Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 258.1 by Hunter on 2023/05/19 17:59

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with HollySys PLC** =
910
911 == **LK MODBUS RTU** ==
912
913 **HMI Settings**
914
915 |=Item|=Recommended|=Note
916 |=Protocol|HollySys LK MODBUS RTU|
917 |=Connection|RS485|
918 |=Baud rate|38400|
919 |=Stop bits|1|
920 |=Data bits|8|
921 |=Parity|NONE|
922 |=PLC Station No.|1|
923 |=HMI Station No.|0|
924
925 **Address List**
926
927 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
928 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
929 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
930 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
931 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
932 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
933 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
934 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
935
936 **Cable Wiring**
937
938 (% style="text-align:center" %)
939 [[image:Hollysys485.png]]
940
941 = **Create communication with Inovance PLC** =
942
943 == **H1U/H2U serial protocol** ==
944
945 **HMI Settings**
946
947 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
948 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
949 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
950 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
951 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
952 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
953 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
954 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
955 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
956
957 (% class="wikigeneratedid" %)
958 **Address List**
959
960 (% style="width:1014px" %)
961 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
962 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
963 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
964 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
965 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
966 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
967 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
968 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
969 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
970 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
971 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
972 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
973 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
974 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
975 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
976 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
977 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
978 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
979
980 (% class="wikigeneratedid" %)
981 **Cable Wiring**
982
983 (% style="text-align:center" %)
984 [[image:Inovance.png]]
985
986 == **H3U serial protocol** ==
987
988 **HMI Settings**
989
990 |=**Item**|=**Settings**|=**Note**
991 |Protocol|INOVANCE H3U PLC|
992 |Connection|RS422|
993 |Baud rate|9600|
994 |Data bit|7|
995 |Parity|EVEN|
996 |Stop bit|1|
997 |PLC station No.|0|
998
999 **Address List**
1000
1001 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1002 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1003 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1004 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1005 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1006 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1007 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1008 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1009 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1010 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1011 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1012 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1013 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1014 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1015 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1016 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1017 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1018 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1019 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1020
1021 **Configure the communication protocol**
1022
1023 (% style="text-align:center" %)
1024 [[image:image-20220830170114-4.png]]
1025
1026 [[image:image-20220830170017-3.png]]
1027
1028 **Cable Wiring**
1029
1030 (% style="text-align:center" %)
1031 [[image:Inovance.png]]
1032
1033 == **H3U Ethernet portocol** ==
1034
1035 **HMI Settings**
1036
1037 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1038 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1039 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1040 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1041 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1042 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1043
1044 **Address List**
1045
1046 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1047 |Bit|M|M DDDD|0~~8511|
1048 |Bit|SM|SM DDDD|0~~1023|
1049 |Bit|S|S DDDD|0~~4095|
1050 |Bit|T|T DDD|0~~511|
1051 |Bit|C|C DDD|0~~255|
1052 |Bit|X|X OOO|0~~571|
1053 |Bit|Y|Y OOO|0~~571|
1054 |Word|D|D DDDD|0~~8511|
1055 |Word|SD |SD DDDD|0~~1023|
1056 |Word|R|R DDDDD|0~~32767|
1057 |Word|T|T DDD|0~~255|
1058 |Word|C|C DDD|0~~199|
1059 |Double Word|C|C DDD|200~~255|
1060
1061 **Cable Wiring**
1062
1063 (% style="text-align:center" %)
1064 [[image:CommonEthernet.png]]
1065
1066 = Create communication with LS** PLC** =
1067
1068 == **XGB serial protocol ** ==
1069
1070 **HMI Settings**
1071
1072 |=**Item**|=**Settings**|=**Note**
1073 |Protocol|LS XGB CPU DRIECT|
1074 |Connection|RS232|
1075 |Baud rate|115200|
1076 |Data bit|8|
1077 |Parity|NONE|
1078 |Stop bit|1|
1079 |PLC station No.|1|
1080
1081 **Address List**
1082
1083 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1084 |Bit|P|P|P DDDD.f|0~~2047|
1085 |Bit|M|M|M DDDD.f|0~~2047|
1086 |Bit|L|L|L DDDDD.f|0~~11263|
1087 |Bit|K|K|K DDDD.f|0~~2559|
1088 |Bit|F|F|F DDDD.f|0~~2047|
1089 |Bit|S|S|S DDDDD|0~~12799|
1090 |Bit|D|D|D DDDDD.f|0~~32767|
1091 |Bit|U|U|U FFFF.f|0~~7f31|
1092 |Bit|T|T|T DDDD.f|0~~2047|
1093 |Bit|C|C|C DDDD.f|0~~2047|
1094 |Word|P|P|P DDDD|0~~2047|
1095 |Word|M|M|M DDDD|0~~2047|
1096 |Word|L|L|L DDDDD|0~~11263|
1097 |Word|K|K|K DDDD|0~~2559|
1098 |Word|F|F|F DDDD|0~~2047|
1099 |Word|C|C|C DDDD|0~~2047|
1100 |Word|T|T|T DDDD|0~~2047|
1101 |Word|D|D|D DDDDD|0~~32767|
1102 |Word|N|N|N DDDDD|0~~21503|
1103 |Word|U|U|U FFFF|0~~7f31|
1104 |Word|Z|Z|Z DDD|0~~127|
1105 |Word|R|R|R DDDDD|0~~32767|
1106 |Word|ZR|ZR|Z DDDDD|0~~32767|
1107 |Word|TS|TS|TS DDDD|0~~2047|
1108 |Word|CS|CS|CS DDDD|0~~2047|
1109 |Word|S|S|S DDDDD|0~~12799|
1110
1111 **Configure the communication protocol**
1112
1113 (% style="text-align:center" %)
1114 [[image:image-20221028174410-1.png]]
1115
1116 (% style="text-align:center" %)
1117 [[image:image-20221028174753-2.png]]
1118
1119 (% style="text-align:center" %)
1120 [[image:image-20221028181125-4.png]]
1121
1122 **Pin Definition Diagram**
1123
1124 (% style="text-align:center" %)
1125 [[image:image-20221028180930-3.png]]
1126
1127 == **XBC serial protocol** ==
1128
1129 **HMI Settings**
1130
1131 |=**Item**|=**Settings**|=**Note**
1132 |Protocol|LS XBC CNet|
1133 |Connection|RS232|
1134 |Baud rate|115200|
1135 |Data bit|8|
1136 |Parity|NONE|
1137 |Stop bit|1|
1138 |PLC station No.|1|
1139
1140 **Address List**
1141
1142 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1143 |Bit|P|P|P d|0~~2047|
1144 |Bit|M|M|M d|0~~2047|
1145 |Bit|L|L|L d|0~~11263|
1146 |Bit|K|K|K d|0~~16183|
1147 |Bit|F|F|F d|0~~2047|
1148 |Bit|D|D|D d|0~~32767|
1149 |Bit|R|R|R d|0~~32767|
1150 |Bit|U|U|U d|0~~4095|
1151 |Word|P|P|P d|0~~2047|
1152 |Word|M|M|M d|0~~2047|
1153 |Word|L|L|L d|0~~11263|
1154 |Word|K|K|K d|0~~16183|
1155 |Word|F|F|F d|0~~2047|
1156 |Word|C|C|C d|0~~2047|
1157 |Word|T|T|T d|0~~2047|
1158 |Word|D|D|D d|0~~32767|
1159 |Word|N|N|N d|0~~21503|
1160 |Word|R|R|R d|0~~32767|
1161 |Word|U|U|U d|0~~4095|
1162 |Word|Z|Z|Z d|0~~127|
1163 |Word|S|S|S d|0~~127|
1164
1165 **Configure the communication protocol**
1166
1167 (% style="text-align:center" %)
1168 [[image:image-20220831170807-1.png]]
1169
1170 (% style="text-align:center" %)
1171 [[image:image-20220830174733-2.png]]
1172
1173 **Cable Wiring**
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20220830174659-1.png]]
1177
1178 Pin Definition Diagram
1179
1180 (% style="text-align:center" %)
1181 [[image:image-20220830173402-8.png]]
1182
1183 == **XGK FEnet Ethernet protocol** ==
1184
1185 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1186
1187 **HMI Settings**
1188
1189 |**Items**|**Settings**|**Note**
1190 |Protocol|LG XGK FEnet(Ethernet)|
1191 |Connection|Ethernet|
1192 |Port No.|2004|
1193
1194 **Address List**
1195
1196 |**Type**|**Register**|**Range**|**Format**|**Note**
1197 |(% rowspan="14" %)Word|P|0~~2047|P d|
1198 |M|0~~2047|M d|
1199 |K|0~~2047|K d|
1200 |F|0~~2047|F d|
1201 |T|0~~2047|T d|
1202 |C|0~~2047|C d|
1203 |Z|0~~127|Z d|
1204 |S|0~~127|S d|
1205 |L|0~~11263|L d|
1206 |N|0~~21503|N d|
1207 |D|0~~32767|D d|
1208 |R|0~~32767|R d|
1209 |ZR|0~~65535|ZR d|
1210 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1211
1212 **✎Note:**
1213
1214 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1215 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1216 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1217
1218 **Communication settings in HMI**
1219
1220 Enable HMI Ethernet in [Project Settings];
1221
1222 (% style="text-align:center" %)
1223 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1224
1225 Set PLC IP in [Device IP] settings;
1226
1227 (% style="text-align:center" %)
1228 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1229
1230 **Cable Wiring**
1231
1232
1233 (% style="text-align:center" %)
1234 [[image:CommonEthernet.png]]
1235
1236 = Create communication with **Mitsubishi PLC** =
1237
1238 == **FX1S, 1N, 2N Series Protocol** ==
1239
1240 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1241
1242 **HMI Settings**
1243
1244 |**Item**|**Settings**|**Note**
1245 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1246 |Connection|RS422/RS485/RS232|
1247 |Baud rate|9600~~115200|
1248 |Data bit|7/8|
1249 |Parity|EVEN/Odd/None|
1250 |Stop bit|1/2|
1251 |PLC station No.|1~~255|
1252
1253 **Address List**
1254
1255 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1256 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1257 |Y|Y|Y o|0~~303237|
1258 |M|M|M d|0~~99999|
1259 |T|T|T d|0~~99999|
1260 |C|C|C d|0~~99999|
1261 |S|S|S d|0~~99999|
1262 |SM|SM|SM d|8000~~9999|
1263 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1264 |Y|Y|Y o|0~~303237|
1265 |M|M|M d|0~~99999|
1266 |T|T|T d|0~~99999|
1267 |C|C|C d|0~~199|
1268 |D|D|D d|0~~7999|
1269 |S|S|S d|0~~99999|
1270 |SD|SD|SD d|8000~~9999|
1271
1272 **Cable Wiring**
1273
1274 * **RS485**
1275
1276 (% style="text-align:center" %)
1277 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1278
1279 (% style="text-align:center" %)
1280 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1281
1282 * **RS422**
1283
1284 (% style="text-align:center" %)
1285 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1286
1287 **✎Note:** COM3 only available in PI8000/PI9000 series.
