CF|CF|CF d|0~~99999|
2436 |Bit|FF|FF|FF d|0~~99999|
2437 |Bit|C|C|C d|0~~99999|
2438 |Bit|EM0|EM0|EM0 d|0~~99999|
2439 |Bit|EM1|EM1|EM1 d|0~~99999|
2440 |Bit|EM2|EM2|EM2 d|0~~99999|
2441 |Bit|EM3|EM3|EM3 d|0~~99999|
2442 |Bit|EM4|EM4|EM4 d|0~~99999|
2443 |Bit|EM5|EM5|EM5 h|0~~99999|
2444 |Bit|EM6|EM6|EM6 d|0~~99999|
2445 |Bit|EM7|EM7|EM7 d|0~~99999|
2446 |Bit|EM8|EM8|EM8 d|0~~99999|
2447 |Bit|EM9|EM9|EM9 d|0~~99999|
2448 |Bit|EMA|EMA|EMA d|0~~99999|
2449 |Bit|EMB|EMB|EMB d|0~~99999|
2450 |Bit|EMC|EMC|EMC d|0~~99999|
2451 |Bit|Lamp|Lamp|Lamp d|0~~0|
2452 |Word|CIO|CIO|CIO d|0~~99999|
2453 |Word|W|W|W d|0~~99999|
2454 |Word|D|D|D d|0~~99999|
2455 |Word|H|H|H d|0~~99999|
2456 |Word|A|A|A d|0~~99999|
2457 |Word|T|T|T h|0~~99999|
2458 |Word|CF|CF|CF d|0~~99999|
2459 |Word|FF|FF|FF d|0~~99999|
2460 |Word|C|C|C d|0~~99999|
2461 |Word|EM0|EM0|EM0 d|0~~99999|
2462 |Word|EM1|EM1|EM1 d|0~~99999|
2463 |Word|EM2|EM2|EM2 d|0~~99999|
2464 |Word|EM3|EM3|EM3 d|0~~99999|
2465 |Word|EM4|EM4|EM4 d|0~~99999|
2466 |Word|EM5|EM5|EM5 h|0~~99999|
2467 |Word|EM6|EM6|EM6 d|0~~99999|
2468 |Word|EM7|EM7|EM7 d|0~~99999|
2469 |Word|EM8|EM8|EM8 d|0~~99999|
2470 |Word|EM9|EM9|EM9 d|0~~99999|
2471 |Word|EMA|EMA|EMA d|0~~99999|
2472 |Word|EMB|EMB|EMB d|0~~99999|
2473 |Word|EMC|EMC|EMC d|0~~99999|
2474 |Word|IR|IR|IR d|0~~99999|
2475 |Word|DR|DR|DR d|0~~99999|
2476
2477 **Configure the communication protocol**
2478
2479 (% style="text-align:center" %)
2480 [[image:image-20220830143348-1.png]]
2481
2482 (% style="text-align:center" %)
2483 [[image:image-20220830143511-2.png]]
2484
2485 **Configure CJ1W-EIP21 connect with HMI**
2486
2487 (% style="text-align:center" %)
2488 [[image:ftEVGvAprh.png]]
2489
2490 Select TCP_Client_2N
2491
2492 (% style="text-align:center" %)
2493 [[image:RURXWcgyCd.png]]
2494
2495 **Cable Wiring**
2496
2497 Pin Definition Diagram
2498
2499 (% style="text-align:center" %)
2500 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2501
2502 == **CP1E/CP1H serial protocol** ==
2503
2504 Supported device: OMRON CS1(CP1E/CP1H)
2505
2506 **HMI Settings**
2507
2508 |=**Items**|=**Settings**|=**Note**
2509 |Protocol|OMRON CS1(CP1E/CP1H)|
2510 |Connection|RS232 (9600, 2, 7, EVEN)|
2511 |Port No.|None|
2512 |PLC station No.|0|
2513
2514 **Address List**
2515
2516 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2517 |Bit|CIO|CIO|CIO d|0~~99999|
2518 |Bit|W|W|W d|0~~99999|
2519 |Bit|D|D|D d|0~~99999|
2520 |Bit|H|H|H d|0~~99999|
2521 |Bit|A|A|A d|0~~99999|
2522 |Bit|TF|T|T h|0~~99999|
2523 |Bit|CF|CF|CF d|0~~99999|
2524 |Bit|T|FF|FF d|0~~99999|
2525 |Bit|C|C|C d|0~~99999|
2526 |Bit|EM0|EM0|EM0 d|0~~99999|
2527 |Bit|EM1|EM1|EM1 d|0~~99999|
2528 |Bit|EM2|EM2|EM2 d|0~~99999|
2529 |Bit|EM3|EM3|EM3 d|0~~99999|
2530 |Bit|EM4|EM4|EM4 d|0~~99999|
2531 |Bit|EM5|EM5|EM5 h|0~~99999|
2532 |Bit|EM6|EM6|EM6 d|0~~99999|
2533 |Bit|EM7|EM7|EM7 d|0~~99999|
2534 |Bit|EM8|EM8|EM8 d|0~~99999|
2535 |Bit|EM9|EM9|EM9 d|0~~99999|
2536 |Bit|EMA|EMA|EMA d|0~~99999|
2537 |Bit|EMB|EMB|EMB d|0~~99999|
2538 |Bit|EMC|EMC|EMC d|0~~99999|
2539 |Word|CIO|CIO|CIO d|0~~99999|
2540 |Word|W|W|W d|0~~99999|
2541 |Word|D|D|D d|0~~99999|
2542 |Word|H|H|H d|0~~99999|
2543 |Word|A|A|A d|0~~99999|
2544 |Word|T|T|T h|0~~99999|
2545 |Word|CIO|CF|CF d|0~~99999|
2546 |Word|C|C|C d|0~~99999|
2547 |Word|EM0|EM0|EM0 d|0~~99999|
2548 |Word|EM1|EM1|EM1 d|0~~99999|
2549 |Word|EM2|EM2|EM2 d|0~~99999|
2550 |Word|EM3|EM3|EM3 d|0~~99999|
2551 |Word|EM4|EM4|EM4 d|0~~99999|
2552 |Word|EM5|EM5|EM5 h|0~~99999|
2553 |Word|EM6|EM6|EM6 d|0~~99999|
2554 |Word|EM7|EM7|EM7 d|0~~99999|
2555 |Word|EM8|EM8|EM8 d|0~~99999|
2556 |Word|EM9|EM9|EM9 d|0~~99999|
2557 |Word|EMA|EMA|EMA d|0~~99999|
2558 |Word|EMB|EMB|EMB d|0~~99999|
2559 |Word|EMC|EMC|EMC d|0~~99999|
2560 |Word|IR|IR|IR d|0~~99999|
2561 |Word|DR|DR|DR d|0~~99999|
2562
2563 **Configure the communication protocol**
2564
2565 (% style="text-align:center" %)
2566 [[image:image-20220902153118-1.png]]
2567
2568 (% style="text-align:center" %)
2569 [[image:image-20220902151322-2.png]]
2570
2571 **Cable Wiring**
2572
2573 (% style="text-align:center" %)
2574 [[image:image-20220902153949-2.png]]
2575
2576 Pin Definition Diagram
2577
2578 (% style="text-align:center" %)
2579 [[image:image-20220902154056-3.png]]
2580
2581 == **EC55 Protocol** ==
2582
2583 Supported device: EC55 temperature instrument
2584
2585 **1)HMI Settings**
2586
2587 |**Items**|**Settings**|**Note**
2588 |Protocol|Omron EC55|
2589 |Connection|RS485 (9600, 2, 7, EVEN)|
2590 |Port No.|None|
2591 |PLC station No.|0|
2592
2593 **2)Address List**
2594
2595 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2596 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2597 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2598 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2599 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2600 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2601 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2602 |CP|-|0-6|Read controller intrinsic property
2603 |CS|-|0-2|Read controller states
2604 |CA|-|0-17|Action command
2605
2606 **3)Device Settings**
2607
2608 Omron E5CC PLC configuration
2609
2610 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2611
2612 (% style="text-align:center" %)
2613 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2614
2615 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2616
2617 (% style="text-align:center" %)
2618 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2619
2620 **✎Note:** The communication settings for HMI should be consistent with this setting.
