Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 248.1 by Hunter on 2023/05/06 14:18

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with Inovance PLC** =
910
911 == **H1U/H2U serial protocol** ==
912
913 **HMI Settings**
914
915 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
916 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
917 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
918 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
919 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
920 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
921 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
922 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
923 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
924
925 (% class="wikigeneratedid" %)
926 **Address List**
927
928 (% style="width:1014px" %)
929 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
930 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
931 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
932 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
933 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
934 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
935 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
936 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
937 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
938 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
939 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
940 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
941 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
942 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
943 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
944 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
945 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
946 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
947
948 (% class="wikigeneratedid" %)
949 **Cable Wiring**
950
951 (% style="text-align:center" %)
952 [[image:Inovance.png]]
953
954 == **H3U serial protocol** ==
955
956 **HMI Settings**
957
958 |=**Item**|=**Settings**|=**Note**
959 |Protocol|INOVANCE H3U PLC|
960 |Connection|RS422|
961 |Baud rate|9600|
962 |Data bit|7|
963 |Parity|EVEN|
964 |Stop bit|1|
965 |PLC station No.|0|
966
967 **Address List**
968
969 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
970 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
971 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
972 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
973 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
974 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
975 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
976 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
977 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
978 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
979 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
980 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
981 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
982 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
983 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
984 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
985 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
986 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
987 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
988
989 **Configure the communication protocol**
990
991 (% style="text-align:center" %)
992 [[image:image-20220830170114-4.png]]
993
994 [[image:image-20220830170017-3.png]]
995
996 **Cable Wiring**
997
998 (% style="text-align:center" %)
999 [[image:Inovance.png]]
1000
1001 == **H3U Ethernet portocol** ==
1002
1003 **HMI Settings**
1004
1005 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1006 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1007 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1008 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1009 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1010 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1011
1012 **Address List**
1013
1014 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1015 |Bit|M|M DDDD|0~~8511|
1016 |Bit|SM|SM DDDD|0~~1023|
1017 |Bit|S|S DDDD|0~~4095|
1018 |Bit|T|T DDD|0~~511|
1019 |Bit|C|C DDD|0~~255|
1020 |Bit|X|X OOO|0~~571|
1021 |Bit|Y|Y OOO|0~~571|
1022 |Word|D|D DDDD|0~~8511|
1023 |Word|SD |SD DDDD|0~~1023|
1024 |Word|R|R DDDDD|0~~32767|
1025 |Word|T|T DDD|0~~255|
1026 |Word|C|C DDD|0~~199|
1027 |Double Word|C|C DDD|200~~255|
1028
1029 **Cable Wiring**
1030
1031 (% style="text-align:center" %)
1032 [[image:CommonEthernet.png]]
1033
1034 = Create communication with **Mitsubishi PLC** =
1035
1036 == **FX1S, 1N, 2N Series Protocol** ==
1037
1038 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1039
1040 **HMI Settings**
1041
1042 |**Item**|**Settings**|**Note**
1043 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1044 |Connection|RS422/RS485/RS232|
1045 |Baud rate|9600~~115200|
1046 |Data bit|7/8|
1047 |Parity|EVEN/Odd/None|
1048 |Stop bit|1/2|
1049 |PLC station No.|1~~255|
1050
1051 **Address List**
1052
1053 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1054 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1055 |Y|Y|Y o|0~~303237|
1056 |M|M|M d|0~~99999|
1057 |T|T|T d|0~~99999|
1058 |C|C|C d|0~~99999|
1059 |S|S|S d|0~~99999|
1060 |SM|SM|SM d|8000~~9999|
1061 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1062 |Y|Y|Y o|0~~303237|
1063 |M|M|M d|0~~99999|
1064 |T|T|T d|0~~99999|
1065 |C|C|C d|0~~199|
1066 |D|D|D d|0~~7999|
1067 |S|S|S d|0~~99999|
1068 |SD|SD|SD d|8000~~9999|
1069
1070 **Cable Wiring**
1071
1072 * **RS485**
1073
1074 (% style="text-align:center" %)
1075 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1076
1077 (% style="text-align:center" %)
1078 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1079
1080 * **RS422**
1081
1082 (% style="text-align:center" %)
1083 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1084
1085 **✎Note:** COM3 only available in PI8000/PI9000 series.
1086
1087 == **FX3U/3G/3GA serial protocol** ==
1088
1089 **HMI Settings**
1090
1091 |=**Item**|=**Settings**|=**Note**
1092 |Protocol|Mitsubishi FX3U/3G/3GA|
1093 |Connection|RS422|
1094 |Baud rate|9600~~115200|
1095 |Data bit|7/8|
1096 |Parity|EVEN/Odd/None|
1097 |Stop bit|1/2|
1098 |PLC station No.|1~~255|
1099
1100 **Address List**
1101
1102 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1103 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1104 |Y|Y|Y o|0~~303237|
1105 |M|M|M d|0~~99999|
1106 |T|T|T d|0~~99999|
1107 |C|C|C d|0~~99999|
1108 |S|S|S d|0~~99999|
1109 |SM|SM|SM d|8000~~9999|
1110 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1111 |Y|Y|Y o|0~~303237|
1112 |M|M|M d|0~~99999|
1113 |T|T|T d|0~~99999|
1114 |C|C|C d|0~~199|
1115 |D|D|D d|0~~7999|
1116 |S|S|S d|0~~99999|
1117 |SD|SD|SD d|8000~~9999|
1118
1119 **Configure the communication protocol**
1120
1121 (% style="text-align:center" %)
1122 [[image:image-20220831095222-1.png]]
1123
1124 (% style="text-align:center" %)
1125 [[image:image-20220831095743-2.png]]
1126
1127 **Wiring**
1128
1129 (% style="text-align:center" %)
1130 [[image:image-20220831100314-6.png]]
1131
1132 == **FX3U Ethernet Protocol** ==
1133
1134 Mitsubishi FX3U series PLC
1135
1136 **HMI Settings**
1137
1138 |Items|Settings|Note
1139 |Protocol|Mitsubishi FX3U|
1140 |Connection|Ethernet|
1141 |Port No.|5009|Must be the same as the PLC setting
1142 |PLC station No.|0|
1143
1144 **Address List**
1145
1146 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1147 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1148 |Y|Y|Y OOO|0~~377|
1149 |M|M|M DDDD|0~~7679|
1150 |SM|SM|SM DDDD|8000~~8511|
1151 |S|S|S DDDD|0~~4095|
1152 |TS|TS|TS DDD|0~~511|
1153 |CS|CS|CS DDD|0~~255|
1154 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1155 |TN|TN|TN DDD|0~~511|
1156 |D|D|D DDDD|0~~7999|
1157 |SD|SD|SD DDDD|8000~~8511|
1158 |R|R|R DDDDD|0~~32767|
1159
1160 **Ethernet Module Settings**
1161
1162 FX3U-ENET-L module configuration
1163 Set up the FX3U-ENET-L Ethernet module settings as follows.
1164 Select the module location, which in this document is Module 0.
1165
1166 [[image:image-20221115140802-1.png]]
1167
1168 Select "Operational setting" to enter the following screen.
1169
1170 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1171
1172 [[image:image-20221115142728-4.png]]
1173
1174 Select "Open setting" to enter the setting interface, the settings are as follows.
1175
1176 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1177
1178 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1179
1180 [[image:image-20221115142945-5.png]]
1181
1182 Click on "transter setup" - "PC side I/F setting", see the following figure.
1183
1184 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1185
1186 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1187
1188 [[image:image-20221115143341-6.png||height="426" width="712"]]
1189
1190 Read and write data from the Ethernet module
1191
1192 [[image:image-20221115143703-7.png]]
1193
1194 Set "Transter setup" to COM communication, and read or write operation as shown below
1195
1196 [[image:image-20221115143809-8.png]]
1197
1198 **PLC Settings (GX Works 2)**
1199
1200 Create a blank FX5U project
1201
1202 Find Current Connection in the navigation
1203
1204 [[image:image-20221115144335-9.png||height="422" width="706"]]
1205
1206 Select Connection Channel List
1207
1208 Select Ethernet board communication
1209
1210 [[image:image-20221115144824-10.png||height="421" width="705"]]
1211
1212 Select Ethernet Module
1213 Set the IP address of the PLC
1214
1215 [[image:image-20221115145228-11.png||height="674" width="708"]]
1216
1217 Read or write PLC data, in this document is read
1218
1219 [[image:image-20221115145553-12.png||height="424" width="711"]]
1220
1221 [[image:image-20221115145559-13.png||height="424" width="711"]]
1222
1223 **HMI Communication Setting**
1224
1225 [[image:image-20221115150003-14.png||height="425" width="712"]]
1226
1227 [[image:image-20221115150235-15.png||height="427" width="713"]]
1228
1229 [[image:image-20221115145559-13.png||height="424" width="711"]]
1230
1231 **HMI Communication Setting**
1232
1233 [[image:image-20221115150003-14.png||height="425" width="712"]]
1234
1235 [[image:image-20221115150235-15.png||height="427" width="713"]]
1236
1237 == **FX5U Serial Port Protocol** ==
1238
1239 Mitsubishi FX5U series PLC
1240
1241 **HMI Settings**
1242
1243 |**Item**|**Settings**|**Note**
1244 |Protocol|Mitsubishi FX5U|
1245 |Connection|RS422/RS485|
1246 |Baud rate|9600|
1247 |Data bit|7|
1248 |Parity|Odd|
1249 |Stop bit|1|
1250 |PLC station No.|1~~255|Need to be the same as PLC settings
1251
1252 **Address List**
1253
1254 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1255 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1256 |Y|Y|Y o|0~~303237|
1257 |M|M|M d|0~~99999|
1258 |B|B|B h|0~~7FFF|
1259 |F|F|F d|0~~32767|
1260 |SB|SB|SB h|0~~7FFF|
1261 |TS|TS|TS d|0~~1023|
1262 |TC|TC|TC d|0~~1023|
1263 |STS|STS|STS d|0~~1023|
1264 |STC|STC|STS d|0~~1023|
1265 |CS|CS|CS d|0~~1023|
1266 |CC|CC|CC d|0~~1023|
1267 |SM|SM|SM d|0~~9999|
1268 |L|L|L d|0~~32767|
1269 |S|S|S d|0~~4095|
1270 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1271 |TN|TN|TN d|0~~1023|
1272 |STN|STN|STN d|0~~1023|
1273 |CN|CN|CN d|0~~1023|
1274 |R|R|R d|0~~32767|
1275 |SW|SW|SW h|0~~7FFF|
1276 |Z|Z|Z d|0~~23|
1277 |D|D|D d|0~~7999|
1278 |SD|SD|SD d|0~~11999|
1279
1280 **PLC Settings (GX Works 3)**
1281
1282 Create a blank FX5U project
1283
1284 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1288
1289 Select protocol in the setting item, and set parameters.
1290
1291 (% style="text-align:center" %)
1292 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1293
1294 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1295
1296 (% style="text-align:center" %)
1297 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1298
1299 Click the [Apply] button to finish the setting.
1300
1301 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1302
1303 (% style="text-align:center" %)
1304 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1305
1306 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1307
1308 Done.
1309
1310 **Cable Wiring**
1311
1312 * **RS485**
1313
1314 (% style="text-align:center" %)
1315 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1316
1317 (% style="text-align:center" %)
1318 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1319
1320 * **RS422**
1321
1322 (% style="text-align:center" %)
1323 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1324
1325 **✎Note:** COM3 only available in PI8000/PI9000 series.
