Wiki source code of 11 PLC Protocol

Version 297.1 by Hunter on 2023/08/24 11:40

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation of the Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON PLC =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 **✎Note:**
159
160 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
161 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
162
163 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
164
165 (% class="wikigeneratedid" id="HHMIsettings" %)
166 **HMI settings**
167
168 **Download PIStudio Software**
169
170 Please visit the link below to get the latest version PIstudio for HMI programming:
171
172 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
173
174 **Create a new HMI project connect with PLC**
175
176 Check the link below for the video to show you how to get started with a new project
177
178 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
179
180 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
181
182 **General**
183
184 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
185
186 **Protocol settings**
187
188 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
189
190 Please select the protocol, when creating a new project.
191
192 1. Select the COM port for communication;
193 1. PLC type: It means PLC brand, like WECON;
194 1. PLC model: It shows the model of PLC, such as LX3V;
195
196 (% style="text-align:center" %)
197 [[image:image-20220819093729-1.png]]
198
199 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
200
201 (% style="text-align:center" %)
202 [[image:image-20220819093729-2.png]]
203
204
205 The steps to change the protocol for project are as follows.
206
207 1. Click [Setting] to open the [Communication device] window;
208 1. Select communication port, such as COM1;
209 1. Select Serial port for communication, such as RS422;
210 1. Select device type (device brand), such as WECON;
211 1. Select the protocol for communication, such as WECON LX3V;
212
213 (% style="text-align:center" %)
214 [[image:image-20220819093729-3.png]]
215
216 **Parameter settings**
217
218 The parameters settings are in [Communication] window, shown as following below.
219
220 1. Click [Setting] to open the [COM port setting] window;
221 1. Set the parameters such as [connection], [Baud rate] and so on;
222
223 (% style="text-align:center" %)
224 [[image:image-20220819093729-4.png||height="636" width="818"]]
225
226 (% start="3" %)
227 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
228
229 (% style="text-align:center" %)
230 [[image:image-20220819093729-5.png]]
231
232 **Set PLC address in HMI screen**
233
234 1. Place the objects to HMI screen;
235 1. Double-click the object to open the setting window;
236 1. Click “Edit” to open the address setting windows;
237 1. Connection: select the serial port in HMI;
238 1. Address type: All the PLC address types will be display in this list, such as M;
239 1. Address No.: Please input the number of this address, such as 0;
240
241 [[image:image-20220819093729-6.jpeg]]
242
243 **HMI Compilation Download**
244
245 [[image:image-20220902171247-1.png]]
246
247 **Communication cable**
248
249 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
250
251 (% style="text-align:center" %)
252 [[image:image-20220819093729-7.png]]
253
254 **HMI communication PLC use Modbus **
255
256 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
257 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
258
259 (% class="wikigeneratedid" id="HPLCsettings" %)
260 **PLC settings**
261
262 **Download PLC Software**
263
264 Please visit below link to get the latest version PLC Editor for HMI programming
265
266 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
267 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
268
269 **Start a new PLC project**
270
271 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
272
273 (% style="text-align:center" %)
274 [[image:image-20220819101447-3.jpeg]]
275
276 **Add a new instruction **
277
278 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
279
280 (% style="text-align:center" %)
281 [[image:image-20220819105530-1.png]]
282
283 You could also select the ladder symbol from the menu bar directly.
284
285 [[image:image-20220819093729-12.png]]
286
287 **Add comment to PLC program**
288
289 (% style="text-align:center" %)
290 [[image:image-20220819105630-3.png]]
291
292 **Add the statement to PLC program**
293
294 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
295
296 (% style="text-align:center" %)
297 [[image:image-20220819105644-4.png]]
298
299 **Compile **
300
301 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
302
303 [[image:image-20220819093729-15.png]]
304
305 **Download setting **
306
307 Click on “Transfer Setup” to select download mode.
308
309 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
310
311 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
312
313 [[image:image-20220819093729-17.png]]
314
315 **Upload PLC program from PLC**
316
317 Read the PLC program from PLC to computer.
318
319 [[image:image-20220819093729-18.png]]
320
321 **Device monitor**
322
323 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
324
325 [[image:image-20220819093730-19.png]]
326
327 **Online monitor**
328
329 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
330
331 [[image:image-20220819093730-20.png]]
332
333 **Monitor edit**
334
335 In this mode, you could edit the PLC program during PLC is running. 
336
337
338 (% style="text-align:center" %)
339 [[image:image-20220819105928-9.png||height="229" width="669"]]
340
341 == **LX5V Series** ==
342
343 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
344
345 **Software configuration of PLC**
346
347 PLC programming software
348
349 (% style="text-align:center" %)
350 [[image:image-20220810164710-1.png]]
351
352 **New PLC project**
353
354 Click "New Project" and select the PLC model.
355
356 [[image:image-20220810172412-1.png]]
357
358 **Set Serial port parameters**
359
360 Follow the steps below to configure Serial port parameters.
361
362 * Baud rate:115200
363 * Data bit:8
364 * Stop bit:1
365 * Parity:No verification
366
367 [[image:image-20220810165759-3.png]]
368
369 **Registers list**
370
371 [[image:image-20220811102219-3.png]]
372
373 **HMI software configuration**
374
375 HMI programming software
376
377 (% style="text-align:center" %)
378 [[image:image-20220810171237-4.png]]
379
380 **New HMI project**
381
382 Click New Project and select the HMI model.
383
384 [[image:image-20220810172010-5.png]]
385
386 Set communication port parameters
387
388 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
389
390 * Baud rate:115200
391 * Data bit:8
392 * Stop bit:1
393 * Parity:No verification
394
395 [[image:image-20220811104012-1.png]]
396
397 **hardware connection**
398
399 Hardware wiring diagram
400
401 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
402
403 (% style="text-align:center" %)
404 [[image:image-20220811103005-4.png]]
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103227-7.png]]
408
409 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
410
411 == **LX5V-N Ethernet** ==
412
413 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
414
415 **Software configuration of PLC**
416
417 **PLC programming software**
418
419 (% style="text-align:center" %)
420 [[image:image-20220810164710-1.png]]
421
422 **New PLC project**
423
424 Click New Project and select the PLC model.
425
426 [[image:image-20220811115454-1.png]]
427
428 **Set Ethernet port parameters**
429
430 Follow the steps below to configure Ethernet parameters
431
432 * PLC IP address:192.168.39.200
433 * default gateway:192.168.39.1
434 * subnet mask:255.255.255.0
435
436 [[image:image-20220811140530-2.png]]
437
438 **Registers list**
439
440 [[image:image-20220811102219-3.png]]
441
442 **HMI software configuration**
443
444 HMI programming software
445
446
447 (% style="text-align:center" %)
448 [[image:image-20220810171237-4.png]]
449
450 **New HMI project**
451
452 Click New Project and select the HMI model.
453
454 [[image:image-20220810172010-5.png]]
455
456 **Set communication port parameters**
457
458 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
459
460 * HMI IP address:192.168.39.201
461 * Default gateway:192.168.39.1
462 * Subnet mask:255.255.255.0
463
464 [[image:image-20220811170753-2.png]]
465
466 Next, click Communication Settings to configure the IP of the HMI communication object.
467
468 [[image:image-20220811163047-1.png]]
469
470 **Hardware connection**
471
472 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
473
474 (% style="text-align:center" %)
475 [[image:image-20220811170248-1.png]]
476
477 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
478
479 = ABB =
480
481 == **AC500** ==
482
483 Support Series: ABB AC500
484
485 **HMI Settings**
486
487 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
488 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
489 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
490 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
491 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
496
497 **Address List**
498
499 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
500 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
501 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
502 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
503
504 **Cable Wiring**
505
506 (% style="text-align:center" %)
507 [[image:ABB AC500.gif]]
508
509 = Abzil =
510
511 == **Abzil CPL Protocol** ==
512
513 Supported series: SDC series
514
515 **HMI Settings**
516
517 (% style="width:1003px" %)
518 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
519 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
520 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
521 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
522 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
523 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
524 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
525 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
526
527 **Address List**
528
529 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
530 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
531 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
532 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
533 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
540 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
541 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
542 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
548
549 **Cable Wiring**
550
551 (% style="text-align:center" %)
552 [[image:Azbil CPL485.gif]]
553
554 = Crouzet =
555
556 == **M3 (FBD)** ==
557
558 Support Series: Crouzet Millenium 3 CD12/CB12
559
560 **HMI Settings**
561
562 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
563 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
564 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
565 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
566 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
567 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
568 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
569 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
571
572 **Address List**
573
574 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
575 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
576 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
577 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
578 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
579 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
580 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
581 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
582 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
583 Time1: Second
584
585 Time2: Minute
586
587 Time3: Hour
588
589 Time4: Day
590
591 Time5: Month
592
593 Time6: Year
594 )))
595 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
596 Running command(Write only)
597
598 ~=2: Run mode; =1: Stop mode;
599 )))
600
601 **Cable Wiring**
602
603 (% style="text-align:center" %)
604 [[image:CrouzetRS232.png]]
605
606 {{info}}
607 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
608 {{/info}}
609
610 = Danfoss =
611
612 == **FC Series** ==
613
614 Support Series: VLT FC300 Drive
615
616 **HMI Settings**
617
618 (% style="width:988px" %)
619 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended
620 |=(% style="width: 262px;" %)Protocol|(% style="text-align:center; vertical-align:middle; width:487px" %)Danfoss FC Series
621 |=(% style="width: 262px;" %)Connection|(% style="text-align:center; vertical-align:middle; width:487px" %)RS485
622 |=(% style="width: 262px;" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:487px" %)9600
623 |=(% style="width: 262px;" %)Stop bits|(% style="text-align:center; vertical-align:middle; width:487px" %)1
624 |=(% style="width: 262px;" %)Data bits|(% style="text-align:center; vertical-align:middle; width:487px" %)8
625 |=(% style="width: 262px;" %)Parity|(% style="text-align:center; vertical-align:middle; width:487px" %)EVEN
626 |=(% style="width: 262px;" %)PLC Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)1
627 |=(% style="width: 262px;" %)HMI Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)0
628
629 **Address List**
630
631 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
632 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
633 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
634 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
635 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
636
637 **Cable Wiring**
638
639 (% style="text-align:center" %)
640 [[image:Danfoss.png]]
641
642 = **Delta** =
643
644 == DVP Series ==
645
646 (% class="wikigeneratedid" %)
647 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
648
649 **HMI Settings**
650
651 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
652 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
653 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
654 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
655 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
656 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
657 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
658 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
659
660 **Address List**
661
662 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
663 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
664 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
665 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
669 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
670 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
671 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
672
673 (% class="wikigeneratedid" %)
674 **Configure the communication protocol**
675
676 (% style="text-align:center" %)
677 [[image:image-20220829152327-6.png]]
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152016-3.png]]
681
682 (% class="wikigeneratedid" %)
683 **Cable Wiring**
684
685
686 (% style="text-align:center" %)
687 [[image:image-20220829152102-5.png]]
688
689 == DVP Modbus TCP ==
690
691 (% class="wikigeneratedid" %)
692 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
693
694 **HMI Settings**
695
696 |=**Items**|=**Settings**|=**Note**
697 |Protocol|DELTA DVP Modbus TCP|
698 |Connection|Ethernet|
699 |Port No.|201|Must be the same as the PLC setting
700 |PLC station No.|0|Must be the same as the PLC setting
701
702 **Address List**
703
704 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
705 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
706 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
707 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
712 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
713 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
714
715 )))
716 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
717 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
718
719 )))
720
721 (% class="wikigeneratedid" %)
722 **Configure the communication protocol**
723
724 (% style="text-align:center" %)
725 [[image:image-20220829155452-1.png]]
726
727 [[image:image-20220829162116-2.png]]
728
729 **Cable Wiring**
730
731 (% style="text-align:center" %)
732 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
733
734 == **AS300 MODBUS RTU** ==
735
736 Supported Series: Delta AS200/AS300
737
738 **HMI Settings**
739
740 |**Item**|**Settings**|**Note**
741 |Protocol|DELTA AS300 MODBUS RTU|
742 |Connection|RS485|
743 |Baud rate|9600|
744 |Data bit|8|
745 |Parity|NONE|
746 |Stop bit|1|
747 |PLC station No.|1|
748
749 **Address List**
750
751 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
752 |Bit|X|X|Xdd.dd|0~~63.15|Read only
753 |Bit|Y|Y|Ydd.dd|0~~63.15|
754 |Bit|D|D|Dddddd|0~~29999|
755 |Bit|M|M|Mdddd|0~~8191|
756 |Bit|SM|SM|SMdddd|0~~4095|
757 |Bit|S|S|Sdddd|0~~2047|
758 |Bit|T|T|Tddd|0~~511|
759 |Bit|C|C|Cddd|0~~511|
760 |Bit|HC|HC|HCddd|0~~255|Double Word
761 |Word|X|X|Xdd|0~~63|
762 |Word|Y|Y|(((
763 Ydd
764 )))|0~~63|
765 |Word|SR|SR|SRdddd|0~~2047|Special register
766 |Word|D|D|Dddddd|0~~29999|
767 |Word|T|T|Tddd|0~~511|
768 |Word|C|C|Cddd|0~~511|
769 |Word|E|E|Ed|0~~9|
770
771 **Configure the communication protocol**
772
773 Create project
774
775 (% style="text-align:center" %)
776 [[image:AsCreateProject.png]]
777
778 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
779
780 (% style="text-align:center" %)
781 [[image:AScommunicarw.png]]
