Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 253.1 by Hunter on 2023/05/09 10:36

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with Inovance PLC** =
910
911 == **H1U/H2U serial protocol** ==
912
913 **HMI Settings**
914
915 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
916 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
917 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
918 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
919 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
920 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
921 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
922 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
923 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
924
925 (% class="wikigeneratedid" %)
926 **Address List**
927
928 (% style="width:1014px" %)
929 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
930 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
931 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
932 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
933 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
934 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
935 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
936 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
937 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
938 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
939 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
940 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
941 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
942 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
943 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
944 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
945 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
946 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
947
948 (% class="wikigeneratedid" %)
949 **Cable Wiring**
950
951 (% style="text-align:center" %)
952 [[image:Inovance.png]]
953
954 == **H3U serial protocol** ==
955
956 **HMI Settings**
957
958 |=**Item**|=**Settings**|=**Note**
959 |Protocol|INOVANCE H3U PLC|
960 |Connection|RS422|
961 |Baud rate|9600|
962 |Data bit|7|
963 |Parity|EVEN|
964 |Stop bit|1|
965 |PLC station No.|0|
966
967 **Address List**
968
969 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
970 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
971 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
972 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
973 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
974 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
975 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
976 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
977 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
978 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
979 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
980 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
981 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
982 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
983 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
984 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
985 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
986 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
987 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
988
989 **Configure the communication protocol**
990
991 (% style="text-align:center" %)
992 [[image:image-20220830170114-4.png]]
993
994 [[image:image-20220830170017-3.png]]
995
996 **Cable Wiring**
997
998 (% style="text-align:center" %)
999 [[image:Inovance.png]]
1000
1001 == **H3U Ethernet portocol** ==
1002
1003 **HMI Settings**
1004
1005 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1006 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1007 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1008 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1009 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1010 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1011
1012 **Address List**
1013
1014 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1015 |Bit|M|M DDDD|0~~8511|
1016 |Bit|SM|SM DDDD|0~~1023|
1017 |Bit|S|S DDDD|0~~4095|
1018 |Bit|T|T DDD|0~~511|
1019 |Bit|C|C DDD|0~~255|
1020 |Bit|X|X OOO|0~~571|
1021 |Bit|Y|Y OOO|0~~571|
1022 |Word|D|D DDDD|0~~8511|
1023 |Word|SD |SD DDDD|0~~1023|
1024 |Word|R|R DDDDD|0~~32767|
1025 |Word|T|T DDD|0~~255|
1026 |Word|C|C DDD|0~~199|
1027 |Double Word|C|C DDD|200~~255|
1028
1029 **Cable Wiring**
1030
1031 (% style="text-align:center" %)
1032 [[image:CommonEthernet.png]]
1033
1034 = Create communication with LS** PLC** =
1035
1036 == **XGB serial protocol ** ==
1037
1038 **HMI Settings**
1039
1040 |=**Item**|=**Settings**|=**Note**
1041 |Protocol|LS XGB CPU DRIECT|
1042 |Connection|RS232|
1043 |Baud rate|115200|
1044 |Data bit|8|
1045 |Parity|NONE|
1046 |Stop bit|1|
1047 |PLC station No.|1|
1048
1049 **Address List**
1050
1051 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1052 |Bit|P|P|P DDDD.f|0~~2047|
1053 |Bit|M|M|M DDDD.f|0~~2047|
1054 |Bit|L|L|L DDDDD.f|0~~11263|
1055 |Bit|K|K|K DDDD.f|0~~2559|
1056 |Bit|F|F|F DDDD.f|0~~2047|
1057 |Bit|S|S|S DDDDD|0~~12799|
1058 |Bit|D|D|D DDDDD.f|0~~32767|
1059 |Bit|U|U|U FFFF.f|0~~7f31|
1060 |Bit|T|T|T DDDD.f|0~~2047|
1061 |Bit|C|C|C DDDD.f|0~~2047|
1062 |Word|P|P|P DDDD|0~~2047|
1063 |Word|M|M|M DDDD|0~~2047|
1064 |Word|L|L|L DDDDD|0~~11263|
1065 |Word|K|K|K DDDD|0~~2559|
1066 |Word|F|F|F DDDD|0~~2047|
1067 |Word|C|C|C DDDD|0~~2047|
1068 |Word|T|T|T DDDD|0~~2047|
1069 |Word|D|D|D DDDDD|0~~32767|
1070 |Word|N|N|N DDDDD|0~~21503|
1071 |Word|U|U|U FFFF|0~~7f31|
1072 |Word|Z|Z|Z DDD|0~~127|
1073 |Word|R|R|R DDDDD|0~~32767|
1074 |Word|ZR|ZR|Z DDDDD|0~~32767|
1075 |Word|TS|TS|TS DDDD|0~~2047|
1076 |Word|CS|CS|CS DDDD|0~~2047|
1077 |Word|S|S|S DDDDD|0~~12799|
1078
1079 **Configure the communication protocol**
1080
1081 (% style="text-align:center" %)
1082 [[image:image-20221028174410-1.png]]
1083
1084 (% style="text-align:center" %)
1085 [[image:image-20221028174753-2.png]]
1086
1087 (% style="text-align:center" %)
1088 [[image:image-20221028181125-4.png]]
1089
1090 **Pin Definition Diagram**
1091
1092 (% style="text-align:center" %)
1093 [[image:image-20221028180930-3.png]]
1094
1095 == **XBC serial protocol** ==
1096
1097 **HMI Settings**
1098
1099 |=**Item**|=**Settings**|=**Note**
1100 |Protocol|LS XBC CNet|
1101 |Connection|RS232|
1102 |Baud rate|115200|
1103 |Data bit|8|
1104 |Parity|NONE|
1105 |Stop bit|1|
1106 |PLC station No.|1|
1107
1108 **Address List**
1109
1110 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1111 |Bit|P|P|P d|0~~2047|
1112 |Bit|M|M|M d|0~~2047|
1113 |Bit|L|L|L d|0~~11263|
1114 |Bit|K|K|K d|0~~16183|
1115 |Bit|F|F|F d|0~~2047|
1116 |Bit|D|D|D d|0~~32767|
1117 |Bit|R|R|R d|0~~32767|
1118 |Bit|U|U|U d|0~~4095|
1119 |Word|P|P|P d|0~~2047|
1120 |Word|M|M|M d|0~~2047|
1121 |Word|L|L|L d|0~~11263|
1122 |Word|K|K|K d|0~~16183|
1123 |Word|F|F|F d|0~~2047|
1124 |Word|C|C|C d|0~~2047|
1125 |Word|T|T|T d|0~~2047|
1126 |Word|D|D|D d|0~~32767|
1127 |Word|N|N|N d|0~~21503|
1128 |Word|R|R|R d|0~~32767|
1129 |Word|U|U|U d|0~~4095|
1130 |Word|Z|Z|Z d|0~~127|
1131 |Word|S|S|S d|0~~127|
1132
1133 **Configure the communication protocol**
1134
1135 (% style="text-align:center" %)
1136 [[image:image-20220831170807-1.png]]
1137
1138 (% style="text-align:center" %)
1139 [[image:image-20220830174733-2.png]]
1140
1141 **Cable Wiring**
1142
1143 (% style="text-align:center" %)
1144 [[image:image-20220830174659-1.png]]
1145
1146 Pin Definition Diagram
1147
1148 (% style="text-align:center" %)
1149 [[image:image-20220830173402-8.png]]
1150
1151 == **XGK FEnet Ethernet protocol** ==
1152
1153 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1154
1155 **HMI Settings**
1156
1157 |**Items**|**Settings**|**Note**
1158 |Protocol|LG XGK FEnet(Ethernet)|
1159 |Connection|Ethernet|
1160 |Port No.|2004|
1161
1162 **Address List**
1163
1164 |**Type**|**Register**|**Range**|**Format**|**Note**
1165 |(% rowspan="14" %)Word|P|0~~2047|P d|
1166 |M|0~~2047|M d|
1167 |K|0~~2047|K d|
1168 |F|0~~2047|F d|
1169 |T|0~~2047|T d|
1170 |C|0~~2047|C d|
1171 |Z|0~~127|Z d|
1172 |S|0~~127|S d|
1173 |L|0~~11263|L d|
1174 |N|0~~21503|N d|
1175 |D|0~~32767|D d|
1176 |R|0~~32767|R d|
1177 |ZR|0~~65535|ZR d|
1178 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1179
1180 **✎Note:**
1181
1182 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1183 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1184 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1185
1186 **Communication settings in HMI**
1187
1188 Enable HMI Ethernet in [Project Settings];
1189
1190 (% style="text-align:center" %)
1191 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1192
1193 Set PLC IP in [Device IP] settings;
1194
1195 (% style="text-align:center" %)
1196 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1197
1198 **Cable Wiring**
1199
1200
1201 (% style="text-align:center" %)
1202 [[image:CommonEthernet.png]]
1203
1204 = Create communication with **Mitsubishi PLC** =
1205
1206 == **FX1S, 1N, 2N Series Protocol** ==
1207
1208 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1209
1210 **HMI Settings**
1211
1212 |**Item**|**Settings**|**Note**
1213 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1214 |Connection|RS422/RS485/RS232|
1215 |Baud rate|9600~~115200|
1216 |Data bit|7/8|
1217 |Parity|EVEN/Odd/None|
1218 |Stop bit|1/2|
1219 |PLC station No.|1~~255|
1220
1221 **Address List**
1222
1223 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1224 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1225 |Y|Y|Y o|0~~303237|
1226 |M|M|M d|0~~99999|
1227 |T|T|T d|0~~99999|
1228 |C|C|C d|0~~99999|
1229 |S|S|S d|0~~99999|
1230 |SM|SM|SM d|8000~~9999|
1231 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1232 |Y|Y|Y o|0~~303237|
1233 |M|M|M d|0~~99999|
1234 |T|T|T d|0~~99999|
1235 |C|C|C d|0~~199|
1236 |D|D|D d|0~~7999|
1237 |S|S|S d|0~~99999|
1238 |SD|SD|SD d|8000~~9999|
1239
1240 **Cable Wiring**
1241
1242 * **RS485**
1243
1244 (% style="text-align:center" %)
1245 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1246
1247 (% style="text-align:center" %)
1248 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1249
1250 * **RS422**
1251
1252 (% style="text-align:center" %)
1253 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1254
1255 **✎Note:** COM3 only available in PI8000/PI9000 series.
1256
1257 == **FX3U/3G/3GA serial protocol** ==
1258
1259 **HMI Settings**
1260
1261 |=**Item**|=**Settings**|=**Note**
1262 |Protocol|Mitsubishi FX3U/3G/3GA|
1263 |Connection|RS422|
1264 |Baud rate|9600~~115200|
1265 |Data bit|7/8|
1266 |Parity|EVEN/Odd/None|
1267 |Stop bit|1/2|
1268 |PLC station No.|1~~255|
1269
1270 **Address List**
1271
1272 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1273 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1274 |Y|Y|Y o|0~~303237|
1275 |M|M|M d|0~~99999|
1276 |T|T|T d|0~~99999|
1277 |C|C|C d|0~~99999|
1278 |S|S|S d|0~~99999|
1279 |SM|SM|SM d|8000~~9999|
1280 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1281 |Y|Y|Y o|0~~303237|
1282 |M|M|M d|0~~99999|
1283 |T|T|T d|0~~99999|
1284 |C|C|C d|0~~199|
1285 |D|D|D d|0~~7999|
1286 |S|S|S d|0~~99999|
1287 |SD|SD|SD d|8000~~9999|
1288
1289 **Configure the communication protocol**
1290
1291 (% style="text-align:center" %)
1292 [[image:image-20220831095222-1.png]]
1293
1294 (% style="text-align:center" %)
1295 [[image:image-20220831095743-2.png]]
1296
1297 **Wiring**
1298
1299 (% style="text-align:center" %)
1300 [[image:image-20220831100314-6.png]]
1301
1302 == **FX3U Ethernet Protocol** ==
1303
1304 Mitsubishi FX3U series PLC
1305
1306 **HMI Settings**
1307
1308 |Items|Settings|Note
1309 |Protocol|Mitsubishi FX3U|
1310 |Connection|Ethernet|
1311 |Port No.|5009|Must be the same as the PLC setting
1312 |PLC station No.|0|
1313
1314 **Address List**
1315
1316 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1317 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1318 |Y|Y|Y OOO|0~~377|
1319 |M|M|M DDDD|0~~7679|
1320 |SM|SM|SM DDDD|8000~~8511|
1321 |S|S|S DDDD|0~~4095|
1322 |TS|TS|TS DDD|0~~511|
1323 |CS|CS|CS DDD|0~~255|
1324 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1325 |TN|TN|TN DDD|0~~511|
1326 |D|D|D DDDD|0~~7999|
1327 |SD|SD|SD DDDD|8000~~8511|
1328 |R|R|R DDDDD|0~~32767|
1329
1330 **Ethernet Module Settings**
1331
1332 FX3U-ENET-L module configuration
1333 Set up the FX3U-ENET-L Ethernet module settings as follows.
1334 Select the module location, which in this document is Module 0.
1335
1336 [[image:image-20221115140802-1.png]]
1337
1338 Select "Operational setting" to enter the following screen.
1339
1340 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1341
1342 [[image:image-20221115142728-4.png]]
