Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 257.2 by Hunter on 2023/05/19 17:37

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with HollySys PLC** =
910
911 == **LK MODBUS RTU** ==
912
913 **HMI Settings**
914
915 |=Item|=Recommended|=Note
916 |=Protocol|HollySys LK MODBUS RTU|
917 |=Connection|RS485|
918 |=Baud rate|38400|
919 |=Stop bits|1|
920 |=Data bits|8|
921 |=Parity|NONE|
922 |=PLC Station No.|1|
923 |=HMI Station No.|0|
924
925
926
927 = **Create communication with Inovance PLC** =
928
929 == **H1U/H2U serial protocol** ==
930
931 **HMI Settings**
932
933 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
934 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
935 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
936 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
937 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
938 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
939 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
940 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
941 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
942
943 (% class="wikigeneratedid" %)
944 **Address List**
945
946 (% style="width:1014px" %)
947 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
948 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
949 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
950 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
951 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
952 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
953 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
954 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
955 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
956 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
957 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
958 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
959 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
960 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
961 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
962 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
963 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
964 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
965
966 (% class="wikigeneratedid" %)
967 **Cable Wiring**
968
969 (% style="text-align:center" %)
970 [[image:Inovance.png]]
971
972 == **H3U serial protocol** ==
973
974 **HMI Settings**
975
976 |=**Item**|=**Settings**|=**Note**
977 |Protocol|INOVANCE H3U PLC|
978 |Connection|RS422|
979 |Baud rate|9600|
980 |Data bit|7|
981 |Parity|EVEN|
982 |Stop bit|1|
983 |PLC station No.|0|
984
985 **Address List**
986
987 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
988 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
989 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
990 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
991 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
992 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
993 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
994 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
995 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
996 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
997 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
998 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
999 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1000 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1001 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1002 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1003 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1004 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1005 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1006
1007 **Configure the communication protocol**
1008
1009 (% style="text-align:center" %)
1010 [[image:image-20220830170114-4.png]]
1011
1012 [[image:image-20220830170017-3.png]]
1013
1014 **Cable Wiring**
1015
1016 (% style="text-align:center" %)
1017 [[image:Inovance.png]]
1018
1019 == **H3U Ethernet portocol** ==
1020
1021 **HMI Settings**
1022
1023 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1024 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1025 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1026 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1027 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1028 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1029
1030 **Address List**
1031
1032 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1033 |Bit|M|M DDDD|0~~8511|
1034 |Bit|SM|SM DDDD|0~~1023|
1035 |Bit|S|S DDDD|0~~4095|
1036 |Bit|T|T DDD|0~~511|
1037 |Bit|C|C DDD|0~~255|
1038 |Bit|X|X OOO|0~~571|
1039 |Bit|Y|Y OOO|0~~571|
1040 |Word|D|D DDDD|0~~8511|
1041 |Word|SD |SD DDDD|0~~1023|
1042 |Word|R|R DDDDD|0~~32767|
1043 |Word|T|T DDD|0~~255|
1044 |Word|C|C DDD|0~~199|
1045 |Double Word|C|C DDD|200~~255|
1046
1047 **Cable Wiring**
1048
1049 (% style="text-align:center" %)
1050 [[image:CommonEthernet.png]]
1051
1052 = Create communication with LS** PLC** =
1053
1054 == **XGB serial protocol ** ==
1055
1056 **HMI Settings**
1057
1058 |=**Item**|=**Settings**|=**Note**
1059 |Protocol|LS XGB CPU DRIECT|
1060 |Connection|RS232|
1061 |Baud rate|115200|
1062 |Data bit|8|
1063 |Parity|NONE|
1064 |Stop bit|1|
1065 |PLC station No.|1|
1066
1067 **Address List**
1068
1069 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1070 |Bit|P|P|P DDDD.f|0~~2047|
1071 |Bit|M|M|M DDDD.f|0~~2047|
1072 |Bit|L|L|L DDDDD.f|0~~11263|
1073 |Bit|K|K|K DDDD.f|0~~2559|
1074 |Bit|F|F|F DDDD.f|0~~2047|
1075 |Bit|S|S|S DDDDD|0~~12799|
1076 |Bit|D|D|D DDDDD.f|0~~32767|
1077 |Bit|U|U|U FFFF.f|0~~7f31|
1078 |Bit|T|T|T DDDD.f|0~~2047|
1079 |Bit|C|C|C DDDD.f|0~~2047|
1080 |Word|P|P|P DDDD|0~~2047|
1081 |Word|M|M|M DDDD|0~~2047|
1082 |Word|L|L|L DDDDD|0~~11263|
1083 |Word|K|K|K DDDD|0~~2559|
1084 |Word|F|F|F DDDD|0~~2047|
1085 |Word|C|C|C DDDD|0~~2047|
1086 |Word|T|T|T DDDD|0~~2047|
1087 |Word|D|D|D DDDDD|0~~32767|
1088 |Word|N|N|N DDDDD|0~~21503|
1089 |Word|U|U|U FFFF|0~~7f31|
1090 |Word|Z|Z|Z DDD|0~~127|
1091 |Word|R|R|R DDDDD|0~~32767|
1092 |Word|ZR|ZR|Z DDDDD|0~~32767|
1093 |Word|TS|TS|TS DDDD|0~~2047|
1094 |Word|CS|CS|CS DDDD|0~~2047|
1095 |Word|S|S|S DDDDD|0~~12799|
1096
1097 **Configure the communication protocol**
1098
1099 (% style="text-align:center" %)
1100 [[image:image-20221028174410-1.png]]
1101
1102 (% style="text-align:center" %)
1103 [[image:image-20221028174753-2.png]]
1104
1105 (% style="text-align:center" %)
1106 [[image:image-20221028181125-4.png]]
1107
1108 **Pin Definition Diagram**
1109
1110 (% style="text-align:center" %)
1111 [[image:image-20221028180930-3.png]]
1112
1113 == **XBC serial protocol** ==
1114
1115 **HMI Settings**
1116
1117 |=**Item**|=**Settings**|=**Note**
1118 |Protocol|LS XBC CNet|
1119 |Connection|RS232|
1120 |Baud rate|115200|
1121 |Data bit|8|
1122 |Parity|NONE|
1123 |Stop bit|1|
1124 |PLC station No.|1|
1125
1126 **Address List**
1127
1128 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1129 |Bit|P|P|P d|0~~2047|
1130 |Bit|M|M|M d|0~~2047|
1131 |Bit|L|L|L d|0~~11263|
1132 |Bit|K|K|K d|0~~16183|
1133 |Bit|F|F|F d|0~~2047|
1134 |Bit|D|D|D d|0~~32767|
1135 |Bit|R|R|R d|0~~32767|
1136 |Bit|U|U|U d|0~~4095|
1137 |Word|P|P|P d|0~~2047|
1138 |Word|M|M|M d|0~~2047|
1139 |Word|L|L|L d|0~~11263|
1140 |Word|K|K|K d|0~~16183|
1141 |Word|F|F|F d|0~~2047|
1142 |Word|C|C|C d|0~~2047|
1143 |Word|T|T|T d|0~~2047|
1144 |Word|D|D|D d|0~~32767|
1145 |Word|N|N|N d|0~~21503|
1146 |Word|R|R|R d|0~~32767|
1147 |Word|U|U|U d|0~~4095|
1148 |Word|Z|Z|Z d|0~~127|
1149 |Word|S|S|S d|0~~127|
1150
1151 **Configure the communication protocol**
1152
1153 (% style="text-align:center" %)
1154 [[image:image-20220831170807-1.png]]
1155
1156 (% style="text-align:center" %)
1157 [[image:image-20220830174733-2.png]]
1158
1159 **Cable Wiring**
1160
1161 (% style="text-align:center" %)
1162 [[image:image-20220830174659-1.png]]
1163
1164 Pin Definition Diagram
1165
1166 (% style="text-align:center" %)
1167 [[image:image-20220830173402-8.png]]
1168
1169 == **XGK FEnet Ethernet protocol** ==
1170
1171 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1172
1173 **HMI Settings**
1174
1175 |**Items**|**Settings**|**Note**
1176 |Protocol|LG XGK FEnet(Ethernet)|
1177 |Connection|Ethernet|
1178 |Port No.|2004|
1179
1180 **Address List**
1181
1182 |**Type**|**Register**|**Range**|**Format**|**Note**
1183 |(% rowspan="14" %)Word|P|0~~2047|P d|
1184 |M|0~~2047|M d|
1185 |K|0~~2047|K d|
1186 |F|0~~2047|F d|
1187 |T|0~~2047|T d|
1188 |C|0~~2047|C d|
1189 |Z|0~~127|Z d|
1190 |S|0~~127|S d|
1191 |L|0~~11263|L d|
1192 |N|0~~21503|N d|
1193 |D|0~~32767|D d|
1194 |R|0~~32767|R d|
1195 |ZR|0~~65535|ZR d|
1196 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1197
1198 **✎Note:**
1199
1200 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1201 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1202 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1203
1204 **Communication settings in HMI**
1205
1206 Enable HMI Ethernet in [Project Settings];
1207
1208 (% style="text-align:center" %)
1209 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1210
1211 Set PLC IP in [Device IP] settings;
1212
1213 (% style="text-align:center" %)
1214 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1215
1216 **Cable Wiring**
1217
1218
1219 (% style="text-align:center" %)
1220 [[image:CommonEthernet.png]]
1221
1222 = Create communication with **Mitsubishi PLC** =
1223
1224 == **FX1S, 1N, 2N Series Protocol** ==
1225
1226 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1227
1228 **HMI Settings**
1229
1230 |**Item**|**Settings**|**Note**
1231 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1232 |Connection|RS422/RS485/RS232|
1233 |Baud rate|9600~~115200|
1234 |Data bit|7/8|
1235 |Parity|EVEN/Odd/None|
1236 |Stop bit|1/2|
1237 |PLC station No.|1~~255|
1238
1239 **Address List**
1240
1241 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1242 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1243 |Y|Y|Y o|0~~303237|
1244 |M|M|M d|0~~99999|
1245 |T|T|T d|0~~99999|
1246 |C|C|C d|0~~99999|
1247 |S|S|S d|0~~99999|
1248 |SM|SM|SM d|8000~~9999|
1249 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1250 |Y|Y|Y o|0~~303237|
1251 |M|M|M d|0~~99999|
1252 |T|T|T d|0~~99999|
1253 |C|C|C d|0~~199|
1254 |D|D|D d|0~~7999|
1255 |S|S|S d|0~~99999|
1256 |SD|SD|SD d|8000~~9999|
1257
1258 **Cable Wiring**
1259
1260 * **RS485**
1261
1262 (% style="text-align:center" %)
1263 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1264
1265 (% style="text-align:center" %)
1266 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1267
1268 * **RS422**
1269
1270 (% style="text-align:center" %)
1271 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1272
1273 **✎Note:** COM3 only available in PI8000/PI9000 series.