782
783 Double click the HWCONFIG to open the communication settings window.
784
785 (% style="text-align:center" %)
786 [[image:ASHWCONFIG.png]]
787
788 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
789
790 (% style="text-align:center" %)
791 [[image:ASHSCONFIGICON.png]]
792
793 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
794
795 (% style="text-align:center" %)
796 [[image:ASModbusMode.png]]
797
798 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
799
800 (% style="text-align:center" %)
801 [[image:ASconfigIP.png]]
802
803 (% style="text-align:center" %)
804 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
805
806
807 (% style="text-align:center" %)
808 [[image:image-20220830094657-2.png]]
809
810 **Cable Wiring**
811
812 (% style="text-align:center" %)
813 [[image:image-20220830141138-1.png]]
814
815 Pin Definition Diagram
816
817 (% style="text-align:center" %)
818 [[image:image-20220830095131-1.png]]
819
820 == **AS300 MODBUS TCP** ==
821
822 **HMI Settings**
823
824 |=**Items**|=**Settings**|=**Note**
825 |Protocol|DELTA AS300 MODBUS TCP|
826 |Connection|Ethernet|
827 |Port No.|502|
828 |Device No.|1|
829 |HMI No.|0|
830
831 **Address List**
832
833 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
834 |Bit|X|X|X d|0~~63|
835 |Bit|Y|Y|Y d|0~~63|
836 |Bit|D|D|D d|0~~29999|
837 |Bit|M|M|M d|0~~8191|
838 |Bit|SM|SM|SM d|0~~4095|
839 |Bit|S|S|S h|0~~2047|
840 |Bit|T|T|T d|0~~511|
841 |Bit|C|C|C d|0~~511|
842 |Bit|HC|HC|HC d|0~~255|
843 |Word|X|X|X h|0~~63|
844 |Word|Y|Y|Y d|0~~63|
845 |Word|SR|SR|SR d|0~~2047|
846 |Word|D|D|D d|0~~29999|
847 |Word|T|T|T d|0~~511|
848 |Word|C|C|C h|0~~511|
849 |Word|E|E|E d|0~~9|
850
851 **Configure the communication protocol**
852
853 (% style="text-align:center" %)
854 [[image:image-20220830140537-1.png]]
855
856 (% style="text-align:center" %)
857 [[image:image-20220830140629-2.png]]
858
859 **Cable Wiring**
860
861 (% style="text-align:center" %)
862 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
863
864 = **EMERSON** =
865
866 == **RTU Slave Protocol** ==
867
868 Supported series: EC10 series
869
870 **HMI Settings**
871
872 |**Item**|**Settings**|**Note**
873 |Protocol|Emerson 984 RTU Slave MODBUS|
874 |Connection|RS485|
875 |Baud rate|19200|
876 |Data bit|8|
877 |Parity|EVEN|
878 |Stop bit|1|
879 |PLC station No.|1
880
881 **PLC Settings**
882
883 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
884
885 (% style="text-align:center" %)
886 [[image:ControlStarSystemBlock.png]]
887
888 (% style="text-align:center" %)
889 [[image:ControlStarCommunicate.png]]
890
891 (% style="text-align:center" %)
892 [[image:ControlStarModbus.png]]
893
894 **Address List**
895
896 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
897 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
898 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
899 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
900 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
901 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
902 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
903 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
904 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
905 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
906 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
907 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
908 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
909 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
910 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
911 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
912 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
913 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
914 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
915 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
916 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
917 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
918
919 **Cable Wiring**
920
921 (% style="text-align:center" %)
922 [[image:Emerson.gif]]
923
924 = **HollySys PLC** =
925
926 == **LK MODBUS RTU** ==
927
928 Supported Series: HollySys LK series CPU
929
930 **HMI Settings**
931
932 |=Item|=Recommended|=Note
933 |=Protocol|HollySys LK MODBUS RTU|
934 |=Connection|RS485|
935 |=Baud rate|38400|
936 |=Stop bits|1|
937 |=Data bits|8|
938 |=Parity|NONE|
939 |=PLC Station No.|1|
940 |=HMI Station No.|0|
941
942 **Address List**
943
944 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
945 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
946 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
947 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
948 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
949 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
950 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
951 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
952
953 **Cable Wiring**
954
955 (% style="text-align:center" %)
956 [[image:Hollysys485.png]]
957
958 == **LM MODBUS RTU** ==
959
960 Supported Series: HollySys LM3109/LM3107 PLC
961
962 **HMI Settings**
963
964 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
965 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
966 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
967 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
968 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
969 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
970 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
971 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
972 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
973
974 **Address List**
975
976 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
977 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
978 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
979 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
980 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
981 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
982 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
983 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
984
985 **Cable Wiring**
986
987 RS232
988
989 (% style="text-align:center" %)
990 [[image:HollySys LM Modbus RTU.gif]]
991
992 RS485
993
994 (% style="text-align:center" %)
995 [[image:Hollysys LM Modbus RTU.gif]]
996
997 = **Inovance PLC** =
998
999 == **H1U/H2U Serial** ==
1000
1001 **HMI Settings**
1002
1003 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1004 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1005 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1006 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1007 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1008 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1009 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1010 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1011 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1012
1013 (% class="wikigeneratedid" %)
1014 **Address List**
1015
1016 (% style="width:1014px" %)
1017 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1018 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1019 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1020 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1021 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1022 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1023 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1026 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1027 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1028 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1029 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1030 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1031 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1034 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1035
1036 (% class="wikigeneratedid" %)
1037 **Cable Wiring**
1038
1039 (% style="text-align:center" %)
1040 [[image:Inovance.png]]
1041
1042 == **H3U Serial** ==
1043
1044 **HMI Settings**
1045
1046 |=**Item**|=**Settings**|=**Note**
1047 |Protocol|INOVANCE H3U PLC|
1048 |Connection|RS422|
1049 |Baud rate|9600|
1050 |Data bit|7|
1051 |Parity|EVEN|
1052 |Stop bit|1|
1053 |PLC station No.|0|
1054
1055 **Address List**
1056
1057 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1058 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1059 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1060 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1061 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1062 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1063 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1066 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1067 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1068 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1069 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1070 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1071 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1075 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1076
1077 **Configure the communication protocol**
1078
1079 (% style="text-align:center" %)
1080 [[image:image-20220830170114-4.png]]
1081
1082 [[image:image-20220830170017-3.png]]
1083
1084 **Cable Wiring**
1085
1086 (% style="text-align:center" %)
1087 [[image:Inovance.png]]
1088
1089 == **H3U Ethernet portocol** ==
1090
1091 **HMI Settings**
1092
1093 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1094 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1095 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1096 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1097 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1098 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1099
1100 **Address List**
1101
1102 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1103 |Bit|M|M DDDD|0~~8511|
1104 |Bit|SM|SM DDDD|0~~1023|
1105 |Bit|S|S DDDD|0~~4095|
1106 |Bit|T|T DDD|0~~511|
1107 |Bit|C|C DDD|0~~255|
1108 |Bit|X|X OOO|0~~571|
1109 |Bit|Y|Y OOO|0~~571|
1110 |Word|D|D DDDD|0~~8511|
1111 |Word|SD |SD DDDD|0~~1023|
1112 |Word|R|R DDDDD|0~~32767|
1113 |Word|T|T DDD|0~~255|
1114 |Word|C|C DDD|0~~199|
1115 |Double Word|C|C DDD|200~~255|
1116
1117 **Cable Wiring**
1118
1119 (% style="text-align:center" %)
1120 [[image:CommonEthernet.png]]
1121
1122 = LS** PLC** =
1123
1124 == **XGB serial** ==
1125
1126 **HMI Settings**
1127
1128 |=**Item**|=**Settings**|=**Note**
1129 |Protocol|LS XGB CPU DRIECT|
1130 |Connection|RS232|
1131 |Baud rate|115200|
1132 |Data bit|8|
1133 |Parity|NONE|
1134 |Stop bit|1|
1135 |PLC station No.|1|
1136
1137 **Address List**
1138
1139 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1140 |Bit|P|P|P DDDD.f|0~~2047|
1141 |Bit|M|M|M DDDD.f|0~~2047|
1142 |Bit|L|L|L DDDDD.f|0~~11263|
1143 |Bit|K|K|K DDDD.f|0~~2559|
1144 |Bit|F|F|F DDDD.f|0~~2047|
1145 |Bit|S|S|S DDDDD|0~~12799|
1146 |Bit|D|D|D DDDDD.f|0~~32767|
1147 |Bit|U|U|U FFFF.f|0~~7f31|
1148 |Bit|T|T|T DDDD.f|0~~2047|
1149 |Bit|C|C|C DDDD.f|0~~2047|
1150 |Word|P|P|P DDDD|0~~2047|
1151 |Word|M|M|M DDDD|0~~2047|
1152 |Word|L|L|L DDDDD|0~~11263|
1153 |Word|K|K|K DDDD|0~~2559|
1154 |Word|F|F|F DDDD|0~~2047|
1155 |Word|C|C|C DDDD|0~~2047|
1156 |Word|T|T|T DDDD|0~~2047|
1157 |Word|D|D|D DDDDD|0~~32767|
1158 |Word|N|N|N DDDDD|0~~21503|
1159 |Word|U|U|U FFFF|0~~7f31|
1160 |Word|Z|Z|Z DDD|0~~127|
1161 |Word|R|R|R DDDDD|0~~32767|
1162 |Word|ZR|ZR|Z DDDDD|0~~32767|
1163 |Word|TS|TS|TS DDDD|0~~2047|
1164 |Word|CS|CS|CS DDDD|0~~2047|
1165 |Word|S|S|S DDDDD|0~~12799|
1166
1167 **Configure the communication protocol**
1168
1169 (% style="text-align:center" %)
1170 [[image:image-20221028174410-1.png]]
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20221028174753-2.png]]
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028181125-4.png]]
1177
1178 **Pin Definition Diagram**
1179
1180 (% style="text-align:center" %)
1181 [[image:image-20221028180930-3.png]]
1182
1183 == **XBC serial** ==
1184
1185 **HMI Settings**
1186
1187 |=**Item**|=**Settings**|=**Note**
1188 |Protocol|LS XBC CNet|
1189 |Connection|RS232|
1190 |Baud rate|115200|
1191 |Data bit|8|
1192 |Parity|NONE|
1193 |Stop bit|1|
1194 |PLC station No.|1|
1195
1196 **Address List**
1197
1198 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1199 |Bit|P|P|P d|0~~2047|
1200 |Bit|M|M|M d|0~~2047|
1201 |Bit|L|L|L d|0~~11263|
1202 |Bit|K|K|K d|0~~16183|
1203 |Bit|F|F|F d|0~~2047|
1204 |Bit|D|D|D d|0~~32767|
1205 |Bit|R|R|R d|0~~32767|
1206 |Bit|U|U|U d|0~~4095|
1207 |Word|P|P|P d|0~~2047|
1208 |Word|M|M|M d|0~~2047|
1209 |Word|L|L|L d|0~~11263|
1210 |Word|K|K|K d|0~~16183|
1211 |Word|F|F|F d|0~~2047|
1212 |Word|C|C|C d|0~~2047|
1213 |Word|T|T|T d|0~~2047|
1214 |Word|D|D|D d|0~~32767|
1215 |Word|N|N|N d|0~~21503|
1216 |Word|R|R|R d|0~~32767|
1217 |Word|U|U|U d|0~~4095|
1218 |Word|Z|Z|Z d|0~~127|
1219 |Word|S|S|S d|0~~127|
1220
1221 **Configure the communication protocol**
1222
1223 (% style="text-align:center" %)
1224 [[image:image-20220831170807-1.png]]
1225
1226 (% style="text-align:center" %)
1227 [[image:image-20220830174733-2.png]]
1228
1229 **Cable Wiring**
1230
1231 (% style="text-align:center" %)
1232 [[image:image-20220830174659-1.png]]
1233
1234 Pin Definition Diagram
1235
1236 (% style="text-align:center" %)
1237 [[image:image-20220830173402-8.png]]
1238
1239 == **XGK FEnet(Ethernet)** ==
1240
1241 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1242
1243 **HMI Settings**
1244
1245 |**Items**|**Settings**|**Note**
1246 |Protocol|LG XGK FEnet(Ethernet)|
1247 |Connection|Ethernet|
1248 |Port No.|2004|
1249
1250 **Address List**
1251
1252 |**Type**|**Register**|**Range**|**Format**|**Note**
1253 |(% rowspan="14" %)Word|P|0~~2047|P d|
1254 |M|0~~2047|M d|
1255 |K|0~~2047|K d|
1256 |F|0~~2047|F d|
1257 |T|0~~2047|T d|
1258 |C|0~~2047|C d|
1259 |Z|0~~127|Z d|
1260 |S|0~~127|S d|
1261 |L|0~~11263|L d|
1262 |N|0~~21503|N d|
1263 |D|0~~32767|D d|
1264 |R|0~~32767|R d|
1265 |ZR|0~~65535|ZR d|
1266 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1267
1268 **✎Note:**
1269
1270 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1271 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1272 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1273
1274 **Communication settings in HMI**
1275
1276 Enable HMI Ethernet in [Project Settings];
1277
1278 (% style="text-align:center" %)
1279 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1280
1281 Set PLC IP in [Device IP] settings;
1282
1283 (% style="text-align:center" %)
1284 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1285
1286 **Cable Wiring**
1287
1288
1289 (% style="text-align:center" %)
1290 [[image:CommonEthernet.png]]
1291
1292 = **Mitsubishi** =
1293
1294 == **FX1S, 1N, 2N Series** ==
1295
1296 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1297
1298 **HMI Settings**
1299
1300 |**Item**|**Settings**|**Note**
1301 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1302 |Connection|RS422/RS485/RS232|
1303 |Baud rate|9600~~115200|
1304 |Data bit|7/8|
1305 |Parity|EVEN/Odd/None|
1306 |Stop bit|1/2|
1307 |PLC station No.|1~~255|
1308
1309 **Address List**
1310
1311 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1312 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1313 |Y|Y|Y o|0~~303237|
1314 |M|M|M d|0~~99999|
1315 |T|T|T d|0~~99999|
1316 |C|C|C d|0~~99999|
1317 |S|S|S d|0~~99999|
1318 |SM|SM|SM d|8000~~9999|
1319 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1320 |Y|Y|Y o|0~~303237|
1321 |M|M|M d|0~~99999|
1322 |T|T|T d|0~~99999|
1323 |C|C|C d|0~~199|
1324 |D|D|D d|0~~7999|
1325 |S|S|S d|0~~99999|
1326 |SD|SD|SD d|8000~~9999|
1327
1328 **Cable Wiring**
1329
1330 * **RS485**
1331
1332 (% style="text-align:center" %)
1333 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1337
1338 * **RS422**
1339
1340 (% style="text-align:center" %)
1341 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1342
1343 **✎Note:** COM3 only available in PI8000/PI9000 series.
