Wiki source code of 11 PLC Protocol

Version 292.1 by Devin Chen on 2023/08/22 19:15

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation of the Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON PLC =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 **✎Note:**
159
160 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
161 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
162
163 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
164
165 (% class="wikigeneratedid" id="HHMIsettings" %)
166 **HMI settings**
167
168 **Download PIStudio Software**
169
170 Please visit the link below to get the latest version PIstudio for HMI programming:
171
172 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
173
174 **Create a new HMI project connect with PLC**
175
176 Check the link below for the video to show you how to get started with a new project
177
178 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
179
180 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
181
182 **General**
183
184 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
185
186 **Protocol settings**
187
188 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
189
190 Please select the protocol, when creating a new project.
191
192 1. Select the COM port for communication;
193 1. PLC type: It means PLC brand, like WECON;
194 1. PLC model: It shows the model of PLC, such as LX3V;
195
196 (% style="text-align:center" %)
197 [[image:image-20220819093729-1.png]]
198
199 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
200
201 (% style="text-align:center" %)
202 [[image:image-20220819093729-2.png]]
203
204
205 The steps to change the protocol for project are as follows.
206
207 1. Click [Setting] to open the [Communication device] window;
208 1. Select communication port, such as COM1;
209 1. Select Serial port for communication, such as RS422;
210 1. Select device type (device brand), such as WECON;
211 1. Select the protocol for communication, such as WECON LX3V;
212
213 (% style="text-align:center" %)
214 [[image:image-20220819093729-3.png]]
215
216 **Parameter settings**
217
218 The parameters settings are in [Communication] window, shown as following below.
219
220 1. Click [Setting] to open the [COM port setting] window;
221 1. Set the parameters such as [connection], [Baud rate] and so on;
222
223 (% style="text-align:center" %)
224 [[image:image-20220819093729-4.png||height="636" width="818"]]
225
226 (% start="3" %)
227 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
228
229 (% style="text-align:center" %)
230 [[image:image-20220819093729-5.png]]
231
232 **Set PLC address in HMI screen**
233
234 1. Place the objects to HMI screen;
235 1. Double-click the object to open the setting window;
236 1. Click “Edit” to open the address setting windows;
237 1. Connection: select the serial port in HMI;
238 1. Address type: All the PLC address types will be display in this list, such as M;
239 1. Address No.: Please input the number of this address, such as 0;
240
241 [[image:image-20220819093729-6.jpeg]]
242
243 **HMI Compilation Download**
244
245 [[image:image-20220902171247-1.png]]
246
247 **Communication cable**
248
249 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
250
251 (% style="text-align:center" %)
252 [[image:image-20220819093729-7.png]]
253
254 **HMI communication PLC use Modbus **
255
256 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
257 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
258
259 (% class="wikigeneratedid" id="HPLCsettings" %)
260 **PLC settings**
261
262 **Download PLC Software**
263
264 Please visit below link to get the latest version PLC Editor for HMI programming
265
266 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
267 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
268
269 **Start a new PLC project**
270
271 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
272
273 (% style="text-align:center" %)
274 [[image:image-20220819101447-3.jpeg]]
275
276 **Add a new instruction **
277
278 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
279
280 (% style="text-align:center" %)
281 [[image:image-20220819105530-1.png]]
282
283 You could also select the ladder symbol from the menu bar directly.
284
285 [[image:image-20220819093729-12.png]]
286
287 **Add comment to PLC program**
288
289 (% style="text-align:center" %)
290 [[image:image-20220819105630-3.png]]
291
292 **Add the statement to PLC program**
293
294 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
295
296 (% style="text-align:center" %)
297 [[image:image-20220819105644-4.png]]
298
299 **Compile **
300
301 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
302
303 [[image:image-20220819093729-15.png]]
304
305 **Download setting **
306
307 Click on “Transfer Setup” to select download mode.
308
309 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
310
311 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
312
313 [[image:image-20220819093729-17.png]]
314
315 **Upload PLC program from PLC**
316
317 Read the PLC program from PLC to computer.
318
319 [[image:image-20220819093729-18.png]]
320
321 **Device monitor**
322
323 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
324
325 [[image:image-20220819093730-19.png]]
326
327 **Online monitor**
328
329 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
330
331 [[image:image-20220819093730-20.png]]
332
333 **Monitor edit**
334
335 In this mode, you could edit the PLC program during PLC is running. 
336
337
338 (% style="text-align:center" %)
339 [[image:image-20220819105928-9.png||height="229" width="669"]]
340
341 == **LX5V Series** ==
342
343 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
344
345 **Software configuration of PLC**
346
347 PLC programming software
348
349 (% style="text-align:center" %)
350 [[image:image-20220810164710-1.png]]
351
352 **New PLC project**
353
354 Click "New Project" and select the PLC model.
355
356 [[image:image-20220810172412-1.png]]
357
358 **Set Serial port parameters**
359
360 Follow the steps below to configure Serial port parameters.
361
362 * Baud rate:115200
363 * Data bit:8
364 * Stop bit:1
365 * Parity:No verification
366
367 [[image:image-20220810165759-3.png]]
368
369 **Registers list**
370
371 [[image:image-20220811102219-3.png]]
372
373 **HMI software configuration**
374
375 HMI programming software
376
377 (% style="text-align:center" %)
378 [[image:image-20220810171237-4.png]]
379
380 **New HMI project**
381
382 Click New Project and select the HMI model.
383
384 [[image:image-20220810172010-5.png]]
385
386 Set communication port parameters
387
388 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
389
390 * Baud rate:115200
391 * Data bit:8
392 * Stop bit:1
393 * Parity:No verification
394
395 [[image:image-20220811104012-1.png]]
396
397 **hardware connection**
398
399 Hardware wiring diagram
400
401 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
402
403 (% style="text-align:center" %)
404 [[image:image-20220811103005-4.png]]
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103227-7.png]]
408
409 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
410
411 == **LX5V-N Ethernet** ==
412
413 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
414
415 **Software configuration of PLC**
416
417 **PLC programming software**
418
419 (% style="text-align:center" %)
420 [[image:image-20220810164710-1.png]]
421
422 **New PLC project**
423
424 Click New Project and select the PLC model.
425
426 [[image:image-20220811115454-1.png]]
427
428 **Set Ethernet port parameters**
429
430 Follow the steps below to configure Ethernet parameters
431
432 * PLC IP address:192.168.39.200
433 * default gateway:192.168.39.1
434 * subnet mask:255.255.255.0
435
436 [[image:image-20220811140530-2.png]]
437
438 **Registers list**
439
440 [[image:image-20220811102219-3.png]]
441
442 **HMI software configuration**
443
444 HMI programming software
445
446
447 (% style="text-align:center" %)
448 [[image:image-20220810171237-4.png]]
449
450 **New HMI project**
451
452 Click New Project and select the HMI model.
453
454 [[image:image-20220810172010-5.png]]
455
456 **Set communication port parameters**
457
458 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
459
460 * HMI IP address:192.168.39.201
461 * Default gateway:192.168.39.1
462 * Subnet mask:255.255.255.0
463
464 [[image:image-20220811170753-2.png]]
465
466 Next, click Communication Settings to configure the IP of the HMI communication object.
467
468 [[image:image-20220811163047-1.png]]
469
470 **Hardware connection**
471
472 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
473
474 (% style="text-align:center" %)
475 [[image:image-20220811170248-1.png]]
476
477 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
478
479 = ABB =
480
481 == **AC500** ==
482
483 Support Series: ABB AC500
484
485 **HMI Settings**
486
487 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
488 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
489 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
490 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
491 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
496
497 **Address List**
498
499 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
500 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
501 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
502 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
503
504 **Cable Wiring**
505
506 (% style="text-align:center" %)
507 [[image:ABB AC500.gif]]
508
509 = Abzil =
510
511 == **Abzil CPL Protocol** ==
512
513 Supported series: SDC series
514
515 **HMI Settings**
516
517 (% style="width:1003px" %)
518 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
519 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
520 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
521 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
522 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
523 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
524 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
525 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
526
527 **Address List**
528
529 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
530 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
531 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
532 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
533 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
540 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
541 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
542 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
548
549 **Cable Wiring**
550
551 (% style="text-align:center" %)
552 [[image:Azbil CPL485.gif]]
553
554 = Crouzet =
555
556 == **M3 (FBD)** ==
557
558 Support Series: Crouzet Millenium 3 CD12/CB12
559
560 **HMI Settings**
561
562 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
563 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
564 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
565 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
566 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
567 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
568 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
569 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
571
572 **Address List**
573
574 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
575 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
576 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
577 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
578 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
579 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
580 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
581 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
582 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
583 Time1: Second
584
585 Time2: Minute
586
587 Time3: Hour
588
589 Time4: Day
590
591 Time5: Month
592
593 Time6: Year
594 )))
595 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
596 Running command(Write only)
597
598 ~=2: Run mode; =1: Stop mode;
599 )))
600
601 **Cable Wiring**
602
603 (% style="text-align:center" %)
604 [[image:CrouzetRS232.png]]
605
606 {{info}}
607 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
608 {{/info}}
609
610 = Create communication with Danfoss Drive =
611
612 == **FC Series Protocol** ==
613
614 Support Series: VLT FC300 Drive
615
616 **HMI Settings**
617
618 (% style="width:988px" %)
619 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended
620 |=(% style="width: 262px;" %)Protocol|(% style="text-align:center; vertical-align:middle; width:487px" %)Danfoss FC Series
621 |=(% style="width: 262px;" %)Connection|(% style="text-align:center; vertical-align:middle; width:487px" %)RS485
622 |=(% style="width: 262px;" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:487px" %)9600
623 |=(% style="width: 262px;" %)Stop bits|(% style="text-align:center; vertical-align:middle; width:487px" %)1
624 |=(% style="width: 262px;" %)Data bits|(% style="text-align:center; vertical-align:middle; width:487px" %)8
625 |=(% style="width: 262px;" %)Parity|(% style="text-align:center; vertical-align:middle; width:487px" %)EVEN
626 |=(% style="width: 262px;" %)PLC Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)1
627 |=(% style="width: 262px;" %)HMI Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)0
628
629 **Address List**
630
631 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
632 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
633 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
634 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
635 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
636
637 **Cable Wiring**
638
639 (% style="text-align:center" %)
640 [[image:Danfoss.png]]
641
642 = Create communication with **Delta PLC** =
643
644 == DVP serial protocol ==
645
646 (% class="wikigeneratedid" %)
647 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
648
649 **HMI Settings**
650
651 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
652 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
653 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
654 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
655 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
656 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
657 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
658 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
659
660 **Address List**
661
662 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
663 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
664 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
665 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
669 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
670 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
671 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
672
673 (% class="wikigeneratedid" %)
674 **Configure the communication protocol**
675
676 (% style="text-align:center" %)
677 [[image:image-20220829152327-6.png]]
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152016-3.png]]
681
682 (% class="wikigeneratedid" %)
683 **Cable Wiring**
684
685 (% class="wikigeneratedid" id="H" %)
686 [[image:image-20220829152610-7.png]]
687
688 (% style="text-align:center" %)
689 [[image:image-20220829152102-5.png]]
690
691 == DVP Ethernet Protocol ==
692
693 (% class="wikigeneratedid" %)
694 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
695
696 **HMI Settings**
697
698 |=**Items**|=**Settings**|=**Note**
699 |Protocol|DELTA DVP Modbus TCP|
700 |Connection|Ethernet|
701 |Port No.|201|Must be the same as the PLC setting
702 |PLC station No.|0|Must be the same as the PLC setting
703
704 **Address List**
705
706 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
707 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
712 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
713 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
714 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
715 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
716
717 )))
718 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
719 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
720
721 )))
722
723 (% class="wikigeneratedid" %)
724 **Configure the communication protocol**
725
726 (% style="text-align:center" %)
727 [[image:image-20220829155452-1.png]]
728
729 [[image:image-20220829162116-2.png]]
730
731 **Cable Wiring**
732
733 (% style="text-align:center" %)
734 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
735
736 == **AS serial protocol** ==
737
738 Supported Series: Delta AS200/AS300
739
740 **HMI Settings**
741
742 |**Item**|**Settings**|**Note**
743 |Protocol|DELTA AS300 MODBUS RTU|
744 |Connection|RS485|
745 |Baud rate|9600|
746 |Data bit|8|
747 |Parity|NONE|
748 |Stop bit|1|
749 |PLC station No.|1|
750
751 **Address List**
752
753 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
754 |Bit|X|X|Xdd.dd|0~~63.15|Read only
755 |Bit|Y|Y|Ydd.dd|0~~63.15|
756 |Bit|D|D|Dddddd|0~~29999|
757 |Bit|M|M|Mdddd|0~~8191|
758 |Bit|SM|SM|SMdddd|0~~4095|
759 |Bit|S|S|Sdddd|0~~2047|
760 |Bit|T|T|Tddd|0~~511|
761 |Bit|C|C|Cddd|0~~511|
762 |Bit|HC|HC|HCddd|0~~255|Double Word
763 |Word|X|X|Xdd|0~~63|
764 |Word|Y|Y|(((
765 Ydd
766 )))|0~~63|
767 |Word|SR|SR|SRdddd|0~~2047|Special register
768 |Word|D|D|Dddddd|0~~29999|
769 |Word|T|T|Tddd|0~~511|
770 |Word|C|C|Cddd|0~~511|
771 |Word|E|E|Ed|0~~9|
772
773 **Configure the communication protocol**
774
775 Create project
776
777 (% style="text-align:center" %)
778 [[image:AsCreateProject.png]]
779
780 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
781
782 (% style="text-align:center" %)
783 [[image:AScommunicarw.png]]