1274
1275 == **FX3U/3G/3GA serial protocol** ==
1276
1277 **HMI Settings**
1278
1279 |=**Item**|=**Settings**|=**Note**
1280 |Protocol|Mitsubishi FX3U/3G/3GA|
1281 |Connection|RS422|
1282 |Baud rate|9600~~115200|
1283 |Data bit|7/8|
1284 |Parity|EVEN/Odd/None|
1285 |Stop bit|1/2|
1286 |PLC station No.|1~~255|
1287
1288 **Address List**
1289
1290 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1291 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1292 |Y|Y|Y o|0~~303237|
1293 |M|M|M d|0~~99999|
1294 |T|T|T d|0~~99999|
1295 |C|C|C d|0~~99999|
1296 |S|S|S d|0~~99999|
1297 |SM|SM|SM d|8000~~9999|
1298 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1299 |Y|Y|Y o|0~~303237|
1300 |M|M|M d|0~~99999|
1301 |T|T|T d|0~~99999|
1302 |C|C|C d|0~~199|
1303 |D|D|D d|0~~7999|
1304 |S|S|S d|0~~99999|
1305 |SD|SD|SD d|8000~~9999|
1306
1307 **Configure the communication protocol**
1308
1309 (% style="text-align:center" %)
1310 [[image:image-20220831095222-1.png]]
1311
1312 (% style="text-align:center" %)
1313 [[image:image-20220831095743-2.png]]
1314
1315 **Wiring**
1316
1317 (% style="text-align:center" %)
1318 [[image:image-20220831100314-6.png]]
1319
1320 == **FX3U Ethernet Protocol** ==
1321
1322 Mitsubishi FX3U series PLC
1323
1324 **HMI Settings**
1325
1326 |Items|Settings|Note
1327 |Protocol|Mitsubishi FX3U|
1328 |Connection|Ethernet|
1329 |Port No.|5009|Must be the same as the PLC setting
1330 |PLC station No.|0|
1331
1332 **Address List**
1333
1334 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1335 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1336 |Y|Y|Y OOO|0~~377|
1337 |M|M|M DDDD|0~~7679|
1338 |SM|SM|SM DDDD|8000~~8511|
1339 |S|S|S DDDD|0~~4095|
1340 |TS|TS|TS DDD|0~~511|
1341 |CS|CS|CS DDD|0~~255|
1342 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1343 |TN|TN|TN DDD|0~~511|
1344 |D|D|D DDDD|0~~7999|
1345 |SD|SD|SD DDDD|8000~~8511|
1346 |R|R|R DDDDD|0~~32767|
1347
1348 **Ethernet Module Settings**
1349
1350 FX3U-ENET-L module configuration
1351 Set up the FX3U-ENET-L Ethernet module settings as follows.
1352 Select the module location, which in this document is Module 0.
1353
1354 [[image:image-20221115140802-1.png]]
1355
1356 Select "Operational setting" to enter the following screen.
1357
1358 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1359
1360 [[image:image-20221115142728-4.png]]
1361
1362 Select "Open setting" to enter the setting interface, the settings are as follows.
1363
1364 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1365
1366 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1367
1368 [[image:image-20221115142945-5.png]]
1369
1370 Click on "transter setup" - "PC side I/F setting", see the following figure.
1371
1372 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1373
1374 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1375
1376 [[image:image-20221115143341-6.png||height="426" width="712"]]
1377
1378 Read and write data from the Ethernet module
1379
1380 [[image:image-20221115143703-7.png]]
1381
1382 Set "Transter setup" to COM communication, and read or write operation as shown below
1383
1384 [[image:image-20221115143809-8.png]]
1385
1386 **PLC Settings (GX Works 2)**
1387
1388 Create a blank FX5U project
1389
1390 Find Current Connection in the navigation
1391
1392 [[image:image-20221115144335-9.png||height="422" width="706"]]
1393
1394 Select Connection Channel List
1395
1396 Select Ethernet board communication
1397
1398 [[image:image-20221115144824-10.png||height="421" width="705"]]
1399
1400 Select Ethernet Module
1401 Set the IP address of the PLC
1402
1403 [[image:image-20221115145228-11.png||height="674" width="708"]]
1404
1405 Read or write PLC data, in this document is read
1406
1407 [[image:image-20221115145553-12.png||height="424" width="711"]]
1408
1409 [[image:image-20221115145559-13.png||height="424" width="711"]]
1410
1411 **HMI Communication Setting**
1412
1413 [[image:image-20221115150003-14.png||height="425" width="712"]]
1414
1415 [[image:image-20221115150235-15.png||height="427" width="713"]]
1416
1417 [[image:image-20221115145559-13.png||height="424" width="711"]]
1418
1419 **HMI Communication Setting**
1420
1421 [[image:image-20221115150003-14.png||height="425" width="712"]]
1422
1423 [[image:image-20221115150235-15.png||height="427" width="713"]]
1424
1425 == **FX5U Serial Port Protocol** ==
1426
1427 Mitsubishi FX5U series PLC
1428
1429 **HMI Settings**
1430
1431 |**Item**|**Settings**|**Note**
1432 |Protocol|Mitsubishi FX5U|
1433 |Connection|RS422/RS485|
1434 |Baud rate|9600|
1435 |Data bit|7|
1436 |Parity|Odd|
1437 |Stop bit|1|
1438 |PLC station No.|1~~255|Need to be the same as PLC settings
1439
1440 **Address List**
1441
1442 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1443 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1444 |Y|Y|Y o|0~~303237|
1445 |M|M|M d|0~~99999|
1446 |B|B|B h|0~~7FFF|
1447 |F|F|F d|0~~32767|
1448 |SB|SB|SB h|0~~7FFF|
1449 |TS|TS|TS d|0~~1023|
1450 |TC|TC|TC d|0~~1023|
1451 |STS|STS|STS d|0~~1023|
1452 |STC|STC|STS d|0~~1023|
1453 |CS|CS|CS d|0~~1023|
1454 |CC|CC|CC d|0~~1023|
1455 |SM|SM|SM d|0~~9999|
1456 |L|L|L d|0~~32767|
1457 |S|S|S d|0~~4095|
1458 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1459 |TN|TN|TN d|0~~1023|
1460 |STN|STN|STN d|0~~1023|
1461 |CN|CN|CN d|0~~1023|
1462 |R|R|R d|0~~32767|
1463 |SW|SW|SW h|0~~7FFF|
1464 |Z|Z|Z d|0~~23|
1465 |D|D|D d|0~~7999|
1466 |SD|SD|SD d|0~~11999|
1467
1468 **PLC Settings (GX Works 3)**
1469
1470 Create a blank FX5U project
1471
1472 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1473
1474 (% style="text-align:center" %)
1475 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1476
1477 Select protocol in the setting item, and set parameters.
1478
1479 (% style="text-align:center" %)
1480 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1481
1482 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1483
1484 (% style="text-align:center" %)
1485 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1486
1487 Click the [Apply] button to finish the setting.
1488
1489 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1490
1491 (% style="text-align:center" %)
1492 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1493
1494 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1495
1496 Done.
1497
1498 **Cable Wiring**
1499
1500 * **RS485**
1501
1502 (% style="text-align:center" %)
1503 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1504
1505 (% style="text-align:center" %)
1506 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1507
1508 * **RS422**
1509
1510 (% style="text-align:center" %)
1511 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1512
1513 **✎Note:** COM3 only available in PI8000/PI9000 series.
1514
1515 == **L02 Serial Protocol** ==
1516
1517 Mitsubishi L02 series CPU built-in serial port.
1518
1519 **HMI Settings**
1520
1521 |=**Item**|=**Settings**|=**Note**
1522 |Protocol|Mitsubishi L02|
1523 |Connection|RS422|
1524 |Baud rate|115200|
1525 |Data bit|8|
1526 |Parity|Odd|
1527 |Stop bit|1|
1528 |PLC station No.|1~~255|Need to be the same as PLC settings
1529
1530 **Address List**
1531
1532 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1533 |Bit|X|X|X h|0~~FFFF|
1534 |Bit|Y|Y|Y h|0~~FFFF|
1535 |Bit|M|M|M d|0~~9999|
1536 |Bit|L|L|L d|0~~9999|
1537 |Bit|F|F|F d|0~~9999|
1538 |Bit|B|B|B h|0~~FFFF|
1539 |Bit|V|V|V d|0~~2047|
1540 |Bit|TC|TC|TC d|0~~9999|
1541 |Bit|SS|SS|SS d|0~~9999|
1542 |Bit|SC|SC|SC d|0~~9999|
1543 |Bit|CS|CS|CS d|0~~9999|
1544 |Bit|CC|CC|CC d|0~~9999|
1545 |Bit|SB|SB|SB h|0~~FFFF|
1546 |Bit|SM|SM|SM d|0~~2047|
1547 |Bit|STS|STS|STS d|0~~1023|
1548 |Bit|S|S|S d|0~~9999|
1549 |Bit|DX|DX|DX h|0~~FFFF|
1550 |Bit|DY|DY|DY h|0~~FFFF|
1551 |Bit|TS|TS|TS d|0~~9999|
1552 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1553 |Word|W|W|W h|0~~FFFF|
1554 |Word|TN|TN|TN d|0~~99999|
1555 |Word|SN|SN|SN d|0~~99999|
1556 |Word|CN|CN|CN d|0~~99999|
1557 |Word|R|R|R d|0~~99999|
1558 |Word|SW|SW|SW h|0~~FFFF|
1559 |Word|Z|Z|Z d|0~~99999|
1560 |Word|ZR|ZR|ZR h|0~~FFFF|
1561 |Word|D|D|D d|0~~99999|
1562
1563 **Communication Settings**
1564
1565 (% style="text-align:center" %)
1566 [[image:image-20220831105732-3.png]]
1567
1568 (% style="text-align:center" %)
1569 [[image:image-20220831110004-5.png]]
1570
1571 **Cable Wiring**
1572
1573 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1574
1575 Pin Definition Diagram
1576
1577 (% style="text-align:center" %)
