Wiki source code of 11 PLC Protocol

Version 287.1 by Leo Wei on 2023/08/08 10:18

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation of the Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON PLC =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 **✎Note:**
159
160 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
161 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
162
163 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
164
165 (% class="wikigeneratedid" id="HHMIsettings" %)
166 **HMI settings**
167
168 **Download PIStudio Software**
169
170 Please visit the link below to get the latest version PIstudio for HMI programming:
171
172 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
173
174 **Create a new HMI project connect with PLC**
175
176 Check the link below for the video to show you how to get started with a new project
177
178 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
179
180 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
181
182 **General**
183
184 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
185
186 **Protocol settings**
187
188 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
189
190 Please select the protocol, when creating a new project.
191
192 1. Select the COM port for communication;
193 1. PLC type: It means PLC brand, like WECON;
194 1. PLC model: It shows the model of PLC, such as LX3V;
195
196 (% style="text-align:center" %)
197 [[image:image-20220819093729-1.png]]
198
199 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
200
201 (% style="text-align:center" %)
202 [[image:image-20220819093729-2.png]]
203
204
205 The steps to change the protocol for project are as follows.
206
207 1. Click [Setting] to open the [Communication device] window;
208 1. Select communication port, such as COM1;
209 1. Select Serial port for communication, such as RS422;
210 1. Select device type (device brand), such as WECON;
211 1. Select the protocol for communication, such as WECON LX3V;
212
213 (% style="text-align:center" %)
214 [[image:image-20220819093729-3.png]]
215
216 **Parameter settings**
217
218 The parameters settings are in [Communication] window, shown as following below.
219
220 1. Click [Setting] to open the [COM port setting] window;
221 1. Set the parameters such as [connection], [Baud rate] and so on;
222
223 (% style="text-align:center" %)
224 [[image:image-20220819093729-4.png||height="636" width="818"]]
225
226 (% start="3" %)
227 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
228
229 (% style="text-align:center" %)
230 [[image:image-20220819093729-5.png]]
231
232 **Set PLC address in HMI screen**
233
234 1. Place the objects to HMI screen;
235 1. Double-click the object to open the setting window;
236 1. Click “Edit” to open the address setting windows;
237 1. Connection: select the serial port in HMI;
238 1. Address type: All the PLC address types will be display in this list, such as M;
239 1. Address No.: Please input the number of this address, such as 0;
240
241 [[image:image-20220819093729-6.jpeg]]
242
243 **HMI Compilation Download**
244
245 [[image:image-20220902171247-1.png]]
246
247 **Communication cable**
248
249 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
250
251 (% style="text-align:center" %)
252 [[image:image-20220819093729-7.png]]
253
254 **HMI communication PLC use Modbus **
255
256 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
257 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
258
259 (% class="wikigeneratedid" id="HPLCsettings" %)
260 **PLC settings**
261
262 **Download PLC Software**
263
264 Please visit below link to get the latest version PLC Editor for HMI programming
265
266 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
267 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
268
269 **Start a new PLC project**
270
271 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
272
273 (% style="text-align:center" %)
274 [[image:image-20220819101447-3.jpeg]]
275
276 **Add a new instruction **
277
278 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
279
280 (% style="text-align:center" %)
281 [[image:image-20220819105530-1.png]]
282
283 You could also select the ladder symbol from the menu bar directly.
284
285 [[image:image-20220819093729-12.png]]
286
287 **Add comment to PLC program**
288
289 (% style="text-align:center" %)
290 [[image:image-20220819105630-3.png]]
291
292 **Add the statement to PLC program**
293
294 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
295
296 (% style="text-align:center" %)
297 [[image:image-20220819105644-4.png]]
298
299 **Compile **
300
301 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
302
303 [[image:image-20220819093729-15.png]]
304
305 **Download setting **
306
307 Click on “Transfer Setup” to select download mode.
308
309 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
310
311 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
312
313 [[image:image-20220819093729-17.png]]
314
315 **Upload PLC program from PLC**
316
317 Read the PLC program from PLC to computer.
318
319 [[image:image-20220819093729-18.png]]
320
321 **Device monitor**
322
323 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
324
325 [[image:image-20220819093730-19.png]]
326
327 **Online monitor**
328
329 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
330
331 [[image:image-20220819093730-20.png]]
332
333 **Monitor edit**
334
335 In this mode, you could edit the PLC program during PLC is running. 
336
337
338 (% style="text-align:center" %)
339 [[image:image-20220819105928-9.png||height="229" width="669"]]
340
341 == **LX5V Series** ==
342
343 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
344
345 **Software configuration of PLC**
346
347 PLC programming software
348
349 (% style="text-align:center" %)
350 [[image:image-20220810164710-1.png]]
351
352 **New PLC project**
353
354 Click "New Project" and select the PLC model.
355
356 [[image:image-20220810172412-1.png]]
357
358 **Set Serial port parameters**
359
360 Follow the steps below to configure Serial port parameters.
361
362 * Baud rate:115200
363 * Data bit:8
364 * Stop bit:1
365 * Parity:No verification
366
367 [[image:image-20220810165759-3.png]]
368
369 **Registers list**
370
371 [[image:image-20220811102219-3.png]]
372
373 **HMI software configuration**
374
375 HMI programming software
376
377 (% style="text-align:center" %)
378 [[image:image-20220810171237-4.png]]
379
380 **New HMI project**
381
382 Click New Project and select the HMI model.
383
384 [[image:image-20220810172010-5.png]]
385
386 Set communication port parameters
387
388 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
389
390 * Baud rate:115200
391 * Data bit:8
392 * Stop bit:1
393 * Parity:No verification
394
395 [[image:image-20220811104012-1.png]]
396
397 **hardware connection**
398
399 Hardware wiring diagram
400
401 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
402
403 (% style="text-align:center" %)
404 [[image:image-20220811103005-4.png]]
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103227-7.png]]
408
409 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
410
411 == **LX5V-N Ethernet** ==
412
413 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
414
415 **Software configuration of PLC**
416
417 **PLC programming software**
418
419 (% style="text-align:center" %)
420 [[image:image-20220810164710-1.png]]
421
422 **New PLC project**
423
424 Click New Project and select the PLC model.
425
426 [[image:image-20220811115454-1.png]]
427
428 **Set Ethernet port parameters**
429
430 Follow the steps below to configure Ethernet parameters
431
432 * PLC IP address:192.168.39.200
433 * default gateway:192.168.39.1
434 * subnet mask:255.255.255.0
435
436 [[image:image-20220811140530-2.png]]
437
438 **Registers list**
439
440 [[image:image-20220811102219-3.png]]
441
442 **HMI software configuration**
443
444 HMI programming software
445
446
447 (% style="text-align:center" %)
448 [[image:image-20220810171237-4.png]]
449
450 **New HMI project**
451
452 Click New Project and select the HMI model.
453
454 [[image:image-20220810172010-5.png]]
455
456 **Set communication port parameters**
457
458 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
459
460 * HMI IP address:192.168.39.201
461 * Default gateway:192.168.39.1
462 * Subnet mask:255.255.255.0
463
464 [[image:image-20220811170753-2.png]]
465
466 Next, click Communication Settings to configure the IP of the HMI communication object.
467
468 [[image:image-20220811163047-1.png]]
469
470 **Hardware connection**
471
472 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
473
474 (% style="text-align:center" %)
475 [[image:image-20220811170248-1.png]]
476
477 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
478
479 = ABB =
480
481 == **AC500** ==
482
483 Support Series: ABB AC500
484
485 **HMI Settings**
486
487 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
488 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
489 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
490 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
491 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
496
497 **Address List**
498
499 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
500 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
501 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
502 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
503
504 **Cable Wiring**
505
506 (% style="text-align:center" %)
507 [[image:ABB AC500.gif]]
508
509 = Abzil =
510
511 == **Abzil CPL Protocol** ==
512
513 Supported series: SDC series
514
515 **HMI Settings**
516
517 (% style="width:1003px" %)
518 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
519 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
520 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
521 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
522 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
523 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
524 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
525 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
526
527 **Address List**
528
529 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
530 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
531 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
532 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
533 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
540 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
541 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
542 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
548
549 **Cable Wiring**
550
551 (% style="text-align:center" %)
552 [[image:Azbil CPL485.gif]]
553
554 = Crouzet =
555
556 == **M3 (FBD)** ==
557
558 Support Series: Crouzet Millenium 3 CD12/CB12
559
560 **HMI Settings**
561
562 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
563 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
564 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
565 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
566 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
567 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
568 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
569 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
571
572 **Address List**
573
574 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
575 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
576 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
577 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
578 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
579 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
580 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
581 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
582 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
583 Time1: Second
584
585 Time2: Minute
586
587 Time3: Hour
588
589 Time4: Day
590
591 Time5: Month
592
593 Time6: Year
594 )))
595 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
596 Running command(Write only)
597
598 ~=2: Run mode; =1: Stop mode;
599 )))
600
601 **Cable Wiring**
602
603 (% style="text-align:center" %)
604 [[image:CrouzetRS232.png]]
605
606 {{info}}
607 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
608 {{/info}}
609
610 = Create communication with Danfoss Drive =
611
612 == **FC Series Protocol** ==
613
614 Support Series: VLT FC300 Drive
615
616 **HMI Settings**
617
618 (% style="width:988px" %)
619 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended |=(% style="width: 237px;" %)Note
620 |=(% style="width: 262px;" %)Protocol|(% style="width:487px" %)Danfoss FC Series|(% style="width:237px" %)
621 |=(% style="width: 262px;" %)Connection|(% style="width:487px" %)RS485|(% style="width:237px" %)
622 |=(% style="width: 262px;" %)Baud rate|(% style="width:487px" %)9600|(% style="width:237px" %)
623 |=(% style="width: 262px;" %)Stop bits|(% style="width:487px" %)1|(% style="width:237px" %)
624 |=(% style="width: 262px;" %)Data bits|(% style="width:487px" %)8|(% style="width:237px" %)
625 |=(% style="width: 262px;" %)Parity|(% style="width:487px" %)EVEN|(% style="width:237px" %)
626 |=(% style="width: 262px;" %)PLC Station No.|(% style="width:487px" %)1|(% style="width:237px" %)
627 |=(% style="width: 262px;" %)HMI Station No.|(% style="width:487px" %)0|(% style="width:237px" %)
628
629 **Address List**
630
631 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
632 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
633 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
634 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
635 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
636
637 **Cable Wiring**
638
639 (% style="text-align:center" %)
640 [[image:Danfoss.png]]
641
642 = Create communication with **Delta PLC** =
643
644 == DVP serial protocol ==
645
646 (% class="wikigeneratedid" %)
647 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
648
649 **HMI Settings**
650
651 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
652 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
653 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
654 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
655 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
656 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
657 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
658 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
659
660 **Address List**
661
662 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
663 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
664 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
665 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
669 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
670 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
671 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
672
673 (% class="wikigeneratedid" %)
674 **Configure the communication protocol**
675
676 (% style="text-align:center" %)
677 [[image:image-20220829152327-6.png]]
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152016-3.png]]
681
682 (% class="wikigeneratedid" %)
683 **Cable Wiring**
684
685 (% class="wikigeneratedid" id="H" %)
686 [[image:image-20220829152610-7.png]]
687
688 (% style="text-align:center" %)
689 [[image:image-20220829152102-5.png]]
690
691 == DVP Ethernet Protocol ==
692
693 (% class="wikigeneratedid" %)
694 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
695
696 **HMI Settings**
697
698 |=**Items**|=**Settings**|=**Note**
699 |Protocol|DELTA DVP Modbus TCP|
700 |Connection|Ethernet|
701 |Port No.|201|Must be the same as the PLC setting
702 |PLC station No.|0|Must be the same as the PLC setting
703
704 **Address List**
705
706 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
707 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
712 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
713 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
714 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
715 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
716
717 )))
718 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
719 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
720
721 )))
722
723 (% class="wikigeneratedid" %)
724 **Configure the communication protocol**
725
726 (% style="text-align:center" %)
727 [[image:image-20220829155452-1.png]]
728
729 [[image:image-20220829162116-2.png]]
730
731 **Cable Wiring**
732
733 (% style="text-align:center" %)
734 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
735
736 == **AS serial protocol** ==
737
738 Supported Series: Delta AS200/AS300
739
740 **HMI Settings**
741
742 |**Item**|**Settings**|**Note**
743 |Protocol|DELTA AS300 MODBUS RTU|
744 |Connection|RS485|
745 |Baud rate|9600|
746 |Data bit|8|
747 |Parity|NONE|
748 |Stop bit|1|
749 |PLC station No.|1|
750
751 **Address List**
752
753 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
754 |Bit|X|X|Xdd.dd|0~~63.15|Read only
755 |Bit|Y|Y|Ydd.dd|0~~63.15|
756 |Bit|D|D|Dddddd|0~~29999|
757 |Bit|M|M|Mdddd|0~~8191|
758 |Bit|SM|SM|SMdddd|0~~4095|
759 |Bit|S|S|Sdddd|0~~2047|
760 |Bit|T|T|Tddd|0~~511|
761 |Bit|C|C|Cddd|0~~511|
762 |Bit|HC|HC|HCddd|0~~255|Double Word
763 |Word|X|X|Xdd|0~~63|
764 |Word|Y|Y|(((
765 Ydd
766 )))|0~~63|
767 |Word|SR|SR|SRdddd|0~~2047|Special register
768 |Word|D|D|Dddddd|0~~29999|
769 |Word|T|T|Tddd|0~~511|
770 |Word|C|C|Cddd|0~~511|
771 |Word|E|E|Ed|0~~9|
772
773 **Configure the communication protocol**
774
775 Create project
776
777 (% style="text-align:center" %)
778 [[image:AsCreateProject.png]]
779
780 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
781
782 (% style="text-align:center" %)
783 [[image:AScommunicarw.png]]
