Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 247.4 by Hunter on 2023/05/06 14:11

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |**Type**|(% style="width:238px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" %)Bit|(% style="width:238px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:238px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:238px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:238px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:238px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:238px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:238px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:238px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:238px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:238px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:238px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:238px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="9" %)Word|(% style="width:238px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:238px" %)SD|(% style="width:311px" %)SDDDD|0~~255|
896 |(% style="width:238px" %)Z|(% style="width:311px" %)ZDD|0~~15|
897 |(% style="width:238px" %)T1|(% style="width:311px" %)T1DDD|0~~255|
898 |(% style="width:238px" %)04|(% style="width:311px" %)04DDDD|0~~9999|
899 |(% style="width:238px" %)05|(% style="width:311px" %)05DDDD|0~~9999|
900 |(% style="width:238px" %)06|(% style="width:311px" %)06DDDD|0~~9999|
901 |(% style="width:238px" %)07|(% style="width:311px" %)07DDDD|0~~9999|
902 |(% style="width:238px" %)08|(% style="width:311px" %)08DDDD|0~~9999|
903
904 = **Create communication with Inovance PLC** =
905
906 == **H1U/H2U serial protocol** ==
907
908 **HMI Settings**
909
910 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
911 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
912 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
913 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
914 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
915 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
916 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
917 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
918 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
919
920 (% class="wikigeneratedid" %)
921 **Address List**
922
923 (% style="width:1014px" %)
924 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
925 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
926 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
927 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
928 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
929 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
930 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
931 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
932 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
933 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
934 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
935 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
936 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
937 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
938 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
939 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
940 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
941 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
942
943 (% class="wikigeneratedid" %)
944 **Cable Wiring**
945
946 (% style="text-align:center" %)
947 [[image:Inovance.png]]
948
949 == **H3U serial protocol** ==
950
951 **HMI Settings**
952
953 |=**Item**|=**Settings**|=**Note**
954 |Protocol|INOVANCE H3U PLC|
955 |Connection|RS422|
956 |Baud rate|9600|
957 |Data bit|7|
958 |Parity|EVEN|
959 |Stop bit|1|
960 |PLC station No.|0|
961
962 **Address List**
963
964 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
965 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
966 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
967 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
968 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
969 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
970 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
971 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
972 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
973 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
974 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
975 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
976 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
977 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
978 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
979 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
980 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
981 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
982 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
983
984 **Configure the communication protocol**
985
986 (% style="text-align:center" %)
987 [[image:image-20220830170114-4.png]]
988
989 [[image:image-20220830170017-3.png]]
990
991 **Cable Wiring**
992
993 (% style="text-align:center" %)
994 [[image:Inovance.png]]
995
996 == **H3U Ethernet portocol** ==
997
998 **HMI Settings**
999
1000 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1001 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1002 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1003 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1004 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1005 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1006
1007 **Address List**
1008
1009 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1010 |Bit|M|M DDDD|0~~8511|
1011 |Bit|SM|SM DDDD|0~~1023|
1012 |Bit|S|S DDDD|0~~4095|
1013 |Bit|T|T DDD|0~~511|
1014 |Bit|C|C DDD|0~~255|
1015 |Bit|X|X OOO|0~~571|
1016 |Bit|Y|Y OOO|0~~571|
1017 |Word|D|D DDDD|0~~8511|
1018 |Word|SD |SD DDDD|0~~1023|
1019 |Word|R|R DDDDD|0~~32767|
1020 |Word|T|T DDD|0~~255|
1021 |Word|C|C DDD|0~~199|
1022 |Double Word|C|C DDD|200~~255|
1023
1024 **Cable Wiring**
1025
1026 (% style="text-align:center" %)
1027 [[image:CommonEthernet.png]]
1028
1029 = Create communication with **Mitsubishi PLC** =
1030
1031 == **FX1S, 1N, 2N Series Protocol** ==
1032
1033 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1034
1035 **HMI Settings**
1036
1037 |**Item**|**Settings**|**Note**
1038 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1039 |Connection|RS422/RS485/RS232|
1040 |Baud rate|9600~~115200|
1041 |Data bit|7/8|
1042 |Parity|EVEN/Odd/None|
1043 |Stop bit|1/2|
1044 |PLC station No.|1~~255|
1045
1046 **Address List**
1047
1048 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1049 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1050 |Y|Y|Y o|0~~303237|
1051 |M|M|M d|0~~99999|
1052 |T|T|T d|0~~99999|
1053 |C|C|C d|0~~99999|
1054 |S|S|S d|0~~99999|
1055 |SM|SM|SM d|8000~~9999|
1056 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1057 |Y|Y|Y o|0~~303237|
1058 |M|M|M d|0~~99999|
1059 |T|T|T d|0~~99999|
1060 |C|C|C d|0~~199|
1061 |D|D|D d|0~~7999|
1062 |S|S|S d|0~~99999|
1063 |SD|SD|SD d|8000~~9999|
1064
1065 **Cable Wiring**
1066
1067 * **RS485**
1068
1069 (% style="text-align:center" %)
1070 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1071
1072 (% style="text-align:center" %)
1073 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1074
1075 * **RS422**
1076
1077 (% style="text-align:center" %)
1078 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1079
1080 **✎Note:** COM3 only available in PI8000/PI9000 series.
1081
1082 == **FX3U/3G/3GA serial protocol** ==
1083
1084 **HMI Settings**
1085
1086 |=**Item**|=**Settings**|=**Note**
1087 |Protocol|Mitsubishi FX3U/3G/3GA|
1088 |Connection|RS422|
1089 |Baud rate|9600~~115200|
1090 |Data bit|7/8|
1091 |Parity|EVEN/Odd/None|
1092 |Stop bit|1/2|
1093 |PLC station No.|1~~255|
1094
1095 **Address List**
1096
1097 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1098 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1099 |Y|Y|Y o|0~~303237|
1100 |M|M|M d|0~~99999|
1101 |T|T|T d|0~~99999|
1102 |C|C|C d|0~~99999|
1103 |S|S|S d|0~~99999|
1104 |SM|SM|SM d|8000~~9999|
1105 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1106 |Y|Y|Y o|0~~303237|
1107 |M|M|M d|0~~99999|
1108 |T|T|T d|0~~99999|
1109 |C|C|C d|0~~199|
1110 |D|D|D d|0~~7999|
1111 |S|S|S d|0~~99999|
1112 |SD|SD|SD d|8000~~9999|
1113
1114 **Configure the communication protocol**
1115
1116 (% style="text-align:center" %)
1117 [[image:image-20220831095222-1.png]]
1118
1119 (% style="text-align:center" %)
1120 [[image:image-20220831095743-2.png]]
1121
1122 **Wiring**
1123
1124 (% style="text-align:center" %)
1125 [[image:image-20220831100314-6.png]]
1126
1127 == **FX3U Ethernet Protocol** ==
1128
1129 Mitsubishi FX3U series PLC
1130
1131 **HMI Settings**
1132
1133 |Items|Settings|Note
1134 |Protocol|Mitsubishi FX3U|
1135 |Connection|Ethernet|
1136 |Port No.|5009|Must be the same as the PLC setting
1137 |PLC station No.|0|
1138
1139 **Address List**
1140
1141 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1142 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1143 |Y|Y|Y OOO|0~~377|
1144 |M|M|M DDDD|0~~7679|
1145 |SM|SM|SM DDDD|8000~~8511|
1146 |S|S|S DDDD|0~~4095|
1147 |TS|TS|TS DDD|0~~511|
1148 |CS|CS|CS DDD|0~~255|
1149 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1150 |TN|TN|TN DDD|0~~511|
1151 |D|D|D DDDD|0~~7999|
1152 |SD|SD|SD DDDD|8000~~8511|
1153 |R|R|R DDDDD|0~~32767|
1154
1155 **Ethernet Module Settings**
1156
1157 FX3U-ENET-L module configuration
1158 Set up the FX3U-ENET-L Ethernet module settings as follows.
1159 Select the module location, which in this document is Module 0.
1160
1161 [[image:image-20221115140802-1.png]]
1162
1163 Select "Operational setting" to enter the following screen.
1164
1165 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1166
1167 [[image:image-20221115142728-4.png]]
1168
1169 Select "Open setting" to enter the setting interface, the settings are as follows.
1170
1171 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1172
1173 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1174
1175 [[image:image-20221115142945-5.png]]
1176
1177 Click on "transter setup" - "PC side I/F setting", see the following figure.
1178
1179 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1180
1181 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1182
1183 [[image:image-20221115143341-6.png||height="426" width="712"]]
1184
1185 Read and write data from the Ethernet module
1186
1187 [[image:image-20221115143703-7.png]]
1188
1189 Set "Transter setup" to COM communication, and read or write operation as shown below
1190
1191 [[image:image-20221115143809-8.png]]
1192
1193 **PLC Settings (GX Works 2)**
1194
1195 Create a blank FX5U project
1196
1197 Find Current Connection in the navigation
1198
1199 [[image:image-20221115144335-9.png||height="422" width="706"]]
1200
1201 Select Connection Channel List
1202
1203 Select Ethernet board communication
1204
1205 [[image:image-20221115144824-10.png||height="421" width="705"]]
1206
1207 Select Ethernet Module
1208 Set the IP address of the PLC
1209
1210 [[image:image-20221115145228-11.png||height="674" width="708"]]
1211
1212 Read or write PLC data, in this document is read
1213
1214 [[image:image-20221115145553-12.png||height="424" width="711"]]
1215
1216 [[image:image-20221115145559-13.png||height="424" width="711"]]
1217
1218 **HMI Communication Setting**
1219
1220 [[image:image-20221115150003-14.png||height="425" width="712"]]
1221
1222 [[image:image-20221115150235-15.png||height="427" width="713"]]
1223
1224 [[image:image-20221115145559-13.png||height="424" width="711"]]
1225
1226 **HMI Communication Setting**
1227
1228 [[image:image-20221115150003-14.png||height="425" width="712"]]
1229
1230 [[image:image-20221115150235-15.png||height="427" width="713"]]
1231
1232 == **FX5U Serial Port Protocol** ==
1233
1234 Mitsubishi FX5U series PLC
1235
1236 **HMI Settings**
1237
1238 |**Item**|**Settings**|**Note**
1239 |Protocol|Mitsubishi FX5U|
1240 |Connection|RS422/RS485|
1241 |Baud rate|9600|
1242 |Data bit|7|
1243 |Parity|Odd|
1244 |Stop bit|1|
1245 |PLC station No.|1~~255|Need to be the same as PLC settings
1246
1247 **Address List**
1248
1249 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1250 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1251 |Y|Y|Y o|0~~303237|
1252 |M|M|M d|0~~99999|
1253 |B|B|B h|0~~7FFF|
1254 |F|F|F d|0~~32767|
1255 |SB|SB|SB h|0~~7FFF|
1256 |TS|TS|TS d|0~~1023|
1257 |TC|TC|TC d|0~~1023|
1258 |STS|STS|STS d|0~~1023|
1259 |STC|STC|STS d|0~~1023|
1260 |CS|CS|CS d|0~~1023|
1261 |CC|CC|CC d|0~~1023|
1262 |SM|SM|SM d|0~~9999|
1263 |L|L|L d|0~~32767|
1264 |S|S|S d|0~~4095|
1265 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1266 |TN|TN|TN d|0~~1023|
1267 |STN|STN|STN d|0~~1023|
1268 |CN|CN|CN d|0~~1023|
1269 |R|R|R d|0~~32767|
1270 |SW|SW|SW h|0~~7FFF|
1271 |Z|Z|Z d|0~~23|
1272 |D|D|D d|0~~7999|
1273 |SD|SD|SD d|0~~11999|
1274
1275 **PLC Settings (GX Works 3)**
1276
1277 Create a blank FX5U project
1278
1279 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1283
1284 Select protocol in the setting item, and set parameters.
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1288
1289 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1290
1291 (% style="text-align:center" %)
1292 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1293
1294 Click the [Apply] button to finish the setting.
1295
1296 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1297
1298 (% style="text-align:center" %)
1299 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1300
1301 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1302
1303 Done.
1304
1305 **Cable Wiring**
1306
1307 * **RS485**
1308
1309 (% style="text-align:center" %)
1310 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1311
1312 (% style="text-align:center" %)
1313 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1314
1315 * **RS422**
1316
1317 (% style="text-align:center" %)
1318 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1319
1320 **✎Note:** COM3 only available in PI8000/PI9000 series.