2621
2622 **Cable Wiring**
2623
2624 (% style="text-align:center" %)
2625 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2626
2627 (% style="text-align:center" %)
2628 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2629
2630 **✎Note:**
2631
2632 * COM3 only available in PI8000/PI9000 series.
2633 * CA address could not support continuous writing function;
2634 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2635 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2636 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2637 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2638 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2639 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2640 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2641
2642 == **EtherNet/IP NX series Protocol** ==
2643
2644 Supported series: Omron NX/NJ series
2645
2646 **HMI Setting**
2647
2648 |**Items**|**Settings**|**Note**
2649 |Protocol|Omron NX Ethernet/IP|
2650 |Connection|Ethernet|
2651 |Port No.|44818|
2652 |PLC station No.|1|
2653
2654 **Instruction**
2655
2656 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2657
2658 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2659
2660 (% style="text-align:center" %)
2661 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2662
2663 **Export labels from Sysmac Studio**
2664
2665 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2666
2667 (% style="text-align:center" %)
2668 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2669
2670 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2671
2672 Click [Label manage];
2673
2674 (% style="text-align:center" %)
2675 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2676
2677 Click [Import labels] and then select the file exported in step 1;
2678
2679 (% style="text-align:center" %)
2680 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2681
2682 The Import Status field shows the result, click [OK] to finish importing address labels;
2683
2684 (% style="text-align:center" %)
2685 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2686
2687 **Communication Settings**
2688
2689 Enable HMI Ethernet in [Project Settings];
2690
2691 (% style="text-align:center" %)
2692 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2693
2694 Set PLC IP in [Device IP] settings;
2695
2696 (% style="text-align:center" %)
2697 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2698
2699 (% style="text-align:center" %)
2700 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2701
2702 **Cable Wiring**
2703
2704 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2705
2706 == CV/CJ1M/CS1H ==
2707
2708 **HMI Setting:**
2709
2710 |=(% scope="row" %)**Parameters**|=**Recommended**
2711 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2712 |=**PLC I/F**|RS232
2713 |=**Baud rate**|9600
2714 |=**Data bits**|7
2715 |=**Parity**|Even
2716 |=**Stop bits**|2
2717 |=**PLC sta. no.**|0
2718
2719 **PLC Setting:**
2720
2721 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2722
2723 **Device Address:**
2724
2725 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2726 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2727 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2728 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2729 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2730 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2731 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2732 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2733 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2734 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2735 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2736 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2737 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2738 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2739 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2740 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2741 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2742 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2743 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2744 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2745 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2746 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2747 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2748 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2749
2750 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2751 |=W|LR_W|DDDD|0 ~~ 4095|
2752 |=W|TC|DDD|0 ~~ 511|
2753 |=W|DM|DDDD|0 ~~ 9999|Data Register
2754
2755 **Wiring Diagram:**
2756
2757 **RS-232**
2758
2759 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2760
2761 Communication Module:
2762
2763 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2764
2765 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2766
2767 (% style="text-align:center" %)
2768 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2769
2770 = Create communication with Xinje** PLC** =
2771
2772 == XC serial protocol ==
2773
2774 **HMI Settings**
2775
2776 |**Item**|**Settings**|**Note**
2777 |Protocol|XINJE XC MODBUS|
2778 |Connection|RS232|
2779 |Baud rate|19200|
2780 |Data bit|8|
2781 |Parity|EVEN|
2782 |Stop bit|1|
2783 |PLC station No.|1|
2784
2785 **Address List**
2786
2787 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2788 |Bit|M|M|M d|0~~8511|
2789 |Bit|X|X|X o|0~~1747|
2790 |Bit|Y|Y|Y o|0~~1747|
2791 |Bit|S|S|S d|0~~1023|
2792 |Bit|T|T|T d|0~~4095|
2793 |Bit|C|C|C d|0~~634|
2794 |Word|D|D|D d|0~~8511|
2795 |Word|TD|TD|TD d|0~~618|
2796 |Word|CD|CD|CD d|0~~634|
2797 |Word|FD|FD|FD d|0~~8511|
2798
2799 **Configure the communication protocol**
2800
2801 (% style="text-align:center" %)
2802 [[image:image-20220830154105-1.png]]
2803
2804 (% style="text-align:center" %)
2805 [[image:image-20220830154159-3.png]]
2806
2807 **Cable Wiring**
2808
2809 Figure
2810
2811 [[image:image-20220830155728-4.png]]
2812
2813 Pin Definition Diagram
2814
2815 (% style="text-align:center" %)
2816 [[image:image-20220830154131-2.png]]
2817
2818 == XD serial protocol ==
2819
2820 **HMI Settings**
2821
2822 Supported Series: Xinjie XD/XE Series PLC
2823
2824 |=**Item**|=**Settings**|=**Note**
2825 |Protocol|XINJE XD/XC MODBUS|
2826 |Connection|RS232|
2827 |Baud rate|19200|
2828 |Data bit|8|
2829 |Parity|EVEN|
2830 |Stop bit|1|
2831 |PLC station No.|1|
2832
2833 **Address List**
2834
2835 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2836 |Bit|M|M|M d|0~~74999|
2837 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2838 |Bit|X2xx|X2xx|X2xx o|0~~277|
2839 |Bit|X|X|X o|0~~77|
2840 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2841 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2842 |Bit|Y|Y|Y o|0~~4095|
2843 |Bit|SM|SM|SM d|0~~4999|(((
2844
2845 )))
2846 |Bit|T|T|T d|0~~4999|
2847 |Bit|C|C|C d|0~~4999|
2848 |Bit|ET|ET|ET d|0~~31|
2849 |Bit|SE|SE|SE d|0~~31|
2850 |Bit|HM|HM|HM d|0~~11999|
2851 |Bit|HSC|HSC|HSC d|0~~39|
2852 |Bit|HS|HS|HS d|0~~999|
2853 |Bit|HT|HT|HT d|0~~1999|
2854 |Bit|HC|HC|HC d|0~~1999|
2855 |Bit|S|S|S d|0~~7999|
2856 |Word|D|D|D d|0~~69999|
2857 |Word|ID|ID|ID d|0~~99|
2858 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2859 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2860 |Word|QD|QD|QD d|0~~99|
2861 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2862 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2863 |Word|SD|SD|SD d|0~~4999|
2864 |Word|TD|TD|TD d|0~~575|
2865 |Word|CD|CD|CD d|0~~575|
2866 |Word|ETD|ETD|ETD d|0~~31|
2867 |Word|HD|HD|HD d|0~~24999|
2868 |Word|HSD|HSD|HSD d|0~~1023|
2869 |Word|HTD|HTD|HTD d|0~~95|
2870 |Word|HCD|HCD|HCD d|0~~95|
2871 |Word|HSCD|HSCD|HSCD d|0~~31|
2872 |Word|FD|FD|FD d|0~~8191|
2873 |Word|SFD|SFD|SFD d|0~~5999|
2874 |Word|FS|FS|FS d|0~~47|
2875
2876 **Configure the communication protocol**
2877
2878 (% style="text-align:center" %)
2879 [[image:image-20220830160042-1.png]]
2880
2881 (% style="text-align:center" %)
2882 [[image:image-20220830160129-2.png]]
