Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 260.1 by Hunter on 2023/06/20 13:51

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with HollySys PLC** =
910
911 == **LK MODBUS RTU** ==
912
913 Supported Series: HollySys LK series CPU
914
915 **HMI Settings**
916
917 |=Item|=Recommended|=Note
918 |=Protocol|HollySys LK MODBUS RTU|
919 |=Connection|RS485|
920 |=Baud rate|38400|
921 |=Stop bits|1|
922 |=Data bits|8|
923 |=Parity|NONE|
924 |=PLC Station No.|1|
925 |=HMI Station No.|0|
926
927 **Address List**
928
929 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
930 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
931 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
932 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
933 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
934 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
935 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
936 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
937
938 **Cable Wiring**
939
940 (% style="text-align:center" %)
941 [[image:Hollysys485.png]]
942
943 = **Create communication with Inovance PLC** =
944
945 == **H1U/H2U serial protocol** ==
946
947 **HMI Settings**
948
949 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
950 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
951 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
952 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
953 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
954 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
955 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
956 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
957 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
958
959 (% class="wikigeneratedid" %)
960 **Address List**
961
962 (% style="width:1014px" %)
963 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
964 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
965 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
966 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
967 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
968 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
969 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
970 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
971 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
972 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
973 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
974 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
975 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
976 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
977 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
978 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
979 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
980 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
981
982 (% class="wikigeneratedid" %)
983 **Cable Wiring**
984
985 (% style="text-align:center" %)
986 [[image:Inovance.png]]
987
988 == **H3U serial protocol** ==
989
990 **HMI Settings**
991
992 |=**Item**|=**Settings**|=**Note**
993 |Protocol|INOVANCE H3U PLC|
994 |Connection|RS422|
995 |Baud rate|9600|
996 |Data bit|7|
997 |Parity|EVEN|
998 |Stop bit|1|
999 |PLC station No.|0|
1000
1001 **Address List**
1002
1003 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1004 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1005 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1006 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1007 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1008 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1009 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1010 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1011 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1012 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1013 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1014 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1015 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1016 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1017 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1018 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1019 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1020 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1021 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1022
1023 **Configure the communication protocol**
1024
1025 (% style="text-align:center" %)
1026 [[image:image-20220830170114-4.png]]
1027
1028 [[image:image-20220830170017-3.png]]
1029
1030 **Cable Wiring**
1031
1032 (% style="text-align:center" %)
1033 [[image:Inovance.png]]
1034
1035 == **H3U Ethernet portocol** ==
1036
1037 **HMI Settings**
1038
1039 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1040 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1041 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1042 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1043 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1044 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1045
1046 **Address List**
1047
1048 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1049 |Bit|M|M DDDD|0~~8511|
1050 |Bit|SM|SM DDDD|0~~1023|
1051 |Bit|S|S DDDD|0~~4095|
1052 |Bit|T|T DDD|0~~511|
1053 |Bit|C|C DDD|0~~255|
1054 |Bit|X|X OOO|0~~571|
1055 |Bit|Y|Y OOO|0~~571|
1056 |Word|D|D DDDD|0~~8511|
1057 |Word|SD |SD DDDD|0~~1023|
1058 |Word|R|R DDDDD|0~~32767|
1059 |Word|T|T DDD|0~~255|
1060 |Word|C|C DDD|0~~199|
1061 |Double Word|C|C DDD|200~~255|
1062
1063 **Cable Wiring**
1064
1065 (% style="text-align:center" %)
1066 [[image:CommonEthernet.png]]
1067
1068 = Create communication with LS** PLC** =
1069
1070 == **XGB serial protocol ** ==
1071
1072 **HMI Settings**
1073
1074 |=**Item**|=**Settings**|=**Note**
1075 |Protocol|LS XGB CPU DRIECT|
1076 |Connection|RS232|
1077 |Baud rate|115200|
1078 |Data bit|8|
1079 |Parity|NONE|
1080 |Stop bit|1|
1081 |PLC station No.|1|
1082
1083 **Address List**
1084
1085 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1086 |Bit|P|P|P DDDD.f|0~~2047|
1087 |Bit|M|M|M DDDD.f|0~~2047|
1088 |Bit|L|L|L DDDDD.f|0~~11263|
1089 |Bit|K|K|K DDDD.f|0~~2559|
1090 |Bit|F|F|F DDDD.f|0~~2047|
1091 |Bit|S|S|S DDDDD|0~~12799|
1092 |Bit|D|D|D DDDDD.f|0~~32767|
1093 |Bit|U|U|U FFFF.f|0~~7f31|
1094 |Bit|T|T|T DDDD.f|0~~2047|
1095 |Bit|C|C|C DDDD.f|0~~2047|
1096 |Word|P|P|P DDDD|0~~2047|
1097 |Word|M|M|M DDDD|0~~2047|
1098 |Word|L|L|L DDDDD|0~~11263|
1099 |Word|K|K|K DDDD|0~~2559|
1100 |Word|F|F|F DDDD|0~~2047|
1101 |Word|C|C|C DDDD|0~~2047|
1102 |Word|T|T|T DDDD|0~~2047|
1103 |Word|D|D|D DDDDD|0~~32767|
1104 |Word|N|N|N DDDDD|0~~21503|
1105 |Word|U|U|U FFFF|0~~7f31|
1106 |Word|Z|Z|Z DDD|0~~127|
1107 |Word|R|R|R DDDDD|0~~32767|
1108 |Word|ZR|ZR|Z DDDDD|0~~32767|
1109 |Word|TS|TS|TS DDDD|0~~2047|
1110 |Word|CS|CS|CS DDDD|0~~2047|
1111 |Word|S|S|S DDDDD|0~~12799|
1112
1113 **Configure the communication protocol**
1114
1115 (% style="text-align:center" %)
1116 [[image:image-20221028174410-1.png]]
1117
1118 (% style="text-align:center" %)
1119 [[image:image-20221028174753-2.png]]
1120
1121 (% style="text-align:center" %)
1122 [[image:image-20221028181125-4.png]]
1123
1124 **Pin Definition Diagram**
1125
1126 (% style="text-align:center" %)
1127 [[image:image-20221028180930-3.png]]
1128
1129 == **XBC serial protocol** ==
1130
1131 **HMI Settings**
1132
1133 |=**Item**|=**Settings**|=**Note**
1134 |Protocol|LS XBC CNet|
1135 |Connection|RS232|
1136 |Baud rate|115200|
1137 |Data bit|8|
1138 |Parity|NONE|
1139 |Stop bit|1|
1140 |PLC station No.|1|
1141
1142 **Address List**
1143
1144 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1145 |Bit|P|P|P d|0~~2047|
1146 |Bit|M|M|M d|0~~2047|
1147 |Bit|L|L|L d|0~~11263|
1148 |Bit|K|K|K d|0~~16183|
1149 |Bit|F|F|F d|0~~2047|
1150 |Bit|D|D|D d|0~~32767|
1151 |Bit|R|R|R d|0~~32767|
1152 |Bit|U|U|U d|0~~4095|
1153 |Word|P|P|P d|0~~2047|
1154 |Word|M|M|M d|0~~2047|
1155 |Word|L|L|L d|0~~11263|
1156 |Word|K|K|K d|0~~16183|
1157 |Word|F|F|F d|0~~2047|
1158 |Word|C|C|C d|0~~2047|
1159 |Word|T|T|T d|0~~2047|
1160 |Word|D|D|D d|0~~32767|
1161 |Word|N|N|N d|0~~21503|
1162 |Word|R|R|R d|0~~32767|
1163 |Word|U|U|U d|0~~4095|
1164 |Word|Z|Z|Z d|0~~127|
1165 |Word|S|S|S d|0~~127|
1166
1167 **Configure the communication protocol**
1168
1169 (% style="text-align:center" %)
1170 [[image:image-20220831170807-1.png]]
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20220830174733-2.png]]
1174
1175 **Cable Wiring**
1176
1177 (% style="text-align:center" %)
1178 [[image:image-20220830174659-1.png]]
1179
1180 Pin Definition Diagram
1181
1182 (% style="text-align:center" %)
1183 [[image:image-20220830173402-8.png]]
1184
1185 == **XGK FEnet Ethernet protocol** ==
1186
1187 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1188
1189 **HMI Settings**
1190
1191 |**Items**|**Settings**|**Note**
1192 |Protocol|LG XGK FEnet(Ethernet)|
1193 |Connection|Ethernet|
1194 |Port No.|2004|
1195
1196 **Address List**
1197
1198 |**Type**|**Register**|**Range**|**Format**|**Note**
1199 |(% rowspan="14" %)Word|P|0~~2047|P d|
1200 |M|0~~2047|M d|
1201 |K|0~~2047|K d|
1202 |F|0~~2047|F d|
1203 |T|0~~2047|T d|
1204 |C|0~~2047|C d|
1205 |Z|0~~127|Z d|
1206 |S|0~~127|S d|
1207 |L|0~~11263|L d|
1208 |N|0~~21503|N d|
1209 |D|0~~32767|D d|
1210 |R|0~~32767|R d|
1211 |ZR|0~~65535|ZR d|
1212 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1213
1214 **✎Note:**
1215
1216 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1217 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1218 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1219
1220 **Communication settings in HMI**
1221
1222 Enable HMI Ethernet in [Project Settings];
1223
1224 (% style="text-align:center" %)
1225 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1226
1227 Set PLC IP in [Device IP] settings;
1228
1229 (% style="text-align:center" %)
1230 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1231
1232 **Cable Wiring**
1233
1234
1235 (% style="text-align:center" %)
1236 [[image:CommonEthernet.png]]
1237
1238 = Create communication with **Mitsubishi PLC** =
1239
1240 == **FX1S, 1N, 2N Series Protocol** ==
1241
1242 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1243
1244 **HMI Settings**
1245
1246 |**Item**|**Settings**|**Note**
1247 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1248 |Connection|RS422/RS485/RS232|
1249 |Baud rate|9600~~115200|
1250 |Data bit|7/8|
1251 |Parity|EVEN/Odd/None|
1252 |Stop bit|1/2|
1253 |PLC station No.|1~~255|
1254
1255 **Address List**
1256
1257 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1258 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1259 |Y|Y|Y o|0~~303237|
1260 |M|M|M d|0~~99999|
1261 |T|T|T d|0~~99999|
1262 |C|C|C d|0~~99999|
1263 |S|S|S d|0~~99999|
1264 |SM|SM|SM d|8000~~9999|
1265 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1266 |Y|Y|Y o|0~~303237|
1267 |M|M|M d|0~~99999|
1268 |T|T|T d|0~~99999|
1269 |C|C|C d|0~~199|
1270 |D|D|D d|0~~7999|
1271 |S|S|S d|0~~99999|
1272 |SD|SD|SD d|8000~~9999|
1273
1274 **Cable Wiring**
1275
1276 * **RS485**
1277
1278 (% style="text-align:center" %)
1279 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1283
1284 * **RS422**
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1288
1289 **✎Note:** COM3 only available in PI8000/PI9000 series.