1321
1322 == **L02 Serial Protocol** ==
1323
1324 Mitsubishi L02 series CPU built-in serial port.
1325
1326 **HMI Settings**
1327
1328 |=**Item**|=**Settings**|=**Note**
1329 |Protocol|Mitsubishi L02|
1330 |Connection|RS422|
1331 |Baud rate|115200|
1332 |Data bit|8|
1333 |Parity|Odd|
1334 |Stop bit|1|
1335 |PLC station No.|1~~255|Need to be the same as PLC settings
1336
1337 **Address List**
1338
1339 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1340 |Bit|X|X|X h|0~~FFFF|
1341 |Bit|Y|Y|Y h|0~~FFFF|
1342 |Bit|M|M|M d|0~~9999|
1343 |Bit|L|L|L d|0~~9999|
1344 |Bit|F|F|F d|0~~9999|
1345 |Bit|B|B|B h|0~~FFFF|
1346 |Bit|V|V|V d|0~~2047|
1347 |Bit|TC|TC|TC d|0~~9999|
1348 |Bit|SS|SS|SS d|0~~9999|
1349 |Bit|SC|SC|SC d|0~~9999|
1350 |Bit|CS|CS|CS d|0~~9999|
1351 |Bit|CC|CC|CC d|0~~9999|
1352 |Bit|SB|SB|SB h|0~~FFFF|
1353 |Bit|SM|SM|SM d|0~~2047|
1354 |Bit|STS|STS|STS d|0~~1023|
1355 |Bit|S|S|S d|0~~9999|
1356 |Bit|DX|DX|DX h|0~~FFFF|
1357 |Bit|DY|DY|DY h|0~~FFFF|
1358 |Bit|TS|TS|TS d|0~~9999|
1359 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1360 |Word|W|W|W h|0~~FFFF|
1361 |Word|TN|TN|TN d|0~~99999|
1362 |Word|SN|SN|SN d|0~~99999|
1363 |Word|CN|CN|CN d|0~~99999|
1364 |Word|R|R|R d|0~~99999|
1365 |Word|SW|SW|SW h|0~~FFFF|
1366 |Word|Z|Z|Z d|0~~99999|
1367 |Word|ZR|ZR|ZR h|0~~FFFF|
1368 |Word|D|D|D d|0~~99999|
1369
1370 **Communication Settings**
1371
1372 (% style="text-align:center" %)
1373 [[image:image-20220831105732-3.png]]
1374
1375 (% style="text-align:center" %)
1376 [[image:image-20220831110004-5.png]]
1377
1378 **Cable Wiring**
1379
1380 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1381
1382 Pin Definition Diagram
1383
1384 (% style="text-align:center" %)
1385 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1386
1387 == **L02 MELSEC (Ethernet) Protocol** ==
1388
1389 Mitsubishi Q series CPU built-in Ethernet port.
1390
1391 **HMI Settings**
1392
1393 |**Items**|**Settings**|**Note**
1394 |Protocol|MIT L02 CPU MELSEC|
1395 |Connection|Ethernet|
1396 |Port No.|1025|Must be the same as the PLC setting
1397 |PLC station No.|0|Must be the same as the PLC setting
1398
1399 **Address List**
1400
1401 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1402 |Bit|X|X|X h|0~~FFFF|
1403 |Bit|Y|Y|Y h|0~~FFFF|
1404 |Bit|M|M|M d|0~~9999|
1405 |Bit|L|L|L d|0~~9999|
1406 |Bit|F|F|F d|0~~9999|
1407 |Bit|B|B|B h|0~~FFFF|
1408 |Bit|V|V|V d|0~~2047|
1409 |Bit|TC|TC|TC d|0~~9999|
1410 |Bit|SS|SS|SS d|0~~9999|
1411 |Bit|SC|SC|SC d|0~~9999|
1412 |Bit|CS|CS|CS d|0~~9999|
1413 |Bit|CC|CC|CC d|0~~9999|
1414 |Bit|SB|SB|SB h|0~~FFFF|
1415 |Bit|SM|SM|SM d|0~~2047|
1416 |Bit|STS|STS|STS d|0~~1023|
1417 |Bit|S|S|S d|0~~9999|
1418 |Bit|DX|DX|DX h|0~~FFFF|
1419 |Bit|DY|DY|DY h|0~~FFFF|
1420 |Bit|TS|TS|TS d|0~~9999|
1421 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1422 |Word|W|W|W h|0~~FFFF|
1423 |Word|TN|TN|TN d|0~~99999|
1424 |Word|SN|SN|SN d|0~~99999|
1425 |Word|CN|CN|CN d|0~~99999|
1426 |Word|R|R|R d|0~~99999|
1427 |Word|SW|SW|SW h|0~~FFFF|
1428 |Word|Z|Z|Z d|0~~99999|
1429 |Word|ZR|ZR|ZR h|0~~FFFF|
1430 |Word|D|D|D d|0~~99999|
1431
1432 **Communication Settings**
1433
1434 Enable HMI Ethernet in [Project Settings];
1435
1436 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1437
1438 Set PLC IP in [Device IP] settings;
1439
1440 (% style="text-align:center" %)
1441 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1442
1443 **PLC Settings (GX Works2 )**
1444
1445 Create a project
1446
1447 Set PLC IP, subnet mask and gateway;
1448
1449 Select [Binary Code] as communication data code;
1450
1451 (% style="text-align:center" %)
1452 [[image:image-20221108202109-2.png||height="636" width="732"]]
1453
1454 Set PLC port number, for example 1025
1455
1456 (% style="text-align:center" %)
1457 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1458
1459 Save settings;
1460
1461 Download project into PLC device;
1462
1463 Restart PLC device;
1464
1465 **Cable Wiring**
1466
1467 (% style="text-align:center" %)
1468 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1469
1470 == **QJ71C24N MELSEC Protocol** ==
1471
1472 Mitsubishi QJ71C24N communication module built-in serial port;
1473
1474 **HMI Settings**
1475
1476 |**Items**|**Settings**|**Note**
1477 |Protocol|MIT QJ71 MELSEC|
1478 |Connection|422|
1479 |Baud rate|9600|
1480 |Data bit|8|
1481 |Parity|ODD|
1482 |Stop bit|1|
1483 |PLC station No.|1~~255|Need to be the same as PLC settings
1484
1485 **Address List**
1486
1487 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1488 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1489 |Y|Y|Y FFFF|0~~1FFF|
1490 |M|M|M DDDDD|0~~99999|
1491 |L|L|L DDDD|0~~8191|
1492 |F|F|F DDDD|0~~2047|
1493 |V|V|V DDDD|0~~2047|
1494 |B|B|B FFFF|0~~1FFF|
1495 |TS|TS|TS DDDD|0~~2047|
1496 |TC|TC|TC DDDD|0~~2047|
1497 |SS|SS|SS DDDD|0~~2047|
1498 |SC|SC|SC DDDD|0~~2047|
1499 |CS|CS|CS DDDD|0~~1023|
1500 |CC|CC|CC DDDD|0~~1023|
1501 |SB|SB|SB FFF|0~~7FF|
1502 |S|S|S D|0~~8191|
1503 |DX|DX|DX FFFF|0~~1FFF|
1504 |DY|DY|DY FFFF|0~~1FFF|
1505 |SM_|SM_|SM_ DDDD|8000~~9999|
1506 |SM|SM|SM DDDD|0~~2047|
1507 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1508 |D|D|D DDDDD|0~~12287|
1509 |W|W|W FFFF|0~~1FFF|
1510 |TN|TN|TN DDDD|0~~2047|
1511 |SN|SN|SN DDDD|0~~2047|
1512 |CN|CN|CN DDDD|0~~1023|
1513 |R|R|R DDDDD|0~~32767|
1514 |SW|SW|SW FFF|0~~7FF|
1515 |Z|Z|Z D|0~~15|
1516 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1517
1518 **Communication Settings**
1519
1520 (% style="text-align:center" %)
1521 [[image:image-20221109135738-1.png]]
1522
1523 (% style="text-align:center" %)
1524 [[image:image-20221109140016-3.png]]
1525
1526 Pin Definition Diagram
1527
1528 (% style="text-align:center" %)
1529 [[image:image-20221109140406-4.png]]
1530
1531 == **QJ71E71 MELSEC Protocol** ==
1532
1533 Mitsubishi QJ71E71 Ethernet communication module;
1534
1535 **HMI Settings**
1536
1537 |**Items**|**Settings**|**Note**
1538 |Protocol|MIT QJ71E71 MELSEC|
1539 |Connection|Ethernet|
1540 |Port No.|1025|Must be the same as the PLC setting
1541 |PLC station No.|0|Must be the same as the PLC setting
1542
1543 **Address List**
1544
1545 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1546 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1547 |Y|Y|Y h|0~~1FFF|
1548 |M|M|M d|0~~99999|
1549 |L|L|L d|0~~8191|
1550 |F|F|F d|0~~2047|
1551 |B|B|B h|0~~1FFF|
1552 |V|V|V d|0~~2047|
1553 |TS|TS|TS d|0~~2047|
1554 |TC|TC|TC d|0~~2047|
1555 |SS|SS|SS d|0~~2047|
1556 |SC|SC|SC d|0~~2047|
1557 |CS|CS|CS d|0~~1023|
1558 |CC|CC|CC d|0~~1023|
1559 |SB|SB|SB h|0~~7FF|
1560 |S|S|S d|0~~8191|
1561 |DX|DX|DX h|0~~1FFF|
1562 |DY|DY|DY h|0~~1FFF|
1563 |SM|SM|SM d|8000~~9999|
1564 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1565 |D|D|D d|0~~12287|
1566 |W|W|W h|0~~1FFF|
1567 |TN|TN|TN d|0~~2047|
1568 |SN|SN|SN d|0~~2047|
1569 |CN|CN|CN d|0~~1023|
1570 |R|R|R d|0~~32767|
1571 |SW|SW|SW h|0~~7FF|
1572 |Z|Z|Z d|0~~15|
1573 |ZR|ZR|ZR h|0~~FE7FF|
1574
1575 **HMI Communication Settings**
1576
1577 1) Enable HMI Ethernet in [Project Settings];
1578
1579 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1580
1581 2) Set PLC IP in [Device IP] settings
1582
1583 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1584
1585 **PLC Settings(GX Works2)**
1586
1587 * Click [Ethernet/CC IE/MELSECNET];
1588 * Please select [Ethernet] as network type;
1589 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1590 * Select [Online] as Mode;
1591 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1592 * Click [Operation setting] to set IP;
1593 * Select [Binary Code] as [Communication Data Code];
1594 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1595 * Click [Open setting]
1596 * Set protocol: TCP;
1597 * Set [unpassive] in [Open system];
1598 * Set [receive] in [Fixed buffer];
1599 * Set [procedure Exist] in [Fixed buffer communication];
1600 * Disable [Pairing open];
1601 * Set [No confirm] in [Existence confirmation];
1602 * Host station port number: 5009;
1603 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1604 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1605 * Download project into PLC and restart it
1606
1607 **Cable Wiring**
1608
1609
1610 (% style="text-align:center" %)
1611 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1612
1613 = Create communication with **Rockwell PLC** =
1614
1615 == **DF1 Protocol** ==
1616
1617 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1618
1619 **HMI Settings**
1620
1621 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1622 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
1623 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1624 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1625 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1626 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1627 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1628 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1629 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1630
1631 **Address List**
1632
1633 (% class="table-bordered" %)
1634 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1635 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1636 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1637 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
1638 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1639 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
1640 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1641 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1642 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1643 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1644 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1645 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
1646
1647 **Cable Wiring**
1648
1649 (% style="text-align:center" %)
1650 [[image:AB.gif]]
1651
1652 == **DF1 Advanced Protocol** ==
1653
1654 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1655
1656 **HMI Settings**
1657
1658 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1659 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
1660 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1661 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1662 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1663 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1664 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1665 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1666 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1667
1668 **Address List**
1669
1670 (% class="table-bordered" %)
1671 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1672 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1673 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1674 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1675 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
1676 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1677 Bit data file B0~~B99
1678
1679 First two digits is for file number
1680
1681 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
1682 )))
1683 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
1684 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1685 Integer data file bit format N0~~N99
1686
1687 First two digits is for file number
1688
1689 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
1690 )))
1691 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1692 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1693 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1694 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1695 Timer Preset Value