784
785 Double click the HWCONFIG to open the communication settings window.
786
787 (% style="text-align:center" %)
788 [[image:ASHWCONFIG.png]]
789
790 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
791
792 (% style="text-align:center" %)
793 [[image:ASHSCONFIGICON.png]]
794
795 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
796
797 (% style="text-align:center" %)
798 [[image:ASModbusMode.png]]
799
800 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
801
802 (% style="text-align:center" %)
803 [[image:ASconfigIP.png]]
804
805 (% style="text-align:center" %)
806 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
807
808
809 (% style="text-align:center" %)
810 [[image:image-20220830094657-2.png]]
811
812 **Cable Wiring**
813
814 (% style="text-align:center" %)
815 [[image:image-20220830141138-1.png]]
816
817 Pin Definition Diagram
818
819 (% style="text-align:center" %)
820 [[image:image-20220830095131-1.png]]
821
822 == AS Ethernet Protocol ==
823
824 **HMI Settings**
825
826 |=**Items**|=**Settings**|=**Note**
827 |Protocol|DELTA AS300 MODBUS TCP|
828 |Connection|Ethernet|
829 |Port No.|502|
830 |Device No.|1|
831 |HMI No.|0|
832
833 **Address List**
834
835 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
836 |Bit|X|X|X d|0~~63|
837 |Bit|Y|Y|Y d|0~~63|
838 |Bit|D|D|D d|0~~29999|
839 |Bit|M|M|M d|0~~8191|
840 |Bit|SM|SM|SM d|0~~4095|
841 |Bit|S|S|S h|0~~2047|
842 |Bit|T|T|T d|0~~511|
843 |Bit|C|C|C d|0~~511|
844 |Bit|HC|HC|HC d|0~~255|
845 |Word|X|X|X h|0~~63|
846 |Word|Y|Y|Y d|0~~63|
847 |Word|SR|SR|SR d|0~~2047|
848 |Word|D|D|D d|0~~29999|
849 |Word|T|T|T d|0~~511|
850 |Word|C|C|C h|0~~511|
851 |Word|E|E|E d|0~~9|
852
853 **Configure the communication protocol**
854
855 (% style="text-align:center" %)
856 [[image:image-20220830140537-1.png]]
857
858 (% style="text-align:center" %)
859 [[image:image-20220830140629-2.png]]
860
861 **Cable Wiring**
862
863 [[image:image-20220830094929-1.png]]
864
865 Pin Definition Diagram
866
867 (% style="text-align:center" %)
868 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
869
870 = **Create communication with EMERSON PLC** =
871
872 == **RTU Slave Protocol** ==
873
874 Supported series: EC10 series
875
876 **HMI Settings**
877
878 |**Item**|**Settings**|**Note**
879 |Protocol|Emerson 984 RTU Slave MODBUS|
880 |Connection|RS485|
881 |Baud rate|19200|
882 |Data bit|8|
883 |Parity|EVEN|
884 |Stop bit|1|
885 |PLC station No.|1
886
887 **PLC Settings**
888
889 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
890
891 (% style="text-align:center" %)
892 [[image:ControlStarSystemBlock.png]]
893
894 (% style="text-align:center" %)
895 [[image:ControlStarCommunicate.png]]
896
897 (% style="text-align:center" %)
898 [[image:ControlStarModbus.png]]
899
900 **Address List**
901
902 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
903 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
904 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
905 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
906 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
907 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
908 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
909 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
910 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
911 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
912 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
913 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
914 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
915 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
916 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
917 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
918 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
919 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
920 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
921 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
922 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
923 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
924
925 **Cable Wiring**
926
927 (% style="text-align:center" %)
928 [[image:Emerson.gif]]
929
930 = **Create communication with HollySys PLC** =
931
932 == **LK MODBUS RTU** ==
933
934 Supported Series: HollySys LK series CPU
935
936 **HMI Settings**
937
938 |=Item|=Recommended|=Note
939 |=Protocol|HollySys LK MODBUS RTU|
940 |=Connection|RS485|
941 |=Baud rate|38400|
942 |=Stop bits|1|
943 |=Data bits|8|
944 |=Parity|NONE|
945 |=PLC Station No.|1|
946 |=HMI Station No.|0|
947
948 **Address List**
949
950 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
951 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
952 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
953 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
954 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
955 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
956 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
957 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
958
959 **Cable Wiring**
960
961 (% style="text-align:center" %)
962 [[image:Hollysys485.png]]
963
964 == **LM MODBUS RTU** ==
965
966 Supported Series: HollySys LM3109/LM3107 PLC
967
968 **HMI Settings**
969
970 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
971 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
972 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
973 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
974 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
975 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
976 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
977 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
978 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
979
980 **Address List**
981
982 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
983 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
984 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
985 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
986 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
987 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
988 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
989 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
990
991 **Cable Wiring**
992
993 RS232
994
995 (% style="text-align:center" %)
996 [[image:HollySys LM Modbus RTU.gif]]
997
998 RS485
999
1000 (% style="text-align:center" %)
1001 [[image:Hollysys LM Modbus RTU.gif]]
1002
1003 = **Create communication with Inovance PLC** =
1004
1005 == **H1U/H2U serial protocol** ==
1006
1007 **HMI Settings**
1008
1009 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1010 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1011 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1012 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1013 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1014 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1015 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1016 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1017 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1018
1019 (% class="wikigeneratedid" %)
1020 **Address List**
1021
1022 (% style="width:1014px" %)
1023 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1026 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1027 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1028 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1029 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1030 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1031 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1034 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1035 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1036 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1037 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1038 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1039 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1040 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1041
1042 (% class="wikigeneratedid" %)
1043 **Cable Wiring**
1044
1045 (% style="text-align:center" %)
1046 [[image:Inovance.png]]
1047
1048 == **H3U serial protocol** ==
1049
1050 **HMI Settings**
1051
1052 |=**Item**|=**Settings**|=**Note**
1053 |Protocol|INOVANCE H3U PLC|
1054 |Connection|RS422|
1055 |Baud rate|9600|
1056 |Data bit|7|
1057 |Parity|EVEN|
1058 |Stop bit|1|
1059 |PLC station No.|0|
1060
1061 **Address List**
1062
1063 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1066 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1067 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1068 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1069 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1070 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1071 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1075 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1076 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1077 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1078 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1079 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1080 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1081 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1082
1083 **Configure the communication protocol**
1084
1085 (% style="text-align:center" %)
1086 [[image:image-20220830170114-4.png]]
1087
1088 [[image:image-20220830170017-3.png]]
1089
1090 **Cable Wiring**
1091
1092 (% style="text-align:center" %)
1093 [[image:Inovance.png]]
1094
1095 == **H3U Ethernet portocol** ==
1096
1097 **HMI Settings**
1098
1099 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1100 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1101 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1102 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1103 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1104 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1105
1106 **Address List**
1107
1108 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1109 |Bit|M|M DDDD|0~~8511|
1110 |Bit|SM|SM DDDD|0~~1023|
1111 |Bit|S|S DDDD|0~~4095|
1112 |Bit|T|T DDD|0~~511|
1113 |Bit|C|C DDD|0~~255|
1114 |Bit|X|X OOO|0~~571|
1115 |Bit|Y|Y OOO|0~~571|
1116 |Word|D|D DDDD|0~~8511|
1117 |Word|SD |SD DDDD|0~~1023|
1118 |Word|R|R DDDDD|0~~32767|
1119 |Word|T|T DDD|0~~255|
1120 |Word|C|C DDD|0~~199|
1121 |Double Word|C|C DDD|200~~255|
1122
1123 **Cable Wiring**
1124
1125 (% style="text-align:center" %)
1126 [[image:CommonEthernet.png]]
1127
1128 = Create communication with LS** PLC** =
1129
1130 == **XGB serial protocol ** ==
1131
1132 **HMI Settings**
1133
1134 |=**Item**|=**Settings**|=**Note**
1135 |Protocol|LS XGB CPU DRIECT|
1136 |Connection|RS232|
1137 |Baud rate|115200|
1138 |Data bit|8|
1139 |Parity|NONE|
1140 |Stop bit|1|
1141 |PLC station No.|1|
1142
1143 **Address List**
1144
1145 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1146 |Bit|P|P|P DDDD.f|0~~2047|
1147 |Bit|M|M|M DDDD.f|0~~2047|
1148 |Bit|L|L|L DDDDD.f|0~~11263|
1149 |Bit|K|K|K DDDD.f|0~~2559|
1150 |Bit|F|F|F DDDD.f|0~~2047|
1151 |Bit|S|S|S DDDDD|0~~12799|
1152 |Bit|D|D|D DDDDD.f|0~~32767|
1153 |Bit|U|U|U FFFF.f|0~~7f31|
1154 |Bit|T|T|T DDDD.f|0~~2047|
1155 |Bit|C|C|C DDDD.f|0~~2047|
1156 |Word|P|P|P DDDD|0~~2047|
1157 |Word|M|M|M DDDD|0~~2047|
1158 |Word|L|L|L DDDDD|0~~11263|
1159 |Word|K|K|K DDDD|0~~2559|
1160 |Word|F|F|F DDDD|0~~2047|
1161 |Word|C|C|C DDDD|0~~2047|
1162 |Word|T|T|T DDDD|0~~2047|
1163 |Word|D|D|D DDDDD|0~~32767|
1164 |Word|N|N|N DDDDD|0~~21503|
1165 |Word|U|U|U FFFF|0~~7f31|
1166 |Word|Z|Z|Z DDD|0~~127|
1167 |Word|R|R|R DDDDD|0~~32767|
1168 |Word|ZR|ZR|Z DDDDD|0~~32767|
1169 |Word|TS|TS|TS DDDD|0~~2047|
1170 |Word|CS|CS|CS DDDD|0~~2047|
1171 |Word|S|S|S DDDDD|0~~12799|
1172
1173 **Configure the communication protocol**
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028174410-1.png]]
1177
1178 (% style="text-align:center" %)
1179 [[image:image-20221028174753-2.png]]
1180
1181 (% style="text-align:center" %)
1182 [[image:image-20221028181125-4.png]]
1183
1184 **Pin Definition Diagram**
1185
1186 (% style="text-align:center" %)
1187 [[image:image-20221028180930-3.png]]
1188
1189 == **XBC serial protocol** ==
1190
1191 **HMI Settings**
1192
1193 |=**Item**|=**Settings**|=**Note**
1194 |Protocol|LS XBC CNet|
1195 |Connection|RS232|
1196 |Baud rate|115200|
1197 |Data bit|8|
1198 |Parity|NONE|
1199 |Stop bit|1|
1200 |PLC station No.|1|
1201
1202 **Address List**
1203
1204 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1205 |Bit|P|P|P d|0~~2047|
1206 |Bit|M|M|M d|0~~2047|
1207 |Bit|L|L|L d|0~~11263|
1208 |Bit|K|K|K d|0~~16183|
1209 |Bit|F|F|F d|0~~2047|
1210 |Bit|D|D|D d|0~~32767|
1211 |Bit|R|R|R d|0~~32767|
1212 |Bit|U|U|U d|0~~4095|
1213 |Word|P|P|P d|0~~2047|
1214 |Word|M|M|M d|0~~2047|
1215 |Word|L|L|L d|0~~11263|
1216 |Word|K|K|K d|0~~16183|
1217 |Word|F|F|F d|0~~2047|
1218 |Word|C|C|C d|0~~2047|
1219 |Word|T|T|T d|0~~2047|
1220 |Word|D|D|D d|0~~32767|
1221 |Word|N|N|N d|0~~21503|
1222 |Word|R|R|R d|0~~32767|
1223 |Word|U|U|U d|0~~4095|
1224 |Word|Z|Z|Z d|0~~127|
1225 |Word|S|S|S d|0~~127|
1226
1227 **Configure the communication protocol**
1228
1229 (% style="text-align:center" %)
1230 [[image:image-20220831170807-1.png]]
1231
1232 (% style="text-align:center" %)
1233 [[image:image-20220830174733-2.png]]
1234
1235 **Cable Wiring**
1236
1237 (% style="text-align:center" %)
1238 [[image:image-20220830174659-1.png]]
1239
1240 Pin Definition Diagram
1241
1242 (% style="text-align:center" %)
1243 [[image:image-20220830173402-8.png]]
1244
1245 == **XGK FEnet Ethernet protocol** ==
1246
1247 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1248
1249 **HMI Settings**
1250
1251 |**Items**|**Settings**|**Note**
1252 |Protocol|LG XGK FEnet(Ethernet)|
1253 |Connection|Ethernet|
1254 |Port No.|2004|
1255
1256 **Address List**
1257
1258 |**Type**|**Register**|**Range**|**Format**|**Note**
1259 |(% rowspan="14" %)Word|P|0~~2047|P d|
1260 |M|0~~2047|M d|
1261 |K|0~~2047|K d|
1262 |F|0~~2047|F d|
1263 |T|0~~2047|T d|
1264 |C|0~~2047|C d|
1265 |Z|0~~127|Z d|
1266 |S|0~~127|S d|
1267 |L|0~~11263|L d|
1268 |N|0~~21503|N d|
1269 |D|0~~32767|D d|
1270 |R|0~~32767|R d|
1271 |ZR|0~~65535|ZR d|
1272 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1273
1274 **✎Note:**
1275
1276 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1277 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1278 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1279
1280 **Communication settings in HMI**
1281
1282 Enable HMI Ethernet in [Project Settings];
1283
1284 (% style="text-align:center" %)
1285 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1286
1287 Set PLC IP in [Device IP] settings;
1288
1289 (% style="text-align:center" %)
1290 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1291
1292 **Cable Wiring**
1293
1294
1295 (% style="text-align:center" %)
1296 [[image:CommonEthernet.png]]
1297
1298 = Create communication with **Mitsubishi PLC** =
1299
1300 == **FX1S, 1N, 2N Series Protocol** ==
1301
1302 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1303
1304 **HMI Settings**
1305
1306 |**Item**|**Settings**|**Note**
1307 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1308 |Connection|RS422/RS485/RS232|
1309 |Baud rate|9600~~115200|
1310 |Data bit|7/8|
1311 |Parity|EVEN/Odd/None|
1312 |Stop bit|1/2|
1313 |PLC station No.|1~~255|
1314
1315 **Address List**
1316
1317 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1318 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1319 |Y|Y|Y o|0~~303237|
1320 |M|M|M d|0~~99999|
1321 |T|T|T d|0~~99999|
1322 |C|C|C d|0~~99999|
1323 |S|S|S d|0~~99999|
1324 |SM|SM|SM d|8000~~9999|
1325 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1326 |Y|Y|Y o|0~~303237|
1327 |M|M|M d|0~~99999|
1328 |T|T|T d|0~~99999|
1329 |C|C|C d|0~~199|
1330 |D|D|D d|0~~7999|
1331 |S|S|S d|0~~99999|
1332 |SD|SD|SD d|8000~~9999|
1333
1334 **Cable Wiring**
1335
1336 * **RS485**
1337
1338 (% style="text-align:center" %)
1339 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1343
1344 * **RS422**
1345
1346 (% style="text-align:center" %)
1347 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1348
1349 **✎Note:** COM3 only available in PI8000/PI9000 series.