1578 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1579
1580 == **L02 MELSEC (Ethernet) Protocol** ==
1581
1582 Mitsubishi Q series CPU built-in Ethernet port.
1583
1584 **HMI Settings**
1585
1586 |**Items**|**Settings**|**Note**
1587 |Protocol|MIT L02 CPU MELSEC|
1588 |Connection|Ethernet|
1589 |Port No.|1025|Must be the same as the PLC setting
1590 |PLC station No.|0|Must be the same as the PLC setting
1591
1592 **Address List**
1593
1594 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1595 |Bit|X|X|X h|0~~FFFF|
1596 |Bit|Y|Y|Y h|0~~FFFF|
1597 |Bit|M|M|M d|0~~9999|
1598 |Bit|L|L|L d|0~~9999|
1599 |Bit|F|F|F d|0~~9999|
1600 |Bit|B|B|B h|0~~FFFF|
1601 |Bit|V|V|V d|0~~2047|
1602 |Bit|TC|TC|TC d|0~~9999|
1603 |Bit|SS|SS|SS d|0~~9999|
1604 |Bit|SC|SC|SC d|0~~9999|
1605 |Bit|CS|CS|CS d|0~~9999|
1606 |Bit|CC|CC|CC d|0~~9999|
1607 |Bit|SB|SB|SB h|0~~FFFF|
1608 |Bit|SM|SM|SM d|0~~2047|
1609 |Bit|STS|STS|STS d|0~~1023|
1610 |Bit|S|S|S d|0~~9999|
1611 |Bit|DX|DX|DX h|0~~FFFF|
1612 |Bit|DY|DY|DY h|0~~FFFF|
1613 |Bit|TS|TS|TS d|0~~9999|
1614 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1615 |Word|W|W|W h|0~~FFFF|
1616 |Word|TN|TN|TN d|0~~99999|
1617 |Word|SN|SN|SN d|0~~99999|
1618 |Word|CN|CN|CN d|0~~99999|
1619 |Word|R|R|R d|0~~99999|
1620 |Word|SW|SW|SW h|0~~FFFF|
1621 |Word|Z|Z|Z d|0~~99999|
1622 |Word|ZR|ZR|ZR h|0~~FFFF|
1623 |Word|D|D|D d|0~~99999|
1624
1625 **Communication Settings**
1626
1627 Enable HMI Ethernet in [Project Settings];
1628
1629 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1630
1631 Set PLC IP in [Device IP] settings;
1632
1633 (% style="text-align:center" %)
1634 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1635
1636 **PLC Settings (GX Works2 )**
1637
1638 Create a project
1639
1640 Set PLC IP, subnet mask and gateway;
1641
1642 Select [Binary Code] as communication data code;
1643
1644 (% style="text-align:center" %)
1645 [[image:image-20221108202109-2.png||height="636" width="732"]]
1646
1647 Set PLC port number, for example 1025
1648
1649 (% style="text-align:center" %)
1650 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1651
1652 Save settings;
1653
1654 Download project into PLC device;
1655
1656 Restart PLC device;
1657
1658 **Cable Wiring**
1659
1660 (% style="text-align:center" %)
1661 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1662
1663 == **QJ71C24N MELSEC Protocol** ==
1664
1665 Mitsubishi QJ71C24N communication module built-in serial port;
1666
1667 **HMI Settings**
1668
1669 |**Items**|**Settings**|**Note**
1670 |Protocol|MIT QJ71 MELSEC|
1671 |Connection|422|
1672 |Baud rate|9600|
1673 |Data bit|8|
1674 |Parity|ODD|
1675 |Stop bit|1|
1676 |PLC station No.|1~~255|Need to be the same as PLC settings
1677
1678 **Address List**
1679
1680 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1681 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1682 |Y|Y|Y FFFF|0~~1FFF|
1683 |M|M|M DDDDD|0~~99999|
1684 |L|L|L DDDD|0~~8191|
1685 |F|F|F DDDD|0~~2047|
1686 |V|V|V DDDD|0~~2047|
1687 |B|B|B FFFF|0~~1FFF|
1688 |TS|TS|TS DDDD|0~~2047|
1689 |TC|TC|TC DDDD|0~~2047|
1690 |SS|SS|SS DDDD|0~~2047|
1691 |SC|SC|SC DDDD|0~~2047|
1692 |CS|CS|CS DDDD|0~~1023|
1693 |CC|CC|CC DDDD|0~~1023|
1694 |SB|SB|SB FFF|0~~7FF|
1695 |S|S|S D|0~~8191|
1696 |DX|DX|DX FFFF|0~~1FFF|
1697 |DY|DY|DY FFFF|0~~1FFF|
1698 |SM_|SM_|SM_ DDDD|8000~~9999|
1699 |SM|SM|SM DDDD|0~~2047|
1700 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1701 |D|D|D DDDDD|0~~12287|
1702 |W|W|W FFFF|0~~1FFF|
1703 |TN|TN|TN DDDD|0~~2047|
1704 |SN|SN|SN DDDD|0~~2047|
1705 |CN|CN|CN DDDD|0~~1023|
1706 |R|R|R DDDDD|0~~32767|
1707 |SW|SW|SW FFF|0~~7FF|
1708 |Z|Z|Z D|0~~15|
1709 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1710
1711 **Communication Settings**
1712
1713 (% style="text-align:center" %)
1714 [[image:image-20221109135738-1.png]]
1715
1716 (% style="text-align:center" %)
1717 [[image:image-20221109140016-3.png]]
1718
1719 Pin Definition Diagram
1720
1721 (% style="text-align:center" %)
1722 [[image:image-20221109140406-4.png]]
1723
1724 == **QJ71E71 MELSEC Protocol** ==
1725
1726 Mitsubishi QJ71E71 Ethernet communication module;
1727
1728 **HMI Settings**
1729
1730 |**Items**|**Settings**|**Note**
1731 |Protocol|MIT QJ71E71 MELSEC|
1732 |Connection|Ethernet|
1733 |Port No.|1025|Must be the same as the PLC setting
1734 |PLC station No.|0|Must be the same as the PLC setting
1735
1736 **Address List**
1737
1738 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1739 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1740 |Y|Y|Y h|0~~1FFF|
1741 |M|M|M d|0~~99999|
1742 |L|L|L d|0~~8191|
1743 |F|F|F d|0~~2047|
1744 |B|B|B h|0~~1FFF|
1745 |V|V|V d|0~~2047|
1746 |TS|TS|TS d|0~~2047|
1747 |TC|TC|TC d|0~~2047|
1748 |SS|SS|SS d|0~~2047|
1749 |SC|SC|SC d|0~~2047|
1750 |CS|CS|CS d|0~~1023|
1751 |CC|CC|CC d|0~~1023|
1752 |SB|SB|SB h|0~~7FF|
1753 |S|S|S d|0~~8191|
1754 |DX|DX|DX h|0~~1FFF|
1755 |DY|DY|DY h|0~~1FFF|
1756 |SM|SM|SM d|8000~~9999|
1757 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1758 |D|D|D d|0~~12287|
1759 |W|W|W h|0~~1FFF|
1760 |TN|TN|TN d|0~~2047|
1761 |SN|SN|SN d|0~~2047|
1762 |CN|CN|CN d|0~~1023|
1763 |R|R|R d|0~~32767|
1764 |SW|SW|SW h|0~~7FF|
1765 |Z|Z|Z d|0~~15|
1766 |ZR|ZR|ZR h|0~~FE7FF|
1767
1768 **HMI Communication Settings**
1769
1770 1) Enable HMI Ethernet in [Project Settings];
1771
1772 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1773
1774 2) Set PLC IP in [Device IP] settings
1775
1776 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1777
1778 **PLC Settings(GX Works2)**
1779
1780 * Click [Ethernet/CC IE/MELSECNET];
1781 * Please select [Ethernet] as network type;
1782 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1783 * Select [Online] as Mode;
1784 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1785 * Click [Operation setting] to set IP;
1786 * Select [Binary Code] as [Communication Data Code];
1787 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1788 * Click [Open setting]
1789 * Set protocol: TCP;
1790 * Set [unpassive] in [Open system];
1791 * Set [receive] in [Fixed buffer];
1792 * Set [procedure Exist] in [Fixed buffer communication];
1793 * Disable [Pairing open];
1794 * Set [No confirm] in [Existence confirmation];
1795 * Host station port number: 5009;
1796 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1797 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1798 * Download project into PLC and restart it
1799
1800 **Cable Wiring**
1801
1802 (% style="text-align:center" %)
1803 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1804
1805 = Create communication with **MODBUS** =
1806
1807 == **MODBUS RTU Master** ==
1808
1809 Supported Series: MODBUS RTU CONTROLLER
1810
1811 HMI works as MODBUS SLAVE connecting with MASTER
1812
1813 (% style="text-align:center" %)
1814 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1815
1816 (% style="text-align:center" %)
1817 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1818
1819 (% style="text-align:center" %)
1820 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1821
1822 **HMI Settings**
1823
1824 |**Items**|**Settings**|**Note**
1825 |Protocol|MODBUS RTU Master|
1826 |Connection|RS485/RS232|
1827 |Baud rate|2400~~187500|
1828 |Data bit|8|
1829 |Parity|Even/ Odd/ None|
1830 |Stop bit|1/2|
1831 |Station No.|0~~255|
1832
1833 **Address List**
1834
1835 |**Type**|**HMI address**|**MODBUS code**|**Range**
1836 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1837 |Word|HDW3500~~HDW7999|4|0~~4499
1838
1839 **Cable Wiring**
1840
1841 * **RS485**
1842
1843 (% style="text-align:center" %)
1844 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1845
1846 (% style="text-align:center" %)
1847 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1848
1849 * **RS232**
1850
1851 (% style="text-align:center" %)
1852 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1853
1854 **✎Note:** COM3 only available in PI8000/PI9000 series.
1855
1856 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1857
1858 Supported Series: MODBUS RTU CONTROLLER
1859
1860 HMI works as MODBUS MASTER connecting with SLAVE.
1861
1862 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1863
1864 (% style="text-align:center" %)
1865 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1866
1867 (% style="text-align:center" %)
1868 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1869
1870 (% style="text-align:center" %)
1871 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1872
1873 **HMI Settings**
1874
1875 |**Items**|**Settings**|**Note**
1876 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1877 |Connection|RS485/RS232|
1878 |Baud rate|2400~~187500|
1879 |Data bit|8|
1880 |Parity|Even/ Odd/ None|
1881 |Stop bit|1/2|
1882 |PLC station No.|0~~255|
1883
1884 **Address List**
1885
1886 |**Type**|**Address Type**|**Function code & Description**
1887 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1888 |06 (write single register: write a binary value to a holding register)
1889 |10 (write values to multiple addresses )
1890 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1891 |06 (write single register: write a binary value to a holding register)
1892 |10 (write values to multiple addresses )
1893 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1894 |06 (write single register: write a binary value to a holding register)
1895 |10 (write values to multiple addresses )
1896 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1897 |10 (write values to multiple addresses )
1898 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1899 |05 (Force a single coil to force the on/off state of a logic coil)
1900 |0F (Write multiple bits, ie write continuously)
1901 |(% rowspan="3" %)1|02 (Read the input state)
1902 |05 (Force a single coil to force the on/off state of a logic coil)
1903 |0F (Write multiple bits)
1904 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1905 |05 (Force a single coil to force the on/off state of a logic coil)
1906 |0F (Write multiple bits)
1907 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1908 |0F (Write multiple bits)
1909
1910 **✎Note:**
1911
1912 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1913 * The function codes sent out are the same as those that read and write words.
1914
1915 **Station number for more than one slaves**
1916
1917 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1918
1919 (% style="text-align:center" %)
1920 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1921
1922 **Cable Wiring**
1923
1924 * **RS485**
1925
1926 (% style="text-align:center" %)
1927 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1928
1929 (% style="text-align:center" %)
1930 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1931
1932 * **RS232**
1933
1934 (% style="text-align:center" %)
1935 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1936
1937 **✎Note:** COM3 only available in PI8000/PI9000 series.
1938
1939 == **Communicate with Modbus Meter** ==
1940
1941 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
1942
1943 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
1944
1945 (% style="text-align:center" %)
1946 [[image:LinfeeDiagram.png]]
1947
1948 2. Check the specific Modbus parameter in the communication menu from LED display.
1949
1950 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
1951
1952 {{info}}
1953 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
1954 {{/info}}
1955
1956 (% style="text-align:center" %)
1957 [[image:MeterModbusAllView.png]]
1958
1959 3. Create new project and change the Communication settings.
1960
1961 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
1962
1963 (% style="text-align:center" %)
1964 [[image:PIStudioSetupMeterModbusPara.png]]