1326
1327 == **L02 Serial Protocol** ==
1328
1329 Mitsubishi L02 series CPU built-in serial port.
1330
1331 **HMI Settings**
1332
1333 |=**Item**|=**Settings**|=**Note**
1334 |Protocol|Mitsubishi L02|
1335 |Connection|RS422|
1336 |Baud rate|115200|
1337 |Data bit|8|
1338 |Parity|Odd|
1339 |Stop bit|1|
1340 |PLC station No.|1~~255|Need to be the same as PLC settings
1341
1342 **Address List**
1343
1344 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1345 |Bit|X|X|X h|0~~FFFF|
1346 |Bit|Y|Y|Y h|0~~FFFF|
1347 |Bit|M|M|M d|0~~9999|
1348 |Bit|L|L|L d|0~~9999|
1349 |Bit|F|F|F d|0~~9999|
1350 |Bit|B|B|B h|0~~FFFF|
1351 |Bit|V|V|V d|0~~2047|
1352 |Bit|TC|TC|TC d|0~~9999|
1353 |Bit|SS|SS|SS d|0~~9999|
1354 |Bit|SC|SC|SC d|0~~9999|
1355 |Bit|CS|CS|CS d|0~~9999|
1356 |Bit|CC|CC|CC d|0~~9999|
1357 |Bit|SB|SB|SB h|0~~FFFF|
1358 |Bit|SM|SM|SM d|0~~2047|
1359 |Bit|STS|STS|STS d|0~~1023|
1360 |Bit|S|S|S d|0~~9999|
1361 |Bit|DX|DX|DX h|0~~FFFF|
1362 |Bit|DY|DY|DY h|0~~FFFF|
1363 |Bit|TS|TS|TS d|0~~9999|
1364 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1365 |Word|W|W|W h|0~~FFFF|
1366 |Word|TN|TN|TN d|0~~99999|
1367 |Word|SN|SN|SN d|0~~99999|
1368 |Word|CN|CN|CN d|0~~99999|
1369 |Word|R|R|R d|0~~99999|
1370 |Word|SW|SW|SW h|0~~FFFF|
1371 |Word|Z|Z|Z d|0~~99999|
1372 |Word|ZR|ZR|ZR h|0~~FFFF|
1373 |Word|D|D|D d|0~~99999|
1374
1375 **Communication Settings**
1376
1377 (% style="text-align:center" %)
1378 [[image:image-20220831105732-3.png]]
1379
1380 (% style="text-align:center" %)
1381 [[image:image-20220831110004-5.png]]
1382
1383 **Cable Wiring**
1384
1385 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1386
1387 Pin Definition Diagram
1388
1389 (% style="text-align:center" %)
1390 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1391
1392 == **L02 MELSEC (Ethernet) Protocol** ==
1393
1394 Mitsubishi Q series CPU built-in Ethernet port.
1395
1396 **HMI Settings**
1397
1398 |**Items**|**Settings**|**Note**
1399 |Protocol|MIT L02 CPU MELSEC|
1400 |Connection|Ethernet|
1401 |Port No.|1025|Must be the same as the PLC setting
1402 |PLC station No.|0|Must be the same as the PLC setting
1403
1404 **Address List**
1405
1406 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1407 |Bit|X|X|X h|0~~FFFF|
1408 |Bit|Y|Y|Y h|0~~FFFF|
1409 |Bit|M|M|M d|0~~9999|
1410 |Bit|L|L|L d|0~~9999|
1411 |Bit|F|F|F d|0~~9999|
1412 |Bit|B|B|B h|0~~FFFF|
1413 |Bit|V|V|V d|0~~2047|
1414 |Bit|TC|TC|TC d|0~~9999|
1415 |Bit|SS|SS|SS d|0~~9999|
1416 |Bit|SC|SC|SC d|0~~9999|
1417 |Bit|CS|CS|CS d|0~~9999|
1418 |Bit|CC|CC|CC d|0~~9999|
1419 |Bit|SB|SB|SB h|0~~FFFF|
1420 |Bit|SM|SM|SM d|0~~2047|
1421 |Bit|STS|STS|STS d|0~~1023|
1422 |Bit|S|S|S d|0~~9999|
1423 |Bit|DX|DX|DX h|0~~FFFF|
1424 |Bit|DY|DY|DY h|0~~FFFF|
1425 |Bit|TS|TS|TS d|0~~9999|
1426 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1427 |Word|W|W|W h|0~~FFFF|
1428 |Word|TN|TN|TN d|0~~99999|
1429 |Word|SN|SN|SN d|0~~99999|
1430 |Word|CN|CN|CN d|0~~99999|
1431 |Word|R|R|R d|0~~99999|
1432 |Word|SW|SW|SW h|0~~FFFF|
1433 |Word|Z|Z|Z d|0~~99999|
1434 |Word|ZR|ZR|ZR h|0~~FFFF|
1435 |Word|D|D|D d|0~~99999|
1436
1437 **Communication Settings**
1438
1439 Enable HMI Ethernet in [Project Settings];
1440
1441 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1442
1443 Set PLC IP in [Device IP] settings;
1444
1445 (% style="text-align:center" %)
1446 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1447
1448 **PLC Settings (GX Works2 )**
1449
1450 Create a project
1451
1452 Set PLC IP, subnet mask and gateway;
1453
1454 Select [Binary Code] as communication data code;
1455
1456 (% style="text-align:center" %)
1457 [[image:image-20221108202109-2.png||height="636" width="732"]]
1458
1459 Set PLC port number, for example 1025
1460
1461 (% style="text-align:center" %)
1462 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1463
1464 Save settings;
1465
1466 Download project into PLC device;
1467
1468 Restart PLC device;
1469
1470 **Cable Wiring**
1471
1472 (% style="text-align:center" %)
1473 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1474
1475 == **QJ71C24N MELSEC Protocol** ==
1476
1477 Mitsubishi QJ71C24N communication module built-in serial port;
1478
1479 **HMI Settings**
1480
1481 |**Items**|**Settings**|**Note**
1482 |Protocol|MIT QJ71 MELSEC|
1483 |Connection|422|
1484 |Baud rate|9600|
1485 |Data bit|8|
1486 |Parity|ODD|
1487 |Stop bit|1|
1488 |PLC station No.|1~~255|Need to be the same as PLC settings
1489
1490 **Address List**
1491
1492 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1493 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1494 |Y|Y|Y FFFF|0~~1FFF|
1495 |M|M|M DDDDD|0~~99999|
1496 |L|L|L DDDD|0~~8191|
1497 |F|F|F DDDD|0~~2047|
1498 |V|V|V DDDD|0~~2047|
1499 |B|B|B FFFF|0~~1FFF|
1500 |TS|TS|TS DDDD|0~~2047|
1501 |TC|TC|TC DDDD|0~~2047|
1502 |SS|SS|SS DDDD|0~~2047|
1503 |SC|SC|SC DDDD|0~~2047|
1504 |CS|CS|CS DDDD|0~~1023|
1505 |CC|CC|CC DDDD|0~~1023|
1506 |SB|SB|SB FFF|0~~7FF|
1507 |S|S|S D|0~~8191|
1508 |DX|DX|DX FFFF|0~~1FFF|
1509 |DY|DY|DY FFFF|0~~1FFF|
1510 |SM_|SM_|SM_ DDDD|8000~~9999|
1511 |SM|SM|SM DDDD|0~~2047|
1512 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1513 |D|D|D DDDDD|0~~12287|
1514 |W|W|W FFFF|0~~1FFF|
1515 |TN|TN|TN DDDD|0~~2047|
1516 |SN|SN|SN DDDD|0~~2047|
1517 |CN|CN|CN DDDD|0~~1023|
1518 |R|R|R DDDDD|0~~32767|
1519 |SW|SW|SW FFF|0~~7FF|
1520 |Z|Z|Z D|0~~15|
1521 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1522
1523 **Communication Settings**
1524
1525 (% style="text-align:center" %)
1526 [[image:image-20221109135738-1.png]]
1527
1528 (% style="text-align:center" %)
1529 [[image:image-20221109140016-3.png]]
1530
1531 Pin Definition Diagram
1532
1533 (% style="text-align:center" %)
1534 [[image:image-20221109140406-4.png]]
1535
1536 == **QJ71E71 MELSEC Protocol** ==
1537
1538 Mitsubishi QJ71E71 Ethernet communication module;
1539
1540 **HMI Settings**
1541
1542 |**Items**|**Settings**|**Note**
1543 |Protocol|MIT QJ71E71 MELSEC|
1544 |Connection|Ethernet|
1545 |Port No.|1025|Must be the same as the PLC setting
1546 |PLC station No.|0|Must be the same as the PLC setting
1547
1548 **Address List**
1549
1550 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1551 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1552 |Y|Y|Y h|0~~1FFF|
1553 |M|M|M d|0~~99999|
1554 |L|L|L d|0~~8191|
1555 |F|F|F d|0~~2047|
1556 |B|B|B h|0~~1FFF|
1557 |V|V|V d|0~~2047|
1558 |TS|TS|TS d|0~~2047|
1559 |TC|TC|TC d|0~~2047|
1560 |SS|SS|SS d|0~~2047|
1561 |SC|SC|SC d|0~~2047|
1562 |CS|CS|CS d|0~~1023|
1563 |CC|CC|CC d|0~~1023|
1564 |SB|SB|SB h|0~~7FF|
1565 |S|S|S d|0~~8191|
1566 |DX|DX|DX h|0~~1FFF|
1567 |DY|DY|DY h|0~~1FFF|
1568 |SM|SM|SM d|8000~~9999|
1569 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1570 |D|D|D d|0~~12287|
1571 |W|W|W h|0~~1FFF|
1572 |TN|TN|TN d|0~~2047|
1573 |SN|SN|SN d|0~~2047|
1574 |CN|CN|CN d|0~~1023|
1575 |R|R|R d|0~~32767|
1576 |SW|SW|SW h|0~~7FF|
1577 |Z|Z|Z d|0~~15|
1578 |ZR|ZR|ZR h|0~~FE7FF|
1579
1580 **HMI Communication Settings**
1581
1582 1) Enable HMI Ethernet in [Project Settings];
1583
1584 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1585
1586 2) Set PLC IP in [Device IP] settings
1587
1588 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1589
1590 **PLC Settings(GX Works2)**
1591
1592 * Click [Ethernet/CC IE/MELSECNET];
1593 * Please select [Ethernet] as network type;
1594 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1595 * Select [Online] as Mode;
1596 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1597 * Click [Operation setting] to set IP;
1598 * Select [Binary Code] as [Communication Data Code];
1599 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1600 * Click [Open setting]
1601 * Set protocol: TCP;
1602 * Set [unpassive] in [Open system];
1603 * Set [receive] in [Fixed buffer];
1604 * Set [procedure Exist] in [Fixed buffer communication];
1605 * Disable [Pairing open];
1606 * Set [No confirm] in [Existence confirmation];
1607 * Host station port number: 5009;
1608 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1609 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1610 * Download project into PLC and restart it
1611
1612 **Cable Wiring**
1613
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1617
1618 = Create communication with **Rockwell PLC** =
1619
1620 == **DF1 Protocol** ==
1621
1622 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1623
1624 **HMI Settings**
1625
1626 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1627 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
1628 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1629 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1630 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1631 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1632 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1633 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1634 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1635
1636 **Address List**
1637
1638 (% class="table-bordered" %)
1639 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1640 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1641 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1642 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
1643 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1644 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
1645 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1646 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1647 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1648 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1649 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1650 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
1651
1652 **Cable Wiring**
1653
1654 (% style="text-align:center" %)
1655 [[image:AB.gif]]
1656
1657 == **DF1 Advanced Protocol** ==
1658
1659 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
1660
1661 **HMI Settings**
1662
1663 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
1664 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
1665 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
1666 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
1667 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
1668 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
1669 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
1670 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
1671 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
1672
1673 **Address List**
1674
1675 (% class="table-bordered" %)
1676 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
1677 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
1678 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
1679 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
1680 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
1681 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1682 Bit data file B0~~B99
1683
1684 First two digits is for file number
1685
1686 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
1687 )))
1688 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
1689 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
1690 Integer data file bit format N0~~N99
1691
1692 First two digits is for file number
1693
1694 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
1695 )))
1696 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
1697 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
1698 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
1699 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1700 Timer Preset Value
1701
1702 First two digits is for file number
1703
1704 For example, TNS99255 represents file number T99, address 255.
1705 )))
1706 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1707 Timer Accumulator Value
1708
1709 First two digits is for file number
1710
1711 For example, TNP99255 represents file number T99, address 255.
1712 )))
1713 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
1714 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
1715 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1716 Counter Preset Value
1717
1718 First two digits is for file number
1719
1720 For example, CNS99255 represents file number C99, address 255.
1721 )))
1722 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1723 Counter Accumulator Value
1724
1725 First two digits is for file number
1726
1727 For example, CNP99255 represents file number C99, address 255.
1728 )))
1729 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
1730 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1731 Integer data file
1732
1733 First two digits is for file number
1734
1735 For example, NN99255 represents file number N99, address 255.
1736 )))
1737 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
1738 Only able to communicate with file number F8
1739 )))
1740 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
1741 Floating point data file
1742
1743 First two digits is for file number
1744
1745 For example, FN99255 represents file number F99, address 255.
1746 )))
1747 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
1748
1749 **Cable Wiring**
1750
1751 (% style="text-align:center" %)
1752 [[image:AB.gif]]
1753
1754 == **MicroLogix Protocol** ==
1755
1756 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
1757
1758 **HMI Settings**
1759
1760 (% class="table-bordered" %)
1761 |**Item**|**Settings**|**Note**
1762 |Protocol|Allen-Bradlley MicroLogix|
1763 |Connection|RS232|
1764 |Baud rate|19200|
1765 |Data bit|8|
1766 |Parity|None|
1767 |Stop bit|1|
1768 |PLC station No.|1|
1769
1770 **Address List**
1771
1772 (% class="table-bordered" %)
1773 |**Type**|**Device registers**|**Format**|**Range**|**Note**
1774 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
1775 |O|O d.d|0.0~~255.15|
1776 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1777 |S|S d.d|0.0~~255.15|
1778 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
1779 |(% rowspan="9" %)Word|S|S d|0~~255|
1780 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
1781 |TP|TP nnhh|0~~ffff
1782 |CS|CS nnhh|0~~ffff
1783 |CP|CP nnhh|0~~ffff
1784 |N|N nnhh|0~~ffff
1785 |C|C nnhh|0~~ffff
1786 |T|T nnhh|0~~ffff
1787 |R|R nnhh|0~~ffff
1788
1789 **Cable Wiring**
1790
1791
1792 (% style="text-align:center" %)
1793 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
1794
1795 == **CompactLogix FreeTag Ethernet protocol** ==
1796
1797 Allen-Brandly CompactLogix
1798
1799 **HMI Settings**
1800
1801 (% class="table-bordered" %)
1802 |**Items**|**Settings**|**Note**
1803 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
1804 |Connection|Ethernet|
1805 |Port No.|44818|
1806
1807 **PLC Setting**
1808
1809 Create new tags
1810
1811 (% style="text-align:center" %)
1812 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
1813
1814 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
1815
1816 (% style="text-align:center" %)
1817 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
1818
1819 Import labels, please open [Communication] window and click [Import label];
1820
1821 Select csv file, all tags will be displayed as belows;
1822
1823 (% style="text-align:center" %)
1824 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
1825
1826 **✎Note:**
1827
1828 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
1829
1830 (% style="text-align:center" %)
1831 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
1832
1833 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
1834
1835 **Communication settings in HMI**
1836
1837 Enable HMI Ethernet in [Project Settings];
1838
1839 (% style="text-align:center" %)
1840 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
1841
1842 Set PLC IP in [Device IP] settings;
1843
1844 (% style="text-align:center" %)
1845 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1846
1847 **Cable Wiring**
1848
1849 (% style="text-align:center" %)
1850 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
1851
1852 == **MicroLogix 1200** **protocol** ==
1853
1854 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
1855
1856 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
1857 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
1858 * **Word address S:** The word address ranges from 0 to 255 (decimal).