2883
2884 **Cable Wiring**
2885
2886 (% style="text-align:center" %)
2887 [[image:image-20220905093902-1.png]]
2888
2889 Pin Definition Diagram
2890
2891 (% style="text-align:center" %)
2892 [[image:image-20220830160232-3.png]]
2893
2894 = Create communication with Panasonic** PLC** =
2895
2896 == **FP serial protocol** ==
2897
2898 **1)HMI Settings**
2899
2900 |**Item**|**Settings**|**Note**
2901 |Protocol|Panasonic FP MFWTOCOL|
2902 |Connection|RS232|
2903 |Baud rate|9600|
2904 |Data bit|8|
2905 |Parity|ODD|
2906 |Stop bit|1|
2907 |PLC station No.|1|
2908
2909 **2)Address List**
2910
2911 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2912 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2913 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2914 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2915 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2916 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2917 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2918 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2919 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2920 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2921 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2922 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2923 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2924 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2925 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2926 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2927
2928 **3)Configure the communication protocol**
2929
2930 [[image:image-20220830171050-1.png]]
2931
2932 [[image:image-20220830171126-2.png]]
2933
2934 **4)Cable Wiring**
2935
2936 Figure
2937
2938 [[image:image-20220830171328-4.png]]
2939
2940 Pin Definition Diagram
2941
2942 [[image:image-20220830171146-3.png]]
2943
2944 = Create communication with LS** PLC** =
2945
2946 == **XGB serial protocol ** ==
2947
2948 **HMI Settings**
2949
2950
2951 |=**Item**|=**Settings**|=**Note**
2952 |Protocol|LS XGB CPU DRIECT|
2953 |Connection|RS232|
2954 |Baud rate|115200|
2955 |Data bit|8|
2956 |Parity|NONE|
2957 |Stop bit|1|
2958 |PLC station No.|1|
2959
2960 **Address List**
2961
2962
2963 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
2964 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
2965 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
2966 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
2967 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
2968 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
2969 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2970 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
2971 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
2972 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
2973 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
2974 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
2975 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
2976 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
2977 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
2978 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
2979 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
2980 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
2981 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
2982 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
2983 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
2984 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
2985 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
2986 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
2987 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
2988 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
2989 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
2990
2991 **Configure the communication protocol**
2992
2993 (% style="text-align:center" %)
2994 [[image:image-20221028174410-1.png]]
2995
2996 (% style="text-align:center" %)
2997 [[image:image-20221028174753-2.png]]
2998
2999
3000 (% style="text-align:center" %)
3001 [[image:image-20221028181125-4.png]]
3002
3003 **Pin Definition Diagram**
3004
3005 (% style="text-align:center" %)
3006 [[image:image-20221028180930-3.png]]
3007
3008 = Create communication with LS** PLC** =
3009
3010 == **XBC serial protocol** ==
3011
3012 **HMI Settings**
3013
3014 |=**Item**|=**Settings**|=**Note**
3015 |Protocol|LS XBC CNet|
3016 |Connection|RS232|
3017 |Baud rate|115200|
3018 |Data bit|8|
3019 |Parity|NONE|
3020 |Stop bit|1|
3021 |PLC station No.|1|
3022
3023 **Address List**
3024
3025 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3026 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3027 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3028 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3029 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3030 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3031 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3032 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3033 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3034 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3035 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3036 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3037 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3038 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3039 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3040 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3041 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3042 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3043 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3044 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3045 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3046 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3047
3048 **Configure the communication protocol**
3049
3050 (% style="text-align:center" %)
3051 [[image:image-20220831170807-1.png]]
3052
3053 (% style="text-align:center" %)
3054 [[image:image-20220830174733-2.png]]
3055
3056 **Cable Wiring**
3057
3058 (% style="text-align:center" %)
3059 [[image:image-20220830174659-1.png]]
3060
3061 Pin Definition Diagram
3062
3063 (% style="text-align:center" %)
3064 [[image:image-20220830173402-8.png]]
3065
3066 == **XGK FEnet Ethernet protocol** ==
3067
3068 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3069
3070 **HMI Settings**
3071
3072 |**Items**|**Settings**|**Note**
3073 |Protocol|LG XGK FEnet(Ethernet)|
3074 |Connection|Ethernet|
3075 |Port No.|2004|
3076
3077 **Address List**
3078
3079 |**Type**|**Register**|**Range**|**Format**|**Note**
3080 |(% rowspan="14" %)Word|P|0~~2047|P d|
3081 |M|0~~2047|M d|
3082 |K|0~~2047|K d|
3083 |F|0~~2047|F d|
3084 |T|0~~2047|T d|
3085 |C|0~~2047|C d|
3086 |Z|0~~127|Z d|
3087 |S|0~~127|S d|
3088 |L|0~~11263|L d|
3089 |N|0~~21503|N d|
3090 |D|0~~32767|D d|
3091 |R|0~~32767|R d|
3092 |ZR|0~~65535|ZR d|
3093 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3094
3095 **✎Note:**
3096
3097 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3098 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3099 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3100
3101 **Communication settings in HMI**
3102
3103 Enable HMI Ethernet in [Project Settings];
3104
3105 (% style="text-align:center" %)
3106 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3107
3108 Set PLC IP in [Device IP] settings;
3109
3110 (% style="text-align:center" %)
3111 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3112
3113 **Cable Wiring**
3114
3115 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3116
3117 = Create communication with LS** PLC** =
3118
3119 == **XBC serial protocol** ==
3120
3121 **HMI Settings**
3122
3123 |=**Item**|=**Settings**|=**Note**
3124 |Protocol|LS XBC CNet|
3125 |Connection|RS232|
3126 |Baud rate|115200|
3127 |Data bit|8|
3128 |Parity|NONE|
3129 |Stop bit|1|
3130 |PLC station No.|1|
3131
3132 **Address List**
3133