1965
1966 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
1967
1968 The following table is intercept part of the manual for Linfee Modbus manual.
1969
1970 **0x03/0x04 command data register address**:
1971
1972 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
1973 | HEX|DEC| | | |
1974 |0x00|0|Reserved| | |
1975 |0x02|2|Reserved| | |
1976 |0x04|4|Reserved| | |
1977 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
1978 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
1979 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
1980 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
1981 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
1982 |0x10|16|Uca|float|2|Line Voltage data, Unit V
1983 |0x12|18|Ia|float|2|Phase Current data, Unit A
1984 |0x14|20|Ib|float|2|Phase Current data, Unit A
1985 |0x16|22|Ic|float|2|Phase Current data, Unit A
1986
1987 {{info}}
1988 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
1989 {{/info}}
1990
1991 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
1992
1993 (% style="text-align:center" %)
1994 [[image:MeterModbusPInumericSet.png]]
1995
1996 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
1997
1998 (% style="text-align:center" %)
1999 [[image:MeterModbusNumericInputFormat.png]]
2000
2001 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2002
2003 (% style="text-align:center" %)
2004 [[image:ActualHMIModbusResult.jpg]]
2005
2006 == **MODBUS TCP Slave (All function)** ==
2007
2008 Supported series: MODBUS TCP controller
2009
2010 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2011
2012 (% style="text-align:center" %)
2013 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2014
2015 (% style="text-align:center" %)
2016 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2017
2018 (% style="text-align:center" %)
2019 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2020
2021 **HMI Setting**
2022
2023 |**Items**|**Settings**|**Note**
2024 |Protocol|MODBUS TCP Slave (All function)|
2025 |Connection|Ethernet|
2026 |Port No.|502|
2027 |PLC station No.|1|
2028
2029 **Address List**
2030
2031 |**Type**|**Register**|**Function code & Description**
2032 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2033 |06 (write single register: write a binary value to a holding register)
2034 |10 (write values to multiple addresses )
2035 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2036 |06 (write single register: write a binary value to a holding register)
2037 |10 (write values to multiple addresses )
2038 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2039 |06 (write single register: write a binary value to a holding register)
2040 |10 (write values to multiple addresses )
2041 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2042 |10 (write values to multiple addresses )
2043 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2044 |05 (Force a single coil to force the on/off state of a logic coil)
2045 |0F (Write multiple bits, ie write continuously)
2046 |(% rowspan="3" %)1|02 (Read the input state)
2047 |05 (Force a single coil to force the on/off state of a logic coil)
2048 |0F (Write multiple bits)
2049 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2050 |05 (Force a single coil to force the on/off state of a logic coil)
2051 |0F (Write multiple bits)
2052 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2053 |0F (Write multiple bits)
2054
2055 **Communication Settings**
2056
2057 Enable HMI Ethernet in [Project Settings];
2058
2059 (% style="text-align:center" %)
2060 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2061
2062 Set PLC IP in [Device IP] settings;
2063
2064 (% style="text-align:center" %)
2065 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2066
2067 **Cable Wiring**
2068
2069 (% style="text-align:center" %)
2070 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2071
2072 = Create communication with **Omron** PLC =
2073
2074 == CJ TCP FINS Ethemet  Protocol ==
2075
2076 Supported device:CJ series、CJ1W-EIP21
2077
2078 **HMI Settings**
2079
2080 |=**Items**|=**Settings**|=**Note**
2081 |Protocol|OMRON CJ TCP FINS Ethemet|
2082 |Connection|Ethernet|
2083 |Port No.|9600|
2084 |Device No.|0|
2085 |HMI No.|0|(((
2086
2087 )))
2088
2089 **Address List**
2090
2091 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2092 |Bit|CIO|CIO|CIO d|0~~99999|
2093 |Bit|W|W|W d|0~~99999|
2094 |Bit|D|D|D d|0~~99999|
2095 |Bit|H|H|H d|0~~99999|
2096 |Bit|A|A|A d|0~~99999|
2097 |Bit|T|T|T h|0~~99999|
2098 |Bit|CF|CF|CF d|0~~99999|
2099 |Bit|FF|FF|FF d|0~~99999|
2100 |Bit|C|C|C d|0~~99999|
2101 |Bit|EM0|EM0|EM0 d|0~~99999|
2102 |Bit|EM1|EM1|EM1 d|0~~99999|
2103 |Bit|EM2|EM2|EM2 d|0~~99999|
2104 |Bit|EM3|EM3|EM3 d|0~~99999|
2105 |Bit|EM4|EM4|EM4 d|0~~99999|
2106 |Bit|EM5|EM5|EM5 h|0~~99999|
2107 |Bit|EM6|EM6|EM6 d|0~~99999|
2108 |Bit|EM7|EM7|EM7 d|0~~99999|
2109 |Bit|EM8|EM8|EM8 d|0~~99999|
2110 |Bit|EM9|EM9|EM9 d|0~~99999|
2111 |Bit|EMA|EMA|EMA d|0~~99999|
2112 |Bit|EMB|EMB|EMB d|0~~99999|
2113 |Bit|EMC|EMC|EMC d|0~~99999|
2114 |Bit|Lamp|Lamp|Lamp d|0~~0|
2115 |Word|CIO|CIO|CIO d|0~~99999|
2116 |Word|W|W|W d|0~~99999|
2117 |Word|D|D|D d|0~~99999|
2118 |Word|H|H|H d|0~~99999|
2119 |Word|A|A|A d|0~~99999|
2120 |Word|T|T|T h|0~~99999|
2121 |Word|CF|CF|CF d|0~~99999|
2122 |Word|FF|FF|FF d|0~~99999|
2123 |Word|C|C|C d|0~~99999|
2124 |Word|EM0|EM0|EM0 d|0~~99999|
2125 |Word|EM1|EM1|EM1 d|0~~99999|
2126 |Word|EM2|EM2|EM2 d|0~~99999|
2127 |Word|EM3|EM3|EM3 d|0~~99999|
2128 |Word|EM4|EM4|EM4 d|0~~99999|
2129 |Word|EM5|EM5|EM5 h|0~~99999|
2130 |Word|EM6|EM6|EM6 d|0~~99999|
2131 |Word|EM7|EM7|EM7 d|0~~99999|
2132 |Word|EM8|EM8|EM8 d|0~~99999|
2133 |Word|EM9|EM9|EM9 d|0~~99999|
2134 |Word|EMA|EMA|EMA d|0~~99999|
2135 |Word|EMB|EMB|EMB d|0~~99999|
2136 |Word|EMC|EMC|EMC d|0~~99999|
2137 |Word|IR|IR|IR d|0~~99999|
2138 |Word|DR|DR|DR d|0~~99999|
2139
2140 **Configure the communication protocol**
2141
2142 (% style="text-align:center" %)
2143 [[image:image-20220830143348-1.png]]
2144
2145 (% style="text-align:center" %)
2146 [[image:image-20220830143511-2.png]]
2147
2148 **Configure CJ1W-EIP21 connect with HMI**
2149
2150 (% style="text-align:center" %)
2151 [[image:ftEVGvAprh.png]]
2152
2153 Select TCP_Client_2N
2154
2155 (% style="text-align:center" %)
2156 [[image:RURXWcgyCd.png]]
2157
2158 **Cable Wiring**
2159
2160 Pin Definition Diagram
2161
2162 (% style="text-align:center" %)
2163 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2164
2165 == **CP1E/CP1H serial protocol** ==
2166
2167 Supported device: OMRON CS1(CP1E/CP1H)
2168
2169 **HMI Settings**
2170
2171 |=**Items**|=**Settings**|=**Note**
2172 |Protocol|OMRON CS1(CP1E/CP1H)|
2173 |Connection|RS232 (9600, 2, 7, EVEN)|
2174 |Port No.|None|
2175 |PLC station No.|0|
2176
2177 **Address List**
2178
2179 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2180 |Bit|CIO|CIO|CIO d|0~~99999|
2181 |Bit|W|W|W d|0~~99999|
2182 |Bit|D|D|D d|0~~99999|
2183 |Bit|H|H|H d|0~~99999|
2184 |Bit|A|A|A d|0~~99999|
2185 |Bit|TF|T|T h|0~~99999|
2186 |Bit|CF|CF|CF d|0~~99999|
2187 |Bit|T|FF|FF d|0~~99999|
2188 |Bit|C|C|C d|0~~99999|
2189 |Bit|EM0|EM0|EM0 d|0~~99999|
2190 |Bit|EM1|EM1|EM1 d|0~~99999|
2191 |Bit|EM2|EM2|EM2 d|0~~99999|
2192 |Bit|EM3|EM3|EM3 d|0~~99999|
2193 |Bit|EM4|EM4|EM4 d|0~~99999|
2194 |Bit|EM5|EM5|EM5 h|0~~99999|
2195 |Bit|EM6|EM6|EM6 d|0~~99999|
2196 |Bit|EM7|EM7|EM7 d|0~~99999|
2197 |Bit|EM8|EM8|EM8 d|0~~99999|
2198 |Bit|EM9|EM9|EM9 d|0~~99999|
2199 |Bit|EMA|EMA|EMA d|0~~99999|
2200 |Bit|EMB|EMB|EMB d|0~~99999|
2201 |Bit|EMC|EMC|EMC d|0~~99999|
2202 |Word|CIO|CIO|CIO d|0~~99999|
2203 |Word|W|W|W d|0~~99999|
2204 |Word|D|D|D d|0~~99999|
2205 |Word|H|H|H d|0~~99999|
2206 |Word|A|A|A d|0~~99999|
2207 |Word|T|T|T h|0~~99999|
2208 |Word|CIO|CF|CF d|0~~99999|
2209 |Word|C|C|C d|0~~99999|
2210 |Word|EM0|EM0|EM0 d|0~~99999|
2211 |Word|EM1|EM1|EM1 d|0~~99999|
2212 |Word|EM2|EM2|EM2 d|0~~99999|
2213 |Word|EM3|EM3|EM3 d|0~~99999|
2214 |Word|EM4|EM4|EM4 d|0~~99999|
2215 |Word|EM5|EM5|EM5 h|0~~99999|
2216 |Word|EM6|EM6|EM6 d|0~~99999|
2217 |Word|EM7|EM7|EM7 d|0~~99999|
2218 |Word|EM8|EM8|EM8 d|0~~99999|
2219 |Word|EM9|EM9|EM9 d|0~~99999|
2220 |Word|EMA|EMA|EMA d|0~~99999|
2221 |Word|EMB|EMB|EMB d|0~~99999|
2222 |Word|EMC|EMC|EMC d|0~~99999|
2223 |Word|IR|IR|IR d|0~~99999|
2224 |Word|DR|DR|DR d|0~~99999|
2225
2226 **Configure the communication protocol**
2227
2228 (% style="text-align:center" %)
2229 [[image:image-20220902153118-1.png]]
2230
2231 (% style="text-align:center" %)
2232 [[image:image-20220902151322-2.png]]
2233
2234 **Cable Wiring**
2235
2236 (% style="text-align:center" %)
2237 [[image:image-20220902153949-2.png]]
2238
2239 Pin Definition Diagram
2240
2241 (% style="text-align:center" %)
2242 [[image:image-20220902154056-3.png]]
2243
2244 == **EC55 Protocol** ==
2245
2246 Supported device: EC55 temperature instrument
2247
2248 **1)HMI Settings**
2249
2250 |**Items**|**Settings**|**Note**
2251 |Protocol|Omron EC55|
2252 |Connection|RS485 (9600, 2, 7, EVEN)|
2253 |Port No.|None|
2254 |PLC station No.|0|
2255
2256 **2)Address List**
2257
2258 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2259 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2260 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2261 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2262 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2263 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2264 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2265 |CP|-|0-6|Read controller intrinsic property
2266 |CS|-|0-2|Read controller states
2267 |CA|-|0-17|Action command
2268
2269 **3)Device Settings**
2270
2271 Omron E5CC PLC configuration
2272
2273 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2274
2275 (% style="text-align:center" %)
2276 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2277
2278 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2279
2280 (% style="text-align:center" %)
2281 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2282
2283 **✎Note:** The communication settings for HMI should be consistent with this setting.
2284
2285 **Cable Wiring**
2286
2287 (% style="text-align:center" %)
2288 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2289
2290 (% style="text-align:center" %)
2291 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2292
2293 **✎Note:**
2294
2295 * COM3 only available in PI8000/PI9000 series.
2296 * CA address could not support continuous writing function;
2297 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2298 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2299 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2300 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2301 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2302 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2303 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2304
2305 == **EtherNet/IP NX series Protocol** ==
2306
2307 Supported series: Omron NX/NJ series
2308
2309 **HMI Setting**
2310
2311 |**Items**|**Settings**|**Note**
2312 |Protocol|Omron NX Ethernet/IP|
2313 |Connection|Ethernet|
2314 |Port No.|44818|
2315 |PLC station No.|1|
2316
2317 **Instruction**
2318
2319 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2320
2321 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2322
2323 (% style="text-align:center" %)
2324 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2325
2326 **Export labels from Sysmac Studio**
2327
2328 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2329
2330 (% style="text-align:center" %)
2331 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2332
2333 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2334
2335 Click [Label manage];
2336
2337 (% style="text-align:center" %)
2338 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2339
2340 Click [Import labels] and then select the file exported in step 1;
2341
2342 (% style="text-align:center" %)
2343 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2344
2345 The Import Status field shows the result, click [OK] to finish importing address labels;
2346
2347 (% style="text-align:center" %)
2348 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2349
2350 **Communication Settings**
2351
2352 Enable HMI Ethernet in [Project Settings];
2353
2354 (% style="text-align:center" %)
2355 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2356
2357 Set PLC IP in [Device IP] settings;
2358
2359 (% style="text-align:center" %)
2360 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2361
2362 (% style="text-align:center" %)
2363 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2364
2365 **Cable Wiring**
2366
2367 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2368
2369 == CV/CJ1M/CS1H ==
2370
2371 **HMI Setting:**
2372
2373 |=**Parameters**|=**Recommended**
2374 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2375 |=**PLC I/F**|RS232
2376 |=**Baud rate**|9600
2377 |=**Data bits**|7
2378 |=**Parity**|Even
2379 |=**Stop bits**|2
2380 |=**PLC sta. no.**|0
2381
2382 **PLC Setting:**
2383
2384 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2385
2386 **Device Address:**
2387
2388 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2389 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2390 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2391 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2392 |=B|H|DDDDdd|0 ~~ 409515|
2393 |=B|A|DDDDdd|0 ~~ 409515|
2394 |=B|TF|DDDDdd|0 ~~ 409515|
2395 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2396 |=B|T|DDDD|0 ~~ 4095|
2397 |=B|C|DDDD|0 ~~ 4095|
2398 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2399 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2400 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2401 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2402 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2403 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2404 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2405 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2406 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2407 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2408 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2409 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2410 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2411 |=B|Lamp|D|0~~0|
2412
2413 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2414 |=W|LR_W|DDDD|0 ~~ 4095|
2415 |=W|TC|DDD|0 ~~ 511|
2416 |=W|DM|DDDD|0 ~~ 9999|Data Register
2417
2418 **Wiring Diagram:**
2419
2420 **RS-232**
2421
2422 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2423
2424 Communication Module:
2425
2426 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2427
2428 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2429
2430 (% style="text-align:center" %)
2431 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2432
2433 = Create communication with **Rockwell PLC** =
2434
2435 == **DF1 Protocol** ==
2436
2437 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2438
2439 **HMI Settings**
2440
2441 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2442 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2443 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2444 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2445 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2446 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2447 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2448 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2449 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2450
2451 **Address List**
2452
2453 (% class="table-bordered" %)
2454 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2455 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2456 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2457 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2458 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2459 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2460 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2461 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2462 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2463 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2464 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2465 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2466
2467 **Cable Wiring**
2468
2469 (% style="text-align:center" %)
2470 [[image:AB.gif]]
2471
2472 == **DF1 Advanced Protocol** ==
2473
2474 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2475
2476 **HMI Settings**
2477
2478 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2479 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2480 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2481 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2482 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2483 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2484 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2485 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2486 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2487
2488 **Address List**
2489
2490 (% class="table-bordered" %)
2491 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2492 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2493 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2494 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2495 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2496 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2497 Bit data file B0~~B99
2498
2499 First two digits is for file number
2500
2501 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2502 )))
2503 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2504 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2505 Integer data file bit format N0~~N99
2506
2507 First two digits is for file number
2508
2509 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2510 )))
2511 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2512 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2513 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2514 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2515 Timer Preset Value