1696
1697 First two digits is for file number
1698
1699 For example, TNS99255 represents file number T99, address 255.
1700 )))
1701 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1702 Timer Accumulator Value
1703
1704 First two digits is for file number
1705
1706 For example, TNP99255 represents file number T99, address 255.
1707 )))
1708 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1709 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1710 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1711 Counter Preset Value
1712
1713 First two digits is for file number
1714
1715 For example, CNS99255 represents file number C99, address 255.
1716 )))
1717 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1718 Counter Accumulator Value
1719
1720 First two digits is for file number
1721
1722 For example, CNP99255 represents file number C99, address 255.
1723 )))
1724 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
1725 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1726 Integer data file
1727
1728 First two digits is for file number
1729
1730 For example, NN99255 represents file number N99, address 255.
1731 )))
1732 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
1733 Only able to communicate with file number F8
1734 )))
1735 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1736 Floating point data file
1737
1738 First two digits is for file number
1739
1740 For example, FN99255 represents file number F99, address 255.
1741 )))
1742 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
1743
1744 **Cable Wiring**
1745
1746 (% style="text-align:center" %)
1747 [[image:AB.gif]]
1748
1749 == **MicroLogix Protocol** ==
1750
1751 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
1752
1753 **HMI Settings**
1754
1755 (% class="table-bordered" %)
1756 |**Item**|**Settings**|**Note**
1757 |Protocol|Allen-Bradlley MicroLogix|
1758 |Connection|RS232|
1759 |Baud rate|19200|
1760 |Data bit|8|
1761 |Parity|None|
1762 |Stop bit|1|
1763 |PLC station No.|1|
1764
1765 **Address List**
1766
1767 (% class="table-bordered" %)
1768 |**Type**|**Device registers**|**Format**|**Range**|**Note**
1769 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
1770 |O|O d.d|0.0~~255.15|
1771 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1772 |S|S d.d|0.0~~255.15|
1773 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1774 |(% rowspan="9" %)Word|S|S d|0~~255|
1775 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
1776 |TP|TP nnhh|0~~ffff
1777 |CS|CS nnhh|0~~ffff
1778 |CP|CP nnhh|0~~ffff
1779 |N|N nnhh|0~~ffff
1780 |C|C nnhh|0~~ffff
1781 |T|T nnhh|0~~ffff
1782 |R|R nnhh|0~~ffff
1783
1784 **Cable Wiring**
1785
1786
1787 (% style="text-align:center" %)
1788 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
1789
1790 == **CompactLogix FreeTag Ethernet protocol** ==
1791
1792 Allen-Brandly CompactLogix
1793
1794 **HMI Settings**
1795
1796 (% class="table-bordered" %)
1797 |**Items**|**Settings**|**Note**
1798 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
1799 |Connection|Ethernet|
1800 |Port No.|44818|
1801
1802 **PLC Setting**
1803
1804 Create new tags
1805
1806 (% style="text-align:center" %)
1807 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
1808
1809 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
1810
1811 (% style="text-align:center" %)
1812 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
1813
1814 Import labels, please open [Communication] window and click [Import label];
1815
1816 Select csv file, all tags will be displayed as belows;
1817
1818 (% style="text-align:center" %)
1819 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
1820
1821 **✎Note:**
1822
1823 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
1824
1825 (% style="text-align:center" %)
1826 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
1827
1828 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
1829
1830 **Communication settings in HMI**
1831
1832 Enable HMI Ethernet in [Project Settings];
1833
1834 (% style="text-align:center" %)
1835 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
1836
1837 Set PLC IP in [Device IP] settings;
1838
1839 (% style="text-align:center" %)
1840 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1841
1842 **Cable Wiring**
1843
1844 (% style="text-align:center" %)
1845 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
1846
1847 == **MicroLogix 1200** **protocol** ==
1848
1849 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
1850
1851 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
1852 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
1853 * **Word address S:** The word address ranges from 0 to 255 (decimal).
1854 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
1855
1856 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
1857
1858 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
1859 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
1860 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
1861 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
1862 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
1863 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
1864 |**PLC word address type**|**Address format**|**Address range**
1865 |S|ddd|S0 ~~ 255
1866 |TS|ffff|TS0 ~~ FFFF
1867 |TP|ffff|TP0 ~~ FFFF
1868 |CS|ffff|CS0 ~~ FFFF
1869 |CP|ffff|CP0 ~~ FFFF
1870 |N|ffff|N0 ~~ FFFF
1871 |F|ffff|F0 ~~ FFFF
1872
1873 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
1874
1875 == **S7-200 Smart Ethernet Protocol** ==
1876
1877 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1878
1879 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1880
1881 **HMI Setting**
1882
1883 (% class="table-bordered" %)
1884 |**Items**|**Settings**|**Note**
1885 |Protocol|Simens S7-200 Smart Ethernet|
1886 |Connection|Ethernet|
1887 |Port No.|102|
1888 |PLC station No.|2|
1889
1890 **Address List**
1891
1892 (% class="table-bordered" %)
1893 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1894 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1895 |Q|Q|Q ddddd.o|0.0~~99999.7|
1896 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1897 |V|V|V ddddd.o|0.0~~99999.7|
1898 |M|M|M ddddd.o|0.0~~99999.7|
1899 |SM|SM|ddddd.o|0.0~~99999.7|
1900 |S|S|ddddd.o|0.0~~99999.7|Read only
1901 |T|T|ddddd|0~~99999|Timer state, read only
1902 |C|C|ddddd|0~~99999|Counter state, read only
1903 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1904 |Q|QW|QW ddddd|0~~99999|
1905 |AI|AIW|AIW ddddd|0~~99999|
1906 |AQ|VB|VB ddddd|0~~99999|
1907 |V|VW|VW ddddd|0~~99998|(((
1908 VW0=VB (0~~1)
1909
1910 VW2=VB (2~~3)
1911
1912 Address value is a multiple of 2
1913 )))
1914 |V|VD|VD ddddd|0~~99998|(((
1915 VD0=VB (0~~3)
1916
1917 VD2=VB (4~~7)
1918
1919 Address value is a multiple of 4
1920 )))
1921 |M|MB|MB ddddd|0~~99999|
1922 |M|MW|MW ddddd|0~~99999|(((
1923 MW0=MB(0~~1)
1924
1925 MW2=MB(2~~3)
1926
1927 Address value is a multiple of 2
1928 )))
1929 |M|MD|MD ddddd|0~~99999|(((
1930 MD0=MB(0~~3)
1931
1932 MD4=MB(4~~7)
1933
1934 Address value is a multiple of 4
1935 )))
1936 |T|TW|TW ddddd|0~~99999|Value of timer
1937 |C|CW|CW ddddd|0~~99999|Value of counter
1938 |W|SW|SW ddddd|0~~99999|
1939
1940 **Communication Settings**
1941
1942 Enable HMI Ethernet in [Project Settings];
1943
1944 (% style="text-align:center" %)
1945 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1946
1947 Set PLC IP in [Device IP] settings;
1948
1949 (% style="text-align:center" %)
1950 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1951
1952 * PLC IP Address: PLC IP
1953 * PLC pot No.: 102(fixed)
1954 * Network:TCP_Client_2N(fixed)
1955
1956 (% style="text-align:center" %)
1957 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1958
1959 * Wait timeout: depend on actual network situation (more than 1500 ms)
1960
1961 **Cable Wiring**
1962
1963 (% style="text-align:center" %)
1964 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1965
1966 == **S7-300 Ethernet Protocol** ==
1967
1968 Supported Series: Siemens S7-300 series PLC
1969
1970 **HMI Setting**
1971
1972 (% class="table-bordered" %)
1973 |**Items**|**Settings**|**Note**
1974 |Protocol|Simens S7-300 Ethernet|
1975 |Connection|Ethernet|
1976 |Port No.|102|
1977 |PLC station No.|2|Need to be same as the PLC setting
1978
1979 **Address List**
1980
1981 (% class="table-bordered" %)
1982 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1983 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1984 |Q|Q|Q ddddd.o|0.0~~99999.7|
1985 |M|M|M ddddd.o|0.0~~99999.7|
1986 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
1987 nnnn: block number;
1988
1989 dddd: address;
1990 )))
1991 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
1992 |Q|QW|QW ddddd|0~~99999|
1993 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
1994 |MW|MW ddddd|0~~99999|(((
1995 MW0=MB(0~~1)
1996
1997 MW2=MB(2~~3)
1998
1999 Address value is a multiple of 2
2000 )))
2001 |MD|MD ddddd|0~~99999|(((
2002 MD0=MB(0~~3)
2003
2004 MD4=MB(4~~7)
2005
2006 Address value is a multiple of 4
2007 )))
2008 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2009 nnnn: block number;
2010
2011 dddd: address
2012 )))
2013 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2014 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2015
2016 **Communication Settings**
2017
2018 Enable HMI Ethernet in [Project Settings];
2019
2020 (% style="text-align:center" %)
2021 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2022
2023 Set PLC IP in [Device IP] settings;
2024
2025 (% style="text-align:center" %)
2026 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2027
2028 * PLC IP Address: PLC IP
2029 * PLC pot No.: 102(fixed)
2030 * Network:TCP_Client_2N(fixed)
2031
2032 (% style="text-align:center" %)
2033 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2034
2035 * Wait timeout: depend on actual network situation (more than 1500 ms)
2036
2037 **Cable Wiring**
2038
2039 (% style="text-align:center" %)
2040 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2041
2042 == **S7-1200 Ethernet Protocol** ==
2043
2044 Supported Series: Siemens S7-1200
2045
2046 **HMI Setting**
2047
2048 (% class="table-bordered" %)
2049 |**Items**|**Settings**|**Note**
2050 |Protocol|Siemens S7-1200|
2051 |Connection|Ethernet|
2052 |Port No.|102|
2053 |PLC station No.|2|
2054
2055 **Address List**
2056
2057 (% class="table-bordered" %)
2058 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2059 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2060 d:0~-~-9999
2061
2062 o:0-7
2063 )))|
2064 |Q|Q|Q d.o|(((
2065 d:0~-~-9999
2066
2067 o:0-7
2068 )))|
2069 |M|M|M d.o|(((
2070 d:0~-~-9999
2071
2072 o:0-7
2073 )))|
2074 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2075 nn:0-9999,
2076
2077 dddd:0-9999,
2078
2079 o:0-7
2080 )))|(((
2081 nn:DB No.
2082
2083 dddd:address value
2084
2085 o: digit address
2086 )))
2087 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2088 |M|MW|MW d|d:0-99999|(((
2089 MW0=MB(0~~1)
2090
2091 MW2=MB(2~~3)
2092
2093 Address value is a multiple of 2
2094 )))
2095 |M|MD|MD d|d:0-99999|(((
2096 MD0=MB(0~~3)
2097
2098 MD4=MB(4~~7)
2099
2100 Address value is a multiple of 4
2101 )))
2102 |I|IW|IW d|d:0-99999|
2103 |Q|QW|QW d|d:0-99999|
2104 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2105 nn:0-9999
2106
2107 dddd:0-9999
2108 )))|(((
2109 nn:DB No.
2110
2111 dddd:address value
2112 )))
2113 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2114 nn:0-9999
2115
2116 dddd:0-9999
2117 )))|(((
2118 nn:DB No.
2119
2120 dddd:address value
2121
2122 Address value is a multiple of 2
2123 )))
2124 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2125 nn:0-9999
2126
2127 dddd:0-9999
2128 )))|(((
2129 nn:DB No.