3134 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3135 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3136 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3137 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3138 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3139 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3140 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3141 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3142 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3143 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3144 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3145 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3146 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3147 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3148 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3149 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3150 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3151 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3152 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3153 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3154 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3155 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3156
3157 **Configure the communication protocol**
3158
3159 (% style="text-align:center" %)
3160 [[image:image-20220831170807-1.png]]
3161
3162 (% style="text-align:center" %)
3163 [[image:image-20220830174733-2.png]]
3164
3165 **Cable Wiring**
3166
3167 (% style="text-align:center" %)
3168 [[image:image-20220830174659-1.png]]
3169
3170 Pin Definition Diagram
3171
3172 (% style="text-align:center" %)
3173 [[image:image-20220830173402-8.png]]
3174
3175 == **XGK FEnet Ethernet protocol** ==
3176
3177 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3178
3179 **HMI Settings**
3180
3181 |**Items**|**Settings**|**Note**
3182 |Protocol|LG XGK FEnet(Ethernet)|
3183 |Connection|Ethernet|
3184 |Port No.|2004|
3185
3186 **Address List**
3187
3188 |**Type**|**Register**|**Range**|**Format**|**Note**
3189 |(% rowspan="14" %)Word|P|0~~2047|P d|
3190 |M|0~~2047|M d|
3191 |K|0~~2047|K d|
3192 |F|0~~2047|F d|
3193 |T|0~~2047|T d|
3194 |C|0~~2047|C d|
3195 |Z|0~~127|Z d|
3196 |S|0~~127|S d|
3197 |L|0~~11263|L d|
3198 |N|0~~21503|N d|
3199 |D|0~~32767|D d|
3200 |R|0~~32767|R d|
3201 |ZR|0~~65535|ZR d|
3202 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3203
3204 **✎Note:**
3205
3206 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3207 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3208 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3209
3210 **Communication settings in HMI**
3211
3212 Enable HMI Ethernet in [Project Settings];
3213
3214 (% style="text-align:center" %)
3215 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3216
3217 Set PLC IP in [Device IP] settings;
3218
3219 (% style="text-align:center" %)
3220 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3221
3222 **Cable Wiring**
3223
3224 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3225
3226 = Create communication with **SHIMADEN PLC** =
3227
3228 == **FP23 series protocol** ==
3229
3230 Supported series: SHIMADEN FP23 series
3231
3232 **HMI Setting**
3233
3234 |**Items**|**Settings**|**Note**
3235 |Protocol|SHIMADEN FP23 series|
3236 |Connection|RS485 (9600, 1, 7, EVEN)|
3237 |Port No.|None|
3238 |PLC station No.|0|
3239
3240 **Address List**
3241
3242 |**Device address**|**HMI register**|**Address range**|**Type**
3243 |0040-0043(HEX)|FP040|100064-200067|Read only
3244 |0100-010B(HEX)|FP100|100256-200267|Read only
3245 |0110-0142(HEX)|FP110|100272-200322|Read only
3246 |0182-0252(HEX)|FP182|100386-200594|Write only
3247 |0280-0281(HEX)|FP280|100640-200641|Read only
3248 |0300-030B(HEX)|FP300|100768-200779|Read and write
3249 |0380-039F(HEX)|FP380|100896-200927|Read and write
3250 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3251 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3252 |0600-0670(HEX)|FP600|101536-201814|Read and write
3253 |0720-0738(HEX)|FP720|101824-201848|Read and write
3254 |0800-083F(HEX)|FP800|102048-202111|Read and write
3255 |0900-0952(HEX)|FP900|102304-202386|Read and write
3256 | |Ctrl|0-2|
3257
3258 **✎Note:**
3259
3260 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3261 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3262 * The Ctrl register is used to store the control group number and BCC check mode.
3263
3264 **Ctrl Register Description**
3265
3266 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3267 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3268 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3269 * Ctrl3 reserved
3270
3271 **✎Note:**
3272
3273 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3274
3275 **Cable Wiring**
3276
3277 (% style="text-align:center" %)
3278 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3279
3280 (% style="text-align:center" %)
3281 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3282
3283 **✎Note:** COM3 only available in PI8000/PI9000 series.
3284
3285 == **SR90 protocol** ==
3286
3287 Supported series: SHIMADEN SR90 series
3288
3289 **HMI Setting**
3290
3291 |**Items**|**Settings**|**Note**
3292 |Protocol|SHIMADEN SR90 protocol|
3293 |Connection|RS485 (1200, 1, 7, EVEN)|
3294 |Port No.|None|
3295 |PLC station No.|0|
3296
3297 **Address List**
3298
3299 |**Device address**|**HMI register**|**Address range**|**Type**
3300 |0040-0043 (HEX)|SR040|100064-100067|Read only
3301 |0100-010A(HEX)|SR0100|100256-100266|Read only
3302 |0182-018C(HEX)|SR0182|100386-100396|Write only
3303 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3304 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3305 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3306 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3307 | |Ctrl|0-2|~-~-
3308
3309 **✎Note:**
3310
3311 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3312 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3313 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3314
3315 **Ctrl Register Description**
3316
3317 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3318 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3319 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3320 * Ctrl3 reserved
3321
3322 **✎Note:**
3323
3324 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3325
3326 **Cable Wiring**
3327
3328 (% style="text-align:center" %)
3329 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3330
3331 (% style="text-align:center" %)
3332 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3333
3334 **✎Note:** COM3 only available in PI8000/PI9000 series.
3335
3336 == **MR13 series(standard protocol)** ==
3337
3338 Supported series: SHIMADEN MR13 series
3339
3340 **HMI Setting**
3341
3342 |**Items**|**Settings**|**Note**
3343 |Protocol|SHIMADEN standard protocol|
3344 |Connection|RS485 (1200, 1, 7, EVEN)|
3345 |Port No.|None|
3346 |PLC station No.|0|
3347
3348 **Address List**
3349
3350 |**Device address**|**HMI register**|**Address range**|**Type**
3351 |0100-010B(HEX)|MR100|100256-300267|Read only
3352 |0111-0126(HEX)|MR111|100273-300294|Read only
3353 |0184-0192(HEX)|MR184|100388-300402|Write only
3354 |0280-0282(HEX)|MR280|100640-300642|Read only
3355 |0300-030B(HEX)|MR300|100768-300779|Read/write
3356 |0314-0317(HEX)|MR314|100788-300791|Read/write
3357 |031A(HEX)|MR31A|100794-300794|Read/write
3358 |0320-0321(HEX)|MR320|100800-300801|Read/write
3359 |0400-0504(HEX)|MR400|101024-301284|Read/write
3360 |0506(HEX)|MR506|101286-301286|Read/write
3361 |0510-0514(HEX)|MR510|101296-301300|Read/write
3362 |0516-0524(HEX)|MR516|101302-301316|Read/write
3363 |0526(HEX)|MR526|101318-301318|Read/write
3364 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3365 |~-~-|Ctrl|0-2|~-~-
3366
3367 **✎Note:**
3368
3369 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3370 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3371 * The Ctrl register is used to store the control group number and BCC check mode.