1344
1345 == **FX3U/3G/3GA Serial** ==
1346
1347 **HMI Settings**
1348
1349 |=**Item**|=**Settings**|=**Note**
1350 |Protocol|Mitsubishi FX3U/3G/3GA|
1351 |Connection|RS422|
1352 |Baud rate|9600~~115200|
1353 |Data bit|7/8|
1354 |Parity|EVEN/Odd/None|
1355 |Stop bit|1/2|
1356 |PLC station No.|1~~255|
1357
1358 **Address List**
1359
1360 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1361 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1362 |Y|Y|Y o|0~~303237|
1363 |M|M|M d|0~~99999|
1364 |T|T|T d|0~~99999|
1365 |C|C|C d|0~~99999|
1366 |S|S|S d|0~~99999|
1367 |SM|SM|SM d|8000~~9999|
1368 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1369 |Y|Y|Y o|0~~303237|
1370 |M|M|M d|0~~99999|
1371 |T|T|T d|0~~99999|
1372 |C|C|C d|0~~199|
1373 |D|D|D d|0~~7999|
1374 |S|S|S d|0~~99999|
1375 |SD|SD|SD d|8000~~9999|
1376
1377 **Configure the communication protocol**
1378
1379 (% style="text-align:center" %)
1380 [[image:image-20220831095222-1.png]]
1381
1382 (% style="text-align:center" %)
1383 [[image:image-20220831095743-2.png]]
1384
1385 **Wiring**
1386
1387 (% style="text-align:center" %)
1388 [[image:image-20220831100314-6.png]]
1389
1390 == **FX NOPROTOCOL** ==
1391
1392 Mitsubishi FX3G-RS232-BD
1393
1394 **HMI Settings**
1395
1396 |=**Item**|=**Settings**|=**Note**
1397 |Protocol|Mitsubishi FX NOPROTOCOL|
1398 |Connection|RS232|
1399 |Baud rate|9600|
1400 |Data bit|7|
1401 |Parity|EVEN|
1402 |Stop bit|1|
1403 |PLC station No.|0|
1404
1405 **Address List**
1406
1407 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1408 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1409 |Y|Y|Y o|0~~303237|
1410 |M|M|M d|0~~99999|
1411 |T|T|T d|0~~99999|
1412 |C|C|C d|0~~99999|
1413 |S|S|S d|0~~99999|
1414 |SM|SM|SM d|8000~~9999|
1415 |Lamp|Lamp|Lamp d|0~~0|
1416 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1417 |Y|Y|Y o|0~~303237|
1418 |M|M|M d|0~~99999|
1419 |T|T|T d|0~~99999|
1420 |C|C|C d|0~~199|
1421 |D|D|D d|0~~7999|
1422 |S|S|S d|0~~99999|
1423 |SD|SD|SD d|8000~~9999|
1424
1425 **Configure the communication protocol**
1426
1427 (% style="text-align:center" %)
1428 [[image:1.png]]
1429
1430 (% style="text-align:center" %)
1431 [[image:2.png]]
1432
1433 **Wiring**
1434
1435 (% style="text-align:center" %)
1436 [[image:3.png]]
1437
1438 == **FX3U Ethernet** ==
1439
1440 Mitsubishi FX3U series PLC
1441
1442 **HMI Settings**
1443
1444 |Items|Settings|Note
1445 |Protocol|Mitsubishi FX3U Ethernet|
1446 |Connection|Ethernet|
1447 |Port No.|5009|Must be the same as the PLC setting
1448 |PLC station No.|0|
1449
1450 **Address List**
1451
1452 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1453 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1454 |Y|Y|Y OOO|0~~377|
1455 |M|M|M DDDD|0~~7679|
1456 |SM|SM|SM DDDD|8000~~8511|
1457 |S|S|S DDDD|0~~4095|
1458 |TS|TS|TS DDD|0~~511|
1459 |CS|CS|CS DDD|0~~255|
1460 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1461 |TN|TN|TN DDD|0~~511|
1462 |D|D|D DDDD|0~~7999|
1463 |SD|SD|SD DDDD|8000~~8511|
1464 |R|R|R DDDDD|0~~32767|
1465
1466 **Ethernet Module Settings**
1467
1468 FX3U-ENET-L module configuration
1469 Set up the FX3U-ENET-L Ethernet module settings as follows.
1470 Select the module location, which in this document is Module 0.
1471
1472 [[image:image-20221115140802-1.png]]
1473
1474 Select "Operational setting" to enter the following screen.
1475
1476 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1477
1478 [[image:image-20221115142728-4.png]]
1479
1480 Select "Open setting" to enter the setting interface, the settings are as follows.
1481
1482 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1483
1484 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1485
1486 [[image:image-20221115142945-5.png]]
1487
1488 Click on "transter setup" - "PC side I/F setting", see the following figure.
1489
1490 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1491
1492 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1493
1494 [[image:image-20221115143341-6.png||height="426" width="712"]]
1495
1496 Read and write data from the Ethernet module
1497
1498 [[image:image-20221115143703-7.png]]
1499
1500 Set "Transter setup" to COM communication, and read or write operation as shown below
1501
1502 [[image:image-20221115143809-8.png]]
1503
1504 **PLC Settings (GX Works 2)**
1505
1506 Create a blank FX5U project
1507
1508 Find Current Connection in the navigation
1509
1510 [[image:image-20221115144335-9.png||height="422" width="706"]]
1511
1512 Select Connection Channel List
1513
1514 Select Ethernet board communication
1515
1516 [[image:image-20221115144824-10.png||height="421" width="705"]]
1517
1518 Select Ethernet Module
1519 Set the IP address of the PLC
1520
1521 [[image:image-20221115145228-11.png||height="674" width="708"]]
1522
1523 Read or write PLC data, in this document is read
1524
1525 [[image:image-20221115145553-12.png||height="424" width="711"]]
1526
1527 [[image:image-20221115145559-13.png||height="424" width="711"]]
1528
1529 **HMI Communication Setting**
1530
1531 [[image:image-20221115150003-14.png||height="425" width="712"]]
1532
1533 [[image:image-20221115150235-15.png||height="427" width="713"]]
1534
1535 [[image:image-20221115145559-13.png||height="424" width="711"]]
1536
1537 **HMI Communication Setting**
1538
1539 [[image:image-20221115150003-14.png||height="425" width="712"]]
1540
1541 [[image:image-20221115150235-15.png||height="427" width="713"]]
1542
1543 == **FX5U Serial** ==
1544
1545 Mitsubishi FX5U series PLC
1546
1547 **HMI Settings**
1548
1549 |**Item**|**Settings**|**Note**
1550 |Protocol|Mitsubishi FX5U|
1551 |Connection|RS422/RS485|
1552 |Baud rate|9600|
1553 |Data bit|7|
1554 |Parity|Odd|
1555 |Stop bit|1|
1556 |PLC station No.|1~~255|Need to be the same as PLC settings
1557
1558 **Address List**
1559
1560 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1561 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1562 |Y|Y|Y o|0~~303237|
1563 |M|M|M d|0~~99999|
1564 |B|B|B h|0~~7FFF|
1565 |F|F|F d|0~~32767|
1566 |SB|SB|SB h|0~~7FFF|
1567 |TS|TS|TS d|0~~1023|
1568 |TC|TC|TC d|0~~1023|
1569 |STS|STS|STS d|0~~1023|
1570 |STC|STC|STS d|0~~1023|
1571 |CS|CS|CS d|0~~1023|
1572 |CC|CC|CC d|0~~1023|
1573 |SM|SM|SM d|0~~9999|
1574 |L|L|L d|0~~32767|
1575 |S|S|S d|0~~4095|
1576 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1577 |TN|TN|TN d|0~~1023|
1578 |STN|STN|STN d|0~~1023|
1579 |CN|CN|CN d|0~~1023|
1580 |R|R|R d|0~~32767|
1581 |SW|SW|SW h|0~~7FFF|
1582 |Z|Z|Z d|0~~23|
1583 |D|D|D d|0~~7999|
1584 |SD|SD|SD d|0~~11999|
1585
1586 **PLC Settings (GX Works 3)**
1587
1588 Create a blank FX5U project
1589
1590 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1591
1592 (% style="text-align:center" %)
1593 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1594
1595 Select protocol in the setting item, and set parameters.
1596
1597 (% style="text-align:center" %)
1598 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1599
1600 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1601
1602 (% style="text-align:center" %)
1603 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1604
1605 Click the [Apply] button to finish the setting.
1606
1607 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1608
1609 (% style="text-align:center" %)
1610 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1611
1612 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1613
1614 Done.
1615
1616 **Cable Wiring**
1617
1618 * **RS485**
1619
1620 (% style="text-align:center" %)
1621 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1622
1623 (% style="text-align:center" %)
1624 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1625
1626 * **RS422**
1627
1628 (% style="text-align:center" %)
1629 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1630
1631 **✎Note:** COM3 only available in PI8000/PI9000 series.
1632
1633 == **L02 CPU Port** ==
1634
1635 Mitsubishi L02 series CPU built-in serial port.
1636
1637 **HMI Settings**
1638
1639 |=**Item**|=**Settings**|=**Note**
1640 |Protocol|Mitsubishi L02 CPU Port|
1641 |Connection|RS422|
1642 |Baud rate|115200|
1643 |Data bit|8|
1644 |Parity|Odd|
1645 |Stop bit|1|
1646 |PLC station No.|1~~255|Need to be the same as PLC settings
1647
1648 **Address List**
1649
1650 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1651 |Bit|X|X|X h|0~~FFFF|
1652 |Bit|Y|Y|Y h|0~~FFFF|
1653 |Bit|M|M|M d|0~~9999|
1654 |Bit|L|L|L d|0~~9999|
1655 |Bit|F|F|F d|0~~9999|
1656 |Bit|B|B|B h|0~~FFFF|
1657 |Bit|V|V|V d|0~~2047|
1658 |Bit|TC|TC|TC d|0~~9999|
1659 |Bit|SS|SS|SS d|0~~9999|
1660 |Bit|SC|SC|SC d|0~~9999|
1661 |Bit|CS|CS|CS d|0~~9999|
1662 |Bit|CC|CC|CC d|0~~9999|
1663 |Bit|SB|SB|SB h|0~~FFFF|
1664 |Bit|SM|SM|SM d|0~~2047|
1665 |Bit|STS|STS|STS d|0~~1023|
1666 |Bit|S|S|S d|0~~9999|
1667 |Bit|DX|DX|DX h|0~~FFFF|
1668 |Bit|DY|DY|DY h|0~~FFFF|
1669 |Bit|TS|TS|TS d|0~~9999|
1670 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1671 |Word|W|W|W h|0~~FFFF|
1672 |Word|TN|TN|TN d|0~~99999|
1673 |Word|SN|SN|SN d|0~~99999|
1674 |Word|CN|CN|CN d|0~~99999|
1675 |Word|R|R|R d|0~~99999|
1676 |Word|SW|SW|SW h|0~~FFFF|
1677 |Word|Z|Z|Z d|0~~99999|
1678 |Word|ZR|ZR|ZR h|0~~FFFF|
1679 |Word|D|D|D d|0~~99999|
1680
1681 **Communication Settings**
1682
1683 (% style="text-align:center" %)
1684 [[image:image-20220831105732-3.png]]
1685
1686 (% style="text-align:center" %)
1687 [[image:image-20220831110004-5.png]]
1688
1689 **Cable Wiring**
1690
1691 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1692
1693 Pin Definition Diagram
1694
1695 (% style="text-align:center" %)
1696 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1697
1698 == **L02 CPU MELSEC(Ethernet)** ==
1699
1700 Mitsubishi Q series CPU built-in Ethernet port.
1701
1702 **HMI Settings**
1703
1704 |**Items**|**Settings**|**Note**
1705 |Protocol|MITSUBISHI L02 CPU MELSEC|
1706 |Connection|Ethernet|
1707 |Port No.|1025|Must be the same as the PLC setting
1708 |PLC station No.|0|Must be the same as the PLC setting
1709
1710 **Address List**
1711
1712 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1713 |Bit|X|X|X h|0~~FFFF|
1714 |Bit|Y|Y|Y h|0~~FFFF|
1715 |Bit|M|M|M d|0~~9999|
1716 |Bit|L|L|L d|0~~9999|
1717 |Bit|F|F|F d|0~~9999|
1718 |Bit|B|B|B h|0~~FFFF|
1719 |Bit|V|V|V d|0~~2047|
1720 |Bit|TC|TC|TC d|0~~9999|
1721 |Bit|SS|SS|SS d|0~~9999|
1722 |Bit|SC|SC|SC d|0~~9999|
1723 |Bit|CS|CS|CS d|0~~9999|
1724 |Bit|CC|CC|CC d|0~~9999|
1725 |Bit|SB|SB|SB h|0~~FFFF|
1726 |Bit|SM|SM|SM d|0~~2047|
1727 |Bit|STS|STS|STS d|0~~1023|
1728 |Bit|S|S|S d|0~~9999|
1729 |Bit|DX|DX|DX h|0~~FFFF|
1730 |Bit|DY|DY|DY h|0~~FFFF|
1731 |Bit|TS|TS|TS d|0~~9999|
1732 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1733 |Word|W|W|W h|0~~FFFF|
1734 |Word|TN|TN|TN d|0~~99999|
1735 |Word|SN|SN|SN d|0~~99999|
1736 |Word|CN|CN|CN d|0~~99999|
1737 |Word|R|R|R d|0~~99999|
1738 |Word|SW|SW|SW h|0~~FFFF|
1739 |Word|Z|Z|Z d|0~~99999|
1740 |Word|ZR|ZR|ZR h|0~~FFFF|
1741 |Word|D|D|D d|0~~99999|
1742
1743 **Communication Settings**
1744
1745 Enable HMI Ethernet in [Project Settings];
1746
1747 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1748
1749 Set PLC IP in [Device IP] settings;
1750
1751 (% style="text-align:center" %)
1752 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1753
1754 **PLC Settings (GX Works2 )**
1755
1756 Create a project
1757
1758 Set PLC IP, subnet mask and gateway;
1759
1760 Select [Binary Code] as communication data code;
1761
1762 (% style="text-align:center" %)
1763 [[image:image-20221108202109-2.png||height="636" width="732"]]
1764
1765 Set PLC port number, for example 1025
1766
1767 (% style="text-align:center" %)
1768 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1769
1770 Save settings;
1771
1772 Download project into PLC device;
1773
1774 Restart PLC device;
1775
1776 **Cable Wiring**
1777
1778 (% style="text-align:center" %)
1779 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1780
1781 == **QJ71C24N MELSEC** ==
1782
1783 Mitsubishi QJ71C24N communication module built-in serial port;
1784
1785 **HMI Settings**
1786
1787 |**Items**|**Settings**|**Note**
1788 |Protocol|MITSUBISHI QJ71 MELSEC|
1789 |Connection|422|
1790 |Baud rate|9600|
1791 |Data bit|8|
1792 |Parity|ODD|
1793 |Stop bit|1|
1794 |PLC station No.|1~~255|Need to be the same as PLC settings
1795
1796 **Address List**
1797
1798 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1799 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1800 |Y|Y|Y FFFF|0~~1FFF|
1801 |M|M|M DDDDD|0~~99999|
1802 |L|L|L DDDD|0~~8191|
1803 |F|F|F DDDD|0~~2047|
1804 |V|V|V DDDD|0~~2047|
1805 |B|B|B FFFF|0~~1FFF|
1806 |TS|TS|TS DDDD|0~~2047|
1807 |TC|TC|TC DDDD|0~~2047|
1808 |SS|SS|SS DDDD|0~~2047|
1809 |SC|SC|SC DDDD|0~~2047|
1810 |CS|CS|CS DDDD|0~~1023|
1811 |CC|CC|CC DDDD|0~~1023|
1812 |SB|SB|SB FFF|0~~7FF|
1813 |S|S|S D|0~~8191|
1814 |DX|DX|DX FFFF|0~~1FFF|
1815 |DY|DY|DY FFFF|0~~1FFF|
1816 |SM_|SM_|SM_ DDDD|8000~~9999|
1817 |SM|SM|SM DDDD|0~~2047|
1818 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1819 |D|D|D DDDDD|0~~12287|
1820 |W|W|W FFFF|0~~1FFF|
1821 |TN|TN|TN DDDD|0~~2047|
1822 |SN|SN|SN DDDD|0~~2047|
1823 |CN|CN|CN DDDD|0~~1023|
1824 |R|R|R DDDDD|0~~32767|
1825 |SW|SW|SW FFF|0~~7FF|
1826 |Z|Z|Z D|0~~15|
1827 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1828
1829 **Communication Settings**
1830
1831 (% style="text-align:center" %)
1832 [[image:image-20221109135738-1.png]]
1833
1834 (% style="text-align:center" %)
1835 [[image:image-20221109140016-3.png]]
1836
1837 Pin Definition Diagram
1838
1839 (% style="text-align:center" %)
1840 [[image:image-20221109140406-4.png]]
1841
1842 == **QJ71E71 MELSEC** ==
1843
1844 Mitsubishi QJ71E71 Ethernet communication module;
1845
1846 **HMI Settings**
1847
1848 |**Items**|**Settings**|**Note**
1849 |Protocol|MITSUBISHI QJ71E71 MELSEC|
1850 |Connection|Ethernet|
1851 |Port No.|1025|Must be the same as the PLC setting
1852 |PLC station No.|0|Must be the same as the PLC setting
1853
1854 **Address List**
1855
1856 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1857 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1858 |Y|Y|Y h|0~~1FFF|
1859 |M|M|M d|0~~99999|
1860 |L|L|L d|0~~8191|
1861 |F|F|F d|0~~2047|
1862 |B|B|B h|0~~1FFF|
1863 |V|V|V d|0~~2047|
1864 |TS|TS|TS d|0~~2047|
1865 |TC|TC|TC d|0~~2047|
1866 |SS|SS|SS d|0~~2047|
1867 |SC|SC|SC d|0~~2047|
1868 |CS|CS|CS d|0~~1023|
1869 |CC|CC|CC d|0~~1023|
1870 |SB|SB|SB h|0~~7FF|
1871 |S|S|S d|0~~8191|