1290
1291 == **FX3U/3G/3GA serial protocol** ==
1292
1293 **HMI Settings**
1294
1295 |=**Item**|=**Settings**|=**Note**
1296 |Protocol|Mitsubishi FX3U/3G/3GA|
1297 |Connection|RS422|
1298 |Baud rate|9600~~115200|
1299 |Data bit|7/8|
1300 |Parity|EVEN/Odd/None|
1301 |Stop bit|1/2|
1302 |PLC station No.|1~~255|
1303
1304 **Address List**
1305
1306 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1307 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1308 |Y|Y|Y o|0~~303237|
1309 |M|M|M d|0~~99999|
1310 |T|T|T d|0~~99999|
1311 |C|C|C d|0~~99999|
1312 |S|S|S d|0~~99999|
1313 |SM|SM|SM d|8000~~9999|
1314 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1315 |Y|Y|Y o|0~~303237|
1316 |M|M|M d|0~~99999|
1317 |T|T|T d|0~~99999|
1318 |C|C|C d|0~~199|
1319 |D|D|D d|0~~7999|
1320 |S|S|S d|0~~99999|
1321 |SD|SD|SD d|8000~~9999|
1322
1323 **Configure the communication protocol**
1324
1325 (% style="text-align:center" %)
1326 [[image:image-20220831095222-1.png]]
1327
1328 (% style="text-align:center" %)
1329 [[image:image-20220831095743-2.png]]
1330
1331 **Wiring**
1332
1333 (% style="text-align:center" %)
1334 [[image:image-20220831100314-6.png]]
1335
1336 == **FX3U Ethernet Protocol** ==
1337
1338 Mitsubishi FX3U series PLC
1339
1340 **HMI Settings**
1341
1342 |Items|Settings|Note
1343 |Protocol|Mitsubishi FX3U|
1344 |Connection|Ethernet|
1345 |Port No.|5009|Must be the same as the PLC setting
1346 |PLC station No.|0|
1347
1348 **Address List**
1349
1350 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1351 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1352 |Y|Y|Y OOO|0~~377|
1353 |M|M|M DDDD|0~~7679|
1354 |SM|SM|SM DDDD|8000~~8511|
1355 |S|S|S DDDD|0~~4095|
1356 |TS|TS|TS DDD|0~~511|
1357 |CS|CS|CS DDD|0~~255|
1358 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1359 |TN|TN|TN DDD|0~~511|
1360 |D|D|D DDDD|0~~7999|
1361 |SD|SD|SD DDDD|8000~~8511|
1362 |R|R|R DDDDD|0~~32767|
1363
1364 **Ethernet Module Settings**
1365
1366 FX3U-ENET-L module configuration
1367 Set up the FX3U-ENET-L Ethernet module settings as follows.
1368 Select the module location, which in this document is Module 0.
1369
1370 [[image:image-20221115140802-1.png]]
1371
1372 Select "Operational setting" to enter the following screen.
1373
1374 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1375
1376 [[image:image-20221115142728-4.png]]
1377
1378 Select "Open setting" to enter the setting interface, the settings are as follows.
1379
1380 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1381
1382 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1383
1384 [[image:image-20221115142945-5.png]]
1385
1386 Click on "transter setup" - "PC side I/F setting", see the following figure.
1387
1388 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1389
1390 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1391
1392 [[image:image-20221115143341-6.png||height="426" width="712"]]
1393
1394 Read and write data from the Ethernet module
1395
1396 [[image:image-20221115143703-7.png]]
1397
1398 Set "Transter setup" to COM communication, and read or write operation as shown below
1399
1400 [[image:image-20221115143809-8.png]]
1401
1402 **PLC Settings (GX Works 2)**
1403
1404 Create a blank FX5U project
1405
1406 Find Current Connection in the navigation
1407
1408 [[image:image-20221115144335-9.png||height="422" width="706"]]
1409
1410 Select Connection Channel List
1411
1412 Select Ethernet board communication
1413
1414 [[image:image-20221115144824-10.png||height="421" width="705"]]
1415
1416 Select Ethernet Module
1417 Set the IP address of the PLC
1418
1419 [[image:image-20221115145228-11.png||height="674" width="708"]]
1420
1421 Read or write PLC data, in this document is read
1422
1423 [[image:image-20221115145553-12.png||height="424" width="711"]]
1424
1425 [[image:image-20221115145559-13.png||height="424" width="711"]]
1426
1427 **HMI Communication Setting**
1428
1429 [[image:image-20221115150003-14.png||height="425" width="712"]]
1430
1431 [[image:image-20221115150235-15.png||height="427" width="713"]]
1432
1433 [[image:image-20221115145559-13.png||height="424" width="711"]]
1434
1435 **HMI Communication Setting**
1436
1437 [[image:image-20221115150003-14.png||height="425" width="712"]]
1438
1439 [[image:image-20221115150235-15.png||height="427" width="713"]]
1440
1441 == **FX5U Serial Port Protocol** ==
1442
1443 Mitsubishi FX5U series PLC
1444
1445 **HMI Settings**
1446
1447 |**Item**|**Settings**|**Note**
1448 |Protocol|Mitsubishi FX5U|
1449 |Connection|RS422/RS485|
1450 |Baud rate|9600|
1451 |Data bit|7|
1452 |Parity|Odd|
1453 |Stop bit|1|
1454 |PLC station No.|1~~255|Need to be the same as PLC settings
1455
1456 **Address List**
1457
1458 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1459 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1460 |Y|Y|Y o|0~~303237|
1461 |M|M|M d|0~~99999|
1462 |B|B|B h|0~~7FFF|
1463 |F|F|F d|0~~32767|
1464 |SB|SB|SB h|0~~7FFF|
1465 |TS|TS|TS d|0~~1023|
1466 |TC|TC|TC d|0~~1023|
1467 |STS|STS|STS d|0~~1023|
1468 |STC|STC|STS d|0~~1023|
1469 |CS|CS|CS d|0~~1023|
1470 |CC|CC|CC d|0~~1023|
1471 |SM|SM|SM d|0~~9999|
1472 |L|L|L d|0~~32767|
1473 |S|S|S d|0~~4095|
1474 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1475 |TN|TN|TN d|0~~1023|
1476 |STN|STN|STN d|0~~1023|
1477 |CN|CN|CN d|0~~1023|
1478 |R|R|R d|0~~32767|
1479 |SW|SW|SW h|0~~7FFF|
1480 |Z|Z|Z d|0~~23|
1481 |D|D|D d|0~~7999|
1482 |SD|SD|SD d|0~~11999|
1483
1484 **PLC Settings (GX Works 3)**
1485
1486 Create a blank FX5U project
1487
1488 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1489
1490 (% style="text-align:center" %)
1491 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1492
1493 Select protocol in the setting item, and set parameters.
1494
1495 (% style="text-align:center" %)
1496 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1497
1498 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1499
1500 (% style="text-align:center" %)
1501 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1502
1503 Click the [Apply] button to finish the setting.
1504
1505 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1506
1507 (% style="text-align:center" %)
1508 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1509
1510 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1511
1512 Done.
1513
1514 **Cable Wiring**
1515
1516 * **RS485**
1517
1518 (% style="text-align:center" %)
1519 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1520
1521 (% style="text-align:center" %)
1522 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1523
1524 * **RS422**
1525
1526 (% style="text-align:center" %)
1527 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1528
1529 **✎Note:** COM3 only available in PI8000/PI9000 series.
1530
1531 == **L02 Serial Protocol** ==
1532
1533 Mitsubishi L02 series CPU built-in serial port.
1534
1535 **HMI Settings**
1536
1537 |=**Item**|=**Settings**|=**Note**
1538 |Protocol|Mitsubishi L02|
1539 |Connection|RS422|
1540 |Baud rate|115200|
1541 |Data bit|8|
1542 |Parity|Odd|
1543 |Stop bit|1|
1544 |PLC station No.|1~~255|Need to be the same as PLC settings
1545
1546 **Address List**
1547
1548 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1549 |Bit|X|X|X h|0~~FFFF|
1550 |Bit|Y|Y|Y h|0~~FFFF|
1551 |Bit|M|M|M d|0~~9999|
1552 |Bit|L|L|L d|0~~9999|
1553 |Bit|F|F|F d|0~~9999|
1554 |Bit|B|B|B h|0~~FFFF|
1555 |Bit|V|V|V d|0~~2047|
1556 |Bit|TC|TC|TC d|0~~9999|
1557 |Bit|SS|SS|SS d|0~~9999|
1558 |Bit|SC|SC|SC d|0~~9999|
1559 |Bit|CS|CS|CS d|0~~9999|
1560 |Bit|CC|CC|CC d|0~~9999|
1561 |Bit|SB|SB|SB h|0~~FFFF|
1562 |Bit|SM|SM|SM d|0~~2047|
1563 |Bit|STS|STS|STS d|0~~1023|
1564 |Bit|S|S|S d|0~~9999|
1565 |Bit|DX|DX|DX h|0~~FFFF|
1566 |Bit|DY|DY|DY h|0~~FFFF|
1567 |Bit|TS|TS|TS d|0~~9999|
1568 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1569 |Word|W|W|W h|0~~FFFF|
1570 |Word|TN|TN|TN d|0~~99999|
1571 |Word|SN|SN|SN d|0~~99999|
1572 |Word|CN|CN|CN d|0~~99999|
1573 |Word|R|R|R d|0~~99999|
1574 |Word|SW|SW|SW h|0~~FFFF|
1575 |Word|Z|Z|Z d|0~~99999|
1576 |Word|ZR|ZR|ZR h|0~~FFFF|
1577 |Word|D|D|D d|0~~99999|
1578
1579 **Communication Settings**
1580
1581 (% style="text-align:center" %)
1582 [[image:image-20220831105732-3.png]]
1583
1584 (% style="text-align:center" %)
1585 [[image:image-20220831110004-5.png]]
1586
1587 **Cable Wiring**
1588
1589 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1590
1591 Pin Definition Diagram
1592
1593 (% style="text-align:center" %)