1350
1351 == **FX3U/3G/3GA serial protocol** ==
1352
1353 **HMI Settings**
1354
1355 |=**Item**|=**Settings**|=**Note**
1356 |Protocol|Mitsubishi FX3U/3G/3GA|
1357 |Connection|RS422|
1358 |Baud rate|9600~~115200|
1359 |Data bit|7/8|
1360 |Parity|EVEN/Odd/None|
1361 |Stop bit|1/2|
1362 |PLC station No.|1~~255|
1363
1364 **Address List**
1365
1366 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1367 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1368 |Y|Y|Y o|0~~303237|
1369 |M|M|M d|0~~99999|
1370 |T|T|T d|0~~99999|
1371 |C|C|C d|0~~99999|
1372 |S|S|S d|0~~99999|
1373 |SM|SM|SM d|8000~~9999|
1374 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1375 |Y|Y|Y o|0~~303237|
1376 |M|M|M d|0~~99999|
1377 |T|T|T d|0~~99999|
1378 |C|C|C d|0~~199|
1379 |D|D|D d|0~~7999|
1380 |S|S|S d|0~~99999|
1381 |SD|SD|SD d|8000~~9999|
1382
1383 **Configure the communication protocol**
1384
1385 (% style="text-align:center" %)
1386 [[image:image-20220831095222-1.png]]
1387
1388 (% style="text-align:center" %)
1389 [[image:image-20220831095743-2.png]]
1390
1391 **Wiring**
1392
1393 (% style="text-align:center" %)
1394 [[image:image-20220831100314-6.png]]
1395
1396 == **FX NOPROTOCOL** ==
1397
1398 Mitsubishi FX3G-RS232-BD
1399
1400 **HMI Settings**
1401
1402 |=**Item**|=**Settings**|=**Note**
1403 |Protocol|Mitsubishi FX NOPROTOCOL|
1404 |Connection|RS232|
1405 |Baud rate|9600|
1406 |Data bit|7|
1407 |Parity|EVEN|
1408 |Stop bit|1|
1409 |PLC station No.|0|
1410
1411 **Address List**
1412
1413 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1414 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1415 |Y|Y|Y o|0~~303237|
1416 |M|M|M d|0~~99999|
1417 |T|T|T d|0~~99999|
1418 |C|C|C d|0~~99999|
1419 |S|S|S d|0~~99999|
1420 |SM|SM|SM d|8000~~9999|
1421 |Lamp|Lamp|Lamp d|0~~0|
1422 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1423 |Y|Y|Y o|0~~303237|
1424 |M|M|M d|0~~99999|
1425 |T|T|T d|0~~99999|
1426 |C|C|C d|0~~199|
1427 |D|D|D d|0~~7999|
1428 |S|S|S d|0~~99999|
1429 |SD|SD|SD d|8000~~9999|
1430
1431 **Configure the communication protocol**
1432
1433 (% style="text-align:center" %)
1434 [[image:1.png]]
1435
1436 (% style="text-align:center" %)
1437 [[image:2.png]]
1438
1439 **Wiring**
1440
1441 (% style="text-align:center" %)
1442 [[image:3.png]]
1443
1444 == **FX3U Ethernet Protocol** ==
1445
1446 Mitsubishi FX3U series PLC
1447
1448 **HMI Settings**
1449
1450 |Items|Settings|Note
1451 |Protocol|Mitsubishi FX3U|
1452 |Connection|Ethernet|
1453 |Port No.|5009|Must be the same as the PLC setting
1454 |PLC station No.|0|
1455
1456 **Address List**
1457
1458 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1459 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1460 |Y|Y|Y OOO|0~~377|
1461 |M|M|M DDDD|0~~7679|
1462 |SM|SM|SM DDDD|8000~~8511|
1463 |S|S|S DDDD|0~~4095|
1464 |TS|TS|TS DDD|0~~511|
1465 |CS|CS|CS DDD|0~~255|
1466 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1467 |TN|TN|TN DDD|0~~511|
1468 |D|D|D DDDD|0~~7999|
1469 |SD|SD|SD DDDD|8000~~8511|
1470 |R|R|R DDDDD|0~~32767|
1471
1472 **Ethernet Module Settings**
1473
1474 FX3U-ENET-L module configuration
1475 Set up the FX3U-ENET-L Ethernet module settings as follows.
1476 Select the module location, which in this document is Module 0.
1477
1478 [[image:image-20221115140802-1.png]]
1479
1480 Select "Operational setting" to enter the following screen.
1481
1482 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1483
1484 [[image:image-20221115142728-4.png]]
1485
1486 Select "Open setting" to enter the setting interface, the settings are as follows.
1487
1488 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1489
1490 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1491
1492 [[image:image-20221115142945-5.png]]
1493
1494 Click on "transter setup" - "PC side I/F setting", see the following figure.
1495
1496 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1497
1498 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1499
1500 [[image:image-20221115143341-6.png||height="426" width="712"]]
1501
1502 Read and write data from the Ethernet module
1503
1504 [[image:image-20221115143703-7.png]]
1505
1506 Set "Transter setup" to COM communication, and read or write operation as shown below
1507
1508 [[image:image-20221115143809-8.png]]
1509
1510 **PLC Settings (GX Works 2)**
1511
1512 Create a blank FX5U project
1513
1514 Find Current Connection in the navigation
1515
1516 [[image:image-20221115144335-9.png||height="422" width="706"]]
1517
1518 Select Connection Channel List
1519
1520 Select Ethernet board communication
1521
1522 [[image:image-20221115144824-10.png||height="421" width="705"]]
1523
1524 Select Ethernet Module
1525 Set the IP address of the PLC
1526
1527 [[image:image-20221115145228-11.png||height="674" width="708"]]
1528
1529 Read or write PLC data, in this document is read
1530
1531 [[image:image-20221115145553-12.png||height="424" width="711"]]
1532
1533 [[image:image-20221115145559-13.png||height="424" width="711"]]
1534
1535 **HMI Communication Setting**
1536
1537 [[image:image-20221115150003-14.png||height="425" width="712"]]
1538
1539 [[image:image-20221115150235-15.png||height="427" width="713"]]
1540
1541 [[image:image-20221115145559-13.png||height="424" width="711"]]
1542
1543 **HMI Communication Setting**
1544
1545 [[image:image-20221115150003-14.png||height="425" width="712"]]
1546
1547 [[image:image-20221115150235-15.png||height="427" width="713"]]
1548
1549 == **FX5U Serial Port Protocol** ==
1550
1551 Mitsubishi FX5U series PLC
1552
1553 **HMI Settings**
1554
1555 |**Item**|**Settings**|**Note**
1556 |Protocol|Mitsubishi FX5U|
1557 |Connection|RS422/RS485|
1558 |Baud rate|9600|
1559 |Data bit|7|
1560 |Parity|Odd|
1561 |Stop bit|1|
1562 |PLC station No.|1~~255|Need to be the same as PLC settings
1563
1564 **Address List**
1565
1566 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1567 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1568 |Y|Y|Y o|0~~303237|
1569 |M|M|M d|0~~99999|
1570 |B|B|B h|0~~7FFF|
1571 |F|F|F d|0~~32767|
1572 |SB|SB|SB h|0~~7FFF|
1573 |TS|TS|TS d|0~~1023|
1574 |TC|TC|TC d|0~~1023|
1575 |STS|STS|STS d|0~~1023|
1576 |STC|STC|STS d|0~~1023|
1577 |CS|CS|CS d|0~~1023|
1578 |CC|CC|CC d|0~~1023|
1579 |SM|SM|SM d|0~~9999|
1580 |L|L|L d|0~~32767|
1581 |S|S|S d|0~~4095|
1582 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1583 |TN|TN|TN d|0~~1023|
1584 |STN|STN|STN d|0~~1023|
1585 |CN|CN|CN d|0~~1023|
1586 |R|R|R d|0~~32767|
1587 |SW|SW|SW h|0~~7FFF|
1588 |Z|Z|Z d|0~~23|
1589 |D|D|D d|0~~7999|
1590 |SD|SD|SD d|0~~11999|
1591
1592 **PLC Settings (GX Works 3)**
1593
1594 Create a blank FX5U project
1595
1596 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1597
1598 (% style="text-align:center" %)
1599 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1600
1601 Select protocol in the setting item, and set parameters.
1602
1603 (% style="text-align:center" %)
1604 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1605
1606 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1607
1608 (% style="text-align:center" %)
1609 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1610
1611 Click the [Apply] button to finish the setting.
1612
1613 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1617
1618 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1619
1620 Done.
1621
1622 **Cable Wiring**
1623
1624 * **RS485**
1625
1626 (% style="text-align:center" %)
1627 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1628
1629 (% style="text-align:center" %)
1630 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1631
1632 * **RS422**
1633
1634 (% style="text-align:center" %)
1635 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1636
1637 **✎Note:** COM3 only available in PI8000/PI9000 series.
1638
1639 == **L02 Serial Protocol** ==
1640
1641 Mitsubishi L02 series CPU built-in serial port.
1642
1643 **HMI Settings**
1644
1645 |=**Item**|=**Settings**|=**Note**
1646 |Protocol|Mitsubishi L02|
1647 |Connection|RS422|
1648 |Baud rate|115200|
1649 |Data bit|8|
1650 |Parity|Odd|
1651 |Stop bit|1|
1652 |PLC station No.|1~~255|Need to be the same as PLC settings
1653
1654 **Address List**
1655
1656 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1657 |Bit|X|X|X h|0~~FFFF|
1658 |Bit|Y|Y|Y h|0~~FFFF|
1659 |Bit|M|M|M d|0~~9999|
1660 |Bit|L|L|L d|0~~9999|
1661 |Bit|F|F|F d|0~~9999|
1662 |Bit|B|B|B h|0~~FFFF|
1663 |Bit|V|V|V d|0~~2047|
1664 |Bit|TC|TC|TC d|0~~9999|
1665 |Bit|SS|SS|SS d|0~~9999|
1666 |Bit|SC|SC|SC d|0~~9999|
1667 |Bit|CS|CS|CS d|0~~9999|
1668 |Bit|CC|CC|CC d|0~~9999|
1669 |Bit|SB|SB|SB h|0~~FFFF|
1670 |Bit|SM|SM|SM d|0~~2047|
1671 |Bit|STS|STS|STS d|0~~1023|
1672 |Bit|S|S|S d|0~~9999|
1673 |Bit|DX|DX|DX h|0~~FFFF|
1674 |Bit|DY|DY|DY h|0~~FFFF|
1675 |Bit|TS|TS|TS d|0~~9999|
1676 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1677 |Word|W|W|W h|0~~FFFF|
1678 |Word|TN|TN|TN d|0~~99999|
1679 |Word|SN|SN|SN d|0~~99999|
1680 |Word|CN|CN|CN d|0~~99999|
1681 |Word|R|R|R d|0~~99999|
1682 |Word|SW|SW|SW h|0~~FFFF|
1683 |Word|Z|Z|Z d|0~~99999|
1684 |Word|ZR|ZR|ZR h|0~~FFFF|
1685 |Word|D|D|D d|0~~99999|
1686
1687 **Communication Settings**
1688
1689 (% style="text-align:center" %)
1690 [[image:image-20220831105732-3.png]]
1691
1692 (% style="text-align:center" %)
1693 [[image:image-20220831110004-5.png]]
1694
1695 **Cable Wiring**
1696
1697 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1698
1699 Pin Definition Diagram
1700
1701 (% style="text-align:center" %)