2130
2131 dddd:address value
2132
2133 Address value is a multiple of 4
2134 )))
2135
2136 **Communication Settings**
2137
2138 Enable HMI Ethernet in [Project Settings];
2139
2140 (% style="text-align:center" %)
2141 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2142
2143 Set PLC IP in [Device IP] settings;
2144
2145 (% style="text-align:center" %)
2146 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2147
2148 **✎Note:**
2149
2150 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2151 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2152 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2153 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2154
2155 **PLC Settings**
2156
2157 Add BD
2158
2159 * Please uncheck [Symbolic access only] option;
2160
2161 (% style="text-align:center" %)
2162 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2163
2164 Address settings, using BD2 as example.
2165
2166 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2167 * 2 represent DB block number
2168 * xxxx represent address
2169
2170 **Such as:**
2171
2172 * DBxDBB20000 = DB2.DBB0
2173 * DBxDBW20004 = DB2.DBW4
2174
2175 (% style="text-align:center" %)
2176 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2177
2178 **How to connect with S7-1200 Firmware V4.0**
2179
2180 PLC configuration
2181
2182 * Double click [device configuration] in Siemens via software
2183 * Double click [protection] to enter protection configuration screen
2184
2185 (% style="text-align:center" %)
2186 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2187
2188 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2189
2190 (% style="text-align:center" %)
2191 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2192
2193 DB settings
2194
2195 * Right click [DB], select [properties]
2196 * Uncheck [optimized block access]
2197
2198 **Cable Wiring**
2199
2200 (% style="text-align:center" %)
2201 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2202
2203 == **S7-XXX Ethernet Protocol** ==
2204
2205 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2206
2207 **HMI Setting**
2208
2209 (% class="table-bordered" style="width:823px" %)
2210 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2211 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2212 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2213 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2214 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2215 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2216
2217 Slot from TIA Portal is equal to Device No. of PIStudio
2218
2219 Rack from TIA Portal is equal to HMI No. of PIStudio
2220
2221 (% style="text-align:center" %)
2222 [[image:S7-XXXCommunication Settings.png]]
2223
2224 (% style="text-align:center" %)
2225 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2226
2227 **Address List**
2228
2229 (% class="table-bordered" %)
2230 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2231 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2232 d:0~-~-9999
2233
2234 o:0-7
2235 )))|
2236 |Q|Q|Q d.o|(((
2237 d:0~-~-9999
2238
2239 o:0-7
2240 )))|
2241 |M|M|M d.o|(((
2242 d:0~-~-9999
2243
2244 o:0-7
2245 )))|
2246 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2247 nn:0-9999,
2248
2249 dddd:0-9999,
2250
2251 o:0-7
2252 )))|(((
2253 nn:DB No.
2254
2255 dddd:address value
2256
2257 o: digit address
2258 )))
2259 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2260 |M|MW|MW d|d:0-99999|(((
2261 MW0=MB(0~~1)
2262
2263 MW2=MB(2~~3)
2264
2265 Address value is a multiple of 2
2266 )))
2267 |M|MD|MD d|d:0-99999|(((
2268 MD0=MB(0~~3)
2269
2270 MD4=MB(4~~7)
2271
2272 Address value is a multiple of 4
2273 )))
2274 |I|IW|IW d|d:0-99999|
2275 |Q|QW|QW d|d:0-99999|
2276 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2277 nn:0-9999
2278
2279 dddd:0-9999
2280 )))|(((
2281 nn:DB No.
2282
2283 dddd:address value
2284 )))
2285 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2286 nn:0-9999
2287
2288 dddd:0-9999
2289 )))|(((
2290 nn:DB No.
2291
2292 dddd:address value
2293
2294 Address value is a multiple of 2
2295 )))
2296 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2297 nn:0-9999
2298
2299 dddd:0-9999
2300 )))|(((
2301 nn:DB No.
2302
2303 dddd:address value
2304
2305 Address value is a multiple of 4
2306 )))
2307
2308 **Communication Settings**
2309
2310 Enable HMI Ethernet in [Project Settings];
2311
2312 (% style="text-align:center" %)
2313 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2314
2315 Set PLC IP in [Device IP] settings;
2316
2317 (% style="text-align:center" %)
2318 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2319
2320 **✎Note:**
2321
2322 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2323 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2324
2325 **Cable Wiring**
2326
2327 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2328
2329 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
2330
2331 Supported Series: Siemens Logo 0BA0, 0BA1 series
2332
2333 **HMI Settings**
2334
2335 (% class="table-bordered" %)
2336 |**Items**|**Settings**|**Note**
2337 |Protocol|Siemens LOGO|
2338 |Connection|Ethernet|
2339 |Port No.|102|
2340 |PLC station No.|2|
2341
2342 **Address List**
2343
2344 (% class="table-bordered" %)
2345 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2346 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2347 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2348 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2349 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2350 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2351 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2352 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2353 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2354 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2355 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2356 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2357 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2358 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2359 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2360 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2361
2362 **PLC Settings in LOGO Software:**
2363
2364 Click [Tools]~-~-[Ethernet Connections],shown as below.
2365
2366 (% style="text-align:center" %)
2367 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2368
2369 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2370
2371 (% style="text-align:center" %)
2372 [[image:image-20221228142937-4.png]]
2373
2374 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2375
2376 (% style="text-align:center" %)
2377 [[image:image-20221228143047-5.png]]
2378
2379 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2380
2381 (% style="text-align:center" %)
2382 [[image:image-20221228143246-6.png]]
2383
2384
2385 **HMI Communication Settings**
2386
2387 Set PLC IP in [Device IP] settings;
2388
2389 (% style="text-align:center" %)
2390 [[image:image-20221228143614-7.png]]
2391
2392 Enable HMI Ethernet in [Project Settings];
2393
2394 (% style="text-align:center" %)
2395 [[image:image-20221228144229-9.png]]
2396
2397 TSAP setting
2398
2399 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2400 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
2401 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
2402 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
2403 ie, ig series: use HSW1200, HSW1201.
2404 HMI V2.0: use HSW1200, HSW1201.
2405
2406 **✎Note:**
2407
2408 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
2409 * HSW10119/HSW1201 is set up as shown.
2410 * (((
2411 (% style="text-align:center" %)
2412 [[image:image-20221228144800-11.png]]
2413 )))
2414 * (((
2415 (% style="text-align:center" %)
2416 [[image:image-20221228144708-10.png]]
2417 )))
2418
2419 * AI word address and Ibit address are read-only and cannot be written on HMI.
2420 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
2421 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
2422 * Written value of RTC cannot exceed 255.
2423
2424 **Cable Wiring**
2425
2426 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2427
2428 == S7-300 232 ==
2429
2430 **HMI Setting:**
2431
2432 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2433 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
2434 |=**PLC I/F**|RS232| |
2435 |=**Baud rate**|19200|9600,19200|
2436 |=**Data bits**|8| |
2437 |=**Parity**|Odd| |
2438 |=**Stop bits**|1| |
2439 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
2440
2441 **Device Address**
2442
2443 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2444 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
2445 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
2446 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
2447 |=Word|(((
2448 DB1 to DB99
2449 )))|DDDDDo|0 ~~ 655327|
2450 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
2451 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
2452 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
2453 |=Double word|MD|DDDD|0 ~~ 4094|
2454 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
2455 Data Register Double Word (must be even)
2456 )))
2457 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
2458
2459 **Cable Wiring**
2460
2461 (% style="text-align:center" %)
2462 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
2463
2464 = Create communication with **Omron** PLC =
2465
2466 == CJ TCP FINS Ethemet  Protocol ==
2467
2468 Supported device:CJ series、CJ1W-EIP21
2469
2470 **HMI Settings**
2471
2472 |=**Items**|=**Settings**|=**Note**
2473 |Protocol|OMRON CJ TCP FINS Ethemet|
2474 |Connection|Ethernet|
2475 |Port No.|9600|
2476 |Device No.|0|
2477 |HMI No.|0|(((
2478
2479 )))
2480
2481 **Address List**
2482
2483 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2484 |Bit|CIO|CIO|CIO d|0~~99999|
2485 |Bit|W|W|W d|0~~99999|
2486 |Bit|D|D|D d|0~~99999|
2487 |Bit|H|H|H d|0~~99999|
2488 |Bit|A|A|A d|0~~99999|
2489 |Bit|T|T|T h|0~~99999|
2490 |Bit|CF|CF|CF d|0~~99999|
2491 |Bit|FF|FF|FF d|0~~99999|
2492 |Bit|C|C|C d|0~~99999|
2493 |Bit|EM0|EM0|EM0 d|0~~99999|
2494 |Bit|EM1|EM1|EM1 d|0~~99999|
2495 |Bit|EM2|EM2|EM2 d|0~~99999|
2496 |Bit|EM3|EM3|EM3 d|0~~99999|
2497 |Bit|EM4|EM4|EM4 d|0~~99999|
2498 |Bit|EM5|EM5|EM5 h|0~~99999|
2499 |Bit|EM6|EM6|EM6 d|0~~99999|
2500 |Bit|EM7|EM7|EM7 d|0~~99999|
2501 |Bit|EM8|EM8|EM8 d|0~~99999|
2502 |Bit|EM9|EM9|EM9 d|0~~99999|
2503 |Bit|EMA|EMA|EMA d|0~~99999|
2504 |Bit|EMB|EMB|EMB d|0~~99999|
2505 |Bit|EMC|EMC|EMC d|0~~99999|
2506 |Bit|Lamp|Lamp|Lamp d|0~~0|
2507 |Word|CIO|CIO|CIO d|0~~99999|
2508 |Word|W|W|W d|0~~99999|
2509 |Word|D|D|D d|0~~99999|
2510 |Word|H|H|H d|0~~99999|
2511 |Word|A|A|A d|0~~99999|
2512 |Word|T|T|T h|0~~99999|
2513 |Word|CF|CF|CF d|0~~99999|
2514 |Word|FF|FF|FF d|0~~99999|
2515 |Word|C|C|C d|0~~99999|
2516 |Word|EM0|EM0|EM0 d|0~~99999|
2517 |Word|EM1|EM1|EM1 d|0~~99999|
2518 |Word|EM2|EM2|EM2 d|0~~99999|
2519 |Word|EM3|EM3|EM3 d|0~~99999|
2520 |Word|EM4|EM4|EM4 d|0~~99999|
2521 |Word|EM5|EM5|EM5 h|0~~99999|
2522 |Word|EM6|EM6|EM6 d|0~~99999|
2523 |Word|EM7|EM7|EM7 d|0~~99999|
2524 |Word|EM8|EM8|EM8 d|0~~99999|
2525 |Word|EM9|EM9|EM9 d|0~~99999|
2526 |Word|EMA|EMA|EMA d|0~~99999|
2527 |Word|EMB|EMB|EMB d|0~~99999|
2528 |Word|EMC|EMC|EMC d|0~~99999|
2529 |Word|IR|IR|IR d|0~~99999|
2530 |Word|DR|DR|DR d|0~~99999|
2531
2532 **Configure the communication protocol**
2533
2534 (% style="text-align:center" %)
2535 [[image:image-20220830143348-1.png]]
2536
2537 (% style="text-align:center" %)
2538 [[image:image-20220830143511-2.png]]
2539
2540 **Configure CJ1W-EIP21 connect with HMI**
2541
2542 (% style="text-align:center" %)
2543 [[image:ftEVGvAprh.png]]
2544
2545 Select TCP_Client_2N
2546
2547 (% style="text-align:center" %)
2548 [[image:RURXWcgyCd.png]]
2549
2550 **Cable Wiring**
2551
2552 Pin Definition Diagram
2553
2554 (% style="text-align:center" %)
2555 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2556
2557 == **CP1E/CP1H serial protocol** ==
2558
2559 Supported device: OMRON CS1(CP1E/CP1H)
2560
2561 **HMI Settings**
2562
2563 |=**Items**|=**Settings**|=**Note**
2564 |Protocol|OMRON CS1(CP1E/CP1H)|
2565 |Connection|RS232 (9600, 2, 7, EVEN)|
2566 |Port No.|None|
2567 |PLC station No.|0|
2568
2569 **Address List**
2570
2571 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2572 |Bit|CIO|CIO|CIO d|0~~99999|
2573 |Bit|W|W|W d|0~~99999|
2574 |Bit|D|D|D d|0~~99999|
2575 |Bit|H|H|H d|0~~99999|
2576 |Bit|A|A|A d|0~~99999|
2577 |Bit|TF|T|T h|0~~99999|
2578 |Bit|CF|CF|CF d|0~~99999|
2579 |Bit|T|FF|FF d|0~~99999|
2580 |Bit|C|C|C d|0~~99999|
2581 |Bit|EM0|EM0|EM0 d|0~~99999|
2582 |Bit|EM1|EM1|EM1 d|0~~99999|
2583 |Bit|EM2|EM2|EM2 d|0~~99999|
2584 |Bit|EM3|EM3|EM3 d|0~~99999|
2585 |Bit|EM4|EM4|EM4 d|0~~99999|
2586 |Bit|EM5|EM5|EM5 h|0~~99999|
2587 |Bit|EM6|EM6|EM6 d|0~~99999|
2588 |Bit|EM7|EM7|EM7 d|0~~99999|
2589 |Bit|EM8|EM8|EM8 d|0~~99999|
2590 |Bit|EM9|EM9|EM9 d|0~~99999|
2591 |Bit|EMA|EMA|EMA d|0~~99999|
2592 |Bit|EMB|EMB|EMB d|0~~99999|
2593 |Bit|EMC|EMC|EMC d|0~~99999|
2594 |Word|CIO|CIO|CIO d|0~~99999|
2595 |Word|W|W|W d|0~~99999|
2596 |Word|D|D|D d|0~~99999|
2597 |Word|H|H|H d|0~~99999|
2598 |Word|A|A|A d|0~~99999|
2599 |Word|T|T|T h|0~~99999|
2600 |Word|CIO|CF|CF d|0~~99999|
2601 |Word|C|C|C d|0~~99999|
2602 |Word|EM0|EM0|EM0 d|0~~99999|
2603 |Word|EM1|EM1|EM1 d|0~~99999|
2604 |Word|EM2|EM2|EM2 d|0~~99999|
2605 |Word|EM3|EM3|EM3 d|0~~99999|
2606 |Word|EM4|EM4|EM4 d|0~~99999|
2607 |Word|EM5|EM5|EM5 h|0~~99999|
2608 |Word|EM6|EM6|EM6 d|0~~99999|
2609 |Word|EM7|EM7|EM7 d|0~~99999|
2610 |Word|EM8|EM8|EM8 d|0~~99999|
2611 |Word|EM9|EM9|EM9 d|0~~99999|
2612 |Word|EMA|EMA|EMA d|0~~99999|
2613 |Word|EMB|EMB|EMB d|0~~99999|
2614 |Word|EMC|EMC|EMC d|0~~99999|
2615 |Word|IR|IR|IR d|0~~99999|
2616 |Word|DR|DR|DR d|0~~99999|
2617
2618 **Configure the communication protocol**
2619
2620 (% style="text-align:center" %)
2621 [[image:image-20220902153118-1.png]]
2622
2623 (% style="text-align:center" %)
2624 [[image:image-20220902151322-2.png]]
2625
2626 **Cable Wiring**
2627
2628 (% style="text-align:center" %)
2629 [[image:image-20220902153949-2.png]]
2630
2631 Pin Definition Diagram
2632
2633 (% style="text-align:center" %)
2634 [[image:image-20220902154056-3.png]]
2635
2636 == **EC55 Protocol** ==
2637
2638 Supported device: EC55 temperature instrument
2639
2640 **1)HMI Settings**
2641
2642 |**Items**|**Settings**|**Note**
2643 |Protocol|Omron EC55|
2644 |Connection|RS485 (9600, 2, 7, EVEN)|
2645 |Port No.|None|
2646 |PLC station No.|0|
2647
2648 **2)Address List**
2649
2650 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2651 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2652 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2653 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2654 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2655 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2656 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2657 |CP|-|0-6|Read controller intrinsic property
2658 |CS|-|0-2|Read controller states
2659 |CA|-|0-17|Action command
2660
2661 **3)Device Settings**
2662
2663 Omron E5CC PLC configuration
2664
2665 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2666
2667 (% style="text-align:center" %)
2668 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2669
2670 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2671
2672 (% style="text-align:center" %)
2673 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2674
2675 **✎Note:** The communication settings for HMI should be consistent with this setting.