3372
3373 **Ctrl Register Description**
3374
3375 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3376 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3377 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3378 * Ctrl3 reserved
3379
3380 **✎Note:**
3381
3382 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3383
3384 **Cable Wiring**
3385
3386 (% style="text-align:center" %)
3387 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3388
3389 (% style="text-align:center" %)
3390 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3391
3392 **✎Note:** COM3 only available in PI8000/PI9000 series.
3393
3394 = Create communication with **MODBUS** =
3395
3396 == **MODBUS RTU Master** ==
3397
3398 Supported Series: MODBUS RTU CONTROLLER
3399
3400 HMI works as MODBUS SLAVE connecting with MASTER
3401
3402 (% style="text-align:center" %)
3403 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3404
3405
3406 (% style="text-align:center" %)
3407 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3408
3409
3410 (% style="text-align:center" %)
3411 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3412
3413 **HMI Settings**
3414
3415 (% class="table-bordered" %)
3416 |**Items**|**Settings**|**Note**
3417 |Protocol|MODBUS RTU Master|
3418 |Connection|RS485/RS232|
3419 |Baud rate|2400~~187500|
3420 |Data bit|8|
3421 |Parity|Even/ Odd/ None|
3422 |Stop bit|1/2|
3423 |Station No.|0~~255|
3424
3425 **Address List**
3426
3427 (% class="table-bordered" %)
3428 |**Type**|**HMI address**|**MODBUS code**|**Range**
3429 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3430 |Word|HDW3500~~HDW7999|4|0~~4499
3431
3432 **Cable Wiring**
3433
3434 * **RS485**
3435
3436 (% style="text-align:center" %)
3437 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3438
3439 (% style="text-align:center" %)
3440 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3441
3442 * **RS232**
3443
3444 (% style="text-align:center" %)
3445 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3446
3447 **✎Note:** COM3 only available in PI8000/PI9000 series.
3448
3449 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3450
3451 Supported Series: MODBUS RTU CONTROLLER
3452
3453 HMI works as MODBUS MASTER connecting with SLAVE.
3454
3455 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3456
3457 (% style="text-align:center" %)
3458 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3459
3460
3461 (% style="text-align:center" %)
3462 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3463
3464
3465 (% style="text-align:center" %)
3466 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3467
3468 **HMI Settings**
3469
3470 (% class="table-bordered" %)
3471 |**Items**|**Settings**|**Note**
3472 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3473 |Connection|RS485/RS232|
3474 |Baud rate|2400~~187500|
3475 |Data bit|8|
3476 |Parity|Even/ Odd/ None|
3477 |Stop bit|1/2|
3478 |PLC station No.|0~~255|
3479
3480 **Address List**
3481
3482 (% class="table-bordered" %)
3483 |**Type**|**Address Type**|**Function code & Description**
3484 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3485 |06 (write single register: write a binary value to a holding register)
3486 |10 (write values to multiple addresses )
3487 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3488 |06 (write single register: write a binary value to a holding register)
3489 |10 (write values to multiple addresses )
3490 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3491 |06 (write single register: write a binary value to a holding register)
3492 |10 (write values to multiple addresses )
3493 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3494 |10 (write values to multiple addresses )
3495 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3496 |05 (Force a single coil to force the on/off state of a logic coil)
3497 |0F (Write multiple bits, ie write continuously)
3498 |(% rowspan="3" %)1|02 (Read the input state)
3499 |05 (Force a single coil to force the on/off state of a logic coil)
3500 |0F (Write multiple bits)
3501 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3502 |05 (Force a single coil to force the on/off state of a logic coil)
3503 |0F (Write multiple bits)
3504 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3505 |0F (Write multiple bits)
3506
3507 **✎Note:**
3508
3509 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3510 * The function codes sent out are the same as those that read and write words.
3511
3512 **Station number for more than one slaves**
3513
3514 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3515
3516 (% style="text-align:center" %)
3517 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3518
3519 **Cable Wiring**
3520
3521 * **RS485**
3522
3523 (% style="text-align:center" %)
3524 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3525
3526 (% style="text-align:center" %)
3527 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3528
3529 * **RS232**
3530
3531 (% style="text-align:center" %)
3532 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3533
3534 **✎Note:** COM3 only available in PI8000/PI9000 series.
3535
3536 == **Communicate with Modbus Meter** ==
3537
3538 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
3539
3540 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
3541
3542 (% style="text-align:center" %)
3543 [[image:LinfeeDiagram.png]]
3544
3545 (% class="wikigeneratedid" %)
3546 2. Check the specific Modbus parameter in the communication menu from LED display.
3547
3548 (% class="wikigeneratedid" %)
3549 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
3550
3551 {{info}}
3552 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
3553 {{/info}}
3554
3555 (% style="text-align:center" %)
3556 [[image:MeterModbusAllView.png]]
3557
3558 3. Create new project and change the Communication settings.
3559
3560 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
3561
3562 (% style="text-align:center" %)
3563 [[image:PIStudioSetupMeterModbusPara.png]]
3564
3565 (% class="wikigeneratedid" %)
3566 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
3567
3568 (% class="wikigeneratedid" %)