2516
2517 First two digits is for file number
2518
2519 For example, TNS99255 represents file number T99, address 255.
2520 )))
2521 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2522 Timer Accumulator Value
2523
2524 First two digits is for file number
2525
2526 For example, TNP99255 represents file number T99, address 255.
2527 )))
2528 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2529 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2530 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2531 Counter Preset Value
2532
2533 First two digits is for file number
2534
2535 For example, CNS99255 represents file number C99, address 255.
2536 )))
2537 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2538 Counter Accumulator Value
2539
2540 First two digits is for file number
2541
2542 For example, CNP99255 represents file number C99, address 255.
2543 )))
2544 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2545 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2546 Integer data file
2547
2548 First two digits is for file number
2549
2550 For example, NN99255 represents file number N99, address 255.
2551 )))
2552 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2553 Only able to communicate with file number F8
2554 )))
2555 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2556 Floating point data file
2557
2558 First two digits is for file number
2559
2560 For example, FN99255 represents file number F99, address 255.
2561 )))
2562 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2563
2564 **Cable Wiring**
2565
2566 (% style="text-align:center" %)
2567 [[image:AB.gif]]
2568
2569 == **MicroLogix Protocol** ==
2570
2571 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2572
2573 **HMI Settings**
2574
2575 (% class="table-bordered" %)
2576 |**Item**|**Settings**|**Note**
2577 |Protocol|Allen-Bradlley MicroLogix|
2578 |Connection|RS232|
2579 |Baud rate|19200|
2580 |Data bit|8|
2581 |Parity|None|
2582 |Stop bit|1|
2583 |PLC station No.|1|
2584
2585 **Address List**
2586
2587 (% class="table-bordered" %)
2588 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2589 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2590 |O|O d.d|0.0~~255.15|
2591 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2592 |S|S d.d|0.0~~255.15|
2593 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2594 |(% rowspan="9" %)Word|S|S d|0~~255|
2595 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2596 |TP|TP nnhh|0~~ffff
2597 |CS|CS nnhh|0~~ffff
2598 |CP|CP nnhh|0~~ffff
2599 |N|N nnhh|0~~ffff
2600 |C|C nnhh|0~~ffff
2601 |T|T nnhh|0~~ffff
2602 |R|R nnhh|0~~ffff
2603
2604 **Cable Wiring**
2605
2606 (% style="text-align:center" %)
2607 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2608
2609 == **CompactLogix FreeTag Ethernet protocol** ==
2610
2611 Allen-Brandly CompactLogix
2612
2613 **HMI Settings**
2614
2615 (% class="table-bordered" %)
2616 |**Items**|**Settings**|**Note**
2617 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2618 |Connection|Ethernet|
2619 |Port No.|44818|
2620
2621 **PLC Setting**
2622
2623 Create new tags
2624
2625 (% style="text-align:center" %)
2626 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2627
2628 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2629
2630 (% style="text-align:center" %)
2631 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2632
2633 Import labels, please open [Communication] window and click [Import label];
2634
2635 Select csv file, all tags will be displayed as belows;
2636
2637 (% style="text-align:center" %)
2638 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2639
2640 **✎Note:**
2641
2642 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2643
2644 (% style="text-align:center" %)
2645 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2646
2647 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2648
2649 **Communication settings in HMI**
2650
2651 Enable HMI Ethernet in [Project Settings];
2652
2653 (% style="text-align:center" %)
2654 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2655
2656 Set PLC IP in [Device IP] settings;
2657
2658 (% style="text-align:center" %)
2659 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2660
2661 **Cable Wiring**
2662
2663 (% style="text-align:center" %)
2664 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2665
2666 == **MicroLogix 1200** **protocol** ==
2667
2668 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2669
2670 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2671 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2672 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2673 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2674
2675 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2676
2677 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2678 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2679 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2680 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2681 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2682 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2683 |**PLC word address type**|**Address format**|**Address range**
2684 |S|ddd|S0 ~~ 255
2685 |TS|ffff|TS0 ~~ FFFF
2686 |TP|ffff|TP0 ~~ FFFF
2687 |CS|ffff|CS0 ~~ FFFF
2688 |CP|ffff|CP0 ~~ FFFF
2689 |N|ffff|N0 ~~ FFFF
2690 |F|ffff|F0 ~~ FFFF
2691
2692 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2693
2694 == **S7-200 Smart Ethernet Protocol** ==
2695
2696 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2697
2698 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2699
2700 **HMI Setting**
2701
2702 (% class="table-bordered" %)
2703 |**Items**|**Settings**|**Note**
2704 |Protocol|Simens S7-200 Smart Ethernet|
2705 |Connection|Ethernet|
2706 |Port No.|102|
2707 |PLC station No.|2|
2708
2709 **Address List**
2710
2711 (% class="table-bordered" %)
2712 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2713 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2714 |Q|Q|Q ddddd.o|0.0~~99999.7|
2715 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2716 |V|V|V ddddd.o|0.0~~99999.7|
2717 |M|M|M ddddd.o|0.0~~99999.7|
2718 |SM|SM|ddddd.o|0.0~~99999.7|
2719 |S|S|ddddd.o|0.0~~99999.7|Read only
2720 |T|T|ddddd|0~~99999|Timer state, read only
2721 |C|C|ddddd|0~~99999|Counter state, read only
2722 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2723 |Q|QW|QW ddddd|0~~99999|
2724 |AI|AIW|AIW ddddd|0~~99999|
2725 |AQ|VB|VB ddddd|0~~99999|
2726 |V|VW|VW ddddd|0~~99998|(((
2727 VW0=VB (0~~1)
2728
2729 VW2=VB (2~~3)
2730
2731 Address value is a multiple of 2
2732 )))
2733 |V|VD|VD ddddd|0~~99998|(((
2734 VD0=VB (0~~3)
2735
2736 VD2=VB (4~~7)
2737
2738 Address value is a multiple of 4
2739 )))
2740 |M|MB|MB ddddd|0~~99999|
2741 |M|MW|MW ddddd|0~~99999|(((
2742 MW0=MB(0~~1)
2743
2744 MW2=MB(2~~3)
2745
2746 Address value is a multiple of 2
2747 )))
2748 |M|MD|MD ddddd|0~~99999|(((
2749 MD0=MB(0~~3)
2750
2751 MD4=MB(4~~7)
2752
2753 Address value is a multiple of 4
2754 )))
2755 |T|TW|TW ddddd|0~~99999|Value of timer
2756 |C|CW|CW ddddd|0~~99999|Value of counter
2757 |W|SW|SW ddddd|0~~99999|
2758
2759 **Communication Settings**
2760
2761 Enable HMI Ethernet in [Project Settings];
2762
2763 (% style="text-align:center" %)
2764 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2765
2766 Set PLC IP in [Device IP] settings;
2767
2768 (% style="text-align:center" %)
2769 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2770
2771 * PLC IP Address: PLC IP
2772 * PLC pot No.: 102(fixed)
2773 * Network:TCP_Client_2N(fixed)
2774
2775 (% style="text-align:center" %)
2776 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2777
2778 * Wait timeout: depend on actual network situation (more than 1500 ms)
2779
2780 **Cable Wiring**
2781
2782 (% style="text-align:center" %)
2783 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2784
2785 == **S7-300 Ethernet Protocol** ==
2786
2787 Supported Series: Siemens S7-300 series PLC
2788
2789 **HMI Setting**
2790
2791 (% class="table-bordered" %)
2792 |**Items**|**Settings**|**Note**
2793 |Protocol|Simens S7-300 Ethernet|
2794 |Connection|Ethernet|
2795 |Port No.|102|
2796 |PLC station No.|2|Need to be same as the PLC setting
2797
2798 **Address List**
2799
2800 (% class="table-bordered" %)
2801 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2802 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2803 |Q|Q|Q ddddd.o|0.0~~99999.7|
2804 |M|M|M ddddd.o|0.0~~99999.7|
2805 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2806 nnnn: block number;
2807
2808 dddd: address;
2809 )))
2810 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2811 |Q|QW|QW ddddd|0~~99999|
2812 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2813 |MW|MW ddddd|0~~99999|(((
2814 MW0=MB(0~~1)
2815
2816 MW2=MB(2~~3)
2817
2818 Address value is a multiple of 2
2819 )))
2820 |MD|MD ddddd|0~~99999|(((
2821 MD0=MB(0~~3)
2822
2823 MD4=MB(4~~7)
2824
2825 Address value is a multiple of 4
2826 )))
2827 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2828 nnnn: block number;
2829
2830 dddd: address
2831 )))
2832 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2833 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2834
2835 **Communication Settings**
2836
2837 Enable HMI Ethernet in [Project Settings];
2838
2839 (% style="text-align:center" %)
2840 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2841
2842 Set PLC IP in [Device IP] settings;
2843
2844 (% style="text-align:center" %)
2845 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2846
2847 * PLC IP Address: PLC IP
2848 * PLC pot No.: 102(fixed)
2849 * Network:TCP_Client_2N(fixed)
2850
2851 (% style="text-align:center" %)
2852 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2853
2854 * Wait timeout: depend on actual network situation (more than 1500 ms)
2855
2856 **Cable Wiring**
2857
2858 (% style="text-align:center" %)
2859 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2860
2861 == **S7-1200 Ethernet Protocol** ==
2862
2863 Supported Series: Siemens S7-1200
2864
2865 **HMI Setting**
2866
2867 (% class="table-bordered" %)
2868 |**Items**|**Settings**|**Note**
2869 |Protocol|Siemens S7-1200|
2870 |Connection|Ethernet|
2871 |Port No.|102|
2872 |PLC station No.|2|
2873
2874 **Address List**
2875
2876 (% class="table-bordered" %)
2877 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2878 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2879 d:0~-~-9999
2880
2881 o:0-7
2882 )))|
2883 |Q|Q|Q d.o|(((
2884 d:0~-~-9999
2885
2886 o:0-7
2887 )))|
2888 |M|M|M d.o|(((
2889 d:0~-~-9999
2890
2891 o:0-7
2892 )))|
2893 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2894 nn:0-9999,
2895
2896 dddd:0-9999,
2897
2898 o:0-7
2899 )))|(((
2900 nn:DB No.
2901
2902 dddd:address value
2903
2904 o: digit address
2905 )))
2906 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2907 |M|MW|MW d|d:0-99999|(((
2908 MW0=MB(0~~1)
2909
2910 MW2=MB(2~~3)
2911
2912 Address value is a multiple of 2
2913 )))
2914 |M|MD|MD d|d:0-99999|(((
2915 MD0=MB(0~~3)
2916
2917 MD4=MB(4~~7)
2918
2919 Address value is a multiple of 4
2920 )))
2921 |I|IW|IW d|d:0-99999|
2922 |Q|QW|QW d|d:0-99999|
2923 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2924 nn:0-9999
2925
2926 dddd:0-9999
2927 )))|(((
2928 nn:DB No.
2929
2930 dddd:address value
2931 )))
2932 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2933 nn:0-9999
2934
2935 dddd:0-9999
2936 )))|(((
2937 nn:DB No.
2938
2939 dddd:address value
2940
2941 Address value is a multiple of 2
2942 )))
2943 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2944 nn:0-9999
2945
2946 dddd:0-9999
2947 )))|(((
2948 nn:DB No.