1343
1344 Select "Open setting" to enter the setting interface, the settings are as follows.
1345
1346 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1347
1348 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1349
1350 [[image:image-20221115142945-5.png]]
1351
1352 Click on "transter setup" - "PC side I/F setting", see the following figure.
1353
1354 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1355
1356 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1357
1358 [[image:image-20221115143341-6.png||height="426" width="712"]]
1359
1360 Read and write data from the Ethernet module
1361
1362 [[image:image-20221115143703-7.png]]
1363
1364 Set "Transter setup" to COM communication, and read or write operation as shown below
1365
1366 [[image:image-20221115143809-8.png]]
1367
1368 **PLC Settings (GX Works 2)**
1369
1370 Create a blank FX5U project
1371
1372 Find Current Connection in the navigation
1373
1374 [[image:image-20221115144335-9.png||height="422" width="706"]]
1375
1376 Select Connection Channel List
1377
1378 Select Ethernet board communication
1379
1380 [[image:image-20221115144824-10.png||height="421" width="705"]]
1381
1382 Select Ethernet Module
1383 Set the IP address of the PLC
1384
1385 [[image:image-20221115145228-11.png||height="674" width="708"]]
1386
1387 Read or write PLC data, in this document is read
1388
1389 [[image:image-20221115145553-12.png||height="424" width="711"]]
1390
1391 [[image:image-20221115145559-13.png||height="424" width="711"]]
1392
1393 **HMI Communication Setting**
1394
1395 [[image:image-20221115150003-14.png||height="425" width="712"]]
1396
1397 [[image:image-20221115150235-15.png||height="427" width="713"]]
1398
1399 [[image:image-20221115145559-13.png||height="424" width="711"]]
1400
1401 **HMI Communication Setting**
1402
1403 [[image:image-20221115150003-14.png||height="425" width="712"]]
1404
1405 [[image:image-20221115150235-15.png||height="427" width="713"]]
1406
1407 == **FX5U Serial Port Protocol** ==
1408
1409 Mitsubishi FX5U series PLC
1410
1411 **HMI Settings**
1412
1413 |**Item**|**Settings**|**Note**
1414 |Protocol|Mitsubishi FX5U|
1415 |Connection|RS422/RS485|
1416 |Baud rate|9600|
1417 |Data bit|7|
1418 |Parity|Odd|
1419 |Stop bit|1|
1420 |PLC station No.|1~~255|Need to be the same as PLC settings
1421
1422 **Address List**
1423
1424 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1425 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1426 |Y|Y|Y o|0~~303237|
1427 |M|M|M d|0~~99999|
1428 |B|B|B h|0~~7FFF|
1429 |F|F|F d|0~~32767|
1430 |SB|SB|SB h|0~~7FFF|
1431 |TS|TS|TS d|0~~1023|
1432 |TC|TC|TC d|0~~1023|
1433 |STS|STS|STS d|0~~1023|
1434 |STC|STC|STS d|0~~1023|
1435 |CS|CS|CS d|0~~1023|
1436 |CC|CC|CC d|0~~1023|
1437 |SM|SM|SM d|0~~9999|
1438 |L|L|L d|0~~32767|
1439 |S|S|S d|0~~4095|
1440 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1441 |TN|TN|TN d|0~~1023|
1442 |STN|STN|STN d|0~~1023|
1443 |CN|CN|CN d|0~~1023|
1444 |R|R|R d|0~~32767|
1445 |SW|SW|SW h|0~~7FFF|
1446 |Z|Z|Z d|0~~23|
1447 |D|D|D d|0~~7999|
1448 |SD|SD|SD d|0~~11999|
1449
1450 **PLC Settings (GX Works 3)**
1451
1452 Create a blank FX5U project
1453
1454 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1455
1456 (% style="text-align:center" %)
1457 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1458
1459 Select protocol in the setting item, and set parameters.
1460
1461 (% style="text-align:center" %)
1462 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1463
1464 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1465
1466 (% style="text-align:center" %)
1467 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1468
1469 Click the [Apply] button to finish the setting.
1470
1471 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1472
1473 (% style="text-align:center" %)
1474 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1475
1476 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1477
1478 Done.
1479
1480 **Cable Wiring**
1481
1482 * **RS485**
1483
1484 (% style="text-align:center" %)
1485 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1486
1487 (% style="text-align:center" %)
1488 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1489
1490 * **RS422**
1491
1492 (% style="text-align:center" %)
1493 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1494
1495 **✎Note:** COM3 only available in PI8000/PI9000 series.
1496
1497 == **L02 Serial Protocol** ==
1498
1499 Mitsubishi L02 series CPU built-in serial port.
1500
1501 **HMI Settings**
1502
1503 |=**Item**|=**Settings**|=**Note**
1504 |Protocol|Mitsubishi L02|
1505 |Connection|RS422|
1506 |Baud rate|115200|
1507 |Data bit|8|
1508 |Parity|Odd|
1509 |Stop bit|1|
1510 |PLC station No.|1~~255|Need to be the same as PLC settings
1511
1512 **Address List**
1513
1514 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1515 |Bit|X|X|X h|0~~FFFF|
1516 |Bit|Y|Y|Y h|0~~FFFF|
1517 |Bit|M|M|M d|0~~9999|
1518 |Bit|L|L|L d|0~~9999|
1519 |Bit|F|F|F d|0~~9999|
1520 |Bit|B|B|B h|0~~FFFF|
1521 |Bit|V|V|V d|0~~2047|
1522 |Bit|TC|TC|TC d|0~~9999|
1523 |Bit|SS|SS|SS d|0~~9999|
1524 |Bit|SC|SC|SC d|0~~9999|
1525 |Bit|CS|CS|CS d|0~~9999|
1526 |Bit|CC|CC|CC d|0~~9999|
1527 |Bit|SB|SB|SB h|0~~FFFF|
1528 |Bit|SM|SM|SM d|0~~2047|
1529 |Bit|STS|STS|STS d|0~~1023|
1530 |Bit|S|S|S d|0~~9999|
1531 |Bit|DX|DX|DX h|0~~FFFF|
1532 |Bit|DY|DY|DY h|0~~FFFF|
1533 |Bit|TS|TS|TS d|0~~9999|
1534 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1535 |Word|W|W|W h|0~~FFFF|
1536 |Word|TN|TN|TN d|0~~99999|
1537 |Word|SN|SN|SN d|0~~99999|
1538 |Word|CN|CN|CN d|0~~99999|
1539 |Word|R|R|R d|0~~99999|
1540 |Word|SW|SW|SW h|0~~FFFF|
1541 |Word|Z|Z|Z d|0~~99999|
1542 |Word|ZR|ZR|ZR h|0~~FFFF|
1543 |Word|D|D|D d|0~~99999|
1544
1545 **Communication Settings**
1546
1547 (% style="text-align:center" %)
1548 [[image:image-20220831105732-3.png]]
1549
1550 (% style="text-align:center" %)
1551 [[image:image-20220831110004-5.png]]
1552
1553 **Cable Wiring**
1554
1555 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1556
1557 Pin Definition Diagram
1558
1559 (% style="text-align:center" %)
1560 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1561
1562 == **L02 MELSEC (Ethernet) Protocol** ==
1563
1564 Mitsubishi Q series CPU built-in Ethernet port.
1565
1566 **HMI Settings**
1567
1568 |**Items**|**Settings**|**Note**
1569 |Protocol|MIT L02 CPU MELSEC|
1570 |Connection|Ethernet|
1571 |Port No.|1025|Must be the same as the PLC setting
1572 |PLC station No.|0|Must be the same as the PLC setting
1573
1574 **Address List**
1575
1576 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1577 |Bit|X|X|X h|0~~FFFF|
1578 |Bit|Y|Y|Y h|0~~FFFF|
1579 |Bit|M|M|M d|0~~9999|
1580 |Bit|L|L|L d|0~~9999|
1581 |Bit|F|F|F d|0~~9999|
1582 |Bit|B|B|B h|0~~FFFF|
1583 |Bit|V|V|V d|0~~2047|
1584 |Bit|TC|TC|TC d|0~~9999|
1585 |Bit|SS|SS|SS d|0~~9999|
1586 |Bit|SC|SC|SC d|0~~9999|
1587 |Bit|CS|CS|CS d|0~~9999|
1588 |Bit|CC|CC|CC d|0~~9999|
1589 |Bit|SB|SB|SB h|0~~FFFF|
1590 |Bit|SM|SM|SM d|0~~2047|
1591 |Bit|STS|STS|STS d|0~~1023|
1592 |Bit|S|S|S d|0~~9999|
1593 |Bit|DX|DX|DX h|0~~FFFF|
1594 |Bit|DY|DY|DY h|0~~FFFF|
1595 |Bit|TS|TS|TS d|0~~9999|
1596 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1597 |Word|W|W|W h|0~~FFFF|
1598 |Word|TN|TN|TN d|0~~99999|
1599 |Word|SN|SN|SN d|0~~99999|
1600 |Word|CN|CN|CN d|0~~99999|
1601 |Word|R|R|R d|0~~99999|
1602 |Word|SW|SW|SW h|0~~FFFF|
1603 |Word|Z|Z|Z d|0~~99999|
1604 |Word|ZR|ZR|ZR h|0~~FFFF|
1605 |Word|D|D|D d|0~~99999|
1606
1607 **Communication Settings**
1608
1609 Enable HMI Ethernet in [Project Settings];
1610
1611 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1612
1613 Set PLC IP in [Device IP] settings;
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1617
1618 **PLC Settings (GX Works2 )**
1619
1620 Create a project
1621
1622 Set PLC IP, subnet mask and gateway;
1623
1624 Select [Binary Code] as communication data code;
1625
1626 (% style="text-align:center" %)
1627 [[image:image-20221108202109-2.png||height="636" width="732"]]
1628
1629 Set PLC port number, for example 1025
1630
1631 (% style="text-align:center" %)
1632 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1633
1634 Save settings;
1635
1636 Download project into PLC device;
1637
1638 Restart PLC device;
1639
1640 **Cable Wiring**
1641
1642 (% style="text-align:center" %)
1643 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1644
1645 == **QJ71C24N MELSEC Protocol** ==
1646
1647 Mitsubishi QJ71C24N communication module built-in serial port;
1648
1649 **HMI Settings**
1650
1651 |**Items**|**Settings**|**Note**
1652 |Protocol|MIT QJ71 MELSEC|
1653 |Connection|422|
1654 |Baud rate|9600|
1655 |Data bit|8|
1656 |Parity|ODD|
1657 |Stop bit|1|
1658 |PLC station No.|1~~255|Need to be the same as PLC settings
1659
1660 **Address List**
1661
1662 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1663 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1664 |Y|Y|Y FFFF|0~~1FFF|
1665 |M|M|M DDDDD|0~~99999|
1666 |L|L|L DDDD|0~~8191|
1667 |F|F|F DDDD|0~~2047|
1668 |V|V|V DDDD|0~~2047|
1669 |B|B|B FFFF|0~~1FFF|
1670 |TS|TS|TS DDDD|0~~2047|
1671 |TC|TC|TC DDDD|0~~2047|
1672 |SS|SS|SS DDDD|0~~2047|
1673 |SC|SC|SC DDDD|0~~2047|
1674 |CS|CS|CS DDDD|0~~1023|
1675 |CC|CC|CC DDDD|0~~1023|
1676 |SB|SB|SB FFF|0~~7FF|
1677 |S|S|S D|0~~8191|
1678 |DX|DX|DX FFFF|0~~1FFF|
1679 |DY|DY|DY FFFF|0~~1FFF|
1680 |SM_|SM_|SM_ DDDD|8000~~9999|
1681 |SM|SM|SM DDDD|0~~2047|
1682 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1683 |D|D|D DDDDD|0~~12287|
1684 |W|W|W FFFF|0~~1FFF|
1685 |TN|TN|TN DDDD|0~~2047|
1686 |SN|SN|SN DDDD|0~~2047|
1687 |CN|CN|CN DDDD|0~~1023|
1688 |R|R|R DDDDD|0~~32767|
1689 |SW|SW|SW FFF|0~~7FF|
1690 |Z|Z|Z D|0~~15|
1691 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1692
1693 **Communication Settings**
1694
1695 (% style="text-align:center" %)
1696 [[image:image-20221109135738-1.png]]
1697
1698 (% style="text-align:center" %)
1699 [[image:image-20221109140016-3.png]]
1700
1701 Pin Definition Diagram
1702
1703 (% style="text-align:center" %)
1704 [[image:image-20221109140406-4.png]]
1705
1706 == **QJ71E71 MELSEC Protocol** ==
1707
1708 Mitsubishi QJ71E71 Ethernet communication module;
1709
1710 **HMI Settings**
1711
1712 |**Items**|**Settings**|**Note**
1713 |Protocol|MIT QJ71E71 MELSEC|
1714 |Connection|Ethernet|
1715 |Port No.|1025|Must be the same as the PLC setting
1716 |PLC station No.|0|Must be the same as the PLC setting
1717
1718 **Address List**
1719
1720 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1721 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1722 |Y|Y|Y h|0~~1FFF|
1723 |M|M|M d|0~~99999|
1724 |L|L|L d|0~~8191|
1725 |F|F|F d|0~~2047|
1726 |B|B|B h|0~~1FFF|
1727 |V|V|V d|0~~2047|
1728 |TS|TS|TS d|0~~2047|
1729 |TC|TC|TC d|0~~2047|
1730 |SS|SS|SS d|0~~2047|
1731 |SC|SC|SC d|0~~2047|
1732 |CS|CS|CS d|0~~1023|
1733 |CC|CC|CC d|0~~1023|
1734 |SB|SB|SB h|0~~7FF|
1735 |S|S|S d|0~~8191|
1736 |DX|DX|DX h|0~~1FFF|
1737 |DY|DY|DY h|0~~1FFF|
1738 |SM|SM|SM d|8000~~9999|
1739 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1740 |D|D|D d|0~~12287|
1741 |W|W|W h|0~~1FFF|
1742 |TN|TN|TN d|0~~2047|
1743 |SN|SN|SN d|0~~2047|
1744 |CN|CN|CN d|0~~1023|
1745 |R|R|R d|0~~32767|
1746 |SW|SW|SW h|0~~7FF|
1747 |Z|Z|Z d|0~~15|
1748 |ZR|ZR|ZR h|0~~FE7FF|
1749
1750 **HMI Communication Settings**
1751
1752 1) Enable HMI Ethernet in [Project Settings];
1753
1754 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1755
1756 2) Set PLC IP in [Device IP] settings
1757
1758 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1759
1760 **PLC Settings(GX Works2)**
1761
1762 * Click [Ethernet/CC IE/MELSECNET];
1763 * Please select [Ethernet] as network type;
1764 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1765 * Select [Online] as Mode;
1766 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1767 * Click [Operation setting] to set IP;
1768 * Select [Binary Code] as [Communication Data Code];
1769 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1770 * Click [Open setting]
1771 * Set protocol: TCP;
1772 * Set [unpassive] in [Open system];
1773 * Set [receive] in [Fixed buffer];
1774 * Set [procedure Exist] in [Fixed buffer communication];
1775 * Disable [Pairing open];
1776 * Set [No confirm] in [Existence confirmation];
1777 * Host station port number: 5009;
1778 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1779 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1780 * Download project into PLC and restart it
1781
1782 **Cable Wiring**
1783
1784 (% style="text-align:center" %)
1785 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1786
1787 = Create communication with **MODBUS** =
1788
1789 == **MODBUS RTU Master** ==
1790
1791 Supported Series: MODBUS RTU CONTROLLER
1792
1793 HMI works as MODBUS SLAVE connecting with MASTER
1794
1795 (% style="text-align:center" %)
1796 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1797
1798 (% style="text-align:center" %)
1799 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1800
1801 (% style="text-align:center" %)
1802 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1803
1804 **HMI Settings**
1805
1806 |**Items**|**Settings**|**Note**
1807 |Protocol|MODBUS RTU Master|
1808 |Connection|RS485/RS232|
1809 |Baud rate|2400~~187500|
1810 |Data bit|8|
1811 |Parity|Even/ Odd/ None|
1812 |Stop bit|1/2|
1813 |Station No.|0~~255|
1814
1815 **Address List**
1816
1817 |**Type**|**HMI address**|**MODBUS code**|**Range**
1818 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1819 |Word|HDW3500~~HDW7999|4|0~~4499
1820
1821 **Cable Wiring**
1822
1823 * **RS485**
1824
1825 (% style="text-align:center" %)
1826 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1827
1828 (% style="text-align:center" %)
1829 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1830
1831 * **RS232**
1832
1833 (% style="text-align:center" %)
1834 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1835
1836 **✎Note:** COM3 only available in PI8000/PI9000 series.