1859 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
1860
1861 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
1862
1863 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
1864 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
1865 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
1866 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
1867 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
1868 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
1869 |**PLC word address type**|**Address format**|**Address range**
1870 |S|ddd|S0 ~~ 255
1871 |TS|ffff|TS0 ~~ FFFF
1872 |TP|ffff|TP0 ~~ FFFF
1873 |CS|ffff|CS0 ~~ FFFF
1874 |CP|ffff|CP0 ~~ FFFF
1875 |N|ffff|N0 ~~ FFFF
1876 |F|ffff|F0 ~~ FFFF
1877
1878 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
1879
1880 == **S7-200 Smart Ethernet Protocol** ==
1881
1882 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1883
1884 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1885
1886 **HMI Setting**
1887
1888 (% class="table-bordered" %)
1889 |**Items**|**Settings**|**Note**
1890 |Protocol|Simens S7-200 Smart Ethernet|
1891 |Connection|Ethernet|
1892 |Port No.|102|
1893 |PLC station No.|2|
1894
1895 **Address List**
1896
1897 (% class="table-bordered" %)
1898 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1899 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1900 |Q|Q|Q ddddd.o|0.0~~99999.7|
1901 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1902 |V|V|V ddddd.o|0.0~~99999.7|
1903 |M|M|M ddddd.o|0.0~~99999.7|
1904 |SM|SM|ddddd.o|0.0~~99999.7|
1905 |S|S|ddddd.o|0.0~~99999.7|Read only
1906 |T|T|ddddd|0~~99999|Timer state, read only
1907 |C|C|ddddd|0~~99999|Counter state, read only
1908 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1909 |Q|QW|QW ddddd|0~~99999|
1910 |AI|AIW|AIW ddddd|0~~99999|
1911 |AQ|VB|VB ddddd|0~~99999|
1912 |V|VW|VW ddddd|0~~99998|(((
1913 VW0=VB (0~~1)
1914
1915 VW2=VB (2~~3)
1916
1917 Address value is a multiple of 2
1918 )))
1919 |V|VD|VD ddddd|0~~99998|(((
1920 VD0=VB (0~~3)
1921
1922 VD2=VB (4~~7)
1923
1924 Address value is a multiple of 4
1925 )))
1926 |M|MB|MB ddddd|0~~99999|
1927 |M|MW|MW ddddd|0~~99999|(((
1928 MW0=MB(0~~1)
1929
1930 MW2=MB(2~~3)
1931
1932 Address value is a multiple of 2
1933 )))
1934 |M|MD|MD ddddd|0~~99999|(((
1935 MD0=MB(0~~3)
1936
1937 MD4=MB(4~~7)
1938
1939 Address value is a multiple of 4
1940 )))
1941 |T|TW|TW ddddd|0~~99999|Value of timer
1942 |C|CW|CW ddddd|0~~99999|Value of counter
1943 |W|SW|SW ddddd|0~~99999|
1944
1945 **Communication Settings**
1946
1947 Enable HMI Ethernet in [Project Settings];
1948
1949 (% style="text-align:center" %)
1950 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1951
1952 Set PLC IP in [Device IP] settings;
1953
1954 (% style="text-align:center" %)
1955 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1956
1957 * PLC IP Address: PLC IP
1958 * PLC pot No.: 102(fixed)
1959 * Network:TCP_Client_2N(fixed)
1960
1961 (% style="text-align:center" %)
1962 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1963
1964 * Wait timeout: depend on actual network situation (more than 1500 ms)
1965
1966 **Cable Wiring**
1967
1968 (% style="text-align:center" %)
1969 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1970
1971 == **S7-300 Ethernet Protocol** ==
1972
1973 Supported Series: Siemens S7-300 series PLC
1974
1975 **HMI Setting**
1976
1977 (% class="table-bordered" %)
1978 |**Items**|**Settings**|**Note**
1979 |Protocol|Simens S7-300 Ethernet|
1980 |Connection|Ethernet|
1981 |Port No.|102|
1982 |PLC station No.|2|Need to be same as the PLC setting
1983
1984 **Address List**
1985
1986 (% class="table-bordered" %)
1987 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1988 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1989 |Q|Q|Q ddddd.o|0.0~~99999.7|
1990 |M|M|M ddddd.o|0.0~~99999.7|
1991 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
1992 nnnn: block number;
1993
1994 dddd: address;
1995 )))
1996 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
1997 |Q|QW|QW ddddd|0~~99999|
1998 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
1999 |MW|MW ddddd|0~~99999|(((
2000 MW0=MB(0~~1)
2001
2002 MW2=MB(2~~3)
2003
2004 Address value is a multiple of 2
2005 )))
2006 |MD|MD ddddd|0~~99999|(((
2007 MD0=MB(0~~3)
2008
2009 MD4=MB(4~~7)
2010
2011 Address value is a multiple of 4
2012 )))
2013 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2014 nnnn: block number;
2015
2016 dddd: address
2017 )))
2018 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2019 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2020
2021 **Communication Settings**
2022
2023 Enable HMI Ethernet in [Project Settings];
2024
2025 (% style="text-align:center" %)
2026 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2027
2028 Set PLC IP in [Device IP] settings;
2029
2030 (% style="text-align:center" %)
2031 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2032
2033 * PLC IP Address: PLC IP
2034 * PLC pot No.: 102(fixed)
2035 * Network:TCP_Client_2N(fixed)
2036
2037 (% style="text-align:center" %)
2038 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2039
2040 * Wait timeout: depend on actual network situation (more than 1500 ms)
2041
2042 **Cable Wiring**
2043
2044 (% style="text-align:center" %)
2045 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2046
2047 == **S7-1200 Ethernet Protocol** ==
2048
2049 Supported Series: Siemens S7-1200
2050
2051 **HMI Setting**
2052
2053 (% class="table-bordered" %)
2054 |**Items**|**Settings**|**Note**
2055 |Protocol|Siemens S7-1200|
2056 |Connection|Ethernet|
2057 |Port No.|102|
2058 |PLC station No.|2|
2059
2060 **Address List**
2061
2062 (% class="table-bordered" %)
2063 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2064 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2065 d:0~-~-9999
2066
2067 o:0-7
2068 )))|
2069 |Q|Q|Q d.o|(((
2070 d:0~-~-9999
2071
2072 o:0-7
2073 )))|
2074 |M|M|M d.o|(((
2075 d:0~-~-9999
2076
2077 o:0-7
2078 )))|
2079 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2080 nn:0-9999,
2081
2082 dddd:0-9999,
2083
2084 o:0-7
2085 )))|(((
2086 nn:DB No.
2087
2088 dddd:address value
2089
2090 o: digit address
2091 )))
2092 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2093 |M|MW|MW d|d:0-99999|(((
2094 MW0=MB(0~~1)
2095
2096 MW2=MB(2~~3)
2097
2098 Address value is a multiple of 2
2099 )))
2100 |M|MD|MD d|d:0-99999|(((
2101 MD0=MB(0~~3)
2102
2103 MD4=MB(4~~7)
2104
2105 Address value is a multiple of 4
2106 )))
2107 |I|IW|IW d|d:0-99999|
2108 |Q|QW|QW d|d:0-99999|
2109 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2110 nn:0-9999
2111
2112 dddd:0-9999
2113 )))|(((
2114 nn:DB No.
2115
2116 dddd:address value
2117 )))
2118 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2119 nn:0-9999
2120
2121 dddd:0-9999
2122 )))|(((
2123 nn:DB No.
2124
2125 dddd:address value
2126
2127 Address value is a multiple of 2
2128 )))
2129 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2130 nn:0-9999
2131
2132 dddd:0-9999
2133 )))|(((
2134 nn:DB No.
2135
2136 dddd:address value
2137
2138 Address value is a multiple of 4
2139 )))
2140
2141 **Communication Settings**
2142
2143 Enable HMI Ethernet in [Project Settings];
2144
2145 (% style="text-align:center" %)
2146 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2147
2148 Set PLC IP in [Device IP] settings;
2149
2150 (% style="text-align:center" %)
2151 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2152
2153 **✎Note:**
2154
2155 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2156 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2157 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2158 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2159
2160 **PLC Settings**
2161
2162 Add BD
2163
2164 * Please uncheck [Symbolic access only] option;
2165
2166 (% style="text-align:center" %)
2167 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2168
2169 Address settings, using BD2 as example.
2170
2171 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2172 * 2 represent DB block number
2173 * xxxx represent address
2174
2175 **Such as:**
2176
2177 * DBxDBB20000 = DB2.DBB0
2178 * DBxDBW20004 = DB2.DBW4
2179
2180 (% style="text-align:center" %)
2181 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2182
2183 **How to connect with S7-1200 Firmware V4.0**
2184
2185 PLC configuration
2186
2187 * Double click [device configuration] in Siemens via software
2188 * Double click [protection] to enter protection configuration screen
2189
2190 (% style="text-align:center" %)
2191 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2192
2193 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2194
2195 (% style="text-align:center" %)
2196 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2197
2198 DB settings
2199
2200 * Right click [DB], select [properties]
2201 * Uncheck [optimized block access]
2202
2203 **Cable Wiring**
2204
2205 (% style="text-align:center" %)
2206 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2207
2208 == **S7-XXX Ethernet Protocol** ==
2209
2210 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2211
2212 **HMI Setting**
2213
2214 (% class="table-bordered" style="width:823px" %)
2215 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2216 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2217 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2218 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2219 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2220 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2221
2222 Slot from TIA Portal is equal to Device No. of PIStudio
2223
2224 Rack from TIA Portal is equal to HMI No. of PIStudio
2225
2226 (% style="text-align:center" %)
2227 [[image:S7-XXXCommunication Settings.png]]
2228
2229 (% style="text-align:center" %)
2230 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2231
2232 **Address List**
2233
2234 (% class="table-bordered" %)
2235 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2236 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2237 d:0~-~-9999
2238
2239 o:0-7
2240 )))|
2241 |Q|Q|Q d.o|(((
2242 d:0~-~-9999
2243
2244 o:0-7
2245 )))|
2246 |M|M|M d.o|(((
2247 d:0~-~-9999
2248
2249 o:0-7
2250 )))|
2251 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2252 nn:0-9999,
2253
2254 dddd:0-9999,
2255
2256 o:0-7
2257 )))|(((
2258 nn:DB No.
2259
2260 dddd:address value
2261
2262 o: digit address
2263 )))
2264 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2265 |M|MW|MW d|d:0-99999|(((
2266 MW0=MB(0~~1)
2267
2268 MW2=MB(2~~3)
2269
2270 Address value is a multiple of 2
2271 )))
2272 |M|MD|MD d|d:0-99999|(((
2273 MD0=MB(0~~3)
2274
2275 MD4=MB(4~~7)
2276
2277 Address value is a multiple of 4
2278 )))
2279 |I|IW|IW d|d:0-99999|
2280 |Q|QW|QW d|d:0-99999|
2281 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2282 nn:0-9999
2283
2284 dddd:0-9999
2285 )))|(((
2286 nn:DB No.
2287
2288 dddd:address value
2289 )))
2290 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2291 nn:0-9999
2292
2293 dddd:0-9999
2294 )))|(((
2295 nn:DB No.
