Contact us for more information
X
*Company Name
*Name
*Email Address
Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 261.1 by Hunter on 2023/06/20 14:06

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **HMI Compilation Download**
223
224 [[image:image-20220902171247-1.png]]
225
226 **Communication cable**
227
228 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
229
230 (% style="text-align:center" %)
231 [[image:image-20220819093729-7.png]]
232
233 **HMI communication PLC use Modbus **
234
235 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
236 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
237
238 (% class="wikigeneratedid" id="HPLCsettings" %)
239 **PLC settings**
240
241 **Download PLC Software**
242
243 Please visit below link to get the latest version PLC Editor for HMI programming
244
245 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
246 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
247
248 **Start a new PLC project**
249
250 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
251
252 (% style="text-align:center" %)
253 [[image:image-20220819101447-3.jpeg]]
254
255 **Add a new instruction **
256
257 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
258
259 (% style="text-align:center" %)
260 [[image:image-20220819105530-1.png]]
261
262 You could also select the ladder symbol from the menu bar directly.
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 PLC programming software
327
328 (% style="text-align:center" %)
329 [[image:image-20220810164710-1.png]]
330
331 **New PLC project**
332
333 Click "New Project" and select the PLC model.
334
335 [[image:image-20220810172412-1.png]]
336
337 **Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters.
340
341 * Baud rate:115200
342 * Data bit:8
343 * Stop bit:1
344 * Parity:No verification
345
346 [[image:image-20220810165759-3.png]]
347
348 **Registers list**
349
350 [[image:image-20220811102219-3.png]]
351
352 **HMI software configuration**
353
354 HMI programming software
355
356 (% style="text-align:center" %)
357 [[image:image-20220810171237-4.png]]
358
359 **New HMI project**
360
361 Click New Project and select the HMI model.
362
363 [[image:image-20220810172010-5.png]]
364
365 Set communication port parameters
366
367 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
368
369 * Baud rate:115200
370 * Data bit:8
371 * Stop bit:1
372 * Parity:No verification
373
374 [[image:image-20220811104012-1.png]]
375
376 **hardware connection**
377
378 Hardware wiring diagram
379
380 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
381
382 (% style="text-align:center" %)
383 [[image:image-20220811103005-4.png]]
384
385 (% style="text-align:center" %)
386 [[image:image-20220811103227-7.png]]
387
388 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
389
390 == **LX5V-N Ethernet protocol** ==
391
392 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
393
394 **Software configuration of PLC**
395
396 **PLC programming software**
397
398 (% style="text-align:center" %)
399 [[image:image-20220810164710-1.png]]
400
401 **New PLC project**
402
403 Click New Project and select the PLC model.
404
405 [[image:image-20220811115454-1.png]]
406
407 **Set Ethernet port parameters**
408
409 Follow the steps below to configure Ethernet parameters
410
411 * PLC IP address:192.168.39.200
412 * default gateway:192.168.39.1
413 * subnet mask:255.255.255.0
414
415 [[image:image-20220811140530-2.png]]
416
417 **Registers list**
418
419 [[image:image-20220811102219-3.png]]
420
421 **HMI software configuration**
422
423 HMI programming software
424
425
426 (% style="text-align:center" %)
427 [[image:image-20220810171237-4.png]]
428
429 **New HMI project**
430
431 Click New Project and select the HMI model.
432
433 [[image:image-20220810172010-5.png]]
434
435 **Set communication port parameters**
436
437 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
438
439 * HMI IP address:192.168.39.201
440 * Default gateway:192.168.39.1
441 * Subnet mask:255.255.255.0
442
443 [[image:image-20220811170753-2.png]]
444
445 Next, click Communication Settings to configure the IP of the HMI communication object.
446
447 [[image:image-20220811163047-1.png]]
448
449 **Hardware connection**
450
451 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
452
453 (% style="text-align:center" %)
454 [[image:image-20220811170248-1.png]]
455
456 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
457
458 = Create communication with ABB PLC =
459
460 == **AC500 Protocol** ==
461
462 Support Series: ABB AC500
463
464 **HMI Settings**
465
466 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
467 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
468 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
469 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
470 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
471 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
472 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
473 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
474 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
475
476 **Address List**
477
478 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
479 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
480 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
481 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
482
483 **Cable Wiring**
484
485 (% style="text-align:center" %)
486 [[image:ABB AC500.gif]]
487
488 = Create communication with Abzil Controller =
489
490 == **Abzil CPL Protocol** ==
491
492 Supported series: SDC series
493
494 **HMI Settings**
495
496 (% style="width:1003px" %)
497 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
498 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
499 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
500 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
501 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
502 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
503 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
504 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
505
506 **Address List**
507
508 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
509 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
510 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
511 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
512 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
513 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
514 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
515 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
516 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
517 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
518 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
519 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
520 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
521 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
522 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
523 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
524 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
525 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
526 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:Azbil CPL485.gif]]
532
533 = Create communication with Crouzet PLC =
534
535 == **M3 (FBD) Protocol** ==
536
537 Support Series: Crouzet Millenium 3 CD12/CB12
538
539 **HMI Settings**
540
541 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
542 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
543 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
544 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
545 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
546 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
547 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
548 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
549 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
550
551 **Address List**
552
553 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
554 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
555 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
556 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
557 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
558 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
559 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
560 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
561 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
562 Time1: Second
563
564 Time2: Minute
565
566 Time3: Hour
567
568 Time4: Day
569
570 Time5: Month
571
572 Time6: Year
573 )))
574 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
575 Running command(Write only)
576
577 ~=2: Run mode; =1: Stop mode;
578 )))
579
580 **Cable Wiring**
581
582 (% style="text-align:center" %)
583 [[image:CrouzetRS232.png]]
584
585 {{info}}
586 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
587 {{/info}}
588
589 = Create communication with Danfoss Drive =
590
591 == **FC Series Protocol** ==
592
593 Support Series: VLT FC300 Drive
594
595 **HMI Settings**
596
597 (% style="width:988px" %)
598 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
599 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
600 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
601 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
602 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
603 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
604 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
605 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
606 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
607
608 **Address List**
609
610 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
611 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
612 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
613 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
614 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
615
616 **Cable Wiring**
617
618 (% style="text-align:center" %)
619 [[image:Danfoss.png]]
620
621 = Create communication with **Delta PLC** =
622
623 == DVP serial protocol ==
624
625 (% class="wikigeneratedid" %)
626 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
627
628 **HMI Settings**
629
630 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
631 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
632 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
633 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
634 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
635 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
636 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
637 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
638
639 **Address List**
640
641 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
642 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
643 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
644 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
645 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
646 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
647 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
648 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
649 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
650 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
651
652 (% class="wikigeneratedid" %)
653 **Configure the communication protocol**
654
655 (% style="text-align:center" %)
656 [[image:image-20220829152327-6.png]]
657
658 (% style="text-align:center" %)
659 [[image:image-20220829152016-3.png]]
660
661 (% class="wikigeneratedid" %)
662 **Cable Wiring**
663
664 (% class="wikigeneratedid" id="H" %)
665 [[image:image-20220829152610-7.png]]
666
667 (% style="text-align:center" %)
668 [[image:image-20220829152102-5.png]]
669
670 == DVP Ethernet Protocol ==
671
672 (% class="wikigeneratedid" %)
673 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
674
675 **HMI Settings**
676
677 |=**Items**|=**Settings**|=**Note**
678 |Protocol|DELTA DVP Modbus TCP|
679 |Connection|Ethernet|
680 |Port No.|201|Must be the same as the PLC setting
681 |PLC station No.|0|Must be the same as the PLC setting
682
683 **Address List**
684
685 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
686 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
687 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
688 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
689 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
690 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
691 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
692 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
693 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
694 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
695
696 )))
697 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
698 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
699
700 )))
701
702 (% class="wikigeneratedid" %)
703 **Configure the communication protocol**
704
705 (% style="text-align:center" %)
706 [[image:image-20220829155452-1.png]]
707
708 [[image:image-20220829162116-2.png]]
709
710 **Cable Wiring**
711
712 (% style="text-align:center" %)
713 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
714
715 == **AS serial protocol** ==
716
717 Supported Series: Delta AS200/AS300
718
719 **HMI Settings**
720
721 |**Item**|**Settings**|**Note**
722 |Protocol|DELTA AS300 MODBUS RTU|
723 |Connection|RS485|
724 |Baud rate|9600|
725 |Data bit|8|
726 |Parity|NONE|
727 |Stop bit|1|
728 |PLC station No.|1|
729
730 **Address List**
731
732 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
733 |Bit|X|X|Xdd.dd|0~~63.15|Read only
734 |Bit|Y|Y|Ydd.dd|0~~63.15|
735 |Bit|D|D|Dddddd|0~~29999|
736 |Bit|M|M|Mdddd|0~~8191|
737 |Bit|SM|SM|SMdddd|0~~4095|
738 |Bit|S|S|Sdddd|0~~2047|
739 |Bit|T|T|Tddd|0~~511|
740 |Bit|C|C|Cddd|0~~511|
741 |Bit|HC|HC|HCddd|0~~255|Double Word
742 |Word|X|X|Xdd|0~~63|
743 |Word|Y|Y|(((
744 Ydd
745 )))|0~~63|
746 |Word|SR|SR|SRdddd|0~~2047|Special register
747 |Word|D|D|Dddddd|0~~29999|
748 |Word|T|T|Tddd|0~~511|
749 |Word|C|C|Cddd|0~~511|
750 |Word|E|E|Ed|0~~9|
751
752 **Configure the communication protocol**
753
754 Create project
755
756 (% style="text-align:center" %)
757 [[image:AsCreateProject.png]]
758
759 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
760
761 (% style="text-align:center" %)
762 [[image:AScommunicarw.png]]
763
764 Double click the HWCONFIG to open the communication settings window.
765
766 (% style="text-align:center" %)
767 [[image:ASHWCONFIG.png]]
768
769 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
770
771 (% style="text-align:center" %)
772 [[image:ASHSCONFIGICON.png]]
773
774 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
775
776 (% style="text-align:center" %)
777 [[image:ASModbusMode.png]]
778
779 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
780
781 (% style="text-align:center" %)
782 [[image:ASconfigIP.png]]
783
784 (% style="text-align:center" %)
785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
786
787
788 (% style="text-align:center" %)
789 [[image:image-20220830094657-2.png]]
790
791 **Cable Wiring**
792
793 (% style="text-align:center" %)
794 [[image:image-20220830141138-1.png]]
795
796 Pin Definition Diagram
797
798 (% style="text-align:center" %)
799 [[image:image-20220830095131-1.png]]
800
801 == AS Ethernet Protocol ==
802
803 **HMI Settings**
804
805 |=**Items**|=**Settings**|=**Note**
806 |Protocol|DELTA AS300 MODBUS TCP|
807 |Connection|Ethernet|
808 |Port No.|502|
809 |Device No.|1|
810 |HMI No.|0|
811
812 **Address List**
813
814 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
815 |Bit|X|X|X d|0~~63|
816 |Bit|Y|Y|Y d|0~~63|
817 |Bit|D|D|D d|0~~29999|
818 |Bit|M|M|M d|0~~8191|
819 |Bit|SM|SM|SM d|0~~4095|
820 |Bit|S|S|S h|0~~2047|
821 |Bit|T|T|T d|0~~511|
822 |Bit|C|C|C d|0~~511|
823 |Bit|HC|HC|HC d|0~~255|
824 |Word|X|X|X h|0~~63|
825 |Word|Y|Y|Y d|0~~63|
826 |Word|SR|SR|SR d|0~~2047|
827 |Word|D|D|D d|0~~29999|
828 |Word|T|T|T d|0~~511|
829 |Word|C|C|C h|0~~511|
830 |Word|E|E|E d|0~~9|
831
832 **Configure the communication protocol**
833
834 (% style="text-align:center" %)
835 [[image:image-20220830140537-1.png]]