1872 |DX|DX|DX h|0~~1FFF|
1873 |DY|DY|DY h|0~~1FFF|
1874 |SM|SM|SM d|8000~~9999|
1875 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1876 |D|D|D d|0~~12287|
1877 |W|W|W h|0~~1FFF|
1878 |TN|TN|TN d|0~~2047|
1879 |SN|SN|SN d|0~~2047|
1880 |CN|CN|CN d|0~~1023|
1881 |R|R|R d|0~~32767|
1882 |SW|SW|SW h|0~~7FF|
1883 |Z|Z|Z d|0~~15|
1884 |ZR|ZR|ZR h|0~~FE7FF|
1885
1886 **HMI Communication Settings**
1887
1888 1) Enable HMI Ethernet in [Project Settings];
1889
1890 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1891
1892 2) Set PLC IP in [Device IP] settings
1893
1894 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1895
1896 **PLC Settings(GX Works2)**
1897
1898 * Click [Ethernet/CC IE/MELSECNET];
1899 * Please select [Ethernet] as network type;
1900 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1901 * Select [Online] as Mode;
1902 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1903 * Click [Operation setting] to set IP;
1904 * Select [Binary Code] as [Communication Data Code];
1905 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1906 * Click [Open setting]
1907 * Set protocol: TCP;
1908 * Set [unpassive] in [Open system];
1909 * Set [receive] in [Fixed buffer];
1910 * Set [procedure Exist] in [Fixed buffer communication];
1911 * Disable [Pairing open];
1912 * Set [No confirm] in [Existence confirmation];
1913 * Host station port number: 5009;
1914 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1915 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1916 * Download project into PLC and restart it
1917
1918 **Cable Wiring**
1919
1920 (% style="text-align:center" %)
1921 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1922
1923 = **MODBUS** =
1924
1925 == **MODBUS RTU Master** ==
1926
1927 Supported Series: MODBUS RTU CONTROLLER
1928
1929 HMI works as MODBUS SLAVE connecting with MASTER
1930
1931 (% style="text-align:center" %)
1932 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1933
1934 (% style="text-align:center" %)
1935 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1939
1940 **HMI Settings**
1941
1942 |**Items**|**Settings**|**Note**
1943 |Protocol|MODBUS RTU Master|
1944 |Connection|RS485/RS232|
1945 |Baud rate|2400~~187500|
1946 |Data bit|8|
1947 |Parity|Even/ Odd/ None|
1948 |Stop bit|1/2|
1949 |Station No.|0~~255|
1950
1951 **Address List**
1952
1953 |**Type**|**HMI address**|**MODBUS code**|**Range**
1954 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1955 |Word|HDW3500~~HDW7999|4|0~~4499
1956
1957 **Cable Wiring**
1958
1959 * **RS485**
1960
1961 (% style="text-align:center" %)
1962 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1963
1964 (% style="text-align:center" %)
1965 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1966
1967 * **RS232**
1968
1969 (% style="text-align:center" %)
1970 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1971
1972 **✎Note:** COM3 only available in PI8000/PI9000 series.
1973
1974 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1975
1976 Supported Series: MODBUS RTU CONTROLLER
1977
1978 HMI works as MODBUS MASTER connecting with SLAVE.
1979
1980 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1981
1982 (% style="text-align:center" %)
1983 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1990
1991 **HMI Settings**
1992
1993 |**Items**|**Settings**|**Note**
1994 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1995 |Connection|RS485/RS232|
1996 |Baud rate|2400~~187500|
1997 |Data bit|8|
1998 |Parity|Even/ Odd/ None|
1999 |Stop bit|1/2|
2000 |PLC station No.|0~~255|
2001
2002 **Address List**
2003
2004 |**Type**|**Address Type**|**Function code & Description**
2005 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2006 |06 (write single register: write a binary value to a holding register)
2007 |10 (write values to multiple addresses )
2008 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2009 |06 (write single register: write a binary value to a holding register)
2010 |10 (write values to multiple addresses )
2011 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2015 |10 (write values to multiple addresses )
2016 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2017 |05 (Force a single coil to force the on/off state of a logic coil)
2018 |0F (Write multiple bits, ie write continuously)
2019 |(% rowspan="3" %)1|02 (Read the input state)
2020 |05 (Force a single coil to force the on/off state of a logic coil)
2021 |0F (Write multiple bits)
2022 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits)
2025 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2026 |0F (Write multiple bits)
2027
2028 **✎Note:**
2029
2030 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2031 * The function codes sent out are the same as those that read and write words.
2032
2033 **Station number for more than one slaves**
2034
2035 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2036
2037 (% style="text-align:center" %)
2038 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2039
2040 **Cable Wiring**
2041
2042 * **RS485**
2043
2044 (% style="text-align:center" %)
2045 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2046
2047 (% style="text-align:center" %)
2048 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2049
2050 * **RS232**
2051
2052 (% style="text-align:center" %)
2053 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2054
2055 **✎Note:** COM3 only available in PI8000/PI9000 series.
2056
2057 == **Modbus Meter** ==
2058
2059 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2060
2061 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2062
2063 (% style="text-align:center" %)
2064 [[image:LinfeeDiagram.png]]
2065
2066 2. Check the specific Modbus parameter in the communication menu from LED display.
2067
2068 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2069
2070 {{info}}
2071 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2072 {{/info}}
2073
2074 (% style="text-align:center" %)
2075 [[image:MeterModbusAllView.png]]
2076
2077 3. Create new project and change the Communication settings.
2078
2079 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2080
2081 (% style="text-align:center" %)
2082 [[image:PIStudioSetupMeterModbusPara.png]]
2083
2084 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2085
2086 The following table is intercept part of the manual for Linfee Modbus manual.
2087
2088 **0x03/0x04 command data register address**:
2089
2090 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2091 | HEX|DEC| | | |
2092 |0x00|0|Reserved| | |
2093 |0x02|2|Reserved| | |
2094 |0x04|4|Reserved| | |
2095 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2096 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2097 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2098 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2099 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2100 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2101 |0x12|18|Ia|float|2|Phase Current data, Unit A
2102 |0x14|20|Ib|float|2|Phase Current data, Unit A
2103 |0x16|22|Ic|float|2|Phase Current data, Unit A
2104
2105 {{info}}
2106 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2107 {{/info}}
2108
2109 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2110
2111 (% style="text-align:center" %)
2112 [[image:MeterModbusPInumericSet.png]]
2113
2114 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2115
2116 (% style="text-align:center" %)
2117 [[image:MeterModbusNumericInputFormat.png]]
2118
2119 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2120
2121 (% style="text-align:center" %)
2122 [[image:ActualHMIModbusResult.jpg]]
2123
2124 == **MODBUS TCP Slave (All function)** ==
2125
2126 Supported series: MODBUS TCP controller
2127
2128 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2129
2130 (% style="text-align:center" %)
2131 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2132
2133 (% style="text-align:center" %)
2134 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2138
2139 **HMI Setting**
2140
2141 |**Items**|**Settings**|**Note**
2142 |Protocol|MODBUS TCP Slave (All function)|
2143 |Connection|Ethernet|
2144 |Port No.|502|
2145 |PLC station No.|1|
2146
2147 **Address List**
2148
2149 |**Type**|**Register**|**Function code & Description**
2150 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2151 |06 (write single register: write a binary value to a holding register)
2152 |10 (write values to multiple addresses )
2153 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2154 |06 (write single register: write a binary value to a holding register)
2155 |10 (write values to multiple addresses )
2156 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2160 |10 (write values to multiple addresses )
2161 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2162 |05 (Force a single coil to force the on/off state of a logic coil)
2163 |0F (Write multiple bits, ie write continuously)
2164 |(% rowspan="3" %)1|02 (Read the input state)
2165 |05 (Force a single coil to force the on/off state of a logic coil)
2166 |0F (Write multiple bits)
2167 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits)
2170 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2171 |0F (Write multiple bits)
2172
2173 **Communication Settings**
2174
2175 Enable HMI Ethernet in [Project Settings];
2176
2177 (% style="text-align:center" %)
2178 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2179
2180 Set PLC IP in [Device IP] settings;
2181
2182 (% style="text-align:center" %)
2183 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2184
2185 **Cable Wiring**
2186
2187 (% style="text-align:center" %)
2188 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2189
2190 = **Omron** PLC =
2191
2192 == CJ TCP FINS Ethemet ==
2193
2194 Supported device:CJ series, CJ1W-EIP21
2195
2196 **HMI Settings**
2197
2198 |=**Items**|=**Settings**|=**Note**
2199 |Protocol|OMRON CJ TCP FINS Ethemet|
2200 |Connection|Ethernet|
2201 |Port No.|9600|
2202 |Device No.|0|
2203 |HMI No.|0|(((
2204
2205 )))
2206
2207 **Address List**
2208
2209 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2210 |Bit|CIO|CIO|CIO d|0~~99999|
2211 |Bit|W|W|W d|0~~99999|
2212 |Bit|D|D|D d|0~~99999|
2213 |Bit|H|H|H d|0~~99999|
2214 |Bit|A|A|A d|0~~99999|
2215 |Bit|T|T|T h|0~~99999|
2216 |Bit|CF|CF|CF d|0~~99999|
2217 |Bit|FF|FF|FF d|0~~99999|
2218 |Bit|C|C|C d|0~~99999|
2219 |Bit|EM0|EM0|EM0 d|0~~99999|
2220 |Bit|EM1|EM1|EM1 d|0~~99999|
2221 |Bit|EM2|EM2|EM2 d|0~~99999|
2222 |Bit|EM3|EM3|EM3 d|0~~99999|
2223 |Bit|EM4|EM4|EM4 d|0~~99999|
2224 |Bit|EM5|EM5|EM5 h|0~~99999|
2225 |Bit|EM6|EM6|EM6 d|0~~99999|
2226 |Bit|EM7|EM7|EM7 d|0~~99999|
2227 |Bit|EM8|EM8|EM8 d|0~~99999|
2228 |Bit|EM9|EM9|EM9 d|0~~99999|
2229 |Bit|EMA|EMA|EMA d|0~~99999|
2230 |Bit|EMB|EMB|EMB d|0~~99999|
2231 |Bit|EMC|EMC|EMC d|0~~99999|
2232 |Bit|Lamp|Lamp|Lamp d|0~~0|
2233 |Word|CIO|CIO|CIO d|0~~99999|
2234 |Word|W|W|W d|0~~99999|
2235 |Word|D|D|D d|0~~99999|
2236 |Word|H|H|H d|0~~99999|
2237 |Word|A|A|A d|0~~99999|
2238 |Word|T|T|T h|0~~99999|
2239 |Word|CF|CF|CF d|0~~99999|
2240 |Word|FF|FF|FF d|0~~99999|
2241 |Word|C|C|C d|0~~99999|
2242 |Word|EM0|EM0|EM0 d|0~~99999|
2243 |Word|EM1|EM1|EM1 d|0~~99999|
2244 |Word|EM2|EM2|EM2 d|0~~99999|
2245 |Word|EM3|EM3|EM3 d|0~~99999|
2246 |Word|EM4|EM4|EM4 d|0~~99999|
2247 |Word|EM5|EM5|EM5 h|0~~99999|
2248 |Word|EM6|EM6|EM6 d|0~~99999|
2249 |Word|EM7|EM7|EM7 d|0~~99999|
2250 |Word|EM8|EM8|EM8 d|0~~99999|
2251 |Word|EM9|EM9|EM9 d|0~~99999|
2252 |Word|EMA|EMA|EMA d|0~~99999|
2253 |Word|EMB|EMB|EMB d|0~~99999|
2254 |Word|EMC|EMC|EMC d|0~~99999|
2255 |Word|IR|IR|IR d|0~~99999|
2256 |Word|DR|DR|DR d|0~~99999|
2257
2258 **Configure the communication protocol**
2259
2260 (% style="text-align:center" %)
2261 [[image:image-20220830143348-1.png]]
2262
2263 (% style="text-align:center" %)
2264 [[image:image-20220830143511-2.png]]
2265
2266 **Configure CJ1W-EIP21 connect with HMI**
2267
2268 (% style="text-align:center" %)
2269 [[image:ftEVGvAprh.png]]
2270
2271 Select TCP_Client_2N
2272
2273 (% style="text-align:center" %)
2274 [[image:RURXWcgyCd.png]]
2275
2276 **Cable Wiring**
2277
2278 Pin Definition Diagram
2279
2280 (% style="text-align:center" %)
2281 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2282
2283 == **CS1(CP1E/CP1H)** ==
2284
2285 Supported device: OMRON CS1(CP1E/CP1H)
2286
2287 **HMI Settings**
2288
2289 |=**Items**|=**Settings**|=**Note**
2290 |Protocol|OMRON CS1(CP1E/CP1H)|
2291 |Connection|RS232 (9600, 2, 7, EVEN)|
2292 |Port No.|None|
2293 |PLC station No.|0|
2294
2295 **Address List**
2296
2297 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2298 |Bit|CIO|CIO|CIO d|0~~99999|
2299 |Bit|W|W|W d|0~~99999|
2300 |Bit|D|D|D d|0~~99999|
2301 |Bit|H|H|H d|0~~99999|
2302 |Bit|A|A|A d|0~~99999|
2303 |Bit|TF|T|T h|0~~99999|
2304 |Bit|CF|CF|CF d|0~~99999|
2305 |Bit|T|FF|FF d|0~~99999|
2306 |Bit|C|C|C d|0~~99999|
2307 |Bit|EM0|EM0|EM0 d|0~~99999|
2308 |Bit|EM1|EM1|EM1 d|0~~99999|
2309 |Bit|EM2|EM2|EM2 d|0~~99999|
2310 |Bit|EM3|EM3|EM3 d|0~~99999|
2311 |Bit|EM4|EM4|EM4 d|0~~99999|
2312 |Bit|EM5|EM5|EM5 h|0~~99999|
2313 |Bit|EM6|EM6|EM6 d|0~~99999|
2314 |Bit|EM7|EM7|EM7 d|0~~99999|
2315 |Bit|EM8|EM8|EM8 d|0~~99999|
2316 |Bit|EM9|EM9|EM9 d|0~~99999|
2317 |Bit|EMA|EMA|EMA d|0~~99999|
2318 |Bit|EMB|EMB|EMB d|0~~99999|
2319 |Bit|EMC|EMC|EMC d|0~~99999|
2320 |Word|CIO|CIO|CIO d|0~~99999|
2321 |Word|W|W|W d|0~~99999|
2322 |Word|D|D|D d|0~~99999|
2323 |Word|H|H|H d|0~~99999|
2324 |Word|A|A|A d|0~~99999|
2325 |Word|T|T|T h|0~~99999|
2326 |Word|CIO|CF|CF d|0~~99999|
2327 |Word|C|C|C d|0~~99999|
2328 |Word|EM0|EM0|EM0 d|0~~99999|
2329 |Word|EM1|EM1|EM1 d|0~~99999|
2330 |Word|EM2|EM2|EM2 d|0~~99999|
2331 |Word|EM3|EM3|EM3 d|0~~99999|
2332 |Word|EM4|EM4|EM4 d|0~~99999|
2333 |Word|EM5|EM5|EM5 h|0~~99999|
2334 |Word|EM6|EM6|EM6 d|0~~99999|
2335 |Word|EM7|EM7|EM7 d|0~~99999|
2336 |Word|EM8|EM8|EM8 d|0~~99999|
2337 |Word|EM9|EM9|EM9 d|0~~99999|
2338 |Word|EMA|EMA|EMA d|0~~99999|
2339 |Word|EMB|EMB|EMB d|0~~99999|
2340 |Word|EMC|EMC|EMC d|0~~99999|
2341 |Word|IR|IR|IR d|0~~99999|
2342 |Word|DR|DR|DR d|0~~99999|
2343
2344 **Configure the communication protocol**
2345
2346 (% style="text-align:center" %)
2347 [[image:image-20220902153118-1.png]]
2348
2349 (% style="text-align:center" %)
2350 [[image:image-20220902151322-2.png]]
2351
2352 (% id="cke_bm_27437S" style="display:none" %)** **(%%)**PLC Settings(CX-Programmer)**