2949
2950 dddd:address value
2951
2952 Address value is a multiple of 4
2953 )))
2954
2955 **Communication Settings**
2956
2957 Enable HMI Ethernet in [Project Settings];
2958
2959 (% style="text-align:center" %)
2960 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2961
2962 Set PLC IP in [Device IP] settings;
2963
2964 (% style="text-align:center" %)
2965 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2966
2967 **✎Note:**
2968
2969 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2970 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2971 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2972 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2973
2974 **PLC Settings**
2975
2976 Add BD
2977
2978 * Please uncheck [Symbolic access only] option;
2979
2980 (% style="text-align:center" %)
2981 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2982
2983 Address settings, using BD2 as example.
2984
2985 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2986 * 2 represent DB block number
2987 * xxxx represent address
2988
2989 **Such as:**
2990
2991 * DBxDBB20000 = DB2.DBB0
2992 * DBxDBW20004 = DB2.DBW4
2993
2994 (% style="text-align:center" %)
2995 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2996
2997 **How to connect with S7-1200 Firmware V4.0**
2998
2999 PLC configuration
3000
3001 * Double click [device configuration] in Siemens via software
3002 * Double click [protection] to enter protection configuration screen
3003
3004 (% style="text-align:center" %)
3005 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3006
3007 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3008
3009 (% style="text-align:center" %)
3010 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3011
3012 DB settings
3013
3014 * Right click [DB], select [properties]
3015 * Uncheck [optimized block access]
3016
3017 **Cable Wiring**
3018
3019 (% style="text-align:center" %)
3020 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3021
3022 == **S7-XXX Ethernet Protocol** ==
3023
3024 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3025
3026 **HMI Setting**
3027
3028 (% class="table-bordered" style="width:823px" %)
3029 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3030 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3031 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3032 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3033 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3034 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3035
3036 Slot from TIA Portal is equal to Device No. of PIStudio
3037
3038 Rack from TIA Portal is equal to HMI No. of PIStudio
3039
3040 (% style="text-align:center" %)
3041 [[image:S7-XXXCommunication Settings.png]]
3042
3043 (% style="text-align:center" %)
3044 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3045
3046 **Address List**
3047
3048 (% class="table-bordered" %)
3049 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3050 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3051 d:0~-~-9999
3052
3053 o:0-7
3054 )))|
3055 |Q|Q|Q d.o|(((
3056 d:0~-~-9999
3057
3058 o:0-7
3059 )))|
3060 |M|M|M d.o|(((
3061 d:0~-~-9999
3062
3063 o:0-7
3064 )))|
3065 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3066 nn:0-9999,
3067
3068 dddd:0-9999,
3069
3070 o:0-7
3071 )))|(((
3072 nn:DB No.
3073
3074 dddd:address value
3075
3076 o: digit address
3077 )))
3078 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3079 |M|MW|MW d|d:0-99999|(((
3080 MW0=MB(0~~1)
3081
3082 MW2=MB(2~~3)
3083
3084 Address value is a multiple of 2
3085 )))
3086 |M|MD|MD d|d:0-99999|(((
3087 MD0=MB(0~~3)
3088
3089 MD4=MB(4~~7)
3090
3091 Address value is a multiple of 4
3092 )))
3093 |I|IW|IW d|d:0-99999|
3094 |Q|QW|QW d|d:0-99999|
3095 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3096 nn:0-9999
3097
3098 dddd:0-9999
3099 )))|(((
3100 nn:DB No.
3101
3102 dddd:address value
3103 )))
3104 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3105 nn:0-9999
3106
3107 dddd:0-9999
3108 )))|(((
3109 nn:DB No.
3110
3111 dddd:address value
3112
3113 Address value is a multiple of 2
3114 )))
3115 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3116 nn:0-9999
3117
3118 dddd:0-9999
3119 )))|(((
3120 nn:DB No.
3121
3122 dddd:address value
3123
3124 Address value is a multiple of 4
3125 )))
3126
3127 **Communication Settings**
3128
3129 Enable HMI Ethernet in [Project Settings];
3130
3131 (% style="text-align:center" %)
3132 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3133
3134 Set PLC IP in [Device IP] settings;
3135
3136 (% style="text-align:center" %)
3137 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3138
3139 **✎Note:**
3140
3141 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3142 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3143
3144 **Cable Wiring**
3145
3146 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3147
3148 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3149
3150 Supported Series: Siemens Logo 0BA0, 0BA1 series
3151
3152 **HMI Settings**
3153
3154 (% class="table-bordered" %)
3155 |**Items**|**Settings**|**Note**
3156 |Protocol|Siemens LOGO|
3157 |Connection|Ethernet|
3158 |Port No.|102|
3159 |PLC station No.|2|
3160
3161 **Address List**
3162
3163 (% class="table-bordered" %)
3164 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3165 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3166 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3167 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3168 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3169 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3170 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3171 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3172 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3173 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3174 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3175 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3176 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3177 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3178 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3179 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3180
3181 **PLC Settings in LOGO Software:**
3182
3183 Click [Tools]~-~-[Ethernet Connections],shown as below.
3184
3185 (% style="text-align:center" %)
3186 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3187
3188 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3189
3190 (% style="text-align:center" %)
3191 [[image:image-20221228142937-4.png]]
3192
3193 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3194
3195 (% style="text-align:center" %)
3196 [[image:image-20221228143047-5.png]]
3197
3198 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3199
3200 (% style="text-align:center" %)
3201 [[image:image-20221228143246-6.png]]
3202
3203
3204 **HMI Communication Settings**
3205
3206 Set PLC IP in [Device IP] settings;
3207
3208 (% style="text-align:center" %)
3209 [[image:image-20221228143614-7.png]]
3210
3211 Enable HMI Ethernet in [Project Settings];
3212
3213 (% style="text-align:center" %)
3214 [[image:image-20221228144229-9.png]]
3215
3216 TSAP setting
3217
3218 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3219 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3220 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3221 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3222 ie, ig series: use HSW1200, HSW1201.
3223 HMI V2.0: use HSW1200, HSW1201.
3224
3225 **✎Note:**
3226
3227 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3228 * HSW10119/HSW1201 is set up as shown.
3229 * (((
3230 (% style="text-align:center" %)
3231 [[image:image-20221228144800-11.png]]
3232 )))
3233 * (((
3234 (% style="text-align:center" %)
3235 [[image:image-20221228144708-10.png]]
3236 )))
3237
3238 * AI word address and Ibit address are read-only and cannot be written on HMI.
3239 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3240 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3241 * Written value of RTC cannot exceed 255.
3242
3243 **Cable Wiring**
3244
3245 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3246
3247 == S7-300 232 ==
3248
3249 **HMI Setting:**
3250
3251 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3252 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3253 |=**PLC I/F**|RS232| |
3254 |=**Baud rate**|19200|9600,19200|
3255 |=**Data bits**|8| |
3256 |=**Parity**|Odd| |
3257 |=**Stop bits**|1| |
3258 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3259
3260 **Device Address**
3261
3262 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3263 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3264 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3265 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3266 |=Word|(((
3267 DB1 to DB99
3268 )))|DDDDDo|0 ~~ 655327|
3269 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3270 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3271 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3272 |=Double word|MD|DDDD|0 ~~ 4094|
3273 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3274 Data Register Double Word (must be even)
3275 )))
3276 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3277
3278 **Cable Wiring**
3279
3280 (% style="text-align:center" %)
3281 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3282
3283 = Create communication with Xinje** PLC** =
3284
3285 == XC serial protocol ==
3286
3287 **HMI Settings**
3288
3289 |**Item**|**Settings**|**Note**
3290 |Protocol|XINJE XC MODBUS|
3291 |Connection|RS232|
3292 |Baud rate|19200|
3293 |Data bit|8|
3294 |Parity|EVEN|
3295 |Stop bit|1|
3296 |PLC station No.|1|
3297
3298 **Address List**
3299
3300 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3301 |Bit|M|M|M d|0~~8511|
3302 |Bit|X|X|X o|0~~1747|
3303 |Bit|Y|Y|Y o|0~~1747|
3304 |Bit|S|S|S d|0~~1023|
3305 |Bit|T|T|T d|0~~4095|
3306 |Bit|C|C|C d|0~~634|
3307 |Word|D|D|D d|0~~8511|
3308 |Word|TD|TD|TD d|0~~618|
3309 |Word|CD|CD|CD d|0~~634|
3310 |Word|FD|FD|FD d|0~~8511|
3311
3312 **Configure the communication protocol**
3313
3314 (% style="text-align:center" %)
3315 [[image:image-20220830154105-1.png]]
3316
3317 (% style="text-align:center" %)
3318 [[image:image-20220830154159-3.png]]
3319
3320 **Cable Wiring**
3321
3322 Figure
3323
3324 [[image:image-20220830155728-4.png]]
3325
3326 Pin Definition Diagram
3327
3328 (% style="text-align:center" %)
3329 [[image:image-20220830154131-2.png]]
3330
3331 == XD serial protocol ==
3332
3333 **HMI Settings**
3334
3335 Supported Series: Xinjie XD/XE Series PLC
3336
3337 |=**Item**|=**Settings**|=**Note**
3338 |Protocol|XINJE XD/XC MODBUS|
3339 |Connection|RS232|
3340 |Baud rate|19200|
3341 |Data bit|8|
3342 |Parity|EVEN|
3343 |Stop bit|1|
3344 |PLC station No.|1|
3345
3346 **Address List**
3347
3348 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3349 |Bit|M|M|M d|0~~74999|
3350 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3351 |Bit|X2xx|X2xx|X2xx o|0~~277|
3352 |Bit|X|X|X o|0~~77|
3353 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3354 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3355 |Bit|Y|Y|Y o|0~~4095|
3356 |Bit|SM|SM|SM d|0~~4999|(((
3357
3358 )))
3359 |Bit|T|T|T d|0~~4999|
3360 |Bit|C|C|C d|0~~4999|
3361 |Bit|ET|ET|ET d|0~~31|
3362 |Bit|SE|SE|SE d|0~~31|
3363 |Bit|HM|HM|HM d|0~~11999|
3364 |Bit|HSC|HSC|HSC d|0~~39|
3365 |Bit|HS|HS|HS d|0~~999|
3366 |Bit|HT|HT|HT d|0~~1999|
3367 |Bit|HC|HC|HC d|0~~1999|
3368 |Bit|S|S|S d|0~~7999|
3369 |Word|D|D|D d|0~~69999|
3370 |Word|ID|ID|ID d|0~~99|
3371 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3372 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3373 |Word|QD|QD|QD d|0~~99|
3374 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3375 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3376 |Word|SD|SD|SD d|0~~4999|
3377 |Word|TD|TD|TD d|0~~575|
3378 |Word|CD|CD|CD d|0~~575|
3379 |Word|ETD|ETD|ETD d|0~~31|
3380 |Word|HD|HD|HD d|0~~24999|
3381 |Word|HSD|HSD|HSD d|0~~1023|
3382 |Word|HTD|HTD|HTD d|0~~95|
3383 |Word|HCD|HCD|HCD d|0~~95|
3384 |Word|HSCD|HSCD|HSCD d|0~~31|
3385 |Word|FD|FD|FD d|0~~8191|
3386 |Word|SFD|SFD|SFD d|0~~5999|
3387 |Word|FS|FS|FS d|0~~47|
3388
3389 **Configure the communication protocol**
3390
3391 (% style="text-align:center" %)
3392 [[image:image-20220830160042-1.png]]
3393
3394 (% style="text-align:center" %)
3395 [[image:image-20220830160129-2.png]]
3396
3397 **Cable Wiring**
3398
3399 (% style="text-align:center" %)
3400 [[image:image-20220905093902-1.png]]
3401
3402 Pin Definition Diagram
3403
3404 (% style="text-align:center" %)
3405 [[image:image-20220830160232-3.png]]
3406
3407 = Create communication with Panasonic** PLC** =
3408
3409 == **FP serial protocol** ==
3410
3411 **1)HMI Settings**
3412
3413 |**Item**|**Settings**|**Note**
3414 |Protocol|Panasonic FP MFWTOCOL|
3415 |Connection|RS232|
3416 |Baud rate|9600|
3417 |Data bit|8|
3418 |Parity|ODD|
3419 |Stop bit|1|
3420 |PLC station No.|1|
3421
3422 **2)Address List**
3423
3424 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3425 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3426 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3427 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3428 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3429 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3430 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3431 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3432 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3433 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3434 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3435 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3436 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3437 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3438 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3439 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3440
3441 **3)Configure the communication protocol**
3442
3443 [[image:image-20220830171050-1.png]]
3444
3445 [[image:image-20220830171126-2.png]]
3446
3447 **4)Cable Wiring**
3448
3449 Figure
3450
3451 [[image:image-20220830171328-4.png]]
3452
3453 Pin Definition Diagram
3454
3455 [[image:image-20220830171146-3.png]]
3456
3457 = Create communication with **SHIMADEN PLC** =
3458
3459 == **FP23 series protocol** ==
3460
3461 Supported series: SHIMADEN FP23 series
3462
3463 **HMI Setting**
3464
3465 |**Items**|**Settings**|**Note**
3466 |Protocol|SHIMADEN FP23 series|
3467 |Connection|RS485 (9600, 1, 7, EVEN)|
3468 |Port No.|None|
3469 |PLC station No.|0|
3470
3471 **Address List**
3472
3473 |**Device address**|**HMI register**|**Address range**|**Type**
3474 |0040-0043(HEX)|FP040|100064-200067|Read only
3475 |0100-010B(HEX)|FP100|100256-200267|Read only
3476 |0110-0142(HEX)|FP110|100272-200322|Read only
3477 |0182-0252(HEX)|FP182|100386-200594|Write only
3478 |0280-0281(HEX)|FP280|100640-200641|Read only
3479 |0300-030B(HEX)|FP300|100768-200779|Read and write
3480 |0380-039F(HEX)|FP380|100896-200927|Read and write
3481 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3482 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3483 |0600-0670(HEX)|FP600|101536-201814|Read and write
3484 |0720-0738(HEX)|FP720|101824-201848|Read and write
3485 |0800-083F(HEX)|FP800|102048-202111|Read and write
3486 |0900-0952(HEX)|FP900|102304-202386|Read and write
3487 | |Ctrl|0-2|
3488
3489 **✎Note:**
3490
3491 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3492 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3493 * The Ctrl register is used to store the control group number and BCC check mode.