784
785 Double click the HWCONFIG to open the communication settings window.
786
787 (% style="text-align:center" %)
788 [[image:ASHWCONFIG.png]]
789
790 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
791
792 (% style="text-align:center" %)
793 [[image:ASHSCONFIGICON.png]]
794
795 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
796
797 (% style="text-align:center" %)
798 [[image:ASModbusMode.png]]
799
800 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
801
802 (% style="text-align:center" %)
803 [[image:ASconfigIP.png]]
804
805 (% style="text-align:center" %)
806 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
807
808
809 (% style="text-align:center" %)
810 [[image:image-20220830094657-2.png]]
811
812 **Cable Wiring**
813
814 (% style="text-align:center" %)
815 [[image:image-20220830141138-1.png]]
816
817 Pin Definition Diagram
818
819 (% style="text-align:center" %)
820 [[image:image-20220830095131-1.png]]
821
822 == AS Ethernet Protocol ==
823
824 **HMI Settings**
825
826 |=**Items**|=**Settings**|=**Note**
827 |Protocol|DELTA AS300 MODBUS TCP|
828 |Connection|Ethernet|
829 |Port No.|502|
830 |Device No.|1|
831 |HMI No.|0|
832
833 **Address List**
834
835 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
836 |Bit|X|X|X d|0~~63|
837 |Bit|Y|Y|Y d|0~~63|
838 |Bit|D|D|D d|0~~29999|
839 |Bit|M|M|M d|0~~8191|
840 |Bit|SM|SM|SM d|0~~4095|
841 |Bit|S|S|S h|0~~2047|
842 |Bit|T|T|T d|0~~511|
843 |Bit|C|C|C d|0~~511|
844 |Bit|HC|HC|HC d|0~~255|
845 |Word|X|X|X h|0~~63|
846 |Word|Y|Y|Y d|0~~63|
847 |Word|SR|SR|SR d|0~~2047|
848 |Word|D|D|D d|0~~29999|
849 |Word|T|T|T d|0~~511|
850 |Word|C|C|C h|0~~511|
851 |Word|E|E|E d|0~~9|
852
853 **Configure the communication protocol**
854
855 (% style="text-align:center" %)
856 [[image:image-20220830140537-1.png]]
857
858 (% style="text-align:center" %)
859 [[image:image-20220830140629-2.png]]
860
861 **Cable Wiring**
862
863 [[image:image-20220830094929-1.png]]
864
865 Pin Definition Diagram
866
867 (% style="text-align:center" %)
868 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
869
870 = **Create communication with EMERSON PLC** =
871
872 == **RTU Slave Protocol** ==
873
874 Supported series: EC10 series
875
876 **HMI Settings**
877
878 |**Item**|**Settings**|**Note**
879 |Protocol|Emerson 984 RTU Slave MODBUS|
880 |Connection|RS485|
881 |Baud rate|19200|
882 |Data bit|8|
883 |Parity|EVEN|
884 |Stop bit|1|
885 |PLC station No.|1
886
887 **PLC Settings**
888
889 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
890
891 (% style="text-align:center" %)
892 [[image:ControlStarSystemBlock.png]]
893
894 (% style="text-align:center" %)
895 [[image:ControlStarCommunicate.png]]
896
897 (% style="text-align:center" %)
898 [[image:ControlStarModbus.png]]
899
900 **Address List**
901
902 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
903 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
904 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
905 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
906 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
907 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
908 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
909 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
910 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
911 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
912 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
913 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
914 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
915 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
916 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
917 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
918 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
919 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
920 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
921 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
922 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
923 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
924
925 **Cable Wiring**
926
927 (% style="text-align:center" %)
928 [[image:Emerson.gif]]
929
930 = **Create communication with HollySys PLC** =
931
932 == **LK MODBUS RTU** ==
933
934 Supported Series: HollySys LK series CPU
935
936 **HMI Settings**
937
938 |=Item|=Recommended|=Note
939 |=Protocol|HollySys LK MODBUS RTU|
940 |=Connection|RS485|
941 |=Baud rate|38400|
942 |=Stop bits|1|
943 |=Data bits|8|
944 |=Parity|NONE|
945 |=PLC Station No.|1|
946 |=HMI Station No.|0|
947
948 **Address List**
949
950 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
951 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
952 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
953 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
954 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
955 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
956 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
957 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
958
959 **Cable Wiring**
960
961 (% style="text-align:center" %)
962 [[image:Hollysys485.png]]
963
964 == **LM MODBUS RTU** ==
965
966 Supported Series: HollySys LM3109/LM3107 PLC
967
968 **HMI Settings**
969
970 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
971 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
972 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
973 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
974 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
975 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
976 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
977 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
978 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
979
980 **Address List**
981
982 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
983 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
984 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
985 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
986 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
987 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
988 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
989 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
990
991 **Cable Wiring**
992
993 RS232
994
995 (% style="text-align:center" %)
996 [[image:HollySys LM Modbus RTU.gif]]
997
998 RS485
999
1000 (% style="text-align:center" %)
1001 [[image:Hollysys LM Modbus RTU.gif]]
1002
1003 = **Create communication with Inovance PLC** =
1004
1005 == **H1U/H2U serial protocol** ==
1006
1007 **HMI Settings**
1008
1009 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1010 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1011 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1012 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1013 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1014 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1015 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1016 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1017 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1018
1019 (% class="wikigeneratedid" %)
1020 **Address List**
1021
1022 (% style="width:1014px" %)
1023 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1026 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1027 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1028 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1029 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1030 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1031 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1034 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1035 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1036 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1037 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1038 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1039 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1040 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1041
1042 (% class="wikigeneratedid" %)
1043 **Cable Wiring**
1044
1045 (% style="text-align:center" %)
1046 [[image:Inovance.png]]
1047
1048 == **H3U serial protocol** ==
1049
1050 **HMI Settings**
1051
1052 |=**Item**|=**Settings**|=**Note**
1053 |Protocol|INOVANCE H3U PLC|
1054 |Connection|RS422|
1055 |Baud rate|9600|
1056 |Data bit|7|
1057 |Parity|EVEN|
1058 |Stop bit|1|
1059 |PLC station No.|0|
1060
1061 **Address List**
1062
1063 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1066 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1067 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1068 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1069 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1070 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1071 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1075 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1076 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1077 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1078 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1079 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1080 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1081 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1082
1083 **Configure the communication protocol**
1084
1085 (% style="text-align:center" %)
1086 [[image:image-20220830170114-4.png]]
1087
1088 [[image:image-20220830170017-3.png]]
1089
1090 **Cable Wiring**
1091
1092 (% style="text-align:center" %)
1093 [[image:Inovance.png]]
1094
1095 == **H3U Ethernet portocol** ==
1096
1097 **HMI Settings**
1098
1099 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1100 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1101 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1102 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1103 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1104 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1105
1106 **Address List**
1107
1108 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1109 |Bit|M|M DDDD|0~~8511|
1110 |Bit|SM|SM DDDD|0~~1023|
1111 |Bit|S|S DDDD|0~~4095|
1112 |Bit|T|T DDD|0~~511|
1113 |Bit|C|C DDD|0~~255|
1114 |Bit|X|X OOO|0~~571|
1115 |Bit|Y|Y OOO|0~~571|
1116 |Word|D|D DDDD|0~~8511|
1117 |Word|SD |SD DDDD|0~~1023|
1118 |Word|R|R DDDDD|0~~32767|
1119 |Word|T|T DDD|0~~255|
1120 |Word|C|C DDD|0~~199|
1121 |Double Word|C|C DDD|200~~255|
1122
1123 **Cable Wiring**
1124
1125 (% style="text-align:center" %)
1126 [[image:CommonEthernet.png]]
1127
1128 = Create communication with LS** PLC** =
1129
1130 == **XGB serial protocol ** ==
1131
1132 **HMI Settings**
1133
1134 |=**Item**|=**Settings**|=**Note**
1135 |Protocol|LS XGB CPU DRIECT|
1136 |Connection|RS232|
1137 |Baud rate|115200|
1138 |Data bit|8|
1139 |Parity|NONE|
1140 |Stop bit|1|
1141 |PLC station No.|1|
1142
1143 **Address List**
1144
1145 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1146 |Bit|P|P|P DDDD.f|0~~2047|
1147 |Bit|M|M|M DDDD.f|0~~2047|
1148 |Bit|L|L|L DDDDD.f|0~~11263|
1149 |Bit|K|K|K DDDD.f|0~~2559|
1150 |Bit|F|F|F DDDD.f|0~~2047|
1151 |Bit|S|S|S DDDDD|0~~12799|
1152 |Bit|D|D|D DDDDD.f|0~~32767|
1153 |Bit|U|U|U FFFF.f|0~~7f31|
1154 |Bit|T|T|T DDDD.f|0~~2047|
1155 |Bit|C|C|C DDDD.f|0~~2047|
1156 |Word|P|P|P DDDD|0~~2047|
1157 |Word|M|M|M DDDD|0~~2047|
1158 |Word|L|L|L DDDDD|0~~11263|
1159 |Word|K|K|K DDDD|0~~2559|
1160 |Word|F|F|F DDDD|0~~2047|
1161 |Word|C|C|C DDDD|0~~2047|
1162 |Word|T|T|T DDDD|0~~2047|
1163 |Word|D|D|D DDDDD|0~~32767|
1164 |Word|N|N|N DDDDD|0~~21503|
1165 |Word|U|U|U FFFF|0~~7f31|
1166 |Word|Z|Z|Z DDD|0~~127|
1167 |Word|R|R|R DDDDD|0~~32767|
1168 |Word|ZR|ZR|Z DDDDD|0~~32767|
1169 |Word|TS|TS|TS DDDD|0~~2047|
1170 |Word|CS|CS|CS DDDD|0~~2047|
1171 |Word|S|S|S DDDDD|0~~12799|
1172
1173 **Configure the communication protocol**
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028174410-1.png]]
1177
1178 (% style="text-align:center" %)
1179 [[image:image-20221028174753-2.png]]
1180
1181 (% style="text-align:center" %)
1182 [[image:image-20221028181125-4.png]]
1183
1184 **Pin Definition Diagram**
1185
1186 (% style="text-align:center" %)
1187 [[image:image-20221028180930-3.png]]
1188
1189 == **XBC serial protocol** ==
1190
1191 **HMI Settings**
1192
1193 |=**Item**|=**Settings**|=**Note**
1194 |Protocol|LS XBC CNet|
1195 |Connection|RS232|
1196 |Baud rate|115200|
1197 |Data bit|8|
1198 |Parity|NONE|
1199 |Stop bit|1|
1200 |PLC station No.|1|
1201
1202 **Address List**
1203
1204 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1205 |Bit|P|P|P d|0~~2047|
1206 |Bit|M|M|M d|0~~2047|
1207 |Bit|L|L|L d|0~~11263|
1208 |Bit|K|K|K d|0~~16183|
1209 |Bit|F|F|F d|0~~2047|
1210 |Bit|D|D|D d|0~~32767|
1211 |Bit|R|R|R d|0~~32767|
1212 |Bit|U|U|U d|0~~4095|
1213 |Word|P|P|P d|0~~2047|
1214 |Word|M|M|M d|0~~2047|
1215 |Word|L|L|L d|0~~11263|
1216 |Word|K|K|K d|0~~16183|
1217 |Word|F|F|F d|0~~2047|
1218 |Word|C|C|C d|0~~2047|
1219 |Word|T|T|T d|0~~2047|
1220 |Word|D|D|D d|0~~32767|
1221 |Word|N|N|N d|0~~21503|
1222 |Word|R|R|R d|0~~32767|
1223 |Word|U|U|U d|0~~4095|
1224 |Word|Z|Z|Z d|0~~127|
1225 |Word|S|S|S d|0~~127|
1226
1227 **Configure the communication protocol**
1228
1229 (% style="text-align:center" %)
1230 [[image:image-20220831170807-1.png]]
1231
1232 (% style="text-align:center" %)
1233 [[image:image-20220830174733-2.png]]
1234
1235 **Cable Wiring**
1236
1237 (% style="text-align:center" %)
1238 [[image:image-20220830174659-1.png]]
1239
1240 Pin Definition Diagram
1241
1242 (% style="text-align:center" %)
1243 [[image:image-20220830173402-8.png]]
1244
1245 == **XGK FEnet Ethernet protocol** ==
1246
1247 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1248
1249 **HMI Settings**
1250
1251 |**Items**|**Settings**|**Note**
1252 |Protocol|LG XGK FEnet(Ethernet)|
1253 |Connection|Ethernet|
1254 |Port No.|2004|
1255
1256 **Address List**
1257
1258 |**Type**|**Register**|**Range**|**Format**|**Note**
1259 |(% rowspan="14" %)Word|P|0~~2047|P d|
1260 |M|0~~2047|M d|
1261 |K|0~~2047|K d|
1262 |F|0~~2047|F d|
1263 |T|0~~2047|T d|
1264 |C|0~~2047|C d|
1265 |Z|0~~127|Z d|
1266 |S|0~~127|S d|
1267 |L|0~~11263|L d|
1268 |N|0~~21503|N d|
1269 |D|0~~32767|D d|
1270 |R|0~~32767|R d|
1271 |ZR|0~~65535|ZR d|
1272 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1273
1274 **✎Note:**
1275
1276 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1277 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1278 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1279
1280 **Communication settings in HMI**
1281
1282 Enable HMI Ethernet in [Project Settings];
1283
1284 (% style="text-align:center" %)
1285 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1286
1287 Set PLC IP in [Device IP] settings;
1288
1289 (% style="text-align:center" %)
1290 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1291
1292 **Cable Wiring**
1293
1294
1295 (% style="text-align:center" %)
1296 [[image:CommonEthernet.png]]
1297
1298 = Create communication with **Mitsubishi PLC** =
1299
1300 == **FX1S, 1N, 2N Series Protocol** ==
1301
1302 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1303
1304 **HMI Settings**
1305
1306 |**Item**|**Settings**|**Note**
1307 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1308 |Connection|RS422/RS485/RS232|
1309 |Baud rate|9600~~115200|
1310 |Data bit|7/8|
1311 |Parity|EVEN/Odd/None|
1312 |Stop bit|1/2|
1313 |PLC station No.|1~~255|
1314
1315 **Address List**
1316
1317 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1318 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1319 |Y|Y|Y o|0~~303237|
1320 |M|M|M d|0~~99999|
1321 |T|T|T d|0~~99999|
1322 |C|C|C d|0~~99999|
1323 |S|S|S d|0~~99999|
1324 |SM|SM|SM d|8000~~9999|
1325 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1326 |Y|Y|Y o|0~~303237|
1327 |M|M|M d|0~~99999|
1328 |T|T|T d|0~~99999|
1329 |C|C|C d|0~~199|
1330 |D|D|D d|0~~7999|
1331 |S|S|S d|0~~99999|
1332 |SD|SD|SD d|8000~~9999|
1333
1334 **Cable Wiring**
1335
1336 * **RS485**
1337
1338 (% style="text-align:center" %)
1339 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1343
1344 * **RS422**
1345
1346 (% style="text-align:center" %)
1347 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1348
1349 **✎Note:** COM3 only available in PI8000/PI9000 series.