2676
2677 **Cable Wiring**
2678
2679 (% style="text-align:center" %)
2680 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2681
2682 (% style="text-align:center" %)
2683 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2684
2685 **✎Note:**
2686
2687 * COM3 only available in PI8000/PI9000 series.
2688 * CA address could not support continuous writing function;
2689 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2690 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2691 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2692 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2693 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2694 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2695 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2696
2697 == **EtherNet/IP NX series Protocol** ==
2698
2699 Supported series: Omron NX/NJ series
2700
2701 **HMI Setting**
2702
2703 |**Items**|**Settings**|**Note**
2704 |Protocol|Omron NX Ethernet/IP|
2705 |Connection|Ethernet|
2706 |Port No.|44818|
2707 |PLC station No.|1|
2708
2709 **Instruction**
2710
2711 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2712
2713 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2714
2715 (% style="text-align:center" %)
2716 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2717
2718 **Export labels from Sysmac Studio**
2719
2720 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2721
2722 (% style="text-align:center" %)
2723 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2724
2725 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2726
2727 Click [Label manage];
2728
2729 (% style="text-align:center" %)
2730 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2731
2732 Click [Import labels] and then select the file exported in step 1;
2733
2734 (% style="text-align:center" %)
2735 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2736
2737 The Import Status field shows the result, click [OK] to finish importing address labels;
2738
2739 (% style="text-align:center" %)
2740 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2741
2742 **Communication Settings**
2743
2744 Enable HMI Ethernet in [Project Settings];
2745
2746 (% style="text-align:center" %)
2747 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2748
2749 Set PLC IP in [Device IP] settings;
2750
2751 (% style="text-align:center" %)
2752 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2753
2754 (% style="text-align:center" %)
2755 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2756
2757 **Cable Wiring**
2758
2759 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2760
2761 == CV/CJ1M/CS1H ==
2762
2763 **HMI Setting:**
2764
2765 |=(% scope="row" %)**Parameters**|=**Recommended**
2766 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2767 |=**PLC I/F**|RS232
2768 |=**Baud rate**|9600
2769 |=**Data bits**|7
2770 |=**Parity**|Even
2771 |=**Stop bits**|2
2772 |=**PLC sta. no.**|0
2773
2774 **PLC Setting:**
2775
2776 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2777
2778 **Device Address:**
2779
2780 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2781 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2782 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2783 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2784 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2785 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2786 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2787 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2788 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2789 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2790 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2791 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2792 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2793 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2794 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2795 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2796 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2797 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2798 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2799 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2800 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2801 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2802 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2803 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2804
2805 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2806 |=W|LR_W|DDDD|0 ~~ 4095|
2807 |=W|TC|DDD|0 ~~ 511|
2808 |=W|DM|DDDD|0 ~~ 9999|Data Register
2809
2810 **Wiring Diagram:**
2811
2812 **RS-232**
2813
2814 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2815
2816 Communication Module:
2817
2818 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2819
2820 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2821
2822 (% style="text-align:center" %)
2823 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2824
2825 = Create communication with Xinje** PLC** =
2826
2827 == XC serial protocol ==
2828
2829 **HMI Settings**
2830
2831 |**Item**|**Settings**|**Note**
2832 |Protocol|XINJE XC MODBUS|
2833 |Connection|RS232|
2834 |Baud rate|19200|
2835 |Data bit|8|
2836 |Parity|EVEN|
2837 |Stop bit|1|
2838 |PLC station No.|1|
2839
2840 **Address List**
2841
2842 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2843 |Bit|M|M|M d|0~~8511|
2844 |Bit|X|X|X o|0~~1747|
2845 |Bit|Y|Y|Y o|0~~1747|
2846 |Bit|S|S|S d|0~~1023|
2847 |Bit|T|T|T d|0~~4095|
2848 |Bit|C|C|C d|0~~634|
2849 |Word|D|D|D d|0~~8511|
2850 |Word|TD|TD|TD d|0~~618|
2851 |Word|CD|CD|CD d|0~~634|
2852 |Word|FD|FD|FD d|0~~8511|
2853
2854 **Configure the communication protocol**
2855
2856 (% style="text-align:center" %)
2857 [[image:image-20220830154105-1.png]]
2858
2859 (% style="text-align:center" %)
2860 [[image:image-20220830154159-3.png]]
2861
2862 **Cable Wiring**
2863
2864 Figure
2865
2866 [[image:image-20220830155728-4.png]]
2867
2868 Pin Definition Diagram
2869
2870 (% style="text-align:center" %)
2871 [[image:image-20220830154131-2.png]]
2872
2873 == XD serial protocol ==
2874
2875 **HMI Settings**
2876
2877 Supported Series: Xinjie XD/XE Series PLC
2878
2879 |=**Item**|=**Settings**|=**Note**
2880 |Protocol|XINJE XD/XC MODBUS|
2881 |Connection|RS232|
2882 |Baud rate|19200|
2883 |Data bit|8|
2884 |Parity|EVEN|
2885 |Stop bit|1|
2886 |PLC station No.|1|
2887
2888 **Address List**
2889
2890 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2891 |Bit|M|M|M d|0~~74999|
2892 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2893 |Bit|X2xx|X2xx|X2xx o|0~~277|
2894 |Bit|X|X|X o|0~~77|
2895 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2896 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2897 |Bit|Y|Y|Y o|0~~4095|
2898 |Bit|SM|SM|SM d|0~~4999|(((
2899
2900 )))
2901 |Bit|T|T|T d|0~~4999|
2902 |Bit|C|C|C d|0~~4999|
2903 |Bit|ET|ET|ET d|0~~31|
2904 |Bit|SE|SE|SE d|0~~31|
2905 |Bit|HM|HM|HM d|0~~11999|
2906 |Bit|HSC|HSC|HSC d|0~~39|
2907 |Bit|HS|HS|HS d|0~~999|
2908 |Bit|HT|HT|HT d|0~~1999|
2909 |Bit|HC|HC|HC d|0~~1999|
2910 |Bit|S|S|S d|0~~7999|
2911 |Word|D|D|D d|0~~69999|
2912 |Word|ID|ID|ID d|0~~99|
2913 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2914 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2915 |Word|QD|QD|QD d|0~~99|
2916 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2917 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2918 |Word|SD|SD|SD d|0~~4999|
2919 |Word|TD|TD|TD d|0~~575|
2920 |Word|CD|CD|CD d|0~~575|
2921 |Word|ETD|ETD|ETD d|0~~31|
2922 |Word|HD|HD|HD d|0~~24999|
2923 |Word|HSD|HSD|HSD d|0~~1023|
2924 |Word|HTD|HTD|HTD d|0~~95|
2925 |Word|HCD|HCD|HCD d|0~~95|
2926 |Word|HSCD|HSCD|HSCD d|0~~31|
2927 |Word|FD|FD|FD d|0~~8191|
2928 |Word|SFD|SFD|SFD d|0~~5999|
2929 |Word|FS|FS|FS d|0~~47|
2930
2931 **Configure the communication protocol**
2932
2933 (% style="text-align:center" %)
2934 [[image:image-20220830160042-1.png]]
2935
2936 (% style="text-align:center" %)
2937 [[image:image-20220830160129-2.png]]
2938
2939 **Cable Wiring**
2940
2941 (% style="text-align:center" %)
2942 [[image:image-20220905093902-1.png]]
2943
2944 Pin Definition Diagram
2945
2946 (% style="text-align:center" %)
2947 [[image:image-20220830160232-3.png]]
2948
2949 = Create communication with Panasonic** PLC** =
2950
2951 == **FP serial protocol** ==
2952
2953 **1)HMI Settings**
2954
2955 |**Item**|**Settings**|**Note**
2956 |Protocol|Panasonic FP MFWTOCOL|
2957 |Connection|RS232|
2958 |Baud rate|9600|
2959 |Data bit|8|
2960 |Parity|ODD|
2961 |Stop bit|1|
2962 |PLC station No.|1|
2963
2964 **2)Address List**
2965
2966 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2967 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2968 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2969 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2970 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2971 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2972 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2973 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2974 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2975 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2976 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2977 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2978 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2979 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2980 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2981 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2982
2983 **3)Configure the communication protocol**
2984
2985 [[image:image-20220830171050-1.png]]
2986
2987 [[image:image-20220830171126-2.png]]
2988
2989 **4)Cable Wiring**
2990
2991 Figure
2992
2993 [[image:image-20220830171328-4.png]]
2994
2995 Pin Definition Diagram
2996
2997 [[image:image-20220830171146-3.png]]
2998
2999 = Create communication with LS** PLC** =
3000
3001 == **XGB serial protocol ** ==
3002
3003 **HMI Settings**
3004
3005
3006 |=**Item**|=**Settings**|=**Note**
3007 |Protocol|LS XGB CPU DRIECT|
3008 |Connection|RS232|
3009 |Baud rate|115200|
3010 |Data bit|8|
3011 |Parity|NONE|
3012 |Stop bit|1|
3013 |PLC station No.|1|
3014
3015 **Address List**
3016
3017
3018 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3019 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
3020 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
3021 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
3022 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
3023 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
3024 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
3025 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
3026 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
3027 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
3028 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
3029 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
3030 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
3031 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
3032 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
3033 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
3034 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
3035 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
3036 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
3037 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
3038 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
3039 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
3040 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
3041 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
3042 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
3043 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
3044 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
3045
3046 **Configure the communication protocol**
3047
3048 (% style="text-align:center" %)
3049 [[image:image-20221028174410-1.png]]
3050
3051 (% style="text-align:center" %)
3052 [[image:image-20221028174753-2.png]]
3053
3054
3055 (% style="text-align:center" %)
3056 [[image:image-20221028181125-4.png]]
3057
3058 **Pin Definition Diagram**
3059
3060 (% style="text-align:center" %)
3061 [[image:image-20221028180930-3.png]]
3062
3063 = Create communication with LS** PLC** =
3064
3065 == **XBC serial protocol** ==
3066
3067 **HMI Settings**
3068
3069 |=**Item**|=**Settings**|=**Note**
3070 |Protocol|LS XBC CNet|
3071 |Connection|RS232|
3072 |Baud rate|115200|
3073 |Data bit|8|
3074 |Parity|NONE|
3075 |Stop bit|1|
3076 |PLC station No.|1|
3077
3078 **Address List**
3079