3494
3495 **Ctrl Register Description**
3496
3497 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3498 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3499 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3500 * Ctrl3 reserved
3501
3502 **✎Note:**
3503
3504 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3505
3506 **Cable Wiring**
3507
3508 (% style="text-align:center" %)
3509 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3510
3511 (% style="text-align:center" %)
3512 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3513
3514 **✎Note:** COM3 only available in PI8000/PI9000 series.
3515
3516 == **SR90 protocol** ==
3517
3518 Supported series: SHIMADEN SR90 series
3519
3520 **HMI Setting**
3521
3522 |**Items**|**Settings**|**Note**
3523 |Protocol|SHIMADEN SR90 protocol|
3524 |Connection|RS485 (1200, 1, 7, EVEN)|
3525 |Port No.|None|
3526 |PLC station No.|0|
3527
3528 **Address List**
3529
3530 |**Device address**|**HMI register**|**Address range**|**Type**
3531 |0040-0043 (HEX)|SR040|100064-100067|Read only
3532 |0100-010A(HEX)|SR0100|100256-100266|Read only
3533 |0182-018C(HEX)|SR0182|100386-100396|Write only
3534 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3535 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3536 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3537 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3538 | |Ctrl|0-2|~-~-
3539
3540 **✎Note:**
3541
3542 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3543 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3544 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3545
3546 **Ctrl Register Description**
3547
3548 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3549 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3550 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3551 * Ctrl3 reserved
3552
3553 **✎Note:**
3554
3555 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3556
3557 **Cable Wiring**
3558
3559 (% style="text-align:center" %)
3560 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3561
3562 (% style="text-align:center" %)
3563 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3564
3565 **✎Note:** COM3 only available in PI8000/PI9000 series.
3566
3567 == **MR13 series(standard protocol)** ==
3568
3569 Supported series: SHIMADEN MR13 series
3570
3571 **HMI Setting**
3572
3573 |**Items**|**Settings**|**Note**
3574 |Protocol|SHIMADEN standard protocol|
3575 |Connection|RS485 (1200, 1, 7, EVEN)|
3576 |Port No.|None|
3577 |PLC station No.|0|
3578
3579 **Address List**
3580
3581 |**Device address**|**HMI register**|**Address range**|**Type**
3582 |0100-010B(HEX)|MR100|100256-300267|Read only
3583 |0111-0126(HEX)|MR111|100273-300294|Read only
3584 |0184-0192(HEX)|MR184|100388-300402|Write only
3585 |0280-0282(HEX)|MR280|100640-300642|Read only
3586 |0300-030B(HEX)|MR300|100768-300779|Read/write
3587 |0314-0317(HEX)|MR314|100788-300791|Read/write
3588 |031A(HEX)|MR31A|100794-300794|Read/write
3589 |0320-0321(HEX)|MR320|100800-300801|Read/write
3590 |0400-0504(HEX)|MR400|101024-301284|Read/write
3591 |0506(HEX)|MR506|101286-301286|Read/write
3592 |0510-0514(HEX)|MR510|101296-301300|Read/write
3593 |0516-0524(HEX)|MR516|101302-301316|Read/write
3594 |0526(HEX)|MR526|101318-301318|Read/write
3595 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3596 |~-~-|Ctrl|0-2|~-~-
3597
3598 **✎Note:**
3599
3600 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3601 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3602 * The Ctrl register is used to store the control group number and BCC check mode.
3603
3604 **Ctrl Register Description**
3605
3606 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3607 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3608 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3609 * Ctrl3 reserved
3610
3611 **✎Note:**
3612
3613 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3614
3615 **Cable Wiring**
3616
3617 (% style="text-align:center" %)
3618 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3619
3620 (% style="text-align:center" %)
3621 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3622
3623 **✎Note:** COM3 only available in PI8000/PI9000 series.
3624
3625 = **Printer** =
3626
3627 == **TSPL label printer** ==
3628
3629 **Introduction**
3630
3631 TSPL label printer protocol supports following models.
3632
3633 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3634 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3635
3636 **Setting Step**
3637
3638 Select the protocol
3639
3640 * Create a new project, select the TSPL label printer protocol as shown below.
3641
3642 (% style="text-align:center" %)
3643 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3644
3645 Set parameters
3646
3647 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3648
3649 Printer register
3650
3651 (% class="table-bordered" %)
3652 |**Register**|**System**|**Range**|**Function**
3653 |TSPL_SP|decimal|0 - 1|Set the paper size
3654 |TSPL_PT|decimal|0 - 1999|Print text
3655 |TSPL_PQ|decimal|0 - 999|Print QR code
3656 |TSPL_PB|decimal|0 - 999|Print barcode
3657 |TSPL_PR|decimal|0 - 1|Print offset
3658 |TSPL_PN|decimal|0 - 0|Trigger printing
3659 |TSPL_PS|decimal|0 - 0|Print status
3660
3661 * Set paper size:
3662 ** TSPL_SP0: width of paper, unit: mm.
3663 ** TSPL_SP1: height of paper, unit: mm.
3664 * Print text:
3665 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3666 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3667
3668 (% class="table-bordered" %)
3669 |**Register**|**Function**|**Description**
3670 |TSPL_PT0|X coordinate|Unit: dot
3671 |TSPL_PT1|Ycoordinate|Unit: dot
3672 |TSPL_PT2|Rotation angle|(((
3673 0: 0 degrees
3674
3675 1: 90 degrees
3676
3677 2: 180 degrees
3678
3679 3: 270 degrees
3680 )))
3681 |TSPL_PT3|Size|Range: 0-3
3682 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3683
3684 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3685
3686 Print QR code:
3687
3688 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3689 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3690
3691 (% class="table-bordered" %)
3692 |**Register**|**Function**|**Description**
3693 |TSPL_PQ0|X coordinate|Unit: dot
3694 |TSPL_PQ1|Ycoordinate|Unit: dot
3695 |TSPL_PQ2|Rotation angle|(((
3696 0: 0 degrees
3697
3698 1: 90 degrees
3699
3700 2: 180 degrees
3701
3702 3: 270 degrees
3703 )))
3704 |TSPL_PQ3|Size|Range: 0-5
3705 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3706
3707 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3708
3709 Print bar code:
3710
3711 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3712 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3713
3714 (% class="table-bordered" %)
3715 |**Register**|**Function**|**Description**
3716 |TSPL_PB0|X coordinate|Unit: dot
3717 |TSPL_PB1|Ycoordinate|Unit: dot
3718 |TSPL_PB2|Rotation angle|(((
3719 0: 0 degrees
3720
3721 1: 90 degrees
3722
3723 2: 180 degrees
3724
3725 3: 270 degrees
3726 )))
3727 |TSPL_PB3|height|Unit: dot
3728 |TSPL_PB4|width|Range:0-2
3729 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3730
3731 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3732
3733 Print offset:
3734
3735 * TSPL_PR0: X coordinate offset, unit: mm;
3736 * TSPL_PR1: Y coordinate offset, unit: mm.
3737
3738 Trigger printing:
3739
3740 * TSPL_PN0 = 1: trigger the printer to start printing.
3741
3742 Printing status:
3743
3744 * TSPL_PS0 = 1: The printing is normal.
3745 * TSPL_PS0 = 1: The printing is abnormal.
3746
3747 Print picture
3748
3749 * For the function of printing pictures, please refer to the configuration of [Printer object].
3750
3751 Conversion between dot and mm
3752
3753 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3754
3755 == **EpsonTM series** ==
3756
3757 **HMI Settings**
3758
3759 (% class="table-bordered" %)
3760 |**Item**|**Settings**|**Note**
3761 |Protocol|EPSON-TM-T82II/TM-XXX|
3762 |Connection|RS232|
3763 |Baud rate|9600~~115200|
3764 |Data bit|8|
3765 |Parity|None|
3766 |Stop bit|1|
3767 |PLC station No.|1|
3768
3769 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3770
3771 **Printer Settings**
3772
3773 (% class="table-bordered" %)
3774 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3775 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3776 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3777 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3778 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3779 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3780 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3781
3782 **Cable Wiring**
3783
3784 (% style="text-align:center" %)
3785 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3786
3787 (% style="text-align:center" %)
3788 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3789
3790 **✎Note:** COM3 only available in PI8000/PI9000 series.