2353
2354 Open cx-programmer, create a new PLC project or open the project that has been created.
2355 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
2356
2357 (% style="text-align:center" %)
2358 [[image:1.2 工程新建D.png]]
2359
2360 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
2361
2362 (% style="text-align:center" %)
2363 [[image:1.3 串口参数的查看-配置D.png]]
2364
2365 **Cable Wiring**
2366
2367 (% style="text-align:center" %)
2368 [[image:图片3.png||alt="image-20220902153949-2.png"]]
2369
2370 Pin Definition Diagram
2371
2372 (% style="text-align:center" %)
2373 [[image:3.1.2 接口.png||alt="image-20220902154056-3.png" height="235" width="332"]]
2374
2375 == **EC55 Protocol** ==
2376
2377 Supported device: EC55 temperature instrument
2378
2379 **1)HMI Settings**
2380
2381 |**Items**|**Settings**|**Note**
2382 |Protocol|Omron EC55|
2383 |Connection|RS485 (9600, 2, 7, EVEN)|
2384 |Port No.|None|
2385 |PLC station No.|0|
2386
2387 **2)Address List**
2388
2389 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2390 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2391 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2392 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2393 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2394 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2395 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2396 |CP|-|0-6|Read controller intrinsic property
2397 |CS|-|0-2|Read controller states
2398 |CA|-|0-17|Action command
2399
2400 **3)Device Settings**
2401
2402 Omron E5CC PLC configuration
2403
2404 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2405
2406 (% style="text-align:center" %)
2407 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2408
2409 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2410
2411 (% style="text-align:center" %)
2412 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2413
2414 **✎Note:** The communication settings for HMI should be consistent with this setting.
2415
2416 **Cable Wiring**
2417
2418 (% style="text-align:center" %)
2419 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2420
2421 (% style="text-align:center" %)
2422 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2423
2424 **✎Note:**
2425
2426 * COM3 only available in PI8000/PI9000 series.
2427 * CA address could not support continuous writing function;
2428 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2429 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2430 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2431 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2432 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2433 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2434 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2435
2436 == **NX EtherNet/IP** ==
2437
2438 Supported series: Omron NX/NJ series
2439
2440 **HMI Setting**
2441
2442 |**Items**|**Settings**|**Note**
2443 |Protocol|Omron NX Ethernet/IP|
2444 |Connection|Ethernet|
2445 |Port No.|44818|
2446 |PLC station No.|1|
2447
2448 **Instruction**
2449
2450 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2451
2452 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2453
2454 (% style="text-align:center" %)
2455 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2456
2457 **Export labels from Sysmac Studio**
2458
2459 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2460
2461 (% style="text-align:center" %)
2462 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2463
2464 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2465
2466 Click [Label manage];
2467
2468 (% style="text-align:center" %)
2469 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2470
2471 Click [Import labels] and then select the file exported in step 1;
2472
2473 (% style="text-align:center" %)
2474 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2475
2476 The Import Status field shows the result, click [OK] to finish importing address labels;
2477
2478 (% style="text-align:center" %)
2479 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2480
2481 **Communication Settings**
2482
2483 Enable HMI Ethernet in [Project Settings];
2484
2485 (% style="text-align:center" %)
2486 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2487
2488 Set PLC IP in [Device IP] settings;
2489
2490 (% style="text-align:center" %)
2491 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2492
2493 (% style="text-align:center" %)
2494 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2495
2496 **Cable Wiring**
2497
2498 (% style="text-align:center" %)
2499 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2500
2501 == **CV/CJ1M/CS1H** ==
2502
2503 **HMI Setting:**
2504
2505 |=**Parameters**|=**Recommended**
2506 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H
2507 |=**PLC I/F**|RS232
2508 |=**Baud rate**|9600
2509 |=**Data bits**|7
2510 |=**Parity**|Even
2511 |=**Stop bits**|2
2512 |=**PLC sta. no.**|0
2513
2514 **PLC Setting:**
2515
2516 |=**Communication mode**|Host Link Protocol / PLC must be set to monitor mode
2517
2518 **Device Address:**
2519
2520 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2521 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2522 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2523 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2524 |=B|H|DDDDdd|0 ~~ 409515|
2525 |=B|A|DDDDdd|0 ~~ 409515|
2526 |=B|TF|DDDDdd|0 ~~ 409515|
2527 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2528 |=B|T|DDDD|0 ~~ 4095|
2529 |=B|C|DDDD|0 ~~ 4095|
2530 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2531 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2532 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2533 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2534 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2535 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2536 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2537 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2538 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2539 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2540 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2541 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2542 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2543 |=B|Lamp|D|0~~0|
2544
2545 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2546 |=W|LR_W|DDDD|0 ~~ 4095|
2547 |=W|TC|DDD|0 ~~ 511|
2548 |=W|DM|DDDD|0 ~~ 9999|Data Register
2549
2550 **Wiring Diagram:**
2551
2552 **RS-232**
2553
2554 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2555
2556 Communication Module:
2557
2558 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2559
2560 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2561
2562 (% style="text-align:center" %)
2563 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2564
2565 == **OMRON HOSTLINK** ==
2566
2567 Supported series: Omron C200HE series
2568
2569 **HMI Settings(recommended)**
2570
2571 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended
2572 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)OMRON HOSTLINK
2573 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232
2574 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)9600
2575 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)2
2576 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)7
2577 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)EVEN
2578 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)0
2579 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0
2580
2581 (% class="wikigeneratedid" %)
2582 **Address List**
2583
2584 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
2585 |Bit|IR|IR|IR d|0~~99999
2586 |Bit|LR|LR|LR d|0~~99999
2587 |Bit|HR|HR|HR d|0~~99999
2588 |Bit|AR|AR|AR d|0~~99999
2589 |Bit|TIMB|TIMB|TIMB d|0~~99999
2590 |Bit|CNTB|CNTB|CNTB d|0~~99999
2591 |Bit|TIM|TIM|TIM d|0~~99999
2592 |Bit|DM|DM|DM d|0~~99999
2593 |Bit|CNT|CNT|CNT d|0~~99999
2594 |Bit|WR|WR|WR d|0~~99999
2595 |Bit|LAMP|LAMP|LAMP d|0~~0
2596 |Word|IR|IR|IR d|0~~99999
2597 |Word|LR|LR|LR d|0~~99999
2598 |Word|HR|HR|HR d|0~~99999
2599 |Word|AR|AR|AR d|0~~99999
2600 |Word|TIM|TIM|TIM d|0~~99999
2601 |Word|DM|DM|DM d|0~~99999
2602 |Word|CNT|CNT|CNT d|0~~99999
2603 |Word|WR|WR|WR d|0~~99999
2604
2605 **Cable Wiring**
2606
2607 (% style="text-align:center" %)
2608 [[image:3.1.2 接口.png||height="240" width="339"]]
2609
2610 = **Rockwell PLC** =
2611
2612 == **DF1** ==
2613
2614 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2615
2616 **HMI Settings**
2617
2618 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2619 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2620 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2621 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2622 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2623 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2624 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2625 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2626 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2627
2628 **PLC Settings**
2629
2630 DF1 Full Duplex protocol and CRC error check
2631
2632 **Address List**
2633
2634 (% class="table-bordered" %)
2635 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2636 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2637 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2638 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2639 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2640 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2641 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2642 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2643 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2644 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2645 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2646 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2647
2648 **Cable Wiring**
2649
2650 (% style="text-align:center" %)
2651 [[image:AB.gif]]
2652
2653 == **DF1 Advanced** ==
2654
2655 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2656
2657 **HMI Settings**
2658
2659 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2660 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2661 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2662 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2663 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2664 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2665 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2666 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2667 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2668
2669 **PLC Settings**
2670
2671 DF1 Full Duplex protocol and CRC error check
2672
2673 **Address List**
2674
2675 (% class="table-bordered" %)
2676 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2677 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2678 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2679 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2680 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2681 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2682 Bit data file B0~~B99
2683
2684 First two digits is for file number
2685
2686 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2687 )))
2688 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2689 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2690 Integer data file bit format N0~~N99
2691
2692 First two digits is for file number
2693
2694 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2695 )))
2696 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2697 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2698 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2699 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2700 Timer Preset Value
2701
2702 First two digits is for file number
2703
2704 For example, TNS99255 represents file number T99, address 255.
2705 )))
2706 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2707 Timer Accumulator Value
2708
2709 First two digits is for file number
2710
2711 For example, TNP99255 represents file number T99, address 255.
2712 )))
2713 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2714 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2715 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2716 Counter Preset Value
2717
2718 First two digits is for file number
2719
2720 For example, CNS99255 represents file number C99, address 255.
2721 )))
2722 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2723 Counter Accumulator Value
2724
2725 First two digits is for file number
2726
2727 For example, CNP99255 represents file number C99, address 255.
2728 )))
2729 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2730 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2731 Integer data file
2732
2733 First two digits is for file number
2734
2735 For example, NN99255 represents file number N99, address 255.
2736 )))
2737 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2738 Only able to communicate with file number F8
2739 )))
2740 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2741 Floating point data file