1837
1838 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1839
1840 Supported Series: MODBUS RTU CONTROLLER
1841
1842 HMI works as MODBUS MASTER connecting with SLAVE.
1843
1844 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1845
1846 (% style="text-align:center" %)
1847 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1848
1849 (% style="text-align:center" %)
1850 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1851
1852 (% style="text-align:center" %)
1853 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1854
1855 **HMI Settings**
1856
1857 |**Items**|**Settings**|**Note**
1858 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1859 |Connection|RS485/RS232|
1860 |Baud rate|2400~~187500|
1861 |Data bit|8|
1862 |Parity|Even/ Odd/ None|
1863 |Stop bit|1/2|
1864 |PLC station No.|0~~255|
1865
1866 **Address List**
1867
1868 |**Type**|**Address Type**|**Function code & Description**
1869 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1870 |06 (write single register: write a binary value to a holding register)
1871 |10 (write values to multiple addresses )
1872 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1873 |06 (write single register: write a binary value to a holding register)
1874 |10 (write values to multiple addresses )
1875 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1876 |06 (write single register: write a binary value to a holding register)
1877 |10 (write values to multiple addresses )
1878 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1879 |10 (write values to multiple addresses )
1880 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1881 |05 (Force a single coil to force the on/off state of a logic coil)
1882 |0F (Write multiple bits, ie write continuously)
1883 |(% rowspan="3" %)1|02 (Read the input state)
1884 |05 (Force a single coil to force the on/off state of a logic coil)
1885 |0F (Write multiple bits)
1886 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1887 |05 (Force a single coil to force the on/off state of a logic coil)
1888 |0F (Write multiple bits)
1889 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1890 |0F (Write multiple bits)
1891
1892 **✎Note:**
1893
1894 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1895 * The function codes sent out are the same as those that read and write words.
1896
1897 **Station number for more than one slaves**
1898
1899 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1900
1901 (% style="text-align:center" %)
1902 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1903
1904 **Cable Wiring**
1905
1906 * **RS485**
1907
1908 (% style="text-align:center" %)
1909 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1910
1911 (% style="text-align:center" %)
1912 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1913
1914 * **RS232**
1915
1916 (% style="text-align:center" %)
1917 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1918
1919 **✎Note:** COM3 only available in PI8000/PI9000 series.
1920
1921 == **Communicate with Modbus Meter** ==
1922
1923 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
1924
1925 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
1926
1927 (% style="text-align:center" %)
1928 [[image:LinfeeDiagram.png]]
1929
1930 2. Check the specific Modbus parameter in the communication menu from LED display.
1931
1932 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
1933
1934 {{info}}
1935 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
1936 {{/info}}
1937
1938 (% style="text-align:center" %)
1939 [[image:MeterModbusAllView.png]]
1940
1941 3. Create new project and change the Communication settings.
1942
1943 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
1944
1945 (% style="text-align:center" %)
1946 [[image:PIStudioSetupMeterModbusPara.png]]
1947
1948 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
1949
1950 The following table is intercept part of the manual for Linfee Modbus manual.
1951
1952 **0x03/0x04 command data register address**:
1953
1954 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
1955 | HEX|DEC| | | |
1956 |0x00|0|Reserved| | |
1957 |0x02|2|Reserved| | |
1958 |0x04|4|Reserved| | |
1959 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
1960 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
1961 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
1962 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
1963 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
1964 |0x10|16|Uca|float|2|Line Voltage data, Unit V
1965 |0x12|18|Ia|float|2|Phase Current data, Unit A
1966 |0x14|20|Ib|float|2|Phase Current data, Unit A
1967 |0x16|22|Ic|float|2|Phase Current data, Unit A
1968
1969 {{info}}
1970 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
1971 {{/info}}
1972
1973 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
1974
1975 (% style="text-align:center" %)
1976 [[image:MeterModbusPInumericSet.png]]
1977
1978 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
1979
1980 (% style="text-align:center" %)
1981 [[image:MeterModbusNumericInputFormat.png]]
1982
1983 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
1984
1985 (% style="text-align:center" %)
1986 [[image:ActualHMIModbusResult.jpg]]
1987
1988 == **MODBUS TCP Slave (All function)** ==
1989
1990 Supported series: MODBUS TCP controller
1991
1992 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
1993
1994 (% style="text-align:center" %)
1995 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1996
1997 (% style="text-align:center" %)
1998 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1999
2000 (% style="text-align:center" %)
2001 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2002
2003 **HMI Setting**
2004
2005 |**Items**|**Settings**|**Note**
2006 |Protocol|MODBUS TCP Slave (All function)|
2007 |Connection|Ethernet|
2008 |Port No.|502|
2009 |PLC station No.|1|
2010
2011 **Address List**
2012
2013 |**Type**|**Register**|**Function code & Description**
2014 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2015 |06 (write single register: write a binary value to a holding register)
2016 |10 (write values to multiple addresses )
2017 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2018 |06 (write single register: write a binary value to a holding register)
2019 |10 (write values to multiple addresses )
2020 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2021 |06 (write single register: write a binary value to a holding register)
2022 |10 (write values to multiple addresses )
2023 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2024 |10 (write values to multiple addresses )
2025 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2026 |05 (Force a single coil to force the on/off state of a logic coil)
2027 |0F (Write multiple bits, ie write continuously)
2028 |(% rowspan="3" %)1|02 (Read the input state)
2029 |05 (Force a single coil to force the on/off state of a logic coil)
2030 |0F (Write multiple bits)
2031 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2032 |05 (Force a single coil to force the on/off state of a logic coil)
2033 |0F (Write multiple bits)
2034 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2035 |0F (Write multiple bits)
2036
2037 **Communication Settings**
2038
2039 Enable HMI Ethernet in [Project Settings];
2040
2041 (% style="text-align:center" %)
2042 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2043
2044 Set PLC IP in [Device IP] settings;
2045
2046 (% style="text-align:center" %)
2047 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2048
2049 **Cable Wiring**
2050
2051
2052 (% style="text-align:center" %)
2053 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2054
2055 = Create communication with **Rockwell PLC** =
2056
2057 == **DF1 Protocol** ==
2058
2059 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2060
2061 **HMI Settings**
2062
2063 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2064 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2065 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2066 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2067 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2068 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2069 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2070 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2071 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2072
2073 **Address List**
2074
2075 (% class="table-bordered" %)
2076 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2077 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2078 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2079 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2080 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2081 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2082 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2083 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2084 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2085 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2086 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2087 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2088
2089 **Cable Wiring**
2090
2091 (% style="text-align:center" %)
2092 [[image:AB.gif]]
2093
2094 == **DF1 Advanced Protocol** ==
2095
2096 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2097
2098 **HMI Settings**
2099
2100 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2101 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2102 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2103 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2104 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2105 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2106 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2107 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2108 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2109
2110 **Address List**
2111
2112 (% class="table-bordered" %)
2113 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2114 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2115 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2116 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2117 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2118 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2119 Bit data file B0~~B99
2120
2121 First two digits is for file number
2122
2123 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2124 )))
2125 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2126 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2127 Integer data file bit format N0~~N99
2128
2129 First two digits is for file number
2130
2131 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2132 )))
2133 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2134 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2135 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2136 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2137 Timer Preset Value
2138
2139 First two digits is for file number
2140
2141 For example, TNS99255 represents file number T99, address 255.
2142 )))
2143 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2144 Timer Accumulator Value
2145
2146 First two digits is for file number
2147
2148 For example, TNP99255 represents file number T99, address 255.
2149 )))
2150 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2151 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2152 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2153 Counter Preset Value
2154
2155 First two digits is for file number
2156
2157 For example, CNS99255 represents file number C99, address 255.
2158 )))
2159 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2160 Counter Accumulator Value
2161
2162 First two digits is for file number
2163
2164 For example, CNP99255 represents file number C99, address 255.
2165 )))
2166 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2167 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2168 Integer data file
2169
2170 First two digits is for file number
2171
2172 For example, NN99255 represents file number N99, address 255.
2173 )))
2174 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2175 Only able to communicate with file number F8
2176 )))
2177 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2178 Floating point data file