3080 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3081 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3082 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3083 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3084 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3085 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3086 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3087 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3088 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3089 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3090 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3091 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3092 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3093 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3094 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3095 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3096 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3097 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3098 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3099 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3100 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3101 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3102
3103 **Configure the communication protocol**
3104
3105 (% style="text-align:center" %)
3106 [[image:image-20220831170807-1.png]]
3107
3108 (% style="text-align:center" %)
3109 [[image:image-20220830174733-2.png]]
3110
3111 **Cable Wiring**
3112
3113 (% style="text-align:center" %)
3114 [[image:image-20220830174659-1.png]]
3115
3116 Pin Definition Diagram
3117
3118 (% style="text-align:center" %)
3119 [[image:image-20220830173402-8.png]]
3120
3121 == **XGK FEnet Ethernet protocol** ==
3122
3123 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3124
3125 **HMI Settings**
3126
3127 |**Items**|**Settings**|**Note**
3128 |Protocol|LG XGK FEnet(Ethernet)|
3129 |Connection|Ethernet|
3130 |Port No.|2004|
3131
3132 **Address List**
3133
3134 |**Type**|**Register**|**Range**|**Format**|**Note**
3135 |(% rowspan="14" %)Word|P|0~~2047|P d|
3136 |M|0~~2047|M d|
3137 |K|0~~2047|K d|
3138 |F|0~~2047|F d|
3139 |T|0~~2047|T d|
3140 |C|0~~2047|C d|
3141 |Z|0~~127|Z d|
3142 |S|0~~127|S d|
3143 |L|0~~11263|L d|
3144 |N|0~~21503|N d|
3145 |D|0~~32767|D d|
3146 |R|0~~32767|R d|
3147 |ZR|0~~65535|ZR d|
3148 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3149
3150 **✎Note:**
3151
3152 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3153 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3154 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3155
3156 **Communication settings in HMI**
3157
3158 Enable HMI Ethernet in [Project Settings];
3159
3160 (% style="text-align:center" %)
3161 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3162
3163 Set PLC IP in [Device IP] settings;
3164
3165 (% style="text-align:center" %)
3166 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3167
3168 **Cable Wiring**
3169
3170 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3171
3172 = Create communication with LS** PLC** =
3173
3174 == **XBC serial protocol** ==
3175
3176 **HMI Settings**
3177
3178 |=**Item**|=**Settings**|=**Note**
3179 |Protocol|LS XBC CNet|
3180 |Connection|RS232|
3181 |Baud rate|115200|
3182 |Data bit|8|
3183 |Parity|NONE|
3184 |Stop bit|1|
3185 |PLC station No.|1|
3186
3187 **Address List**
3188
3189 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3190 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3191 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3192 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3193 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3194 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3195 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3196 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3197 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3198 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3199 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3200 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3201 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3202 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3203 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3204 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3205 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3206 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3207 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3208 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3209 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3210 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3211
3212 **Configure the communication protocol**
3213
3214 (% style="text-align:center" %)
3215 [[image:image-20220831170807-1.png]]
3216
3217 (% style="text-align:center" %)
3218 [[image:image-20220830174733-2.png]]
3219
3220 **Cable Wiring**
3221
3222 (% style="text-align:center" %)
3223 [[image:image-20220830174659-1.png]]
3224
3225 Pin Definition Diagram
3226
3227 (% style="text-align:center" %)
3228 [[image:image-20220830173402-8.png]]
3229
3230 == **XGK FEnet Ethernet protocol** ==
3231
3232 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3233
3234 **HMI Settings**
3235
3236 |**Items**|**Settings**|**Note**
3237 |Protocol|LG XGK FEnet(Ethernet)|
3238 |Connection|Ethernet|
3239 |Port No.|2004|
3240
3241 **Address List**
3242
3243 |**Type**|**Register**|**Range**|**Format**|**Note**
3244 |(% rowspan="14" %)Word|P|0~~2047|P d|
3245 |M|0~~2047|M d|
3246 |K|0~~2047|K d|
3247 |F|0~~2047|F d|
3248 |T|0~~2047|T d|
3249 |C|0~~2047|C d|
3250 |Z|0~~127|Z d|
3251 |S|0~~127|S d|
3252 |L|0~~11263|L d|
3253 |N|0~~21503|N d|
3254 |D|0~~32767|D d|
3255 |R|0~~32767|R d|
3256 |ZR|0~~65535|ZR d|
3257 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3258
3259 **✎Note:**
3260
3261 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3262 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3263 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3264
3265 **Communication settings in HMI**
3266
3267 Enable HMI Ethernet in [Project Settings];
3268
3269 (% style="text-align:center" %)
3270 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3271
3272 Set PLC IP in [Device IP] settings;
3273
3274 (% style="text-align:center" %)
3275 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3276
3277 **Cable Wiring**
3278
3279 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3280
3281 = Create communication with **SHIMADEN PLC** =
3282
3283 == **FP23 series protocol** ==
3284
3285 Supported series: SHIMADEN FP23 series
3286
3287 **HMI Setting**
3288
3289 |**Items**|**Settings**|**Note**
3290 |Protocol|SHIMADEN FP23 series|
3291 |Connection|RS485 (9600, 1, 7, EVEN)|
3292 |Port No.|None|
3293 |PLC station No.|0|
3294
3295 **Address List**
3296
3297 |**Device address**|**HMI register**|**Address range**|**Type**
3298 |0040-0043(HEX)|FP040|100064-200067|Read only
3299 |0100-010B(HEX)|FP100|100256-200267|Read only
3300 |0110-0142(HEX)|FP110|100272-200322|Read only
3301 |0182-0252(HEX)|FP182|100386-200594|Write only
3302 |0280-0281(HEX)|FP280|100640-200641|Read only
3303 |0300-030B(HEX)|FP300|100768-200779|Read and write
3304 |0380-039F(HEX)|FP380|100896-200927|Read and write
3305 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3306 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3307 |0600-0670(HEX)|FP600|101536-201814|Read and write
3308 |0720-0738(HEX)|FP720|101824-201848|Read and write
3309 |0800-083F(HEX)|FP800|102048-202111|Read and write
3310 |0900-0952(HEX)|FP900|102304-202386|Read and write
3311 | |Ctrl|0-2|
3312
3313 **✎Note:**
3314
3315 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3316 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3317 * The Ctrl register is used to store the control group number and BCC check mode.
3318
3319 **Ctrl Register Description**
3320
3321 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3322 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3323 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3324 * Ctrl3 reserved
3325
3326 **✎Note:**
3327
3328 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3329
3330 **Cable Wiring**
3331
3332 (% style="text-align:center" %)
3333 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3334
3335 (% style="text-align:center" %)
3336 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3337
3338 **✎Note:** COM3 only available in PI8000/PI9000 series.
3339
3340 == **SR90 protocol** ==
3341
3342 Supported series: SHIMADEN SR90 series
3343
3344 **HMI Setting**
3345
3346 |**Items**|**Settings**|**Note**
3347 |Protocol|SHIMADEN SR90 protocol|
3348 |Connection|RS485 (1200, 1, 7, EVEN)|
3349 |Port No.|None|
3350 |PLC station No.|0|
3351
3352 **Address List**
3353
3354 |**Device address**|**HMI register**|**Address range**|**Type**
3355 |0040-0043 (HEX)|SR040|100064-100067|Read only
3356 |0100-010A(HEX)|SR0100|100256-100266|Read only
3357 |0182-018C(HEX)|SR0182|100386-100396|Write only
3358 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3359 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3360 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3361 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3362 | |Ctrl|0-2|~-~-
3363
3364 **✎Note:**
3365
3366 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3367 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3368 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3369
3370 **Ctrl Register Description**
3371
3372 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3373 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3374 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3375 * Ctrl3 reserved
3376
3377 **✎Note:**
3378
3379 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3380
3381 **Cable Wiring**
3382
3383 (% style="text-align:center" %)
3384 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3385
3386 (% style="text-align:center" %)
3387 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3388
3389 **✎Note:** COM3 only available in PI8000/PI9000 series.
3390
3391 == **MR13 series(standard protocol)** ==
3392
3393 Supported series: SHIMADEN MR13 series
3394
3395 **HMI Setting**
3396
3397 |**Items**|**Settings**|**Note**
3398 |Protocol|SHIMADEN standard protocol|
3399 |Connection|RS485 (1200, 1, 7, EVEN)|
3400 |Port No.|None|
3401 |PLC station No.|0|
3402
3403 **Address List**
3404
3405 |**Device address**|**HMI register**|**Address range**|**Type**
3406 |0100-010B(HEX)|MR100|100256-300267|Read only
3407 |0111-0126(HEX)|MR111|100273-300294|Read only
3408 |0184-0192(HEX)|MR184|100388-300402|Write only
3409 |0280-0282(HEX)|MR280|100640-300642|Read only
3410 |0300-030B(HEX)|MR300|100768-300779|Read/write
3411 |0314-0317(HEX)|MR314|100788-300791|Read/write
3412 |031A(HEX)|MR31A|100794-300794|Read/write
3413 |0320-0321(HEX)|MR320|100800-300801|Read/write
3414 |0400-0504(HEX)|MR400|101024-301284|Read/write
3415 |0506(HEX)|MR506|101286-301286|Read/write
3416 |0510-0514(HEX)|MR510|101296-301300|Read/write
3417 |0516-0524(HEX)|MR516|101302-301316|Read/write
3418 |0526(HEX)|MR526|101318-301318|Read/write
3419 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3420 |~-~-|Ctrl|0-2|~-~-
3421
3422 **✎Note:**
3423
3424 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3425 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3426 * The Ctrl register is used to store the control group number and BCC check mode.
3427
3428 **Ctrl Register Description**
3429
3430 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3431 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3432 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3433 * Ctrl3 reserved
3434
3435 **✎Note:**
3436
3437 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3438
3439 **Cable Wiring**
3440
3441 (% style="text-align:center" %)
3442 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3443
3444 (% style="text-align:center" %)
3445 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3446
3447 **✎Note:** COM3 only available in PI8000/PI9000 series.
3448
3449 = Create communication with **MODBUS** =
3450
3451 == **MODBUS RTU Master** ==
3452
3453 Supported Series: MODBUS RTU CONTROLLER
3454
3455 HMI works as MODBUS SLAVE connecting with MASTER
3456
3457 (% style="text-align:center" %)
3458 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3459
3460
3461 (% style="text-align:center" %)
3462 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3463
3464
3465 (% style="text-align:center" %)
3466 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3467
3468 **HMI Settings**
3469
3470 (% class="table-bordered" %)
3471 |**Items**|**Settings**|**Note**
3472 |Protocol|MODBUS RTU Master|
3473 |Connection|RS485/RS232|
3474 |Baud rate|2400~~187500|
3475 |Data bit|8|
3476 |Parity|Even/ Odd/ None|
3477 |Stop bit|1/2|
3478 |Station No.|0~~255|
3479
3480 **Address List**
3481
3482 (% class="table-bordered" %)
3483 |**Type**|**HMI address**|**MODBUS code**|**Range**
3484 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3485 |Word|HDW3500~~HDW7999|4|0~~4499
3486
3487 **Cable Wiring**
3488
3489 * **RS485**
3490
3491 (% style="text-align:center" %)
3492 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3493
3494 (% style="text-align:center" %)
3495 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3496
3497 * **RS232**
3498
3499 (% style="text-align:center" %)
3500 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3501
3502 **✎Note:** COM3 only available in PI8000/PI9000 series.