836
837 (% style="text-align:center" %)
838 [[image:image-20220830140629-2.png]]
839
840 **Cable Wiring**
841
842 [[image:image-20220830094929-1.png]]
843
844 Pin Definition Diagram
845
846 (% style="text-align:center" %)
847 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
848
849 = **Create communication with EMERSON PLC** =
850
851 == **RTU Slave Protocol** ==
852
853 Supported series: EC10 series
854
855 **HMI Settings**
856
857 |**Item**|**Settings**|**Note**
858 |Protocol|Emerson 984 RTU Slave MODBUS|
859 |Connection|RS485|
860 |Baud rate|19200|
861 |Data bit|8|
862 |Parity|EVEN|
863 |Stop bit|1|
864 |PLC station No.|1
865
866 **PLC Settings**
867
868 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
869
870 (% style="text-align:center" %)
871 [[image:ControlStarSystemBlock.png]]
872
873 (% style="text-align:center" %)
874 [[image:ControlStarCommunicate.png]]
875
876 (% style="text-align:center" %)
877 [[image:ControlStarModbus.png]]
878
879 **Address List**
880
881 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
882 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
883 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
884 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
885 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
886 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
887 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
888 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
889 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
890 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
891 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
892 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
893 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
894 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
895 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
896 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
897 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
898 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
899 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
900 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
901 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
902 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
903
904 **Cable Wiring**
905
906 (% style="text-align:center" %)
907 [[image:Emerson.gif]]
908
909 = **Create communication with HollySys PLC** =
910
911 == **LK MODBUS RTU** ==
912
913 Supported Series: HollySys LK series CPU
914
915 **HMI Settings**
916
917 |=Item|=Recommended|=Note
918 |=Protocol|HollySys LK MODBUS RTU|
919 |=Connection|RS485|
920 |=Baud rate|38400|
921 |=Stop bits|1|
922 |=Data bits|8|
923 |=Parity|NONE|
924 |=PLC Station No.|1|
925 |=HMI Station No.|0|
926
927 **Address List**
928
929 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
930 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
931 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
932 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
933 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
934 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
935 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
936 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
937
938 **Cable Wiring**
939
940 (% style="text-align:center" %)
941 [[image:Hollysys485.png]]
942
943 = **Create communication with Inovance PLC** =
944
945 == **H1U/H2U serial protocol** ==
946
947 **HMI Settings**
948
949 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
950 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
951 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
952 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
953 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
954 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
955 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
956 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
957 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
958
959 (% class="wikigeneratedid" %)
960 **Address List**
961
962 (% style="width:1014px" %)
963 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
964 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
965 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
966 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
967 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
968 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
969 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
970 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
971 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
972 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
973 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
974 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
975 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
976 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
977 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
978 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
979 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
980 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
981
982 (% class="wikigeneratedid" %)
983 **Cable Wiring**
984
985 (% style="text-align:center" %)
986 [[image:Inovance.png]]
987
988 == **H3U serial protocol** ==
989
990 **HMI Settings**
991
992 |=**Item**|=**Settings**|=**Note**
993 |Protocol|INOVANCE H3U PLC|
994 |Connection|RS422|
995 |Baud rate|9600|
996 |Data bit|7|
997 |Parity|EVEN|
998 |Stop bit|1|
999 |PLC station No.|0|
1000
1001 **Address List**
1002
1003 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1004 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1005 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1006 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1007 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1008 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1009 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1010 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1011 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1012 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1013 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1014 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1015 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1016 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1017 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1018 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1019 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1020 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1021 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1022
1023 **Configure the communication protocol**
1024
1025 (% style="text-align:center" %)
1026 [[image:image-20220830170114-4.png]]
1027
1028 [[image:image-20220830170017-3.png]]
1029
1030 **Cable Wiring**
1031
1032 (% style="text-align:center" %)
1033 [[image:Inovance.png]]
1034
1035 == **H3U Ethernet portocol** ==
1036
1037 **HMI Settings**
1038
1039 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1040 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1041 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1042 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1043 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1044 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1045
1046 **Address List**
1047
1048 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1049 |Bit|M|M DDDD|0~~8511|
1050 |Bit|SM|SM DDDD|0~~1023|
1051 |Bit|S|S DDDD|0~~4095|
1052 |Bit|T|T DDD|0~~511|
1053 |Bit|C|C DDD|0~~255|
1054 |Bit|X|X OOO|0~~571|
1055 |Bit|Y|Y OOO|0~~571|
1056 |Word|D|D DDDD|0~~8511|
1057 |Word|SD |SD DDDD|0~~1023|
1058 |Word|R|R DDDDD|0~~32767|
1059 |Word|T|T DDD|0~~255|
1060 |Word|C|C DDD|0~~199|
1061 |Double Word|C|C DDD|200~~255|
1062
1063 **Cable Wiring**
1064
1065 (% style="text-align:center" %)
1066 [[image:CommonEthernet.png]]
1067
1068 = Create communication with LS** PLC** =
1069
1070 == **XGB serial protocol ** ==
1071
1072 **HMI Settings**
1073
1074 |=**Item**|=**Settings**|=**Note**
1075 |Protocol|LS XGB CPU DRIECT|
1076 |Connection|RS232|
1077 |Baud rate|115200|
1078 |Data bit|8|
1079 |Parity|NONE|
1080 |Stop bit|1|
1081 |PLC station No.|1|
1082
1083 **Address List**
1084
1085 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1086 |Bit|P|P|P DDDD.f|0~~2047|
1087 |Bit|M|M|M DDDD.f|0~~2047|
1088 |Bit|L|L|L DDDDD.f|0~~11263|
1089 |Bit|K|K|K DDDD.f|0~~2559|
1090 |Bit|F|F|F DDDD.f|0~~2047|
1091 |Bit|S|S|S DDDDD|0~~12799|
1092 |Bit|D|D|D DDDDD.f|0~~32767|
1093 |Bit|U|U|U FFFF.f|0~~7f31|
1094 |Bit|T|T|T DDDD.f|0~~2047|
1095 |Bit|C|C|C DDDD.f|0~~2047|
1096 |Word|P|P|P DDDD|0~~2047|
1097 |Word|M|M|M DDDD|0~~2047|
1098 |Word|L|L|L DDDDD|0~~11263|
1099 |Word|K|K|K DDDD|0~~2559|
1100 |Word|F|F|F DDDD|0~~2047|
1101 |Word|C|C|C DDDD|0~~2047|
1102 |Word|T|T|T DDDD|0~~2047|
1103 |Word|D|D|D DDDDD|0~~32767|
1104 |Word|N|N|N DDDDD|0~~21503|
1105 |Word|U|U|U FFFF|0~~7f31|
1106 |Word|Z|Z|Z DDD|0~~127|
1107 |Word|R|R|R DDDDD|0~~32767|
1108 |Word|ZR|ZR|Z DDDDD|0~~32767|
1109 |Word|TS|TS|TS DDDD|0~~2047|
1110 |Word|CS|CS|CS DDDD|0~~2047|
1111 |Word|S|S|S DDDDD|0~~12799|
1112
1113 **Configure the communication protocol**
1114
1115 (% style="text-align:center" %)
1116 [[image:image-20221028174410-1.png]]
1117
1118 (% style="text-align:center" %)
1119 [[image:image-20221028174753-2.png]]
1120
1121 (% style="text-align:center" %)
1122 [[image:image-20221028181125-4.png]]
1123
1124 **Pin Definition Diagram**
1125
1126 (% style="text-align:center" %)
1127 [[image:image-20221028180930-3.png]]
1128
1129 == **XBC serial protocol** ==
1130
1131 **HMI Settings**
1132
1133 |=**Item**|=**Settings**|=**Note**
1134 |Protocol|LS XBC CNet|
1135 |Connection|RS232|
1136 |Baud rate|115200|
1137 |Data bit|8|
1138 |Parity|NONE|
1139 |Stop bit|1|
1140 |PLC station No.|1|
1141
1142 **Address List**
1143
1144 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1145 |Bit|P|P|P d|0~~2047|
1146 |Bit|M|M|M d|0~~2047|
1147 |Bit|L|L|L d|0~~11263|
1148 |Bit|K|K|K d|0~~16183|
1149 |Bit|F|F|F d|0~~2047|
1150 |Bit|D|D|D d|0~~32767|
1151 |Bit|R|R|R d|0~~32767|
1152 |Bit|U|U|U d|0~~4095|
1153 |Word|P|P|P d|0~~2047|
1154 |Word|M|M|M d|0~~2047|
1155 |Word|L|L|L d|0~~11263|
1156 |Word|K|K|K d|0~~16183|
1157 |Word|F|F|F d|0~~2047|
1158 |Word|C|C|C d|0~~2047|
1159 |Word|T|T|T d|0~~2047|
1160 |Word|D|D|D d|0~~32767|
1161 |Word|N|N|N d|0~~21503|
1162 |Word|R|R|R d|0~~32767|
1163 |Word|U|U|U d|0~~4095|
1164 |Word|Z|Z|Z d|0~~127|
1165 |Word|S|S|S d|0~~127|
1166
1167 **Configure the communication protocol**
1168
1169 (% style="text-align:center" %)
1170 [[image:image-20220831170807-1.png]]
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20220830174733-2.png]]
1174
1175 **Cable Wiring**
1176
1177 (% style="text-align:center" %)
1178 [[image:image-20220830174659-1.png]]
1179
1180 Pin Definition Diagram
1181
1182 (% style="text-align:center" %)
1183 [[image:image-20220830173402-8.png]]
1184
1185 == **XGK FEnet Ethernet protocol** ==
1186
1187 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1188
1189 **HMI Settings**
1190
1191 |**Items**|**Settings**|**Note**
1192 |Protocol|LG XGK FEnet(Ethernet)|
1193 |Connection|Ethernet|
1194 |Port No.|2004|
1195
1196 **Address List**
1197
1198 |**Type**|**Register**|**Range**|**Format**|**Note**
1199 |(% rowspan="14" %)Word|P|0~~2047|P d|
1200 |M|0~~2047|M d|
1201 |K|0~~2047|K d|
1202 |F|0~~2047|F d|
1203 |T|0~~2047|T d|
1204 |C|0~~2047|C d|
1205 |Z|0~~127|Z d|
1206 |S|0~~127|S d|
1207 |L|0~~11263|L d|
1208 |N|0~~21503|N d|
1209 |D|0~~32767|D d|
1210 |R|0~~32767|R d|
1211 |ZR|0~~65535|ZR d|
1212 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1213
1214 **✎Note:**
1215
1216 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1217 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1218 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1219
1220 **Communication settings in HMI**
1221
1222 Enable HMI Ethernet in [Project Settings];
1223
1224 (% style="text-align:center" %)
1225 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1226
1227 Set PLC IP in [Device IP] settings;
1228
1229 (% style="text-align:center" %)
1230 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1231
1232 **Cable Wiring**
1233
1234
1235 (% style="text-align:center" %)
1236 [[image:CommonEthernet.png]]
1237
1238 = Create communication with **Mitsubishi PLC** =
1239
1240 == **FX1S, 1N, 2N Series Protocol** ==
1241
1242 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1243
1244 **HMI Settings**
1245
1246 |**Item**|**Settings**|**Note**
1247 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1248 |Connection|RS422/RS485/RS232|
1249 |Baud rate|9600~~115200|
1250 |Data bit|7/8|
1251 |Parity|EVEN/Odd/None|
1252 |Stop bit|1/2|
1253 |PLC station No.|1~~255|
1254
1255 **Address List**
1256
1257 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1258 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1259 |Y|Y|Y o|0~~303237|
1260 |M|M|M d|0~~99999|
1261 |T|T|T d|0~~99999|
1262 |C|C|C d|0~~99999|
1263 |S|S|S d|0~~99999|
1264 |SM|SM|SM d|8000~~9999|
1265 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1266 |Y|Y|Y o|0~~303237|
1267 |M|M|M d|0~~99999|
1268 |T|T|T d|0~~99999|
1269 |C|C|C d|0~~199|
1270 |D|D|D d|0~~7999|
1271 |S|S|S d|0~~99999|
1272 |SD|SD|SD d|8000~~9999|
1273
1274 **Cable Wiring**
1275
1276 * **RS485**
1277
1278 (% style="text-align:center" %)
1279 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1283
1284 * **RS422**
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1288
1289 **✎Note:** COM3 only available in PI8000/PI9000 series.
1290
1291 == **FX3U/3G/3GA serial protocol** ==
1292
1293 **HMI Settings**
1294
1295 |=**Item**|=**Settings**|=**Note**
1296 |Protocol|Mitsubishi FX3U/3G/3GA|
1297 |Connection|RS422|
1298 |Baud rate|9600~~115200|
1299 |Data bit|7/8|
1300 |Parity|EVEN/Odd/None|
1301 |Stop bit|1/2|
1302 |PLC station No.|1~~255|
1303
1304 **Address List**
1305
1306 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1307 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1308 |Y|Y|Y o|0~~303237|
1309 |M|M|M d|0~~99999|
1310 |T|T|T d|0~~99999|
1311 |C|C|C d|0~~99999|
1312 |S|S|S d|0~~99999|
1313 |SM|SM|SM d|8000~~9999|
1314 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1315 |Y|Y|Y o|0~~303237|
1316 |M|M|M d|0~~99999|
1317 |T|T|T d|0~~99999|
1318 |C|C|C d|0~~199|
1319 |D|D|D d|0~~7999|
1320 |S|S|S d|0~~99999|
1321 |SD|SD|SD d|8000~~9999|
1322
1323 **Configure the communication protocol**
1324
1325 (% style="text-align:center" %)
1326 [[image:image-20220831095222-1.png]]
1327
1328 (% style="text-align:center" %)
1329 [[image:image-20220831095743-2.png]]
1330
1331 **Wiring**
1332
1333 (% style="text-align:center" %)
1334 [[image:image-20220831100314-6.png]]
1335
1336 == **FX3U Ethernet Protocol** ==
1337
1338 Mitsubishi FX3U series PLC
1339
1340 **HMI Settings**
1341
1342 |Items|Settings|Note
1343 |Protocol|Mitsubishi FX3U|
1344 |Connection|Ethernet|
1345 |Port No.|5009|Must be the same as the PLC setting
1346 |PLC station No.|0|
1347
1348 **Address List**
1349
1350 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1351 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1352 |Y|Y|Y OOO|0~~377|
1353 |M|M|M DDDD|0~~7679|
1354 |SM|SM|SM DDDD|8000~~8511|
1355 |S|S|S DDDD|0~~4095|
1356 |TS|TS|TS DDD|0~~511|
1357 |CS|CS|CS DDD|0~~255|
1358 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1359 |TN|TN|TN DDD|0~~511|
1360 |D|D|D DDDD|0~~7999|
1361 |SD|SD|SD DDDD|8000~~8511|
1362 |R|R|R DDDDD|0~~32767|
1363
1364 **Ethernet Module Settings**
1365
1366 FX3U-ENET-L module configuration
1367 Set up the FX3U-ENET-L Ethernet module settings as follows.
1368 Select the module location, which in this document is Module 0.
1369
1370 [[image:image-20221115140802-1.png]]
1371
1372 Select "Operational setting" to enter the following screen.
1373
1374 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1375
1376 [[image:image-20221115142728-4.png]]
1377
1378 Select "Open setting" to enter the setting interface, the settings are as follows.
1379
1380 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1381
1382 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1383
1384 [[image:image-20221115142945-5.png]]