2296
2297 dddd:address value
2298
2299 Address value is a multiple of 2
2300 )))
2301 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2302 nn:0-9999
2303
2304 dddd:0-9999
2305 )))|(((
2306 nn:DB No.
2307
2308 dddd:address value
2309
2310 Address value is a multiple of 4
2311 )))
2312
2313 **Communication Settings**
2314
2315 Enable HMI Ethernet in [Project Settings];
2316
2317 (% style="text-align:center" %)
2318 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2319
2320 Set PLC IP in [Device IP] settings;
2321
2322 (% style="text-align:center" %)
2323 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2324
2325 **✎Note:**
2326
2327 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2328 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2329
2330 **Cable Wiring**
2331
2332 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2333
2334 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
2335
2336 Supported Series: Siemens Logo 0BA0, 0BA1 series
2337
2338 **HMI Settings**
2339
2340 (% class="table-bordered" %)
2341 |**Items**|**Settings**|**Note**
2342 |Protocol|Siemens LOGO|
2343 |Connection|Ethernet|
2344 |Port No.|102|
2345 |PLC station No.|2|
2346
2347 **Address List**
2348
2349 (% class="table-bordered" %)
2350 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2351 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2352 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2353 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2354 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2355 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2356 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2357 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2358 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2359 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2360 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2361 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2362 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2363 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2364 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2365 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2366
2367 **PLC Settings in LOGO Software:**
2368
2369 Click [Tools]~-~-[Ethernet Connections],shown as below.
2370
2371 (% style="text-align:center" %)
2372 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2373
2374 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2375
2376 (% style="text-align:center" %)
2377 [[image:image-20221228142937-4.png]]
2378
2379 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2380
2381 (% style="text-align:center" %)
2382 [[image:image-20221228143047-5.png]]
2383
2384 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2385
2386 (% style="text-align:center" %)
2387 [[image:image-20221228143246-6.png]]
2388
2389
2390 **HMI Communication Settings**
2391
2392 Set PLC IP in [Device IP] settings;
2393
2394 (% style="text-align:center" %)
2395 [[image:image-20221228143614-7.png]]
2396
2397 Enable HMI Ethernet in [Project Settings];
2398
2399 (% style="text-align:center" %)
2400 [[image:image-20221228144229-9.png]]
2401
2402 TSAP setting
2403
2404 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2405 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
2406 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
2407 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
2408 ie, ig series: use HSW1200, HSW1201.
2409 HMI V2.0: use HSW1200, HSW1201.
2410
2411 **✎Note:**
2412
2413 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
2414 * HSW10119/HSW1201 is set up as shown.
2415 * (((
2416 (% style="text-align:center" %)
2417 [[image:image-20221228144800-11.png]]
2418 )))
2419 * (((
2420 (% style="text-align:center" %)
2421 [[image:image-20221228144708-10.png]]
2422 )))
2423
2424 * AI word address and Ibit address are read-only and cannot be written on HMI.
2425 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
2426 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
2427 * Written value of RTC cannot exceed 255.
2428
2429 **Cable Wiring**
2430
2431 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2432
2433 == S7-300 232 ==
2434
2435 **HMI Setting:**
2436
2437 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2438 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
2439 |=**PLC I/F**|RS232| |
2440 |=**Baud rate**|19200|9600,19200|
2441 |=**Data bits**|8| |
2442 |=**Parity**|Odd| |
2443 |=**Stop bits**|1| |
2444 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
2445
2446 **Device Address**
2447
2448 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2449 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
2450 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
2451 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
2452 |=Word|(((
2453 DB1 to DB99
2454 )))|DDDDDo|0 ~~ 655327|
2455 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
2456 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
2457 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
2458 |=Double word|MD|DDDD|0 ~~ 4094|
2459 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
2460 Data Register Double Word (must be even)
2461 )))
2462 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
2463
2464 **Cable Wiring**
2465
2466 (% style="text-align:center" %)
2467 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
2468
2469 = Create communication with **Omron** PLC =
2470
2471 == CJ TCP FINS Ethemet  Protocol ==
2472
2473 Supported device:CJ series、CJ1W-EIP21
2474
2475 **HMI Settings**
2476
2477 |=**Items**|=**Settings**|=**Note**
2478 |Protocol|OMRON CJ TCP FINS Ethemet|
2479 |Connection|Ethernet|
2480 |Port No.|9600|
2481 |Device No.|0|
2482 |HMI No.|0|(((
2483
2484 )))
2485
2486 **Address List**
2487
2488 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2489 |Bit|CIO|CIO|CIO d|0~~99999|
2490 |Bit|W|W|W d|0~~99999|
2491 |Bit|D|D|D d|0~~99999|
2492 |Bit|H|H|H d|0~~99999|
2493 |Bit|A|A|A d|0~~99999|
2494 |Bit|T|T|T h|0~~99999|
2495 |Bit|CF|CF|CF d|0~~99999|
2496 |Bit|FF|FF|FF d|0~~99999|
2497 |Bit|C|C|C d|0~~99999|
2498 |Bit|EM0|EM0|EM0 d|0~~99999|
2499 |Bit|EM1|EM1|EM1 d|0~~99999|
2500 |Bit|EM2|EM2|EM2 d|0~~99999|
2501 |Bit|EM3|EM3|EM3 d|0~~99999|
2502 |Bit|EM4|EM4|EM4 d|0~~99999|
2503 |Bit|EM5|EM5|EM5 h|0~~99999|
2504 |Bit|EM6|EM6|EM6 d|0~~99999|
2505 |Bit|EM7|EM7|EM7 d|0~~99999|
2506 |Bit|EM8|EM8|EM8 d|0~~99999|
2507 |Bit|EM9|EM9|EM9 d|0~~99999|
2508 |Bit|EMA|EMA|EMA d|0~~99999|
2509 |Bit|EMB|EMB|EMB d|0~~99999|
2510 |Bit|EMC|EMC|EMC d|0~~99999|
2511 |Bit|Lamp|Lamp|Lamp d|0~~0|
2512 |Word|CIO|CIO|CIO d|0~~99999|
2513 |Word|W|W|W d|0~~99999|
2514 |Word|D|D|D d|0~~99999|
2515 |Word|H|H|H d|0~~99999|
2516 |Word|A|A|A d|0~~99999|
2517 |Word|T|T|T h|0~~99999|
2518 |Word|CF|CF|CF d|0~~99999|
2519 |Word|FF|FF|FF d|0~~99999|
2520 |Word|C|C|C d|0~~99999|
2521 |Word|EM0|EM0|EM0 d|0~~99999|
2522 |Word|EM1|EM1|EM1 d|0~~99999|
2523 |Word|EM2|EM2|EM2 d|0~~99999|
2524 |Word|EM3|EM3|EM3 d|0~~99999|
2525 |Word|EM4|EM4|EM4 d|0~~99999|
2526 |Word|EM5|EM5|EM5 h|0~~99999|
2527 |Word|EM6|EM6|EM6 d|0~~99999|
2528 |Word|EM7|EM7|EM7 d|0~~99999|
2529 |Word|EM8|EM8|EM8 d|0~~99999|
2530 |Word|EM9|EM9|EM9 d|0~~99999|
2531 |Word|EMA|EMA|EMA d|0~~99999|
2532 |Word|EMB|EMB|EMB d|0~~99999|
2533 |Word|EMC|EMC|EMC d|0~~99999|
2534 |Word|IR|IR|IR d|0~~99999|
2535 |Word|DR|DR|DR d|0~~99999|
2536
2537 **Configure the communication protocol**
2538
2539 (% style="text-align:center" %)
2540 [[image:image-20220830143348-1.png]]
2541
2542 (% style="text-align:center" %)
2543 [[image:image-20220830143511-2.png]]
2544
2545 **Configure CJ1W-EIP21 connect with HMI**
2546
2547 (% style="text-align:center" %)
2548 [[image:ftEVGvAprh.png]]
2549
2550 Select TCP_Client_2N
2551
2552 (% style="text-align:center" %)
2553 [[image:RURXWcgyCd.png]]
2554
2555 **Cable Wiring**
2556
2557 Pin Definition Diagram
2558
2559 (% style="text-align:center" %)
2560 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2561
2562 == **CP1E/CP1H serial protocol** ==
2563
2564 Supported device: OMRON CS1(CP1E/CP1H)
2565
2566 **HMI Settings**
2567
2568 |=**Items**|=**Settings**|=**Note**
2569 |Protocol|OMRON CS1(CP1E/CP1H)|
2570 |Connection|RS232 (9600, 2, 7, EVEN)|
2571 |Port No.|None|
2572 |PLC station No.|0|
2573
2574 **Address List**
2575
2576 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2577 |Bit|CIO|CIO|CIO d|0~~99999|
2578 |Bit|W|W|W d|0~~99999|
2579 |Bit|D|D|D d|0~~99999|
2580 |Bit|H|H|H d|0~~99999|
2581 |Bit|A|A|A d|0~~99999|
2582 |Bit|TF|T|T h|0~~99999|
2583 |Bit|CF|CF|CF d|0~~99999|
2584 |Bit|T|FF|FF d|0~~99999|
2585 |Bit|C|C|C d|0~~99999|
2586 |Bit|EM0|EM0|EM0 d|0~~99999|
2587 |Bit|EM1|EM1|EM1 d|0~~99999|
2588 |Bit|EM2|EM2|EM2 d|0~~99999|
2589 |Bit|EM3|EM3|EM3 d|0~~99999|
2590 |Bit|EM4|EM4|EM4 d|0~~99999|
2591 |Bit|EM5|EM5|EM5 h|0~~99999|
2592 |Bit|EM6|EM6|EM6 d|0~~99999|
2593 |Bit|EM7|EM7|EM7 d|0~~99999|
2594 |Bit|EM8|EM8|EM8 d|0~~99999|
2595 |Bit|EM9|EM9|EM9 d|0~~99999|
2596 |Bit|EMA|EMA|EMA d|0~~99999|
2597 |Bit|EMB|EMB|EMB d|0~~99999|
2598 |Bit|EMC|EMC|EMC d|0~~99999|
2599 |Word|CIO|CIO|CIO d|0~~99999|
2600 |Word|W|W|W d|0~~99999|
2601 |Word|D|D|D d|0~~99999|
2602 |Word|H|H|H d|0~~99999|
2603 |Word|A|A|A d|0~~99999|
2604 |Word|T|T|T h|0~~99999|
2605 |Word|CIO|CF|CF d|0~~99999|
2606 |Word|C|C|C d|0~~99999|
2607 |Word|EM0|EM0|EM0 d|0~~99999|
2608 |Word|EM1|EM1|EM1 d|0~~99999|
2609 |Word|EM2|EM2|EM2 d|0~~99999|
2610 |Word|EM3|EM3|EM3 d|0~~99999|
2611 |Word|EM4|EM4|EM4 d|0~~99999|
2612 |Word|EM5|EM5|EM5 h|0~~99999|
2613 |Word|EM6|EM6|EM6 d|0~~99999|
2614 |Word|EM7|EM7|EM7 d|0~~99999|
2615 |Word|EM8|EM8|EM8 d|0~~99999|
2616 |Word|EM9|EM9|EM9 d|0~~99999|
2617 |Word|EMA|EMA|EMA d|0~~99999|
2618 |Word|EMB|EMB|EMB d|0~~99999|
2619 |Word|EMC|EMC|EMC d|0~~99999|
2620 |Word|IR|IR|IR d|0~~99999|
2621 |Word|DR|DR|DR d|0~~99999|
2622
2623 **Configure the communication protocol**
2624
2625 (% style="text-align:center" %)
2626 [[image:image-20220902153118-1.png]]
2627
2628 (% style="text-align:center" %)
2629 [[image:image-20220902151322-2.png]]
2630
2631 **Cable Wiring**
2632
2633 (% style="text-align:center" %)
2634 [[image:image-20220902153949-2.png]]
2635
2636 Pin Definition Diagram
2637
2638 (% style="text-align:center" %)
2639 [[image:image-20220902154056-3.png]]
2640
2641 == **EC55 Protocol** ==
2642
2643 Supported device: EC55 temperature instrument
2644
2645 **1)HMI Settings**
2646
2647 |**Items**|**Settings**|**Note**
2648 |Protocol|Omron EC55|
2649 |Connection|RS485 (9600, 2, 7, EVEN)|
2650 |Port No.|None|
2651 |PLC station No.|0|
2652
2653 **2)Address List**
2654
2655 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2656 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2657 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2658 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2659 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2660 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2661 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2662 |CP|-|0-6|Read controller intrinsic property
2663 |CS|-|0-2|Read controller states
2664 |CA|-|0-17|Action command
2665
2666 **3)Device Settings**
2667
2668 Omron E5CC PLC configuration
2669
2670 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2671
2672 (% style="text-align:center" %)
2673 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2674
2675 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2676
2677 (% style="text-align:center" %)
2678 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2679
2680 **✎Note:** The communication settings for HMI should be consistent with this setting.