1702 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1703
1704 == **L02 MELSEC (Ethernet) Protocol** ==
1705
1706 Mitsubishi Q series CPU built-in Ethernet port.
1707
1708 **HMI Settings**
1709
1710 |**Items**|**Settings**|**Note**
1711 |Protocol|MIT L02 CPU MELSEC|
1712 |Connection|Ethernet|
1713 |Port No.|1025|Must be the same as the PLC setting
1714 |PLC station No.|0|Must be the same as the PLC setting
1715
1716 **Address List**
1717
1718 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1719 |Bit|X|X|X h|0~~FFFF|
1720 |Bit|Y|Y|Y h|0~~FFFF|
1721 |Bit|M|M|M d|0~~9999|
1722 |Bit|L|L|L d|0~~9999|
1723 |Bit|F|F|F d|0~~9999|
1724 |Bit|B|B|B h|0~~FFFF|
1725 |Bit|V|V|V d|0~~2047|
1726 |Bit|TC|TC|TC d|0~~9999|
1727 |Bit|SS|SS|SS d|0~~9999|
1728 |Bit|SC|SC|SC d|0~~9999|
1729 |Bit|CS|CS|CS d|0~~9999|
1730 |Bit|CC|CC|CC d|0~~9999|
1731 |Bit|SB|SB|SB h|0~~FFFF|
1732 |Bit|SM|SM|SM d|0~~2047|
1733 |Bit|STS|STS|STS d|0~~1023|
1734 |Bit|S|S|S d|0~~9999|
1735 |Bit|DX|DX|DX h|0~~FFFF|
1736 |Bit|DY|DY|DY h|0~~FFFF|
1737 |Bit|TS|TS|TS d|0~~9999|
1738 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1739 |Word|W|W|W h|0~~FFFF|
1740 |Word|TN|TN|TN d|0~~99999|
1741 |Word|SN|SN|SN d|0~~99999|
1742 |Word|CN|CN|CN d|0~~99999|
1743 |Word|R|R|R d|0~~99999|
1744 |Word|SW|SW|SW h|0~~FFFF|
1745 |Word|Z|Z|Z d|0~~99999|
1746 |Word|ZR|ZR|ZR h|0~~FFFF|
1747 |Word|D|D|D d|0~~99999|
1748
1749 **Communication Settings**
1750
1751 Enable HMI Ethernet in [Project Settings];
1752
1753 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1754
1755 Set PLC IP in [Device IP] settings;
1756
1757 (% style="text-align:center" %)
1758 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1759
1760 **PLC Settings (GX Works2 )**
1761
1762 Create a project
1763
1764 Set PLC IP, subnet mask and gateway;
1765
1766 Select [Binary Code] as communication data code;
1767
1768 (% style="text-align:center" %)
1769 [[image:image-20221108202109-2.png||height="636" width="732"]]
1770
1771 Set PLC port number, for example 1025
1772
1773 (% style="text-align:center" %)
1774 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1775
1776 Save settings;
1777
1778 Download project into PLC device;
1779
1780 Restart PLC device;
1781
1782 **Cable Wiring**
1783
1784 (% style="text-align:center" %)
1785 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1786
1787 == **QJ71C24N MELSEC Protocol** ==
1788
1789 Mitsubishi QJ71C24N communication module built-in serial port;
1790
1791 **HMI Settings**
1792
1793 |**Items**|**Settings**|**Note**
1794 |Protocol|MIT QJ71 MELSEC|
1795 |Connection|422|
1796 |Baud rate|9600|
1797 |Data bit|8|
1798 |Parity|ODD|
1799 |Stop bit|1|
1800 |PLC station No.|1~~255|Need to be the same as PLC settings
1801
1802 **Address List**
1803
1804 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1805 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1806 |Y|Y|Y FFFF|0~~1FFF|
1807 |M|M|M DDDDD|0~~99999|
1808 |L|L|L DDDD|0~~8191|
1809 |F|F|F DDDD|0~~2047|
1810 |V|V|V DDDD|0~~2047|
1811 |B|B|B FFFF|0~~1FFF|
1812 |TS|TS|TS DDDD|0~~2047|
1813 |TC|TC|TC DDDD|0~~2047|
1814 |SS|SS|SS DDDD|0~~2047|
1815 |SC|SC|SC DDDD|0~~2047|
1816 |CS|CS|CS DDDD|0~~1023|
1817 |CC|CC|CC DDDD|0~~1023|
1818 |SB|SB|SB FFF|0~~7FF|
1819 |S|S|S D|0~~8191|
1820 |DX|DX|DX FFFF|0~~1FFF|
1821 |DY|DY|DY FFFF|0~~1FFF|
1822 |SM_|SM_|SM_ DDDD|8000~~9999|
1823 |SM|SM|SM DDDD|0~~2047|
1824 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1825 |D|D|D DDDDD|0~~12287|
1826 |W|W|W FFFF|0~~1FFF|
1827 |TN|TN|TN DDDD|0~~2047|
1828 |SN|SN|SN DDDD|0~~2047|
1829 |CN|CN|CN DDDD|0~~1023|
1830 |R|R|R DDDDD|0~~32767|
1831 |SW|SW|SW FFF|0~~7FF|
1832 |Z|Z|Z D|0~~15|
1833 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1834
1835 **Communication Settings**
1836
1837 (% style="text-align:center" %)
1838 [[image:image-20221109135738-1.png]]
1839
1840 (% style="text-align:center" %)
1841 [[image:image-20221109140016-3.png]]
1842
1843 Pin Definition Diagram
1844
1845 (% style="text-align:center" %)
1846 [[image:image-20221109140406-4.png]]
1847
1848 == **QJ71E71 MELSEC Protocol** ==
1849
1850 Mitsubishi QJ71E71 Ethernet communication module;
1851
1852 **HMI Settings**
1853
1854 |**Items**|**Settings**|**Note**
1855 |Protocol|MIT QJ71E71 MELSEC|
1856 |Connection|Ethernet|
1857 |Port No.|1025|Must be the same as the PLC setting
1858 |PLC station No.|0|Must be the same as the PLC setting
1859
1860 **Address List**
1861
1862 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1863 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1864 |Y|Y|Y h|0~~1FFF|
1865 |M|M|M d|0~~99999|
1866 |L|L|L d|0~~8191|
1867 |F|F|F d|0~~2047|
1868 |B|B|B h|0~~1FFF|
1869 |V|V|V d|0~~2047|
1870 |TS|TS|TS d|0~~2047|
1871 |TC|TC|TC d|0~~2047|
1872 |SS|SS|SS d|0~~2047|
1873 |SC|SC|SC d|0~~2047|
1874 |CS|CS|CS d|0~~1023|
1875 |CC|CC|CC d|0~~1023|
1876 |SB|SB|SB h|0~~7FF|
1877 |S|S|S d|0~~8191|
1878 |DX|DX|DX h|0~~1FFF|
1879 |DY|DY|DY h|0~~1FFF|
1880 |SM|SM|SM d|8000~~9999|
1881 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1882 |D|D|D d|0~~12287|
1883 |W|W|W h|0~~1FFF|
1884 |TN|TN|TN d|0~~2047|
1885 |SN|SN|SN d|0~~2047|
1886 |CN|CN|CN d|0~~1023|
1887 |R|R|R d|0~~32767|
1888 |SW|SW|SW h|0~~7FF|
1889 |Z|Z|Z d|0~~15|
1890 |ZR|ZR|ZR h|0~~FE7FF|
1891
1892 **HMI Communication Settings**
1893
1894 1) Enable HMI Ethernet in [Project Settings];
1895
1896 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1897
1898 2) Set PLC IP in [Device IP] settings
1899
1900 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1901
1902 **PLC Settings(GX Works2)**
1903
1904 * Click [Ethernet/CC IE/MELSECNET];
1905 * Please select [Ethernet] as network type;
1906 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1907 * Select [Online] as Mode;
1908 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1909 * Click [Operation setting] to set IP;
1910 * Select [Binary Code] as [Communication Data Code];
1911 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1912 * Click [Open setting]
1913 * Set protocol: TCP;
1914 * Set [unpassive] in [Open system];
1915 * Set [receive] in [Fixed buffer];
1916 * Set [procedure Exist] in [Fixed buffer communication];
1917 * Disable [Pairing open];
1918 * Set [No confirm] in [Existence confirmation];
1919 * Host station port number: 5009;
1920 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1921 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1922 * Download project into PLC and restart it
1923
1924 **Cable Wiring**
1925
1926 (% style="text-align:center" %)
1927 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1928
1929 = Create communication with **MODBUS** =
1930
1931 == **MODBUS RTU Master** ==
1932
1933 Supported Series: MODBUS RTU CONTROLLER
1934
1935 HMI works as MODBUS SLAVE connecting with MASTER
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1939
1940 (% style="text-align:center" %)
1941 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1942
1943 (% style="text-align:center" %)
1944 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1945
1946 **HMI Settings**
1947
1948 |**Items**|**Settings**|**Note**
1949 |Protocol|MODBUS RTU Master|
1950 |Connection|RS485/RS232|
1951 |Baud rate|2400~~187500|
1952 |Data bit|8|
1953 |Parity|Even/ Odd/ None|
1954 |Stop bit|1/2|
1955 |Station No.|0~~255|
1956
1957 **Address List**
1958
1959 |**Type**|**HMI address**|**MODBUS code**|**Range**
1960 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1961 |Word|HDW3500~~HDW7999|4|0~~4499
1962
1963 **Cable Wiring**
1964
1965 * **RS485**
1966
1967 (% style="text-align:center" %)
1968 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1969
1970 (% style="text-align:center" %)
1971 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1972
1973 * **RS232**
1974
1975 (% style="text-align:center" %)
1976 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1977
1978 **✎Note:** COM3 only available in PI8000/PI9000 series.
1979
1980 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1981
1982 Supported Series: MODBUS RTU CONTROLLER
1983
1984 HMI works as MODBUS MASTER connecting with SLAVE.
1985
1986 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1990
1991 (% style="text-align:center" %)
1992 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1993
1994 (% style="text-align:center" %)
1995 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1996
1997 **HMI Settings**
1998
1999 |**Items**|**Settings**|**Note**
2000 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2001 |Connection|RS485/RS232|
2002 |Baud rate|2400~~187500|
2003 |Data bit|8|
2004 |Parity|Even/ Odd/ None|
2005 |Stop bit|1/2|
2006 |PLC station No.|0~~255|
2007
2008 **Address List**
2009
2010 |**Type**|**Address Type**|**Function code & Description**
2011 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2015 |06 (write single register: write a binary value to a holding register)
2016 |10 (write values to multiple addresses )
2017 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2018 |06 (write single register: write a binary value to a holding register)
2019 |10 (write values to multiple addresses )
2020 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2021 |10 (write values to multiple addresses )
2022 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits, ie write continuously)
2025 |(% rowspan="3" %)1|02 (Read the input state)
2026 |05 (Force a single coil to force the on/off state of a logic coil)
2027 |0F (Write multiple bits)
2028 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2029 |05 (Force a single coil to force the on/off state of a logic coil)
2030 |0F (Write multiple bits)
2031 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2032 |0F (Write multiple bits)
2033
2034 **✎Note:**
2035
2036 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2037 * The function codes sent out are the same as those that read and write words.
2038
2039 **Station number for more than one slaves**
2040
2041 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2042
2043 (% style="text-align:center" %)
2044 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2045
2046 **Cable Wiring**
2047
2048 * **RS485**
2049
2050 (% style="text-align:center" %)
2051 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2052
2053 (% style="text-align:center" %)
2054 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2055
2056 * **RS232**
2057
2058 (% style="text-align:center" %)
2059 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2060
2061 **✎Note:** COM3 only available in PI8000/PI9000 series.
2062
2063 == **Communicate with Modbus Meter** ==
2064
2065 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2066
2067 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2068
2069 (% style="text-align:center" %)
2070 [[image:LinfeeDiagram.png]]
2071
2072 2. Check the specific Modbus parameter in the communication menu from LED display.
2073
2074 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2075
2076 {{info}}
2077 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2078 {{/info}}
2079
2080 (% style="text-align:center" %)
2081 [[image:MeterModbusAllView.png]]
2082
2083 3. Create new project and change the Communication settings.
2084
2085 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2086
2087 (% style="text-align:center" %)
2088 [[image:PIStudioSetupMeterModbusPara.png]]
2089
2090 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2091
2092 The following table is intercept part of the manual for Linfee Modbus manual.
2093
2094 **0x03/0x04 command data register address**:
2095
2096 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2097 | HEX|DEC| | | |
2098 |0x00|0|Reserved| | |
2099 |0x02|2|Reserved| | |
2100 |0x04|4|Reserved| | |
2101 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2102 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2103 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2104 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2105 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2106 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2107 |0x12|18|Ia|float|2|Phase Current data, Unit A
2108 |0x14|20|Ib|float|2|Phase Current data, Unit A
2109 |0x16|22|Ic|float|2|Phase Current data, Unit A
2110
2111 {{info}}
2112 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2113 {{/info}}
2114
2115 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2116
2117 (% style="text-align:center" %)
2118 [[image:MeterModbusPInumericSet.png]]
2119
2120 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2121
2122 (% style="text-align:center" %)
2123 [[image:MeterModbusNumericInputFormat.png]]
2124
2125 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2126
2127 (% style="text-align:center" %)
2128 [[image:ActualHMIModbusResult.jpg]]
2129
2130 == **MODBUS TCP Slave (All function)** ==
2131
2132 Supported series: MODBUS TCP controller
2133
2134 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2138
2139 (% style="text-align:center" %)
2140 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2141
2142 (% style="text-align:center" %)
2143 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2144
2145 **HMI Setting**
2146
2147 |**Items**|**Settings**|**Note**
2148 |Protocol|MODBUS TCP Slave (All function)|
2149 |Connection|Ethernet|
2150 |Port No.|502|
2151 |PLC station No.|1|
2152
2153 **Address List**
2154
2155 |**Type**|**Register**|**Function code & Description**
2156 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2160 |06 (write single register: write a binary value to a holding register)
2161 |10 (write values to multiple addresses )
2162 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2163 |06 (write single register: write a binary value to a holding register)
2164 |10 (write values to multiple addresses )
2165 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2166 |10 (write values to multiple addresses )
2167 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits, ie write continuously)
2170 |(% rowspan="3" %)1|02 (Read the input state)
2171 |05 (Force a single coil to force the on/off state of a logic coil)
2172 |0F (Write multiple bits)
2173 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2174 |05 (Force a single coil to force the on/off state of a logic coil)
2175 |0F (Write multiple bits)
2176 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2177 |0F (Write multiple bits)
2178
2179 **Communication Settings**
2180
2181 Enable HMI Ethernet in [Project Settings];
2182
2183 (% style="text-align:center" %)
2184 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2185
2186 Set PLC IP in [Device IP] settings;
2187
2188 (% style="text-align:center" %)
2189 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2190
2191 **Cable Wiring**
2192
2193 (% style="text-align:center" %)
2194 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2195
2196 = Create communication with **Omron** PLC =
2197
2198 == CJ TCP FINS Ethemet  Protocol ==
2199
2200 Supported device:CJ series、CJ1W-EIP21
2201
2202 **HMI Settings**
2203
2204 |=**Items**|=**Settings**|=**Note**
2205 |Protocol|OMRON CJ TCP FINS Ethemet|
2206 |Connection|Ethernet|
2207 |Port No.|9600|
2208 |Device No.|0|
2209 |HMI No.|0|(((
2210
2211 )))
2212
2213 **Address List**
2214
2215 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2216 |Bit|CIO|CIO|CIO d|0~~99999|
2217 |Bit|W|W|W d|0~~99999|