3791
3792
3793 = Create communication with **Schneider PLC** =
3794
3795 == **Schneider MODBUS RTU** ==
3796
3797 **HMI Setting**
3798
3799 |=**Parameters**|=**Recommended**|=**Notes**
3800 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3801 |Connection|RS485|
3802 |**Baud rate**|19200|
3803 |**Data bit**|8|
3804 |**Parity**|Even|
3805 |**Stop bit**|1|
3806 |**PLC station No.**|1|
3807
3808 **PLC Setting**
3809
3810 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3811
3812 **Device Address**
3813
3814 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3815 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3816 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3817 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3818 |W|MW|DDDDDD|0 ~~ 999999|Output register
3819 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3820
3821 **Wiring Diagram**
3822
3823 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3824
3825 (% style="text-align:center" %)
3826 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3827
3828 = **Barcode Scanner** =
3829
3830 Supported: DELI 14880 barcode scanner
3831
3832 **HMI Setting**
3833
3834 |**Items**|**Settings**|**Note**
3835 |Protocol|Barcode Scanner|
3836 |Connection|USB|
3837
3838 **Operating Procedures**
3839
3840 Select [Barcode Scanner];
3841
3842 (% style="text-align:center" %)
3843 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3844
3845 Set address for receiving;
3846
3847 Set correct length;
3848
3849 (% style="text-align:center" %)
3850 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3851
3852 **✎Note:**
3853
3854 * The protocol uploads the information acquired by the USB scanner to the HMI;
3855 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3856 * Recommended model: DELI 14880 barcode scanner;
3857
3858 = **Hitachi EHV Series (Ethernet)** =
3859
3860 Supported series: Hitachi EHV series
3861
3862 **HMI Settings**
3863
3864 (% class="table-bordered" %)
3865 |**Items**|**Settings**|**Note**
3866 |Protocol|Hitachi EHV series|
3867 |Connection|Ethernet|
3868 |Port No.|3004~~3007|
3869
3870 **Address List**
3871
3872 (% class="table-bordered" %)
3873 |**Type**|**Register**|**Range**|**Format**|**Note**
3874 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3875 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3876 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3877 H1H2H3H4 Module main number
3878
3879 H1: Remote number
3880
3881 H2: Unit number
3882
3883 H3: Slot number
3884
3885 H4: Word number of Module
3886
3887 H Sub number of Module
3888
3889 For example:X21.3
3890
3891 Slot number 2
3892
3893 Word number of module is 1
3894
3895 Bit number of module is 3
3896
3897 Remote number and unit number are 0
3898 )))
3899 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3900 |R|0 – FF.f (Hex)|R HH.h|
3901 |L|0 - 73FF.f (Hex)|L HHHH.h|
3902 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3903 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3904 H1H2H3H4 Module main number
3905
3906 H1: Remote number
3907
3908 H2: Unit number
3909
3910 H3: Slot number
3911
3912 H4: Word number of module
3913
3914 For example:WX21
3915
3916 Word number of module is 1
3917
3918 Slot number is 2
3919
3920 Remote number and unit number are 0
3921 )))
3922 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3923 |WR|0 – FFFF (Hex)|WR HHHH|
3924 |WL|0 - 73FF (Hex)|WL HHHH|
3925 |TC|0 - 2559|TC DDDD|
3926
3927 **Communication settings in HMI**
3928
3929 Enable HMI Ethernet in [Project Settings];
3930
3931 (% style="text-align:center" %)
3932 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3933
3934 Set PLC IP in [Device IP] settings;
3935
3936 (% style="text-align:center" %)
3937 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3938
3939 **PLC Configuration**
3940
3941 Connect with PLC, select[Online mode];
3942
3943 (% style="text-align:center" %)
3944 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3945
3946 Set IP address, it is the same LAN parameters with HMI;
3947
3948 (% style="text-align:center" %)
3949 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3950
3951 3) Save PLC communication parameter, and restart PLC
3952
3953 **PLC Monitor Mode**
3954
3955 Connect with PLC and choose to “online” mode
3956
3957 (% style="text-align:center" %)
3958 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3959
3960 Open I/O monitor sheet1
3961
3962 (% style="text-align:center" %)
3963 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3964
3965 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3966
3967 (% style="text-align:center" %)
3968 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3969
3970 Enter the register address, click OK to view the value of the register.
3971
3972 (% style="text-align:center" %)
3973 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3974
3975 (% style="text-align:center" %)
3976 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3977
3978 **✎Note:**
3979
3980 * Both word registers and bit registers support even continuous read/write functions;
3981 * The range of registers is based on the specific PLC type;
3982
3983 **Cable Wiring**
3984
3985 (% style="text-align:center" %)
3986 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3987
3988 = **IEC60870-5 104 Client** =
3989
3990 **HMI Setting**
3991
3992 (% class="table-bordered" %)
3993 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3994 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3995 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3996 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3997
3998 **Address List**
3999
4000 (% class="table-bordered" %)
4001 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4002 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4003 |(% style="width:461px" %)SCNA|0~~16777215.7
4004 |(% style="width:461px" %)DPTB|0~~16777215.7
4005 |(% style="width:461px" %)DCNA|0~~16777215.7
4006 |(% style="width:461px" %)METF|0~~16777215.7
4007 |(% style="width:461px" %)SENC|0~~16777215.7
4008 |(% style="width:461px" %)SENA|0~~16777215.7
4009 |(% style="width:461px" %)MENA|0~~16777215.7
4010 |(% style="width:461px" %)METD|0~~16777215.7
4011 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4012 |(% style="width:461px" %)SCNA|0~~16777215
4013 |(% style="width:461px" %)DPTB|0~~16777215
4014 |(% style="width:461px" %)DCNA|0~~16777215
4015 |(% style="width:461px" %)SENA|0~~16777215
4016 |(% style="width:461px" %)MENA|0~~16777215
4017 |(% style="width:461px" %)METD|0~~16777215
4018 |(% style="width:461px" %)INRO|0~~16777215
4019 |(% style="width:461px" %)TIMESYN|0~~16777215
4020 |(% style="width:461px" %)TIMEZ|0~~16777215
4021 |(% style="width:461px" %)NTP|0~~16777215
4022 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4023 |(% style="width:461px" %)SENC|0~~16777215
4024
4025 **Address Configuration**
4026
4027 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4028
4029 (% style="text-align:center" %)
4030 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4031
4032 (% style="text-align:center" %)
4033 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4034
4035 Extended tag name
4036
4037 Address range for the extended tag.
4038
4039 **Communication Settings**
4040
4041 Enable HMI Ethernet in [Project Settings];
4042
4043 (% style="text-align:center" %)
4044 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4045
4046 Set PLC IP in [Device IP] settings;
4047
4048 (% style="text-align:center" %)
4049 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4050
4051 **Cable Wiring**
4052
4053 (% style="text-align:center" %)
4054 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4055
4056 = **OpenCAN** =
4057
4058 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4059
4060 This protocol is only available in PI8000 series HMI.
4061
4062 **HMI Settings**
4063
4064 |**Items**|**Settings**|**Note**
4065 |Protocol|OPENCAN|
4066 |Connection|CAN port|
4067 |Baud rate|250000|
4068
4069 **CAN frame setting in HMI**
4070
4071 Click [OpenCAN setting] button in communication setting window;
4072
4073 (% style="text-align:center" %)
4074 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4075
4076 Click [Add] to create a new frame;
4077
4078 (% style="text-align:center" %)
4079 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4080
4081 |**No**|**Items**|**Description**
4082 |1|Add|add a frame related to register address
4083 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4084 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4085 |4|Modify|Modify the frames in frame management
4086 |5|Copy|Copy one frame to another
4087 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4088 |7|Empty|All frames in the list are cleared
4089 |8|Browse|Displays configuration files in XML format in IE
4090 |9|OK|Complete the configuration of the frame and exit
4091
4092 Set CANBUS frame in setting windows
4093
4094 (% style="text-align:center" %)
4095 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4096
4097 |**No**|**Items**|**Description**
4098 |1|ID|Set the ID of a can frame in hexadecimal format;
4099 |2|ID assign|split the ID by PF, PS, and SA;
4100 |3|Frame type|Select Standard frame or Extended Frame;
4101 |4|Frame format|Select between data frame and remote Frame;
4102 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4103 |6|Use address|(((
4104 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4105
4106 **Edit:** Set a bit or word address by its format;
4107
4108 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4109 )))
4110 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4111 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4112 |Feedback mode: feedback mode includes no response, confirm response and data response;
4113 |No response: the device or touch screen will not receive feedback;
4114 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4115 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4116 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4117 |Response timeout: sets whether the response frame timeout;
4118 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4119 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4120 |Manually send: a manually send tick indicates only one send;
4121 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4122 |10|Note|Fill the text to explain the meaning of the frame;
4123 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4124 |12|Current operation display|Display the description of current operation;
4125 |13|Add|Add a new frame;
4126 |14|Save frame|Save the configured frame format;
4127 |15|Cancel|Cancel the frame configuration;
4128
4129 Set CAN address (Read or write operation);
4130
4131 (% style="text-align:center" %)
4132 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4133
4134 |**No.**|**Item**|**Description**
4135 |1|Current address|Displays the register type and register address set by the user in the data access interface
4136 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4137 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4138 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4139 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4140 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4141 |If the trigger condition is a writing operation, there are two situations:(((
4142 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4143 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4144 )))
4145 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4146 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4147 |4|Add|Add current configuration
4148 |5|Close|Close the configuration window to exit
4149
4150 **Multiple Packages Settings**
4151
4152 (% style="text-align:center" %)
4153 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4154
4155 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4156
4157 Select Multiple package type
4158
4159 * Not Multiple packages
4160 * J1939 Multiple packages
4161 * Customized Multiple packages
4162
4163 Click [Edit Receive data] for [Receive] settings
4164
4165 * Start code+ Total length (J1939)
4166
4167 (% style="text-align:center" %)
4168 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4169
4170 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4171
4172 * Start code + Data max length (J1939)
4173
4174 (% style="text-align:center" %)
4175 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4176
4177 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4178
4179 * Data max length (J1939)
4180
4181 (% style="text-align:center" %)
4182 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4183
4184 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4185
4186 * Customized multiple package
4187
4188 (% style="text-align:center" %)
4189 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4190
4191 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4192
4193 Click [Edit Send data] for [Send] setting
4194
4195 * J1939
4196
4197 (% style="text-align:center" %)
4198 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4199
4200 [Data] is all data to be sent.
4201
4202 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4203
4204 * Customized multiple package
4205
4206 (% style="text-align:center" %)
4207 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4208
4209 [Data] is all data to be sent.
4210
4211 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4212
4213 **Cable Wiring**
4214
4215 (% style="text-align:center" %)
4216 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4217
4218 **✎Note:** The address interval between each frame need to be more than a word address;
4219
4220
4221 = **User Defined Protocol** =
4222
4223 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4224
4225 **HMI Settings**
4226
4227 |**Items**|**Settings**|**Note**
4228 |Protocol|User defined protocol|
4229 |Connection|RS485/RS232|
4230 |Baud rate|2400~~187500|
4231 |Stop bits|1/ 2|
4232 |Data bits|7/ 8|
4233 |Parity|None/ Even/ ODD|
4234
4235 **Operating Procedures**
4236
4237 Select [User defined protocol];
4238
4239 Click [User defined protocol] button to open setting window as below;
4240
4241 (% style="text-align:center" %)
4242 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4243
4244 Configure user defined command;
4245
4246 (% style="text-align:center" %)
4247 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4248
4249 |**No**|**Item**|**Description**
4250 |1|Instruction edit|The required command.
4251 |2|Mode|Write to address or read from the address.
4252 |3|Format|Encode format: HEX or ASCII.
4253 |4|Other|(((
4254 **No receiving: **HMI does not respond to the receiving command.
4255
4256 **Send after receiving:** HMI responds to the receiving command.
4257 )))
4258 |5|Manually send|(((
4259 Respond once after trigger the address.
4260
4261 Address: set the trigger address.
4262 )))
4263 |6|Add|Save this setting.
4264 |7|Cancel|Cancel current settings.
4265 |(% rowspan="4" %)8|Add|Add a new command.
4266 |Edit|Edit the selected command.
4267 |Delete|Delete the selected command.
4268 |Clear|Clear all the commands.
4269 |9|Instruction list|Display all current commands.
4270 |10|Address List|Display all the addresses added.
4271 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4272 |Export|Export current command settings to local storage.
4273 |Browse|Browse local command files.
4274 |Advanced|Combine two commands.
4275 |Exit|Complete editing and exit setting.
4276
4277 **Operating Procedures**
4278
4279 Click [Add] to create a new command, as below shows;
4280
4281 (% style="text-align:center" %)
4282 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4283
4284 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4285
4286 (% style="text-align:center" %)
4287 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4288
4289 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4290
4291 (% style="text-align:center" %)
4292 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4293
4294 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4295
4296 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4297
4298 Check settings;
4299
4300 (% style="text-align:center" %)
4301 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4302
4303 |**No**|**Items**|**Description**
4304 |1|Add checking|Add checking command when receiving the data.
4305 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4306 |Differ with send check|Set return checking.
4307 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4308 |Length: The data length need to be checked.
4309
4310 Object settings;
4311
4312 (% style="text-align:center" %)
4313 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4314
4315 |**No**|**Items**|**Description**
4316 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4317 |Address: the triggering address;
4318 |Note: description to object;
4319 |2|Byte order|The numerical display order;
4320
4321 Data length settings;
4322
4323 (% style="text-align:center" %)
4324 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4325
4326 |**No**|**Item**|**Description**
4327 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4328 |Length: the return data length.
4329 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4330 |Length: the write data length.
4331
4332 Instruction length settings
4333
4334 (% style="text-align:center" %)
4335 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4336
4337 |**No**|**Item**|**Description**
4338 |1|Send length|The instruction data will only send designated data length.
4339 |2|Return length|The responds data length.
4340 |3|End code|Instruction will not be terminated until receiving [End code];
4341
4342 **Cable Wiring**
4343
4344 * **RS485**
4345
4346 (% style="text-align:center" %)
4347 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4348
4349 (% style="text-align:center" %)
4350 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4351
4352 * **RS232**
4353
4354 (% style="text-align:center" %)
4355 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4356
4357 **✎Note:** COM3 only available in PI8000/PI9000 series.