2179
2180 First two digits is for file number
2181
2182 For example, FN99255 represents file number F99, address 255.
2183 )))
2184 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2185
2186 **Cable Wiring**
2187
2188 (% style="text-align:center" %)
2189 [[image:AB.gif]]
2190
2191 == **MicroLogix Protocol** ==
2192
2193 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2194
2195 **HMI Settings**
2196
2197 (% class="table-bordered" %)
2198 |**Item**|**Settings**|**Note**
2199 |Protocol|Allen-Bradlley MicroLogix|
2200 |Connection|RS232|
2201 |Baud rate|19200|
2202 |Data bit|8|
2203 |Parity|None|
2204 |Stop bit|1|
2205 |PLC station No.|1|
2206
2207 **Address List**
2208
2209 (% class="table-bordered" %)
2210 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2211 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2212 |O|O d.d|0.0~~255.15|
2213 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2214 |S|S d.d|0.0~~255.15|
2215 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2216 |(% rowspan="9" %)Word|S|S d|0~~255|
2217 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2218 |TP|TP nnhh|0~~ffff
2219 |CS|CS nnhh|0~~ffff
2220 |CP|CP nnhh|0~~ffff
2221 |N|N nnhh|0~~ffff
2222 |C|C nnhh|0~~ffff
2223 |T|T nnhh|0~~ffff
2224 |R|R nnhh|0~~ffff
2225
2226 **Cable Wiring**
2227
2228
2229 (% style="text-align:center" %)
2230 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2231
2232 == **CompactLogix FreeTag Ethernet protocol** ==
2233
2234 Allen-Brandly CompactLogix
2235
2236 **HMI Settings**
2237
2238 (% class="table-bordered" %)
2239 |**Items**|**Settings**|**Note**
2240 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2241 |Connection|Ethernet|
2242 |Port No.|44818|
2243
2244 **PLC Setting**
2245
2246 Create new tags
2247
2248 (% style="text-align:center" %)
2249 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2250
2251 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2252
2253 (% style="text-align:center" %)
2254 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2255
2256 Import labels, please open [Communication] window and click [Import label];
2257
2258 Select csv file, all tags will be displayed as belows;
2259
2260 (% style="text-align:center" %)
2261 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2262
2263 **✎Note:**
2264
2265 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2266
2267 (% style="text-align:center" %)
2268 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2269
2270 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2271
2272 **Communication settings in HMI**
2273
2274 Enable HMI Ethernet in [Project Settings];
2275
2276 (% style="text-align:center" %)
2277 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2278
2279 Set PLC IP in [Device IP] settings;
2280
2281 (% style="text-align:center" %)
2282 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2283
2284 **Cable Wiring**
2285
2286 (% style="text-align:center" %)
2287 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2288
2289 == **MicroLogix 1200** **protocol** ==
2290
2291 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2292
2293 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2294 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2295 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2296 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2297
2298 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2299
2300 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2301 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2302 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2303 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2304 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2305 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2306 |**PLC word address type**|**Address format**|**Address range**
2307 |S|ddd|S0 ~~ 255
2308 |TS|ffff|TS0 ~~ FFFF
2309 |TP|ffff|TP0 ~~ FFFF
2310 |CS|ffff|CS0 ~~ FFFF
2311 |CP|ffff|CP0 ~~ FFFF
2312 |N|ffff|N0 ~~ FFFF
2313 |F|ffff|F0 ~~ FFFF
2314
2315 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2316
2317 == **S7-200 Smart Ethernet Protocol** ==
2318
2319 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2320
2321 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2322
2323 **HMI Setting**
2324
2325 (% class="table-bordered" %)
2326 |**Items**|**Settings**|**Note**
2327 |Protocol|Simens S7-200 Smart Ethernet|
2328 |Connection|Ethernet|
2329 |Port No.|102|
2330 |PLC station No.|2|
2331
2332 **Address List**
2333
2334 (% class="table-bordered" %)
2335 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2336 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2337 |Q|Q|Q ddddd.o|0.0~~99999.7|
2338 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2339 |V|V|V ddddd.o|0.0~~99999.7|
2340 |M|M|M ddddd.o|0.0~~99999.7|
2341 |SM|SM|ddddd.o|0.0~~99999.7|
2342 |S|S|ddddd.o|0.0~~99999.7|Read only
2343 |T|T|ddddd|0~~99999|Timer state, read only
2344 |C|C|ddddd|0~~99999|Counter state, read only
2345 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2346 |Q|QW|QW ddddd|0~~99999|
2347 |AI|AIW|AIW ddddd|0~~99999|
2348 |AQ|VB|VB ddddd|0~~99999|
2349 |V|VW|VW ddddd|0~~99998|(((
2350 VW0=VB (0~~1)
2351
2352 VW2=VB (2~~3)
2353
2354 Address value is a multiple of 2
2355 )))
2356 |V|VD|VD ddddd|0~~99998|(((
2357 VD0=VB (0~~3)
2358
2359 VD2=VB (4~~7)
2360
2361 Address value is a multiple of 4
2362 )))
2363 |M|MB|MB ddddd|0~~99999|
2364 |M|MW|MW ddddd|0~~99999|(((
2365 MW0=MB(0~~1)
2366
2367 MW2=MB(2~~3)
2368
2369 Address value is a multiple of 2
2370 )))
2371 |M|MD|MD ddddd|0~~99999|(((
2372 MD0=MB(0~~3)
2373
2374 MD4=MB(4~~7)
2375
2376 Address value is a multiple of 4
2377 )))
2378 |T|TW|TW ddddd|0~~99999|Value of timer
2379 |C|CW|CW ddddd|0~~99999|Value of counter
2380 |W|SW|SW ddddd|0~~99999|
2381
2382 **Communication Settings**
2383
2384 Enable HMI Ethernet in [Project Settings];
2385
2386 (% style="text-align:center" %)
2387 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2388
2389 Set PLC IP in [Device IP] settings;
2390
2391 (% style="text-align:center" %)
2392 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2393
2394 * PLC IP Address: PLC IP
2395 * PLC pot No.: 102(fixed)
2396 * Network:TCP_Client_2N(fixed)
2397
2398 (% style="text-align:center" %)
2399 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2400
2401 * Wait timeout: depend on actual network situation (more than 1500 ms)
2402
2403 **Cable Wiring**
2404
2405 (% style="text-align:center" %)
2406 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2407
2408 == **S7-300 Ethernet Protocol** ==
2409
2410 Supported Series: Siemens S7-300 series PLC
2411
2412 **HMI Setting**
2413
2414 (% class="table-bordered" %)
2415 |**Items**|**Settings**|**Note**
2416 |Protocol|Simens S7-300 Ethernet|
2417 |Connection|Ethernet|
2418 |Port No.|102|
2419 |PLC station No.|2|Need to be same as the PLC setting
2420
2421 **Address List**
2422
2423 (% class="table-bordered" %)
2424 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2425 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2426 |Q|Q|Q ddddd.o|0.0~~99999.7|
2427 |M|M|M ddddd.o|0.0~~99999.7|
2428 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2429 nnnn: block number;
2430
2431 dddd: address;
2432 )))
2433 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2434 |Q|QW|QW ddddd|0~~99999|
2435 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2436 |MW|MW ddddd|0~~99999|(((
2437 MW0=MB(0~~1)
2438
2439 MW2=MB(2~~3)
2440
2441 Address value is a multiple of 2
2442 )))
2443 |MD|MD ddddd|0~~99999|(((
2444 MD0=MB(0~~3)
2445
2446 MD4=MB(4~~7)
2447
2448 Address value is a multiple of 4
2449 )))
2450 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2451 nnnn: block number;
2452
2453 dddd: address
2454 )))
2455 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2456 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2457
2458 **Communication Settings**
2459
2460 Enable HMI Ethernet in [Project Settings];
2461
2462 (% style="text-align:center" %)
2463 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2464
2465 Set PLC IP in [Device IP] settings;
2466
2467 (% style="text-align:center" %)
2468 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2469
2470 * PLC IP Address: PLC IP
2471 * PLC pot No.: 102(fixed)
2472 * Network:TCP_Client_2N(fixed)
2473
2474 (% style="text-align:center" %)
2475 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2476
2477 * Wait timeout: depend on actual network situation (more than 1500 ms)
2478
2479 **Cable Wiring**
2480
2481 (% style="text-align:center" %)
2482 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2483
2484 == **S7-1200 Ethernet Protocol** ==
2485
2486 Supported Series: Siemens S7-1200
2487
2488 **HMI Setting**
2489
2490 (% class="table-bordered" %)
2491 |**Items**|**Settings**|**Note**
2492 |Protocol|Siemens S7-1200|
2493 |Connection|Ethernet|
2494 |Port No.|102|
2495 |PLC station No.|2|
2496
2497 **Address List**
2498
2499 (% class="table-bordered" %)
2500 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2501 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2502 d:0~-~-9999
2503
2504 o:0-7
2505 )))|
2506 |Q|Q|Q d.o|(((
2507 d:0~-~-9999
2508
2509 o:0-7
2510 )))|
2511 |M|M|M d.o|(((
2512 d:0~-~-9999
2513
2514 o:0-7
2515 )))|
2516 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2517 nn:0-9999,
2518
2519 dddd:0-9999,
2520
2521 o:0-7
2522 )))|(((
2523 nn:DB No.
2524
2525 dddd:address value
2526
2527 o: digit address
2528 )))
2529 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2530 |M|MW|MW d|d:0-99999|(((
2531 MW0=MB(0~~1)
2532
2533 MW2=MB(2~~3)
2534
2535 Address value is a multiple of 2
2536 )))
2537 |M|MD|MD d|d:0-99999|(((
2538 MD0=MB(0~~3)
2539
2540 MD4=MB(4~~7)
2541
2542 Address value is a multiple of 4
2543 )))
2544 |I|IW|IW d|d:0-99999|
2545 |Q|QW|QW d|d:0-99999|
2546 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2547 nn:0-9999
2548
2549 dddd:0-9999
2550 )))|(((
2551 nn:DB No.
2552
2553 dddd:address value
2554 )))
2555 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2556 nn:0-9999
2557
2558 dddd:0-9999
2559 )))|(((
2560 nn:DB No.
2561
2562 dddd:address value
2563
2564 Address value is a multiple of 2
2565 )))
2566 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2567 nn:0-9999
2568
2569 dddd:0-9999
2570 )))|(((
2571 nn:DB No.
2572
2573 dddd:address value
2574
2575 Address value is a multiple of 4
2576 )))
2577
2578 **Communication Settings**
2579
2580 Enable HMI Ethernet in [Project Settings];
2581
2582 (% style="text-align:center" %)
2583 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2584
2585 Set PLC IP in [Device IP] settings;
2586
2587 (% style="text-align:center" %)
2588 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2589
2590 **✎Note:**
2591
2592 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2593 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2594 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2595 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2596
2597 **PLC Settings**
2598
2599 Add BD
2600
2601 * Please uncheck [Symbolic access only] option;
2602
2603 (% style="text-align:center" %)
2604 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2605
2606 Address settings, using BD2 as example.
2607
2608 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2609 * 2 represent DB block number
2610 * xxxx represent address
2611
2612 **Such as:**
2613
2614 * DBxDBB20000 = DB2.DBB0
2615 * DBxDBW20004 = DB2.DBW4
2616
2617 (% style="text-align:center" %)
2618 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2619
2620 **How to connect with S7-1200 Firmware V4.0**
2621
2622 PLC configuration
2623
2624 * Double click [device configuration] in Siemens via software
2625 * Double click [protection] to enter protection configuration screen
2626
2627 (% style="text-align:center" %)
2628 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2629
2630 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2631
2632 (% style="text-align:center" %)
2633 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2634
2635 DB settings
2636
2637 * Right click [DB], select [properties]
2638 * Uncheck [optimized block access]
2639
2640 **Cable Wiring**
2641
2642 (% style="text-align:center" %)
2643 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2644
2645 == **S7-XXX Ethernet Protocol** ==
2646
2647 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2648
2649 **HMI Setting**
2650
2651 (% class="table-bordered" style="width:823px" %)
2652 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2653 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2654 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2655 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2656 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2657 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2658
2659 Slot from TIA Portal is equal to Device No. of PIStudio
2660
2661 Rack from TIA Portal is equal to HMI No. of PIStudio
2662
2663 (% style="text-align:center" %)
2664 [[image:S7-XXXCommunication Settings.png]]
2665
2666 (% style="text-align:center" %)
2667 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2668
2669 **Address List**
2670
2671 (% class="table-bordered" %)
2672 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2673 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2674 d:0~-~-9999
2675
2676 o:0-7
2677 )))|
2678 |Q|Q|Q d.o|(((
2679 d:0~-~-9999
2680
2681 o:0-7
2682 )))|
2683 |M|M|M d.o|(((
2684 d:0~-~-9999
2685
2686 o:0-7
2687 )))|
2688 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2689 nn:0-9999,
2690
2691 dddd:0-9999,
2692
2693 o:0-7
2694 )))|(((
2695 nn:DB No.
2696
2697 dddd:address value
2698
2699 o: digit address
2700 )))
2701 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2702 |M|MW|MW d|d:0-99999|(((
2703 MW0=MB(0~~1)
2704
2705 MW2=MB(2~~3)
2706
2707 Address value is a multiple of 2
2708 )))
2709 |M|MD|MD d|d:0-99999|(((
2710 MD0=MB(0~~3)
2711
2712 MD4=MB(4~~7)
2713
2714 Address value is a multiple of 4
2715 )))
2716 |I|IW|IW d|d:0-99999|
2717 |Q|QW|QW d|d:0-99999|
2718 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2719 nn:0-9999
2720
2721 dddd:0-9999
2722 )))|(((
2723 nn:DB No.
2724
2725 dddd:address value
2726 )))
2727 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2728 nn:0-9999
2729
2730 dddd:0-9999
2731 )))|(((
2732 nn:DB No.
2733
2734 dddd:address value
2735
2736 Address value is a multiple of 2
2737 )))
2738 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2739 nn:0-9999
2740
2741 dddd:0-9999
2742 )))|(((
2743 nn:DB No.
2744
2745 dddd:address value
2746
2747 Address value is a multiple of 4
2748 )))
2749
2750 **Communication Settings**
2751
2752 Enable HMI Ethernet in [Project Settings];
2753
2754 (% style="text-align:center" %)
2755 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2756
2757 Set PLC IP in [Device IP] settings;
2758
2759 (% style="text-align:center" %)
2760 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2761
2762 **✎Note:**
2763
2764 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2765 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2766
2767 **Cable Wiring**
2768
2769 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2770
2771 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
2772
2773 Supported Series: Siemens Logo 0BA0, 0BA1 series
2774
2775 **HMI Settings**
2776
2777 (% class="table-bordered" %)
2778 |**Items**|**Settings**|**Note**
2779 |Protocol|Siemens LOGO|
2780 |Connection|Ethernet|
2781 |Port No.|102|
2782 |PLC station No.|2|
2783
2784 **Address List**
2785
2786 (% class="table-bordered" %)
2787 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2788 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2789 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2790 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2791 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2792 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2793 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2794 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2795 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2796 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2797 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2798 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2799 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2800 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2801 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2802 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2803
2804 **PLC Settings in LOGO Software:**
2805
2806 Click [Tools]~-~-[Ethernet Connections],shown as below.
2807
2808 (% style="text-align:center" %)
2809 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2810
2811 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2812
2813 (% style="text-align:center" %)
2814 [[image:image-20221228142937-4.png]]
2815
2816 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2817
2818 (% style="text-align:center" %)
2819 [[image:image-20221228143047-5.png]]
2820
2821 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2822
2823 (% style="text-align:center" %)
2824 [[image:image-20221228143246-6.png]]
2825
2826
2827 **HMI Communication Settings**
2828
2829 Set PLC IP in [Device IP] settings;
2830
2831 (% style="text-align:center" %)
2832 [[image:image-20221228143614-7.png]]
2833
2834 Enable HMI Ethernet in [Project Settings];
2835
2836 (% style="text-align:center" %)
2837 [[image:image-20221228144229-9.png]]
2838
2839 TSAP setting
2840
2841 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2842 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
2843 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
2844 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
2845 ie, ig series: use HSW1200, HSW1201.