1594 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1595
1596 == **L02 MELSEC (Ethernet) Protocol** ==
1597
1598 Mitsubishi Q series CPU built-in Ethernet port.
1599
1600 **HMI Settings**
1601
1602 |**Items**|**Settings**|**Note**
1603 |Protocol|MIT L02 CPU MELSEC|
1604 |Connection|Ethernet|
1605 |Port No.|1025|Must be the same as the PLC setting
1606 |PLC station No.|0|Must be the same as the PLC setting
1607
1608 **Address List**
1609
1610 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1611 |Bit|X|X|X h|0~~FFFF|
1612 |Bit|Y|Y|Y h|0~~FFFF|
1613 |Bit|M|M|M d|0~~9999|
1614 |Bit|L|L|L d|0~~9999|
1615 |Bit|F|F|F d|0~~9999|
1616 |Bit|B|B|B h|0~~FFFF|
1617 |Bit|V|V|V d|0~~2047|
1618 |Bit|TC|TC|TC d|0~~9999|
1619 |Bit|SS|SS|SS d|0~~9999|
1620 |Bit|SC|SC|SC d|0~~9999|
1621 |Bit|CS|CS|CS d|0~~9999|
1622 |Bit|CC|CC|CC d|0~~9999|
1623 |Bit|SB|SB|SB h|0~~FFFF|
1624 |Bit|SM|SM|SM d|0~~2047|
1625 |Bit|STS|STS|STS d|0~~1023|
1626 |Bit|S|S|S d|0~~9999|
1627 |Bit|DX|DX|DX h|0~~FFFF|
1628 |Bit|DY|DY|DY h|0~~FFFF|
1629 |Bit|TS|TS|TS d|0~~9999|
1630 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1631 |Word|W|W|W h|0~~FFFF|
1632 |Word|TN|TN|TN d|0~~99999|
1633 |Word|SN|SN|SN d|0~~99999|
1634 |Word|CN|CN|CN d|0~~99999|
1635 |Word|R|R|R d|0~~99999|
1636 |Word|SW|SW|SW h|0~~FFFF|
1637 |Word|Z|Z|Z d|0~~99999|
1638 |Word|ZR|ZR|ZR h|0~~FFFF|
1639 |Word|D|D|D d|0~~99999|
1640
1641 **Communication Settings**
1642
1643 Enable HMI Ethernet in [Project Settings];
1644
1645 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1646
1647 Set PLC IP in [Device IP] settings;
1648
1649 (% style="text-align:center" %)
1650 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1651
1652 **PLC Settings (GX Works2 )**
1653
1654 Create a project
1655
1656 Set PLC IP, subnet mask and gateway;
1657
1658 Select [Binary Code] as communication data code;
1659
1660 (% style="text-align:center" %)
1661 [[image:image-20221108202109-2.png||height="636" width="732"]]
1662
1663 Set PLC port number, for example 1025
1664
1665 (% style="text-align:center" %)
1666 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1667
1668 Save settings;
1669
1670 Download project into PLC device;
1671
1672 Restart PLC device;
1673
1674 **Cable Wiring**
1675
1676 (% style="text-align:center" %)
1677 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1678
1679 == **QJ71C24N MELSEC Protocol** ==
1680
1681 Mitsubishi QJ71C24N communication module built-in serial port;
1682
1683 **HMI Settings**
1684
1685 |**Items**|**Settings**|**Note**
1686 |Protocol|MIT QJ71 MELSEC|
1687 |Connection|422|
1688 |Baud rate|9600|
1689 |Data bit|8|
1690 |Parity|ODD|
1691 |Stop bit|1|
1692 |PLC station No.|1~~255|Need to be the same as PLC settings
1693
1694 **Address List**
1695
1696 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1697 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1698 |Y|Y|Y FFFF|0~~1FFF|
1699 |M|M|M DDDDD|0~~99999|
1700 |L|L|L DDDD|0~~8191|
1701 |F|F|F DDDD|0~~2047|
1702 |V|V|V DDDD|0~~2047|
1703 |B|B|B FFFF|0~~1FFF|
1704 |TS|TS|TS DDDD|0~~2047|
1705 |TC|TC|TC DDDD|0~~2047|
1706 |SS|SS|SS DDDD|0~~2047|
1707 |SC|SC|SC DDDD|0~~2047|
1708 |CS|CS|CS DDDD|0~~1023|
1709 |CC|CC|CC DDDD|0~~1023|
1710 |SB|SB|SB FFF|0~~7FF|
1711 |S|S|S D|0~~8191|
1712 |DX|DX|DX FFFF|0~~1FFF|
1713 |DY|DY|DY FFFF|0~~1FFF|
1714 |SM_|SM_|SM_ DDDD|8000~~9999|
1715 |SM|SM|SM DDDD|0~~2047|
1716 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1717 |D|D|D DDDDD|0~~12287|
1718 |W|W|W FFFF|0~~1FFF|
1719 |TN|TN|TN DDDD|0~~2047|
1720 |SN|SN|SN DDDD|0~~2047|
1721 |CN|CN|CN DDDD|0~~1023|
1722 |R|R|R DDDDD|0~~32767|
1723 |SW|SW|SW FFF|0~~7FF|
1724 |Z|Z|Z D|0~~15|
1725 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1726
1727 **Communication Settings**
1728
1729 (% style="text-align:center" %)
1730 [[image:image-20221109135738-1.png]]
1731
1732 (% style="text-align:center" %)
1733 [[image:image-20221109140016-3.png]]
1734
1735 Pin Definition Diagram
1736
1737 (% style="text-align:center" %)
1738 [[image:image-20221109140406-4.png]]
1739
1740 == **QJ71E71 MELSEC Protocol** ==
1741
1742 Mitsubishi QJ71E71 Ethernet communication module;
1743
1744 **HMI Settings**
1745
1746 |**Items**|**Settings**|**Note**
1747 |Protocol|MIT QJ71E71 MELSEC|
1748 |Connection|Ethernet|
1749 |Port No.|1025|Must be the same as the PLC setting
1750 |PLC station No.|0|Must be the same as the PLC setting
1751
1752 **Address List**
1753
1754 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1755 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1756 |Y|Y|Y h|0~~1FFF|
1757 |M|M|M d|0~~99999|
1758 |L|L|L d|0~~8191|
1759 |F|F|F d|0~~2047|
1760 |B|B|B h|0~~1FFF|
1761 |V|V|V d|0~~2047|
1762 |TS|TS|TS d|0~~2047|
1763 |TC|TC|TC d|0~~2047|
1764 |SS|SS|SS d|0~~2047|
1765 |SC|SC|SC d|0~~2047|
1766 |CS|CS|CS d|0~~1023|
1767 |CC|CC|CC d|0~~1023|
1768 |SB|SB|SB h|0~~7FF|
1769 |S|S|S d|0~~8191|
1770 |DX|DX|DX h|0~~1FFF|
1771 |DY|DY|DY h|0~~1FFF|
1772 |SM|SM|SM d|8000~~9999|
1773 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1774 |D|D|D d|0~~12287|
1775 |W|W|W h|0~~1FFF|
1776 |TN|TN|TN d|0~~2047|
1777 |SN|SN|SN d|0~~2047|
1778 |CN|CN|CN d|0~~1023|
1779 |R|R|R d|0~~32767|
1780 |SW|SW|SW h|0~~7FF|
1781 |Z|Z|Z d|0~~15|
1782 |ZR|ZR|ZR h|0~~FE7FF|
1783
1784 **HMI Communication Settings**
1785
1786 1) Enable HMI Ethernet in [Project Settings];
1787
1788 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1789
1790 2) Set PLC IP in [Device IP] settings
1791
1792 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1793
1794 **PLC Settings(GX Works2)**
1795
1796 * Click [Ethernet/CC IE/MELSECNET];
1797 * Please select [Ethernet] as network type;
1798 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1799 * Select [Online] as Mode;
1800 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1801 * Click [Operation setting] to set IP;
1802 * Select [Binary Code] as [Communication Data Code];
1803 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1804 * Click [Open setting]
1805 * Set protocol: TCP;
1806 * Set [unpassive] in [Open system];
1807 * Set [receive] in [Fixed buffer];
1808 * Set [procedure Exist] in [Fixed buffer communication];
1809 * Disable [Pairing open];
1810 * Set [No confirm] in [Existence confirmation];
1811 * Host station port number: 5009;
1812 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1813 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1814 * Download project into PLC and restart it
1815
1816 **Cable Wiring**
1817
1818 (% style="text-align:center" %)
1819 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1820
1821 = Create communication with **MODBUS** =
1822
1823 == **MODBUS RTU Master** ==
1824
1825 Supported Series: MODBUS RTU CONTROLLER
1826
1827 HMI works as MODBUS SLAVE connecting with MASTER
1828
1829 (% style="text-align:center" %)
1830 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1831
1832 (% style="text-align:center" %)
1833 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1834
1835 (% style="text-align:center" %)
1836 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1837
1838 **HMI Settings**
1839
1840 |**Items**|**Settings**|**Note**
1841 |Protocol|MODBUS RTU Master|
1842 |Connection|RS485/RS232|
1843 |Baud rate|2400~~187500|
1844 |Data bit|8|
1845 |Parity|Even/ Odd/ None|
1846 |Stop bit|1/2|
1847 |Station No.|0~~255|
1848
1849 **Address List**
1850
1851 |**Type**|**HMI address**|**MODBUS code**|**Range**
1852 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1853 |Word|HDW3500~~HDW7999|4|0~~4499
1854
1855 **Cable Wiring**
1856
1857 * **RS485**
1858
1859 (% style="text-align:center" %)
1860 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1861
1862 (% style="text-align:center" %)
1863 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1864
1865 * **RS232**
1866
1867 (% style="text-align:center" %)
1868 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1869
1870 **✎Note:** COM3 only available in PI8000/PI9000 series.
1871
1872 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1873
1874 Supported Series: MODBUS RTU CONTROLLER
1875
1876 HMI works as MODBUS MASTER connecting with SLAVE.
1877
1878 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1879
1880 (% style="text-align:center" %)
1881 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1882
1883 (% style="text-align:center" %)
1884 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1885
1886 (% style="text-align:center" %)
1887 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1888
1889 **HMI Settings**
1890
1891 |**Items**|**Settings**|**Note**
1892 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1893 |Connection|RS485/RS232|
1894 |Baud rate|2400~~187500|
1895 |Data bit|8|
1896 |Parity|Even/ Odd/ None|
1897 |Stop bit|1/2|
1898 |PLC station No.|0~~255|
1899
1900 **Address List**
1901
1902 |**Type**|**Address Type**|**Function code & Description**
1903 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1904 |06 (write single register: write a binary value to a holding register)
1905 |10 (write values to multiple addresses )
1906 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1907 |06 (write single register: write a binary value to a holding register)
1908 |10 (write values to multiple addresses )
1909 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1910 |06 (write single register: write a binary value to a holding register)
1911 |10 (write values to multiple addresses )
1912 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1913 |10 (write values to multiple addresses )
1914 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1915 |05 (Force a single coil to force the on/off state of a logic coil)
1916 |0F (Write multiple bits, ie write continuously)
1917 |(% rowspan="3" %)1|02 (Read the input state)
1918 |05 (Force a single coil to force the on/off state of a logic coil)
1919 |0F (Write multiple bits)
1920 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1921 |05 (Force a single coil to force the on/off state of a logic coil)
1922 |0F (Write multiple bits)
1923 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1924 |0F (Write multiple bits)
1925
1926 **✎Note:**
1927
1928 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1929 * The function codes sent out are the same as those that read and write words.
1930
1931 **Station number for more than one slaves**
1932
1933 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1934
1935 (% style="text-align:center" %)
1936 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1937
1938 **Cable Wiring**
1939
1940 * **RS485**
1941
1942 (% style="text-align:center" %)
1943 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1944
1945 (% style="text-align:center" %)
1946 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1947
1948 * **RS232**
1949
1950 (% style="text-align:center" %)
1951 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1952
1953 **✎Note:** COM3 only available in PI8000/PI9000 series.
1954
1955 == **Communicate with Modbus Meter** ==
1956
1957 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
1958
1959 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
1960
1961 (% style="text-align:center" %)
1962 [[image:LinfeeDiagram.png]]
1963
1964 2. Check the specific Modbus parameter in the communication menu from LED display.
1965
1966 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
1967
1968 {{info}}
1969 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
1970 {{/info}}
1971
1972 (% style="text-align:center" %)
1973 [[image:MeterModbusAllView.png]]
1974
1975 3. Create new project and change the Communication settings.
1976
1977 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
1978
1979 (% style="text-align:center" %)
1980 [[image:PIStudioSetupMeterModbusPara.png]]