1288
1289 == **FX3U/3G/3GA serial protocol** ==
1290
1291 **HMI Settings**
1292
1293 |=**Item**|=**Settings**|=**Note**
1294 |Protocol|Mitsubishi FX3U/3G/3GA|
1295 |Connection|RS422|
1296 |Baud rate|9600~~115200|
1297 |Data bit|7/8|
1298 |Parity|EVEN/Odd/None|
1299 |Stop bit|1/2|
1300 |PLC station No.|1~~255|
1301
1302 **Address List**
1303
1304 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1305 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1306 |Y|Y|Y o|0~~303237|
1307 |M|M|M d|0~~99999|
1308 |T|T|T d|0~~99999|
1309 |C|C|C d|0~~99999|
1310 |S|S|S d|0~~99999|
1311 |SM|SM|SM d|8000~~9999|
1312 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1313 |Y|Y|Y o|0~~303237|
1314 |M|M|M d|0~~99999|
1315 |T|T|T d|0~~99999|
1316 |C|C|C d|0~~199|
1317 |D|D|D d|0~~7999|
1318 |S|S|S d|0~~99999|
1319 |SD|SD|SD d|8000~~9999|
1320
1321 **Configure the communication protocol**
1322
1323 (% style="text-align:center" %)
1324 [[image:image-20220831095222-1.png]]
1325
1326 (% style="text-align:center" %)
1327 [[image:image-20220831095743-2.png]]
1328
1329 **Wiring**
1330
1331 (% style="text-align:center" %)
1332 [[image:image-20220831100314-6.png]]
1333
1334 == **FX3U Ethernet Protocol** ==
1335
1336 Mitsubishi FX3U series PLC
1337
1338 **HMI Settings**
1339
1340 |Items|Settings|Note
1341 |Protocol|Mitsubishi FX3U|
1342 |Connection|Ethernet|
1343 |Port No.|5009|Must be the same as the PLC setting
1344 |PLC station No.|0|
1345
1346 **Address List**
1347
1348 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1349 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1350 |Y|Y|Y OOO|0~~377|
1351 |M|M|M DDDD|0~~7679|
1352 |SM|SM|SM DDDD|8000~~8511|
1353 |S|S|S DDDD|0~~4095|
1354 |TS|TS|TS DDD|0~~511|
1355 |CS|CS|CS DDD|0~~255|
1356 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1357 |TN|TN|TN DDD|0~~511|
1358 |D|D|D DDDD|0~~7999|
1359 |SD|SD|SD DDDD|8000~~8511|
1360 |R|R|R DDDDD|0~~32767|
1361
1362 **Ethernet Module Settings**
1363
1364 FX3U-ENET-L module configuration
1365 Set up the FX3U-ENET-L Ethernet module settings as follows.
1366 Select the module location, which in this document is Module 0.
1367
1368 [[image:image-20221115140802-1.png]]
1369
1370 Select "Operational setting" to enter the following screen.
1371
1372 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1373
1374 [[image:image-20221115142728-4.png]]
1375
1376 Select "Open setting" to enter the setting interface, the settings are as follows.
1377
1378 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1379
1380 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1381
1382 [[image:image-20221115142945-5.png]]
1383
1384 Click on "transter setup" - "PC side I/F setting", see the following figure.
1385
1386 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1387
1388 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1389
1390 [[image:image-20221115143341-6.png||height="426" width="712"]]
1391
1392 Read and write data from the Ethernet module
1393
1394 [[image:image-20221115143703-7.png]]
1395
1396 Set "Transter setup" to COM communication, and read or write operation as shown below
1397
1398 [[image:image-20221115143809-8.png]]
1399
1400 **PLC Settings (GX Works 2)**
1401
1402 Create a blank FX5U project
1403
1404 Find Current Connection in the navigation
1405
1406 [[image:image-20221115144335-9.png||height="422" width="706"]]
1407
1408 Select Connection Channel List
1409
1410 Select Ethernet board communication
1411
1412 [[image:image-20221115144824-10.png||height="421" width="705"]]
1413
1414 Select Ethernet Module
1415 Set the IP address of the PLC
1416
1417 [[image:image-20221115145228-11.png||height="674" width="708"]]
1418
1419 Read or write PLC data, in this document is read
1420
1421 [[image:image-20221115145553-12.png||height="424" width="711"]]
1422
1423 [[image:image-20221115145559-13.png||height="424" width="711"]]
1424
1425 **HMI Communication Setting**
1426
1427 [[image:image-20221115150003-14.png||height="425" width="712"]]
1428
1429 [[image:image-20221115150235-15.png||height="427" width="713"]]
1430
1431 [[image:image-20221115145559-13.png||height="424" width="711"]]
1432
1433 **HMI Communication Setting**
1434
1435 [[image:image-20221115150003-14.png||height="425" width="712"]]
1436
1437 [[image:image-20221115150235-15.png||height="427" width="713"]]
1438
1439 == **FX5U Serial Port Protocol** ==
1440
1441 Mitsubishi FX5U series PLC
1442
1443 **HMI Settings**
1444
1445 |**Item**|**Settings**|**Note**
1446 |Protocol|Mitsubishi FX5U|
1447 |Connection|RS422/RS485|
1448 |Baud rate|9600|
1449 |Data bit|7|
1450 |Parity|Odd|
1451 |Stop bit|1|
1452 |PLC station No.|1~~255|Need to be the same as PLC settings
1453
1454 **Address List**
1455
1456 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1457 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1458 |Y|Y|Y o|0~~303237|
1459 |M|M|M d|0~~99999|
1460 |B|B|B h|0~~7FFF|
1461 |F|F|F d|0~~32767|
1462 |SB|SB|SB h|0~~7FFF|
1463 |TS|TS|TS d|0~~1023|
1464 |TC|TC|TC d|0~~1023|
1465 |STS|STS|STS d|0~~1023|
1466 |STC|STC|STS d|0~~1023|
1467 |CS|CS|CS d|0~~1023|
1468 |CC|CC|CC d|0~~1023|
1469 |SM|SM|SM d|0~~9999|
1470 |L|L|L d|0~~32767|
1471 |S|S|S d|0~~4095|
1472 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1473 |TN|TN|TN d|0~~1023|
1474 |STN|STN|STN d|0~~1023|
1475 |CN|CN|CN d|0~~1023|
1476 |R|R|R d|0~~32767|
1477 |SW|SW|SW h|0~~7FFF|
1478 |Z|Z|Z d|0~~23|
1479 |D|D|D d|0~~7999|
1480 |SD|SD|SD d|0~~11999|
1481
1482 **PLC Settings (GX Works 3)**
1483
1484 Create a blank FX5U project
1485
1486 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1487
1488 (% style="text-align:center" %)
1489 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1490
1491 Select protocol in the setting item, and set parameters.
1492
1493 (% style="text-align:center" %)
1494 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1495
1496 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1497
1498 (% style="text-align:center" %)
1499 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1500
1501 Click the [Apply] button to finish the setting.
1502
1503 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1504
1505 (% style="text-align:center" %)
1506 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1507
1508 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1509
1510 Done.
1511
1512 **Cable Wiring**
1513
1514 * **RS485**
1515
1516 (% style="text-align:center" %)
1517 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1518
1519 (% style="text-align:center" %)
1520 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1521
1522 * **RS422**
1523
1524 (% style="text-align:center" %)
1525 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1526
1527 **✎Note:** COM3 only available in PI8000/PI9000 series.
1528
1529 == **L02 Serial Protocol** ==
1530
1531 Mitsubishi L02 series CPU built-in serial port.
1532
1533 **HMI Settings**
1534
1535 |=**Item**|=**Settings**|=**Note**
1536 |Protocol|Mitsubishi L02|
1537 |Connection|RS422|
1538 |Baud rate|115200|
1539 |Data bit|8|
1540 |Parity|Odd|
1541 |Stop bit|1|
1542 |PLC station No.|1~~255|Need to be the same as PLC settings
1543
1544 **Address List**
1545
1546 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1547 |Bit|X|X|X h|0~~FFFF|
1548 |Bit|Y|Y|Y h|0~~FFFF|
1549 |Bit|M|M|M d|0~~9999|
1550 |Bit|L|L|L d|0~~9999|
1551 |Bit|F|F|F d|0~~9999|
1552 |Bit|B|B|B h|0~~FFFF|
1553 |Bit|V|V|V d|0~~2047|
1554 |Bit|TC|TC|TC d|0~~9999|
1555 |Bit|SS|SS|SS d|0~~9999|
1556 |Bit|SC|SC|SC d|0~~9999|
1557 |Bit|CS|CS|CS d|0~~9999|
1558 |Bit|CC|CC|CC d|0~~9999|
1559 |Bit|SB|SB|SB h|0~~FFFF|
1560 |Bit|SM|SM|SM d|0~~2047|
1561 |Bit|STS|STS|STS d|0~~1023|
1562 |Bit|S|S|S d|0~~9999|
1563 |Bit|DX|DX|DX h|0~~FFFF|
1564 |Bit|DY|DY|DY h|0~~FFFF|
1565 |Bit|TS|TS|TS d|0~~9999|
1566 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1567 |Word|W|W|W h|0~~FFFF|
1568 |Word|TN|TN|TN d|0~~99999|
1569 |Word|SN|SN|SN d|0~~99999|
1570 |Word|CN|CN|CN d|0~~99999|
1571 |Word|R|R|R d|0~~99999|
1572 |Word|SW|SW|SW h|0~~FFFF|
1573 |Word|Z|Z|Z d|0~~99999|
1574 |Word|ZR|ZR|ZR h|0~~FFFF|
1575 |Word|D|D|D d|0~~99999|
1576
1577 **Communication Settings**
1578
1579 (% style="text-align:center" %)
1580 [[image:image-20220831105732-3.png]]
1581
1582 (% style="text-align:center" %)
1583 [[image:image-20220831110004-5.png]]
1584
1585 **Cable Wiring**
1586
1587 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1588
1589 Pin Definition Diagram
1590
1591 (% style="text-align:center" %)