2846 HMI V2.0: use HSW1200, HSW1201.
2847
2848 **✎Note:**
2849
2850 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
2851 * HSW10119/HSW1201 is set up as shown.
2852 * (((
2853 (% style="text-align:center" %)
2854 [[image:image-20221228144800-11.png]]
2855 )))
2856 * (((
2857 (% style="text-align:center" %)
2858 [[image:image-20221228144708-10.png]]
2859 )))
2860
2861 * AI word address and Ibit address are read-only and cannot be written on HMI.
2862 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
2863 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
2864 * Written value of RTC cannot exceed 255.
2865
2866 **Cable Wiring**
2867
2868 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2869
2870 == S7-300 232 ==
2871
2872 **HMI Setting:**
2873
2874 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
2875 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
2876 |=**PLC I/F**|RS232| |
2877 |=**Baud rate**|19200|9600,19200|
2878 |=**Data bits**|8| |
2879 |=**Parity**|Odd| |
2880 |=**Stop bits**|1| |
2881 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
2882
2883 **Device Address**
2884
2885 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2886 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
2887 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
2888 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
2889 |=Word|(((
2890 DB1 to DB99
2891 )))|DDDDDo|0 ~~ 655327|
2892 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
2893 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
2894 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
2895 |=Double word|MD|DDDD|0 ~~ 4094|
2896 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
2897 Data Register Double Word (must be even)
2898 )))
2899 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
2900
2901 **Cable Wiring**
2902
2903 (% style="text-align:center" %)
2904 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
2905
2906 = Create communication with **Omron** PLC =
2907
2908 == CJ TCP FINS Ethemet  Protocol ==
2909
2910 Supported device:CJ series、CJ1W-EIP21
2911
2912 **HMI Settings**
2913
2914 |=**Items**|=**Settings**|=**Note**
2915 |Protocol|OMRON CJ TCP FINS Ethemet|
2916 |Connection|Ethernet|
2917 |Port No.|9600|
2918 |Device No.|0|
2919 |HMI No.|0|(((
2920
2921 )))
2922
2923 **Address List**
2924
2925 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2926 |Bit|CIO|CIO|CIO d|0~~99999|
2927 |Bit|W|W|W d|0~~99999|
2928 |Bit|D|D|D d|0~~99999|
2929 |Bit|H|H|H d|0~~99999|
2930 |Bit|A|A|A d|0~~99999|
2931 |Bit|T|T|T h|0~~99999|
2932 |Bit|CF|CF|CF d|0~~99999|
2933 |Bit|FF|FF|FF d|0~~99999|
2934 |Bit|C|C|C d|0~~99999|
2935 |Bit|EM0|EM0|EM0 d|0~~99999|
2936 |Bit|EM1|EM1|EM1 d|0~~99999|
2937 |Bit|EM2|EM2|EM2 d|0~~99999|
2938 |Bit|EM3|EM3|EM3 d|0~~99999|
2939 |Bit|EM4|EM4|EM4 d|0~~99999|
2940 |Bit|EM5|EM5|EM5 h|0~~99999|
2941 |Bit|EM6|EM6|EM6 d|0~~99999|
2942 |Bit|EM7|EM7|EM7 d|0~~99999|
2943 |Bit|EM8|EM8|EM8 d|0~~99999|
2944 |Bit|EM9|EM9|EM9 d|0~~99999|
2945 |Bit|EMA|EMA|EMA d|0~~99999|
2946 |Bit|EMB|EMB|EMB d|0~~99999|
2947 |Bit|EMC|EMC|EMC d|0~~99999|
2948 |Bit|Lamp|Lamp|Lamp d|0~~0|
2949 |Word|CIO|CIO|CIO d|0~~99999|
2950 |Word|W|W|W d|0~~99999|
2951 |Word|D|D|D d|0~~99999|
2952 |Word|H|H|H d|0~~99999|
2953 |Word|A|A|A d|0~~99999|
2954 |Word|T|T|T h|0~~99999|
2955 |Word|CF|CF|CF d|0~~99999|
2956 |Word|FF|FF|FF d|0~~99999|
2957 |Word|C|C|C d|0~~99999|
2958 |Word|EM0|EM0|EM0 d|0~~99999|
2959 |Word|EM1|EM1|EM1 d|0~~99999|
2960 |Word|EM2|EM2|EM2 d|0~~99999|
2961 |Word|EM3|EM3|EM3 d|0~~99999|
2962 |Word|EM4|EM4|EM4 d|0~~99999|
2963 |Word|EM5|EM5|EM5 h|0~~99999|
2964 |Word|EM6|EM6|EM6 d|0~~99999|
2965 |Word|EM7|EM7|EM7 d|0~~99999|
2966 |Word|EM8|EM8|EM8 d|0~~99999|
2967 |Word|EM9|EM9|EM9 d|0~~99999|
2968 |Word|EMA|EMA|EMA d|0~~99999|
2969 |Word|EMB|EMB|EMB d|0~~99999|
2970 |Word|EMC|EMC|EMC d|0~~99999|
2971 |Word|IR|IR|IR d|0~~99999|
2972 |Word|DR|DR|DR d|0~~99999|
2973
2974 **Configure the communication protocol**
2975
2976 (% style="text-align:center" %)
2977 [[image:image-20220830143348-1.png]]
2978
2979 (% style="text-align:center" %)
2980 [[image:image-20220830143511-2.png]]
2981
2982 **Configure CJ1W-EIP21 connect with HMI**
2983
2984 (% style="text-align:center" %)
2985 [[image:ftEVGvAprh.png]]
2986
2987 Select TCP_Client_2N
2988
2989 (% style="text-align:center" %)
2990 [[image:RURXWcgyCd.png]]
2991
2992 **Cable Wiring**
2993
2994 Pin Definition Diagram
2995
2996 (% style="text-align:center" %)
2997 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2998
2999 == **CP1E/CP1H serial protocol** ==
3000
3001 Supported device: OMRON CS1(CP1E/CP1H)
3002
3003 **HMI Settings**
3004
3005 |=**Items**|=**Settings**|=**Note**
3006 |Protocol|OMRON CS1(CP1E/CP1H)|
3007 |Connection|RS232 (9600, 2, 7, EVEN)|
3008 |Port No.|None|
3009 |PLC station No.|0|
3010
3011 **Address List**
3012
3013 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3014 |Bit|CIO|CIO|CIO d|0~~99999|
3015 |Bit|W|W|W d|0~~99999|
3016 |Bit|D|D|D d|0~~99999|
3017 |Bit|H|H|H d|0~~99999|
3018 |Bit|A|A|A d|0~~99999|
3019 |Bit|TF|T|T h|0~~99999|
3020 |Bit|CF|CF|CF d|0~~99999|
3021 |Bit|T|FF|FF d|0~~99999|
3022 |Bit|C|C|C d|0~~99999|
3023 |Bit|EM0|EM0|EM0 d|0~~99999|
3024 |Bit|EM1|EM1|EM1 d|0~~99999|
3025 |Bit|EM2|EM2|EM2 d|0~~99999|
3026 |Bit|EM3|EM3|EM3 d|0~~99999|
3027 |Bit|EM4|EM4|EM4 d|0~~99999|
3028 |Bit|EM5|EM5|EM5 h|0~~99999|
3029 |Bit|EM6|EM6|EM6 d|0~~99999|
3030 |Bit|EM7|EM7|EM7 d|0~~99999|
3031 |Bit|EM8|EM8|EM8 d|0~~99999|
3032 |Bit|EM9|EM9|EM9 d|0~~99999|
3033 |Bit|EMA|EMA|EMA d|0~~99999|
3034 |Bit|EMB|EMB|EMB d|0~~99999|
3035 |Bit|EMC|EMC|EMC d|0~~99999|
3036 |Word|CIO|CIO|CIO d|0~~99999|
3037 |Word|W|W|W d|0~~99999|
3038 |Word|D|D|D d|0~~99999|
3039 |Word|H|H|H d|0~~99999|
3040 |Word|A|A|A d|0~~99999|
3041 |Word|T|T|T h|0~~99999|
3042 |Word|CIO|CF|CF d|0~~99999|
3043 |Word|C|C|C d|0~~99999|
3044 |Word|EM0|EM0|EM0 d|0~~99999|
3045 |Word|EM1|EM1|EM1 d|0~~99999|
3046 |Word|EM2|EM2|EM2 d|0~~99999|
3047 |Word|EM3|EM3|EM3 d|0~~99999|
3048 |Word|EM4|EM4|EM4 d|0~~99999|
3049 |Word|EM5|EM5|EM5 h|0~~99999|
3050 |Word|EM6|EM6|EM6 d|0~~99999|
3051 |Word|EM7|EM7|EM7 d|0~~99999|
3052 |Word|EM8|EM8|EM8 d|0~~99999|
3053 |Word|EM9|EM9|EM9 d|0~~99999|
3054 |Word|EMA|EMA|EMA d|0~~99999|
3055 |Word|EMB|EMB|EMB d|0~~99999|
3056 |Word|EMC|EMC|EMC d|0~~99999|
3057 |Word|IR|IR|IR d|0~~99999|
3058 |Word|DR|DR|DR d|0~~99999|
3059
3060 **Configure the communication protocol**
3061
3062 (% style="text-align:center" %)
3063 [[image:image-20220902153118-1.png]]
3064
3065 (% style="text-align:center" %)
3066 [[image:image-20220902151322-2.png]]
3067
3068 **Cable Wiring**
3069
3070 (% style="text-align:center" %)
3071 [[image:image-20220902153949-2.png]]
3072
3073 Pin Definition Diagram
3074
3075 (% style="text-align:center" %)
3076 [[image:image-20220902154056-3.png]]
3077
3078 == **EC55 Protocol** ==
3079
3080 Supported device: EC55 temperature instrument
3081
3082 **1)HMI Settings**
3083
3084 |**Items**|**Settings**|**Note**
3085 |Protocol|Omron EC55|
3086 |Connection|RS485 (9600, 2, 7, EVEN)|
3087 |Port No.|None|
3088 |PLC station No.|0|
3089
3090 **2)Address List**
3091
3092 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
3093 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
3094 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
3095 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
3096 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
3097 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
3098 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
3099 |CP|-|0-6|Read controller intrinsic property
3100 |CS|-|0-2|Read controller states
3101 |CA|-|0-17|Action command
3102
3103 **3)Device Settings**
3104
3105 Omron E5CC PLC configuration
3106
3107 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
3108
3109 (% style="text-align:center" %)
3110 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
3111
3112 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
3113
3114 (% style="text-align:center" %)
3115 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
3116
3117 **✎Note:** The communication settings for HMI should be consistent with this setting.
3118
3119 **Cable Wiring**
3120
3121 (% style="text-align:center" %)
3122 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3123
3124 (% style="text-align:center" %)
3125 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3126
3127 **✎Note:**
3128
3129 * COM3 only available in PI8000/PI9000 series.