1981
1982 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
1983
1984 The following table is intercept part of the manual for Linfee Modbus manual.
1985
1986 **0x03/0x04 command data register address**:
1987
1988 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
1989 | HEX|DEC| | | |
1990 |0x00|0|Reserved| | |
1991 |0x02|2|Reserved| | |
1992 |0x04|4|Reserved| | |
1993 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
1994 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
1995 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
1996 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
1997 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
1998 |0x10|16|Uca|float|2|Line Voltage data, Unit V
1999 |0x12|18|Ia|float|2|Phase Current data, Unit A
2000 |0x14|20|Ib|float|2|Phase Current data, Unit A
2001 |0x16|22|Ic|float|2|Phase Current data, Unit A
2002
2003 {{info}}
2004 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2005 {{/info}}
2006
2007 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2008
2009 (% style="text-align:center" %)
2010 [[image:MeterModbusPInumericSet.png]]
2011
2012 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2013
2014 (% style="text-align:center" %)
2015 [[image:MeterModbusNumericInputFormat.png]]
2016
2017 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2018
2019 (% style="text-align:center" %)
2020 [[image:ActualHMIModbusResult.jpg]]
2021
2022 == **MODBUS TCP Slave (All function)** ==
2023
2024 Supported series: MODBUS TCP controller
2025
2026 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2027
2028 (% style="text-align:center" %)
2029 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2030
2031 (% style="text-align:center" %)
2032 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2033
2034 (% style="text-align:center" %)
2035 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2036
2037 **HMI Setting**
2038
2039 |**Items**|**Settings**|**Note**
2040 |Protocol|MODBUS TCP Slave (All function)|
2041 |Connection|Ethernet|
2042 |Port No.|502|
2043 |PLC station No.|1|
2044
2045 **Address List**
2046
2047 |**Type**|**Register**|**Function code & Description**
2048 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2049 |06 (write single register: write a binary value to a holding register)
2050 |10 (write values to multiple addresses )
2051 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2052 |06 (write single register: write a binary value to a holding register)
2053 |10 (write values to multiple addresses )
2054 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2055 |06 (write single register: write a binary value to a holding register)
2056 |10 (write values to multiple addresses )
2057 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2058 |10 (write values to multiple addresses )
2059 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2060 |05 (Force a single coil to force the on/off state of a logic coil)
2061 |0F (Write multiple bits, ie write continuously)
2062 |(% rowspan="3" %)1|02 (Read the input state)
2063 |05 (Force a single coil to force the on/off state of a logic coil)
2064 |0F (Write multiple bits)
2065 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2066 |05 (Force a single coil to force the on/off state of a logic coil)
2067 |0F (Write multiple bits)
2068 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2069 |0F (Write multiple bits)
2070
2071 **Communication Settings**
2072
2073 Enable HMI Ethernet in [Project Settings];
2074
2075 (% style="text-align:center" %)
2076 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2077
2078 Set PLC IP in [Device IP] settings;
2079
2080 (% style="text-align:center" %)
2081 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2082
2083 **Cable Wiring**
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2087
2088 = Create communication with **Omron** PLC =
2089
2090 == CJ TCP FINS Ethemet  Protocol ==
2091
2092 Supported device:CJ series、CJ1W-EIP21
2093
2094 **HMI Settings**
2095
2096 |=**Items**|=**Settings**|=**Note**
2097 |Protocol|OMRON CJ TCP FINS Ethemet|
2098 |Connection|Ethernet|
2099 |Port No.|9600|
2100 |Device No.|0|
2101 |HMI No.|0|(((
2102
2103 )))
2104
2105 **Address List**
2106
2107 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2108 |Bit|CIO|CIO|CIO d|0~~99999|
2109 |Bit|W|W|W d|0~~99999|
2110 |Bit|D|D|D d|0~~99999|
2111 |Bit|H|H|H d|0~~99999|
2112 |Bit|A|A|A d|0~~99999|
2113 |Bit|T|T|T h|0~~99999|
2114 |Bit|CF|CF|CF d|0~~99999|
2115 |Bit|FF|FF|FF d|0~~99999|
2116 |Bit|C|C|C d|0~~99999|
2117 |Bit|EM0|EM0|EM0 d|0~~99999|
2118 |Bit|EM1|EM1|EM1 d|0~~99999|
2119 |Bit|EM2|EM2|EM2 d|0~~99999|
2120 |Bit|EM3|EM3|EM3 d|0~~99999|
2121 |Bit|EM4|EM4|EM4 d|0~~99999|
2122 |Bit|EM5|EM5|EM5 h|0~~99999|
2123 |Bit|EM6|EM6|EM6 d|0~~99999|
2124 |Bit|EM7|EM7|EM7 d|0~~99999|
2125 |Bit|EM8|EM8|EM8 d|0~~99999|
2126 |Bit|EM9|EM9|EM9 d|0~~99999|
2127 |Bit|EMA|EMA|EMA d|0~~99999|
2128 |Bit|EMB|EMB|EMB d|0~~99999|
2129 |Bit|EMC|EMC|EMC d|0~~99999|
2130 |Bit|Lamp|Lamp|Lamp d|0~~0|
2131 |Word|CIO|CIO|CIO d|0~~99999|
2132 |Word|W|W|W d|0~~99999|
2133 |Word|D|D|D d|0~~99999|
2134 |Word|H|H|H d|0~~99999|
2135 |Word|A|A|A d|0~~99999|
2136 |Word|T|T|T h|0~~99999|
2137 |Word|CF|CF|CF d|0~~99999|
2138 |Word|FF|FF|FF d|0~~99999|
2139 |Word|C|C|C d|0~~99999|
2140 |Word|EM0|EM0|EM0 d|0~~99999|
2141 |Word|EM1|EM1|EM1 d|0~~99999|
2142 |Word|EM2|EM2|EM2 d|0~~99999|
2143 |Word|EM3|EM3|EM3 d|0~~99999|
2144 |Word|EM4|EM4|EM4 d|0~~99999|
2145 |Word|EM5|EM5|EM5 h|0~~99999|
2146 |Word|EM6|EM6|EM6 d|0~~99999|
2147 |Word|EM7|EM7|EM7 d|0~~99999|
2148 |Word|EM8|EM8|EM8 d|0~~99999|
2149 |Word|EM9|EM9|EM9 d|0~~99999|
2150 |Word|EMA|EMA|EMA d|0~~99999|
2151 |Word|EMB|EMB|EMB d|0~~99999|
2152 |Word|EMC|EMC|EMC d|0~~99999|
2153 |Word|IR|IR|IR d|0~~99999|
2154 |Word|DR|DR|DR d|0~~99999|
2155
2156 **Configure the communication protocol**
2157
2158 (% style="text-align:center" %)
2159 [[image:image-20220830143348-1.png]]
2160
2161 (% style="text-align:center" %)
2162 [[image:image-20220830143511-2.png]]
2163
2164 **Configure CJ1W-EIP21 connect with HMI**
2165
2166 (% style="text-align:center" %)
2167 [[image:ftEVGvAprh.png]]
2168
2169 Select TCP_Client_2N
2170
2171 (% style="text-align:center" %)
2172 [[image:RURXWcgyCd.png]]
2173
2174 **Cable Wiring**
2175
2176 Pin Definition Diagram
2177
2178 (% style="text-align:center" %)
2179 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2180
2181 == **CP1E/CP1H serial protocol** ==
2182
2183 Supported device: OMRON CS1(CP1E/CP1H)
2184
2185 **HMI Settings**
2186
2187 |=**Items**|=**Settings**|=**Note**
2188 |Protocol|OMRON CS1(CP1E/CP1H)|
2189 |Connection|RS232 (9600, 2, 7, EVEN)|
2190 |Port No.|None|
2191 |PLC station No.|0|
2192
2193 **Address List**
2194
2195 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2196 |Bit|CIO|CIO|CIO d|0~~99999|
2197 |Bit|W|W|W d|0~~99999|
2198 |Bit|D|D|D d|0~~99999|
2199 |Bit|H|H|H d|0~~99999|
2200 |Bit|A|A|A d|0~~99999|
2201 |Bit|TF|T|T h|0~~99999|
2202 |Bit|CF|CF|CF d|0~~99999|
2203 |Bit|T|FF|FF d|0~~99999|
2204 |Bit|C|C|C d|0~~99999|
2205 |Bit|EM0|EM0|EM0 d|0~~99999|
2206 |Bit|EM1|EM1|EM1 d|0~~99999|
2207 |Bit|EM2|EM2|EM2 d|0~~99999|
2208 |Bit|EM3|EM3|EM3 d|0~~99999|
2209 |Bit|EM4|EM4|EM4 d|0~~99999|
2210 |Bit|EM5|EM5|EM5 h|0~~99999|
2211 |Bit|EM6|EM6|EM6 d|0~~99999|
2212 |Bit|EM7|EM7|EM7 d|0~~99999|
2213 |Bit|EM8|EM8|EM8 d|0~~99999|
2214 |Bit|EM9|EM9|EM9 d|0~~99999|
2215 |Bit|EMA|EMA|EMA d|0~~99999|
2216 |Bit|EMB|EMB|EMB d|0~~99999|
2217 |Bit|EMC|EMC|EMC d|0~~99999|
2218 |Word|CIO|CIO|CIO d|0~~99999|
2219 |Word|W|W|W d|0~~99999|
2220 |Word|D|D|D d|0~~99999|
2221 |Word|H|H|H d|0~~99999|
2222 |Word|A|A|A d|0~~99999|
2223 |Word|T|T|T h|0~~99999|
2224 |Word|CIO|CF|CF d|0~~99999|
2225 |Word|C|C|C d|0~~99999|
2226 |Word|EM0|EM0|EM0 d|0~~99999|
2227 |Word|EM1|EM1|EM1 d|0~~99999|
2228 |Word|EM2|EM2|EM2 d|0~~99999|
2229 |Word|EM3|EM3|EM3 d|0~~99999|
2230 |Word|EM4|EM4|EM4 d|0~~99999|
2231 |Word|EM5|EM5|EM5 h|0~~99999|
2232 |Word|EM6|EM6|EM6 d|0~~99999|
2233 |Word|EM7|EM7|EM7 d|0~~99999|
2234 |Word|EM8|EM8|EM8 d|0~~99999|
2235 |Word|EM9|EM9|EM9 d|0~~99999|
2236 |Word|EMA|EMA|EMA d|0~~99999|
2237 |Word|EMB|EMB|EMB d|0~~99999|
2238 |Word|EMC|EMC|EMC d|0~~99999|
2239 |Word|IR|IR|IR d|0~~99999|
2240 |Word|DR|DR|DR d|0~~99999|
2241
2242 **Configure the communication protocol**
2243
2244 (% style="text-align:center" %)
2245 [[image:image-20220902153118-1.png]]
2246
2247 (% style="text-align:center" %)
2248 [[image:image-20220902151322-2.png]]
2249
2250 **Cable Wiring**
2251
2252 (% style="text-align:center" %)
2253 [[image:image-20220902153949-2.png]]
2254
2255 Pin Definition Diagram
2256
2257 (% style="text-align:center" %)
2258 [[image:image-20220902154056-3.png]]
2259
2260 == **EC55 Protocol** ==
2261
2262 Supported device: EC55 temperature instrument
2263
2264 **1)HMI Settings**
2265
2266 |**Items**|**Settings**|**Note**
2267 |Protocol|Omron EC55|
2268 |Connection|RS485 (9600, 2, 7, EVEN)|
2269 |Port No.|None|
2270 |PLC station No.|0|
2271
2272 **2)Address List**
2273
2274 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2275 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2276 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2277 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2278 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2279 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2280 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2281 |CP|-|0-6|Read controller intrinsic property
2282 |CS|-|0-2|Read controller states
2283 |CA|-|0-17|Action command
2284
2285 **3)Device Settings**
2286
2287 Omron E5CC PLC configuration
2288
2289 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2290
2291 (% style="text-align:center" %)
2292 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2293
2294 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2295
2296 (% style="text-align:center" %)
2297 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2298
2299 **✎Note:** The communication settings for HMI should be consistent with this setting.
2300
2301 **Cable Wiring**
2302
2303 (% style="text-align:center" %)
2304 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2305
2306 (% style="text-align:center" %)
2307 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2308
2309 **✎Note:**
2310
2311 * COM3 only available in PI8000/PI9000 series.
2312 * CA address could not support continuous writing function;
2313 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2314 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2315 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2316 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2317 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2318 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2319 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2320
2321 == **EtherNet/IP NX series Protocol** ==
2322
2323 Supported series: Omron NX/NJ series
2324
2325 **HMI Setting**
2326
2327 |**Items**|**Settings**|**Note**
2328 |Protocol|Omron NX Ethernet/IP|
2329 |Connection|Ethernet|
2330 |Port No.|44818|
2331 |PLC station No.|1|
2332
2333 **Instruction**
2334
2335 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2336
2337 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2338
2339 (% style="text-align:center" %)
2340 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2341
2342 **Export labels from Sysmac Studio**
2343
2344 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2345
2346 (% style="text-align:center" %)
2347 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2348
2349 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2350
2351 Click [Label manage];
2352
2353 (% style="text-align:center" %)
2354 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2355
2356 Click [Import labels] and then select the file exported in step 1;
2357
2358 (% style="text-align:center" %)
2359 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2360
2361 The Import Status field shows the result, click [OK] to finish importing address labels;
2362
2363 (% style="text-align:center" %)
2364 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2365
2366 **Communication Settings**
2367
2368 Enable HMI Ethernet in [Project Settings];
2369
2370 (% style="text-align:center" %)
2371 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2372
2373 Set PLC IP in [Device IP] settings;
2374
2375 (% style="text-align:center" %)
2376 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2377
2378 (% style="text-align:center" %)
2379 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2380
2381 **Cable Wiring**
2382
2383 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2384
2385 == CV/CJ1M/CS1H ==
2386
2387 **HMI Setting:**
2388
2389 |=**Parameters**|=**Recommended**
2390 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2391 |=**PLC I/F**|RS232
2392 |=**Baud rate**|9600
2393 |=**Data bits**|7
2394 |=**Parity**|Even
2395 |=**Stop bits**|2
2396 |=**PLC sta. no.**|0
2397
2398 **PLC Setting:**
2399
2400 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2401
2402 **Device Address:**
2403
2404 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2405 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2406 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2407 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2408 |=B|H|DDDDdd|0 ~~ 409515|
2409 |=B|A|DDDDdd|0 ~~ 409515|
2410 |=B|TF|DDDDdd|0 ~~ 409515|
2411 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2412 |=B|T|DDDD|0 ~~ 4095|
2413 |=B|C|DDDD|0 ~~ 4095|
2414 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2415 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2416 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2417 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2418 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2419 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2420 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2421 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2422 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2423 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2424 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2425 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2426 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2427 |=B|Lamp|D|0~~0|
2428
2429 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2430 |=W|LR_W|DDDD|0 ~~ 4095|
2431 |=W|TC|DDD|0 ~~ 511|
2432 |=W|DM|DDDD|0 ~~ 9999|Data Register
2433
2434 **Wiring Diagram:**
2435
2436 **RS-232**
2437
2438 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2439
2440 Communication Module:
2441
2442 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2443
2444 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2445
2446 (% style="text-align:center" %)
2447 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2448
2449 = Create communication with **Rockwell PLC** =
2450
2451 == **DF1 Protocol** ==
2452
2453 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2454
2455 **HMI Settings**
2456
2457 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2458 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2459 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2460 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2461 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2462 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2463 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2464 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2465 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2466
2467 **PLC Settings**
2468
2469 DF1 Full Duplex protocol and CRC error check
2470
2471 **Address List**
2472
2473 (% class="table-bordered" %)
2474 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2475 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2476 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2477 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2478 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2479 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2480 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2481 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2482 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2483 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2484 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2485 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2486
2487 **Cable Wiring**
2488
2489 (% style="text-align:center" %)
2490 [[image:AB.gif]]
2491
2492 == **DF1 Advanced Protocol** ==
2493
2494 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2495
2496 **HMI Settings**
2497
2498 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2499 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2500 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2501 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2502 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2503 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2504 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2505 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2506 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2507
2508 **Address List**
2509
2510 (% class="table-bordered" %)
2511 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2512 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2513 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2514 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2515 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2516 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2517 Bit data file B0~~B99
2518
2519 First two digits is for file number
2520
2521 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2522 )))
2523 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2524 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2525 Integer data file bit format N0~~N99
2526
2527 First two digits is for file number
2528
2529 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2530 )))
2531 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2532 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2533 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2534 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2535 Timer Preset Value