1350
1351 == **FX3U/3G/3GA serial protocol** ==
1352
1353 **HMI Settings**
1354
1355 |=**Item**|=**Settings**|=**Note**
1356 |Protocol|Mitsubishi FX3U/3G/3GA|
1357 |Connection|RS422|
1358 |Baud rate|9600~~115200|
1359 |Data bit|7/8|
1360 |Parity|EVEN/Odd/None|
1361 |Stop bit|1/2|
1362 |PLC station No.|1~~255|
1363
1364 **Address List**
1365
1366 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1367 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1368 |Y|Y|Y o|0~~303237|
1369 |M|M|M d|0~~99999|
1370 |T|T|T d|0~~99999|
1371 |C|C|C d|0~~99999|
1372 |S|S|S d|0~~99999|
1373 |SM|SM|SM d|8000~~9999|
1374 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1375 |Y|Y|Y o|0~~303237|
1376 |M|M|M d|0~~99999|
1377 |T|T|T d|0~~99999|
1378 |C|C|C d|0~~199|
1379 |D|D|D d|0~~7999|
1380 |S|S|S d|0~~99999|
1381 |SD|SD|SD d|8000~~9999|
1382
1383 **Configure the communication protocol**
1384
1385 (% style="text-align:center" %)
1386 [[image:image-20220831095222-1.png]]
1387
1388 (% style="text-align:center" %)
1389 [[image:image-20220831095743-2.png]]
1390
1391 **Wiring**
1392
1393 (% style="text-align:center" %)
1394 [[image:image-20220831100314-6.png]]
1395
1396 == **FX NOPROTOCOL** ==
1397
1398 Mitsubishi FX3G-RS232-BD
1399
1400 **HMI Settings**
1401
1402 |=**Item**|=**Settings**|=**Note**
1403 |Protocol|Mitsubishi FX NOPROTOCOL|
1404 |Connection|RS232|
1405 |Baud rate|9600|
1406 |Data bit|7|
1407 |Parity|EVEN|
1408 |Stop bit|1|
1409 |PLC station No.|0|
1410
1411 **Address List**
1412
1413 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1414 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1415 |Y|Y|Y o|0~~303237|
1416 |M|M|M d|0~~99999|
1417 |T|T|T d|0~~99999|
1418 |C|C|C d|0~~99999|
1419 |S|S|S d|0~~99999|
1420 |SM|SM|SM d|8000~~9999|
1421 |Lamp|Lamp|Lamp d|0~~0|
1422 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1423 |Y|Y|Y o|0~~303237|
1424 |M|M|M d|0~~99999|
1425 |T|T|T d|0~~99999|
1426 |C|C|C d|0~~199|
1427 |D|D|D d|0~~7999|
1428 |S|S|S d|0~~99999|
1429 |SD|SD|SD d|8000~~9999|
1430
1431 **Configure the communication protocol**
1432
1433 (% style="text-align:center" %)
1434 [[image:1.png]]
1435
1436 (% style="text-align:center" %)
1437 [[image:2.png]]
1438
1439 **Wiring**
1440
1441 (% style="text-align:center" %)
1442 [[image:3.png]]
1443
1444 == **FX3U Ethernet Protocol** ==
1445
1446 Mitsubishi FX3U series PLC
1447
1448 **HMI Settings**
1449
1450 |Items|Settings|Note
1451 |Protocol|Mitsubishi FX3U|
1452 |Connection|Ethernet|
1453 |Port No.|5009|Must be the same as the PLC setting
1454 |PLC station No.|0|
1455
1456 **Address List**
1457
1458 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1459 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1460 |Y|Y|Y OOO|0~~377|
1461 |M|M|M DDDD|0~~7679|
1462 |SM|SM|SM DDDD|8000~~8511|
1463 |S|S|S DDDD|0~~4095|
1464 |TS|TS|TS DDD|0~~511|
1465 |CS|CS|CS DDD|0~~255|
1466 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1467 |TN|TN|TN DDD|0~~511|
1468 |D|D|D DDDD|0~~7999|
1469 |SD|SD|SD DDDD|8000~~8511|
1470 |R|R|R DDDDD|0~~32767|
1471
1472 **Ethernet Module Settings**
1473
1474 FX3U-ENET-L module configuration
1475 Set up the FX3U-ENET-L Ethernet module settings as follows.
1476 Select the module location, which in this document is Module 0.
1477
1478 [[image:image-20221115140802-1.png]]
1479
1480 Select "Operational setting" to enter the following screen.
1481
1482 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1483
1484 [[image:image-20221115142728-4.png]]
1485
1486 Select "Open setting" to enter the setting interface, the settings are as follows.
1487
1488 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1489
1490 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1491
1492 [[image:image-20221115142945-5.png]]
1493
1494 Click on "transter setup" - "PC side I/F setting", see the following figure.
1495
1496 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1497
1498 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1499
1500 [[image:image-20221115143341-6.png||height="426" width="712"]]
1501
1502 Read and write data from the Ethernet module
1503
1504 [[image:image-20221115143703-7.png]]
1505
1506 Set "Transter setup" to COM communication, and read or write operation as shown below
1507
1508 [[image:image-20221115143809-8.png]]
1509
1510 **PLC Settings (GX Works 2)**
1511
1512 Create a blank FX5U project
1513
1514 Find Current Connection in the navigation
1515
1516 [[image:image-20221115144335-9.png||height="422" width="706"]]
1517
1518 Select Connection Channel List
1519
1520 Select Ethernet board communication
1521
1522 [[image:image-20221115144824-10.png||height="421" width="705"]]
1523
1524 Select Ethernet Module
1525 Set the IP address of the PLC
1526
1527 [[image:image-20221115145228-11.png||height="674" width="708"]]
1528
1529 Read or write PLC data, in this document is read
1530
1531 [[image:image-20221115145553-12.png||height="424" width="711"]]
1532
1533 [[image:image-20221115145559-13.png||height="424" width="711"]]
1534
1535 **HMI Communication Setting**
1536
1537 [[image:image-20221115150003-14.png||height="425" width="712"]]
1538
1539 [[image:image-20221115150235-15.png||height="427" width="713"]]
1540
1541 [[image:image-20221115145559-13.png||height="424" width="711"]]
1542
1543 **HMI Communication Setting**
1544
1545 [[image:image-20221115150003-14.png||height="425" width="712"]]
1546
1547 [[image:image-20221115150235-15.png||height="427" width="713"]]
1548
1549 == **FX5U Serial Port Protocol** ==
1550
1551 Mitsubishi FX5U series PLC
1552
1553 **HMI Settings**
1554
1555 |**Item**|**Settings**|**Note**
1556 |Protocol|Mitsubishi FX5U|
1557 |Connection|RS422/RS485|
1558 |Baud rate|9600|
1559 |Data bit|7|
1560 |Parity|Odd|
1561 |Stop bit|1|
1562 |PLC station No.|1~~255|Need to be the same as PLC settings
1563
1564 **Address List**
1565
1566 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1567 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1568 |Y|Y|Y o|0~~303237|
1569 |M|M|M d|0~~99999|
1570 |B|B|B h|0~~7FFF|
1571 |F|F|F d|0~~32767|
1572 |SB|SB|SB h|0~~7FFF|
1573 |TS|TS|TS d|0~~1023|
1574 |TC|TC|TC d|0~~1023|
1575 |STS|STS|STS d|0~~1023|
1576 |STC|STC|STS d|0~~1023|
1577 |CS|CS|CS d|0~~1023|
1578 |CC|CC|CC d|0~~1023|
1579 |SM|SM|SM d|0~~9999|
1580 |L|L|L d|0~~32767|
1581 |S|S|S d|0~~4095|
1582 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1583 |TN|TN|TN d|0~~1023|
1584 |STN|STN|STN d|0~~1023|
1585 |CN|CN|CN d|0~~1023|
1586 |R|R|R d|0~~32767|
1587 |SW|SW|SW h|0~~7FFF|
1588 |Z|Z|Z d|0~~23|
1589 |D|D|D d|0~~7999|
1590 |SD|SD|SD d|0~~11999|
1591
1592 **PLC Settings (GX Works 3)**
1593
1594 Create a blank FX5U project
1595
1596 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1597
1598 (% style="text-align:center" %)
1599 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1600
1601 Select protocol in the setting item, and set parameters.
1602
1603 (% style="text-align:center" %)
1604 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1605
1606 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1607
1608 (% style="text-align:center" %)
1609 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1610
1611 Click the [Apply] button to finish the setting.
1612
1613 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1614
1615 (% style="text-align:center" %)
1616 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1617
1618 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1619
1620 Done.
1621
1622 **Cable Wiring**
1623
1624 * **RS485**
1625
1626 (% style="text-align:center" %)
1627 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1628
1629 (% style="text-align:center" %)
1630 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1631
1632 * **RS422**
1633
1634 (% style="text-align:center" %)
1635 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1636
1637 **✎Note:** COM3 only available in PI8000/PI9000 series.
1638
1639 == **L02 Serial Protocol** ==
1640
1641 Mitsubishi L02 series CPU built-in serial port.
1642
1643 **HMI Settings**
1644
1645 |=**Item**|=**Settings**|=**Note**
1646 |Protocol|Mitsubishi L02|
1647 |Connection|RS422|
1648 |Baud rate|115200|
1649 |Data bit|8|
1650 |Parity|Odd|
1651 |Stop bit|1|
1652 |PLC station No.|1~~255|Need to be the same as PLC settings
1653
1654 **Address List**
1655
1656 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1657 |Bit|X|X|X h|0~~FFFF|
1658 |Bit|Y|Y|Y h|0~~FFFF|
1659 |Bit|M|M|M d|0~~9999|
1660 |Bit|L|L|L d|0~~9999|
1661 |Bit|F|F|F d|0~~9999|
1662 |Bit|B|B|B h|0~~FFFF|
1663 |Bit|V|V|V d|0~~2047|
1664 |Bit|TC|TC|TC d|0~~9999|
1665 |Bit|SS|SS|SS d|0~~9999|
1666 |Bit|SC|SC|SC d|0~~9999|
1667 |Bit|CS|CS|CS d|0~~9999|
1668 |Bit|CC|CC|CC d|0~~9999|
1669 |Bit|SB|SB|SB h|0~~FFFF|
1670 |Bit|SM|SM|SM d|0~~2047|
1671 |Bit|STS|STS|STS d|0~~1023|
1672 |Bit|S|S|S d|0~~9999|
1673 |Bit|DX|DX|DX h|0~~FFFF|
1674 |Bit|DY|DY|DY h|0~~FFFF|
1675 |Bit|TS|TS|TS d|0~~9999|
1676 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1677 |Word|W|W|W h|0~~FFFF|
1678 |Word|TN|TN|TN d|0~~99999|
1679 |Word|SN|SN|SN d|0~~99999|
1680 |Word|CN|CN|CN d|0~~99999|
1681 |Word|R|R|R d|0~~99999|
1682 |Word|SW|SW|SW h|0~~FFFF|
1683 |Word|Z|Z|Z d|0~~99999|
1684 |Word|ZR|ZR|ZR h|0~~FFFF|
1685 |Word|D|D|D d|0~~99999|
1686
1687 **Communication Settings**
1688
1689 (% style="text-align:center" %)
1690 [[image:image-20220831105732-3.png]]
1691
1692 (% style="text-align:center" %)
1693 [[image:image-20220831110004-5.png]]
1694
1695 **Cable Wiring**
1696
1697 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1698
1699 Pin Definition Diagram
1700
1701 (% style="text-align:center" %)