2218 |Bit|D|D|D d|0~~99999|
2219 |Bit|H|H|H d|0~~99999|
2220 |Bit|A|A|A d|0~~99999|
2221 |Bit|T|T|T h|0~~99999|
2222 |Bit|CF|CF|CF d|0~~99999|
2223 |Bit|FF|FF|FF d|0~~99999|
2224 |Bit|C|C|C d|0~~99999|
2225 |Bit|EM0|EM0|EM0 d|0~~99999|
2226 |Bit|EM1|EM1|EM1 d|0~~99999|
2227 |Bit|EM2|EM2|EM2 d|0~~99999|
2228 |Bit|EM3|EM3|EM3 d|0~~99999|
2229 |Bit|EM4|EM4|EM4 d|0~~99999|
2230 |Bit|EM5|EM5|EM5 h|0~~99999|
2231 |Bit|EM6|EM6|EM6 d|0~~99999|
2232 |Bit|EM7|EM7|EM7 d|0~~99999|
2233 |Bit|EM8|EM8|EM8 d|0~~99999|
2234 |Bit|EM9|EM9|EM9 d|0~~99999|
2235 |Bit|EMA|EMA|EMA d|0~~99999|
2236 |Bit|EMB|EMB|EMB d|0~~99999|
2237 |Bit|EMC|EMC|EMC d|0~~99999|
2238 |Bit|Lamp|Lamp|Lamp d|0~~0|
2239 |Word|CIO|CIO|CIO d|0~~99999|
2240 |Word|W|W|W d|0~~99999|
2241 |Word|D|D|D d|0~~99999|
2242 |Word|H|H|H d|0~~99999|
2243 |Word|A|A|A d|0~~99999|
2244 |Word|T|T|T h|0~~99999|
2245 |Word|CF|CF|CF d|0~~99999|
2246 |Word|FF|FF|FF d|0~~99999|
2247 |Word|C|C|C d|0~~99999|
2248 |Word|EM0|EM0|EM0 d|0~~99999|
2249 |Word|EM1|EM1|EM1 d|0~~99999|
2250 |Word|EM2|EM2|EM2 d|0~~99999|
2251 |Word|EM3|EM3|EM3 d|0~~99999|
2252 |Word|EM4|EM4|EM4 d|0~~99999|
2253 |Word|EM5|EM5|EM5 h|0~~99999|
2254 |Word|EM6|EM6|EM6 d|0~~99999|
2255 |Word|EM7|EM7|EM7 d|0~~99999|
2256 |Word|EM8|EM8|EM8 d|0~~99999|
2257 |Word|EM9|EM9|EM9 d|0~~99999|
2258 |Word|EMA|EMA|EMA d|0~~99999|
2259 |Word|EMB|EMB|EMB d|0~~99999|
2260 |Word|EMC|EMC|EMC d|0~~99999|
2261 |Word|IR|IR|IR d|0~~99999|
2262 |Word|DR|DR|DR d|0~~99999|
2263
2264 **Configure the communication protocol**
2265
2266 (% style="text-align:center" %)
2267 [[image:image-20220830143348-1.png]]
2268
2269 (% style="text-align:center" %)
2270 [[image:image-20220830143511-2.png]]
2271
2272 **Configure CJ1W-EIP21 connect with HMI**
2273
2274 (% style="text-align:center" %)
2275 [[image:ftEVGvAprh.png]]
2276
2277 Select TCP_Client_2N
2278
2279 (% style="text-align:center" %)
2280 [[image:RURXWcgyCd.png]]
2281
2282 **Cable Wiring**
2283
2284 Pin Definition Diagram
2285
2286 (% style="text-align:center" %)
2287 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2288
2289 == **CP1E/CP1H serial protocol** ==
2290
2291 Supported device: OMRON CS1(CP1E/CP1H)
2292
2293 **HMI Settings**
2294
2295 |=**Items**|=**Settings**|=**Note**
2296 |Protocol|OMRON CS1(CP1E/CP1H)|
2297 |Connection|RS232 (9600, 2, 7, EVEN)|
2298 |Port No.|None|
2299 |PLC station No.|0|
2300
2301 **Address List**
2302
2303 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2304 |Bit|CIO|CIO|CIO d|0~~99999|
2305 |Bit|W|W|W d|0~~99999|
2306 |Bit|D|D|D d|0~~99999|
2307 |Bit|H|H|H d|0~~99999|
2308 |Bit|A|A|A d|0~~99999|
2309 |Bit|TF|T|T h|0~~99999|
2310 |Bit|CF|CF|CF d|0~~99999|
2311 |Bit|T|FF|FF d|0~~99999|
2312 |Bit|C|C|C d|0~~99999|
2313 |Bit|EM0|EM0|EM0 d|0~~99999|
2314 |Bit|EM1|EM1|EM1 d|0~~99999|
2315 |Bit|EM2|EM2|EM2 d|0~~99999|
2316 |Bit|EM3|EM3|EM3 d|0~~99999|
2317 |Bit|EM4|EM4|EM4 d|0~~99999|
2318 |Bit|EM5|EM5|EM5 h|0~~99999|
2319 |Bit|EM6|EM6|EM6 d|0~~99999|
2320 |Bit|EM7|EM7|EM7 d|0~~99999|
2321 |Bit|EM8|EM8|EM8 d|0~~99999|
2322 |Bit|EM9|EM9|EM9 d|0~~99999|
2323 |Bit|EMA|EMA|EMA d|0~~99999|
2324 |Bit|EMB|EMB|EMB d|0~~99999|
2325 |Bit|EMC|EMC|EMC d|0~~99999|
2326 |Word|CIO|CIO|CIO d|0~~99999|
2327 |Word|W|W|W d|0~~99999|
2328 |Word|D|D|D d|0~~99999|
2329 |Word|H|H|H d|0~~99999|
2330 |Word|A|A|A d|0~~99999|
2331 |Word|T|T|T h|0~~99999|
2332 |Word|CIO|CF|CF d|0~~99999|
2333 |Word|C|C|C d|0~~99999|
2334 |Word|EM0|EM0|EM0 d|0~~99999|
2335 |Word|EM1|EM1|EM1 d|0~~99999|
2336 |Word|EM2|EM2|EM2 d|0~~99999|
2337 |Word|EM3|EM3|EM3 d|0~~99999|
2338 |Word|EM4|EM4|EM4 d|0~~99999|
2339 |Word|EM5|EM5|EM5 h|0~~99999|
2340 |Word|EM6|EM6|EM6 d|0~~99999|
2341 |Word|EM7|EM7|EM7 d|0~~99999|
2342 |Word|EM8|EM8|EM8 d|0~~99999|
2343 |Word|EM9|EM9|EM9 d|0~~99999|
2344 |Word|EMA|EMA|EMA d|0~~99999|
2345 |Word|EMB|EMB|EMB d|0~~99999|
2346 |Word|EMC|EMC|EMC d|0~~99999|
2347 |Word|IR|IR|IR d|0~~99999|
2348 |Word|DR|DR|DR d|0~~99999|
2349
2350 **Configure the communication protocol**
2351
2352 (% style="text-align:center" %)
2353 [[image:image-20220902153118-1.png]]
2354
2355 (% style="text-align:center" %)
2356 [[image:image-20220902151322-2.png]]
2357
2358 **Cable Wiring**
2359
2360 (% style="text-align:center" %)
2361 [[image:image-20220902153949-2.png]]
2362
2363 Pin Definition Diagram
2364
2365 (% style="text-align:center" %)
2366 [[image:image-20220902154056-3.png]]
2367
2368 == **EC55 Protocol** ==
2369
2370 Supported device: EC55 temperature instrument
2371
2372 **1)HMI Settings**
2373
2374 |**Items**|**Settings**|**Note**
2375 |Protocol|Omron EC55|
2376 |Connection|RS485 (9600, 2, 7, EVEN)|
2377 |Port No.|None|
2378 |PLC station No.|0|
2379
2380 **2)Address List**
2381
2382 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2383 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2384 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2385 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2386 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2387 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2388 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2389 |CP|-|0-6|Read controller intrinsic property
2390 |CS|-|0-2|Read controller states
2391 |CA|-|0-17|Action command
2392
2393 **3)Device Settings**
2394
2395 Omron E5CC PLC configuration
2396
2397 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2398
2399 (% style="text-align:center" %)
2400 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2401
2402 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2403
2404 (% style="text-align:center" %)
2405 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2406
2407 **✎Note:** The communication settings for HMI should be consistent with this setting.
2408
2409 **Cable Wiring**
2410
2411 (% style="text-align:center" %)
2412 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2413
2414 (% style="text-align:center" %)
2415 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2416
2417 **✎Note:**
2418
2419 * COM3 only available in PI8000/PI9000 series.
2420 * CA address could not support continuous writing function;
2421 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2422 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2423 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2424 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2425 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2426 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2427 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2428
2429 == **EtherNet/IP NX series Protocol** ==
2430
2431 Supported series: Omron NX/NJ series
2432
2433 **HMI Setting**
2434
2435 |**Items**|**Settings**|**Note**
2436 |Protocol|Omron NX Ethernet/IP|
2437 |Connection|Ethernet|
2438 |Port No.|44818|
2439 |PLC station No.|1|
2440
2441 **Instruction**
2442
2443 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2444
2445 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2446
2447 (% style="text-align:center" %)
2448 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2449
2450 **Export labels from Sysmac Studio**
2451
2452 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2453
2454 (% style="text-align:center" %)
2455 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2456
2457 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2458
2459 Click [Label manage];
2460
2461 (% style="text-align:center" %)
2462 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2463
2464 Click [Import labels] and then select the file exported in step 1;
2465
2466 (% style="text-align:center" %)
2467 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2468
2469 The Import Status field shows the result, click [OK] to finish importing address labels;
2470
2471 (% style="text-align:center" %)
2472 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2473
2474 **Communication Settings**
2475
2476 Enable HMI Ethernet in [Project Settings];
2477
2478 (% style="text-align:center" %)
2479 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2480
2481 Set PLC IP in [Device IP] settings;
2482
2483 (% style="text-align:center" %)
2484 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2485
2486 (% style="text-align:center" %)
2487 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2488
2489 **Cable Wiring**
2490
2491 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2492
2493 == CV/CJ1M/CS1H ==
2494
2495 **HMI Setting:**
2496
2497 |=**Parameters**|=**Recommended**
2498 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2499 |=**PLC I/F**|RS232
2500 |=**Baud rate**|9600
2501 |=**Data bits**|7
2502 |=**Parity**|Even
2503 |=**Stop bits**|2
2504 |=**PLC sta. no.**|0
2505
2506 **PLC Setting:**
2507
2508 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2509
2510 **Device Address:**
2511
2512 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2513 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2514 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2515 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2516 |=B|H|DDDDdd|0 ~~ 409515|
2517 |=B|A|DDDDdd|0 ~~ 409515|
2518 |=B|TF|DDDDdd|0 ~~ 409515|
2519 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2520 |=B|T|DDDD|0 ~~ 4095|
2521 |=B|C|DDDD|0 ~~ 4095|
2522 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2523 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2524 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2525 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2526 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2527 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2528 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2529 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2530 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2531 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2532 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2533 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2534 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2535 |=B|Lamp|D|0~~0|
2536
2537 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2538 |=W|LR_W|DDDD|0 ~~ 4095|
2539 |=W|TC|DDD|0 ~~ 511|
2540 |=W|DM|DDDD|0 ~~ 9999|Data Register
2541
2542 **Wiring Diagram:**
2543
2544 **RS-232**
2545
2546 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2547
2548 Communication Module:
2549
2550 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2551
2552 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2553
2554 (% style="text-align:center" %)
2555 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2556
2557 = Create communication with **Rockwell PLC** =
2558
2559 == **DF1 Protocol** ==
2560
2561 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2562
2563 **HMI Settings**
2564
2565 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2566 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2567 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2568 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2569 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2570 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2571 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2572 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2573 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2574
2575 **PLC Settings**
2576
2577 DF1 Full Duplex protocol and CRC error check
2578
2579 **Address List**
2580
2581 (% class="table-bordered" %)
2582 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2583 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2584 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2585 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2586 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2587 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2588 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2589 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2590 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2591 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2592 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2593 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2594
2595 **Cable Wiring**
2596
2597 (% style="text-align:center" %)
2598 [[image:AB.gif]]
2599
2600 == **DF1 Advanced Protocol** ==
2601
2602 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2603
2604 **HMI Settings**
2605
2606 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2607 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2608 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2609 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2610 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2611 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2612 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2613 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2614 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2615
2616 **PLC Settings**
2617
2618 DF1 Full Duplex protocol and CRC error check
2619
2620 **Address List**
2621
2622 (% class="table-bordered" %)
2623 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2624 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2625 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2626 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2627 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2628 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2629 Bit data file B0~~B99
2630
2631 First two digits is for file number
2632
2633 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2634 )))
2635 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2636 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2637 Integer data file bit format N0~~N99
2638
2639 First two digits is for file number
2640
2641 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2642 )))
2643 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2644 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2645 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2646 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2647 Timer Preset Value
2648
2649 First two digits is for file number
2650
2651 For example, TNS99255 represents file number T99, address 255.
2652 )))
2653 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2654 Timer Accumulator Value
2655
2656 First two digits is for file number
2657
2658 For example, TNP99255 represents file number T99, address 255.
2659 )))
2660 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2661 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2662 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2663 Counter Preset Value
2664
2665 First two digits is for file number
2666
2667 For example, CNS99255 represents file number C99, address 255.
2668 )))
2669 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2670 Counter Accumulator Value
2671
2672 First two digits is for file number
2673
2674 For example, CNP99255 represents file number C99, address 255.
2675 )))
2676 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2677 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2678 Integer data file
2679
2680 First two digits is for file number
2681
2682 For example, NN99255 represents file number N99, address 255.
2683 )))
2684 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2685 Only able to communicate with file number F8
2686 )))
2687 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2688 Floating point data file