3130 * CA address could not support continuous writing function;
3131 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
3132 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
3133 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
3134 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
3135 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
3136 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
3137 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
3138
3139 == **EtherNet/IP NX series Protocol** ==
3140
3141 Supported series: Omron NX/NJ series
3142
3143 **HMI Setting**
3144
3145 |**Items**|**Settings**|**Note**
3146 |Protocol|Omron NX Ethernet/IP|
3147 |Connection|Ethernet|
3148 |Port No.|44818|
3149 |PLC station No.|1|
3150
3151 **Instruction**
3152
3153 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
3154
3155 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
3156
3157 (% style="text-align:center" %)
3158 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
3159
3160 **Export labels from Sysmac Studio**
3161
3162 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
3163
3164 (% style="text-align:center" %)
3165 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
3166
3167 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
3168
3169 Click [Label manage];
3170
3171 (% style="text-align:center" %)
3172 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
3173
3174 Click [Import labels] and then select the file exported in step 1;
3175
3176 (% style="text-align:center" %)
3177 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
3178
3179 The Import Status field shows the result, click [OK] to finish importing address labels;
3180
3181 (% style="text-align:center" %)
3182 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
3183
3184 **Communication Settings**
3185
3186 Enable HMI Ethernet in [Project Settings];
3187
3188 (% style="text-align:center" %)
3189 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3190
3191 Set PLC IP in [Device IP] settings;
3192
3193 (% style="text-align:center" %)
3194 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
3195
3196 (% style="text-align:center" %)
3197 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
3198
3199 **Cable Wiring**
3200
3201 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3202
3203 == CV/CJ1M/CS1H ==
3204
3205 **HMI Setting:**
3206
3207 |=(% scope="row" %)**Parameters**|=**Recommended**
3208 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
3209 |=**PLC I/F**|RS232
3210 |=**Baud rate**|9600
3211 |=**Data bits**|7
3212 |=**Parity**|Even
3213 |=**Stop bits**|2
3214 |=**PLC sta. no.**|0
3215
3216 **PLC Setting:**
3217
3218 |=(% scope="row" %)**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
3219
3220 **Device Address:**
3221
3222 |=(% scope="row" style="width: 141px;" %)**Bit/Word**|=(% style="width: 276px;" %)**Device type**|=**Format**|=**Range**|=**Memo**
3223 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
3224 |=(% style="width: 141px;" %)B|(% style="width:276px" %)W|DDDDdd|0 ~~ 409515|Hold Relay
3225 |=(% style="width: 141px;" %)B|(% style="width:276px" %)D|DDDDdd|0 ~~ 409515|Link Relay
3226 |=(% style="width: 141px;" %)B|(% style="width:276px" %)H|DDDDdd|0 ~~ 409515|
3227 |=(% style="width: 141px;" %)B|(% style="width:276px" %)A|DDDDdd|0 ~~ 409515|
3228 |=(% style="width: 141px;" %)B|(% style="width:276px" %)TF|DDDDdd|0 ~~ 409515|
3229 |=(% style="width: 141px;" %)B|(% style="width:276px" %)CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
3230 |=(% style="width: 141px;" %)B|(% style="width:276px" %)T|DDDD|0 ~~ 4095|
3231 |=(% style="width: 141px;" %)B|(% style="width:276px" %)C|DDDD|0 ~~ 4095|
3232 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM0|DDDDDdd|0 ~~ 99999.15|
3233 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM1|DDDDDdd|0 ~~ 99999.15|
3234 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM2|DDDDDdd|0 ~~ 99999.15|
3235 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM3|DDDDDdd|0 ~~ 99999.15|
3236 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM4|DDDDDdd|0 ~~ 99999.15|
3237 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM5|DDDDDdd|0 ~~ 99999.15|
3238 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM6|DDDDDdd|0 ~~ 99999.15|
3239 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM7|DDDDDdd|0 ~~ 99999.15|
3240 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM8|DDDDDdd|0 ~~ 99999.15|
3241 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EM9|DDDDDdd|0 ~~ 99999.15|
3242 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMA|DDDDDdd|0 ~~ 99999.15|
3243 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMB|DDDDDdd|0 ~~ 99999.15|
3244 |=(% style="width: 141px;" %)B|(% style="width:276px" %)EMC|DDDDDdd|0 ~~ 99999.15|
3245 |=(% style="width: 141px;" %)B|(% style="width:276px" %)Lamp|D|0~~0|
3246
3247 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3248 |=W|LR_W|DDDD|0 ~~ 4095|
3249 |=W|TC|DDD|0 ~~ 511|
3250 |=W|DM|DDDD|0 ~~ 9999|Data Register
3251
3252 **Wiring Diagram:**
3253
3254 **RS-232**
3255
3256 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
3257
3258 Communication Module:
3259
3260 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
3261
3262 The serial port pin assignments may vary between HMI models, please click the following link for more information.
3263
3264 (% style="text-align:center" %)
3265 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
3266
3267 = Create communication with Xinje** PLC** =
3268
3269 == XC serial protocol ==
3270
3271 **HMI Settings**
3272
3273 |**Item**|**Settings**|**Note**
3274 |Protocol|XINJE XC MODBUS|
3275 |Connection|RS232|
3276 |Baud rate|19200|
3277 |Data bit|8|
3278 |Parity|EVEN|
3279 |Stop bit|1|
3280 |PLC station No.|1|
3281
3282 **Address List**
3283
3284 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3285 |Bit|M|M|M d|0~~8511|
3286 |Bit|X|X|X o|0~~1747|
3287 |Bit|Y|Y|Y o|0~~1747|
3288 |Bit|S|S|S d|0~~1023|
3289 |Bit|T|T|T d|0~~4095|
3290 |Bit|C|C|C d|0~~634|
3291 |Word|D|D|D d|0~~8511|
3292 |Word|TD|TD|TD d|0~~618|
3293 |Word|CD|CD|CD d|0~~634|
3294 |Word|FD|FD|FD d|0~~8511|
3295
3296 **Configure the communication protocol**
3297
3298 (% style="text-align:center" %)
3299 [[image:image-20220830154105-1.png]]
3300
3301 (% style="text-align:center" %)
3302 [[image:image-20220830154159-3.png]]
3303
3304 **Cable Wiring**
3305
3306 Figure
3307
3308 [[image:image-20220830155728-4.png]]
3309
3310 Pin Definition Diagram
3311
3312 (% style="text-align:center" %)
3313 [[image:image-20220830154131-2.png]]
3314
3315 == XD serial protocol ==
3316
3317 **HMI Settings**
3318
3319 Supported Series: Xinjie XD/XE Series PLC
3320
3321 |=**Item**|=**Settings**|=**Note**
3322 |Protocol|XINJE XD/XC MODBUS|
3323 |Connection|RS232|
3324 |Baud rate|19200|
3325 |Data bit|8|
3326 |Parity|EVEN|
3327 |Stop bit|1|
3328 |PLC station No.|1|
3329
3330 **Address List**
3331
3332 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3333 |Bit|M|M|M d|0~~74999|
3334 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3335 |Bit|X2xx|X2xx|X2xx o|0~~277|
3336 |Bit|X|X|X o|0~~77|
3337 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3338 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3339 |Bit|Y|Y|Y o|0~~4095|
3340 |Bit|SM|SM|SM d|0~~4999|(((
3341
3342 )))
3343 |Bit|T|T|T d|0~~4999|
3344 |Bit|C|C|C d|0~~4999|
3345 |Bit|ET|ET|ET d|0~~31|
3346 |Bit|SE|SE|SE d|0~~31|
3347 |Bit|HM|HM|HM d|0~~11999|
3348 |Bit|HSC|HSC|HSC d|0~~39|
3349 |Bit|HS|HS|HS d|0~~999|
3350 |Bit|HT|HT|HT d|0~~1999|
3351 |Bit|HC|HC|HC d|0~~1999|
3352 |Bit|S|S|S d|0~~7999|
3353 |Word|D|D|D d|0~~69999|
3354 |Word|ID|ID|ID d|0~~99|
3355 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3356 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3357 |Word|QD|QD|QD d|0~~99|
3358 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3359 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3360 |Word|SD|SD|SD d|0~~4999|
3361 |Word|TD|TD|TD d|0~~575|
3362 |Word|CD|CD|CD d|0~~575|
3363 |Word|ETD|ETD|ETD d|0~~31|
3364 |Word|HD|HD|HD d|0~~24999|
3365 |Word|HSD|HSD|HSD d|0~~1023|
3366 |Word|HTD|HTD|HTD d|0~~95|
3367 |Word|HCD|HCD|HCD d|0~~95|
3368 |Word|HSCD|HSCD|HSCD d|0~~31|
3369 |Word|FD|FD|FD d|0~~8191|
3370 |Word|SFD|SFD|SFD d|0~~5999|
3371 |Word|FS|FS|FS d|0~~47|
3372
3373 **Configure the communication protocol**
3374
3375 (% style="text-align:center" %)
3376 [[image:image-20220830160042-1.png]]
3377
3378 (% style="text-align:center" %)
3379 [[image:image-20220830160129-2.png]]
3380
3381 **Cable Wiring**
3382
3383 (% style="text-align:center" %)
3384 [[image:image-20220905093902-1.png]]
3385
3386 Pin Definition Diagram
3387
3388 (% style="text-align:center" %)
3389 [[image:image-20220830160232-3.png]]
3390
3391 = Create communication with Panasonic** PLC** =
3392
3393 == **FP serial protocol** ==
3394
3395 **1)HMI Settings**
3396
3397 |**Item**|**Settings**|**Note**
3398 |Protocol|Panasonic FP MFWTOCOL|
3399 |Connection|RS232|
3400 |Baud rate|9600|
3401 |Data bit|8|
3402 |Parity|ODD|
3403 |Stop bit|1|
3404 |PLC station No.|1|
3405
3406 **2)Address List**
3407
3408 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3409 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3410 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3411 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3412 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3413 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3414 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3415 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3416 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3417 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3418 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3419 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3420 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3421 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3422 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3423 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3424
3425 **3)Configure the communication protocol**
3426
3427 [[image:image-20220830171050-1.png]]
3428
3429 [[image:image-20220830171126-2.png]]
3430
3431 **4)Cable Wiring**
3432
3433 Figure
3434
3435 [[image:image-20220830171328-4.png]]
3436
3437 Pin Definition Diagram
3438
3439 [[image:image-20220830171146-3.png]]
3440
3441 = Create communication with **SHIMADEN PLC** =
3442
3443 == **FP23 series protocol** ==
3444
3445 Supported series: SHIMADEN FP23 series
3446
3447 **HMI Setting**
3448
3449 |**Items**|**Settings**|**Note**
3450 |Protocol|SHIMADEN FP23 series|
3451 |Connection|RS485 (9600, 1, 7, EVEN)|
3452 |Port No.|None|
3453 |PLC station No.|0|
3454
3455 **Address List**
3456
3457 |**Device address**|**HMI register**|**Address range**|**Type**
3458 |0040-0043(HEX)|FP040|100064-200067|Read only
3459 |0100-010B(HEX)|FP100|100256-200267|Read only
3460 |0110-0142(HEX)|FP110|100272-200322|Read only
3461 |0182-0252(HEX)|FP182|100386-200594|Write only
3462 |0280-0281(HEX)|FP280|100640-200641|Read only
3463 |0300-030B(HEX)|FP300|100768-200779|Read and write
3464 |0380-039F(HEX)|FP380|100896-200927|Read and write
3465 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3466 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3467 |0600-0670(HEX)|FP600|101536-201814|Read and write
3468 |0720-0738(HEX)|FP720|101824-201848|Read and write
3469 |0800-083F(HEX)|FP800|102048-202111|Read and write
3470 |0900-0952(HEX)|FP900|102304-202386|Read and write
3471 | |Ctrl|0-2|
3472
3473 **✎Note:**
3474
3475 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3476 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3477 * The Ctrl register is used to store the control group number and BCC check mode.
3478
3479 **Ctrl Register Description**
3480
3481 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3482 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3483 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3484 * Ctrl3 reserved
3485
3486 **✎Note:**
3487
3488 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3489
3490 **Cable Wiring**
3491
3492 (% style="text-align:center" %)
3493 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3494
3495 (% style="text-align:center" %)
3496 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3497
3498 **✎Note:** COM3 only available in PI8000/PI9000 series.
3499
3500 == **SR90 protocol** ==
3501
3502 Supported series: SHIMADEN SR90 series
3503
3504 **HMI Setting**
3505
3506 |**Items**|**Settings**|**Note**
3507 |Protocol|SHIMADEN SR90 protocol|
3508 |Connection|RS485 (1200, 1, 7, EVEN)|
3509 |Port No.|None|
3510 |PLC station No.|0|
3511
3512 **Address List**
3513
3514 |**Device address**|**HMI register**|**Address range**|**Type**
3515 |0040-0043 (HEX)|SR040|100064-100067|Read only
3516 |0100-010A(HEX)|SR0100|100256-100266|Read only
3517 |0182-018C(HEX)|SR0182|100386-100396|Write only
3518 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3519 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3520 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3521 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3522 | |Ctrl|0-2|~-~-
3523
3524 **✎Note:**
3525
3526 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3527 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3528 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3529
3530 **Ctrl Register Description**
3531
3532 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3533 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3534 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3535 * Ctrl3 reserved
3536
3537 **✎Note:**
3538
3539 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3540
3541 **Cable Wiring**
3542
3543 (% style="text-align:center" %)
3544 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3545
3546 (% style="text-align:center" %)
3547 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3548
3549 **✎Note:** COM3 only available in PI8000/PI9000 series.
3550
3551 == **MR13 series(standard protocol)** ==
3552
3553 Supported series: SHIMADEN MR13 series
3554
3555 **HMI Setting**
3556
3557 |**Items**|**Settings**|**Note**
3558 |Protocol|SHIMADEN standard protocol|
3559 |Connection|RS485 (1200, 1, 7, EVEN)|
3560 |Port No.|None|
3561 |PLC station No.|0|
3562
3563 **Address List**
3564
3565 |**Device address**|**HMI register**|**Address range**|**Type**
3566 |0100-010B(HEX)|MR100|100256-300267|Read only
3567 |0111-0126(HEX)|MR111|100273-300294|Read only
3568 |0184-0192(HEX)|MR184|100388-300402|Write only
3569 |0280-0282(HEX)|MR280|100640-300642|Read only
3570 |0300-030B(HEX)|MR300|100768-300779|Read/write
3571 |0314-0317(HEX)|MR314|100788-300791|Read/write
3572 |031A(HEX)|MR31A|100794-300794|Read/write
3573 |0320-0321(HEX)|MR320|100800-300801|Read/write
3574 |0400-0504(HEX)|MR400|101024-301284|Read/write
3575 |0506(HEX)|MR506|101286-301286|Read/write
3576 |0510-0514(HEX)|MR510|101296-301300|Read/write
3577 |0516-0524(HEX)|MR516|101302-301316|Read/write
3578 |0526(HEX)|MR526|101318-301318|Read/write
3579 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3580 |~-~-|Ctrl|0-2|~-~-
3581
3582 **✎Note:**
3583
3584 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3585 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3586 * The Ctrl register is used to store the control group number and BCC check mode.
3587
3588 **Ctrl Register Description**
3589
3590 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3591 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3592 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3593 * Ctrl3 reserved
3594
3595 **✎Note:**
3596
3597 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3598
3599 **Cable Wiring**
3600
3601 (% style="text-align:center" %)
3602 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3603
3604 (% style="text-align:center" %)
3605 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3606
3607 **✎Note:** COM3 only available in PI8000/PI9000 series.