1385
1386 Click on "transter setup" - "PC side I/F setting", see the following figure.
1387
1388 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1389
1390 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1391
1392 [[image:image-20221115143341-6.png||height="426" width="712"]]
1393
1394 Read and write data from the Ethernet module
1395
1396 [[image:image-20221115143703-7.png]]
1397
1398 Set "Transter setup" to COM communication, and read or write operation as shown below
1399
1400 [[image:image-20221115143809-8.png]]
1401
1402 **PLC Settings (GX Works 2)**
1403
1404 Create a blank FX5U project
1405
1406 Find Current Connection in the navigation
1407
1408 [[image:image-20221115144335-9.png||height="422" width="706"]]
1409
1410 Select Connection Channel List
1411
1412 Select Ethernet board communication
1413
1414 [[image:image-20221115144824-10.png||height="421" width="705"]]
1415
1416 Select Ethernet Module
1417 Set the IP address of the PLC
1418
1419 [[image:image-20221115145228-11.png||height="674" width="708"]]
1420
1421 Read or write PLC data, in this document is read
1422
1423 [[image:image-20221115145553-12.png||height="424" width="711"]]
1424
1425 [[image:image-20221115145559-13.png||height="424" width="711"]]
1426
1427 **HMI Communication Setting**
1428
1429 [[image:image-20221115150003-14.png||height="425" width="712"]]
1430
1431 [[image:image-20221115150235-15.png||height="427" width="713"]]
1432
1433 [[image:image-20221115145559-13.png||height="424" width="711"]]
1434
1435 **HMI Communication Setting**
1436
1437 [[image:image-20221115150003-14.png||height="425" width="712"]]
1438
1439 [[image:image-20221115150235-15.png||height="427" width="713"]]
1440
1441 == **FX5U Serial Port Protocol** ==
1442
1443 Mitsubishi FX5U series PLC
1444
1445 **HMI Settings**
1446
1447 |**Item**|**Settings**|**Note**
1448 |Protocol|Mitsubishi FX5U|
1449 |Connection|RS422/RS485|
1450 |Baud rate|9600|
1451 |Data bit|7|
1452 |Parity|Odd|
1453 |Stop bit|1|
1454 |PLC station No.|1~~255|Need to be the same as PLC settings
1455
1456 **Address List**
1457
1458 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1459 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1460 |Y|Y|Y o|0~~303237|
1461 |M|M|M d|0~~99999|
1462 |B|B|B h|0~~7FFF|
1463 |F|F|F d|0~~32767|
1464 |SB|SB|SB h|0~~7FFF|
1465 |TS|TS|TS d|0~~1023|
1466 |TC|TC|TC d|0~~1023|
1467 |STS|STS|STS d|0~~1023|
1468 |STC|STC|STS d|0~~1023|
1469 |CS|CS|CS d|0~~1023|
1470 |CC|CC|CC d|0~~1023|
1471 |SM|SM|SM d|0~~9999|
1472 |L|L|L d|0~~32767|
1473 |S|S|S d|0~~4095|
1474 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1475 |TN|TN|TN d|0~~1023|
1476 |STN|STN|STN d|0~~1023|
1477 |CN|CN|CN d|0~~1023|
1478 |R|R|R d|0~~32767|
1479 |SW|SW|SW h|0~~7FFF|
1480 |Z|Z|Z d|0~~23|
1481 |D|D|D d|0~~7999|
1482 |SD|SD|SD d|0~~11999|
1483
1484 **PLC Settings (GX Works 3)**
1485
1486 Create a blank FX5U project
1487
1488 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1489
1490 (% style="text-align:center" %)
1491 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1492
1493 Select protocol in the setting item, and set parameters.
1494
1495 (% style="text-align:center" %)
1496 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1497
1498 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1499
1500 (% style="text-align:center" %)
1501 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1502
1503 Click the [Apply] button to finish the setting.
1504
1505 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1506
1507 (% style="text-align:center" %)
1508 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1509
1510 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1511
1512 Done.
1513
1514 **Cable Wiring**
1515
1516 * **RS485**
1517
1518 (% style="text-align:center" %)
1519 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1520
1521 (% style="text-align:center" %)
1522 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1523
1524 * **RS422**
1525
1526 (% style="text-align:center" %)
1527 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1528
1529 **✎Note:** COM3 only available in PI8000/PI9000 series.
1530
1531 == **L02 Serial Protocol** ==
1532
1533 Mitsubishi L02 series CPU built-in serial port.
1534
1535 **HMI Settings**
1536
1537 |=**Item**|=**Settings**|=**Note**
1538 |Protocol|Mitsubishi L02|
1539 |Connection|RS422|
1540 |Baud rate|115200|
1541 |Data bit|8|
1542 |Parity|Odd|
1543 |Stop bit|1|
1544 |PLC station No.|1~~255|Need to be the same as PLC settings
1545
1546 **Address List**
1547
1548 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1549 |Bit|X|X|X h|0~~FFFF|
1550 |Bit|Y|Y|Y h|0~~FFFF|
1551 |Bit|M|M|M d|0~~9999|
1552 |Bit|L|L|L d|0~~9999|
1553 |Bit|F|F|F d|0~~9999|
1554 |Bit|B|B|B h|0~~FFFF|
1555 |Bit|V|V|V d|0~~2047|
1556 |Bit|TC|TC|TC d|0~~9999|
1557 |Bit|SS|SS|SS d|0~~9999|
1558 |Bit|SC|SC|SC d|0~~9999|
1559 |Bit|CS|CS|CS d|0~~9999|
1560 |Bit|CC|CC|CC d|0~~9999|
1561 |Bit|SB|SB|SB h|0~~FFFF|
1562 |Bit|SM|SM|SM d|0~~2047|
1563 |Bit|STS|STS|STS d|0~~1023|
1564 |Bit|S|S|S d|0~~9999|
1565 |Bit|DX|DX|DX h|0~~FFFF|
1566 |Bit|DY|DY|DY h|0~~FFFF|
1567 |Bit|TS|TS|TS d|0~~9999|
1568 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1569 |Word|W|W|W h|0~~FFFF|
1570 |Word|TN|TN|TN d|0~~99999|
1571 |Word|SN|SN|SN d|0~~99999|
1572 |Word|CN|CN|CN d|0~~99999|
1573 |Word|R|R|R d|0~~99999|
1574 |Word|SW|SW|SW h|0~~FFFF|
1575 |Word|Z|Z|Z d|0~~99999|
1576 |Word|ZR|ZR|ZR h|0~~FFFF|
1577 |Word|D|D|D d|0~~99999|
1578
1579 **Communication Settings**
1580
1581 (% style="text-align:center" %)
1582 [[image:image-20220831105732-3.png]]
1583
1584 (% style="text-align:center" %)
1585 [[image:image-20220831110004-5.png]]
1586
1587 **Cable Wiring**
1588
1589 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1590
1591 Pin Definition Diagram
1592
1593 (% style="text-align:center" %)
1594 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1595
1596 == **L02 MELSEC (Ethernet) Protocol** ==
1597
1598 Mitsubishi Q series CPU built-in Ethernet port.
1599
1600 **HMI Settings**
1601
1602 |**Items**|**Settings**|**Note**
1603 |Protocol|MIT L02 CPU MELSEC|
1604 |Connection|Ethernet|
1605 |Port No.|1025|Must be the same as the PLC setting
1606 |PLC station No.|0|Must be the same as the PLC setting
1607
1608 **Address List**
1609
1610 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1611 |Bit|X|X|X h|0~~FFFF|
1612 |Bit|Y|Y|Y h|0~~FFFF|
1613 |Bit|M|M|M d|0~~9999|
1614 |Bit|L|L|L d|0~~9999|
1615 |Bit|F|F|F d|0~~9999|
1616 |Bit|B|B|B h|0~~FFFF|
1617 |Bit|V|V|V d|0~~2047|
1618 |Bit|TC|TC|TC d|0~~9999|
1619 |Bit|SS|SS|SS d|0~~9999|
1620 |Bit|SC|SC|SC d|0~~9999|
1621 |Bit|CS|CS|CS d|0~~9999|
1622 |Bit|CC|CC|CC d|0~~9999|
1623 |Bit|SB|SB|SB h|0~~FFFF|
1624 |Bit|SM|SM|SM d|0~~2047|
1625 |Bit|STS|STS|STS d|0~~1023|
1626 |Bit|S|S|S d|0~~9999|
1627 |Bit|DX|DX|DX h|0~~FFFF|
1628 |Bit|DY|DY|DY h|0~~FFFF|
1629 |Bit|TS|TS|TS d|0~~9999|
1630 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1631 |Word|W|W|W h|0~~FFFF|
1632 |Word|TN|TN|TN d|0~~99999|
1633 |Word|SN|SN|SN d|0~~99999|
1634 |Word|CN|CN|CN d|0~~99999|
1635 |Word|R|R|R d|0~~99999|
1636 |Word|SW|SW|SW h|0~~FFFF|
1637 |Word|Z|Z|Z d|0~~99999|
1638 |Word|ZR|ZR|ZR h|0~~FFFF|
1639 |Word|D|D|D d|0~~99999|
1640
1641 **Communication Settings**
1642
1643 Enable HMI Ethernet in [Project Settings];
1644
1645 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1646
1647 Set PLC IP in [Device IP] settings;
1648
1649 (% style="text-align:center" %)
1650 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1651
1652 **PLC Settings (GX Works2 )**
1653
1654 Create a project
1655
1656 Set PLC IP, subnet mask and gateway;
1657
1658 Select [Binary Code] as communication data code;
1659
1660 (% style="text-align:center" %)
1661 [[image:image-20221108202109-2.png||height="636" width="732"]]
1662
1663 Set PLC port number, for example 1025
1664
1665 (% style="text-align:center" %)
1666 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1667
1668 Save settings;
1669
1670 Download project into PLC device;
1671
1672 Restart PLC device;
1673
1674 **Cable Wiring**
1675
1676 (% style="text-align:center" %)
1677 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1678
1679 == **QJ71C24N MELSEC Protocol** ==
1680
1681 Mitsubishi QJ71C24N communication module built-in serial port;
1682
1683 **HMI Settings**
1684
1685 |**Items**|**Settings**|**Note**
1686 |Protocol|MIT QJ71 MELSEC|
1687 |Connection|422|
1688 |Baud rate|9600|
1689 |Data bit|8|
1690 |Parity|ODD|
1691 |Stop bit|1|
1692 |PLC station No.|1~~255|Need to be the same as PLC settings
1693
1694 **Address List**
1695
1696 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1697 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1698 |Y|Y|Y FFFF|0~~1FFF|
1699 |M|M|M DDDDD|0~~99999|
1700 |L|L|L DDDD|0~~8191|
1701 |F|F|F DDDD|0~~2047|
1702 |V|V|V DDDD|0~~2047|
1703 |B|B|B FFFF|0~~1FFF|
1704 |TS|TS|TS DDDD|0~~2047|
1705 |TC|TC|TC DDDD|0~~2047|
1706 |SS|SS|SS DDDD|0~~2047|
1707 |SC|SC|SC DDDD|0~~2047|
1708 |CS|CS|CS DDDD|0~~1023|
1709 |CC|CC|CC DDDD|0~~1023|
1710 |SB|SB|SB FFF|0~~7FF|
1711 |S|S|S D|0~~8191|
1712 |DX|DX|DX FFFF|0~~1FFF|
1713 |DY|DY|DY FFFF|0~~1FFF|
1714 |SM_|SM_|SM_ DDDD|8000~~9999|
1715 |SM|SM|SM DDDD|0~~2047|
1716 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1717 |D|D|D DDDDD|0~~12287|
1718 |W|W|W FFFF|0~~1FFF|
1719 |TN|TN|TN DDDD|0~~2047|
1720 |SN|SN|SN DDDD|0~~2047|
1721 |CN|CN|CN DDDD|0~~1023|
1722 |R|R|R DDDDD|0~~32767|
1723 |SW|SW|SW FFF|0~~7FF|
1724 |Z|Z|Z D|0~~15|
1725 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1726
1727 **Communication Settings**
1728
1729 (% style="text-align:center" %)
1730 [[image:image-20221109135738-1.png]]
1731
1732 (% style="text-align:center" %)
1733 [[image:image-20221109140016-3.png]]
1734
1735 Pin Definition Diagram
1736
1737 (% style="text-align:center" %)
1738 [[image:image-20221109140406-4.png]]
1739
1740 == **QJ71E71 MELSEC Protocol** ==
1741
1742 Mitsubishi QJ71E71 Ethernet communication module;
1743
1744 **HMI Settings**
1745
1746 |**Items**|**Settings**|**Note**
1747 |Protocol|MIT QJ71E71 MELSEC|
1748 |Connection|Ethernet|
1749 |Port No.|1025|Must be the same as the PLC setting
1750 |PLC station No.|0|Must be the same as the PLC setting
1751
1752 **Address List**
1753
1754 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1755 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1756 |Y|Y|Y h|0~~1FFF|
1757 |M|M|M d|0~~99999|
1758 |L|L|L d|0~~8191|
1759 |F|F|F d|0~~2047|
1760 |B|B|B h|0~~1FFF|
1761 |V|V|V d|0~~2047|
1762 |TS|TS|TS d|0~~2047|
1763 |TC|TC|TC d|0~~2047|
1764 |SS|SS|SS d|0~~2047|
1765 |SC|SC|SC d|0~~2047|
1766 |CS|CS|CS d|0~~1023|
1767 |CC|CC|CC d|0~~1023|
1768 |SB|SB|SB h|0~~7FF|
1769 |S|S|S d|0~~8191|
1770 |DX|DX|DX h|0~~1FFF|
1771 |DY|DY|DY h|0~~1FFF|
1772 |SM|SM|SM d|8000~~9999|
1773 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1774 |D|D|D d|0~~12287|
1775 |W|W|W h|0~~1FFF|
1776 |TN|TN|TN d|0~~2047|
1777 |SN|SN|SN d|0~~2047|
1778 |CN|CN|CN d|0~~1023|
1779 |R|R|R d|0~~32767|
1780 |SW|SW|SW h|0~~7FF|
1781 |Z|Z|Z d|0~~15|
1782 |ZR|ZR|ZR h|0~~FE7FF|
1783
1784 **HMI Communication Settings**
1785
1786 1) Enable HMI Ethernet in [Project Settings];
1787
1788 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1789
1790 2) Set PLC IP in [Device IP] settings
1791
1792 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1793
1794 **PLC Settings(GX Works2)**
1795
1796 * Click [Ethernet/CC IE/MELSECNET];
1797 * Please select [Ethernet] as network type;
1798 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1799 * Select [Online] as Mode;
1800 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1801 * Click [Operation setting] to set IP;
1802 * Select [Binary Code] as [Communication Data Code];
1803 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1804 * Click [Open setting]
1805 * Set protocol: TCP;
1806 * Set [unpassive] in [Open system];
1807 * Set [receive] in [Fixed buffer];
1808 * Set [procedure Exist] in [Fixed buffer communication];
1809 * Disable [Pairing open];
1810 * Set [No confirm] in [Existence confirmation];
1811 * Host station port number: 5009;
1812 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1813 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1814 * Download project into PLC and restart it
1815
1816 **Cable Wiring**
1817
1818 (% style="text-align:center" %)
1819 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1820
1821 = Create communication with **MODBUS** =
1822
1823 == **MODBUS RTU Master** ==
1824
1825 Supported Series: MODBUS RTU CONTROLLER
1826
1827 HMI works as MODBUS SLAVE connecting with MASTER
1828
1829 (% style="text-align:center" %)
1830 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1831
1832 (% style="text-align:center" %)
1833 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1834
1835 (% style="text-align:center" %)
1836 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1837
1838 **HMI Settings**
1839
1840 |**Items**|**Settings**|**Note**
1841 |Protocol|MODBUS RTU Master|
1842 |Connection|RS485/RS232|
1843 |Baud rate|2400~~187500|
1844 |Data bit|8|
1845 |Parity|Even/ Odd/ None|
1846 |Stop bit|1/2|
1847 |Station No.|0~~255|
1848
1849 **Address List**
1850
1851 |**Type**|**HMI address**|**MODBUS code**|**Range**
1852 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1853 |Word|HDW3500~~HDW7999|4|0~~4499
1854
1855 **Cable Wiring**
1856
1857 * **RS485**
1858
1859 (% style="text-align:center" %)
1860 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1861
1862 (% style="text-align:center" %)
1863 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1864
1865 * **RS232**
1866
1867 (% style="text-align:center" %)
1868 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1869
1870 **✎Note:** COM3 only available in PI8000/PI9000 series.