2681
2682 **Cable Wiring**
2683
2684 (% style="text-align:center" %)
2685 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2686
2687 (% style="text-align:center" %)
2688 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2689
2690 **✎Note:**
2691
2692 * COM3 only available in PI8000/PI9000 series.
2693 * CA address could not support continuous writing function;
2694 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2695 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2696 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2697 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2698 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2699 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2700 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2701
2702 == **EtherNet/IP NX series Protocol** ==
2703
2704 Supported series: Omron NX/NJ series
2705
2706 **HMI Setting**
2707
2708 |**Items**|**Settings**|**Note**
2709 |Protocol|Omron NX Ethernet/IP|
2710 |Connection|Ethernet|
2711 |Port No.|44818|
2712 |PLC station No.|1|
2713
2714 **Instruction**
2715
2716 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2717
2718 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2719
2720 (% style="text-align:center" %)
2721 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2722
2723 **Export labels from Sysmac Studio**
2724
2725 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2726
2727 (% style="text-align:center" %)
2728 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2729
2730 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2731
2732 Click [Label manage];
2733
2734 (% style="text-align:center" %)
2735 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2736
2737 Click [Import labels] and then select the file exported in step 1;
2738
2739 (% style="text-align:center" %)
2740 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2741
2742 The Import Status field shows the result, click [OK] to finish importing address labels;
2743
2744 (% style="text-align:center" %)
2745 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2746
2747 **Communication Settings**
2748
2749 Enable HMI Ethernet in [Project Settings];
2750
2751 (% style="text-align:center" %)
2752 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2753
2754 Set PLC IP in [Device IP] settings;
2755
2756 (% style="text-align:center" %)
2757 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2758
2759 (% style="text-align:center" %)
2760 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2761
2762 **Cable Wiring**
2763
2764 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2765
2766 == CV/CJ1M/CS1H ==
2767
2768 **HMI Setting:**
2769
2770 |=(% scope="row" %)**Parameters**|=**Recommended**
2771 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2772 |=**PLC I/F**|RS232
2773 |=**Baud rate**|9600
2774 |=**Data bits**|7
2775 |=**Parity**|Even
2776 |=**Stop bits**|2
2777 |=**PLC sta. no.**|0
2778
2779 **PLC Setting:**
2780
2781 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2782
2783 **Device Address:**
2784
2785 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
2786 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2787 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
2788 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
2789 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
2790 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
2791 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
2792 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2793 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
2794 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
2795 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
2796 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
2797 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
2798 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
2799 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
2800 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
2801 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
2802 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
2803 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
2804 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
2805 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
2806 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
2807 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
2808 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
2809
2810 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2811 |=W|LR_W|DDDD|0 ~~ 4095|
2812 |=W|TC|DDD|0 ~~ 511|
2813 |=W|DM|DDDD|0 ~~ 9999|Data Register
2814
2815 **Wiring Diagram:**
2816
2817 **RS-232**
2818
2819 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2820
2821 Communication Module:
2822
2823 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2824
2825 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2826
2827 (% style="text-align:center" %)
2828 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2829
2830 = Create communication with Xinje** PLC** =
2831
2832 == XC serial protocol ==
2833
2834 **HMI Settings**
2835
2836 |**Item**|**Settings**|**Note**
2837 |Protocol|XINJE XC MODBUS|
2838 |Connection|RS232|
2839 |Baud rate|19200|
2840 |Data bit|8|
2841 |Parity|EVEN|
2842 |Stop bit|1|
2843 |PLC station No.|1|
2844
2845 **Address List**
2846
2847 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2848 |Bit|M|M|M d|0~~8511|
2849 |Bit|X|X|X o|0~~1747|
2850 |Bit|Y|Y|Y o|0~~1747|
2851 |Bit|S|S|S d|0~~1023|
2852 |Bit|T|T|T d|0~~4095|
2853 |Bit|C|C|C d|0~~634|
2854 |Word|D|D|D d|0~~8511|
2855 |Word|TD|TD|TD d|0~~618|
2856 |Word|CD|CD|CD d|0~~634|
2857 |Word|FD|FD|FD d|0~~8511|
2858
2859 **Configure the communication protocol**
2860
2861 (% style="text-align:center" %)
2862 [[image:image-20220830154105-1.png]]
2863
2864 (% style="text-align:center" %)
2865 [[image:image-20220830154159-3.png]]
2866
2867 **Cable Wiring**
2868
2869 Figure
2870
2871 [[image:image-20220830155728-4.png]]
2872
2873 Pin Definition Diagram
2874
2875 (% style="text-align:center" %)
2876 [[image:image-20220830154131-2.png]]
2877
2878 == XD serial protocol ==
2879
2880 **HMI Settings**
2881
2882 Supported Series: Xinjie XD/XE Series PLC
2883
2884 |=**Item**|=**Settings**|=**Note**
2885 |Protocol|XINJE XD/XC MODBUS|
2886 |Connection|RS232|
2887 |Baud rate|19200|
2888 |Data bit|8|
2889 |Parity|EVEN|
2890 |Stop bit|1|
2891 |PLC station No.|1|
2892
2893 **Address List**
2894
2895 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2896 |Bit|M|M|M d|0~~74999|
2897 |Bit|X1xx|X1xx|X1xx o|0~~1177|
2898 |Bit|X2xx|X2xx|X2xx o|0~~277|
2899 |Bit|X|X|X o|0~~77|
2900 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
2901 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
2902 |Bit|Y|Y|Y o|0~~4095|
2903 |Bit|SM|SM|SM d|0~~4999|(((
2904
2905 )))
2906 |Bit|T|T|T d|0~~4999|
2907 |Bit|C|C|C d|0~~4999|
2908 |Bit|ET|ET|ET d|0~~31|
2909 |Bit|SE|SE|SE d|0~~31|
2910 |Bit|HM|HM|HM d|0~~11999|
2911 |Bit|HSC|HSC|HSC d|0~~39|
2912 |Bit|HS|HS|HS d|0~~999|
2913 |Bit|HT|HT|HT d|0~~1999|
2914 |Bit|HC|HC|HC d|0~~1999|
2915 |Bit|S|S|S d|0~~7999|
2916 |Word|D|D|D d|0~~69999|
2917 |Word|ID|ID|ID d|0~~99|
2918 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
2919 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
2920 |Word|QD|QD|QD d|0~~99|
2921 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
2922 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
2923 |Word|SD|SD|SD d|0~~4999|
2924 |Word|TD|TD|TD d|0~~575|
2925 |Word|CD|CD|CD d|0~~575|
2926 |Word|ETD|ETD|ETD d|0~~31|
2927 |Word|HD|HD|HD d|0~~24999|
2928 |Word|HSD|HSD|HSD d|0~~1023|
2929 |Word|HTD|HTD|HTD d|0~~95|
2930 |Word|HCD|HCD|HCD d|0~~95|
2931 |Word|HSCD|HSCD|HSCD d|0~~31|
2932 |Word|FD|FD|FD d|0~~8191|
2933 |Word|SFD|SFD|SFD d|0~~5999|
2934 |Word|FS|FS|FS d|0~~47|
2935
2936 **Configure the communication protocol**
2937
2938 (% style="text-align:center" %)
2939 [[image:image-20220830160042-1.png]]
2940
2941 (% style="text-align:center" %)
2942 [[image:image-20220830160129-2.png]]
2943
2944 **Cable Wiring**
2945
2946 (% style="text-align:center" %)
2947 [[image:image-20220905093902-1.png]]
2948
2949 Pin Definition Diagram
2950
2951 (% style="text-align:center" %)
2952 [[image:image-20220830160232-3.png]]
2953
2954 = Create communication with Panasonic** PLC** =
2955
2956 == **FP serial protocol** ==
2957
2958 **1)HMI Settings**
2959
2960 |**Item**|**Settings**|**Note**
2961 |Protocol|Panasonic FP MFWTOCOL|
2962 |Connection|RS232|
2963 |Baud rate|9600|
2964 |Data bit|8|
2965 |Parity|ODD|
2966 |Stop bit|1|
2967 |PLC station No.|1|
2968
2969 **2)Address List**
2970
2971 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
2972 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
2973 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
2974 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
2975 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
2976 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
2977 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
2978 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
2979 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
2980 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
2981 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
2982 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
2983 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
2984 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
2985 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
2986 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
2987
2988 **3)Configure the communication protocol**
2989
2990 [[image:image-20220830171050-1.png]]
2991
2992 [[image:image-20220830171126-2.png]]
2993
2994 **4)Cable Wiring**
2995
2996 Figure
2997
2998 [[image:image-20220830171328-4.png]]
2999
3000 Pin Definition Diagram
3001
3002 [[image:image-20220830171146-3.png]]
3003
3004 = Create communication with LS** PLC** =
3005
3006 == **XGB serial protocol ** ==
3007
3008 **HMI Settings**
3009
3010
3011 |=**Item**|=**Settings**|=**Note**
3012 |Protocol|LS XGB CPU DRIECT|
3013 |Connection|RS232|
3014 |Baud rate|115200|
3015 |Data bit|8|
3016 |Parity|NONE|
3017 |Stop bit|1|
3018 |PLC station No.|1|
3019
3020 **Address List**
3021
3022
3023 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3024 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD.f|(% style="width:168px" %)0~~2047|
3025 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD.f|(% style="width:168px" %)0~~2047|
3026 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD.f|(% style="width:168px" %)0~~11263|
3027 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD.f|(% style="width:168px" %)0~~2559|
3028 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD.f|(% style="width:168px" %)0~~2047|
3029 |(% style="width:117px" %)Bit|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
3030 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD.f|(% style="width:168px" %)0~~32767|
3031 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF.f|(% style="width:168px" %)0~~7f31|
3032 |(% style="width:117px" %)Bit|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD.f|(% style="width:168px" %)0~~2047|
3033 |(% style="width:117px" %)Bit|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD.f|(% style="width:168px" %)0~~2047|
3034 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P DDDD|(% style="width:168px" %)0~~2047|
3035 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M DDDD|(% style="width:168px" %)0~~2047|
3036 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L DDDDD|(% style="width:168px" %)0~~11263|
3037 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K DDDD|(% style="width:168px" %)0~~2559|
3038 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F DDDD|(% style="width:168px" %)0~~2047|
3039 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C DDDD|(% style="width:168px" %)0~~2047|
3040 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T DDDD|(% style="width:168px" %)0~~2047|
3041 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D DDDDD|(% style="width:168px" %)0~~32767|
3042 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N DDDDD|(% style="width:168px" %)0~~21503|
3043 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U FFFF|(% style="width:168px" %)0~~7f31|
3044 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z DDD|(% style="width:168px" %)0~~127|
3045 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R DDDDD|(% style="width:168px" %)0~~32767|
3046 |(% style="width:117px" %)Word|(% style="width:271px" %)ZR|(% style="width:291px" %)ZR|(% style="width:171px" %)Z DDDDD|(% style="width:168px" %)0~~32767|
3047 |(% style="width:117px" %)Word|(% style="width:271px" %)TS|(% style="width:291px" %)TS|(% style="width:171px" %)TS DDDD|(% style="width:168px" %)0~~2047|
3048 |(% style="width:117px" %)Word|(% style="width:271px" %)CS|(% style="width:291px" %)CS|(% style="width:171px" %)CS DDDD|(% style="width:168px" %)0~~2047|
3049 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S DDDDD|(% style="width:168px" %)0~~12799|
3050
3051 **Configure the communication protocol**
3052
3053 (% style="text-align:center" %)
3054 [[image:image-20221028174410-1.png]]
3055
3056 (% style="text-align:center" %)
3057 [[image:image-20221028174753-2.png]]
3058
3059
3060 (% style="text-align:center" %)
3061 [[image:image-20221028181125-4.png]]
3062
3063 **Pin Definition Diagram**
3064
3065 (% style="text-align:center" %)
3066 [[image:image-20221028180930-3.png]]
3067
3068 = Create communication with LS** PLC** =
3069
3070 == **XBC serial protocol** ==
3071
3072 **HMI Settings**
3073
3074 |=**Item**|=**Settings**|=**Note**
3075 |Protocol|LS XBC CNet|
3076 |Connection|RS232|
3077 |Baud rate|115200|
3078 |Data bit|8|
3079 |Parity|NONE|
3080 |Stop bit|1|
3081 |PLC station No.|1|
3082
3083 **Address List**
3084
3085 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3086 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3087 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3088 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3089 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3090 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3091 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3092 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3093 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3094 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3095 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3096 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3097 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3098 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3099 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3100 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3101 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3102 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3103 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3104 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3105 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3106 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3107