2689
2690 First two digits is for file number
2691
2692 For example, FN99255 represents file number F99, address 255.
2693 )))
2694 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2695
2696 **Cable Wiring**
2697
2698 (% style="text-align:center" %)
2699 [[image:AB.gif]]
2700
2701 == **MicroLogix Protocol** ==
2702
2703 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2704
2705 **HMI Settings**
2706
2707 (% class="table-bordered" %)
2708 |**Item**|**Settings**|**Note**
2709 |Protocol|Allen-Bradlley MicroLogix|
2710 |Connection|RS232|
2711 |Baud rate|19200|
2712 |Data bit|8|
2713 |Parity|None|
2714 |Stop bit|1|
2715 |PLC station No.|1|
2716
2717 **Address List**
2718
2719 (% class="table-bordered" %)
2720 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2721 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2722 |O|O d.d|0.0~~255.15|
2723 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2724 |S|S d.d|0.0~~255.15|
2725 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2726 |(% rowspan="9" %)Word|S|S d|0~~255|
2727 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2728 |TP|TP nnhh|0~~ffff
2729 |CS|CS nnhh|0~~ffff
2730 |CP|CP nnhh|0~~ffff
2731 |N|N nnhh|0~~ffff
2732 |C|C nnhh|0~~ffff
2733 |T|T nnhh|0~~ffff
2734 |R|R nnhh|0~~ffff
2735
2736 **Cable Wiring**
2737
2738 (% style="text-align:center" %)
2739 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2740
2741 == **CompactLogix FreeTag Ethernet protocol** ==
2742
2743 Allen-Brandly CompactLogix
2744
2745 **HMI Settings**
2746
2747 (% class="table-bordered" %)
2748 |**Items**|**Settings**|**Note**
2749 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2750 |Connection|Ethernet|
2751 |Port No.|44818|
2752
2753 **PLC Setting**
2754
2755 Create new tags
2756
2757 (% style="text-align:center" %)
2758 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2759
2760 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2761
2762 (% style="text-align:center" %)
2763 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2764
2765 Import labels, please open [Communication] window and click [Import label];
2766
2767 Select csv file, all tags will be displayed as belows;
2768
2769 (% style="text-align:center" %)
2770 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2771
2772 **✎Note:**
2773
2774 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2775
2776 (% style="text-align:center" %)
2777 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2778
2779 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2780
2781 **Communication settings in HMI**
2782
2783 Enable HMI Ethernet in [Project Settings];
2784
2785 (% style="text-align:center" %)
2786 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2787
2788 Set PLC IP in [Device IP] settings;
2789
2790 (% style="text-align:center" %)
2791 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2792
2793 **Cable Wiring**
2794
2795 (% style="text-align:center" %)
2796 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2797
2798 == **MicroLogix 1200** **protocol** ==
2799
2800 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2801
2802 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2803 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2804 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2805 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2806
2807 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2808
2809 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2810 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2811 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2812 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2813 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2814 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2815 |**PLC word address type**|**Address format**|**Address range**
2816 |S|ddd|S0 ~~ 255
2817 |TS|ffff|TS0 ~~ FFFF
2818 |TP|ffff|TP0 ~~ FFFF
2819 |CS|ffff|CS0 ~~ FFFF
2820 |CP|ffff|CP0 ~~ FFFF
2821 |N|ffff|N0 ~~ FFFF
2822 |F|ffff|F0 ~~ FFFF
2823
2824 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2825
2826 == **S7-200 Smart Ethernet Protocol** ==
2827
2828 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2829
2830 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2831
2832 **HMI Setting**
2833
2834 (% class="table-bordered" %)
2835 |**Items**|**Settings**|**Note**
2836 |Protocol|Simens S7-200 Smart Ethernet|
2837 |Connection|Ethernet|
2838 |Port No.|102|
2839 |PLC station No.|2|
2840
2841 **Address List**
2842
2843 (% class="table-bordered" %)
2844 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2845 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2846 |Q|Q|Q ddddd.o|0.0~~99999.7|
2847 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2848 |V|V|V ddddd.o|0.0~~99999.7|
2849 |M|M|M ddddd.o|0.0~~99999.7|
2850 |SM|SM|ddddd.o|0.0~~99999.7|
2851 |S|S|ddddd.o|0.0~~99999.7|Read only
2852 |T|T|ddddd|0~~99999|Timer state, read only
2853 |C|C|ddddd|0~~99999|Counter state, read only
2854 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2855 |Q|QW|QW ddddd|0~~99999|
2856 |AI|AIW|AIW ddddd|0~~99999|
2857 |AQ|VB|VB ddddd|0~~99999|
2858 |V|VW|VW ddddd|0~~99998|(((
2859 VW0=VB (0~~1)
2860
2861 VW2=VB (2~~3)
2862
2863 Address value is a multiple of 2
2864 )))
2865 |V|VD|VD ddddd|0~~99998|(((
2866 VD0=VB (0~~3)
2867
2868 VD2=VB (4~~7)
2869
2870 Address value is a multiple of 4
2871 )))
2872 |M|MB|MB ddddd|0~~99999|
2873 |M|MW|MW ddddd|0~~99999|(((
2874 MW0=MB(0~~1)
2875
2876 MW2=MB(2~~3)
2877
2878 Address value is a multiple of 2
2879 )))
2880 |M|MD|MD ddddd|0~~99999|(((
2881 MD0=MB(0~~3)
2882
2883 MD4=MB(4~~7)
2884
2885 Address value is a multiple of 4
2886 )))
2887 |T|TW|TW ddddd|0~~99999|Value of timer
2888 |C|CW|CW ddddd|0~~99999|Value of counter
2889 |W|SW|SW ddddd|0~~99999|
2890
2891 **Communication Settings**
2892
2893 Enable HMI Ethernet in [Project Settings];
2894
2895 (% style="text-align:center" %)
2896 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2897
2898 Set PLC IP in [Device IP] settings;
2899
2900 (% style="text-align:center" %)
2901 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2902
2903 * PLC IP Address: PLC IP
2904 * PLC pot No.: 102(fixed)
2905 * Network:TCP_Client_2N(fixed)
2906
2907 (% style="text-align:center" %)
2908 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2909
2910 * Wait timeout: depend on actual network situation (more than 1500 ms)
2911
2912 **Cable Wiring**
2913
2914 (% style="text-align:center" %)
2915 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2916
2917 == **S7-300 Ethernet Protocol** ==
2918
2919 Supported Series: Siemens S7-300 series PLC
2920
2921 **HMI Setting**
2922
2923 (% class="table-bordered" %)
2924 |**Items**|**Settings**|**Note**
2925 |Protocol|Simens S7-300 Ethernet|
2926 |Connection|Ethernet|
2927 |Port No.|102|
2928 |PLC station No.|2|Need to be same as the PLC setting
2929
2930 **Address List**
2931
2932 (% class="table-bordered" %)
2933 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2934 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2935 |Q|Q|Q ddddd.o|0.0~~99999.7|
2936 |M|M|M ddddd.o|0.0~~99999.7|
2937 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2938 nnnn: block number;
2939
2940 dddd: address;
2941 )))
2942 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2943 |Q|QW|QW ddddd|0~~99999|
2944 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2945 |MW|MW ddddd|0~~99999|(((
2946 MW0=MB(0~~1)
2947
2948 MW2=MB(2~~3)
2949
2950 Address value is a multiple of 2
2951 )))
2952 |MD|MD ddddd|0~~99999|(((
2953 MD0=MB(0~~3)
2954
2955 MD4=MB(4~~7)
2956
2957 Address value is a multiple of 4
2958 )))
2959 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2960 nnnn: block number;
2961
2962 dddd: address
2963 )))
2964 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2965 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2966
2967 **Communication Settings**
2968
2969 Enable HMI Ethernet in [Project Settings];
2970
2971 (% style="text-align:center" %)
2972 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2973
2974 Set PLC IP in [Device IP] settings;
2975
2976 (% style="text-align:center" %)
2977 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2978
2979 * PLC IP Address: PLC IP
2980 * PLC pot No.: 102(fixed)
2981 * Network:TCP_Client_2N(fixed)
2982
2983 (% style="text-align:center" %)
2984 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2985
2986 * Wait timeout: depend on actual network situation (more than 1500 ms)
2987
2988 **Cable Wiring**
2989
2990 (% style="text-align:center" %)
2991 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2992
2993 == **S7-1200 Ethernet Protocol** ==
2994
2995 Supported Series: Siemens S7-1200
2996
2997 **HMI Setting**
2998
2999 (% class="table-bordered" %)
3000 |**Items**|**Settings**|**Note**
3001 |Protocol|Siemens S7-1200|
3002 |Connection|Ethernet|
3003 |Port No.|102|
3004 |PLC station No.|2|
3005
3006 **Address List**
3007
3008 (% class="table-bordered" %)
3009 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3010 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3011 d:0~-~-9999
3012
3013 o:0-7
3014 )))|
3015 |Q|Q|Q d.o|(((
3016 d:0~-~-9999
3017
3018 o:0-7
3019 )))|
3020 |M|M|M d.o|(((
3021 d:0~-~-9999
3022
3023 o:0-7
3024 )))|
3025 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3026 nn:0-9999,
3027
3028 dddd:0-9999,
3029
3030 o:0-7
3031 )))|(((
3032 nn:DB No.
3033
3034 dddd:address value
3035
3036 o: digit address
3037 )))
3038 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3039 |M|MW|MW d|d:0-99999|(((
3040 MW0=MB(0~~1)
3041
3042 MW2=MB(2~~3)
3043
3044 Address value is a multiple of 2
3045 )))
3046 |M|MD|MD d|d:0-99999|(((
3047 MD0=MB(0~~3)
3048
3049 MD4=MB(4~~7)
3050
3051 Address value is a multiple of 4
3052 )))
3053 |I|IW|IW d|d:0-99999|
3054 |Q|QW|QW d|d:0-99999|
3055 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3056 nn:0-9999
3057
3058 dddd:0-9999
3059 )))|(((
3060 nn:DB No.
3061
3062 dddd:address value
3063 )))
3064 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3065 nn:0-9999
3066
3067 dddd:0-9999
3068 )))|(((
3069 nn:DB No.
3070
3071 dddd:address value
3072
3073 Address value is a multiple of 2
3074 )))
3075 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3076 nn:0-9999
3077
3078 dddd:0-9999
3079 )))|(((
3080 nn:DB No.
3081
3082 dddd:address value
3083
3084 Address value is a multiple of 4
3085 )))
3086
3087 **Communication Settings**
3088
3089 Enable HMI Ethernet in [Project Settings];
3090
3091 (% style="text-align:center" %)
3092 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3093
3094 Set PLC IP in [Device IP] settings;
3095
3096 (% style="text-align:center" %)
3097 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3098
3099 **✎Note:**
3100
3101 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3102 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3103 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3104 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3105
3106 **PLC Settings**
3107
3108 Add BD
3109
3110 * Please uncheck [Symbolic access only] option;
3111
3112 (% style="text-align:center" %)
3113 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3114
3115 Address settings, using BD2 as example.
3116
3117 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3118 * 2 represent DB block number
3119 * xxxx represent address
3120
3121 **Such as:**
3122
3123 * DBxDBB20000 = DB2.DBB0
3124 * DBxDBW20004 = DB2.DBW4
3125
3126 (% style="text-align:center" %)
3127 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3128
3129 **How to connect with S7-1200 Firmware V4.0**
3130
3131 PLC configuration
3132
3133 * Double click [device configuration] in Siemens via software
3134 * Double click [protection] to enter protection configuration screen
3135
3136 (% style="text-align:center" %)
3137 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3138
3139 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3140
3141 (% style="text-align:center" %)
3142 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3143
3144 DB settings
3145
3146 * Right click [DB], select [properties]
3147 * Uncheck [optimized block access]
3148
3149 **Cable Wiring**
3150
3151 (% style="text-align:center" %)
3152 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3153
3154 == **S7-XXX Ethernet Protocol** ==
3155
3156 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3157
3158 **HMI Setting**
3159
3160 (% class="table-bordered" style="width:823px" %)
3161 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3162 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3163 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3164 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3165 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3166 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3167
3168 Slot from TIA Portal is equal to Device No. of PIStudio
3169
3170 Rack from TIA Portal is equal to HMI No. of PIStudio
3171
3172 (% style="text-align:center" %)
3173 [[image:S7-XXXCommunication Settings.png]]
3174
3175 (% style="text-align:center" %)
3176 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3177
3178 **Address List**
3179
3180 (% class="table-bordered" %)
3181 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3182 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3183 d:0~-~-9999
3184
3185 o:0-7
3186 )))|
3187 |Q|Q|Q d.o|(((
3188 d:0~-~-9999
3189
3190 o:0-7
3191 )))|
3192 |M|M|M d.o|(((
3193 d:0~-~-9999
3194
3195 o:0-7
3196 )))|
3197 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3198 nn:0-9999,
3199
3200 dddd:0-9999,
3201
3202 o:0-7
3203 )))|(((
3204 nn:DB No.
3205
3206 dddd:address value
3207
3208 o: digit address
3209 )))
3210 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3211 |M|MW|MW d|d:0-99999|(((
3212 MW0=MB(0~~1)
3213
3214 MW2=MB(2~~3)
3215
3216 Address value is a multiple of 2
3217 )))
3218 |M|MD|MD d|d:0-99999|(((
3219 MD0=MB(0~~3)
3220
3221 MD4=MB(4~~7)
3222
3223 Address value is a multiple of 4
3224 )))
3225 |I|IW|IW d|d:0-99999|
3226 |Q|QW|QW d|d:0-99999|
3227 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3228 nn:0-9999
3229
3230 dddd:0-9999
3231 )))|(((
3232 nn:DB No.
3233
3234 dddd:address value
3235 )))
3236 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3237 nn:0-9999
3238
3239 dddd:0-9999
3240 )))|(((
3241 nn:DB No.
3242
3243 dddd:address value
3244
3245 Address value is a multiple of 2
3246 )))
3247 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3248 nn:0-9999
3249
3250 dddd:0-9999
3251 )))|(((
3252 nn:DB No.
3253
3254 dddd:address value
3255
3256 Address value is a multiple of 4
3257 )))
3258
3259 **Communication Settings**
3260
3261 Enable HMI Ethernet in [Project Settings];
3262
3263 (% style="text-align:center" %)
3264 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3265
3266 Set PLC IP in [Device IP] settings;
3267
3268 (% style="text-align:center" %)
3269 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3270
3271 **✎Note:**
3272
3273 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3274 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3275
3276 **Cable Wiring**
3277
3278 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3279
3280 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3281
3282 Supported Series: Siemens Logo 0BA0, 0BA1 series
3283
3284 **HMI Settings**
3285
3286 (% class="table-bordered" %)
3287 |**Items**|**Settings**|**Note**
3288 |Protocol|Siemens LOGO|
3289 |Connection|Ethernet|
3290 |Port No.|102|
3291 |PLC station No.|2|
3292
3293 **Address List**
3294
3295 (% class="table-bordered" %)
3296 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3297 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3298 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3299 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3300 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3301 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3302 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3303 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3304 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3305 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3306 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3307 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3308 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3309 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3310 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3311 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3312
3313 **PLC Settings in LOGO Software:**
3314
3315 Click [Tools]~-~-[Ethernet Connections],shown as below.
3316
3317 (% style="text-align:center" %)
3318 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3319
3320 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3321
3322 (% style="text-align:center" %)
3323 [[image:image-20221228142937-4.png]]
3324
3325 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3326
3327 (% style="text-align:center" %)
3328 [[image:image-20221228143047-5.png]]
3329
3330 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3331
3332 (% style="text-align:center" %)
3333 [[image:image-20221228143246-6.png]]
3334
3335
3336 **HMI Communication Settings**
3337
3338 Set PLC IP in [Device IP] settings;
3339
3340 (% style="text-align:center" %)
3341 [[image:image-20221228143614-7.png]]
3342
3343 Enable HMI Ethernet in [Project Settings];
3344
3345 (% style="text-align:center" %)
3346 [[image:image-20221228144229-9.png]]
3347
3348 TSAP setting
3349
3350 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3351 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3352 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3353 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3354 ie, ig series: use HSW1200, HSW1201.
3355 HMI V2.0: use HSW1200, HSW1201.
3356
3357 **✎Note:**
3358
3359 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3360 * HSW10119/HSW1201 is set up as shown.
3361 * (((
3362 (% style="text-align:center" %)
3363 [[image:image-20221228144800-11.png]]
3364 )))
3365 * (((
3366 (% style="text-align:center" %)
3367 [[image:image-20221228144708-10.png]]
3368 )))
3369
3370 * AI word address and Ibit address are read-only and cannot be written on HMI.
3371 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3372 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3373 * Written value of RTC cannot exceed 255.