3503
3504 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3505
3506 Supported Series: MODBUS RTU CONTROLLER
3507
3508 HMI works as MODBUS MASTER connecting with SLAVE.
3509
3510 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3511
3512 (% style="text-align:center" %)
3513 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3514
3515
3516 (% style="text-align:center" %)
3517 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3518
3519
3520 (% style="text-align:center" %)
3521 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3522
3523 **HMI Settings**
3524
3525 (% class="table-bordered" %)
3526 |**Items**|**Settings**|**Note**
3527 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3528 |Connection|RS485/RS232|
3529 |Baud rate|2400~~187500|
3530 |Data bit|8|
3531 |Parity|Even/ Odd/ None|
3532 |Stop bit|1/2|
3533 |PLC station No.|0~~255|
3534
3535 **Address List**
3536
3537 (% class="table-bordered" %)
3538 |**Type**|**Address Type**|**Function code & Description**
3539 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3540 |06 (write single register: write a binary value to a holding register)
3541 |10 (write values to multiple addresses )
3542 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3543 |06 (write single register: write a binary value to a holding register)
3544 |10 (write values to multiple addresses )
3545 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3546 |06 (write single register: write a binary value to a holding register)
3547 |10 (write values to multiple addresses )
3548 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3549 |10 (write values to multiple addresses )
3550 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3551 |05 (Force a single coil to force the on/off state of a logic coil)
3552 |0F (Write multiple bits, ie write continuously)
3553 |(% rowspan="3" %)1|02 (Read the input state)
3554 |05 (Force a single coil to force the on/off state of a logic coil)
3555 |0F (Write multiple bits)
3556 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3557 |05 (Force a single coil to force the on/off state of a logic coil)
3558 |0F (Write multiple bits)
3559 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3560 |0F (Write multiple bits)
3561
3562 **✎Note:**
3563
3564 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3565 * The function codes sent out are the same as those that read and write words.
3566
3567 **Station number for more than one slaves**
3568
3569 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3570
3571 (% style="text-align:center" %)
3572 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3573
3574 **Cable Wiring**
3575
3576 * **RS485**
3577
3578 (% style="text-align:center" %)
3579 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3580
3581 (% style="text-align:center" %)
3582 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3583
3584 * **RS232**
3585
3586 (% style="text-align:center" %)
3587 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3588
3589 **✎Note:** COM3 only available in PI8000/PI9000 series.
3590
3591 == **Communicate with Modbus Meter** ==
3592
3593 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
3594
3595 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
3596
3597 (% style="text-align:center" %)
3598 [[image:LinfeeDiagram.png]]
3599
3600 (% class="wikigeneratedid" %)
3601 2. Check the specific Modbus parameter in the communication menu from LED display.
3602
3603 (% class="wikigeneratedid" %)
3604 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
3605
3606 {{info}}
3607 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
3608 {{/info}}
3609
3610 (% style="text-align:center" %)
3611 [[image:MeterModbusAllView.png]]
3612
3613 3. Create new project and change the Communication settings.
3614
3615 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
3616
3617 (% style="text-align:center" %)
3618 [[image:PIStudioSetupMeterModbusPara.png]]
3619
3620 (% class="wikigeneratedid" %)
3621 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
3622
3623 (% class="wikigeneratedid" %)
3624 The following table is intercept part of the manual for Linfee Modbus manual.
3625
3626 (% class="wikigeneratedid" %)
3627 **0x03/0x04 command data register address**:
3628
3629 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
3630 | HEX|DEC| | | |
3631 |0x00|0|Reserved| | |
3632 |0x02|2|Reserved| | |
3633 |0x04|4|Reserved| | |
3634 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
3635 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
3636 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
3637 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
3638 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
3639 |0x10|16|Uca|float|2|Line Voltage data, Unit V
3640 |0x12|18|Ia|float|2|Phase Current data, Unit A
3641 |0x14|20|Ib|float|2|Phase Current data, Unit A
3642 |0x16|22|Ic|float|2|Phase Current data, Unit A
3643
3644 {{info}}
3645 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
3646 {{/info}}
3647
3648 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
3649
3650 (% style="text-align:center" %)
3651 [[image:MeterModbusPInumericSet.png]]
3652
3653 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
3654
3655 (% style="text-align:center" %)
3656 [[image:MeterModbusNumericInputFormat.png]]
3657
3658 (% class="wikigeneratedid" %)
3659 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
3660
3661 (% style="text-align:center" %)
3662 [[image:ActualHMIModbusResult.jpg]]
3663
3664 == **MODBUS TCP Slave (All function)** ==
3665
3666 Supported series: MODBUS TCP controller
3667
3668 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3669
3670 (% style="text-align:center" %)
3671 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3672
3673 (% style="text-align:center" %)
3674 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3675
3676
3677 (% style="text-align:center" %)
3678 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3679
3680 **HMI Setting**
3681
3682 (% class="table-bordered" %)
3683 |**Items**|**Settings**|**Note**
3684 |Protocol|MODBUS TCP Slave (All function)|
3685 |Connection|Ethernet|
3686 |Port No.|502|
3687 |PLC station No.|1|
3688
3689 **Address List**
3690
3691 (% class="table-bordered" %)
3692 |**Type**|**Register**|**Function code & Description**
3693 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3694 |06 (write single register: write a binary value to a holding register)
3695 |10 (write values to multiple addresses )
3696 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3697 |06 (write single register: write a binary value to a holding register)
3698 |10 (write values to multiple addresses )
3699 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3700 |06 (write single register: write a binary value to a holding register)
3701 |10 (write values to multiple addresses )
3702 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3703 |10 (write values to multiple addresses )
3704 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3705 |05 (Force a single coil to force the on/off state of a logic coil)
3706 |0F (Write multiple bits, ie write continuously)
3707 |(% rowspan="3" %)1|02 (Read the input state)
3708 |05 (Force a single coil to force the on/off state of a logic coil)
3709 |0F (Write multiple bits)
3710 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3711 |05 (Force a single coil to force the on/off state of a logic coil)
3712 |0F (Write multiple bits)
3713 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3714 |0F (Write multiple bits)
3715
3716 **Communication Settings**
3717
3718 Enable HMI Ethernet in [Project Settings];
3719
3720 (% style="text-align:center" %)
3721 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3722
3723 Set PLC IP in [Device IP] settings;
3724
3725 (% style="text-align:center" %)
3726 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3727
3728 **Cable Wiring**
3729
3730 (% style="text-align:center" %)
3731 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3732
3733 = **Printer** =
3734
3735 == **TSPL label printer** ==
3736
3737 **Introduction**
3738
3739 TSPL label printer protocol supports following models.
3740
3741 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3742 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3743
3744 **Setting Step**
3745
3746 Select the protocol
3747
3748 * Create a new project, select the TSPL label printer protocol as shown below.
3749
3750 (% style="text-align:center" %)
3751 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3752
3753 Set parameters
3754
3755 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3756
3757 Printer register
3758
3759 (% class="table-bordered" %)
3760 |**Register**|**System**|**Range**|**Function**
3761 |TSPL_SP|decimal|0 - 1|Set the paper size
3762 |TSPL_PT|decimal|0 - 1999|Print text
3763 |TSPL_PQ|decimal|0 - 999|Print QR code
3764 |TSPL_PB|decimal|0 - 999|Print barcode
3765 |TSPL_PR|decimal|0 - 1|Print offset
3766 |TSPL_PN|decimal|0 - 0|Trigger printing
3767 |TSPL_PS|decimal|0 - 0|Print status
3768
3769 * Set paper size:
3770 ** TSPL_SP0: width of paper, unit: mm.
3771 ** TSPL_SP1: height of paper, unit: mm.
3772 * Print text:
3773 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3774 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3775
3776 (% class="table-bordered" %)
3777 |**Register**|**Function**|**Description**
3778 |TSPL_PT0|X coordinate|Unit: dot
3779 |TSPL_PT1|Ycoordinate|Unit: dot
3780 |TSPL_PT2|Rotation angle|(((
3781 0: 0 degrees
3782
3783 1: 90 degrees
3784
3785 2: 180 degrees
3786
3787 3: 270 degrees
3788 )))
3789 |TSPL_PT3|Size|Range: 0-3
3790 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3791
3792 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3793
3794 Print QR code:
3795
3796 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3797 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3798
3799 (% class="table-bordered" %)
3800 |**Register**|**Function**|**Description**
3801 |TSPL_PQ0|X coordinate|Unit: dot
3802 |TSPL_PQ1|Ycoordinate|Unit: dot
3803 |TSPL_PQ2|Rotation angle|(((
3804 0: 0 degrees
3805
3806 1: 90 degrees
3807
3808 2: 180 degrees
3809
3810 3: 270 degrees
3811 )))
3812 |TSPL_PQ3|Size|Range: 0-5
3813 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3814
3815 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3816
3817 Print bar code:
3818
3819 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3820 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3821
3822 (% class="table-bordered" %)
3823 |**Register**|**Function**|**Description**
3824 |TSPL_PB0|X coordinate|Unit: dot
3825 |TSPL_PB1|Ycoordinate|Unit: dot
3826 |TSPL_PB2|Rotation angle|(((
3827 0: 0 degrees
3828
3829 1: 90 degrees
3830
3831 2: 180 degrees
3832
3833 3: 270 degrees
3834 )))
3835 |TSPL_PB3|height|Unit: dot
3836 |TSPL_PB4|width|Range:0-2
3837 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3838
3839 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3840
3841 Print offset:
3842
3843 * TSPL_PR0: X coordinate offset, unit: mm;
3844 * TSPL_PR1: Y coordinate offset, unit: mm.
3845
3846 Trigger printing:
3847
3848 * TSPL_PN0 = 1: trigger the printer to start printing.
3849
3850 Printing status:
3851
3852 * TSPL_PS0 = 1: The printing is normal.
3853 * TSPL_PS0 = 1: The printing is abnormal.
3854
3855 Print picture
3856
3857 * For the function of printing pictures, please refer to the configuration of [Printer object].
3858
3859 Conversion between dot and mm
3860
3861 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3862
3863 == **EpsonTM series** ==
3864
3865 **HMI Settings**
3866
3867 (% class="table-bordered" %)
3868 |**Item**|**Settings**|**Note**
3869 |Protocol|EPSON-TM-T82II/TM-XXX|
3870 |Connection|RS232|
3871 |Baud rate|9600~~115200|
3872 |Data bit|8|
3873 |Parity|None|
3874 |Stop bit|1|
3875 |PLC station No.|1|
3876
3877 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3878
3879 **Printer Settings**
3880
3881 (% class="table-bordered" %)
3882 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3883 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3884 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3885 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3886 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3887 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3888 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3889
3890 **Cable Wiring**
3891
3892 (% style="text-align:center" %)
3893 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3894
3895 (% style="text-align:center" %)
3896 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3897
3898 **✎Note:** COM3 only available in PI8000/PI9000 series.