1871
1872 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1873
1874 Supported Series: MODBUS RTU CONTROLLER
1875
1876 HMI works as MODBUS MASTER connecting with SLAVE.
1877
1878 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1879
1880 (% style="text-align:center" %)
1881 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1882
1883 (% style="text-align:center" %)
1884 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1885
1886 (% style="text-align:center" %)
1887 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1888
1889 **HMI Settings**
1890
1891 |**Items**|**Settings**|**Note**
1892 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1893 |Connection|RS485/RS232|
1894 |Baud rate|2400~~187500|
1895 |Data bit|8|
1896 |Parity|Even/ Odd/ None|
1897 |Stop bit|1/2|
1898 |PLC station No.|0~~255|
1899
1900 **Address List**
1901
1902 |**Type**|**Address Type**|**Function code & Description**
1903 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1904 |06 (write single register: write a binary value to a holding register)
1905 |10 (write values to multiple addresses )
1906 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1907 |06 (write single register: write a binary value to a holding register)
1908 |10 (write values to multiple addresses )
1909 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1910 |06 (write single register: write a binary value to a holding register)
1911 |10 (write values to multiple addresses )
1912 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1913 |10 (write values to multiple addresses )
1914 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1915 |05 (Force a single coil to force the on/off state of a logic coil)
1916 |0F (Write multiple bits, ie write continuously)
1917 |(% rowspan="3" %)1|02 (Read the input state)
1918 |05 (Force a single coil to force the on/off state of a logic coil)
1919 |0F (Write multiple bits)
1920 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1921 |05 (Force a single coil to force the on/off state of a logic coil)
1922 |0F (Write multiple bits)
1923 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1924 |0F (Write multiple bits)
1925
1926 **✎Note:**
1927
1928 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1929 * The function codes sent out are the same as those that read and write words.
1930
1931 **Station number for more than one slaves**
1932
1933 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1934
1935 (% style="text-align:center" %)
1936 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1937
1938 **Cable Wiring**
1939
1940 * **RS485**
1941
1942 (% style="text-align:center" %)
1943 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1944
1945 (% style="text-align:center" %)
1946 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1947
1948 * **RS232**
1949
1950 (% style="text-align:center" %)
1951 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1952
1953 **✎Note:** COM3 only available in PI8000/PI9000 series.
1954
1955 == **Communicate with Modbus Meter** ==
1956
1957 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
1958
1959 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
1960
1961 (% style="text-align:center" %)
1962 [[image:LinfeeDiagram.png]]
1963
1964 2. Check the specific Modbus parameter in the communication menu from LED display.
1965
1966 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
1967
1968 {{info}}
1969 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
1970 {{/info}}
1971
1972 (% style="text-align:center" %)
1973 [[image:MeterModbusAllView.png]]
1974
1975 3. Create new project and change the Communication settings.
1976
1977 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
1978
1979 (% style="text-align:center" %)
1980 [[image:PIStudioSetupMeterModbusPara.png]]
1981
1982 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
1983
1984 The following table is intercept part of the manual for Linfee Modbus manual.
1985
1986 **0x03/0x04 command data register address**:
1987
1988 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
1989 | HEX|DEC| | | |
1990 |0x00|0|Reserved| | |
1991 |0x02|2|Reserved| | |
1992 |0x04|4|Reserved| | |
1993 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
1994 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
1995 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
1996 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
1997 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
1998 |0x10|16|Uca|float|2|Line Voltage data, Unit V
1999 |0x12|18|Ia|float|2|Phase Current data, Unit A
2000 |0x14|20|Ib|float|2|Phase Current data, Unit A
2001 |0x16|22|Ic|float|2|Phase Current data, Unit A
2002
2003 {{info}}
2004 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2005 {{/info}}
2006
2007 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2008
2009 (% style="text-align:center" %)
2010 [[image:MeterModbusPInumericSet.png]]
2011
2012 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2013
2014 (% style="text-align:center" %)
2015 [[image:MeterModbusNumericInputFormat.png]]
2016
2017 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2018
2019 (% style="text-align:center" %)
2020 [[image:ActualHMIModbusResult.jpg]]
2021
2022 == **MODBUS TCP Slave (All function)** ==
2023
2024 Supported series: MODBUS TCP controller
2025
2026 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2027
2028 (% style="text-align:center" %)
2029 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2030
2031 (% style="text-align:center" %)
2032 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2033
2034 (% style="text-align:center" %)
2035 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2036
2037 **HMI Setting**
2038
2039 |**Items**|**Settings**|**Note**
2040 |Protocol|MODBUS TCP Slave (All function)|
2041 |Connection|Ethernet|
2042 |Port No.|502|
2043 |PLC station No.|1|
2044
2045 **Address List**
2046
2047 |**Type**|**Register**|**Function code & Description**
2048 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2049 |06 (write single register: write a binary value to a holding register)
2050 |10 (write values to multiple addresses )
2051 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2052 |06 (write single register: write a binary value to a holding register)
2053 |10 (write values to multiple addresses )
2054 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2055 |06 (write single register: write a binary value to a holding register)
2056 |10 (write values to multiple addresses )
2057 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2058 |10 (write values to multiple addresses )
2059 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2060 |05 (Force a single coil to force the on/off state of a logic coil)
2061 |0F (Write multiple bits, ie write continuously)
2062 |(% rowspan="3" %)1|02 (Read the input state)
2063 |05 (Force a single coil to force the on/off state of a logic coil)
2064 |0F (Write multiple bits)
2065 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2066 |05 (Force a single coil to force the on/off state of a logic coil)
2067 |0F (Write multiple bits)
2068 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2069 |0F (Write multiple bits)
2070
2071 **Communication Settings**
2072
2073 Enable HMI Ethernet in [Project Settings];
2074
2075 (% style="text-align:center" %)
2076 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2077
2078 Set PLC IP in [Device IP] settings;
2079
2080 (% style="text-align:center" %)
2081 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2082
2083 **Cable Wiring**
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2087
2088 = Create communication with **Omron** PLC =
2089
2090 == CJ TCP FINS Ethemet  Protocol ==
2091
2092 Supported device:CJ series、CJ1W-EIP21
2093
2094 **HMI Settings**
2095
2096 |=**Items**|=**Settings**|=**Note**
2097 |Protocol|OMRON CJ TCP FINS Ethemet|
2098 |Connection|Ethernet|
2099 |Port No.|9600|
2100 |Device No.|0|
2101 |HMI No.|0|(((
2102
2103 )))
2104
2105 **Address List**
2106
2107 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2108 |Bit|CIO|CIO|CIO d|0~~99999|
2109 |Bit|W|W|W d|0~~99999|
2110 |Bit|D|D|D d|0~~99999|
2111 |Bit|H|H|H d|0~~99999|
2112 |Bit|A|A|A d|0~~99999|
2113 |Bit|T|T|T h|0~~99999|
2114 |Bit|CF|CF|CF d|0~~99999|
2115 |Bit|FF|FF|FF d|0~~99999|
2116 |Bit|C|C|C d|0~~99999|
2117 |Bit|EM0|EM0|EM0 d|0~~99999|
2118 |Bit|EM1|EM1|EM1 d|0~~99999|
2119 |Bit|EM2|EM2|EM2 d|0~~99999|
2120 |Bit|EM3|EM3|EM3 d|0~~99999|
2121 |Bit|EM4|EM4|EM4 d|0~~99999|
2122 |Bit|EM5|EM5|EM5 h|0~~99999|
2123 |Bit|EM6|EM6|EM6 d|0~~99999|
2124 |Bit|EM7|EM7|EM7 d|0~~99999|
2125 |Bit|EM8|EM8|EM8 d|0~~99999|
2126 |Bit|EM9|EM9|EM9 d|0~~99999|
2127 |Bit|EMA|EMA|EMA d|0~~99999|
2128 |Bit|EMB|EMB|EMB d|0~~99999|
2129 |Bit|EMC|EMC|EMC d|0~~99999|
2130 |Bit|Lamp|Lamp|Lamp d|0~~0|
2131 |Word|CIO|CIO|CIO d|0~~99999|
2132 |Word|W|W|W d|0~~99999|
2133 |Word|D|D|D d|0~~99999|
2134 |Word|H|H|H d|0~~99999|
2135 |Word|A|A|A d|0~~99999|
2136 |Word|T|T|T h|0~~99999|
2137 |Word|CF|CF|CF d|0~~99999|
2138 |Word|FF|FF|FF d|0~~99999|
2139 |Word|C|C|C d|0~~99999|
2140 |Word|EM0|EM0|EM0 d|0~~99999|
2141 |Word|EM1|EM1|EM1 d|0~~99999|
2142 |Word|EM2|EM2|EM2 d|0~~99999|
2143 |Word|EM3|EM3|EM3 d|0~~99999|
2144 |Word|EM4|EM4|EM4 d|0~~99999|
2145 |Word|EM5|EM5|EM5 h|0~~99999|
2146 |Word|EM6|EM6|EM6 d|0~~99999|
2147 |Word|EM7|EM7|EM7 d|0~~99999|
2148 |Word|EM8|EM8|EM8 d|0~~99999|
2149 |Word|EM9|EM9|EM9 d|0~~99999|
2150 |Word|EMA|EMA|EMA d|0~~99999|
2151 |Word|EMB|EMB|EMB d|0~~99999|
2152 |Word|EMC|EMC|EMC d|0~~99999|
2153 |Word|IR|IR|IR d|0~~99999|
2154 |Word|DR|DR|DR d|0~~99999|
2155
2156 **Configure the communication protocol**
2157
2158 (% style="text-align:center" %)
2159 [[image:image-20220830143348-1.png]]
2160
2161 (% style="text-align:center" %)
2162 [[image:image-20220830143511-2.png]]
2163
2164 **Configure CJ1W-EIP21 connect with HMI**
2165
2166 (% style="text-align:center" %)
2167 [[image:ftEVGvAprh.png]]
2168
2169 Select TCP_Client_2N
2170
2171 (% style="text-align:center" %)
2172 [[image:RURXWcgyCd.png]]
2173
2174 **Cable Wiring**
2175
2176 Pin Definition Diagram
2177
2178 (% style="text-align:center" %)
2179 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2180
2181 == **CP1E/CP1H serial protocol** ==
2182
2183 Supported device: OMRON CS1(CP1E/CP1H)
2184
2185 **HMI Settings**
2186
2187 |=**Items**|=**Settings**|=**Note**
2188 |Protocol|OMRON CS1(CP1E/CP1H)|
2189 |Connection|RS232 (9600, 2, 7, EVEN)|
2190 |Port No.|None|
2191 |PLC station No.|0|
2192
2193 **Address List**
2194
2195 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2196 |Bit|CIO|CIO|CIO d|0~~99999|
2197 |Bit|W|W|W d|0~~99999|
2198 |Bit|D|D|D d|0~~99999|
2199 |Bit|H|H|H d|0~~99999|
2200 |Bit|A|A|A d|0~~99999|
2201 |Bit|TF|T|T h|0~~99999|
2202 |Bit|CF|CF|CF d|0~~99999|
2203 |Bit|T|FF|FF d|0~~99999|
2204 |Bit|C|C|C d|0~~99999|
2205 |Bit|EM0|EM0|EM0 d|0~~99999|
2206 |Bit|EM1|EM1|EM1 d|0~~99999|
2207 |Bit|EM2|EM2|EM2 d|0~~99999|
2208 |Bit|EM3|EM3|EM3 d|0~~99999|
2209 |Bit|EM4|EM4|EM4 d|0~~99999|
2210 |Bit|EM5|EM5|EM5 h|0~~99999|
2211 |Bit|EM6|EM6|EM6 d|0~~99999|
2212 |Bit|EM7|EM7|EM7 d|0~~99999|
2213 |Bit|EM8|EM8|EM8 d|0~~99999|
2214 |Bit|EM9|EM9|EM9 d|0~~99999|
2215 |Bit|EMA|EMA|EMA d|0~~99999|
2216 |Bit|EMB|EMB|EMB d|0~~99999|
2217 |Bit|EMC|EMC|EMC d|0~~99999|
2218 |Word|CIO|CIO|CIO d|0~~99999|
2219 |Word|W|W|W d|0~~99999|
2220 |Word|D|D|D d|0~~99999|
2221 |Word|H|H|H d|0~~99999|
2222 |Word|A|A|A d|0~~99999|
2223 |Word|T|T|T h|0~~99999|
2224 |Word|CIO|CF|CF d|0~~99999|
2225 |Word|C|C|C d|0~~99999|
2226 |Word|EM0|EM0|EM0 d|0~~99999|
2227 |Word|EM1|EM1|EM1 d|0~~99999|
2228 |Word|EM2|EM2|EM2 d|0~~99999|
2229 |Word|EM3|EM3|EM3 d|0~~99999|
2230 |Word|EM4|EM4|EM4 d|0~~99999|
2231 |Word|EM5|EM5|EM5 h|0~~99999|
2232 |Word|EM6|EM6|EM6 d|0~~99999|
2233 |Word|EM7|EM7|EM7 d|0~~99999|
2234 |Word|EM8|EM8|EM8 d|0~~99999|
2235 |Word|EM9|EM9|EM9 d|0~~99999|
2236 |Word|EMA|EMA|EMA d|0~~99999|
2237 |Word|EMB|EMB|EMB d|0~~99999|
2238 |Word|EMC|EMC|EMC d|0~~99999|
2239 |Word|IR|IR|IR d|0~~99999|
2240 |Word|DR|DR|DR d|0~~99999|
2241
2242 **Configure the communication protocol**
2243
2244 (% style="text-align:center" %)
2245 [[image:image-20220902153118-1.png]]
2246
2247 (% style="text-align:center" %)
2248 [[image:image-20220902151322-2.png]]
2249
2250 **Cable Wiring**
2251
2252 (% style="text-align:center" %)
2253 [[image:image-20220902153949-2.png]]
2254
2255 Pin Definition Diagram
2256
2257 (% style="text-align:center" %)
2258 [[image:image-20220902154056-3.png]]
2259
2260 == **EC55 Protocol** ==
2261
2262 Supported device: EC55 temperature instrument
2263
2264 **1)HMI Settings**
2265
2266 |**Items**|**Settings**|**Note**
2267 |Protocol|Omron EC55|
2268 |Connection|RS485 (9600, 2, 7, EVEN)|
2269 |Port No.|None|
2270 |PLC station No.|0|
2271
2272 **2)Address List**
2273
2274 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2275 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2276 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2277 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2278 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2279 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2280 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2281 |CP|-|0-6|Read controller intrinsic property
2282 |CS|-|0-2|Read controller states
2283 |CA|-|0-17|Action command
2284
2285 **3)Device Settings**
2286
2287 Omron E5CC PLC configuration
2288
2289 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2290
2291 (% style="text-align:center" %)
2292 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2293
2294 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2295
2296 (% style="text-align:center" %)
2297 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2298
2299 **✎Note:** The communication settings for HMI should be consistent with this setting.