3374
3375 **Cable Wiring**
3376
3377 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3378
3379 == S7-300 232 ==
3380
3381 **HMI Setting:**
3382
3383 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3384 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3385 |=**PLC I/F**|RS232| |
3386 |=**Baud rate**|19200|9600,19200|
3387 |=**Data bits**|8| |
3388 |=**Parity**|Odd| |
3389 |=**Stop bits**|1| |
3390 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3391
3392 **Device Address**
3393
3394 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3395 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3396 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3397 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3398 |=Word|(((
3399 DB1 to DB99
3400 )))|DDDDDo|0 ~~ 655327|
3401 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3402 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3403 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3404 |=Double word|MD|DDDD|0 ~~ 4094|
3405 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3406 Data Register Double Word (must be even)
3407 )))
3408 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3409
3410 **Cable Wiring**
3411
3412 (% style="text-align:center" %)
3413 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3414
3415 = Create communication with Xinje** PLC** =
3416
3417 == XC serial protocol ==
3418
3419 **HMI Settings**
3420
3421 |**Item**|**Settings**|**Note**
3422 |Protocol|XINJE XC MODBUS|
3423 |Connection|RS232|
3424 |Baud rate|19200|
3425 |Data bit|8|
3426 |Parity|EVEN|
3427 |Stop bit|1|
3428 |PLC station No.|1|
3429
3430 **Address List**
3431
3432 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3433 |Bit|M|M|M d|0~~8511|
3434 |Bit|X|X|X o|0~~1747|
3435 |Bit|Y|Y|Y o|0~~1747|
3436 |Bit|S|S|S d|0~~1023|
3437 |Bit|T|T|T d|0~~4095|
3438 |Bit|C|C|C d|0~~634|
3439 |Word|D|D|D d|0~~8511|
3440 |Word|TD|TD|TD d|0~~618|
3441 |Word|CD|CD|CD d|0~~634|
3442 |Word|FD|FD|FD d|0~~8511|
3443
3444 **Configure the communication protocol**
3445
3446 (% style="text-align:center" %)
3447 [[image:image-20220830154105-1.png]]
3448
3449 (% style="text-align:center" %)
3450 [[image:image-20220830154159-3.png]]
3451
3452 **Cable Wiring**
3453
3454 Figure
3455
3456 [[image:image-20220830155728-4.png]]
3457
3458 Pin Definition Diagram
3459
3460 (% style="text-align:center" %)
3461 [[image:image-20220830154131-2.png]]
3462
3463 == XD serial protocol ==
3464
3465 **HMI Settings**
3466
3467 Supported Series: Xinjie XD/XE Series PLC
3468
3469 |=**Item**|=**Settings**|=**Note**
3470 |Protocol|XINJE XD/XC MODBUS|
3471 |Connection|RS232|
3472 |Baud rate|19200|
3473 |Data bit|8|
3474 |Parity|EVEN|
3475 |Stop bit|1|
3476 |PLC station No.|1|
3477
3478 **Address List**
3479
3480 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3481 |Bit|M|M|M d|0~~74999|
3482 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3483 |Bit|X2xx|X2xx|X2xx o|0~~277|
3484 |Bit|X|X|X o|0~~77|
3485 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3486 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3487 |Bit|Y|Y|Y o|0~~4095|
3488 |Bit|SM|SM|SM d|0~~4999|(((
3489
3490 )))
3491 |Bit|T|T|T d|0~~4999|
3492 |Bit|C|C|C d|0~~4999|
3493 |Bit|ET|ET|ET d|0~~31|
3494 |Bit|SE|SE|SE d|0~~31|
3495 |Bit|HM|HM|HM d|0~~11999|
3496 |Bit|HSC|HSC|HSC d|0~~39|
3497 |Bit|HS|HS|HS d|0~~999|
3498 |Bit|HT|HT|HT d|0~~1999|
3499 |Bit|HC|HC|HC d|0~~1999|
3500 |Bit|S|S|S d|0~~7999|
3501 |Word|D|D|D d|0~~69999|
3502 |Word|ID|ID|ID d|0~~99|
3503 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3504 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3505 |Word|QD|QD|QD d|0~~99|
3506 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3507 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3508 |Word|SD|SD|SD d|0~~4999|
3509 |Word|TD|TD|TD d|0~~575|
3510 |Word|CD|CD|CD d|0~~575|
3511 |Word|ETD|ETD|ETD d|0~~31|
3512 |Word|HD|HD|HD d|0~~24999|
3513 |Word|HSD|HSD|HSD d|0~~1023|
3514 |Word|HTD|HTD|HTD d|0~~95|
3515 |Word|HCD|HCD|HCD d|0~~95|
3516 |Word|HSCD|HSCD|HSCD d|0~~31|
3517 |Word|FD|FD|FD d|0~~8191|
3518 |Word|SFD|SFD|SFD d|0~~5999|
3519 |Word|FS|FS|FS d|0~~47|
3520
3521 **Configure the communication protocol**
3522
3523 (% style="text-align:center" %)
3524 [[image:image-20220830160042-1.png]]
3525
3526 (% style="text-align:center" %)
3527 [[image:image-20220830160129-2.png]]
3528
3529 **Cable Wiring**
3530
3531 (% style="text-align:center" %)
3532 [[image:image-20220905093902-1.png]]
3533
3534 Pin Definition Diagram
3535
3536 (% style="text-align:center" %)
3537 [[image:image-20220830160232-3.png]]
3538
3539 = Create communication with Panasonic** PLC** =
3540
3541 == **FP serial protocol** ==
3542
3543 **1)HMI Settings**
3544
3545 |**Item**|**Settings**|**Note**
3546 |Protocol|Panasonic FP MFWTOCOL|
3547 |Connection|RS232|
3548 |Baud rate|9600|
3549 |Data bit|8|
3550 |Parity|ODD|
3551 |Stop bit|1|
3552 |PLC station No.|1|
3553
3554 **2)Address List**
3555
3556 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3557 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3558 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3559 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3560 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3561 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3562 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3563 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3564 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3565 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3566 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3567 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3568 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3569 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3570 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3571 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3572
3573 **3)Configure the communication protocol**
3574
3575 [[image:image-20220830171050-1.png]]
3576
3577 [[image:image-20220830171126-2.png]]
3578
3579 **4)Cable Wiring**
3580
3581 Figure
3582
3583 [[image:image-20220830171328-4.png]]
3584
3585 Pin Definition Diagram
3586
3587 [[image:image-20220830171146-3.png]]
3588
3589 = Create communication with **SHIMADEN PLC** =
3590
3591 == **FP23 series protocol** ==
3592
3593 Supported series: SHIMADEN FP23 series
3594
3595 **HMI Setting**
3596
3597 |**Items**|**Settings**|**Note**
3598 |Protocol|SHIMADEN FP23 series|
3599 |Connection|RS485 (9600, 1, 7, EVEN)|
3600 |Port No.|None|
3601 |PLC station No.|0|
3602
3603 **Address List**
3604
3605 |**Device address**|**HMI register**|**Address range**|**Type**
3606 |0040-0043(HEX)|FP040|100064-200067|Read only
3607 |0100-010B(HEX)|FP100|100256-200267|Read only
3608 |0110-0142(HEX)|FP110|100272-200322|Read only
3609 |0182-0252(HEX)|FP182|100386-200594|Write only
3610 |0280-0281(HEX)|FP280|100640-200641|Read only
3611 |0300-030B(HEX)|FP300|100768-200779|Read and write
3612 |0380-039F(HEX)|FP380|100896-200927|Read and write
3613 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3614 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3615 |0600-0670(HEX)|FP600|101536-201814|Read and write
3616 |0720-0738(HEX)|FP720|101824-201848|Read and write
3617 |0800-083F(HEX)|FP800|102048-202111|Read and write
3618 |0900-0952(HEX)|FP900|102304-202386|Read and write
3619 | |Ctrl|0-2|
3620
3621 **✎Note:**
3622
3623 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3624 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3625 * The Ctrl register is used to store the control group number and BCC check mode.
3626
3627 **Ctrl Register Description**
3628
3629 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3630 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3631 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3632 * Ctrl3 reserved
3633
3634 **✎Note:**
3635
3636 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3637
3638 **Cable Wiring**
3639
3640 (% style="text-align:center" %)
3641 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3642
3643 (% style="text-align:center" %)
3644 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3645
3646 **✎Note:** COM3 only available in PI8000/PI9000 series.
3647
3648 == **SR90 protocol** ==
3649
3650 Supported series: SHIMADEN SR90 series
3651
3652 **HMI Setting**
3653
3654 |**Items**|**Settings**|**Note**
3655 |Protocol|SHIMADEN SR90 protocol|
3656 |Connection|RS485 (1200, 1, 7, EVEN)|
3657 |Port No.|None|
3658 |PLC station No.|0|
3659
3660 **Address List**
3661
3662 |**Device address**|**HMI register**|**Address range**|**Type**
3663 |0040-0043 (HEX)|SR040|100064-100067|Read only
3664 |0100-010A(HEX)|SR0100|100256-100266|Read only
3665 |0182-018C(HEX)|SR0182|100386-100396|Write only
3666 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3667 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3668 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3669 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3670 | |Ctrl|0-2|~-~-
3671
3672 **✎Note:**
3673
3674 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3675 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3676 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3677
3678 **Ctrl Register Description**
3679
3680 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3681 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3682 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3683 * Ctrl3 reserved
3684
3685 **✎Note:**
3686
3687 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3688
3689 **Cable Wiring**
3690
3691 (% style="text-align:center" %)
3692 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3693
3694 (% style="text-align:center" %)
3695 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3696
3697 **✎Note:** COM3 only available in PI8000/PI9000 series.
3698
3699 == **MR13 series(standard protocol)** ==
3700
3701 Supported series: SHIMADEN MR13 series
3702
3703 **HMI Setting**
3704
3705 |**Items**|**Settings**|**Note**
3706 |Protocol|SHIMADEN standard protocol|
3707 |Connection|RS485 (1200, 1, 7, EVEN)|
3708 |Port No.|None|
3709 |PLC station No.|0|
3710
3711 **Address List**
3712
3713 |**Device address**|**HMI register**|**Address range**|**Type**
3714 |0100-010B(HEX)|MR100|100256-300267|Read only
3715 |0111-0126(HEX)|MR111|100273-300294|Read only
3716 |0184-0192(HEX)|MR184|100388-300402|Write only
3717 |0280-0282(HEX)|MR280|100640-300642|Read only
3718 |0300-030B(HEX)|MR300|100768-300779|Read/write
3719 |0314-0317(HEX)|MR314|100788-300791|Read/write
3720 |031A(HEX)|MR31A|100794-300794|Read/write
3721 |0320-0321(HEX)|MR320|100800-300801|Read/write
3722 |0400-0504(HEX)|MR400|101024-301284|Read/write
3723 |0506(HEX)|MR506|101286-301286|Read/write
3724 |0510-0514(HEX)|MR510|101296-301300|Read/write
3725 |0516-0524(HEX)|MR516|101302-301316|Read/write
3726 |0526(HEX)|MR526|101318-301318|Read/write
3727 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3728 |~-~-|Ctrl|0-2|~-~-
3729
3730 **✎Note:**
3731
3732 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3733 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3734 * The Ctrl register is used to store the control group number and BCC check mode.
3735
3736 **Ctrl Register Description**
3737
3738 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3739 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3740 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3741 * Ctrl3 reserved
3742
3743 **✎Note:**
3744
3745 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3746
3747 **Cable Wiring**
3748
3749 (% style="text-align:center" %)
3750 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3751
3752 (% style="text-align:center" %)
3753 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3754
3755 **✎Note:** COM3 only available in PI8000/PI9000 series.
3756
3757 = **Printer** =
3758
3759 == **TSPL label printer** ==
3760
3761 **Introduction**
3762
3763 TSPL label printer protocol supports following models.
3764
3765 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3766 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3767
3768 **Setting Step**
3769
3770 Select the protocol
3771
3772 * Create a new project, select the TSPL label printer protocol as shown below.
3773
3774 (% style="text-align:center" %)
3775 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3776
3777 Set parameters
3778
3779 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3780
3781 Printer register
3782
3783 (% class="table-bordered" %)
3784 |**Register**|**System**|**Range**|**Function**
3785 |TSPL_SP|decimal|0 - 1|Set the paper size
3786 |TSPL_PT|decimal|0 - 1999|Print text
3787 |TSPL_PQ|decimal|0 - 999|Print QR code
3788 |TSPL_PB|decimal|0 - 999|Print barcode
3789 |TSPL_PR|decimal|0 - 1|Print offset
3790 |TSPL_PN|decimal|0 - 0|Trigger printing
3791 |TSPL_PS|decimal|0 - 0|Print status
3792
3793 * Set paper size:
3794 ** TSPL_SP0: width of paper, unit: mm.
3795 ** TSPL_SP1: height of paper, unit: mm.
3796 * Print text:
3797 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3798 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3799
3800 (% class="table-bordered" %)
3801 |**Register**|**Function**|**Description**
3802 |TSPL_PT0|X coordinate|Unit: dot
3803 |TSPL_PT1|Ycoordinate|Unit: dot
3804 |TSPL_PT2|Rotation angle|(((
3805 0: 0 degrees
3806
3807 1: 90 degrees
3808
3809 2: 180 degrees
3810
3811 3: 270 degrees
3812 )))
3813 |TSPL_PT3|Size|Range: 0-3
3814 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3815
3816 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3817
3818 Print QR code:
3819
3820 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3821 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3822
3823 (% class="table-bordered" %)
3824 |**Register**|**Function**|**Description**
3825 |TSPL_PQ0|X coordinate|Unit: dot
3826 |TSPL_PQ1|Ycoordinate|Unit: dot
3827 |TSPL_PQ2|Rotation angle|(((
3828 0: 0 degrees
3829
3830 1: 90 degrees
3831
3832 2: 180 degrees
3833
3834 3: 270 degrees
3835 )))
3836 |TSPL_PQ3|Size|Range: 0-5
3837 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3838
3839 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3840
3841 Print bar code:
3842
3843 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3844 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3845
3846 (% class="table-bordered" %)
3847 |**Register**|**Function**|**Description**
3848 |TSPL_PB0|X coordinate|Unit: dot
3849 |TSPL_PB1|Ycoordinate|Unit: dot
3850 |TSPL_PB2|Rotation angle|(((
3851 0: 0 degrees
3852
3853 1: 90 degrees
3854
3855 2: 180 degrees
3856
3857 3: 270 degrees
3858 )))
3859 |TSPL_PB3|height|Unit: dot
3860 |TSPL_PB4|width|Range:0-2
3861 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3862
3863 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3864
3865 Print offset:
3866
3867 * TSPL_PR0: X coordinate offset, unit: mm;
3868 * TSPL_PR1: Y coordinate offset, unit: mm.
3869
3870 Trigger printing:
3871
3872 * TSPL_PN0 = 1: trigger the printer to start printing.
3873
3874 Printing status:
3875
3876 * TSPL_PS0 = 1: The printing is normal.
3877 * TSPL_PS0 = 1: The printing is abnormal.
3878
3879 Print picture
3880
3881 * For the function of printing pictures, please refer to the configuration of [Printer object].
3882
3883 Conversion between dot and mm
3884
3885 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3886
3887 == **EpsonTM series** ==
3888
3889 **HMI Settings**
3890
3891 (% class="table-bordered" %)
3892 |**Item**|**Settings**|**Note**
3893 |Protocol|EPSON-TM-T82II/TM-XXX|
3894 |Connection|RS232|
3895 |Baud rate|9600~~115200|
3896 |Data bit|8|
3897 |Parity|None|
3898 |Stop bit|1|
3899 |PLC station No.|1|
3900
3901 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3902
3903 **Printer Settings**
3904
3905 (% class="table-bordered" %)
3906 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3907 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3908 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3909 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3910 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3911 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3912 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3913
3914 **Cable Wiring**
3915
3916 (% style="text-align:center" %)
3917 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3918
3919 (% style="text-align:center" %)
3920 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3921
3922 **✎Note:** COM3 only available in PI8000/PI9000 series.