2742
2743 First two digits is for file number
2744
2745 For example, FN99255 represents file number F99, address 255.
2746 )))
2747 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2748
2749 **Cable Wiring**
2750
2751 (% style="text-align:center" %)
2752 [[image:AB.gif]]
2753
2754 == **MicroLogix** ==
2755
2756 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2757
2758 **HMI Settings**
2759
2760 (% class="table-bordered" %)
2761 |**Item**|**Settings**|**Note**
2762 |Protocol|Allen-Bradlley MicroLogix|
2763 |Connection|RS232|
2764 |Baud rate|19200|
2765 |Data bit|8|
2766 |Parity|None|
2767 |Stop bit|1|
2768 |PLC station No.|1|
2769
2770 **Address List**
2771
2772 (% class="table-bordered" %)
2773 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2774 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2775 |O|O d.d|0.0~~255.15|
2776 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2777 |S|S d.d|0.0~~255.15|
2778 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2779 |(% rowspan="9" %)Word|S|S d|0~~255|
2780 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2781 |TP|TP nnhh|0~~ffff
2782 |CS|CS nnhh|0~~ffff
2783 |CP|CP nnhh|0~~ffff
2784 |N|N nnhh|0~~ffff
2785 |C|C nnhh|0~~ffff
2786 |T|T nnhh|0~~ffff
2787 |R|R nnhh|0~~ffff
2788
2789 **Cable Wiring**
2790
2791 (% style="text-align:center" %)
2792 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2793
2794 == **EtherNet/IP(CompactLogix Series)** ==
2795
2796 Allen-Brandly Compact Logix Free Tag
2797
2798 **HMI Settings**
2799
2800 (% class="table-bordered" %)
2801 |**Items**|**Settings**|**Note**
2802 |Protocol|EtherNet/IP(CompactLogix Series)|
2803 |Connection|Ethernet|
2804 |Port No.|44818|
2805
2806 **PLC Setting**
2807
2808 Create new tags
2809
2810 (% style="text-align:center" %)
2811 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2812
2813 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2814
2815 (% style="text-align:center" %)
2816 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2817
2818 Import labels, please open [Communication] window and click [Import label];
2819
2820 Select csv file, all tags will be displayed as belows;
2821
2822 (% style="text-align:center" %)
2823 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2824
2825 **✎Note:**
2826
2827 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2828
2829 (% style="text-align:center" %)
2830 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2831
2832 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2833
2834 **Communication settings in HMI**
2835
2836 Enable HMI Ethernet in [Project Settings];
2837
2838 (% style="text-align:center" %)
2839 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2840
2841 Set PLC IP in [Device IP] settings;
2842
2843 (% style="text-align:center" %)
2844 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2845
2846 **Cable Wiring**
2847
2848 (% style="text-align:center" %)
2849 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2850
2851 == **MicroLogix 1200** ==
2852
2853 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2854
2855 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2856 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2857 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2858 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2859
2860 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2861
2862 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2863 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2864 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2865 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2866 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2867 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2868 |**PLC word address type**|**Address format**|**Address range**
2869 |S|ddd|S0 ~~ 255
2870 |TS|ffff|TS0 ~~ FFFF
2871 |TP|ffff|TP0 ~~ FFFF
2872 |CS|ffff|CS0 ~~ FFFF
2873 |CP|ffff|CP0 ~~ FFFF
2874 |N|ffff|N0 ~~ FFFF
2875 |F|ffff|F0 ~~ FFFF
2876
2877 = **Siemens PLC** =
2878
2879 == **S7-200 Smart Ethernet** ==
2880
2881 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2882
2883 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2884
2885 **HMI Setting**
2886
2887 (% class="table-bordered" %)
2888 |**Items**|**Settings**|**Note**
2889 |Protocol|Simens S7-200 Smart Ethernet|
2890 |Connection|Ethernet|
2891 |Port No.|102|
2892 |PLC station No.|2|
2893
2894 **Address List**
2895
2896 (% class="table-bordered" %)
2897 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2898 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2899 |Q|Q|Q ddddd.o|0.0~~99999.7|
2900 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2901 |V|V|V ddddd.o|0.0~~99999.7|
2902 |M|M|M ddddd.o|0.0~~99999.7|
2903 |SM|SM|ddddd.o|0.0~~99999.7|
2904 |S|S|ddddd.o|0.0~~99999.7|Read only
2905 |T|T|ddddd|0~~99999|Timer state, read only
2906 |C|C|ddddd|0~~99999|Counter state, read only
2907 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2908 |Q|QW|QW ddddd|0~~99999|
2909 |AI|AIW|AIW ddddd|0~~99999|
2910 |AQ|VB|VB ddddd|0~~99999|
2911 |V|VW|VW ddddd|0~~99998|(((
2912 VW0=VB (0~~1)
2913
2914 VW2=VB (2~~3)
2915
2916 Address value is a multiple of 2
2917 )))
2918 |V|VD|VD ddddd|0~~99998|(((
2919 VD0=VB (0~~3)
2920
2921 VD2=VB (4~~7)
2922
2923 Address value is a multiple of 4
2924 )))
2925 |M|MB|MB ddddd|0~~99999|
2926 |M|MW|MW ddddd|0~~99999|(((
2927 MW0=MB(0~~1)
2928
2929 MW2=MB(2~~3)
2930
2931 Address value is a multiple of 2
2932 )))
2933 |M|MD|MD ddddd|0~~99999|(((
2934 MD0=MB(0~~3)
2935
2936 MD4=MB(4~~7)
2937
2938 Address value is a multiple of 4
2939 )))
2940 |T|TW|TW ddddd|0~~99999|Value of timer
2941 |C|CW|CW ddddd|0~~99999|Value of counter
2942 |W|SW|SW ddddd|0~~99999|
2943
2944 **Communication Settings**
2945
2946 Enable HMI Ethernet in [Project Settings];
2947
2948 (% style="text-align:center" %)
2949 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2950
2951 Set PLC IP in [Device IP] settings;
2952
2953 (% style="text-align:center" %)
2954 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2955
2956 * PLC IP Address: PLC IP
2957 * PLC pot No.: 102(fixed)
2958 * Network:TCP_Client_2N(fixed)
2959
2960 (% style="text-align:center" %)
2961 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2962
2963 * Wait timeout: depend on actual network situation (more than 1500 ms)
2964
2965 **Cable Wiring**
2966
2967 (% style="text-align:center" %)
2968 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2969
2970 == **S7-300 Ethernet** ==
2971
2972 Supported Series: Siemens S7-300 series PLC
2973
2974 **HMI Setting**
2975
2976 (% class="table-bordered" %)
2977 |**Items**|**Settings**|**Note**
2978 |Protocol|Simens S7-300 Ethernet|
2979 |Connection|Ethernet|
2980 |Port No.|102|
2981 |PLC station No.|2|Need to be same as the PLC setting
2982
2983 **Address List**
2984
2985 (% class="table-bordered" %)
2986 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2987 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2988 |Q|Q|Q ddddd.o|0.0~~99999.7|
2989 |M|M|M ddddd.o|0.0~~99999.7|
2990 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
2991 nnnn: block number;
2992
2993 dddd: address;
2994 )))
2995 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2996 |Q|QW|QW ddddd|0~~99999|
2997 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2998 |MW|MW ddddd|0~~99999|(((
2999 MW0=MB(0~~1)
3000
3001 MW2=MB(2~~3)
3002
3003 Address value is a multiple of 2
3004 )))
3005 |MD|MD ddddd|0~~99999|(((
3006 MD0=MB(0~~3)
3007
3008 MD4=MB(4~~7)
3009
3010 Address value is a multiple of 4
3011 )))
3012 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
3013 nnnn: block number;
3014
3015 dddd: address
3016 )))
3017 |DBxDBW|DBxDBW nnnndddd|0~~99999999
3018 |DBxDBD|DBxDBD nnnndddd|0~~99999999
3019
3020 **Communication Settings**
3021
3022 Enable HMI Ethernet in [Project Settings];
3023
3024 (% style="text-align:center" %)
3025 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3026
3027 Set PLC IP in [Device IP] settings;
3028
3029 (% style="text-align:center" %)
3030 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
3031
3032 * PLC IP Address: PLC IP
3033 * PLC pot No.: 102(fixed)
3034 * Network:TCP_Client_2N(fixed)
3035
3036 (% style="text-align:center" %)
3037 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3038
3039 * Wait timeout: depend on actual network situation (more than 1500 ms)
3040
3041 **Cable Wiring**
3042
3043 (% style="text-align:center" %)
3044 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3045
3046 == **S7-1200 Ethernet** ==
3047
3048 Supported Series: Siemens S7-1200
3049
3050 **HMI Setting**
3051
3052 (% class="table-bordered" %)
3053 |**Items**|**Settings**|**Note**
3054 |Protocol|Siemens S7-1200|
3055 |Connection|Ethernet|
3056 |Port No.|102|
3057 |PLC station No.|2|
3058
3059 **Address List**
3060
3061 (% class="table-bordered" %)
3062 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3063 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3064 d:0~-~-9999
3065
3066 o:0-7
3067 )))|
3068 |Q|Q|Q d.o|(((
3069 d:0~-~-9999
3070
3071 o:0-7
3072 )))|
3073 |M|M|M d.o|(((
3074 d:0~-~-9999
3075
3076 o:0-7
3077 )))|
3078 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3079 nn:0-9999,
3080
3081 dddd:0-9999,
3082
3083 o:0-7
3084 )))|(((
3085 nn:DB No.
3086
3087 dddd:address value
3088
3089 o: digit address
3090 )))
3091 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3092 |M|MW|MW d|d:0-99999|(((
3093 MW0=MB(0~~1)
3094
3095 MW2=MB(2~~3)
3096
3097 Address value is a multiple of 2
3098 )))
3099 |M|MD|MD d|d:0-99999|(((
3100 MD0=MB(0~~3)
3101
3102 MD4=MB(4~~7)
3103
3104 Address value is a multiple of 4
3105 )))
3106 |I|IW|IW d|d:0-99999|
3107 |Q|QW|QW d|d:0-99999|
3108 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3109 nn:0-9999
3110
3111 dddd:0-9999
3112 )))|(((
3113 nn:DB No.
3114
3115 dddd:address value
3116 )))
3117 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3118 nn:0-9999
3119
3120 dddd:0-9999
3121 )))|(((
3122 nn:DB No.
3123
3124 dddd:address value
3125
3126 Address value is a multiple of 2
3127 )))
3128 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3129 nn:0-9999
3130
3131 dddd:0-9999
3132 )))|(((
3133 nn:DB No.
3134
3135 dddd:address value
3136
3137 Address value is a multiple of 4
3138 )))
3139
3140 **Communication Settings**
3141
3142 Enable HMI Ethernet in [Project Settings];
3143
3144 (% style="text-align:center" %)
3145 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3146
3147 Set PLC IP in [Device IP] settings;
3148
3149 (% style="text-align:center" %)
3150 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3151
3152 **✎Note:**
3153
3154 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3155 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3156 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3157 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3158
3159 **PLC Settings**
3160
3161 Add BD
3162
3163 * Please uncheck [Symbolic access only] option;
3164
3165 (% style="text-align:center" %)
3166 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3167
3168 Address settings, using BD2 as example.
3169
3170 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3171 * 2 represent DB block number
3172 * xxxx represent address
3173
3174 **Such as:**
3175
3176 * DBxDBB20000 = DB2.DBB0
3177 * DBxDBW20004 = DB2.DBW4
3178
3179 (% style="text-align:center" %)
3180 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3181
3182 **How to connect with S7-1200 Firmware V4.0**
3183
3184 PLC configuration
3185
3186 * Double click [device configuration] in Siemens via software
3187 * Double click [protection] to enter protection configuration screen
3188
3189 (% style="text-align:center" %)
3190 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3191
3192 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3193
3194 (% style="text-align:center" %)
3195 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3196
3197 DB settings
3198
3199 * Right click [DB], select [properties]
3200 * Uncheck [optimized block access]
3201
3202 **Cable Wiring**
3203
3204 (% style="text-align:center" %)
3205 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3206
3207 == **S7-XXX Ethernet** ==
3208
3209 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3210
3211 **HMI Setting**
3212
3213 (% class="table-bordered" style="width:823px" %)
3214 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3215 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3216 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3217 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3218 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3219 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3220
3221 Slot from TIA Portal is equal to Device No. of PIStudio
3222
3223 Rack from TIA Portal is equal to HMI No. of PIStudio
3224
3225 (% style="text-align:center" %)
3226 [[image:S7-XXXCommunication Settings.png]]
3227
3228 (% style="text-align:center" %)
3229 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3230
3231 **Address List**
3232
3233 (% class="table-bordered" %)
3234 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3235 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3236 d:0~-~-9999
3237
3238 o:0-7
3239 )))|
3240 |Q|Q|Q d.o|(((
3241 d:0~-~-9999
3242
3243 o:0-7
3244 )))|
3245 |M|M|M d.o|(((
3246 d:0~-~-9999
3247
3248 o:0-7
3249 )))|
3250 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3251 nn:0-9999,
3252
3253 dddd:0-9999,
3254
3255 o:0-7
3256 )))|(((
3257 nn:DB No.
3258
3259 dddd:address value
3260
3261 o: digit address
3262 )))
3263 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3264 |M|MW|MW d|d:0-99999|(((
3265 MW0=MB(0~~1)
3266
3267 MW2=MB(2~~3)
3268
3269 Address value is a multiple of 2
3270 )))
3271 |M|MD|MD d|d:0-99999|(((
3272 MD0=MB(0~~3)
3273
3274 MD4=MB(4~~7)
3275
3276 Address value is a multiple of 4
3277 )))
3278 |I|IW|IW d|d:0-99999|
3279 |Q|QW|QW d|d:0-99999|
3280 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3281 nn:0-9999
3282
3283 dddd:0-9999
3284 )))|(((
3285 nn:DB No.
3286
3287 dddd:address value
3288 )))
3289 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3290 nn:0-9999
3291
3292 dddd:0-9999
3293 )))|(((
3294 nn:DB No.
3295
3296 dddd:address value
3297
3298 Address value is a multiple of 2
3299 )))
3300 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3301 nn:0-9999
3302
3303 dddd:0-9999
3304 )))|(((
3305 nn:DB No.
3306
3307 dddd:address value
3308
3309 Address value is a multiple of 4
3310 )))
3311
3312 **Communication Settings**
3313
3314 Enable HMI Ethernet in [Project Settings];
3315
3316 (% style="text-align:center" %)
3317 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3318
3319 Set PLC IP in [Device IP] settings;
3320
3321 (% style="text-align:center" %)
3322 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3323
3324 **✎Note:**
3325
3326 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3327 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3328
3329 **Cable Wiring**
3330
3331 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3332
3333 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
3334
3335 Supported Series: Siemens Logo 0BA0, 0BA1 series
3336
3337 **HMI Settings**
3338
3339 (% class="table-bordered" %)
3340 |**Items**|**Settings**|**Note**
3341 |Protocol|Siemens LOGO|
3342 |Connection|Ethernet|
3343 |Port No.|102|
3344 |PLC station No.|2|
3345
3346 **Address List**
3347
3348 (% class="table-bordered" %)
3349 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3350 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3351 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3352 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3353 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3354 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3355 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3356 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3357 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3358 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3359 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3360 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3361 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3362 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3363 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3364 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3365
3366 **PLC Settings in LOGO Software:**
3367
3368 Click [Tools]~-~-[Ethernet Connections],shown as below.
3369
3370 (% style="text-align:center" %)
3371 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3372
3373 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3374
3375 (% style="text-align:center" %)
3376 [[image:image-20221228142937-4.png]]
3377
3378 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3379
3380 (% style="text-align:center" %)
3381 [[image:image-20221228143047-5.png]]
3382
3383 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3384
3385 (% style="text-align:center" %)
3386 [[image:image-20221228143246-6.png]]
3387
3388
3389 **HMI Communication Settings**
3390
3391 Set PLC IP in [Device IP] settings;
3392
3393 (% style="text-align:center" %)
3394 [[image:image-20221228143614-7.png]]
3395
3396 Enable HMI Ethernet in [Project Settings];
3397
3398 (% style="text-align:center" %)
3399 [[image:image-20221228144229-9.png]]
3400
3401 TSAP setting
3402
3403 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3404 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3405 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3406 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3407 ie, ig series: use HSW1200, HSW1201.
3408 HMI V2.0: use HSW1200, HSW1201.
3409
3410 **✎Note:**
3411
3412 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3413 * HSW10119/HSW1201 is set up as shown.
3414 * (((
3415 (% style="text-align:center" %)
3416 [[image:image-20221228144800-11.png]]
3417 )))
3418 * (((
3419 (% style="text-align:center" %)
3420 [[image:image-20221228144708-10.png]]
3421 )))
3422
3423 * AI word address and Ibit address are read-only and cannot be written on HMI.
3424 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3425 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3426 * Written value of RTC cannot exceed 255.