3569 The following table is intercept part of the manual for Linfee Modbus manual.
3570
3571 (% class="wikigeneratedid" %)
3572 **0x03/0x04 command data register address**:
3573
3574 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
3575 | HEX|DEC| | | |
3576 |0x00|0|Reserved| | |
3577 |0x02|2|Reserved| | |
3578 |0x04|4|Reserved| | |
3579 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
3580 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
3581 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
3582 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
3583 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
3584 |0x10|16|Uca|float|2|Line Voltage data, Unit V
3585 |0x12|18|Ia|float|2|Phase Current data, Unit A
3586 |0x14|20|Ib|float|2|Phase Current data, Unit A
3587 |0x16|22|Ic|float|2|Phase Current data, Unit A
3588
3589 {{info}}
3590 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
3591 {{/info}}
3592
3593 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
3594
3595 (% style="text-align:center" %)
3596 [[image:MeterModbusPInumericSet.png]]
3597
3598 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
3599
3600 (% style="text-align:center" %)
3601 [[image:MeterModbusNumericInputFormat.png]]
3602
3603 (% class="wikigeneratedid" %)
3604 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
3605
3606 (% style="text-align:center" %)
3607 [[image:ActualHMIModbusResult.jpg]]
3608
3609 == **MODBUS TCP Slave (All function)** ==
3610
3611 Supported series: MODBUS TCP controller
3612
3613 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3614
3615 (% style="text-align:center" %)
3616 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3617
3618 (% style="text-align:center" %)
3619 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3620
3621
3622 (% style="text-align:center" %)
3623 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3624
3625 **HMI Setting**
3626
3627 (% class="table-bordered" %)
3628 |**Items**|**Settings**|**Note**
3629 |Protocol|MODBUS TCP Slave (All function)|
3630 |Connection|Ethernet|
3631 |Port No.|502|
3632 |PLC station No.|1|
3633
3634 **Address List**
3635
3636 (% class="table-bordered" %)
3637 |**Type**|**Register**|**Function code & Description**
3638 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3639 |06 (write single register: write a binary value to a holding register)
3640 |10 (write values to multiple addresses )
3641 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3642 |06 (write single register: write a binary value to a holding register)
3643 |10 (write values to multiple addresses )
3644 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3645 |06 (write single register: write a binary value to a holding register)
3646 |10 (write values to multiple addresses )
3647 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3648 |10 (write values to multiple addresses )
3649 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3650 |05 (Force a single coil to force the on/off state of a logic coil)
3651 |0F (Write multiple bits, ie write continuously)
3652 |(% rowspan="3" %)1|02 (Read the input state)
3653 |05 (Force a single coil to force the on/off state of a logic coil)
3654 |0F (Write multiple bits)
3655 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3656 |05 (Force a single coil to force the on/off state of a logic coil)
3657 |0F (Write multiple bits)
3658 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3659 |0F (Write multiple bits)
3660
3661 **Communication Settings**
3662
3663 Enable HMI Ethernet in [Project Settings];
3664
3665 (% style="text-align:center" %)
3666 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3667
3668 Set PLC IP in [Device IP] settings;
3669
3670 (% style="text-align:center" %)
3671 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3672
3673 **Cable Wiring**
3674
3675 (% style="text-align:center" %)
3676 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3677
3678 = **Printer** =
3679
3680 == **TSPL label printer** ==
3681
3682 **Introduction**
3683
3684 TSPL label printer protocol supports following models.
3685
3686 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3687 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3688
3689 **Setting Step**
3690
3691 Select the protocol
3692
3693 * Create a new project, select the TSPL label printer protocol as shown below.
3694
3695 (% style="text-align:center" %)
3696 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3697
3698 Set parameters
3699
3700 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3701
3702 Printer register
3703
3704 (% class="table-bordered" %)
3705 |**Register**|**System**|**Range**|**Function**
3706 |TSPL_SP|decimal|0 - 1|Set the paper size
3707 |TSPL_PT|decimal|0 - 1999|Print text
3708 |TSPL_PQ|decimal|0 - 999|Print QR code
3709 |TSPL_PB|decimal|0 - 999|Print barcode
3710 |TSPL_PR|decimal|0 - 1|Print offset
3711 |TSPL_PN|decimal|0 - 0|Trigger printing
3712 |TSPL_PS|decimal|0 - 0|Print status
3713
3714 * Set paper size:
3715 ** TSPL_SP0: width of paper, unit: mm.
3716 ** TSPL_SP1: height of paper, unit: mm.
3717 * Print text:
3718 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3719 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3720
3721 (% class="table-bordered" %)
3722 |**Register**|**Function**|**Description**
3723 |TSPL_PT0|X coordinate|Unit: dot
3724 |TSPL_PT1|Ycoordinate|Unit: dot
3725 |TSPL_PT2|Rotation angle|(((
3726 0: 0 degrees
3727
3728 1: 90 degrees
3729
3730 2: 180 degrees
3731
3732 3: 270 degrees
3733 )))
3734 |TSPL_PT3|Size|Range: 0-3
3735 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3736
3737 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3738
3739 Print QR code:
3740
3741 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3742 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3743
3744 (% class="table-bordered" %)
3745 |**Register**|**Function**|**Description**
3746 |TSPL_PQ0|X coordinate|Unit: dot
3747 |TSPL_PQ1|Ycoordinate|Unit: dot
3748 |TSPL_PQ2|Rotation angle|(((
3749 0: 0 degrees
3750
3751 1: 90 degrees
3752
3753 2: 180 degrees
3754
3755 3: 270 degrees
3756 )))
3757 |TSPL_PQ3|Size|Range: 0-5
3758 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3759
3760 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3761
3762 Print bar code:
3763
3764 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3765 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3766
3767 (% class="table-bordered" %)
3768 |**Register**|**Function**|**Description**
3769 |TSPL_PB0|X coordinate|Unit: dot
3770 |TSPL_PB1|Ycoordinate|Unit: dot
3771 |TSPL_PB2|Rotation angle|(((
3772 0: 0 degrees
3773
3774 1: 90 degrees
3775
3776 2: 180 degrees
3777
3778 3: 270 degrees
3779 )))
3780 |TSPL_PB3|height|Unit: dot
3781 |TSPL_PB4|width|Range:0-2
3782 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3783
3784 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3785
3786 Print offset:
3787
3788 * TSPL_PR0: X coordinate offset, unit: mm;
3789 * TSPL_PR1: Y coordinate offset, unit: mm.
3790
3791 Trigger printing:
3792
3793 * TSPL_PN0 = 1: trigger the printer to start printing.
3794
3795 Printing status:
3796
3797 * TSPL_PS0 = 1: The printing is normal.
3798 * TSPL_PS0 = 1: The printing is abnormal.
3799
3800 Print picture
3801
3802 * For the function of printing pictures, please refer to the configuration of [Printer object].
3803
3804 Conversion between dot and mm
3805
3806 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3807
3808 == **EpsonTM series** ==
3809
3810 **HMI Settings**
3811
3812 (% class="table-bordered" %)
3813 |**Item**|**Settings**|**Note**
3814 |Protocol|EPSON-TM-T82II/TM-XXX|
3815 |Connection|RS232|
3816 |Baud rate|9600~~115200|
3817 |Data bit|8|
3818 |Parity|None|
3819 |Stop bit|1|
3820 |PLC station No.|1|
3821
3822 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3823
3824 **Printer Settings**
3825
3826 (% class="table-bordered" %)
3827 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3828 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3829 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3830 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3831 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3832 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3833 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3834
3835 **Cable Wiring**
3836
3837 (% style="text-align:center" %)
3838 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3839
3840 (% style="text-align:center" %)
3841 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3842
3843 **✎Note:** COM3 only available in PI8000/PI9000 series.