3899
3900
3901 = Create communication with **Schneider PLC** =
3902
3903 == **Schneider MODBUS RTU** ==
3904
3905 **HMI Setting**
3906
3907 |=**Parameters**|=**Recommended**|=**Notes**
3908 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3909 |Connection|RS485|
3910 |**Baud rate**|19200|
3911 |**Data bit**|8|
3912 |**Parity**|Even|
3913 |**Stop bit**|1|
3914 |**PLC station No.**|1|
3915
3916 **PLC Setting**
3917
3918 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3919
3920 **Device Address**
3921
3922 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3923 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3924 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3925 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3926 |W|MW|DDDDDD|0 ~~ 999999|Output register
3927 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3928
3929 **Wiring Diagram**
3930
3931 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3932
3933 (% style="text-align:center" %)
3934 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3935
3936 = **Barcode Scanner** =
3937
3938 Supported: DELI 14880 barcode scanner
3939
3940 **HMI Setting**
3941
3942 |**Items**|**Settings**|**Note**
3943 |Protocol|Barcode Scanner|
3944 |Connection|USB|
3945
3946 **Operating Procedures**
3947
3948 Select [Barcode Scanner];
3949
3950 (% style="text-align:center" %)
3951 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3952
3953 Set address for receiving;
3954
3955 Set correct length;
3956
3957 (% style="text-align:center" %)
3958 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3959
3960 **✎Note:**
3961
3962 * The protocol uploads the information acquired by the USB scanner to the HMI;
3963 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3964 * Recommended model: DELI 14880 barcode scanner;
3965
3966 = **Hitachi EHV Series (Ethernet)** =
3967
3968 Supported series: Hitachi EHV series
3969
3970 **HMI Settings**
3971
3972 (% class="table-bordered" %)
3973 |**Items**|**Settings**|**Note**
3974 |Protocol|Hitachi EHV series|
3975 |Connection|Ethernet|
3976 |Port No.|3004~~3007|
3977
3978 **Address List**
3979
3980 (% class="table-bordered" %)
3981 |**Type**|**Register**|**Range**|**Format**|**Note**
3982 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3983 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3984 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3985 H1H2H3H4 Module main number
3986
3987 H1: Remote number
3988
3989 H2: Unit number
3990
3991 H3: Slot number
3992
3993 H4: Word number of Module
3994
3995 H Sub number of Module
3996
3997 For example:X21.3
3998
3999 Slot number 2
4000
4001 Word number of module is 1
4002
4003 Bit number of module is 3
4004
4005 Remote number and unit number are 0
4006 )))
4007 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4008 |R|0 – FF.f (Hex)|R HH.h|
4009 |L|0 - 73FF.f (Hex)|L HHHH.h|
4010 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4011 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4012 H1H2H3H4 Module main number
4013
4014 H1: Remote number
4015
4016 H2: Unit number
4017
4018 H3: Slot number
4019
4020 H4: Word number of module
4021
4022 For example:WX21
4023
4024 Word number of module is 1
4025
4026 Slot number is 2
4027
4028 Remote number and unit number are 0
4029 )))
4030 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4031 |WR|0 – FFFF (Hex)|WR HHHH|
4032 |WL|0 - 73FF (Hex)|WL HHHH|
4033 |TC|0 - 2559|TC DDDD|
4034
4035 **Communication settings in HMI**
4036
4037 Enable HMI Ethernet in [Project Settings];
4038
4039 (% style="text-align:center" %)
4040 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4041
4042 Set PLC IP in [Device IP] settings;
4043
4044 (% style="text-align:center" %)
4045 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4046
4047 **PLC Configuration**
4048
4049 Connect with PLC, select[Online mode];
4050
4051 (% style="text-align:center" %)
4052 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4053
4054 Set IP address, it is the same LAN parameters with HMI;
4055
4056 (% style="text-align:center" %)
4057 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4058
4059 3) Save PLC communication parameter, and restart PLC
4060
4061 **PLC Monitor Mode**
4062
4063 Connect with PLC and choose to “online” mode
4064
4065 (% style="text-align:center" %)
4066 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4067
4068 Open I/O monitor sheet1
4069
4070 (% style="text-align:center" %)
4071 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4072
4073 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4074
4075 (% style="text-align:center" %)
4076 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4077
4078 Enter the register address, click OK to view the value of the register.
4079
4080 (% style="text-align:center" %)
4081 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4082
4083 (% style="text-align:center" %)
4084 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4085
4086 **✎Note:**
4087
4088 * Both word registers and bit registers support even continuous read/write functions;
4089 * The range of registers is based on the specific PLC type;
4090
4091 **Cable Wiring**
4092
4093 (% style="text-align:center" %)
4094 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4095
4096 = **IEC60870-5 104 Client** =
4097
4098 **HMI Setting**
4099
4100 (% class="table-bordered" %)
4101 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4102 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4103 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4104 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4105
4106 **Address List**
4107
4108 (% class="table-bordered" %)
4109 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4110 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4111 |(% style="width:461px" %)SCNA|0~~16777215.7
4112 |(% style="width:461px" %)DPTB|0~~16777215.7
4113 |(% style="width:461px" %)DCNA|0~~16777215.7
4114 |(% style="width:461px" %)METF|0~~16777215.7
4115 |(% style="width:461px" %)SENC|0~~16777215.7
4116 |(% style="width:461px" %)SENA|0~~16777215.7
4117 |(% style="width:461px" %)MENA|0~~16777215.7
4118 |(% style="width:461px" %)METD|0~~16777215.7
4119 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4120 |(% style="width:461px" %)SCNA|0~~16777215
4121 |(% style="width:461px" %)DPTB|0~~16777215
4122 |(% style="width:461px" %)DCNA|0~~16777215
4123 |(% style="width:461px" %)SENA|0~~16777215
4124 |(% style="width:461px" %)MENA|0~~16777215
4125 |(% style="width:461px" %)METD|0~~16777215
4126 |(% style="width:461px" %)INRO|0~~16777215
4127 |(% style="width:461px" %)TIMESYN|0~~16777215
4128 |(% style="width:461px" %)TIMEZ|0~~16777215
4129 |(% style="width:461px" %)NTP|0~~16777215
4130 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4131 |(% style="width:461px" %)SENC|0~~16777215
4132
4133 **Address Configuration**
4134
4135 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4136
4137 (% style="text-align:center" %)
4138 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4139
4140 (% style="text-align:center" %)
4141 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4142
4143 Extended tag name
4144
4145 Address range for the extended tag.
4146
4147 **Communication Settings**
4148
4149 Enable HMI Ethernet in [Project Settings];
4150
4151 (% style="text-align:center" %)
4152 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4153
4154 Set PLC IP in [Device IP] settings;
4155
4156 (% style="text-align:center" %)
4157 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4158
4159 **Cable Wiring**
4160
4161 (% style="text-align:center" %)
4162 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4163
4164 = **OpenCAN** =
4165
4166 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4167
4168 This protocol is only available in PI8000 series HMI.
4169
4170 **HMI Settings**
4171
4172 |**Items**|**Settings**|**Note**
4173 |Protocol|OPENCAN|
4174 |Connection|CAN port|
4175 |Baud rate|250000|
4176
4177 **CAN frame setting in HMI**
4178
4179 Click [OpenCAN setting] button in communication setting window;
4180
4181 (% style="text-align:center" %)
4182 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4183
4184 Click [Add] to create a new frame;
4185
4186 (% style="text-align:center" %)
4187 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4188
4189 |**No**|**Items**|**Description**
4190 |1|Add|add a frame related to register address
4191 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4192 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4193 |4|Modify|Modify the frames in frame management
4194 |5|Copy|Copy one frame to another
4195 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4196 |7|Empty|All frames in the list are cleared
4197 |8|Browse|Displays configuration files in XML format in IE
4198 |9|OK|Complete the configuration of the frame and exit
4199
4200 Set CANBUS frame in setting windows
4201
4202 (% style="text-align:center" %)
4203 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4204
4205 |**No**|**Items**|**Description**
4206 |1|ID|Set the ID of a can frame in hexadecimal format;
4207 |2|ID assign|split the ID by PF, PS, and SA;
4208 |3|Frame type|Select Standard frame or Extended Frame;
4209 |4|Frame format|Select between data frame and remote Frame;
4210 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4211 |6|Use address|(((
4212 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4213
4214 **Edit:** Set a bit or word address by its format;
4215
4216 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4217 )))
4218 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4219 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4220 |Feedback mode: feedback mode includes no response, confirm response and data response;
4221 |No response: the device or touch screen will not receive feedback;
4222 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4223 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4224 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4225 |Response timeout: sets whether the response frame timeout;
4226 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4227 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4228 |Manually send: a manually send tick indicates only one send;
4229 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4230 |10|Note|Fill the text to explain the meaning of the frame;
4231 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4232 |12|Current operation display|Display the description of current operation;
4233 |13|Add|Add a new frame;
4234 |14|Save frame|Save the configured frame format;
4235 |15|Cancel|Cancel the frame configuration;
4236
4237 Set CAN address (Read or write operation);
4238
4239 (% style="text-align:center" %)
4240 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4241
4242 |**No.**|**Item**|**Description**
4243 |1|Current address|Displays the register type and register address set by the user in the data access interface
4244 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4245 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4246 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4247 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4248 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4249 |If the trigger condition is a writing operation, there are two situations:(((
4250 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4251 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4252 )))
4253 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4254 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4255 |4|Add|Add current configuration
4256 |5|Close|Close the configuration window to exit
4257
4258 **Multiple Packages Settings**
4259
4260 (% style="text-align:center" %)
4261 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4262
4263 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4264
4265 Select Multiple package type
4266
4267 * Not Multiple packages
4268 * J1939 Multiple packages
4269 * Customized Multiple packages
4270
4271 Click [Edit Receive data] for [Receive] settings
4272
4273 * Start code+ Total length (J1939)
4274
4275 (% style="text-align:center" %)
4276 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4277
4278 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4279
4280 * Start code + Data max length (J1939)
4281
4282 (% style="text-align:center" %)
4283 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4284
4285 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4286
4287 * Data max length (J1939)
4288
4289 (% style="text-align:center" %)
4290 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4291
4292 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4293
4294 * Customized multiple package
4295
4296 (% style="text-align:center" %)
4297 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4298
4299 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4300
4301 Click [Edit Send data] for [Send] setting
4302
4303 * J1939
4304
4305 (% style="text-align:center" %)
4306 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4307
4308 [Data] is all data to be sent.
4309
4310 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4311
4312 * Customized multiple package
4313
4314 (% style="text-align:center" %)
4315 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4316
4317 [Data] is all data to be sent.
4318
4319 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4320
4321 **Cable Wiring**
4322
4323 (% style="text-align:center" %)
4324 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4325
4326 **✎Note:** The address interval between each frame need to be more than a word address;
4327
4328
4329 = **User Defined Protocol** =
4330
4331 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4332
4333 **HMI Settings**
4334
4335 |**Items**|**Settings**|**Note**
4336 |Protocol|User defined protocol|
4337 |Connection|RS485/RS232|
4338 |Baud rate|2400~~187500|
4339 |Stop bits|1/ 2|
4340 |Data bits|7/ 8|
4341 |Parity|None/ Even/ ODD|
4342
4343 **Operating Procedures**
4344
4345 Select [User defined protocol];
4346
4347 Click [User defined protocol] button to open setting window as below;
4348
4349 (% style="text-align:center" %)
4350 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4351
4352 Configure user defined command;
4353
4354 (% style="text-align:center" %)
4355 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4356
4357 |**No**|**Item**|**Description**
4358 |1|Instruction edit|The required command.
4359 |2|Mode|Write to address or read from the address.
4360 |3|Format|Encode format: HEX or ASCII.
4361 |4|Other|(((
4362 **No receiving: **HMI does not respond to the receiving command.
4363
4364 **Send after receiving:** HMI responds to the receiving command.
4365 )))
4366 |5|Manually send|(((
4367 Respond once after trigger the address.
4368
4369 Address: set the trigger address.
4370 )))
4371 |6|Add|Save this setting.
4372 |7|Cancel|Cancel current settings.
4373 |(% rowspan="4" %)8|Add|Add a new command.
4374 |Edit|Edit the selected command.
4375 |Delete|Delete the selected command.
4376 |Clear|Clear all the commands.
4377 |9|Instruction list|Display all current commands.
4378 |10|Address List|Display all the addresses added.
4379 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4380 |Export|Export current command settings to local storage.
4381 |Browse|Browse local command files.
4382 |Advanced|Combine two commands.
4383 |Exit|Complete editing and exit setting.
4384
4385 **Operating Procedures**
4386
4387 Click [Add] to create a new command, as below shows;
4388
4389 (% style="text-align:center" %)
4390 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4391
4392 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4393
4394 (% style="text-align:center" %)
4395 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4396
4397 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4398
4399 (% style="text-align:center" %)
4400 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4401
4402 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4403
4404 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4405
4406 Check settings;
4407
4408 (% style="text-align:center" %)
4409 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4410
4411 |**No**|**Items**|**Description**
4412 |1|Add checking|Add checking command when receiving the data.
4413 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4414 |Differ with send check|Set return checking.
4415 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4416 |Length: The data length need to be checked.
4417
4418 Object settings;
4419
4420 (% style="text-align:center" %)
4421 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4422
4423 |**No**|**Items**|**Description**
4424 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4425 |Address: the triggering address;
4426 |Note: description to object;
4427 |2|Byte order|The numerical display order;
4428
4429 Data length settings;
4430
4431 (% style="text-align:center" %)
4432 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4433
4434 |**No**|**Item**|**Description**
4435 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4436 |Length: the return data length.
4437 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4438 |Length: the write data length.
4439
4440 Instruction length settings
4441
4442 (% style="text-align:center" %)
4443 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4444
4445 |**No**|**Item**|**Description**
4446 |1|Send length|The instruction data will only send designated data length.
4447 |2|Return length|The responds data length.
4448 |3|End code|Instruction will not be terminated until receiving [End code];
4449
4450 **Cable Wiring**
4451
4452 * **RS485**
4453
4454 (% style="text-align:center" %)
4455 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4456
4457 (% style="text-align:center" %)
4458 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4459
4460 * **RS232**
4461
4462 (% style="text-align:center" %)
4463 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4464
4465 **✎Note:** COM3 only available in PI8000/PI9000 series.