3427
3428 **Cable Wiring**
3429
3430 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3431
3432 == **S7-300 232** ==
3433
3434 **HMI Setting:**
3435
3436 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3437 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3438 |=**PLC I/F**|RS232| |
3439 |=**Baud rate**|19200|9600,19200|
3440 |=**Data bits**|8| |
3441 |=**Parity**|Odd| |
3442 |=**Stop bits**|1| |
3443 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3444
3445 **Device Address**
3446
3447 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3448 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3449 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3450 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3451 |=Word|(((
3452 DB1 to DB99
3453 )))|DDDDDo|0 ~~ 655327|
3454 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3455 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3456 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3457 |=Double word|MD|DDDD|0 ~~ 4094|
3458 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3459 Data Register Double Word (must be even)
3460 )))
3461 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3462
3463 **Cable Wiring**
3464
3465 (% style="text-align:center" %)
3466 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3467
3468 = Xinje** PLC** =
3469
3470 == **XC serial protocol** ==
3471
3472 **HMI Settings**
3473
3474 |**Item**|**Settings**|**Note**
3475 |Protocol|XINJE XC MODBUS|
3476 |Connection|RS232|
3477 |Baud rate|19200|
3478 |Data bit|8|
3479 |Parity|EVEN|
3480 |Stop bit|1|
3481 |PLC station No.|1|
3482
3483 **Address List**
3484
3485 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3486 |Bit|M|M|M d|0~~8511|
3487 |Bit|X|X|X o|0~~1747|
3488 |Bit|Y|Y|Y o|0~~1747|
3489 |Bit|S|S|S d|0~~1023|
3490 |Bit|T|T|T d|0~~4095|
3491 |Bit|C|C|C d|0~~634|
3492 |Word|D|D|D d|0~~8511|
3493 |Word|TD|TD|TD d|0~~618|
3494 |Word|CD|CD|CD d|0~~634|
3495 |Word|FD|FD|FD d|0~~8511|
3496
3497 **Configure the communication protocol**
3498
3499 (% style="text-align:center" %)
3500 [[image:image-20220830154105-1.png]]
3501
3502 (% style="text-align:center" %)
3503 [[image:image-20220830154159-3.png]]
3504
3505 **Cable Wiring**
3506
3507 Figure
3508
3509 [[image:image-20220830155728-4.png]]
3510
3511 Pin Definition Diagram
3512
3513 (% style="text-align:center" %)
3514 [[image:image-20220830154131-2.png]]
3515
3516 == **XD serial protocol** ==
3517
3518 **HMI Settings**
3519
3520 Supported Series: Xinjie XD/XE Series PLC
3521
3522 |=**Item**|=**Settings**|=**Note**
3523 |Protocol|XINJE XD/XC MODBUS|
3524 |Connection|RS232|
3525 |Baud rate|19200|
3526 |Data bit|8|
3527 |Parity|EVEN|
3528 |Stop bit|1|
3529 |PLC station No.|1|
3530
3531 **Address List**
3532
3533 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3534 |Bit|M|M|M d|0~~74999|
3535 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3536 |Bit|X2xx|X2xx|X2xx o|0~~277|
3537 |Bit|X|X|X o|0~~77|
3538 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3539 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3540 |Bit|Y|Y|Y o|0~~4095|
3541 |Bit|SM|SM|SM d|0~~4999|(((
3542
3543 )))
3544 |Bit|T|T|T d|0~~4999|
3545 |Bit|C|C|C d|0~~4999|
3546 |Bit|ET|ET|ET d|0~~31|
3547 |Bit|SE|SE|SE d|0~~31|
3548 |Bit|HM|HM|HM d|0~~11999|
3549 |Bit|HSC|HSC|HSC d|0~~39|
3550 |Bit|HS|HS|HS d|0~~999|
3551 |Bit|HT|HT|HT d|0~~1999|
3552 |Bit|HC|HC|HC d|0~~1999|
3553 |Bit|S|S|S d|0~~7999|
3554 |Word|D|D|D d|0~~69999|
3555 |Word|ID|ID|ID d|0~~99|
3556 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3557 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3558 |Word|QD|QD|QD d|0~~99|
3559 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3560 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3561 |Word|SD|SD|SD d|0~~4999|
3562 |Word|TD|TD|TD d|0~~575|
3563 |Word|CD|CD|CD d|0~~575|
3564 |Word|ETD|ETD|ETD d|0~~31|
3565 |Word|HD|HD|HD d|0~~24999|
3566 |Word|HSD|HSD|HSD d|0~~1023|
3567 |Word|HTD|HTD|HTD d|0~~95|
3568 |Word|HCD|HCD|HCD d|0~~95|
3569 |Word|HSCD|HSCD|HSCD d|0~~31|
3570 |Word|FD|FD|FD d|0~~8191|
3571 |Word|SFD|SFD|SFD d|0~~5999|
3572 |Word|FS|FS|FS d|0~~47|
3573
3574 **Configure the communication protocol**
3575
3576 (% style="text-align:center" %)
3577 [[image:image-20220830160042-1.png]]
3578
3579 (% style="text-align:center" %)
3580 [[image:image-20220830160129-2.png]]
3581
3582 **Cable Wiring**
3583
3584 (% style="text-align:center" %)
3585 [[image:image-20220905093902-1.png]]
3586
3587 Pin Definition Diagram
3588
3589 (% style="text-align:center" %)
3590 [[image:image-20220830160232-3.png]]
3591
3592 = Panasonic =
3593
3594 == **FP Serial** ==
3595
3596 **1)HMI Settings**
3597
3598 |**Item**|**Settings**|**Note**
3599 |Protocol|Panasonic FP MFWTOCOL|
3600 |Connection|RS232|
3601 |Baud rate|9600|
3602 |Data bit|8|
3603 |Parity|ODD|
3604 |Stop bit|1|
3605 |PLC station No.|1|
3606
3607 **2)Address List**
3608
3609 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3610 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3611 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3612 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3613 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3614 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3615 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3616 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3617 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3618 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3619 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3620 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3621 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3622 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3623 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3624 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3625
3626 **3)Configure the communication protocol**
3627
3628 [[image:image-20220830171050-1.png]]
3629
3630 [[image:image-20220830171126-2.png]]
3631
3632 **4)Cable Wiring**
3633
3634 Figure
3635
3636 [[image:image-20220830171328-4.png]]
3637
3638 Pin Definition Diagram
3639
3640 [[image:image-20220830171146-3.png]]
3641
3642 = **SHIMADEN PLC** =
3643
3644 == **FP23 series** ==
3645
3646 Supported series: SHIMADEN FP23 series
3647
3648 **HMI Setting**
3649
3650 |**Items**|**Settings**|**Note**
3651 |Protocol|SHIMADEN FP23 series|
3652 |Connection|RS485 (9600, 1, 7, EVEN)|
3653 |Port No.|None|
3654 |PLC station No.|0|
3655
3656 **Address List**
3657
3658 |**Device address**|**HMI register**|**Address range**|**Type**
3659 |0040-0043(HEX)|FP040|100064-200067|Read only
3660 |0100-010B(HEX)|FP100|100256-200267|Read only
3661 |0110-0142(HEX)|FP110|100272-200322|Read only
3662 |0182-0252(HEX)|FP182|100386-200594|Write only
3663 |0280-0281(HEX)|FP280|100640-200641|Read only
3664 |0300-030B(HEX)|FP300|100768-200779|Read and write
3665 |0380-039F(HEX)|FP380|100896-200927|Read and write
3666 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3667 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3668 |0600-0670(HEX)|FP600|101536-201814|Read and write
3669 |0720-0738(HEX)|FP720|101824-201848|Read and write
3670 |0800-083F(HEX)|FP800|102048-202111|Read and write
3671 |0900-0952(HEX)|FP900|102304-202386|Read and write
3672 | |Ctrl|0-2|
3673
3674 **✎Note:**
3675
3676 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3677 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3678 * The Ctrl register is used to store the control group number and BCC check mode.
3679
3680 **Ctrl Register Description**
3681
3682 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3683 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3684 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3685 * Ctrl3 reserved
3686
3687 **✎Note:**
3688
3689 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3690
3691 **Cable Wiring**
3692
3693 (% style="text-align:center" %)
3694 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3695
3696 (% style="text-align:center" %)
3697 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3698
3699 **✎Note:** COM3 only available in PI8000/PI9000 series.
3700
3701 == **SR90 protocol** ==
3702
3703 Supported series: SHIMADEN SR90 series
3704
3705 **HMI Setting**
3706
3707 |**Items**|**Settings**|**Note**
3708 |Protocol|SHIMADEN SR90 protocol|
3709 |Connection|RS485 (1200, 1, 7, EVEN)|
3710 |Port No.|None|
3711 |PLC station No.|0|
3712
3713 **Address List**
3714
3715 |**Device address**|**HMI register**|**Address range**|**Type**
3716 |0040-0043 (HEX)|SR040|100064-100067|Read only
3717 |0100-010A(HEX)|SR0100|100256-100266|Read only
3718 |0182-018C(HEX)|SR0182|100386-100396|Write only
3719 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3720 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3721 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3722 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3723 | |Ctrl|0-2|~-~-
3724
3725 **✎Note:**
3726
3727 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3728 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3729 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3730
3731 **Ctrl Register Description**
3732
3733 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3734 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3735 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3736 * Ctrl3 reserved
3737
3738 **✎Note:**
3739
3740 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3741
3742 **Cable Wiring**
3743
3744 (% style="text-align:center" %)
3745 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3746
3747 (% style="text-align:center" %)
3748 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3749
3750 **✎Note:** COM3 only available in PI8000/PI9000 series.
3751
3752 == **MR13 series(standard protocol)** ==
3753
3754 Supported series: SHIMADEN MR13 series
3755
3756 **HMI Setting**
3757
3758 |**Items**|**Settings**|**Note**
3759 |Protocol|SHIMADEN standard protocol|
3760 |Connection|RS485 (1200, 1, 7, EVEN)|
3761 |Port No.|None|
3762 |PLC station No.|0|
3763
3764 **Address List**
3765
3766 |**Device address**|**HMI register**|**Address range**|**Type**
3767 |0100-010B(HEX)|MR100|100256-300267|Read only
3768 |0111-0126(HEX)|MR111|100273-300294|Read only
3769 |0184-0192(HEX)|MR184|100388-300402|Write only
3770 |0280-0282(HEX)|MR280|100640-300642|Read only
3771 |0300-030B(HEX)|MR300|100768-300779|Read/write
3772 |0314-0317(HEX)|MR314|100788-300791|Read/write
3773 |031A(HEX)|MR31A|100794-300794|Read/write
3774 |0320-0321(HEX)|MR320|100800-300801|Read/write
3775 |0400-0504(HEX)|MR400|101024-301284|Read/write
3776 |0506(HEX)|MR506|101286-301286|Read/write
3777 |0510-0514(HEX)|MR510|101296-301300|Read/write
3778 |0516-0524(HEX)|MR516|101302-301316|Read/write
3779 |0526(HEX)|MR526|101318-301318|Read/write
3780 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3781 |~-~-|Ctrl|0-2|~-~-
3782
3783 **✎Note:**
3784
3785 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3786 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3787 * The Ctrl register is used to store the control group number and BCC check mode.
3788
3789 **Ctrl Register Description**
3790
3791 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3792 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3793 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3794 * Ctrl3 reserved
3795
3796 **✎Note:**
3797
3798 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3799
3800 **Cable Wiring**
3801
3802 (% style="text-align:center" %)
3803 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3804
3805 (% style="text-align:center" %)
3806 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3807
3808 **✎Note:** COM3 only available in PI8000/PI9000 series.
3809
3810 = **Printer** =
3811
3812 == **TSPL label printer** ==
3813
3814 **Introduction**
3815
3816 TSPL label printer protocol supports following models.
3817
3818 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3819 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3820
3821 **Setting Step**
3822
3823 Select the protocol
3824
3825 * Create a new project, select the TSPL label printer protocol as shown below.
3826
3827 (% style="text-align:center" %)
3828 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3829
3830 Set parameters
3831
3832 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3833
3834 Printer register
3835
3836 (% class="table-bordered" %)
3837 |**Register**|**System**|**Range**|**Function**
3838 |TSPL_SP|decimal|0 - 1|Set the paper size
3839 |TSPL_PT|decimal|0 - 1999|Print text
3840 |TSPL_PQ|decimal|0 - 999|Print QR code
3841 |TSPL_PB|decimal|0 - 999|Print barcode
3842 |TSPL_PR|decimal|0 - 1|Print offset
3843 |TSPL_PN|decimal|0 - 0|Trigger printing
3844 |TSPL_PS|decimal|0 - 0|Print status
3845
3846 * Set paper size:
3847 ** TSPL_SP0: width of paper, unit: mm.
3848 ** TSPL_SP1: height of paper, unit: mm.
3849 * Print text:
3850 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3851 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3852
3853 (% class="table-bordered" %)
3854 |**Register**|**Function**|**Description**
3855 |TSPL_PT0|X coordinate|Unit: dot
3856 |TSPL_PT1|Ycoordinate|Unit: dot
3857 |TSPL_PT2|Rotation angle|(((
3858 0: 0 degrees
3859
3860 1: 90 degrees
3861
3862 2: 180 degrees
3863
3864 3: 270 degrees
3865 )))
3866 |TSPL_PT3|Size|Range: 0-3
3867 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3868
3869 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3870
3871 Print QR code:
3872
3873 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3874 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3875
3876 (% class="table-bordered" %)
3877 |**Register**|**Function**|**Description**
3878 |TSPL_PQ0|X coordinate|Unit: dot
3879 |TSPL_PQ1|Ycoordinate|Unit: dot
3880 |TSPL_PQ2|Rotation angle|(((
3881 0: 0 degrees
3882
3883 1: 90 degrees
3884
3885 2: 180 degrees
3886
3887 3: 270 degrees
3888 )))
3889 |TSPL_PQ3|Size|Range: 0-5
3890 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3891
3892 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3893
3894 Print bar code:
3895
3896 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3897 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3898
3899 (% class="table-bordered" %)
3900 |**Register**|**Function**|**Description**
3901 |TSPL_PB0|X coordinate|Unit: dot
3902 |TSPL_PB1|Ycoordinate|Unit: dot
3903 |TSPL_PB2|Rotation angle|(((
3904 0: 0 degrees
3905
3906 1: 90 degrees
3907
3908 2: 180 degrees
3909
3910 3: 270 degrees
3911 )))
3912 |TSPL_PB3|height|Unit: dot
3913 |TSPL_PB4|width|Range:0-2
3914 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3915
3916 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3917
3918 Print offset:
3919
3920 * TSPL_PR0: X coordinate offset, unit: mm;
3921 * TSPL_PR1: Y coordinate offset, unit: mm.
3922
3923 Trigger printing:
3924
3925 * TSPL_PN0 = 1: trigger the printer to start printing.
3926
3927 Printing status:
3928
3929 * TSPL_PS0 = 1: The printing is normal.
3930 * TSPL_PS0 = 1: The printing is abnormal.
3931
3932 Print picture
3933
3934 * For the function of printing pictures, please refer to the configuration of [Printer object].