2300
2301 **Cable Wiring**
2302
2303 (% style="text-align:center" %)
2304 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2305
2306 (% style="text-align:center" %)
2307 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2308
2309 **✎Note:**
2310
2311 * COM3 only available in PI8000/PI9000 series.
2312 * CA address could not support continuous writing function;
2313 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2314 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2315 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2316 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2317 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2318 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2319 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2320
2321 == **EtherNet/IP NX series Protocol** ==
2322
2323 Supported series: Omron NX/NJ series
2324
2325 **HMI Setting**
2326
2327 |**Items**|**Settings**|**Note**
2328 |Protocol|Omron NX Ethernet/IP|
2329 |Connection|Ethernet|
2330 |Port No.|44818|
2331 |PLC station No.|1|
2332
2333 **Instruction**
2334
2335 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2336
2337 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2338
2339 (% style="text-align:center" %)
2340 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2341
2342 **Export labels from Sysmac Studio**
2343
2344 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2345
2346 (% style="text-align:center" %)
2347 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2348
2349 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2350
2351 Click [Label manage];
2352
2353 (% style="text-align:center" %)
2354 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2355
2356 Click [Import labels] and then select the file exported in step 1;
2357
2358 (% style="text-align:center" %)
2359 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2360
2361 The Import Status field shows the result, click [OK] to finish importing address labels;
2362
2363 (% style="text-align:center" %)
2364 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2365
2366 **Communication Settings**
2367
2368 Enable HMI Ethernet in [Project Settings];
2369
2370 (% style="text-align:center" %)
2371 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2372
2373 Set PLC IP in [Device IP] settings;
2374
2375 (% style="text-align:center" %)
2376 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2377
2378 (% style="text-align:center" %)
2379 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2380
2381 **Cable Wiring**
2382
2383 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2384
2385 == CV/CJ1M/CS1H ==
2386
2387 **HMI Setting:**
2388
2389 |=**Parameters**|=**Recommended**
2390 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2391 |=**PLC I/F**|RS232
2392 |=**Baud rate**|9600
2393 |=**Data bits**|7
2394 |=**Parity**|Even
2395 |=**Stop bits**|2
2396 |=**PLC sta. no.**|0
2397
2398 **PLC Setting:**
2399
2400 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2401
2402 **Device Address:**
2403
2404 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2405 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2406 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2407 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2408 |=B|H|DDDDdd|0 ~~ 409515|
2409 |=B|A|DDDDdd|0 ~~ 409515|
2410 |=B|TF|DDDDdd|0 ~~ 409515|
2411 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2412 |=B|T|DDDD|0 ~~ 4095|
2413 |=B|C|DDDD|0 ~~ 4095|
2414 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2415 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2416 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2417 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2418 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2419 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2420 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2421 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2422 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2423 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2424 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2425 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2426 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2427 |=B|Lamp|D|0~~0|
2428
2429 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2430 |=W|LR_W|DDDD|0 ~~ 4095|
2431 |=W|TC|DDD|0 ~~ 511|
2432 |=W|DM|DDDD|0 ~~ 9999|Data Register
2433
2434 **Wiring Diagram:**
2435
2436 **RS-232**
2437
2438 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2439
2440 Communication Module:
2441
2442 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2443
2444 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2445
2446 (% style="text-align:center" %)
2447 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2448
2449 = Create communication with **Rockwell PLC** =
2450
2451 == **DF1 Protocol** ==
2452
2453 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2454
2455 **HMI Settings**
2456
2457 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2458 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2459 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2460 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2461 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2462 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2463 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2464 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2465 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2466
2467 **PLC Settings**
2468
2469 DF1 Full Duplex protocol and CRC error check
2470
2471 **Address List**
2472
2473 (% class="table-bordered" %)
2474 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2475 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2476 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2477 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2478 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2479 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2480 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2481 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2482 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2483 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2484 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2485 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2486
2487 **Cable Wiring**
2488
2489 (% style="text-align:center" %)
2490 [[image:AB.gif]]
2491
2492 == **DF1 Advanced Protocol** ==
2493
2494 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2495
2496 **HMI Settings**
2497
2498 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2499 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2500 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2501 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2502 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2503 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2504 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2505 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2506 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2507
2508 **PLC Settings**
2509
2510 DF1 Full Duplex protocol and CRC error check
2511
2512 **Address List**
2513
2514 (% class="table-bordered" %)
2515 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2516 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2517 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2518 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2519 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2520 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2521 Bit data file B0~~B99
2522
2523 First two digits is for file number
2524
2525 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2526 )))
2527 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2528 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2529 Integer data file bit format N0~~N99
2530
2531 First two digits is for file number
2532
2533 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2534 )))
2535 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2536 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2537 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2538 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2539 Timer Preset Value
2540
2541 First two digits is for file number
2542
2543 For example, TNS99255 represents file number T99, address 255.
2544 )))
2545 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2546 Timer Accumulator Value
2547
2548 First two digits is for file number
2549
2550 For example, TNP99255 represents file number T99, address 255.
2551 )))
2552 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2553 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2554 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2555 Counter Preset Value
2556
2557 First two digits is for file number
2558
2559 For example, CNS99255 represents file number C99, address 255.
2560 )))
2561 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2562 Counter Accumulator Value
2563
2564 First two digits is for file number
2565
2566 For example, CNP99255 represents file number C99, address 255.
2567 )))
2568 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2569 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2570 Integer data file
2571
2572 First two digits is for file number
2573
2574 For example, NN99255 represents file number N99, address 255.
2575 )))
2576 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2577 Only able to communicate with file number F8
2578 )))
2579 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2580 Floating point data file
2581
2582 First two digits is for file number
2583
2584 For example, FN99255 represents file number F99, address 255.
2585 )))
2586 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2587
2588 **Cable Wiring**
2589
2590 (% style="text-align:center" %)
2591 [[image:AB.gif]]
2592
2593 == **MicroLogix Protocol** ==
2594
2595 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2596
2597 **HMI Settings**
2598
2599 (% class="table-bordered" %)
2600 |**Item**|**Settings**|**Note**
2601 |Protocol|Allen-Bradlley MicroLogix|
2602 |Connection|RS232|
2603 |Baud rate|19200|
2604 |Data bit|8|
2605 |Parity|None|
2606 |Stop bit|1|
2607 |PLC station No.|1|
2608
2609 **Address List**
2610
2611 (% class="table-bordered" %)
2612 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2613 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2614 |O|O d.d|0.0~~255.15|
2615 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2616 |S|S d.d|0.0~~255.15|
2617 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2618 |(% rowspan="9" %)Word|S|S d|0~~255|
2619 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2620 |TP|TP nnhh|0~~ffff
2621 |CS|CS nnhh|0~~ffff
2622 |CP|CP nnhh|0~~ffff
2623 |N|N nnhh|0~~ffff
2624 |C|C nnhh|0~~ffff
2625 |T|T nnhh|0~~ffff
2626 |R|R nnhh|0~~ffff
2627
2628 **Cable Wiring**
2629
2630 (% style="text-align:center" %)
2631 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2632
2633 == **CompactLogix FreeTag Ethernet protocol** ==
2634
2635 Allen-Brandly CompactLogix
2636
2637 **HMI Settings**
2638
2639 (% class="table-bordered" %)
2640 |**Items**|**Settings**|**Note**
2641 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2642 |Connection|Ethernet|
2643 |Port No.|44818|
2644
2645 **PLC Setting**
2646
2647 Create new tags
2648
2649 (% style="text-align:center" %)
2650 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2651
2652 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2653
2654 (% style="text-align:center" %)
2655 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2656
2657 Import labels, please open [Communication] window and click [Import label];
2658
2659 Select csv file, all tags will be displayed as belows;
2660
2661 (% style="text-align:center" %)
2662 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2663
2664 **✎Note:**
2665
2666 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2667
2668 (% style="text-align:center" %)
2669 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2670
2671 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2672
2673 **Communication settings in HMI**
2674
2675 Enable HMI Ethernet in [Project Settings];
2676
2677 (% style="text-align:center" %)
2678 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2679
2680 Set PLC IP in [Device IP] settings;
2681
2682 (% style="text-align:center" %)
2683 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2684
2685 **Cable Wiring**
2686
2687 (% style="text-align:center" %)
2688 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2689
2690 == **MicroLogix 1200** **protocol** ==
2691
2692 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2693
2694 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2695 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2696 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2697 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2698
2699 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2700
2701 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2702 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2703 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2704 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2705 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2706 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2707 |**PLC word address type**|**Address format**|**Address range**
2708 |S|ddd|S0 ~~ 255
2709 |TS|ffff|TS0 ~~ FFFF
2710 |TP|ffff|TP0 ~~ FFFF
2711 |CS|ffff|CS0 ~~ FFFF
2712 |CP|ffff|CP0 ~~ FFFF
2713 |N|ffff|N0 ~~ FFFF
2714 |F|ffff|F0 ~~ FFFF
2715
2716 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2717
2718 == **S7-200 Smart Ethernet Protocol** ==
2719
2720 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2721
2722 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2723
2724 **HMI Setting**
2725
2726 (% class="table-bordered" %)
2727 |**Items**|**Settings**|**Note**
2728 |Protocol|Simens S7-200 Smart Ethernet|
2729 |Connection|Ethernet|
2730 |Port No.|102|
2731 |PLC station No.|2|
2732
2733 **Address List**
2734
2735 (% class="table-bordered" %)
2736 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2737 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2738 |Q|Q|Q ddddd.o|0.0~~99999.7|
2739 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2740 |V|V|V ddddd.o|0.0~~99999.7|
2741 |M|M|M ddddd.o|0.0~~99999.7|
2742 |SM|SM|ddddd.o|0.0~~99999.7|
2743 |S|S|ddddd.o|0.0~~99999.7|Read only
2744 |T|T|ddddd|0~~99999|Timer state, read only
2745 |C|C|ddddd|0~~99999|Counter state, read only
2746 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2747 |Q|QW|QW ddddd|0~~99999|
2748 |AI|AIW|AIW ddddd|0~~99999|
2749 |AQ|VB|VB ddddd|0~~99999|
2750 |V|VW|VW ddddd|0~~99998|(((
2751 VW0=VB (0~~1)
2752
2753 VW2=VB (2~~3)
2754
2755 Address value is a multiple of 2
2756 )))
2757 |V|VD|VD ddddd|0~~99998|(((
2758 VD0=VB (0~~3)
2759
2760 VD2=VB (4~~7)
2761
2762 Address value is a multiple of 4
2763 )))
2764 |M|MB|MB ddddd|0~~99999|
2765 |M|MW|MW ddddd|0~~99999|(((
2766 MW0=MB(0~~1)
2767
2768 MW2=MB(2~~3)
2769
2770 Address value is a multiple of 2
2771 )))
2772 |M|MD|MD ddddd|0~~99999|(((
2773 MD0=MB(0~~3)
2774
2775 MD4=MB(4~~7)
2776
2777 Address value is a multiple of 4
2778 )))
2779 |T|TW|TW ddddd|0~~99999|Value of timer
2780 |C|CW|CW ddddd|0~~99999|Value of counter
2781 |W|SW|SW ddddd|0~~99999|
2782
2783 **Communication Settings**
2784
2785 Enable HMI Ethernet in [Project Settings];
2786
2787 (% style="text-align:center" %)
2788 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2789
2790 Set PLC IP in [Device IP] settings;
2791
2792 (% style="text-align:center" %)
2793 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2794
2795 * PLC IP Address: PLC IP
2796 * PLC pot No.: 102(fixed)
2797 * Network:TCP_Client_2N(fixed)
2798
2799 (% style="text-align:center" %)
2800 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2801
2802 * Wait timeout: depend on actual network situation (more than 1500 ms)
2803
2804 **Cable Wiring**
2805
2806 (% style="text-align:center" %)
2807 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2808
2809 == **S7-300 Ethernet Protocol** ==
2810
2811 Supported Series: Siemens S7-300 series PLC
2812
2813 **HMI Setting**
2814
2815 (% class="table-bordered" %)
2816 |**Items**|**Settings**|**Note**
2817 |Protocol|Simens S7-300 Ethernet|
2818 |Connection|Ethernet|
2819 |Port No.|102|
2820 |PLC station No.|2|Need to be same as the PLC setting
2821
2822 **Address List**
2823
2824 (% class="table-bordered" %)
2825 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2826 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2827 |Q|Q|Q ddddd.o|0.0~~99999.7|
2828 |M|M|M ddddd.o|0.0~~99999.7|
2829 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2830 nnnn: block number;
2831
2832 dddd: address;
2833 )))
2834 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2835 |Q|QW|QW ddddd|0~~99999|
2836 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2837 |MW|MW ddddd|0~~99999|(((
2838 MW0=MB(0~~1)
2839
2840 MW2=MB(2~~3)
2841
2842 Address value is a multiple of 2
2843 )))
2844 |MD|MD ddddd|0~~99999|(((
2845 MD0=MB(0~~3)
2846
2847 MD4=MB(4~~7)
2848
2849 Address value is a multiple of 4
2850 )))
2851 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2852 nnnn: block number;
2853
2854 dddd: address
2855 )))
2856 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2857 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2858
2859 **Communication Settings**
2860
2861 Enable HMI Ethernet in [Project Settings];
2862
2863 (% style="text-align:center" %)
2864 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2865
2866 Set PLC IP in [Device IP] settings;
2867
2868 (% style="text-align:center" %)
2869 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2870
2871 * PLC IP Address: PLC IP
2872 * PLC pot No.: 102(fixed)
2873 * Network:TCP_Client_2N(fixed)
2874
2875 (% style="text-align:center" %)
2876 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2877
2878 * Wait timeout: depend on actual network situation (more than 1500 ms)
2879
2880 **Cable Wiring**
2881
2882 (% style="text-align:center" %)
2883 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2884
2885 == **S7-1200 Ethernet Protocol** ==
2886
2887 Supported Series: Siemens S7-1200
2888
2889 **HMI Setting**
2890
2891 (% class="table-bordered" %)
2892 |**Items**|**Settings**|**Note**
2893 |Protocol|Siemens S7-1200|
2894 |Connection|Ethernet|
2895 |Port No.|102|
2896 |PLC station No.|2|
2897
2898 **Address List**
2899
2900 (% class="table-bordered" %)
2901 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2902 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2903 d:0~-~-9999
2904
2905 o:0-7
2906 )))|
2907 |Q|Q|Q d.o|(((
2908 d:0~-~-9999
2909
2910 o:0-7
2911 )))|
2912 |M|M|M d.o|(((
2913 d:0~-~-9999
2914
2915 o:0-7
2916 )))|
2917 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2918 nn:0-9999,
2919
2920 dddd:0-9999,
2921
2922 o:0-7
2923 )))|(((
2924 nn:DB No.