3844
3845
3846 = Create communication with **Schneider PLC** =
3847
3848 == **Schneider MODBUS RTU** ==
3849
3850 **HMI Setting**
3851
3852 |=**Parameters**|=**Recommended**|=**Notes**
3853 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3854 |Connection|RS485|
3855 |**Baud rate**|19200|
3856 |**Data bit**|8|
3857 |**Parity**|Even|
3858 |**Stop bit**|1|
3859 |**PLC station No.**|1|
3860
3861 **PLC Setting**
3862
3863 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3864
3865 **Device Address**
3866
3867 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3868 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3869 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3870 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3871 |W|MW|DDDDDD|0 ~~ 999999|Output register
3872 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3873
3874 **Wiring Diagram**
3875
3876 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3877
3878 (% style="text-align:center" %)
3879 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3880
3881 = **Barcode Scanner** =
3882
3883 Supported: DELI 14880 barcode scanner
3884
3885 **HMI Setting**
3886
3887 |**Items**|**Settings**|**Note**
3888 |Protocol|Barcode Scanner|
3889 |Connection|USB|
3890
3891 **Operating Procedures**
3892
3893 Select [Barcode Scanner];
3894
3895 (% style="text-align:center" %)
3896 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3897
3898 Set address for receiving;
3899
3900 Set correct length;
3901
3902 (% style="text-align:center" %)
3903 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3904
3905 **✎Note:**
3906
3907 * The protocol uploads the information acquired by the USB scanner to the HMI;
3908 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3909 * Recommended model: DELI 14880 barcode scanner;
3910
3911 = **Hitachi EHV Series (Ethernet)** =
3912
3913 Supported series: Hitachi EHV series
3914
3915 **HMI Settings**
3916
3917 (% class="table-bordered" %)
3918 |**Items**|**Settings**|**Note**
3919 |Protocol|Hitachi EHV series|
3920 |Connection|Ethernet|
3921 |Port No.|3004~~3007|
3922
3923 **Address List**
3924
3925 (% class="table-bordered" %)
3926 |**Type**|**Register**|**Range**|**Format**|**Note**
3927 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3928 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3929 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3930 H1H2H3H4 Module main number
3931
3932 H1: Remote number
3933
3934 H2: Unit number
3935
3936 H3: Slot number
3937
3938 H4: Word number of Module
3939
3940 H Sub number of Module
3941
3942 For example:X21.3
3943
3944 Slot number 2
3945
3946 Word number of module is 1
3947
3948 Bit number of module is 3
3949
3950 Remote number and unit number are 0
3951 )))
3952 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3953 |R|0 – FF.f (Hex)|R HH.h|
3954 |L|0 - 73FF.f (Hex)|L HHHH.h|
3955 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3956 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3957 H1H2H3H4 Module main number
3958
3959 H1: Remote number
3960
3961 H2: Unit number
3962
3963 H3: Slot number
3964
3965 H4: Word number of module
3966
3967 For example:WX21
3968
3969 Word number of module is 1
3970
3971 Slot number is 2
3972
3973 Remote number and unit number are 0
3974 )))
3975 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3976 |WR|0 – FFFF (Hex)|WR HHHH|
3977 |WL|0 - 73FF (Hex)|WL HHHH|
3978 |TC|0 - 2559|TC DDDD|
3979
3980 **Communication settings in HMI**
3981
3982 Enable HMI Ethernet in [Project Settings];
3983
3984 (% style="text-align:center" %)
3985 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3986
3987 Set PLC IP in [Device IP] settings;
3988
3989 (% style="text-align:center" %)
3990 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3991
3992 **PLC Configuration**
3993
3994 Connect with PLC, select[Online mode];
3995
3996 (% style="text-align:center" %)
3997 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3998
3999 Set IP address, it is the same LAN parameters with HMI;
4000
4001 (% style="text-align:center" %)
4002 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4003
4004 3) Save PLC communication parameter, and restart PLC
4005
4006 **PLC Monitor Mode**
4007
4008 Connect with PLC and choose to “online” mode
4009
4010 (% style="text-align:center" %)
4011 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4012
4013 Open I/O monitor sheet1
4014
4015 (% style="text-align:center" %)
4016 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4017
4018 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4019
4020 (% style="text-align:center" %)
4021 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4022
4023 Enter the register address, click OK to view the value of the register.
4024
4025 (% style="text-align:center" %)
4026 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4027
4028 (% style="text-align:center" %)
4029 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4030
4031 **✎Note:**
4032
4033 * Both word registers and bit registers support even continuous read/write functions;
4034 * The range of registers is based on the specific PLC type;
4035
4036 **Cable Wiring**
4037
4038 (% style="text-align:center" %)
4039 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4040
4041 = **IEC60870-5 104 Client** =
4042
4043 **HMI Setting**
4044
4045 (% class="table-bordered" %)
4046 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4047 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4048 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4049 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4050
4051 **Address List**
4052
4053 (% class="table-bordered" %)
4054 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4055 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4056 |(% style="width:461px" %)SCNA|0~~16777215.7
4057 |(% style="width:461px" %)DPTB|0~~16777215.7
4058 |(% style="width:461px" %)DCNA|0~~16777215.7
4059 |(% style="width:461px" %)METF|0~~16777215.7
4060 |(% style="width:461px" %)SENC|0~~16777215.7
4061 |(% style="width:461px" %)SENA|0~~16777215.7
4062 |(% style="width:461px" %)MENA|0~~16777215.7
4063 |(% style="width:461px" %)METD|0~~16777215.7
4064 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4065 |(% style="width:461px" %)SCNA|0~~16777215
4066 |(% style="width:461px" %)DPTB|0~~16777215
4067 |(% style="width:461px" %)DCNA|0~~16777215
4068 |(% style="width:461px" %)SENA|0~~16777215
4069 |(% style="width:461px" %)MENA|0~~16777215
4070 |(% style="width:461px" %)METD|0~~16777215
4071 |(% style="width:461px" %)INRO|0~~16777215
4072 |(% style="width:461px" %)TIMESYN|0~~16777215
4073 |(% style="width:461px" %)TIMEZ|0~~16777215
4074 |(% style="width:461px" %)NTP|0~~16777215
4075 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4076 |(% style="width:461px" %)SENC|0~~16777215
4077
4078 **Address Configuration**
4079
4080 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4081
4082 (% style="text-align:center" %)
4083 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4084
4085 (% style="text-align:center" %)
4086 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4087
4088 Extended tag name
4089
4090 Address range for the extended tag.
4091
4092 **Communication Settings**
4093
4094 Enable HMI Ethernet in [Project Settings];
4095
4096 (% style="text-align:center" %)
4097 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4098
4099 Set PLC IP in [Device IP] settings;
4100
4101 (% style="text-align:center" %)
4102 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4103
4104 **Cable Wiring**
4105
4106 (% style="text-align:center" %)