3935
3936 Conversion between dot and mm
3937
3938 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3939
3940 == **EpsonTM series** ==
3941
3942 **HMI Settings**
3943
3944 (% class="table-bordered" %)
3945 |**Item**|**Settings**|**Note**
3946 |Protocol|EPSON-TM-T82II/TM-XXX|
3947 |Connection|RS232|
3948 |Baud rate|9600~~115200|
3949 |Data bit|8|
3950 |Parity|None|
3951 |Stop bit|1|
3952 |PLC station No.|1|
3953
3954 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3955
3956 **Printer Settings**
3957
3958 (% class="table-bordered" %)
3959 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3960 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3961 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3962 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3963 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3964 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3965 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3966
3967 **Cable Wiring**
3968
3969 (% style="text-align:center" %)
3970 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3971
3972 (% style="text-align:center" %)
3973 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3974
3975 **✎Note:** COM3 only available in PI8000/PI9000 series.
3976
3977
3978 = **Schneider** =
3979
3980 == **Schneider MODBUS RTU** ==
3981
3982 **HMI Setting**
3983
3984 |=**Parameters**|=**Recommended**|=**Notes**
3985 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3986 |Connection|RS485|
3987 |**Baud rate**|19200|
3988 |**Data bit**|8|
3989 |**Parity**|Even|
3990 |**Stop bit**|1|
3991 |**PLC station No.**|1|
3992
3993 **PLC Setting**
3994
3995 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3996
3997 **Device Address**
3998
3999 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
4000 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
4001 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
4002 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
4003 |W|MW|DDDDDD|0 ~~ 999999|Output register
4004 |DW|MD|DDDDDD|0 ~~ 999999|Output register
4005
4006 **Wiring Diagram**
4007
4008 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
4009
4010 (% style="text-align:center" %)
4011 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
4012
4013 = **Barcode Scanner** =
4014
4015 Supported: DELI 14880 barcode scanner
4016
4017 **HMI Setting**
4018
4019 |**Items**|**Settings**|**Note**
4020 |Protocol|Barcode Scanner|
4021 |Connection|USB|
4022
4023 **Operating Procedures**
4024
4025 Select [Barcode Scanner];
4026
4027 (% style="text-align:center" %)
4028 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
4029
4030 Set address for receiving;
4031
4032 Set correct length;
4033
4034 (% style="text-align:center" %)
4035 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
4036
4037 **✎Note:**
4038
4039 * The protocol uploads the information acquired by the USB scanner to the HMI;
4040 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4041 * Recommended model: DELI 14880 barcode scanner;
4042
4043 = **Hitachi EHV Series (Ethernet)** =
4044
4045 Supported series: Hitachi EHV series
4046
4047 **HMI Settings**
4048
4049 (% class="table-bordered" %)
4050 |**Items**|**Settings**|**Note**
4051 |Protocol|Hitachi EHV series|
4052 |Connection|Ethernet|
4053 |Port No.|3004~~3007|
4054
4055 **Address List**
4056
4057 (% class="table-bordered" %)
4058 |**Type**|**Register**|**Range**|**Format**|**Note**
4059 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4060 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4061 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4062 H1H2H3H4 Module main number
4063
4064 H1: Remote number
4065
4066 H2: Unit number
4067
4068 H3: Slot number
4069
4070 H4: Word number of Module
4071
4072 H Sub number of Module
4073
4074 For example:X21.3
4075
4076 Slot number 2
4077
4078 Word number of module is 1
4079
4080 Bit number of module is 3
4081
4082 Remote number and unit number are 0
4083 )))
4084 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4085 |R|0 – FF.f (Hex)|R HH.h|
4086 |L|0 - 73FF.f (Hex)|L HHHH.h|
4087 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4088 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4089 H1H2H3H4 Module main number
4090
4091 H1: Remote number
4092
4093 H2: Unit number
4094
4095 H3: Slot number
4096
4097 H4: Word number of module
4098
4099 For example:WX21
4100
4101 Word number of module is 1
4102
4103 Slot number is 2
4104
4105 Remote number and unit number are 0
4106 )))
4107 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4108 |WR|0 – FFFF (Hex)|WR HHHH|
4109 |WL|0 - 73FF (Hex)|WL HHHH|
4110 |TC|0 - 2559|TC DDDD|
4111
4112 **Communication settings in HMI**
4113
4114 Enable HMI Ethernet in [Project Settings];
4115
4116 (% style="text-align:center" %)
4117 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4118
4119 Set PLC IP in [Device IP] settings;
4120
4121 (% style="text-align:center" %)
4122 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4123
4124 **PLC Configuration**
4125
4126 Connect with PLC, select[Online mode];
4127
4128 (% style="text-align:center" %)
4129 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4130
4131 Set IP address, it is the same LAN parameters with HMI;
4132
4133 (% style="text-align:center" %)
4134 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4135
4136 3) Save PLC communication parameter, and restart PLC
4137
4138 **PLC Monitor Mode**
4139
4140 Connect with PLC and choose to “online” mode
4141
4142 (% style="text-align:center" %)
4143 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4144
4145 Open I/O monitor sheet1
4146
4147 (% style="text-align:center" %)
4148 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4149
4150 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4151
4152 (% style="text-align:center" %)
4153 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4154
4155 Enter the register address, click OK to view the value of the register.
4156
4157 (% style="text-align:center" %)
4158 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4159
4160 (% style="text-align:center" %)
4161 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4162
4163 **✎Note:**
4164
4165 * Both word registers and bit registers support even continuous read/write functions;
4166 * The range of registers is based on the specific PLC type;
4167
4168 **Cable Wiring**
4169
4170 (% style="text-align:center" %)
4171 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4172
4173 = **IEC60870-5 104 Client** =
4174
4175 **HMI Setting**
4176
4177 (% class="table-bordered" %)
4178 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4179 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4180 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4181 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4182
4183 **Address List**
4184
4185 (% class="table-bordered" %)
4186 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4187 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4188 |(% style="width:461px" %)SCNA|0~~16777215.7
4189 |(% style="width:461px" %)DPTB|0~~16777215.7
4190 |(% style="width:461px" %)DCNA|0~~16777215.7
4191 |(% style="width:461px" %)METF|0~~16777215.7
4192 |(% style="width:461px" %)SENC|0~~16777215.7
4193 |(% style="width:461px" %)SENA|0~~16777215.7
4194 |(% style="width:461px" %)MENA|0~~16777215.7
4195 |(% style="width:461px" %)METD|0~~16777215.7
4196 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4197 |(% style="width:461px" %)SCNA|0~~16777215
4198 |(% style="width:461px" %)DPTB|0~~16777215
4199 |(% style="width:461px" %)DCNA|0~~16777215
4200 |(% style="width:461px" %)SENA|0~~16777215
4201 |(% style="width:461px" %)MENA|0~~16777215
4202 |(% style="width:461px" %)METD|0~~16777215
4203 |(% style="width:461px" %)INRO|0~~16777215
4204 |(% style="width:461px" %)TIMESYN|0~~16777215
4205 |(% style="width:461px" %)TIMEZ|0~~16777215
4206 |(% style="width:461px" %)NTP|0~~16777215
4207 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4208 |(% style="width:461px" %)SENC|0~~16777215
4209
4210 **Address Configuration**
4211
4212 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4213
4214 (% style="text-align:center" %)
4215 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4216
4217 (% style="text-align:center" %)
4218 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4219
4220 Extended tag name
4221
4222 Address range for the extended tag.
4223
4224 **Communication Settings**
4225
4226 Enable HMI Ethernet in [Project Settings];
4227
4228 (% style="text-align:center" %)
4229 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4230
4231 Set PLC IP in [Device IP] settings;
4232
4233 (% style="text-align:center" %)
4234 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4235
4236 **Cable Wiring**
4237
4238 (% style="text-align:center" %)
4239 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4240
4241 = **OpenCAN** =
4242
4243 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4244
4245 This protocol is only available in PI8000 series HMI.
4246
4247 **HMI Settings**
4248
4249 |**Items**|**Settings**|**Note**
4250 |Protocol|OPENCAN|
4251 |Connection|CAN port|
4252 |Baud rate|250000|
4253
4254 **CAN frame setting in HMI**
4255
4256 Click [OpenCAN setting] button in communication setting window;
4257
4258 (% style="text-align:center" %)
4259 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4260
4261 Click [Add] to create a new frame;
4262
4263 (% style="text-align:center" %)
4264 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4265
4266 |**No**|**Items**|**Description**
4267 |1|Add|add a frame related to register address
4268 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4269 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4270 |4|Modify|Modify the frames in frame management
4271 |5|Copy|Copy one frame to another
4272 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4273 |7|Empty|All frames in the list are cleared
4274 |8|Browse|Displays configuration files in XML format in IE
4275 |9|OK|Complete the configuration of the frame and exit
4276
4277 Set CANBUS frame in setting windows
4278
4279 (% style="text-align:center" %)
4280 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4281
4282 |**No**|**Items**|**Description**
4283 |1|ID|Set the ID of a can frame in hexadecimal format;
4284 |2|ID assign|split the ID by PF, PS, and SA;
4285 |3|Frame type|Select Standard frame or Extended Frame;
4286 |4|Frame format|Select between data frame and remote Frame;
4287 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4288 |6|Use address|(((
4289 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4290
4291 **Edit:** Set a bit or word address by its format;
4292
4293 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4294 )))
4295 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4296 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4297 |Feedback mode: feedback mode includes no response, confirm response and data response;
4298 |No response: the device or touch screen will not receive feedback;
4299 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4300 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4301 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4302 |Response timeout: sets whether the response frame timeout;
4303 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4304 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4305 |Manually send: a manually send tick indicates only one send;
4306 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4307 |10|Note|Fill the text to explain the meaning of the frame;
4308 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4309 |12|Current operation display|Display the description of current operation;
4310 |13|Add|Add a new frame;
4311 |14|Save frame|Save the configured frame format;
4312 |15|Cancel|Cancel the frame configuration;
4313
4314 Set CAN address (Read or write operation);
4315
4316 (% style="text-align:center" %)
4317 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4318
4319 |**No.**|**Item**|**Description**
4320 |1|Current address|Displays the register type and register address set by the user in the data access interface
4321 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4322 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4323 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4324 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4325 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4326 |If the trigger condition is a writing operation, there are two situations:(((
4327 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4328 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4329 )))
4330 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4331 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4332 |4|Add|Add current configuration
4333 |5|Close|Close the configuration window to exit
4334
4335 **Multiple Packages Settings**
4336
4337 (% style="text-align:center" %)
4338 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4339
4340 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4341
4342 Select Multiple package type
4343
4344 * Not Multiple packages
4345 * J1939 Multiple packages
4346 * Customized Multiple packages
4347
4348 Click [Edit Receive data] for [Receive] settings
4349
4350 * Start code+ Total length (J1939)
4351
4352 (% style="text-align:center" %)
4353 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4354
4355 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4356
4357 * Start code + Data max length (J1939)
4358
4359 (% style="text-align:center" %)
4360 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4361
4362 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4363
4364 * Data max length (J1939)
4365
4366 (% style="text-align:center" %)
4367 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4368
4369 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4370
4371 * Customized multiple package
4372
4373 (% style="text-align:center" %)
4374 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4375
4376 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4377
4378 Click [Edit Send data] for [Send] setting
4379
4380 * J1939
4381
4382 (% style="text-align:center" %)
4383 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4384
4385 [Data] is all data to be sent.
4386
4387 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4388
4389 * Customized multiple package
4390
4391 (% style="text-align:center" %)
4392 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4393
4394 [Data] is all data to be sent.
4395
4396 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4397
4398 **Cable Wiring**
4399
4400 (% style="text-align:center" %)
4401 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4402
4403 **✎Note:** The address interval between each frame need to be more than a word address;
4404
4405
4406 = **User Defined Protocol** =
4407
4408 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4409
4410 **HMI Settings**
4411
4412 |**Items**|**Settings**|**Note**
4413 |Protocol|User defined protocol|
4414 |Connection|RS485/RS232|
4415 |Baud rate|2400~~187500|
4416 |Stop bits|1/ 2|
4417 |Data bits|7/ 8|
4418 |Parity|None/ Even/ ODD|
4419
4420 **Operating Procedures**
4421
4422 Select [User defined protocol];
4423
4424 Click [User defined protocol] button to open setting window as below;
4425
4426 (% style="text-align:center" %)
4427 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4428
4429 Configure user defined command;
4430
4431 (% style="text-align:center" %)
4432 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4433
4434 |**No**|**Item**|**Description**
4435 |1|Instruction edit|The required command.
4436 |2|Mode|Write to address or read from the address.
4437 |3|Format|Encode format: HEX or ASCII.
4438 |4|Other|(((
4439 **No receiving: **HMI does not respond to the receiving command.
4440
4441 **Send after receiving:** HMI responds to the receiving command.
4442 )))
4443 |5|Manually send|(((
4444 Respond once after trigger the address.
4445
4446 Address: set the trigger address.
4447 )))
4448 |6|Add|Save this setting.
4449 |7|Cancel|Cancel current settings.
4450 |(% rowspan="4" %)8|Add|Add a new command.
4451 |Edit|Edit the selected command.
4452 |Delete|Delete the selected command.
4453 |Clear|Clear all the commands.
4454 |9|Instruction list|Display all current commands.
4455 |10|Address List|Display all the addresses added.
4456 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4457 |Export|Export current command settings to local storage.
4458 |Browse|Browse local command files.
4459 |Advanced|Combine two commands.
4460 |Exit|Complete editing and exit setting.
4461
4462 **Operating Procedures**
4463
4464 Click [Add] to create a new command, as below shows;
4465
4466 (% style="text-align:center" %)
4467 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4468
4469 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4470
4471 (% style="text-align:center" %)
4472 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4473
4474 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4475
4476 (% style="text-align:center" %)
4477 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4478
4479 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4480
4481 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4482
4483 Check settings;
4484
4485 (% style="text-align:center" %)
4486 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4487
4488 |**No**|**Items**|**Description**
4489 |1|Add checking|Add checking command when receiving the data.
4490 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4491 |Differ with send check|Set return checking.
4492 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4493 |Length: The data length need to be checked.
4494
4495 Object settings;
4496
4497 (% style="text-align:center" %)
4498 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4499
4500 |**No**|**Items**|**Description**
4501 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4502 |Address: the triggering address;
4503 |Note: description to object;
4504 |2|Byte order|The numerical display order;
4505
4506 Data length settings;
4507
4508 (% style="text-align:center" %)
4509 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4510
4511 |**No**|**Item**|**Description**
4512 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4513 |Length: the return data length.
4514 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4515 |Length: the write data length.
4516
4517 Instruction length settings
4518
4519 (% style="text-align:center" %)
4520 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4521
4522 |**No**|**Item**|**Description**
4523 |1|Send length|The instruction data will only send designated data length.
4524 |2|Return length|The responds data length.
4525 |3|End code|Instruction will not be terminated until receiving [End code];
4526
4527 **Cable Wiring**
4528
4529 * **RS485**
4530
4531 (% style="text-align:center" %)
4532 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4533
4534 (% style="text-align:center" %)
4535 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4536
4537 * **RS232**
4538
4539 (% style="text-align:center" %)
4540 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4541
4542 **✎Note:** COM3 only available in PI8000/PI9000 series.