1702 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1703
1704 == **L02 MELSEC (Ethernet) Protocol** ==
1705
1706 Mitsubishi Q series CPU built-in Ethernet port.
1707
1708 **HMI Settings**
1709
1710 |**Items**|**Settings**|**Note**
1711 |Protocol|MIT L02 CPU MELSEC|
1712 |Connection|Ethernet|
1713 |Port No.|1025|Must be the same as the PLC setting
1714 |PLC station No.|0|Must be the same as the PLC setting
1715
1716 **Address List**
1717
1718 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1719 |Bit|X|X|X h|0~~FFFF|
1720 |Bit|Y|Y|Y h|0~~FFFF|
1721 |Bit|M|M|M d|0~~9999|
1722 |Bit|L|L|L d|0~~9999|
1723 |Bit|F|F|F d|0~~9999|
1724 |Bit|B|B|B h|0~~FFFF|
1725 |Bit|V|V|V d|0~~2047|
1726 |Bit|TC|TC|TC d|0~~9999|
1727 |Bit|SS|SS|SS d|0~~9999|
1728 |Bit|SC|SC|SC d|0~~9999|
1729 |Bit|CS|CS|CS d|0~~9999|
1730 |Bit|CC|CC|CC d|0~~9999|
1731 |Bit|SB|SB|SB h|0~~FFFF|
1732 |Bit|SM|SM|SM d|0~~2047|
1733 |Bit|STS|STS|STS d|0~~1023|
1734 |Bit|S|S|S d|0~~9999|
1735 |Bit|DX|DX|DX h|0~~FFFF|
1736 |Bit|DY|DY|DY h|0~~FFFF|
1737 |Bit|TS|TS|TS d|0~~9999|
1738 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1739 |Word|W|W|W h|0~~FFFF|
1740 |Word|TN|TN|TN d|0~~99999|
1741 |Word|SN|SN|SN d|0~~99999|
1742 |Word|CN|CN|CN d|0~~99999|
1743 |Word|R|R|R d|0~~99999|
1744 |Word|SW|SW|SW h|0~~FFFF|
1745 |Word|Z|Z|Z d|0~~99999|
1746 |Word|ZR|ZR|ZR h|0~~FFFF|
1747 |Word|D|D|D d|0~~99999|
1748
1749 **Communication Settings**
1750
1751 Enable HMI Ethernet in [Project Settings];
1752
1753 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1754
1755 Set PLC IP in [Device IP] settings;
1756
1757 (% style="text-align:center" %)
1758 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1759
1760 **PLC Settings (GX Works2 )**
1761
1762 Create a project
1763
1764 Set PLC IP, subnet mask and gateway;
1765
1766 Select [Binary Code] as communication data code;
1767
1768 (% style="text-align:center" %)
1769 [[image:image-20221108202109-2.png||height="636" width="732"]]
1770
1771 Set PLC port number, for example 1025
1772
1773 (% style="text-align:center" %)
1774 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1775
1776 Save settings;
1777
1778 Download project into PLC device;
1779
1780 Restart PLC device;
1781
1782 **Cable Wiring**
1783
1784 (% style="text-align:center" %)
1785 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1786
1787 == **QJ71C24N MELSEC Protocol** ==
1788
1789 Mitsubishi QJ71C24N communication module built-in serial port;
1790
1791 **HMI Settings**
1792
1793 |**Items**|**Settings**|**Note**
1794 |Protocol|MIT QJ71 MELSEC|
1795 |Connection|422|
1796 |Baud rate|9600|
1797 |Data bit|8|
1798 |Parity|ODD|
1799 |Stop bit|1|
1800 |PLC station No.|1~~255|Need to be the same as PLC settings
1801
1802 **Address List**
1803
1804 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1805 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1806 |Y|Y|Y FFFF|0~~1FFF|
1807 |M|M|M DDDDD|0~~99999|
1808 |L|L|L DDDD|0~~8191|
1809 |F|F|F DDDD|0~~2047|
1810 |V|V|V DDDD|0~~2047|
1811 |B|B|B FFFF|0~~1FFF|
1812 |TS|TS|TS DDDD|0~~2047|
1813 |TC|TC|TC DDDD|0~~2047|
1814 |SS|SS|SS DDDD|0~~2047|
1815 |SC|SC|SC DDDD|0~~2047|
1816 |CS|CS|CS DDDD|0~~1023|
1817 |CC|CC|CC DDDD|0~~1023|
1818 |SB|SB|SB FFF|0~~7FF|
1819 |S|S|S D|0~~8191|
1820 |DX|DX|DX FFFF|0~~1FFF|
1821 |DY|DY|DY FFFF|0~~1FFF|
1822 |SM_|SM_|SM_ DDDD|8000~~9999|
1823 |SM|SM|SM DDDD|0~~2047|
1824 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1825 |D|D|D DDDDD|0~~12287|
1826 |W|W|W FFFF|0~~1FFF|
1827 |TN|TN|TN DDDD|0~~2047|
1828 |SN|SN|SN DDDD|0~~2047|
1829 |CN|CN|CN DDDD|0~~1023|
1830 |R|R|R DDDDD|0~~32767|
1831 |SW|SW|SW FFF|0~~7FF|
1832 |Z|Z|Z D|0~~15|
1833 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1834
1835 **Communication Settings**
1836
1837 (% style="text-align:center" %)
1838 [[image:image-20221109135738-1.png]]
1839
1840 (% style="text-align:center" %)
1841 [[image:image-20221109140016-3.png]]
1842
1843 Pin Definition Diagram
1844
1845 (% style="text-align:center" %)
1846 [[image:image-20221109140406-4.png]]
1847
1848 == **QJ71E71 MELSEC Protocol** ==
1849
1850 Mitsubishi QJ71E71 Ethernet communication module;
1851
1852 **HMI Settings**
1853
1854 |**Items**|**Settings**|**Note**
1855 |Protocol|MIT QJ71E71 MELSEC|
1856 |Connection|Ethernet|
1857 |Port No.|1025|Must be the same as the PLC setting
1858 |PLC station No.|0|Must be the same as the PLC setting
1859
1860 **Address List**
1861
1862 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1863 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1864 |Y|Y|Y h|0~~1FFF|
1865 |M|M|M d|0~~99999|
1866 |L|L|L d|0~~8191|
1867 |F|F|F d|0~~2047|
1868 |B|B|B h|0~~1FFF|
1869 |V|V|V d|0~~2047|
1870 |TS|TS|TS d|0~~2047|
1871 |TC|TC|TC d|0~~2047|
1872 |SS|SS|SS d|0~~2047|
1873 |SC|SC|SC d|0~~2047|
1874 |CS|CS|CS d|0~~1023|
1875 |CC|CC|CC d|0~~1023|
1876 |SB|SB|SB h|0~~7FF|
1877 |S|S|S d|0~~8191|
1878 |DX|DX|DX h|0~~1FFF|
1879 |DY|DY|DY h|0~~1FFF|
1880 |SM|SM|SM d|8000~~9999|
1881 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1882 |D|D|D d|0~~12287|
1883 |W|W|W h|0~~1FFF|
1884 |TN|TN|TN d|0~~2047|
1885 |SN|SN|SN d|0~~2047|
1886 |CN|CN|CN d|0~~1023|
1887 |R|R|R d|0~~32767|
1888 |SW|SW|SW h|0~~7FF|
1889 |Z|Z|Z d|0~~15|
1890 |ZR|ZR|ZR h|0~~FE7FF|
1891
1892 **HMI Communication Settings**
1893
1894 1) Enable HMI Ethernet in [Project Settings];
1895
1896 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1897
1898 2) Set PLC IP in [Device IP] settings
1899
1900 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1901
1902 **PLC Settings(GX Works2)**
1903
1904 * Click [Ethernet/CC IE/MELSECNET];
1905 * Please select [Ethernet] as network type;
1906 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1907 * Select [Online] as Mode;
1908 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1909 * Click [Operation setting] to set IP;
1910 * Select [Binary Code] as [Communication Data Code];
1911 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1912 * Click [Open setting]
1913 * Set protocol: TCP;
1914 * Set [unpassive] in [Open system];
1915 * Set [receive] in [Fixed buffer];
1916 * Set [procedure Exist] in [Fixed buffer communication];
1917 * Disable [Pairing open];
1918 * Set [No confirm] in [Existence confirmation];
1919 * Host station port number: 5009;
1920 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1921 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1922 * Download project into PLC and restart it
1923
1924 **Cable Wiring**
1925
1926 (% style="text-align:center" %)
1927 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1928
1929 = Create communication with **MODBUS** =
1930
1931 == **MODBUS RTU Master** ==
1932
1933 Supported Series: MODBUS RTU CONTROLLER
1934
1935 HMI works as MODBUS SLAVE connecting with MASTER
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1939
1940 (% style="text-align:center" %)
1941 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1942
1943 (% style="text-align:center" %)
1944 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1945
1946 **HMI Settings**
1947
1948 |**Items**|**Settings**|**Note**
1949 |Protocol|MODBUS RTU Master|
1950 |Connection|RS485/RS232|
1951 |Baud rate|2400~~187500|
1952 |Data bit|8|
1953 |Parity|Even/ Odd/ None|
1954 |Stop bit|1/2|
1955 |Station No.|0~~255|
1956
1957 **Address List**
1958
1959 |**Type**|**HMI address**|**MODBUS code**|**Range**
1960 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1961 |Word|HDW3500~~HDW7999|4|0~~4499
1962
1963 **Cable Wiring**
1964
1965 * **RS485**
1966
1967 (% style="text-align:center" %)
1968 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1969
1970 (% style="text-align:center" %)
1971 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1972
1973 * **RS232**
1974
1975 (% style="text-align:center" %)
1976 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1977
1978 **✎Note:** COM3 only available in PI8000/PI9000 series.
1979
1980 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1981
1982 Supported Series: MODBUS RTU CONTROLLER
1983
1984 HMI works as MODBUS MASTER connecting with SLAVE.
1985
1986 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1990
1991 (% style="text-align:center" %)
1992 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1993
1994 (% style="text-align:center" %)
1995 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1996
1997 **HMI Settings**
1998
1999 |**Items**|**Settings**|**Note**
2000 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2001 |Connection|RS485/RS232|
2002 |Baud rate|2400~~187500|
2003 |Data bit|8|
2004 |Parity|Even/ Odd/ None|
2005 |Stop bit|1/2|
2006 |PLC station No.|0~~255|
2007
2008 **Address List**
2009
2010 |**Type**|**Address Type**|**Function code & Description**
2011 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2015 |06 (write single register: write a binary value to a holding register)
2016 |10 (write values to multiple addresses )
2017 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2018 |06 (write single register: write a binary value to a holding register)
2019 |10 (write values to multiple addresses )
2020 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2021 |10 (write values to multiple addresses )
2022 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits, ie write continuously)
2025 |(% rowspan="3" %)1|02 (Read the input state)
2026 |05 (Force a single coil to force the on/off state of a logic coil)
2027 |0F (Write multiple bits)
2028 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2029 |05 (Force a single coil to force the on/off state of a logic coil)
2030 |0F (Write multiple bits)
2031 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2032 |0F (Write multiple bits)
2033
2034 **✎Note:**
2035
2036 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2037 * The function codes sent out are the same as those that read and write words.
2038
2039 **Station number for more than one slaves**
2040
2041 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2042
2043 (% style="text-align:center" %)
2044 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2045
2046 **Cable Wiring**
2047
2048 * **RS485**
2049
2050 (% style="text-align:center" %)
2051 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2052
2053 (% style="text-align:center" %)
2054 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2055
2056 * **RS232**
2057
2058 (% style="text-align:center" %)
2059 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2060
2061 **✎Note:** COM3 only available in PI8000/PI9000 series.
2062
2063 == **Communicate with Modbus Meter** ==
2064
2065 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2066
2067 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2068
2069 (% style="text-align:center" %)
2070 [[image:LinfeeDiagram.png]]
2071
2072 2. Check the specific Modbus parameter in the communication menu from LED display.
2073
2074 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2075
2076 {{info}}
2077 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2078 {{/info}}
2079
2080 (% style="text-align:center" %)
2081 [[image:MeterModbusAllView.png]]
2082
2083 3. Create new project and change the Communication settings.
2084
2085 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2086
2087 (% style="text-align:center" %)
2088 [[image:PIStudioSetupMeterModbusPara.png]]
2089
2090 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2091
2092 The following table is intercept part of the manual for Linfee Modbus manual.
2093
2094 **0x03/0x04 command data register address**:
2095
2096 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2097 | HEX|DEC| | | |
2098 |0x00|0|Reserved| | |
2099 |0x02|2|Reserved| | |
2100 |0x04|4|Reserved| | |
2101 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2102 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2103 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2104 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2105 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2106 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2107 |0x12|18|Ia|float|2|Phase Current data, Unit A
2108 |0x14|20|Ib|float|2|Phase Current data, Unit A
2109 |0x16|22|Ic|float|2|Phase Current data, Unit A
2110
2111 {{info}}
2112 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2113 {{/info}}
2114
2115 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2116
2117 (% style="text-align:center" %)
2118 [[image:MeterModbusPInumericSet.png]]
2119
2120 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2121
2122 (% style="text-align:center" %)
2123 [[image:MeterModbusNumericInputFormat.png]]
2124
2125 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2126
2127 (% style="text-align:center" %)
2128 [[image:ActualHMIModbusResult.jpg]]
2129
2130 == **MODBUS TCP Slave (All function)** ==
2131
2132 Supported series: MODBUS TCP controller
2133
2134 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2138
2139 (% style="text-align:center" %)
2140 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2141
2142 (% style="text-align:center" %)
2143 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2144
2145 **HMI Setting**
2146
2147 |**Items**|**Settings**|**Note**
2148 |Protocol|MODBUS TCP Slave (All function)|
2149 |Connection|Ethernet|
2150 |Port No.|502|
2151 |PLC station No.|1|
2152
2153 **Address List**
2154
2155 |**Type**|**Register**|**Function code & Description**
2156 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2160 |06 (write single register: write a binary value to a holding register)
2161 |10 (write values to multiple addresses )
2162 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2163 |06 (write single register: write a binary value to a holding register)
2164 |10 (write values to multiple addresses )
2165 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2166 |10 (write values to multiple addresses )
2167 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits, ie write continuously)
2170 |(% rowspan="3" %)1|02 (Read the input state)
2171 |05 (Force a single coil to force the on/off state of a logic coil)
2172 |0F (Write multiple bits)
2173 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2174 |05 (Force a single coil to force the on/off state of a logic coil)
2175 |0F (Write multiple bits)
2176 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2177 |0F (Write multiple bits)
2178
2179 **Communication Settings**
2180
2181 Enable HMI Ethernet in [Project Settings];
2182
2183 (% style="text-align:center" %)
2184 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2185
2186 Set PLC IP in [Device IP] settings;
2187
2188 (% style="text-align:center" %)
2189 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2190
2191 **Cable Wiring**
2192
2193 (% style="text-align:center" %)
2194 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2195
2196 = Create communication with **Omron** PLC =
2197
2198 == CJ TCP FINS Ethemet  Protocol ==
2199
2200 Supported device:CJ series、CJ1W-EIP21
2201
2202 **HMI Settings**
2203
2204 |=**Items**|=**Settings**|=**Note**
2205 |Protocol|OMRON CJ TCP FINS Ethemet|
2206 |Connection|Ethernet|
2207 |Port No.|9600|
2208 |Device No.|0|
2209 |HMI No.|0|(((
2210
2211 )))
2212
2213 **Address List**
2214
2215 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2216 |Bit|CIO|CIO|CIO d|0~~99999|
2217 |Bit|W|W|W d|0~~99999|
2218 |Bit|D|D|D d|0~~99999|
2219 |Bit|H|H|H d|0~~99999|
2220 |Bit|A|A|A d|0~~99999|
2221 |Bit|T|T|T h|0~~99999|
2222 |Bit|CF|CF|CF d|0~~99999|
2223 |Bit|FF|FF|FF d|0~~99999|
2224 |Bit|C|C|C d|0~~99999|
2225 |Bit|EM0|EM0|EM0 d|0~~99999|
2226 |Bit|EM1|EM1|EM1 d|0~~99999|
2227 |Bit|EM2|EM2|EM2 d|0~~99999|
2228 |Bit|EM3|EM3|EM3 d|0~~99999|
2229 |Bit|EM4|EM4|EM4 d|0~~99999|
2230 |Bit|EM5|EM5|EM5 h|0~~99999|
2231 |Bit|EM6|EM6|EM6 d|0~~99999|
2232 |Bit|EM7|EM7|EM7 d|0~~99999|
2233 |Bit|EM8|EM8|EM8 d|0~~99999|
2234 |Bit|EM9|EM9|EM9 d|0~~99999|
2235 |Bit|EMA|EMA|EMA d|0~~99999|
2236 |Bit|EMB|EMB|EMB d|0~~99999|
2237 |Bit|EMC|EMC|EMC d|0~~99999|
2238 |Bit|Lamp|Lamp|Lamp d|0~~0|
2239 |Word|CIO|CIO|CIO d|0~~99999|
2240 |Word|W|W|W d|0~~99999|
2241 |Word|D|D|D d|0~~99999|
2242 |Word|H|H|H d|0~~99999|
2243 |Word|A|A|A d|0~~99999|
2244 |Word|T|T|T h|0~~99999|
2245 |Word|CF|CF|CF d|0~~99999|
2246 |Word|FF|FF|FF d|0~~99999|
2247 |Word|C|C|C d|0~~99999|
2248 |Word|EM0|EM0|EM0 d|0~~99999|
2249 |Word|EM1|EM1|EM1 d|0~~99999|
2250 |Word|EM2|EM2|EM2 d|0~~99999|
2251 |Word|EM3|EM3|EM3 d|0~~99999|
2252 |Word|EM4|EM4|EM4 d|0~~99999|
2253 |Word|EM5|EM5|EM5 h|0~~99999|
2254 |Word|EM6|EM6|EM6 d|0~~99999|
2255 |Word|EM7|EM7|EM7 d|0~~99999|
2256 |Word|EM8|EM8|EM8 d|0~~99999|
2257 |Word|EM9|EM9|EM9 d|0~~99999|
2258 |Word|EMA|EMA|EMA d|0~~99999|
2259 |Word|EMB|EMB|EMB d|0~~99999|
2260 |Word|EMC|EMC|EMC d|0~~99999|
2261 |Word|IR|IR|IR d|0~~99999|
2262 |Word|DR|DR|DR d|0~~99999|
2263
2264 **Configure the communication protocol**
2265
2266 (% style="text-align:center" %)
2267 [[image:image-20220830143348-1.png]]
2268
2269 (% style="text-align:center" %)
2270 [[image:image-20220830143511-2.png]]
2271
2272 **Configure CJ1W-EIP21 connect with HMI**
2273
2274 (% style="text-align:center" %)
2275 [[image:ftEVGvAprh.png]]
2276
2277 Select TCP_Client_2N
2278
2279 (% style="text-align:center" %)
2280 [[image:RURXWcgyCd.png]]
2281
2282 **Cable Wiring**
2283
2284 Pin Definition Diagram
2285
2286 (% style="text-align:center" %)