2536
2537 First two digits is for file number
2538
2539 For example, TNS99255 represents file number T99, address 255.
2540 )))
2541 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2542 Timer Accumulator Value
2543
2544 First two digits is for file number
2545
2546 For example, TNP99255 represents file number T99, address 255.
2547 )))
2548 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2549 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2550 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2551 Counter Preset Value
2552
2553 First two digits is for file number
2554
2555 For example, CNS99255 represents file number C99, address 255.
2556 )))
2557 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2558 Counter Accumulator Value
2559
2560 First two digits is for file number
2561
2562 For example, CNP99255 represents file number C99, address 255.
2563 )))
2564 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2565 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2566 Integer data file
2567
2568 First two digits is for file number
2569
2570 For example, NN99255 represents file number N99, address 255.
2571 )))
2572 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2573 Only able to communicate with file number F8
2574 )))
2575 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2576 Floating point data file
2577
2578 First two digits is for file number
2579
2580 For example, FN99255 represents file number F99, address 255.
2581 )))
2582 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2583
2584 **Cable Wiring**
2585
2586 (% style="text-align:center" %)
2587 [[image:AB.gif]]
2588
2589 == **MicroLogix Protocol** ==
2590
2591 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2592
2593 **HMI Settings**
2594
2595 (% class="table-bordered" %)
2596 |**Item**|**Settings**|**Note**
2597 |Protocol|Allen-Bradlley MicroLogix|
2598 |Connection|RS232|
2599 |Baud rate|19200|
2600 |Data bit|8|
2601 |Parity|None|
2602 |Stop bit|1|
2603 |PLC station No.|1|
2604
2605 **Address List**
2606
2607 (% class="table-bordered" %)
2608 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2609 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2610 |O|O d.d|0.0~~255.15|
2611 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2612 |S|S d.d|0.0~~255.15|
2613 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2614 |(% rowspan="9" %)Word|S|S d|0~~255|
2615 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2616 |TP|TP nnhh|0~~ffff
2617 |CS|CS nnhh|0~~ffff
2618 |CP|CP nnhh|0~~ffff
2619 |N|N nnhh|0~~ffff
2620 |C|C nnhh|0~~ffff
2621 |T|T nnhh|0~~ffff
2622 |R|R nnhh|0~~ffff
2623
2624 **Cable Wiring**
2625
2626 (% style="text-align:center" %)
2627 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2628
2629 == **CompactLogix FreeTag Ethernet protocol** ==
2630
2631 Allen-Brandly CompactLogix
2632
2633 **HMI Settings**
2634
2635 (% class="table-bordered" %)
2636 |**Items**|**Settings**|**Note**
2637 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2638 |Connection|Ethernet|
2639 |Port No.|44818|
2640
2641 **PLC Setting**
2642
2643 Create new tags
2644
2645 (% style="text-align:center" %)
2646 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2647
2648 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2649
2650 (% style="text-align:center" %)
2651 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2652
2653 Import labels, please open [Communication] window and click [Import label];
2654
2655 Select csv file, all tags will be displayed as belows;
2656
2657 (% style="text-align:center" %)
2658 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2659
2660 **✎Note:**
2661
2662 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2663
2664 (% style="text-align:center" %)
2665 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2666
2667 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2668
2669 **Communication settings in HMI**
2670
2671 Enable HMI Ethernet in [Project Settings];
2672
2673 (% style="text-align:center" %)
2674 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2675
2676 Set PLC IP in [Device IP] settings;
2677
2678 (% style="text-align:center" %)
2679 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2680
2681 **Cable Wiring**
2682
2683 (% style="text-align:center" %)
2684 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2685
2686 == **MicroLogix 1200** **protocol** ==
2687
2688 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2689
2690 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2691 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2692 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2693 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2694
2695 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2696
2697 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2698 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2699 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2700 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2701 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2702 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2703 |**PLC word address type**|**Address format**|**Address range**
2704 |S|ddd|S0 ~~ 255
2705 |TS|ffff|TS0 ~~ FFFF
2706 |TP|ffff|TP0 ~~ FFFF
2707 |CS|ffff|CS0 ~~ FFFF
2708 |CP|ffff|CP0 ~~ FFFF
2709 |N|ffff|N0 ~~ FFFF
2710 |F|ffff|F0 ~~ FFFF
2711
2712 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2713
2714 == **S7-200 Smart Ethernet Protocol** ==
2715
2716 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2717
2718 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2719
2720 **HMI Setting**
2721
2722 (% class="table-bordered" %)
2723 |**Items**|**Settings**|**Note**
2724 |Protocol|Simens S7-200 Smart Ethernet|
2725 |Connection|Ethernet|
2726 |Port No.|102|
2727 |PLC station No.|2|
2728
2729 **Address List**
2730
2731 (% class="table-bordered" %)
2732 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2733 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2734 |Q|Q|Q ddddd.o|0.0~~99999.7|
2735 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2736 |V|V|V ddddd.o|0.0~~99999.7|
2737 |M|M|M ddddd.o|0.0~~99999.7|
2738 |SM|SM|ddddd.o|0.0~~99999.7|
2739 |S|S|ddddd.o|0.0~~99999.7|Read only
2740 |T|T|ddddd|0~~99999|Timer state, read only
2741 |C|C|ddddd|0~~99999|Counter state, read only
2742 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2743 |Q|QW|QW ddddd|0~~99999|
2744 |AI|AIW|AIW ddddd|0~~99999|
2745 |AQ|VB|VB ddddd|0~~99999|
2746 |V|VW|VW ddddd|0~~99998|(((
2747 VW0=VB (0~~1)
2748
2749 VW2=VB (2~~3)
2750
2751 Address value is a multiple of 2
2752 )))
2753 |V|VD|VD ddddd|0~~99998|(((
2754 VD0=VB (0~~3)
2755
2756 VD2=VB (4~~7)
2757
2758 Address value is a multiple of 4
2759 )))
2760 |M|MB|MB ddddd|0~~99999|
2761 |M|MW|MW ddddd|0~~99999|(((
2762 MW0=MB(0~~1)
2763
2764 MW2=MB(2~~3)
2765
2766 Address value is a multiple of 2
2767 )))
2768 |M|MD|MD ddddd|0~~99999|(((
2769 MD0=MB(0~~3)
2770
2771 MD4=MB(4~~7)
2772
2773 Address value is a multiple of 4
2774 )))
2775 |T|TW|TW ddddd|0~~99999|Value of timer
2776 |C|CW|CW ddddd|0~~99999|Value of counter
2777 |W|SW|SW ddddd|0~~99999|
2778
2779 **Communication Settings**
2780
2781 Enable HMI Ethernet in [Project Settings];
2782
2783 (% style="text-align:center" %)
2784 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2785
2786 Set PLC IP in [Device IP] settings;
2787
2788 (% style="text-align:center" %)
2789 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2790
2791 * PLC IP Address: PLC IP
2792 * PLC pot No.: 102(fixed)
2793 * Network:TCP_Client_2N(fixed)
2794
2795 (% style="text-align:center" %)
2796 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2797
2798 * Wait timeout: depend on actual network situation (more than 1500 ms)
2799
2800 **Cable Wiring**
2801
2802 (% style="text-align:center" %)
2803 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2804
2805 == **S7-300 Ethernet Protocol** ==
2806
2807 Supported Series: Siemens S7-300 series PLC
2808
2809 **HMI Setting**
2810
2811 (% class="table-bordered" %)
2812 |**Items**|**Settings**|**Note**
2813 |Protocol|Simens S7-300 Ethernet|
2814 |Connection|Ethernet|
2815 |Port No.|102|
2816 |PLC station No.|2|Need to be same as the PLC setting
2817
2818 **Address List**
2819
2820 (% class="table-bordered" %)
2821 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2822 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2823 |Q|Q|Q ddddd.o|0.0~~99999.7|
2824 |M|M|M ddddd.o|0.0~~99999.7|
2825 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2826 nnnn: block number;
2827
2828 dddd: address;
2829 )))
2830 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2831 |Q|QW|QW ddddd|0~~99999|
2832 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2833 |MW|MW ddddd|0~~99999|(((
2834 MW0=MB(0~~1)
2835
2836 MW2=MB(2~~3)
2837
2838 Address value is a multiple of 2
2839 )))
2840 |MD|MD ddddd|0~~99999|(((
2841 MD0=MB(0~~3)
2842
2843 MD4=MB(4~~7)
2844
2845 Address value is a multiple of 4
2846 )))
2847 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2848 nnnn: block number;
2849
2850 dddd: address
2851 )))
2852 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2853 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2854
2855 **Communication Settings**
2856
2857 Enable HMI Ethernet in [Project Settings];
2858
2859 (% style="text-align:center" %)
2860 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2861
2862 Set PLC IP in [Device IP] settings;
2863
2864 (% style="text-align:center" %)
2865 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2866
2867 * PLC IP Address: PLC IP
2868 * PLC pot No.: 102(fixed)
2869 * Network:TCP_Client_2N(fixed)
2870
2871 (% style="text-align:center" %)
2872 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2873
2874 * Wait timeout: depend on actual network situation (more than 1500 ms)
2875
2876 **Cable Wiring**
2877
2878 (% style="text-align:center" %)
2879 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2880
2881 == **S7-1200 Ethernet Protocol** ==
2882
2883 Supported Series: Siemens S7-1200
2884
2885 **HMI Setting**
2886
2887 (% class="table-bordered" %)
2888 |**Items**|**Settings**|**Note**
2889 |Protocol|Siemens S7-1200|
2890 |Connection|Ethernet|
2891 |Port No.|102|
2892 |PLC station No.|2|
2893
2894 **Address List**
2895
2896 (% class="table-bordered" %)
2897 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2898 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2899 d:0~-~-9999
2900
2901 o:0-7
2902 )))|
2903 |Q|Q|Q d.o|(((
2904 d:0~-~-9999
2905
2906 o:0-7
2907 )))|
2908 |M|M|M d.o|(((
2909 d:0~-~-9999
2910
2911 o:0-7
2912 )))|
2913 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2914 nn:0-9999,
2915
2916 dddd:0-9999,
2917
2918 o:0-7
2919 )))|(((
2920 nn:DB No.
2921
2922 dddd:address value
2923
2924 o: digit address
2925 )))
2926 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2927 |M|MW|MW d|d:0-99999|(((
2928 MW0=MB(0~~1)
2929
2930 MW2=MB(2~~3)
2931
2932 Address value is a multiple of 2
2933 )))
2934 |M|MD|MD d|d:0-99999|(((
2935 MD0=MB(0~~3)
2936
2937 MD4=MB(4~~7)
2938
2939 Address value is a multiple of 4
2940 )))
2941 |I|IW|IW d|d:0-99999|
2942 |Q|QW|QW d|d:0-99999|
2943 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2944 nn:0-9999
2945
2946 dddd:0-9999
2947 )))|(((
2948 nn:DB No.
2949
2950 dddd:address value
2951 )))
2952 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2953 nn:0-9999
2954
2955 dddd:0-9999
2956 )))|(((
2957 nn:DB No.
2958
2959 dddd:address value
2960
2961 Address value is a multiple of 2
2962 )))
2963 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2964 nn:0-9999
2965
2966 dddd:0-9999
2967 )))|(((
2968 nn:DB No.