1592 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1593
1594 == **L02 MELSEC (Ethernet) Protocol** ==
1595
1596 Mitsubishi Q series CPU built-in Ethernet port.
1597
1598 **HMI Settings**
1599
1600 |**Items**|**Settings**|**Note**
1601 |Protocol|MIT L02 CPU MELSEC|
1602 |Connection|Ethernet|
1603 |Port No.|1025|Must be the same as the PLC setting
1604 |PLC station No.|0|Must be the same as the PLC setting
1605
1606 **Address List**
1607
1608 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1609 |Bit|X|X|X h|0~~FFFF|
1610 |Bit|Y|Y|Y h|0~~FFFF|
1611 |Bit|M|M|M d|0~~9999|
1612 |Bit|L|L|L d|0~~9999|
1613 |Bit|F|F|F d|0~~9999|
1614 |Bit|B|B|B h|0~~FFFF|
1615 |Bit|V|V|V d|0~~2047|
1616 |Bit|TC|TC|TC d|0~~9999|
1617 |Bit|SS|SS|SS d|0~~9999|
1618 |Bit|SC|SC|SC d|0~~9999|
1619 |Bit|CS|CS|CS d|0~~9999|
1620 |Bit|CC|CC|CC d|0~~9999|
1621 |Bit|SB|SB|SB h|0~~FFFF|
1622 |Bit|SM|SM|SM d|0~~2047|
1623 |Bit|STS|STS|STS d|0~~1023|
1624 |Bit|S|S|S d|0~~9999|
1625 |Bit|DX|DX|DX h|0~~FFFF|
1626 |Bit|DY|DY|DY h|0~~FFFF|
1627 |Bit|TS|TS|TS d|0~~9999|
1628 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1629 |Word|W|W|W h|0~~FFFF|
1630 |Word|TN|TN|TN d|0~~99999|
1631 |Word|SN|SN|SN d|0~~99999|
1632 |Word|CN|CN|CN d|0~~99999|
1633 |Word|R|R|R d|0~~99999|
1634 |Word|SW|SW|SW h|0~~FFFF|
1635 |Word|Z|Z|Z d|0~~99999|
1636 |Word|ZR|ZR|ZR h|0~~FFFF|
1637 |Word|D|D|D d|0~~99999|
1638
1639 **Communication Settings**
1640
1641 Enable HMI Ethernet in [Project Settings];
1642
1643 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1644
1645 Set PLC IP in [Device IP] settings;
1646
1647 (% style="text-align:center" %)
1648 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1649
1650 **PLC Settings (GX Works2 )**
1651
1652 Create a project
1653
1654 Set PLC IP, subnet mask and gateway;
1655
1656 Select [Binary Code] as communication data code;
1657
1658 (% style="text-align:center" %)
1659 [[image:image-20221108202109-2.png||height="636" width="732"]]
1660
1661 Set PLC port number, for example 1025
1662
1663 (% style="text-align:center" %)
1664 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1665
1666 Save settings;
1667
1668 Download project into PLC device;
1669
1670 Restart PLC device;
1671
1672 **Cable Wiring**
1673
1674 (% style="text-align:center" %)
1675 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1676
1677 == **QJ71C24N MELSEC Protocol** ==
1678
1679 Mitsubishi QJ71C24N communication module built-in serial port;
1680
1681 **HMI Settings**
1682
1683 |**Items**|**Settings**|**Note**
1684 |Protocol|MIT QJ71 MELSEC|
1685 |Connection|422|
1686 |Baud rate|9600|
1687 |Data bit|8|
1688 |Parity|ODD|
1689 |Stop bit|1|
1690 |PLC station No.|1~~255|Need to be the same as PLC settings
1691
1692 **Address List**
1693
1694 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1695 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1696 |Y|Y|Y FFFF|0~~1FFF|
1697 |M|M|M DDDDD|0~~99999|
1698 |L|L|L DDDD|0~~8191|
1699 |F|F|F DDDD|0~~2047|
1700 |V|V|V DDDD|0~~2047|
1701 |B|B|B FFFF|0~~1FFF|
1702 |TS|TS|TS DDDD|0~~2047|
1703 |TC|TC|TC DDDD|0~~2047|
1704 |SS|SS|SS DDDD|0~~2047|
1705 |SC|SC|SC DDDD|0~~2047|
1706 |CS|CS|CS DDDD|0~~1023|
1707 |CC|CC|CC DDDD|0~~1023|
1708 |SB|SB|SB FFF|0~~7FF|
1709 |S|S|S D|0~~8191|
1710 |DX|DX|DX FFFF|0~~1FFF|
1711 |DY|DY|DY FFFF|0~~1FFF|
1712 |SM_|SM_|SM_ DDDD|8000~~9999|
1713 |SM|SM|SM DDDD|0~~2047|
1714 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1715 |D|D|D DDDDD|0~~12287|
1716 |W|W|W FFFF|0~~1FFF|
1717 |TN|TN|TN DDDD|0~~2047|
1718 |SN|SN|SN DDDD|0~~2047|
1719 |CN|CN|CN DDDD|0~~1023|
1720 |R|R|R DDDDD|0~~32767|
1721 |SW|SW|SW FFF|0~~7FF|
1722 |Z|Z|Z D|0~~15|
1723 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1724
1725 **Communication Settings**
1726
1727 (% style="text-align:center" %)
1728 [[image:image-20221109135738-1.png]]
1729
1730 (% style="text-align:center" %)
1731 [[image:image-20221109140016-3.png]]
1732
1733 Pin Definition Diagram
1734
1735 (% style="text-align:center" %)
1736 [[image:image-20221109140406-4.png]]
1737
1738 == **QJ71E71 MELSEC Protocol** ==
1739
1740 Mitsubishi QJ71E71 Ethernet communication module;
1741
1742 **HMI Settings**
1743
1744 |**Items**|**Settings**|**Note**
1745 |Protocol|MIT QJ71E71 MELSEC|
1746 |Connection|Ethernet|
1747 |Port No.|1025|Must be the same as the PLC setting
1748 |PLC station No.|0|Must be the same as the PLC setting
1749
1750 **Address List**
1751
1752 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1753 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1754 |Y|Y|Y h|0~~1FFF|
1755 |M|M|M d|0~~99999|
1756 |L|L|L d|0~~8191|
1757 |F|F|F d|0~~2047|
1758 |B|B|B h|0~~1FFF|
1759 |V|V|V d|0~~2047|
1760 |TS|TS|TS d|0~~2047|
1761 |TC|TC|TC d|0~~2047|
1762 |SS|SS|SS d|0~~2047|
1763 |SC|SC|SC d|0~~2047|
1764 |CS|CS|CS d|0~~1023|
1765 |CC|CC|CC d|0~~1023|
1766 |SB|SB|SB h|0~~7FF|
1767 |S|S|S d|0~~8191|
1768 |DX|DX|DX h|0~~1FFF|
1769 |DY|DY|DY h|0~~1FFF|
1770 |SM|SM|SM d|8000~~9999|
1771 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1772 |D|D|D d|0~~12287|
1773 |W|W|W h|0~~1FFF|
1774 |TN|TN|TN d|0~~2047|
1775 |SN|SN|SN d|0~~2047|
1776 |CN|CN|CN d|0~~1023|
1777 |R|R|R d|0~~32767|
1778 |SW|SW|SW h|0~~7FF|
1779 |Z|Z|Z d|0~~15|
1780 |ZR|ZR|ZR h|0~~FE7FF|
1781
1782 **HMI Communication Settings**
1783
1784 1) Enable HMI Ethernet in [Project Settings];
1785
1786 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1787
1788 2) Set PLC IP in [Device IP] settings
1789
1790 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1791
1792 **PLC Settings(GX Works2)**
1793
1794 * Click [Ethernet/CC IE/MELSECNET];
1795 * Please select [Ethernet] as network type;
1796 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1797 * Select [Online] as Mode;
1798 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1799 * Click [Operation setting] to set IP;
1800 * Select [Binary Code] as [Communication Data Code];
1801 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1802 * Click [Open setting]
1803 * Set protocol: TCP;
1804 * Set [unpassive] in [Open system];
1805 * Set [receive] in [Fixed buffer];
1806 * Set [procedure Exist] in [Fixed buffer communication];
1807 * Disable [Pairing open];
1808 * Set [No confirm] in [Existence confirmation];
1809 * Host station port number: 5009;
1810 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1811 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1812 * Download project into PLC and restart it
1813
1814 **Cable Wiring**
1815
1816 (% style="text-align:center" %)
1817 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1818
1819 = Create communication with **MODBUS** =
1820
1821 == **MODBUS RTU Master** ==
1822
1823 Supported Series: MODBUS RTU CONTROLLER
1824
1825 HMI works as MODBUS SLAVE connecting with MASTER
1826
1827 (% style="text-align:center" %)
1828 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1829
1830 (% style="text-align:center" %)
1831 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1832
1833 (% style="text-align:center" %)
1834 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1835
1836 **HMI Settings**
1837
1838 |**Items**|**Settings**|**Note**
1839 |Protocol|MODBUS RTU Master|
1840 |Connection|RS485/RS232|
1841 |Baud rate|2400~~187500|
1842 |Data bit|8|
1843 |Parity|Even/ Odd/ None|
1844 |Stop bit|1/2|
1845 |Station No.|0~~255|
1846
1847 **Address List**
1848
1849 |**Type**|**HMI address**|**MODBUS code**|**Range**
1850 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1851 |Word|HDW3500~~HDW7999|4|0~~4499
1852
1853 **Cable Wiring**
1854
1855 * **RS485**
1856
1857 (% style="text-align:center" %)
1858 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1859
1860 (% style="text-align:center" %)
1861 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1862
1863 * **RS232**
1864
1865 (% style="text-align:center" %)
1866 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1867
1868 **✎Note:** COM3 only available in PI8000/PI9000 series.
1869
1870 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1871
1872 Supported Series: MODBUS RTU CONTROLLER
1873
1874 HMI works as MODBUS MASTER connecting with SLAVE.
1875
1876 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1877
1878 (% style="text-align:center" %)
1879 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1880
1881 (% style="text-align:center" %)
1882 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1883
1884 (% style="text-align:center" %)
1885 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1886
1887 **HMI Settings**
1888
1889 |**Items**|**Settings**|**Note**
1890 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1891 |Connection|RS485/RS232|
1892 |Baud rate|2400~~187500|
1893 |Data bit|8|
1894 |Parity|Even/ Odd/ None|
1895 |Stop bit|1/2|
1896 |PLC station No.|0~~255|
1897
1898 **Address List**
1899
1900 |**Type**|**Address Type**|**Function code & Description**
1901 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1902 |06 (write single register: write a binary value to a holding register)
1903 |10 (write values to multiple addresses )
1904 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1905 |06 (write single register: write a binary value to a holding register)
1906 |10 (write values to multiple addresses )
1907 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1908 |06 (write single register: write a binary value to a holding register)
1909 |10 (write values to multiple addresses )
1910 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1911 |10 (write values to multiple addresses )
1912 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1913 |05 (Force a single coil to force the on/off state of a logic coil)
1914 |0F (Write multiple bits, ie write continuously)
1915 |(% rowspan="3" %)1|02 (Read the input state)
1916 |05 (Force a single coil to force the on/off state of a logic coil)
1917 |0F (Write multiple bits)
1918 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1919 |05 (Force a single coil to force the on/off state of a logic coil)
1920 |0F (Write multiple bits)
1921 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1922 |0F (Write multiple bits)
1923
1924 **✎Note:**
1925
1926 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1927 * The function codes sent out are the same as those that read and write words.
1928
1929 **Station number for more than one slaves**
1930
1931 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1932
1933 (% style="text-align:center" %)
1934 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1935
1936 **Cable Wiring**
1937
1938 * **RS485**
1939
1940 (% style="text-align:center" %)
1941 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1942
1943 (% style="text-align:center" %)
1944 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1945
1946 * **RS232**
1947
1948 (% style="text-align:center" %)
1949 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1950
1951 **✎Note:** COM3 only available in PI8000/PI9000 series.
1952
1953 == **Communicate with Modbus Meter** ==
1954
1955 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
1956
1957 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
1958
1959 (% style="text-align:center" %)
1960 [[image:LinfeeDiagram.png]]
1961
1962 2. Check the specific Modbus parameter in the communication menu from LED display.
1963
1964 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
1965
1966 {{info}}
1967 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
1968 {{/info}}
1969
1970 (% style="text-align:center" %)
1971 [[image:MeterModbusAllView.png]]
1972
1973 3. Create new project and change the Communication settings.
1974
1975 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
1976
1977 (% style="text-align:center" %)
1978 [[image:PIStudioSetupMeterModbusPara.png]]