2925
2926 dddd:address value
2927
2928 o: digit address
2929 )))
2930 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2931 |M|MW|MW d|d:0-99999|(((
2932 MW0=MB(0~~1)
2933
2934 MW2=MB(2~~3)
2935
2936 Address value is a multiple of 2
2937 )))
2938 |M|MD|MD d|d:0-99999|(((
2939 MD0=MB(0~~3)
2940
2941 MD4=MB(4~~7)
2942
2943 Address value is a multiple of 4
2944 )))
2945 |I|IW|IW d|d:0-99999|
2946 |Q|QW|QW d|d:0-99999|
2947 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2948 nn:0-9999
2949
2950 dddd:0-9999
2951 )))|(((
2952 nn:DB No.
2953
2954 dddd:address value
2955 )))
2956 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2957 nn:0-9999
2958
2959 dddd:0-9999
2960 )))|(((
2961 nn:DB No.
2962
2963 dddd:address value
2964
2965 Address value is a multiple of 2
2966 )))
2967 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2968 nn:0-9999
2969
2970 dddd:0-9999
2971 )))|(((
2972 nn:DB No.
2973
2974 dddd:address value
2975
2976 Address value is a multiple of 4
2977 )))
2978
2979 **Communication Settings**
2980
2981 Enable HMI Ethernet in [Project Settings];
2982
2983 (% style="text-align:center" %)
2984 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2985
2986 Set PLC IP in [Device IP] settings;
2987
2988 (% style="text-align:center" %)
2989 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2990
2991 **✎Note:**
2992
2993 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2994 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2995 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
2996 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
2997
2998 **PLC Settings**
2999
3000 Add BD
3001
3002 * Please uncheck [Symbolic access only] option;
3003
3004 (% style="text-align:center" %)
3005 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3006
3007 Address settings, using BD2 as example.
3008
3009 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3010 * 2 represent DB block number
3011 * xxxx represent address
3012
3013 **Such as:**
3014
3015 * DBxDBB20000 = DB2.DBB0
3016 * DBxDBW20004 = DB2.DBW4
3017
3018 (% style="text-align:center" %)
3019 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3020
3021 **How to connect with S7-1200 Firmware V4.0**
3022
3023 PLC configuration
3024
3025 * Double click [device configuration] in Siemens via software
3026 * Double click [protection] to enter protection configuration screen
3027
3028 (% style="text-align:center" %)
3029 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3030
3031 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3032
3033 (% style="text-align:center" %)
3034 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3035
3036 DB settings
3037
3038 * Right click [DB], select [properties]
3039 * Uncheck [optimized block access]
3040
3041 **Cable Wiring**
3042
3043 (% style="text-align:center" %)
3044 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3045
3046 == **S7-XXX Ethernet Protocol** ==
3047
3048 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3049
3050 **HMI Setting**
3051
3052 (% class="table-bordered" style="width:823px" %)
3053 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3054 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3055 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3056 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3057 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3058 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3059
3060 Slot from TIA Portal is equal to Device No. of PIStudio
3061
3062 Rack from TIA Portal is equal to HMI No. of PIStudio
3063
3064 (% style="text-align:center" %)
3065 [[image:S7-XXXCommunication Settings.png]]
3066
3067 (% style="text-align:center" %)
3068 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3069
3070 **Address List**
3071
3072 (% class="table-bordered" %)
3073 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3074 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3075 d:0~-~-9999
3076
3077 o:0-7
3078 )))|
3079 |Q|Q|Q d.o|(((
3080 d:0~-~-9999
3081
3082 o:0-7
3083 )))|
3084 |M|M|M d.o|(((
3085 d:0~-~-9999
3086
3087 o:0-7
3088 )))|
3089 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3090 nn:0-9999,
3091
3092 dddd:0-9999,
3093
3094 o:0-7
3095 )))|(((
3096 nn:DB No.
3097
3098 dddd:address value
3099
3100 o: digit address
3101 )))
3102 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3103 |M|MW|MW d|d:0-99999|(((
3104 MW0=MB(0~~1)
3105
3106 MW2=MB(2~~3)
3107
3108 Address value is a multiple of 2
3109 )))
3110 |M|MD|MD d|d:0-99999|(((
3111 MD0=MB(0~~3)
3112
3113 MD4=MB(4~~7)
3114
3115 Address value is a multiple of 4
3116 )))
3117 |I|IW|IW d|d:0-99999|
3118 |Q|QW|QW d|d:0-99999|
3119 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3120 nn:0-9999
3121
3122 dddd:0-9999
3123 )))|(((
3124 nn:DB No.
3125
3126 dddd:address value
3127 )))
3128 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3129 nn:0-9999
3130
3131 dddd:0-9999
3132 )))|(((
3133 nn:DB No.
3134
3135 dddd:address value
3136
3137 Address value is a multiple of 2
3138 )))
3139 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3140 nn:0-9999
3141
3142 dddd:0-9999
3143 )))|(((
3144 nn:DB No.
3145
3146 dddd:address value
3147
3148 Address value is a multiple of 4
3149 )))
3150
3151 **Communication Settings**
3152
3153 Enable HMI Ethernet in [Project Settings];
3154
3155 (% style="text-align:center" %)
3156 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3157
3158 Set PLC IP in [Device IP] settings;
3159
3160 (% style="text-align:center" %)
3161 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3162
3163 **✎Note:**
3164
3165 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3166 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3167
3168 **Cable Wiring**
3169
3170 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3171
3172 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3173
3174 Supported Series: Siemens Logo 0BA0, 0BA1 series
3175
3176 **HMI Settings**
3177
3178 (% class="table-bordered" %)
3179 |**Items**|**Settings**|**Note**
3180 |Protocol|Siemens LOGO|
3181 |Connection|Ethernet|
3182 |Port No.|102|
3183 |PLC station No.|2|
3184
3185 **Address List**
3186
3187 (% class="table-bordered" %)
3188 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3189 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3190 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3191 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3192 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3193 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3194 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3195 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3196 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3197 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3198 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3199 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3200 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3201 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3202 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3203 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3204
3205 **PLC Settings in LOGO Software:**
3206
3207 Click [Tools]~-~-[Ethernet Connections],shown as below.
3208
3209 (% style="text-align:center" %)
3210 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3211
3212 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3213
3214 (% style="text-align:center" %)
3215 [[image:image-20221228142937-4.png]]
3216
3217 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3218
3219 (% style="text-align:center" %)
3220 [[image:image-20221228143047-5.png]]
3221
3222 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3223
3224 (% style="text-align:center" %)
3225 [[image:image-20221228143246-6.png]]
3226
3227
3228 **HMI Communication Settings**
3229
3230 Set PLC IP in [Device IP] settings;
3231
3232 (% style="text-align:center" %)
3233 [[image:image-20221228143614-7.png]]
3234
3235 Enable HMI Ethernet in [Project Settings];
3236
3237 (% style="text-align:center" %)
3238 [[image:image-20221228144229-9.png]]
3239
3240 TSAP setting
3241
3242 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3243 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3244 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3245 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3246 ie, ig series: use HSW1200, HSW1201.
3247 HMI V2.0: use HSW1200, HSW1201.
3248
3249 **✎Note:**
3250
3251 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3252 * HSW10119/HSW1201 is set up as shown.
3253 * (((
3254 (% style="text-align:center" %)
3255 [[image:image-20221228144800-11.png]]
3256 )))
3257 * (((
3258 (% style="text-align:center" %)
3259 [[image:image-20221228144708-10.png]]
3260 )))
3261
3262 * AI word address and Ibit address are read-only and cannot be written on HMI.
3263 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3264 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3265 * Written value of RTC cannot exceed 255.