3923
3924
3925 = Create communication with **Schneider PLC** =
3926
3927 == **Schneider MODBUS RTU** ==
3928
3929 **HMI Setting**
3930
3931 |=**Parameters**|=**Recommended**|=**Notes**
3932 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3933 |Connection|RS485|
3934 |**Baud rate**|19200|
3935 |**Data bit**|8|
3936 |**Parity**|Even|
3937 |**Stop bit**|1|
3938 |**PLC station No.**|1|
3939
3940 **PLC Setting**
3941
3942 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3943
3944 **Device Address**
3945
3946 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3947 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3948 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3949 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3950 |W|MW|DDDDDD|0 ~~ 999999|Output register
3951 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3952
3953 **Wiring Diagram**
3954
3955 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3956
3957 (% style="text-align:center" %)
3958 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3959
3960 = **Barcode Scanner** =
3961
3962 Supported: DELI 14880 barcode scanner
3963
3964 **HMI Setting**
3965
3966 |**Items**|**Settings**|**Note**
3967 |Protocol|Barcode Scanner|
3968 |Connection|USB|
3969
3970 **Operating Procedures**
3971
3972 Select [Barcode Scanner];
3973
3974 (% style="text-align:center" %)
3975 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3976
3977 Set address for receiving;
3978
3979 Set correct length;
3980
3981 (% style="text-align:center" %)
3982 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3983
3984 **✎Note:**
3985
3986 * The protocol uploads the information acquired by the USB scanner to the HMI;
3987 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3988 * Recommended model: DELI 14880 barcode scanner;
3989
3990 = **Hitachi EHV Series (Ethernet)** =
3991
3992 Supported series: Hitachi EHV series
3993
3994 **HMI Settings**
3995
3996 (% class="table-bordered" %)
3997 |**Items**|**Settings**|**Note**
3998 |Protocol|Hitachi EHV series|
3999 |Connection|Ethernet|
4000 |Port No.|3004~~3007|
4001
4002 **Address List**
4003
4004 (% class="table-bordered" %)
4005 |**Type**|**Register**|**Range**|**Format**|**Note**
4006 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4007 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4008 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4009 H1H2H3H4 Module main number
4010
4011 H1: Remote number
4012
4013 H2: Unit number
4014
4015 H3: Slot number
4016
4017 H4: Word number of Module
4018
4019 H Sub number of Module
4020
4021 For example:X21.3
4022
4023 Slot number 2
4024
4025 Word number of module is 1
4026
4027 Bit number of module is 3
4028
4029 Remote number and unit number are 0
4030 )))
4031 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4032 |R|0 – FF.f (Hex)|R HH.h|
4033 |L|0 - 73FF.f (Hex)|L HHHH.h|
4034 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4035 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4036 H1H2H3H4 Module main number
4037
4038 H1: Remote number
4039
4040 H2: Unit number
4041
4042 H3: Slot number
4043
4044 H4: Word number of module
4045
4046 For example:WX21
4047
4048 Word number of module is 1
4049
4050 Slot number is 2
4051
4052 Remote number and unit number are 0
4053 )))
4054 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4055 |WR|0 – FFFF (Hex)|WR HHHH|
4056 |WL|0 - 73FF (Hex)|WL HHHH|
4057 |TC|0 - 2559|TC DDDD|
4058
4059 **Communication settings in HMI**
4060
4061 Enable HMI Ethernet in [Project Settings];
4062
4063 (% style="text-align:center" %)
4064 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4065
4066 Set PLC IP in [Device IP] settings;
4067
4068 (% style="text-align:center" %)
4069 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4070
4071 **PLC Configuration**
4072
4073 Connect with PLC, select[Online mode];
4074
4075 (% style="text-align:center" %)
4076 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4077
4078 Set IP address, it is the same LAN parameters with HMI;
4079
4080 (% style="text-align:center" %)
4081 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4082
4083 3) Save PLC communication parameter, and restart PLC
4084
4085 **PLC Monitor Mode**
4086
4087 Connect with PLC and choose to “online” mode
4088
4089 (% style="text-align:center" %)
4090 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4091
4092 Open I/O monitor sheet1
4093
4094 (% style="text-align:center" %)
4095 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4096
4097 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4098
4099 (% style="text-align:center" %)
4100 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4101
4102 Enter the register address, click OK to view the value of the register.
4103
4104 (% style="text-align:center" %)
4105 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4106
4107 (% style="text-align:center" %)
4108 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4109
4110 **✎Note:**
4111
4112 * Both word registers and bit registers support even continuous read/write functions;
4113 * The range of registers is based on the specific PLC type;
4114
4115 **Cable Wiring**
4116
4117 (% style="text-align:center" %)
4118 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4119
4120 = **IEC60870-5 104 Client** =
4121
4122 **HMI Setting**
4123
4124 (% class="table-bordered" %)
4125 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4126 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4127 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4128 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4129
4130 **Address List**
4131
4132 (% class="table-bordered" %)
4133 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4134 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4135 |(% style="width:461px" %)SCNA|0~~16777215.7
4136 |(% style="width:461px" %)DPTB|0~~16777215.7
4137 |(% style="width:461px" %)DCNA|0~~16777215.7
4138 |(% style="width:461px" %)METF|0~~16777215.7
4139 |(% style="width:461px" %)SENC|0~~16777215.7
4140 |(% style="width:461px" %)SENA|0~~16777215.7
4141 |(% style="width:461px" %)MENA|0~~16777215.7
4142 |(% style="width:461px" %)METD|0~~16777215.7
4143 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4144 |(% style="width:461px" %)SCNA|0~~16777215
4145 |(% style="width:461px" %)DPTB|0~~16777215
4146 |(% style="width:461px" %)DCNA|0~~16777215
4147 |(% style="width:461px" %)SENA|0~~16777215
4148 |(% style="width:461px" %)MENA|0~~16777215
4149 |(% style="width:461px" %)METD|0~~16777215
4150 |(% style="width:461px" %)INRO|0~~16777215
4151 |(% style="width:461px" %)TIMESYN|0~~16777215
4152 |(% style="width:461px" %)TIMEZ|0~~16777215
4153 |(% style="width:461px" %)NTP|0~~16777215
4154 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4155 |(% style="width:461px" %)SENC|0~~16777215
4156
4157 **Address Configuration**
4158
4159 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4160
4161 (% style="text-align:center" %)
4162 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4163
4164 (% style="text-align:center" %)
4165 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4166
4167 Extended tag name
4168
4169 Address range for the extended tag.
4170
4171 **Communication Settings**
4172
4173 Enable HMI Ethernet in [Project Settings];
4174
4175 (% style="text-align:center" %)
4176 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4177
4178 Set PLC IP in [Device IP] settings;
4179
4180 (% style="text-align:center" %)
4181 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4182
4183 **Cable Wiring**
4184
4185 (% style="text-align:center" %)
4186 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4187
4188 = **OpenCAN** =
4189
4190 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4191
4192 This protocol is only available in PI8000 series HMI.
4193
4194 **HMI Settings**
4195
4196 |**Items**|**Settings**|**Note**
4197 |Protocol|OPENCAN|
4198 |Connection|CAN port|
4199 |Baud rate|250000|
4200
4201 **CAN frame setting in HMI**
4202
4203 Click [OpenCAN setting] button in communication setting window;
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4207
4208 Click [Add] to create a new frame;
4209
4210 (% style="text-align:center" %)
4211 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4212
4213 |**No**|**Items**|**Description**
4214 |1|Add|add a frame related to register address
4215 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4216 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4217 |4|Modify|Modify the frames in frame management
4218 |5|Copy|Copy one frame to another
4219 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4220 |7|Empty|All frames in the list are cleared
4221 |8|Browse|Displays configuration files in XML format in IE
4222 |9|OK|Complete the configuration of the frame and exit
4223
4224 Set CANBUS frame in setting windows
4225
4226 (% style="text-align:center" %)
4227 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4228
4229 |**No**|**Items**|**Description**
4230 |1|ID|Set the ID of a can frame in hexadecimal format;
4231 |2|ID assign|split the ID by PF, PS, and SA;
4232 |3|Frame type|Select Standard frame or Extended Frame;
4233 |4|Frame format|Select between data frame and remote Frame;
4234 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4235 |6|Use address|(((
4236 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4237
4238 **Edit:** Set a bit or word address by its format;
4239
4240 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4241 )))
4242 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4243 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4244 |Feedback mode: feedback mode includes no response, confirm response and data response;
4245 |No response: the device or touch screen will not receive feedback;
4246 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4247 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4248 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4249 |Response timeout: sets whether the response frame timeout;
4250 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4251 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4252 |Manually send: a manually send tick indicates only one send;
4253 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4254 |10|Note|Fill the text to explain the meaning of the frame;
4255 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4256 |12|Current operation display|Display the description of current operation;
4257 |13|Add|Add a new frame;
4258 |14|Save frame|Save the configured frame format;
4259 |15|Cancel|Cancel the frame configuration;
4260
4261 Set CAN address (Read or write operation);
4262
4263 (% style="text-align:center" %)
4264 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4265
4266 |**No.**|**Item**|**Description**
4267 |1|Current address|Displays the register type and register address set by the user in the data access interface
4268 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4269 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4270 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4271 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4272 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4273 |If the trigger condition is a writing operation, there are two situations:(((
4274 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4275 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4276 )))
4277 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4278 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4279 |4|Add|Add current configuration
4280 |5|Close|Close the configuration window to exit
4281
4282 **Multiple Packages Settings**
4283
4284 (% style="text-align:center" %)
4285 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4286
4287 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4288
4289 Select Multiple package type
4290
4291 * Not Multiple packages
4292 * J1939 Multiple packages
4293 * Customized Multiple packages
4294
4295 Click [Edit Receive data] for [Receive] settings
4296
4297 * Start code+ Total length (J1939)
4298
4299 (% style="text-align:center" %)
4300 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4301
4302 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4303
4304 * Start code + Data max length (J1939)
4305
4306 (% style="text-align:center" %)
4307 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4308
4309 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4310
4311 * Data max length (J1939)
4312
4313 (% style="text-align:center" %)
4314 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4315
4316 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4317
4318 * Customized multiple package
4319
4320 (% style="text-align:center" %)
4321 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4322
4323 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4324
4325 Click [Edit Send data] for [Send] setting
4326
4327 * J1939
4328
4329 (% style="text-align:center" %)
4330 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4331
4332 [Data] is all data to be sent.
4333
4334 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4335
4336 * Customized multiple package
4337
4338 (% style="text-align:center" %)
4339 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4340
4341 [Data] is all data to be sent.
4342
4343 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4344
4345 **Cable Wiring**
4346
4347 (% style="text-align:center" %)
4348 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4349
4350 **✎Note:** The address interval between each frame need to be more than a word address;
4351
4352
4353 = **User Defined Protocol** =
4354
4355 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4356
4357 **HMI Settings**
4358
4359 |**Items**|**Settings**|**Note**
4360 |Protocol|User defined protocol|
4361 |Connection|RS485/RS232|
4362 |Baud rate|2400~~187500|
4363 |Stop bits|1/ 2|
4364 |Data bits|7/ 8|
4365 |Parity|None/ Even/ ODD|
4366
4367 **Operating Procedures**
4368
4369 Select [User defined protocol];
4370
4371 Click [User defined protocol] button to open setting window as below;
4372
4373 (% style="text-align:center" %)
4374 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4375
4376 Configure user defined command;
4377
4378 (% style="text-align:center" %)
4379 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4380
4381 |**No**|**Item**|**Description**
4382 |1|Instruction edit|The required command.
4383 |2|Mode|Write to address or read from the address.
4384 |3|Format|Encode format: HEX or ASCII.
4385 |4|Other|(((
4386 **No receiving: **HMI does not respond to the receiving command.
4387
4388 **Send after receiving:** HMI responds to the receiving command.
4389 )))
4390 |5|Manually send|(((
4391 Respond once after trigger the address.
4392
4393 Address: set the trigger address.
4394 )))
4395 |6|Add|Save this setting.
4396 |7|Cancel|Cancel current settings.
4397 |(% rowspan="4" %)8|Add|Add a new command.
4398 |Edit|Edit the selected command.
4399 |Delete|Delete the selected command.
4400 |Clear|Clear all the commands.
4401 |9|Instruction list|Display all current commands.
4402 |10|Address List|Display all the addresses added.
4403 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4404 |Export|Export current command settings to local storage.
4405 |Browse|Browse local command files.
4406 |Advanced|Combine two commands.
4407 |Exit|Complete editing and exit setting.
4408
4409 **Operating Procedures**
4410
4411 Click [Add] to create a new command, as below shows;
4412
4413 (% style="text-align:center" %)
4414 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4415
4416 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4417
4418 (% style="text-align:center" %)
4419 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4420
4421 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4422
4423 (% style="text-align:center" %)
4424 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4425
4426 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4427
4428 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4429
4430 Check settings;
4431
4432 (% style="text-align:center" %)
4433 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4434
4435 |**No**|**Items**|**Description**
4436 |1|Add checking|Add checking command when receiving the data.
4437 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4438 |Differ with send check|Set return checking.
4439 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4440 |Length: The data length need to be checked.
4441
4442 Object settings;
4443
4444 (% style="text-align:center" %)
4445 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4446
4447 |**No**|**Items**|**Description**
4448 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4449 |Address: the triggering address;
4450 |Note: description to object;
4451 |2|Byte order|The numerical display order;
4452
4453 Data length settings;
4454
4455 (% style="text-align:center" %)
4456 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4457
4458 |**No**|**Item**|**Description**
4459 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4460 |Length: the return data length.
4461 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4462 |Length: the write data length.
4463
4464 Instruction length settings
4465
4466 (% style="text-align:center" %)
4467 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4468
4469 |**No**|**Item**|**Description**
4470 |1|Send length|The instruction data will only send designated data length.
4471 |2|Return length|The responds data length.
4472 |3|End code|Instruction will not be terminated until receiving [End code];
4473
4474 **Cable Wiring**
4475
4476 * **RS485**
4477
4478 (% style="text-align:center" %)
4479 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4480
4481 (% style="text-align:center" %)
4482 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4483
4484 * **RS232**
4485
4486 (% style="text-align:center" %)
4487 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4488
4489 **✎Note:** COM3 only available in PI8000/PI9000 series.