2287 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2288
2289 == **CP1E/CP1H serial protocol** ==
2290
2291 Supported device: OMRON CS1(CP1E/CP1H)
2292
2293 **PLC Settings(CX-Programmer)**
2294
2295 Open cx-programmer, create a new PLC project or open the project that has been created.
2296 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
2297
2298 (% style="text-align:center" %)
2299 [[image:1.2 工程新建D.png]]
2300
2301 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
2302
2303 (% style="text-align:center" %)
2304 [[image:1.3 串口参数的查看-配置D.png]]
2305
2306 **HMI Settings**
2307
2308 |=**Items**|=**Settings**|=**Note**
2309 |Protocol|OMRON CS1(CP1E/CP1H)|
2310 |Connection|RS232 (9600, 2, 7, EVEN)|
2311 |Port No.|None|
2312 |PLC station No.|0|
2313
2314 **Address List**
2315
2316 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2317 |Bit|CIO|CIO|CIO d|0~~99999|
2318 |Bit|W|W|W d|0~~99999|
2319 |Bit|D|D|D d|0~~99999|
2320 |Bit|H|H|H d|0~~99999|
2321 |Bit|A|A|A d|0~~99999|
2322 |Bit|TF|T|T h|0~~99999|
2323 |Bit|CF|CF|CF d|0~~99999|
2324 |Bit|T|FF|FF d|0~~99999|
2325 |Bit|C|C|C d|0~~99999|
2326 |Bit|EM0|EM0|EM0 d|0~~99999|
2327 |Bit|EM1|EM1|EM1 d|0~~99999|
2328 |Bit|EM2|EM2|EM2 d|0~~99999|
2329 |Bit|EM3|EM3|EM3 d|0~~99999|
2330 |Bit|EM4|EM4|EM4 d|0~~99999|
2331 |Bit|EM5|EM5|EM5 h|0~~99999|
2332 |Bit|EM6|EM6|EM6 d|0~~99999|
2333 |Bit|EM7|EM7|EM7 d|0~~99999|
2334 |Bit|EM8|EM8|EM8 d|0~~99999|
2335 |Bit|EM9|EM9|EM9 d|0~~99999|
2336 |Bit|EMA|EMA|EMA d|0~~99999|
2337 |Bit|EMB|EMB|EMB d|0~~99999|
2338 |Bit|EMC|EMC|EMC d|0~~99999|
2339 |Word|CIO|CIO|CIO d|0~~99999|
2340 |Word|W|W|W d|0~~99999|
2341 |Word|D|D|D d|0~~99999|
2342 |Word|H|H|H d|0~~99999|
2343 |Word|A|A|A d|0~~99999|
2344 |Word|T|T|T h|0~~99999|
2345 |Word|CIO|CF|CF d|0~~99999|
2346 |Word|C|C|C d|0~~99999|
2347 |Word|EM0|EM0|EM0 d|0~~99999|
2348 |Word|EM1|EM1|EM1 d|0~~99999|
2349 |Word|EM2|EM2|EM2 d|0~~99999|
2350 |Word|EM3|EM3|EM3 d|0~~99999|
2351 |Word|EM4|EM4|EM4 d|0~~99999|
2352 |Word|EM5|EM5|EM5 h|0~~99999|
2353 |Word|EM6|EM6|EM6 d|0~~99999|
2354 |Word|EM7|EM7|EM7 d|0~~99999|
2355 |Word|EM8|EM8|EM8 d|0~~99999|
2356 |Word|EM9|EM9|EM9 d|0~~99999|
2357 |Word|EMA|EMA|EMA d|0~~99999|
2358 |Word|EMB|EMB|EMB d|0~~99999|
2359 |Word|EMC|EMC|EMC d|0~~99999|
2360 |Word|IR|IR|IR d|0~~99999|
2361 |Word|DR|DR|DR d|0~~99999|
2362
2363 **Configure the communication protocol**
2364
2365 (% style="text-align:center" %)
2366 [[image:image-20220902153118-1.png]]
2367
2368 (% style="text-align:center" %)
2369 [[image:image-20220902151322-2.png]]
2370
2371 **Cable Wiring**
2372
2373 (% style="text-align:center" %)
2374 [[image:图片3.png||alt="image-20220902153949-2.png"]]
2375
2376 Pin Definition Diagram
2377
2378 (% style="text-align:center" %)
2379 [[image:3.1.2 接口.png||alt="image-20220902154056-3.png" height="235" width="332"]]
2380
2381 == **EC55 Protocol** ==
2382
2383 Supported device: EC55 temperature instrument
2384
2385 **1)HMI Settings**
2386
2387 |**Items**|**Settings**|**Note**
2388 |Protocol|Omron EC55|
2389 |Connection|RS485 (9600, 2, 7, EVEN)|
2390 |Port No.|None|
2391 |PLC station No.|0|
2392
2393 **2)Address List**
2394
2395 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2396 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2397 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2398 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2399 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2400 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2401 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2402 |CP|-|0-6|Read controller intrinsic property
2403 |CS|-|0-2|Read controller states
2404 |CA|-|0-17|Action command
2405
2406 **3)Device Settings**
2407
2408 Omron E5CC PLC configuration
2409
2410 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2411
2412 (% style="text-align:center" %)
2413 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2414
2415 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2416
2417 (% style="text-align:center" %)
2418 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2419
2420 **✎Note:** The communication settings for HMI should be consistent with this setting.
2421
2422 **Cable Wiring**
2423
2424 (% style="text-align:center" %)
2425 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2426
2427 (% style="text-align:center" %)
2428 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2429
2430 **✎Note:**
2431
2432 * COM3 only available in PI8000/PI9000 series.
2433 * CA address could not support continuous writing function;
2434 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2435 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2436 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2437 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2438 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2439 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2440 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2441
2442 == **EtherNet/IP NX series Protocol** ==
2443
2444 Supported series: Omron NX/NJ series
2445
2446 **HMI Setting**
2447
2448 |**Items**|**Settings**|**Note**
2449 |Protocol|Omron NX Ethernet/IP|
2450 |Connection|Ethernet|
2451 |Port No.|44818|
2452 |PLC station No.|1|
2453
2454 **Instruction**
2455
2456 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2457
2458 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2459
2460 (% style="text-align:center" %)
2461 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2462
2463 **Export labels from Sysmac Studio**
2464
2465 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2466
2467 (% style="text-align:center" %)
2468 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2469
2470 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2471
2472 Click [Label manage];
2473
2474 (% style="text-align:center" %)
2475 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2476
2477 Click [Import labels] and then select the file exported in step 1;
2478
2479 (% style="text-align:center" %)
2480 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2481
2482 The Import Status field shows the result, click [OK] to finish importing address labels;
2483
2484 (% style="text-align:center" %)
2485 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2486
2487 **Communication Settings**
2488
2489 Enable HMI Ethernet in [Project Settings];
2490
2491 (% style="text-align:center" %)
2492 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2493
2494 Set PLC IP in [Device IP] settings;
2495
2496 (% style="text-align:center" %)
2497 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2498
2499 (% style="text-align:center" %)
2500 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2501
2502 **Cable Wiring**
2503
2504 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2505
2506 == CV/CJ1M/CS1H ==
2507
2508 **HMI Setting:**
2509
2510 |=**Parameters**|=**Recommended**
2511 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H Series
2512 |=**PLC I/F**|RS232
2513 |=**Baud rate**|9600
2514 |=**Data bits**|7
2515 |=**Parity**|Even
2516 |=**Stop bits**|2
2517 |=**PLC sta. no.**|0
2518
2519 **PLC Setting:**
2520
2521 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2522
2523 **Device Address:**
2524
2525 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2526 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2527 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2528 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2529 |=B|H|DDDDdd|0 ~~ 409515|
2530 |=B|A|DDDDdd|0 ~~ 409515|
2531 |=B|TF|DDDDdd|0 ~~ 409515|
2532 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2533 |=B|T|DDDD|0 ~~ 4095|
2534 |=B|C|DDDD|0 ~~ 4095|
2535 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2536 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2537 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2538 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2539 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2540 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2541 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2542 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2543 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2544 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2545 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2546 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2547 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2548 |=B|Lamp|D|0~~0|
2549
2550 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2551 |=W|LR_W|DDDD|0 ~~ 4095|
2552 |=W|TC|DDD|0 ~~ 511|
2553 |=W|DM|DDDD|0 ~~ 9999|Data Register
2554
2555 **Wiring Diagram:**
2556
2557 **RS-232**
2558
2559 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2560
2561 Communication Module:
2562
2563 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2564
2565 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2566
2567 (% style="text-align:center" %)
2568 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2569
2570 = Create communication with **Rockwell PLC** =
2571
2572 == **DF1 Protocol** ==
2573
2574 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2575
2576 **HMI Settings**
2577
2578 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2579 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2580 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2581 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2582 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2583 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2584 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2585 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2586 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2587
2588 **PLC Settings**
2589
2590 DF1 Full Duplex protocol and CRC error check
2591
2592 **Address List**
2593
2594 (% class="table-bordered" %)
2595 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2596 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2597 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2598 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2599 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2600 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2601 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2602 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2603 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2604 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2605 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2606 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2607
2608 **Cable Wiring**
2609
2610 (% style="text-align:center" %)
2611 [[image:AB.gif]]
2612
2613 == **DF1 Advanced Protocol** ==
2614
2615 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2616
2617 **HMI Settings**
2618
2619 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2620 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2621 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2622 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2623 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2624 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2625 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2626 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2627 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2628
2629 **PLC Settings**
2630
2631 DF1 Full Duplex protocol and CRC error check
2632
2633 **Address List**
2634
2635 (% class="table-bordered" %)
2636 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2637 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2638 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2639 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2640 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2641 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2642 Bit data file B0~~B99
2643
2644 First two digits is for file number
2645
2646 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2647 )))
2648 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2649 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2650 Integer data file bit format N0~~N99
2651
2652 First two digits is for file number
2653
2654 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2655 )))
2656 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2657 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2658 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2659 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2660 Timer Preset Value
2661
2662 First two digits is for file number
2663
2664 For example, TNS99255 represents file number T99, address 255.
2665 )))
2666 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2667 Timer Accumulator Value
2668
2669 First two digits is for file number
2670
2671 For example, TNP99255 represents file number T99, address 255.
2672 )))
2673 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2674 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2675 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2676 Counter Preset Value
2677
2678 First two digits is for file number
2679
2680 For example, CNS99255 represents file number C99, address 255.
2681 )))
2682 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2683 Counter Accumulator Value
2684
2685 First two digits is for file number
2686
2687 For example, CNP99255 represents file number C99, address 255.
2688 )))
2689 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2690 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2691 Integer data file
2692
2693 First two digits is for file number
2694
2695 For example, NN99255 represents file number N99, address 255.
2696 )))
2697 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2698 Only able to communicate with file number F8
2699 )))
2700 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2701 Floating point data file