3266
3267 **Cable Wiring**
3268
3269 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3270
3271 == S7-300 232 ==
3272
3273 **HMI Setting:**
3274
3275 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3276 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3277 |=**PLC I/F**|RS232| |
3278 |=**Baud rate**|19200|9600,19200|
3279 |=**Data bits**|8| |
3280 |=**Parity**|Odd| |
3281 |=**Stop bits**|1| |
3282 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3283
3284 **Device Address**
3285
3286 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3287 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3288 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3289 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3290 |=Word|(((
3291 DB1 to DB99
3292 )))|DDDDDo|0 ~~ 655327|
3293 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3294 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3295 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3296 |=Double word|MD|DDDD|0 ~~ 4094|
3297 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3298 Data Register Double Word (must be even)
3299 )))
3300 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3301
3302 **Cable Wiring**
3303
3304 (% style="text-align:center" %)
3305 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3306
3307 = Create communication with Xinje** PLC** =
3308
3309 == XC serial protocol ==
3310
3311 **HMI Settings**
3312
3313 |**Item**|**Settings**|**Note**
3314 |Protocol|XINJE XC MODBUS|
3315 |Connection|RS232|
3316 |Baud rate|19200|
3317 |Data bit|8|
3318 |Parity|EVEN|
3319 |Stop bit|1|
3320 |PLC station No.|1|
3321
3322 **Address List**
3323
3324 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3325 |Bit|M|M|M d|0~~8511|
3326 |Bit|X|X|X o|0~~1747|
3327 |Bit|Y|Y|Y o|0~~1747|
3328 |Bit|S|S|S d|0~~1023|
3329 |Bit|T|T|T d|0~~4095|
3330 |Bit|C|C|C d|0~~634|
3331 |Word|D|D|D d|0~~8511|
3332 |Word|TD|TD|TD d|0~~618|
3333 |Word|CD|CD|CD d|0~~634|
3334 |Word|FD|FD|FD d|0~~8511|
3335
3336 **Configure the communication protocol**
3337
3338 (% style="text-align:center" %)
3339 [[image:image-20220830154105-1.png]]
3340
3341 (% style="text-align:center" %)
3342 [[image:image-20220830154159-3.png]]
3343
3344 **Cable Wiring**
3345
3346 Figure
3347
3348 [[image:image-20220830155728-4.png]]
3349
3350 Pin Definition Diagram
3351
3352 (% style="text-align:center" %)
3353 [[image:image-20220830154131-2.png]]
3354
3355 == XD serial protocol ==
3356
3357 **HMI Settings**
3358
3359 Supported Series: Xinjie XD/XE Series PLC
3360
3361 |=**Item**|=**Settings**|=**Note**
3362 |Protocol|XINJE XD/XC MODBUS|
3363 |Connection|RS232|
3364 |Baud rate|19200|
3365 |Data bit|8|
3366 |Parity|EVEN|
3367 |Stop bit|1|
3368 |PLC station No.|1|
3369
3370 **Address List**
3371
3372 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3373 |Bit|M|M|M d|0~~74999|
3374 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3375 |Bit|X2xx|X2xx|X2xx o|0~~277|
3376 |Bit|X|X|X o|0~~77|
3377 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3378 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3379 |Bit|Y|Y|Y o|0~~4095|
3380 |Bit|SM|SM|SM d|0~~4999|(((
3381
3382 )))
3383 |Bit|T|T|T d|0~~4999|
3384 |Bit|C|C|C d|0~~4999|
3385 |Bit|ET|ET|ET d|0~~31|
3386 |Bit|SE|SE|SE d|0~~31|
3387 |Bit|HM|HM|HM d|0~~11999|
3388 |Bit|HSC|HSC|HSC d|0~~39|
3389 |Bit|HS|HS|HS d|0~~999|
3390 |Bit|HT|HT|HT d|0~~1999|
3391 |Bit|HC|HC|HC d|0~~1999|
3392 |Bit|S|S|S d|0~~7999|
3393 |Word|D|D|D d|0~~69999|
3394 |Word|ID|ID|ID d|0~~99|
3395 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3396 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3397 |Word|QD|QD|QD d|0~~99|
3398 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3399 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3400 |Word|SD|SD|SD d|0~~4999|
3401 |Word|TD|TD|TD d|0~~575|
3402 |Word|CD|CD|CD d|0~~575|
3403 |Word|ETD|ETD|ETD d|0~~31|
3404 |Word|HD|HD|HD d|0~~24999|
3405 |Word|HSD|HSD|HSD d|0~~1023|
3406 |Word|HTD|HTD|HTD d|0~~95|
3407 |Word|HCD|HCD|HCD d|0~~95|
3408 |Word|HSCD|HSCD|HSCD d|0~~31|
3409 |Word|FD|FD|FD d|0~~8191|
3410 |Word|SFD|SFD|SFD d|0~~5999|
3411 |Word|FS|FS|FS d|0~~47|
3412
3413 **Configure the communication protocol**
3414
3415 (% style="text-align:center" %)
3416 [[image:image-20220830160042-1.png]]
3417
3418 (% style="text-align:center" %)
3419 [[image:image-20220830160129-2.png]]
3420
3421 **Cable Wiring**
3422
3423 (% style="text-align:center" %)
3424 [[image:image-20220905093902-1.png]]
3425
3426 Pin Definition Diagram
3427
3428 (% style="text-align:center" %)
3429 [[image:image-20220830160232-3.png]]
3430
3431 = Create communication with Panasonic** PLC** =
3432
3433 == **FP serial protocol** ==
3434
3435 **1)HMI Settings**
3436
3437 |**Item**|**Settings**|**Note**
3438 |Protocol|Panasonic FP MFWTOCOL|
3439 |Connection|RS232|
3440 |Baud rate|9600|
3441 |Data bit|8|
3442 |Parity|ODD|
3443 |Stop bit|1|
3444 |PLC station No.|1|
3445
3446 **2)Address List**
3447
3448 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3449 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3450 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3451 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3452 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3453 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3454 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3455 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3456 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3457 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3458 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3459 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3460 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3461 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3462 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3463 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3464
3465 **3)Configure the communication protocol**
3466
3467 [[image:image-20220830171050-1.png]]
3468
3469 [[image:image-20220830171126-2.png]]
3470
3471 **4)Cable Wiring**
3472
3473 Figure
3474
3475 [[image:image-20220830171328-4.png]]
3476
3477 Pin Definition Diagram
3478
3479 [[image:image-20220830171146-3.png]]
3480
3481 = Create communication with **SHIMADEN PLC** =
3482
3483 == **FP23 series protocol** ==
3484
3485 Supported series: SHIMADEN FP23 series
3486
3487 **HMI Setting**
3488
3489 |**Items**|**Settings**|**Note**
3490 |Protocol|SHIMADEN FP23 series|
3491 |Connection|RS485 (9600, 1, 7, EVEN)|
3492 |Port No.|None|
3493 |PLC station No.|0|
3494
3495 **Address List**
3496
3497 |**Device address**|**HMI register**|**Address range**|**Type**
3498 |0040-0043(HEX)|FP040|100064-200067|Read only
3499 |0100-010B(HEX)|FP100|100256-200267|Read only
3500 |0110-0142(HEX)|FP110|100272-200322|Read only
3501 |0182-0252(HEX)|FP182|100386-200594|Write only
3502 |0280-0281(HEX)|FP280|100640-200641|Read only
3503 |0300-030B(HEX)|FP300|100768-200779|Read and write
3504 |0380-039F(HEX)|FP380|100896-200927|Read and write
3505 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3506 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3507 |0600-0670(HEX)|FP600|101536-201814|Read and write
3508 |0720-0738(HEX)|FP720|101824-201848|Read and write
3509 |0800-083F(HEX)|FP800|102048-202111|Read and write
3510 |0900-0952(HEX)|FP900|102304-202386|Read and write
3511 | |Ctrl|0-2|
3512
3513 **✎Note:**
3514
3515 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3516 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3517 * The Ctrl register is used to store the control group number and BCC check mode.
3518
3519 **Ctrl Register Description**
3520
3521 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3522 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3523 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3524 * Ctrl3 reserved
3525
3526 **✎Note:**
3527
3528 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3529
3530 **Cable Wiring**
3531
3532 (% style="text-align:center" %)
3533 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3534
3535 (% style="text-align:center" %)
3536 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3537
3538 **✎Note:** COM3 only available in PI8000/PI9000 series.
3539
3540 == **SR90 protocol** ==
3541
3542 Supported series: SHIMADEN SR90 series
3543
3544 **HMI Setting**
3545
3546 |**Items**|**Settings**|**Note**
3547 |Protocol|SHIMADEN SR90 protocol|
3548 |Connection|RS485 (1200, 1, 7, EVEN)|
3549 |Port No.|None|
3550 |PLC station No.|0|
3551
3552 **Address List**
3553
3554 |**Device address**|**HMI register**|**Address range**|**Type**
3555 |0040-0043 (HEX)|SR040|100064-100067|Read only
3556 |0100-010A(HEX)|SR0100|100256-100266|Read only
3557 |0182-018C(HEX)|SR0182|100386-100396|Write only
3558 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3559 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3560 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3561 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3562 | |Ctrl|0-2|~-~-
3563
3564 **✎Note:**
3565
3566 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3567 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3568 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3569
3570 **Ctrl Register Description**
3571
3572 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3573 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3574 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3575 * Ctrl3 reserved
3576
3577 **✎Note:**
3578
3579 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3580
3581 **Cable Wiring**
3582
3583 (% style="text-align:center" %)
3584 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3585
3586 (% style="text-align:center" %)
3587 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3588
3589 **✎Note:** COM3 only available in PI8000/PI9000 series.
3590
3591 == **MR13 series(standard protocol)** ==
3592
3593 Supported series: SHIMADEN MR13 series
3594
3595 **HMI Setting**
3596
3597 |**Items**|**Settings**|**Note**
3598 |Protocol|SHIMADEN standard protocol|
3599 |Connection|RS485 (1200, 1, 7, EVEN)|
3600 |Port No.|None|
3601 |PLC station No.|0|
3602
3603 **Address List**
3604
3605 |**Device address**|**HMI register**|**Address range**|**Type**
3606 |0100-010B(HEX)|MR100|100256-300267|Read only
3607 |0111-0126(HEX)|MR111|100273-300294|Read only
3608 |0184-0192(HEX)|MR184|100388-300402|Write only
3609 |0280-0282(HEX)|MR280|100640-300642|Read only
3610 |0300-030B(HEX)|MR300|100768-300779|Read/write
3611 |0314-0317(HEX)|MR314|100788-300791|Read/write
3612 |031A(HEX)|MR31A|100794-300794|Read/write
3613 |0320-0321(HEX)|MR320|100800-300801|Read/write
3614 |0400-0504(HEX)|MR400|101024-301284|Read/write
3615 |0506(HEX)|MR506|101286-301286|Read/write
3616 |0510-0514(HEX)|MR510|101296-301300|Read/write
3617 |0516-0524(HEX)|MR516|101302-301316|Read/write
3618 |0526(HEX)|MR526|101318-301318|Read/write
3619 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3620 |~-~-|Ctrl|0-2|~-~-
3621
3622 **✎Note:**
3623
3624 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3625 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3626 * The Ctrl register is used to store the control group number and BCC check mode.
3627
3628 **Ctrl Register Description**
3629
3630 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3631 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3632 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3633 * Ctrl3 reserved
3634
3635 **✎Note:**
3636
3637 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3638
3639 **Cable Wiring**
3640
3641 (% style="text-align:center" %)
3642 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3643
3644 (% style="text-align:center" %)
3645 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3646
3647 **✎Note:** COM3 only available in PI8000/PI9000 series.
3648
3649 = **Printer** =
3650
3651 == **TSPL label printer** ==
3652
3653 **Introduction**
3654
3655 TSPL label printer protocol supports following models.
3656
3657 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3658 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3659
3660 **Setting Step**
3661
3662 Select the protocol
3663
3664 * Create a new project, select the TSPL label printer protocol as shown below.
3665
3666 (% style="text-align:center" %)
3667 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3668
3669 Set parameters
3670
3671 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3672
3673 Printer register
3674
3675 (% class="table-bordered" %)
3676 |**Register**|**System**|**Range**|**Function**
3677 |TSPL_SP|decimal|0 - 1|Set the paper size
3678 |TSPL_PT|decimal|0 - 1999|Print text
3679 |TSPL_PQ|decimal|0 - 999|Print QR code
3680 |TSPL_PB|decimal|0 - 999|Print barcode
3681 |TSPL_PR|decimal|0 - 1|Print offset
3682 |TSPL_PN|decimal|0 - 0|Trigger printing
3683 |TSPL_PS|decimal|0 - 0|Print status
3684
3685 * Set paper size:
3686 ** TSPL_SP0: width of paper, unit: mm.
3687 ** TSPL_SP1: height of paper, unit: mm.
3688 * Print text:
3689 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3690 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3691
3692 (% class="table-bordered" %)
3693 |**Register**|**Function**|**Description**
3694 |TSPL_PT0|X coordinate|Unit: dot
3695 |TSPL_PT1|Ycoordinate|Unit: dot
3696 |TSPL_PT2|Rotation angle|(((
3697 0: 0 degrees
3698
3699 1: 90 degrees
3700
3701 2: 180 degrees
3702
3703 3: 270 degrees
3704 )))
3705 |TSPL_PT3|Size|Range: 0-3
3706 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3707
3708 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3709
3710 Print QR code:
3711
3712 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3713 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3714
3715 (% class="table-bordered" %)
3716 |**Register**|**Function**|**Description**
3717 |TSPL_PQ0|X coordinate|Unit: dot
3718 |TSPL_PQ1|Ycoordinate|Unit: dot
3719 |TSPL_PQ2|Rotation angle|(((
3720 0: 0 degrees
3721
3722 1: 90 degrees
3723
3724 2: 180 degrees
3725
3726 3: 270 degrees
3727 )))
3728 |TSPL_PQ3|Size|Range: 0-5
3729 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3730
3731 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3732
3733 Print bar code:
3734
3735 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3736 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3737
3738 (% class="table-bordered" %)
3739 |**Register**|**Function**|**Description**
3740 |TSPL_PB0|X coordinate|Unit: dot
3741 |TSPL_PB1|Ycoordinate|Unit: dot
3742 |TSPL_PB2|Rotation angle|(((
3743 0: 0 degrees
3744
3745 1: 90 degrees
3746
3747 2: 180 degrees
3748
3749 3: 270 degrees
3750 )))
3751 |TSPL_PB3|height|Unit: dot
3752 |TSPL_PB4|width|Range:0-2
3753 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3754
3755 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3756
3757 Print offset:
3758
3759 * TSPL_PR0: X coordinate offset, unit: mm;
3760 * TSPL_PR1: Y coordinate offset, unit: mm.
3761
3762 Trigger printing:
3763
3764 * TSPL_PN0 = 1: trigger the printer to start printing.
3765
3766 Printing status:
3767
3768 * TSPL_PS0 = 1: The printing is normal.
3769 * TSPL_PS0 = 1: The printing is abnormal.
3770
3771 Print picture
3772
3773 * For the function of printing pictures, please refer to the configuration of [Printer object].
3774
3775 Conversion between dot and mm
3776
3777 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3778
3779 == **EpsonTM series** ==
3780
3781 **HMI Settings**
3782
3783 (% class="table-bordered" %)
3784 |**Item**|**Settings**|**Note**
3785 |Protocol|EPSON-TM-T82II/TM-XXX|
3786 |Connection|RS232|
3787 |Baud rate|9600~~115200|
3788 |Data bit|8|
3789 |Parity|None|
3790 |Stop bit|1|
3791 |PLC station No.|1|
3792
3793 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3794
3795 **Printer Settings**
3796
3797 (% class="table-bordered" %)
3798 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3799 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3800 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3801 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3802 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3803 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3804 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3805
3806 **Cable Wiring**
3807
3808 (% style="text-align:center" %)
3809 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3810
3811 (% style="text-align:center" %)
3812 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3813
3814 **✎Note:** COM3 only available in PI8000/PI9000 series.