3108 **Configure the communication protocol**
3109
3110 (% style="text-align:center" %)
3111 [[image:image-20220831170807-1.png]]
3112
3113 (% style="text-align:center" %)
3114 [[image:image-20220830174733-2.png]]
3115
3116 **Cable Wiring**
3117
3118 (% style="text-align:center" %)
3119 [[image:image-20220830174659-1.png]]
3120
3121 Pin Definition Diagram
3122
3123 (% style="text-align:center" %)
3124 [[image:image-20220830173402-8.png]]
3125
3126 == **XGK FEnet Ethernet protocol** ==
3127
3128 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3129
3130 **HMI Settings**
3131
3132 |**Items**|**Settings**|**Note**
3133 |Protocol|LG XGK FEnet(Ethernet)|
3134 |Connection|Ethernet|
3135 |Port No.|2004|
3136
3137 **Address List**
3138
3139 |**Type**|**Register**|**Range**|**Format**|**Note**
3140 |(% rowspan="14" %)Word|P|0~~2047|P d|
3141 |M|0~~2047|M d|
3142 |K|0~~2047|K d|
3143 |F|0~~2047|F d|
3144 |T|0~~2047|T d|
3145 |C|0~~2047|C d|
3146 |Z|0~~127|Z d|
3147 |S|0~~127|S d|
3148 |L|0~~11263|L d|
3149 |N|0~~21503|N d|
3150 |D|0~~32767|D d|
3151 |R|0~~32767|R d|
3152 |ZR|0~~65535|ZR d|
3153 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3154
3155 **✎Note:**
3156
3157 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3158 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3159 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3160
3161 **Communication settings in HMI**
3162
3163 Enable HMI Ethernet in [Project Settings];
3164
3165 (% style="text-align:center" %)
3166 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3167
3168 Set PLC IP in [Device IP] settings;
3169
3170 (% style="text-align:center" %)
3171 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3172
3173 **Cable Wiring**
3174
3175 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3176
3177 = Create communication with LS** PLC** =
3178
3179 == **XBC serial protocol** ==
3180
3181 **HMI Settings**
3182
3183 |=**Item**|=**Settings**|=**Note**
3184 |Protocol|LS XBC CNet|
3185 |Connection|RS232|
3186 |Baud rate|115200|
3187 |Data bit|8|
3188 |Parity|NONE|
3189 |Stop bit|1|
3190 |PLC station No.|1|
3191
3192 **Address List**
3193
3194 |=(% style="width: 117px;" %)**Type**|=(% style="width: 271px;" %)**Device registers**|=(% style="width: 291px;" %)**HMI registers**|=(% style="width: 171px;" %)**Format**|=(% style="width: 168px;" %)**Range**|=**Note**
3195 |(% style="width:117px" %)Bit|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3196 |(% style="width:117px" %)Bit|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3197 |(% style="width:117px" %)Bit|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3198 |(% style="width:117px" %)Bit|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3199 |(% style="width:117px" %)Bit|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3200 |(% style="width:117px" %)Bit|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3201 |(% style="width:117px" %)Bit|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3202 |(% style="width:117px" %)Bit|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3203 |(% style="width:117px" %)Word|(% style="width:271px" %)P|(% style="width:291px" %)P|(% style="width:171px" %)P d|(% style="width:168px" %)0~~2047|
3204 |(% style="width:117px" %)Word|(% style="width:271px" %)M|(% style="width:291px" %)M|(% style="width:171px" %)M d|(% style="width:168px" %)0~~2047|
3205 |(% style="width:117px" %)Word|(% style="width:271px" %)L|(% style="width:291px" %)L|(% style="width:171px" %)L d|(% style="width:168px" %)0~~11263|
3206 |(% style="width:117px" %)Word|(% style="width:271px" %)K|(% style="width:291px" %)K|(% style="width:171px" %)K d|(% style="width:168px" %)0~~16183|
3207 |(% style="width:117px" %)Word|(% style="width:271px" %)F|(% style="width:291px" %)F|(% style="width:171px" %)F d|(% style="width:168px" %)0~~2047|
3208 |(% style="width:117px" %)Word|(% style="width:271px" %)C|(% style="width:291px" %)C|(% style="width:171px" %)C d|(% style="width:168px" %)0~~2047|
3209 |(% style="width:117px" %)Word|(% style="width:271px" %)T|(% style="width:291px" %)T|(% style="width:171px" %)T d|(% style="width:168px" %)0~~2047|
3210 |(% style="width:117px" %)Word|(% style="width:271px" %)D|(% style="width:291px" %)D|(% style="width:171px" %)D d|(% style="width:168px" %)0~~32767|
3211 |(% style="width:117px" %)Word|(% style="width:271px" %)N|(% style="width:291px" %)N|(% style="width:171px" %)N d|(% style="width:168px" %)0~~21503|
3212 |(% style="width:117px" %)Word|(% style="width:271px" %)R|(% style="width:291px" %)R|(% style="width:171px" %)R d|(% style="width:168px" %)0~~32767|
3213 |(% style="width:117px" %)Word|(% style="width:271px" %)U|(% style="width:291px" %)U|(% style="width:171px" %)U d|(% style="width:168px" %)0~~4095|
3214 |(% style="width:117px" %)Word|(% style="width:271px" %)Z|(% style="width:291px" %)Z|(% style="width:171px" %)Z d|(% style="width:168px" %)0~~127|
3215 |(% style="width:117px" %)Word|(% style="width:271px" %)S|(% style="width:291px" %)S|(% style="width:171px" %)S d|(% style="width:168px" %)0~~127|
3216
3217 **Configure the communication protocol**
3218
3219 (% style="text-align:center" %)
3220 [[image:image-20220831170807-1.png]]
3221
3222 (% style="text-align:center" %)
3223 [[image:image-20220830174733-2.png]]
3224
3225 **Cable Wiring**
3226
3227 (% style="text-align:center" %)
3228 [[image:image-20220830174659-1.png]]
3229
3230 Pin Definition Diagram
3231
3232 (% style="text-align:center" %)
3233 [[image:image-20220830173402-8.png]]
3234
3235 == **XGK FEnet Ethernet protocol** ==
3236
3237 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3238
3239 **HMI Settings**
3240
3241 |**Items**|**Settings**|**Note**
3242 |Protocol|LG XGK FEnet(Ethernet)|
3243 |Connection|Ethernet|
3244 |Port No.|2004|
3245
3246 **Address List**
3247
3248 |**Type**|**Register**|**Range**|**Format**|**Note**
3249 |(% rowspan="14" %)Word|P|0~~2047|P d|
3250 |M|0~~2047|M d|
3251 |K|0~~2047|K d|
3252 |F|0~~2047|F d|
3253 |T|0~~2047|T d|
3254 |C|0~~2047|C d|
3255 |Z|0~~127|Z d|
3256 |S|0~~127|S d|
3257 |L|0~~11263|L d|
3258 |N|0~~21503|N d|
3259 |D|0~~32767|D d|
3260 |R|0~~32767|R d|
3261 |ZR|0~~65535|ZR d|
3262 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3263
3264 **✎Note:**
3265
3266 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3267 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3268 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3269
3270 **Communication settings in HMI**
3271
3272 Enable HMI Ethernet in [Project Settings];
3273
3274 (% style="text-align:center" %)
3275 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3276
3277 Set PLC IP in [Device IP] settings;
3278
3279 (% style="text-align:center" %)
3280 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3281
3282 **Cable Wiring**
3283
3284 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3285
3286 = Create communication with **SHIMADEN PLC** =
3287
3288 == **FP23 series protocol** ==
3289
3290 Supported series: SHIMADEN FP23 series
3291
3292 **HMI Setting**
3293
3294 |**Items**|**Settings**|**Note**
3295 |Protocol|SHIMADEN FP23 series|
3296 |Connection|RS485 (9600, 1, 7, EVEN)|
3297 |Port No.|None|
3298 |PLC station No.|0|
3299
3300 **Address List**
3301
3302 |**Device address**|**HMI register**|**Address range**|**Type**
3303 |0040-0043(HEX)|FP040|100064-200067|Read only
3304 |0100-010B(HEX)|FP100|100256-200267|Read only
3305 |0110-0142(HEX)|FP110|100272-200322|Read only
3306 |0182-0252(HEX)|FP182|100386-200594|Write only
3307 |0280-0281(HEX)|FP280|100640-200641|Read only
3308 |0300-030B(HEX)|FP300|100768-200779|Read and write
3309 |0380-039F(HEX)|FP380|100896-200927|Read and write
3310 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3311 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3312 |0600-0670(HEX)|FP600|101536-201814|Read and write
3313 |0720-0738(HEX)|FP720|101824-201848|Read and write
3314 |0800-083F(HEX)|FP800|102048-202111|Read and write
3315 |0900-0952(HEX)|FP900|102304-202386|Read and write
3316 | |Ctrl|0-2|
3317
3318 **✎Note:**
3319
3320 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3321 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3322 * The Ctrl register is used to store the control group number and BCC check mode.
3323
3324 **Ctrl Register Description**
3325
3326 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3327 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3328 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3329 * Ctrl3 reserved
3330
3331 **✎Note:**
3332
3333 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3334
3335 **Cable Wiring**
3336
3337 (% style="text-align:center" %)
3338 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3339
3340 (% style="text-align:center" %)
3341 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3342
3343 **✎Note:** COM3 only available in PI8000/PI9000 series.
3344
3345 == **SR90 protocol** ==
3346
3347 Supported series: SHIMADEN SR90 series
3348
3349 **HMI Setting**
3350
3351 |**Items**|**Settings**|**Note**
3352 |Protocol|SHIMADEN SR90 protocol|
3353 |Connection|RS485 (1200, 1, 7, EVEN)|
3354 |Port No.|None|
3355 |PLC station No.|0|
3356
3357 **Address List**
3358
3359 |**Device address**|**HMI register**|**Address range**|**Type**
3360 |0040-0043 (HEX)|SR040|100064-100067|Read only
3361 |0100-010A(HEX)|SR0100|100256-100266|Read only
3362 |0182-018C(HEX)|SR0182|100386-100396|Write only
3363 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3364 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3365 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3366 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3367 | |Ctrl|0-2|~-~-
3368
3369 **✎Note:**
3370
3371 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3372 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3373 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3374
3375 **Ctrl Register Description**
3376
3377 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3378 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3379 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3380 * Ctrl3 reserved
3381
3382 **✎Note:**
3383
3384 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3385
3386 **Cable Wiring**
3387
3388 (% style="text-align:center" %)
3389 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3390
3391 (% style="text-align:center" %)
3392 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3393
3394 **✎Note:** COM3 only available in PI8000/PI9000 series.
3395
3396 == **MR13 series(standard protocol)** ==
3397
3398 Supported series: SHIMADEN MR13 series
3399
3400 **HMI Setting**
3401
3402 |**Items**|**Settings**|**Note**
3403 |Protocol|SHIMADEN standard protocol|
3404 |Connection|RS485 (1200, 1, 7, EVEN)|
3405 |Port No.|None|
3406 |PLC station No.|0|
3407
3408 **Address List**
3409
3410 |**Device address**|**HMI register**|**Address range**|**Type**
3411 |0100-010B(HEX)|MR100|100256-300267|Read only
3412 |0111-0126(HEX)|MR111|100273-300294|Read only
3413 |0184-0192(HEX)|MR184|100388-300402|Write only
3414 |0280-0282(HEX)|MR280|100640-300642|Read only
3415 |0300-030B(HEX)|MR300|100768-300779|Read/write
3416 |0314-0317(HEX)|MR314|100788-300791|Read/write
3417 |031A(HEX)|MR31A|100794-300794|Read/write
3418 |0320-0321(HEX)|MR320|100800-300801|Read/write
3419 |0400-0504(HEX)|MR400|101024-301284|Read/write
3420 |0506(HEX)|MR506|101286-301286|Read/write
3421 |0510-0514(HEX)|MR510|101296-301300|Read/write
3422 |0516-0524(HEX)|MR516|101302-301316|Read/write
3423 |0526(HEX)|MR526|101318-301318|Read/write
3424 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3425 |~-~-|Ctrl|0-2|~-~-
3426
3427 **✎Note:**
3428
3429 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3430 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3431 * The Ctrl register is used to store the control group number and BCC check mode.
3432
3433 **Ctrl Register Description**
3434
3435 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3436 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3437 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3438 * Ctrl3 reserved
3439
3440 **✎Note:**
3441
3442 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3443
3444 **Cable Wiring**
3445
3446 (% style="text-align:center" %)
3447 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3448
3449 (% style="text-align:center" %)
3450 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3451
3452 **✎Note:** COM3 only available in PI8000/PI9000 series.
3453
3454 = Create communication with **MODBUS** =
3455
3456 == **MODBUS RTU Master** ==
3457
3458 Supported Series: MODBUS RTU CONTROLLER
3459
3460 HMI works as MODBUS SLAVE connecting with MASTER
3461
3462 (% style="text-align:center" %)
3463 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3464
3465
3466 (% style="text-align:center" %)
3467 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3468
3469
3470 (% style="text-align:center" %)
3471 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3472
3473 **HMI Settings**
3474
3475 (% class="table-bordered" %)
3476 |**Items**|**Settings**|**Note**
3477 |Protocol|MODBUS RTU Master|
3478 |Connection|RS485/RS232|
3479 |Baud rate|2400~~187500|
3480 |Data bit|8|
3481 |Parity|Even/ Odd/ None|
3482 |Stop bit|1/2|
3483 |Station No.|0~~255|
3484
3485 **Address List**
3486
3487 (% class="table-bordered" %)
3488 |**Type**|**HMI address**|**MODBUS code**|**Range**
3489 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3490 |Word|HDW3500~~HDW7999|4|0~~4499
3491
3492 **Cable Wiring**
3493
3494 * **RS485**
3495
3496 (% style="text-align:center" %)
3497 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3498
3499 (% style="text-align:center" %)
3500 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3501
3502 * **RS232**
3503
3504 (% style="text-align:center" %)
3505 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3506
3507 **✎Note:** COM3 only available in PI8000/PI9000 series.