1979
1980 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
1981
1982 The following table is intercept part of the manual for Linfee Modbus manual.
1983
1984 **0x03/0x04 command data register address**:
1985
1986 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
1987 | HEX|DEC| | | |
1988 |0x00|0|Reserved| | |
1989 |0x02|2|Reserved| | |
1990 |0x04|4|Reserved| | |
1991 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
1992 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
1993 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
1994 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
1995 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
1996 |0x10|16|Uca|float|2|Line Voltage data, Unit V
1997 |0x12|18|Ia|float|2|Phase Current data, Unit A
1998 |0x14|20|Ib|float|2|Phase Current data, Unit A
1999 |0x16|22|Ic|float|2|Phase Current data, Unit A
2000
2001 {{info}}
2002 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2003 {{/info}}
2004
2005 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2006
2007 (% style="text-align:center" %)
2008 [[image:MeterModbusPInumericSet.png]]
2009
2010 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2011
2012 (% style="text-align:center" %)
2013 [[image:MeterModbusNumericInputFormat.png]]
2014
2015 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2016
2017 (% style="text-align:center" %)
2018 [[image:ActualHMIModbusResult.jpg]]
2019
2020 == **MODBUS TCP Slave (All function)** ==
2021
2022 Supported series: MODBUS TCP controller
2023
2024 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2025
2026 (% style="text-align:center" %)
2027 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2028
2029 (% style="text-align:center" %)
2030 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2031
2032 (% style="text-align:center" %)
2033 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2034
2035 **HMI Setting**
2036
2037 |**Items**|**Settings**|**Note**
2038 |Protocol|MODBUS TCP Slave (All function)|
2039 |Connection|Ethernet|
2040 |Port No.|502|
2041 |PLC station No.|1|
2042
2043 **Address List**
2044
2045 |**Type**|**Register**|**Function code & Description**
2046 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2047 |06 (write single register: write a binary value to a holding register)
2048 |10 (write values to multiple addresses )
2049 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2050 |06 (write single register: write a binary value to a holding register)
2051 |10 (write values to multiple addresses )
2052 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2053 |06 (write single register: write a binary value to a holding register)
2054 |10 (write values to multiple addresses )
2055 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2056 |10 (write values to multiple addresses )
2057 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2058 |05 (Force a single coil to force the on/off state of a logic coil)
2059 |0F (Write multiple bits, ie write continuously)
2060 |(% rowspan="3" %)1|02 (Read the input state)
2061 |05 (Force a single coil to force the on/off state of a logic coil)
2062 |0F (Write multiple bits)
2063 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2064 |05 (Force a single coil to force the on/off state of a logic coil)
2065 |0F (Write multiple bits)
2066 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2067 |0F (Write multiple bits)
2068
2069 **Communication Settings**
2070
2071 Enable HMI Ethernet in [Project Settings];
2072
2073 (% style="text-align:center" %)
2074 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2075
2076 Set PLC IP in [Device IP] settings;
2077
2078 (% style="text-align:center" %)
2079 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2080
2081 **Cable Wiring**
2082
2083 (% style="text-align:center" %)
2084 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2085
2086 = Create communication with **Omron** PLC =
2087
2088 == CJ TCP FINS Ethemet  Protocol ==
2089
2090 Supported device:CJ series、CJ1W-EIP21
2091
2092 **HMI Settings**
2093
2094 |=**Items**|=**Settings**|=**Note**
2095 |Protocol|OMRON CJ TCP FINS Ethemet|
2096 |Connection|Ethernet|
2097 |Port No.|9600|
2098 |Device No.|0|
2099 |HMI No.|0|(((
2100
2101 )))
2102
2103 **Address List**
2104
2105 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2106 |Bit|CIO|CIO|CIO d|0~~99999|
2107 |Bit|W|W|W d|0~~99999|
2108 |Bit|D|D|D d|0~~99999|
2109 |Bit|H|H|H d|0~~99999|
2110 |Bit|A|A|A d|0~~99999|
2111 |Bit|T|T|T h|0~~99999|
2112 |Bit|CF|CF|CF d|0~~99999|
2113 |Bit|FF|FF|FF d|0~~99999|
2114 |Bit|C|C|C d|0~~99999|
2115 |Bit|EM0|EM0|EM0 d|0~~99999|
2116 |Bit|EM1|EM1|EM1 d|0~~99999|
2117 |Bit|EM2|EM2|EM2 d|0~~99999|
2118 |Bit|EM3|EM3|EM3 d|0~~99999|
2119 |Bit|EM4|EM4|EM4 d|0~~99999|
2120 |Bit|EM5|EM5|EM5 h|0~~99999|
2121 |Bit|EM6|EM6|EM6 d|0~~99999|
2122 |Bit|EM7|EM7|EM7 d|0~~99999|
2123 |Bit|EM8|EM8|EM8 d|0~~99999|
2124 |Bit|EM9|EM9|EM9 d|0~~99999|
2125 |Bit|EMA|EMA|EMA d|0~~99999|
2126 |Bit|EMB|EMB|EMB d|0~~99999|
2127 |Bit|EMC|EMC|EMC d|0~~99999|
2128 |Bit|Lamp|Lamp|Lamp d|0~~0|
2129 |Word|CIO|CIO|CIO d|0~~99999|
2130 |Word|W|W|W d|0~~99999|
2131 |Word|D|D|D d|0~~99999|
2132 |Word|H|H|H d|0~~99999|
2133 |Word|A|A|A d|0~~99999|
2134 |Word|T|T|T h|0~~99999|
2135 |Word|CF|CF|CF d|0~~99999|
2136 |Word|FF|FF|FF d|0~~99999|
2137 |Word|C|C|C d|0~~99999|
2138 |Word|EM0|EM0|EM0 d|0~~99999|
2139 |Word|EM1|EM1|EM1 d|0~~99999|
2140 |Word|EM2|EM2|EM2 d|0~~99999|
2141 |Word|EM3|EM3|EM3 d|0~~99999|
2142 |Word|EM4|EM4|EM4 d|0~~99999|
2143 |Word|EM5|EM5|EM5 h|0~~99999|
2144 |Word|EM6|EM6|EM6 d|0~~99999|
2145 |Word|EM7|EM7|EM7 d|0~~99999|
2146 |Word|EM8|EM8|EM8 d|0~~99999|
2147 |Word|EM9|EM9|EM9 d|0~~99999|
2148 |Word|EMA|EMA|EMA d|0~~99999|
2149 |Word|EMB|EMB|EMB d|0~~99999|
2150 |Word|EMC|EMC|EMC d|0~~99999|
2151 |Word|IR|IR|IR d|0~~99999|
2152 |Word|DR|DR|DR d|0~~99999|
2153
2154 **Configure the communication protocol**
2155
2156 (% style="text-align:center" %)
2157 [[image:image-20220830143348-1.png]]
2158
2159 (% style="text-align:center" %)
2160 [[image:image-20220830143511-2.png]]
2161
2162 **Configure CJ1W-EIP21 connect with HMI**
2163
2164 (% style="text-align:center" %)
2165 [[image:ftEVGvAprh.png]]
2166
2167 Select TCP_Client_2N
2168
2169 (% style="text-align:center" %)
2170 [[image:RURXWcgyCd.png]]
2171
2172 **Cable Wiring**
2173
2174 Pin Definition Diagram
2175
2176 (% style="text-align:center" %)
2177 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2178
2179 == **CP1E/CP1H serial protocol** ==
2180
2181 Supported device: OMRON CS1(CP1E/CP1H)
2182
2183 **HMI Settings**
2184
2185 |=**Items**|=**Settings**|=**Note**
2186 |Protocol|OMRON CS1(CP1E/CP1H)|
2187 |Connection|RS232 (9600, 2, 7, EVEN)|
2188 |Port No.|None|
2189 |PLC station No.|0|
2190
2191 **Address List**
2192
2193 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2194 |Bit|CIO|CIO|CIO d|0~~99999|
2195 |Bit|W|W|W d|0~~99999|
2196 |Bit|D|D|D d|0~~99999|
2197 |Bit|H|H|H d|0~~99999|
2198 |Bit|A|A|A d|0~~99999|
2199 |Bit|TF|T|T h|0~~99999|
2200 |Bit|CF|CF|CF d|0~~99999|
2201 |Bit|T|FF|FF d|0~~99999|
2202 |Bit|C|C|C d|0~~99999|
2203 |Bit|EM0|EM0|EM0 d|0~~99999|
2204 |Bit|EM1|EM1|EM1 d|0~~99999|
2205 |Bit|EM2|EM2|EM2 d|0~~99999|
2206 |Bit|EM3|EM3|EM3 d|0~~99999|
2207 |Bit|EM4|EM4|EM4 d|0~~99999|
2208 |Bit|EM5|EM5|EM5 h|0~~99999|
2209 |Bit|EM6|EM6|EM6 d|0~~99999|
2210 |Bit|EM7|EM7|EM7 d|0~~99999|
2211 |Bit|EM8|EM8|EM8 d|0~~99999|
2212 |Bit|EM9|EM9|EM9 d|0~~99999|
2213 |Bit|EMA|EMA|EMA d|0~~99999|
2214 |Bit|EMB|EMB|EMB d|0~~99999|
2215 |Bit|EMC|EMC|EMC d|0~~99999|
2216 |Word|CIO|CIO|CIO d|0~~99999|
2217 |Word|W|W|W d|0~~99999|
2218 |Word|D|D|D d|0~~99999|
2219 |Word|H|H|H d|0~~99999|
2220 |Word|A|A|A d|0~~99999|
2221 |Word|T|T|T h|0~~99999|
2222 |Word|CIO|CF|CF d|0~~99999|
2223 |Word|C|C|C d|0~~99999|
2224 |Word|EM0|EM0|EM0 d|0~~99999|
2225 |Word|EM1|EM1|EM1 d|0~~99999|
2226 |Word|EM2|EM2|EM2 d|0~~99999|
2227 |Word|EM3|EM3|EM3 d|0~~99999|
2228 |Word|EM4|EM4|EM4 d|0~~99999|
2229 |Word|EM5|EM5|EM5 h|0~~99999|
2230 |Word|EM6|EM6|EM6 d|0~~99999|
2231 |Word|EM7|EM7|EM7 d|0~~99999|
2232 |Word|EM8|EM8|EM8 d|0~~99999|
2233 |Word|EM9|EM9|EM9 d|0~~99999|
2234 |Word|EMA|EMA|EMA d|0~~99999|
2235 |Word|EMB|EMB|EMB d|0~~99999|
2236 |Word|EMC|EMC|EMC d|0~~99999|
2237 |Word|IR|IR|IR d|0~~99999|
2238 |Word|DR|DR|DR d|0~~99999|
2239
2240 **Configure the communication protocol**
2241
2242 (% style="text-align:center" %)
2243 [[image:image-20220902153118-1.png]]
2244
2245 (% style="text-align:center" %)
2246 [[image:image-20220902151322-2.png]]
2247
2248 **Cable Wiring**
2249
2250 (% style="text-align:center" %)
2251 [[image:image-20220902153949-2.png]]
2252
2253 Pin Definition Diagram
2254
2255 (% style="text-align:center" %)
2256 [[image:image-20220902154056-3.png]]
2257
2258 == **EC55 Protocol** ==
2259
2260 Supported device: EC55 temperature instrument
2261
2262 **1)HMI Settings**
2263
2264 |**Items**|**Settings**|**Note**
2265 |Protocol|Omron EC55|
2266 |Connection|RS485 (9600, 2, 7, EVEN)|
2267 |Port No.|None|
2268 |PLC station No.|0|
2269
2270 **2)Address List**
2271
2272 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2273 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2274 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2275 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2276 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2277 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2278 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2279 |CP|-|0-6|Read controller intrinsic property
2280 |CS|-|0-2|Read controller states
2281 |CA|-|0-17|Action command
2282
2283 **3)Device Settings**
2284
2285 Omron E5CC PLC configuration
2286
2287 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2288
2289 (% style="text-align:center" %)
2290 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2291
2292 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2293
2294 (% style="text-align:center" %)
2295 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2296
2297 **✎Note:** The communication settings for HMI should be consistent with this setting.
2298
2299 **Cable Wiring**
2300
2301 (% style="text-align:center" %)
2302 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2303
2304 (% style="text-align:center" %)
2305 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2306
2307 **✎Note:**
2308
2309 * COM3 only available in PI8000/PI9000 series.
2310 * CA address could not support continuous writing function;
2311 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2312 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2313 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2314 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2315 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2316 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2317 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2318
2319 == **EtherNet/IP NX series Protocol** ==
2320
2321 Supported series: Omron NX/NJ series
2322
2323 **HMI Setting**
2324
2325 |**Items**|**Settings**|**Note**
2326 |Protocol|Omron NX Ethernet/IP|
2327 |Connection|Ethernet|
2328 |Port No.|44818|
2329 |PLC station No.|1|
2330
2331 **Instruction**
2332
2333 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2334
2335 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2336
2337 (% style="text-align:center" %)
2338 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2339
2340 **Export labels from Sysmac Studio**
2341
2342 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2343
2344 (% style="text-align:center" %)
2345 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2346
2347 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2348
2349 Click [Label manage];
2350
2351 (% style="text-align:center" %)
2352 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2353
2354 Click [Import labels] and then select the file exported in step 1;
2355
2356 (% style="text-align:center" %)
2357 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2358
2359 The Import Status field shows the result, click [OK] to finish importing address labels;
2360
2361 (% style="text-align:center" %)
2362 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2363
2364 **Communication Settings**
2365
2366 Enable HMI Ethernet in [Project Settings];
2367
2368 (% style="text-align:center" %)
2369 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2370
2371 Set PLC IP in [Device IP] settings;
2372
2373 (% style="text-align:center" %)
2374 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2375
2376 (% style="text-align:center" %)
2377 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2378
2379 **Cable Wiring**
2380
2381 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2382
2383 == CV/CJ1M/CS1H ==
2384
2385 **HMI Setting:**
2386
2387 |=**Parameters**|=**Recommended**
2388 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2389 |=**PLC I/F**|RS232
2390 |=**Baud rate**|9600
2391 |=**Data bits**|7
2392 |=**Parity**|Even
2393 |=**Stop bits**|2
2394 |=**PLC sta. no.**|0
2395
2396 **PLC Setting:**
2397
2398 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2399
2400 **Device Address:**
2401
2402 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2403 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2404 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2405 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2406 |=B|H|DDDDdd|0 ~~ 409515|
2407 |=B|A|DDDDdd|0 ~~ 409515|
2408 |=B|TF|DDDDdd|0 ~~ 409515|
2409 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2410 |=B|T|DDDD|0 ~~ 4095|
2411 |=B|C|DDDD|0 ~~ 4095|
2412 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2413 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2414 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2415 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2416 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2417 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2418 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2419 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2420 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2421 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2422 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2423 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2424 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2425 |=B|Lamp|D|0~~0|
2426
2427 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2428 |=W|LR_W|DDDD|0 ~~ 4095|
2429 |=W|TC|DDD|0 ~~ 511|
2430 |=W|DM|DDDD|0 ~~ 9999|Data Register
2431
2432 **Wiring Diagram:**
2433
2434 **RS-232**
2435
2436 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2437
2438 Communication Module:
2439
2440 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2441
2442 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2443
2444 (% style="text-align:center" %)
2445 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2446
2447 = Create communication with **Rockwell PLC** =
2448
2449 == **DF1 Protocol** ==
2450
2451 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2452
2453 **HMI Settings**
2454
2455 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2456 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2457 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2458 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2459 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2460 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2461 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2462 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2463 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2464
2465 **Address List**
2466
2467 (% class="table-bordered" %)
2468 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2469 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2470 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2471 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2472 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2473 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2474 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2475 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2476 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2477 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2478 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2479 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2480
2481 **Cable Wiring**
2482
2483 (% style="text-align:center" %)
2484 [[image:AB.gif]]
2485
2486 == **DF1 Advanced Protocol** ==
2487
2488 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2489
2490 **HMI Settings**
2491
2492 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2493 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2494 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2495 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2496 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2497 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2498 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2499 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2500 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2501
2502 **Address List**
2503
2504 (% class="table-bordered" %)
2505 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2506 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2507 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2508 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2509 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2510 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2511 Bit data file B0~~B99
2512
2513 First two digits is for file number
2514
2515 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2516 )))
2517 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2518 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2519 Integer data file bit format N0~~N99
2520
2521 First two digits is for file number
2522
2523 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2524 )))
2525 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2526 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2527 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2528 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2529 Timer Preset Value