3815
3816
3817 = Create communication with **Schneider PLC** =
3818
3819 == **Schneider MODBUS RTU** ==
3820
3821 **HMI Setting**
3822
3823 |=**Parameters**|=**Recommended**|=**Notes**
3824 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3825 |Connection|RS485|
3826 |**Baud rate**|19200|
3827 |**Data bit**|8|
3828 |**Parity**|Even|
3829 |**Stop bit**|1|
3830 |**PLC station No.**|1|
3831
3832 **PLC Setting**
3833
3834 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3835
3836 **Device Address**
3837
3838 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3839 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3840 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3841 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3842 |W|MW|DDDDDD|0 ~~ 999999|Output register
3843 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3844
3845 **Wiring Diagram**
3846
3847 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3848
3849 (% style="text-align:center" %)
3850 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3851
3852 = **Barcode Scanner** =
3853
3854 Supported: DELI 14880 barcode scanner
3855
3856 **HMI Setting**
3857
3858 |**Items**|**Settings**|**Note**
3859 |Protocol|Barcode Scanner|
3860 |Connection|USB|
3861
3862 **Operating Procedures**
3863
3864 Select [Barcode Scanner];
3865
3866 (% style="text-align:center" %)
3867 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3868
3869 Set address for receiving;
3870
3871 Set correct length;
3872
3873 (% style="text-align:center" %)
3874 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3875
3876 **✎Note:**
3877
3878 * The protocol uploads the information acquired by the USB scanner to the HMI;
3879 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3880 * Recommended model: DELI 14880 barcode scanner;
3881
3882 = **Hitachi EHV Series (Ethernet)** =
3883
3884 Supported series: Hitachi EHV series
3885
3886 **HMI Settings**
3887
3888 (% class="table-bordered" %)
3889 |**Items**|**Settings**|**Note**
3890 |Protocol|Hitachi EHV series|
3891 |Connection|Ethernet|
3892 |Port No.|3004~~3007|
3893
3894 **Address List**
3895
3896 (% class="table-bordered" %)
3897 |**Type**|**Register**|**Range**|**Format**|**Note**
3898 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3899 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3900 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3901 H1H2H3H4 Module main number
3902
3903 H1: Remote number
3904
3905 H2: Unit number
3906
3907 H3: Slot number
3908
3909 H4: Word number of Module
3910
3911 H Sub number of Module
3912
3913 For example:X21.3
3914
3915 Slot number 2
3916
3917 Word number of module is 1
3918
3919 Bit number of module is 3
3920
3921 Remote number and unit number are 0
3922 )))
3923 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3924 |R|0 – FF.f (Hex)|R HH.h|
3925 |L|0 - 73FF.f (Hex)|L HHHH.h|
3926 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3927 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3928 H1H2H3H4 Module main number
3929
3930 H1: Remote number
3931
3932 H2: Unit number
3933
3934 H3: Slot number
3935
3936 H4: Word number of module
3937
3938 For example:WX21
3939
3940 Word number of module is 1
3941
3942 Slot number is 2
3943
3944 Remote number and unit number are 0
3945 )))
3946 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3947 |WR|0 – FFFF (Hex)|WR HHHH|
3948 |WL|0 - 73FF (Hex)|WL HHHH|
3949 |TC|0 - 2559|TC DDDD|
3950
3951 **Communication settings in HMI**
3952
3953 Enable HMI Ethernet in [Project Settings];
3954
3955 (% style="text-align:center" %)
3956 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3957
3958 Set PLC IP in [Device IP] settings;
3959
3960 (% style="text-align:center" %)
3961 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3962
3963 **PLC Configuration**
3964
3965 Connect with PLC, select[Online mode];
3966
3967 (% style="text-align:center" %)
3968 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3969
3970 Set IP address, it is the same LAN parameters with HMI;
3971
3972 (% style="text-align:center" %)
3973 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3974
3975 3) Save PLC communication parameter, and restart PLC
3976
3977 **PLC Monitor Mode**
3978
3979 Connect with PLC and choose to “online” mode
3980
3981 (% style="text-align:center" %)
3982 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3983
3984 Open I/O monitor sheet1
3985
3986 (% style="text-align:center" %)
3987 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3988
3989 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3990
3991 (% style="text-align:center" %)
3992 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3993
3994 Enter the register address, click OK to view the value of the register.
3995
3996 (% style="text-align:center" %)
3997 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3998
3999 (% style="text-align:center" %)
4000 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4001
4002 **✎Note:**
4003
4004 * Both word registers and bit registers support even continuous read/write functions;
4005 * The range of registers is based on the specific PLC type;
4006
4007 **Cable Wiring**
4008
4009 (% style="text-align:center" %)
4010 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4011
4012 = **IEC60870-5 104 Client** =
4013
4014 **HMI Setting**
4015
4016 (% class="table-bordered" %)
4017 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4018 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4019 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4020 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4021
4022 **Address List**
4023
4024 (% class="table-bordered" %)
4025 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4026 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4027 |(% style="width:461px" %)SCNA|0~~16777215.7
4028 |(% style="width:461px" %)DPTB|0~~16777215.7
4029 |(% style="width:461px" %)DCNA|0~~16777215.7
4030 |(% style="width:461px" %)METF|0~~16777215.7
4031 |(% style="width:461px" %)SENC|0~~16777215.7
4032 |(% style="width:461px" %)SENA|0~~16777215.7
4033 |(% style="width:461px" %)MENA|0~~16777215.7
4034 |(% style="width:461px" %)METD|0~~16777215.7
4035 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4036 |(% style="width:461px" %)SCNA|0~~16777215
4037 |(% style="width:461px" %)DPTB|0~~16777215
4038 |(% style="width:461px" %)DCNA|0~~16777215
4039 |(% style="width:461px" %)SENA|0~~16777215
4040 |(% style="width:461px" %)MENA|0~~16777215
4041 |(% style="width:461px" %)METD|0~~16777215
4042 |(% style="width:461px" %)INRO|0~~16777215
4043 |(% style="width:461px" %)TIMESYN|0~~16777215
4044 |(% style="width:461px" %)TIMEZ|0~~16777215
4045 |(% style="width:461px" %)NTP|0~~16777215
4046 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4047 |(% style="width:461px" %)SENC|0~~16777215
4048
4049 **Address Configuration**
4050
4051 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4052
4053 (% style="text-align:center" %)
4054 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4055
4056 (% style="text-align:center" %)
4057 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4058
4059 Extended tag name
4060
4061 Address range for the extended tag.
4062
4063 **Communication Settings**
4064
4065 Enable HMI Ethernet in [Project Settings];
4066
4067 (% style="text-align:center" %)
4068 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4069
4070 Set PLC IP in [Device IP] settings;
4071
4072 (% style="text-align:center" %)
4073 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4074
4075 **Cable Wiring**
4076
4077 (% style="text-align:center" %)
4078 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4079
4080 = **OpenCAN** =
4081
4082 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4083
4084 This protocol is only available in PI8000 series HMI.
4085
4086 **HMI Settings**
4087
4088 |**Items**|**Settings**|**Note**
4089 |Protocol|OPENCAN|
4090 |Connection|CAN port|
4091 |Baud rate|250000|
4092
4093 **CAN frame setting in HMI**
4094
4095 Click [OpenCAN setting] button in communication setting window;
4096
4097 (% style="text-align:center" %)
4098 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4099
4100 Click [Add] to create a new frame;
4101
4102 (% style="text-align:center" %)
4103 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4104
4105 |**No**|**Items**|**Description**
4106 |1|Add|add a frame related to register address
4107 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4108 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4109 |4|Modify|Modify the frames in frame management
4110 |5|Copy|Copy one frame to another
4111 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4112 |7|Empty|All frames in the list are cleared
4113 |8|Browse|Displays configuration files in XML format in IE
4114 |9|OK|Complete the configuration of the frame and exit
4115
4116 Set CANBUS frame in setting windows
4117
4118 (% style="text-align:center" %)
4119 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4120
4121 |**No**|**Items**|**Description**
4122 |1|ID|Set the ID of a can frame in hexadecimal format;
4123 |2|ID assign|split the ID by PF, PS, and SA;
4124 |3|Frame type|Select Standard frame or Extended Frame;
4125 |4|Frame format|Select between data frame and remote Frame;
4126 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4127 |6|Use address|(((
4128 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4129
4130 **Edit:** Set a bit or word address by its format;
4131
4132 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4133 )))
4134 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4135 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4136 |Feedback mode: feedback mode includes no response, confirm response and data response;
4137 |No response: the device or touch screen will not receive feedback;
4138 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4139 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4140 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4141 |Response timeout: sets whether the response frame timeout;
4142 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4143 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4144 |Manually send: a manually send tick indicates only one send;
4145 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4146 |10|Note|Fill the text to explain the meaning of the frame;
4147 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4148 |12|Current operation display|Display the description of current operation;
4149 |13|Add|Add a new frame;
4150 |14|Save frame|Save the configured frame format;
4151 |15|Cancel|Cancel the frame configuration;
4152
4153 Set CAN address (Read or write operation);
4154
4155 (% style="text-align:center" %)
4156 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4157
4158 |**No.**|**Item**|**Description**
4159 |1|Current address|Displays the register type and register address set by the user in the data access interface
4160 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4161 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4162 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4163 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4164 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4165 |If the trigger condition is a writing operation, there are two situations:(((
4166 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4167 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4168 )))
4169 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4170 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4171 |4|Add|Add current configuration
4172 |5|Close|Close the configuration window to exit
4173
4174 **Multiple Packages Settings**
4175
4176 (% style="text-align:center" %)
4177 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4178
4179 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4180
4181 Select Multiple package type
4182
4183 * Not Multiple packages
4184 * J1939 Multiple packages
4185 * Customized Multiple packages
4186
4187 Click [Edit Receive data] for [Receive] settings
4188
4189 * Start code+ Total length (J1939)
4190
4191 (% style="text-align:center" %)
4192 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4193
4194 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4195
4196 * Start code + Data max length (J1939)
4197
4198 (% style="text-align:center" %)
4199 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4200
4201 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4202
4203 * Data max length (J1939)
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4207
4208 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4209
4210 * Customized multiple package
4211
4212 (% style="text-align:center" %)
4213 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4214
4215 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4216
4217 Click [Edit Send data] for [Send] setting
4218
4219 * J1939
4220
4221 (% style="text-align:center" %)
4222 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4223
4224 [Data] is all data to be sent.
4225
4226 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4227
4228 * Customized multiple package
4229
4230 (% style="text-align:center" %)
4231 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4232
4233 [Data] is all data to be sent.
4234
4235 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4236
4237 **Cable Wiring**
4238
4239 (% style="text-align:center" %)
4240 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4241
4242 **✎Note:** The address interval between each frame need to be more than a word address;
4243
4244
4245 = **User Defined Protocol** =
4246
4247 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4248
4249 **HMI Settings**
4250
4251 |**Items**|**Settings**|**Note**
4252 |Protocol|User defined protocol|
4253 |Connection|RS485/RS232|
4254 |Baud rate|2400~~187500|
4255 |Stop bits|1/ 2|
4256 |Data bits|7/ 8|
4257 |Parity|None/ Even/ ODD|
4258
4259 **Operating Procedures**
4260
4261 Select [User defined protocol];
4262
4263 Click [User defined protocol] button to open setting window as below;
4264
4265 (% style="text-align:center" %)
4266 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4267
4268 Configure user defined command;
4269
4270 (% style="text-align:center" %)
4271 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4272
4273 |**No**|**Item**|**Description**
4274 |1|Instruction edit|The required command.
4275 |2|Mode|Write to address or read from the address.
4276 |3|Format|Encode format: HEX or ASCII.
4277 |4|Other|(((
4278 **No receiving: **HMI does not respond to the receiving command.
4279
4280 **Send after receiving:** HMI responds to the receiving command.
4281 )))
4282 |5|Manually send|(((
4283 Respond once after trigger the address.
4284
4285 Address: set the trigger address.
4286 )))
4287 |6|Add|Save this setting.
4288 |7|Cancel|Cancel current settings.
4289 |(% rowspan="4" %)8|Add|Add a new command.
4290 |Edit|Edit the selected command.
4291 |Delete|Delete the selected command.
4292 |Clear|Clear all the commands.
4293 |9|Instruction list|Display all current commands.
4294 |10|Address List|Display all the addresses added.
4295 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4296 |Export|Export current command settings to local storage.
4297 |Browse|Browse local command files.
4298 |Advanced|Combine two commands.
4299 |Exit|Complete editing and exit setting.
4300
4301 **Operating Procedures**
4302
4303 Click [Add] to create a new command, as below shows;
4304
4305 (% style="text-align:center" %)
4306 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4307
4308 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4309
4310 (% style="text-align:center" %)
4311 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4312
4313 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4314
4315 (% style="text-align:center" %)
4316 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4317
4318 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4319
4320 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4321
4322 Check settings;
4323
4324 (% style="text-align:center" %)
4325 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4326
4327 |**No**|**Items**|**Description**
4328 |1|Add checking|Add checking command when receiving the data.
4329 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4330 |Differ with send check|Set return checking.
4331 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4332 |Length: The data length need to be checked.
4333
4334 Object settings;
4335
4336 (% style="text-align:center" %)
4337 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4338
4339 |**No**|**Items**|**Description**
4340 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4341 |Address: the triggering address;
4342 |Note: description to object;
4343 |2|Byte order|The numerical display order;
4344
4345 Data length settings;
4346
4347 (% style="text-align:center" %)
4348 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4349
4350 |**No**|**Item**|**Description**
4351 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4352 |Length: the return data length.
4353 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4354 |Length: the write data length.
4355
4356 Instruction length settings
4357
4358 (% style="text-align:center" %)
4359 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4360
4361 |**No**|**Item**|**Description**
4362 |1|Send length|The instruction data will only send designated data length.
4363 |2|Return length|The responds data length.
4364 |3|End code|Instruction will not be terminated until receiving [End code];
4365
4366 **Cable Wiring**
4367
4368 * **RS485**
4369
4370 (% style="text-align:center" %)
4371 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4372
4373 (% style="text-align:center" %)
4374 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4375
4376 * **RS232**
4377
4378 (% style="text-align:center" %)
4379 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4380
4381 **✎Note:** COM3 only available in PI8000/PI9000 series.