3608
3609 = Create communication with **MODBUS** =
3610
3611 == **MODBUS RTU Master** ==
3612
3613 Supported Series: MODBUS RTU CONTROLLER
3614
3615 HMI works as MODBUS SLAVE connecting with MASTER
3616
3617 (% style="text-align:center" %)
3618 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3619
3620
3621 (% style="text-align:center" %)
3622 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3623
3624
3625 (% style="text-align:center" %)
3626 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3627
3628 **HMI Settings**
3629
3630 (% class="table-bordered" %)
3631 |**Items**|**Settings**|**Note**
3632 |Protocol|MODBUS RTU Master|
3633 |Connection|RS485/RS232|
3634 |Baud rate|2400~~187500|
3635 |Data bit|8|
3636 |Parity|Even/ Odd/ None|
3637 |Stop bit|1/2|
3638 |Station No.|0~~255|
3639
3640 **Address List**
3641
3642 (% class="table-bordered" %)
3643 |**Type**|**HMI address**|**MODBUS code**|**Range**
3644 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
3645 |Word|HDW3500~~HDW7999|4|0~~4499
3646
3647 **Cable Wiring**
3648
3649 * **RS485**
3650
3651 (% style="text-align:center" %)
3652 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3653
3654 (% style="text-align:center" %)
3655 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3656
3657 * **RS232**
3658
3659 (% style="text-align:center" %)
3660 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3661
3662 **✎Note:** COM3 only available in PI8000/PI9000 series.
3663
3664 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
3665
3666 Supported Series: MODBUS RTU CONTROLLER
3667
3668 HMI works as MODBUS MASTER connecting with SLAVE.
3669
3670 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
3671
3672 (% style="text-align:center" %)
3673 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3674
3675
3676 (% style="text-align:center" %)
3677 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3678
3679
3680 (% style="text-align:center" %)
3681 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
3682
3683 **HMI Settings**
3684
3685 (% class="table-bordered" %)
3686 |**Items**|**Settings**|**Note**
3687 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
3688 |Connection|RS485/RS232|
3689 |Baud rate|2400~~187500|
3690 |Data bit|8|
3691 |Parity|Even/ Odd/ None|
3692 |Stop bit|1/2|
3693 |PLC station No.|0~~255|
3694
3695 **Address List**
3696
3697 (% class="table-bordered" %)
3698 |**Type**|**Address Type**|**Function code & Description**
3699 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3700 |06 (write single register: write a binary value to a holding register)
3701 |10 (write values to multiple addresses )
3702 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3703 |06 (write single register: write a binary value to a holding register)
3704 |10 (write values to multiple addresses )
3705 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3706 |06 (write single register: write a binary value to a holding register)
3707 |10 (write values to multiple addresses )
3708 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3709 |10 (write values to multiple addresses )
3710 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3711 |05 (Force a single coil to force the on/off state of a logic coil)
3712 |0F (Write multiple bits, ie write continuously)
3713 |(% rowspan="3" %)1|02 (Read the input state)
3714 |05 (Force a single coil to force the on/off state of a logic coil)
3715 |0F (Write multiple bits)
3716 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3717 |05 (Force a single coil to force the on/off state of a logic coil)
3718 |0F (Write multiple bits)
3719 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3720 |0F (Write multiple bits)
3721
3722 **✎Note:**
3723
3724 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
3725 * The function codes sent out are the same as those that read and write words.
3726
3727 **Station number for more than one slaves**
3728
3729 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
3730
3731 (% style="text-align:center" %)
3732 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
3733
3734 **Cable Wiring**
3735
3736 * **RS485**
3737
3738 (% style="text-align:center" %)
3739 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3740
3741 (% style="text-align:center" %)
3742 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
3743
3744 * **RS232**
3745
3746 (% style="text-align:center" %)
3747 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
3748
3749 **✎Note:** COM3 only available in PI8000/PI9000 series.
3750
3751 == **Communicate with Modbus Meter** ==
3752
3753 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
3754
3755 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
3756
3757 (% style="text-align:center" %)
3758 [[image:LinfeeDiagram.png]]
3759
3760 (% class="wikigeneratedid" %)
3761 2. Check the specific Modbus parameter in the communication menu from LED display.
3762
3763 (% class="wikigeneratedid" %)
3764 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
3765
3766 {{info}}
3767 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
3768 {{/info}}
3769
3770 (% style="text-align:center" %)
3771 [[image:MeterModbusAllView.png]]
3772
3773 3. Create new project and change the Communication settings.
3774
3775 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
3776
3777 (% style="text-align:center" %)
3778 [[image:PIStudioSetupMeterModbusPara.png]]
3779
3780 (% class="wikigeneratedid" %)
3781 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
3782
3783 (% class="wikigeneratedid" %)
3784 The following table is intercept part of the manual for Linfee Modbus manual.
3785
3786 (% class="wikigeneratedid" %)
3787 **0x03/0x04 command data register address**:
3788
3789 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
3790 | HEX|DEC| | | |
3791 |0x00|0|Reserved| | |
3792 |0x02|2|Reserved| | |
3793 |0x04|4|Reserved| | |
3794 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
3795 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
3796 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
3797 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
3798 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
3799 |0x10|16|Uca|float|2|Line Voltage data, Unit V
3800 |0x12|18|Ia|float|2|Phase Current data, Unit A
3801 |0x14|20|Ib|float|2|Phase Current data, Unit A
3802 |0x16|22|Ic|float|2|Phase Current data, Unit A
3803
3804 {{info}}
3805 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
3806 {{/info}}
3807
3808 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
3809
3810 (% style="text-align:center" %)
3811 [[image:MeterModbusPInumericSet.png]]
3812
3813 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
3814
3815 (% style="text-align:center" %)
3816 [[image:MeterModbusNumericInputFormat.png]]
3817
3818 (% class="wikigeneratedid" %)
3819 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
3820
3821 (% style="text-align:center" %)
3822 [[image:ActualHMIModbusResult.jpg]]
3823
3824 == **MODBUS TCP Slave (All function)** ==
3825
3826 Supported series: MODBUS TCP controller
3827
3828 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
3829
3830 (% style="text-align:center" %)
3831 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
3832
3833 (% style="text-align:center" %)
3834 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
3835
3836
3837 (% style="text-align:center" %)
3838 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
3839
3840 **HMI Setting**
3841
3842 (% class="table-bordered" %)
3843 |**Items**|**Settings**|**Note**
3844 |Protocol|MODBUS TCP Slave (All function)|
3845 |Connection|Ethernet|
3846 |Port No.|502|
3847 |PLC station No.|1|
3848
3849 **Address List**
3850
3851 (% class="table-bordered" %)
3852 |**Type**|**Register**|**Function code & Description**
3853 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
3854 |06 (write single register: write a binary value to a holding register)
3855 |10 (write values to multiple addresses )
3856 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
3857 |06 (write single register: write a binary value to a holding register)
3858 |10 (write values to multiple addresses )
3859 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
3860 |06 (write single register: write a binary value to a holding register)
3861 |10 (write values to multiple addresses )
3862 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
3863 |10 (write values to multiple addresses )
3864 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
3865 |05 (Force a single coil to force the on/off state of a logic coil)
3866 |0F (Write multiple bits, ie write continuously)
3867 |(% rowspan="3" %)1|02 (Read the input state)
3868 |05 (Force a single coil to force the on/off state of a logic coil)
3869 |0F (Write multiple bits)
3870 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
3871 |05 (Force a single coil to force the on/off state of a logic coil)
3872 |0F (Write multiple bits)
3873 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
3874 |0F (Write multiple bits)
3875
3876 **Communication Settings**
3877
3878 Enable HMI Ethernet in [Project Settings];
3879
3880 (% style="text-align:center" %)
3881 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3882
3883 Set PLC IP in [Device IP] settings;
3884
3885 (% style="text-align:center" %)
3886 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3887
3888 **Cable Wiring**
3889
3890 (% style="text-align:center" %)
3891 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3892
3893 = **Printer** =
3894
3895 == **TSPL label printer** ==
3896
3897 **Introduction**
3898
3899 TSPL label printer protocol supports following models.
3900
3901 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3902 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3903
3904 **Setting Step**
3905
3906 Select the protocol
3907
3908 * Create a new project, select the TSPL label printer protocol as shown below.
3909
3910 (% style="text-align:center" %)
3911 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3912
3913 Set parameters
3914
3915 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3916
3917 Printer register
3918
3919 (% class="table-bordered" %)
3920 |**Register**|**System**|**Range**|**Function**
3921 |TSPL_SP|decimal|0 - 1|Set the paper size
3922 |TSPL_PT|decimal|0 - 1999|Print text
3923 |TSPL_PQ|decimal|0 - 999|Print QR code
3924 |TSPL_PB|decimal|0 - 999|Print barcode
3925 |TSPL_PR|decimal|0 - 1|Print offset
3926 |TSPL_PN|decimal|0 - 0|Trigger printing
3927 |TSPL_PS|decimal|0 - 0|Print status
3928
3929 * Set paper size:
3930 ** TSPL_SP0: width of paper, unit: mm.
3931 ** TSPL_SP1: height of paper, unit: mm.
3932 * Print text:
3933 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3934 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3935
3936 (% class="table-bordered" %)
3937 |**Register**|**Function**|**Description**
3938 |TSPL_PT0|X coordinate|Unit: dot
3939 |TSPL_PT1|Ycoordinate|Unit: dot
3940 |TSPL_PT2|Rotation angle|(((
3941 0: 0 degrees
3942
3943 1: 90 degrees
3944
3945 2: 180 degrees
3946
3947 3: 270 degrees
3948 )))
3949 |TSPL_PT3|Size|Range: 0-3
3950 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3951
3952 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3953
3954 Print QR code:
3955
3956 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3957 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3958
3959 (% class="table-bordered" %)
3960 |**Register**|**Function**|**Description**
3961 |TSPL_PQ0|X coordinate|Unit: dot
3962 |TSPL_PQ1|Ycoordinate|Unit: dot
3963 |TSPL_PQ2|Rotation angle|(((
3964 0: 0 degrees
3965
3966 1: 90 degrees
3967
3968 2: 180 degrees
3969
3970 3: 270 degrees
3971 )))
3972 |TSPL_PQ3|Size|Range: 0-5
3973 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3974
3975 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3976
3977 Print bar code:
3978
3979 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3980 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3981
3982 (% class="table-bordered" %)
3983 |**Register**|**Function**|**Description**
3984 |TSPL_PB0|X coordinate|Unit: dot
3985 |TSPL_PB1|Ycoordinate|Unit: dot
3986 |TSPL_PB2|Rotation angle|(((
3987 0: 0 degrees
3988
3989 1: 90 degrees
3990
3991 2: 180 degrees
3992
3993 3: 270 degrees
3994 )))
3995 |TSPL_PB3|height|Unit: dot
3996 |TSPL_PB4|width|Range:0-2
3997 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3998
3999 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
4000
4001 Print offset:
4002
4003 * TSPL_PR0: X coordinate offset, unit: mm;
4004 * TSPL_PR1: Y coordinate offset, unit: mm.
4005
4006 Trigger printing:
4007
4008 * TSPL_PN0 = 1: trigger the printer to start printing.
4009
4010 Printing status:
4011
4012 * TSPL_PS0 = 1: The printing is normal.
4013 * TSPL_PS0 = 1: The printing is abnormal.
4014
4015 Print picture
4016
4017 * For the function of printing pictures, please refer to the configuration of [Printer object].
4018
4019 Conversion between dot and mm
4020
4021 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
4022
4023 == **EpsonTM series** ==
4024
4025 **HMI Settings**
4026
4027 (% class="table-bordered" %)
4028 |**Item**|**Settings**|**Note**
4029 |Protocol|EPSON-TM-T82II/TM-XXX|
4030 |Connection|RS232|
4031 |Baud rate|9600~~115200|
4032 |Data bit|8|
4033 |Parity|None|
4034 |Stop bit|1|
4035 |PLC station No.|1|
4036
4037 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
4038
4039 **Printer Settings**
4040
4041 (% class="table-bordered" %)
4042 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
4043 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
4044 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
4045 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
4046 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
4047 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
4048 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
4049
4050 **Cable Wiring**
4051
4052 (% style="text-align:center" %)
4053 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4054
4055 (% style="text-align:center" %)
4056 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4057
4058 **✎Note:** COM3 only available in PI8000/PI9000 series.