2530
2531 First two digits is for file number
2532
2533 For example, TNS99255 represents file number T99, address 255.
2534 )))
2535 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2536 Timer Accumulator Value
2537
2538 First two digits is for file number
2539
2540 For example, TNP99255 represents file number T99, address 255.
2541 )))
2542 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2543 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2544 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2545 Counter Preset Value
2546
2547 First two digits is for file number
2548
2549 For example, CNS99255 represents file number C99, address 255.
2550 )))
2551 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2552 Counter Accumulator Value
2553
2554 First two digits is for file number
2555
2556 For example, CNP99255 represents file number C99, address 255.
2557 )))
2558 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2559 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2560 Integer data file
2561
2562 First two digits is for file number
2563
2564 For example, NN99255 represents file number N99, address 255.
2565 )))
2566 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2567 Only able to communicate with file number F8
2568 )))
2569 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2570 Floating point data file
2571
2572 First two digits is for file number
2573
2574 For example, FN99255 represents file number F99, address 255.
2575 )))
2576 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2577
2578 **Cable Wiring**
2579
2580 (% style="text-align:center" %)
2581 [[image:AB.gif]]
2582
2583 == **MicroLogix Protocol** ==
2584
2585 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2586
2587 **HMI Settings**
2588
2589 (% class="table-bordered" %)
2590 |**Item**|**Settings**|**Note**
2591 |Protocol|Allen-Bradlley MicroLogix|
2592 |Connection|RS232|
2593 |Baud rate|19200|
2594 |Data bit|8|
2595 |Parity|None|
2596 |Stop bit|1|
2597 |PLC station No.|1|
2598
2599 **Address List**
2600
2601 (% class="table-bordered" %)
2602 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2603 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2604 |O|O d.d|0.0~~255.15|
2605 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2606 |S|S d.d|0.0~~255.15|
2607 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2608 |(% rowspan="9" %)Word|S|S d|0~~255|
2609 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2610 |TP|TP nnhh|0~~ffff
2611 |CS|CS nnhh|0~~ffff
2612 |CP|CP nnhh|0~~ffff
2613 |N|N nnhh|0~~ffff
2614 |C|C nnhh|0~~ffff
2615 |T|T nnhh|0~~ffff
2616 |R|R nnhh|0~~ffff
2617
2618 **Cable Wiring**
2619
2620 (% style="text-align:center" %)
2621 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2622
2623 == **CompactLogix FreeTag Ethernet protocol** ==
2624
2625 Allen-Brandly CompactLogix
2626
2627 **HMI Settings**
2628
2629 (% class="table-bordered" %)
2630 |**Items**|**Settings**|**Note**
2631 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2632 |Connection|Ethernet|
2633 |Port No.|44818|
2634
2635 **PLC Setting**
2636
2637 Create new tags
2638
2639 (% style="text-align:center" %)
2640 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2641
2642 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2643
2644 (% style="text-align:center" %)
2645 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2646
2647 Import labels, please open [Communication] window and click [Import label];
2648
2649 Select csv file, all tags will be displayed as belows;
2650
2651 (% style="text-align:center" %)
2652 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2653
2654 **✎Note:**
2655
2656 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2657
2658 (% style="text-align:center" %)
2659 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2660
2661 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2662
2663 **Communication settings in HMI**
2664
2665 Enable HMI Ethernet in [Project Settings];
2666
2667 (% style="text-align:center" %)
2668 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2669
2670 Set PLC IP in [Device IP] settings;
2671
2672 (% style="text-align:center" %)
2673 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2674
2675 **Cable Wiring**
2676
2677 (% style="text-align:center" %)
2678 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2679
2680 == **MicroLogix 1200** **protocol** ==
2681
2682 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2683
2684 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2685 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2686 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2687 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2688
2689 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2690
2691 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2692 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2693 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2694 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2695 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2696 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2697 |**PLC word address type**|**Address format**|**Address range**
2698 |S|ddd|S0 ~~ 255
2699 |TS|ffff|TS0 ~~ FFFF
2700 |TP|ffff|TP0 ~~ FFFF
2701 |CS|ffff|CS0 ~~ FFFF
2702 |CP|ffff|CP0 ~~ FFFF
2703 |N|ffff|N0 ~~ FFFF
2704 |F|ffff|F0 ~~ FFFF
2705
2706 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2707
2708 == **S7-200 Smart Ethernet Protocol** ==
2709
2710 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2711
2712 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2713
2714 **HMI Setting**
2715
2716 (% class="table-bordered" %)
2717 |**Items**|**Settings**|**Note**
2718 |Protocol|Simens S7-200 Smart Ethernet|
2719 |Connection|Ethernet|
2720 |Port No.|102|
2721 |PLC station No.|2|
2722
2723 **Address List**
2724
2725 (% class="table-bordered" %)
2726 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2727 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2728 |Q|Q|Q ddddd.o|0.0~~99999.7|
2729 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2730 |V|V|V ddddd.o|0.0~~99999.7|
2731 |M|M|M ddddd.o|0.0~~99999.7|
2732 |SM|SM|ddddd.o|0.0~~99999.7|
2733 |S|S|ddddd.o|0.0~~99999.7|Read only
2734 |T|T|ddddd|0~~99999|Timer state, read only
2735 |C|C|ddddd|0~~99999|Counter state, read only
2736 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2737 |Q|QW|QW ddddd|0~~99999|
2738 |AI|AIW|AIW ddddd|0~~99999|
2739 |AQ|VB|VB ddddd|0~~99999|
2740 |V|VW|VW ddddd|0~~99998|(((
2741 VW0=VB (0~~1)
2742
2743 VW2=VB (2~~3)
2744
2745 Address value is a multiple of 2
2746 )))
2747 |V|VD|VD ddddd|0~~99998|(((
2748 VD0=VB (0~~3)
2749
2750 VD2=VB (4~~7)
2751
2752 Address value is a multiple of 4
2753 )))
2754 |M|MB|MB ddddd|0~~99999|
2755 |M|MW|MW ddddd|0~~99999|(((
2756 MW0=MB(0~~1)
2757
2758 MW2=MB(2~~3)
2759
2760 Address value is a multiple of 2
2761 )))
2762 |M|MD|MD ddddd|0~~99999|(((
2763 MD0=MB(0~~3)
2764
2765 MD4=MB(4~~7)
2766
2767 Address value is a multiple of 4
2768 )))
2769 |T|TW|TW ddddd|0~~99999|Value of timer
2770 |C|CW|CW ddddd|0~~99999|Value of counter
2771 |W|SW|SW ddddd|0~~99999|
2772
2773 **Communication Settings**
2774
2775 Enable HMI Ethernet in [Project Settings];
2776
2777 (% style="text-align:center" %)
2778 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2779
2780 Set PLC IP in [Device IP] settings;
2781
2782 (% style="text-align:center" %)
2783 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2784
2785 * PLC IP Address: PLC IP
2786 * PLC pot No.: 102(fixed)
2787 * Network:TCP_Client_2N(fixed)
2788
2789 (% style="text-align:center" %)
2790 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2791
2792 * Wait timeout: depend on actual network situation (more than 1500 ms)
2793
2794 **Cable Wiring**
2795
2796 (% style="text-align:center" %)
2797 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2798
2799 == **S7-300 Ethernet Protocol** ==
2800
2801 Supported Series: Siemens S7-300 series PLC
2802
2803 **HMI Setting**
2804
2805 (% class="table-bordered" %)
2806 |**Items**|**Settings**|**Note**
2807 |Protocol|Simens S7-300 Ethernet|
2808 |Connection|Ethernet|
2809 |Port No.|102|
2810 |PLC station No.|2|Need to be same as the PLC setting
2811
2812 **Address List**
2813
2814 (% class="table-bordered" %)
2815 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2816 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2817 |Q|Q|Q ddddd.o|0.0~~99999.7|
2818 |M|M|M ddddd.o|0.0~~99999.7|
2819 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2820 nnnn: block number;
2821
2822 dddd: address;
2823 )))
2824 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2825 |Q|QW|QW ddddd|0~~99999|
2826 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2827 |MW|MW ddddd|0~~99999|(((
2828 MW0=MB(0~~1)
2829
2830 MW2=MB(2~~3)
2831
2832 Address value is a multiple of 2
2833 )))
2834 |MD|MD ddddd|0~~99999|(((
2835 MD0=MB(0~~3)
2836
2837 MD4=MB(4~~7)
2838
2839 Address value is a multiple of 4
2840 )))
2841 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2842 nnnn: block number;
2843
2844 dddd: address
2845 )))
2846 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2847 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2848
2849 **Communication Settings**
2850
2851 Enable HMI Ethernet in [Project Settings];
2852
2853 (% style="text-align:center" %)
2854 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2855
2856 Set PLC IP in [Device IP] settings;
2857
2858 (% style="text-align:center" %)
2859 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2860
2861 * PLC IP Address: PLC IP
2862 * PLC pot No.: 102(fixed)
2863 * Network:TCP_Client_2N(fixed)
2864
2865 (% style="text-align:center" %)
2866 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2867
2868 * Wait timeout: depend on actual network situation (more than 1500 ms)
2869
2870 **Cable Wiring**
2871
2872 (% style="text-align:center" %)
2873 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2874
2875 == **S7-1200 Ethernet Protocol** ==
2876
2877 Supported Series: Siemens S7-1200
2878
2879 **HMI Setting**
2880
2881 (% class="table-bordered" %)
2882 |**Items**|**Settings**|**Note**
2883 |Protocol|Siemens S7-1200|
2884 |Connection|Ethernet|
2885 |Port No.|102|
2886 |PLC station No.|2|
2887
2888 **Address List**
2889
2890 (% class="table-bordered" %)
2891 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2892 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2893 d:0~-~-9999
2894
2895 o:0-7
2896 )))|
2897 |Q|Q|Q d.o|(((
2898 d:0~-~-9999
2899
2900 o:0-7
2901 )))|
2902 |M|M|M d.o|(((
2903 d:0~-~-9999
2904
2905 o:0-7
2906 )))|
2907 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2908 nn:0-9999,
2909
2910 dddd:0-9999,
2911
2912 o:0-7
2913 )))|(((
2914 nn:DB No.
2915
2916 dddd:address value
2917
2918 o: digit address
2919 )))
2920 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2921 |M|MW|MW d|d:0-99999|(((
2922 MW0=MB(0~~1)
2923
2924 MW2=MB(2~~3)
2925
2926 Address value is a multiple of 2
2927 )))
2928 |M|MD|MD d|d:0-99999|(((
2929 MD0=MB(0~~3)
2930
2931 MD4=MB(4~~7)
2932
2933 Address value is a multiple of 4
2934 )))
2935 |I|IW|IW d|d:0-99999|
2936 |Q|QW|QW d|d:0-99999|
2937 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2938 nn:0-9999
2939
2940 dddd:0-9999
2941 )))|(((
2942 nn:DB No.
2943
2944 dddd:address value
2945 )))
2946 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2947 nn:0-9999
2948
2949 dddd:0-9999
2950 )))|(((
2951 nn:DB No.
2952
2953 dddd:address value
2954
2955 Address value is a multiple of 2
2956 )))
2957 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2958 nn:0-9999
2959
2960 dddd:0-9999
2961 )))|(((
2962 nn:DB No.