2702
2703 First two digits is for file number
2704
2705 For example, FN99255 represents file number F99, address 255.
2706 )))
2707 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2708
2709 **Cable Wiring**
2710
2711 (% style="text-align:center" %)
2712 [[image:AB.gif]]
2713
2714 == **MicroLogix Protocol** ==
2715
2716 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2717
2718 **HMI Settings**
2719
2720 (% class="table-bordered" %)
2721 |**Item**|**Settings**|**Note**
2722 |Protocol|Allen-Bradlley MicroLogix|
2723 |Connection|RS232|
2724 |Baud rate|19200|
2725 |Data bit|8|
2726 |Parity|None|
2727 |Stop bit|1|
2728 |PLC station No.|1|
2729
2730 **Address List**
2731
2732 (% class="table-bordered" %)
2733 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2734 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2735 |O|O d.d|0.0~~255.15|
2736 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2737 |S|S d.d|0.0~~255.15|
2738 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2739 |(% rowspan="9" %)Word|S|S d|0~~255|
2740 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2741 |TP|TP nnhh|0~~ffff
2742 |CS|CS nnhh|0~~ffff
2743 |CP|CP nnhh|0~~ffff
2744 |N|N nnhh|0~~ffff
2745 |C|C nnhh|0~~ffff
2746 |T|T nnhh|0~~ffff
2747 |R|R nnhh|0~~ffff
2748
2749 **Cable Wiring**
2750
2751 (% style="text-align:center" %)
2752 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2753
2754 == **CompactLogix FreeTag Ethernet protocol** ==
2755
2756 Allen-Brandly CompactLogix
2757
2758 **HMI Settings**
2759
2760 (% class="table-bordered" %)
2761 |**Items**|**Settings**|**Note**
2762 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
2763 |Connection|Ethernet|
2764 |Port No.|44818|
2765
2766 **PLC Setting**
2767
2768 Create new tags
2769
2770 (% style="text-align:center" %)
2771 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2772
2773 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2774
2775 (% style="text-align:center" %)
2776 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2777
2778 Import labels, please open [Communication] window and click [Import label];
2779
2780 Select csv file, all tags will be displayed as belows;
2781
2782 (% style="text-align:center" %)
2783 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2784
2785 **✎Note:**
2786
2787 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2788
2789 (% style="text-align:center" %)
2790 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2791
2792 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2793
2794 **Communication settings in HMI**
2795
2796 Enable HMI Ethernet in [Project Settings];
2797
2798 (% style="text-align:center" %)
2799 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2800
2801 Set PLC IP in [Device IP] settings;
2802
2803 (% style="text-align:center" %)
2804 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2805
2806 **Cable Wiring**
2807
2808 (% style="text-align:center" %)
2809 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2810
2811 == **MicroLogix 1200** **protocol** ==
2812
2813 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2814
2815 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2816 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2817 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2818 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2819
2820 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2821
2822 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2823 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2824 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2825 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2826 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2827 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2828 |**PLC word address type**|**Address format**|**Address range**
2829 |S|ddd|S0 ~~ 255
2830 |TS|ffff|TS0 ~~ FFFF
2831 |TP|ffff|TP0 ~~ FFFF
2832 |CS|ffff|CS0 ~~ FFFF
2833 |CP|ffff|CP0 ~~ FFFF
2834 |N|ffff|N0 ~~ FFFF
2835 |F|ffff|F0 ~~ FFFF
2836
2837 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens PLC** =
2838
2839 == **S7-200 Smart Ethernet Protocol** ==
2840
2841 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2842
2843 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2844
2845 **HMI Setting**
2846
2847 (% class="table-bordered" %)
2848 |**Items**|**Settings**|**Note**
2849 |Protocol|Simens S7-200 Smart Ethernet|
2850 |Connection|Ethernet|
2851 |Port No.|102|
2852 |PLC station No.|2|
2853
2854 **Address List**
2855
2856 (% class="table-bordered" %)
2857 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2858 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2859 |Q|Q|Q ddddd.o|0.0~~99999.7|
2860 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2861 |V|V|V ddddd.o|0.0~~99999.7|
2862 |M|M|M ddddd.o|0.0~~99999.7|
2863 |SM|SM|ddddd.o|0.0~~99999.7|
2864 |S|S|ddddd.o|0.0~~99999.7|Read only
2865 |T|T|ddddd|0~~99999|Timer state, read only
2866 |C|C|ddddd|0~~99999|Counter state, read only
2867 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2868 |Q|QW|QW ddddd|0~~99999|
2869 |AI|AIW|AIW ddddd|0~~99999|
2870 |AQ|VB|VB ddddd|0~~99999|
2871 |V|VW|VW ddddd|0~~99998|(((
2872 VW0=VB (0~~1)
2873
2874 VW2=VB (2~~3)
2875
2876 Address value is a multiple of 2
2877 )))
2878 |V|VD|VD ddddd|0~~99998|(((
2879 VD0=VB (0~~3)
2880
2881 VD2=VB (4~~7)
2882
2883 Address value is a multiple of 4
2884 )))
2885 |M|MB|MB ddddd|0~~99999|
2886 |M|MW|MW ddddd|0~~99999|(((
2887 MW0=MB(0~~1)
2888
2889 MW2=MB(2~~3)
2890
2891 Address value is a multiple of 2
2892 )))
2893 |M|MD|MD ddddd|0~~99999|(((
2894 MD0=MB(0~~3)
2895
2896 MD4=MB(4~~7)
2897
2898 Address value is a multiple of 4
2899 )))
2900 |T|TW|TW ddddd|0~~99999|Value of timer
2901 |C|CW|CW ddddd|0~~99999|Value of counter
2902 |W|SW|SW ddddd|0~~99999|
2903
2904 **Communication Settings**
2905
2906 Enable HMI Ethernet in [Project Settings];
2907
2908 (% style="text-align:center" %)
2909 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2910
2911 Set PLC IP in [Device IP] settings;
2912
2913 (% style="text-align:center" %)
2914 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2915
2916 * PLC IP Address: PLC IP
2917 * PLC pot No.: 102(fixed)
2918 * Network:TCP_Client_2N(fixed)
2919
2920 (% style="text-align:center" %)
2921 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2922
2923 * Wait timeout: depend on actual network situation (more than 1500 ms)
2924
2925 **Cable Wiring**
2926
2927 (% style="text-align:center" %)
2928 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2929
2930 == **S7-300 Ethernet Protocol** ==
2931
2932 Supported Series: Siemens S7-300 series PLC
2933
2934 **HMI Setting**
2935
2936 (% class="table-bordered" %)
2937 |**Items**|**Settings**|**Note**
2938 |Protocol|Simens S7-300 Ethernet|
2939 |Connection|Ethernet|
2940 |Port No.|102|
2941 |PLC station No.|2|Need to be same as the PLC setting
2942
2943 **Address List**
2944
2945 (% class="table-bordered" %)
2946 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2947 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2948 |Q|Q|Q ddddd.o|0.0~~99999.7|
2949 |M|M|M ddddd.o|0.0~~99999.7|
2950 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2951 nnnn: block number;
2952
2953 dddd: address;
2954 )))
2955 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2956 |Q|QW|QW ddddd|0~~99999|
2957 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2958 |MW|MW ddddd|0~~99999|(((
2959 MW0=MB(0~~1)
2960
2961 MW2=MB(2~~3)
2962
2963 Address value is a multiple of 2
2964 )))
2965 |MD|MD ddddd|0~~99999|(((
2966 MD0=MB(0~~3)
2967
2968 MD4=MB(4~~7)
2969
2970 Address value is a multiple of 4
2971 )))
2972 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
2973 nnnn: block number;
2974
2975 dddd: address
2976 )))
2977 |DBxDBW|DBxDBW nnnndddd|0~~99999999
2978 |DBxDBD|DBxDBD nnnndddd|0~~99999999
2979
2980 **Communication Settings**
2981
2982 Enable HMI Ethernet in [Project Settings];
2983
2984 (% style="text-align:center" %)
2985 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2986
2987 Set PLC IP in [Device IP] settings;
2988
2989 (% style="text-align:center" %)
2990 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2991
2992 * PLC IP Address: PLC IP
2993 * PLC pot No.: 102(fixed)
2994 * Network:TCP_Client_2N(fixed)
2995
2996 (% style="text-align:center" %)
2997 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2998
2999 * Wait timeout: depend on actual network situation (more than 1500 ms)
3000
3001 **Cable Wiring**
3002
3003 (% style="text-align:center" %)
3004 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3005
3006 == **S7-1200 Ethernet Protocol** ==
3007
3008 Supported Series: Siemens S7-1200
3009
3010 **HMI Setting**
3011
3012 (% class="table-bordered" %)
3013 |**Items**|**Settings**|**Note**
3014 |Protocol|Siemens S7-1200|
3015 |Connection|Ethernet|
3016 |Port No.|102|
3017 |PLC station No.|2|
3018
3019 **Address List**
3020
3021 (% class="table-bordered" %)
3022 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3023 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3024 d:0~-~-9999
3025
3026 o:0-7
3027 )))|
3028 |Q|Q|Q d.o|(((
3029 d:0~-~-9999
3030
3031 o:0-7
3032 )))|
3033 |M|M|M d.o|(((
3034 d:0~-~-9999
3035
3036 o:0-7
3037 )))|
3038 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3039 nn:0-9999,
3040
3041 dddd:0-9999,
3042
3043 o:0-7
3044 )))|(((
3045 nn:DB No.
3046
3047 dddd:address value
3048
3049 o: digit address
3050 )))
3051 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3052 |M|MW|MW d|d:0-99999|(((
3053 MW0=MB(0~~1)
3054
3055 MW2=MB(2~~3)
3056
3057 Address value is a multiple of 2
3058 )))
3059 |M|MD|MD d|d:0-99999|(((
3060 MD0=MB(0~~3)
3061
3062 MD4=MB(4~~7)
3063
3064 Address value is a multiple of 4
3065 )))
3066 |I|IW|IW d|d:0-99999|
3067 |Q|QW|QW d|d:0-99999|
3068 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3069 nn:0-9999
3070
3071 dddd:0-9999
3072 )))|(((
3073 nn:DB No.
3074
3075 dddd:address value
3076 )))
3077 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3078 nn:0-9999
3079
3080 dddd:0-9999
3081 )))|(((
3082 nn:DB No.
3083
3084 dddd:address value
3085
3086 Address value is a multiple of 2
3087 )))
3088 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3089 nn:0-9999
3090
3091 dddd:0-9999
3092 )))|(((
3093 nn:DB No.
3094
3095 dddd:address value
3096
3097 Address value is a multiple of 4
3098 )))
3099
3100 **Communication Settings**
3101
3102 Enable HMI Ethernet in [Project Settings];
3103
3104 (% style="text-align:center" %)
3105 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3106
3107 Set PLC IP in [Device IP] settings;
3108
3109 (% style="text-align:center" %)
3110 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3111
3112 **✎Note:**
3113
3114 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3115 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3116 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3117 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3118
3119 **PLC Settings**
3120
3121 Add BD
3122
3123 * Please uncheck [Symbolic access only] option;
3124
3125 (% style="text-align:center" %)
3126 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3127
3128 Address settings, using BD2 as example.
3129
3130 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3131 * 2 represent DB block number
3132 * xxxx represent address
3133
3134 **Such as:**
3135
3136 * DBxDBB20000 = DB2.DBB0
3137 * DBxDBW20004 = DB2.DBW4
3138
3139 (% style="text-align:center" %)
3140 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3141
3142 **How to connect with S7-1200 Firmware V4.0**
3143
3144 PLC configuration
3145
3146 * Double click [device configuration] in Siemens via software
3147 * Double click [protection] to enter protection configuration screen
3148
3149 (% style="text-align:center" %)
3150 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3151
3152 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3153
3154 (% style="text-align:center" %)
3155 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3156
3157 DB settings
3158
3159 * Right click [DB], select [properties]
3160 * Uncheck [optimized block access]
3161
3162 **Cable Wiring**
3163
3164 (% style="text-align:center" %)
3165 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3166
3167 == **S7-XXX Ethernet Protocol** ==
3168
3169 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3170
3171 **HMI Setting**
3172
3173 (% class="table-bordered" style="width:823px" %)
3174 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3175 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3176 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3177 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3178 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3179 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3180
3181 Slot from TIA Portal is equal to Device No. of PIStudio
3182
3183 Rack from TIA Portal is equal to HMI No. of PIStudio
3184
3185 (% style="text-align:center" %)
3186 [[image:S7-XXXCommunication Settings.png]]
3187
3188 (% style="text-align:center" %)
3189 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3190
3191 **Address List**
3192
3193 (% class="table-bordered" %)
3194 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3195 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3196 d:0~-~-9999
3197
3198 o:0-7
3199 )))|
3200 |Q|Q|Q d.o|(((
3201 d:0~-~-9999
3202
3203 o:0-7
3204 )))|
3205 |M|M|M d.o|(((
3206 d:0~-~-9999
3207
3208 o:0-7
3209 )))|
3210 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3211 nn:0-9999,
3212
3213 dddd:0-9999,
3214
3215 o:0-7
3216 )))|(((
3217 nn:DB No.
3218
3219 dddd:address value
3220
3221 o: digit address
3222 )))
3223 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3224 |M|MW|MW d|d:0-99999|(((
3225 MW0=MB(0~~1)
3226
3227 MW2=MB(2~~3)
3228
3229 Address value is a multiple of 2
3230 )))
3231 |M|MD|MD d|d:0-99999|(((
3232 MD0=MB(0~~3)
3233
3234 MD4=MB(4~~7)
3235
3236 Address value is a multiple of 4
3237 )))
3238 |I|IW|IW d|d:0-99999|
3239 |Q|QW|QW d|d:0-99999|
3240 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3241 nn:0-9999
3242
3243 dddd:0-9999
3244 )))|(((
3245 nn:DB No.
3246
3247 dddd:address value
3248 )))
3249 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3250 nn:0-9999
3251
3252 dddd:0-9999
3253 )))|(((
3254 nn:DB No.
3255
3256 dddd:address value
3257
3258 Address value is a multiple of 2
3259 )))
3260 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3261 nn:0-9999
3262
3263 dddd:0-9999
3264 )))|(((
3265 nn:DB No.
3266
3267 dddd:address value
3268
3269 Address value is a multiple of 4
3270 )))
3271
3272 **Communication Settings**
3273
3274 Enable HMI Ethernet in [Project Settings];
3275
3276 (% style="text-align:center" %)
3277 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3278
3279 Set PLC IP in [Device IP] settings;
3280
3281 (% style="text-align:center" %)
3282 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3283
3284 **✎Note:**
3285
3286 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3287 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3288
3289 **Cable Wiring**
3290
3291 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3292
3293 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
3294
3295 Supported Series: Siemens Logo 0BA0, 0BA1 series
3296
3297 **HMI Settings**
3298
3299 (% class="table-bordered" %)
3300 |**Items**|**Settings**|**Note**
3301 |Protocol|Siemens LOGO|
3302 |Connection|Ethernet|
3303 |Port No.|102|
3304 |PLC station No.|2|
3305
3306 **Address List**
3307
3308 (% class="table-bordered" %)
3309 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3310 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3311 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3312 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3313 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3314 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3315 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3316 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3317 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3318 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3319 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3320 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3321 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3322 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3323 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3324 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3325
3326 **PLC Settings in LOGO Software:**
3327
3328 Click [Tools]~-~-[Ethernet Connections],shown as below.
3329
3330 (% style="text-align:center" %)
3331 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3332
3333 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3334
3335 (% style="text-align:center" %)
3336 [[image:image-20221228142937-4.png]]
3337
3338 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3339
3340 (% style="text-align:center" %)
3341 [[image:image-20221228143047-5.png]]
3342
3343 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3344
3345 (% style="text-align:center" %)
3346 [[image:image-20221228143246-6.png]]
3347
3348
3349 **HMI Communication Settings**
3350
3351 Set PLC IP in [Device IP] settings;
3352
3353 (% style="text-align:center" %)
3354 [[image:image-20221228143614-7.png]]
3355
3356 Enable HMI Ethernet in [Project Settings];
3357
3358 (% style="text-align:center" %)
3359 [[image:image-20221228144229-9.png]]
3360
3361 TSAP setting
3362
3363 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3364 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3365 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3366 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3367 ie, ig series: use HSW1200, HSW1201.
3368 HMI V2.0: use HSW1200, HSW1201.
3369
3370 **✎Note:**
3371
3372 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3373 * HSW10119/HSW1201 is set up as shown.
3374 * (((
3375 (% style="text-align:center" %)
3376 [[image:image-20221228144800-11.png]]
3377 )))
3378 * (((
3379 (% style="text-align:center" %)
3380 [[image:image-20221228144708-10.png]]
3381 )))
3382
3383 * AI word address and Ibit address are read-only and cannot be written on HMI.
3384 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3385 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3386 * Written value of RTC cannot exceed 255.