4059
4060
4061 = Create communication with **Schneider PLC** =
4062
4063 == **Schneider MODBUS RTU** ==
4064
4065 **HMI Setting**
4066
4067 |=**Parameters**|=**Recommended**|=**Notes**
4068 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
4069 |Connection|RS485|
4070 |**Baud rate**|19200|
4071 |**Data bit**|8|
4072 |**Parity**|Even|
4073 |**Stop bit**|1|
4074 |**PLC station No.**|1|
4075
4076 **PLC Setting**
4077
4078 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
4079
4080 **Device Address**
4081
4082 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
4083 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
4084 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
4085 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
4086 |W|MW|DDDDDD|0 ~~ 999999|Output register
4087 |DW|MD|DDDDDD|0 ~~ 999999|Output register
4088
4089 **Wiring Diagram**
4090
4091 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
4092
4093 (% style="text-align:center" %)
4094 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
4095
4096 = **Barcode Scanner** =
4097
4098 Supported: DELI 14880 barcode scanner
4099
4100 **HMI Setting**
4101
4102 |**Items**|**Settings**|**Note**
4103 |Protocol|Barcode Scanner|
4104 |Connection|USB|
4105
4106 **Operating Procedures**
4107
4108 Select [Barcode Scanner];
4109
4110 (% style="text-align:center" %)
4111 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
4112
4113 Set address for receiving;
4114
4115 Set correct length;
4116
4117 (% style="text-align:center" %)
4118 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
4119
4120 **✎Note:**
4121
4122 * The protocol uploads the information acquired by the USB scanner to the HMI;
4123 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4124 * Recommended model: DELI 14880 barcode scanner;
4125
4126 = **Hitachi EHV Series (Ethernet)** =
4127
4128 Supported series: Hitachi EHV series
4129
4130 **HMI Settings**
4131
4132 (% class="table-bordered" %)
4133 |**Items**|**Settings**|**Note**
4134 |Protocol|Hitachi EHV series|
4135 |Connection|Ethernet|
4136 |Port No.|3004~~3007|
4137
4138 **Address List**
4139
4140 (% class="table-bordered" %)
4141 |**Type**|**Register**|**Range**|**Format**|**Note**
4142 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4143 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4144 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4145 H1H2H3H4 Module main number
4146
4147 H1: Remote number
4148
4149 H2: Unit number
4150
4151 H3: Slot number
4152
4153 H4: Word number of Module
4154
4155 H Sub number of Module
4156
4157 For example:X21.3
4158
4159 Slot number 2
4160
4161 Word number of module is 1
4162
4163 Bit number of module is 3
4164
4165 Remote number and unit number are 0
4166 )))
4167 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4168 |R|0 – FF.f (Hex)|R HH.h|
4169 |L|0 - 73FF.f (Hex)|L HHHH.h|
4170 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4171 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4172 H1H2H3H4 Module main number
4173
4174 H1: Remote number
4175
4176 H2: Unit number
4177
4178 H3: Slot number
4179
4180 H4: Word number of module
4181
4182 For example:WX21
4183
4184 Word number of module is 1
4185
4186 Slot number is 2
4187
4188 Remote number and unit number are 0
4189 )))
4190 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4191 |WR|0 – FFFF (Hex)|WR HHHH|
4192 |WL|0 - 73FF (Hex)|WL HHHH|
4193 |TC|0 - 2559|TC DDDD|
4194
4195 **Communication settings in HMI**
4196
4197 Enable HMI Ethernet in [Project Settings];
4198
4199 (% style="text-align:center" %)
4200 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4201
4202 Set PLC IP in [Device IP] settings;
4203
4204 (% style="text-align:center" %)
4205 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4206
4207 **PLC Configuration**
4208
4209 Connect with PLC, select[Online mode];
4210
4211 (% style="text-align:center" %)
4212 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4213
4214 Set IP address, it is the same LAN parameters with HMI;
4215
4216 (% style="text-align:center" %)
4217 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4218
4219 3) Save PLC communication parameter, and restart PLC
4220
4221 **PLC Monitor Mode**
4222
4223 Connect with PLC and choose to “online” mode
4224
4225 (% style="text-align:center" %)
4226 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4227
4228 Open I/O monitor sheet1
4229
4230 (% style="text-align:center" %)
4231 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4232
4233 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4234
4235 (% style="text-align:center" %)
4236 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4237
4238 Enter the register address, click OK to view the value of the register.
4239
4240 (% style="text-align:center" %)
4241 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4242
4243 (% style="text-align:center" %)
4244 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4245
4246 **✎Note:**
4247
4248 * Both word registers and bit registers support even continuous read/write functions;
4249 * The range of registers is based on the specific PLC type;
4250
4251 **Cable Wiring**
4252
4253 (% style="text-align:center" %)
4254 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4255
4256 = **IEC60870-5 104 Client** =
4257
4258 **HMI Setting**
4259
4260 (% class="table-bordered" %)
4261 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4262 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4263 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4264 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4265
4266 **Address List**
4267
4268 (% class="table-bordered" %)
4269 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4270 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4271 |(% style="width:461px" %)SCNA|0~~16777215.7
4272 |(% style="width:461px" %)DPTB|0~~16777215.7
4273 |(% style="width:461px" %)DCNA|0~~16777215.7
4274 |(% style="width:461px" %)METF|0~~16777215.7
4275 |(% style="width:461px" %)SENC|0~~16777215.7
4276 |(% style="width:461px" %)SENA|0~~16777215.7
4277 |(% style="width:461px" %)MENA|0~~16777215.7
4278 |(% style="width:461px" %)METD|0~~16777215.7
4279 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4280 |(% style="width:461px" %)SCNA|0~~16777215
4281 |(% style="width:461px" %)DPTB|0~~16777215
4282 |(% style="width:461px" %)DCNA|0~~16777215
4283 |(% style="width:461px" %)SENA|0~~16777215
4284 |(% style="width:461px" %)MENA|0~~16777215
4285 |(% style="width:461px" %)METD|0~~16777215
4286 |(% style="width:461px" %)INRO|0~~16777215
4287 |(% style="width:461px" %)TIMESYN|0~~16777215
4288 |(% style="width:461px" %)TIMEZ|0~~16777215
4289 |(% style="width:461px" %)NTP|0~~16777215
4290 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4291 |(% style="width:461px" %)SENC|0~~16777215
4292
4293 **Address Configuration**
4294
4295 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4296
4297 (% style="text-align:center" %)
4298 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4299
4300 (% style="text-align:center" %)
4301 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4302
4303 Extended tag name
4304
4305 Address range for the extended tag.
4306
4307 **Communication Settings**
4308
4309 Enable HMI Ethernet in [Project Settings];
4310
4311 (% style="text-align:center" %)
4312 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4313
4314 Set PLC IP in [Device IP] settings;
4315
4316 (% style="text-align:center" %)
4317 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4318
4319 **Cable Wiring**
4320
4321 (% style="text-align:center" %)
4322 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4323
4324 = **OpenCAN** =
4325
4326 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4327
4328 This protocol is only available in PI8000 series HMI.
4329
4330 **HMI Settings**
4331
4332 |**Items**|**Settings**|**Note**
4333 |Protocol|OPENCAN|
4334 |Connection|CAN port|
4335 |Baud rate|250000|
4336
4337 **CAN frame setting in HMI**
4338
4339 Click [OpenCAN setting] button in communication setting window;
4340
4341 (% style="text-align:center" %)
4342 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4343
4344 Click [Add] to create a new frame;
4345
4346 (% style="text-align:center" %)
4347 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4348
4349 |**No**|**Items**|**Description**
4350 |1|Add|add a frame related to register address
4351 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4352 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4353 |4|Modify|Modify the frames in frame management
4354 |5|Copy|Copy one frame to another
4355 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4356 |7|Empty|All frames in the list are cleared
4357 |8|Browse|Displays configuration files in XML format in IE
4358 |9|OK|Complete the configuration of the frame and exit
4359
4360 Set CANBUS frame in setting windows
4361
4362 (% style="text-align:center" %)
4363 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4364
4365 |**No**|**Items**|**Description**
4366 |1|ID|Set the ID of a can frame in hexadecimal format;
4367 |2|ID assign|split the ID by PF, PS, and SA;
4368 |3|Frame type|Select Standard frame or Extended Frame;
4369 |4|Frame format|Select between data frame and remote Frame;
4370 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4371 |6|Use address|(((
4372 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4373
4374 **Edit:** Set a bit or word address by its format;
4375
4376 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4377 )))
4378 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4379 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4380 |Feedback mode: feedback mode includes no response, confirm response and data response;
4381 |No response: the device or touch screen will not receive feedback;
4382 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4383 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4384 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4385 |Response timeout: sets whether the response frame timeout;
4386 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4387 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4388 |Manually send: a manually send tick indicates only one send;
4389 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4390 |10|Note|Fill the text to explain the meaning of the frame;
4391 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4392 |12|Current operation display|Display the description of current operation;
4393 |13|Add|Add a new frame;
4394 |14|Save frame|Save the configured frame format;
4395 |15|Cancel|Cancel the frame configuration;
4396
4397 Set CAN address (Read or write operation);
4398
4399 (% style="text-align:center" %)
4400 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4401
4402 |**No.**|**Item**|**Description**
4403 |1|Current address|Displays the register type and register address set by the user in the data access interface
4404 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4405 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4406 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4407 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4408 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4409 |If the trigger condition is a writing operation, there are two situations:(((
4410 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4411 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4412 )))
4413 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4414 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4415 |4|Add|Add current configuration
4416 |5|Close|Close the configuration window to exit
4417
4418 **Multiple Packages Settings**
4419
4420 (% style="text-align:center" %)
4421 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4422
4423 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4424
4425 Select Multiple package type
4426
4427 * Not Multiple packages
4428 * J1939 Multiple packages
4429 * Customized Multiple packages
4430
4431 Click [Edit Receive data] for [Receive] settings
4432
4433 * Start code+ Total length (J1939)
4434
4435 (% style="text-align:center" %)
4436 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4437
4438 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4439
4440 * Start code + Data max length (J1939)
4441
4442 (% style="text-align:center" %)
4443 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4444
4445 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4446
4447 * Data max length (J1939)
4448
4449 (% style="text-align:center" %)
4450 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4451
4452 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4453
4454 * Customized multiple package
4455
4456 (% style="text-align:center" %)
4457 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4458
4459 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4460
4461 Click [Edit Send data] for [Send] setting
4462
4463 * J1939
4464
4465 (% style="text-align:center" %)
4466 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4467
4468 [Data] is all data to be sent.
4469
4470 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4471
4472 * Customized multiple package
4473
4474 (% style="text-align:center" %)
4475 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4476
4477 [Data] is all data to be sent.
4478
4479 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4480
4481 **Cable Wiring**
4482
4483 (% style="text-align:center" %)
4484 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4485
4486 **✎Note:** The address interval between each frame need to be more than a word address;
4487
4488
4489 = **User Defined Protocol** =
4490
4491 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4492
4493 **HMI Settings**
4494
4495 |**Items**|**Settings**|**Note**
4496 |Protocol|User defined protocol|
4497 |Connection|RS485/RS232|
4498 |Baud rate|2400~~187500|
4499 |Stop bits|1/ 2|
4500 |Data bits|7/ 8|
4501 |Parity|None/ Even/ ODD|
4502
4503 **Operating Procedures**
4504
4505 Select [User defined protocol];
4506
4507 Click [User defined protocol] button to open setting window as below;
4508
4509 (% style="text-align:center" %)
4510 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4511
4512 Configure user defined command;
4513
4514 (% style="text-align:center" %)
4515 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4516
4517 |**No**|**Item**|**Description**
4518 |1|Instruction edit|The required command.
4519 |2|Mode|Write to address or read from the address.
4520 |3|Format|Encode format: HEX or ASCII.
4521 |4|Other|(((
4522 **No receiving: **HMI does not respond to the receiving command.
4523
4524 **Send after receiving:** HMI responds to the receiving command.
4525 )))
4526 |5|Manually send|(((
4527 Respond once after trigger the address.
4528
4529 Address: set the trigger address.
4530 )))
4531 |6|Add|Save this setting.
4532 |7|Cancel|Cancel current settings.
4533 |(% rowspan="4" %)8|Add|Add a new command.
4534 |Edit|Edit the selected command.
4535 |Delete|Delete the selected command.
4536 |Clear|Clear all the commands.
4537 |9|Instruction list|Display all current commands.
4538 |10|Address List|Display all the addresses added.
4539 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4540 |Export|Export current command settings to local storage.
4541 |Browse|Browse local command files.
4542 |Advanced|Combine two commands.
4543 |Exit|Complete editing and exit setting.
4544
4545 **Operating Procedures**
4546
4547 Click [Add] to create a new command, as below shows;
4548
4549 (% style="text-align:center" %)
4550 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4551
4552 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4553
4554 (% style="text-align:center" %)
4555 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4556
4557 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4558
4559 (% style="text-align:center" %)
4560 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4561
4562 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4563
4564 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4565
4566 Check settings;
4567
4568 (% style="text-align:center" %)
4569 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4570
4571 |**No**|**Items**|**Description**
4572 |1|Add checking|Add checking command when receiving the data.
4573 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4574 |Differ with send check|Set return checking.
4575 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4576 |Length: The data length need to be checked.
4577
4578 Object settings;
4579
4580 (% style="text-align:center" %)
4581 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4582
4583 |**No**|**Items**|**Description**
4584 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4585 |Address: the triggering address;
4586 |Note: description to object;
4587 |2|Byte order|The numerical display order;
4588
4589 Data length settings;
4590
4591 (% style="text-align:center" %)
4592 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4593
4594 |**No**|**Item**|**Description**
4595 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4596 |Length: the return data length.
4597 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4598 |Length: the write data length.
4599
4600 Instruction length settings
4601
4602 (% style="text-align:center" %)
4603 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4604
4605 |**No**|**Item**|**Description**
4606 |1|Send length|The instruction data will only send designated data length.
4607 |2|Return length|The responds data length.
4608 |3|End code|Instruction will not be terminated until receiving [End code];
4609
4610 **Cable Wiring**
4611
4612 * **RS485**
4613
4614 (% style="text-align:center" %)
4615 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4616
4617 (% style="text-align:center" %)
4618 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4619
4620 * **RS232**
4621
4622 (% style="text-align:center" %)
4623 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4624
4625 **✎Note:** COM3 only available in PI8000/PI9000 series.