2963
2964 dddd:address value
2965
2966 Address value is a multiple of 4
2967 )))
2968
2969 **Communication Settings**
2970
2971 Enable HMI Ethernet in [Project Settings];
2972
2973 (% style="text-align:center" %)
2974 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2975
2976 Set PLC IP in [Device IP] settings;
2977
2978 (% style="text-align:center" %)
2979 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2980
2981 **✎Note:**
2982
2983 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2984 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2985 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2986 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2987
2988 **PLC Settings**
2989
2990 Add BD
2991
2992 * Please uncheck [Symbolic access only] option;
2993
2994 (% style="text-align:center" %)
2995 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2996
2997 Address settings, using BD2 as example.
2998
2999 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3000 * 2 represent DB block number
3001 * xxxx represent address
3002
3003 **Such as:**
3004
3005 * DBxDBB20000 = DB2.DBB0
3006 * DBxDBW20004 = DB2.DBW4
3007
3008 (% style="text-align:center" %)
3009 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3010
3011 **How to connect with S7-1200 Firmware V4.0**
3012
3013 PLC configuration
3014
3015 * Double click [device configuration] in Siemens via software
3016 * Double click [protection] to enter protection configuration screen
3017
3018 (% style="text-align:center" %)
3019 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3020
3021 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3022
3023 (% style="text-align:center" %)
3024 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3025
3026 DB settings
3027
3028 * Right click [DB], select [properties]
3029 * Uncheck [optimized block access]
3030
3031 **Cable Wiring**
3032
3033 (% style="text-align:center" %)
3034 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3035
3036 == **S7-XXX Ethernet Protocol** ==
3037
3038 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3039
3040 **HMI Setting**
3041
3042 (% class="table-bordered" style="width:823px" %)
3043 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3044 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3045 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3046 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3047 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3048 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3049
3050 Slot from TIA Portal is equal to Device No. of PIStudio
3051
3052 Rack from TIA Portal is equal to HMI No. of PIStudio
3053
3054 (% style="text-align:center" %)
3055 [[image:S7-XXXCommunication Settings.png]]
3056
3057 (% style="text-align:center" %)
3058 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3059
3060 **Address List**
3061
3062 (% class="table-bordered" %)
3063 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3064 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3065 d:0~-~-9999
3066
3067 o:0-7
3068 )))|
3069 |Q|Q|Q d.o|(((
3070 d:0~-~-9999
3071
3072 o:0-7
3073 )))|
3074 |M|M|M d.o|(((
3075 d:0~-~-9999
3076
3077 o:0-7
3078 )))|
3079 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3080 nn:0-9999,
3081
3082 dddd:0-9999,
3083
3084 o:0-7
3085 )))|(((
3086 nn:DB No.
3087
3088 dddd:address value
3089
3090 o: digit address
3091 )))
3092 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3093 |M|MW|MW d|d:0-99999|(((
3094 MW0=MB(0~~1)
3095
3096 MW2=MB(2~~3)
3097
3098 Address value is a multiple of 2
3099 )))
3100 |M|MD|MD d|d:0-99999|(((
3101 MD0=MB(0~~3)
3102
3103 MD4=MB(4~~7)
3104
3105 Address value is a multiple of 4
3106 )))
3107 |I|IW|IW d|d:0-99999|
3108 |Q|QW|QW d|d:0-99999|
3109 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3110 nn:0-9999
3111
3112 dddd:0-9999
3113 )))|(((
3114 nn:DB No.
3115
3116 dddd:address value
3117 )))
3118 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3119 nn:0-9999
3120
3121 dddd:0-9999
3122 )))|(((
3123 nn:DB No.
3124
3125 dddd:address value
3126
3127 Address value is a multiple of 2
3128 )))
3129 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3130 nn:0-9999
3131
3132 dddd:0-9999
3133 )))|(((
3134 nn:DB No.
3135
3136 dddd:address value
3137
3138 Address value is a multiple of 4
3139 )))
3140
3141 **Communication Settings**
3142
3143 Enable HMI Ethernet in [Project Settings];
3144
3145 (% style="text-align:center" %)
3146 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3147
3148 Set PLC IP in [Device IP] settings;
3149
3150 (% style="text-align:center" %)
3151 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3152
3153 **✎Note:**
3154
3155 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3156 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3157
3158 **Cable Wiring**
3159
3160 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3161
3162 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3163
3164 Supported Series: Siemens Logo 0BA0, 0BA1 series
3165
3166 **HMI Settings**
3167
3168 (% class="table-bordered" %)
3169 |**Items**|**Settings**|**Note**
3170 |Protocol|Siemens LOGO|
3171 |Connection|Ethernet|
3172 |Port No.|102|
3173 |PLC station No.|2|
3174
3175 **Address List**
3176
3177 (% class="table-bordered" %)
3178 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3179 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3180 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3181 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3182 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3183 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3184 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3185 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3186 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3187 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3188 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3189 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3190 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3191 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3192 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3193 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3194
3195 **PLC Settings in LOGO Software:**
3196
3197 Click [Tools]~-~-[Ethernet Connections],shown as below.
3198
3199 (% style="text-align:center" %)
3200 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3201
3202 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3203
3204 (% style="text-align:center" %)
3205 [[image:image-20221228142937-4.png]]
3206
3207 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3208
3209 (% style="text-align:center" %)
3210 [[image:image-20221228143047-5.png]]
3211
3212 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3213
3214 (% style="text-align:center" %)
3215 [[image:image-20221228143246-6.png]]
3216
3217
3218 **HMI Communication Settings**
3219
3220 Set PLC IP in [Device IP] settings;
3221
3222 (% style="text-align:center" %)
3223 [[image:image-20221228143614-7.png]]
3224
3225 Enable HMI Ethernet in [Project Settings];
3226
3227 (% style="text-align:center" %)
3228 [[image:image-20221228144229-9.png]]
3229
3230 TSAP setting
3231
3232 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3233 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3234 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3235 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3236 ie, ig series: use HSW1200, HSW1201.
3237 HMI V2.0: use HSW1200, HSW1201.
3238
3239 **✎Note:**
3240
3241 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3242 * HSW10119/HSW1201 is set up as shown.
3243 * (((
3244 (% style="text-align:center" %)
3245 [[image:image-20221228144800-11.png]]
3246 )))
3247 * (((
3248 (% style="text-align:center" %)
3249 [[image:image-20221228144708-10.png]]
3250 )))
3251
3252 * AI word address and Ibit address are read-only and cannot be written on HMI.
3253 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3254 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3255 * Written value of RTC cannot exceed 255.
3256
3257 **Cable Wiring**
3258
3259 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3260
3261 == S7-300 232 ==
3262
3263 **HMI Setting:**
3264
3265 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3266 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3267 |=**PLC I/F**|RS232| |
3268 |=**Baud rate**|19200|9600,19200|
3269 |=**Data bits**|8| |
3270 |=**Parity**|Odd| |
3271 |=**Stop bits**|1| |
3272 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3273
3274 **Device Address**
3275
3276 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3277 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3278 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3279 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3280 |=Word|(((
3281 DB1 to DB99
3282 )))|DDDDDo|0 ~~ 655327|
3283 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3284 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3285 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3286 |=Double word|MD|DDDD|0 ~~ 4094|
3287 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3288 Data Register Double Word (must be even)
3289 )))
3290 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3291
3292 **Cable Wiring**
3293
3294 (% style="text-align:center" %)
3295 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3296
3297 = Create communication with Xinje** PLC** =
3298
3299 == XC serial protocol ==
3300
3301 **HMI Settings**
3302
3303 |**Item**|**Settings**|**Note**
3304 |Protocol|XINJE XC MODBUS|
3305 |Connection|RS232|
3306 |Baud rate|19200|
3307 |Data bit|8|
3308 |Parity|EVEN|
3309 |Stop bit|1|
3310 |PLC station No.|1|
3311
3312 **Address List**
3313
3314 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3315 |Bit|M|M|M d|0~~8511|
3316 |Bit|X|X|X o|0~~1747|
3317 |Bit|Y|Y|Y o|0~~1747|
3318 |Bit|S|S|S d|0~~1023|
3319 |Bit|T|T|T d|0~~4095|
3320 |Bit|C|C|C d|0~~634|
3321 |Word|D|D|D d|0~~8511|
3322 |Word|TD|TD|TD d|0~~618|
3323 |Word|CD|CD|CD d|0~~634|
3324 |Word|FD|FD|FD d|0~~8511|
3325
3326 **Configure the communication protocol**
3327
3328 (% style="text-align:center" %)
3329 [[image:image-20220830154105-1.png]]
3330
3331 (% style="text-align:center" %)
3332 [[image:image-20220830154159-3.png]]
3333
3334 **Cable Wiring**
3335
3336 Figure
3337
3338 [[image:image-20220830155728-4.png]]
3339
3340 Pin Definition Diagram
3341
3342 (% style="text-align:center" %)
3343 [[image:image-20220830154131-2.png]]
3344
3345 == XD serial protocol ==
3346
3347 **HMI Settings**
3348
3349 Supported Series: Xinjie XD/XE Series PLC
3350
3351 |=**Item**|=**Settings**|=**Note**
3352 |Protocol|XINJE XD/XC MODBUS|
3353 |Connection|RS232|
3354 |Baud rate|19200|
3355 |Data bit|8|
3356 |Parity|EVEN|
3357 |Stop bit|1|
3358 |PLC station No.|1|
3359
3360 **Address List**
3361
3362 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3363 |Bit|M|M|M d|0~~74999|
3364 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3365 |Bit|X2xx|X2xx|X2xx o|0~~277|
3366 |Bit|X|X|X o|0~~77|
3367 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3368 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3369 |Bit|Y|Y|Y o|0~~4095|
3370 |Bit|SM|SM|SM d|0~~4999|(((
3371
3372 )))
3373 |Bit|T|T|T d|0~~4999|
3374 |Bit|C|C|C d|0~~4999|
3375 |Bit|ET|ET|ET d|0~~31|
3376 |Bit|SE|SE|SE d|0~~31|
3377 |Bit|HM|HM|HM d|0~~11999|
3378 |Bit|HSC|HSC|HSC d|0~~39|
3379 |Bit|HS|HS|HS d|0~~999|
3380 |Bit|HT|HT|HT d|0~~1999|
3381 |Bit|HC|HC|HC d|0~~1999|
3382 |Bit|S|S|S d|0~~7999|
3383 |Word|D|D|D d|0~~69999|
3384 |Word|ID|ID|ID d|0~~99|
3385 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3386 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3387 |Word|QD|QD|QD d|0~~99|
3388 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3389 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3390 |Word|SD|SD|SD d|0~~4999|
3391 |Word|TD|TD|TD d|0~~575|
3392 |Word|CD|CD|CD d|0~~575|
3393 |Word|ETD|ETD|ETD d|0~~31|
3394 |Word|HD|HD|HD d|0~~24999|
3395 |Word|HSD|HSD|HSD d|0~~1023|
3396 |Word|HTD|HTD|HTD d|0~~95|
3397 |Word|HCD|HCD|HCD d|0~~95|
3398 |Word|HSCD|HSCD|HSCD d|0~~31|
3399 |Word|FD|FD|FD d|0~~8191|
3400 |Word|SFD|SFD|SFD d|0~~5999|
3401 |Word|FS|FS|FS d|0~~47|
3402
3403 **Configure the communication protocol**
3404
3405 (% style="text-align:center" %)
3406 [[image:image-20220830160042-1.png]]
3407
3408 (% style="text-align:center" %)
3409 [[image:image-20220830160129-2.png]]
3410
3411 **Cable Wiring**
3412
3413 (% style="text-align:center" %)
3414 [[image:image-20220905093902-1.png]]
3415
3416 Pin Definition Diagram
3417
3418 (% style="text-align:center" %)
3419 [[image:image-20220830160232-3.png]]
3420
3421 = Create communication with Panasonic** PLC** =
3422
3423 == **FP serial protocol** ==
3424
3425 **1)HMI Settings**
3426
3427 |**Item**|**Settings**|**Note**
3428 |Protocol|Panasonic FP MFWTOCOL|
3429 |Connection|RS232|
3430 |Baud rate|9600|
3431 |Data bit|8|
3432 |Parity|ODD|
3433 |Stop bit|1|
3434 |PLC station No.|1|
3435
3436 **2)Address List**
3437
3438 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3439 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3440 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3441 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3442 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3443 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3444 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3445 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3446 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3447 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3448 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3449 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3450 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3451 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3452 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3453 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3454
3455 **3)Configure the communication protocol**
3456
3457 [[image:image-20220830171050-1.png]]
3458
3459 [[image:image-20220830171126-2.png]]
3460
3461 **4)Cable Wiring**
3462
3463 Figure
3464
3465 [[image:image-20220830171328-4.png]]
3466
3467 Pin Definition Diagram
3468
3469 [[image:image-20220830171146-3.png]]
3470
3471 = Create communication with **SHIMADEN PLC** =
3472
3473 == **FP23 series protocol** ==
3474
3475 Supported series: SHIMADEN FP23 series
3476
3477 **HMI Setting**
3478
3479 |**Items**|**Settings**|**Note**
3480 |Protocol|SHIMADEN FP23 series|
3481 |Connection|RS485 (9600, 1, 7, EVEN)|
3482 |Port No.|None|
3483 |PLC station No.|0|
3484
3485 **Address List**
3486
3487 |**Device address**|**HMI register**|**Address range**|**Type**
3488 |0040-0043(HEX)|FP040|100064-200067|Read only
3489 |0100-010B(HEX)|FP100|100256-200267|Read only
3490 |0110-0142(HEX)|FP110|100272-200322|Read only
3491 |0182-0252(HEX)|FP182|100386-200594|Write only
3492 |0280-0281(HEX)|FP280|100640-200641|Read only
3493 |0300-030B(HEX)|FP300|100768-200779|Read and write
3494 |0380-039F(HEX)|FP380|100896-200927|Read and write
3495 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3496 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3497 |0600-0670(HEX)|FP600|101536-201814|Read and write
3498 |0720-0738(HEX)|FP720|101824-201848|Read and write
3499 |0800-083F(HEX)|FP800|102048-202111|Read and write
3500 |0900-0952(HEX)|FP900|102304-202386|Read and write
3501 | |Ctrl|0-2|
3502
3503 **✎Note:**
3504
3505 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3506 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3507 * The Ctrl register is used to store the control group number and BCC check mode.