3387
3388 **Cable Wiring**
3389
3390 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3391
3392 == S7-300 232 ==
3393
3394 **HMI Setting:**
3395
3396 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3397 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3398 |=**PLC I/F**|RS232| |
3399 |=**Baud rate**|19200|9600,19200|
3400 |=**Data bits**|8| |
3401 |=**Parity**|Odd| |
3402 |=**Stop bits**|1| |
3403 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3404
3405 **Device Address**
3406
3407 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3408 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3409 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3410 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3411 |=Word|(((
3412 DB1 to DB99
3413 )))|DDDDDo|0 ~~ 655327|
3414 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3415 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3416 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3417 |=Double word|MD|DDDD|0 ~~ 4094|
3418 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3419 Data Register Double Word (must be even)
3420 )))
3421 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3422
3423 **Cable Wiring**
3424
3425 (% style="text-align:center" %)
3426 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3427
3428 = Create communication with Xinje** PLC** =
3429
3430 == XC serial protocol ==
3431
3432 **HMI Settings**
3433
3434 |**Item**|**Settings**|**Note**
3435 |Protocol|XINJE XC MODBUS|
3436 |Connection|RS232|
3437 |Baud rate|19200|
3438 |Data bit|8|
3439 |Parity|EVEN|
3440 |Stop bit|1|
3441 |PLC station No.|1|
3442
3443 **Address List**
3444
3445 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3446 |Bit|M|M|M d|0~~8511|
3447 |Bit|X|X|X o|0~~1747|
3448 |Bit|Y|Y|Y o|0~~1747|
3449 |Bit|S|S|S d|0~~1023|
3450 |Bit|T|T|T d|0~~4095|
3451 |Bit|C|C|C d|0~~634|
3452 |Word|D|D|D d|0~~8511|
3453 |Word|TD|TD|TD d|0~~618|
3454 |Word|CD|CD|CD d|0~~634|
3455 |Word|FD|FD|FD d|0~~8511|
3456
3457 **Configure the communication protocol**
3458
3459 (% style="text-align:center" %)
3460 [[image:image-20220830154105-1.png]]
3461
3462 (% style="text-align:center" %)
3463 [[image:image-20220830154159-3.png]]
3464
3465 **Cable Wiring**
3466
3467 Figure
3468
3469 [[image:image-20220830155728-4.png]]
3470
3471 Pin Definition Diagram
3472
3473 (% style="text-align:center" %)
3474 [[image:image-20220830154131-2.png]]
3475
3476 == XD serial protocol ==
3477
3478 **HMI Settings**
3479
3480 Supported Series: Xinjie XD/XE Series PLC
3481
3482 |=**Item**|=**Settings**|=**Note**
3483 |Protocol|XINJE XD/XC MODBUS|
3484 |Connection|RS232|
3485 |Baud rate|19200|
3486 |Data bit|8|
3487 |Parity|EVEN|
3488 |Stop bit|1|
3489 |PLC station No.|1|
3490
3491 **Address List**
3492
3493 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3494 |Bit|M|M|M d|0~~74999|
3495 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3496 |Bit|X2xx|X2xx|X2xx o|0~~277|
3497 |Bit|X|X|X o|0~~77|
3498 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3499 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3500 |Bit|Y|Y|Y o|0~~4095|
3501 |Bit|SM|SM|SM d|0~~4999|(((
3502
3503 )))
3504 |Bit|T|T|T d|0~~4999|
3505 |Bit|C|C|C d|0~~4999|
3506 |Bit|ET|ET|ET d|0~~31|
3507 |Bit|SE|SE|SE d|0~~31|
3508 |Bit|HM|HM|HM d|0~~11999|
3509 |Bit|HSC|HSC|HSC d|0~~39|
3510 |Bit|HS|HS|HS d|0~~999|
3511 |Bit|HT|HT|HT d|0~~1999|
3512 |Bit|HC|HC|HC d|0~~1999|
3513 |Bit|S|S|S d|0~~7999|
3514 |Word|D|D|D d|0~~69999|
3515 |Word|ID|ID|ID d|0~~99|
3516 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3517 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3518 |Word|QD|QD|QD d|0~~99|
3519 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3520 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3521 |Word|SD|SD|SD d|0~~4999|
3522 |Word|TD|TD|TD d|0~~575|
3523 |Word|CD|CD|CD d|0~~575|
3524 |Word|ETD|ETD|ETD d|0~~31|
3525 |Word|HD|HD|HD d|0~~24999|
3526 |Word|HSD|HSD|HSD d|0~~1023|
3527 |Word|HTD|HTD|HTD d|0~~95|
3528 |Word|HCD|HCD|HCD d|0~~95|
3529 |Word|HSCD|HSCD|HSCD d|0~~31|
3530 |Word|FD|FD|FD d|0~~8191|
3531 |Word|SFD|SFD|SFD d|0~~5999|
3532 |Word|FS|FS|FS d|0~~47|
3533
3534 **Configure the communication protocol**
3535
3536 (% style="text-align:center" %)
3537 [[image:image-20220830160042-1.png]]
3538
3539 (% style="text-align:center" %)
3540 [[image:image-20220830160129-2.png]]
3541
3542 **Cable Wiring**
3543
3544 (% style="text-align:center" %)
3545 [[image:image-20220905093902-1.png]]
3546
3547 Pin Definition Diagram
3548
3549 (% style="text-align:center" %)
3550 [[image:image-20220830160232-3.png]]
3551
3552 = Create communication with Panasonic** PLC** =
3553
3554 == **FP serial protocol** ==
3555
3556 **1)HMI Settings**
3557
3558 |**Item**|**Settings**|**Note**
3559 |Protocol|Panasonic FP MFWTOCOL|
3560 |Connection|RS232|
3561 |Baud rate|9600|
3562 |Data bit|8|
3563 |Parity|ODD|
3564 |Stop bit|1|
3565 |PLC station No.|1|
3566
3567 **2)Address List**
3568
3569 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3570 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3571 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3572 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3573 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3574 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3575 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3576 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3577 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3578 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3579 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3580 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3581 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3582 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3583 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3584 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3585
3586 **3)Configure the communication protocol**
3587
3588 [[image:image-20220830171050-1.png]]
3589
3590 [[image:image-20220830171126-2.png]]
3591
3592 **4)Cable Wiring**
3593
3594 Figure
3595
3596 [[image:image-20220830171328-4.png]]
3597
3598 Pin Definition Diagram
3599
3600 [[image:image-20220830171146-3.png]]
3601
3602 = Create communication with **SHIMADEN PLC** =
3603
3604 == **FP23 series protocol** ==
3605
3606 Supported series: SHIMADEN FP23 series
3607
3608 **HMI Setting**
3609
3610 |**Items**|**Settings**|**Note**
3611 |Protocol|SHIMADEN FP23 series|
3612 |Connection|RS485 (9600, 1, 7, EVEN)|
3613 |Port No.|None|
3614 |PLC station No.|0|
3615
3616 **Address List**
3617
3618 |**Device address**|**HMI register**|**Address range**|**Type**
3619 |0040-0043(HEX)|FP040|100064-200067|Read only
3620 |0100-010B(HEX)|FP100|100256-200267|Read only
3621 |0110-0142(HEX)|FP110|100272-200322|Read only
3622 |0182-0252(HEX)|FP182|100386-200594|Write only
3623 |0280-0281(HEX)|FP280|100640-200641|Read only
3624 |0300-030B(HEX)|FP300|100768-200779|Read and write
3625 |0380-039F(HEX)|FP380|100896-200927|Read and write
3626 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3627 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3628 |0600-0670(HEX)|FP600|101536-201814|Read and write
3629 |0720-0738(HEX)|FP720|101824-201848|Read and write
3630 |0800-083F(HEX)|FP800|102048-202111|Read and write
3631 |0900-0952(HEX)|FP900|102304-202386|Read and write
3632 | |Ctrl|0-2|
3633
3634 **✎Note:**
3635
3636 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3637 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3638 * The Ctrl register is used to store the control group number and BCC check mode.
3639
3640 **Ctrl Register Description**
3641
3642 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3643 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3644 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3645 * Ctrl3 reserved
3646
3647 **✎Note:**
3648
3649 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3650
3651 **Cable Wiring**
3652
3653 (% style="text-align:center" %)
3654 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3655
3656 (% style="text-align:center" %)
3657 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3658
3659 **✎Note:** COM3 only available in PI8000/PI9000 series.
3660
3661 == **SR90 protocol** ==
3662
3663 Supported series: SHIMADEN SR90 series
3664
3665 **HMI Setting**
3666
3667 |**Items**|**Settings**|**Note**
3668 |Protocol|SHIMADEN SR90 protocol|
3669 |Connection|RS485 (1200, 1, 7, EVEN)|
3670 |Port No.|None|
3671 |PLC station No.|0|
3672
3673 **Address List**
3674
3675 |**Device address**|**HMI register**|**Address range**|**Type**
3676 |0040-0043 (HEX)|SR040|100064-100067|Read only
3677 |0100-010A(HEX)|SR0100|100256-100266|Read only
3678 |0182-018C(HEX)|SR0182|100386-100396|Write only
3679 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3680 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3681 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3682 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3683 | |Ctrl|0-2|~-~-
3684
3685 **✎Note:**
3686
3687 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3688 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3689 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3690
3691 **Ctrl Register Description**
3692
3693 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3694 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3695 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3696 * Ctrl3 reserved
3697
3698 **✎Note:**
3699
3700 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3701
3702 **Cable Wiring**
3703
3704 (% style="text-align:center" %)
3705 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3706
3707 (% style="text-align:center" %)
3708 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3709
3710 **✎Note:** COM3 only available in PI8000/PI9000 series.
3711
3712 == **MR13 series(standard protocol)** ==
3713
3714 Supported series: SHIMADEN MR13 series
3715
3716 **HMI Setting**
3717
3718 |**Items**|**Settings**|**Note**
3719 |Protocol|SHIMADEN standard protocol|
3720 |Connection|RS485 (1200, 1, 7, EVEN)|
3721 |Port No.|None|
3722 |PLC station No.|0|
3723
3724 **Address List**
3725
3726 |**Device address**|**HMI register**|**Address range**|**Type**
3727 |0100-010B(HEX)|MR100|100256-300267|Read only
3728 |0111-0126(HEX)|MR111|100273-300294|Read only
3729 |0184-0192(HEX)|MR184|100388-300402|Write only
3730 |0280-0282(HEX)|MR280|100640-300642|Read only
3731 |0300-030B(HEX)|MR300|100768-300779|Read/write
3732 |0314-0317(HEX)|MR314|100788-300791|Read/write
3733 |031A(HEX)|MR31A|100794-300794|Read/write
3734 |0320-0321(HEX)|MR320|100800-300801|Read/write
3735 |0400-0504(HEX)|MR400|101024-301284|Read/write
3736 |0506(HEX)|MR506|101286-301286|Read/write
3737 |0510-0514(HEX)|MR510|101296-301300|Read/write
3738 |0516-0524(HEX)|MR516|101302-301316|Read/write
3739 |0526(HEX)|MR526|101318-301318|Read/write
3740 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3741 |~-~-|Ctrl|0-2|~-~-
3742
3743 **✎Note:**
3744
3745 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3746 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3747 * The Ctrl register is used to store the control group number and BCC check mode.
3748
3749 **Ctrl Register Description**
3750
3751 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3752 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3753 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3754 * Ctrl3 reserved
3755
3756 **✎Note:**
3757
3758 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3759
3760 **Cable Wiring**
3761
3762 (% style="text-align:center" %)
3763 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3764
3765 (% style="text-align:center" %)
3766 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3767
3768 **✎Note:** COM3 only available in PI8000/PI9000 series.
3769
3770 = **Printer** =
3771
3772 == **TSPL label printer** ==
3773
3774 **Introduction**
3775
3776 TSPL label printer protocol supports following models.
3777
3778 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3779 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3780
3781 **Setting Step**
3782
3783 Select the protocol
3784
3785 * Create a new project, select the TSPL label printer protocol as shown below.
3786
3787 (% style="text-align:center" %)
3788 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3789
3790 Set parameters
3791
3792 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3793
3794 Printer register
3795
3796 (% class="table-bordered" %)
3797 |**Register**|**System**|**Range**|**Function**
3798 |TSPL_SP|decimal|0 - 1|Set the paper size
3799 |TSPL_PT|decimal|0 - 1999|Print text
3800 |TSPL_PQ|decimal|0 - 999|Print QR code
3801 |TSPL_PB|decimal|0 - 999|Print barcode
3802 |TSPL_PR|decimal|0 - 1|Print offset
3803 |TSPL_PN|decimal|0 - 0|Trigger printing
3804 |TSPL_PS|decimal|0 - 0|Print status
3805
3806 * Set paper size:
3807 ** TSPL_SP0: width of paper, unit: mm.
3808 ** TSPL_SP1: height of paper, unit: mm.
3809 * Print text:
3810 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3811 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3812
3813 (% class="table-bordered" %)
3814 |**Register**|**Function**|**Description**
3815 |TSPL_PT0|X coordinate|Unit: dot
3816 |TSPL_PT1|Ycoordinate|Unit: dot
3817 |TSPL_PT2|Rotation angle|(((
3818 0: 0 degrees
3819
3820 1: 90 degrees
3821
3822 2: 180 degrees
3823
3824 3: 270 degrees
3825 )))
3826 |TSPL_PT3|Size|Range: 0-3
3827 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3828
3829 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3830
3831 Print QR code:
3832
3833 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3834 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3835
3836 (% class="table-bordered" %)
3837 |**Register**|**Function**|**Description**
3838 |TSPL_PQ0|X coordinate|Unit: dot
3839 |TSPL_PQ1|Ycoordinate|Unit: dot
3840 |TSPL_PQ2|Rotation angle|(((
3841 0: 0 degrees
3842
3843 1: 90 degrees
3844
3845 2: 180 degrees
3846
3847 3: 270 degrees
3848 )))
3849 |TSPL_PQ3|Size|Range: 0-5
3850 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3851
3852 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3853
3854 Print bar code:
3855
3856 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3857 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3858
3859 (% class="table-bordered" %)
3860 |**Register**|**Function**|**Description**
3861 |TSPL_PB0|X coordinate|Unit: dot
3862 |TSPL_PB1|Ycoordinate|Unit: dot
3863 |TSPL_PB2|Rotation angle|(((
3864 0: 0 degrees
3865
3866 1: 90 degrees
3867
3868 2: 180 degrees
3869
3870 3: 270 degrees
3871 )))
3872 |TSPL_PB3|height|Unit: dot
3873 |TSPL_PB4|width|Range:0-2
3874 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3875
3876 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3877
3878 Print offset:
3879
3880 * TSPL_PR0: X coordinate offset, unit: mm;
3881 * TSPL_PR1: Y coordinate offset, unit: mm.
3882
3883 Trigger printing:
3884
3885 * TSPL_PN0 = 1: trigger the printer to start printing.
3886
3887 Printing status:
3888
3889 * TSPL_PS0 = 1: The printing is normal.
3890 * TSPL_PS0 = 1: The printing is abnormal.
3891
3892 Print picture
3893
3894 * For the function of printing pictures, please refer to the configuration of [Printer object].
3895
3896 Conversion between dot and mm
3897
3898 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3899
3900 == **EpsonTM series** ==
3901
3902 **HMI Settings**
3903
3904 (% class="table-bordered" %)
3905 |**Item**|**Settings**|**Note**
3906 |Protocol|EPSON-TM-T82II/TM-XXX|
3907 |Connection|RS232|
3908 |Baud rate|9600~~115200|
3909 |Data bit|8|
3910 |Parity|None|
3911 |Stop bit|1|
3912 |PLC station No.|1|
3913
3914 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3915
3916 **Printer Settings**
3917
3918 (% class="table-bordered" %)
3919 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3920 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3921 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3922 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3923 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3924 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3925 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3926
3927 **Cable Wiring**
3928
3929 (% style="text-align:center" %)
3930 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3931
3932 (% style="text-align:center" %)
3933 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3934
3935 **✎Note:** COM3 only available in PI8000/PI9000 series.