2969
2970 dddd:address value
2971
2972 Address value is a multiple of 4
2973 )))
2974
2975 **Communication Settings**
2976
2977 Enable HMI Ethernet in [Project Settings];
2978
2979 (% style="text-align:center" %)
2980 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2981
2982 Set PLC IP in [Device IP] settings;
2983
2984 (% style="text-align:center" %)
2985 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2986
2987 **✎Note:**
2988
2989 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2990 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2991 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2992 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2993
2994 **PLC Settings**
2995
2996 Add BD
2997
2998 * Please uncheck [Symbolic access only] option;
2999
3000 (% style="text-align:center" %)
3001 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3002
3003 Address settings, using BD2 as example.
3004
3005 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3006 * 2 represent DB block number
3007 * xxxx represent address
3008
3009 **Such as:**
3010
3011 * DBxDBB20000 = DB2.DBB0
3012 * DBxDBW20004 = DB2.DBW4
3013
3014 (% style="text-align:center" %)
3015 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3016
3017 **How to connect with S7-1200 Firmware V4.0**
3018
3019 PLC configuration
3020
3021 * Double click [device configuration] in Siemens via software
3022 * Double click [protection] to enter protection configuration screen
3023
3024 (% style="text-align:center" %)
3025 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3026
3027 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3028
3029 (% style="text-align:center" %)
3030 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3031
3032 DB settings
3033
3034 * Right click [DB], select [properties]
3035 * Uncheck [optimized block access]
3036
3037 **Cable Wiring**
3038
3039 (% style="text-align:center" %)
3040 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3041
3042 == **S7-XXX Ethernet Protocol** ==
3043
3044 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3045
3046 **HMI Setting**
3047
3048 (% class="table-bordered" style="width:823px" %)
3049 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3050 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3051 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3052 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3053 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3054 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3055
3056 Slot from TIA Portal is equal to Device No. of PIStudio
3057
3058 Rack from TIA Portal is equal to HMI No. of PIStudio
3059
3060 (% style="text-align:center" %)
3061 [[image:S7-XXXCommunication Settings.png]]
3062
3063 (% style="text-align:center" %)
3064 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3065
3066 **Address List**
3067
3068 (% class="table-bordered" %)
3069 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3070 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3071 d:0~-~-9999
3072
3073 o:0-7
3074 )))|
3075 |Q|Q|Q d.o|(((
3076 d:0~-~-9999
3077
3078 o:0-7
3079 )))|
3080 |M|M|M d.o|(((
3081 d:0~-~-9999
3082
3083 o:0-7
3084 )))|
3085 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3086 nn:0-9999,
3087
3088 dddd:0-9999,
3089
3090 o:0-7
3091 )))|(((
3092 nn:DB No.
3093
3094 dddd:address value
3095
3096 o: digit address
3097 )))
3098 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3099 |M|MW|MW d|d:0-99999|(((
3100 MW0=MB(0~~1)
3101
3102 MW2=MB(2~~3)
3103
3104 Address value is a multiple of 2
3105 )))
3106 |M|MD|MD d|d:0-99999|(((
3107 MD0=MB(0~~3)
3108
3109 MD4=MB(4~~7)
3110
3111 Address value is a multiple of 4
3112 )))
3113 |I|IW|IW d|d:0-99999|
3114 |Q|QW|QW d|d:0-99999|
3115 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3116 nn:0-9999
3117
3118 dddd:0-9999
3119 )))|(((
3120 nn:DB No.
3121
3122 dddd:address value
3123 )))
3124 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3125 nn:0-9999
3126
3127 dddd:0-9999
3128 )))|(((
3129 nn:DB No.
3130
3131 dddd:address value
3132
3133 Address value is a multiple of 2
3134 )))
3135 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3136 nn:0-9999
3137
3138 dddd:0-9999
3139 )))|(((
3140 nn:DB No.
3141
3142 dddd:address value
3143
3144 Address value is a multiple of 4
3145 )))
3146
3147 **Communication Settings**
3148
3149 Enable HMI Ethernet in [Project Settings];
3150
3151 (% style="text-align:center" %)
3152 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3153
3154 Set PLC IP in [Device IP] settings;
3155
3156 (% style="text-align:center" %)
3157 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3158
3159 **✎Note:**
3160
3161 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3162 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3163
3164 **Cable Wiring**
3165
3166 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3167
3168 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3169
3170 Supported Series: Siemens Logo 0BA0, 0BA1 series
3171
3172 **HMI Settings**
3173
3174 (% class="table-bordered" %)
3175 |**Items**|**Settings**|**Note**
3176 |Protocol|Siemens LOGO|
3177 |Connection|Ethernet|
3178 |Port No.|102|
3179 |PLC station No.|2|
3180
3181 **Address List**
3182
3183 (% class="table-bordered" %)
3184 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3185 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3186 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3187 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3188 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3189 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3190 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3191 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3192 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3193 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3194 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3195 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3196 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3197 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3198 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3199 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3200
3201 **PLC Settings in LOGO Software:**
3202
3203 Click [Tools]~-~-[Ethernet Connections],shown as below.
3204
3205 (% style="text-align:center" %)
3206 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3207
3208 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3209
3210 (% style="text-align:center" %)
3211 [[image:image-20221228142937-4.png]]
3212
3213 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3214
3215 (% style="text-align:center" %)
3216 [[image:image-20221228143047-5.png]]
3217
3218 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3219
3220 (% style="text-align:center" %)
3221 [[image:image-20221228143246-6.png]]
3222
3223
3224 **HMI Communication Settings**
3225
3226 Set PLC IP in [Device IP] settings;
3227
3228 (% style="text-align:center" %)
3229 [[image:image-20221228143614-7.png]]
3230
3231 Enable HMI Ethernet in [Project Settings];
3232
3233 (% style="text-align:center" %)
3234 [[image:image-20221228144229-9.png]]
3235
3236 TSAP setting
3237
3238 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3239 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3240 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3241 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3242 ie, ig series: use HSW1200, HSW1201.
3243 HMI V2.0: use HSW1200, HSW1201.
3244
3245 **✎Note:**
3246
3247 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3248 * HSW10119/HSW1201 is set up as shown.
3249 * (((
3250 (% style="text-align:center" %)
3251 [[image:image-20221228144800-11.png]]
3252 )))
3253 * (((
3254 (% style="text-align:center" %)
3255 [[image:image-20221228144708-10.png]]
3256 )))
3257
3258 * AI word address and Ibit address are read-only and cannot be written on HMI.
3259 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3260 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3261 * Written value of RTC cannot exceed 255.
3262
3263 **Cable Wiring**
3264
3265 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3266
3267 == S7-300 232 ==
3268
3269 **HMI Setting:**
3270
3271 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3272 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3273 |=**PLC I/F**|RS232| |
3274 |=**Baud rate**|19200|9600,19200|
3275 |=**Data bits**|8| |
3276 |=**Parity**|Odd| |
3277 |=**Stop bits**|1| |
3278 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3279
3280 **Device Address**
3281
3282 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3283 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3284 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3285 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3286 |=Word|(((
3287 DB1 to DB99
3288 )))|DDDDDo|0 ~~ 655327|
3289 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3290 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3291 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3292 |=Double word|MD|DDDD|0 ~~ 4094|
3293 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3294 Data Register Double Word (must be even)
3295 )))
3296 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3297
3298 **Cable Wiring**
3299
3300 (% style="text-align:center" %)
3301 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3302
3303 = Create communication with Xinje** PLC** =
3304
3305 == XC serial protocol ==
3306
3307 **HMI Settings**
3308
3309 |**Item**|**Settings**|**Note**
3310 |Protocol|XINJE XC MODBUS|
3311 |Connection|RS232|
3312 |Baud rate|19200|
3313 |Data bit|8|
3314 |Parity|EVEN|
3315 |Stop bit|1|
3316 |PLC station No.|1|
3317
3318 **Address List**
3319
3320 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3321 |Bit|M|M|M d|0~~8511|
3322 |Bit|X|X|X o|0~~1747|
3323 |Bit|Y|Y|Y o|0~~1747|
3324 |Bit|S|S|S d|0~~1023|
3325 |Bit|T|T|T d|0~~4095|
3326 |Bit|C|C|C d|0~~634|
3327 |Word|D|D|D d|0~~8511|
3328 |Word|TD|TD|TD d|0~~618|
3329 |Word|CD|CD|CD d|0~~634|
3330 |Word|FD|FD|FD d|0~~8511|
3331
3332 **Configure the communication protocol**
3333
3334 (% style="text-align:center" %)
3335 [[image:image-20220830154105-1.png]]
3336
3337 (% style="text-align:center" %)
3338 [[image:image-20220830154159-3.png]]
3339
3340 **Cable Wiring**
3341
3342 Figure
3343
3344 [[image:image-20220830155728-4.png]]
3345
3346 Pin Definition Diagram
3347
3348 (% style="text-align:center" %)
3349 [[image:image-20220830154131-2.png]]
3350
3351 == XD serial protocol ==
3352
3353 **HMI Settings**
3354
3355 Supported Series: Xinjie XD/XE Series PLC
3356
3357 |=**Item**|=**Settings**|=**Note**
3358 |Protocol|XINJE XD/XC MODBUS|
3359 |Connection|RS232|
3360 |Baud rate|19200|
3361 |Data bit|8|
3362 |Parity|EVEN|
3363 |Stop bit|1|
3364 |PLC station No.|1|
3365
3366 **Address List**
3367
3368 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3369 |Bit|M|M|M d|0~~74999|
3370 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3371 |Bit|X2xx|X2xx|X2xx o|0~~277|
3372 |Bit|X|X|X o|0~~77|
3373 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3374 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3375 |Bit|Y|Y|Y o|0~~4095|
3376 |Bit|SM|SM|SM d|0~~4999|(((
3377
3378 )))
3379 |Bit|T|T|T d|0~~4999|
3380 |Bit|C|C|C d|0~~4999|
3381 |Bit|ET|ET|ET d|0~~31|
3382 |Bit|SE|SE|SE d|0~~31|
3383 |Bit|HM|HM|HM d|0~~11999|
3384 |Bit|HSC|HSC|HSC d|0~~39|
3385 |Bit|HS|HS|HS d|0~~999|
3386 |Bit|HT|HT|HT d|0~~1999|
3387 |Bit|HC|HC|HC d|0~~1999|
3388 |Bit|S|S|S d|0~~7999|
3389 |Word|D|D|D d|0~~69999|
3390 |Word|ID|ID|ID d|0~~99|
3391 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3392 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3393 |Word|QD|QD|QD d|0~~99|
3394 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3395 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3396 |Word|SD|SD|SD d|0~~4999|
3397 |Word|TD|TD|TD d|0~~575|
3398 |Word|CD|CD|CD d|0~~575|
3399 |Word|ETD|ETD|ETD d|0~~31|
3400 |Word|HD|HD|HD d|0~~24999|
3401 |Word|HSD|HSD|HSD d|0~~1023|
3402 |Word|HTD|HTD|HTD d|0~~95|
3403 |Word|HCD|HCD|HCD d|0~~95|
3404 |Word|HSCD|HSCD|HSCD d|0~~31|
3405 |Word|FD|FD|FD d|0~~8191|
3406 |Word|SFD|SFD|SFD d|0~~5999|
3407 |Word|FS|FS|FS d|0~~47|
3408
3409 **Configure the communication protocol**
3410
3411 (% style="text-align:center" %)
3412 [[image:image-20220830160042-1.png]]
3413
3414 (% style="text-align:center" %)
3415 [[image:image-20220830160129-2.png]]
3416
3417 **Cable Wiring**
3418
3419 (% style="text-align:center" %)
3420 [[image:image-20220905093902-1.png]]
3421
3422 Pin Definition Diagram
3423
3424 (% style="text-align:center" %)
3425 [[image:image-20220830160232-3.png]]
3426
3427 = Create communication with Panasonic** PLC** =
3428
3429 == **FP serial protocol** ==
3430
3431 **1)HMI Settings**
3432
3433 |**Item**|**Settings**|**Note**
3434 |Protocol|Panasonic FP MFWTOCOL|
3435 |Connection|RS232|
3436 |Baud rate|9600|
3437 |Data bit|8|
3438 |Parity|ODD|
3439 |Stop bit|1|
3440 |PLC station No.|1|
3441
3442 **2)Address List**
3443
3444 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3445 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3446 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3447 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3448 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3449 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3450 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3451 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3452 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3453 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3454 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3455 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3456 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3457 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3458 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3459 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3460
3461 **3)Configure the communication protocol**
3462
3463 [[image:image-20220830171050-1.png]]
3464
3465 [[image:image-20220830171126-2.png]]
3466
3467 **4)Cable Wiring**
3468
3469 Figure
3470
3471 [[image:image-20220830171328-4.png]]
3472
3473 Pin Definition Diagram
3474
3475 [[image:image-20220830171146-3.png]]
3476
3477 = Create communication with **SHIMADEN PLC** =
3478
3479 == **FP23 series protocol** ==
3480
3481 Supported series: SHIMADEN FP23 series
3482
3483 **HMI Setting**
3484
3485 |**Items**|**Settings**|**Note**
3486 |Protocol|SHIMADEN FP23 series|
3487 |Connection|RS485 (9600, 1, 7, EVEN)|
3488 |Port No.|None|
3489 |PLC station No.|0|
3490
3491 **Address List**
3492
3493 |**Device address**|**HMI register**|**Address range**|**Type**
3494 |0040-0043(HEX)|FP040|100064-200067|Read only
3495 |0100-010B(HEX)|FP100|100256-200267|Read only
3496 |0110-0142(HEX)|FP110|100272-200322|Read only
3497 |0182-0252(HEX)|FP182|100386-200594|Write only
3498 |0280-0281(HEX)|FP280|100640-200641|Read only
3499 |0300-030B(HEX)|FP300|100768-200779|Read and write
3500 |0380-039F(HEX)|FP380|100896-200927|Read and write
3501 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3502 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3503 |0600-0670(HEX)|FP600|101536-201814|Read and write
3504 |0720-0738(HEX)|FP720|101824-201848|Read and write
3505 |0800-083F(HEX)|FP800|102048-202111|Read and write
3506 |0900-0952(HEX)|FP900|102304-202386|Read and write
3507 | |Ctrl|0-2|
3508
3509 **✎Note:**
3510
3511 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3512 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3513 * The Ctrl register is used to store the control group number and BCC check mode.