3508
3509 **Ctrl Register Description**
3510
3511 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3512 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3513 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3514 * Ctrl3 reserved
3515
3516 **✎Note:**
3517
3518 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3519
3520 **Cable Wiring**
3521
3522 (% style="text-align:center" %)
3523 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3524
3525 (% style="text-align:center" %)
3526 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3527
3528 **✎Note:** COM3 only available in PI8000/PI9000 series.
3529
3530 == **SR90 protocol** ==
3531
3532 Supported series: SHIMADEN SR90 series
3533
3534 **HMI Setting**
3535
3536 |**Items**|**Settings**|**Note**
3537 |Protocol|SHIMADEN SR90 protocol|
3538 |Connection|RS485 (1200, 1, 7, EVEN)|
3539 |Port No.|None|
3540 |PLC station No.|0|
3541
3542 **Address List**
3543
3544 |**Device address**|**HMI register**|**Address range**|**Type**
3545 |0040-0043 (HEX)|SR040|100064-100067|Read only
3546 |0100-010A(HEX)|SR0100|100256-100266|Read only
3547 |0182-018C(HEX)|SR0182|100386-100396|Write only
3548 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3549 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3550 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3551 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3552 | |Ctrl|0-2|~-~-
3553
3554 **✎Note:**
3555
3556 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3557 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3558 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3559
3560 **Ctrl Register Description**
3561
3562 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3563 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3564 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3565 * Ctrl3 reserved
3566
3567 **✎Note:**
3568
3569 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3570
3571 **Cable Wiring**
3572
3573 (% style="text-align:center" %)
3574 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3575
3576 (% style="text-align:center" %)
3577 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3578
3579 **✎Note:** COM3 only available in PI8000/PI9000 series.
3580
3581 == **MR13 series(standard protocol)** ==
3582
3583 Supported series: SHIMADEN MR13 series
3584
3585 **HMI Setting**
3586
3587 |**Items**|**Settings**|**Note**
3588 |Protocol|SHIMADEN standard protocol|
3589 |Connection|RS485 (1200, 1, 7, EVEN)|
3590 |Port No.|None|
3591 |PLC station No.|0|
3592
3593 **Address List**
3594
3595 |**Device address**|**HMI register**|**Address range**|**Type**
3596 |0100-010B(HEX)|MR100|100256-300267|Read only
3597 |0111-0126(HEX)|MR111|100273-300294|Read only
3598 |0184-0192(HEX)|MR184|100388-300402|Write only
3599 |0280-0282(HEX)|MR280|100640-300642|Read only
3600 |0300-030B(HEX)|MR300|100768-300779|Read/write
3601 |0314-0317(HEX)|MR314|100788-300791|Read/write
3602 |031A(HEX)|MR31A|100794-300794|Read/write
3603 |0320-0321(HEX)|MR320|100800-300801|Read/write
3604 |0400-0504(HEX)|MR400|101024-301284|Read/write
3605 |0506(HEX)|MR506|101286-301286|Read/write
3606 |0510-0514(HEX)|MR510|101296-301300|Read/write
3607 |0516-0524(HEX)|MR516|101302-301316|Read/write
3608 |0526(HEX)|MR526|101318-301318|Read/write
3609 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3610 |~-~-|Ctrl|0-2|~-~-
3611
3612 **✎Note:**
3613
3614 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3615 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3616 * The Ctrl register is used to store the control group number and BCC check mode.
3617
3618 **Ctrl Register Description**
3619
3620 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3621 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3622 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3623 * Ctrl3 reserved
3624
3625 **✎Note:**
3626
3627 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3628
3629 **Cable Wiring**
3630
3631 (% style="text-align:center" %)
3632 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3633
3634 (% style="text-align:center" %)
3635 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3636
3637 **✎Note:** COM3 only available in PI8000/PI9000 series.
3638
3639 = **Printer** =
3640
3641 == **TSPL label printer** ==
3642
3643 **Introduction**
3644
3645 TSPL label printer protocol supports following models.
3646
3647 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3648 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3649
3650 **Setting Step**
3651
3652 Select the protocol
3653
3654 * Create a new project, select the TSPL label printer protocol as shown below.
3655
3656 (% style="text-align:center" %)
3657 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3658
3659 Set parameters
3660
3661 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3662
3663 Printer register
3664
3665 (% class="table-bordered" %)
3666 |**Register**|**System**|**Range**|**Function**
3667 |TSPL_SP|decimal|0 - 1|Set the paper size
3668 |TSPL_PT|decimal|0 - 1999|Print text
3669 |TSPL_PQ|decimal|0 - 999|Print QR code
3670 |TSPL_PB|decimal|0 - 999|Print barcode
3671 |TSPL_PR|decimal|0 - 1|Print offset
3672 |TSPL_PN|decimal|0 - 0|Trigger printing
3673 |TSPL_PS|decimal|0 - 0|Print status
3674
3675 * Set paper size:
3676 ** TSPL_SP0: width of paper, unit: mm.
3677 ** TSPL_SP1: height of paper, unit: mm.
3678 * Print text:
3679 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3680 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3681
3682 (% class="table-bordered" %)
3683 |**Register**|**Function**|**Description**
3684 |TSPL_PT0|X coordinate|Unit: dot
3685 |TSPL_PT1|Ycoordinate|Unit: dot
3686 |TSPL_PT2|Rotation angle|(((
3687 0: 0 degrees
3688
3689 1: 90 degrees
3690
3691 2: 180 degrees
3692
3693 3: 270 degrees
3694 )))
3695 |TSPL_PT3|Size|Range: 0-3
3696 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3697
3698 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3699
3700 Print QR code:
3701
3702 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3703 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3704
3705 (% class="table-bordered" %)
3706 |**Register**|**Function**|**Description**
3707 |TSPL_PQ0|X coordinate|Unit: dot
3708 |TSPL_PQ1|Ycoordinate|Unit: dot
3709 |TSPL_PQ2|Rotation angle|(((
3710 0: 0 degrees
3711
3712 1: 90 degrees
3713
3714 2: 180 degrees
3715
3716 3: 270 degrees
3717 )))
3718 |TSPL_PQ3|Size|Range: 0-5
3719 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3720
3721 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3722
3723 Print bar code:
3724
3725 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3726 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3727
3728 (% class="table-bordered" %)
3729 |**Register**|**Function**|**Description**
3730 |TSPL_PB0|X coordinate|Unit: dot
3731 |TSPL_PB1|Ycoordinate|Unit: dot
3732 |TSPL_PB2|Rotation angle|(((
3733 0: 0 degrees
3734
3735 1: 90 degrees
3736
3737 2: 180 degrees
3738
3739 3: 270 degrees
3740 )))
3741 |TSPL_PB3|height|Unit: dot
3742 |TSPL_PB4|width|Range:0-2
3743 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3744
3745 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3746
3747 Print offset:
3748
3749 * TSPL_PR0: X coordinate offset, unit: mm;
3750 * TSPL_PR1: Y coordinate offset, unit: mm.
3751
3752 Trigger printing:
3753
3754 * TSPL_PN0 = 1: trigger the printer to start printing.
3755
3756 Printing status:
3757
3758 * TSPL_PS0 = 1: The printing is normal.
3759 * TSPL_PS0 = 1: The printing is abnormal.
3760
3761 Print picture
3762
3763 * For the function of printing pictures, please refer to the configuration of [Printer object].
3764
3765 Conversion between dot and mm
3766
3767 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3768
3769 == **EpsonTM series** ==
3770
3771 **HMI Settings**
3772
3773 (% class="table-bordered" %)
3774 |**Item**|**Settings**|**Note**
3775 |Protocol|EPSON-TM-T82II/TM-XXX|
3776 |Connection|RS232|
3777 |Baud rate|9600~~115200|
3778 |Data bit|8|
3779 |Parity|None|
3780 |Stop bit|1|
3781 |PLC station No.|1|
3782
3783 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3784
3785 **Printer Settings**
3786
3787 (% class="table-bordered" %)
3788 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3789 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3790 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3791 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3792 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3793 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3794 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3795
3796 **Cable Wiring**
3797
3798 (% style="text-align:center" %)
3799 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3800
3801 (% style="text-align:center" %)
3802 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3803
3804 **✎Note:** COM3 only available in PI8000/PI9000 series.