3508
3509 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3510
3511 Supported Series: MODBUS RTU CONTROLLER
3512
3513 HMI works as MODBUS MASTER connecting with SLAVE.
3514
3515 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3516
3517 (% style="text-align:center" %)
3518 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3519
3520
3521 (% style="text-align:center" %)
3522 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3523
3524
3525 (% style="text-align:center" %)
3526 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3527
3528 **HMI Settings**
3529
3530 (% class="table-bordered" %)
3531 |**Items**|**Settings**|**Note**
3532 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3533 |Connection|RS485/RS232|
3534 |Baud rate|2400~~187500|
3535 |Data bit|8|
3536 |Parity|Even/ Odd/ None|
3537 |Stop bit|1/2|
3538 |PLC station No.|0~~255|
3539
3540 **Address List**
3541
3542 (% class="table-bordered" %)
3543 |**Type**|**Address Type**|**Function code & Description**
3544 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3545 |06 (write single register: write a binary value to a holding register)
3546 |10 (write values to multiple addresses )
3547 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3548 |06 (write single register: write a binary value to a holding register)
3549 |10 (write values to multiple addresses )
3550 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3551 |06 (write single register: write a binary value to a holding register)
3552 |10 (write values to multiple addresses )
3553 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3554 |10 (write values to multiple addresses )
3555 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3556 |05 (Force a single coil to force the on/off state of a logic coil)
3557 |0F (Write multiple bits, ie write continuously)
3558 |(% rowspan="3" %)1|02 (Read the input state)
3559 |05 (Force a single coil to force the on/off state of a logic coil)
3560 |0F (Write multiple bits)
3561 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3562 |05 (Force a single coil to force the on/off state of a logic coil)
3563 |0F (Write multiple bits)
3564 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3565 |0F (Write multiple bits)
3566
3567 **✎Note:**
3568
3569 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3570 * The function codes sent out are the same as those that read and write words.
3571
3572 **Station number for more than one slaves**
3573
3574 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3575
3576 (% style="text-align:center" %)
3577 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3578
3579 **Cable Wiring**
3580
3581 * **RS485**
3582
3583 (% style="text-align:center" %)
3584 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3585
3586 (% style="text-align:center" %)
3587 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3588
3589 * **RS232**
3590
3591 (% style="text-align:center" %)
3592 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3593
3594 **✎Note:** COM3 only available in PI8000/PI9000 series.
3595
3596 == **Communicate with Modbus Meter** ==
3597
3598 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
3599
3600 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
3601
3602 (% style="text-align:center" %)
3603 [[image:LinfeeDiagram.png]]
3604
3605 (% class="wikigeneratedid" %)
3606 2. Check the specific Modbus parameter in the communication menu from LED display.
3607
3608 (% class="wikigeneratedid" %)
3609 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
3610
3611 {{info}}
3612 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
3613 {{/info}}
3614
3615 (% style="text-align:center" %)
3616 [[image:MeterModbusAllView.png]]
3617
3618 3. Create new project and change the Communication settings.
3619
3620 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
3621
3622 (% style="text-align:center" %)
3623 [[image:PIStudioSetupMeterModbusPara.png]]
3624
3625 (% class="wikigeneratedid" %)
3626 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
3627
3628 (% class="wikigeneratedid" %)
3629 The following table is intercept part of the manual for Linfee Modbus manual.
3630
3631 (% class="wikigeneratedid" %)
3632 **0x03/0x04 command data register address**:
3633
3634 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
3635 | HEX|DEC| | | |
3636 |0x00|0|Reserved| | |
3637 |0x02|2|Reserved| | |
3638 |0x04|4|Reserved| | |
3639 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
3640 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
3641 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
3642 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
3643 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
3644 |0x10|16|Uca|float|2|Line Voltage data, Unit V
3645 |0x12|18|Ia|float|2|Phase Current data, Unit A
3646 |0x14|20|Ib|float|2|Phase Current data, Unit A
3647 |0x16|22|Ic|float|2|Phase Current data, Unit A
3648
3649 {{info}}
3650 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
3651 {{/info}}
3652
3653 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
3654
3655 (% style="text-align:center" %)
3656 [[image:MeterModbusPInumericSet.png]]
3657
3658 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
3659
3660 (% style="text-align:center" %)
3661 [[image:MeterModbusNumericInputFormat.png]]
3662
3663 (% class="wikigeneratedid" %)
3664 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
3665
3666 (% style="text-align:center" %)
3667 [[image:ActualHMIModbusResult.jpg]]
3668
3669 == **MODBUS TCP Slave (All function)** ==
3670
3671 Supported series: MODBUS TCP controller
3672
3673 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3674
3675 (% style="text-align:center" %)
3676 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3677
3678 (% style="text-align:center" %)
3679 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3680
3681
3682 (% style="text-align:center" %)
3683 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3684
3685 **HMI Setting**
3686
3687 (% class="table-bordered" %)
3688 |**Items**|**Settings**|**Note**
3689 |Protocol|MODBUS TCP Slave (All function)|
3690 |Connection|Ethernet|
3691 |Port No.|502|
3692 |PLC station No.|1|
3693
3694 **Address List**
3695
3696 (% class="table-bordered" %)
3697 |**Type**|**Register**|**Function code & Description**
3698 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3699 |06 (write single register: write a binary value to a holding register)
3700 |10 (write values to multiple addresses )
3701 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3702 |06 (write single register: write a binary value to a holding register)
3703 |10 (write values to multiple addresses )
3704 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3705 |06 (write single register: write a binary value to a holding register)
3706 |10 (write values to multiple addresses )
3707 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3708 |10 (write values to multiple addresses )
3709 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3710 |05 (Force a single coil to force the on/off state of a logic coil)
3711 |0F (Write multiple bits, ie write continuously)
3712 |(% rowspan="3" %)1|02 (Read the input state)
3713 |05 (Force a single coil to force the on/off state of a logic coil)
3714 |0F (Write multiple bits)
3715 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3716 |05 (Force a single coil to force the on/off state of a logic coil)
3717 |0F (Write multiple bits)
3718 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3719 |0F (Write multiple bits)
3720
3721 **Communication Settings**
3722
3723 Enable HMI Ethernet in [Project Settings];
3724
3725 (% style="text-align:center" %)
3726 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3727
3728 Set PLC IP in [Device IP] settings;
3729
3730 (% style="text-align:center" %)
3731 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3732
3733 **Cable Wiring**
3734
3735 (% style="text-align:center" %)
3736 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3737
3738 = **Printer** =
3739
3740 == **TSPL label printer** ==
3741
3742 **Introduction**
3743
3744 TSPL label printer protocol supports following models.
3745
3746 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3747 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3748
3749 **Setting Step**
3750
3751 Select the protocol
3752
3753 * Create a new project, select the TSPL label printer protocol as shown below.
3754
3755 (% style="text-align:center" %)
3756 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3757
3758 Set parameters
3759
3760 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3761
3762 Printer register
3763
3764 (% class="table-bordered" %)
3765 |**Register**|**System**|**Range**|**Function**
3766 |TSPL_SP|decimal|0 - 1|Set the paper size
3767 |TSPL_PT|decimal|0 - 1999|Print text
3768 |TSPL_PQ|decimal|0 - 999|Print QR code
3769 |TSPL_PB|decimal|0 - 999|Print barcode
3770 |TSPL_PR|decimal|0 - 1|Print offset
3771 |TSPL_PN|decimal|0 - 0|Trigger printing
3772 |TSPL_PS|decimal|0 - 0|Print status
3773
3774 * Set paper size:
3775 ** TSPL_SP0: width of paper, unit: mm.
3776 ** TSPL_SP1: height of paper, unit: mm.
3777 * Print text:
3778 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3779 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3780
3781 (% class="table-bordered" %)
3782 |**Register**|**Function**|**Description**
3783 |TSPL_PT0|X coordinate|Unit: dot
3784 |TSPL_PT1|Ycoordinate|Unit: dot
3785 |TSPL_PT2|Rotation angle|(((
3786 0: 0 degrees
3787
3788 1: 90 degrees
3789
3790 2: 180 degrees
3791
3792 3: 270 degrees
3793 )))
3794 |TSPL_PT3|Size|Range: 0-3
3795 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3796
3797 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3798
3799 Print QR code:
3800
3801 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3802 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3803
3804 (% class="table-bordered" %)
3805 |**Register**|**Function**|**Description**
3806 |TSPL_PQ0|X coordinate|Unit: dot
3807 |TSPL_PQ1|Ycoordinate|Unit: dot
3808 |TSPL_PQ2|Rotation angle|(((
3809 0: 0 degrees
3810
3811 1: 90 degrees
3812
3813 2: 180 degrees
3814
3815 3: 270 degrees
3816 )))
3817 |TSPL_PQ3|Size|Range: 0-5
3818 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3819
3820 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3821
3822 Print bar code:
3823
3824 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3825 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3826
3827 (% class="table-bordered" %)
3828 |**Register**|**Function**|**Description**
3829 |TSPL_PB0|X coordinate|Unit: dot
3830 |TSPL_PB1|Ycoordinate|Unit: dot
3831 |TSPL_PB2|Rotation angle|(((
3832 0: 0 degrees
3833
3834 1: 90 degrees
3835
3836 2: 180 degrees
3837
3838 3: 270 degrees
3839 )))
3840 |TSPL_PB3|height|Unit: dot
3841 |TSPL_PB4|width|Range:0-2
3842 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3843
3844 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3845
3846 Print offset:
3847
3848 * TSPL_PR0: X coordinate offset, unit: mm;
3849 * TSPL_PR1: Y coordinate offset, unit: mm.
3850
3851 Trigger printing:
3852
3853 * TSPL_PN0 = 1: trigger the printer to start printing.
3854
3855 Printing status:
3856
3857 * TSPL_PS0 = 1: The printing is normal.
3858 * TSPL_PS0 = 1: The printing is abnormal.
3859
3860 Print picture
3861
3862 * For the function of printing pictures, please refer to the configuration of [Printer object].
3863
3864 Conversion between dot and mm
3865
3866 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3867
3868 == **EpsonTM series** ==
3869
3870 **HMI Settings**
3871
3872 (% class="table-bordered" %)
3873 |**Item**|**Settings**|**Note**
3874 |Protocol|EPSON-TM-T82II/TM-XXX|
3875 |Connection|RS232|
3876 |Baud rate|9600~~115200|
3877 |Data bit|8|
3878 |Parity|None|
3879 |Stop bit|1|
3880 |PLC station No.|1|
3881
3882 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3883
3884 **Printer Settings**
3885
3886 (% class="table-bordered" %)
3887 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3888 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3889 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3890 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3891 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3892 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3893 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3894
3895 **Cable Wiring**
3896
3897 (% style="text-align:center" %)
3898 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3899
3900 (% style="text-align:center" %)
3901 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3902
3903 **✎Note:** COM3 only available in PI8000/PI9000 series.