3514
3515 **Ctrl Register Description**
3516
3517 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3518 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3519 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3520 * Ctrl3 reserved
3521
3522 **✎Note:**
3523
3524 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3525
3526 **Cable Wiring**
3527
3528 (% style="text-align:center" %)
3529 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3530
3531 (% style="text-align:center" %)
3532 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3533
3534 **✎Note:** COM3 only available in PI8000/PI9000 series.
3535
3536 == **SR90 protocol** ==
3537
3538 Supported series: SHIMADEN SR90 series
3539
3540 **HMI Setting**
3541
3542 |**Items**|**Settings**|**Note**
3543 |Protocol|SHIMADEN SR90 protocol|
3544 |Connection|RS485 (1200, 1, 7, EVEN)|
3545 |Port No.|None|
3546 |PLC station No.|0|
3547
3548 **Address List**
3549
3550 |**Device address**|**HMI register**|**Address range**|**Type**
3551 |0040-0043 (HEX)|SR040|100064-100067|Read only
3552 |0100-010A(HEX)|SR0100|100256-100266|Read only
3553 |0182-018C(HEX)|SR0182|100386-100396|Write only
3554 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3555 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3556 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3557 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3558 | |Ctrl|0-2|~-~-
3559
3560 **✎Note:**
3561
3562 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3563 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3564 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3565
3566 **Ctrl Register Description**
3567
3568 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3569 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3570 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3571 * Ctrl3 reserved
3572
3573 **✎Note:**
3574
3575 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3576
3577 **Cable Wiring**
3578
3579 (% style="text-align:center" %)
3580 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3581
3582 (% style="text-align:center" %)
3583 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3584
3585 **✎Note:** COM3 only available in PI8000/PI9000 series.
3586
3587 == **MR13 series(standard protocol)** ==
3588
3589 Supported series: SHIMADEN MR13 series
3590
3591 **HMI Setting**
3592
3593 |**Items**|**Settings**|**Note**
3594 |Protocol|SHIMADEN standard protocol|
3595 |Connection|RS485 (1200, 1, 7, EVEN)|
3596 |Port No.|None|
3597 |PLC station No.|0|
3598
3599 **Address List**
3600
3601 |**Device address**|**HMI register**|**Address range**|**Type**
3602 |0100-010B(HEX)|MR100|100256-300267|Read only
3603 |0111-0126(HEX)|MR111|100273-300294|Read only
3604 |0184-0192(HEX)|MR184|100388-300402|Write only
3605 |0280-0282(HEX)|MR280|100640-300642|Read only
3606 |0300-030B(HEX)|MR300|100768-300779|Read/write
3607 |0314-0317(HEX)|MR314|100788-300791|Read/write
3608 |031A(HEX)|MR31A|100794-300794|Read/write
3609 |0320-0321(HEX)|MR320|100800-300801|Read/write
3610 |0400-0504(HEX)|MR400|101024-301284|Read/write
3611 |0506(HEX)|MR506|101286-301286|Read/write
3612 |0510-0514(HEX)|MR510|101296-301300|Read/write
3613 |0516-0524(HEX)|MR516|101302-301316|Read/write
3614 |0526(HEX)|MR526|101318-301318|Read/write
3615 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3616 |~-~-|Ctrl|0-2|~-~-
3617
3618 **✎Note:**
3619
3620 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3621 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3622 * The Ctrl register is used to store the control group number and BCC check mode.
3623
3624 **Ctrl Register Description**
3625
3626 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3627 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3628 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3629 * Ctrl3 reserved
3630
3631 **✎Note:**
3632
3633 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3634
3635 **Cable Wiring**
3636
3637 (% style="text-align:center" %)
3638 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3639
3640 (% style="text-align:center" %)
3641 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3642
3643 **✎Note:** COM3 only available in PI8000/PI9000 series.
3644
3645 = **Printer** =
3646
3647 == **TSPL label printer** ==
3648
3649 **Introduction**
3650
3651 TSPL label printer protocol supports following models.
3652
3653 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3654 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3655
3656 **Setting Step**
3657
3658 Select the protocol
3659
3660 * Create a new project, select the TSPL label printer protocol as shown below.
3661
3662 (% style="text-align:center" %)
3663 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3664
3665 Set parameters
3666
3667 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3668
3669 Printer register
3670
3671 (% class="table-bordered" %)
3672 |**Register**|**System**|**Range**|**Function**
3673 |TSPL_SP|decimal|0 - 1|Set the paper size
3674 |TSPL_PT|decimal|0 - 1999|Print text
3675 |TSPL_PQ|decimal|0 - 999|Print QR code
3676 |TSPL_PB|decimal|0 - 999|Print barcode
3677 |TSPL_PR|decimal|0 - 1|Print offset
3678 |TSPL_PN|decimal|0 - 0|Trigger printing
3679 |TSPL_PS|decimal|0 - 0|Print status
3680
3681 * Set paper size:
3682 ** TSPL_SP0: width of paper, unit: mm.
3683 ** TSPL_SP1: height of paper, unit: mm.
3684 * Print text:
3685 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3686 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3687
3688 (% class="table-bordered" %)
3689 |**Register**|**Function**|**Description**
3690 |TSPL_PT0|X coordinate|Unit: dot
3691 |TSPL_PT1|Ycoordinate|Unit: dot
3692 |TSPL_PT2|Rotation angle|(((
3693 0: 0 degrees
3694
3695 1: 90 degrees
3696
3697 2: 180 degrees
3698
3699 3: 270 degrees
3700 )))
3701 |TSPL_PT3|Size|Range: 0-3
3702 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3703
3704 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3705
3706 Print QR code:
3707
3708 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3709 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3710
3711 (% class="table-bordered" %)
3712 |**Register**|**Function**|**Description**
3713 |TSPL_PQ0|X coordinate|Unit: dot
3714 |TSPL_PQ1|Ycoordinate|Unit: dot
3715 |TSPL_PQ2|Rotation angle|(((
3716 0: 0 degrees
3717
3718 1: 90 degrees
3719
3720 2: 180 degrees
3721
3722 3: 270 degrees
3723 )))
3724 |TSPL_PQ3|Size|Range: 0-5
3725 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3726
3727 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3728
3729 Print bar code:
3730
3731 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3732 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3733
3734 (% class="table-bordered" %)
3735 |**Register**|**Function**|**Description**
3736 |TSPL_PB0|X coordinate|Unit: dot
3737 |TSPL_PB1|Ycoordinate|Unit: dot
3738 |TSPL_PB2|Rotation angle|(((
3739 0: 0 degrees
3740
3741 1: 90 degrees
3742
3743 2: 180 degrees
3744
3745 3: 270 degrees
3746 )))
3747 |TSPL_PB3|height|Unit: dot
3748 |TSPL_PB4|width|Range:0-2
3749 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3750
3751 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3752
3753 Print offset:
3754
3755 * TSPL_PR0: X coordinate offset, unit: mm;
3756 * TSPL_PR1: Y coordinate offset, unit: mm.
3757
3758 Trigger printing:
3759
3760 * TSPL_PN0 = 1: trigger the printer to start printing.
3761
3762 Printing status:
3763
3764 * TSPL_PS0 = 1: The printing is normal.
3765 * TSPL_PS0 = 1: The printing is abnormal.
3766
3767 Print picture
3768
3769 * For the function of printing pictures, please refer to the configuration of [Printer object].
3770
3771 Conversion between dot and mm
3772
3773 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3774
3775 == **EpsonTM series** ==
3776
3777 **HMI Settings**
3778
3779 (% class="table-bordered" %)
3780 |**Item**|**Settings**|**Note**
3781 |Protocol|EPSON-TM-T82II/TM-XXX|
3782 |Connection|RS232|
3783 |Baud rate|9600~~115200|
3784 |Data bit|8|
3785 |Parity|None|
3786 |Stop bit|1|
3787 |PLC station No.|1|
3788
3789 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3790
3791 **Printer Settings**
3792
3793 (% class="table-bordered" %)
3794 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3795 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3796 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3797 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3798 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3799 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3800 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3801
3802 **Cable Wiring**
3803
3804 (% style="text-align:center" %)
3805 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3806
3807 (% style="text-align:center" %)
3808 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3809
3810 **✎Note:** COM3 only available in PI8000/PI9000 series.