3805
3806
3807 = Create communication with **Schneider PLC** =
3808
3809 == **Schneider MODBUS RTU** ==
3810
3811 **HMI Setting**
3812
3813 |=**Parameters**|=**Recommended**|=**Notes**
3814 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3815 |Connection|RS485|
3816 |**Baud rate**|19200|
3817 |**Data bit**|8|
3818 |**Parity**|Even|
3819 |**Stop bit**|1|
3820 |**PLC station No.**|1|
3821
3822 **PLC Setting**
3823
3824 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3825
3826 **Device Address**
3827
3828 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3829 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3830 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3831 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3832 |W|MW|DDDDDD|0 ~~ 999999|Output register
3833 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3834
3835 **Wiring Diagram**
3836
3837 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3838
3839 (% style="text-align:center" %)
3840 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3841
3842 = **Barcode Scanner** =
3843
3844 Supported: DELI 14880 barcode scanner
3845
3846 **HMI Setting**
3847
3848 |**Items**|**Settings**|**Note**
3849 |Protocol|Barcode Scanner|
3850 |Connection|USB|
3851
3852 **Operating Procedures**
3853
3854 Select [Barcode Scanner];
3855
3856 (% style="text-align:center" %)
3857 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3858
3859 Set address for receiving;
3860
3861 Set correct length;
3862
3863 (% style="text-align:center" %)
3864 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3865
3866 **✎Note:**
3867
3868 * The protocol uploads the information acquired by the USB scanner to the HMI;
3869 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3870 * Recommended model: DELI 14880 barcode scanner;
3871
3872 = **Hitachi EHV Series (Ethernet)** =
3873
3874 Supported series: Hitachi EHV series
3875
3876 **HMI Settings**
3877
3878 (% class="table-bordered" %)
3879 |**Items**|**Settings**|**Note**
3880 |Protocol|Hitachi EHV series|
3881 |Connection|Ethernet|
3882 |Port No.|3004~~3007|
3883
3884 **Address List**
3885
3886 (% class="table-bordered" %)
3887 |**Type**|**Register**|**Range**|**Format**|**Note**
3888 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3889 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3890 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3891 H1H2H3H4 Module main number
3892
3893 H1: Remote number
3894
3895 H2: Unit number
3896
3897 H3: Slot number
3898
3899 H4: Word number of Module
3900
3901 H Sub number of Module
3902
3903 For example:X21.3
3904
3905 Slot number 2
3906
3907 Word number of module is 1
3908
3909 Bit number of module is 3
3910
3911 Remote number and unit number are 0
3912 )))
3913 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3914 |R|0 – FF.f (Hex)|R HH.h|
3915 |L|0 - 73FF.f (Hex)|L HHHH.h|
3916 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3917 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3918 H1H2H3H4 Module main number
3919
3920 H1: Remote number
3921
3922 H2: Unit number
3923
3924 H3: Slot number
3925
3926 H4: Word number of module
3927
3928 For example:WX21
3929
3930 Word number of module is 1
3931
3932 Slot number is 2
3933
3934 Remote number and unit number are 0
3935 )))
3936 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3937 |WR|0 – FFFF (Hex)|WR HHHH|
3938 |WL|0 - 73FF (Hex)|WL HHHH|
3939 |TC|0 - 2559|TC DDDD|
3940
3941 **Communication settings in HMI**
3942
3943 Enable HMI Ethernet in [Project Settings];
3944
3945 (% style="text-align:center" %)
3946 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3947
3948 Set PLC IP in [Device IP] settings;
3949
3950 (% style="text-align:center" %)
3951 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3952
3953 **PLC Configuration**
3954
3955 Connect with PLC, select[Online mode];
3956
3957 (% style="text-align:center" %)
3958 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3959
3960 Set IP address, it is the same LAN parameters with HMI;
3961
3962 (% style="text-align:center" %)
3963 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3964
3965 3) Save PLC communication parameter, and restart PLC
3966
3967 **PLC Monitor Mode**
3968
3969 Connect with PLC and choose to “online” mode
3970
3971 (% style="text-align:center" %)
3972 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3973
3974 Open I/O monitor sheet1
3975
3976 (% style="text-align:center" %)
3977 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3978
3979 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3980
3981 (% style="text-align:center" %)
3982 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3983
3984 Enter the register address, click OK to view the value of the register.
3985
3986 (% style="text-align:center" %)
3987 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3988
3989 (% style="text-align:center" %)
3990 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3991
3992 **✎Note:**
3993
3994 * Both word registers and bit registers support even continuous read/write functions;
3995 * The range of registers is based on the specific PLC type;
3996
3997 **Cable Wiring**
3998
3999 (% style="text-align:center" %)
4000 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4001
4002 = **IEC60870-5 104 Client** =
4003
4004 **HMI Setting**
4005
4006 (% class="table-bordered" %)
4007 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4008 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4009 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4010 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4011
4012 **Address List**
4013
4014 (% class="table-bordered" %)
4015 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4016 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4017 |(% style="width:461px" %)SCNA|0~~16777215.7
4018 |(% style="width:461px" %)DPTB|0~~16777215.7
4019 |(% style="width:461px" %)DCNA|0~~16777215.7
4020 |(% style="width:461px" %)METF|0~~16777215.7
4021 |(% style="width:461px" %)SENC|0~~16777215.7
4022 |(% style="width:461px" %)SENA|0~~16777215.7
4023 |(% style="width:461px" %)MENA|0~~16777215.7
4024 |(% style="width:461px" %)METD|0~~16777215.7
4025 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4026 |(% style="width:461px" %)SCNA|0~~16777215
4027 |(% style="width:461px" %)DPTB|0~~16777215
4028 |(% style="width:461px" %)DCNA|0~~16777215
4029 |(% style="width:461px" %)SENA|0~~16777215
4030 |(% style="width:461px" %)MENA|0~~16777215
4031 |(% style="width:461px" %)METD|0~~16777215
4032 |(% style="width:461px" %)INRO|0~~16777215
4033 |(% style="width:461px" %)TIMESYN|0~~16777215
4034 |(% style="width:461px" %)TIMEZ|0~~16777215
4035 |(% style="width:461px" %)NTP|0~~16777215
4036 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4037 |(% style="width:461px" %)SENC|0~~16777215
4038
4039 **Address Configuration**
4040
4041 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4042
4043 (% style="text-align:center" %)
4044 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4045
4046 (% style="text-align:center" %)
4047 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4048
4049 Extended tag name
4050
4051 Address range for the extended tag.
4052
4053 **Communication Settings**
4054
4055 Enable HMI Ethernet in [Project Settings];
4056
4057 (% style="text-align:center" %)
4058 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4059
4060 Set PLC IP in [Device IP] settings;
4061
4062 (% style="text-align:center" %)
4063 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4064
4065 **Cable Wiring**
4066
4067 (% style="text-align:center" %)
4068 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4069
4070 = **OpenCAN** =
4071
4072 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4073
4074 This protocol is only available in PI8000 series HMI.
4075
4076 **HMI Settings**
4077
4078 |**Items**|**Settings**|**Note**
4079 |Protocol|OPENCAN|
4080 |Connection|CAN port|
4081 |Baud rate|250000|
4082
4083 **CAN frame setting in HMI**
4084
4085 Click [OpenCAN setting] button in communication setting window;
4086
4087 (% style="text-align:center" %)
4088 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4089
4090 Click [Add] to create a new frame;
4091
4092 (% style="text-align:center" %)
4093 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4094
4095 |**No**|**Items**|**Description**
4096 |1|Add|add a frame related to register address
4097 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4098 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4099 |4|Modify|Modify the frames in frame management
4100 |5|Copy|Copy one frame to another
4101 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4102 |7|Empty|All frames in the list are cleared
4103 |8|Browse|Displays configuration files in XML format in IE
4104 |9|OK|Complete the configuration of the frame and exit
4105
4106 Set CANBUS frame in setting windows
4107
4108 (% style="text-align:center" %)
4109 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4110
4111 |**No**|**Items**|**Description**
4112 |1|ID|Set the ID of a can frame in hexadecimal format;
4113 |2|ID assign|split the ID by PF, PS, and SA;
4114 |3|Frame type|Select Standard frame or Extended Frame;
4115 |4|Frame format|Select between data frame and remote Frame;
4116 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4117 |6|Use address|(((
4118 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4119
4120 **Edit:** Set a bit or word address by its format;
4121
4122 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4123 )))
4124 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4125 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4126 |Feedback mode: feedback mode includes no response, confirm response and data response;
4127 |No response: the device or touch screen will not receive feedback;
4128 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4129 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4130 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4131 |Response timeout: sets whether the response frame timeout;
4132 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4133 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4134 |Manually send: a manually send tick indicates only one send;
4135 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4136 |10|Note|Fill the text to explain the meaning of the frame;
4137 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4138 |12|Current operation display|Display the description of current operation;
4139 |13|Add|Add a new frame;
4140 |14|Save frame|Save the configured frame format;
4141 |15|Cancel|Cancel the frame configuration;
4142
4143 Set CAN address (Read or write operation);
4144
4145 (% style="text-align:center" %)
4146 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4147
4148 |**No.**|**Item**|**Description**
4149 |1|Current address|Displays the register type and register address set by the user in the data access interface
4150 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4151 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4152 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4153 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4154 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4155 |If the trigger condition is a writing operation, there are two situations:(((
4156 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4157 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4158 )))
4159 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4160 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4161 |4|Add|Add current configuration
4162 |5|Close|Close the configuration window to exit
4163
4164 **Multiple Packages Settings**
4165
4166 (% style="text-align:center" %)
4167 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4168
4169 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4170
4171 Select Multiple package type
4172
4173 * Not Multiple packages
4174 * J1939 Multiple packages
4175 * Customized Multiple packages
4176
4177 Click [Edit Receive data] for [Receive] settings
4178
4179 * Start code+ Total length (J1939)
4180
4181 (% style="text-align:center" %)
4182 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4183
4184 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4185
4186 * Start code + Data max length (J1939)
4187
4188 (% style="text-align:center" %)
4189 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4190
4191 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4192
4193 * Data max length (J1939)
4194
4195 (% style="text-align:center" %)
4196 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4197
4198 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4199
4200 * Customized multiple package
4201
4202 (% style="text-align:center" %)
4203 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4204
4205 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4206
4207 Click [Edit Send data] for [Send] setting
4208
4209 * J1939
4210
4211 (% style="text-align:center" %)
4212 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4213
4214 [Data] is all data to be sent.
4215
4216 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4217
4218 * Customized multiple package
4219
4220 (% style="text-align:center" %)
4221 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4222
4223 [Data] is all data to be sent.
4224
4225 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4226
4227 **Cable Wiring**
4228
4229 (% style="text-align:center" %)
4230 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4231
4232 **✎Note:** The address interval between each frame need to be more than a word address;
4233
4234
4235 = **User Defined Protocol** =
4236
4237 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4238
4239 **HMI Settings**
4240
4241 |**Items**|**Settings**|**Note**
4242 |Protocol|User defined protocol|
4243 |Connection|RS485/RS232|
4244 |Baud rate|2400~~187500|
4245 |Stop bits|1/ 2|
4246 |Data bits|7/ 8|
4247 |Parity|None/ Even/ ODD|
4248
4249 **Operating Procedures**
4250
4251 Select [User defined protocol];
4252
4253 Click [User defined protocol] button to open setting window as below;
4254
4255 (% style="text-align:center" %)
4256 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4257
4258 Configure user defined command;
4259
4260 (% style="text-align:center" %)
4261 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4262
4263 |**No**|**Item**|**Description**
4264 |1|Instruction edit|The required command.
4265 |2|Mode|Write to address or read from the address.
4266 |3|Format|Encode format: HEX or ASCII.
4267 |4|Other|(((
4268 **No receiving: **HMI does not respond to the receiving command.
4269
4270 **Send after receiving:** HMI responds to the receiving command.
4271 )))
4272 |5|Manually send|(((
4273 Respond once after trigger the address.
4274
4275 Address: set the trigger address.
4276 )))
4277 |6|Add|Save this setting.
4278 |7|Cancel|Cancel current settings.
4279 |(% rowspan="4" %)8|Add|Add a new command.
4280 |Edit|Edit the selected command.
4281 |Delete|Delete the selected command.
4282 |Clear|Clear all the commands.
4283 |9|Instruction list|Display all current commands.
4284 |10|Address List|Display all the addresses added.
4285 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4286 |Export|Export current command settings to local storage.
4287 |Browse|Browse local command files.
4288 |Advanced|Combine two commands.
4289 |Exit|Complete editing and exit setting.
4290
4291 **Operating Procedures**
4292
4293 Click [Add] to create a new command, as below shows;
4294
4295 (% style="text-align:center" %)
4296 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4297
4298 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4299
4300 (% style="text-align:center" %)
4301 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4302
4303 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4304
4305 (% style="text-align:center" %)
4306 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4307
4308 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4309
4310 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4311
4312 Check settings;
4313
4314 (% style="text-align:center" %)
4315 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4316
4317 |**No**|**Items**|**Description**
4318 |1|Add checking|Add checking command when receiving the data.
4319 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4320 |Differ with send check|Set return checking.
4321 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4322 |Length: The data length need to be checked.
4323
4324 Object settings;
4325
4326 (% style="text-align:center" %)
4327 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4328
4329 |**No**|**Items**|**Description**
4330 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4331 |Address: the triggering address;
4332 |Note: description to object;
4333 |2|Byte order|The numerical display order;
4334
4335 Data length settings;
4336
4337 (% style="text-align:center" %)
4338 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4339
4340 |**No**|**Item**|**Description**
4341 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4342 |Length: the return data length.
4343 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4344 |Length: the write data length.
4345
4346 Instruction length settings
4347
4348 (% style="text-align:center" %)
4349 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4350
4351 |**No**|**Item**|**Description**
4352 |1|Send length|The instruction data will only send designated data length.
4353 |2|Return length|The responds data length.
4354 |3|End code|Instruction will not be terminated until receiving [End code];
4355
4356 **Cable Wiring**
4357
4358 * **RS485**
4359
4360 (% style="text-align:center" %)
4361 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4362
4363 (% style="text-align:center" %)
4364 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4365
4366 * **RS232**
4367
4368 (% style="text-align:center" %)
4369 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4370
4371 **✎Note:** COM3 only available in PI8000/PI9000 series.