3936
3937
3938 = Create communication with **Schneider PLC** =
3939
3940 == **Schneider MODBUS RTU** ==
3941
3942 **HMI Setting**
3943
3944 |=**Parameters**|=**Recommended**|=**Notes**
3945 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3946 |Connection|RS485|
3947 |**Baud rate**|19200|
3948 |**Data bit**|8|
3949 |**Parity**|Even|
3950 |**Stop bit**|1|
3951 |**PLC station No.**|1|
3952
3953 **PLC Setting**
3954
3955 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3956
3957 **Device Address**
3958
3959 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3960 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3961 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3962 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3963 |W|MW|DDDDDD|0 ~~ 999999|Output register
3964 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3965
3966 **Wiring Diagram**
3967
3968 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3969
3970 (% style="text-align:center" %)
3971 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3972
3973 = **Barcode Scanner** =
3974
3975 Supported: DELI 14880 barcode scanner
3976
3977 **HMI Setting**
3978
3979 |**Items**|**Settings**|**Note**
3980 |Protocol|Barcode Scanner|
3981 |Connection|USB|
3982
3983 **Operating Procedures**
3984
3985 Select [Barcode Scanner];
3986
3987 (% style="text-align:center" %)
3988 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3989
3990 Set address for receiving;
3991
3992 Set correct length;
3993
3994 (% style="text-align:center" %)
3995 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3996
3997 **✎Note:**
3998
3999 * The protocol uploads the information acquired by the USB scanner to the HMI;
4000 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4001 * Recommended model: DELI 14880 barcode scanner;
4002
4003 = **Hitachi EHV Series (Ethernet)** =
4004
4005 Supported series: Hitachi EHV series
4006
4007 **HMI Settings**
4008
4009 (% class="table-bordered" %)
4010 |**Items**|**Settings**|**Note**
4011 |Protocol|Hitachi EHV series|
4012 |Connection|Ethernet|
4013 |Port No.|3004~~3007|
4014
4015 **Address List**
4016
4017 (% class="table-bordered" %)
4018 |**Type**|**Register**|**Range**|**Format**|**Note**
4019 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4020 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4021 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4022 H1H2H3H4 Module main number
4023
4024 H1: Remote number
4025
4026 H2: Unit number
4027
4028 H3: Slot number
4029
4030 H4: Word number of Module
4031
4032 H Sub number of Module
4033
4034 For example:X21.3
4035
4036 Slot number 2
4037
4038 Word number of module is 1
4039
4040 Bit number of module is 3
4041
4042 Remote number and unit number are 0
4043 )))
4044 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4045 |R|0 – FF.f (Hex)|R HH.h|
4046 |L|0 - 73FF.f (Hex)|L HHHH.h|
4047 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4048 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4049 H1H2H3H4 Module main number
4050
4051 H1: Remote number
4052
4053 H2: Unit number
4054
4055 H3: Slot number
4056
4057 H4: Word number of module
4058
4059 For example:WX21
4060
4061 Word number of module is 1
4062
4063 Slot number is 2
4064
4065 Remote number and unit number are 0
4066 )))
4067 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4068 |WR|0 – FFFF (Hex)|WR HHHH|
4069 |WL|0 - 73FF (Hex)|WL HHHH|
4070 |TC|0 - 2559|TC DDDD|
4071
4072 **Communication settings in HMI**
4073
4074 Enable HMI Ethernet in [Project Settings];
4075
4076 (% style="text-align:center" %)
4077 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4078
4079 Set PLC IP in [Device IP] settings;
4080
4081 (% style="text-align:center" %)
4082 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4083
4084 **PLC Configuration**
4085
4086 Connect with PLC, select[Online mode];
4087
4088 (% style="text-align:center" %)
4089 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4090
4091 Set IP address, it is the same LAN parameters with HMI;
4092
4093 (% style="text-align:center" %)
4094 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4095
4096 3) Save PLC communication parameter, and restart PLC
4097
4098 **PLC Monitor Mode**
4099
4100 Connect with PLC and choose to “online” mode
4101
4102 (% style="text-align:center" %)
4103 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4104
4105 Open I/O monitor sheet1
4106
4107 (% style="text-align:center" %)
4108 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4109
4110 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4111
4112 (% style="text-align:center" %)
4113 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4114
4115 Enter the register address, click OK to view the value of the register.
4116
4117 (% style="text-align:center" %)
4118 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4119
4120 (% style="text-align:center" %)
4121 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4122
4123 **✎Note:**
4124
4125 * Both word registers and bit registers support even continuous read/write functions;
4126 * The range of registers is based on the specific PLC type;
4127
4128 **Cable Wiring**
4129
4130 (% style="text-align:center" %)
4131 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4132
4133 = **IEC60870-5 104 Client** =
4134
4135 **HMI Setting**
4136
4137 (% class="table-bordered" %)
4138 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4139 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4140 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4141 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4142
4143 **Address List**
4144
4145 (% class="table-bordered" %)
4146 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4147 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4148 |(% style="width:461px" %)SCNA|0~~16777215.7
4149 |(% style="width:461px" %)DPTB|0~~16777215.7
4150 |(% style="width:461px" %)DCNA|0~~16777215.7
4151 |(% style="width:461px" %)METF|0~~16777215.7
4152 |(% style="width:461px" %)SENC|0~~16777215.7
4153 |(% style="width:461px" %)SENA|0~~16777215.7
4154 |(% style="width:461px" %)MENA|0~~16777215.7
4155 |(% style="width:461px" %)METD|0~~16777215.7
4156 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4157 |(% style="width:461px" %)SCNA|0~~16777215
4158 |(% style="width:461px" %)DPTB|0~~16777215
4159 |(% style="width:461px" %)DCNA|0~~16777215
4160 |(% style="width:461px" %)SENA|0~~16777215
4161 |(% style="width:461px" %)MENA|0~~16777215
4162 |(% style="width:461px" %)METD|0~~16777215
4163 |(% style="width:461px" %)INRO|0~~16777215
4164 |(% style="width:461px" %)TIMESYN|0~~16777215
4165 |(% style="width:461px" %)TIMEZ|0~~16777215
4166 |(% style="width:461px" %)NTP|0~~16777215
4167 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4168 |(% style="width:461px" %)SENC|0~~16777215
4169
4170 **Address Configuration**
4171
4172 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4173
4174 (% style="text-align:center" %)
4175 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4176
4177 (% style="text-align:center" %)
4178 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4179
4180 Extended tag name
4181
4182 Address range for the extended tag.
4183
4184 **Communication Settings**
4185
4186 Enable HMI Ethernet in [Project Settings];
4187
4188 (% style="text-align:center" %)
4189 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4190
4191 Set PLC IP in [Device IP] settings;
4192
4193 (% style="text-align:center" %)
4194 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4195
4196 **Cable Wiring**
4197
4198 (% style="text-align:center" %)
4199 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4200
4201 = **OpenCAN** =
4202
4203 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4204
4205 This protocol is only available in PI8000 series HMI.
4206
4207 **HMI Settings**
4208
4209 |**Items**|**Settings**|**Note**
4210 |Protocol|OPENCAN|
4211 |Connection|CAN port|
4212 |Baud rate|250000|
4213
4214 **CAN frame setting in HMI**
4215
4216 Click [OpenCAN setting] button in communication setting window;
4217
4218 (% style="text-align:center" %)
4219 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4220
4221 Click [Add] to create a new frame;
4222
4223 (% style="text-align:center" %)
4224 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4225
4226 |**No**|**Items**|**Description**
4227 |1|Add|add a frame related to register address
4228 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4229 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4230 |4|Modify|Modify the frames in frame management
4231 |5|Copy|Copy one frame to another
4232 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4233 |7|Empty|All frames in the list are cleared
4234 |8|Browse|Displays configuration files in XML format in IE
4235 |9|OK|Complete the configuration of the frame and exit
4236
4237 Set CANBUS frame in setting windows
4238
4239 (% style="text-align:center" %)
4240 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4241
4242 |**No**|**Items**|**Description**
4243 |1|ID|Set the ID of a can frame in hexadecimal format;
4244 |2|ID assign|split the ID by PF, PS, and SA;
4245 |3|Frame type|Select Standard frame or Extended Frame;
4246 |4|Frame format|Select between data frame and remote Frame;
4247 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4248 |6|Use address|(((
4249 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4250
4251 **Edit:** Set a bit or word address by its format;
4252
4253 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4254 )))
4255 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4256 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4257 |Feedback mode: feedback mode includes no response, confirm response and data response;
4258 |No response: the device or touch screen will not receive feedback;
4259 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4260 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4261 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4262 |Response timeout: sets whether the response frame timeout;
4263 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4264 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4265 |Manually send: a manually send tick indicates only one send;
4266 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4267 |10|Note|Fill the text to explain the meaning of the frame;
4268 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4269 |12|Current operation display|Display the description of current operation;
4270 |13|Add|Add a new frame;
4271 |14|Save frame|Save the configured frame format;
4272 |15|Cancel|Cancel the frame configuration;
4273
4274 Set CAN address (Read or write operation);
4275
4276 (% style="text-align:center" %)
4277 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4278
4279 |**No.**|**Item**|**Description**
4280 |1|Current address|Displays the register type and register address set by the user in the data access interface
4281 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4282 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4283 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4284 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4285 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4286 |If the trigger condition is a writing operation, there are two situations:(((
4287 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4288 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4289 )))
4290 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4291 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4292 |4|Add|Add current configuration
4293 |5|Close|Close the configuration window to exit
4294
4295 **Multiple Packages Settings**
4296
4297 (% style="text-align:center" %)
4298 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4299
4300 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4301
4302 Select Multiple package type
4303
4304 * Not Multiple packages
4305 * J1939 Multiple packages
4306 * Customized Multiple packages
4307
4308 Click [Edit Receive data] for [Receive] settings
4309
4310 * Start code+ Total length (J1939)
4311
4312 (% style="text-align:center" %)
4313 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4314
4315 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4316
4317 * Start code + Data max length (J1939)
4318
4319 (% style="text-align:center" %)
4320 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4321
4322 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4323
4324 * Data max length (J1939)
4325
4326 (% style="text-align:center" %)
4327 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4328
4329 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4330
4331 * Customized multiple package
4332
4333 (% style="text-align:center" %)
4334 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4335
4336 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4337
4338 Click [Edit Send data] for [Send] setting
4339
4340 * J1939
4341
4342 (% style="text-align:center" %)
4343 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4344
4345 [Data] is all data to be sent.
4346
4347 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4348
4349 * Customized multiple package
4350
4351 (% style="text-align:center" %)
4352 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4353
4354 [Data] is all data to be sent.
4355
4356 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4357
4358 **Cable Wiring**
4359
4360 (% style="text-align:center" %)
4361 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4362
4363 **✎Note:** The address interval between each frame need to be more than a word address;
4364
4365
4366 = **User Defined Protocol** =
4367
4368 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4369
4370 **HMI Settings**
4371
4372 |**Items**|**Settings**|**Note**
4373 |Protocol|User defined protocol|
4374 |Connection|RS485/RS232|
4375 |Baud rate|2400~~187500|
4376 |Stop bits|1/ 2|
4377 |Data bits|7/ 8|
4378 |Parity|None/ Even/ ODD|
4379
4380 **Operating Procedures**
4381
4382 Select [User defined protocol];
4383
4384 Click [User defined protocol] button to open setting window as below;
4385
4386 (% style="text-align:center" %)
4387 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4388
4389 Configure user defined command;
4390
4391 (% style="text-align:center" %)
4392 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4393
4394 |**No**|**Item**|**Description**
4395 |1|Instruction edit|The required command.
4396 |2|Mode|Write to address or read from the address.
4397 |3|Format|Encode format: HEX or ASCII.
4398 |4|Other|(((
4399 **No receiving: **HMI does not respond to the receiving command.
4400
4401 **Send after receiving:** HMI responds to the receiving command.
4402 )))
4403 |5|Manually send|(((
4404 Respond once after trigger the address.
4405
4406 Address: set the trigger address.
4407 )))
4408 |6|Add|Save this setting.
4409 |7|Cancel|Cancel current settings.
4410 |(% rowspan="4" %)8|Add|Add a new command.
4411 |Edit|Edit the selected command.
4412 |Delete|Delete the selected command.
4413 |Clear|Clear all the commands.
4414 |9|Instruction list|Display all current commands.
4415 |10|Address List|Display all the addresses added.
4416 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4417 |Export|Export current command settings to local storage.
4418 |Browse|Browse local command files.
4419 |Advanced|Combine two commands.
4420 |Exit|Complete editing and exit setting.
4421
4422 **Operating Procedures**
4423
4424 Click [Add] to create a new command, as below shows;
4425
4426 (% style="text-align:center" %)
4427 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4428
4429 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4430
4431 (% style="text-align:center" %)
4432 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4433
4434 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4435
4436 (% style="text-align:center" %)
4437 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4438
4439 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4440
4441 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4442
4443 Check settings;
4444
4445 (% style="text-align:center" %)
4446 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4447
4448 |**No**|**Items**|**Description**
4449 |1|Add checking|Add checking command when receiving the data.
4450 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4451 |Differ with send check|Set return checking.
4452 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4453 |Length: The data length need to be checked.
4454
4455 Object settings;
4456
4457 (% style="text-align:center" %)
4458 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4459
4460 |**No**|**Items**|**Description**
4461 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4462 |Address: the triggering address;
4463 |Note: description to object;
4464 |2|Byte order|The numerical display order;
4465
4466 Data length settings;
4467
4468 (% style="text-align:center" %)
4469 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4470
4471 |**No**|**Item**|**Description**
4472 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4473 |Length: the return data length.
4474 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4475 |Length: the write data length.
4476
4477 Instruction length settings
4478
4479 (% style="text-align:center" %)
4480 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4481
4482 |**No**|**Item**|**Description**
4483 |1|Send length|The instruction data will only send designated data length.
4484 |2|Return length|The responds data length.
4485 |3|End code|Instruction will not be terminated until receiving [End code];
4486
4487 **Cable Wiring**
4488
4489 * **RS485**
4490
4491 (% style="text-align:center" %)
4492 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4493
4494 (% style="text-align:center" %)
4495 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4496
4497 * **RS232**
4498
4499 (% style="text-align:center" %)
4500 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4501
4502 **✎Note:** COM3 only available in PI8000/PI9000 series.