3811
3812
3813 = Create communication with **Schneider PLC** =
3814
3815 == **Schneider MODBUS RTU** ==
3816
3817 **HMI Setting**
3818
3819 |=**Parameters**|=**Recommended**|=**Notes**
3820 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3821 |Connection|RS485|
3822 |**Baud rate**|19200|
3823 |**Data bit**|8|
3824 |**Parity**|Even|
3825 |**Stop bit**|1|
3826 |**PLC station No.**|1|
3827
3828 **PLC Setting**
3829
3830 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3831
3832 **Device Address**
3833
3834 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3835 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3836 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3837 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3838 |W|MW|DDDDDD|0 ~~ 999999|Output register
3839 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3840
3841 **Wiring Diagram**
3842
3843 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3844
3845 (% style="text-align:center" %)
3846 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3847
3848 = **Barcode Scanner** =
3849
3850 Supported: DELI 14880 barcode scanner
3851
3852 **HMI Setting**
3853
3854 |**Items**|**Settings**|**Note**
3855 |Protocol|Barcode Scanner|
3856 |Connection|USB|
3857
3858 **Operating Procedures**
3859
3860 Select [Barcode Scanner];
3861
3862 (% style="text-align:center" %)
3863 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3864
3865 Set address for receiving;
3866
3867 Set correct length;
3868
3869 (% style="text-align:center" %)
3870 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3871
3872 **✎Note:**
3873
3874 * The protocol uploads the information acquired by the USB scanner to the HMI;
3875 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3876 * Recommended model: DELI 14880 barcode scanner;
3877
3878 = **Hitachi EHV Series (Ethernet)** =
3879
3880 Supported series: Hitachi EHV series
3881
3882 **HMI Settings**
3883
3884 (% class="table-bordered" %)
3885 |**Items**|**Settings**|**Note**
3886 |Protocol|Hitachi EHV series|
3887 |Connection|Ethernet|
3888 |Port No.|3004~~3007|
3889
3890 **Address List**
3891
3892 (% class="table-bordered" %)
3893 |**Type**|**Register**|**Range**|**Format**|**Note**
3894 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3895 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3896 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3897 H1H2H3H4 Module main number
3898
3899 H1: Remote number
3900
3901 H2: Unit number
3902
3903 H3: Slot number
3904
3905 H4: Word number of Module
3906
3907 H Sub number of Module
3908
3909 For example:X21.3
3910
3911 Slot number 2
3912
3913 Word number of module is 1
3914
3915 Bit number of module is 3
3916
3917 Remote number and unit number are 0
3918 )))
3919 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3920 |R|0 – FF.f (Hex)|R HH.h|
3921 |L|0 - 73FF.f (Hex)|L HHHH.h|
3922 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3923 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3924 H1H2H3H4 Module main number
3925
3926 H1: Remote number
3927
3928 H2: Unit number
3929
3930 H3: Slot number
3931
3932 H4: Word number of module
3933
3934 For example:WX21
3935
3936 Word number of module is 1
3937
3938 Slot number is 2
3939
3940 Remote number and unit number are 0
3941 )))
3942 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3943 |WR|0 – FFFF (Hex)|WR HHHH|
3944 |WL|0 - 73FF (Hex)|WL HHHH|
3945 |TC|0 - 2559|TC DDDD|
3946
3947 **Communication settings in HMI**
3948
3949 Enable HMI Ethernet in [Project Settings];
3950
3951 (% style="text-align:center" %)
3952 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3953
3954 Set PLC IP in [Device IP] settings;
3955
3956 (% style="text-align:center" %)
3957 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3958
3959 **PLC Configuration**
3960
3961 Connect with PLC, select[Online mode];
3962
3963 (% style="text-align:center" %)
3964 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3965
3966 Set IP address, it is the same LAN parameters with HMI;
3967
3968 (% style="text-align:center" %)
3969 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3970
3971 3) Save PLC communication parameter, and restart PLC
3972
3973 **PLC Monitor Mode**
3974
3975 Connect with PLC and choose to “online” mode
3976
3977 (% style="text-align:center" %)
3978 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3979
3980 Open I/O monitor sheet1
3981
3982 (% style="text-align:center" %)
3983 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3984
3985 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3986
3987 (% style="text-align:center" %)
3988 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3989
3990 Enter the register address, click OK to view the value of the register.
3991
3992 (% style="text-align:center" %)
3993 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3994
3995 (% style="text-align:center" %)
3996 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3997
3998 **✎Note:**
3999
4000 * Both word registers and bit registers support even continuous read/write functions;
4001 * The range of registers is based on the specific PLC type;
4002
4003 **Cable Wiring**
4004
4005 (% style="text-align:center" %)
4006 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4007
4008 = **IEC60870-5 104 Client** =
4009
4010 **HMI Setting**
4011
4012 (% class="table-bordered" %)
4013 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4014 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4015 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4016 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4017
4018 **Address List**
4019
4020 (% class="table-bordered" %)
4021 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4022 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4023 |(% style="width:461px" %)SCNA|0~~16777215.7
4024 |(% style="width:461px" %)DPTB|0~~16777215.7
4025 |(% style="width:461px" %)DCNA|0~~16777215.7
4026 |(% style="width:461px" %)METF|0~~16777215.7
4027 |(% style="width:461px" %)SENC|0~~16777215.7
4028 |(% style="width:461px" %)SENA|0~~16777215.7
4029 |(% style="width:461px" %)MENA|0~~16777215.7
4030 |(% style="width:461px" %)METD|0~~16777215.7
4031 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4032 |(% style="width:461px" %)SCNA|0~~16777215
4033 |(% style="width:461px" %)DPTB|0~~16777215
4034 |(% style="width:461px" %)DCNA|0~~16777215
4035 |(% style="width:461px" %)SENA|0~~16777215
4036 |(% style="width:461px" %)MENA|0~~16777215
4037 |(% style="width:461px" %)METD|0~~16777215
4038 |(% style="width:461px" %)INRO|0~~16777215
4039 |(% style="width:461px" %)TIMESYN|0~~16777215
4040 |(% style="width:461px" %)TIMEZ|0~~16777215
4041 |(% style="width:461px" %)NTP|0~~16777215
4042 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4043 |(% style="width:461px" %)SENC|0~~16777215
4044
4045 **Address Configuration**
4046
4047 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4048
4049 (% style="text-align:center" %)
4050 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4051
4052 (% style="text-align:center" %)
4053 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4054
4055 Extended tag name
4056
4057 Address range for the extended tag.
4058
4059 **Communication Settings**
4060
4061 Enable HMI Ethernet in [Project Settings];
4062
4063 (% style="text-align:center" %)
4064 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4065
4066 Set PLC IP in [Device IP] settings;
4067
4068 (% style="text-align:center" %)
4069 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4070
4071 **Cable Wiring**
4072
4073 (% style="text-align:center" %)
4074 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4075
4076 = **OpenCAN** =
4077
4078 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4079
4080 This protocol is only available in PI8000 series HMI.
4081
4082 **HMI Settings**
4083
4084 |**Items**|**Settings**|**Note**
4085 |Protocol|OPENCAN|
4086 |Connection|CAN port|
4087 |Baud rate|250000|
4088
4089 **CAN frame setting in HMI**
4090
4091 Click [OpenCAN setting] button in communication setting window;
4092
4093 (% style="text-align:center" %)
4094 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4095
4096 Click [Add] to create a new frame;
4097
4098 (% style="text-align:center" %)
4099 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4100
4101 |**No**|**Items**|**Description**
4102 |1|Add|add a frame related to register address
4103 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4104 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4105 |4|Modify|Modify the frames in frame management
4106 |5|Copy|Copy one frame to another
4107 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4108 |7|Empty|All frames in the list are cleared
4109 |8|Browse|Displays configuration files in XML format in IE
4110 |9|OK|Complete the configuration of the frame and exit
4111
4112 Set CANBUS frame in setting windows
4113
4114 (% style="text-align:center" %)
4115 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4116
4117 |**No**|**Items**|**Description**
4118 |1|ID|Set the ID of a can frame in hexadecimal format;
4119 |2|ID assign|split the ID by PF, PS, and SA;
4120 |3|Frame type|Select Standard frame or Extended Frame;
4121 |4|Frame format|Select between data frame and remote Frame;
4122 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4123 |6|Use address|(((
4124 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4125
4126 **Edit:** Set a bit or word address by its format;
4127
4128 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4129 )))
4130 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4131 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4132 |Feedback mode: feedback mode includes no response, confirm response and data response;
4133 |No response: the device or touch screen will not receive feedback;
4134 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4135 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4136 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4137 |Response timeout: sets whether the response frame timeout;
4138 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4139 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4140 |Manually send: a manually send tick indicates only one send;
4141 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4142 |10|Note|Fill the text to explain the meaning of the frame;
4143 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4144 |12|Current operation display|Display the description of current operation;
4145 |13|Add|Add a new frame;
4146 |14|Save frame|Save the configured frame format;
4147 |15|Cancel|Cancel the frame configuration;
4148
4149 Set CAN address (Read or write operation);
4150
4151 (% style="text-align:center" %)
4152 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4153
4154 |**No.**|**Item**|**Description**
4155 |1|Current address|Displays the register type and register address set by the user in the data access interface
4156 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4157 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4158 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4159 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4160 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4161 |If the trigger condition is a writing operation, there are two situations:(((
4162 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4163 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4164 )))
4165 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4166 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4167 |4|Add|Add current configuration
4168 |5|Close|Close the configuration window to exit
4169
4170 **Multiple Packages Settings**
4171
4172 (% style="text-align:center" %)
4173 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4174
4175 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4176
4177 Select Multiple package type
4178
4179 * Not Multiple packages
4180 * J1939 Multiple packages
4181 * Customized Multiple packages
4182
4183 Click [Edit Receive data] for [Receive] settings
4184
4185 * Start code+ Total length (J1939)
4186
4187 (% style="text-align:center" %)
4188 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4189
4190 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4191
4192 * Start code + Data max length (J1939)
4193
4194 (% style="text-align:center" %)
4195 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4196
4197 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4198
4199 * Data max length (J1939)
4200
4201 (% style="text-align:center" %)
4202 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4203
4204 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4205
4206 * Customized multiple package
4207
4208 (% style="text-align:center" %)
4209 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4210
4211 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4212
4213 Click [Edit Send data] for [Send] setting
4214
4215 * J1939
4216
4217 (% style="text-align:center" %)
4218 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4219
4220 [Data] is all data to be sent.
4221
4222 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4223
4224 * Customized multiple package
4225
4226 (% style="text-align:center" %)
4227 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4228
4229 [Data] is all data to be sent.
4230
4231 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4232
4233 **Cable Wiring**
4234
4235 (% style="text-align:center" %)
4236 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4237
4238 **✎Note:** The address interval between each frame need to be more than a word address;
4239
4240
4241 = **User Defined Protocol** =
4242
4243 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4244
4245 **HMI Settings**
4246
4247 |**Items**|**Settings**|**Note**
4248 |Protocol|User defined protocol|
4249 |Connection|RS485/RS232|
4250 |Baud rate|2400~~187500|
4251 |Stop bits|1/ 2|
4252 |Data bits|7/ 8|
4253 |Parity|None/ Even/ ODD|
4254
4255 **Operating Procedures**
4256
4257 Select [User defined protocol];
4258
4259 Click [User defined protocol] button to open setting window as below;
4260
4261 (% style="text-align:center" %)
4262 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4263
4264 Configure user defined command;
4265
4266 (% style="text-align:center" %)
4267 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4268
4269 |**No**|**Item**|**Description**
4270 |1|Instruction edit|The required command.
4271 |2|Mode|Write to address or read from the address.
4272 |3|Format|Encode format: HEX or ASCII.
4273 |4|Other|(((
4274 **No receiving: **HMI does not respond to the receiving command.
4275
4276 **Send after receiving:** HMI responds to the receiving command.
4277 )))
4278 |5|Manually send|(((
4279 Respond once after trigger the address.
4280
4281 Address: set the trigger address.
4282 )))
4283 |6|Add|Save this setting.
4284 |7|Cancel|Cancel current settings.
4285 |(% rowspan="4" %)8|Add|Add a new command.
4286 |Edit|Edit the selected command.
4287 |Delete|Delete the selected command.
4288 |Clear|Clear all the commands.
4289 |9|Instruction list|Display all current commands.
4290 |10|Address List|Display all the addresses added.
4291 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4292 |Export|Export current command settings to local storage.
4293 |Browse|Browse local command files.
4294 |Advanced|Combine two commands.
4295 |Exit|Complete editing and exit setting.
4296
4297 **Operating Procedures**
4298
4299 Click [Add] to create a new command, as below shows;
4300
4301 (% style="text-align:center" %)
4302 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4303
4304 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4305
4306 (% style="text-align:center" %)
4307 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4308
4309 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4310
4311 (% style="text-align:center" %)
4312 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4313
4314 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4315
4316 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4317
4318 Check settings;
4319
4320 (% style="text-align:center" %)
4321 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4322
4323 |**No**|**Items**|**Description**
4324 |1|Add checking|Add checking command when receiving the data.
4325 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4326 |Differ with send check|Set return checking.
4327 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4328 |Length: The data length need to be checked.
4329
4330 Object settings;
4331
4332 (% style="text-align:center" %)
4333 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4334
4335 |**No**|**Items**|**Description**
4336 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4337 |Address: the triggering address;
4338 |Note: description to object;
4339 |2|Byte order|The numerical display order;
4340
4341 Data length settings;
4342
4343 (% style="text-align:center" %)
4344 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4345
4346 |**No**|**Item**|**Description**
4347 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4348 |Length: the return data length.
4349 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4350 |Length: the write data length.
4351
4352 Instruction length settings
4353
4354 (% style="text-align:center" %)
4355 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4356
4357 |**No**|**Item**|**Description**
4358 |1|Send length|The instruction data will only send designated data length.
4359 |2|Return length|The responds data length.
4360 |3|End code|Instruction will not be terminated until receiving [End code];
4361
4362 **Cable Wiring**
4363
4364 * **RS485**
4365
4366 (% style="text-align:center" %)
4367 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4368
4369 (% style="text-align:center" %)
4370 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4371
4372 * **RS232**
4373
4374 (% style="text-align:center" %)
4375 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4376
4377 **✎Note:** COM3 only available in PI8000/PI9000 series.