3904
3905
3906 = Create communication with **Schneider PLC** =
3907
3908 == **Schneider MODBUS RTU** ==
3909
3910 **HMI Setting**
3911
3912 |=**Parameters**|=**Recommended**|=**Notes**
3913 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3914 |Connection|RS485|
3915 |**Baud rate**|19200|
3916 |**Data bit**|8|
3917 |**Parity**|Even|
3918 |**Stop bit**|1|
3919 |**PLC station No.**|1|
3920
3921 **PLC Setting**
3922
3923 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3924
3925 **Device Address**
3926
3927 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3928 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3929 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3930 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3931 |W|MW|DDDDDD|0 ~~ 999999|Output register
3932 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3933
3934 **Wiring Diagram**
3935
3936 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3937
3938 (% style="text-align:center" %)
3939 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3940
3941 = **Barcode Scanner** =
3942
3943 Supported: DELI 14880 barcode scanner
3944
3945 **HMI Setting**
3946
3947 |**Items**|**Settings**|**Note**
3948 |Protocol|Barcode Scanner|
3949 |Connection|USB|
3950
3951 **Operating Procedures**
3952
3953 Select [Barcode Scanner];
3954
3955 (% style="text-align:center" %)
3956 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3957
3958 Set address for receiving;
3959
3960 Set correct length;
3961
3962 (% style="text-align:center" %)
3963 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3964
3965 **✎Note:**
3966
3967 * The protocol uploads the information acquired by the USB scanner to the HMI;
3968 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3969 * Recommended model: DELI 14880 barcode scanner;
3970
3971 = **Hitachi EHV Series (Ethernet)** =
3972
3973 Supported series: Hitachi EHV series
3974
3975 **HMI Settings**
3976
3977 (% class="table-bordered" %)
3978 |**Items**|**Settings**|**Note**
3979 |Protocol|Hitachi EHV series|
3980 |Connection|Ethernet|
3981 |Port No.|3004~~3007|
3982
3983 **Address List**
3984
3985 (% class="table-bordered" %)
3986 |**Type**|**Register**|**Range**|**Format**|**Note**
3987 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3988 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3989 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3990 H1H2H3H4 Module main number
3991
3992 H1: Remote number
3993
3994 H2: Unit number
3995
3996 H3: Slot number
3997
3998 H4: Word number of Module
3999
4000 H Sub number of Module
4001
4002 For example:X21.3
4003
4004 Slot number 2
4005
4006 Word number of module is 1
4007
4008 Bit number of module is 3
4009
4010 Remote number and unit number are 0
4011 )))
4012 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4013 |R|0 – FF.f (Hex)|R HH.h|
4014 |L|0 - 73FF.f (Hex)|L HHHH.h|
4015 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4016 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4017 H1H2H3H4 Module main number
4018
4019 H1: Remote number
4020
4021 H2: Unit number
4022
4023 H3: Slot number
4024
4025 H4: Word number of module
4026
4027 For example:WX21
4028
4029 Word number of module is 1
4030
4031 Slot number is 2
4032
4033 Remote number and unit number are 0
4034 )))
4035 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4036 |WR|0 – FFFF (Hex)|WR HHHH|
4037 |WL|0 - 73FF (Hex)|WL HHHH|
4038 |TC|0 - 2559|TC DDDD|
4039
4040 **Communication settings in HMI**
4041
4042 Enable HMI Ethernet in [Project Settings];
4043
4044 (% style="text-align:center" %)
4045 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4046
4047 Set PLC IP in [Device IP] settings;
4048
4049 (% style="text-align:center" %)
4050 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4051
4052 **PLC Configuration**
4053
4054 Connect with PLC, select[Online mode];
4055
4056 (% style="text-align:center" %)
4057 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4058
4059 Set IP address, it is the same LAN parameters with HMI;
4060
4061 (% style="text-align:center" %)
4062 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4063
4064 3) Save PLC communication parameter, and restart PLC
4065
4066 **PLC Monitor Mode**
4067
4068 Connect with PLC and choose to “online” mode
4069
4070 (% style="text-align:center" %)
4071 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4072
4073 Open I/O monitor sheet1
4074
4075 (% style="text-align:center" %)
4076 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4077
4078 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4079
4080 (% style="text-align:center" %)
4081 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4082
4083 Enter the register address, click OK to view the value of the register.
4084
4085 (% style="text-align:center" %)
4086 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4087
4088 (% style="text-align:center" %)
4089 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4090
4091 **✎Note:**
4092
4093 * Both word registers and bit registers support even continuous read/write functions;
4094 * The range of registers is based on the specific PLC type;
4095
4096 **Cable Wiring**
4097
4098 (% style="text-align:center" %)
4099 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4100
4101 = **IEC60870-5 104 Client** =
4102
4103 **HMI Setting**
4104
4105 (% class="table-bordered" %)
4106 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4107 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4108 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4109 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4110
4111 **Address List**
4112
4113 (% class="table-bordered" %)
4114 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4115 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4116 |(% style="width:461px" %)SCNA|0~~16777215.7
4117 |(% style="width:461px" %)DPTB|0~~16777215.7
4118 |(% style="width:461px" %)DCNA|0~~16777215.7
4119 |(% style="width:461px" %)METF|0~~16777215.7
4120 |(% style="width:461px" %)SENC|0~~16777215.7
4121 |(% style="width:461px" %)SENA|0~~16777215.7
4122 |(% style="width:461px" %)MENA|0~~16777215.7
4123 |(% style="width:461px" %)METD|0~~16777215.7
4124 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4125 |(% style="width:461px" %)SCNA|0~~16777215
4126 |(% style="width:461px" %)DPTB|0~~16777215
4127 |(% style="width:461px" %)DCNA|0~~16777215
4128 |(% style="width:461px" %)SENA|0~~16777215
4129 |(% style="width:461px" %)MENA|0~~16777215
4130 |(% style="width:461px" %)METD|0~~16777215
4131 |(% style="width:461px" %)INRO|0~~16777215
4132 |(% style="width:461px" %)TIMESYN|0~~16777215
4133 |(% style="width:461px" %)TIMEZ|0~~16777215
4134 |(% style="width:461px" %)NTP|0~~16777215
4135 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4136 |(% style="width:461px" %)SENC|0~~16777215
4137
4138 **Address Configuration**
4139
4140 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4141
4142 (% style="text-align:center" %)
4143 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4144
4145 (% style="text-align:center" %)
4146 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4147
4148 Extended tag name
4149
4150 Address range for the extended tag.
4151
4152 **Communication Settings**
4153
4154 Enable HMI Ethernet in [Project Settings];
4155
4156 (% style="text-align:center" %)
4157 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4158
4159 Set PLC IP in [Device IP] settings;
4160
4161 (% style="text-align:center" %)
4162 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4163
4164 **Cable Wiring**
4165
4166 (% style="text-align:center" %)
4167 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4168
4169 = **OpenCAN** =
4170
4171 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4172
4173 This protocol is only available in PI8000 series HMI.
4174
4175 **HMI Settings**
4176
4177 |**Items**|**Settings**|**Note**
4178 |Protocol|OPENCAN|
4179 |Connection|CAN port|
4180 |Baud rate|250000|
4181
4182 **CAN frame setting in HMI**
4183
4184 Click [OpenCAN setting] button in communication setting window;
4185
4186 (% style="text-align:center" %)
4187 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4188
4189 Click [Add] to create a new frame;
4190
4191 (% style="text-align:center" %)
4192 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4193
4194 |**No**|**Items**|**Description**
4195 |1|Add|add a frame related to register address
4196 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4197 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4198 |4|Modify|Modify the frames in frame management
4199 |5|Copy|Copy one frame to another
4200 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4201 |7|Empty|All frames in the list are cleared
4202 |8|Browse|Displays configuration files in XML format in IE
4203 |9|OK|Complete the configuration of the frame and exit
4204
4205 Set CANBUS frame in setting windows
4206
4207 (% style="text-align:center" %)
4208 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4209
4210 |**No**|**Items**|**Description**
4211 |1|ID|Set the ID of a can frame in hexadecimal format;
4212 |2|ID assign|split the ID by PF, PS, and SA;
4213 |3|Frame type|Select Standard frame or Extended Frame;
4214 |4|Frame format|Select between data frame and remote Frame;
4215 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4216 |6|Use address|(((
4217 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4218
4219 **Edit:** Set a bit or word address by its format;
4220
4221 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4222 )))
4223 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4224 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4225 |Feedback mode: feedback mode includes no response, confirm response and data response;
4226 |No response: the device or touch screen will not receive feedback;
4227 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4228 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4229 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4230 |Response timeout: sets whether the response frame timeout;
4231 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4232 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4233 |Manually send: a manually send tick indicates only one send;
4234 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4235 |10|Note|Fill the text to explain the meaning of the frame;
4236 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4237 |12|Current operation display|Display the description of current operation;
4238 |13|Add|Add a new frame;
4239 |14|Save frame|Save the configured frame format;
4240 |15|Cancel|Cancel the frame configuration;
4241
4242 Set CAN address (Read or write operation);
4243
4244 (% style="text-align:center" %)
4245 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4246
4247 |**No.**|**Item**|**Description**
4248 |1|Current address|Displays the register type and register address set by the user in the data access interface
4249 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4250 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4251 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4252 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4253 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4254 |If the trigger condition is a writing operation, there are two situations:(((
4255 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4256 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4257 )))
4258 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4259 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4260 |4|Add|Add current configuration
4261 |5|Close|Close the configuration window to exit
4262
4263 **Multiple Packages Settings**
4264
4265 (% style="text-align:center" %)
4266 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4267
4268 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4269
4270 Select Multiple package type
4271
4272 * Not Multiple packages
4273 * J1939 Multiple packages
4274 * Customized Multiple packages
4275
4276 Click [Edit Receive data] for [Receive] settings
4277
4278 * Start code+ Total length (J1939)
4279
4280 (% style="text-align:center" %)
4281 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4282
4283 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4284
4285 * Start code + Data max length (J1939)
4286
4287 (% style="text-align:center" %)
4288 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4289
4290 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4291
4292 * Data max length (J1939)
4293
4294 (% style="text-align:center" %)
4295 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4296
4297 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4298
4299 * Customized multiple package
4300
4301 (% style="text-align:center" %)
4302 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4303
4304 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4305
4306 Click [Edit Send data] for [Send] setting
4307
4308 * J1939
4309
4310 (% style="text-align:center" %)
4311 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4312
4313 [Data] is all data to be sent.
4314
4315 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4316
4317 * Customized multiple package
4318
4319 (% style="text-align:center" %)
4320 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4321
4322 [Data] is all data to be sent.
4323
4324 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4325
4326 **Cable Wiring**
4327
4328 (% style="text-align:center" %)
4329 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4330
4331 **✎Note:** The address interval between each frame need to be more than a word address;
4332
4333
4334 = **User Defined Protocol** =
4335
4336 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4337
4338 **HMI Settings**
4339
4340 |**Items**|**Settings**|**Note**
4341 |Protocol|User defined protocol|
4342 |Connection|RS485/RS232|
4343 |Baud rate|2400~~187500|
4344 |Stop bits|1/ 2|
4345 |Data bits|7/ 8|
4346 |Parity|None/ Even/ ODD|
4347
4348 **Operating Procedures**
4349
4350 Select [User defined protocol];
4351
4352 Click [User defined protocol] button to open setting window as below;
4353
4354 (% style="text-align:center" %)
4355 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4356
4357 Configure user defined command;
4358
4359 (% style="text-align:center" %)
4360 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4361
4362 |**No**|**Item**|**Description**
4363 |1|Instruction edit|The required command.
4364 |2|Mode|Write to address or read from the address.
4365 |3|Format|Encode format: HEX or ASCII.
4366 |4|Other|(((
4367 **No receiving: **HMI does not respond to the receiving command.
4368
4369 **Send after receiving:** HMI responds to the receiving command.
4370 )))
4371 |5|Manually send|(((
4372 Respond once after trigger the address.
4373
4374 Address: set the trigger address.
4375 )))
4376 |6|Add|Save this setting.
4377 |7|Cancel|Cancel current settings.
4378 |(% rowspan="4" %)8|Add|Add a new command.
4379 |Edit|Edit the selected command.
4380 |Delete|Delete the selected command.
4381 |Clear|Clear all the commands.
4382 |9|Instruction list|Display all current commands.
4383 |10|Address List|Display all the addresses added.
4384 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4385 |Export|Export current command settings to local storage.
4386 |Browse|Browse local command files.
4387 |Advanced|Combine two commands.
4388 |Exit|Complete editing and exit setting.
4389
4390 **Operating Procedures**
4391
4392 Click [Add] to create a new command, as below shows;
4393
4394 (% style="text-align:center" %)
4395 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4396
4397 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4398
4399 (% style="text-align:center" %)
4400 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4401
4402 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4403
4404 (% style="text-align:center" %)
4405 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4406
4407 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4408
4409 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4410
4411 Check settings;
4412
4413 (% style="text-align:center" %)
4414 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4415
4416 |**No**|**Items**|**Description**
4417 |1|Add checking|Add checking command when receiving the data.
4418 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4419 |Differ with send check|Set return checking.
4420 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4421 |Length: The data length need to be checked.
4422
4423 Object settings;
4424
4425 (% style="text-align:center" %)
4426 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4427
4428 |**No**|**Items**|**Description**
4429 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4430 |Address: the triggering address;
4431 |Note: description to object;
4432 |2|Byte order|The numerical display order;
4433
4434 Data length settings;
4435
4436 (% style="text-align:center" %)
4437 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4438
4439 |**No**|**Item**|**Description**
4440 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4441 |Length: the return data length.
4442 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4443 |Length: the write data length.
4444
4445 Instruction length settings
4446
4447 (% style="text-align:center" %)
4448 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4449
4450 |**No**|**Item**|**Description**
4451 |1|Send length|The instruction data will only send designated data length.
4452 |2|Return length|The responds data length.
4453 |3|End code|Instruction will not be terminated until receiving [End code];
4454
4455 **Cable Wiring**
4456
4457 * **RS485**
4458
4459 (% style="text-align:center" %)
4460 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4461
4462 (% style="text-align:center" %)
4463 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4464
4465 * **RS232**
4466
4467 (% style="text-align:center" %)
4468 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4469
4470 **✎Note:** COM3 only available in PI8000/PI9000 series.