4107 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4108
4109 = **OpenCAN** =
4110
4111 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4112
4113 This protocol is only available in PI8000 series HMI.
4114
4115 **HMI Settings**
4116
4117 |**Items**|**Settings**|**Note**
4118 |Protocol|OPENCAN|
4119 |Connection|CAN port|
4120 |Baud rate|250000|
4121
4122 **CAN frame setting in HMI**
4123
4124 Click [OpenCAN setting] button in communication setting window;
4125
4126 (% style="text-align:center" %)
4127 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4128
4129 Click [Add] to create a new frame;
4130
4131 (% style="text-align:center" %)
4132 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4133
4134 |**No**|**Items**|**Description**
4135 |1|Add|add a frame related to register address
4136 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4137 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4138 |4|Modify|Modify the frames in frame management
4139 |5|Copy|Copy one frame to another
4140 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4141 |7|Empty|All frames in the list are cleared
4142 |8|Browse|Displays configuration files in XML format in IE
4143 |9|OK|Complete the configuration of the frame and exit
4144
4145 Set CANBUS frame in setting windows
4146
4147 (% style="text-align:center" %)
4148 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4149
4150 |**No**|**Items**|**Description**
4151 |1|ID|Set the ID of a can frame in hexadecimal format;
4152 |2|ID assign|split the ID by PF, PS, and SA;
4153 |3|Frame type|Select Standard frame or Extended Frame;
4154 |4|Frame format|Select between data frame and remote Frame;
4155 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4156 |6|Use address|(((
4157 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4158
4159 **Edit:** Set a bit or word address by its format;
4160
4161 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4162 )))
4163 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4164 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4165 |Feedback mode: feedback mode includes no response, confirm response and data response;
4166 |No response: the device or touch screen will not receive feedback;
4167 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4168 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4169 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4170 |Response timeout: sets whether the response frame timeout;
4171 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4172 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4173 |Manually send: a manually send tick indicates only one send;
4174 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4175 |10|Note|Fill the text to explain the meaning of the frame;
4176 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4177 |12|Current operation display|Display the description of current operation;
4178 |13|Add|Add a new frame;
4179 |14|Save frame|Save the configured frame format;
4180 |15|Cancel|Cancel the frame configuration;
4181
4182 Set CAN address (Read or write operation);
4183
4184 (% style="text-align:center" %)
4185 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4186
4187 |**No.**|**Item**|**Description**
4188 |1|Current address|Displays the register type and register address set by the user in the data access interface
4189 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4190 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4191 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4192 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4193 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4194 |If the trigger condition is a writing operation, there are two situations:(((
4195 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4196 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4197 )))
4198 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4199 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4200 |4|Add|Add current configuration
4201 |5|Close|Close the configuration window to exit
4202
4203 **Multiple Packages Settings**
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4207
4208 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4209
4210 Select Multiple package type
4211
4212 * Not Multiple packages
4213 * J1939 Multiple packages
4214 * Customized Multiple packages
4215
4216 Click [Edit Receive data] for [Receive] settings
4217
4218 * Start code+ Total length (J1939)
4219
4220 (% style="text-align:center" %)
4221 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4222
4223 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4224
4225 * Start code + Data max length (J1939)
4226
4227 (% style="text-align:center" %)
4228 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4229
4230 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4231
4232 * Data max length (J1939)
4233
4234 (% style="text-align:center" %)
4235 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4236
4237 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4238
4239 * Customized multiple package
4240
4241 (% style="text-align:center" %)
4242 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4243
4244 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4245
4246 Click [Edit Send data] for [Send] setting
4247
4248 * J1939
4249
4250 (% style="text-align:center" %)
4251 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4252
4253 [Data] is all data to be sent.
4254
4255 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4256
4257 * Customized multiple package
4258
4259 (% style="text-align:center" %)
4260 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4261
4262 [Data] is all data to be sent.
4263
4264 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4265
4266 **Cable Wiring**
4267
4268 (% style="text-align:center" %)
4269 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4270
4271 **✎Note:** The address interval between each frame need to be more than a word address;
4272
4273
4274 = **User Defined Protocol** =
4275
4276 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4277
4278 **HMI Settings**
4279
4280 |**Items**|**Settings**|**Note**
4281 |Protocol|User defined protocol|
4282 |Connection|RS485/RS232|
4283 |Baud rate|2400~~187500|
4284 |Stop bits|1/ 2|
4285 |Data bits|7/ 8|
4286 |Parity|None/ Even/ ODD|
4287
4288 **Operating Procedures**
4289
4290 Select [User defined protocol];
4291
4292 Click [User defined protocol] button to open setting window as below;
4293
4294 (% style="text-align:center" %)
4295 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4296
4297 Configure user defined command;
4298
4299 (% style="text-align:center" %)
4300 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4301
4302 |**No**|**Item**|**Description**
4303 |1|Instruction edit|The required command.
4304 |2|Mode|Write to address or read from the address.
4305 |3|Format|Encode format: HEX or ASCII.
4306 |4|Other|(((
4307 **No receiving: **HMI does not respond to the receiving command.
4308
4309 **Send after receiving:** HMI responds to the receiving command.
4310 )))
4311 |5|Manually send|(((
4312 Respond once after trigger the address.
4313
4314 Address: set the trigger address.
4315 )))
4316 |6|Add|Save this setting.
4317 |7|Cancel|Cancel current settings.
4318 |(% rowspan="4" %)8|Add|Add a new command.
4319 |Edit|Edit the selected command.
4320 |Delete|Delete the selected command.
4321 |Clear|Clear all the commands.
4322 |9|Instruction list|Display all current commands.
4323 |10|Address List|Display all the addresses added.
4324 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4325 |Export|Export current command settings to local storage.
4326 |Browse|Browse local command files.
4327 |Advanced|Combine two commands.
4328 |Exit|Complete editing and exit setting.
4329
4330 **Operating Procedures**
4331
4332 Click [Add] to create a new command, as below shows;
4333
4334 (% style="text-align:center" %)
4335 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4336
4337 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4338
4339 (% style="text-align:center" %)
4340 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4341
4342 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4343
4344 (% style="text-align:center" %)
4345 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4346
4347 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4348
4349 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4350
4351 Check settings;
4352
4353 (% style="text-align:center" %)
4354 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4355
4356 |**No**|**Items**|**Description**
4357 |1|Add checking|Add checking command when receiving the data.
4358 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4359 |Differ with send check|Set return checking.
4360 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4361 |Length: The data length need to be checked.
4362
4363 Object settings;
4364
4365 (% style="text-align:center" %)
4366 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4367
4368 |**No**|**Items**|**Description**
4369 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4370 |Address: the triggering address;
4371 |Note: description to object;
4372 |2|Byte order|The numerical display order;
4373
4374 Data length settings;
4375
4376 (% style="text-align:center" %)
4377 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4378
4379 |**No**|**Item**|**Description**
4380 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4381 |Length: the return data length.
4382 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4383 |Length: the write data length.
4384
4385 Instruction length settings
4386
4387 (% style="text-align:center" %)
4388 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4389
4390 |**No**|**Item**|**Description**
4391 |1|Send length|The instruction data will only send designated data length.
4392 |2|Return length|The responds data length.
4393 |3|End code|Instruction will not be terminated until receiving [End code];
4394
4395 **Cable Wiring**
4396
4397 * **RS485**
4398
4399 (% style="text-align:center" %)
4400 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4401
4402 (% style="text-align:center" %)
4403 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4404
4405 * **RS232**
4406
4407 (% style="text-align:center" %)
4408 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4409
4410 **✎Note:** COM3 only available in PI8000/PI9000 series.